Sei sulla pagina 1di 2

®

DSEGenset

DSE4410/20
ENVIRONMENTAL TESTING STANDARDS

ELECTRO-MAGNETIC COMPATIBILITY
BS EN 61000-6-2

AUTO START & AUTO MAINS FAILURE EMC Generic Immunity Standard for
the Industrial Environment

CONTROL MODULES
BS EN 61000-6-4
EMC Generic Emission Standard for
the Industrial Environment
FEATURES ELECTRICAL SAFETY
BS EN 60950
Safety of Information Technology Equipment,
including Electrical Business Equipment

The DSE4410 is an Auto Start Both modules offer electronic TEMPERATURE


Control Module and the DSE4420 (CAN) and non-electronic (magnetic BS EN 60068-2-1
o
Ab/Ae Cold Test -30 C
is an Auto Mains (Utility) Failure pick-up/alternator sensing) engine BS EN 60068-2-2
Control Module with 3 phase versions and offer a number of Bb/Be Dry Heat +70 oC
sensing, suitable for a wide variety flexible inputs, outputs and engine VIBRATION
of single, diesel or gas, gen-set protections so the system can be BS EN 60068-2-6
applications. easily adapted to suit a wide range Ten sweeps in each of three
major axes
of application demands. 5 Hz to 8 Hz @ +/-7.5 mm,
Monitoring, speed, frequency, 8 Hz to 500 Hz @ 2 gn
voltage, oil pressure, coolant The modules can be easily HUMIDITY
temperature and fuel level, the configured using the DSE BS EN 60068-2-30
modules will display warnings, Configuration Suite PC software. Db Damp Heat Cyclic 20/55 oC
@ 95% RH 48 Hours
shutdown and engine status Selected front panel editing is also BS EN 60068-2-78
information on the back-lit LCD available. Cab Damp Heat Static 40 oC
@ 93% RH 48 Hours
screen and illuminated LED.
SHOCK
BS EN 60068-2-27
Three shocks in each of three major axes
15 gn in 11 mS

DEGREES OF PROTECTION
PROVIDED BY ENCLOSURES
BS EN 60529
IP65 - Front of module when installed into the
control panel with the supplied sealing gasket.

COMPREHENSIVE FEATURE LIST TO SUIT A


WIDE VARIETY OF GEN-SET APPLICATIONS
PC

4 2 3

USB CONFIGURABLE DC OUTPUTS ANALOGUE DC POWER


PORT INPUTS SENDERS SUPPLY 8-35V

DEUTZ
DSE4410/20 ISUZU
PERKINS
CATERPILLAR
MTU
7 VOLVO
CUMMINS
OTHER SCANIA

MAINS (UTILITY) DC OUTPUTS GENERATOR CHARGE FUEL & CRANK ELECTRONIC


SENSING SENSING ALTERNATOR OUTPUTS ENGINES OR
DSE4420 ONLY (Flexible with CAN) MAGNETIC PICK-UP
VOLTS
VOLTS D+
+ + W/L +

1ph 1 1 1ph
2ph 2ph
3ph 3ph
N N

ISSUE 4
®

DSEGenset

DSE4410/20
SPECIFICATION

DC SUPPLY
CONTINUOUS VOLTAGE RATING

AUTO START & AUTO MAINS FAILURE 8 V to 35 V Continuous

CONTROL MODULES CRANKING DROPOUTS


Able to survive 0 V for 50 mS, providing
supply was at least 10V before dropout and
FEATURES supply recovers to 5 V. This is achieved
without the need for internal batteries. LEDs
and backlight will not be maintained during
cranking.

MAXIMUM OPERATING CURRENT


150 mA at 12 V, 80 mA at 24 V

MAXIMUM STANDBY CURRENT


DSE4420 50 mA at 12 V, 30 mA at 24 V

CHARGE FAIL/EXCITATION RANGE


0 V to 35 V

MAGNETIC PICK UP
VOLTAGE RANGE
DSE4410 +/- 0.5 V to 70 V

FREQUENCY RANGE
10,000 Hz (max)

OUTPUTS
OUTPUT A (FUEL)
2 Amp DC at supply voltage

OUTPUT B (START)
2 Amp DC at supply voltage

AUXILIARY OUTPUTS C,D,E,F


2 Amp DC at supply voltage

MAINS (UTILITY) DSE74420 ONLY


VOLTAGE RANGE
15 V - 333 V AC (L-N)

FREQUENCY RANGE
3.5 Hz to 75 Hz

GENERATOR
KEY FEATURES • Engine pre-heat • Multiple engine parameters VOLTAGE RANGE
• CAN and magnetic pick-up/Alt. • Protected Solid State Outputs are monitored simultaneously 15 V - 333 V AC (L-N)
sensing versions (specify on (PSS) • Module can be configured to
FREQUENCY RANGE
ordering) • Advanced metering capability suit individual applications 3.5 Hz to 75 Hz
• 3 phase generator monitoring • Front panel/PC programming • Compatible with a wide range
• Four digital inputs/three • Hours counter of CAN engines DIMENSIONS
OVERALL
analogue inputs • LED indicators • IP65 rating offers advanced 180 mm x 116 mm x 42 mm
• Six outputs (all six configurable • Back-lit character icon LCD resistance to water ingress 7.1” x 4.6” x 1.7”
on CANbus version, four display when the gasket is fitted
PANEL CUT-OUT
configurable on magnetic pick- • License-free PC software. 154 mm x 98 mm
up version) KEY BENEFITS 6” x 3.9”
• Three phase sensing • Automatically transfers between
MAXIMUM PANEL THICKNESS
• Event log (5) mains (utility) and generator 8 mm (0.3”)
• 50/60 Hz calibration setting power (DSE4420 only)
• Configurable timers • Hours counter provides
• Automatic shutdown or warning accurate information for
when fault conditions are monitoring and maintenance
detected periods
• Overspeed protection • User-friendly set-up and button
• Manual and remote start layout

RELATED MATERIALS
TITLE PART NO’S
DSE4410 Installation Instructions 053-078
DSE4420 Installation Instructions 053-079
DSE4400 Quick Start Guide 057-103
DSE4400 Operator Manual 057-111
DSE4400 Configuration Suite PC Manual 057-093

DEEP SEA ELECTRONICS PLC UK DEEP SEA ELECTRONICS INC USA


Highfield House, Hunmanby Industrial Estate, Hunmanby YO14 0PH 3230 Williams Avenue, Rockford, IL 61101-2668 USA
TELEPHONE +44 (0) 1723 890099 FACSIMILE +44 (0) 1723 893303 TELEPHONE +1 (815) 316 8706 FACSIMILE +1 (815) 316 8708
EMAIL sales@deepseaplc.com WEBSITE www.deepseaplc.com EMAIL sales@deepseausa.com WEBSITE www.deepseausa.com

Deep Sea Electronics Plc maintains a policy of continuous development and reserves the right to change Registered in England & Wales No.01319649 055-068/01/16 (5)