**$-6HULHV+LJK9ROWDJH6LOLFRQ
5HFWLILHU)RU(OHFWURVWDWLF3UHFLSLWDWRU
We will be with you in the future days. Providing you with top quality products and
services is our perpetual goal – Zhicheng Environmental Protection will create a good
business together with you!
Catalog
Chapter I General………………………………………..………………………..1
OperationEquipment........................................................................….16
1
Chapter VIII Packing, Transportation and Open-package Inspection of
Table 2: parameter list of component and parts for GGAj02-A/KV series high voltage rectifier
Table 3: capacity list of GGAj02-A/KV series high voltage rectifier for electrostatic
precipitator…………………….…………………………………………………….…..29
Table 4: cross reference table for type selection of capacity of GGAj02-A/KV series high
Figure 1: wiring diagram for control system of GGAj02-A/KV series high voltage rectifier for
electrostatic precipitator…………………………………………………………...……32
Figure 2: schematic diagram for control system of GGAj02-A/KV series high voltage rectifier
Figure 3: schematic diagram for control system of GGAj02-A/KV series high voltage rectifier
Figure 4: outline and structural diagram for GGAj02-A/KV series high voltage control
cabinet…………………………………………………………………………………..35
Figure 5: outline and structural diagram and parameter list for GGAj02-A/KV series high
Figure 6: outline diagram for side entry bottom exit high voltage isolation switch cabinet……..37
2
2SHUDWLQJ ,QVWUXFWLRQV IRU **$M 6HULHV +LJK 9ROWDJH 6LOLFRQ 5HFWLILHU IRU (OHFWURVWDWLF 3UHFLSLWDWRU
Chapter I General
I. Product name, model and executive standard
1. Product name: high voltage rectifier for electrostatic precipitator.
2. The model of this product is defined as follows:
G G Aj 02 (ZC11) - A / kV -
Sector Use
Metallurgical To be used for smelting of black and nonferrous metals, dedusting, recovery
industry of raw materials for metal smelting and their comprehensive utilization
Building To be used for dedusting and raw material recovery in the cement and
material industry refractory industries
Electric power
To be used for flue gas dedusting of the boiler
industry
Petroleum To be used for separation of salt, moisture or other impurities contained in
industry crude oil
1
)XMLDQ/RQJ\DQ=KLFKHQJ(QYLURQPHQWDO3URWHFWLRQ&R/WG
2SHUDWLQJ,QVWUXFWLRQVIRU**$M6HULHV+LJK9ROWDJH6LOLFRQ5HFWLILHUIRU(OHFWURVWDWLF3UHFLSLWDWRU
Chemical To be used for recovery of valuable constituents in flue gas and defogging
industry and dedusting, etc. in the acid production industry
Light and textile
To be used for recovery and dedusting in the paper and textile industries
industries
Precision
To be used for air purification and improvement of product quality
machinery
2. Product features:
As the high voltage power supply is a core product for electrostatic dedusting, we always pay
close attention to technical progress, seek innovation and improve strategies.
GGAj02 series high voltage power supply takes the HVC-ZC11 intelligent controller for high
voltage power supply most recently researched and developed by our company as its kernel control
component. The HVC-ZC11 intelligent controller for high voltage power supply is a new generation
controller designed and manufactured by using modern electronic technology, which is focused on
four great objectives of “all-digital technical feature, high precision spark response and control,
ingenious control function and network-based design concept”, based on sufficient absorption of the
essence of DAVC controller product manufactured by American GE company and in combination
with many incisive control theories. The product has the following main technical features:
Ƹ It selects the 32-bit ARM7 core based MCU as its central processing unit (CPU), which
can acquire relevant data in real time and calculate the electric field parameter and spark
parameter rapidly, thus controlling the trigger angle of silicon controlled rectifier accurately.
It has advantages such as rapid response speed, accurate control and high reliability, etc.
Ƹ It selects 240×128 high-brightness blue-screen LCD for information display. Total Chinese
information display and advanced wizard push-key program make the man-machine
interface become very clear and easy for operation. It can be designed into multiple
language display according to needs so as to meet the requirements of export projects.
Ƹ The advanced control program is provided with many operating modes, which can be
selected appropriately according to the use requirements in different industries and various
operating conditions on site so as to make the electrostatic precipitator reach the best
operating effect. Its dynamic spark tracing and detection technology can automatically
distinguish flashover in different intensities and carry out corresponding control, thus
2
)XMLDQ/RQJ\DQ=KLFKHQJ(QYLURQPHQWDO3URWHFWLRQ&R/WG
2SHUDWLQJ ,QVWUXFWLRQV IRU **$M 6HULHV +LJK 9ROWDJH 6LOLFRQ 5HFWLILHU IRU (OHFWURVWDWLF 3UHFLSLWDWRU
making the voltage of electric field recovered from flashover as fast as possible and
improving the efficiency of dust collection. Its perfect and reliable protective functions
make the electrostatic precipitator able to operate stably and reliably for a long period of
time.
Ƹ With the photoelectric full isolation technology and switch power technology as well as the
circuit board designed and manufactured by adopting advanced surface mounting
technology (SMT), the product is featured with preeminent quality, high reliability, strong
anti-interference ability, etc. Meanwhile, the controller is mounted on the door plate with
advantages such as compact structure, convenient operation, etc.
Ƹ The shutdown recording program can record the most recent fault as well as the operating
parameters and time when the fault occurs, which provides great convenience in the
troubleshooting. Meanwhile, the controller implements registration management and green
shade service, thus the user can obtain the best aftersales service.
Ƹ With strong communication networking function, it can realize seamless communication
with the DCS system of our party or a third party.
a. It adopts the most common RS485 serial communication interface on site and
follows MODBUS communication protocol, thus it can conduct data exchange directly
with the PLC and DCS of any mainstream brand in the world; the operating data and
controlling parameters of each power supply can be uploaded to the host computer of DCS
through MODBUS communication protocol; alternatively, the high voltage data of several
electric fields can first be integrated to the PLC in the low voltage control system and then
be uploaded to the host computer through the communication interface (Ethernet or
MODBUS) on the PLC itself by utilizing the margin list, and the host computer manages,
regulates and controls each high voltage equipment indirectly through PLC.
b. It reserves CAN2.0 communication interface, which can realize the high speed
communication connection between up to 127 sets of high voltage power supplies and a
single PLC or host monitoring computer at the same time, build the required DCS work
station and realize data acquisition and exchange with the highest communication speed up
to 1MB/S (40M) and the maximum communication distance of a single node up to 10KM
(5KB/S). For the user who requires CAN2.0 communication, it only needs to change the
3
)XMLDQ/RQJ\DQ=KLFKHQJ(QYLURQPHQWDO3URWHFWLRQ&R/WG
2SHUDWLQJ,QVWUXFWLRQVIRU**$M6HULHV+LJK9ROWDJH6LOLFRQ5HFWLILHUIRU(OHFWURVWDWLF3UHFLSLWDWRU
communication module.
c. Besides being designed with RS485 and CAN2.0 full open communication
interfaces, the HVC-ZC11 intelligent controller for high voltage power supply is also
designed with hard wired communication interfaces, which can build non-open
communication connection conveniently with the DCS of a third party and realize the
function of remote startup and shutdown and voltage regulation of equipment.
Chapter II
5
)XMLDQ/RQJ\DQ=KLFKHQJ(QYLURQPHQWDO3URWHFWLRQ&R/WG
2SHUDWLQJ,QVWUXFWLRQVIRU**$M6HULHV+LJK9ROWDJH6LOLFRQ5HFWLILHUIRU(OHFWURVWDWLF3UHFLSLWDWRU
Chapter III
outline dimensions of 600×600×2200. The color of cabinet frame is: GSB05-1426-2001 [light sea
(iron) blue], and the color of door plate is: GSB05-1426-2001 (sea grey). The cable entry mode is
divided into: top entry and bottom entry. If you have any special requirement for the outline
dimensions and colors, please put forward it when placing an order.
For the appearance of high voltage control cabinet, see attached figure (3).
2. Rectifier transformer
The rectifier transformer is an oil-immersed natural cooling type, including such two sections
as of alternating current booster and high voltage silicon bridge rectifier stack. The transformer
adopts the ri-shaped iron core (“ri” is a Chinese character), which is featured with small loss, low
temperature rise and small volume through computer-aided optimized design. The silicon rectifier
stack adopts avalanche components with long service lifetime, which can be recovered by itself
after instant breakdown and is mounted in the transformer container.
According to the series program recommended by the national standards, the rated output
direct current (average) of rectifier transformer is (unit: A): 0.05, 0.1, 0.2, 0.4, 0.6, 0.7, 0.8, 1.0, 1.2,
1.4, 1.6, 1.8 and 2.0, that is, thirteen grades altogether; and the rated output direct current voltage is
(unit: KV): 40, 50, 60, 66, 72, 80, 90, 100 and 120.
For the rated current and voltage beyond the above series program, we can provide them
according to the user’s requirements.
The structural type of rectifier transformer is high impedance rectifier transformer, which is
divided into the type of cable exit at the high voltage side (outdoor type) and the type of cable exit
at the top (indoor type).
For the outline drawing of rectifier transformer, see attached figure (4).
3. Damping resistor
The damping resistor is connected in series between the high voltage output end of rectifier
transformer and the cathode line of electrostatic precipitator, which is a protective component in the
electric circuit system of rectifier. It plays an important role in the suppression of flashover impact
current, absorption of higher harmonic wave and protection of control circuit during the operation.
For the outdoor type rectifier transformer (with cable exit at the high voltage side) provided
with high voltage isolation switch cabinet, the damping resistor is commonly mounted in the high
voltage isolation switch cabinet.
7
)XMLDQ/RQJ\DQ=KLFKHQJ(QYLURQPHQWDO3URWHFWLRQ&R/WG
2SHUDWLQJ,QVWUXFWLRQVIRU**$M6HULHV+LJK9ROWDJH6LOLFRQ5HFWLILHUIRU(OHFWURVWDWLF3UHFLSLWDWRU
The resistance and power of damping resistor shall be selected according to “Parameter List
for Main Components in the Primary Circuit” (attached table 2).
4. High voltage isolation switch and switch cabinet
The high voltage isolation switch is used to connect the high voltage incoming terminal in the
electric field of electrostatic precipitator with the high voltage output terminal of rectifier
transformer or the ground so as to ensure the personal safety during the repair of electrostatic
precipitator.
The high voltage isolation switch cabinet is generally used with the outdoor type rectifier
transformer and is placed between the rectifier transformer and temperature holding cabinet. The
flange of high voltage protective cover on the outdoor type rectifier transformer shall be joined to
the inlet flange of switch cabinet. The high voltage inlet and outlet directions of high voltage
isolation switch cabinet as well as the on-off operating direction of high voltage isolation switch
shall be determined by the user according to site arrangement.
II. Operating principle of primary circuit
For the electric schematic diagram, see attached figure (2).
The electric schematic diagram is mainly composed of primary circuit, operating control
circuit and auxiliary circuit (e.g. cooling fan), etc. The single phase alternating current 380V, 50 Hz
power supply is connected with the primary contactor KM1 through fuses FU1 and FU2. After the
control of primary contactor KM1, one output is connected with the input terminal A of transformer
through two silicon controlled rectifiers V1 and V2 in inverse parallel; the other output is connected
with the X1 terminal of transformer through the primary current transformer TA1. The phase-shifted
and voltage-regulated single phase alternating current power supply is output as the negative high
voltage after the voltage boosting and current rectification of transformer, and is supplied to the
electrostatic precipitator through the damping resistor. R7 and R6 are respectively the current
sampling resistor and voltage sampling resistor at the direct current high voltage side. The
secondary current and secondary voltage sampling signals are sent to the controller, which output
the conduction angle of trigger signal controlled thyristor (silicon controlled rectifier) after the
operation and processing of computer system. This automatic control system adopts the dual
closed-loop automatic control system with current inner loop feedback and voltage outer loop
feedback. The functions of other main components in the primary circuit are as follows:
8
)XMLDQ/RQJ\DQ=KLFKHQJ(QYLURQPHQWDO3URWHFWLRQ&R/WG
2SHUDWLQJ ,QVWUXFWLRQV IRU **$M 6HULHV +LJK 9ROWDJH 6LOLFRQ 5HFWLILHU IRU (OHFWURVWDWLF 3UHFLSLWDWRU
Alternating current voltmeter PV1: it displays the primary side voltage of rectifier transformer
after the voltage regulation of silicon controlled rectifier.
Alternating current ammeter PA1: it displays the primary side current of rectifier transformer.
Direct current voltmeter PV2: it displays the direct current voltage output by the equipment,
also called the secondary voltage.
Direct current ammeter PA2: it displays the direct current output by the equipment, also called
the secondary current.
R1 and C1 are resistance-capacitance absorption circuits.
Piezoresistors RV1-5: they absorb surge overvoltage.
Damping resistor R5: it buffers the spark discharge current and damps the parasitic oscillation
caused by LC distribution parameter in high voltage output circuit.
Resistor R4: it is a high voltage sampling dropping resistor.
Current transformer TA1: it provides the analog meter and controller with primary current
signal.
The power switch SA1 for control circuit: the on-off control for power supply of control circuit
and selection of local control/central control can be realized through SA1.
Isolation transformer T2: it provides the control circuit and remote control communication
board with AC 220V alternating current power supply after the isolation and voltage transformation
of single phase 380V, 50Hz power supply.
Safety interlock relay KA1: it realizes the safety interlock control of high voltage control
system. The system can be allowed to start up only after each safety interlock link is closed in
position and it is picked up.
Startup/shutdown control relay KA2: it realizes the startup and shutdown control of high
voltage control system. The control auxiliary contactor KM2 is energized after it is picked up, thus
controlling the pick-up of primary contactor KM1; and the control intermediate contactor KM2 and
the primary contactor KM1 are both de-energized and released after it is de-energized.
Fault alarm relay KA3: when any fault trip phenomenon appears in the system, it will act and
send out a sound and light alarm signal.
Primary contactor KM1: it controls the switch-on or cut-off of primary circuit.
Auxiliary contactor KM2: it controls the pick-up or release of primary contactor KM1.
9
)XMLDQ/RQJ\DQ=KLFKHQJ(QYLURQPHQWDO3URWHFWLRQ&R/WG
2SHUDWLQJ,QVWUXFWLRQVIRU**$M6HULHV+LJK9ROWDJH6LOLFRQ5HFWLILHUIRU(OHFWURVWDWLF3UHFLSLWDWRU
Chapter IV
Measurement High voltage output High voltage output to High voltage output to
object to earth current sampling voltage sampling
Reverse Forward
Resistance (M) ᧺2500 direction ˚ direction ˘ ᧹78
2500 0.5
High voltage output
Measurement Low voltage terminal to
to low voltage
object earth
terminal
2. Installation of transformer
(1) When lifting the transformer, the wire cable with the diameter of 20~25mm shall be used to
10
)XMLDQ/RQJ\DQ=KLFKHQJ(QYLURQPHQWDO3URWHFWLRQ&R/WG
2SHUDWLQJ ,QVWUXFWLRQV IRU **$M 6HULHV +LJK 9ROWDJH 6LOLFRQ 5HFWLILHU IRU (OHFWURVWDWLF 3UHFLSLWDWRU
hook up the lifting eyes on the transformer tank body for lifting; if the lifting hooks are used for
lifting, then the diameter of lifting hooks shall not be more than 30mm so as to avoid damaging the
radiating fins due to compression. It is strictly forbidden the use the lifting eyes on the tank cover to
lift the entire transformer.
(2) When the high voltage rectifier transformer is installed in the isolation chamber, it shall be
kept more than 1m away from walls.
(3) After the installation and commissioning of high voltage rectifier transformer are finished
in position, the universal wheel shall be fixed at the bottom of transformer with channel steel so as
to prevent the displacement.
3. Installation of high voltage control cabinet
The high voltage control cabinet must be fixed with anchor bolts according to the requirement
of outline drawing.
4. Installation and arrangement of circuit
(1) Conduct wiring according to attached figure 1. Besides providing 380V alternating current
power supply, the power supply incoming line must also provide N line with a cross section not less
than 2.5mm2.
(2) According to relevant provisions of low voltage power distribution, select the specified
copper core cable to connect the power supply, high voltage control cabinet and silicon rectifier
transformer. The current and voltage feedback signal wires shall adopt RVVP4×1.5mm² shielded
cable, and the metal shielded layer shall have single end earthing within the controller or high
voltage control cabinet. When the equipment communicates with the PLC or host computer, it shall
adopt DJYPVP3×2×0.5 mm² triple twisted pair pairwise shielded cable.
Note: the secondary current and voltage sampling signals and the rectifier transformer oil
temperature sampling signal must be connected with the control cabinet through their respective
shielded cables, which cannot be replaced by common control cables.
(3) The earthing terminals of control cabinet, rectifier transformer and load shell must all be
grounded very reliably, with their earthing resistance not more than 2.0. In order to prevent the
interference, the earthing terminals of high voltage control cabinet, rectifier transformer and load
(e.g. the anode of electrostatic precipitator) shall be connected with each other at the same point for
earth connection
11
)XMLDQ/RQJ\DQ=KLFKHQJ(QYLURQPHQWDO3URWHFWLRQ&R/WG
2SHUDWLQJ,QVWUXFWLRQVIRU**$M6HULHV+LJK9ROWDJH6LOLFRQ5HFWLILHUIRU(OHFWURVWDWLF3UHFLSLWDWRU
The detailed arrangement method for earthing wires is as follows: a piece of multi-strand
copper core wire with a cross section not less than 35mm2 shall be directly arranged from the
earthing terminal of each rectifier transformer to the earthing busbar of high voltage control cabinet.
Meanwhile, a piece of multi-strand copper core wire with a cross section not less than 16mm2 shall
be arranged from the earthing terminal of rectifier transformer to the earthing bolt on the
transformer shell, then a piece of multi-strand copper core wire with a cross section not less than
16mm2 shall be arranged from the earthing bolt to the anode of load (i.e. the shell of main body).
(4) The equipment wiring shall comply with relevant provisions of high voltage and low
voltage wiring specified by the country.
(5) In order to prevent the interference, during the cable arrangement, the power cable, signal
cable and communication cable shall be separately arranged so as to avoid mutual cross
interference.
II. Simulation commissioning of equipment
1. False-load test of the high voltage control cabinet
In order to ensure the safe reliability of equipment, before the first operation and reoperation
after the repair of the equipment, two pieces of power primary cables must be disconnected between
the high voltage control cabinet and rectifier transformer; two incandescent lamp bulbs with their
power not less than 100W shall be connected with each other in series and then be connected with
the power outlet terminal of high voltage control cabinet. Do voltage stepup test in manual
operating mode by using normal equipment starting method so as to ensure that the equipment will
be connected with the rectifier transformer to work at load only after the silicon controlled rectifier
can be triggered normally.
2. Fault alarm test of the equipment
(1) Oil temperature alarm: the rectifier transformer shall be equipped with a PT100
temperature sensor. When the transformer oil temperature reaches 85ć, the controller will send out
a trip signal and give an alarm, and the display screen of controller will display the oil temperature
out-of-tolerance fault of transformer.
(2) High voltage safety interlock: after the installation of transformer, control cabinet and load,
it is necessary to interlock the high voltage output available switch with the startup operation of
control cabinet so as to ensure safe power supply. When the safety interlock is not available, it is not
12
)XMLDQ/RQJ\DQ=KLFKHQJ(QYLURQPHQWDO3URWHFWLRQ&R/WG
2SHUDWLQJ ,QVWUXFWLRQV IRU **$M 6HULHV +LJK 9ROWDJH 6LOLFRQ 5HFWLILHU IRU (OHFWURVWDWLF 3UHFLSLWDWRU
allowed to start the equipment, and the controller has the prompt for unavailable safety interlock.
(3) Load open-circuit/short-circuit protection: when the high voltage output of transformer is
open-circuited, the controller can trip for open circuit and meanwhile control the secondary voltage
does not exceed the rated value; when the high voltage output of transformer is short-circuited, the
controller can trip for short circuit and meanwhile control the secondary current does not exceed the
rated value.
III. Equipment use
1. Check and adjustment before the first startup
(1) Disconnect the power supply for entering the control cabinet;
(2) Check if the plug of controller is connected reliably;
(3) Check if all wires are correct and reliable;
(4) Check if all fuses are in good conditions and without looseness;
(5) Check the insulation of load (electric field of electrostatic precipitator) with a 2500V
megger, and its resistance value shall be above 100M generally.
(6) Check if the secondary current and voltage sampling resistances comply with the
requirements with a multimeter. For the standard secondary current sampling resistance of the
equipment of various specifications, see attached table (2), and the secondary voltage sampling
resistance is 7.8K.
2. Local startup of the equipment:
Close the circuit breaker QF1 of operating power supply, and the “power indicator” green lamp
HL1 will be lit. The master switch SA1 will be changed over to “local” position. The HVC-ZC11
high voltage intelligent controller for power supply will be energized for self-check and be rest by
itself. The display screen will display the salutatory interface, then enter the shutdown recording
interface. After the “confirmation” key is pressed, the system will enter the initial waiting interface.
At this time, if the “automatic” key is pressed, then the controller will automatically control the
pick-up of primary contactor KM1. After that, the voltage will be increased slowly until it reaches a
set limit value. Then, it will operate around this value. When the “manual” key is pressed, it will
enter the manual waiting interface. At this time, the required operation can be selected according to
the menu. After the primary contactor KM1 is picked up, the “power indicator” green lamp HL1
will be turned out and the “system operating” red lamp HL2 will be lit, thus the system will enter
13
)XMLDQ/RQJ\DQ=KLFKHQJ(QYLURQPHQWDO3URWHFWLRQ&R/WG
2SHUDWLQJ,QVWUXFWLRQVIRU**$M6HULHV+LJK9ROWDJH6LOLFRQ5HFWLILHUIRU(OHFWURVWDWLF3UHFLSLWDWRU
temperature: 028ć
Reset Reset
Prompt: the system is at the initial waiting state! Prompt: this cabinet is at the manual waiting state!
Primary voltage: 000V Secondary voltage: 000KV Primary voltage: 000V Secondary voltage: 000KV
Primary current: 000A Secondary current: 000mA Primary current: 000A Secondary current: 000mA
Reset Reset
Prompt: this cabinet is at the automatic voltage step-up state! Voltage limit: 072KV Turn-off wave number: 01
Primary voltage: 321V Secondary voltage: 066KV Current limit: 800mA Slow step-up rate: 05
Primary current: 198A Secondary current: 752mA Shortcut limit: current Recovery wave number: 06
Reset Reset
6. Fault trip:
15
)XMLDQ/RQJ\DQ=KLFKHQJ(QYLURQPHQWDO3URWHFWLRQ&R/WG
2SHUDWLQJ,QVWUXFWLRQVIRU**$M6HULHV+LJK9ROWDJH6LOLFRQ5HFWLILHUIRU(OHFWURVWDWLF3UHFLSLWDWRU
When the faults such as permanent short circuit, open circuit, primary overload, oil
temperature out-of-tolerance, heavy gas alarm, etc. occur in the electric field, the HVC-ZC11
controller will judge them automatically and output the trip signal. At this time, the startup and
shutdown control relay KA2 will be de-energized, the contacts KM2 and KM1 will be released to
disconnect the primary circuit, the fault alarm relay KA3 will be energized, and the fault alarm
buzzer HA1 will give a sound and light alarm. LCD will display the fault parameters and fault
causes. After the “confirmation” key is pressed, the fault alarm relay KA3 will be energized, stop
giving an alarm and return to the initial waiting interface.
IV. Precautions for equipment use
1. In order to ensure the equipment and personal safety, it is strictly forbidden to change over
the high voltage isolation switch or switch off the power supply switch directly when the equipment
is at operating state.
2. The current and voltage feedback signal wires between the rectifier transformer and control
cabinet must use metal shielded wires so as to prevent from the interference.
3. In order to ensure the personal safety, it is strictly forbidden to enter the high voltage
isolation chamber during the operation of equipment.
1.Fault characteristics of (1) The high voltage isolating knife is (1) Put the high voltage
short circuit: very low grounded. isolating knife at the electric
primary voltage, relatively (2) The high voltage cable is breakdown or field position.
big primary current, nearly the insulation of terminal connector is (2) Handle or replace the
zero secondary voltage and damaged or breakdown, thus causing a cable or terminal connector.
very big secondary short circuit to earth. (3) Discharge the ash
current. (3) The ash hopper of electric field has a accumulated in the ash
serious ash accumulation, thus causing a hopper.
short circuit between the electric cathode (4) Shut down the boiler to
16
)XMLDQ/RQJ\DQ=KLFKHQJ(QYLURQPHQWDO3URWHFWLRQ&R/WG
2SHUDWLQJ ,QVWUXFWLRQV IRU **$M 6HULHV +LJK 9ROWDJH 6LOLFRQ 5HFWLILHU IRU (OHFWURVWDWLF 3UHFLSLWDWRU
2.Fault characteristics of (1) The high voltage isolating knife is not (1) Put the high voltage
open circuit: relatively in position. isolating knife at the electric
low primary voltage, field position.
nearly zero primary (2) The damping resistor at the top of (2) Replace the damping
current, very high electric field is blown out. resistor.
secondary voltage and
zero secondary current.
3.Fault characteristics: (1) The rapping period of electric cathode (1) Adjust the rapping
normal primary voltage, is too long, thus causing a serious ash period.
relatively low primary accumulation on the line of electric
17
)XMLDQ/RQJ\DQ=KLFKHQJ(QYLURQPHQWDO3URWHFWLRQ&R/WG
2SHUDWLQJ,QVWUXFWLRQVIRU**$M6HULHV+LJK9ROWDJH6LOLFRQ5HFWLILHUIRU(OHFWURVWDWLF3UHFLSLWDWRU
current, relatively low cathode and generating a corona (2) Handle and improve the
secondary voltage and obstruction. rapping system.
obviously reduced (2) The rapping force of electric cathode is
secondary current. not big enough. (3) Handle the fault or shut
(3) The rapping device for the line of down the boiler to handle
electric cathode has a fault. the seized hammerhead, etc.
(4) The flue dust concentration at the inlet (4) Contact the boiler to
of electric field is too high. adjust the combustion and
(5) The dust specific resistance is too big, calcined powder.
thus causing a back corona (too high or too (5) Change the coal type.
low secondary current).
4.Fault characteristics:
lower primary voltage, (1) The trigger pulse circuit of silicon (1) Replace the pulse trigger
lower primary current, controlled rectifier is not symmetric. plate.
lower secondary voltage
and lower secondary (2) A silicon controlled rectifier is (2) Replace the damaged
current. All of them have short-circuited, thus causing deflected silicon controlled rectifier.
vibration. The high voltage excitation operation.
rectifier transformer is
accompanied by abnormal
sound. With the increase of
current, the “puffing”
sound will be raised and
the oil temperature will be
increased.
5. Fault characteristics:
normal primary voltage
and normal primary (1) The meter is damaged. Replace the meter.
current. No display on
the meter of secondary
18
)XMLDQ/RQJ\DQ=KLFKHQJ(QYLURQPHQWDO3URWHFWLRQ&R/WG
2SHUDWLQJ ,QVWUXFWLRQV IRU **$M 6HULHV +LJK 9ROWDJH 6LOLFRQ 5HFWLILHU IRU (OHFWURVWDWLF 3UHFLSLWDWRU
voltage or secondary
current, but normal
display on the
controller.
6. Fault characteristics:
when the “startup” key
is pressed, the fault type (1) The resistance-capacitance absorption
displayed on the capacitor C1 or the resistance-capacitance Replace the fault
controller is: “short absorption resistor R1 is damaged. component.
circuit alarm” or “open (2) One or two silicon controlled rectifiers
circuit alarm”, and are damaged.
meanwhile, measure the
output terminal with a
multimeter (wire size:
104, 108), which is as
big as power supply
voltage.
7. Fault characteristics:
when the “step-up” key (1) The primary contactor has a fault or the
is pressed, the primary primary circuit is not formed. Replace the fault
current, primary (2) The controller or the pulse trigger plate component.
voltage, secondary has a fault.
current and secondary
voltage do not have any
reaction and are always
zero.
8. Fault characteristics:
once startup, the
equipment will trip. The (1) One or two silicon controlled rectifiers (1) Replace the fault silicon
controller will display are short-circuited. controlled rectifier.
19
)XMLDQ/RQJ\DQ=KLFKHQJ(QYLURQPHQWDO3URWHFWLRQ&R/WG
2SHUDWLQJ,QVWUXFWLRQVIRU**$M6HULHV+LJK9ROWDJH6LOLFRQ5HFWLILHUIRU(OHFWURVWDWLF3UHFLSLWDWRU
Chapter VI
20
)XMLDQ/RQJ\DQ=KLFKHQJ(QYLURQPHQWDO3URWHFWLRQ&R/WG
2SHUDWLQJ ,QVWUXFWLRQV IRU **$M 6HULHV +LJK 9ROWDJH 6LOLFRQ 5HFWLILHU IRU (OHFWURVWDWLF 3UHFLSLWDWRU
1. When it has any doubt about the interior after the rectifier transformer has any collision or
other events during the transportation or it needs to conduct repair after a fault occurs during the
operation, the active part inspection shall be conducted.
2. Active part operation for rectifier transformer
(1) Before the active part is lifted, first loosen the oil drain valve on the lower part of
transformer tank and discharge about 80KGS of transformer oil. Pay attention to ensure that the
discharged oil is contained and sealed in a clean vessel so as to prevent the transformer oil from
being polluted. Meanwhile, its storage time shall be as short as possible for fear of becoming damp
and reducing the dielectric strength.
(2) Remove all connecting bolts on the tank cover and tank body.
(3) Before the active part is lifted, for the outdoor type, first open the small cover plate and
stretch the hand into the oil tank. The lifting can be conducted only when the wires between the
high voltage output and porcelain insulator connecting terminal are released with a wrench. After
the active part inspection is finished, the active part shall be put into the oil tank and then restored to
its original condition.
(4) When the active part is lifted, pay attention to the balance of gravity center on the active
part. Four corners of the oil tank shall be monitored so as to prevent from the collision between the
active part and tank body and cause any damage.
(5) After the active part inspection is finished, put the active part into the oil tank and install
and fasten it in opposite direction. Connect the high voltage output wire and fill in the transformer
oil.
3. Main items in the active part inspection are as follows:
(1) If the coil has any collision injury and if the silicon rectifier stack has any crack;
(2) If the high voltage porcelain insulator has any damage and if all parts and fasteners have
any looseness phenomenon;
(3) The iron core shall be grounded reliably and only grounded at one point; for that with a
core-crossing screw stem, measure the insulation resistance between it and core with a 2500V
megger, and the resistance value must be more than 1000M.
4. Precautions for the active part inspection for transformer:
(1) The lifting of active part shall be conducted in good weather conditions when it is dry
21
)XMLDQ/RQJ\DQ=KLFKHQJ(QYLURQPHQWDO3URWHFWLRQ&R/WG
2SHUDWLQJ,QVWUXFWLRQVIRU**$M6HULHV+LJK9ROWDJH6LOLFRQ5HFWLILHUIRU(OHFWURVWDWLF3UHFLSLWDWRU
without dust and moisture (the relative humidity shall not be more than 75%) and at a clean position.
Its lifting time shall be as short as possible so as to avoid from becoming damp or being polluted
and thus reducing the dielectricity. The active part inspection cannot be conducted in rainy days.
(2) When the lifted active part is exposed to the air, its continuous time for contacting with the
air outside shall not exceed the following provisions:
In dry air (the relative humidity of air shall not be more than 65%) 3 hours.
In humid air (the relative humidity of air shall not be more than 75%) 1 hours.
(3) After the rectifier transformer goes through the active part inspection, the power-on test can
be conducted only after the transformer oil is filled back and generally stands for 24 hours for fear
of high voltage discharge in bubbles.
5. Withstand voltage test for transformer oil
If the condition permits, the breakdown voltage shall be measured for transformer oil. The oil
sample shall be taken from the oil drain valve. At this time, the oil temperature shall not be lower
than +5ć. The transformer oil must go through the withstand voltage test, and the average instant
breakdown voltage value of five tests shall be more than 35KV/2.5mm. If the breakdown voltage of oil
is lower than the required value, it can be used only when the causes are found out and it is handled
accordingly. In addition, if it needs to replenish oil, it is preferable to add the oil of same grade as far as
possible. In case the oil grade is different, then it can be mixed for use only after the chemical analysis is
conducted in advance.
6. Withstand voltage test for transformer
The rectifier transformer has already go through the induced voltage withstand test and applied
high voltage test before leaving the factory. If the high voltage test is required on the site, then it is
necessary to short circuit the high voltage set on the silicon rectifier stack, disassemble the high
voltage measuring resistor and current feedback outlet wire, put them into the oil again and stand
for 24 hours. Then the high voltage porcelain insulator shall go through the withstand voltage test to
earth. Otherwise, the applied high voltage test can not be conducted. For the silicon rectifier
transformer below 72KV, its test voltage shall be more than 1.1 times of rated voltage and less than
1.5 times of rated voltage.
22
)XMLDQ/RQJ\DQ=KLFKHQJ(QYLURQPHQWDO3URWHFWLRQ&R/WG
2SHUDWLQJ ,QVWUXFWLRQV IRU **$M 6HULHV +LJK 9ROWDJH 6LOLFRQ 5HFWLILHU IRU (OHFWURVWDWLF 3UHFLSLWDWRU
Chapter VII
Chapter VIII
problems of missing and damage. After finding out the causes jointly, the responsible party shall
bear the responsibility and pay the amount dues to the manufacturer.
V. After the equipment arrives in the site, for any missing, damage, etc. of equipment purely due to
improper storage and use, all responsibilities shall be borne by the user itself.
VI. The warranty period of equipment shall be 12 months from the commencement date of
installation and commissioning or 18 months from the delivery date of equipment, whichever is
earlier.
24
)XMLDQ/RQJ\DQ=KLFKHQJ(QYLURQPHQWDO3URWHFWLRQ&R/WG
2SHUDWLQJ ,QVWUXFWLRQV IRU **$M 6HULHV +LJK 9ROWDJH 6LOLFRQ 5HFWLILHU IRU (OHFWURVWDWLF 3UHFLSLWDWRU
Table 1: parameter list of common component and parts for GGAj02-A/KV series high voltage
rectifier for electrostatic precipitator
Position
No. Name Model Remarks
No.
NFM1-22/FS
3 HA1 Fault alarm buzzer Yellow
AC220V
Startup/shutdown control
11 KA2 HF18FF/024-2Z1D With frame
relay
RV2ᇬ
16 Piezoresistor MY31-720V/5KA
RV3
26
)XMLDQ/RQJ\DQ=KLFKHQJ(QYLURQPHQWDO3URWHFWLRQ&R/WG
2SHUDWLQJ ,QVWUXFWLRQV IRU **$M 6HULHV +LJK 9ROWDJH 6LOLFRQ 5HFWLILHU IRU (OHFWURVWDWLF 3UHFLSLWDWRU
Table 2: parameter list of component and parts for GGAj02-A/KV series high voltage rectifier
for electrostatic precipitator
Name &
specification
of
Primary Silicon Direct Current
components Capacitor Current Alternating
contactor Common controlled Resistor current Damping sampling
and parts U1~3 transformer current
KM1 fuse rectifier R1 ammeter resistor resistor
CJ48B-2 TA1/TA2 ammeter
HDLRTO V1/V2 KP RX20 A2 6C2 - R5 ZG12 R7
-500V BH-0.66 A1 6L2-A
series 0.1MA RX20
Equipment
model
66
0.5 200 1.0 20/12
72
80 160 200/5 200
800 1200/1
60 150/5 150
66
0.6 20/10
72 250 500 50/20 200/5 200
200
80
27
)XMLDQ/RQJ\DQ=KLFKHQJ(QYLURQPHQWDO3URWHFWLRQ&R/WG
2SHUDWLQJ,QVWUXFWLRQVIRU**$M6HULHV+LJK9ROWDJH6LOLFRQ5HFWLILHUIRU(OHFWURVWDWLF3UHFLSLWDWRU
60
66
0.7 30/8.6
72
80 250/5 250
60 200/5 200
66
0.8 250 1000 30/7.5
72 300
250/5 250
80
500
60
66
1.0 300/5 300 30/6
72
80 400/5 400
315
60
350
66 300/5 300
1.1 30/5.5
72
80 400/5 400
1500
60 300/5 300
66
1.2 30/5
72
400 400
2800/
80
400/5 400
60 700
66
1.4 50/4.3
72
80 800 500/5 500
60
450 2.0 400/5 400
66
1.5 50/4
72
80
60
500
66
1.6 2000 50/3.75
72 500/5 500
80
500
60
66
1.8 50/3.4
72
3000/
80 600/5 600
60 500/5 500 500
550
66 630 1000
2.0 2500 50/3
72 600/5 600
80 600
28
)XMLDQ/RQJ\DQ=KLFKHQJ(QYLURQPHQWDO3URWHFWLRQ&R/WG
2SHUDWLQJ ,QVWUXFWLRQV IRU **$M 6HULHV +LJK 9ROWDJH 6LOLFRQ 5HFWLILHU IRU (OHFWURVWDWLF 3UHFLSLWDWRU
Table 3: capacity list of GGAj02-A/KV series high voltage rectifier for electrostatic precipitator
29
)XMLDQ/RQJ\DQ=KLFKHQJ(QYLURQPHQWDO3URWHFWLRQ&R/WG
2SHUDWLQJ,QVWUXFWLRQVIRU**$M6HULHV+LJK9ROWDJH6LOLFRQ5HFWLILHUIRU(OHFWURVWDWLF3UHFLSLWDWRU
60 180 68 60 48
66 199 76 66 53
0.8 0.8
72 217 82 72 58
80 241 92 80 64
60 226 86 60 60
66 248 94 66 66
1.0 1.0
72 271 103 72 72
80 301 115 80 80
60 248 94 60 66
66 273 104 66 73
1.1 1.1
72 298 113 72 79
80 331 126 80 88
60 271 103 60 72
66 298 113 66 79
1.2 1.2
72 325 124 72 86
80 361 137 80 96
60 322 122 60 84
66 351 133 66 92
1.4 1.4
72 378 144 72 101
380/220
80 420 160 80 112
60 338 128 60 90
66 372 141 66 99
1.5 1.5
72 406 154 72 108
80 451 171 80 120
60 361 137 60 96
66 397 151 66 106
1.6 1.6
72 433 165 72 115
80 481 183 80 128
60 406 154 60 108
66 447 170 66 119
1.8 1.8
72 487 185 72 130
80 541 206 80 144
60 451 171 60 120
66 496 188 66 132
2.0 2.0
72 541 206 72 144
80 602 229 80 160
30
)XMLDQ/RQJ\DQ=KLFKHQJ(QYLURQPHQWDO3URWHFWLRQ&R/WG
2SHUDWLQJ ,QVWUXFWLRQV IRU **$M 6HULHV +LJK 9ROWDJH 6LOLFRQ 5HFWLILHU IRU (OHFWURVWDWLF 3UHFLSLWDWRU
Table 4: cross reference table for type selection of capacity of GGAj02-A/KV series high voltage
rectifier for electrostatic precipitator
Due to difference in the body structure and operation site of equipment, the secondary current
of equipment will vary from each other. For specific type selection, the type selected by the design
institute shall govern, and this table is only for reference
31
)XMLDQ/RQJ\DQ=KLFKHQJ(QYLURQPHQWDO3URWHFWLRQ&R/WG
Scope Of Business
★ GGAJ02 Series Single-Phase High Voltage Rectifier For Electrostatic Precipitator;
★ GGAJ06 Series Three-Phase High Voltage Rectifier For Electrostatic Precipitator;
★ HF Series High Frequency, High Voltage Power Supply For Electrostatic Precipitator;
★ Low Voltage Control System And Complete Project For Electrostatic Precipitator And
Bag Dust Collector, Desulphurization, Denitrification And Pneumatic Ash Handling.
★ Industrial Automatic Control System And Complete Project;
★ Development Of Application Software.
Address: Dongbao Industrial Concentrated Area, Longzhou Industrial Park, Fujian Province
Tel.: +86-597-2337888
Fax: +86-597-2303182
E-Mail: fjzchb@163.com
Postal Code: 364000