Sei sulla pagina 1di 8

providing insights for today’s hvac system designer

Engineers Newsletter
volume 47–3

impacts of
Chilled-Water System Design Decisions

Primary-secondary system bypass


This Engineers Newsletter walks through
a number of design decisions, with
Bypass line sizing sizing. The premise of a primary-
discussion and examples to explain how secondary system is to hydraulically
This seemingly simple decision can have
and why those decisions are made. separate (decouple) the primary (chiller)
significant consequences if not done
flow from the secondary (system) flow.
correctly.
This decoupling prevents the operating
• In a primary-secondary system, the pressures of chiller pumps from impacting
While designing a chilled-water
bypass pipe should be the same the operating pressures of the system
system, a myriad of decisions must
diameter as the pipe going into the pumps. This is accomplished by installing
be made. Experienced engineers
largest chiller. Its length should be a bypass line with a small pressure drop.
often make these decisions
about 8-10 pipe diameters long or The bypass allows water to flow in either
"automatically" as they have in the
have an equivalent pressure drop. direction and is used to indicate chiller and
past, based on what they have
learned from experience. Today, all • In a variable primary flow (VPF) primary pump sequencing in this system
engineers likely use an internet system, the bypass line should be arrangement (Figure 1).
search engine to get direction, but sized for the largest minimum flow
Chillers and constant flow primary pumps
when there are differing—or even rate and it will have a control valve.
are enabled in pairs, making the primary
conflicting—recommendations a
The reasons behind this guidance follow. flow rate a step function. As system load
decision must be made.
and flow increase, the excess flow rate
Common decisions regarding (from supply to return) in the bypass line
chilled-water system designs decreases. At the point that system flow
include: rate exceeds chiller flow rate, deficit flow

• bypass line sizing in variable Figure 1. Primary-secondary system


flow systems
• dynamically varying condenser
primary
water flow
pumps
• number of chilled-water pumps
to operate secondary
pumps with
• series chillers and power VSDs
consumption chilled-water
coling coils
• whether to use pressure- with two-way
independent control valves valves

bypass line, free of restrictions, sized the same as the


largest chiller’s pipe, aim for a pressure drop equivalent to a
pipe that is 8-10 pipe diameters long.

©2018 Trane. All rights reserved. 1


(from return to supply) in the bypass Figure 2. Oversized bypass can allow simultaneous flow in both directions
line occurs. This warm, deficit water
flow increases the system supply- chiller return chiller supply
water water
water temperature and at some point
an additional chiller and primary pump
are enabled.
short-circuited chiller
A chiller and pump are disabled when supply water

excess flow rate in the bypass line is


high enough to still have excess flow
after a primary pump is turned off.
Therefore the maximum flow rate the
bypass line ever experiences is a little short-circuited system
higher than the design flow rate of the return water
largest chiller. Often designers wait for
10-15 percent excess flow, to ensure
system system
that chillers are not cycled on and off return water supply water
rapidly. Therefore the bypass pipe
should be sized for 110 to115 percent
• Much of that water continues to the Add pressure drop. A better option
of the largest chiller's flow rate—which
chillers but some of the warm water may be to place an orifice in the line. This
most designers simplify to the same
(due to low pressure drop in the can simply be a plate with a hole in it.
as the pipe size going into the largest
bypass) flows in the deficit direction This imposes a pressure drop, but allows
chiller.
in the bypass line (from return to the water to flow freely in either the surplus
supply). or deficit direction. In a few extreme
What happens if bypass sizing is cases it has been neccessary to
not right? Too little or too much As a result there is simultaneous flow in completely block off the oversized/short
pressure can cause issues... opposite directions because the bypass bypass pipe and install a properly sized
line has become so large it functions like pipe of sufficient length to eliminate the
Too small, pressure too high? An a tank! mixing condition.
undersized bypass line can result in
high fluid velocity, which in extreme The diluted (higher) system supply-water The best way to avoid issues in a
conditions may cause pipe erosion, temperature results in more pumping primary-secondary system is to size the
vibration and acoustic issues. The high energy. The short-circuited supply water bypass line properly during the design
fluid velocity can also result in high mixing with return water results in process. Simply check the drawings and
enough pressure drop so that flow is reduced chiller return-water temperature. ensure that the bypass line is smaller
restricted through the bypass, and This can restrict the chillers’ ability to than the manifold, and the same size as
may actually cause the primary and fully load. the pipe going into the largest chiller and
secondary pump pressures and flow 8 to 10 equivalent pipe diameters long. If
rates to affect each other. If the pipes are already installed how the pipe is less than 8 to10 pipe
can the situation be improved? A diameters long, using elbows to form a
Too large, pressure too low? A
resolution for too low of a pressure drop "U" adds an appropriate pressure drop.
benefit of an oversized bypass pipe is a
is to impose a modest restriction to keep
very low pressure drop, however if it's
water from short-circuiting. Aim for the Variable-primary-flow system bypass
too low, the water may not flow as
equivalent pressure drop of a pipe that is line sizing. Conceptually a variable-
intended. Figure 2 illustrates the issue:
8 to 10 pipe diameters long. primary-flow system is simpler to get
• Cold water leaves the chillers and right. The valve in the bypass line only
flows into the chiller supply Often the first solution considered is to
opens when the system flow rate
manifold. add a valve. Given that the bypass line is
approaches the minimum flow rate of the
oversized, it’s likely the additional valve
• A portion of that cold water flows operating chiller(s). So the bypass pipe
will be big and expensive. It’s also likely
toward the secondary pump. and valve only need to be sized for the
that at some point a well-meaning but
However due to the very low largest minimum flow rate. Usually that's
uninformed operator will close the valve
pressure drop in the bypass, some the largest chiller's minimum flow rate.
too much. Or, they might open it all the
of the cold water seeks the path of However, depending on chiller
way and defeat this solution. Recall that
least resistance and flows through selections, the largest minimum flow
the bypass line in a primary-secondary
the bypass line in the excess rate might not be for the largest chiller in
system should allow water to flow freely,
direction. the plant. Also consider the combined
in either direction, as needed.
minimum flow required when two
• Similarily in the return-water side,
chillers are operating at part load, just
warm return water flows in the
before sequencing off one chiller.
system return manifold.

2 Trane Engineers Newsletter volume 47-3 providing insights for today’s HVAC system designer
Table 1. Plant annualized kW/ton and percent savings compared to two-chiller base for three alternatives
Should we dynamically vary
Condenser
the condenser water flow? Chiller Cooling water flow
Condenser Tower Plant
Alternative water flow control annualized Savings
type tower fan rate
Yes, savings are available in existing type method* kW/ton
(gpm/ton)
systems designed between 2.5 to 3.2
gpm/ton (12 to 9.4ºF ΔT) condenser water Base VS VS 3 CF Opt 0.5462 NA
flow rate. Controls complexity should be
accounted for and the system needs to be Variable CW flow VS VS 3 VF Opt 0.5260 3.7%
properly commissioned.
Reduced design VS VS 2 CF Opt 0.5255 3.8%
No, in new systems designed for 1.8 to 2.2 CW flow
gpm/ton (16.6 to 13.6ºF ΔT) condenser
water flow rate since they already achieve Reduced design VS VS 2 VF Opt 0.5252 3.8%
CW flow and
almost all the savings and reduce system variable CW flow
complexity—a lot. Systems designed at
these flow rates do not require varying the *Near optimal control (Opt) is minimum the sum of chiller + cooling tower fan kW at each operating point during
condenser water flow rate. the year

Why? Varying condenser water flow rate Example. Let’s compare the condenser • Pumps are smaller with significantly
can be complicated. There are several limit water flow options. lower power
conditions and setpoints to manage:
It's imperative that the sum of chiller, • Chiller power rises marginally
• The flow rate has to stay above the
condenser water pump and cooling tower • Cooling towers become more effective
minimum flow rate as defined by the
fan power is considered. Less-than-optimal as heat exchangers, since warmer
highest of minimum tower flow,
results can happen if decisions are based water is sent to the cooling tower,
minimum chiller flow, or to produce the
on only one component. resulting in
static lift in the open portion of the
condenser water system. When any of The measure of efficiency is the annual – Reduced tower fan power
these are close to the system design kWh of chiller, cooling tower fans and
flow, variable flow should not be – Reduced tower cost
condenser water pumps divided by the
attempted. annual ton-hours of cooling. This results in – Possible reduction of tower size
• At each operating point during the year, annualized performance in terms of (which further reduces tower cost).
determine the optimal condenser kW/ton for those components.
water pump and cooling tower speed. Observations. In all cases the operating
Table 1 illustrates a comparison of four savings (Table 1) are very similar, so what
• Make sure not to reduce the alternative two-chiller systems: guidance can be provided?
condenser flow at conditions and
operating points that cause the chiller • Base design of 3 gpm/ton and constant • Many existing systems were designed
to surge. condenser water flow rate (CF) using historical practices and a
• Design of 3 gpm/ton and varying condenser flow rate of 3 gpm/ton. In
• Ensure the sequence is documented
condenser water flow rate (VF) existing systems, annualized plant
and properly commissioned. energy can be reduced by varying the
• Design of 2 gpm/ton with constant condenser flow rate. Be sure to
This complexity requires that the system condenser water flow rate
be commissioned, the controls remain properly commission the system and
• Design of 2 gpm/ton and varying ensure control is performed correctly
operational and future changes are
accommodated. Careful consideration condenser water flow rate long-term.
should be made for system changes such • For new systems or when all existing
as chiller, pump, and/or tower Assumptions. These alternatives assume chillers are being replaced, using low
replacements. the pipe size remains unchanged. And that design condenser flow rates and
near optimal tower control resets the constant flow reduces installed costs,
tower water setpoint to achieve the saves the same amount of energy (or
Table 2. Industry recommendations for
condenser water design flow rates minimum sum of the chiller plus cooling more) as if condenser flow rate is varied
tower fan kW at each operating point and and keeps system control both
Flow rate(s) during the year. Two gpm/ton is shown in simple and understandable.
Source ∆T (ºF) (gpm/ton) our example but projects have varying
Historical 9.4 3.0 optimal design flow rates.
practice
Today’s Industry recommendations Effect of flow rate on equipment. With
ASHRAE 12-18 2.3 - 1.7 reduced design condenser water flow rate
GreenGuide1 based on present industry
Kelly and Chan2 15 2.0 recommendations (Table 2):
Taylor3 15 1.9

providing insights for today’s HVAC system designer Trane Engineers Newsletter volume 47–3 3
Figure 3. Pressure drops in a VPF system
Does operating two pumps chiller flow rate and
at lower speed save more pressure drops identical
energy than operating one pump and fitting
pump? flow rate and
pressure drops change
Perhaps a little, but not nearly as much
as many people think. A B
system flow rate and pressure drops
identical

Why? This came up during an


ASHRAE conference conversation with
coils and
respect to the affinity laws, and a wise valves
consulting engineer raised his
eyebrows and said one word: "Think."

As it turns out, the reason the question pipes, elbows


is asked is because of a and fittings
misunderstanding, or perhaps lack of
thinking—about the pump, or affinity,
laws. The pump laws describe the
relationship between flow rate and
power and, in a straight pipe that
relationship is cubic. So the thought Example. Consider the system in So, is operating an additional pump
process is, if an additional pump is Figure 3. At a given point in time, the beneficial?
enabled, the flow rate per pump will go system flow rate is identical—no matter
how many pumps operate—because it's • The system flow rate does not
down and the kW per pump will go change,
down with the cube of that flow rate. dependent on the required coil flow rates.
The flow rate is the same through the coils • Almost the entire system pressure
This just isn't true - and is an improper and valves, as well as the pipes, elbows drop is identical.
understanding of the pump laws for and fittings. Meaning their pressure drop
• There is only a small change in
this situation. What did we miss? is the same. The flow rate through the
system pressure drop - between the
chillers also remains identical, as do their
pump return and supply manifold.
As the pump power equation below pressure drops. The only change in the
shows, pump power is dependent on system is that there are now two paths for • And without study, we don't know if
the flow rate and system pressure drop water flow across the pump manifold. the pump, motor and drive
irrespective of the number of pumps efficiencies are better or worse at
that are operating. The 0.746 and 3960 When the flow rate through the operating reduced pump speed. Some pump
terms are conversion factors. In the pump is reduced, so is the pressure drop manufacturer's selection programs
denominator are the pump, motor and through its fittings - and the pump itself. can provide manifolded pump/drive
drive efficiencies. They may improve or So there is a pressure drop reduction - but efficiency ratings with various
worsen at different pump operating it is only the pressure drop from the return numbers of pumps in operation.
conditions. manifold (A) to the supply manifold (B),
and through the pump. As long as combined efficiency is the
same or better, the result is pump power
How about pump, motor and drive that is a little lower - due to the system
efficiencies with two pumps operating? pressure drop being a little lower. But it is
Burt Rishel's ASHRAE Journal article4 nowhere near the "cubic" pump savings
titled, "Wire-to-Water Efficiency of that some assume.
Pumping Systems," explains that there are
some operating conditions that allow the
combined pump, motor and drive
efficiency to rise when more pumps
operate. While it takes some calculation
time, if the combined efficiency is higher,
pump power is lower.

4 Trane Engineers Newsletter volume 47-3 providing insights for today’s HVAC system designer
Figure 4. Chiller lift
How much power can be
saved by piping chillers in a
kW a load x lift
"series counterflow" lift Pcnd – Pevp
arrangement compared to lift Tlvg cnd – Tlvg evp
98.9ºF
piping chillers in parallel? 98.9ºF – 37ºF

lift (ΔT) 85ºF


Almost 13 percent chiller power 61.9ºF
reduction is available by piping in a
series-counterflow configuration. 55ºF
37ºF
• Using Trane Duplex chillers, more
that 19 percent can be saved.
Increased pumping power reduces temperatures are based on a system So the respective lifts are:
these savings a little, but can be installed in a convention center and
• Downstream chiller: 54.3°F
mitigated. detailed in an ASHRAE Journal5 article.
Each chiller is designed to produce 37°F • Upstream chiller: 53.8°F
• Series evaporators and condensers
chilled water and return water back to the
should be considered when system • Average: 54.05°F
cooling tower at 98.9°F. So the lift of each
temperature differences are
chiller is 61.9°F. The average lift reduction compared to
14°F or larger.
chillers piped in parallel is 7.85°F. Since
The chillers could also be piped with both
power is proportional to lift, the power
Why? Before we examine the system evaporators and condensers in series
production is reduced by 12.7 percent.
configuration, recall that the two major (Figure 5). To simplify chiller selection,
impacts on chiller performance are: the chiller making the coldest chilled When designing a chilled-water system,
water receives the coolest tower water. optimized system performance is the goal.
• The cooling load the chiller must
This is referred to as "counterflow" since
satisfy.
the condenser water flows counter to the While the chillers become more efficient,
• The refrigerant "lift" the compressor chilled water. By installing the chillers in there is additional pump power due to the
must develop. series, two levels of thermal staging are higher pressure drop of pumping all the
created—reducing each chiller's lift. water through both chillers. In order to
Chiller power is proportional to load minimize pumping energy, it’s common to
multiplied by lift. So when either load or The upstream chiller receives 55ºF return design series systems with ΔTs of 14°F or
lift are reduced, so is chiller power. water and satisfies about half of the load, larger. ANSI/ASHRAE/IESNA 90.1-2016
cooling the water to 45.1°F. The requires a 15°F chilled-water ΔT, so series
Chiller power (kW) Load x Lift downstream chiller then cools the water chillers are expected to become more
to the desired 37°F. common. One may also consider utilizing
So, what is "lift"? . Refrigerant is single-pass evaporators and condensers to
compressed from its evaporator On the condenser side, the flow goes in
reduce pressure drop and pump power.
pressure to its condenser pressure. This the opposite (counter) direction. The
difference is referred to as the lift. So downstream chiller receives 85°F water
measuring these pressures allows lift to and raises it to 91.3°F. The upstream
be determined. But measuring further increases the condenser water
temperatures is simpler. temperature to 98.9°F.
Figure 5. Chiller lift reduction savings series-series (or series counterflow)
Since refrigerant is saturated in both
vessels, at a specific refrigerant condenser water
pressure the refrigerant has a specific
temperature. The colder the evaporator
refrigerant and the warmer the
condenser refrigerant, the higher the lift.
To simplify, lift is often approximated to
the difference between leaving upstream downstream
condenser water temperature and
leaving evaporator water temperature.

With this background, Figure 4 shows


the lift calculation for a chiller used in a
plant where both the evaporators and
condensers are piped in parallel. These

providing insights for today’s HVAC system designer Trane Engineers Newsletter volume 47–3 5
Now let's take the same design using Figure 6. Chiller lift reduction savings series-series-series (or series-series counterflow)
two Trane Duplex® chillers (Figure 6).
Each Duplex chiller is essentially a
condenser water
packaged series-counterflow chiller.
Installing two of these chillers in series
results in four levels of thermal staging.
The lift is reduced to an average of 50.1°F.
This staging results in over 19 percent
reduction in lift compared to the base
parallel configuration. Parallel lift = 61.9ºF
Series lift = 50.1ºF 48.9ºF
To summarize, chiller power is directly 50.0ºF 50.3ºF
proportional to compressor lift. A simple Lift reduction = 51.1ºF
(61.9 - 50.1) = 11.8ºF
way to reduce chiller power by almost 13
percent is to pipe the chillers in a series-
counterflow arrangement. Two Duplex
chillers in a series-counterflow
arrangement save over 19 percent chiller
power (Table 3).

Table 3. Lift versus chiller power


Configuration Lift Reduction (%)
Parallel 61.9ºF baseline
Series counterflow 54.05ºF 12.7
Series counterflow
50.1ºF 19.1
duplex

Additional questions about series Figure 7. Series arrangement of evaporators and condensers
chillers.
evaporators condensers
What about redundancy? To allow either
chiller to operate alone if the other chiller circuit 1 circuit 2 circuit 1 circuit 2
is being serviced, manual bypass lines
and valves are encouraged. When more
circuit 1 circuit 2 circuit 1 circuit 2
than two chillers are installed, chillers can
be piped in upstream and downstream
"pods" with a manifold between them circuit 1 circuit 2 circuit 1 circuit 2
(Figure 7). This allows any upstream chiller
to operate with any downstream chiller
3 chiller modules 3 chiller modules
and provides the same redundancy as if
all chillers were piped in parallel. Trane
Applications Engineering can provide circuit 1 circuit 2 circuit 1 circuit 2
options for series-counter flow system
configurations and their operating
characteristics. circuit 1 circuit 2 circuit 1 circuit 2

Chiller selection capacity. A system circuit 1 circuit 2 circuit 1 circuit 2


can be designed with each chiller handling
50 percent of the load, but it can be more
efficient if the capacity split is optimized.
A typical optimized (efficiency and cost)
split has the upstream chiller designed to
meet 53 percent of the load and the
downstream the remaining 47 percent.
Another benefit is that both chillers can
make the system supply-water
temperature in the event the downstream
chiller is down or being serviced.

6 Trane Engineers Newsletter volume 47-3 providing insights for today’s HVAC system designer
to these system pressure changes. Thus, flow measurement and valve
Should pressure- the "controllability" of a conventional characteristics.
independent control valves control valve is significantly affected by
variations in pressure. The mechanical variety basically
be used? combines two valve types into one:
What if there were a separate device that • First, a pressure regulating section.
Pressure-independent control valves absorbed the system pressure variations
(PICVs) have come down in price, are As system pressures change, the
so that the control valve always pressure regulating section
readily available and help maintain experienced its selected pressure
system ΔT, but are higher priced than automatically adjusts to keep a
differential? Or what if the valve control constant pressure across the control
pressure-dependent valves. Is the gains could be dynamically recalibrated to
additional cost worth it? section of the valve.
compensate for the changes in system
pressure? In other words, what if we • Next, the control section of the valve
Definition. Let’s begin by explaining could make the control valve pressure is modulated by the control system to
what a pressure-independent control independent? The valve would always adjust the flow through the valve as
valve is. Those who have sized a have its selected control authority, it space conditions change.
conventional control valve are probably would always pass only its design flow
familiar with the flow coefficient Mechanical pressure-independent valve
when wide open, and it would offer
calculation shown below. advantages include:
control stability.
• Compact size when compared to a
To select the appropriate valve, one must A pressure-independent control valve conventional control valve plus flow
first determine the required flow yields a number of advantages: limiting valve package, or to their
coefficient; given a flow rate through the electronic counterparts,
• Valve control becomes much more
valve and a desired pressure drop across
stable. To maintain space temperature, • Depending on the manufacturer,
the valve. The valve is selected to have an
the actuator no longer has to adjust for capability to be paired with any rotary
"authority" that will provide accurate and
varying system pressures. This will actuator,
stable control.
extend valve and actuator life. Also,
stability positively impacts system • Easy and straightforward to select,
efficiency and coil performance. • No additional controls or
• Accuracy improves because the valve programming required,
Where, is now controlling flow directly. • Near instantaneous response to
Cv = valve flow coefficient • Selection is easier. Simply choose a changes in system pressure which
Q = flow rate (gpm) valve that provides the needed flow provides optimal control stability.
SG = Fluid specific gravity (water = 1.0) rate (gpm)—a flow coefficient
On the other hand, an electronic
ΔP = Valve pressure drop (psi) calculation is no longer needed
pressure-independent valve doesn't
upfront.
Rearranging this equation, we see that actually maintain a constant differential
flow is dependent on the pressure • Installation is easier because pressure- pressure across the control valve surface.
differential for a given valve. independent valves automatically Instead, it achieves independent control
balance the system. No separate similar to a pressure-independent VAV air
balancing valves are required. valve: it includes a flow meter in series
with a standard control valve. The
Stability and accuracy are particularly electronics calculate the instantaneous
important. Anything that causes a valve to flow and pressure across the valve and
lose accurate and stable flow control, continuously recalibrates the control
Valve performance would be fine if the under any operating condition, can result coefficients to provide stable and
pressure differential across the valve was in lower than desired average waterside accurate control.
always at the selection condition. But ΔT. Due to a subsequent increase in
during operation, other parts of the required flow rate, lower ΔT results in an Likewise, the electronic variety has a
system are constantly changing. This increase in pump power and a decrease in number of advantages:
causes the pressure at the valve to chiller plant efficiency. Sometimes the
• Potential for lower hardware costs,
change also. With a fixed coefficient, the impacts are very significant.
• Provision for actual load
flow therefore has no option but to also
There are two different technologies used measurement,
vary.
to implement pressure-independent
• Programmable for alternative
Even if nothing has changed in a control; mechanical pressure regulation
operation methods. For example, the
particular space, the control valve must across the control valve and electronic
valve could be set up to limit delta T,
now modulate to adjust flow in response gain modulation for the control valve using
not flow.

Note: The 2016 ASHRAE Handbook - Systems and Equipment p.47 states
that, "...an authority between 0.25 and 0.5 usually provides the right balance
between controllability and energy performance."
differential pressure of valve
authority =
differential pressure of valve + differential pessure of branch

providing insights for today’s HVAC system designer Trane Engineers Newsletter volume 47–3 7
Both mechanical and electrionic pressure- Figure 8. Pressure-independent versus conventional valve operation in Atlanta
(3rd and 4th floor performance)
independent valves have communication
capability to enable data sharing and
trending.

Advantages should be weighed against


the additional complexity. For example,
special software is needed to setup and
maintain the valves for the life of the
product. Also, operators need to be
trained in this software and software
must be kept current.

Example office building. So now that


we understand what a pressure-
independent control valve can do for a
building system, let's look at case study.

A high rise building in Atlanta was


identified as a good candidate because it
had existing control problems. Once Summary. By Trane Applications Engineering. To subscribe or
view previous issues of the Engineers Newsletter visit
those problems were identified and • Pressure-independent valves are trane.com/EN. Send comments to ENL@trane.com.
resolved, one floor was retrofitted with a more stable and more accurate,
pressure-independent control valve and which improves system ΔT.
was compared to a floor that kept the
existing conventional control valve • Pressure-independent valves make
(Figure 8). valve selection much easier. A lot of References
conventional valves are poorly [1] ASHRAE GreenGuide (third edition), Atlanta, GA:
First notice how both valves are able to selected, or one valve CV is selected ASHRAE, 2010.
control to a high chilled-water ΔT. In other for the whole building, even though
words: a pressure independent valve isn't the pressure across valves varies [2] Kelly, D. W. and Tumin Chan, "Optimizing Chilled-
water Plants," Heating/Piping/Air Conditioning,
required to achieve higher ΔTs. However, significantly by distance from the January, 1999.
the conventional control valve is less system pumps. It's highly unlikely a
stable than the pressure independent poorly selected valve will provide [3] Taylor, S. “Optimizing Design & Control Of Chilled
valve. In particular, notice the good control. Water Plants.” ASHRAE Journal, (December 2011):
considerable variation in valve position for 22-34. Available at www.ashrae.org.
• Pressure-independent valves are
the conventional valve. [4] Rishel, Burt, "Wire-to-Water Efficiency of Pumping
easier to install since they eliminate
Systems," ASHRAE Journal, April, 2001.
As previously discussed, stability the need for balancing valves.
improves ΔT. Also, less action on the • Considering the price premium has [5] Schwedler, M. "Series-Series Counterflow for
actuator should improve actuator Central Chilled-Water Plants," ASHRAE Journal.
been steadily dropping, pressure-
(June 2002):pp. 23-29
reliability. independent valves may be cost
neutral if all costs, including
balancing, are considered.

So are pressure-independent valves


worth it? If you're not sure you can get
high quality, properly selected, location-
specific valves installed on a job; then by
all means, specify quality pressure
independent valves. It should be well
worth the customer's investment.

Trane, the Circle Logo, and TRACE are trademarks of Trane in the United States and other countries. ASHRAE is a regis-
tered trademark of the American Society of Heating, Refrigeration, and Air-Conditioning Engineers, Inc. Trane is a brand
of Ingersoll Rand, a world leader in creating comfortable, sustainable and efficient environments. Ingersoll Rand's family
of brands includes Club Car®, Ingersoll Rand®, Thermo King® and Trane®.

Trane, This newsletter is for informational purposes only and does not constitute legal advice.
A business of Ingersoll Rand Trane believes the facts and suggestions presented here to be accurate. However, final design and
application decisions are your responsibility. Trane disclaims any responsibility for actions taken on
For more information, contact your local Trane
the material presented.
office or e-mail us at comfort@trane.com

8 Trane Engineers Newsletter volume 47–3 ADM-APN067-EN (October 2018)

Potrebbero piacerti anche