TECHNICAL DEPARTMENT

Voltage Drop in Air, Ground and Duct


SN Description mV/A/m in air mV/A/m in ground mV/A/m in Duct
1 4C*95MM2 CU/XLPE/SWA/PVC 0.06 0.06 0.07
2 4C*25MM2 CU/XLPE/SWA/PVC 0.14 0.14 0.16
3 4C*50MM2 CU/XLPE/SWA/PVC 0.09 0.09 0.10
4 4C*16MM2 CU/XLPE/SWA/PVC 0.18 0.18 0.21
5 2C*10MM2 CU/XLPE/SWA/PVC 0.21 0.23 0.26
6 4C*10MM2 CU/XLPE/SWA/PVC 0.23 0.23 0.26
7 EARTH CABLE 1*150mm2 CU/PVC 0.04 0.07
8 EARTH CABLE 1*50mm2 CU/PVC 0.07 0.13
9 EARTH CABLE 1*25mm2 CU/PVC 0.10 0.25
10 EARTH CABLE 1*35mm2 CU/PVC 0.09 0.16
11 EARTH CABLE 1*16mm2 CU/PVC 0.13 0.33
12 EARTH CABLE 1*10mm2 CU/PVC 0.18 0.43
13 NYA WIRE 4mm2 Cu/PVC 0.43 0.83
14 NYA WIRE 6mm2 Cu/PVC 0.24 0.60
15 NYA WIRE 10mm2 Cu/PVC 0.18 0.43
16 NYA WIRE 16mm2 Cu/PVC 0.13 0.33
17 NYA WIRE 25mm2 Cu/PVC 0.10 0.25

Vd maximum acceptable volt drop (in volts) 2.50%


I Currect carry capacity per phase
Vd

V phase voltage 450 for Cu/PVC


600 for LV cables
L cable length 1000 m
t air air temperature 50 Deg
t ground Ground temperature 35 Deg
Soil thermal resistivity 2.5 ˚Cm/ W

Depth of lay 0.7 m


TECHNICAL DEPARTMENT
TECHNICAL DEPARTMENT