Aluminum
Interlocked
Armor
High Tensile
Aluminum
Interlocked
Armor
Teck-90
with Fiber
Optics
Teck-90
Continuous
Welded
Armor
ALUMINUM
Catalog
Number
Size ARMOR
No. of
AWG
No.MEDIUM
of Insulation VOLTAGE
Conductors
Jacket
Strands
Ground
Thickness Thickness Wire Size
Armor
Diameter
Overall
Diameter
Net
Weight
5
(Mils) (Mils) AWG (Inch) (Inch) (Lbs/Mft)
GK300-01402 14 2 7 30 50 14 0.50 0.61 176
GK300-01403 14 3 7 30 50 14 0.52 0.63 185
GK300-01404 14 4 7 30 50 14 0.56 0.67 210
GK300-01405 14 5 7 30 50 14 0.60 0.71 270
5-1
GK-500 Aluminum Interlocked Armor
2,400V (5KV)
Applications
– Non Shielded
Typical applications are for power distribution in pulp and paper mills,
steel mills, food processing plants, commercial centers, mines, generating
stations, refineries, industrial plants and chemical plants. They may be
installed in racks, trays, ladders, raceways, aerial installations, direct
burial and concrete-encased installations.
Aluminum interlocked armor cables provide an economical and versatile
alternative to a conduit system.
All cable under this specification is recognized by the NEC as 2400V
non-shielded cable.
Construction
Three compact stranded copper conductors, extruded EPR semi-
conducting strand screen over individual conductors, EPR insulation,
print phase ID, with one grounding conductor, fillers and binder tape
over the core, aluminum interlocked armor with yellow PVC jacket.
Sizes: 8 AWG to 1000 Kcmil
Other Options available upon request: XLP insulation, colors, low smoke,
zero halogen (LSZH), low corrosion jackets and customized ground wires.
• CU Conductor Standards
• EPR Insulation • ICEA S-96-659 (NEMA WC 71) – Non-shielded cables rated 2001-5000
volts for use in the distribution of electric energy
• Non Shielded
• UL 1072 – Medium voltage power cables
• One Ground Wire
• Aluminum Interlocked Armor • IEEE 1202 – Flame testing of cables for use in cable tray in industrial and
commercial occupancies (70,000 BTU/hr)
• PVC Jacket
• ICEA T-29-520 – Vertical cable tray flame tests (210,000 BTU/hr)
• EPR / AIA / PVC
*Ampacities are based on the NEC 2011 Handbook: Ampacities of an Insulated Three-Conductor Copper Cable Isolated in Air.
For other installations, refer to the NEC Handbook. The above data is approximate and subject to normal manufacturing tolerances.
Insulation thickness 90 Mils is available upon request.
5-3
GK-501 Aluminum Interlocked Armor
5kV 133% or 8kV 100%
Applications
– Shielded
Typical applications are for power distribution in pulp and paper mills,
steel mills, food processing plants, commercial centers, mines, generating
stations, refineries, industrial plants and chemical plants. They may be
installed in racks, trays, ladders, raceways, aerial installations, direct burial
and concrete-encased installations.
Aluminum interlocked armor cables provide an economical and versatile
alternative to a conduit system.
Construction
Three compact stranded copper conductors, extruded semiconducting
EPR strand screen, EPR insulation, extruded semiconducting EPR
insulation screen, phase identification strips, and copper shield tape
overlapping, over individual conductors, with one stranded copper
grounding conductor, fillers, and binder tape over the core, aluminum
interlocked armor with yellow PVC jacket.
Sizes: 6 AWG to 1000 Kcmil
Other Options available upon request: XLP insulation, colors, low
smoke, zero halogen (LSZH), low corrosion jackets and customized
ground wires.
• CU Conductor Standards
• EPR Insulation
•U
L 1072 - Medium voltage power cables
• CU Tape Shielded
• ICEA S-93-639 (NEMA WC 74) - 5-46 kV shielded power cable for use
• One Ground Wire in the transmission and distribution of electric energy
• Aluminum Interlocked Armor
• IEEE 1202 – Flame testing of cables for use in cable tray in industrial
• PVC Jacket and commercial occupancies (70,000 BTU/hr)
• EPR / AIA / PVC
*Ampacities are based on the NEC 2011 Handbook: Ampacities of an Insulated Three-Conductor Copper Cable Isolated in Air.
For other installations, refer to the NEC Handbook. The above data is approximate and subject to normal manufacturing tolerances.
Compressed conductors available upon request.
†
5-5
GK-502 Aluminum Interlocked Armor
15kV 100% and 15kV 133%
Applications
– Shielded
Typical applications are for power distribution in pulp and paper mills,
steel mills, food processing plants, commercial centers, mines, generating
stations, refineries, industrial plants and chemical plants. They may be
installed in racks, trays, ladders, raceways, aerial installations, direct burial
and concrete-encased installations.
Aluminum interlocked armor cables provide an economical and versatile
alternative to a conduit system.
Construction
Three compact stranded copper conductors, extruded semiconducting
EPR strand screen, EPR insulation, extruded semiconducting EPR
insulation screen, phase identification strips, and copper shield tape
overlapping, over individual conductors, with one stranded copper
grounding conductor, fillers, and binder tape over the core, aluminum
interlocked armor with red PVC jacket.
Sizes: 2 AWG to 1000 Kcmil
Other Options available upon request: XLP insulation, colors, low
smoke, zero halogen (LSZH), low corrosion jackets and customized
ground wires.
• CU Conductor Standards
• EPR Insulation
•U
L 1072 – Medium voltage power cables
• CU Tape Shielded
• ICEA S-93-639 (NEMA WC 74) – 5-46 kV shielded power cable for use
• One Ground Wire in the transmission and distribution of electricenergy
• Aluminum Interlocked Armor
• IEEE 1202 – Flame testing of cables for use in cable tray in industria
• PVC Jacket and commercial occupancies (70,000 BTU/hr)
• EPR / AIA / PVC
*Ampacities are based on the NEC, 2011 Edition, Three-conductors copper cable isolated in air, for other installation refer to the NEC.
The above data is approximate and subject to normal manufacturing tolerances.
†
Compressed conductors available upon request.
5-7
GK-503 Aluminum Interlocked Armor
25KV 100% and 28KV 133%
Applications
– Shielded
Typical applications are for power distribution in pulp and paper mills,
steel mills, food processing plants, commercial centers, mines, generating
stations, refineries, industrial plants and chemical plants. They may be
installed in racks, trays, ladders, raceways, aerial installations, direct burial
and concrete-encased installations.
Aluminum interlocked armor cables provide an economical and versatile
alternative to a conduit system.
Construction
Three compact stranded copper conductors, extruded semiconducting
EPR strand screen, EPR insulation, extruded semiconducting EPR
insulation screen, phase identification strips, and copper shield tape
overlapping, over individual conductors, with one stranded copper
grounding conductor, fillers, and binder tape over the core, aluminum
interlocked armor with red PVC jacket.
Sizes: 1 AWG to 750 Kcmil
Other Options available upon request: XLP insulation, colors, low
smoke, zero halogen (LSZH), low corrosion jackets and customized
ground wires.
• CU Conductor Standards
• EPR Insulation
•U
L 1072 – Medium voltage power cables
• CU Tape Shielded
• ICEA S-93-639 (NEMA WC 74) – 5-46kV shielded power cable for use
• One Ground Wire in the transmission and distribution of electric energy
• Aluminum Interlocked Armor
• IEEE 1202 – Flame testing of cables for use in cable tray in industrial
• PVC Jacket and commercial occupancies (70,000 BTU/hr)
• EPR / AIA / PVC
*Ampacities are based on the NEC, 2011 Edition, Three-conductors copper cable isolated in air, for other installation refer to the NEC.
The above data is approximate and subject to normal manufacturing tolerances.
†
Compressed conductors available upon request.
5-9
GK-504 Aluminum Interlocked Armor
35kV 100% and 35kV 133%
Applications
– Shielded
Typical applications are for power distribution in pulp and paper mills,
steel mills, food processing plants, commercial centers, mines, generating
stations, refineries, industrial plants and chemical plants. They may be
installed in racks, trays, ladders, raceways, aerial installations, direct burial
and concrete-encased installations.
Aluminum interlocked armor cables provide an economical and versatile
alternative to a conduit system.
Construction
Three compact stranded copper conductors, extruded semiconducting
EPR strand screen, EPR insulation, extruded semiconducting EPR
insulation screen, phase identification strips, and copper shield tape
overlapping, over individual conductors, with one stranded copper
grounding conductor, fillers, and binder tape over the core, aluminum
interlocked armor with red PVC jacket.
Sizes: 1/0 AWG to 500 Kcmil
Other Options available upon request: XLP insulation, colors, low
smoke, zero halogen (LSZH), low corrosion jackets and customized
ground wires.
• CU Conductor
• EPR Insulation Standards
•U
L 1072 – Medium voltage power cables
• CU Tape Shielded
• ICEA S-93-639 (NEMA WC 74) – 5-46kV shielded power cable for use
• One Ground Wire
in the transmission and distribution of electric energy
• Aluminum Interlocked Armor
• IEEE 1202 – Flame testing of cables for use in cable tray in industrial
• PVC Jacket and commercial occupancies (70,000 BTU/hr)
• EPR / AIA / PVC
*Ampacities are based on the NEC 2011 Handbook: Ampacities of an Insulated Three-Conductor Copper Cable Isolated in Air.
For other installations, refer to the NEC Handbook. The above data is approximate and subject to normal manufacturing tolerances.
†
Compressed conductors available upon request.
5-11
GK-505 High Tensile Aluminum
Mining Vertical Application
Interlocked Armor
Construction
Three compact stranded copper conductors, extruded semiconducting
EPR strand screen, EPR insulation, extruded semiconducting EPR
insulation screen, phase identification strips, and copper shield tape
overlapping, over individual conductors, with one stranded copper
grounding conductor, black PVC inner jacket over the cores, aluminum
interlocked armor is applied directly over the inner jacket, and a protective
sunlight and ozone resistant jacket of polyvinyl chloride (PVC) suitable
• CU Conductor for installation in temperatures down to -40C, is extruded over the
• EPR or XLP Insulation interlocked armor.
• Concentric Copper Ground Wire Sizes: 1 AWG to 1000 Kcmil
• Inner PVC Jacket Other Options available upon request: XLP insulation, colors, low
• Aluminum Interlocked Armor smoke, zero halogen (LSZH), low corrosion jackets and customized
• PVC Jacket ground wires.
• EPR / PVC – AIA / PVC
• XLP / PVC – AIA / PVC Standards
• CSA C68.3
• CSA C22.2 No. 174
• ICEA S-93-639 (NEMA WC 74) - 5-46 kV Shielded Power Cable for
Use in the Transmission & Distribution of Electric Energy
• IEEE 1202 - Flame testing of cables for use in cable tray in industrial
and commercial occupancies (70,000 BTU/hr)
• ICEA T-29-520 - Vertical Cable Tray Flame Test (210,000 BTU/hr)
• Passes FT-4 Flame Test
Construction
One compact stranded copper conductor, extruded semiconducting
EPR strand screen, EPR insulation, extruded semiconducting EPR
insulation screen and concentric copper ground wires over semi-
conductor insulation, black PVC inner jacket over the concentric ground
wires , aluminum interlocked armor is applied directly over the inner
jacket, and a protective sunlight and ozone resistant jacket of polyvinyl
• CU Conductor
chloride (PVC) suitable for installation in temperatures down to -40 C,
• EPR Insulation
is extruded over the interlocked armor.
• CU Tape Shielded
Sizes: 1 AWG to 1000 Kcmil
• One Ground Wire
• Inner PVC Jacket Other Options available upon request: XLP insulation, colors, low smoke,
zero halogen (LSZH), low corrosion jackets and customized ground wires.
• Aluminum Interlocked Armor
• PVC Jacket
Standards
• EPR / PVC – AIA / PVC or
• CSA C68.3
• XLP / PVC – AIA / PVC
• CSA C22.2 No. 174
• ICEA S-93-639 (NEMA WC 74) – 5-46kV shielded power cable for use
in the transmission & distribution of electric energy
• IEEE 1202 – Flame testing of cables for use in cable tray in industrial
and commercial occupancies (70,000 BTU/hr)
• ICEA T-29-520 – Vertical cable tray flame test (210,000 BTU/hr)
• Passes FT-4 flame test
*Ampacities are based upon cables in free air run, per CEC Part 1, Table 1 & 2. For other installations, please refer to the appropriate
sections of the CEC. The above data is approximate and subject to normal manufacturing tolerances.
Compressed conductors available upon request.
5-15
†
GK-508 teck-90
5kV 133% – Shielded
Applications
Typical applications are for power distribution in pulp and paper mills,
steel mills, food processing plants, commercial centers, mines, generating
stations, refineries, industrial plants and chemical plants. They may be
installed in racks, trays, ladders, raceways, aerial installations, direct burial
and concrete-encased installations.
TECK cables are recommended for severe operating conditions in wet
and dry locations. They can be installed in corrosive environments and
are resistant to mechanical abuse and ozone attack.
Dual PVC jacket (inner/outer) provides extra protection from moisture
and liquid.
Construction
Three compact stranded copper conductors, extruded semiconducting
EPR strand screen, EPR insulation, extruded semiconducting EPR
insulation screen, phase identification strips, and copper shield tape
overlapping, over individual conductors, with one stranded copper
grounding conductor, black PVC inner jacket over the cores, aluminum
interlocked armor is applied directly over the inner jacket, and a protective
sunlight and ozone resistant jacket of polyvinyl chloride (PVC) suitable
for installation in temperatures down to -40C, is extruded over the
• CU Conductor interlocked armor.
• EPR Insulation Sizes: 1 AWG to 1000 Kcmil
• CU Tape Shielded Other Options available upon request: XLP insulation, colors, low
• One Ground Wire smoke, zero halogen (LSZH), low corrosion jackets and customized
• Inner PVC Jacket ground wires.
• Aluminum Interlocked Armor
• PVC Jacket Standards
• EPR / PVC – AIA / PVC or • CSA C68.3
• XLP / PVC – AIA / P VC • CSA C22.2 No. 174
• ICEA S-93-639 (NEMA WC 74) – 5-46kV shielded power cable for use
in the transmission & distribution of electric energy
• IEEE 1202 - Flame testing of cables for use in cable tray in industrial
and commercial occupancies (70,000 BTU/hr)
• ICEA T-29-520 – Vertical cable tray flame test (210,000 BTU/hr)
• Passes FT-4 flame test
*Ampacities are based upon cables in free air run, per CEC Part 1, Table 1 & 2. For other installations, please refer to the appropriate
sections of the CEC. The above data is approximate and subject to normal manufacturing tolerances.
Compressed conductors available upon request.
†
5-17
GK-509 teck-90
15kV 133% – Shielded
Applications
Typical applications are for power distribution in pulp and paper mills,
steel mills, food processing plants, commercial centers, mines, generating
stations, refineries, industrial plants and chemical plants. They may be
installed in racks, trays, ladders, raceways, aerial installations, direct burial
and concrete-encased installations.
TECK cables are recommended for severe operating conditions in wet
and dry locations. They can be installed in corrosive environments and
are resistant to mechanical abuse and ozone attack.
Dual PVC jacketed (inner/outer) provides extra protection from moisture
and liquid.
Construction
Three compact stranded copper conductors, extruded semiconducting
EPR strand screen, EPR insulation, extruded semiconducting EPR
insulation screen, phase identification strips, and copper shield tape over-
lapping, over individual conductors, with one stranded copper grounding
conductor, black PVC inner jacket over the cores, aluminum interlocked
armor is applied directly over the inner jacket, and a protective sunlight
and ozone resistant jacket of polyvinyl chloride (PVC) suitable for installation
in temperatures down to -40C, is extruded over the interlocked armor.
• CU Conductor Sizes: 1 AWG to 1000 Kcmil.
• EPR Insulation Other Options available upon request: XLP insulation, colors, low
• CU Tape Shielded smoke, zero halogen (LSZH), low corrosion jackets and customized
• One Ground Wire ground wires.
• Inner PVC Jacket
• Aluminum Interlocked Armor Standards
• PVC Jacket • CSA C68.3
• EPR / PVC – AIA / PVC or • CSA C22.2 No. 174
• XLP / PVC – AIA /P VC • ICEA S-93-639 (NEMA WC 74) – 5-46kV shielded power cable for use
in the transmission & distribution of electric energy
• IEEE 1202 – Flame testing of cables for use in cable tray in industrial
and commercial occupancies (70,000 BTU/hr)
• ICEA T-29-520 – Vertical cable tray flame test (210,000 BTU/hr)
• Passes FT-4 flame test
*Ampacities are based upon cables in free air run, per CEC Part 1, Table 1 & 2. For other installations, please refer to the appropriate
sections of the CEC. The above data is approximate and subject to normal manufacturing tolerances.
Compressed conductors available upon request.
†
5-19
GK-510 teck-90
35kV 100% and 35kV 133%
Applications
– Shielded
Typical applications are for power distribution in pulp and paper mills,
steel mills, food processing plants, commercial centers, mines, generating
stations, refineries, industrial plants and chemical plants. They may be
installed in racks, trays, ladders, raceways, aerial installations, direct burial
and concrete-encased installations.
TECK cables are recommended for severe operating conditions in wet
and dry locations. They can be installed in corrosive environments and
are resistant to mechanical abuse and ozone attack.
Dual PVC jacketed (inner/outer) provides extra protection from moisture
and liquid.
Construction
Three compact stranded copper conductors, extruded semiconducting
EPR strand screen, EPR insulation, extruded semiconducting EPR
insulation screen, phase identification strips, and copper shield tape over-
lapping, over individual conductors, with one stranded copper grounding
conductor, black PVC inner jacket over the cores, aluminum interlocked
armor is applied directly over the inner jacket, and a protective sunlight
and ozone resistant jacket of polyvinyl chloride (PVC) suitable for installation
in temperatures down to -40C, is extruded over the interlocked armor.
• CU Conductor Sizes: 1 AWG to 1000 Kcmil.
• EPR Insulation Other Options available upon request: XLP insulation, colors, low
• CU Tape Shielded smoke, zero halogen (LSZH), low corrosion jackets and customized
• One Ground Wire ground wires.
• Inner PVC Jacket
• Aluminum Interlocked Armor Standards
• PVC Jacket • CSA C68.3
• EPR / PVC – AIA / PVC or • CSA C22.2 No. 174
• XLP / PVC – AIA /P VC • ICEA S-93-639 (NEMA WC 74) – 5-46kV shielded power cable for use
in the transmission & distribution of electric energy
• IEEE 1202 - Flame testing of cables for use in cable tray in industrial
and commercial occupancies (70,000 BTU/hr)
• ICEA T-29-520 - Vertical cable tray flame test (210,000 BTU/hr)
• Passes FT-4 flame test
*Ampacities are based upon cables in free air run, per CEC Part 1, Table 1 & 2. For other installations, please refer to the appropriate
sections of the CEC. The above data is approximate and subject to normal manufacturing tolerances.
Compressed conductors available upon request.
†
5-21
GK-511 Continuous welded Armor
MC-HL, 2,400V (5KV)
Applications
– Non Shielded
Typical applications are for power distribution in pulp and paper mills,
steel mills, food processing plants, mines, generating stations, refineries,
industrial plants and chemical plants. They may be installed in racks,
trays, ladders, raceaways, aerial installations, direct burial and
concrete-encased installations. MC-HL continuous corrugated aluminum
armor provides a sheath impervious to moisture, liquids, and gases.
For use in Classes I, II, and III, Division 1 and 2 hazardous locations
covered under NEC® Articles 501, 502, and 503.
These cables are capable of operating continuously in wet or dry
locations at a maximum conductor temperature of 90°C for normal
operation, 130°C for emergency overload conditions, and 250°C for
short circuit conditions.
MC-HL provides an impervious sheath recommended as an economical
alternative to traditional conduit systems.
The construction of a continuously corrugated aluminum sheath with
three symmetrically ground wires make this cable ideal for use in
pulse-width modulated and variable frequency drive applications.
Construction
Three compact stranded copper conductors, extruded EPR semi-
• CU Conductor
conducting strand screen over individual conductors, EPR insulation,
• EPR Insulation print phase ID, with 3 grounding conductors, fillers and binder tape
• Non Shielded over the core, corrugated aluminum welded armor is applied over the
• 3 Ground Wires assembly, a protective sunlight and ozone resistant jacket of polyvinyl
• Continuous Corrugated chloride (PVC) suitable for installation in temperatures down to -40C,
Aluminum Armor is extruded over the aluminum welded armor.
• -40°C PVC Jacket Sizes: 2 AWG to 750 Kcmil.
• EPR / CWA / PVC Other Options available upon request: XLP insulation, colors, low
smoke, zero halogen (LSZH), low corrosion jackets and customized
ground wires.
Standards
• ICEA S-96-659 (NEMA WC 71)
• UL 1072 – Medium voltage power cables
• IEEE 1202 – Flame testing of cables for use in cable tray in industrial
and commercial occupancies (70,000 BTU/hr)
• ICEA T-29-520 – Vertical cable tray flame tests (210,000 BTU / hr)
• UL 1309 Listed as marine shipboard cable
• ABS Listed as CWCMC
*Ampacities are based on the NEC, 2011 Edition, Three-conductors copper cable isolated in air, for other installation refer to the NEC.
The above data is approximate and subject to normal manufacturing tolerances.
5-23
GK-512 Continuous welded Armor
MC-HL, 5kV 133%
Applications
– Shielded
Typical applications are for power distribution in pulp and paper mills,
steel mills, food processing plants, mines, generating stations, refin-
eries, industrial plants and chemical plants. They may be installed in
racks, trays, ladders, cable troughs, aerial installations, direct burial and
concrete-encased installations. MC-HL continuous corrugated aluminum
armor provides a sheath impervious to moisture, liquids, and gases.
For use in Classes I, II, and III, Division 1 and 2 hazardous locations
covered under NEC® Articles 501, 502, and 503.
These cables are capable of operating continuously in wet or dry
locations at a maximum conductor temperature of 105°C for normal
operation, 140°C for emergency overload conditions, and 250°C for short
circuit conditions.
MC-HL provides an impervious sheath recommended as an economical
alternative to traditional conduit systems.
The construction of a continuously corrugated aluminum sheath with three
symmetrically ground wires make this cable ideal for use in pulse-width
modulated and variable frequency drive applications.
Construction
Three compact stranded copper conductors, extruded semi-conducting
• CU Conductor
EPR strand screen, EPR insulation, extruded semiconducting EPR
• EPR Insulation insulation screen, phase identification strips, and copper shield tape
• CU Tape Shielded overlapping, over individual conductors, with 3 stranded copper grounding
• 3 Ground Wires conductors, fillers and binder tape over the core, corrugated aluminum
• Continuous Corrugated welded armor is applied over the assembly, a protective sunlight and
Aluminum Armor ozone resistant jacket of polyvinyl chloride (PVC) suitable for installation in
• -40°C PVC Jacket temperatures down to -40C, is extruded over the aluminum welded armor.
• EPR/CWA/PVC Sizes: 2 AWG to 750 Kcmil.
Other Options available upon request: XLP insulation, colors, low smoke,
zero halogen (LSZH), low corrosion jackets and customized ground wires.
Standards
• UL 1072 – Medium voltage power cables
• UL 2225 – Safety metal-clad cables and cable-sealing fittings for use in
hazardous (classified) locations
• UL 1309 – Listed as marine shipboard cable
• ICEA S-93-639 (NEMA WC 74) – 5-46kV shielded power cable for use in
the transmission and distribution of electric energy
• IEEE 1202 – Flame testing of cables for use in cable tray in industrial and
commercial occupancies (70,000 BTU/hr)
• ICEA T-29-520– Vertical tray flame test (210,000 BTU/hr)
*Ampacities are based on the NEC, 2011 Edition, Three-conductors copper cable isolated in air, for other installation refer to the NEC.
The above data is approximate and subject to normal manufacturing tolerances.
5-25
GK-513 Continuous welded Armor
MC-HL, 15kV 133%
Applications
– Shielded
Typical applications are for power distribution in pulp and paper mills,
steel mills, food processing plants, mines, generating stations, refineries,
industrial plants and chemical plants. They may be installed in racks,
trays, ladders, raceways, aerial installations, direct burial and concrete-
encased installations. MC-HL continuous corrugated aluminum armor
provides a sheath impervious to moisture, liquids, and gases.
These cables are for use in Classes I, II, and III, Division 1 and 2 hazardous
locations covered under NEC® Articles 501, 502, and 503. They are
capable of operating continuously in wet or dry locations at a maximum
conductor temperature of 105°C for normal operation, 140°C for
emergency overload conditions, and 250°C for short circuit conditions.
MC-HL provides an impervious sheath recommended as an economical
alternative to traditional conduit systems.
The construction of a continuously corrugated aluminum sheath with three
symmetrically ground wires make this cable ideal for use in pulse-width
modulated and variable frequency drive applications.
Construction
Three compact stranded copper conductors, extruded semiconducting
EPR strand screen, EPR insulation, extruded semiconducting EPR
• CU Conductor insulation screen, phase identification strips, and copper shield tape
• EPR Insulation overlapping, over individual conductors, with one stranded copper
• CU Tape Shielded grounding conductor, fillers and binder tape over the core, corrugated
• One Ground Wire aluminum welded armor is applied over the assembly, a protective
sunlight and ozone resistant jacket of polyvinyl chloride (PVC) suitable
• Continuous Corrugated
for installation in temperatures down to -40C, is extruded over the
Aluminum Armor
aluminum welded armor.
• -40°C PVC Jacket
• EPR / CWA / PVC Sizes: 2 AWG to 750 Kcmil.
Other options available upon request: XLP insulation, colors, low smoke,
zero halogen (LSZH), low corrosion jackets and customized ground wires.
• UL 1309 – Listed as marine shipboard cable • ICEA T-29-520 – Vertical tray flame test
(210,000 BTU/hr)
• ICEA S-93-639 (NEMA WC 74) – 5-46kV shielded
power cable for use in the transmission and
distribution of electric energy
*Ampacities are based on the NEC 2011 Handbook: Ampacities of an Insulated Three-Conductor Copper Cable Isolated in Air.
For other installations, refer to the NEC Handbook. The above data is approximate and subject to normal manufacturing tolerances.
†
Compressed conductors available upon request.
5-27
GK-514 Continuous welded Armor
MC-HL
Applications
25kV 133% or 35kV 100%
– Shielded Typical applications are for power distribution in pulp and paper mills,
steel mills, food processing plants, mines, generating stations, refiner-
ies, industrial plants and chemical plants. They may be installed in racks,
trays, ladders, raceways, aerial installations, direct burial and concrete-
encased installations. MC-HL continuous corrugated aluminum armor
provides a sheath impervious to moisture, liquids, and gases.
For use in Classes I, II, and III, Division 1 and 2 hazardous locations
covered under NEC® Articles 501, 502, and 503.
These cables are capable of operating continuously in wet or dry locations
at a maximum conductor temperature of 105°C for normal operation,
140°C for emergency overload conditions, and 250°C for short circuit
conditions.
MC-HL provides an impervious sheath recommended as an economical
alternative to traditional conduit systems.
The construction of a continuously corrugated aluminum sheath with three
symmetrically ground wires make this cable ideal for use in pulse-width
modulated and variable frequency drive applications.
Construction
Three compact stranded copper conductors, extruded semiconducting
• CU Conductor EPR strand screen, EPR insulation, extruded semiconducting EPR
• EPR Insulation insulation screen, phase identification strips, and copper shield tape
• CU Tape Shielded overlapping, over individual conductors, with one stranded copper
• One Ground Wire grounding conductor, fillers and binder tape over the core, corrugated
• Continuous Corrugated aluminum welded armor is applied over the assembly, a protective
Aluminum Armor sunlight and ozone resistant jacket of polyvinyl chloride (PVC) suitable
• -40°C PVC Jacket for installation in temperatures down to -40C, is extruded over the
aluminum welded armor.
• EPR / CWA / PVC
Sizes: 1/0 AWG to 500 Kcmil.
Other options available upon request: XLP insulation, colors, low smoke,
zero halogen (LSZH), low corrosion jackets and customized ground wires.
Standards
• UL 1072 - Medium Voltage Power Cables
• UL 2225 - Safety metal-clad cables and cable-sealing fittings for use in
hazardous (classified) locations
• UL 1309 - Listed as marine shipboard cable
• ICEA S-93-639 (NEMA WC 74) – 5-46 kV shielded power cable for use in
the transmission and distribution of electric energy
• IEEE 1202 - Flame testing of cable for use in cable tray in industrial and
commercial occupancies (70,000 BTU/hr)
• ICEA T-29-520 – Vertical tray flame test (210,000 BTU/hr)
*Ampacities are based on the NEC 2011 Handbook: Ampacities of an Insulated Three-Conductor Copper Cable Isolated in Air.
For other installations, refer to the NEC Handbook. The above data is approximate and subject to normal manufacturing tolerances.
5-29
GK-515 Continuous welded armor
MC-HL, 35kV 133%
Applications
– Shielded
Typical applications are for power distribution in pulp and paper mills,
steel mills, food processing plants, mines, generating stations, refineries,
industrial plants and chemical plants. They may be installed in racks,
trays, ladders, raceways, aerial installations, direct burial and
concrete-encased installations. MC-HL continuous corrugated aluminum
armor provides a sheath impervious to moisture, liquids, and gases.
For use in Classes I, II, and III, Division 1 and 2 hazardous locations
covered under NEC® Articles 501, 502, and 503.
These cables are capable of operating continuously in wet or dry locations
at a maximum conductor temperature of 105°C for normal operation,
140°C for emergency overload conditions, and 250°C for short circuit
conditions.
MC-HL provides an impervious sheath recommended as an economical
alternative to traditional conduit systems.
The construction of a continuously corrugated aluminum sheath with three
symmetrically ground wires make this cable ideal for use in pulse-width
modulated and variable frequency drive applications.
Construction
Three compact stranded copper conductors, extruded semiconducting
• CU Conductor
EPR strand screen, EPR insulation, extruded semiconducting EPR
• EPR Insulation insulation screen, phase identification strips, and copper shield tape
• CU Tape Shielded overlapping, over individual conductors, with one stranded copper
• One Ground Wire grounding conductor, fillers and binder tape over the core, corrugated
• Continuous Corrugated aluminum welded armor is applied over the assembly, a protective
Aluminum Armor sunlight and ozone resistant jacket of polyvinyl chloride (PVC) suitable
• -40°C PVC Jacket for installation in temperatures down to -40C, is extruded over the
• EPR / CWA / PVC aluminum welded armor.
Sizes: 1/0 AWG to 500 Kcmil.
Other options available upon request: XLP insulation, colors, low smoke,
zero halogen (LSZH), low corrosion jackets and customized ground wires.
Standards
• UL 1072 - Medium voltage power cables
• UL 2225 - Safety metal-clad cables and cable-sealing fittings for use
in hazardous (classified) locations
• UL 1309 - Listed as marine shipboard cable
• ICEA S-93-639 (NEMA WC 74) - 5-46 kV shielded power cable for use in
the transmission and distribution of electric energy
• IEEE 1202 - Flame testing of cable for use in cable tray in industrial and
commercial occupancies (70,000 BTU/hr)
• ICEA T-29-520 – Vertical tray flame test (210,000 BTU/hr)
*Ampacities are based on the NEC 2011 Handbook: Ampacities of an Insulated Three-Conductor Copper Cable Isolated in Air.
For other installations, refer to the NEC Handbook. The above data is approximate and subject to normal manufacturing tolerances.
5-31
NOTES
5-32
Gaffney-Kroese Supply Corp.
fney-Kroese Supply Corp.
We provide safe, reliable
products designed to support
your competitive advantage.