Earth Measurement

Basiic Design

[Jet ermination of !;s.. Z.

Yes

Determ inatio n of UT
or

Recog nized
spec ifi ed
m eas u res M
Fault duration (s) Body current (mA)
0.05 900
0.10 750
0.20 600
0.50 200
1.00 80
2.00 60
5.00 51
10.00 50

Touch voltage (V) Total human body independence Total current body
(Ω) (A)
25 3250 0.0077
50 2500 0.016
75 2000 0.037
100 1725 0.058
125 1550 0.08
150 1400 0.107
175 1325 0.132
200 1275 0.156
225 1225 0.183
400 950 0.420
500 850 0.558
700 775 0.899
1000 775 1.29

Based on standard EN 50522, the touch voltage values are determined depending on the duration
of the damage.
1. Permissible Touch Voltage Calculation

Fault Duration tf ≔0.5

Body Current Limit IBtf ≔0.2 It depends on tf=0.5

Heart Current Factor HF ≔0.7 Eg. For worst case

Body Impendance ZtUt ≔775 For Ut=1080 V

Body Factor BF ≔0.75 Eg. For worst case hand to both feet

1
ZtUt1 ≔775 Utp1 ≔IBtf ⋅ • ZtUt1 ⋅ BF = 166.071
HF
ZtUt2 ≔850
1
ZtUt3 ≔ 775 Utp2 ≔IBtf ⋅ ⋅ ZtUt2 ⋅ BF = 182.143 Utp3 ≔
HF 1
ZtUt4 ≔ 775
ZtUt5 ≔ 950 IBtf ⋅ ⋅ ZtUt3 ⋅ BF = 166.071 Utp4 ≔IBtf ⋅
HF 1 HF
ZtUt6 ≔ 850
ZtUt7 ≔ 775 ⋅ ZtUt4 ⋅ BF = 166.071 Utp5 ≔IBtf ⋅ ⋅ ZtUt5
1 HF
ZtUt8 ≔ 775
ZtUt9 ≔775 ⋅ BF = 203.571 Utp6 ≔IBtf ⋅ ⋅ ZtUt6 ⋅ BF =
1 HF
182.143 Utp7 ≔IBtf ⋅ ⋅ ZtUt7 ⋅ BF = 166.071
1 HF
1 Utp8 ≔IBtf ⋅ ⋅ ZtUt8 ⋅ BF = 166.071 Utp9 ≔
Utp ≔IBtf ⋅ ⋅ ZtUt ⋅ BF
HF HF 1
IBtf ⋅ ⋅ ZtUt9 ⋅ BF = 166.071
HF 1

Fault duration tf Permissible touch voltage Utp


0.05 716
0.10 654
0.20 537
0.50 220
1.00 117
2.00 96
5.00 86
10.00 85

TableB.1 - EN50522
2. Touch Voltage

Ic ≔200 r ≔

0.61

Re1 ≔3.4 UT1 ≔Ic ⋅ Re1 = 680 UT2 ≔Ic UE1 ≔UT1 ⋅ r = 414.8 UE2 ≔
Re2 ≔2.2 ⋅ Re2 = 440 UT2 ⋅ r = 268.4
3

Re3 ≔5.4 UT3 ≔Ic ⋅ Re3 = 1.08 ⋅ 10 UE3 ≔UT3 ⋅ r = 658.8


3
Re4 ≔5.4 UT4 ≔Ic ⋅ Re4 = 1.08 ⋅ 10 UE4 ≔UT4 ⋅ r = 658.8 UE5 ≔
Re5 ≔1.8 UT5 ≔Ic ⋅ Re5 = 360 UT5 ⋅ r = 219.6
Re6 ≔ 2.1 UT6 ≔Ic ⋅ Re6 = 420 UT7 ≔Ic UE6 ≔UT6 ⋅ r = 256.2 UE7
Re7 ≔ 5.4 ⋅ Re7 = 1.08 ⋅ 103 UT8 ≔Ic ⋅ ≔UT7 ⋅ r = 658.8 UE8 ≔
Re8 ≔ 4.1 Re8 = 820 UT9 ≔Ic ⋅ Re9 = UT8 ⋅ r = 500.2 UE9 ≔UT9
Re9 ≔3.4 680 ⋅ r = 414.8

3. Validity of Conditions
First Condition UE<=2*Utp Not fullfilled because the minimal value
UE1 = 414.8 < 2 ⋅ Utp1 = 332.143

Second Condition UE<=4*Utp Fullfilled because the minimal value


UE1 = 414.8 < 4 ⋅ Utp1 = 664.286
3.Transfered Potential between HV to LV systems

R ≔11
A ≔π ⋅ R2 = 380.133 Vx=Voltage on the surface of the soil at point "X"
A = Earthing Grid Area
Vx1 ≔2 ⋅ Utp1 = 332.143 Vx2
≔2 ⋅ Utp2 = 364.286 Vx3 ≔2 ⋅
Utp3 = 332.143 Vx4 ≔2 ⋅
Utp4 = 332.143 Vx5 ≔2 ⋅
Utp5 = 407.143 Vx6 ≔2 ⋅
Utp6 = 364.286 Vx7 ≔2 ⋅
Utp7 = 332.143 Vx8 ≔2 ⋅ Utp8
= 332.143 Vx9 ≔2 ⋅ Utp9 =
332.143

A -1 ⎞
x1 ≔ ⎛Vx1 ⋅ π ⎞
x = Transfered Potential Distance from Substation
⋅ sin - 1 = 0.562
π ⎝ ⎝2 ⋅ UE1 ⎠ ⎠

A -1 ⎞
x2 ≔ ⎛Vx2 ⋅ π ⎞

⋅ sin - 1 = 1.993
π ⎝ ⎝2 ⋅ UE2 ⎠ ⎠

A -1 ⎞
x3 ≔ ⎛Vx3 ⋅ π ⎞

⋅ sin - 1 = 4.456
π ⎝ ⎝2 ⋅ UE3 ⎠ ⎠
⎛ ⎞
A -1
x4 ≔ ⎛Vx4 ⋅ π ⎞ 4.456

⋅ sin -1 =
π ⎝ ⎝2 ⋅ UE4 ⎠ ⎠

A -1 ⎞
x5 ≔ ⎛Vx5 ⋅ π ⎞

⋅ sin - 1 = 37.394
π ⎝ ⎝2 ⋅ UE5 ⎠ ⎠

A -1 ⎞
x6 ≔ ⎛Vx6 ⋅ π ⎞

⋅ sin - 1 = 2.953
π ⎝ ⎝2 ⋅ UE6 ⎠ ⎠
⎛ -1 ⎞
A ⎛Vx7 ⋅ π ⎞
x7 ≔

⋅ sin - 1 = 4.456
π ⎝ ⎝2 ⋅ UE7 ⎠ ⎠

A -1 ⎞
x8 ≔ ⎛Vx8 ⋅ π ⎞

⋅ sin - 1 = 1.732
π ⎝ ⎝2 ⋅ UE8 ⎠ ⎠

A -1 ⎞
x9 ≔ ⎛Vx9 ⋅ π ⎞

⋅ sin - 1 = 0.562
π ⎝ ⎝2 ⋅ UE9 ⎠ ⎠