2 Cement
C-1
Notwithstanding any previous acceptance any bag of cement
containing material which has hardened or otherwise
deteriorated shall be rejected and removed from the site by the
Contractor forthwith and at his own expense. Any cement on
transit or temporarily placed near the mixer or elsewhere,
after removal from the store, shall be adequately protected
from moisture and damage by approved means.
3 Storage of Cement
4 Fine Aggregate
________________________________________________________________
| | | | | | | |
|B.S.Sieve | 5 mm | No. 7 | No. 14 | No. 25 | No. 52 | No. 100|
|__________|_______|_______|________|________|________|________|
| | | | | | | |
|% Passing |95-100 | 70-95 | 45-85 | 25-60 | 5-30 | 0-10 |
|__________|_______|_______|________|________|________|________|
5 Coarse Aggregate
C-2
harmful quantities of clay, crusher dust, organic impurities or
other deleterious matter.
_______________________________________________________
| | | | |
| B.S. Sieve | 20 mm | 10 mm | 5 mm |
|_____________|________|_________|____________________|
| | | | |
| % Passing | 100% | 25 - 55 | Not more than 10 |
|_____________|________|_________|____________________|
C-3
7 Storage of Aggregates
8 Water
Water used for making and curing concrete and for testing the
watertightness of structures shall be fresh, clean and not
contain organic matter, sulphates or other impurities in
sufficient quantities likely to reduce the strength of the
concrete or attack the concrete or the reinforcement. The
Engineer's decision on the suitability or unsuitability of a
source of water for his purpose shall be final.
9 Steel Reinforcement
C-4
All reinforcement shall be cleaned from loose millscales, loose
rust, oil, grease, earth and other harmful matter before being
placed in the forms and shall be free from these at the time
the concrete is placed.
11 Welding of Reinforcement
C-5
V-type and two butt weld bend tests shall be carried out on a
specimen prepared to represent each form of butt welded joint.
The method of making weld tests shall be that laid down in B.S.
709: 1964.
12 Formwork
(i) Sound softwood tongued and grooved boards not less than
20 mm finished thickness, wrought on one side and two
edges, accurately formed and securely fixed to softwood
frames. The surfaces of the formwork shall be worked to a
smooth finish after fabrication.
All formwork shall be erected true to line and level and shall
be adequately secured and braced to prevent deflection or
movement during the placing, tamping or vibrating of the
concrete, and shall be sufficiently tight to prevent loss of
liquid.
The use of wires passing through the concrete for the purpose
of securing the formwork in position shall not be permitted.
Bolts passing through the concrete may be used, but their
number must be kept to the minimum required to secure the
formwork rigidly. The bolts shall be not less than 13 mm in
diameter and of a type with detachable screw off heads so that
the barrels of the bolts remain cast in the concrete while the
detachable heads can be removed with ease. The barrel of every
bolt used in water retaining, water conveying or water
excluding structures shall have a waterstop in the form of a
100 mm x 100 mm x 3.5 mm steel washer on at the mid-length of
the bolt. The weld shall be continuous round the barrel and on
both sides of the washer.
C-6
surfaces within the forms shall be thoroughly flushed with
water. The forms may with the approval of the Engineer be
treated with an approved composition. Care should be taken to
ensure that such composition is kept out of contact with the
reinforcement and concrete joint surfaces, and that there is no
excess of such composition remaining on the forms prior to
concreting.
13 Concrete Proportions
C-7
cube strengths fall below those specified, the cement
proportions shall be increased.
Designed concrete mixes may be used and shall comply with the
recommendations of BS 8110. However,the grades of
concrete to be used shall be as below which supersede table 3.3
of BS 8110:
Nominal
Mix Minimum Maximum Minimum
Equivalent Crushing aggregate Cement
Resistance in Size Content per cu.
N/mm2 m. of finished
Within 28 Days Concrete
after mixing
C-8
G40 40 20mm 330kg
Cement, coarse and fine aggregates and water shall comply with
the foregoing clauses of this specification.
C-9
All sampling and testing will be carried out in accordance with
the standard methods laid down in B.S. 1881 unless otherwise
specified in the following clauses.
18 Rejection of Concrete
C - 10
below, the Engineer shall, at his discretion, order all
concreting work to stop until adequate measures have been taken
to produce concrete which complies with this Specification.
19 Supervision
20 Mixing concrete
C - 11
Each batch of concrete shall contain one or more whole bags of
cement.
The materials for each mix shall be placed in the loading skip
in the following order: coarse aggregate, cement, and fine
aggregate. The water shall be added to the dry materials in the
mixer drum. The quantity of water specified in Table `A' may be
varied up to 5% in order to maintain a constant workability;
but this tolerance shall not be exceeded without prior approval
of the Engineer. Each batch of concrete shall be mixed until
there is a uniform distribution of the materials and the mass
is uniform in colour and consistency. In no case shall the time
of mixing be less than two minutes or more than five minutes
after the water has been added to the batch. Any concrete
surplus to requirements shall be thrown away. In no
circumstances may surplus concrete be remixed for use later.
22 Compaction of Concrete
C - 12
than 4,000 R.P.M. and of a kind approved by the Engineer. They
shall be operated by workmen skilled in their use who shall be
additional to the labourers employed on placing and tamping the
concrete.
C - 13
The floors or roofs are divided into segments bounded by joints
shown on the Drawings. The concrete in each segment shall be
placed and compacted in regular strips across the full width of
the segment. Each strip shall be placed against the previous
strip before the concrete in the latter has attained initial
set. Each segment shall be concreted in one continuous
operation, and the Contractor shall so arrange his concreting
programme that not less than 7 days shall elapse between the
placing of concrete in any two adjacent segments.
C - 14
26 Construction of Wall Footings and Haunches of Water Retaining,
Water Conveying or Water Excluding Structures
28 Joints
The Contractor shall make the joints in the floors, walls and
roofs strictly in accordance with the Drawings. Particular care
shall be taken to ensure that the waterstops wherever shown on
the Drawings are adequately secured so that they will not be
displaced while concrete is being placed. Under no circumstance
shall waterstops be nailed through. Any water stop which has
been perforated shall be rejected and replaced at the
Contractor's expense.
C - 15
1:1-1/2 cement and sand mortar not less than 40 mm thick. The
mortar shall have the consistency of condensed milk.
Any concrete which has been disturbed after it has attained its
initial set shall be rejected and subsequently removed and
replaced by the Contractor at his own expense.
30 Sealing Compounds
31 Waterstops
C - 16
The Contractor shall carefully read the waterstop
manufacturer's instructions before commencing any work
involving the incorporation of waterstops and shall carry out
all work in this connection as recommended by the manufacturer
and to the approval of the Engineer.
33 Curing Concrete
C - 17
completely covered with wet gunny bags, which shall be kept
thoroughly wet continuously by generous application of water
every two hours for a period of 8 days. The water shall be
allowed to run down between the forms and the formed concrete
surfaces. Flat slabs shall have water impounded on them for a
period of at least 10 days after placing.
When all the concrete in the floor and the haunch of any water
retaining, water conveying or water excluding structure have
been placed and the concrete attained the final set, the whole
of the floor shall be flooded with water to a depth of not less
than 75 mm. This depth of water shall be maintained throughout
the rest of the construction period.
34 Striking Formwork
(unloaded) .. 3 days
All areas where the concrete has not been properly consolidated
to a dense uniform surface shall be cut out, and made good to
the satisfaction of the Engineer. All bolt holes left by the
formwork bolts shall be plugged as described herein. The sides
of the holes shall be reamed with a hacksaw blade until the
cement scum is removed. The holes shall then be flushed with a
strong jet of water to remove all loose materials. While the
holes are still wet, the sides of the holes shall be dusted with
C - 18
neat cement using a suitable brush for this purpose.
Immediately following this the holes shall be plugged with a dry
pack consisting of one part of cement and two parts of fine
sand. The mixture of cement and sand shall be made only
sufficiently damp with water to allow it to be rammed solid
without exuding any liquid, and after thorough mixing shall be
placed in the holes in thin layers and solidly compacted over
the entire surface with a hardwood stick and a hammer, and
finally struck off to a true surface.
The Contractor shall, at his own expense, conduct the tests for
water tightness of all water retaining, water conveying, and
water excluding structures and shall provide all the water
required for this purpose.
The structure shall be filled with water to the top water level
shown on the Drawings and maintained at that level for three
days. Should any obvious signs of leakage be observed during
this period, or any subsequent test period, the positions of all
such signs of leakage shall be marked and the test shall be
stopped; and the Contractor shall at his own expense carry out
such remedial measures as the Engineer shall direct including
the complete emptying of the structure if necessary. Should the
leakage be general the remedial measures may include the
complete treatment of the inside surfaces of the structure by
rendering or by the application of some other approved
waterproof coating. When all obvious signs of leakage have been
stopped and made good in accordance with the Engineer's
instructions, the structure shall be refilled to top water
level, and so maintained for three days. At the end of the third
day, provided no further signs of leakage are observed the exact
water level shall be marked, and after a further seventy-two
hour period, the water level shall again be marked and the
difference recorded. During this seventy-two hour period an
C - 19
evaporation test shall be carried out in the manner described
hereunder. The structure shall be deemed watertight and shall
be so accepted in this respect only by the Engineer if the
recorded difference minus the loss of water by evaporation gives
a figure which does not exceed 1/2000 of the depth of the water
originally in the structure. Should, however, the above recorded
difference minus the loss of water by evaporation give a figure
which exceeds 1/2000 of the depth of the water originally in the
structure, the Contractor shall, at his own expense, carry out
the complete treatment of the inside of the structure by
rendering or such other remedial measures as the Engineer may
direct. On completion of such treatment, the Contractor shall at
his own expense retest the structure and repeat these remedial
measures, if found necessary, until watertightness is obtained.
C - 20
Precast concrete surface waterdrains shall be cast in 600 mm
lengths with dimensions as shown on the Drawings. The drains
shall be properly bedded and jointed with 1:3 cement sand
mortar and laid to falls as directed by the Engineer.
41 Concrete Pipes
The pipe section shall not be cut off without the approval of
the Engineer. The joints of the pipes shall be ordinary ogee or
rebated joint, sealed with cement mortar.
42 Ready-Mixed Concrete
C - 21
(i) Delivery notes giving details of quality and mix
proportions
(ii) The time at which each batch of concrete was mixed and
details of any additives used.
C - 22
TABLE `A’
________________________________________________________________________________________________________________________
N/mm2 N/mm2
Grade to be designed 34 50
50
_________________________________________________________________________________________________________________________
Grade to be designed 30 45
45
__________________________________________________________________________________________________________________________
Grade to be designed 27 40
40
__________________________________________________________________________________________________________________________
Grade to be designed 24 35
35
__________________________________________________________________________________________________________________________
C - 25
Note: (i) When concrete is compacted by hand (and not vibrated) the compacting factor and the mix
shall be determined by the Engineer when the preliminary test mixes are made.
N/mm2 N/mm2
Any consecutive 4 3 3
N/mm2 N/mm2
C7.5 to First 2 0 2
C15
First 3 1 2
Any consecutive 4 2 2
C - 25