Sei sulla pagina 1di 8

Chloride®

FP-50z
5 – 160kVA
Industrial AC UPS
CHLORIDE® FP-50Z

Features Feature-rich Industrial AC UPS system embedded with the


yyFully digital UPS solution for latest technologies for optimal power protection and
industrial applications reliability
yyRobust design ensure high The Chloride® FP-50z of Vertiv is an Industrial AC UPS system which is
reliability features designed to meet a wide array of mission critical continuity needs in an
yyUser-friendly display industrial environment. It is embedded with the latest technologies available
in the market today to provide your business maximum power protection
yyDesign and temperature features even in the harshest conditions.
for industrial

yyZero Transfer time

yyGalvanic isolation features

yyState of the art mechanical


Assembly design for ease of
maintenance

yyParallel redundant configuration

yyFully customizable

yyExternal communication capabilities

yyCustomized designs to suit IP


protection requirements

APPLICATIONS

yy Manufacturing:
Pharmaceutical, Textile, Retail

yy Power Generation,

yy T&D Oil and Gas

yy Transportation

yy Cement plants

yy Steel Plants

yy Chemical & Fertilizer

2
A fully digital Industrial UPS Connectivity Options Galvanic isolation features
system
yyUPS MON-II (RS232 or ETHERNET yyAny mains disturbance will not be
yyEasy System configuration through based) transferred to the DC circuit or to
software for on-site modification the output
and retrofitting needs yySNMP (RJ45)
yyLoad remains safe all the time
yyState of the art SPWM Technology yyMODBUS (RS 485) irrespective of switching/transient in
with digital control ensure low yyETHERNET based remote the Mains and sudden other output
electrical noise for the loads/ monitoring (i-REMOTE) load changes in the O/P ACBD
appliances
yyDouble conversion topology
yyA fast transient response provides clean and reliable power
International standards compliant
yyBetter voltage regulation
yyIEC / EN 62040 – 1 : Safety
yyLow total harmonic distortion Parallel redundant configuration
yyIEC / EN 62040 – 2 :
(THD)
Electromagnetic compatibility yyFor 1 Phase up to 3 units in parallel
yyEasy navigation
yyIEC / EN 62040 – 3 : Performance yyImmediate communication between
yyEvent log for analysis of fault & testing the paralleled systems after
occurrence and easier maintenance connection
yyISO 9001 : 2008 : Quality System
yyFP50z-3X1- Input, Battery , Output, yyNo single point of failure
Bypass per Group 170, i.e. total 680
event logs; In FP50z-3X3 --:- 254 yyActive load sharing
High reliability features
event logs
Customization Capability
yy15 to 20 years product lifespan,
yyPush button system control supported by recommend yyCustomized UPS configurations
yy2 lines of 20 characters display preventive maintenance offered at pre-sales stage

yyEnglish & Chinese language display yyFully custom built options meet
required output power, voltage
Design & temperature levels as well as available input
yyFull output rated continuous power and voltage quality levels
Robust mechanical design for
operating temperature 400C yyCustomer requirements like color,
easy maintenance
yyImproved thermal design with protection, PFC etc.
yyState of art front access for a more
ventilation ensures improve in yyCustomized accessories like ACDB,
efficient maintenance
MTBF of the components SCVS, Cell Booster
yyIf necessary, side and rear panels
are removable yyOption of input passive filter for PF
& THDi improvement
yyFan replacement from front or top Transfer time
yyBattery charging requirements
yyEasy access to Thyristors, IGBTs, yySafe transfer to bypass, without a
PCBs break for the connected load yyExtended temperature up to 500C
yy0 s when synchronized on reserve yySeismic qualification
yy<10 ms transfer time in Async mode

3
CHLORIDE® FP-50Z

Technical Specifications

MODEL STANDARD OFFERINGS OPTIONAL


INPUT

Nominal Voltage 415 VAC, 3 Phase, 3 wire ( +10 %, -20 % ); Input 220 VAC 3 Phase
Voltage range of 380/400 3 wire (+ 10 % , -15 % )
Nominal Frequency 50 Hz (± 10 %) 60 Hz (± 6 %)
Input Power factor ≥ 0.88 up to 7.5 kVA and ≥ 0.92 for 10 kVA and ≥ 0.96
above
yy
50 kA (MCCB)
Input Fault Level 10 kA
yy
Input Isolation Transformer (1)
RECTIFIER
Type Full Wave, A-PFC Rectifier 12 Pulse, above 20 kVA Rating
CHARGER
yy
IGBT based Dual mode of charging
Type yy
Suitable to charge VRLA-SMF, Lead
Acid, Ni-Cd battery
Nominal Voltage
±1% -
Regulation
Ripple
<2% -
(without Battery)
Constant Voltage Constant Current (CVCC)
Charging Method Auto & Manual with 0 to 24 Hr programmable
timer
BATTERY
yy240 VDC for 5 to 15 kVA
200 - 320V
yy300 VDC for 20 kVA yy
110 VDC (5-15 kVA UPS)
255V - 350VDC 94V - 160V
Battery Voltage
yy360 VDC for 30-120 kVA yy
220 VDC (20-120 kVA UPS)
290V - 460VDC 189V - 292V
Note : +2 Blocks of 12 V and -1 Block
of 12V possible
Type Ni-Cd / Tubular / VRLA
5 to 10 kVA Up to 15 A
15 to 20 kVA Up to 20 A 2 to 20 kVA 40 A at 110 VDC
Battery Charging 30 to 40 kVA Up to 30 A 2 to 20 kVA 20 A at 220 VDC
Capacity 50 & 80 kVA Up to 40 A 25 to 80 kVA 60 A at 220 VDC
60 kVA Up to 55 A As per Customer request (2)
100 to160 kVA Up to 60 A

Protection Battery Breaker, Reverse Battery Indication Reverse Polarity, Battery Earth Fault
OUTPUT
220V / 230V / 240V AC
Nominal Voltage 110V / 115V / 120V AC
(Step less Adjustable)
Load PF Support
0.6 to Unity (within its kVA / kW rating)
Capacity
Voltage Regulation ± 1 % for 230 VAC ± 2 % for 110 VAC
yy
50 Hz (± 0.1 Hz) in Free Running
Mode
Frequency 60 Hz (± 0.1 Hz)
yy
± 5 % (± 1 to 5 % adjustable)
in Synchronous mode
Waveform True Sine Wave
< 2 % Max. for 100 % Linear Load
Total Harmonic
< 5 % Max. for 100 % Non-Linear Load
Distortion
( IEC 62040–3 )
110% for 60 min, 125% for 10 min. , 150% for 1
Overload Capacity
min
Duty Continuous
IGBT based PWM with INSTANTANEOUS sine
Inverter Philosophy
wave control
For 0 to 100 % step load change, the output
shall remain within ± 5 % and recover to 98 %
Dynamic Response
within 1 cycle
( IEC 62040–3, Class 1 )
Crest Factor 3:1
STATIC SWITCH
Frequency
± 2.5 Hz
Synchronisation
Slew Rate 0.2 Hz/Sec
Transfer yy
In Sync mode – No break in transfer
(Inverter to Bypass) yy
In ASync mode – < 10 ms
yy
In Sync mode – No break in
Re-transfer
re-transfer
(Bypass to Inverter)
yy
In ASync mode – Not applicable
Overload Capacity 1000 % for 100 ms
Manual Bypass
Make Before Break
Operation
yy
Parallel Redundant with
System Configuration Standalone separate batt bank
yy
Hot Stand by
CHLORIDE® FP-50Z

PHYSICAL
Enclosure Protection IP 41 IP 42
RAL 7021 / RAL 7032 / IS 5 – 631/ RAL
9001
Colour RAL 7021 Structure Finish
Structure or as per customer
requirement
Paint Thickness & 90 micron (± 10 micron ) Epoxy Powder
Type Coated
Cooling Forced Air
Cable Entry Bottom Top
Class of Insulation – Class H (Transformer /
Wound Components
Inductor)
GENERAL SPECIFICATIONS
Operating 0 to 45 0C (5-20 kVA) 0 to
Up to 50 0C (2)
Temperature 40 0C (30-120 kVA)
Relative Humidity 0 to 95% (Non-condensing)
Storage Temperature 0 to 50 0C
Utility Socket 230 V / 5 A
Illumination Lamp 11 W CFL Space Heaters
yy
5-20 kVA: 3 x 25 mm CU 3 x 25 mm
CU
yy
30-40 kVA: 3 x 25 mm CU 3 x 25 mm
Earth Busbar
CU
(Ref.IS 3043)
(Earth bus bar running along the panel)
yy
50-120 kVA: 6 x 50 mm copper
(Earth bus bar running along the panel)
yy
PFC with 250 V , 2 A / 6 A
One relay contact for each rating
PFCs
(Rating 250 VAC , 1 A) yy
Transducer 4 to 20 mA
(As per Customer Specifications)
Remote Panel With LCD (Ethernet Connectivity)
UPS Monitoring yy
UPSMON II
Software yy
SNMP, MODBUS
Connectivity RS 232 / RS 485 Ethernet / RS 485
VertivCo.com
© 2017 Vertiv Co. All rights reserved. Vertiv and the Vertiv logo are trademarks or registered trademarks of Vertiv Co. All other names and logos referred to are trade names, trademarks or registered trademarks of their respective owners. While every
precaution has been taken to ensure accuracy and completeness herein, Vertiv Co. assumes no responsibility, and disclaims all liability, for damages resulting from use of this information or for any errors or omissions. Specifications are subject to change
without notice.
Chloride-FP50z-BR-EN-ASIA-v2