GENERAL NOTES LEGENDS

1. ALL ELECTRICAL WORKS HEREIN SHALL BE DONE IN ACCORDANCE WITH THE PROVISIONS OF THE LATEST EDITION OF THE PHILIPPINE ELECTRICAL SYMBOL DESCRIPTION
CODE, THE RULES AND REGULATIONS OF THE AUTHORITIES THAT HAVE JURISDICTION OVER THE PROJECT, AND WITH THE POLICIES OF THE LOCAL POWER SERVICE ENTRANCE
TELECOMMUNICATION SERVICE ENTRANCE
UTILITY COMPANIES FOR ELECTRICAL AND FOR COMMUNICATION.
ENCLOSED CIRCUIT BREAKER IN NEMA-1/3R ENCL.
PROPOSED TRANSPORT
2.
AIR CIRCUIT BREAKER (FREE-STANDING)
TERMINAL PHASE 2
AUTOMATIC TRANSFER SWITCH
3. WIRING METHOD SHALL BE DONE IN THE FOLLOWING MANNER: MANUAL TRANSFER SWITCH GREENFIELD CITY,
A. RIGID STEEL CONDUIT (RSC) - AS SPECIFIED IN THE PLANS, IF ANY. MECHANICAL AND ELECTRICAL INTERLOCK FOR ATS STA. ROSA, LAGUNA
B. POLYVINYL CHLORIDE (PVC) PIPE - FOR PRIMARY AND SECONDARY POWER SERVICE ENTRANCE, TELEPHONE SERVICE ENTRANCE POWER PANEL BOARD
AND LAYOUT EMBEDDED IN THE CONCRETE/SLAB FOR POWER & LIGHTING. BUSBAR/CB GUTTER & ECB
C. FLEXIBLE METAL CONDUIT - FOR CONNECTION BETWEEN JUNC. BOX INSIDE TO LIGHTING OUTLET OF FIXTURES AT DROP CEILING. CIRCUIT HOME RUN
D. ELECTRICAL METALLIC TUBING - FOR INSTALLATION LAYOUT INSIDE DROP CEILING, EXPOSED AND DOUBLE WALL PARTITION,
4. ALL ELECTRICAL MATERIALS/EQUIPMENTS TO BE USED SHALL BE NEW AND OF THE APPROVED TYPE FOR BOTH LOCATION AND PURPOSE. JUNCTION BOX( PULL BOX/TAPPING POINT)
5. GENERAL USE RECEPTACLE SHALL BE RATED 15A, 250V, GROUNDING TYPE WITH PARALLEL SLOTS. SPECIAL PURPOSE OUTLETS SHALL BE OF THE FLOOR SINGLE CONVENIENCE OUTLET
TYPE AND RATING APPROPRIATE FOR THE EQUIPMENT TO BE SERVED. SINGLE CONVENIENCE OUTLET
6. SWITCHES FOR LIGHTS SHALL BE RATED 10A, 230V, AC RATED ONLY. DUPLEX CONVENIENCE OUTLET
PULLBOX(POWER PROVISION)
7. ALL OUTDOOR INSTALLATIONS SHALL BE OF THE WEATHERPROOF TYPE. S SINGLE GANG SWITCH
8. 2Sab 2 GANG SWITCH
3Sabc 3 GANG SWITCH
9. WHERE SPARE CIRCUITS ARE INDICATED IN THE SCHEDULE OF PANELBOARD, THE CONTRACTOR SHALL PROVIDE AN EMPTY CONDUIT S3W 3 WAY SWITCH
2S3Wab 2 GANG 3 WAY SWITCH
STUBBED-OUT INSIDE THE CEILING AND CAPPED.
RU/RD RISER UP/RISER DOWN
10. OUTLET BOXES SHALL BE 1.35MM THICK AND AS FOLLOWS: SB SWITCH BANK
A. CEILING LIGHT OUTLET - 100MM X 100MM X 55MM DEEP OCTAGONAL BOX FOR 1 OR 2 RACEWAY ENTRIES; EMERGENCY LIGHTS W/ SINGLE CONVENIENCE OUTLET
B. LIGHT SWITCHES - 100MM X 100MM X 55MM DEEP SQUARE BOX FOR 3 OR MORE RACEWAY ENTRIES. EXIT LIGHTS SIGNAGE
C. WALL MOUNTED CONVENIENCE - 50MM X 100MM X 55MM DEEP UTILITY BOX HAND DRYER
ACU, TELEPHONE OUTLET, ETC
D. CONVENIENCE OUTLET - 100MM X 100MM X 55MM DEEP SQUARE BOX WITH SPECIAL TYPE RAISED COVER
(FLOOR-MOUNTED) POP-UP 10W LED RECESSED MOUNTED ADJUSTABLE DOWNLIGHT;
E. OTHERS - AS REQUIRED BY EQUIPMENTS SERVED. 59 DEG BEAM SPREAD: 3000k; IP20
32W LED UP AND DOWNLIGHT WALL SCONCE
11. MOUNTING HEIGHTS SHALL BE AS FOLLOWS:CEILING LIGHT OUTLET
1X 20W LED LAMP; BOX-TYPE POWDERCOATED
A. PANELBOARDS, CABINETS & - 1400MM ABOVE FLOOR FINISH ON CENTER OR AS REQUIRED BY FIELD CONDITION 1225mm X 45mm X 20mm; 6500k
DISCONNECTING SWITCHES
B. LIGHT CONTROL SWITCHES - 1400MM ABOVE FLOOR FINISH ON CENTER
C. DESK TOP CONVENIENCE OUTLET - 300MM ABOVE FLOOR FINISH ON CENTER
D. CHIME & FIRE ALARM BELL - 250MM BELOW CEILING @ CENTER
E. OTHERS - AS REQUIRED BY EQUIPMENTS SERVED. 32W LED RECESSED DOWNLIGHT WITH 59 DEG BEAM SPREAD: 3000k
12. THE ENTIRE ELECTRICAL WORKS HEREIN SHALL BE DONE UNDER DIRECT SUPERVISION OF A COMPETENT REGISTERED ELECTRICAL ENGINEER. 32W UPLIGHT, VERIFY DETAIL
PROVISION FOR DATA, PROVIDE 2 - 1 CORE SINGLE MODE FIBER
13. PROVIDE AN ADEQUATE AND EFFECTIVE GROUNDING SYSTEM. IN THE ABSENCE OF GI WATER PIPE IN SERVICE,
14. MOUNTING HEIGHTS OF ALL TYPES OF WRING DEVICES SHALL BE SUBJECT TO PRIOR APPROVAL BY THE ARCHITECT. TELEPHONE PROVISION, PROVIDE 1-4PAIR CAT6 CABLE

POS PROVISION, PROVIDE1-4PAIR CAT6 CABLE


SITE

CIRCUIT BREAKER RATINGS WIRE SCHEDULE


A 20AT 50AF 2PCB 240V 10KAIC B.O.
B 30AT 50AF 2PCB 240V 10KAIC B.O. 2 WIRE + GROUND 3 WIRE + GROUND 4 WIRE + GROUND
C 40AT 50AF 2PCB 240V 10KAIC B.O. SYMBOL CONDUIT SYMBOL CONDUIT SYMBOL CONDUIT
D 50AT 50AF 2PCB 240V 10KAIC B.O.
E 70AT 100AF 2PCB 240V 10KAIC B.O. 3.5 THHN X3.5 15 (EMT) Y3.5 15 (EMT) Z3.5 15 (EMT)
F 100AT 100AF 2PCB 240V 10KAIC B.O. X5.5 15 (EMT) Y5.5 Z5.5
5.5 THHN 15 (EMT) 20 (EMT)
G 125AT 150AF 2PCB 240V 10KAIC B.O.
H 150AT 150AF 2PCB 240V 10KAIC B.O. 8.0 THHN X8.0 20 (EMT) Y8.0 20 (EMT) Z8.0 20 (EMT)
a 20AT 50AF 3PCB 400/240V 14KAIC I. T. 14 THHN X14 20 (EMT) Y14 20 (EMT) Z14 25 (EMT)
b 30AT 50AF 3PCB 400/240V 14KAIC I. T.
c 40AT 50AF 3PCB 400/240V 14KAIC I. T. 22 THHN X22 25 (EMT) Y22 25 (EMT) Z22 32 (EMT) DAVE VERGEL B. CASTRO
d 50AT 50AF 3PCB 400/240V 14KAIC I. T. 30 THHN X30 25 (EMT) Y30 25 (EMT) Z30 32 (EMT)
e 70AT 100AF 3PCB 400/240V 14KAIC I. T.
f 100AT 100AF 3PCB 400/240V 22KAIC I. T. 38 THHN X38 32 (EMT) Y38 32 (EMT) Z38 40 (EMT)
g 125AT 150AF 3PCB 400/240V 22KAIC I. T. 50 THHN X50 32 (EMT) Y50 32 (EMT) Z50 50 (EMT)
h 150AT 150AF 3PCB 400/240V 22KAIC I. T.
i 175AT 150AF 3PCB 400/240V 22KAIC I. T. 60 THHN X60 40 (EMT) Y60 40 (EMT) Z60 50 (EMT)
j 200AT 225AF 3PCB 400/240V 22KAIC I. T. 80 THHN X80 50 (EMT) Y80 40 (EMT) Z80 50 (EMT)
k 225AT 225AF 3PCB 400/240V 22KAIC I. T.
l 250AT 400AF 3PCB 400/240V 35KAIC I. T. 100 THHN X100 50 (EMT) Y100 50 (EMT) Z100 65 (RSC)
m 300AT 400AF 3PCB 400/240V 35KAIC I. T. 125 THHN X125 65 (RSC) Y125 50 (EMT) Z125 65 (RSC)
n 350AT 400AF 3PCB 400/240V 35KAIC I. T.
o 400AT 400AF 3PCB 400/240V 65KAIC I. T. 150 THHN X150 65 (RSC) Y150 50 (EMT) Z150 80 (RSC)
p 500AT 500AF 3PCB 400/240V 65KAIC I. T. 200 THHN X200 65 (RSC) Y200 65 (RSC) Z200 80 (RSC)
q 600AT 600AF 3PCB 400/240V 65KAIC I. T.
250 THHN X250 65 (RSC) Y250 80 (RSC) Z250 90 (RSC)
r 700AT 800AF 3PCB 400/240V 65KAIC I. T.
s 800AT 800AF 3PCB 400/240V 65KAIC I. T. NOTE: WHERE:
s' 800AT 800AF 4PCB 400/240V 65KAIC I. T. SIZE OF GROUNDING CONDUCTORS
SHALL BE IN ACCORDANCE WITH
2Y100
t 1000AT 1000AF 3PCB 400/240V 65KAIC I. T. SIZE OF WIRES (IN MM. SQ.)
u 1200AT 1200AF 3PCB 400/240V 80KAIC I. T. PHILIPPINE ELECTRICAL CODE NUMBER OF WIRES
v 1600AT 1600AF 3PCB 400/240V 80KAIC I. T. (TABLE 2.50.6.13) X - 1 WIRE + 1 NEUTRAL WIRES + GROUND WIRE
or 2 WIRE + GROUND WIRE( for line to line)
w 2000AT 2000AF 3PCB 400/240V 80KAIC I. T. Y - 3 WIRES + GROUND WIRE
x 2500AT 2500AF 3PCB 400/240V 80KAIC I. T. Z - 3 WIRES + 1 NEUTRAL WIRES + GROUND WIRE
y 3200AT 3200AF 3PCB 400/240V 80KAIC I. T. NUMBER OF SETS OF FEEDER
z 4000AT 4000AF 3PCB 400/240V 80KAIC I. T.
s'' 160A 225AF 4PCB 400/240V 35KAIC I. T. *FOR ANY DISCREPANCY, FOLLOW LOAD SCHEDULE

CONRAD C. ERFE, durp

RISER UP TO
GENSET/EE ROOM

JOSE L. SERRANILLA,PEE

MH MH MH

ADVANCE COPY FOR CONSTRUCTION

FOR BIDDING NOT FOR CONSTRUCTION

FOR PERMIT as of 2018 02 26