Apparatus Maintenance and Power


Management For Energy Delivery

ENERGY METER TESTING


WITH
F6150 & F6MCP SOFTWARE
Kamin Dave (Relay Appl. Engr.)
DOBLE ENGINEERING PVT LTD

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA-390 015
DOBLE ENGINEERING COMPANY, 85-WALNET STREET, WATERTOWN, USA
www.doble.com
India

DATE 1/01/2006
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

Meter Details:

----Æ Programmed via front panel or RS485 port


----Æ Uni/Bi-directional configuration
----Æ Parameters calculated are displayed on LCD
----Æ Programmable for external CT/PT ratios
----Æ Immune to electromagnetic interference
----Æ Conform to IEC standards
----Æ Tamper detection features

Technical Specificatiopns:
----Æ Type: ER300N
----Æ Accuracy: CL.05s – IEC60687
----Æ Current (In): 1A or 5A
----Æ Start Current: 0.1*In (for CL.0.5s)
----Æ Power Factor: 4-quadrant operation
----Æ Frequency: 50 Hz +/- 10%
----Æ Load Characteristic: 5VA in potential circuit & 0.5VA in current circuit
----Æ Pulses/unit: 2500
----Æ Input Voltage: 3 X 240Vac

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA-390 015
DOBLE ENGINEERING COMPANY, 85-WALNET STREET, WATERTOWN, USA
www.doble.com
India

DATE 1/01/2006
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery
TEST CIRCUIT

DM-1H/v

Sensor
I1 VA

I2 VB

I3 VC

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA-390 015
DOBLE ENGINEERING COMPANY, 85-WALNET STREET, WATERTOWN, USA
www.doble.com
India

DATE 1/01/2006
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

Sensor output connected to logic input. Pl. ensure the polarity with settings
of logic input.

BNC-connector

DM-1H/v

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA-390 015
DOBLE ENGINEERING COMPANY, 85-WALNET STREET, WATERTOWN, USA
www.doble.com
India

DATE 1/01/2006
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

Connection details:
3-V & 3-I Connections to CT & PT terminals of meter
Sensor position in front of RED LED PULSE
Sensor output to Logic input of F6150

System details:

PT RATIO = 1.0
CT RATIO = 20/1A

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA-390 015
DOBLE ENGINEERING COMPANY, 85-WALNET STREET, WATERTOWN, USA
www.doble.com
India

DATE 1/01/2006
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

Double click on “F6Control Panel” software. Software version:- 3-0155

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA-390 015
DOBLE ENGINEERING COMPANY, 85-WALNET STREET, WATERTOWN, USA
www.doble.com
India

DATE 1/01/2006
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA-390 015
DOBLE ENGINEERING COMPANY, 85-WALNET STREET, WATERTOWN, USA
www.doble.com
India

DATE 1/01/2006
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

STEP:-2

Click on “Settings” in “Device” menu

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA-390 015
DOBLE ENGINEERING COMPANY, 85-WALNET STREET, WATERTOWN, USA
www.doble.com
India

DATE 1/01/2006
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

STEP:-3

Click on “Watthour” & “Varhour” in Add function

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA-390 015
DOBLE ENGINEERING COMPANY, 85-WALNET STREET, WATERTOWN, USA
www.doble.com
India

DATE 1/01/2006
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

STEP:-4

Enter the settings for “Watthour” test in “Watthour” module

Enter Rated Vn (Vph)

Select 3-ph or 1-ph

Automatic calculation for time based on pulse


Enter the “pulse/WH”

Enter the Number of Pulse for test (say, 250)

Note: Always keep VTR/CTR = 1

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA-390 015
DOBLE ENGINEERING COMPANY, 85-WALNET STREET, WATERTOWN, USA
www.doble.com
India

DATE 1/01/2006
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

Calculation for Maximum Test time:

Meter constant = 2500 Pulse/WH = 1/2500 = 0.0004 WH/Pulse


Number of Pulse for Test = 250
Power Factor = 1 (Unity)
Watts Load on Meter = 1.7325*E*I*COS(pHi) = 1.7325*415*1*1 = 718.80 watss

T = {(0.0004)*(3600)*(250)} / (0.71880) = 500.83 s = 8 minutes & 22seconds

Calculation for calibration Qty/Element:


3 - elements
VL-L = 415V
In = 1.0A
Power factor = 1.0
P in watts = 1.7325*415*1*1 = 718.8 Watts

Calibration Qty/Element = 718.8 / 3 = 240 Watts

Calculation for Scale Factor:

Meter constant = 2500 Pulses/KWH


CTR = 1 & VTR = 1

Scale Factor = {(2500)*(CTR)*(VTR)} / 1000 = (2500*1*1) / 1000 = 2.5 Pulse/WH

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA-390 015
DOBLE ENGINEERING COMPANY, 85-WALNET STREET, WATERTOWN, USA
www.doble.com
India

DATE 1/01/2006
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

STEP:-5

Enter the settings for “Varhour” test in “Varhour” module

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA-390 015
DOBLE ENGINEERING COMPANY, 85-WALNET STREET, WATERTOWN, USA
www.doble.com
India

DATE 1/01/2006
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

STEP:-6

Select “Auto/Manual” mode for test

Vector shows the “watts”, “Var” & “VA”

If selection is on “Auto” mode then it is adjusting parameters from device settings

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA-390 015
DOBLE ENGINEERING COMPANY, 85-WALNET STREET, WATERTOWN, USA
www.doble.com
India

DATE 1/01/2006
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

If selection is on “manual” mode then voltage & current values/angles are required to be
enter in control panel

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA-390 015
DOBLE ENGINEERING COMPANY, 85-WALNET STREET, WATERTOWN, USA
www.doble.com
India

DATE 1/01/2006
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

STEP:-7

Watthour Testing:

Select “Watthour” module for test.

“Watthour”

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA-390 015
DOBLE ENGINEERING COMPANY, 85-WALNET STREET, WATERTOWN, USA
www.doble.com
India

DATE 1/01/2006
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

STEP:-8

Press “Logic Settings” button

Select “Input1” as “contact”

Select trigger condition “Open-ÆClose”

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA-390 015
DOBLE ENGINEERING COMPANY, 85-WALNET STREET, WATERTOWN, USA
www.doble.com
India

DATE 1/01/2006
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

STEP:-9

WH Testing at Unity PF:

Press “Enable” buttons

Press “System Output” button after pressing of “Enable” button

Software display shows Input & Output “WH” with graph

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA-390 015
DOBLE ENGINEERING COMPANY, 85-WALNET STREET, WATERTOWN, USA
www.doble.com
India

DATE 1/01/2006
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

After max Test time, Test will automatically stops & display shows Output Pulses with
meter constant

Output Pulses = 250

Output “WH” = 100 WH

System “Output” off automatically after max test time.

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA-390 015
DOBLE ENGINEERING COMPANY, 85-WALNET STREET, WATERTOWN, USA
www.doble.com
India

DATE 1/01/2006
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

F6150 reading compared with Meter reading:

Initial Reading on Meter = 2560.9 KWH -------A


Last Reading on Meter = 2562.9 KWH---------B
Difference = (A – B) = (2562.9 – 2560.9) = 2 KWH----------C

Initial Reading on F6150 = 0.0 KWH -------D


Last Reading on F6150 = 0.1 KWH---------E
Difference = (A – B) = (0.1 – 0) = 0.1 KWH----------F

Reading is on Primary side = 0.1*CTR*PTR = 0.1*20*1 = 2 KWH------D

%ERROR = {(C – D) / D}*100 = {(2 – 2) / 2}*100 = 0%--------------------E

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA-390 015
DOBLE ENGINEERING COMPANY, 85-WALNET STREET, WATERTOWN, USA
www.doble.com
India

DATE 1/01/2006
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

Test report shows source configurations, setting details & Test results.

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA-390 015
DOBLE ENGINEERING COMPANY, 85-WALNET STREET, WATERTOWN, USA
www.doble.com
India

DATE 1/01/2006
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

Test results:

Input Energy

Output Energy
Expected “Pulse/hour”

Actual “Pulse/hour”

%Error

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA-390 015
DOBLE ENGINEERING COMPANY, 85-WALNET STREET, WATERTOWN, USA
www.doble.com
India

DATE 1/01/2006
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA-390 015
DOBLE ENGINEERING COMPANY, 85-WALNET STREET, WATERTOWN, USA
www.doble.com
India

DATE 1/01/2006
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA-390 015
DOBLE ENGINEERING COMPANY, 85-WALNET STREET, WATERTOWN, USA
www.doble.com
India

DATE 1/01/2006
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA-390 015
DOBLE ENGINEERING COMPANY, 85-WALNET STREET, WATERTOWN, USA
www.doble.com
India

DATE 1/01/2006
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

System output automatically stops after 250 PULSES.

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA-390 015
DOBLE ENGINEERING COMPANY, 85-WALNET STREET, WATERTOWN, USA
www.doble.com
India

DATE 1/01/2006
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

Test Results:

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA-390 015
DOBLE ENGINEERING COMPANY, 85-WALNET STREET, WATERTOWN, USA
www.doble.com
India

DATE 1/01/2006
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

Now, select “Varhour”

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA-390 015
DOBLE ENGINEERING COMPANY, 85-WALNET STREET, WATERTOWN, USA
www.doble.com
India

DATE 1/01/2006
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA-390 015
DOBLE ENGINEERING COMPANY, 85-WALNET STREET, WATERTOWN, USA
www.doble.com
India

DATE 1/01/2006
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA-390 015
DOBLE ENGINEERING COMPANY, 85-WALNET STREET, WATERTOWN, USA
www.doble.com
India

DATE 1/01/2006
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

Test Results:

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA-390 015
DOBLE ENGINEERING COMPANY, 85-WALNET STREET, WATERTOWN, USA
www.doble.com
India

DATE 1/01/2006
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

Testing at 0.866 (LAG) Power Factor:

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA-390 015
DOBLE ENGINEERING COMPANY, 85-WALNET STREET, WATERTOWN, USA
www.doble.com
India

DATE 1/01/2006
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA-390 015
DOBLE ENGINEERING COMPANY, 85-WALNET STREET, WATERTOWN, USA
www.doble.com
India

DATE 1/01/2006
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

Initial Reading on Meter = 2560.9 KWH -------A


Last Reading on Meter = 2562.9 KWH---------B
Difference = (A – B) = (2562.9 – 2560.9) = 2 KWH----------C

Initial Reading on F6150 = 0.0 KWH -------D


Last Reading on F6150 = 0.1 KWH---------E
Difference = (A – B) = (0.1 – 0) = 0.1 KWH----------F

Reading is on Primary side = 0.1*CTR*PTR = 0.1*20*1 = 2 KWH------D

%ERROR = {(C – D) / D}*100 = {(2 – 2) / 2}*100 = 0%--------------------E

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA-390 015
DOBLE ENGINEERING COMPANY, 85-WALNET STREET, WATERTOWN, USA
www.doble.com
India

DATE 1/01/2006
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA-390 015
DOBLE ENGINEERING COMPANY, 85-WALNET STREET, WATERTOWN, USA
www.doble.com
India

DATE 1/01/2006
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA-390 015
DOBLE ENGINEERING COMPANY, 85-WALNET STREET, WATERTOWN, USA
www.doble.com
India

DATE 1/01/2006
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA-390 015
DOBLE ENGINEERING COMPANY, 85-WALNET STREET, WATERTOWN, USA
www.doble.com