1.

0 CABLE TRAY MOUNTINGS - GENERAL NOTES


1.1
CLIENT:Unless otherwise specifically mentioned on the relevant layout drawings, all cable tray
mounting works shall be carried out as per these notes.
1.2 Cable tray mounting arrangement type as marked on the layout drawings shall be
adopted.
1.3 Assembly of cable tray mounting structure shall be fabricated, supplied, erected and
painted by the electrical contractor.
1.4 Plate inserts for cable tray mounting structure will be provided by civil contractor in floor
slabs at 1000 mm spacing.
1.5 Cable tray mounting structure shall be welded to the plate inserts or to steel structural
beams/members. Welding of cable tray mounting structure to steel structural
beams/members shall be done with prior approval of Purchaser/ Engineer.
1.6 Wherever embedded plates or steel structural beams/members are not available for
welding the cable tray mounting structure, electrical contractor shall supply the M.S.
plate and fix it to floor slab by four anchor fasteners of minimum 16 mm dia. with
holding power of at least 5000 kg.
1.7 Spacing between cable tray mounting structures shall be 1000 mm for horizontal
straight run of cable trays unless otherwise noted.
1.8 Loading on a horizontal support arm shall not exceed 120kg / metre run of cable.
1.9 Width of the horizontal arms of the mounting structures shall be same as the tray widths
required in the cable layout drawings plus length required for welding to the vertical
supports (maximum tray width will be 750 mm) except where shown otherwise in the
layout drawings.
1.10 The length of the vertical supporting members for horizontal cable tray runs shall be to
suit the number of cable tray tiers indicated in the cable tray layout drawings.
1.11 Spacing between horizontal support arms of vertical cable tray runs shall be 600
mm unless otherwise noted.

REV DT CHDRAFTED
COMPUTER DR
FILE NAME:M2-2007.DOC TATA CONSULTING ENGINEERS TITLE. : CABLE TRAY MOUNTINGS -
HYDERABAD
FP NO : TCE.M2-EL-FP-DWG-003 GENERAL NOTES (SH 1 of 2)
APPROVED. R0 79-04-16
R1 98-
REV DT SR
CH MR
DR
10- K Sd/ SR Sd/PVDM R1
SCALE: NONE
27
DIV. DH-EL
PROJECT. DR. Sd/ SR
CH. Sd/ SR DWG. TCE-M2-EL-CT-S-2007/ R1
1.12 Cable trays shall be welded to tray mounting supports.
1.13
CLIENT:All welds for cable tray mounting steel structure shall be as indicated in cable tray
mounting arrangement drawings.
1.14 Minimum clearance between top most tray tier and structural member/ceiling shall
be 300 mm.
1.15 Minimum vertical clearance below the bottom of the lowest cable tray tier & any
structural member shall be 200 mm and 300 mm in case of steam or process pipe
lines.
1.16 All structural steel supplied by the contractor and exposed surfaces of embedded steel for
cable tray mountings shall be painted as follows unless otherwise noted:
a) For indoor installations : One shop coat of red oxide zinc chromate
primer (site coat for exposed surfaces of
embedded steel) and two site coats of
aluminium alkyd paint.
b) For outdoor installations : Painting with a two pack epoxy coating.
c) For installations in corrosive : Same as per (b) above.
atmospheres both indoors and
outdoors.
1.17 Where any cuts or holes are made or painted surfaces are damaged or welding is done on
finished steel work, these shall be touched up with paints specified above.

END

REV DT CHDRAFTED
COMPUTER DR
FILE NAME:M2-2007.DOC TATA CONSULTING ENGINEERS TITLE. : CABLE TRAY MOUNTINGS -
HYDERABAD
FP NO : TCE.M2-EL-FP-DWG-003 GENERAL NOTES (SH 2 of 2)
APPROVED. R0 79-04-16
R1 98-
REV DT SR
CH MR
DR
10- K Sd/ SR Sd/PVDM R1
SCALE: NONE
27
DIV. DH-EL
PROJECT. DR. Sd/ SR
CH. Sd/ SR DWG. TCE-M2-EL-CT-S-2007/ R1