- Technical description of HVDC Light® technology


2 ABB
Table of Contents
1. Introduction

2. Applications

3. Features

4. Products

5. Descriptions

6. System engineering

7. References

8. Index

After the huge blackout in August 2003, a federal order allowed the
first use of the Cross Sound Cable HVDC Light® Interconnector.
The cable interconnection made a major contribution to getting
Long Island out of the dark and restoring power to hundreds
of thousands of customers across Long Island. LIPA Chairman
Richard Kessel heralded Cross Sound Cable as a “national
symbol of how we need to enhance our infrastructure”.

ABB 3
Proven technology in new applications

Our need for energy as a naturally integrated part of society is increasing,


and electricity is increasing its share of the total energy used. It is truer than
ever that electricity is a base for building a modern society, but also a princi-
pal tool for increasing well-being in developing countries. As a result, greater
focus is directed at how the electricity is generated and distributed. In addi-
tion, society requests less environmental impact from transmission and gen-
eration along with higher reliability and availability. To combine these goals
there is a need for new technologies for transmitting and distributing electrical
energy.

In this book we present our response to these needs, the HVDC Light® tech-
nique. HVDC Light® makes invisible underground transmission systems tech-
nically and economically viable over long distances. The technology is also
well suited for a number of applications such as power supply to offshore plat-
forms, connecting offshore wind farms, improving grid reliability, city infeed and
powering islands. In these applications, specific characteristics of the technol-
ogy such as compact and light weight design, short installation and commis-
sioning time, low operation and maintenance costs and superior control of volt-
ages, active and reactive power can be utilized.

It is my true belief that the HVDC Light® technique will actively contribute to
the development of transmission systems, in line with the requests given from
our society.

March 2008

Per Haugland
Senior Vice President
Grid Systems

4 ABB
INTRODUCTION

1 Introduction

1.0 Development of 1.1 What is HVDC Light®? HVDC Light® has the capability to
HVDC technology HVDC Light® is the successful and rapidly control both active and reac-
– historical background environmentally-friendly way to tive power independently of each
Direct current was the first type of design a power transmission system other, to keep the voltage and fre-
transmission system used in the very for a submarine cable, an under- quency stable. This gives total flex-
early days of electrical engineer- ground cable, using over head lines ibility regarding the location of the
ing. Even though the AC transmis- or as a back-to-back transmission. converters in the AC system, since
sion system later on came to play a the requirements for the short-circuit
very important role, the development HVDC Light® is HVDC technology capacity of the connected AC net-
of DC transmission has always con- based on voltage source converters work are low (SCR down to zero).
tinued. In the 1930s, the striving for (VSCs). Combined with extruded DC
more and more power again raised cables, overhead lines or back-to- The HVDC Light® design is based
the interest in high voltage DC trans- back, power ratings from a few tenths on a modular concept. For DC volt-
mission as an efficient tool for the of megawatts up to over 1,000 MW ages up to ± 150 kV, most of the
transmission of large power volumes are available. HVDC Light® con- equipment is installed in enclosures
from remote localities. This initiated verters are based on insulated gate at the factory. For the highest DC
the development of mercury arc con- bipolar transistors (IGBTs) and oper- voltages, the equipment is installed
verters, and more than 20 years later, ate with high frequency pulse width in buildings. The required sizes of
in 1954, the world’s first commer- modulation in order to achieve high the site areas for the converter sta-
cial HVDC link based on mercury arc speed and, as a consequence, small tions are also small. All equipment
converters went into service between filters and independent control of except the power transformers is
the Swedish mainland and the island both active and reactive power. indoors.
of Gotland. This was followed by
HVDC Light® cables have extruded Well-proven and equipment tested
many small and larger mercury arc
polymer insulation. Their strength at the factory make installation and
schemes around the world. Around
and flexibility make them well suit- commissioning quick and efficient.
20 years later, in the early 1970s, the
ed for severe installation conditions,
thyristor semiconductor started to
both underground as a land cable
replace the mercury converters.
and as a submarine cable.
ABB has delivered more than 60
The converter station designs are
HVDC projects around the world
based on voltage source converters
providing more than 48,000 MW
employing state-of-the-art turn on/turn
capacity. The largest bipole deliv-
off IGBT power semiconductors.
ered is 3150 MW.


Ê£ 
ÊÓ

Installation of an HVDC Light® station

ABB 5
INTRODUCTION

A pair of HVDC Light® land cables


The stations are designed to be The environmental benefits are:
unmanned. They can be operated - Magnetic fields are eliminated
remotely or could even be automat- since HVDC Light® cables are laid 1.2 Reference projects
ic, based on the needs of the inter- in pairs with DC currents in oppo-
connected AC networks. Mainte- site directions. The magnetic field 1.2.1 Gotland HVDC Light®,
nance requirements are determined from a DC cable is not pulsating Sweden
mainly by conventional equipment but static - just as the earth’s nat-
such as the AC breakers, cooling ural magnetic field. The strength - Client need
system, etc. of the field is 1/10th of the earth’s An environmentally-friendly way of
natural magnetic field one meter connecting wind power to the load
The cable system is supplied com- above the ground immediately centre of the grid and high functional
plete with cables, accessories and above the cable. Thus there are requirements on performance in the
installation services. The cables are no relevant magnetic fields when network.
operated in bipolar mode, one cable using HVDC Light® cables.
with positive polarity and one cable - ABB response
with negative polarity. - Risk of oil spill, as in paper-oil 50 MW / ± 25 MVar HVDC Light®
insulated cables, is eliminated. converters and 140 km (2 x 70 km)
The cables have polymeric insulat- ± 80 kV HVDC Light® land cables.
ing material, which is very strong - The cable insulation is an environ- Project commissioned 1999.
and robust. mentally friendly recyclable
PE based material.
This strength and flexibility make
the HVDC Light® cables perfect for - The cable metals can be recycled.
severe installation conditions:
- The submarine cables can be laid - Low smoke generation and no
in deeper waters and on rough halogen is emitted if burning.
bottoms.
Power transmission via cables gives
- The land cables can be installed - no visual impact
less expensively with the plough-
ing technique. - no ground current

- no relevant electromagnetic fields.

6 ABB
INTRODUCTION

- Summary – Gotland HVDC Light® • Stability in the system. 1.2.2 Directlink, Australia
For the Gotland scheme it was pos-
• Power flows, reactive power - Client need
sible to develop and implement
demands, as well as voltage levels Environmentally-friendly power link
practical operational measures
in the system. To meet the output for power trading between two
thanks mainly to the experienced
power variation from the wind tur- states in Australia.
flexibility of HVDC Light®. Essential
aspects to consider were: bines, an automatic power flow con-
trol system has been developed to - ABB response
• Flicker problems were eliminated minimize the losses and avoid over- 3 x 60 MW HVDC Light® convert-
with the installation of HVDC Light®. load on the AC lines. In normal con- ers and 390 km (6 x 65 km) ± 80kV
Apparently, the transient voltage ditions the overall SCADA system HVDC Light® land cables.
control prevents the AC voltage from determines the set points for active Project commissioned 2000.
locking to the flicker. and reactive power to minimize the
total losses in the whole system. - Summary – Directlink
• Transient phenomena at which This function is important, so that Directlink is a 180 MVA HVDC Light®
faults were dominant. This was the there is no need for the operators to project, consisting of three parallel
most significant problem. be on line and to carry out the con- 60 MVA transmission links that con-
trol manually. nect the regional electricity markets
The parallel connection of HVDC
of New South Wales and Queen-
with the AC grid and the weak grid Overall experiences are that the sland. Directlink is a non-regulated
in one station make the response control of the power flow from the project, operating as a generator
time very important. Even the asyn- converters makes the AC grid easi- by delivering energy to the highest
chronous generator behavior has er to supervise than a conventional value regional market.
an impact during AC faults. It has AC network, and the power varia-
been shown that a standard voltage tions do not stress the AC grid as The Directlink project features three
controller cannot be used to man- much as in normal networks. Volt- innovations which minimize its envi-
age these situations. The parameter age quality has also improved with ronmental, aesthetic and com-
settings have to consider that the the increased wind power produc- mercial impact: the cable is buried
system must not be too fast in nor- tion. Sensitive customers, such as underground for the entire 65 km;
mal operation, and that it has to act big industrial companies, now suffer it is an entrepreneurial project that
rapidly when something happens, less from disturbances due to volt- was paid for by its developers, and
which has been easily accomplished age dips and other voltage quality the flow of energy over HVDC Light®
with HVDC Light®. imperfections. Even if the network facilities can be precisely defined
cannot manage all AC faults, the and controlled. The voltage source
Studies of fault events in the AC
average behavior over a year points converter terminals can act inde-
system have shown considerable
to much better voltage quality. pendently of each other to provide
improvements in behavior both
ancillary services (such as VAR sup-
during the faults and at recovery,
port) in the weak networks to which
including improved stability.
Directlink connects.

Experience with the operation of


Directlink with three parallel links
started in the middle of 2000 and
confirms the expected excellent
behavior of the controllability of the
HVDC Light® station in Näs, Gotland transmission.

ABB 7
INTRODUCTION

1.2.3 Tjæreborg, Denmark - Summary – Tjæreborg system is designed to connect via


HVDC Light® the AC transmission automatically if
- Client need The purpose of the Tjæreborg HVDC the wind power production is below
A small-scale HVDC Light® system project was to investigate how the 500 kW, and via the DC cables if the
to be used for testing optimal trans- controllability of HVDC Light® could power is higher than 700 kW.
mission from wind power generation. be used for optimal exploitation of
the wind energy by using the con- Experience has been gained of the
- ABB response verter to provide a collective variable successful use of HVDC Light® for:
8 MVA HVDC Light® converters and frequency to the wind turbines. The
9 km (2 x 4.5 km) ± 9 kV HVDC Light® • Starting and stopping the wind tur-
Tjæreborg wind farm can either be
land cables. Project commissioned bines at low and high wind speeds.
connected via the AC transmission
2000. only, or via the DC transmission only, • Smooth automatic switching
or via the AC and the DC cables in between the AC and DC transmis-
parallel. The HVDC Light® control sion by automatically synchronizing
the wind turbines to the AC grid.

• Start against black network. This


was tested, as an isolated AC grid,
e.g. an islanded wind farm has to be
energized from the DC transmission.

• With a connected wind turbine


generator, the frequency was varied
between 46 and 50 Hz. A separate
test without connected wind tur-
bines demonstrated that the HVDC
Light® inverter frequency could be
varied between 30 Hz and 65 Hz
without any problems.

The Tjæreborg HVDC Light® station

Directlink HVDC Light® station 3 x 60 MW

8 ABB
INTRODUCTION

1.2.4 Eagle Pass, US 1.2.5 Cross Sound Cable, US Testing of the Cross Sound Cable
project was completed in August
- Client need - Client need
2002. The big blackout in the north-
Stabilization of AC voltage and pos- Environmentally-friendly controllable
eastern states happened on August
sibility to import power from Mexico power transmission to Long Island.
14 2003, and the Cross Sound
during emergencies.
transmission became an important
- ABB response
power supply route to Long Island
- ABB response 330 MW MW HVDC Light® convert-
when restoring the network during
36 MVA HVDC Light® back-to-back ers and 84 km (2 x 42 km) ±150 kV
the blackout.
converters. Project commissioned HVDC Light® submarine cables.
2000. Project commissioned 2002. Some hours after the blackout, a
federal order was given to start
- Summary – Eagle Pass The two HVDC Light® power cables
emergency operation. In addition to
HVDC Light® back-to-back was and the multi-fiber optic cable were
providing power to Long Island, the
chosen since other alternatives laid bundled together to minimize
AC voltage control provided by the
would have been more expensive, the impact on the sea bottom and to
link of both the Long Island and the
and building a new AC line would protect oysters, scallops and other
Connecticut networks showed that
have faced the added impediment living species. The cables were bur-
it could keep the AC voltages con-
of having to overcome difficulties ied six feet into the sea floor to give
stant. During the thunderstorms that
in acquiring the necessary rights protection against fishing gear and
occurred before the networks were
of way. Furthermore, if an HVDC ships’ anchors. The submarine Fiber
completely restored, several +100
back-to-back based on convention- Optic cable is furnished with 192
to –70 Mvar swings were noticed
al technology had been considered, fibers.
over 20 seconds. AC voltage was
there were concerns that such a kept constant. The transmission
solution might not provide the nec- - Summary – Cross Sound Cable
remained in emergency operation
essary level of reliability because of The Cross Sound Cable project is
during the fall of 2003. The owner
the weakness of the AC system on a 42 km HVDC Light® transmission
has concluded that the cable inter-
the U.S. side of the border. between New Haven, Connecti-
connection made a major contribu-
cut and Shoreham on Long Island
tion to getting Long Island out of the
To mitigate possible voltage instabil- outside New York. It provides the
dark and restoring power to hun-
ity and, at the same time, to allow transmission of electric energy to
dreds of thousands of customers
power exchange in either direction Long Island. The rating is 330 MW
across Long Island.
between the U.S. and Mexico with- with the possibility of both local and
out first having to disrupt service to remote control.
distribution system customers, an
HVDC Light® back-to-back rated at
36 MVA at 138 kV was installed and
commissioned.

HVDC Light® station at Shoreham

Steady-State 100 MW CT —> LI


during thunderstorm. ACVC APC SHM.
Measurement in Shoreham Converter
Station (DASH-18) Sunday 17 August
2003 – 18:48:00.000

ABB 9
INTRODUCTION

1.2.6 MurrayLink, Australia voltage source converter terminals


can act independently of each other
- Client need
to provide ancillary services (such as
Environmentally-friendly power link
var support and voltage control) in
for power trading between two
the weak networks to which it is con-
states in Australia.
nected. Operating experience is that
its AC voltage control considerably
- ABB response
improves voltage stability and power
200 MW HVDC Light® converters
quality in the connected networks. In
and 360 km (2 x 180 km) ±150 kV
addition, shunt reactors in neighbor- Cable transport for MurrayLink project
HVDC Light® land cables. Project
ing networks can normally be dis-
commissioned 2002.
connected when the link’s AC volt-
age control is on.
- Summary – MurrayLink
MurrayLink is a 180 km under- On the loss of an AC line, there is a
ground 200 MW transmission sys- run-back from 200 MW to zero.
tem between Red Cliffs, Victoria and
Berry, South Australia. It links regional The project has won the Case
electricity markets and uses the abili- EARTH Award for Environmental
ty of HVDC Light® technology to con- Excellence.
trol power flow over the facility. The

Cable laying for MurrayLink project

10 ABB
INTRODUCTION

1.2.7 Troll A, Norway ±60 kV, and converters for two always maintained. There is no tele-
identical transmissions have been communication for control between
- Client need
installed and tested. On the Troll A the rectifier control on land and the
Environmentally-friendly elec-
platform, the HVDC Light® transmis- inverter motor control on the plat-
tric power to feed compressors to
sion system will directly feed a high- form - the only quantity that can be
increase the natural gas production
voltage variable-speed synchronous detected at both ends of the trans-
of the platform, combined with little
machine designed for compressor mission is the DC-link voltage.
need of manpower for operation.
drive with variable frequency and
variable voltage, from zero to max However, the control system has
- ABB response been designed so that, together with
speed (0-63 Hz) and from zero to
2 x 40 MW HVDC Light® convert- a telecommunication link, it could
max voltage (0-56 kV).
ers and 272 km (4 x 68 km) ±60 provide for land-based operation,
kV HVDC Light® submarine cables. The inverter control software has faultfinding and maintenance of the
Project commissioned 2005. been adapted to perform motor platform station.
speed and torque control. The con-
- Summary – Troll A trol hardware is identical for rectifier
With the Troll A pre-compression and motor converters.
project, HVDC transmission con-
verters are, for the first time, being Over the entire motor operating
installed offshore on a platform. The range, unity power factor and low
transmission design for this first harmonics are assured, while suf-
implementation is for 40 MW, ficiently high dynamic response is

ABB 11
INTRODUCTION

1.2.8 Estlink HVDC Light® link, - Summary – Estlink the Estonian side i.e. the converter
Estonia - Finland Estlink is a 350 MW, 31 km under- is automatically switched to house-
ground/ 74 km submarine cable hold operation if the AC grid is lost
- Client need transmission between the Harku making a fast energization of the
Improved security of the electricity substation in Estonia and Espoo network possible after a blackout
supply in the Baltic States and Finland. substation in Finland. It links the in the Estonian network. The imple-
Baltic power system to the Nord- mentation phase of the project was
Reduced dependence of the Bal-
pool market and uses the ability of 19 months, and the link has been in
tic power systems and an alterna-
HVDC Light® technology to control operation since the end of 2006.
tive electricity purchase channel to
the power flow over the facility. The
cover potential deficits in generating
voltage source converter terminals
capacity.
can act independently of each other
to provide ancillary services (such
- ABB response
as var support and voltage control),
350 MW HVDC Light® converters and
thereby improving the voltage stabil-
210 km (2 x 105 km) ± 150 kV HVDC
ity of the Estonian grid. The black-
Light®‚ submarine/land cables. Proj-
start capability is implemented at
ect commissioned 2006.

The HVDC Light® station at Harku on the Estonian side of the link.

12 ABB
INTRODUCTION

1.2.9 Valhall Re-development - Summary - Valhall These factors contribute to the cus-
Project Re-development project tomer BP’s vision of a safe, intelligent,
As a part of the redevelopment of the maintenance-free and remotely con-
- Client need Valhall field in the Norwegian sector, trollable field of the future. In addition,
Supply of electric power from shore, ABB will provide the converter sta- the HVDC Light® system will provide
to replace existing gas turbines tions to enable 78 MW to be supplied a very high quality electric supply
offshore and feed the entire exist- over a distance of almost 300 km from with respect to voltage and frequen-
ing field, as well as a new platform. shore to run the entire field facilities, cy, including during direct online
The important issues are to minimize including a new production and living start-up of the large gas compressor
emissions of CO2 and other climate quarters platform. motors, thereby eliminating the need
gases and, at the same time, to for additional soft start equipment.
reduce the operating and mainte- The main factors behind the decision
nance costs of electricity offshore. to choose power from shore were: The onshore station will be located
- reduced costs at Lista on Norway’s southern coast.
- ABB response Here the alternating current will be
- improved operational efficiency taken from the Norwegian grid at
HVDC Light® converter stations
onshore and offshore rated 78 MW 300 kV and converted to direct cur-
- minimized greenhouse gas emissions
at 150 kV. The project will be com- rent. This will be transmitted at 150 kV
missioned 2009. - improvement of all HSE elements over a distance of 292 km via a sin-
gle power cable with an integrated
metallic return conductor to the new
Valhall platform. There it will be con-
verted back to AC power at 11 kV
in the HVDC module and distributed to
all the platforms in the Valhall field.

Valhall Power from shore project

Offshore Station, Valhall

ABB 13
INTRODUCTION

1.2.10 NordE.ON 1 offshore Independent control of active and utilizing an HVDC Light® intercon-
wind connection - Germany reactive power flow with total control nection of two weak AC networks
of power from zero to full power with- through a 970 km long ±350 kV
- Client need
out filter switching enables smooth overhead line.
A 200 km long submarine/land cable
and reliable operation of the offshore
connection from an offshore wind park In addition:
wind farm.
to be operational within 24 months. - Accurate AC voltage control of
A proven extruded cable technology the weak interconnected AC
- ABB response is used that simplifies installation on networks.
400 MW HVDC Light® converters, land and at sea allowing very short
one offshore on a platform and one - Feed of a passive AC network in
time for cable jointing. The oil-free
land-based and 400 km (2 x 200 the Caprivi strip.
HVDC Light® cables minimize the
km) ±150 kV HVDC Light® subma- environmental impact at sea and on
rine/land cables. The project will be land. - ABB response
commissioned 2009. HVDC Light® converter stations
In operation, the wind power project designed for a DC voltage of
- Summary - NordE.ON 1 offshore will reduce CO2 emissions by nearly ±350 kV to ground, to be built
wind connection 1.5 million tons per year by replacing in two stages:
The NordE.ON 1 offshore wind farm fossil-fuel generation.
cluster will be connected to the Ger- - first stage: a monopole 300 MW
man grid by a 400 MW HVDC Light® The transmission system supports (-350 kV to ground)
transmission system, comprising 75 wind power development in Germany.
- second stage: an upgrade to
km underground and 128 km subma-
2 x 300 MW bipole (±350 kV).
rine cable. Full Grid Code compliance 1.2.11 Caprivi Link
ensures a robust network connection. Interconnector The monopole will be put into oper-
ation at the end of year 2009. Elec-
For both the offshore and the onshore - Client need trode stations about 25 km from the
part, most equipment will be installed Import of hydro power and coal- converter stations.
indoors, thus ensuring safe operation fired power from Zambia to ensure
and minimal environmental impact. a secure power supply in Namibia - Summary – Caprivi Link
Interconnector
The Caprivi Link Interconnector will
be a 2 x 300 MW interconnection
between the Zambezi converter sta-
tion in the Caprivi strip in Namib-
ia, close to the border of Zambia,
and the Gerus converter station,
about 300 km North of Windhoek
in Namibia. The AC voltages are
320 kV and 400 kV at Zambezi and
Gerus respectively.

The converter stations will be inter-


connected by a 970 km long, bipo-
lar ±350 kV DC overhead line. The
conductors of both the negative
and positive polarity will be mount-
ed on the same poles. There will be
double-circuit electrode lines with a
length of about 25 km.

The NordE.ON 1 offshore wind connection

14 ABB
INTRODUCTION

In the monopole stage, the link will The condition for the upgrade to a In the event of outage of the con-
be operated with parallel DC lines 2 x 300 MW bipole is that the AC necting AC lines to Zambezi during
and earth return to reduce line loss- networks at Zambezi and Gerus are power import to Namibia, the power
es. In the bipole stage, the link will reinforced, including a new connec- transmission can be reversed rapidly
be operated as a balanced bipole tion to the Hwange coal fired power in order to re-energize and feed the
with zero ground current. station in Zimbabwe. black AC network at Zambezi.

The AC networks of today are The Zambezi and Gerus converter The client evaluated possible trans-
extremely weak at both ends, with stations will control the AC voltages mission alternatives and found that
short-circuit power levels of around in the surrounding grids rapidly and the HVDC Light® technology is the
300 MVA and long AC lines which accurately over the entire range of most feasible economically and
connect to remote generator sta- active power capability, by a continu- technically solution.
tions. Due to this fact, the AC net- ous adjustment of the reactive power
works are also exposed to a risk of absorption and generation between
50 Hz resonance. ABB has studied - 130 Mvar and + 130 Mvar.
the crucial AC and DC fault cases
and verified that the dynamic perfor-
mance of the HVDC Light® is in line
with the requirements of the client.

The Caprivi Link


Interconnector

Station Layout, Caprivi Link Interconnector

ABB 15
APPLICATIONS

2 Applications

2.1 General 2.2 Cable transmission systems - from the shore to the platform
A power system depends on stable
- from platform to shore
and reliable control of active and 2.2.1 Submarine cables
reactive power to keep its integ- - between platforms
- Power supply to islands
rity. Losing this control may lead to
The power supply to small islands
a system collapse. Voltage source The most important and desirable
is often provided by expensive local
converter (VSC) transmission sys- characteristics for offshore platform
generation, e.g. diesel generation.
tem technology, such as HVDC installations are the low weight and
By installing an HVDC Light® trans-
Light®, has the advantage of being volume of the HVDC Light® converter.
mission system, electricity from the
able almost instantly to change its Offshore, the converter is located
mainland grid can be imported.
working point within its capability, inside a module with a controlled
Another issue is the environmen-
and to control active and reactive environment, which makes it pos-
tal benefits to the island by reducing
power independently. This can be sible to design the converter even
emission from local generation.
used to support the grid with the smaller for an offshore installation
best mixture of active and reactive Since HVDC Light® is based on VSC than for a normal onshore converter
power during stressed conditions. technology, the converter can oper- station.
In many cases, a mix of active and ate without any other voltage source
reactive power is the best solu- on the island, i.e. no local generation
2.2.2 Underground cables
tion compared with active or reac- on the island is needed for proper
tive power only. VSC transmission operation of the system. - Interconnections
systems can therefore give added The environmental advantages of
support to the grid. - Remote small-scale generation HVDC Light® are of high value when
connecting two power systems. This
As an example, simulations done at Remote small-scale generating facili-
refers to the possibilities for control-
ABB have shown that, for a paral- ties are very often located on islands
ling the transmitted power to the
lel case (AC line and DC transmis- that will not need all the generated
desired value, as well as improving
sion), where the VSC transmission power in all situations. This power
AC network stability by providing and
system is connected in parallel with can then be transmitted by HVDC
controlling reactive power and volt-
an AC system, the VSC transmis- Light® to a consumer area on the
age support in the connected net-
sion system can damp oscillations mainland or an adjacent island.
works. Other important factors are:
2-3 times better than reactive shunt
- Interconnecting power systems avoiding loop flows, sharing of spin-
compensation.
ning reserve, emergency power etc.
The advantages of HVDC Light®
The benefits with a VSC transmis- The rapid AC voltage control by
are of high value when connecting
sion system during a grid restora- HVDC Light® converters can also be
between individual power systems,
tion can be considerable, since it used to operate the connected AC
especially when they are asynchro-
can control voltage and stabilize fre- networks close to their maximum
nous. This refers to the possibilities
quency when active power is avail- permitted AC voltage and in this way
for controlling the transmitted power
able at the remote end. The fre- to reduce the line losses in the con-
to an undertaken value, as well as
quency control is then not limited nected AC networks.
being able to provide and control
in the same way as a conventional
reactive power and voltage in both
power plant where boiler dynamics
the connected networks.
may limit the operation during grid
restoration. - Power to/from/between Offshore
platforms
With the above benefits, HVDC
Light® is the preferred system to With its small footprint and its possi-
be used for a variety of transmis- bilities to operate at low short-circuit
sion applications, using submarine power levels or even to operate with
cables, land cables and back-to- a “black” network, HVDC Light® has
back. made it possible to bring electricity:

16 ABB
APPLICATIONS

- Bottlenecks 2.4.1 Asynchronous Connection This is contrary to conventional AC


In addition to the power transmitted by If the AC network is divided into dif- transmission systems, which normally
the HVDC Light® system, an HVDC ferent asynchronous areas, connec- require a high SCR compared with
Light® transmission in parallel with tion between the areas can easily the power to be entered. With the
an existing AC line will increase the be done with HVDC back-to-back imminent arrival of wind power farms
transmitting capacity of the AC line converters. This gives a number of and accounting for a considerable
by the inherent voltage support and advantages: share of the total power generation
power stabilizing capability of the - Sharing of spinning reserve. in a network, wind power farms will
HVDC Light® system. have to be as robust as conventional
- Emergency power exchange power plants and stay online during
- Infeed to cities between the networks various contingencies in the AC net-
Adding new transmission capacity work. Various types of compensa-
- Better utilization of installed gen-
via AC lines into city centers is cost- tion will then be needed to preserve
eration in both networks
ly and in many cases the permits power quality and/or even the stabil-
for new right-of-ways are difficult to - Voltage support ity of the network.
obtain. An HVDC Light® cable needs
less space than an AC overhead line - etc. HVDC Light® does not require any
and can carry more power than an additional compensation, as this
AC cable, and therefore it is often In many cases, the connection is inherent in the converters. It will
the only practical solution, should between two asynchronous areas therefore be an excellent tool for
the city center need more power. is made at a weak connection point bringing wind power into a network
Also, the small footprint of the HVDC in AC systems on the borders of
Light® converter is of importance for the areas. With its possibilities of 2.6 Comparison of AC, conven-
realizing city infeed. Another bene- operating at low short-circuit ratios, tional HVDC and HVDC Light®
fit of HVDC Light® is that it does not HVDC Light® is very suitable for this
type of connection. - Comparison of DC cable system
increase the short-circuit current in and AC cable system
the connected AC networks.
DC cable system
2.4.2 Connection of important - No limit on cable length
2.3 DC OH lines loads
HVDC Light® converters can oper- - No intermediate station needed
For sensitive loads, an HVDC Light®
ate in combination with DC over- back-to-back system is of impor- - No increase of capacitance in the
head lines forming a proper trans- tance for keeping the AC voltage AC network (avoids low-order res-
mission system. An example of this and AC frequency on proper levels if onances)
is the Caprivi Link Interconnector in the quality of those properties of the
Namibia. connected AC network is not suf- - Lower losses
ficient for the connected load. The
- see 1.2.11
fast reactive power control proper- AC cable system
ties of HVDC Light® can be used for - Cable capacitance limits the prac-
2.4 Back-to-back flicker mitigation. tical cable length
A back-to-back station consists of
two HVDC Light® converters located - Reactive compensation is needed
2.5 HVDC Light® and wind
close to each other, i.e. with no DC power generation
cables in between.
HVDC Light® is a transmission sys-
tem which has characteristics suit-
able for connecting large amounts
of wind power to networks, even at
weak points in a network, and with-
out having to improve the short-cir-
cuit ratio.

ABB 17
APPLICATIONS

Comparison of HVDC Light® and conventional HVDC

- HVDC Light®, power from IGBT used as active component The pulse width controls both
50 – 1100 MW in valves active and reactive power

- The IGBT can be switched off with


a control signal. Fully controllable.

- Each terminal is an HVDC = forced commutation up to 2000 Hz


converter plus an SVC

- Suitable both for submarine and


land cable connections - Multi-chip design

- Advanced system features - Forward blocking only

- Footprint (e.g. 550 MW): - Current limiting characteristics


120 x 50 x 11 meters
- Gate turn-off and fully controllable;
- Short delivery time forced commutation

- High-speed device

- Conventional HVDC, power up Thyristor used as active Phase angle control


to 6400 MW component in valves

Pmax Pmin

- The thyristor cannot be switched


off with a control signal.

- Most economical way to transmit - It automatically ceases to conduct


power over long distances. when the voltage reverses.

- Long submarine cable = line commutated, 50/60 Hz


- Single silicon wafer
connections.
- Both forward and reverse blocking
- Around three times more power in
capability
a right-of-way than overhead AC
- Very high surge current capability
- Footprint (e.g. 600 MW):
200 x 120 x 22 meters - No gate turn-off; line commutated

18 ABB
APPLICATIONS

"1, ,ʙÇÊ*ÓÎÊ,
1-Ê 9  Ê*, -°
,
{nä°äää

ÎÈä°äää

Ó{ä°äää

£Óä°äää

ä°äää

‡£Óä°äää
£ää°äää“ £Óä°äää“ £Èä°äää“ Óää°äää“
Û­Vœ˜Û£® /
{nä°äää

ÎÈä°äää

Ó{ä°äää

£Óä°äää

ä°äää

‡£Óä°äää
£ää°äää“ £Óä°äää“ £Èä°äää“ Óää°äää“
Û­,Ι® /
{ää°äää

Îää°äää

Óää°äää

£ää°äää

ä°äää
£ää°äää“ £Óä°äää“ £Èä°äää“ Óää°äää“
Û­`V£®‡Û­`VÓ® /

- Upper trace: Reactor voltage

- Middle trace: Valve voltage


HVDC Light® deep sea cables
- Lower trace: DC Voltage

600.00K CLASSIC CONVERTER 03 .CIR

0.00K

-400.00K
0.00m 80.00m 100.00m
v(trafo1)-v(neutral) T
800.00K

0.00K

-200.00K
0.00m 80.00m 100.00m
-v(R11) T
675.00K

0.00K
0.00m 80.00m 100.00m
v(dc1)-v(dc2) T

- Upper trace: Transformer voltage

- Middle trace: Valve voltage Mass impregnated HVDC cable

- Lower trace: DC voltage

ABB 19
APPLICATIONS

- Simplified single-line diagram for HVDC Light®

6>Ûi
 /ÊEÊ`ˆœ`i

*…>Ãi
/À>˜ÃvœÀ“iÀ Ài>V̜À

DC capacitor

>À“œ˜ˆVÊvˆÌiÀ

- Simplified single-line diagram for conventional HVDC

20 ABB
APPLICATIONS

- An HVDC Light® can control both active and reactive power 2.7 Summary of drivers for
choosing an HVDC Light®
*‡+Ê ˆ>}À>“Ê­Ü…œiÊۜÌ>}iÊÀ>˜}i®
£°Óx £°Óx application

£
2.7.1 AC Network Support
ä°Çx
Operating area - Active and reactive power inde-
Ê
®

pendently and rapidly controlled


°

ä°x
1
°

- Operation down to short-circuit


*

ä°Óx
­

Ê
ratios of zero
À
Ü i

*­ F®

£°Óx £ ä°Çx ä°x ä°Óx ä ä°Óx ä°x ä°Çx £ £°Óx


- Loop flows of power are avoided
œ
*

ä°Óx
i

- Black start is possible


Û
ˆ

ä°x
Ì
V

- Stabilization of connected AC grids




ä°Çx

£
- Sharing spinning reserve between
areas
• £°Óx
£°Óx

• £°Óx + ­ F® £°Óx - Continuously variable power from


,i>V̈ÛiÊ*œÜiÀÊ­*°1°®
full power in one direction to full
Y-axis : active power
power in reverse

- Emergency power support


- Reactive power exchange for conventional HVDC
- Increase power in parallel AC lines

- No commutation failures

- Multi-terminal system simple

- No minimum power - can operate


down to zero power

-…Õ˜Ì - Additional reactive shunt compen-


L> ˜ŽÃ sation is not required. (Only small
harmonic filters are needed.)
> À“ œ˜ˆ V
vˆÌiÀà - Only conventional AC transformers
are required

- The HVDC Light® control can be


designed so that the HVDC Light®
stations can eliminate flicker and
selected harmonics in the AC grid.
Q
+

- The HVDC Light® stations can be


operated as STATCOMs, even if
the HVDC Light® Station is not
connected to the DC line (staged
O,
ä] implementation: build one or two
£
Î stations for voltage stabilization
1, P
£]Ê*
– connect them later with cables
Unbalance
1 ˜ L> >˜ Vi

and you have an interconnection).

ABB 21
APPLICATIONS

2.7.2 Undergrounding by cables 2.8 HVDC Light® cables The following example shows the
- No visible impact of overhead lines difference:
– underground cables instead 2.8.1 Long lifetime with HVDC
Transmission of 550 MW by subma-
The inherent lifetime of insulating rine cables for a distance of 75 km:
- Easier to get permission
materials is better for HVDC than
- No relevant electromagnetic fields for AC. HVDC cable:

- No audible noise, unlike OH lines 150 kV HVDC Light® cables, 2


2.8.2 Submarine cables cables with copper conductor
cross-section of 1400 mm2 and
- Low losses
2.7.3 Required site area for steel wire tensile armor. The weight
HVDC cables are generally much
converters of the two cables is 2 x 32 kg/m =
more efficient for long-distance
- Less space per MW required than 64 kg/m.
transmissions than AC cables, in
for conventional HVDC
particular for high powers. AC cable:
- Indoor design - reduced risk of
The reason is that AC cables must 220 kV XLPE cable, 3 cables with
flashover
be rated for the capacitive charg- copper conductor cross-section
- Small space requirement and low ing current, in addition to the trans- of 1600 mm2 and copper wire ten-
weight are very important for off- mitted active current. The capacitive sile armor. The weight of the three
shore applications charging current is proportional to cables is 3 x 60 kg/m = 180 kg/m.
the length and the voltage of the AC
cable and beyond a certain distance
2.7.4 Environmentally sound there is no capacity left for the active
- Deep sea waters
- Audible sound reduced by indoor power transmission. DC cables have
HVDC Light® cables are suitable for
design no capacitive charging current, i.e.
large water depths, for the following
all the transmission capacity of the
reasons:
- Stations look like any ordinary cable is available for active power
industrial building, no outdoor transmission. The capacitive reactive - The polymeric insulation is
switchyards power generated by long AC cables mechanically robust.
must be taken care of.
- Low building height - The HVDC cables are general-
To avoid ferromagnetic losses AC ly less heavy than AC cables for
- Bipolar operation – no need for submarine cables need non-mag- the same transferred power. This
electrodes netic material for the wire armor, gives lower tensile force during
thus copper or aluminum alloy or laying of the cables.
2.7.5 Energy trading non-magnetic stainless steel wires
are used. - It is advantageous to use galva-
- Fast and accurate power control –
nized steel wires for tensile armor.
you get the power you want For DC cables, there are no mag- A galvanized steel wire has bet-
netic losses, hence galvanized steel ter tensile properties than most
- No filter switching at power change
wires, can be used for the tensile non-magnetic materials that can
- Smooth power reversal (step less armor. be used.
power transfer around zero MW)

22 ABB
APPLICATIONS

- Laying and repair


HVDC Light® cables are very flexible
with respect to various installation
methods, due to their robust and
flexible insulation material. Should a
repair be required, the availability of
>Liʈ˜ÃÌ>>̈œ˜ÊÛiÃÃi
suitable cable ships is thus good.

- The cable can be coiled on a


cable laying ship (except for
>Li
cables with double cross laid
>LiÊÌÀi˜V…iÀ
armor for large depths). The pos-
sibility of coiling the cables makes
it possible to lay the cable from
small barges and transport the
cable by cargo ships without turn-
tables for the cables.
Typical laying and trenching operation
- It is possible in most cases to lay
the two cables of the bipole close
to each other (e.g. by bundling of
the cables) in one common trench.

- The bending radius of the poly-


meric insulated HVDC Light® cable
is smaller compared with paper-
insulated cables, which makes it
possible to use laying ships with
a smaller pay-off wheel, and also
smaller trenching equipment.

- Good resistance when installed


Particularly when comparing with
paper-oil insulated cables, the HVDC
Light® cables can resist repeat-
ed bending without fatigue of the
insulation. This is critical for cables
hanging in spans over an uneven
sea bed.

Coiled cable on small cable laying barge

ABB 23
APPLICATIONS

2.8.3 Underground Cables - Minimum bending radius for - No magnetic fields of power fre-
standard designs quency
- Permitting During installation, the bending radius There is no power frequency mag-
In many cases it is easier to get should exceed 18 x De. netic field from a DC cable; there is
right of way for underground cables, only a static magnetic field, similar to
compared with overhead transmis- When the cable is installed (no force the earth’s magnetic field.
sion lines. The main reasons are: applied to the cable), the bending
radius must exceed 12 x De. Recommended levels of static mag-
- Less visual impact netic field strength are significant-
De is the external diameter of the cable. ly higher than for power frequency
- Smaller width of the required right
fields (from AC power lines), since
of way. - Maximum pulling forces for land there is no induction effect, and the
cables
magnetic fields are similar to that of
- Handling When the pulling nose is attached to
the earth itself.
HVDC Light® cables have many the conductor, the following tensile
advantages compared with other forces should not be exceeded: A conventional mono-polar HVDC
cable types, e.g.: cable scheme with a current of 1000
- 70 N/mm2 for Cu conductors
amps gives a magnetic field of 20
- HVDC Light cables have small-
®

- 40 N/mm2 for Al conductors micro-Tesla magnitude at a distance


er bending radius compared
of 10 meters. This is approximately
with paper insulated cables. This
- Jointing half the magnitude of the earth’s nat-
makes it possible to use smaller
HVDC Light® cable joints are usu- ural magnetic field. With HVDC Light®
cable drums for transportation,
ally installed inside a portable jointing Cables, the magnetic field is reduced
and makes it possible to use com-
house, which is placed in the joint to less than 0.2 micro-Tesla, which
pact installation, e.g. on offshore
bay. This pre-built jointing house is less than 1% of the natural mag-
platforms. The smaller bending
provides adequate light, dust con- netism.
radius also makes it possible to go
around obstacles such as rocks, trol, clean work surfaces and cable
etc. stands to place the joint within com-
fortable reach of the cable jointers.
- HVDC Light® cables are possible A crew of two cable jointers usual-
to handle at lower temperatures ly works together as a team. A joint
compared with paper insulated crew can complete one of these
cables. joints in one working day.

Jointing container, placed over the


cables during jointing at MurrayLink.

24 ABB
FEATURES

3 Features

3.1 Independent power transfer 3.2 Absolute and predictable 3.4 Power reversal
and power quality control power transfer and voltage control The HVDC Light® transmission sys-
The HVDC Light® system allows The active power flow can be deter- tem can transmit active power in
fully independent control of both mined either by means of an active any of the two directions with the
the active and the reactive power power order or by means of fre- same control setup and with the
flow within the operating range of quency control. same main circuit configuration. This
the HVDC Light® system. The active means that an active power trans-
power can be continuously con- The converter stations can be set to fer can be quickly reversed without
trolled from full power export to full generate reactive power through a any change of control mode, and
power import. Normally each sta- reactive power order, or to maintain without any filter switching or con-
tion controls its reactive power flow a desired voltage level in the con- verter blocking. The power reversal
independently of the other station. nected AC network. is obtained by changing the direc-
However, the flow of active power tion of the DC current and not by
The converter’s internal control loop
to the DC network must be bal- changing the polarity of the DC volt-
is active and reactive current, con-
anced, which means that the active age as for conventional HVDC. The
trolled through measurement of the
power leaving the DC network must speed of the reversal is determined
current in the converter inductor and
be equal to the active power com- by the network. The converter could
using orders from settings of active
ing into the DC network, minus the reverse to full power in milliseconds
and reactive power which an opera-
losses in the HVDC Light® system. A if needed.
tor can make.
difference in power would imply that
the DC voltage in the system would The reactive power controller oper-
In an AC network, the voltage at
rapidly increase or decrease, as the ates simultaneously and indepen-
a certain point can be increased/
DC capacitor increases its voltage dently in order to keep the ordered
reduced through the generation/
with increased charge. In a normal reactive power exchange unaffected
consumption of reactive power. This
design, the stored energy is equiv- during the power reversal.
means that HVDC Light® can con-
alent to around 2 ms power trans- trol the AC voltage independently in
mission on the system. To attain this each station. 3.5 Reduced power losses in
power balance, one of the stations connected AC systems
controls the DC voltage. 3.3 Low power operation By controlling the grid voltage level,
HVDC Light® can reduce losses in
This means that the other station Unlike conventional HVDC convert-
the connected grid. Both transmis-
can arbitrarily adjust the transmit- ers, the HVDC Light® converter can
sion line ohmic losses and genera-
ted power within the power capabil- operate at very low power, and even
tor magnetization losses can be
ity limits of the HVDC Light® system, at zero power. The active and reac-
reduced. Significant loss reductions
whereby the station that controls tive powers are controlled indepen-
can be obtained in each of the con-
the DC voltage will adjust its power dently, and at zero active power the
nected networks.
to ensure that the balance (i.e. con- full range of reactive power can be
stant DC voltage) is maintained. The utilized.
3.6 Increased transfer capacity
balance is attained without telecom-
in the existing system
munication between the stations,
quite simply based on measurement - Voltage increase
of the DC voltage. The rapid and accurate voltage con-
trol capability of the HVDC Light®
converter makes it possible to oper-
ate the grid closer to the upper limit.
Transient overvoltages would be
counteracted by the rapid reactive
power response. The higher volt-
age level would allow more power to
be transferred through the AC lines
without exceeding the current limits.

ABB 25
FEATURES

- Stability margins HVDC Light® is able to do this in a 3.9 Islanded operation


Limiting factors for power trans- number of ways: The HVDC Light® converter sta-
fer in the transmission grid also tion normally follows the AC voltage
include voltage stability. If such grid - by modulating the active power
of the connected grid. The voltage
conditions occur where the grid is flow and keeping the voltage as
magnitude and frequency are deter-
exposed to an imminent voltage col- stable as possible
mined by the control systems of the
lapse, HVDC Light® can support generating stations. In the event of a
- by keeping the active power con-
the grid with the necessary reactive voltage collapse, a “black-out”, the
stant and modulating the reactive
power. The grid operator can allow HVDC Light® converter can instanta-
power to achieve damping (SVC-
a higher transmission in the grid if neously switch over to its own inter-
type damping)
the amount of reactive power sup- nal voltage and frequency reference
port that the HVDC Light® converter Line current, power flow or local fre- and disconnect itself from the grid.
can provide is known. The transfer quency may be used as indicators, The converter can then operate as
increase in the grid is larger than the but direct measurement of the volt- an idling “static” generator, ready
installed MVA capacity of the HVDC age angle by means of Phasor Mea- to be connected to a “black” net-
Light® converter. surement Units can also be a solu- work to provide the first electricity to
tion to achieve observability. important loads. The only precondi-
3.7 Powerful damping control tion is that the converter at the other
using P and Q simultaneously 3.8 Fast restoration after end of the DC cable is unaffected by
As well as voltage stability, rotor blackouts the black-out.
angle stability is a limiting factor for HVDC Light® can aid grid restora-
power transfer in a transmission tion in a very favorable way. Volt- 3.10 Flexibility in design
grid. HVDC Light® is a powerful tool age support and frequency support The HVDC Light® station consists of
for damping angle (electro-mechan- are much needed during such con- four parts:
ical) oscillation. The electromechani- ditions. This was proven in August
cal oscillations can be rather com- 2003, when the north-east USA - The DC yard, with DC filtering and
plex with many modes and many experienced a blackout, by the switches
constituent parts. It is therefore excellent performance of the Cross
- The converter, with the IGBT
not always possible to find robust Sound Cable Project that inter-
valves and the converter reactors
damping algorithms that do not connects Connecticut and Long
excite other modes when damping Island. A black-start capability can - The AC filter yard
the first ones. Many control meth- be implemented. It can be benefi-
ods that influence the transmission cial for an HVDC Light® operator to - The grid interface, with power
capacity can experience difficulties speed up grid restoration because transformer and switches
in these complex situations. Mod- the lack of energy (typically the first
ulating shaft power to generators, The different parts are interconnect-
6-24 hours) may initiate considerably
switching on and off load demand ed with HV cables, which make it
higher prices for energy. The black-
or using an HVDC Light® connected easy to separate the parts physically,
start facility is implemented on the
to an asynchronous grid are meth- so as to fit them into available sites.
Estonian side of the Estlink HVDC
ods that can then be considered. Light® Project.
These methods have the advantage
that they actually take away or inject
energy to damp the oscillations.

26 ABB
FEATURES

3.11 Undergrounding quencies might cause radio interfer- 3.14 Indoor design
Except for back-to-back, HVDC ence if not properly controlled and To avoid tall steel supporting struc-
Light® always employs HV cables for shielded. Considering these condi- tures, to facilitate maintenance and
DC power transmission. The cables tions, the overall and detailed design to improve personal safety, the AC
are buried all the way into the DC has been aimed at ensuring prop- filters, converter reactors and DC
part of each converter building. When er mitigation of radio interference filters are mounted directly on low
the landscape has been restored and corresponding fields. The elec- foundations/supports and are kept
after the cable laying, the transmis- tromagnetic field levels around the within a simple warehouse-style
sion route quickly becomes invisible. installation are therefore well below building with lockable gates and
the values stipulated in the relevant doors. The building will keep high-
standards for human exposure. frequency emissions and acoustic
3.12 No relevant magnetic fields
noise low and protect the equipment
The two HVDC Light® cables can The performance is verified through
from adverse weather.
normally be laid close together. As measurements.
they carry the same current in oppo-
site directions, the magnetic fields The HVDC Light® converter installa- 3.15 Short time schedule
from the cables more or less cancel tion is connected to the AC power The converter valves and associ-
each other out. The residual mag- grid/system through AC overhead ated control and cooling systems
netic field is extremely low, compa- lines or AC cables. Effective filter- are factory-assembled in transport-
rable to the level of the earth’s mag- ing prevents current harmonics from able enclosures. This ensures rapid
netic field. loading into the connected AC lines/ installation and on-site testing of the
cables. This means that they can core systems.
Magnetic fields from DC cables are be considered as normal AC lines/
static fields, which do not cause any cables installed within the power The building is made up of stan-
induction effects, as opposed to the grid/system. dardized parts, which are shipped to
fields from AC cables and lines. the site and quickly assembled.
3.13 Low environmental impact
The electromagnetic field around A typical delivery time from order
an HVDC Light® converter installa- The fact that no electric or mag- to hand-over for operation is 20
tion is quite low, since all apparatus netic clearance from the cables is months or less, depending of course
is located in a building designed to needed, and that the converter sta- on local conditions for converter
provide a very efficient shield. The tions are enclosed in a building, sites and cable route.
shielding is needed to minimize emis- makes the impact of the transmis-
sions in the radiofrequency range, i.e. sion system on the environment very
radio interference. The background low. The building can be designed
is that HVDC Light® operates with to resemble other buildings in the
high internal current derivatives and a neighborhood, and the cables are
commutation frequency in the order not even visible.
of 1-2 kHz. Such transients and fre-

ABB 27
PRODUCTS

4 Products

4.1 General 4.1.2 Typical P/Q diagram

4.1.1 Modular concept Id


The modular concept of the ABB
Sb
IGBT valves and standard voltage Ud Power transformer
levels of the DC transmission cables
permit different power levels and $U X tr
mechanical setups to be matched
It Ut n UL IL
optimally to each application. Uc IR UF If
The modularization of HVDC Light® Xc
aims to achieve the most cost-effec-
tive technical and topological solu-
tion for a specific project, combined Simplified circuit diagram
with a short delivery time.

The various configurations provide The fundamental base apparent Where:


the most economical overall solu- power at the filter bus between the
converter reactor and the AC filter is δ = phase angle between the filter
tion. The chosen DC voltages are in
defined as follows (see figure above): voltage UF and the converter volt-
line with the ABB High Voltage Cable
age UC
(HVC) product range, i.e. 80 kV, 150 kV
and 320 kV. The chosen valve cur- L = inductance of the converter
rents are in line with the ABB Semi- reactor
conductors product range. The
The active and reactive power
StakPakTM-type IGBTs from ABB Changing the phase angle controls
components are defined as:
Semiconductors are of a modu- the active power flow between the
lar design, i.e. the active parts, the converter and the filter bus and con-
U F s U C s sin D
IGBT and diode chips, are organized P sequently between the converter
in sub-modules. Thus, the current WL and the AC network.
rating of the device is flexible, rang-
Changing the amplitude difference
ing in steps, i.e. 2 sub, 4 sub and 6 U F s (U F U C ) s cos D
sub. Each sub-module comprises six
Q between the filter voltage UF and
WL the converter voltage UC controls
IGBT chips and three diode chips.
the reactive power flow between the
converter and the filter bus and con-
sequently between the converter
Currents
HVDC Light® modules and the AC network.
580A (2 sub) 1140A (4 sub) 1740A (6 sub)
± 80 kV M1 M2 M3
Voltages ± 150 kV M4 M5 M6
± 320 kV M7 M8 M9

28 ABB
PRODUCTS

,iV̈vˆiÀ ˜ÛiÀÌiÀ With the OPWM (Optimized-Pulse- The P/Q diagram shown is for a
Width-Modulation, ref. Section 5.2.3) back-to-back, i.e. with no distance
$U control strategy, it is possible to cre- between the two stations. The 1st
$U
ate any phase angle or amplitude and 2nd quadrants represent the
(up to a certain limit) by changing the rectifier, and the 3rd and 4th the
PWM pattern. This offers the pos- inverter. A positive value of Q indi-
sibility of controlling both the active cates the delivery of reactive power
UF UC UF and reactive power independently. to the AC network. It should be
UC noted that the reactive power can
D D The typical P/Q diagram, which is be controlled independently in each
valid within the whole steady-state station.
AC network voltage, is shown in the
IR figure below. Note that there are limitations that
have been taken into account in the
calculation of this typical P/Q diagram.
IR
Active power flow
*‡+Ê ˆ>}À>“Ê­Ü…œiÊۜÌ>}iÊÀ>˜}i®
If the UC is in phase-lag, the active £°Óx £°Óx
power flows from AC to DC side
(rectifier) £

If the UC is in phase-lead, the active


ä°Çx
power flows from DC to AC side
(inverter)
ä°x

,i>V̈ÛiÊ«œÜiÀÊ
,i>V̈ÛiÊ«œÜiÀÊ ,i>V̈ÛiÊ«œÜiÀÊ
V̈ÛiÊ*œÜiÀÊ­*°1°®

ä°Óx
Vœ˜ÃՓ«Ìˆœ˜
Vœ˜ÃՓ«Ìˆœ˜ }i˜iÀ>̈œ˜
* ­F ®
$U £°Óx £ ä°Çx ä°x ä°Óx ä ä°Óx ä°x ä°Çx £ £°Óx

ä°Óx
$U $U
ä°x
UF UF UF UC
ä°Çx

UC UC
£

IR IR IR • £°Óx
£°Óx

• £°Óx + ­F ® £°Óx
Reactive power flow ,i>V̈ÛiÊ*œÜiÀÊ­*°1°®

If UF > UC, there is reactive power Typical P/Q diagram within the whole voltage range. Y-axis: Active power
consumption.

If UC > UF, there is reactive power


generation.

ABB 29
PRODUCTS

4.2 HVDC Light® modules for each module. Note that a typical
For a specific project, the appropri- cable size has been chosen for the
ate HVDC Light® module and cable figures in the tables. The procedure
(if any) have to be selected. generally used for the selection of a
cable size leads to the minimum per-
The different HVDC Light® modules missible cross-sectional area, which
are presented below. The typical also minimizes the initial investment
power capacity and total losses for cost of the cable.
different cable lengths are also given

4.2.1 - 80 kV modules

- Data sheet (power) and power capacity vs. cable lengths

Converter types M1 M2 M3
Max. DC voltage (pole to ground) kV 80 80 80
Base power MVA 101 199 304
DC current (IdcN) A 627 1233 1881

Data for 80 kV modules, typical values

DC DC Sending
Converter DC cable Receiving power (MW)
voltage current power
800
types kV A Cu in mm2 MW Back-to-back 50 km 100 km 200 km 400 km
km
M1 80 627 300 102.0 98.7 96.0 93.0
M2 80 1233 1200 200.5 194.0 191.0 188.5 183.0
M3 80 1881 2800 306.1 296.0 293.0 290.5 285.0 274.0

Transfer capability for different cable lengths, typical values 80 kV modules

30 ABB
PRODUCTS

- Typical layout

Example of a 78 MW land station

AC equipment Converter reactors


Converter transformer

23.5 m 4.5 m
13.2 m

8m
DC equipment IGBT valves

A- Typical layout of an offshore


module
The offshore station is designed for
compactness, i.e. space and weight
capacities are very expensive and
scarce resources on an offshore
installation in a marine environment. 12 m
The offshore environment is very
tough. The high-voltage equipment
is installed inside a module with a
ventilation system designed to pro-
tect the high-voltage equipment and
electronics from salt and humid air.

Example of a 78 MW offshore station


30 m

16 m

Approximate weight: 1280 tonnes

ABB 31
PRODUCTS

4.2.2 - 150 kV modules

- Datasheet (power)

Converter types M4 M5 M6
Max. DC voltage (pole to ground) kV 150 150 150
Base power MVA 190 373 570
DC current (IdcN) A 627 1233 1881

Data for 150 kV modules, typical values

DC DC Sending
Converter DC cable Receiving power (MW)
voltage current power
types kV A Cu in mm2 MW Back-to-back 50 km 100 km 200 km 400 km 800 km
M4 150 627 300 191.3 185.0 182.0 179.0 174.0
M5 150 1233 1200 376.0 363.7 361.0 358.0 353.0 342.0
M6 150 1881 2800 573.9 555.1 552.0 549.5 544.0 533.0

Transfer capability for different cable lengths, typical values for 150 kV modules

Typical layout
HVDC Light® 350 MW block

80 x 25 x 11.5 meters

32 ABB
PRODUCTS

4.2.3 - 320 kV modules

- Datasheet (power)

Converter types M7 M8 M9
Max. DC voltage (pole to ground) kV 320 320 320

Base power MVA 405 796 1216

DC current (IdcN) A 627 1233 1881

Data for 320 kV modules, typical values

DC DC DC Sending
Converter Receiving power (MW)
voltage current Cable power
Cu in Back-to-
types kV A MW 50 km 100 km 200 km 400 km 800 km
mm2 back
M7 320 627 300 408.1 396.4 391.4 388.8 382.9 370.6

M8 320 1233 1200 802.2 775.7 772.8 770.1 764.2 752.5 729.0

M9 320 1881 2800 1224.4 1184.1 1180.8 1178.1 1172.2 1160.5 1137.0

Transfer capability for different cable lengths, typical values for 320 kV modules

ABB 33
PRODUCTS

- Typical layout
HVDC Light® 1000 MW block
24 m
43 m
11 m

90 m

34 ABB
PRODUCTS

4.2.4 Asymmetric HVDC Light® - Staged increase of transmitted


As an alternative to balanced (±) power for systems with long dis-
DC voltages from the converter, an tances between terminals
alternative has been introduced in
- Fulfillment of N-1 criteria. In an
the valve configuration to make an
HVDC or HVDC Light® system,
asymmetric DC voltage possible, i.e.
each individual system or pole is a
DC voltage from ground to +DC or
controllable transmission system,
–DC. A monopolar or bipolar HVDC
i.e. the remaining system or pole
Light® configuration as used for con-
will not be subject to overload if
ventional HVDC can be obtained
the other system or pole is sub-
by this means. Two fully insulated
ject to an outage. Therefore, it is
DC cables and one medium voltage
not necessary to reserve capacity
cable are needed in the scheme.
margins on a DC system in order
to fulfill the N-1 criterion, DC links Bipolar HVDC Light® scheme
The asymmetric HVDC Light® is ben-
eficial for transmission systems with: can rather be operated at their
rated power, while still fulfilling the
- Very high requirements of reliability N-1 criterion.
and/or availability, i.e. only infeed
to important loads - Applications with OH lines and
ground electrodes

HVDC Light® Currents


asymmetric modules 580A (2 sub) 1140A (4 sub) 1740A (6 sub)
150kV M1A M2A M3A
Voltages
320 kV M4A M5A M6A

Matrix of HVDC Light asymmetric modules


®

Converter types M1A M2A M3A


Max. DC voltage
kV 150 150 150
(pole to ground)
Base power per pole MVA 94.6 186.5 285
DC current (IdcN) A 627 1233 1881
Data for asymmetric 150 kV modules, typical values per pole

DC DC Sending
Converter DC cable Receiving power per pole (MW)
voltage current power

Cu in Back-to-
types kV A MW 50 km 100 km 200 km 400 km 800 km
mm2 back
M1A 150 627 300 95.6 92.5 90.0 87.1
M2A 150 1233 1200 187.9 181,0 179.0 176.7 171.5
M3A 150 1881 2800 286.9 277.5 274.6 272.3 267.1 256.8
Transfer capability for different cable lengths, typical values asymmetric 150 kV modules per pole

ABB 35
Converter types M4A M5A M6A
Max. DC voltage
kV 320 320 320
(pole to ground)
Base power per pole MVA 202 397 608
DC current (IdcN) A 627 1233 1881

Data for asymmetric 320 kV modules, typical values per pole

DC DC Sending
Converter DC cable Receiving power per pole (MW)
voltage current power

Cu in Back-to-
types kV A MW 50 km 100 km 200 km 400 km 800 km
mm2 back
M4A 320 627 300 204.0 197.3 194.1 190.9 185.6
M5A 320 1233 1200 401.0 387.9 385.0 381.8 376.5 364.8
M6A 320 1881 2800 612.1 592.1 588.8 586.1 580.2 568.5

Transfer capability for different cable lengths, typical values for asymmetric 320 kV modules per pole

4.2.5 Selection of modules 4.3 HVDC Light® Cables


The optimization of the entire proj-
ect, including both converters and 4.3.1 Insulation
cables, must be performed individu- The HVDC Light® polymer cables
ally for each project, since active/ for HVDC are similar to XLPE AC
reactive power demand, cable length, cables, but with a modified polymer-
sea/land cable and cable installation ic insulation. XLPE cables have been
must be considered. In general, it is used for AC since the late 1960s.
more economical to choose a lower
voltage and higher current for short
distances. For longer distances, it is 4.3.2 Submarine Cable Data
more economical in most cases from Cable data (capability, losses, etc.,
the point of view of cable cost and for submarine cables installed in dif-
losses to choose a higher voltage, ferent tropical and moderate climate
even if a higher DC voltage increases zones) are set out below.
the cost of the converters. A choice
of either a balanced or an asym-
metric converter type shall be used
based on the distance between ter-
minals, reliability/availability require-
ments, staged increase of power
capacity, etc. This must also be done
for each specific project.

36 ABB
PRODUCTS

HVDC Light® Cable bipole data


Submarine cables
Tropical climate, submarine cables with copper conductor

Area Ampacity ±80 kV bipole ±150 kV bipole ±320 kV bipole


Weight Diam. Weight Diam. Weight Diam.
Con- Close Spaced Close Spaced Close Spaced Close Spaced
per over per over per over
ductor laying laying laying laying laying laying laying laying
cable cable cable cable cable cable
mm² Amps Amps MW MW kg/m mm MW MW kg/m mm MW MW kg/m mm
95 282 338 45 54 4,7 42 85 101 8,5 60 180 216 15 90
120 323 387 52 62 5,5 44 97 116 9,4 61 207 248 16 91
150 363 436 58 70 6,7 47 109 131 10 63 232 279 17 93
185 411 496 66 79 7,4 49 123 149 11 64 263 317 18 95
240 478 580 76 93 8,4 52 143 174 12 67 306 371 20 99
300 544 662 87 106 9,4 56 163 199 13 69 348 424 22 102
400 626 765 100 122 11 61 188 230 16 75 401 490 24 105
500 722 887 116 142 13 66 217 266 18 78 462 568 26 108
630 835 1030 134 165 15 71 251 309 21 83 534 659 30 114
800 960 1187 154 190 17 76 288 356 24 88 614 760 33 118
1000 1092 1355 175 217 21 81 328 407 26 96 699 867 37 122
1200 1188 1474 190 236 24 85 356 442 29 100 760 943 40 126
1400 1297 1614 208 258 27 89 389 484 32 103 830 1033 43 130
1600 1397 1745 224 279 30 92 419 524 35 107 894 1117 47 133
1800 1490 1860 238 298 32 96 447 558 38 110 954 1190 50 137
2000 1589 1987 254 318 35 99 477 596 41 113 1017 1272 53 140
2200 1676 2086 268 334 40 103 503 626 45 118 1073 1335 58 145
2400 1764 2198 282 352 42 106 529 659 48 121 1129 1407 61 148

Sea soil: Temperature 28 degrees C, Burial 1.0 metre, Thermal resistivity 1.2 K × W /m
Cable: Copper conductor, HVDC polymer insulation, Steel wire armour

Bipolar power transmission is P = 2×U×I×10-3 MW


Bipolar transmission losses are P = 2×R×10-3×I2 W/m
Voltage drop at 100% load is U = R×I V/km

Area Resistance Voltage drop Losses at 50% Losses at 100%


Copper per phase
Close laying Spaced laying Close laying Spaced laying Close laying Spaced laying
Conductor 20 deg.C
mm² ohm/km V/km V/km W/m W/m W/m W/m
95 0,193 65 78 8 12 37 53
120 0,153 59 71 9 12 38 55
150 0,124 54 65 9 13 39 57
185 0,0991 49 59 9 13 40 59
240 0,0754 43 52 9 14 41 60
300 0,0601 39 48 9 14 42 64
400 0,0470 35 43 10 15 44 66
500 0,0366 32 39 10 15 46 69
630 0,0283 28 35 11 16 47 72
800 0,0221 25 31 11 17 48 74
1000 0,0176 23 29 11 17 50 79
1200 0,0151 21 27 11 18 50 80
1400 0,0126 20 24 11 18 52 77
1600 0,0113 19 24 12 18 53 84
1800 0,0098 17 22 12 18 51 82
2000 0,0090 17 21 12 19 54 83
2200 0,0080 16 20 12 19 54 83
2400 0,0073 15 19 12 19 53 84

ABB 37
PRODUCTS

Moderate climate, submarine cables with copper conductor

Area Ampacity ±80 kV bipole ±150 kV bipole ±320 kV bipole


Weight Diam. Weight Diam. Weight Diam.
Con- Close Spaced Close Spaced Close Spaced Close Spaced
per over per over per over
ductor laying laying laying laying laying laying laying laying
cable cable cable cable cable cable
mm² Amps Amps MW MW kg/m mm MW MW kg/m mm MW MW kg/m mm
95 343 404 55 65 4,7 42 103 121 8,5 60 220 259 15 90
120 392 463 63 74 5,5 44 118 139 9,4 61 251 296 16 91
150 441 523 71 84 6,7 47 132 157 10 63 282 335 17 93
185 500 596 80 95 7,4 49 150 179 11 64 320 381 18 95
240 583 697 93 112 8,4 52 175 209 12 67 373 446 20 99
300 662 797 106 128 9,4 56 199 239 13 69 424 510 22 102
400 765 922 122 148 11 61 230 277 16 75 490 590 24 105
500 883 1072 141 172 13 66 265 322 18 78 565 686 26 108
630 1023 1246 164 199 15 71 307 374 21 83 655 797 30 114
800 1175 1438 188 230 17 76 353 431 24 88 752 920 33 118
1000 1335 1644 214 263 21 81 401 493 26 96 854 1052 37 122
1200 1458 1791 233 287 24 85 437 537 29 100 933 1146 40 126
1400 1594 1962 255 314 27 89 478 589 32 103 1020 1256 43 130
1600 1720 2123 275 340 30 92 516 637 35 107 1101 1359 47 133
1800 1830 2265 293 362 32 96 549 680 38 110 1171 1450 50 137
2000 1953 2407 312 385 35 99 586 722 41 113 1250 1540 53 140
2200 2062 2540 330 406 40 103 619 762 45 118 1320 1626 58 145
2400 2170 2678 347 428 42 106 651 803 48 121 1389 1714 61 148

Sea soil: Temperature 15 degrees C, Burial 1.0 metre, Thermal resistivity 1.0 K × W /m
Cable: Copper conductor, HVDC polymer insulation, Steel wire armour

Bipolar power transmission is P = 2×U×I×10 -3 MW


Bipolar transmission losses are P = 2×R×10-3×I2 W/m
Voltage drop at 100% load is U = R×I V/km

Area Resistance Voltage drop Losses at 50% Losses at 100%


Copper per phase
Close laying Spaced laying Close laying Spaced laying Close laying Spaced laying
Conductor 20 deg.C
mm² ohm/km V/km V/km W/m W/m W/m W/m
95 0,193 79 93 12 16 54 75
120 0,153 72 85 12 17 56 79
150 0,124 65 78 12 17 57 82
185 0,0991 59 71 13 18 59 85
240 0,0754 53 63 13 19 62 88
300 0,0601 48 57 14 20 64 91
400 0,0470 43 52 14 21 66 96
500 0,0366 39 47 15 22 69 101
630 0,0283 35 42 15 23 72 105
800 0,0221 31 38 16 23 73 109
1000 0,0176 28 35 16 24 75 115
1200 0,0151 26 32 16 25 76 115
1400 0,0126 24 30 16 25 77 118
1600 0,0113 23 29 17 26 79 123
1800 0,0098 21 27 17 26 77 122
2000 0,0090 21 26 18 27 82 125
2200 0,0080 20 24 17 26 82 122
2400 0,0073 19 23 18 27 82 123

38 ABB
PRODUCTS

4.3.3 Land Cable data


Cable data (capability), losses etc for land cables installed in different tropical and moderate climate zones) are set out
below.

HVDC Light® Cable bipole data


Land Cables

Tropical climate, land cables with aluminium conductor


For higher transmission capacity, see submarine cables with copper conductor

Area Ampacity ±80 kV bipole ±150 kV bipole ±320 kV bipole


Con- Weight Diam. Weight Diam. Weight Diam.
Close Spaced Close Spaced Close Spaced Close Spaced
duc- per over per over per over
laying laying laying laying laying laying laying laying
tor cable cable cable cable cable cable
mm² Amps Amps MW MW kg/m mm MW MW kg/m mm MW MW kg/m mm
95 211 258 34 41 1,2 33 - - - - - - - -
120 240 298 38 48 1,3 34 - - - - - - - -
150 269 332 43 53 1,5 36 81 100 2 50 - - - -
185 305 378 49 60 1,6 38 92 113 3 52 - - - -
240 351 439 56 70 1,9 40 105 132 3 54 225 281 5 80
300 400 503 64 80 2,1 43 120 151 3 57 256 322 6 82
400 456 581 73 93 3 46 137 174 4 60 292 372 6 86
500 536 672 86 108 3 50 161 202 4 63 343 430 7 89
630 591 744 95 119 3 53 177 223 5 67 378 476 8 93
800 711 898 114 144 4 57 213 269 5 71 455 575 8 97
1000 811 1026 130 164 5 61 243 308 6 75 519 657 9 101
1200 888 1123 142 180 6 65 266 337 7 79 568 719 10 105
1400 980 1242 157 199 6 69 294 373 8 83 627 795 11 108
1600 1044 1326 167 212 7 72 313 398 9 86 668 849 12 112
1800 1129 1434 181 229 8 75 339 430 9 89 723 918 13 115
2000 1198 1524 192 244 8 78 359 457 10 92 767 975 14 118
2200 1265 1600 202 256 9 81 380 480 11 95 810 1024 15 121
2400 1330 1681 213 269 10 84 399 504 11 98 851 1076 16 123

Sea soil: Temperature 28 degrees C, Burial 1.0 metre, Thermal resistivity 1.2 K × W /m
Cable: Aluminium conductor, HVDC polymer insulation, Copper wire screen

Bipolar power transmission is P = 2×U×I×10-3 MW


Bipolar transmission losses are P = 2×R×10-3×I2 W/m
Voltage drop at 100% load is U = R×I V/km

Area Resistance Voltage drop Losses at 50% Losses at 100%


Aluminium per pole
Close laying Spaced laying Close laying Spaced laying Close laying Spaced laying
conductor 20 deg. C
mm² ohm/km V/km V/km W/m W/m W/m W/m
95 0,32 81 99 8 11 34 51
120 0,253 73 90 8 12 35 54
150 0,206 66 82 8 12 36 54
185 0,1640 60 74 8 13 37 56
240 0,1250 52 66 8 13 37 58
300 0,1000 48 60 9 14 38 60
400 0,0778 42 54 9 14 38 63
500 0,0605 39 49 9 15 42 66
630 0,0469 33 42 9 14 39 62
800 0,0367 31 39 10 16 44 70
1000 0,0291 28 36 10 16 45 74
1200 0,0247 26 33 10 17 46 74
1400 0,0208 24 31 11 17 47 77
1600 0,0186 23 30 11 17 48 80
1800 0,0162 22 28 11 18 50 80
2000 0,0149 21 27 11 19 50 82
2200 0,0132 20 25 11 18 51 80
2400 0,0121 19 24 11 18 51 81

ABB 39
PRODUCTS

Moderate climate, land cables with aluminium conductor


For higher transmission capacity, see submarine cables with copper conductor

Area Ampacity ±80 kV bipole ±150 kV bipole ±320 kV bipole


Weight Diam. Weight Diam. Weight Diam.
Con- Close Spaced Close Spaced Close Spaced Close Spaced
per over per over per over
ductor laying laying laying laying laying laying laying laying
cable cable cable cable cable cable
mm² Amps Amps MW MW kg/m mm MW MW kg/m mm MW MW kg/m mm
95 258 310 41 50 1,2 33 - - - - - - - -
120 294 357 47 57 1,3 34 - - - - - - - -
150 330 402 53 64 1,5 36 99 121 2 50 - - - -
185 374 458 60 73 1,6 38 112 137 3 52 - - - -
240 432 533 69 85 1,9 40 130 160 3 54 276 341 5 80
300 492 611 79 98 2,1 43 148 183 3 57 315 391 6 82
400 565 705 90 113 3 46 170 212 4 60 362 451 6 86
500 659 816 105 131 3 50 198 245 4 63 422 522 7 89
630 727 964 116 154 3 53 218 289 5 67 465 617 8 93
800 877 1094 140 175 4 57 263 328 5 71 561 700 8 97
1000 1001 1252 160 200 5 61 300 376 6 75 641 801 9 101
1200 1096 1371 175 219 6 65 329 411 7 79 701 877 10 105
1400 1211 1517 194 243 6 69 363 455 8 83 775 971 11 108
1600 1291 1621 207 259 7 72 387 486 9 86 826 1037 12 112
1800 1395 1752 223 280 8 75 419 526 9 89 893 1121 13 115
2000 1482 1866 237 299 8 78 445 560 10 92 948 1194 14 118
2200 1571 1963 251 314 9 81 471 589 11 95 1005 1256 15 121
2400 1652 2066 264 331 10 84 496 620 11 98 1057 1322 16 123

Sea soil: Temperature 15 degrees C, Burial 1.0 metre, Thermal resistivity 1.0 K × W /m
Cable: Aluminium conductor, HVDC polymer insulation, Copper wire screen

Bipolar power transmission is P = 2×U×I×10-3 MW


Bipolar transmission losses are P = 2×R×10-3×I2 W/m
Voltage drop at 100% load is U = R×I V/km

Area Resistance Voltage drop Losses at 50% Losses at 100%


Aluminium per pole
Close laying Spaced laying Close laying Spaced laying Close laying Spaced laying
conductor 20 deg. C
mm² ohm/km V/km V/km W/m W/m W/m W/m
95 0,32 99 119 11 16 51 74
120 0,253 89 108 11 17 52 77
150 0,206 81 99 12 17 53 80
185 0,1640 73 90 12 18 55 82
240 0,1250 65 80 12 18 56 85
300 0,1000 59 73 12 19 58 89
400 0,0778 53 66 13 20 60 93
500 0,0605 48 59 13 21 63 96
630 0,0469 41 54 13 22 60 104
800 0,0367 39 48 14 23 68 105
1000 0,0291 35 44 15 23 70 110
1200 0,0247 32 41 15 24 70 112
1400 0,0208 30 38 16 25 73 115
1600 0,0186 29 36 16 25 75 117
1800 0,0162 27 34 16 26 75 119
2000 0,0149 26 33 17 27 77 123
2200 0,0132 25 31 17 26 79 122
2400 0,0121 24 30 17 27 79 124

40 ABB
DESCRIPTIONS

5 Descriptions

5.1 Main circuit

- Single-line diagram

1
Ú*£ 
Ú*£

³1`

1Ú*

Ú6-

*œÜiÀÊ 1Ú

ÌÀ>˜ÃvœÀ“iÀ

œ˜ÛiÀÌiÀ
Ài>V̜À
*
É,ÊvˆÌiÀ

Õ݈ˆ>ÀÞÊ«œÜiÀ

ÊvˆÌiÀ
‡1`

˜VœÃÕÀi
1
Ú*Ó 
Ú*Ó


œ˜ÛiÀÌiÀÊ Õˆ`ˆ˜}

Single-line diagram of an HVDC Light® Converter

5.1.1 Power transformer The current in the transformer wind- The transformer may be provided
The transformer is an ordinary single- ings contains hardly any harmonics with a tertiary winding to feed the
phase or three-phase power trans- and is not exposed to any DC volt- station auxiliary power system.
former, with a tap changer. The sec- age. In order to maximize the active
ondary voltage, the filter bus voltage, power transfer, the converter gener-
will be controlled with the tap chang- ates a low frequency zero-sequence
er to achieve the maximum active voltage (<0.2 pu), which is blocked
and reactive power from the convert- by the ungrounded transformer sec-
er, both consumption and generation. ondary winding.
The tap changer is located on the
secondary side, which has the larg-
est voltage swing, and also in order
to ensure that the ratio between the
line winding and a possible tertiary
winding is fixed.

ABB 41
DESCRIPTIONS

5.1.2 Converter reactors


The converter reactor is one of the
key components in a voltage source
converter to permit continuous and
independent control of active and
reactive power.

The main purposes of the conver-


ter reactor are:
• to provide low-pass filtering of the
PWM pattern to give the desired
fundamental frequency voltage. The
converter generates harmonics relat-
ed to the switching frequency. The
harmonic currents are blocked by
the converter reactor, and the har-
monic content on the AC bus volt-
age is reduced by an AC filter.

• to provide active and reactive


power control. The fundamental fre-
quency voltage across the reactor
defines the power flow (both active
and reactive) between the AC and
DC sides. Refer to Typical P/Q dia-
gram and active and reactive power
definitions.

• to limit the short-circuit currents

There is one converter reactor per


phase. They consist of vertical coils,
standing on insulators. They are sev-
eral meters tall and several meters in
diameter. Shields eliminate the mag-
netic fields outside the coils.

The short-circuit voltage of the con-


verter reactor is typically 15%.

The stray capacitance across the result in current pulses through all cies, and the capacitance across
reactor should be kept as low as capacitances to ground. These cur- the reactor should therefore be low.
possible in order to minimize the rent pulses should be minimized as These requirements have led to the
harmonics coupled to the filter side they pass through the valve. The fil- design of converter reactors with air
of the reactor. The high dv/dt on the ter side of the reactor can be con- coils without iron cores.
bridge terminal at each switching will sidered as ground at high frequen-

42 ABB
DESCRIPTIONS

5.1.3 DC capacitors 5.1.4 AC filters The distorted waveform of the con-


The primary objective of the valve Voltage source converters can verter terminal voltage can be
DC side capacitor is to provide a be operated with different control described as a series of harmonic
low-inductance path for the turned- schemes, most of which use pulse voltages E 
¤ E h cosh7 1t A h
off current and also to serve as an width modulation to control the ratio h 1
where Eh is the h:th harmonic EMF.
energy store. The capacitor also between the fundamental frequen-
The magnitude of the harmonic
reduces the harmonics ripple on the cy voltage on the DC and AC side.
EMFs will, naturally, vary with the DC
direct voltage. Disturbances in the Looking at the AC side converter
voltage, the switching frequency (or
system (e.g. AC faults) will cause DC terminal, the voltage to ground will
pulse number) of the converter, etc.
voltage variations. The ability to limit be anything but sinusoidal, as indi-
But it will also depend on the cho-
these voltage variations depends on cated in the figures on the follow-
sen PWM technology of the convert-
the size of the DC side capacitor. ing pages. The most frequent appli-
er. To illustrate this, the figures below
cation of voltage source converters
The DC capacitor is an ABB DryQ contain two examples:
is as machine drives (in industrial
capacitor. For high voltage applica- applications), where this is of less • A converter utilizing a sinusoi-
tions, this technology makes pos- or no concern. However, connect- dal PWM with 3rd harmonic injec-
sible capacitors of a dry, self-heal- ing a voltage source converter to tion (that is when a 3rd harmonic is
ing, metallized film design. The DryQ a transmission or distribution sys- added on the fundamental frequen-
design has: tem requires the voltage to be made cy modulator to increase the power
sinusoidal. This is achieved by rating of the converter).
• Twice the capacity in half the
means of the converter reactor and
volume
AC filters. • A converter using a harmonic can-
• Corrosion-free plastic housing cellation PWM or OPWM.

• Low inductance

• Shortened production time and


simplified installation

ABB 43
DESCRIPTIONS

Converter Terminal Phase to Ground Voltage, E


v

−1

0 50 100 150 200 250 300 350


Harmonic content of phase voltage, excluding zero sequence components
1

0.5

0
0 10 20 30 40 50 60 70 80 90 100
Harmonic content of phase voltage, zero sequence components only
1

0.5

0
0 10 20 30 40 50 60 70 80 90 100

Voltage source converter operated with a sinusoidal PWM with 3rd harmonic
injection. The blue dotted line shows the fundamental frequency voltage com-
ponent of the converter terminal to ground voltage.

44 ABB
DESCRIPTIONS

Converter Terminal Phase to Ground Voltage, Ev

−1

0 50 100 150 200 250 300 350


Harmonic content of phase voltage, excluding zero sequence components
1

0.5

0
0 10 20 30 40 50 60 70 80 90 100
Harmonic content of phase voltage, zero sequence components only
1

0.5

0
0 10 20 30 40 50 60 70 80 90 100

Both the above figures give the con- Voltage source converter operated
verter terminal phase-to-ground volt- with a harmonic cancellation PWM.
age (with the fundamental compo- The blue dotted line shows the
nent indicated) together with the fundamental frequency voltage com-
corresponding harmonic spectrum. ponent of the converter terminal to
ground voltage.
The spectrum is given as positive
and negative sequence components
and zero-sequence components.
The power transformer between the C
filter bus and the connecting AC C 1
1
bus will effectively prevent the latter
entering the AC network.
L R
In a typical HVDC Light® scheme, L 1 1
AC filters contain two or three 1
grounded or ungrounded tuned filter
branches.

Example of an HVDC Light® AC filter.

ABB 45
DESCRIPTIONS

Depending on filter performance 5.1.5 DC filters A typical requirement can be


requirements, i.e. permissible volt- For HVDC Light® converters used expressed as an equivalent weighted
age distortion, etc., the filter configu- in combination with HVDC Light® residual current fed into the cable pair
ration may vary between schemes. cables, the filtering on the DC side by at each station. The current is calcu-
But a typical filter size is somewhere the converter DC capacitor and the lated as
between 10 to 30% of the rated line smoothing reactor on the DC side ¤
I eq  (1 / P800 ) *
h
( Phf1 * I h ) 2 where:

power. Typical requirements on filter are considered to provide sufficient


performance are suppression of any harmonics. • Ieq is the psophometrically weight-
Individual harmonic distortion, ed, 800 Hz equivalent disturbing
However, under certain circumstanc-
current.
U es, if the DC cable route shares the
D h  h ≈ 1%
U1 same right of way or runs close by • Ih is the vector sum of harmon-
subscribers telephone wires, railroad ic currents in cable pair conductors
Total harmonic distortion, signaling wires or similar, there is a and screens at harmonic h
THD  ¤D h
h
2
≈ 1.5% to 2.5%
possibility of exposure to harmonic
interference from the cable. Under • Phf1 is the psophometric weight at
these circumstances and for condi- the frequency of h times the funda-
Telephone influence factor, tions where a local preventive mea- mental frequency.
sure is not feasible, e.g. improving the
TIF  ¤5hf C 1 messagehf1 D h 2
≈ 40 to 50 shielding of subscriber wires, the third
The weighting factor in this example is
h
the UIT (CCITT) psophometric weight-
party (telephone company, railway
ing factor.
The above indices are all based on company, etc.) should be consulted
the voltage measured at the point of for permissible interference limits. Sometimes the C-message factor
connection of the DC scheme. The mentioned above is used instead.
first two are direct measures of volt-
age quality, whilst the third, TIF, is a If additional filtering is required, the
weighted measure and is a commonly remedy is to add a filter on the DC
used indication of expected telephone side, consisting of either a common
interference. The TIF value is based mode (zero-sequence) reactor or/ and
on the Cmessage weight presented in a single-tuned filter or filters.
E.E.I. Publication 60-68.

C−message weight vs frequency.


1

0.9

0.8

0.7

0.6

0.5

0.4

0.3

0.2

0.1

0
0 500 1000 1500 2000 2500 3000 3500 4000 4500 5000
Hz
C-message weight

46 ABB
DESCRIPTIONS

Psophometric weight vs frequency.


1.4
Psophometric weight
1.2

0.8

0.6

0.4

0.2

0
0 500 1000 1500 2000 2500 3000 3500 4000 4500 5000
Hz

5.1.6 High-frequency (HF) filters nections. For example, the valves If a power line carrier (PLC) is used
In voltage source converters, the contain HF damping circuits on both nearby in the connected power
necessarily high dv/dt in the switch- the AC and DC sides to ensure that grid, additional PLC filters may be
ing of valves means that the high as little HF disturbance as possible required, i.e. an additional AC line
frequency (HF) noise generation is will spread from the valve area. filter reactor and a properly tuned
significantly higher than for conven- capacitor to earth.
To further limit HF interference, a
tional HVDC converters. To prevent
radio interference (RI) filter capacitor
this HF noise spreading from the
is connected between the AC bus
converter to the connected power
and earth, and an AC line filter reac-
grids, particular attention is given
tor is installed. With these measures,
to the design of the valves, to the
the scheme will meet the require-
shielding of the housings and to
ments of applicable standards for
ensuring proper HF grounding con-
emissions.

R I d ef ens e l i n es
U V alve and reactor enclosures
U E nclosure cable connections
U EM C ROX
U F errites
U RI - Filtering
U House
U E arthing system
U EM C approved aux. systems

Applicable standards
• CISPR 11
• ENV50121-5

ABB 47
DESCRIPTIONS

5.1.7 Valves A complete IGBT position consists


of an IGBT, a gate unit, a voltage
- The IGBT position
divider and a water-cooled heat sink.
The semiconductor used in HVDC
Each gate unit includes gate-driv-
Light® is the StakPak™ IGBT from
ing circuits, surveillance circuits and
ABB Semiconductors. The IGBT
optical interface. The gate-driving
(insulated gate bipolar transistor) is
electronics control the gate voltage
a hybrid of the best of two worlds.
and current at turn-on and turn-off,
As a conducting device, the bipo-
in order to achieve optimal turn-on
lar transistor with its low forward
and turn-off processes of the IGBT.
voltage drop is used for handling
The voltage across the IGBT dur-
high currents. Instead of the regu-
ing switching is measured, and the
lar current-controlled base, the IGBT
information is sent to the valve con-
has a voltage-controlled capaci-
trol unit through an optical fiber. The
tive gate, as in the MOSFET device.
voltage divider connected across the
To increase the power handling, six
IGBT provides the gate unit with the
IGBT chips and three diode chips
current needed to drive the gate and
are connected in parallel in a sub-
feed the optical communication cir-
module. A StakPak™ IGBT has
cuits and the control electronics.
two, four or six sub-modules, which
determine the current rating of the
IGBT.

The StakPak™ IGBT with four and six sub-modules.

48 ABB
DESCRIPTIONS

- Valve function tive potential and the phase terminal All IGBTs and coolers in a stack are
To be able to switch voltages high- and one between the phase terminal mounted tightly together under very
er than the rated voltage of one and the negative potential. Thus, a high pressure, in order to minimize
IGBT, several positions are connect- three-phase converter has six valves, contact resistance and to increase
ed in series in each valve. The most three phase reactors and a set of cooling capacity.
important factor is that all IGBTs DC capacitors. The diagram below
must turn on and off at exactly the shows the schematics of an HVDC The stacks are pressed togeth-
same moment, in order to achieve Light® converter in principle. er with glass fiber bolts, which ful-
an evenly distributed voltage across fill both insulation and mechanical
the valve. ABB has a well-proven - Mechanical design strength criteria. Circular aluminum
solution that regulates each IGBT The HVDC Light® converter valves shields are mounted around the
position individually in the valve to are for DC voltages up to 150 kV IGBT stacks to smooth the electrical
the correct voltage level. The flex- assembled inside an enclosure field around the high-voltage equip-
ibility of the IGBT as a semiconduct- made of steel and aluminum. The ment. The stacks are suspended
ing device also makes it possible to shielded enclosure helps to improve on an insulator from the ceiling of
block the current immediately if a the electromagnetic compatibility of the valve enclosure. This installation
short circuit is detected, and thus the converter. Another advantage method makes the converter resis-
to prevent damage to the converter. is that the enclosure is made as a tant to earthquakes and other move-
A single valve for a 150 kV module standard container, which simplifies ments.
consists of around 300 series-con- the transport of the converter to the
Overall, the assembling method with
nected IGBTs. site. With this method, most of the
shielded stacks hanging in enclo-
HVDC Light® converter parts can
sures with controlled humidity lev-
- Valve bridge be pre-assembled at the produc-
els makes it possible to reduce the
HVDC Light® is based on a two-lev- tion location to minimize the assem-
distances between the high-volt-
el topology, meaning that the out- bly work on site. Some of the testing
age parts and the surroundings.
put voltage is switched between can also be done before transporta-
This makes HVDC Light® a compact
two voltage levels. Each phase has tion, thereby reducing the installation
power transmission technology.
two valves, one between the posi- and commissioning time on site.

6°6£ 6 °6£ 6
°6£

·«…>ÃiÊ

6°6Ó 6 °6Ó 6
°6Ó

Principle schematic of a three-phase two-level HVDC Light® converter.

ABB 49
DESCRIPTIONS

5.1.8 Valve cooling system


All HVDC Light® positions are
equipped with water-cooled heat
sinks providing high-efficiency cool-
ing. The valve cooling systems are
manufactured by SwedeWater, a
member of the ABB group.

To be able to use water as cooling


liquid in direct contact with high volt-
age potentials, it is of great impor-
tance that the water has very low
conductivity. The water is circulat-
ing through the heat sink in close
contact with each IGBT, which effi-
ciently transports the heat away
from the semiconductor. The cool-
ing water circuit is a closed system,
and the water is cooled through
heat exchangers using either air or
a secondary water circuit as cooling
Inside a Valve Enclosure medium.

The water in the valve cooling sys-


Today, there are no issued stan- In this process, the IGBT, the voltage tem passes continuously through a
dards that fully cover the testing of divider and the gate unit are tested de-ionizing system, to keep the con-
an HVDC Light® converter valve. together. ductivity of the water low. The tem-
perature of the water in the valves
The AC and DC voltage applications Afterwards, parts of the converter
is controlled by a MACH-2-based
are tested according to IEC 60700-1 valves are type tested in an H-bridge
cooling control system, for exam-
and IEC 61954, to the extent that the test setup. The tests are performed
ple regulating the number of fans to
standard is applicable. The switch- on a downscale of the converter
be operated in order to achieve the
ing and lightning impulse tests are valves, with only a few positions in
necessary cooling capacity. In addi-
performed according to IEC 60060. series and with a reduced AC volt-
tion to temperature measurements,
However, standard IEC 62501 for age. Four valves are connected in an
the cooling system is also equipped
testing of VSC Valves is under prepa- H-bridge configuration, which makes
with sensors for pressure, water
ration, and as soon as it is valid testing of it possible to test both rectifier and
flow, level and conductivity, and
the HVDC Light® valves will be based inverter operation. Phase angles,
it controls motor-operated valves,
on that standard. voltages, current and filters can be
pumps and fans. If necessary, elec-
adjusted to simulate most of the
All IGBT positions are tested before trical heaters or glycol can be added
HVDC Light® operation modes.
the stacks are assembled, in a to prevent the water from freezing if
sophisticated routine test line. the converter station is located in a
cold area.

50 ABB
DESCRIPTIONS

Valve cooling system.

All major parts of the valve cooling The redundancy of all the equipment The valve cooling system used for
system are provided with redundant also simplifies the maintenance of HVDC Light® is based on the valve
equipment. The control system con- the valve cooling system. If mainte- cooling system used for thyristor
sists of two separate systems that nance is necessary, it is possible to valves in conventional HVDC con-
measure all parameters using differ- change which pump will run manu- verters since 1980.
ent transmitters, all in order to mini- ally directly from the operator com-
mize the risk of an unwanted stop. puter,. Some parts of the cooling
Both systems are able to control system can be closed and discon-
the two main pump motors, and the nected to allow maintenance to be
low-voltage switchgear has switcho- carried out without interrupting the
ver functions to ensure uninterrupt- power transmission.
ible operation. The software also
performs weekly changeovers of
the pumps in operation, in order to
ensure equal wear of the equipment.

ABB 51
DESCRIPTIONS

5.1.9 Station service power - Duplication of all critical equipment The valve enclosures, the control
The station service power system - valve cooling pumps enclosure and all areas that have a
is vital for reliable operation of the high demand because of sensitive
The duplicated valve cooling pumps equipment are detected with air sam-
HVDC Light® station. The design of
are controlled by frequency convert- pling systems. The air sampling sys-
station service power is focused on:
ers for maximum flexibility for the tem can detect smoke at a very early
- Redundant power supplies, one flow control of cooling water. The stage. Being able to detect smoke at
from the internal AC bus and one frequency converter also makes it an early stage is an advantage, since
from an external source. possible to use a DC backup source this can prevent unnecessary tripping
to keep the pump running if auxiliary or shutdown of the station.
The supply to the internal AC bus power is lost for a long time.
can be taken from a yoke winding The power transformer is isolated
on the converter transformer. - station battery system by firewalls. Depending on the local
regulations or client requirements,
In this way, the power supply is The control equipment and other
the transformer may or may not be
guaranteed at all times when the station DC loads are supplied from
protected by a sprinkler system.
station is in operation. The output a duplicated station battery system
The converter reactors have smoke
voltage is 6 –10 kV, which means an with a backup time of at least two
detectors.
intermediate transformer is neces- hours.
sary to provide a 400 V system. If necessary, the valve enclosures
Critical AC loads within the control
and other detected areas with air
The external power supply is taken equipment, such as servers, com-
sampling systems can be protected
from a local AC system provided by puters, LAN switches, etc., are sup-
with total flooding by gas or water
the customer and is used as a back- plied from a DC/AC inverter fed from
mist extinguishing systems in accor-
up source. the station battery and with an auto-
dance with NFPA 2001 or NFPA 750.
matic switchover to the alternative
- Duplication of all critical parts, AC supply in the event of inverter If a water pumping system is
valve cooling pumps, station bat- failure or overload. required, it consists of one electric
teries and battery chargers.
pump and one standby diesel-driv-
en pump. A ring main water loop will
- Automatic changeover 5.1.10 Fire protection
then be located on the site (under-
The incomers to the 400 V switch- For HVDC Light® projects, the fire
ground) for a fire-fighting water sup-
gear have automatic changeover protection area is generally small-
ply. It is connected to an isolation
control. The supply coming from the er than for conventional HVDC, but
valve that will bring redundancy
internal AC bus is pre-selected as a the requirements are the same. The
in the ring main loop for fire fight-
primary supply, and the supply from design of fire-fighting and fire pro-
ing water. Fire hydrants will be posi-
the external local AC system is pre- tection is in accordance with NFPA
tioned at strategic locations around
selected as a backup supply. If the (National Fire Protection Associa-
the site area close to the main loop.
pre-selected supply fails, change- tion) and with the requirements of all
Water supply storage will be con-
over to the backup supply takes authorities having jurisdiction over
nected to the fire fighting water loop.
place within a pre-set time. When any parts of the works.
the pre-selected supply returns, the The signals from the detection sys-
changeover system changes back tem and the pumps will be connect-
to the primary supply within the pre- ed to a fire alarm panel in the opera-
set time. tor control room.

52 ABB
DESCRIPTIONS

5.1.11 Civil engineering work,


building and installation

- General
For HVDC Light® systems up to 150 kV,
land-based stations are built without
a dedicated valve hall. The converter
station has a compact layout, with
the majority of equipment housed
in a typical warehouse-style build-
ing. The buildings are made of sheet
steel and are provided with doors,
stairs and catwalks.

The IGBT’s valves are installed in


steel enclosures, which are placed
on a concrete slab. The control and
cooling equipment is normally also - Site inspection and testing System tests of the HVDC system.
installed in enclosures. Concrete System testing is normally the last
test activity prior to handing over the • Terminal test
slabs are also used for locating the
AC filters and DC equipment. A sim- HVDC system to the client for opera-
- High-voltage energizing
ple steel building is erected over all tion. Prior to system testing, sever-
the equipment. The main functions al other test activities will have been - Terminal operation
of the building are HF shielding, performed.
noise reduction and weather protec- • Transmission test
The general philosophy is that all
tion. All the enclosures (valves, con-
tests must be performed as early In addition to the tests specified
trol and cooling) have a controlled
as possible in order to allow early above, acceptance tests will be per-
indoor environment as regards tem-
remedial work to be done. The on- formed according to the specifica-
perature, humidity and cleanness.
site inspection and test activities tion and contract agreement.
The wall cladding of the building is comprise:
All verifications and tests on site are
normally metal sheeting, which can
Verifications and tests during civil listed in the inspection and test plan
be insulated with sound barriers to
engineering work and during instal- for field tests (ITP).
achieve the required noise level. The
lation of individual equipment/unit.
building can be fitted with a ventila- During inspections, the environmen-
tion system if required. • Verifications and inspection tal impact requirements specified in
during civil engineering work. the various design drawings will also
Transformers and cooling fans are
be verified.
located outside the building. The • Pre-installation verifications.
power transformers are placed on All tests will be performed or super-
solid foundations. The transformer • Verifications during installation. vised by ABB commissioning engi-
is connected to the indoor AC filter neers and ABB experts.
by cables. If required, conventional • Equipment tests.
AC switchgear with breakers, etc., All tests under high-voltage condi-
Testing of subsystems of the HVDC
can be added to connect the power tions, terminal tests and transmis-
system.
transformer to the AC network. sion tests will be directed by ABB’s
• Subsystem functional (circuit) test manager with the assistance of
Both the civil engineering works and ABB commissioning engineers, but
tests.
equipment installation are normally under full operational responsibility
contracted to a local contractor, who • Start up of auxiliary systems, of the customer’s operational orga-
will perform the works under the including building systems. nization.
supervision of ABB engineers.

ABB 53
DESCRIPTIONS

5.1.12 Availability • the design must allow mainte- in the figure below. Since the num-
When designing a modern HVDC nance activities (forced and sched- ber of installed items of equipment
Light® transmission system, one of uled) to be performed with minimum is less for an HVDC Light® scheme
the main design objectives is to min- curtailment of the system operation compared with a conventional
imize the number of forced outag- HVDC scheme, the target value for
• scheduled maintenance that availability is equal or even better for
es and the down time due to forced
requires link shut-down must be HVDC Light® compared with con-
outages and scheduled mainte-
minimized ventional HVDC.
nance.
• the scheduled maintenance time
The HVDC Light® transmission is
has been kept low thanks to few
designed according to the follow-
mechanical parts
ing principles in order to assure high
reliability and availability: Maintainability is increased by the
introduction of redundancy up to
• simple station design
an economically reasonable level.
• use of components with proven The maintenance times, especial-
high reliability ly for work that requires curtailment
of the HVDC Light® transmission,
• automatic supervision should be minimized by the use of
exchange modules or components
• use of redundant and/or back-up
instead of repair.
control systems and equipment
such as measurements, pumps, etc. Observed energy availability from
two of our projects in commercial
• available spare units
operation is above 98%, as shown

Availability, Cross Sound and Murray Link


99,4

99,2

99

98,8

98,6
Availability in %

Guarantee Value

98,4
Average availability

98,2

98

97,8

97,6

97,4
December

August
March

April

September
June
November
July

January

July
May
February
June

October

October

November

December
August

September

2003 Year & month 2004

1) October 2003, Average availability is decreased by annual preventive maintenance in MurrayLink

54 ABB
DESCRIPTIONS

5.1.13 Maintainability The quality assurance program pro- - Decibel scale


The unavailability due to sched- vides the tool to ensure that the Sound is measured as the sound
uled maintenance depends both work in different phases is executed pressure level (usually referred to as
on the design of the HVDC Light® in a predictable manner. the sound level) and is stated as a
transmission and on the organiza- decibel (dB) value, which represents
Several systems for feedback of a value related to a certain reference
tion of the maintenance work. The
experience are used, including fol- sound pressure level.
modern design, which incorporates
low-up and testing during equipment
extensive redundancies for essen-
manufacturing (type testing and rou- It is normal that the value used is
tial systems such as cooling sys-
tine testing for equipment, factory corrected for the spectral sensitiv-
tems, duplicated control systems
system testing for control equipment), ity of the human ear; this is known
and station service power, allows
installation, commissioning and com- as dB(A).
most of the maintenance work to be
mercial operation. The included
done with no interruption of opera-
equipment is in line with applicable - Sound requirements
tion. This work will require 200-400
IEC standards. The most common sound require-
man-hours per year, depending on
ments for the areas outside the sta-
the size of the transmission system.
tion area are set at the following
As an example, the remaining main- 5.1.15 Acoustic noise locations.
tenance effort for a 350 MW mod-
A major part of the equipment that
ule that requires curtailment of the • At the station fence.
generates noise is located inside the
HVDC transmission is estimated (typically 60 dB)
buildings, and this noise can be suc-
to require approximately 160 man-
cessfully attenuated by appropriate-
hours per station every second year. • At the property line.
ly designed acoustic properties of
The time to do this work is estimated
the walls and roof. The station layout • At a given distance /radius from
to be 60 hours, the necessary work-
should also be adapted to fit acous- the station;
force will then be six persons, and
tical requirements.
the minimum scheduled unavailabil- • At the nearest residences.
ity will then be a maximum of 0.35% There may be several different (typically 40 dB)
on average per year. However, with sound requirements for an HVDC
increased staff and proper planning, Light® station. - Acoustic design
the maintenance work can be per- To ensure that noise requirements for
formed in a shorter time. Identifying which of them are valid
the plant will be met, it is necessary
and may be critical for the design
to design and construct the station
of the plant is a major task at the
5.1.14 Quality Assurance/ correctly from the very beginning.
beginning of the acoustic design
Standards process.
ABB has developed an effective
The sound requirements usually
and efficient quality assurance pro-
apply to the areas outside the sta-
gram complying with ISO 9001 and
tion, the space inside the station,
other applicable standards and
and the inside of the buildings/enclo-
an environment management sys-
sures.
tem complying with ISO 14000. The
know-how acquired by long experi- Sound requirements for the outside
ence with HVDC projects of differ- area may vary depending on state
ent kinds, solid technical resources regulations, or on local regulations
and closely developed relations with or industry practices.
key sub-suppliers, ensures reliable
products in compliance with speci-
fications.

ABB 55
DESCRIPTIONS

The process of acoustic design All significant sound sources in the If a fault is detected in the active
of the plant includes the following plant are included in such a model. system, the standby system takes
steps: The most essential elements of sta- over control, becoming the new
tion surroundings which may influ- active system. The faulty system
• Identify the noise requirements for ence the sound propagation from (the previously active system) should
the plant the station are also included in the be checked before being taken into
model. The 3-D model makes it pos- operation as the standby system.
• Identify the real constraints for the
sible to study different possible lay-
noise design
outs and different configurations of - System changeover
• Influence the layout design so that the equipment for the future station. The system switchover commands
the noise requirements will be fulfilled The result of the prediction may be can be initiated manually or auto-
shown as a sound contribution map matically. The manual commands
• Predict the expected noise level for the area around the station and are initiated by a push-button in the
around the equipment used and the can also be supplemented with the active system, while the automatic
entire plant tables containing the exact sound commands are initiated by exten-
level values for the chosen locations sive internal supervision functions
• Decide the maximum permissible
of interest. of the subsystems, or on a protec-
noise levels for the most significant
tion order.
pieces of equipment
5.2 HVDC Light® control and
The switchover commands are
• Decide the acoustic properties protection
always initiated from the currently
of the enclosures, buildings and
active system. This switchover phi-
expected attenuation screens 5.2.1 Redundancy design and
losophy means that a fault or testing
changeover philosophy
• Work out the verification proce- activity in the standby system can-
dures for final compliance with the - Active/standby systems not result in an unintentional swi-
noise requirements for the plant The redundant PCP systems are tchover. Furthermore, a manual swi-
designed as duplicated systems act- tchover order to a faulty standby
- Noise sources in an HVDC Light® ing as active or hot standby. At any system is not possible.
station time only one of the two control sys-
Typical noise sources in the HVDC tems is active, controlling the con-
Light® station are: verter and associated equipment.

• Power transformers; The other system, the standby sys-


tem, is running, but the “outputs”
• Cooling fans for cooling systems;
from that system are disabled.
• Ventilation openings and facades
of the equipment buildings;

• PLC filter components;

• Air-conditioning equipment.

- Prediction model
The calculation for prediction of the
sound contribution from the HVDC
Light® equipment is usually done in
a three-dimensional (3-D) model of
the plant and its surroundings. The
3-D model is created in the qualified
software, which is also used for cal-
culations.

An example of a 3D model and a result map for a typical HVDC Light® station.

56 ABB
DESCRIPTIONS

- Changeover from protections - Protection redundancy • Duplicated inputs and comparison


Control problems may initiate pro- Both AC and DC protection trip in the software.
tection actions. To improve the over- actions are active in both systems,
all reliability performance of the but only some of the DC protections, • Supervision of data bus communi-
HVDC Light® transmission by avoid- i.e. those that may have been initi- cations.
ing unnecessary trips in connec- ated due to a control problem, can
• Supervision of auxiliary power.
tion with control problems, some of order a changeover.
the converter and pole protections Any detected failures in the control
initiate a fast changeover from the Both systems are equipped with
and protection hardware will result in
active to the standby control system. identical protections fed from sepa-
a request for changeover, which will
Before a trip order is issued from rate primary sensors where practi-
be executed if a standby system is
the DC protection system, a sys- cally possible.
available and ready to take over.
tem changeover is performed if the
fault type could have been caused - Self supervision
by a control failure, and the inher- Inadvertent trips are avoided as 5.2.2 Converter control
ent delay in such a changeover is each system is provided with exten- Each HVDC Light® converter is able
acceptable. If the redundant control sive self-supervision, which further to control active and reactive power
system is healthy and successfully enhances system security. Examples independently by simultaneously
re-establishes undisturbed power of methods for self-supervision are: regulating the amplitude and phase
transfer on the HVDC link, the pro- angle of the fundamental compo-
• Inherent supervision in measuring
tections in both systems will reset nent of the converter output voltage.
systems (e.g. DCCT, DCOCT).
and not time out to trip. To achieve The general control scheme of one
proper coordination between block/ • Comparison in the software converter station is shown in the fig-
trip orders, both time and level sep- between actually measured zero ure below.
aration is used. sequence components and zero
sequence components calculated
in the software in the case of three-
phase current measurement.

=U =WP1
-T1

=WT =WZ -U1


i_dc_p

i_pcc tap_pos i u_dc_p


AC_BRK_OPEN
Q1 -T1
PCC -T2

-T11 -T11
=WP2
u_pcc u_f
u_dc_n
i_dc_n

-U1 -T1

Valve Control
tap_pos u_pcc i_pcc i u_f u_dc_p u_dc_n i_dc_p i_dc_n

INTERFACE
AD conversion, Anti-Aliasing Filters, Resampling, Decimation Filters &
Normalization

U_PCC_Alpha/Beta
I_PCC_Alpha/Beta
U_DC_pos/neg
INC_TAP_POS Y_Alpha/Beta
U_Alpha/Beta
CURRENT CONTROL
DEC_TAP_POS Delta_IREF_Q AC Current Control
Voltage Seq. Estimator
P_PCC_REF
DQPLL
Q_PCC_REF PQU ORDER CONTROL DC Voltage Balance Ctrl
Pac Ctrl I_MAX_TEMP 3PWM
$P_PCC_REF
Qac Ctrl Sync. PLL
$Q _PCC_REF Uac Ctrl 3Ix
U_PCC_REF TCC
Temp. Limitation p_ref u_dq_pos
UDC_CTRL
q_ref u_dc_pos/neg
Runback Control CURRENT ORDER
UAC_CTRL
DCVC_enable CONTROL i_dc_pos/neg
AC_BRK_OPEN UDCCOL
Runback i_d_ref
UACCOL
OUT_TEMP
Runback
udc_ref DCVC
PQ2IDQ
i_q_ref
Control block diagram with
simple Single-line diagram
BLOCK block
BLOCK

ABB 57
DESCRIPTIONS

5.2.3 Current control - OPWM - UACCOL


The purpose of current control is to The OPWM (optimal pulse width The AC voltage-dependent current
allow the current through the con- modulation) function must provide order limiter provides control to keep
verter phase reactors and the trans- two functions: calculate the time to the AC filter bus voltage within its
former to be controlled. The con- the next sample instant, and mod- upper and lower limits.
trol operates in a coordinate system ulate the reference voltage vector.
phase synchronous to the funda- OPWM is a modulation method that - PQ2idq
mental frequency in the network, is used for harmonic elimination and The pq2idq calculates the dq cur-
referred to as a dq-frame. The con- for reducing converter losses. The rent orders with respect to the posi-
trol reference object is the trans- harmonic elimination concentrates tive-sequence voltage.
former current. the harmonics to a narrow band-
width, which is beneficial for the filter
design. Thus, the filters can be made 5.2.5 PQU order control
- Voltage sequence decomposition
The voltage sequence decomposi- smaller. The converter losses are The PQU order control object must
tion provides the true positive volt- reduced by switching the valves less mainly calculate and provide the cur-
age sequence, u_dq_pos, for the frequently when the current is high. rent order control block with active
phase-locked loop, the quasi-pos- Using pulse width modulation makes and reactive power references.
itive sequence, u_pcc_p, and the it possible to achieve rapid control of
true negative sequence voltage, u_ the active and reactive power. This - Active power control/frequency
is beneficial when supporting the AC control
pcc_n, for the AC current control
network during disturbances. The The active power control controls
feed-forward voltages.
control is optimized to have a rapid the active power flow by generat-
and stable performance during AC ing a contribution to the DC voltage
- DQPLL and SYNCPLL
system fault recovery. reference depending on the active
The phase-locked loop (PLL) is used
power reference. In isolated mode,
to synchronize the converter con-
the frequency control will control the
trol with the line voltage. The input of
5.2.4 Current order control frequency of the isolated network.
the PLL is the three-phase voltages
The current order control provides
measured at the filter bus.
the reference current for the cur- - Reactive power control
rent control and acts as an interface The reactive power control controls
- AC current control
between the PQU order control that the reactive power.
Controls the currents through the
operates on RMS values and the
converter phase reactors and pro-
momentary control signals within the - AC voltage control
vides a symmetrical three-phase
current control. The AC voltage control controls the
current to the converter, regardless
AC voltage.
of whether the AC network voltage
- DCVC and UDCCOL
is symmetrical or not. The current
The DC voltage control provides - Tap changer control
order is calculated from the power
control of the DC voltage using the The tap changer control is used to
order.
current order. keep the filter bus voltage, and thus
the modulation index, within suit-
able limits.

58 ABB
DESCRIPTIONS

5.2.6 Protections - Protective actions and effects Set lockout of the AC circuit-breaker
Alarms If a trip order has been sent to the
- Protection system philosophy
Alarms are generally generated as AC circuit-breaker, an order to lock
The purpose of the protection sys-
a first action by some protections to out the breaker may also be exe-
tem is to cause a prompt removal of
notify the operator that something is cuted. This is done to prevent the
any element of the electrical system
wrong, but the system will still con- breaker from closing before the
from service in the event of a fault,
tinue to run as before the alarm. operator has checked the cause of
for example when it suffers a short
the trip. The operator can manually
circuit or when it starts to operate
Transient current limiter reset the lockout of the breaker.
in any abnormal manner that might
cause damage or otherwise inter- The transient current limiter stops
sending pulses to the IGBTs corre- Pole isolation
fere with the effective operation of
sponding to the phase with high cur- The pole isolation sequence involves
the rest of the system. The protec-
rent. The pulses are re-established disconnecting the DC side (posi-
tive system is aided in this task by
when the current returns to a safe tive and negative poles) from the DC
the AC circuit-breakers, which dis-
level (i.e. temporary blocking on a cable. This is done either manual-
connect the AC network from the
per phase basis). Overvoltage pro- ly during normal shutdown or auto-
converters and are capable of de-
tection temporarily stops the pulses matically by order from protections
energizing the converter transformer,
in all three phases simultaneously. in the case of faults which require
thereby eliminating the DC current
that the DC side is disconnected, for
and voltage.
Permanent blocking example a cooling water leakage.
The protection system has exten- Permanent blocking means that a
sive self-supervision. Any failures turn-off control pulse will be sent to Start breaker failure protection
detected in the control and protec- all IGBTs and they will stop conduct- At the same time as a trip order is
tion hardware result in appropriate ing immediately. sent to the AC breaker, an order
actions depending on the sever- may also be sent to start the breaker
ity of the fault. Failures may result AC circuit-breaker trip failure protection. If the breaker does
in a request for changeover to the Tripping of the AC circuit-breaker not open properly within a certain
redundant system, which is execut- disconnects the AC network from time, the breaker failure protection
ed if there is a standby system ready the converter equipment. orders re-tripping and/or tripping of
to take over. the next breaker.
This prevents the AC system from
When a protection operates, the feeding a fault on the valve side of
following fault clearing actions are the converter transformer.
taken depending on the type of fault:
In addition, the removal of the AC
• Transient current limitation by voltage source from the convert-
means of temporary blocking of the er valves avoids unnecessary volt-
converter control pulses on a per age stresses, especially when the
phase basis valves have suffered severe current
stresses.
• Permanent blocking of the converter
All protective trip orders to the AC
• Tripping of the AC circuit-breakers
circuit-breakers energize both the A
and B coils of the breakers through
two redundant devices. Two redun-
dant auxiliary power supplies also
feed the redundant trip orders.

ABB 59
DESCRIPTIONS

Protection overview
The figure below shows the protec-
tions included in an HVDC Light®
station

PROTECTION OVERVIEW

-T11
-L1

-Q11

-U1
V1 -T1

-T1
-L1 -X1 -T3

-Q1 -T11 V2

-T2
-Z11

-L1 -T11

-C1 -Q11

-U1

-L1 -R1

-T1

TRANSFORMER CONVERTER BUS CONVERTER DC ABNORMAL


DIFFERENTIAL DIFFERENTIAL OVER CURRENT VOLTAGE
PROTECTION PROTECTION PROTECTION PROTECTION
TRANSFORMER
AC BUS AC TERMINAL DC CABLE
AND MAIN AC BUS
ABNORMAL SHORT CIRCUIT FAULT
OVER CURRENT
VOLTAGE PROTECTION INDICATION
PROTECTION
PROTECTION
TRANSFORMER VALVE
PROTECTIVE AC FILTER SHORT CIRCUIT
RELAYS CAPCITOR PROTECTION
UNBALANCE
CIRCUIT BREAKER PROTECTION VALVE
FAILURE
AC FILTER CURRENT
PROTECTION
RESISTOR/REACTOR DERIVATIVE
OVERLOAD PROTECTION
PROTECTION
IGBT
POSITION
MONITORING

VALVE
COOLING
PROTECTION

60 ABB
DESCRIPTIONS

5.3 Control and protection All critical parts of the system Developments in the field of elec-
platform - MACH 2 are designed with inherent paral- tronics are extremely rapid at pres-
lel redundancy and use the same ent, and the best way to make sure
5.3.1 General redundancy and switchover prin- that the designs can follow and ben-
ciples as used by ABB for HVDC efit from this development is to build
To operate a conventional HVDC
applications since the early 1980s. all systems based on open inter-
or an HVDC Light® transmission as
faces. This can be done by using
efficiently and flexibly as possible, a Because of the extensive use of international and industry stan-
powerful, flexible and reliable con- computers and micro-controllers, it dards, wherever possible, as these
trol and protection system is clearly has been possible to include very standards mean long lifetimes and
required. The control system should powerful internal supervision, which ensure that spare and upgrade parts
not impose any limitations on the will minimize periodic maintenance are readily available.
control of the main system appara- for the control equipment.
tus, such as the converter valves,
and should not prevent the introduc- As a consequence of placing all
tion of new, advanced, control and functions in computers and micro-
protection functions. controllers, the software will play the
most important role in the design of
To fulfill the current and future the system. By using a fully graphi-
requirements of the HVDC and cal functional block programming
HVDC Light® control and protection language and a graphic debugging
system, ABB has developed a fully tool, running on networked standard
computerized control and protection computers, it is possible to establish
system using state-of-the-art com- a very efficient development and test
puters, micro-controllers and digi- environment to produce high quality
tal signal processors connected by programs and documentation.
high-performance industrial stan-
dard buses and fiber optic commu- To achieve high reliability, quality is
nication links. built into every detail from the begin-
ning. This is assured by careful com-
The system, called MACH 2, is ponent selection, strict design rules
designed specifically for convert- and, finally, by he extensive testing
ers in power applications, meaning of all systems in a real-time HVDC
that many compromises have been simulator.
avoided and that both drastic vol-
ume reductions and substantial per-
formance improvements have been
achieved.

ABB 61
DESCRIPTIONS

5.3.2 Control and protection The redundant systems act as active Thanks to the high performance of
system design or hot standby. At any time, only one the MACH 2 equipment, the type of
The HVDC Light® Control and pro- of the two control systems is active, hardware and system software used
tection system, built with the MACH controlling the converter and asso- for an ABB HVDC Light® control sys-
2 equipment, consists of HMI, main ciated equipment. The other sys- tem are the same as in a classic
computer systems, I/O systems and tem, the standby system, is running, HVDC control system. In fact, only
valve control (valve base electronics), but the outputs from that system the application software differs. This
typically arranged as shown in the are disabled. If a fault is detected is also the case with the valve control
figure below. in the active system, the standby (valve base electronics), including
system takes over control, becom- the communication to the IGBT firing
The design criterion for the control ing the active system. The internal unit, although a more advanced firing
system is 100% availability for the supervision giving switchover orders logic is needed for the IGBTs.
transmission system. The way to includes auxiliary power supervision,
achieve this is that no single point program execution supervision (stall
of failure should interrupt operation. alarm), memory testing and supervi-
Therefore, redundancy is provided sion of the I/O system communica-
for all system parts involved in the tion over the field buses. The spe-
power transfer of the HVDC Light® cial ABB feature of using appropriate
transmission. protections for switchover between
systems further increases the con-
trol system reliability.

System Operator Maintenance


Gateway servers Workstation workstation
computer
A
B

LAN

PCPA PCPB
Main computer Main computer
System A System B

Field Bus Systems A Field Bus Systems B

I/O I/O Valve Valve I/O I/O


system 1A system nA Control A Control B system 1B system nB
Valve Interface

Mach 2 Control and Protection system structure

62 ABB
DESCRIPTIONS

5.3.3 Main Computers The main computers for control and


To take full advantage of the rapid protection include one ore more PCI
electronic developments, the main boards, PS803, as an interface with
computers of the Mach 2 system the I/O system. The PS803 boards
are based on high-performance have a general-purpose processor
industrial computer components. and four DSPs for high-performance
This ensures that ABB can take full computing. Control and protection
advantage of the extremely rapid functions are normally running in the
developments in the field of micro- main computer, but the DSPs on the
processors and always design the PS803 boards are used for high-
control and protection system for the performance applications. As an
highest possible performance. example, the firing control system,
including converter sequences, runs
The main computers are built in a single PS803 board.
around COM Express modules with
Intel® Core™ Duo processors, giv- The main computer may also include
ing the main computers very good one or more measuring boards for
performance and, at the same time, optical current measurement.
very low power consumption. The
low power consumption means
that the main computers can be
designed with self-convection cool-
ing. Dust problems connected with
forced air-cooling are therefore
avoided.

The main computers are designed


for mounting in the rear-mounting
plane of control and protection cubi-
cles. The operating status of the
High performance DSP board PS803
computers/systems is clearly indi-
cated on the front on all computers.

5.3.4 I/O system


The process interface of the redun-
dant main computer systems is the
I/O systems, placed in the control
and protection cubicles or in sepa-
rate cubicles or boxes. The field bus
connections between the different
levels of equipment (cubicles) are
always optical to avoid any possible
interference.

Main Computer

ABB 63
DESCRIPTIONS

5.3.5 Communication used for the connection of adjacent ABB has experience with all types of
The communication inside the con- racks in the cubicle. Fiber optic com- telecommunication, ranging from 50
verter station uses a hierarchy of munications on eTDM are used for and 300 bps radio links, via the very
serial buses. A general rule for the communication outside of the cubi- common 1200, 2400 or 9600 bps
use of serial buses is that only indus- cles or control room. communication links using analogue
try (or international) standard buses voice channels, up to digital 64 kbps
Any application (software function) or higher speed links obtained with
are used. This means that no propri-
in a control, protection or I/O system optical fiber connections.
etary buses are used. The objective
can readily communicate with other
is to ensure a long economic lifetime
applications, simply by connecting
for the buses and to ensure that the
their signals respectively to send and 5.3.6 Software
components used to build the bus
receive software function blocks.
structures are available from indepen- - Application software development
dent sources. (HiDraw)
eTDM bus Most application software for the
The eTDM bus used in the Mach 2 HVDC control and protection system
- Local communication
system is primarily a high-speed, sin- is produced using a fully graphical
• The local area network used in the
gle fiber, optical data bus for digitized code-generating tool called HiDraw.
pole is based on the well-known IEEE
analog measurements. Due to the HiDraw is very easy to use, as it is
802.3 (Ethernet).
high-speed-performance of the bus, it based on the easiest possible drag-
• The SCADA LAN is used to transfer has been possible to include the bina- and-drop method. It is designed to
data between the control and protec- ry data from the CAN bus of the I/O produce code either in a high level
tion main computers and the various systems as an “overlay” on the eTDM language (PL/M or ANSI standard C)
clients on the network, OWS, GWS. bus communication. or in assembly language. For func-
tions not available in the comprehen-
The eTDM bus used is characterized
Field Buses sive library (one for each type of pro-
by large data carrying capacity, very
CAN Bus cessor board), it is very easy to design
low latency and “no jitter” operation.
ISO standard buses, ISO 11898, also a new block and to link this to the
This is absolutely essential when used
known as CAN (Control Area Net- schematic with a simple name ref-
to feed the HVDC controls with high
work), are used for communication erence. HiDraw can be run on any
bandwidth measured signals. Each
with binary type I/O devices (discon- industry-standard Windows-compati-
eTDM bus is able to transmit over
nectors and breakers etc.), within the ble computer.
300,000 samples per second (one
I/O systems. The CAN bus combines sample every 3 µS). A schematic drawn in HiDraw con-
a set of properties important for use in
sists of a number of pages. One page
an HVDC station. - Remote communication specifies cycle times and the execu-
If station-to-station communication is tion order of the other pages. HiDraw
• It is a high-speed bus with an effi-
included, it is handled by communica- includes a first on-screen plausibil-
cient short message structure and
tion boards in the main computer of ity check of the drawn schematic and
very low latency.
the pole control and protection (PCP) automatic cross-reference genera-
• There is no master/slave arrange- cubicles. This pole-level communica- tion between the pages. As output,
ment, which means that the bus is tion gives a more robust design than a HiDraw produces code and a “make”
never dependent on the function of centralized station-level telecommuni- file ready to be processed.
any single node to operate correctly. cation unit. The communication is syn-
chronous and conforms to ISO3309 The next step in the workflow is to run
• CAN also have efficient CRC (HDLC frames) for high security. this make file (on the same computer)
checksum and hardware features to which means invoking the necessary
remove a faulty node from the network. If available, a LAN/WAN type of com- compiler/assembler and link locate
munication can also be used which programs (these are usually obtained
The CAN communication within an eliminates the need for special com- from the chip manufacturers e.g. Intel
I/O system is performed via the back- munication boards and provides even and Analog Devices). The result is a
plane of the I/O racks. Extension higher performance. file that is ready to be downloaded
cables with shielded, twisted pairs are
from the computer to the target and
stored in the flash PROMs.

64 ABB
DESCRIPTIONS

UPDATE_FOSYS
29 EXT

Telecom Analog
Telecom Analog SEND
RECEIVE
From Other: SYSTEM SPEED_REF_FOSYS To Other: SYSTEM
Application ID: SEQ
Application ID: SEQ Block No: 2
Block No: 2 Board ID: PCID
Board ID: PCID Enable Hysteresis: 1.0
Cyclic update: 10

TRUE

39 EXT
EDS_IN_OPERATION
29 EXT
SPEED_REF_ENABLE &

48 EXT
SPEED_RT_UP_NORMAL SPEED_REF_RT_UP
SPEED_RT_UP_STARTUP
48 EXT

11 EXT
CONV_DEBLOCKED

48 EXT
MAX_SPEED_REF_LIMIT

PCDA_SPEED_REF SPEED_REF ( PUBLIC )


29 EXT 39

48 EXT
MIN_SPEED_REF_LIMIT

0.0 p.u.

SPEED_RT_DOWN_NORMAL SPEED_REF_RT_DW
48 EXT

48 EXT
SPEED_RT_DOWN_STARTUP

-1
q

Send PCI DPM


Board ID: PCIA
OMEGA_REF_PU DSP1A : 51
Board type: PS801
0.000556 rpm/pu
Area: DSP1
Signal No: 9
Note: speed reference in p.u.
motor shaft speed 1800 rpm <=> 1.0 pu

Design checked by Rev Ind Sheet

Name: SPEED_CTRL B Nordstrom FUNCTIONAL DIAGRAM Troll A


Motor Speed Control Drawing checked by Rev Ind Sheet

H Blom SEQUENCES 38
Proc.type: MainCPU 00
1JNL100089-652
Drawn by Iss by Dept Year Week Cont

Rev Ind Revision Appd Year Week


Type: TASK P Karreby ABB POWER SYSTEMS AB TCC 02/44 39

HiDraw schematic

- Hierarchical design
HiDraw supports hierarchical design
in order to ease understanding of
complex applications and to encour-
age top-down design. Hierarchical
design means an organization of the
drawings in a hierarchical structure,
where symbols on the top layer rep-
resent functionality in rough outlines.
Double-clicking on such a symbol
opens a “hierarchical drawing” with
more details of that symbol, etc. (see
figure below).

ABB 65
DESCRIPTIONS

STEPPING
CURRENT
LOGIC POWER_ORDER
CUR_ORD CUR_ORD_LIM
166
ORDER

LIMITER
FUNCTION

UD

UD

CALC

Name: Func BASE DESIGN


M Hyttinen FUNCTIONAL DIAGRAM
Space for explanation
G Odnegård OWN FUNCTION 00
1000
Proc.type: 02
Type: TASK H Alerman LKC 95 05 4870 210-A 1002

14 UPDATE_FOSYS
B_INTG_OSYS
20 SEND
PO_IO_OSYS IOMAX_TYPE5
20 22 SLFR11
20 PPTS_OSYS 49 OVERLOAD_LIM IO_MAX IO_MAX_TOSTA
1 TYPE5_INIT
22 THYR_TEMPLIM 16 RUNB1
SEND RECEIVE SLFW1 16
TYPE5_UPDATE >1
PO_IO4_FOP ( PUBLIC ) INIT_TYPE5 ( PUBLIC )
34 PO_IO4 45 >1 23
BFOW6
JT
14 UPDATE_TYPE5 ( PUBLIC ) 31
SEND RECEIVE PO_IO_FOSYS ( PUBLIC ) RB1
13 RUNB2 RUNW1
32 RB1_FOSTA >1
PO_IO PO_IO_FOP RECEIVE 19
33
BFOW7 IOMAX ( PUBLIC ) 34
IO_MAX_FOSTA SLFR9

SEND RECEIVE B_INTG_FOSYS ( PUBLIC )


51 STEP_TEST ( PUBLIC ) 35 RUNI1
51 B_INTG B_INTG_FOP SLFB1 13 RB2
RUNB3
BFOW8 SLFR10 19
RB2_FOSTA >1
LEAD SLFB2
25 &
SEND RECEIVE STEP_TRIGG SLFB3
UD_FILT UD_FOP ( PUBLIC )
26 27 STEP_TIME RUNB6
BFOW9 >1
STEP_SIZE TESR3
SLFR2
SEND RECEIVE POWER_ORDER
34 PACK
THYR_TEMP_UPDATE
PPTS PPTS_FOP 49 RUNB4
34 THYR_TEMP_UPDATE_FOSTA >1
19
BFOW10 RUNW2
TYPE3_DP MODMAX
16 TYPE34_DP
16 TYPE4_DP
SEND RECEIVE
BFOW11 UD
IO_CFC_FOP ( PUBLIC ) TYPE34_NS 52
IO_CFC 22 TYPE34_NORM
35 PROJECT_PWR
11
BFOW14 15 PWR_DIR_NORM
BPO_REF_FOSYS ( PUBLIC ) 45 RUNB7
45 BPO_REF BPO_REF_FOP BPO_RAMP_FOSYS ( PUBLIC ) 45 11 SLF_BPO_MAX SLFMAX 13 PROT_ORD_P_BAL
BPO_RAMP SEND RECEIVE BPO_RAMP_FOP SLF_MAX ORD_P_BAL P_BAL ( PUBLIC )
45 11 SLFR1 MODMIN 44 >1
BFOW1 BFOW2 ORD_P_BAL_FOSTA
UPDATE_SLF 19
32 40
32 NEW_SLF_VALUE RUNR2
SLF_INPROG PO_IO1 PO_IO2 ( PUBLIC ) TYPE5_IOMAX
30 PO_IO 34 16
BFOB1 SLF 11 RB1_IOMAX
FINAL_REF CUR_ORD_LIM 31 32 33
29 11 RB2_IOMAX
29 FINAL_RAMP
BPO_REF_OSYS
BFOW12 SEND RECEIVE B_CONT_ON
BPO_RAMP_OSYS 23
BFOW4 SLF_BPO_MIN SLFMIN
11
BFOW13 11 SLF_MIN
49 THYR_TEMP_LIM
SLFR8 PO_IO_TOSTA ( PUBLIC ) 19 THYR_TEMP_LIM_FOSTA
1 19
BFOB2 BPO_REF_FOSTA ( PUBLIC ) 45 THYR_TEMPLIM ( PUBLIC ) 33
BPO_RAMP_FOSTA ( PUBLIC ) 45 PO_IO_ABS ( PUBLIC )
29 31 32 IO_CFC
SEND 36 52 35 RUNR1
RECEIVE IO_CFC_FOP
21
BFOW5
BFOW3 PO_IO ( PUBLIC )
20 21 30
36 41 42
BFOB3

Name: BIPFOP BASE DESIGN BASE DESIGN


M Hyttinen FUNCTIONAL DIAGRAM Name: SLF M Hyttinen FUNCTIONAL DIAGRAM Name: RUNBACK BASE DESIGN
signals to and from other pole Stepping Logic Function
M Hyttinen FUNCTIONAL DIAGRAM
G Odnegård OWN FUNCTION 00
21 G Odnegård POLE POWER CONTROL 33 runback handling
Proc.type: 510 02 G Odnegård OWN FUNCTION 22
00
H Alerman LKC 95 05 4870 210-A 22 H Alerman LKC 95 05 4870 210-A 34
Type: SUBTASK Type: SUBTASK
Type: SUBTASK H Alerman LKC 95 05 4870 210-A 23

STOL0_3
1 STOL_DISABLE ( PUBLIC ) 63
&
ID_100_PU
15 ID_OVER_AMB
ICONT ENABLE_START_STOL
61 STOL0_2 STOL0_9 START_STOL
&
LIM_OFS

SR6
HI_LIM
SR1
&
PO_10
SR8 INTG 64
1
SR12
64 INTG_FOSYS

SR5
LO_LIM
STOL0_1
EN_STOL STOL0_5
1
&
UP_TIME_CONSTANT TIME_CONST ENABLE_LEV

STOL0_14
DOWN_TIME_CONST STOL0_13
UPDATE_FOSYS_OLL
58
RESET_COUNTER

START_STOL

STOL_RUNNING_FOSYS STO3B1
64 STOL_RUNNING STOL_RUNNING_TOSYS ( PUBLIC )
& S Q 1 64
STOL_RUNNING_IND ( PUBLIC )
1 65
STOL_NOT_RUNNING_FOSYS STO3B3
1 R

RESET

RESET STOL_TIME_TOSYS ( PUBLIC )


1 64

64 STOL_TIME_FOSYS Itop Table 03


SR7 Y
STOL_TIME STOL_LIM ( PUBLIC )
SR11 SR4 63

SEC_PER_TIC SR10 SR3 SR9 X


ZERO_PER_TIC
time
OLD_STOL_TIME

Name: STOL BASE DESIGN


M Hyttinen FUNCTIONAL DIAGRAM
short time overload limiter calc.
G Odnegård POLE POWER CONTROL 02
62
Proc.type: 510
Type: SUBTASK H Alerman LKC 95 05 4870 210-A 63

Hierarchical symbols and drawings

5.3.7 Input to system studies trol and protection, with the normal
Code generation is performed by definition files producing code in C,
means of the code definitions in PL/M, or DSP-assembler, are used
an HDF file (HDF = HiDraw Defini- simply by switching the definition files
tion Format). Each graphical symbol used to generate FORTRAN code.
in a symbol library has a name, and
The electromagnetic transient pro-
the name is used to define a piece
gram PSCAD (previously PSCAD
of code in a separate HDF file. This
(previously EMTDC) can use this
open ABB approach is very advanta-
FORTRAN code directly, and an
geous in several aspects. One is from
exact representation of the con-
the HVDC Light® system point of
trol and protection functions is thus
view. The HiDraw drawings for con-
achieved in the digital system studies.

66 ABB
DESCRIPTIONS

5.3.8 Debugging facilities There are also a number of support- 5.3.9 Human-machine interface
For debugging, a fully graphical ing functions, such as single or mul- (HMI)
debugger, known as HiBug, operat- tiple stepping of tasks (one HiDraw A well-designed and flexible human-
ing under Windows is used. page is normally a task) and coordi- machine interface (HMI) is clear-
nated sampling of signals. ly essential when it comes to more
HiBug allows the operator to view demanding application areas such
several HiDraw pages at the same The fact that HiBug allows inspec-
as HVDC Light® power transmission.
time and look at any internal soft- tion of signals while the application
To avoid human errors, all parts of
ware “signal” in real time simply by system is running makes it very use-
these systems must also be easy
double-clicking on the line that rep- ful not only for debugging but also to
to use. The HMI must be able to
resents the signal. Parameters can facilitate maintenance.
announce alarms and perform oper-
be changed easily by double-click- ator controls in a safe and reliable
Because the debugger works in the
ing on their value. way. Incorrect operator actions due
Windows environment, it is also pos-
sible to transfer sets of signal val- to a bad HMI are not acceptable and
For fault tracing, it is easy to fol-
ues to other Windows-compatible could be very costly.
low a signal through several pages
because when a signal passes from programs, such as Excel, for further
The requirements for tools of this
one page to another, a double click analysis.
type are therefore strict. For exam-
on the page reference automatically ple, several thousands of measured
All these development and debug
opens the new page and allows the values, indications and alarms of dif-
tools are, of course, supplied to all
trace to continue immediately on the ferent types need to be handled. All
customers of our plants, to facili-
new page. changes in the state of these signals
tate their maintenance and future
improvements of their HVDC Light® must be recorded with high-time
control and protection systems. resolution for accurate real-time and
post-fault analysis. Time resolution
down to one millisecond between
the stations is often required.

The new generation of integrated


HMIs adopted by ABB in MACH 2™,
the station control and monitoring
(SCM) system, employs the most
advanced software concepts with
regard to system openness and flex-
ibility, as well as ergonomic aspects.
A number of power companies have
made valuable contributions to this
work.

HiBug

ABB 67
DESCRIPTIONS

Distributed over an Ethernet LAN,


the SCM system comprises sev-
eral operator workstations (OWSs)
and SQL servers. The Windows NT
based OWSs are characterized by
high performance and an open soft-
ware architecture based on the lat-
est trends in data engineering sup-
porting TCP/IP, SQL and OPC.

The SCM system integrates a large


number of features such as:

• Control of the HVDC Light® from


process images, see the figure
below

• Sequential Event Recorder, SER,

See the figure below

• Archiving of events SLD for a typical HVDC Light® station

• Powerful alarm handling via list


windows

• Effective user-defined data filtering

• Flexible handling of both on-line


and historical trends

• On-line help functions and direct


access to plant documentation

• TFR analysis

• Remote control via Dispatch Gateway

• Instant access to standard appli-


cations such as e-mail, word pro-
cessing, spreadsheet, Internet

• Automatic performance report


generation developed with the most
versatile graphical package
Event list

68 ABB
DESCRIPTIONS

5.3.10 Maintenance of MACH 2 Another example of integrated self- As the TFR is an integrated part of
supervision is the switch control unit. the HVDC control system, it also
- General
In this unit, the outputs to the break- runs in both the active and the
As far as possible, the ABB control
ers, etc., are continuously monitored standby systems.
equipment is built to avoid periodic
to detect failure of the output circuits
maintenance and provide the short- Any standard software analysis pro-
of the board. Very short repair times
est possible repair times. Due to its gram interpreting the COMTRADE
are facilitated by the self-supervi-
redundant design, the maintenance format, (IEEE C37.111-1991), can be
sion, but another contribution to this
of the control equipment does not used for post-fault analysis of the
is the high degree of integration in all
require any periodic shutdown of stored TFR records.
units. As an example, the entire con-
any main circuit equipment.
trol computer, including the convert-
Maintenance is minimized by the er firing control system, etc., is eas-
extensive use of self-supervision ily changed in a couple of minutes,
built into all microprocessor-based as the whole system is a single-rack
electronic units and the ability to unit with only a handful of connec-
check all measured values dur- tion cables.
ing operation without disturbing the
operation. - Transient fault recorder (TFR)
The TFR integrated in the HVDC
The internal supervision of micro- control system, as a part of the con-
processor-based systems includes trol and protection software, is an
auxiliary power supervision, program invaluable tool for maintenance and
execution supervision (stall alarm), out-performs old-fashioned external
memory test (both program and TFR’s, as it always gives a correct
data memory) and supervision of the representation of the important inter-
I/O system communication over the nal control signals. The TFR continu-
field buses. ously samples the selected channels
to be monitored for fault analysis.
The operation of the field buses is
There is a predefined selection of
monitored by a supervisory function
protection and control signals, but
in the pole control and protection
also a number of channels which
system, which continuously writes to
are available to be chosen freely by
and reads from each individual node
the operator. This makes it possi-
of the system. Any detected fault
ble to monitor any internal signal in
results in an alarm and switchover to
the control and protection software.
the standby system.
Important external signals can, of
course, also be connected for moni-
toring by the TFR.

ABB 69
DESCRIPTIONS

5.4 HVDC Light® Cables

5.4.1 Design
The cables are designed to meet the
current and voltage ratings for the
specified power transmission capac-
ity and for the specified installation
conditions.

5.4.2 Land cable


A general cutaway drawing of the
land cable design is shown below

Conductor
Aluminum or copper

Conductor screen
Semi-conductive polymer

Insulation
Cross linked HVDC polymer

Insulation screen
Semi-conductive polymer

Metallic screen
Copper wires

Swelling tape

Aluminum laminate

Outer covering/Sheath
Polyethylene

70 ABB
DESCRIPTIONS

5.4.3 Submarine cable


A general cutaway drawing of the
submarine cable design is shown
below

Conductor
Aluminum or copper

Conductor screen
Semi-conductive polymer

Insulation
Cross linked HVDC polymer

Insulation screen
Semi-conductive polymer

Swelling tape

Lead alloy sheath

Inner jacket
Polyethylene

Tensile armor
Galvanized steel wires

Outer cover
Polypropylene yarn

ABB 71
DESCRIPTIONS

5.4.4 Deep-sea submarine


cable
A general cutaway drawing of the
deep-sea submarine cable design
is shown below

Conductor
Aluminum or copper

Conductor screen
Semi-conductive polymer

Insulation
Cross linked HVDC polymer

Insulation screen
Semi-conductive polymer

Swelling tape

Lead alloy sheath

Inner jacket
Polyethylene

Tensile armor
Two layers of tensile armors
(laid in counter helix)
Galvanized steel wires

Outer cover
Polypropylene yarn

72 ABB
DESCRIPTIONS

5.5 General design of cables - Metallic screen The outer sheath on land cables is
Typical HVDC Light® cable designs Copper wire screen, for land cables, normally a thermoplastic polyethyl-
are previously shown. with cross-section design for fault ene (PE) sheath or an extruded PVC
currents. sheath. PE is a harder material offer-
ing better mechanical protection,
5.5.1 Cable parts - Metallic sheath and is the first choice for most appli-
A lead alloy sheath is provided for cations.
- Conductor
submarine cables.
The shape of the conductor is round PVC sheaths are classified as halo-
and built up of compacted stranded A metal-polyethylene laminate may gen material and are flame-retar-
round wires or, for large cross-sec- be provided for land cables. The dant.
tions, concentric layers of keystone- laminate is bonded to the polyethyl-
shaped wires. ene, which gives excellent mechani- The surface of the outer sheath may
cal properties. be provided with a thin conduc-
On request, the conductor can be tive layer, which is simultaneous-
water sealed, in order to block longi- ly extruded with, and thus strong-
- Inner jacket (for submarine
tudinally water penetration in case of ly bonded to, the non-conductive
cables)
damage to the cable underlying jacket. This is useful to
A polyethylene sheath is extruded
over the lead sheath. The polyeth- ensure the physical integrity of the
- Insulation system cable in the post-installation test.
ylene sheath provides mechanical
The HVDC polymeric insulation sys-
and corrosion protection for the lead
tem consists of:
sheath.
5.5.2 Standards and
- Conductor screen Recommendations
- Tensile armor (for submarine
- Insulation cables) - Cigré, ELECTRA No. 171 Recom-
The tensile armor consists of gal- mendations for mechanical tests
- Insulation screen vanized round steel wires close to on sub-marine cables
each other twisted round the cable.
The material, specifically developed - Cigré Technical Brochure Ref No
The tensile armor is flooded with
for HVDC cables, is of the highest 219 “Recommendations for test-
bitumen in order to obtain effective
quality, and the insulation system is ing DC extruded cable systems for
corrosion protection.
triple-extruded and dry-cured. The power transmission at a rated volt-
sensitive interface surfaces between The tensile armor is needed when age up to 250 kV”
insulation and conductive screens the cable is laid in the sea. The ten-
are not exposed at any stage of the - IEC 60228 Conductors of insulat-
sile armor also offers mechani-
manufacture of the insulation sys- ed cables
cal protection against impacts and
tem. abrasion for a cable that is not bur- - IEC 60229 Tests on extruded
ied to safe depth in the seabed. over-sheaths which have a special
High-quality material handling sys-
tems, triple extrusion, dry-curing protective function.
- Outer sheath or serving
and super-clean insulation materials
The outer serving for submarine - IEC 60287 Electric cables -
guarantee high-quality products.
cables consists of two layers of poly- Calculation of the current rating
propylene yarn, the inner one impreg-
nated with bitumen. The polypropyl- - IEC 60840 Power cables with
ene yarn is a semi-wet covering. extruded insulation and their
accessories

ABB 73
DESCRIPTIONS

5.5.3 Testing Peak values of UP1, UP2,S and UP2,O 5.5.3.2 Routine and sample test
Tests are performed according to are defined as maximum voltages Routine testing will be performed on
combinations of relevant parts from to ground when a suitable charge is each manufactured length of cable.
transferred from the impulse genera-
- Cigré recommendations for tor to the cable. - Voltage test, UT during 15 minutes.
mechanical testing of submarine
cables published in Electra 171 For land cables also:
5.5.3.1 Type test
- IEC 60840, Power cables with - DC-testing of non-metallic sheath,
The table below summarizes the
extruded insulation and their according to IEC 60229.
status of type-tested HVDC Light®
accessories cable systems (up to year 2007). If The following sample tests are per-
type tests have already been per- formed (generally on one length from
- Cigré “Recommendations for test-
formed, they need not to be repeat- each manufacturing series):
ing DC extruded cable systems for
ed for cables within the scope of
power transmission at a rated volt-
approval as defined by Cigré. - Conductor examination
age up to 250 kV”, published in
Cigré Technical Brochure Ref No Voltage Conductor Number of - Measurement of electrical resis-
219 U0 area performed tance of the conductor
[kV] [mm2] type tests
HVDC Light® Cable test voltages 80 95 2 - Measurement of thickness of insu-
U0 UT UTP1 LIPL UP1 SIPL UP2,S UP2,O 80 300-340 5 lation and non-metallic sheath
kV kV kV kV kV kV kV kV 80 630 2
80 148 116 160 185 143 165 92 150 95 4
- Measurement of diameters on
150 278 217 304 350 275 320 175 150 1000-1600 11
320 555 435 573 660 541 630 350 150 2000 2
complete cable (for information)
320 1200 2
Definitions Total 28 - Hot set test of insulation material

U0 Rated DC voltage. The electrical type tests are com-


posed of following test items: 5.5.3.3 Post-installation test
UT Load cycle test voltage = - Voltage test, UTP1 during 15 min.
1.85U0 at test at works and - Mechanical tests: Bending of land
Factory Acceptance Test. cables as per IEC 60840. Subma- For land cables also:
rine cables as per Cigré Recom-
UTP1 Polarity reversal test voltage mendations, ELECTRA No. 171 – DC-testing on non-metallic sheath,
= 1.45U0, also for clause 3.2. according to IEC 60229
post-installation testing.
- Load Cycle Test
UP1 Lightning impulse voltage
> 1.15LIPL. Not applicable - Superimposed impulse voltage
for HVDC Light® System. test: Switching Surge Withstand
Test, at UP2,S and UP2,O
UP2,S Same polarity switching
impulse voltage > 1.15SIPL.

UP2,O Opposite polarity switching


impulse voltage

74 ABB
DESCRIPTIONS

5.5.4 Cable drums


Land cables are typically transported on cable drums.

Cable lenghts in metres on Wooden drum K14 - K30 and Steel drum St 28 - St 34

Cable
Wooden drum Steel drum
dia.

mm K14 K16 K18 K20 K22 K24 K26 K28 K30 St 28 St 30 St 32 St 34 St 35 St 36 St 37 St 38 St 39 St 40 St 43


36 570 760 850 1155 1560 2090 2860 4000 5800 4600 6080 7670 9350 9930 11130 11750 13000 13600 14900 17700
38 470 630 820 1075 1290 1780 2490 3600 4900 4300 5335 6830 8420 8970 10110 10700 11200 12500 13100 15700
40 450 610 690 900 1100 1560 2220 3200 4400 3700 5085 6030 7530 8050 9130 9680 10250 11400 12000 14500
42 430 500 660 870 1070 1510 2160 3100 3950 3600 4485 5850 6820 7320 8350 8880 9400 9900 11100 12900
44 340 480 530 720 1030 1310 1830 2800 3900 3000 3830 5100 6000 6475 7400 7940 8450 8900 9500 11740
46 330 450 510 690 860 1260 1780 2430 3460 2900 3695 4500 5800 6260 6720 7200 7690 8100 8600 10840
48 310 360 480 660 820 1070 1540 2360 3130 2450 3175 4340 5170 5600 6040 6490 6950 7400 7900 9960
50   360 400 550 670 1020 1490 2090 2820 2410 3120 3880 4670 5090 5520 5960 6410 7300 7800 9330
52   340 385 530 670 910 1280 1830 2750 2300 2990 3720 4490 4890 5300 6730 6165 6600 7060 8500
54   320 360 505 640 870 1280 1775 2450 1880 2520 3200 3920 4300 4680 5080 5490 5900 6340 7690
56   260 360 475 610 825 1090 1715 2380 1840 2470 3130 3850 4220 4600 5600 4990 5400 5810 7120
58   240 275 385 510 720 1040 1550 2090 1800 2410 2740 3410 3775 4140 4510 4900 5300 5710 6560
60     275 365 480 680 990 1490 2030 1760 2050 2680 3340 3690 4050 4050 4430 4800 5200 6450
62     250 365 480 680 460 1270 1770 1390 1940 2540 2850 3170 3500 3850 4200 4570 4570 5730
64     250 345 450 545 825 1270 1730 1350 1890 2180 2780 3100 3420 3420 3675 4100 4470 5220
66     240 345 370 545 825 1230 1535 1320 1575 2125 2710 2710 3020 3340 3675 4000 4010 5100
68     240 320 345 515 785 1025 1475 1280 1530 2060 2340 2640 2940 3250 3250 3580 3910 4610
70       250 345 515 670 1030 1475 1280 1530 2060 2340 2640 2940 2960 3250 3600 3910 4610
72       250 345 480 635 985 1260 1010 1490 1750 2290 2290 2580 2880 3190 3190 3510 4190
74       250 320 400 635 985 1260 980 1440 1690 1950 2230 2510 2800 2800 3100 3420 4080
76       230 320 400 625 810 1210 940 1170 1640 1890 2160 2430 2430 2720 3000 3010 3630
78       230 320 400 600 810 1210 910 1130 1590 1830 2090 2090 2350 2635 2635 2920 3520
80         230 325 500 810 1015 910 1130 1360 1830 1840 2090 2350 2370 2635 2920 3520
82         230 325 470 775 1015 885 1090 1310 1540 1780 2030 2030 2295 2560 2560 3140
84         210 300 470 660 1015 880 1090 1310 1540 1780 2030 2030 2295 2310 2560 3140
86         210 300 470 615 965 660 1050 1270 1490 1720 1720 1970 2220 2220 2495 3050
88         210 275 440 615 840 630 820 1220 1430 1430 1660 1890 1890 2140 2140 2670
90         210 275 440 615 840 630 820 1220 1430 1430 1660 1670 1890 2140 2140 2670
92             355 585 800 610 785 970 1380 1380 1600 1600 1835 1835 2070 2580
94             325 585 800 610 785 970 1180 1380 1390 1600 1835 1835 2070 2340
96             325 485 755 585 755 930 1130 1330 1330 1540 1540 1760 1760 2240
98             325 485 640 580 755 930 1130 1330 1330 1540 1540 1760 1760 2240
100             325 455 640 580 755 930 1130 1140 1330 1340 1540 1760 1760 2240
102                   560 725 900 1080 1080 1280 1280 1490 1490 1710 1930
104                   560 725 900 1080 1080 1280 1280 1490 1490 1710 1930
106                   385 530 690 860 1040 1040 1230 1230 1430 1430 1860
108                   380 530 690 860 1040 1040 1230 1230 1430 1430 1860
110                   380 530 690 860 1040 1040 1230 1230 1430 1430 1860
112                   365 505 660 820 990 990 990 1180 1180 1370 1570
114                   360 505 660 820 820 990 990 1180 1180 1370 1570
116                   360 505 660 820 820 990 990 1180 1180 1370 1570
118                   345 480 625 785 780 950 950 1120 1120 1120 1500
120                   340 480 625 785 780 950 950 950 1120 1120 1500
122                   340 480 625 785 780 790 950 950 1120 1120 1320
124                   325 450 595 595 740 740 900 900 1070 1070 1250
126                   325 450 595 595 740 740 900 900 900 1070 1250
128                   325 450 450 595 740 740 750 900 900 1070 1250
130                   325 450 450 595 740 740 750 900 900 1070 1250
132                   305 305 430 560 560 700 700 850 850 850 1190
134                   305 305 430 560 560 700 700 850 850 850 1190

ABB 75
DESCRIPTIONS

Sizes and weights of wooden drums


  Drum type
  K14 K16 K18 K20 K22 K24 K26 K28 K30
Shipping volume m3 2.14 2.86 3.58 5.12 6.15 7.36 10.56 13.88 17.15
Drum weight incl. battens kg 185 275 320 485 565 625 1145 1460 1820
a Diameter incl battens mm 1475 1675 1875 2075 2275 2475 2700 2900 3100
b Flange diameter mm 1400 1600 1800 2000 2200 2400 2600 2800 3000
c Barrel diameter mm 800 950 1100 1300 1400 1400 1500 1500 1500
d Total width mm 982 1018 1075 1188 1188 1200 1448 1650 1800
e Spindle hole diameter mm 106 106 131 131 131 131 132 132 132

Sizes and weights of steel drums


  Drum type
  St 28 St 30 St 32 St 34 St 35 St 36 St 37 St 38 St 39 St 40 St 43
Shipping volume m3 20.6 23.5 26.6 28.9 31.6 33.4 35.2 37 38.9 40.9 47.1
Drum weight incl. battens kg 1500 1700 2200 2600 2700 2800 3000 3100 3300 3500 4000
a Diameter incl battens mm 2930 3130 3330 3530 3630 3730 3830 3930 4030 4130 4430
b Flange diameter mm 2800 3000 3200 3400 3500 3600 3700 3800 3900 4000 4300
c Barrel diameter mm 2000 2000 2000 2000 2000 2000 2000 2000 2000 2000 2000
d Total width mm 2400 2400 2400 2400 2400 2400 2400 2400 2400 2400 2400
e Spindle hole diameter mm 150 150 150 150 150 150 150 150 150 150 150

Steel drums with outer diameters up


to 4.5 m are available, but transport
restrictions have to be considered.
Special low-loading trailers and per-
mits from traffic authorities may be
required, depending on local regula-
tions and conditions. Special wood-
en drums with a larger barrel diam-
eter or larger width (up to 2.5 m) are
also available, if needed.

5.5.5 Installation - Submarine cables Submarine cable installation may


The cable can be installed on all include the following items of work:
- Land cables
types of seabed, including sand,
The installation of cable systems - Route survey
sediment, rocks and reefs. For pro-
consists mainly of cable pulling,
tection against anchors and fish-
clamping of cable and accessories - Calculation of tensile forces
ing gear, the cable can be buried by
as well as mounting of accessories.
various methods, or can be protect- - Installation plans
The installation design is an impor-
ed by covers.
tant part of the cable system design. - Cable laying vessels
ABB certified erectors perform the The cables can be laid either sepa-
high quality work necessary for the rately or close together, and pro- - Marine works
reliable operation of a cable system tection can be provided by means
during its lifetime. - Burial of the cable
of water jetting or ploughing, either
simultaneously with or after the - Equipment for cable pulling
ABB has long and good experience
cable laying.
of traditional installation technologies
- Directional drilling on shore
including direct burial, duct, shaft,
trough and tunnel, but also trench- - Post-installation testing
less technologies including directional
drilling, pipe jacking and others.

76 ABB
DESCRIPTIONS

5.5.6 Repair tem. A directly buried cable can eas-


ily be opened and repaired in a short
- Fault Location
time by installing a new section of
It is important to perform a fairly fast
cable and two joints.
pre-location of a fault for the repair
planning. The converter protections The basic requirement in this case
identify the cable that is faulty. If pos- would be to have some spare joints,
sible, the pre-location could start spare cable and jointing tools avail-
with an analysis of the records in the able in the customers’ stores.
converter stations in order to give a
rough estimate the location of the
fault. 5.5.7 Accessories
The only accessories required for
- Pre-location of fault with pulse HVDC Light® cable systems are
echo meter or fault location bridge cable joints and terminations.
A fault in the HVDC cable is pre-
located with an impulse genera- - Cable terminations
tor (Thumper) and a Time Domain Terminations are used to connect
Reflection meter (TDR). The thump- the cables to the HVDC convert-
er creates high voltage impulses, Cable termination for 150 kV HVDC
ers. The terminations are mounted
Light® cables.
and the time required for the pulse indoors in the converter stations.
to travel forth and back is measured The termination is made up of sever-
with the TDR. al prefabricated parts.

A fault in the HVDC cable can also


- Cable joints
be located with a fault location
Joints for HVDC Light® are based on
bridge. The fault location bridge is a
field molding or pre-fabricated joint
high-precision instrument based on
techniques.
the Wheatstone measuring bridge,
and a measurement with the fault The field molding method uses a
location bridge should give approxi- mini process to restore the insu-
mately the same distance to the fault lation, and it gives a joint with the
as the TDR. same diameter as the cable.

- Accurate location of a fault Pre-fabricated joints are used to


The principle for this method is to connect the cables. The design
use the powerful thumper to create involves a screwed conductor con-
a flashover at the fault. The sound nector and a pre-fabricated rub-
from the flashover and/or the mag- ber joint body. The body has a built-
netic field from the pulse is picked in semi-conductive deflector and a
up with microphones or with spikes non-linear resistive field control. The
connected to a receiver. one-piece design of the joint body
reduces the amount of sensitive
- Repair time interfaces and simplifies pre-testing
An HVDC Light® cable repair on a of the joint bodies.
land cable should take less than a
week, even if a section has to be
removed and replaced in a duct sys-

ABB 77
DESCRIPTIONS

Pre-fabricated 150 kV HVDC Light® cable joint.

5.5.8 Auxiliary equipment 5.5.10 Reliability of 150 kV MurrayLink Land Cable, Victoria
HVDC Light® Cable projects – South Australia
Other auxiliary equipment may be
137 km HVDC Light® Cables
used for the cable system, e.g.: Cross Sound Submarine Cable, with 1400 mm2 alu-
Connecticut – Long Island
- Cable Temperature Sensing minum conductor
83 km HVDC Light® Cables
Systems
with 1300 mm2 cop- 223 km HVDC Light® Cables
- Forced Cooling Systems per conductor with 1200 mm2 alu-
minum conductor
7 pcs Flexible Cable Joints
5.5.9 Environmental 400 pcs Stiff Cable Joints
4 pcs Cable Terminations
The cable does not contain oil or
4 pcs Cable Terminations
other toxic components. It does not Delivery year 2002.
harm living marine organisms. Due Delivery year 2002
to its design, the cable does not Operating experience very satisfac-
emit electrical fields. The magnetic tory. No faults. Operating experience very satisfac-
field from the cable is negligible. The tory. One fault attributed to external
cable can be recovered and recy- damage.
cled at the end of its useful life.

78 ABB
SYSTEM ENGINEERING

6 System Engineering

6.1 Feasibility study The main circuit design includes the The auxiliary system design includes
During the development of a new following design studies: the design of auxiliary power, valve
project, it is common to perform a cooling, air-conditioning system and
- Main circuit parameters fire protection system.
feasibility study in order to identify
any special requirements to be met - Single-line diagram The layout of the main circuit equip-
by the system design. ABB can sup-
ment is determined by the electro-
ply models of HVDC Light® trans- - Insulation coordination
mechanical design, and the station
missions in the PSS/E simulation
- AC and DC filter design design specifies buildings and foun-
tool. For unusual applications, ABB
dations.
can perform feasibility studies using - Radio interference study
a detailed control representation in
PSCAD (previously EMTDC). 6.3 Validation
- Transient overvoltages
- DPS
For new applications, it is advisable - Transient currents
The performance of the combined
that ABB performs pre-engineering
- Calculation of losses AC and DC system is validated in a
studies, which include main circuit
dynamic performance study (DPS).
design, system performance and
- Availability calculation The setup includes a detailed repre-
station layout design.
sentation of the main circuit equip-
- Audible noise study ment, and the control model is a
6.2 System design copy of the code that will be deliv-
The control system design specifies
A suitable rating of converters and ered to site (see 5.3.7 above). The
the requirements to be met by the
DC cables is determined to satisfy AC systems are represented with a
control and protection system. Dur-
the system requirements. The HVDC detailed representation of the imme-
ing the detailed design, the control
Light® system is adapted to fulfill the diate vicinity and an equivalent
system characteristics are optimized
requirements for the project. Some impedance for the rest of the AC
to meet the requirements.
engineering work needs to be done system. Typical faults and contin-
to define the system solution, equip- The equipment design specifies the gencies are simulated to show that
ment and layout needed. requirements of all the main circuit the total system responds appropri-
apparatus. The rating includes all ately.
The flow diagram below illustrates
relevant continuous and transient
the types of engineering required.
stresses. - FST
During the factory system test (FST),
the control equipment to be deliv-
Ê
>LiÊ
ëiVˆvˆV>̈œ˜Ê œV>ÊÀiµÊ ered is connected to a real-time sim-
ulator. Tests are performed accord-
iVÌÀœ ‡ÊÊ ing to a test sequence list in order to
>ˆ˜Ê
ˆÀVՈÌÊ ÊÊ -Ì>̈œ˜Ê£Ê
iV…>˜ˆV>ÊÊ validate that the control and protec-
`iÈ}˜Ê -ˆ˜}i‡ˆ˜iÊ`ˆ>}À>“Ê `iÈ}˜Ê
`iÈ}˜ÊÊ
tion system performs as required.
Ê
-«iVˆvˆV>̈œ˜Ã


ÊÃÞÃÌi“Ê µÕˆ«“i˜Ì Ê
ÀiµÕˆÀi“i˜ÌÃÊ `iÈ}˜Ê
- Site test
iVÌÀœ ‡Ê‡Ê -Ì>̈œ˜ÊÓÊ During the commissioning of
iV…>˜ˆV> Ê `iÈ}˜Ê

œ˜ÌÀœÊÃÞÃÌi“ÊÊÊ `iÈ}˜Ê
the converter stations, tests are
`iÈ}˜Ê -«iVˆvˆV>̈œ˜ÃÊ performed according to a test
sequence list in order to validate the
ÕÝÊÃÞÃÌi“Ê`iÈ}˜ œV>Ê
ÀiµÕˆÀi“i˜ÌÃÊ
specified functionality of the system.
Õ݈ˆ>ÀÞÊ«œÜiÀ
6>ÛiÊVœœˆ˜}Ê

ABB 79
SYSTEM ENGINEERING

6.4 Digital Models

- Load flow
During load flow calculations, the
converters are normally represent-
ed with constant active power and a
reactive power that is situated with-
in the specified PQ-capability, in the
same way as generators. A load flow
model of a VSC HVDC transmis-
sion is included in the latest version
of PSS/E.

- Stability
The dynamic model controls the
active power to a set-point in one
station and calculates the active
power in the other station, including
current limitations. The reactive power
- Reference cases or the AC voltage is controlled inde-
The figure above shows a compari- pendently in each station. ABB can
son between site measurement and supply dynamic models of HVDC
PSCAD (previously EMTDC) simu- Light® transmissions in the PSS/E
lation of the DC voltage at a load simulation tool.
rejection of 330 MW. Even though
the transient is fast, the behavior is - Dynamic Performance
quite similar. Detailed evaluation of dynamic per-
formance requires an extensive
PSCAD (previously PSCAD (previ-
ously EMTDC) model that can be
supplied to the customer during the
project stage.

80 ABB
REFERENCES

7 References

7.1 Projects 7.3 CIGRÉ/IEEE/CIRED material


Gotland HVDC Light® Project DC Transmission based on VSC

Directlink HVDC Light® Project HVDC Light® and development of VSC

Tjæreborg HVDC Light® Project VSC TRANSMISSION TECHNOLOGIES

Eagle Pass HVDC Light® Project HVDC Light® experiences applicable


to power transmission from offshore
Cross Sound Cable HVDC Light® wind power farms
Project
Cross Sound Cable Project – second-
MurrayLink HVDC Light® Project generation VSC technology for HVDC

Troll A Precompression Project MurrayLink – the longest HVDC


underground cable in the world
Estlink HVDC Light Project
®

Power system stability benefits with


Valhall Re-development Project
VSC DC transmission system
NordE.ON 1 offshore wind connection
New application of voltage source
Caprivi Link interconnector converter HVDC to be installed on
the Troll A gas platform
7.2 Applications
The Gotland HVDC Light® project -
HVDC Light® as interconnector experiences from trial and commercial
operation
HVDC Light® for offshore
CIGRE WG B4-37-2004
Wind power and grid connections

7.4 General
For further material please refer to
ABB HVDC Light® on the Internet:

http://www.abb.com/hvdc

ABB 81
INDEX

8 Index

1 Introduction 5 5 Descriptions 41
1.0 Development of HVDC technology– 5.1 Main circuit 41
historical background 5 5.1.1 Power transformer 41
1.1 What is HVDC Light®? 5 5.1.2 Converter reactors 42
1.2 Reference projects 6 5.1.3 DC capacitors 43
1.2.1 Gotland HVDC Light®, Sweden 6 5.1.4 AC filters 43
1.2.2 Directlink, Australia 7 5.1.5 DC filters 46
1.2.3 Tjæreborg, Denmark 8 5.1.6 High-frequency (HF) filters 47
1.2.4 Eagle Pass, US 9 5.1.7 Valves 48
1.2.5 Cross Sound Cable, US 9 5.1.8 Valve cooling system 50
1.2.6 MurrayLink, Australia 10 5.1.9 Station service power 52
1.2.7 Troll A, Norway 11 5.1.10 Fire protection 52
1.2.8 Estlink HVDC Light® link, Estonia - Finland 12 5.1.11 Civil engineering work,
1.2.9 Valhall Re-development Project 13 building and installation 53
1.2.10 NordE.ON 1 offshore wind connection - 5.1.12 Availability 54
Germany 14 5.1.13 Maintainability 55
1.2.11 Caprivi Link Interconnector 15 5.1.14 Quality Assurance/Standards 55
5.1.15 Acoustic noise 55
2 Applications 16 5.2 HVDC Light® control and protection 56
2.1 General 16 5.2.1 Redundancy design and changeover
2.2 Cable transmission systems 16 philosophy 56
2.2.1 Submarine cables 16 5.2.2 Converter control 57
2.2.2 Underground cables 16 5.2.3 Current control 58
2.3 DC OH lines 17 5.2.4 Current order control 58
2.4 Back-to-back 17 5.2.5 PQU order control 58
2.4.1 Asynchronous Connection 17 5.2.6 Protections 59
2.4.2 Connection of important loads 17 5.3 Control and protection platform - MACH 2 61
2.5 HVDC Light® and wind power generation 17 5.3.1 General 61
2.6 Comparison of AC, conventional 5.3.2 Control and protection system design 62
HVDC and HVDC Light® 17 5.3.3 Main Computers 63
2.7 Summary of drivers for choosing an 5.3.4 I/O system 63
HVDC Light® application 21 5.3.5 Communication 64
2.7.1 AC Network Support 21 5.3.6 Software 64
2.7.2 Undergrounding by cables 22 5.3.7 Input to system studies 66
2.7.3 Required site area for converters 22 5.3.8 Debugging facilities 67
2.7.4 Environmentally sound 22 5.3.9 Human-machine interface (HMI) 67
2.7.5 Energy trading 22 5.3.10 Maintenance of MACH 2 69
2.8 HVDC Light® cables 22 5.4 HVDC Light® Cables 70
2.8.1 Long lifetime with HVDC 22 5.4.1 Design 70
2.8.2 Submarine cables 22 5.4.2 Land cable 70
2.8.3 Underground Cables 24 5.4.3 Submarine cable 71
5.4.4 Deep-sea submarine cable 72
3 Features 25 5.5 General design of cables 73
3.1 Independent power transfer and 5.5.1 Cable parts 73
power quality control 25 5.5.2 Standards and Recommendations 73
3.2 Absolute and predictable power 5.5.3 Testing 74
transfer and voltage control 25 5.5.3.1 Type test 74
3.3 Low power operation 25 5.5.3.2 Routine and sample test 74
3.4 Power reversal 25 5.5.3.3 Post-installation test 74
3.5 Reduced power losses in connected 5.5.4 Cable drums 75
AC systems 25 5.5.5 Installation 76
3.6 Increased transfer capacity in the 5.5.6 Repair 77
existing system 25 5.5.7 Accessories 77
3.7 Powerful damping control using P and 5.5.8 Auxiliary equipment 78
Q simultaneously 26 5.5.9 Environmental 78
3.8 Fast restoration after blackouts 26 5.5.10 Reliability of 150 kV HVDC Light®
3.9 Islanded operation 26 Cable projects 78
3.10 Flexibility in design 26
3.11 Undergrounding 27 6 System Engineering 79
3.12 No magnetic fields 27 6.1 Feasibility study 79
3.13 Low environmental impact 27 6.2 System design 79
3.14 Indoor design 27 6.3 Validation 79
3.15 Short time schedule 27 6.4 Digital Models 80

4 Products 28 7 References 81
4.1 General 28 7.1 Projects 81
4.1.1 Modular concept 28 7.2 Applications 81
4.1.2 Typical P/Q diagram 28 7.3 CIGRÉ/IEEE/CIRED material 81
4.2 HVDC Light® modules 30 7.4 General 81
4.2.1 - 80 kV modules 30
4.2.2 - 150 kV modules 32 8 Index 82
4.2.3 - 320 kV modules 33
4.2.4 Asymmetric HVDC Light® 35
4.2.5 Selection of modules 36
4.3 HVDC Light® Cables 36
4.3.1 Insulation 36
4.3.2 Submarine Cable Data 36
4.3.3 Land Cable data 39