Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
Baguio 79 26 59 15 60
Olongapo 86 30 75 24 60
Manila 88 31 77 25 70
Puerto Princesa 89 32 70 25 85
Tacloban 91 33 79 26 75
Cebu 90 32 77 25 75
Iloilo 90 32 75 24 75
Bacolod 86 30 75 24 75
Zamboanga 91 33 77 25 80
Davao 90 32 75 24 75
General Santos 90 32 73 23 75
Cagayan de Oro 90 32 72 22 75
°F – 32/ 1.8 = °C
°C x 1.8 + 32 = °F
The design outdoor condition of Davao City based on the climatic conditions of
the Philippines is assumed to be 90°F DB (Dry Bulb) and 75°F WB (Wet Bulb).
The design indoor conditions are 78°F DB (Dry Bulb), 65°F WB (Wet Bulb) and
58% RH (Relative Humidity). By locating the two points on the Psychrometric
Chart, the remaining design data can be identified and filled in.
PSYCHROMETRIC CHART
65 °F WB (Wet Bulb)
50 % RH
Grains of Moisture/
Pound of Dry Air 125
Design Requirements:
Type of Establishment :
L1
L2
L3
L4
L5
L6
L7
L8
L9
L10
L11
L12
L14
L15
L16
The design cooling load estimate of each Floor Level and the methods to
calculate these loads will be properly discussed and reflected later in this
chapter.
1.0 Heat Gains Calculations Through Building Walls, Ceilings, Doors, Windows,
and Flooring
Q = u A ΔT (Equation 53)
where;
Q = Heat quantity in Btu per hour
Heat Gains Calculations Through Building Walls, Ceilings, Doors, Window Glass,
and Flooring
Q = u A ΔT (Equation 53)
where;
Q = Heat quantity in Btu per hour
Q = u A ΔT (Equation 53)
Q A = u A (to – ti)
U A = _________ 1_______________
_1_ + _1_ + _1_ + _1_ + _1_ + _1_
fi C1 C2 a C3 fo
where;
fi = 1.65, Heat transfer from inside surface
UA = _________ 1_______________
_1_ + _1_ + _1_ + _1_ + _1_ + _1_
1.65 4.40 1.00 1.10 2.82 6.00
Q FL = UA A (to – ti)
where;
A north = 1,570.96 m²
A south = 82.13 m²
thus;
Q FL = UA A (to – ti)
Q FL = 29,758.4 Btu/hr
where;
Width = 3.00 m
A glass = 40 m x 3.0 m
A glass = 120.0 m²
A glass = 1,291.2 ft ²
6 7 ~ 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
AM AM AM AM AM AM AM PM PM PM PM PM PM PM PM PM PM PM MN
-2 -2 ~ 0 2 4 7 9 12 13 14 14 13 12 10 8 6 4 3 2
°F °F °F °F °F °F °F °F °F °F °F °F °F °F °F °F °F °F °F
Table 6 contains the cooling load temperature difference (CLTD) for conduction
through glass. Similar to the wall and roof CLTD tables, this data is based on the
same indoor temperature of 78°F, and outdoor temperature of 90°F, and a daily
temperature range of 21°F. Assuming the conditions of this requirement meet the
conditions of the table, the CLTD for 2:00 PM (1400 hours) is 13.
Part 3- Glass Transmission and Conduction, Page 23, Cooling Load Estimate
Handbook, The Trane Company, La Crosse, Wisconsin.
Summer Summer
Description
(No Shade) (Indoor Shade)
U U
Single Glass 1.04 0.81
Insulating Glass Double
3/16” –in., air space 0.65 0.58
¼” – in. Air space 0.61 0.55
½” – in. Air space 0.56
½” – in. Air space, low emittance coating 0.52
e = 0.20 0.38 0.37
e = 0.40 0.45 0.44
e = 0.60 0.51 0.48
Insulating Glass Triple
¼” – in. Air space 0.44 0.40
½” – in. Air space 0.39 0.36
Storm Windows
¼” – in. Air space 0.50 0.48
½” – in. Air space 0.50 0.48
By obtaining all the data taken from the Tables and specified design information
and requirements, we can design and calculate for conduction heat gains though
glass,
Q = u A CLTD
where;
U = 0.81___Btu ___
(hr) (ft²) (°F)
AFL = 1,291.2 ft ²
CLTD = 13 °F
Q = U A CLTD
Q = 12,550.46 Btu/hr
where;
Q = Heat quantity in Btu per hour
Type of Shading
Venetian Blinds Roller Shade
Nominal Solar Opaque Translucent
Thickness Trans.
Medium Light Dark White Light
Clear 3/32 ~1/4 0.87 ~0.80
Clear 1/4 ~1/2 0.80 ~0.71
Clear Pattern 1/8 ~1/2 0.87 ~0.79 0.64 0.55 0.59 0.25 0.39
Heat Absorbing 1/8 __
Pattern
Tinted 3/16~7/32 0.74 ~0.71
Heat Absorbing 1/8 ~1/2 0.46
Heat Absorbing 1/8 __ 0.57 0.53 0.45 0.30 0.36
Pattern
Tinted 3/16~7/32 0.59 ~0.45
Heat Absorbing __
or Pattern 0.44~0.30 0.54 0.52 0.40 0.28 0.32
Heat Absorbing 1/8 0.34
Heat Absorbing __ 0.29 ~0.15
or Pattern 0.24 0.42 0.40 0.36 0.28 0.31
Reflective
Coated
Glass
SC = 0.30 0.25 0.23
= 0.40 0.33 0.29
= 0.50 0.42 0.38
= 0.60 0.50 0.44
Table 9 Maximum Solar Heat Gain Factors (SHGF), Btu/ (hr) (ft ²)
Part 3- Glass Transmission and Conduction, Page 24, Cooling Load Estimate
Handbook, The Trane Company, La Crosse, Wisconsin.
40° N Latitude
Month N NE/NW E/W SE/SW S Horizon
Solar Time, Hr
N Room 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19
Latitude Construction
LIGHT 0.05 0.70 0.65 0.65 0.74 0.81 0.87 0.91 0.91 0.88 0.84 0.77 0.80 0.92 0.27
N MEDIUM 0.07 0.73 0.66 0.65 0.73 0.80 0.86 0.89 0.89 0.86 0.82 0.75 0.78 0.91 0.24
HEAVY 0.09 0.75 0.67 0.66 0.74 0.80 0.86 0.89 0.88 0.85 0.80 0.73 0.76 0.88 0.23
LIGHT 0.02 0.55 0.76 0.75 0.60 0.39 0.31 0.28 0.27 0.25 0.23 0.20 0.16 0.12 0.06
NE MEDIUM 0.02 0.56 0.76 0.74 0.58 0.37 0.29 0.27 0.26 0.24 0.22 0.20 0.16 0.12 0.06
HEAVY 0.04 0.57 0.77 0.74 0.58 0.36 0.28 0.26 0.25 0.23 0.21 0.19 0.16 0.11 0.06
LIGHT 0.01 0.45 0.71 0.80 0.77 0.64 0.43 0.29 0.25 0.23 0.20 0.17 0.14 0.10 0.06
E MEDIUM 0.02 0.47 0.72 0.80 0.76 0.62 0.41 0.27 0.24 0.22 0.20 0.17 0.14 0.11 0.06
HEAVY 0.03 0.48 0.72 0.80 0.75 0.61 0.40 0.25 0.22 0.21 0.19 0.16 0.14 0.10 0.06
LIGHT 0.01 0.29 0.56 0.74 0.82 0.81 0.70 0.52 0.35 0.30 0.26 0.22 0.18 0.13 0.08
SE MEDIUM 0.02 0.30 0.57 0.74 0.81 0.79 0.68 0.49 0.33 0.28 0.25 0.22 0.18 0.13 0.08
HEAVY 0.04 0.31 0.57 0.74 0.81 0.79 0.67 0.48 0.31 0.27 0.23 0.20 0.17 0.13 0.07
LIGHT 0.02 0.08 0.15 0.22 0.37 0.58 0.75 0.84 0.82 0.71 0.53 0.37 0.29 0.20 0.11
S MEDIUM 0.03 0.09 0.16 0.22 0.38 0.58 0.75 0.83 0.80 0.69 0.50 0.35 0.27 0.19 0.11
HEAVY 0.04 0.11 0.17 0.24 0.39 0.59 0.75 0.82 0.79 0.67 0.49 0.33 0.26 0.18 0.10
LIGHT 0.02 0.06 0.10 0.13 0.16 0.18 0.22 0.38 0.59 0.76 0.84 0.83 0.72 0.48 0.18
SW MEDIUM 0.03 0.07 0.11 0.14 0.16 0.19 0.22 0.38 0.59 0.75 0.83 0.81 0.69 0.45 0.15
HEAVY 0.04 0.08 0.12 0.15 0.18 0.20 0.23 0.39 0.59 0.75 0.82 0.80 0.68 0.43 0.14
LIGHT 0.02 0.05 0.08 0.11 0.13 0.14 0.15 0.17 0.30 0.53 0.72 0.83 0.83 0.63 0.19
W MEDIUM 0.03 0.06 0.09 0.11 0.13 0.15 0.16 0.17 0.31 0.53 0.72 0.82 0.81 0.61 0.16
HEAVY 0.04 0.07 0.10 0.12 0.14 0.16 0.17 0.18 0.31 0.54 0.71 0.81 0.80 0.59 0.15
LIGHT 0.02 0.06 0.10 0.13 0.16 0.19 0.20 0.21 0.22 0.30 0.52 0.73 0.83 0.71 0.19
NW MEDIUM 0.03 0.07 0.11 0.14 -.17 0.19 0.20 0.21 0.22 0.30 0.52 0.73 0.82 0.69 0.16
HEAVY 0.04 0.08 0.12 0.15 01.8 0.20 0.21 0.22 0.23 0.30 0.52 0.73 0.81 0.67 0.15
LIGHT 0.02 0.10 0.26 0.43 0.59 0.72 0.81 0.87 0.87 0.83 0.74 0.60 0.44 0.27 0.15
HOR MEDIUM 0.03 0.12 0.27 0.44 0.59 0.72 0.81 0.85 0.85 0.81 0.71 0.58 0.42 0.25 0.14
HEAVY 0.05 0.13 0.29 0.45 0.60 0.72 0.81 0.83 0.84 0.79 0.70 0.56 0.40 0.23 0.13
By obtaining all the data taken from the Tables and specified design information
and requirements, we can design and calculate for conduction heat gains
though glass,
where;
Q = 61,316.51 Btu/hr
Therefore,
Q = u A ΔT (Equation 53)
Q ceiling = u A ΔT
Q ceiling = u A ΔT
where;
u = 0.421 Btu/ hr ft² °F
A = 43,133.40 ft²
ΔT = to - ti
to = 90 °F (outside temperature)
Therefore, substitute all the given values to solve the Conduction Heat Gains
through ceiling;
Q ceiling = u A ΔT
Q = u A ΔT (Equation 53)
Q flooring = u A ΔT
Substitute given values taken from Table 23 Transfer Function Coefficients for
Ceilings and Floors, Page 11(From Trane Cooling Load Estimate Handbook, Part
2- Conduction Heat Gains, Page 9).
where;
u = 0.421 Btu/ hr ft² °F
A = 43,133.40 ft²
ΔT = to - ti
to = 90 °F (outside temperature)
Therefore, substitute all the given values to solve the Conduction Heat Gains
through ceiling;
Q ceiling = u A ΔT
Table for Sensible Heat Cooling Load Factors (CLF) for People
Period 4 – Internal Heat Gains, Page 26, Cooling Load Estimate Handbook, The
Trane Company, La Crosse, Wisconsin
Hours After Each Entry in Space
2 0.49 0.58 0.17 0.13 0.10 0.08 0.07 0.06 0.05 0.04 0.0
4 0.49 0.59 0.46 0.71 0.27 0.21 0.16 0.14 0.11 0.10 0.0
6 0.50 0.60 0.67 0.72 0.76 0.79 0.54 0.26 0.21 0.18 0.1
8 0.51 0.61 0.67 0.72 0.76 0.80 0.82 0.84 0.38 0.30 0.2
10 0.53 0.62 0.69 0.74 0.77 0.80 0.83 0.85 0.87 0.89 0.4
12 0.55 0.64 0.70 0.75 0.79 0.81 0.84 0.86 0.88 0.89 0.9
14 0.58 0.66 0.72 0.77 0.80 0.83 0.85 0.87 0.89 0.90 0.9
16 0.62 0.70 0.73 0.79 0.82 0.85 0.87 0.88 0.90 0.91 0.92
18 0.66 0.74 0.79 0.82 0.85 0.87 0.89 0.90 0.92 0.91 0.94
Assume a space is occupied from 8:00 o’clock in the morning up to 5::00 o’clock
in the afternoon, or a total of nine hours (9) hours, and the cooling load is to be
calculated for 2:00 o’clock in the afternoon, or 6 hours after the person/s
occupied the room. By consulting the table, the cooling load factor (CLF) is 0.80
for the 6th (6) hour after entry.
Substituting this factor into the previous sensible heat load calculation:
Q = 32,736 Btu/hr
The equation used to determine the heat gains from, approximately 20% is
added to recognize the heat generated by the ballast.
Q = 39,283.2 Btu/hr
Q = 12,787.5 Btu/hr
Q = 13,640 Btu/hr
Q = 1,364 Btu/hr
Heat gains for several electrical appliances commonly found during function
events. All of these items add to the internal heat gain and must be included in
the cooling load calculation.
14
where,
where,
Dry Food
Warmer 240 820 400 320 80 400 130
Hot Plate 18x20x13 5,200 17700 8000 5300 3600 8900 2800
Coffee
Brewer
/ Burner
/ Warmer 623 2130 1000 770 230 1000 340
Automatic 100 545 300 230 70 300 90
240 27x 21x22 4-burner + 5,000 8500 8500 6400 2000 8500 1700
cups/hr water heater
Coffee Urn 3 gals 2,000 6800 3400 2550 850 3400 1100
5 gals 3,000 10200 5100 3000 1250 5100 1600
8 gals 4,000 13600 6800 2800 6000 9400 2100
Egg Boiler 1,100 3700 1900 1100 700 1900 3200
Deep Fat 14 lbs 13x 22x10 5,500 18700 9400 2800 6600 9400 1500
Fryer 21 lbs 16x 22x10 8,000 27300 13700 4100 9600 13700 3000
QT = QST + QLT
where;
Thus;
To calculate QLT
Therefore, substitute the values of the Total Sensible and Latent Heat Gains of
Several Electrical Appliances respective electrical appliances
QT = QST + QLT
QT = 36,711.12 Btu/hr
Thus;
Q = 15,906.25 Btu/hr
Therefore,
QT = 11,929.69 Btu/hr
Design and Calculation of Conduction Heat Gains for Entrance and Exit
Doors
Area = 11.34 m²
Double Door
Area = 13.44 m²
Materials used in Guestroom and Hallway Doors, from Pages 12-08 ~ 12-09,
Table- 5, Kent’s Mechanical Engineers’ Handbook, in Two Volume, Power
Volume, Edition 12, by J Kenneth Salisbury.
Q = u A ΔT (Equation 53)
Figure 2
U (coefficient of transmission)
fo (inside surface)
Non- Homogeneous
Material Non- Homogeneous
Material
Air Space
Air Space
Non- Homogeneous
Material
fi (outside surface)
thus;
Therefore, solving the Conduction Heat Gains for Guestroom and Hallway Doors
where;
A door = 266.63 ft ²
19
There are two methods if calculating and estimating the quantity of air entering
by infiltration; the crack and the air change method.
The crack method is based upon the average quantity of air known to enter
through cracks and windows and doors when the velocity is constant
The air change method is quicker but less accurate than the crack method. It
involves the use of tables that show the number of air changes per hour that can
be expected in rooms with various exposures.
where;
QI = Heat loss due to Infiltration, Btu/ hour
From Equation 4, Page 12 -11, by Kent’s Mechanical Engineers’ Handbook, in Two Volume, Power
Volume, Edition 12, by J Kenneth Salisbury.
Where;
QI = Heat loss due to Infiltration, Btu/ hour
The window is made of steel construction, double hung sash window, no window
strips and locked.
Where;
Length = 14.0 m x .3.281 ft/ m
Thus getting the calculation of linear feet of cracks for window and frame;
Using the Crack Method Equation to calculate the volume of air entering
Therefore, total volume of air entering from the windows and frames, Va t
Using the Equation–4 to calculate the Sensible Heat Gain from infiltrated air, Q SH
Where;
QI = Heat loss due to Infiltration, Btu/ hour
Using the Equation – 4 to calculate the Latent Heat Gain from infiltrated air, Q LH
Where;
VA = Volume of air entering (crack method), ft³/ min
Psychrometric Chart
Outdoor Design Conditions; Db = 90 °F
Wb = 75 °F
From the Psychrometric Chart reading, the humidity ratio of the indoor air (W i ) is
found to be 72 grains and the outdoor air (Wo) is found to be 102 grains.
Therefore, substituting the information taken from the Psychrometric Chart using
the Equation – 4 to get the Latent Heat gain from infiltrated air, Q LH
QT = QSH + QLH
QT = 51,042.93 Btu/hr
22
Design and Calculations of Ventilation Heat Gains
Design requirement for the Upper Ground Floor Level Tower Building
= 75 °F Wb
= 65 °F Wb
Apartment 10 15 3 2 1½ 1 ¾
Banking Space 7½ 10 3 2 1½ 1 ¾
Barber Shop 7½ 10 3 2 1½ 1 ¾
Beauty Parlor 7½ 10 3 2 1½ 1 2¼
Broker’s Board Room 20 30 8 6 4½ 3 1¾
Cafeteria 15 20 6 4½ 3½ 2½ 2¼
Cocktail Bar 20 30 8 6 4½ 3 ¾
Churches 5 7½ 3 2 1½ 1 ¾
Department Store 7½ 15 3 2 1½ 1 2¼
Director’s Room 30 40 8 6 4½ 3 ¾
Drug Store (with counter) 7½ 3 2 1½ 1 1½
Drug Store (No counter) 10 5 3¾ 3 2 ¾
Funeral Parlor 5 3 2 1½ 1 2¼
Gambling Rooms 20 8 6 4½ 3 ¾
Hospital Room 10 3 2 1½ 1 ¾
Hotel Room 10 3 2 1½ 1 ¾
Office, General 10 4 3 2¼ 1½ 1
Office, Private 10 5 3¾ 3 2 1½
Restaurant 12 5 3¾ 3 2 1½
Shop, Retail 7½ 3 2 1½ 1 ¾
Theater/ Function Rooms 5 7½
Residence 3 2 1½ 1 ¾
For General Applications;
Each person not smoking 5
Each person smoking 20
Where;
QVLH = Heat loss due to Infiltration, Btu/ hour
Using the Equation – 4 to calculate the Latent Heat Gain from Ventilation, Q VLH
where;
VA = Volume of air entering (crack method), ft³/ min
Psychrometric Chart
Wb = 65 °F
From the Psychrometric Chart reading, the humidity ratio of the indoor air (W i ) is
found to be 72 grains and the outdoor air (Wo) is found to be 102 grains.
Therefore, substituting the information taken from the Psychrometric Chart using
the Equation – 4 to get the Latent Heat Gain from Ventilation, Q VLH
QT = QVSH + QVLH
24
QT = 39,060.0 Btu/hr + 63,000 Btu/hr
QT = 102,060 Btu/hr
Obtain the Cooling Load in Btu per hr (Btu/ hr), by converting the load into Tons
of Refrigeration (TOR)
Cooling Load Requirements for Guestroom Floors and Hallways for Upper
Ground Floor Annex Building (Typical Typical Guest Floor Levels)
REFERENCES
Cooling Load Estimate Handbook, The Trane Company, Pammel Creek Road La
Crosse, Wisconsin.
Thermodynamics Sixth Edition, Virgil Moring Faires and Clifford Max Simmang.
Refrigeration and Air Conditioning, 2nd Edition, William F Stoecker and Jones, Mc
Graw- Hill.
COOLING TOWER
Type : Cross Flow Multi- Cell
Brand : Approved Equivalent
Design Capacity : 450 Tons of Refrigeration
Primary Chilled Water Pumps (PCHWP)
Type : Centrifugal
Brand : Approved Equivalent