Sei sulla pagina 1di 4

Refrigeration compressor anti-surge

control
A refrigeration compressor requires the same high-performance and fast-
acting surge control technology as other gas compression circuits

MEDHAT ZAGHLOUL and WAYNE JACOBSON


Compressor Controls Corporation

I
n a ‘normal’ gas compression
circuit, the fluid that is LP stage HP stage
compressed in the compres-
sor, flowing in the immediate 480 kPa 1500 kPa Condenser
upstream and downstream 45.0ºC
process lines and vessels, is all LP suction HP suction
drum drum
in a gaseous phase without any UIC
UIC
HP
change of state from liquid to LP

vapour or from vapour to Accumulator


Liquid
liquid. In this ‘normal’ gas propane
compression circuit, the Flash
150 kPa economiser
LC
compressor could experience −32.0ºC

surge-inducing events due to Chiller/


changes in the process condi- Evaporator
Process
tions downstream of the LC stream LC
compressor (for instance, 480 kPa
Pre-cooler
sudden increase in process +4.0ºC

resistance), due to changes in


the suction of the compressor Figure 1 This two-stage compressor fed by a process chiller requires two
(such as changes to gas compo- anti-surge control loops
sition or inlet pressure and
temperature), or sudden In a refrigeration circuit, the when the process load drops,
changes in the driver perfor- process is ‘closed loop’ and the thus less vapour in the process
mance (sudden drop in shaft gas composition does not chiller is produced.
power or speed, for instance). usually change. Also, the There is therefore a percep-
In the refrigeration circuit change of state in the tion by process designers to
however, there is a change of condenser means that the consider that any surge-induc-
state (from liquid to vapour) discharge resistance changes ing events on a refrigeration
that takes place immediately very slowly (in fact seasonally) compressor are limited and
upstream of the compressor in with the changes in ambient slow occurring and require
the LP process chiller and temperature around the only simple and ‘low perform-
another change of state (from condenser. A possible cause of ing’ surge control technology.
vapour to liquid) almost imme- compression surge can be due This is not a correct perception
diately downstream of the to a drop in vapour available as it ignores the surge-inducing
compressor in the condenser. for compression, which occurs events that could occur because

www.digitalrefining.com/article/1001308 PTQ Q3 2016 1


application, the temperature of
LP stage HP stage the propane gas at the
discharge of the compressor
480 kPa 1500 kPa Condenser may easily reach 130-140°C,
45.0ºC and if recycled back to the LP
LP suction HP suction stage suction drum, would be
drum drum
UIC
problematic on two levels:
LP
• First, the replacement of cold
Accumulator and denser vapour originating
Liquid
propane in the process chiller with hot
Flash
150 kPa economiser
recycle gas would initially
LC
−32.0ºC drive the operating point of the
Chiller/ LP stage further into surge
Evaporator
• Secondly, it would be just a
LC matter of time before the
480 kPa machine tripped on high LP
+4.0ºC stage inlet temperature.
Therefore, good design prac-
Figure 2 If a compressor stage is linked to a flash economiser only, an anti- tice dictates that the recycle gas
surge loop is not required be cooled to a temperature
approximating the vapour
of driver problems, which tend required. This is because the coming from the process
to be fast and sudden. flash economiser, unlike a chiller. A relatively straightfor-
Thus a refrigeration compres- process chiller, provides refrig- ward method of doing this is
sor requires the same erant vapour to the compressor to apply an evaporative cooling
high-performance and fast-act- stage in a manner that is not concept in the sense of releas-
ing surge control technology as dependent on process load ing an atomised fine spray of
‘normal’ gas compression changes. In other words, the liquid refrigerant into the hot
circuits. flash economiser circuit recycle gas stream downstream
provides continuous forward of the anti-surge valve. Since
Number of anti-surge control flow through it at all this almost instantaneously
loops operating conditions of the evaporates, it sufficiently cools
In general, each compressor compressor when it is running. the hot recycle gas stream. This
stage that supplied refrigerant This is illustrated in Figure 2. is typically achieved by install-
to a process chiller requires a ing a specially designed
dedicated anti-surge control The need to provide recycle gas atomising nozzle system into
loop (controller plus valve). cooling the recycle piping, downstream
In the example given in Method 1 – Quenching of the anti-surge valve. This is
Figure 1, where the LP process In refrigeration compressors, it illustrated in Figure 3.
chiller provides refrigerant is advisable to design the anti- When quenching is used as
vapour to the LP stage of the surge (recycle) piping so that it the method to cool the hot
compressor and the pre-cooler commences upstream of the recycle gas, it is not good
provides refrigerant vapour to discharge condenser. The design practice to simply
the HP stage of the compres- reason is straightforward. If modulate the quench valve
sor, two dedicated anti-surge recycle gas was taken from with a slow-acting temperature
control loops would be downstream of the condenser, controller. For example, if the
required. it would be, by definition, surge control system step-
On the other hand, if a mixed phase with mostly a opens the anti-surge valve,
compressor stage is linked to a liquid content and so would be providing a sudden increase of
flash economiser only, then a unsuitable for use as recycle hot refrigerant recycle gas, the
dedicated anti-surge loop for gas. much slower quench controller
that stage is generally not In a propane refrigeration would allow the recycle gas to

2 PTQ Q3 2016 www.digitalrefining.com/article/1001308


be delivered too hot to the LP
LP stage HP stage
suction drum for an unaccept-
able amount of time.
1500 kPa Condenser
Dynamic decoupling
between the anti-surge control- 45.0ºC
LP suction HP suction
ler and the quench controller is drum drum
required so that when the anti- UIC
LP
surge valve opens by a
Accumulator
significant amount, the quench Quench nozzles TT Liquid
controller would also immedi- (See detail)
Liquid quench
propane
TIC
ately open the quench valve by 150 kPa
−32.0ºC
a suitable and proportionate Flash
amount and then allow the Chiller/ LC
economiser
Evaporator
slower temperature control
LC
response to determine the
Quench-nozzle
required final opening of the 480 kPa
detail
+4.0ºC
quench valve based on the
Hot
set-point. recycle gas
The quench controller’s
control action needs to be Liquid
refrigerant
further coordinated with the
anti-surge control system so
that when the anti-surge valve
is closed (or open up to a Figure 3 Evaporative cooling for recycle gas
configurable minimum open-
ing) the liquid quench valve is quench controllers actually Method 2 - Sparging
kept closed regardless of its calculate the temperature Recently, process designers
recycle gas temperature meas- set-point as being offset (or started to utilise the fact that
urement. Also, when the biased) slightly from the satu- there is a continuous supply of
compressor is stopped, the ration temperature as liquid refrigerant in the LP
liquid quench valve needs to expressed by the pressure-en- (and even the MP) suction
be forced closed. thalpy saturation curve drums. It is possible to intro-
Traditional quench control- characteristics for that particu- duce the hot recycle gas into
lers operated with a fixed lar refrigerant. the lower liquid containing
downstream recycle gas There are, however, consider- portion of the suction drum
temperature set-point. able limitations on the use of and design a sparging system
However, the actual saturation quenching that must be that allows the hot recycle gas
temperature of the vapour in considered. to bubble through the liquid
the LP suction drum If the compressor is operated inventory. This causes
mentioned above is a function ‘blocked-in’, that is isolated increased conversion of the
of its operating pressure. from the process chillers for liquid inventory into refriger-
Ideally, the temperature any length of time, the addition ant vapour and, since the
set-point of the quench of liquid quench into the neces- operating pressure of the drum
controller must be adjusted as sary recycle gas will simply does not change appreciably,
the operating pressure in the cause the total refrigerant the produced vapour tempera-
LP suction drum changes. Not inventory to accumulate and ture sent to the compressor
only that, it should typically build up in what is in practice inlet remains unchanged.
be calculated slightly higher a closed circuit. Hence the shaft The sparger needs to be
(but close to) the current satu- load of the compressor will rise designed to efficiently allow
ration temperature in the LP and possibly exceed the capac- the dispersion of the maximum
suction drum. ity of the driver, causing a amount of hot recycle gas as
The latest state-of-the-art compressor trip. small bubbles into the liquid

www.digitalrefining.com/article/1001308 PTQ Q3 2016 3


ing at completely different
Compressor
LP stage HP stage
casing pressure and temperature
conditions compared to the
inlet of the HP stage. Therefore,
Discharge
flow element Condenser a properly designed surge
Sidestream controller for the HP stage
flow element
must include dedicated HP
FT FT FT stage inlet flow rate inferential
?? algorithms that produce
To
UIC UIC
accumulator
LP HP
adequately accurate results for
the whole range of compressor
operation.
LP suction HP suction
drum drum

From LP From HP Medhat Zaghloul is Regional Technology


chiller/evaporator pre-cooler chiller Manager for the Europe, Middle East and
Africa Regions with Compressor Controls
Figure 4 In many cases, it is necessary to provide dedicated anti-surge control- Corporation (CCC), based in the Abu
lers for each stage of the refrigeration compressor Dhabi Office where he is responsible for
the development of technical solutions
inventory without causing the single casing envelopes the and control applications and providing
technical guidance and support. He has
back pressure onto the anti- multiple stages with incoming
over 38 years of experience in the oil
surge valve to build up. In sidestream lines (or outgoing
and gas industry with 15 years specific
terms of sizing the anti-surge extraction lines as the process to instrumentation and controls for the
valve and the design differen- design dictates). This is illus- petrochemical industry. He holds a BSc
tial pressure across it, one must trated in Figure 4. in electrical engineering from the Cairo
consider the operating pressure As may be seen in Figure 4, Institute of Technology in Egypt (now
of the LP suction drum plus measuring the flow rate into the Helwan University).
the static pressure introduced LP stage of the compressor is Wayne Jacobson is Global Technology
by the liquid level that must be straightforward. However, for Manager for the Technology Group in
maintained as liquid inventory the HP stage, it is a different the Des Moines, IA, headquarters of
in the drum. This method elim- story. The flow element located CCC where his responsibilities include
providing technical guidance and
inates the need for quenching in the sidestream line does not
support throughout the organisation,
and the associated control measure the total HP inlet flow
development and improvement of
complexity. rate and the differential pres- control applications, maintaining and
sure generated across that flow improving standard engineering design
Calculating suction flow rate element cannot be simply and practices, and overseeing the overall
in a multi-stage refrigeration added to the differential pres- technical development of engineering
compressor sure generated across the LP staff. He holds a BS in mechanical
In many cases it is necessary to incoming line flow element engineering from the University of
provide dedicated anti-surge because of the considerably Wisconsin, Platteville.
controllers for each stage of the different pressures and temper-
refrigeration compressor. This atures experienced where these
means that the suction flowrate two flow elements are located.
for each stage must be meas- By the same reasoning, the LINKS
ured directly or inferred differential pressure generated
accurately. across the discharge flow More articles from the following
The problem arises with the element, while directly repre- category:
traditional design of these senting the discharge flow rate Rotating Equipment
multi-stage machines where a of the HP stage, is also operat-

4 PTQ Q3 2016 www.digitalrefining.com/article/1001308

Potrebbero piacerti anche