HEAT LOAD ESTIMATION

E 20 MANUAL METHOD
THINGS TO CONSIDER BEFORE HEAT
LOAD ESTIMATION
 ORIENTATION OF THE BUILDING AND LATITUDE
 APPLICATION OF THE BUILDING
 DIMENSIONS OF THE BUILDING
 HEIGHT UPTO THE CEILING
 HEIGHT UPTO THE FALSE CEILING
 IS THE ROOF EXPOSED
 HEIGHT OF THE BEAM AND PROJECTIONS OF THE COLUMN
 SIZE AND NUMBER OF WINDOWS
 WHETHER WINDOWS ARE SHADED
 MATERIAL OF CONSTRUCTION OF WALL, CEILING / ROOF.
 OUTSIDE DESIGN CONDITIONS
 INSIDE DESIGN CONDITIONS
 NO OF PERSONS
 LIGHTING LOAD AND TYPE OF LIGHT
 MACINERY LOAD AND DURATION OF OPERATION
 OTHER ADDITIONAL LOADS
 DURATION OF OPERATION
 SPACE TO LOCATE VARIOUS EQUIPMENTS
 VENTILATION REQUIREMENTS
 DETAILS OF EXHAUST IF ANY
 LEVEL OF CLEANLINESS TO BE MAINTAINED
 AVAILABILITY OF SOFTWATER AND ELECTRICITY
 OTHER RELEVANT INFORMATIONS
OUTSIDE DESIGN DATA FROM ISHRAE HANDBOOK

LOCATION: COCHIN ( page 119)

DAILY RANGE = 10°F


LATITUDE = 9.58 °N

SUMMER
DBT = 95
WBT = 82
RH = 58

REQUIRED INSIDE CONDITIONS


DBT = 75°F
RH = 50%
DBT (°F) WBT (°F) RH (%) W (gr / lb)
OUTSIDE DESIGN DATA 95 82 58 146
INSIDE DESIGN DATA 75 62 50 65

ΔT = OUTSIDE DBT– INSIDE DBT


= 95 – 75 = 20°F

ΔW = OUTSIDE W – INSIDE W
= 146 – 65 = 81 gr/lb
STEP 1:

SOLAR HEAT GAIN THROUGH EXPOSED GLASS ( page 46)

Q = BTU/(hr)( sq.ft window sash area) x WINDOW SASH AREA x OVERALL FACTOR x
CORRECTION FACTOR x STORAGE FACTOR

WEST WINDOW:

Q = 158 x (3 x 4) x 1 x 1.17 x 1
= 2218.32 BTU/hr

NORTH WINDOW:

Q = 39 x (3 x 3 ) x 1 x 1.17 x 1
= 410.62 BTU/hr
STEP 2:

TRANSFERRED HEAT GAIN THROUGH EXPOSED GLASS (page 108)

Q = U x A x ΔT

WEST WINDOW:

Q = 1.13 x (3 x 4) x 20
= 271.2 BTU/hr

NORTH WINDOW:

Q = 1.13 x (3 x 3) x 20
= 203.4 BTU/hr
STEP 3:

HEAT GAIN THROUGH WALL ( page 58)

Q = U x A x ΔT

ΔT = Equivalent Temperature + Correction Factor ( page 52)

NORTH WALL = 0.25 x [(12 x 11) – (3 x 3)] x (8+10)

= 553.5 BTU / hr

WEST WALL = 0.25 x [( 15 x 11 ) – (3x4)] x (28 + 10)

= 1453.5 BTU / hr
STEP 4:

HEAT GAIN THROUGH ROOF

Q = U x A x ΔT

ΔT = Equivalent Temperature + Correction Factor ( page 53)

Q = 0.25 x (12 x 15) x (37+10)


= 2115 BTU / hr

NOTE:

IF THE ROOF IS NOT EXPOSED ie CEILING ΔTactual = ΔT – 5 i.e. 20 -5 =15°F

IF THE ABOVE FLOOR IS AIR CONDTIONED, THERE IS NO NEED TO CONSIDER


CEILING
STEP 5:

HEAT GAIN THROUGH FLOOR

Q = U x A x ΔT

ΔTactual = ΔT – 5 = 20-5 = 15°F

Q = 0.34 x (12 x 15) x 15


= 918 BTU/hr

NOTE:

IF THERE IS A FLOOR BELOW, ΔTactual = ΔT – 5 i.e. 20 -5 =15°F

IF THE BELOW FLOOR IS AIR CONDTIONED, THERE IS NO NEED TO CONSIDER FLOOR


STEP 6:

HEAT GAIN THROUGH PARTITION WALL ( page 58)

Q = U x A x ΔT

ΔTactual = ΔT – 5 = 20-5 = 15°F

Q = 0.31 x (15 x 11)x 15


= 767.25 BTU / hr

NOTE:

IF THE NEARBY ROOM IS AIR CONDTIONED, THERE IS NO NEED TO CONSIDER


PATITION WALL
STEP 7:

HEAT GAIN THROUGH OUTSIDE AIR ( FRESH AIR) ( page 82)

REQUIRED OUTSIDE AIR CFM = NO OF PERSONS x CFM/PERSON + AREA (in sq.ft) x


CFM/sq.ft

= 2 x 5 + 180 x 0.06
=20.8 CFM

QSENSIBLE = 1.08 x CFM x BYPASS FACTOR x ΔT


= 44.928 BTU /hr

QLATENT = 0.68 x CFM x BYPASS FACTOR x ΔW


= 114.56 BTU / hr
STEP 8:
HEAT GAIN THROUGH INFILTRATION

CRACK METHOD
INFILTERED AIR CFM = Crack length x Leakage rate per hour / 60

ACH METHOD
INFILTERED AIR CFM = VOLUME x ACH / 60
ACH Range = 0.5 – 1.5

INFILTERED AIR CFM = 12 x 15x 11 x 1 /60


= 33 CFM

QSENSIBLE = 1.08 x CFM x ΔT


= 712.8 BTU / hr
QLATENT = 0.68 x CFM x ΔW
= 1817.64 BTU / hr
STEP 9:

HEAT GAIN FROM INTERNALS ( page 124 )

a) HEAT GAIN DUE TO OCCUPANCY

QSENSIBLE = NO OF PERSONS x SENSIBLE HEAT PER PERSON DUE TO METABOLIC


ACTIVITY
= 2 x 245 = 490 BTU / hr

QLATENT = NO OF PERSONS x LATENT HEAT PER PERSON DUE TO METABOLIC ACTIVITY


= 2 x 205 = 410 BTU / hr
b) HEAT GAIN DUE TO LIGHTING ( page 109 )

Q = WATTAGE x 3.41
= watt / sq.ft x sq.ft x 3.41
= 1 x 180 x 3.41
= 613.8 BTU / hr

c) HEAT GAIN DUE TO ELECTRICAL EQUIPMENT

Q = WATTAGE x USAGE FACTOR x 3.41

USAGE FACTOR = Operating hours / 24 hours

Q = 150 x (4/24) x 3.41


= 85.25 BTU /hr
Q TOTAL SENSIBLE =

Q TOTAL LATENT =

ADDING 10% AS SAFETY FACTOR TO BOTH SENSIBLE HEAT AND LATENT HEAT

Q TOTAL SENSIBLE =

Q TOTAL LATENT =

Q TOTAL =Q SENSIBLE +Q LATENT

TR = QTOTAL / 12000
=