Electrical Concepts
Tricky but Easy Electrical Engineering!
Multiplier (TSM)
Power System Protection
Electrical Machines
DC Machine
Measurement and
Instrumentation
Plug Setting Multiplier and Time Setting Multiplier are used AC Circuit
parameters are not so used in Numerical Relays but they are Electrical Drives
I consent to my
submitted data being
collected via this form*
SUBSCRIBE NOW
This minimum current in the Relay coil at which Relay starts
to operate is called Pick-up Current. If the current through we respect your privacy and
the Relay coil is less than the pick-up value then Relay won’t take protecting it seriously
Pick-up current = Plug Position x Rated CT Secondary
Current.
As shown in figure above, the plug is kept at 5. This means
that pick-up current of relay will be 5 times of rated CT
Secondary current. Likewise, if we put the plug at 8.75 then
pick-up current of relay will be 8.75 times of the rated CT
Secondary current.
For our case, PSM = 10 (Please see the calculation and case
considered above in our discussion of PSM) and TSM = 0.5
s.
Therefore,
What is Relay? -
Definition and Types of
Relay
electricalbaba.com
Impedance Relay
electricalbaba.com
Over Current Relay and
Its Characteristics
electricalbaba.com
Programmable
Scheme Logic (PSL) in
Numerical Relays
electricalbaba.com
Difference between
Instantaneous and
Definite Time...
electricalbaba.com
Transformer Physical
Protections
electricalbaba.com
Basic Principle of
Relay Operation
electricalbaba.com
Ad
1. Electrical Relay
2. PSM Formula
3. PSM in Relay
— christian erick
says:
December 14, 2016 at 8:37 pm
Reply
— Suryakant
says:
September 8, 2018 at 12:52 am
Reply
1. — admin
says:
September 8, 2018 at 9:21 am
— Peter
says:
September 11, 2018 at 3:07 pm
for a CT: 400/5A, CDG relay or IDMT relay with plug setting of 5A.
what can be my time setting multiplier? please show calculations.
Reply
1. — admin
says:
September 11, 2018 at 7:46 pm
The TMS setting basically depends on the relay
coordination. In case of CDG relay, you can keep
TMS setting anywhere in between 0 to 1 sec
depending upon how fast you want relay to operate.
In case, you keep TMS equal to 0.5 sec, then relay
operating time will be as per the PSM Versus
Operating time Graph. Hope it help. If you still need
any help, please revert. Thank you!