Product datasheet METCOEM1251

Characteristics EasyLogic OEM EM1251 power & energy meter -


Class 0.5, RS-485, 1A

Main

Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Range EasyLogic
Product or component type Energy meter
Product name EasyLogic EM1000
Device short name EM1251
Power monitoring Basic instrumentation
Type of measurement Active and reactive power
Active and reactive energy
Apparent energy
Power factor
Apparent power
[Us] rated supply voltage 44...277 V DC
44...277 V AC at 50/60 Hz +/- 5 Hz

Complementary
Network frequency 50/60 Hz
Power consumption in VA 4.0 VA
Display type Backlit LCD
Information displayed Indication of parameters : 3 fields of 4 characters
Energy consumption : 1 line of 10 characters and 3 decimals
Local signalling Voltage presence indicator light (green)
Calibration (CAL) : LED (red)
Current transformer input External CT, 0...1 A x 3 (three phase)
Measurement current 150...1200 mA
Maximum value measured 999999999.0 kWh reading
9999999999.000 MWh reading
Measurement accuracy +/- 1 % reactive energy
+/- 0.5 % power factor
+/- 0.5 % power
+/- 0.5 % energy
+/- 1 % reactive power
Accuracy class Class 1 power factor
Class 0.5 active energy
Class 0.5 active power
Class 0.5 apparent energy
Class 0.5 apparent power
Class 1 reactive energy
Class 0.5 power factor
Sep 17, 2018
1
Measurement category Category III
Communication port support Flat pin connector (RS485){Space]
Communication port protocol Modbus RTU :
Tamperproof of settings Protected by access code
Mounting support Flush
Panel mounting
Cut-out dimensions 92 x 92 mm
Connections - terminals Current circuit : top screw clamp terminal
RS485 link : side screw clamp terminal
Auxiliary supply : bottom screw clamp terminal
Voltage inputs : bottom screw clamp terminal
Tightening torque 1 N.m 3.5 mm Philips no 1
Overvoltage category III
Product certifications CULus
CE

Environment
Electromagnetic compatibility Electrostatic discharge immunity test IEC 61000-4-2
Conducted RF disturbances IEC 61000-4-6
Voltage dips and interruptions immunity test IEC 61000-4-11
Emission tests class A CISPR 22
Fast transients immunity test IEC 61000-4-4
Surge immunity test IEC 61000-4-4
Voltage/Current impulse IEC 61000-4-1
Radiated susceptibility IEC 61000-4-3
Mounting mode Clipped
Type of installation Indoor installation
IP degree of protection Body : IP20
Front face : IP51
Pollution degree 2
Relative humidity 5...95 % non-condensing
Ambient air temperature for operation -10...60 °C
Ambient air temperature for storage -25...70 °C
Operating altitude <= 2000 m
Standards NMI M 6-1 ed. 2
Width 96 mm
Depth 91 mm
Height 96 mm
Product weight 400 g

Offer Sustainability
RoHS (date code: YYWW) Will not be compliant
Will not be compliant