5.4-29
September 2011 Drawout Vacuum Breakers
Sheet 05 055
Typical Standard Metal-Clad Switchgear Application Layouts, 5–15 kV
1
Line VTs Line VTs
2
Line CPT Line CPT
Bus VTs 1-ph, 15 kVA max. Bus VTs 1-ph, 15 kVA max. 3
52-T
1200 or
2000A
4
Bus 1 Bus 2
5
52-M1 52-M2
1200A 1200 or 1200A 1200A 1200 or 6
2000A 2000A
R M R M R M R M R M
7
CTs CTs CTs CTs CTs
9
Feeder Source 1 Feeder Feeder Source 2
10
Figure 5.4-16. Typical Main-Tie-Main Arrangement with Bus and Line VTs and Line CPTs
5 or 15 kV VCP-W Switchgear, 1200 or 2000A Mains and Tie, 36.00-Inch (914.4 mm) Wide Structures
11
12
Line VTs Line VTs
13
Bus VTs Bus VTs
52-T
1200 or
14
2000 A
Bus 1 Bus 2
15
16
52-M1 52-M2
1200 or 1200A 1200A 1200 or
2000A 2000A 17
R M R M R M R M
19
Figure 5.4-17. Typical Main-Tie-Main Arrangement with Bus and Line VTs, but without Line CPTs—Preferred Arrangement 21
5 or 15 kV VCP-W Switchgear, 1200 or 2000A Mains and Tie, 36.00-Inch (914.4 mm) Wide Structures
ii Feeder Feeder
1
Line VTs
2 CTs
CTs
R M R M
3 Bus VTs
Bus VTs 52-T
1200A 1200 or 1200A
2000A
4
Bus 1 Bus 2
5
52-M2
6 1200A
52-M1
1200 or 1200 or 1200A
2000A 2000A
R M R M R M
7 R M
9
Feeder Source 1 Source 2 Feeder
10
Figure 5.4-18. Typical Main-Tie-Main Arrangement with Bus and Line VTs, but without Line CPTs—Alternate Arrangement
5 or 15 kV VCP-W Switchgear, 1200 or 2000A Mains and Tie, 36.00-Inch (914.4 mm) Wide Structures
11
12
13
Bus VTs Bus VTs
14
15 Bus 1 Bus 2
18 CTs
Line VTs Line VTs
CTs
19
20 Source 1 Source 2
21 Figure 5.4-19. Typical Main-Tie-Main Arrangement with Bus and Line VTs, and Line CPTs
5 or 15 kV VCP-W Switchgear, 3000A Mains and Tie, 36.00-Inch (914.4 mm) Wide Structures
ii
R R
1
M M
2
52-M1 52-M2
3000 A 52-T 3000 A
3000 A 3
Bus 1 Bus 2 4
(Optional (Optional (Optional
Fans) 1 Fans) 1 Fans) 1 5
7
Line VTs Bus VTs Bus VTs Line VTs
Source 1 Source 2
9
Figure 5.4-20. Typical Main-Tie-Main Arrangement with Bus and Line VTs 10
5 or 15 kV VCP-W Switchgear, 3000A Mains and Tie, 36.00-Inch (914.4 mm) Wide Structures
1 This arrangement can be supplied with cooling fans to allow 4000A continuous.
11
Medium Voltage High Resistance
Grounding System
Refer to Tab 36, Section 36.1, for
12
complete product description, single-
line diagram, layout and dimensions 13
of medium voltage high resistance
grounding system.