Metal-Clad Switchgear—VacClad-W—Medium Voltage

5.4-29
September 2011 Drawout Vacuum Breakers
Sheet 05 055
Typical Standard Metal-Clad Switchgear Application Layouts, 5–15 kV

Typical Main-Tie-Main Arrangements (Standard Metal-Clad)


Note: Arrangements shown in Figures 5.4-16–5.4-18 can be provided in 26.00-inch (660.4 mm) wide, 95.00-inch (2413.0 mm) high,
i
96.25-inch (2444.8 mm) deep structures with 50VCPWND, 1200A circuit breakers.
Note: R = Multi-function relay, M = Multi-function meter.
ii

1
Line VTs Line VTs
2
Line CPT Line CPT
Bus VTs 1-ph, 15 kVA max. Bus VTs 1-ph, 15 kVA max. 3
52-T
1200 or
2000A
4
Bus 1 Bus 2

5
52-M1 52-M2
1200A 1200 or 1200A 1200A 1200 or 6
2000A 2000A
R M R M R M R M R M
7
CTs CTs CTs CTs CTs

9
Feeder Source 1 Feeder Feeder Source 2
10
Figure 5.4-16. Typical Main-Tie-Main Arrangement with Bus and Line VTs and Line CPTs
5 or 15 kV VCP-W Switchgear, 1200 or 2000A Mains and Tie, 36.00-Inch (914.4 mm) Wide Structures
11

12
Line VTs Line VTs

13
Bus VTs Bus VTs
52-T
1200 or
14
2000 A

Bus 1 Bus 2
15

16
52-M1 52-M2
1200 or 1200A 1200A 1200 or
2000A 2000A 17
R M R M R M R M

CTs CTs CTs CTs 18

19

Source 1 Feeder Feeder Source 2


20

Figure 5.4-17. Typical Main-Tie-Main Arrangement with Bus and Line VTs, but without Line CPTs—Preferred Arrangement 21
5 or 15 kV VCP-W Switchgear, 1200 or 2000A Mains and Tie, 36.00-Inch (914.4 mm) Wide Structures

CA08104001E For more information, visit: www.eaton.com/consultants


Metal-Clad Switchgear—VacClad-W—Medium Voltage
5.4-30
Drawout Vacuum Breakers September 2011
Sheet 05 056
Typical Standard Metal-Clad Switchgear Application Layouts, 5–15 kV

Typical Main-Tie-Main Arrangements (Continued)


i Note: R = Multi-function relay, M = Multi-function meter

ii Feeder Feeder

1
Line VTs
2 CTs
CTs
R M R M
3 Bus VTs
Bus VTs 52-T
1200A 1200 or 1200A
2000A
4
Bus 1 Bus 2
5
52-M2
6 1200A
52-M1
1200 or 1200 or 1200A
2000A 2000A
R M R M R M
7 R M

CTs CTs CTs CTs


Line VTs
8

9
Feeder Source 1 Source 2 Feeder
10
Figure 5.4-18. Typical Main-Tie-Main Arrangement with Bus and Line VTs, but without Line CPTs—Alternate Arrangement
5 or 15 kV VCP-W Switchgear, 1200 or 2000A Mains and Tie, 36.00-Inch (914.4 mm) Wide Structures
11

12

13
Bus VTs Bus VTs
14

15 Bus 1 Bus 2

Line CPT Line CPT


16 1-ph, 15 kVA max. 1-ph, 15 kVA max.
52-M1 52-T 52-M2
3000A 3000A 3000A
17
R M R M

18 CTs
Line VTs Line VTs
CTs

19

20 Source 1 Source 2

21 Figure 5.4-19. Typical Main-Tie-Main Arrangement with Bus and Line VTs, and Line CPTs
5 or 15 kV VCP-W Switchgear, 3000A Mains and Tie, 36.00-Inch (914.4 mm) Wide Structures

For more information, visit: www.eaton.com/consultants CA08104001E


Metal-Clad Switchgear—VacClad-W—Medium Voltage
5.4-31
September 2011 Drawout Vacuum Breakers
Sheet 05 057
Typical Standard Metal-Clad Switchgear Application Layouts, 5–15 kV

Typical Main-Tie-Main Arrangements (Continued)


Note: R = Multi-function relay, M = Multi-function meter
i

ii

R R
1
M M
2
52-M1 52-M2
3000 A 52-T 3000 A
3000 A 3

Bus 1 Bus 2 4
(Optional (Optional (Optional
Fans) 1 Fans) 1 Fans) 1 5

7
Line VTs Bus VTs Bus VTs Line VTs

Source 1 Source 2
9

Figure 5.4-20. Typical Main-Tie-Main Arrangement with Bus and Line VTs 10
5 or 15 kV VCP-W Switchgear, 3000A Mains and Tie, 36.00-Inch (914.4 mm) Wide Structures
1 This arrangement can be supplied with cooling fans to allow 4000A continuous.
11
Medium Voltage High Resistance
Grounding System
Refer to Tab 36, Section 36.1, for
12
complete product description, single-
line diagram, layout and dimensions 13
of medium voltage high resistance
grounding system.
14

15

16

17

18

19

20

21

CA08104001E For more information, visit: www.eaton.com/consultants