Sei sulla pagina 1di 3

1. Location : Substation-01/ MV Panel Date: 08.04.

2015

Feeder Name : Incomer-01(Feeder-01)

2. Equipment Details:

Make L&T
Type SR61C
Sl.No 05173950
CT Sec 8.75 A
CT Ratio 3200/ 8.75 A
Aux Volts 90-240 V AC

3. General Inspection: OK

4. Service Settings:

PH CT 366
EF CT 366
BFT 0.05
DBL OFF
OC LS 100% In
OC HS 6.0 x In
OC CH 947
OC TS 2.0 Sec
OC TD 100 Mill sec
EF 30% In
EF TD 100 Mill Sec

5. Secondary Injection Test:

5.1. Measurement:

Ref Secondary Current(A) Injected Current(A) Measured Primary Current(A)

R 8.75 8.7 3245


Y 8.75 8.7 3245
B 8.75 8.7 3316
E 8.75 8.7 3240

5.2. Over Current Low set:

Operated Time(S)
Set Pickup X2(17.5A) X3(26.2A)
Drop-of
Ref Current Current CHAR TMS Expected Measured Expecte Measured
current(A)
(A) (A) Delay Delay d Delay Delay
Seconds Seconds Seconds Seconds
RY 8.75 8.7 8.5 947 2.0 22.0 22.87 8.8 8.827
YB 8.75 8.5 8.4 947 2.0 22.0 21.73 8.8 8.822
BR 8.75 8.5 8.4 947 2.0 22.0 20.90 8.8 8.438
Relay record Data:
Set Measured Primary Current(A) Record data
Ref
Current(A) R Y B R Y B
RY 2.0x8.75=17.5 6465 6398 --- 2.0 In 2.0 In ---
YB 2.0x8.75=17.5 --- 6423 6566 --- 2.0 In 2.0 In
BR 2.0x8.75=17.5 6429 --- 6268 2.0 In --- 2.0 In

Set Measured Primary Current(A) Record data


Ref
Current(A) R Y B R Y B
RY 3.0x8.75=26.2 9645 9648 --- 3.0 In 3.0 In ---
YB 3.0x8.75=26.2 --- 9749 9742 --- 3.0 In 3.0 In
BR 3.0x8.75=26.2 9717 --- 9693 3.0 In --- 3.0 In
5.3. Over Current High set:

Set Pickup Set Operated Record data


Ref
Current(A) Current(A) Time(S) Time(S) R Y B
RY 6.0x8.75=52.5 52.5 0.1 0.246 5.9 In 6.0 In ---
YB 6.0x8.75=52.5 52.5 0.2 0.317 --- 6.0 In 6.0 In
BR 6.0x8.75=52.5 52.5 0.4 0.497 6.0 In --- 6.0 In

Above 10000 A can’t be measured

5.4. Earth Fault Low set:

Set Current(A)
Ref Pickup Current(A) Set Time(S) Operating Time(S)
30% In
R-E 2.625 2.609 0.1 0.271
Y-E 2.625 2.617 0.2 0.318
B-E 2.625 2.617 0.4 0.478

Relay record Data:

Set Measured Primary Current(A) Record data


Ref
Current(A) R Y B E R Y B E
R-E 2.625 996.4 --- --- 963.2 0.2 In --- --- 0.3 on
Y-E 2.625 --- 981.1 --- 970.1 --- 0.3 In --- 0.3 On
B-E 2.625 --- --- 1008 972.7 --- --- 0.3 In 0.3 on

6. Primary Injection Test:

Injected Current In Measured Current In Measured Current In


Ref
Primary(A) Relay(A) Energy Meter (A)

RY
YB

7. Functional checks: (Whether Operational Checks OK / Not OK / Not Applicable)

1 CT Wiring from TB to Relay checks OK


2 Correct operation of appropriate indication/All Output relay OK
3 Correct operation of alarm contacts OK
4 Correct circuit breaker tripping contacts OK
5 Relay cover properly fixing OK
6 Correct operating reset switch OK
7 Data Storage/ Fault data Record OK

8. Comments : B phase Current Less then Compare to Other Two Phase(R, Y).
9. Remarks : Relay found Healthy.