Sei sulla pagina 1di 96

EDAMT341716

Preview

VRV X SERIES
RXUQ8-60A(M)YM/A(M)Y14/A(M)Y1S
VRV A SERIES
RXQ6-60A(M)YM/A(M)Y14/A(M)Y1S

Outdoor Unit Only


Cooling Only 50/60 Hz
• Specifications, designs and other content appearing in this brochure are current as of August 2017 but subject to change without notice.
EDAMT341716

Introduction ................................................................................................................. 2
1
2
Part 1 General Information ............................................... 1 ................................ 3
3
Part 2 Outdoor Units ................................................................................................ 23

Cooling Only 50/60 Hz VRV X SERIES .................................. 2 RXUQ-A(M) ................25

Cooling Only 50/60 Hz VRV A SERIES .................................. 3 RXQ-A(M) ................53

Table of Contents 1
Introduction EDAMT341716

1. Introduction
1.1 Publication List of Engineering Data for VRV Products
Published
Refrigerant Type Product Series Book No. Type, Hz Model name Area Note
in
- Change of cooling
operation range
High-COP type of outdoor units
RXQ12-50THY1(E) - Addition of indoor
Singapore, units FXDQ-SP,
Standard type Malaysia, FXSQ, FTKJ
EDMT341410B C/O 50 Hz Jan. 2016
RXQ6-60T(N)Y1(E) Vietnam, - Model change of
Pakistan indoor units FXVQ
Space saving type from M to N series
RXQ18-50T(S)Y1(E) - Deletion of indoor
Inverter units FCQ, FFQ
T(A) and FBQ
- Model change
High-COP type of outdoor
RXQ12-50TAHYM(E) units RXQ from
Singapore, T to TA series
Standard type Malaysia, - Addition of
EDMT341410C C/O 50 Hz RXQ6-60TA(N)YM(E) Vietnam, indoor unit Jun. 2016
Pakistan FXVQ500NY16
Space saving type - New lineup of
RXQ18-50TA(S)YM(E) indoor units
FXBQ, FXBPQ
Singapore,
RXUQ8-20A(M)YM
RXUQ8-20A(M)Y14 Vietnam,
RXUQ8-20A(M)Y1S Malaysia, Preview
EDAMT341716 C/O 50/60 Hz Pakistan, - Outdoor units Aug. 2017
RXQ6-20A(M)YM
RXQ6-20A(M)Y14 Thailand, only
Inverter RXQ6-20A(M)Y1S Indonesia,
A Philippines
EDVN331516 H/P 50 Hz RXYMQ4-6AVE Vietnam - New lineup of Jun. 2015
Air RXYMQ8/9AY1 outdoor units
cooled RXMQ4-6AVE
Singapore,
R410A EDMT331522 C/O 50 Hz RXMQ8/9AY1 Malaysia, - outdoor
New lineup of
units Jul. 2015
Vietnam
Normal type
- Addition of
RXYQ5-54PAY1(E) 6HP outdoor
RXYQ5-54PAYL(E) units (Asean
RXYQ5-54PTL(E)
EDMT341107A H/P 50/60 Hz General and Oceania Dec. 2012
only)
High-COP type
RXYQ16-50PAHY1(E) - Model change
RXYQ16-50PAHYL(E) of FXAQ from
MA to P series
RXYQ16-50PHTL(E)
- Addition of 6HP
Normal type outdoor unit
RXQ5-54PAY1 (Asean and
EDMT341015A C/O 50 Hz General Oceania only) Dec. 2012
High-COP type - Model change
RXQ16-50PAHY1 of FXAQ from
Inverter
MA to P series
P(A)
Single outdoor unit
ED341119 C/O 50 Hz series ASEAN Dec. 2011
RSXQ8-18PY1
C/O 50 Hz ASEAN
ED341211 RX(Y)Q6PAY1 Aug. 2012
H/P 50 Hz Oceania
EDMT37-750A H/R 50 Hz REYQ8-48PY1 General Aug. 2013
ED341014 H/P 50 Hz RQYQ8-48PY1 ASEAN Dec. 2010
ED341207 C/O 50 Hz RQQ8-48PY1 ASEAN Jul. 2012
H/P 50/60 Hz
EDMT34-635A C/O 50/60 Hz
RX(Y)MQ4-6PVE General Dec. 2012

Water RWEYQ8-30PY1
ED34-942 H/P,H/R 50 Hz RWEYQ10-30PYL General Dec. 2009
cooled H/P,H/R 60 Hz RWEYQ10-30PTL
indoor and outdoor General Option
Option for all type OH14-01 50/60 Hz For Apr. 2014
units handbook
Heat Reclaim Ventilator (VAM) GJ ED71-613 50/60 Hz VAM150-2000GJVE General Feb. 2006
- With DX coil
VKM50-100GAMV1 and humidifier
Heat Reclaim Ventilator (VKM) GA(M) ED71-440B 50 Hz
VKM50-100GAV1
General (VKM-GAM) Mar. 2012
- With DX coil
(VKM-GA)

EDAMT341716 as shown by .
H/P: Heat Pump
H/R: Heat Recovery
C/O: Cooling Only

2 Introduction
EDAMT341716

1
Part 1
General Information
1. Model Names of Indoor/Outdoor Units....................................................4
1.1 Singapore and Vietnam............................................................................4
1.2 Malaysia and Pakistan .............................................................................6
1.3 Thailand....................................................................................................8
1.4 Indonesia................................................................................................10
1.5 Philippines ..............................................................................................12
2. External Appearance.............................................................................14
2.1 Outdoor Units .........................................................................................14
3. Combination of Outdoor Units...............................................................16
4. Nomenclature........................................................................................18
5. Capacity Range.....................................................................................19
5.1 For VRV Indoor Units Only.....................................................................19
5.2 For a System with Residential Indoor Units or
VRV Mix Combination ............................................................................22

General Information 3
Model Names of Indoor/Outdoor Units EDAMT341716

1. Model Names of Indoor/Outdoor Units


1.1 Singapore and Vietnam

 VRV Indoor Units


2.2 kW 2.8 kW 3.6 kW 4.5 kW 5.6 kW 7.1 kW 8.0 kW 9.0 kW 11.2 kW 14.0 kW 16.0 kW 22.4 kW 28.0 kW 45.0 kW 56.0 kW Power
Capacity range
0.8 HP 1 HP 1.25 HP 1.6 HP 2 HP 2.5 HP 3 HP 3.2 HP 4 HP 5 HP 6 HP 8 HP 10 HP 16 HP 20 HP supply,
Capacity index 20 25 31.25 40 50 62.5 71 80 100 125 140 200 250 400 500 Standard
Ceiling mounted
cassette
(Round flow FXFSQ — 25A 32A 40A 50A 63A — 80A 100A 125A 140A — — — —
with sensing)
type VM
Ceiling mounted
cassette
(Round flow) FXFQ — 25A 32A 40A 50A 63A — 80A 100A 125A 140A — — — —
type
Ceiling mounted
cassette
(Compact multi FXZQ 20M 25M 32M 40M 50M — — — — — — — — — — VE
flow) type
4-way flow
ceiling
suspended FXUQ — — — — — — 71A — 100A — — — — — — VEB
type
Ceiling mounted
cassette
(Double flow) FXCQ 20M 25M 32M 40M 50M 63M — 80M — 125M — — — — — VE
type
Ceiling mounted
cassette
(Single flow) FXEQ 20A 25A 32A 40A 50A 63A — — — — — — — — — V36
type
FXDQ- 20PD 25PD 32PD — — — — — — — — — — — —
PDVE
Slim ceiling FXDQ- 20PD 25PD 32PD —
mounted duct PDVET — — — — — — — — — — —
type VE
(Standard FXDQ- — — — 40ND 50ND 63ND — — — — — — — — —
series) NDVE
FXDQ- — — — 40ND 50ND 63ND — — — — — — — — —
NDVET
Slim ceiling
mounted duct FXDQ-
type 20SP 25SP 32SP 40SP 50SP 63SP — — — — — — — — — V1
(Compact SP
series)
Middle static
pressure
ceiling FXSQ 20PA 25PA 32PA 40PA 50PA 63PA — 80PA 100PA 125PA 140PA — — — —
mounted duct
type
Ceiling mounted
duct type FXMQ 20PA 25PA 32PA 40PA 50PA 63PA — 80PA 100PA 125PA 140PA — — — —
Ceiling mounted
duct type FXMQ — — — — — — — — — — — 200MA 250MA — —
Ceiling VE
suspended FXHQ — — 32MA — — 63MA — — 100MA — — — — — —
type
Wall mounted
type FXAQ 20P 25P 32P 40P 50P 63P — — — — — — — — —
Floor
standing type FXLQ 20MA 25MA 32MA 40MA 50MA 63MA — — — — — — — — —
Concealed
floor standing FXNQ 20MA 25MA 32MA 40MA 50MA 63MA — — — — — — — — —
type
Floor — — — — — — — — — 125N — 200N 250N 400N 500N Y1
standing duct FXVQ
type — — — — — — — — — — — — — — 500N Y16
Clean type FXBQ — — — 40P 50P 63P — — — — — — — — —
air conditioner FXBPQ VE
— — — — — 63P — — — — — — — — —
Note: FXDQ has following 2 series, as shown below.
FXDQ-PDVET, NDVET: without a drain pump
FXDQ-PDVE, NDVE: with a drain pump

V1, V36: 1 phase, 220-240 V, 50 Hz


VE: 1 phase, 220-240/220 V, 50/60 Hz
VEB, VM: 1 phase, 220-240/220-230 V, 50/60 Hz
Y1, Y16: 3 phase, 380-415 V, 50 Hz

4 General Information
EDAMT341716 Model Names of Indoor/Outdoor Units

 Residential Indoor Units with Connection to BP Units


1
Capacity range 2.5 kW 3.5 kW 5.0 kW 6.0 kW 7.1 kW Power supply,
Capacity index 25 35 50 60 71 Standard
Slim ceiling 25EA 35EA — — —
mounted duct FDKS 25CA 35CA — — — VMB
type — — 50C 60C —
25N 35N 50N — — VMW
FTKJ 1
25N 35N 50N — — VMS
25N 35N 50N — — VMVW
Wall mounted FTKJ 2
25N 35N 50N — — VMVS
type
25D 35D — — — VM
FTKS — — 50B — — VMA
— — 50F 60F 71F VM
Note: BP units are necessary for residential indoor units.
Residential indoor units can be connected with only single outdoor units.

VM: 1 phase, 220-240/220-230 V, 50/60 Hz

1 Only available to the Singapore market.


2 Only available to the Vietnam market.

 BP Units
Type Model name
3 Ports BPMKS967A3
BP units
2 Ports BPMKS967A2

 Air Treatment Equipment


Outdoor-air processing unit
Series Model name Power supply
FXMQ 125MF 200MF 250MF V1
V1: 1 phase, 220-240 V, 50 Hz

Heat Reclaim Ventilator (VKM series)


Series Model name Power supply
Heat reclaim 50GA 80GA 100GA
ventilator with DX coil
Heat reclaim VKM V1
ventilator with DX 50GAM 80GAM 100GAM
coil and humidifier
Note: For details, refer to Engineering Data ED71-440B.

V1: 1 phase, 220-240 V, 50 Hz

Heat Reclaim Ventilator (VAM series)


Series Model name Power supply
Heat reclaim
ventilator VAM 150GJ 250GJ 350GJ 500GJ 650GJ 800GJ 1000GJ 1500GJ 2000GJ VE
Note: For details, refer to Engineering Data ED71-613.

VE: 1 phase, 220-240/220 V, 50/60 Hz

 Outdoor Units
VRV X SERIES
Series Model name Power supply
8A 10A 12A 14A 16A 18A 18AM 20A 20AM 22AM
Outdoor units RXUQ 24AM 26AM 28AM 30AM 32AM 34AM 36AM 38AM 40AM 42AM YM
44AM 46AM 48AM 50AM 52AM 54AM 56AM 58AM 60AM —

VRV A SERIES
Series Model name Power supply
6A 8A 10A 12A 14A 16A 18A 18AM 20A 20AM
Outdoor units RXQ 22AM 24AM 26AM 28AM 30AM 32AM 34AM 36AM 38AM 40AM YM
42AM 44AM 46AM 48AM 50AM 52AM 54AM 56AM 58AM 60AM
YM: 3 phase, 380-415/380 V, 50/60 Hz

General Information 5
Model Names of Indoor/Outdoor Units EDAMT341716

1.2 Malaysia and Pakistan

 VRV Indoor Units


2.2 kW 2.8 kW 3.6 kW 4.5 kW 5.6 kW 7.1 kW 8.0 kW 9.0 kW 11.2 kW 14.0 kW 16.0 kW 22.4 kW 28.0 kW 45.0 kW 56.0 kW Power
Capacity range
0.8 HP 1 HP 1.25 HP 1.6 HP 2 HP 2.5 HP 3 HP 3.2 HP 4 HP 5 HP 6 HP 8 HP 10 HP 16 HP 20 HP supply,
Capacity index 20 25 31.25 40 50 62.5 71 80 100 125 140 200 250 400 500 Standard
Ceiling mounted
cassette
(Round flow FXFSQ — 25A 32A 40A 50A 63A — 80A 100A 125A 140A — — — —
with sensing)
type VM
Ceiling mounted
cassette
(Round flow) FXFQ — 25A 32A 40A 50A 63A — 80A 100A 125A 140A — — — —
type
Ceiling mounted
cassette
(Compact multi FXZQ 20M 25M 32M 40M 50M — — — — — — — — — — VE
flow) type
4-way flow
ceiling
suspended FXUQ — — — — — — 71A — 100A — — — — — — VEB
type
Ceiling mounted
cassette
(Double flow) FXCQ 20M 25M 32M 40M 50M 63M — 80M — 125M — — — — —
type
Ceiling mounted
cassette corner FXKQ — 25MA 32MA 40MA — 63MA — — — — — — — — —
type
FXDQ- 20PD 25PD 32PD — — — — — — — — — — — — VE
PDVE
Slim ceiling FXDQ-
mounted duct PDVET 20PD 25PD 32PD — — — — — — — — — — — —
type
(Standard FXDQ- — — — 40ND 50ND 63ND — — — — — — — — —
series) NDVE
FXDQ- — — — 40ND 50ND 63ND — — — — — — — — —
NDVET
Slim ceiling
mounted duct FXDQ- 20SP 25SP 32SP 40SP 50SP 63SP
type — — — — — — — — — V1
(Compact SP
series)
Middle static
pressure
ceiling FXSQ 20PA 25PA 32PA 40PA 50PA 63PA — 80PA 100PA 125PA 140PA — — — —
mounted duct
type
Ceiling mounted
duct type FXMQ 20PA 25PA 32PA 40PA 50PA 63PA — 80PA 100PA 125PA 140PA — — — —
Ceiling mounted
duct type FXMQ — — — — — — — — — — — 200MA 250MA — —
Ceiling VE
suspended FXHQ — — 32MA — — 63MA — — 100MA — — — — — —
type
Wall mounted
type FXAQ 20P 25P 32P 40P 50P 63P — — — — — — — — —
Floor
standing type FXLQ 20MA 25MA 32MA 40MA 50MA 63MA — — — — — — — — —
Concealed
floor standing FXNQ 20MA 25MA 32MA 40MA 50MA 63MA — — — — — — — — —
type
Floor — — — — — — — — — 125N — 200N 250N 400N 500N Y1
standing duct FXVQ
type — — — — — — — — — — — — — — 500N Y16
Clean type FXBQ  — — — 40P 50P 63P — — — — — — — — —
air conditioner FXBPQ  VE
— — — — — 63P — — — — — — — — —
Note: FXDQ has following 2 series, as shown below.
FXDQ-PDVET, NDVET: without a drain pump
FXDQ-PDVE, NDVE: with a drain pump

V1: 1 phase, 220-240 V, 50 Hz


VE: 1 phase, 220-240/220 V, 50/60 Hz
VEB, VM: 1 phase, 220-240/220-230 V, 50/60 Hz
Y1, Y16: 3 phase, 380-415 V, 50 Hz

 FXBQ and FXBPQ models are not available to the Pakistan market.

6 General Information
EDAMT341716 Model Names of Indoor/Outdoor Units

 Residential Indoor Units with Connection to BP Units


1
Capacity range 2.5 kW 3.5 kW 5.0 kW 6.0 kW 7.1 kW Power supply,
Capacity index 25 35 50 60 71 Standard
Slim ceiling 25EA 35EA — — —
mounted duct FDKS 25CA 35CA — — — VMB
type — — 50C 60C —
25N 35N 50N — — VMMW
FTKJ 
25N 35N 50N — — VMMS
Wall mounted 25D 35D — — — VM
type
FTKS — — 50B — — VMA
— — 50F 60F 71F VM
Note: BP units are necessary for residential indoor units.
Residential indoor units can be connected with only single outdoor units.

VM: 1 phase, 220-240/220-230 V, 50/60 Hz

 FTKJ models are not available to the Pakistan market.

 BP Units
Type Model name
3 Ports BPMKS967A3
BP units
2 Ports BPMKS967A2

 Air Treatment Equipment


Outdoor-air processing unit
Series Model name Power supply
FXMQ 125MF 200MF 250MF V1
V1: 1 phase, 220-240 V, 50 Hz

Heat Reclaim Ventilator (VKM series)


Series Model name Power supply
Heat reclaim 50GA 80GA 100GA
ventilator with DX coil
Heat reclaim VKM V1
ventilator with DX 50GAM 80GAM 100GAM
coil and humidifier
Note: For details, refer to Engineering Data ED71-440B.

V1: 1 phase, 220-240 V, 50 Hz

Heat Reclaim Ventilator (VAM series)


Series Model name Power supply
Heat reclaim
VAM 150GJ 250GJ 350GJ 500GJ 650GJ 800GJ 1000GJ 1500GJ 2000GJ VE
ventilator
Note: For details, refer to Engineering Data ED71-613.

VE: 1 phase, 220-240/220 V, 50/60 Hz

 Outdoor Units
VRV X SERIES
Series Model name Power supply
8A 10A 12A 14A 16A 18A 18AM 20A 20AM 22AM
Outdoor units RXUQ 24AM 26AM 28AM 30AM 32AM 34AM 36AM 38AM 40AM 42AM YM
44AM 46AM 48AM 50AM 52AM 54AM 56AM 58AM 60AM —

VRV A SERIES
Series Model name Power supply
6A 8A 10A 12A 14A 16A 18A 18AM 20A 20AM
Outdoor units RXQ 22AM 24AM 26AM 28AM 30AM 32AM 34AM 36AM 38AM 40AM YM
42AM 44AM 46AM 48AM 50AM 52AM 54AM 56AM 58AM 60AM
YM: 3 phase, 380-415/380 V, 50/60 Hz

General Information 7
Model Names of Indoor/Outdoor Units EDAMT341716

1.3 Thailand

 VRV Indoor Units


2.2 kW 2.8 kW 3.6 kW 4.5 kW 5.6 kW 7.1 kW 8.0 kW 9.0 kW 11.2 kW 14.0 kW 16.0 kW 22.4 kW 28.0 kW 45.0 kW 56.0 kW
Capacity range Power
0.8 HP 1 HP 1.25 HP 1.6 HP 2 HP 2.5 HP 3 HP 3.2 HP 4 HP 5 HP 6 HP 8 HP 10 HP 16 HP 20 HP supply,
Standard
Capacity index 20 25 31.25 40 50 62.5 71 80 100 125 140 200 250 400 500
Ceiling
mounted
cassette
(Round flow FXFSQ — 25A 32A 40A 50A 63A — 80A 100A 125A 140A — — — —
with sensing)
type VS
Ceiling
mounted
cassette FXFQ — 25A 32A 40A 50A 63A — 80A 100A 125A 140A — — — —
(Round flow)
type
Ceiling
mounted
cassette
(Compact FXZQ 20M 25M 32M 40M 50M — — — — — — — — — — VES
multi flow)
type
4-way flow
ceiling
suspended FXUQ — — — — — — 71A — 100A — — — — — — VEB
type
Ceiling
mounted
cassette FXCQ 20M 25M 32M 40M 50M 63M — 80M — 125M — — — — — VE
(Double flow)
type
Ceiling
mounted
cassette FXEQ 20A 25A 32A 40A 50A 63A — — — — — — — — — V36
(Single flow)
type
FXDQ- 20PD 25PD 32PD — — — — — — — — — — — —
PDV2S
Slim ceiling FXDQ-
mounted duct PDVTS 20PD 25PD 32PD — — — — — — — — — — — —
type V2S
(Standard FXDQ-
series) NDV2S — — — 40ND 50ND 63ND — — — — — — — — —

FXDQ- — — — 40ND 50ND 63ND — — — — — — — — —


NDVTS
Slim ceiling
mounted duct
type FXDQ 20SP 25SP 32SP 40SP 50SP 63SP — — — — — — — — — V1
(Compact
series
Middle static
pressure
ceiling FXSQ 20PA 25PA 32PA 40PA 50PA 63PA — 80PA 100PA 125PA 140PA — — — —
mounted duct VS
type
Ceiling FXMQ 20PA 25PA 32PA 40PA 50PA 63PA — 80PA 100PA 125PA 140PA — — — —
mounted duct
type FXMQ — — — — — — — — — — — 200M 250M — — VES
Ceiling
suspended FXHQ — — 32MA — — 63MA — — 100MA — — — — — — VS
type
Wall mounted
type FXAQ 20P 25P 32P 40P 50P 63P — — — — — — — — — VES
Floor
standing type FXLQ 20MA 25MA 32MA 40MA 50MA 63MA — — — — — — — — —
Concealed VE
floor standing FXNQ 20MA 25MA 32MA 40MA 50MA 63MA — — — — — — — — —
type
Floor — — — — — — — — — 125N — 200N 250N 400N 500N Y1
standing duct FXVQ
type — — — — — — — — — — — — — — 500N Y16
Clean type FXBQ — — — 40P 50P 63P — — — — — — — — —
air conditioner VE
FXBPQ — — — — — 63P — — — — — — — — —
Note: FXDQ has following 2 series, as shown below.
FXDQ-PDVTS, NDVTS: without a Drain Pump
FXDQ-PDV2S, NDV2S: with a Drain Pump
V1, V36: 1 phase, 220-240 V, 50 Hz
V2S: 1 phase, 220 V, 50 Hz
VE, VES, VS: 1 phase, 220-240/220 V, 50/60 Hz
Y1: 3 phase, 380-415 V, 50 Hz

8 General Information
EDAMT341716 Model Names of Indoor/Outdoor Units

 Residential Indoor Units with Connection to BP Units


1
Capacity range 2.5 kW 3.5 kW 5.0 kW 6.0 kW 7.1 kW Power supply,
Capacity index 25 35 50 60 71 Standard
09EA 12EA — — —
Slim ceiling
mounted duct FDKS 09CA 12CA — — — VMS
type
— — 18C 24C —
09N 12N 18N — — V1SW
FTKJ
Wall mounted 09N 12N 18N — — V1SS
type 09D 12D — — —
FTKS VMS
— — 18F 24F 28F
Note: BP units are necessary for residential indoor units.
Residential Indoor units can be connected with only single outdoor units.

V1:1 phase, 220-240 V, 50 Hz


VM:1 phase, 220-240/220-230 V, 50/60 Hz
S(VES): Standard

 BP Units
Type Model name
3 Ports BPMKS967B3S
BP units
2 Ports BPMKS967B2S

 Air Treatment Equipment


Outdoor-air processing Unit
Series Model name Power supply
FXMQ 125MF 200MF 250MF V1
V1: 1 phase, 220-240 V, 50 Hz

Heat Reclaim Ventilator (VKM series)


Series Model name Power supply
Heat reclaim
ventilator with DX 50GA 80GA 100GA
coil
VKM V1
Heat reclaim
ventilator with DX 50GAM 80GAM 100GAM
coil and humidifier
Note: For details, refer to Engineering Data ED71-440B.

V1: 1 phase, 220-240 V, 50 Hz

Heat Reclaim Ventilator (VAM series)


Series Model name Power supply
Heat reclaim
VAM 150GJ 250GJ 350GJ 500GJ 650GJ 800GJ 1000GJ 1500GJ 2000GJ VE
ventilator
Note: For details, refer to Engineering Data ED71-613.

VE: 1 phase, 220-240/220 V, 50/60 Hz

 Outdoor Units
VRV X SERIES
Series Model name Power supply,
Standard
8A 10A 12A 14A 16A 18A 18AM 20A 20AM 22AM
Outdoor units RXUQ 24AM 26AM 28AM 30AM 32AM 34AM 36AM 38AM 40AM 42AM Y1S
44AM 46AM 48AM 50AM 52AM 54AM 56AM 58AM 60AM —

VRV A SERIES
Power supply,
Series Model name
Standard
6A 8A 10A 12A 14A 16A 18A 18AM 20A 20AM
Outdoor units RXQ 22AM 24AM 26AM 28AM 30AM 32AM 34AM 36AM 38AM 40AM Y1S
42AM 44AM 46AM 48AM 50AM 52AM 54AM 56AM 58AM 60AM
Y1S: 3 phase, 380-415V, 50Hz (for Thailand)

General Information 9
Model Names of Indoor/Outdoor Units EDAMT341716

1.4 Indonesia

 VRV Indoor Units


2.2 kW 2.8 kW 3.6 kW 4.5 kW 5.6 kW 7.1 kW 9.0 kW 11.2 kW 14.0 kW 16.0 kW 22.4 kW 28.0 kW 45.0 kW 56.0 kW
Capacity range Power
0.8 HP 1 HP 1.25 HP 1.6 HP 2 HP 2.5 HP 3.2 HP 4 HP 5 HP 6 HP 8 HP 10 HP 16 HP 20 HP supply,
Standard
Capacity index 20 25 31.25 40 50 62.5 80 100 125 140 200 250 400 500
Ceiling
mounted
cassette
(Round flow FXFSQ — 25A 32A 40A 50A 63A 80A 100A 125A 140A — — — —
with sensing)
type V4
Ceiling
mounted
cassette FXFQ — 25A 32A 40A 50A 63A 80A 100A 125A 140A — — — —
(Round flow)
type
Ceiling
mounted
cassette
(Compact FXZQ 20M 25M 32M 40M 50M — — — — — — — — —
multi flow)
type
Ceiling
mounted
cassette FXCQ 20M 25M 32M 40M 50M 63M 80M — 125M — — — — —
(Double flow)
type
Ceiling
mounted VE4
cassette FXKQ — 25MA 32MA 40MA — 63MA — — — — — — — —
corner type
FXDQ-
PDVE4 20PD 25PD 32PD — — — — — — — — — — —

Slim ceiling FXDQ-


mounted duct PDVT4 20PD 25PD 32PD — — — — — — — — — — —
type
(Standard FXDQ- — — — 40ND 50ND 63ND — — — — — — — —
series) NDVE4
FXDQ-
— — — 40ND 50ND 63ND — — — — — — — —
NDVT4
Slim ceiling
mounted duct FXDQ-
type 20SP 25SP 32SP 40SP 50SP 63SP — — — — — — — — V14
(Compact SP
series)
Middle static
pressure
ceiling FXSQ 20PA 25PA 32PA 40PA 50PA 63PA 80PA 100PA 125PA 140PA — — — —
mounted duct V4
type
Ceiling FXMQ 20PA 25PA 32PA 40PA 50PA 63PA 80PA 100PA 125PA 140PA — — — —
mounted duct
type FXMQ — — — — — — — — — — 200M 250M — — VE4
Ceiling
suspended FXHQ — — 32MA — — 63MA — 100MA — — — — — — V7
type
Wall mounted
type FXAQ 20P 25P 32P 40P 50P 63P — — — — — — — —
Floor
standing type FXLQ 20MA 25MA 32MA 40MA 50MA 63MA — — — — — — — — VE4
Concealed
floor standing FXNQ 20MA 25MA 32MA 40MA 50MA 63MA — — — — — — — —
type
Floor
standing duct FXVQ — — — — — — — — 125N — 200N 250N 400N 500N Y14
type

Clean type FXBQ — — — 40P 50P 63P — — — — — — — —


air conditioner VE4
FXBPQ — — — — — 63P — — — — — — — —
Note: FXDQ has following 2 series, as shown below.
FXDQ-PDVT4, NDVT4: without a Drain Pump
FXDQ-PDVE4, NDVE4: with a Drain Pump
V4: 1 phase, 230-240 V, 50 Hz
V14:1 phase, 220-240 V, 50 Hz
VE4:1 phase, 220-240/220 V, 50/60 Hz
V7: 1 phase, 220-240/220 V, 50/60 Hz
Y14:3 phase, 380-415 V, 50 Hz

10 General Information
EDAMT341716 Model Names of Indoor/Outdoor Units

 Residential Indoor Units with Connection to BP Units


1
Capacity range 2.5 kW 3.5 kW 5.0 kW 6.0 kW 7.1 kW Power supply,
Capacity index 25 35 50 60 71 Standard
Slim ceiling 25E 35E — — —
mounted duct FDKS VMB4
type 25C 35C 50C 60C —
25N 35N 50N — — VM4W
FTKJ
Wall mounted 25N 35N 50N — — VM4S
type 25D 35D — — —
FTKS VM4
— — 50F 60F 71F
Note: BP units are necessary for residential indoor units.
Residential Indoor units can be connected with only single outdoor units.

VM4:1 phase, 220-240/220-230 V, 50/60 Hz (for Indonesia)

 BP Units
Type Model name
3 Ports BPMKS967A3
BP units
2 Ports BPMKS967A2

 Air Treatment Equipment


Outdoor-air processing Unit
Series Model name Power supply
FXMQ 125MF 200MF 250MF V7
V7: 1 phase, 220-240 V, 50 Hz (for Indonesia)

Heat Reclaim Ventilator (VAM series)


Series Model name Power supply
Heat reclaim
ventilator VAM 150GJ 250GJ 350GJ 500GJ 650GJ 800GJ 1000GJ 1500GJ 2000GJ VE
Note:For details, refer to Engineering Data ED71-613.

VE: 1 phase, 220-240/220 V, 50/60 Hz

 Outdoor Units
VRV X SERIES
Series Model name Power supply
8A 10A 12A 14A 16A 18A 18AM 20A 20AM 22AM
Outdoor units RXUQ 24AM 26AM 28AM 30AM 32AM 34AM 36AM 38AM 40AM 42AM Y14
44AM 46AM 48AM 50AM 52AM 54AM 56AM 58AM 60AM —

VRV A SERIES
Series Model name Power supply
6A 8A 10A 12A 14A 16A 18A 18AM 20A 20AM
Outdoor units RXQ 22AM 24AM 26AM 28AM 30AM 32AM 34AM 36AM 38AM 40AM Y14
42AM 44AM 46AM 48AM 50AM 52AM 54AM 56AM 58AM 60AM
Y14: 3 phase, 380-415 V, 50 Hz (for Indonesia)

General Information 11
Model Names of Indoor/Outdoor Units EDAMT341716

1.5 Philippines

 VRV Indoor Units


2.2 kW 2.8 kW 3.6 kW 4.5 kW 5.6 kW 7.1 kW 8.0 kW 9.0 kW 11.2 kW 14.0 kW 16.0 kW 22.4 kW 28.0 kW 45.0 kW 56.0 kW Power
Capacity range
0.8 HP 1 HP 1.25 HP 1.6 HP 2 HP 2.5 HP 3 HP 3.2 HP 4 HP 5 HP 6 HP 8 HP 10 HP 16 HP 20 HP supply,
Capacity index 20 25 31.25 40 50 62.5 71 80 100 125 140 200 250 400 500 Standard
Ceiling mounted
cassette
(Round flow FXFSQ — 25A 32A 40A 50A 63A — 80A 100A 125A 140A — — — —
with sensing)
type VM
Ceiling mounted
cassette
(Round flow) FXFQ — 25A 32A 40A 50A 63A — 80A 100A 125A 140A — — — —
type
Ceiling mounted
cassette
(Compact multi FXZQ 20M 25M 32M 40M 50M — — — — — — — — — — VE
flow) type
4-way flow
ceiling
suspended FXUQ — — — — — — 71A — 100A — — — — — — VEB
type
Ceiling mounted
cassette
(Double flow) FXCQ 20M 25M 32M 40M 50M 63M — 80M — 125M — — — — —
type
Ceiling mounted
cassette corner FXKQ — 25MA 32MA 40MA — 63MA — — — — — — — — —
type
FXDQ- 20PD 25PD 32PD — — — — — — — — — — — —
PDVE
Slim ceiling FXDQ-
mounted duct PDVET 20PD 25PD 32PD — — — — — — — — — — — —
type
(Standard FXDQ- — — — 40ND 50ND 63ND — — — — — — — — —
series) NDVE
FXDQ- — — — 40ND 50ND 63ND — — — — — — — — —
NDVET
Middle static
pressure VE
ceiling FXSQ 20PA 25PA 32PA 40PA 50PA 63PA — 80PA 100PA 125PA 140PA — — — —
mounted duct
type
Ceiling mounted
duct type FXMQ 20PA 25PA 32PA 40PA 50PA 63PA — 80PA 100PA 125PA 140PA — — — —
Ceiling mounted
duct type FXMQ — — — — — — — — — — — 200MA 250MA — —
Ceiling
suspended FXHQ — — 32MA — — 63MA — — 100MA — — — — — —
type
Wall mounted
type FXAQ 20P 25P 32P 40P 50P 63P — — — — — — — — —
Floor
standing type FXLQ 20MA 25MA 32MA 40MA 50MA 63MA — — — — — — — — —
Concealed
floor standing FXNQ 20MA 25MA 32MA 40MA 50MA 63MA — — — — — — — — —
type
Floor
standing duct FXVQ — — — — — — — — — 125N — 200N 250N 400N 500N TL
type
Clean type FXBQ — — — 40P 50P 63P — — — — — — — — —
air conditioner FXBPQ VE
— — — — — 63P — — — — — — — — —
Note: FXDQ has following 2 series, as shown below.
FXDQ-PDVET, NDVET: without a drain pump
FXDQ-PDVE, NDVE: with a drain pump

VE: 1 phase, 220-240/220 V, 50/60 Hz


VEB, VM: 1 phase, 220-240/220-230 V, 50/60 Hz
TL: 3 phase, 220/230 V, 60 Hz

12 General Information
EDAMT341716 Model Names of Indoor/Outdoor Units

 Residential Indoor Units with Connection to BP Units


1
Capacity range 2.5 kW 3.5 kW 5.0 kW 6.0 kW 7.1 kW Power supply,
Capacity index 25 35 50 60 71 Standard
Slim ceiling
mounted duct CDKS 25K 35K 50K 60K — VM
type
25N 35N 50N — — VMW
Wall mounted FTKJ
type 25N 35N 50N — — VMS
FTKS 25K 35K 50K 60K 71K VM
Note: BP units are necessary for residential indoor units.
Residential indoor units can be connected with only single outdoor units.

VM: 1 phase, 220-240/220-230 V, 50/60 Hz

 BP Units
Type Model name
3 Ports BPMKS967A3
BP units
2 Ports BPMKS967A2

 Air Treatment Equipment


Outdoor-air processing unit
Series Model name Power supply
FXMQ 48MF 72MF 96MF VJU
VJU: 1 phase, 208/230 V, 60 Hz

Heat Reclaim Ventilator (VAM series)


Series Model name Power supply
Heat reclaim
ventilator VAM 150GJ 250GJ 350GJ 500GJ 650GJ 800GJ 1000GJ 1500GJ 2000GJ VE
Note: For details, refer to Engineering Data ED71-613.

VE: 1 phase, 220-240/220 V, 50/60 Hz

 Outdoor Units
VRV X SERIES
Series Model name Power supply
8A 10A 12A 14A 16A 18A 18AM 20A 20AM 22AM
Outdoor units RXUQ 24AM 26AM 28AM 30AM 32AM 34AM 36AM 38AM 40AM 42AM YM
44AM 46AM 48AM 50AM 52AM 54AM 56AM 58AM 60AM —

VRV A SERIES
Series Model name Power supply
6A 8A 10A 12A 14A 16A 18A 18AM 20A 20AM
Outdoor units RXQ 22AM 24AM 26AM 28AM 30AM 32AM 34AM 36AM 38AM 40AM YM
42AM 44AM 46AM 48AM 50AM 52AM 54AM 56AM 58AM 60AM
YM: 3 phase, 380-415/380 V, 50/60 Hz

General Information 13
External Appearance EDAMT341716

2. External Appearance
2.1 Outdoor Units
VRV X SERIES

8, 10, 12, 14, 16, 18, 20 HP 18, 20, 22, 24, 26, 28, 30, 32, 34, 36, 38, 40 HP

RXUQ18AMYM RXUQ18AMY14 RXUQ18AMY1S


RXUQ20AMYM RXUQ20AMY14 RXUQ20AMY1S
RXUQ22AMYM RXUQ22AMY14 RXUQ22AMY1S
RXUQ8AYM RXUQ8AY14 RXUQ8AY1S
RXUQ24AMYM RXUQ24AMY14 RXUQ24AMY1S
RXUQ10AYM RXUQ10AY14 RXUQ10AY1S
RXUQ26AMYM RXUQ26AMY14 RXUQ26AMY1S
RXUQ12AYM RXUQ12AY14 RXUQ12AY1S
RXUQ28AMYM RXUQ28AMY14 RXUQ28AMY1S
RXUQ14AYM RXUQ14AY14 RXUQ14AY1S
RXUQ30AMYM RXUQ30AMY14 RXUQ30AMY1S
RXUQ16AYM RXUQ16AY14 RXUQ16AY1S
RXUQ32AMYM RXUQ32AMY14 RXUQ32AMY1S
RXUQ18AYM RXUQ18AY14 RXUQ18AY1S
RXUQ34AMYM RXUQ34AMY14 RXUQ34AMY1S
RXUQ20AYM RXUQ20AY14 RXUQ20AY1S
RXUQ36AMYM RXUQ36AMY14 RXUQ36AMY1S
RXUQ38AMYM RXUQ38AMY14 RXUQ38AMY1S
RXUQ40AMYM RXUQ40AMY14 RXUQ40AMY1S

42, 44, 46, 48, 50, 52, 54, 56, 58, 60 HP

RXUQ42AMYM RXUQ42AMY14 RXUQ42AMY1S


RXUQ44AMYM RXUQ44AMY14 RXUQ44AMY1S
RXUQ46AMYM RXUQ46AMY14 RXUQ46AMY1S
RXUQ48AMYM RXUQ48AMY14 RXUQ48AMY1S
RXUQ50AMYM RXUQ50AMY14 RXUQ50AMY1S
RXUQ52AMYM RXUQ52AMY14 RXUQ52AMY1S
RXUQ54AMYM RXUQ54AMY14 RXUQ54AMY1S
RXUQ56AMYM RXUQ56AMY14 RXUQ56AMY1S
RXUQ58AMYM RXUQ58AMY14 RXUQ58AMY1S
RXUQ60AMYM RXUQ60AMY14 RXUQ60AMY1S

14 General Information
EDAMT341716 External Appearance

VRV A SERIES
1
6, 8, 10, 12 HP 14, 16, 18, 20 HP

RXQ6AYM RXQ6AY14 RXQ6AY1S RXQ14AYM RXQ14AY14 RXQ14AY1S


RXQ8AYM RXQ8AY14 RXQ8AY1S RXQ16AYM RXQ16AY14 RXQ16AY1S
RXQ10AYM RXQ10AY14 RXQ10AY1S RXQ18AYM RXQ18AY14 RXQ18AY1S
RXQ12AYM RXQ12AY14 RXQ12AY1S RXQ20AYM RXQ20AY14 RXQ20AY1S

18, 20, 22, 24 HP 26, 28, 30 HP 32, 34, 36, 38, 40 HP

RXQ18AMYM RXQ18AMY14 RXQ18AMY1S RXQ26AMYM RXQ26AMY14 RXQ26AMY1S RXQ32AMYM RXQ32AMY14 RXQ32AMY1S


RXQ20AMYM RXQ20AMY14 RXQ20AMY1S RXQ28AMYM RXQ28AMY14 RXQ28AMY1S RXQ34AMYM RXQ34AMY14 RXQ34AMY1S
RXQ22AMYM RXQ22AMY14 RXQ22AMY1S RXQ30AMYM RXQ30AMY14 RXQ30AMY1S RXQ36AMYM RXQ36AMY14 RXQ36AMY1S
RXQ24AMYM RXQ24AMY14 RXQ24AMY1S RXQ38AMYM RXQ38AMY14 RXQ38AMY1S
RXQ40AMYM RXQ40AMY14 RXQ40AMY1S

42, 44 HP 46, 48, 50, 52, 54, 56, 58, 60 HP

RXQ42AMYM RXQ42AMY14 RXQ42AMY1S RXQ46AMYM RXQ46AMY14 RXQ46AMY1S


RXQ44AMYM RXQ44AMY14 RXQ44AMY1S RXQ48AMYM RXQ48AMY14 RXQ48AMY1S
RXQ50AMYM RXQ50AMY14 RXQ50AMY1S
RXQ52AMYM RXQ52AMY14 RXQ52AMY1S
RXQ54AMYM RXQ54AMY14 RXQ54AMY1S
RXQ56AMYM RXQ56AMY14 RXQ56AMY1S
RXQ58AMYM RXQ58AMY14 RXQ58AMY1S
RXQ60AMYM RXQ60AMY14 RXQ60AMY1S

General Information 15
Combination of Outdoor Units EDAMT341716

3. Combination of Outdoor Units


VRV X SERIES
Capacity range 8 HP 10 HP 12 HP 14 HP 16 HP 18 HP 20 HP
Model name RXUQ8A RXUQ10A RXUQ12A RXUQ14A RXUQ16A RXUQ18A RXUQ20A

Capacity range 18 HP 20 HP 22 HP 24 HP 26 HP 28 HP 30 HP 32 HP
Model name RXUQ18AM RXUQ20AM RXUQ22AM RXUQ24AM RXUQ26AM RXUQ28AM RXUQ30AM RXUQ32AM
Outdoor unit 1 RXUQ8A RXUQ8A RXUQ8A RXUQ8A RXUQ8A RXUQ8A RXUQ12A RXUQ12A
Outdoor unit 2 RXUQ10A RXUQ12A RXUQ14A RXUQ16A RXUQ18A RXUQ20A RXUQ18A RXUQ20A
Outdoor unit 3 – – – – – – – –

Capacity range 34 HP 36 HP 38 HP 40 HP 42 HP 44 HP 46 HP 48 HP
Model name RXUQ34AM RXUQ36AM RXUQ38AM RXUQ40AM RXUQ42AM RXUQ44AM RXUQ46AM RXUQ48AM
Outdoor unit 1 RXUQ16A RXUQ18A RXUQ18A RXUQ20A RXUQ8A RXUQ8A RXUQ8A RXUQ8A
Outdoor unit 2 RXUQ18A RXUQ18A RXUQ20A RXUQ20A RXUQ16A RXUQ18A RXUQ18A RXUQ20A
Outdoor unit 3 – – – – RXUQ18A RXUQ18A RXUQ20A RXUQ20A

Capacity range 50 HP 52 HP 54 HP 56 HP 58 HP 60 HP
Model name RXUQ50AM RXUQ52AM RXUQ54AM RXUQ56AM RXUQ58AM RXUQ60AM
Outdoor unit 1 RXUQ12A RXUQ12A RXUQ18A RXUQ18A RXUQ18A RXUQ20A
Outdoor unit 2 RXUQ18A RXUQ20A RXUQ18A RXUQ18A RXUQ20A RXUQ20A
Outdoor unit 3 RXUQ20A RXUQ20A RXUQ18A RXUQ20A RXUQ20A RXUQ20A

System capacity Number Module Outdoor unit multi connection


kW HP of units 8 10 12 14 16 18 20 piping kit 1
22.4 8 1 
28.0 10 1 
33.5 12 1 
40.0 14 1  —
45.0 16 1 
50.0 18 1 
56.0 20 1 
50.4 18 2  
55.9 20 2  
62.4 22 2  
67.4 24 2  
72.4 26 2  
78.4 28 2  
BHFP22P100
83.5 30 2  
89.5 32 2  
95.0 34 2  
100 36 2 
106 38 2  
112 40 2 
117 42 3   
122 44 3  
128 46 3   
134 48 3  
140 50 3   
BHFP22P151
146 52 3  
150 54 3 
156 56 3  
162 58 3  
168 60 3 
Note: 1. For multiple connection, the outdoor unit multi connection piping kit (separately sold) is required.

16 General Information
EDAMT341716 Combination of Outdoor Units

1
VRV A SERIES
Capacity range 6 HP 8 HP 10 HP 12 HP 14 HP 16 HP 18 HP 20 HP
Model name RXQ6A RXQ8A RXQ10A RXQ12A RXQ14A RXQ16A RXQ18A RXQ20A

Capacity range 18 HP 20 HP 22 HP 24 HP 26 HP 28 HP 30 HP 32 HP
Model name RXQ18AM RXQ20AM RXQ22AM RXQ24AM RXQ26AM RXQ28AM RXQ30AM RXQ32AM
Outdoor unit 1 RXQ8A RXQ8A RXQ10A RXQ12A RXQ12A RXQ12A RXQ12A RXQ14A
Outdoor unit 2 RXQ10A RXQ12A RXQ12A RXQ12A RXQ14A RXQ16A RXQ18A RXQ18A
Outdoor unit 3 – – – – – – – –

Capacity range 34 HP 36 HP 38 HP 40 HP 42 HP 44 HP 46 HP 48 HP
Model name RXQ34AM RXQ36AM RXQ38AM RXQ40AM RXQ42AM RXQ44AM RXQ46AM RXQ48AM
Outdoor unit 1 RXQ16A RXQ18A RXQ18A RXQ20A RXQ12A RXQ12A RXQ14A RXQ14A
Outdoor unit 2 RXQ18A RXQ18A RXQ20A RXQ20A RXQ12A RXQ12A RXQ14A RXQ16A
Outdoor unit 3 – – – – RXQ18A RXQ20A RXQ18A RXQ18A

Capacity range 50 HP 52 HP 54 HP 56 HP 58 HP 60 HP
Model name RXQ50AM RXQ52AM RXQ54AM RXQ56AM RXQ58AM RXQ60AM
Outdoor unit 1 RXQ14A RXQ16A RXQ18A RXQ18A RXQ18A RXQ20A
Outdoor unit 2 RXQ18A RXQ18A RXQ18A RXQ18A RXQ20A RXQ20A
Outdoor unit 3 RXQ18A RXQ18A RXQ18A RXQ20A RXQ20A RXQ20A

System capacity Number Module Outdoor unit multi connection


kW HP of units 6 8 10 12 14 16 18 20 piping kit 1
16.0 6 1 
22.4 8 1 
28.0 10 1 
33.5 12 1 

40.0 14 1 
45.0 16 1 
50.0 18 1 
56.0 20 1 
50.4 18 2  
55.9 20 2  
61.5 22 2  
67.0 24 2 
73.5 26 2  
78.5 28 2  
BHFP22P100
83.5 30 2  
90.0 32 2  
95.0 34 2  
100 36 2 
106 38 2  
112 40 2 
117 42 3  
123 44 3  
130 46 3  
135 48 3   
140 50 3  
BHFP22P151
145 52 3  
150 54 3 
156 56 3  
162 58 3  
168 60 3 
Note: 1. For multiple connection, the outdoor unit multi connection piping kit (separately sold) is required.

General Information 17
Nomenclature EDAMT341716

4. Nomenclature
Outdoor Unit

R X U Q 54 AM YM

Power supply symbol


YM: 3 phase, 380-415/380 V, 50/60 Hz
Y14: 3 phase, 380-415 V, 50 Hz (for Indonesia)
Y1S: 3 phase, 380-415 V, 50 Hz (for Thailand)
Module
A: Single unit
AM: Multi unit
Capacity indication
Conversion to kW (Horsepower)
6: 16.0 kW (6 HP)
10: 28.0 kW (10 HP)
60: 168 kW (60 HP)
Refrigerant
Q: R410A
Indicates major design category
U: VRV X SERIES
Blank: VRV A SERIES
Type
Y: Heat pump
Blank: Cooling only
Series category
X: Inverter
Unit category
R: Outdoor unit for air cooled type

18 General Information
EDAMT341716 Capacity Range

1
5. Capacity Range
5.1 For VRV Indoor Units Only
5.1.1 Combination Ratio

Total capacity index of the indoor units


Combination ratio =
Capacity index of the outdoor units

Max. combination ratio


Types of connected indoor units Type of connected air treatment equipment

Min. Including VKM FXMQ-MF


FXDQ, FXFSQ25A,
Type combination FXSQ, When
ratio FXFQ25A, Other When
FXMQ-P, FXFQ25A indoor unit FXMQ-MF
FXAQ, When VKM and indoor FXMQ-MF
and FXVQ models and indoor
FXBQ, units are connected is only units are
at least one connected
FXBPQ unit connected
Single outdoor units 200%
Double outdoor units 50% 200% 130% 160% 130% 100% 100%*
Triple outdoor units 130%
* When outdoor-air processing units (FXMQ-MF) and standard indoor units are connected, the total connection
capacity of the outdoor-air processing units (FXMQ-MF) must not exceed 30% of the capacity index of the
outdoor units. And the connection ratio must not exceed 100%.

Note: When outdoor-air processing mode of FXVQ is selected, be sure to connect as follows:
ASEAN
HP Indoor unit Outdoor unit
5 HP FXVQ125NY1 × 1 RXQ6AYM × 1
8 HP FXVQ200NY1 × 1 RX(U)Q8AYM × 1
10 HP FXVQ250NY1 × 1 RX(U)Q10AYM × 1
16 HP FXVQ400NY1 × 1 RX(U)Q16AYM × 1
FXVQ500NY1 × 1
20 HP RX(U)Q20AYM × 1
FXVQ500NY16 × 1

Indonesia
HP Indoor unit Outdoor unit
5 HP FXVQ125NY1 × 1 RXQ6AY14 × 1
8 HP FXVQ200NY1 × 1 RX(U)Q8AY14 × 1
10 HP FXVQ250NY1 × 1 RX(U)Q10AY14 × 1
16 HP FXVQ400NY1 × 1 RX(U)Q16AY14 × 1
20 HP FXVQ500NY1 × 1 RX(U)Q20AY14 × 1

Thailand
HP Indoor unit Outdoor unit
5 HP FXVQ125NY1 × 1 RXQ6AY1S × 1
8 HP FXVQ200NY1 × 1 RX(U)Q8AY1S × 1
10 HP FXVQ250NY1 × 1 RX(U)Q10AY1S × 1
16 HP FXVQ400NY1 × 1 RX(U)Q16AY1S × 1
FXVQ500NY1 × 1
20 HP RX(U)Q20AY1S × 1
FXVQ500NY16 × 1

General Information 19
Capacity Range EDAMT341716

5.1.2 Outdoor Unit Combinations


VRV X SERIES
Capacity Outdoor unit multi Total capacity index of Maximum number of
kW HP Model name Combination
index connection piping kit *1 connectable indoor units *2 *3 connectable indoor units *2
22.4 8 HP 200 RXUQ8A RXUQ8A — 100 to 260 (400) 13 (20)
28.0 10 HP 250 RXUQ10A RXUQ10A — 125 to 325 (500) 16 (25)
33.5 12 HP 300 RXUQ12A RXUQ12A — 150 to 390 (600) 19 (30)
40.0 14 HP 350 RXUQ14A RXUQ14A — 175 to 455 (700) 22 (35)
45.0 16 HP 400 RXUQ16A RXUQ16A — 200 to 520 (800) 26 (40)
50.0 18 HP 450 RXUQ18A RXUQ18A — 225 to 585 (900) 29 (45)
56.0 20 HP 500 RXUQ20A RXUQ20A — 250 to 650 (1,000) 32 (50)
50.4 18 HP 450 RXUQ18AM RXUQ8A + RXUQ10A 225 to 585 (720) 29 (36)
55.9 20 HP 500 RXUQ20AM RXUQ8A + RXUQ12A 250 to 650 (800) 32 (40)
62.4 22 HP 550 RXUQ22AM RXUQ8A + RXUQ14A 275 to 715 (880) 35 (44)
67.4 24 HP 600 RXUQ24AM RXUQ8A + RXUQ16A 300 to 780 (960) 39 (48)
72.4 26 HP 650 RXUQ26AM RXUQ8A + RXUQ18A 325 to 845 (1,040) 42 (52)
78.4 28 HP 700 RXUQ28AM RXUQ8A + RXUQ20A 350 to 910 (1,120) 45 (56)
BHFP22P100
83.5 30 HP 750 RXUQ30AM RXUQ12A + RXUQ18A 375 to 975 (1,200) 48 (60)
89.5 32 HP 800 RXUQ32AM RXUQ12A + RXUQ20A 400 to 1,040 (1,280) 52 (64)
95.0 34 HP 850 RXUQ34AM RXUQ16A + RXUQ18A 425 to 1,105 (1,360) 55 (64)
100 36 HP 900 RXUQ36AM RXUQ18A × 2 450 to 1,170 (1,440) 58 (64)
106 38 HP 950 RXUQ38AM RXUQ18A + RXUQ20A 475 to 1,235 (1,520) 61 (64)
112 40 HP 1,000 RXUQ40AM RXUQ20A × 2 500 to 1,300 (1,600)
117 42 HP 1,050 RXUQ42AM RXUQ8A + RXUQ16A + RXUQ18A 525 to 1,365 (1,365)
122 44 HP 1,100 RXUQ44AM RXUQ8A + RXUQ18A × 2 550 to 1,430 (1,430)
128 46 HP 1,150 RXUQ46AM RXUQ8A + RXUQ18A + RXUQ20A 575 to 1,495 (1,495)
134 48 HP 1,200 RXUQ48AM RXUQ8A + RXUQ20A × 2 600 to 1,560 (1,560)
140 50 HP 1,250 RXUQ50AM RXUQ12A + RXUQ18A + RXUQ20A 625 to 1,625 (1,625) 64 (64)
BHFP22P151
146 52 HP 1,300 RXUQ52AM RXUQ12A + RXUQ20A × 2 650 to 1,690 (1,690)
150 54 HP 1,350 RXUQ54AM RXUQ18A × 3 675 to 1,755 (1,755)
156 56 HP 1,400 RXUQ56AM RXUQ18A × 2 + RXUQ20A 700 to 1,820 (1,820)
162 58 HP 1,450 RXUQ58AM RXUQ18A + RXUQ20A × 2 725 to 1,885 (1,885)
168 60 HP 1,500 RXUQ60AM RXUQ20A × 3 750 to 1,950 (1,950)
Notes: *1. For multiple connection, the outdoor unit multi connection piping kit (separately sold) is required.
*2. Values inside brackets are based on connection of indoor units rated at maximum capacity, 200% for
single outdoor units, 160% for double outdoor units, and 130% for triple outdoor units.
*3. When outdoor-air processing units (FXMQ-MF) and standard indoor units are connected, the total
connection capacity of the outdoor-air processing units (FXMQ-MF) must not exceed 30% of the
capacity index of the outdoor units. And the connection ratio must not exceed 100%.

20 General Information
EDAMT341716 Capacity Range

VRV A SERIES
1
Capacity Outdoor unit multi Total capacity index of Maximum number of
kW HP Model name Combination
index connection piping kit *1 connectable indoor units *2 *3 connectable indoor units *2
16.0 6 HP 150 RXQ6A RXQ6A — 75 to 195 (300) 9 (15)
22.4 8 HP 200 RXQ8A RXQ8A — 100 to 260 (400) 13 (20)
28.0 10 HP 250 RXQ10A RXQ10A — 125 to 325 (500) 16 (25)
33.5 12 HP 300 RXQ12A RXQ12A — 150 to 390 (600) 19 (30)
40.0 14 HP 350 RXQ14A RXQ14A — 175 to 455 (700) 22 (35)
45.0 16 HP 400 RXQ16A RXQ16A — 200 to 520 (800) 26 (40)
50.0 18 HP 450 RXQ18A RXQ18A — 225 to 585 (900) 29 (45)
56.0 20 HP 500 RXQ20A RXQ20A — 250 to 650 (1,000) 32 (50)
50.4 18 HP 450 RXQ18AM RXQ8A + RXQ10A 225 to 585 (720) 29 (36)
55.9 20 HP 500 RXQ20AM RXQ8A + RXQ12A 250 to 650 (800) 32 (40)
61.5 22 HP 550 RXQ22AM RXQ10A + RXQ12A 275 to 715 (880) 35 (44)
67.0 24 HP 600 RXQ24AM RXQ12A × 2 300 to 780 (960) 39 (48)
73.5 26 HP 650 RXQ26AM RXQ12A + RXQ14A 325 to 845 (1,040) 42 (52)
78.5 28 HP 700 RXQ28AM RXQ12A + RXQ16A 350 to 910 (1,120) 45 (56)
BHFP22P100
83.5 30 HP 750 RXQ30AM RXQ12A + RXQ18A 375 to 975 (1,200) 48 (60)
90.0 32 HP 800 RXQ32AM RXQ14A + RXQ18A 400 to 1,040 (1,280) 52 (64)
95.0 34 HP 850 RXQ34AM RXQ16A + RXQ18A 425 to 1,105 (1,360) 55 (64)
100 36 HP 900 RXQ36AM RXQ18A × 2 450 to 1,170 (1,440) 58 (64)
106 38 HP 950 RXQ38AM RXQ18A + RXQ20A 475 to 1,235 (1,520) 61 (64)
112 40 HP 1,000 RXQ40AM RXQ20A × 2 500 to 1,300 (1,600)
117 42 HP 1,050 RXQ42AM RXQ12A × 2 + RXQ18A 525 to 1,365 (1,365)
123 44 HP 1,100 RXQ44AM RXQ12A × 2 + RXQ20A 550 to 1,430 (1,430)
130 46 HP 1,150 RXQ46AM RXQ14A × 2 + RXQ18A 575 to 1,495 (1,495)
135 48 HP 1,200 RXQ48AM RXQ14A + RXQ16A + RXQ18A 600 to 1,560 (1,560)
140 50 HP 1,250 RXQ50AM RXQ14A + RXQ18A × 2 625 to 1,625 (1,625) 64 (64)
BHFP22P151
145 52 HP 1,300 RXQ52AM RXQ16A + RXQ18A × 2 650 to 1,690 (1,690)
150 54 HP 1,350 RXQ54AM RXQ18A × 3 675 to 1,755 (1,755)
156 56 HP 1,400 RXQ56AM RXQ18A × 2 + RXQ20A 700 to 1,820 (1,820)
162 58 HP 1,450 RXQ58AM RXQ18A + RXQ20A × 2 725 to 1,885 (1,885)
168 60 HP 1,500 RXQ60AM RXQ20A × 3 750 to 1,950 (1,950)
Notes: *1. For multiple connection, the outdoor unit multi connection piping kit (separately sold) is required.
*2. Values inside brackets are based on connection of indoor units rated at maximum capacity, 200% for
single outdoor units, 160% for double outdoor units, and 130% for triple outdoor units.
*3. When outdoor-air processing units (FXMQ-MF) and standard indoor units are connected, the total
connection capacity of the outdoor-air processing units (FXMQ-MF) must not exceed 30% of the
capacity index of the outdoor units. And the connection ratio must not exceed 100%.

General Information 21
Capacity Range EDAMT341716

5.2 For a System with Residential Indoor Units or VRV Mix Combination
5.2.1 Combination Ratio

Total capacity index of the indoor units


Combination ratio =
Capacity index of the outdoor units

Max. combination ratio


Type of connected Type of connected air treatment equipment
Min. combination indoor units VKM FXMQ-MF
Type ratio
When FXMQ-MF and
Residential indoor units When VKM and indoor indoor units are
or VRV mix combination units are connected
connected
Single outdoor units 50% 130% 130% 100% *1
Note: *1. When outdoor-air processing units (FXMQ-MF) and standard indoor units are connected, the total
connection capacity of the outdoor-air processing units (FXMQ-MF) must not exceed 30% of the
capacity index of the outdoor units. And the connection ratio must not exceed 100%.

5.2.2 Outdoor Unit Combinations


VRV X SERIES
Total capacity index of connectable indoor units *2
Capacity Maximum number of
kW HP index Model name *1 Combination ratio (%) connectable indoor units
50% 100% 130%
22.4 8 HP 200 RXUQ8A 100 200 260 13
28.0 10 HP 250 RXUQ10A 125 250 325 16
33.5 12 HP 300 RXUQ12A 150 300 390 19
40.0 14 HP 350 RXUQ14A 175 350 455 22
45.0 16 HP 400 RXUQ16A 200 400 520 26
50.0 18 HP 450 RXUQ18A 225 450 585 29
56.0 20 HP 500 RXUQ20A 250 500 650 32
Notes: *1. Only single outdoor unit (RXUQ8-20A) can be connected.
*2. When outdoor-air processing units (FXMQ-MF) and standard indoor units are connected, the total
connection capacity of the outdoor-air processing units (FXMQ-MF) must not exceed 30% of the
capacity index of the outdoor units. And the connection ratio must not exceed 100%.

VRV A SERIES
Total capacity index of connectable indoor units *2
Capacity Maximum number of
kW HP index Model name *1 Combination ratio (%) connectable indoor units
50% 100% 130%
16.0 6 HP 150 RXQ6A 75 150 195 9
22.4 8 HP 200 RXQ8A 100 200 260 13
28.0 10 HP 250 RXQ10A 125 250 325 16
33.5 12 HP 300 RXQ12A 150 300 390 19
40.0 14 HP 350 RXQ14A 175 350 455 22
45.0 16 HP 400 RXQ16A 200 400 520 26
50.0 18 HP 450 RXQ18A 225 450 585 29
56.0 20 HP 500 RXQ20A 250 500 650 32
Notes: *1. Only single outdoor unit (RXQ6-20A) can be connected.
*2. When outdoor-air processing units (FXMQ-MF) and standard indoor units are connected, the total
connection capacity of the outdoor-air processing units (FXMQ-MF) must not exceed 30% of the
capacity index of the outdoor units. And the connection ratio must not exceed 100%.

22 General Information
EDAMT341716

Part 2
Outdoor Units

RXUQ-A(M)
Cooling Only 50/60 Hz VRV X SERIES. . . . . . . . . . 25

RXQ-A(M)
Cooling Only 50/60 Hz VRV A SERIES. . . . . . . . . . 53

Outdoor Units 23
EDAMT341716

24 Outdoor Units
EDAMT341716

RXUQ-A(M)
2
Cooling Only 50/60 Hz VRV X SERIES

1. Specifications ........................................................................................26
1.1 Cooling Only 50/60 Hz VRV X SERIES (RXUQ-A(M))...........................26
2. Dimensions ...........................................................................................41
2.1 Independent Unit ....................................................................................41
2.2 Combination Unit....................................................................................42
3. Service Space (Reference) ...................................................................44
4. Piping Diagrams....................................................................................45
5. Wiring Diagrams (Reference)................................................................46
6. Field Wiring ...........................................................................................47
7. Operation Limits (Reference) ................................................................50
8. Accessories...........................................................................................51
8.1 Optional Accessories..............................................................................51

RXUQ-A(M) 25
Specifications EDAMT341716

1. Specifications
1.1 Cooling Only 50/60 Hz VRV X SERIES (RXUQ-A(M))
Model Name RXUQ8AYM RXUQ8AY14 RXUQ8AY1S RXUQ10AYM RXUQ10AY14 RXUQ10AY1S
3 phase, 3 phase, 3 phase, 3 phase, 3 phase, 3 phase,
Power Supply 380-415/380 V, 380-415 V, 380-415 V, 380-415/380 V, 380-415 V, 380-415 V,
50/60 Hz 50 Hz 50 Hz 50/60 Hz 50 Hz 50 Hz
kcal/h 19,300 24,100
1 Cooling Capacity Btu/h 76,400 95,500
kW 22.4 28.0
Casing Color Ivory white (5Y7.5/1) Ivory white (5Y7.5/1)
Dimensions: (H×W×D) mm 1,657×1,240×765 1,657×1,240×765
Heat Exchanger Cross fin coil Cross fin coil
Type Hermetically sealed scroll type Hermetically sealed scroll type
Motor Output×
Compressor kW (1.8×1)+(1.7×1) (1.7×1)+(2.8×1)
Number of Units
Starting Method Soft start Soft start
Type Propeller fan Propeller fan
Motor Output kW 0.75×2 0.75×2
Fan
Airflow Rate m³/min 163 192
Drive Direct drive Direct drive
Connecting Liquid Pipe mm 9.5 C1220T (Brazing connection) 9.5 C1220T (Brazing connection)
Pipes Gas Pipe mm 19.1 C1220T (Brazing connection) 22.2 C1220T (Brazing connection)
Mass kg 273 312
2 Sound pressure level dB(A) 55 57
High pressure switch, Fan driver overload protector, High pressure switch, Fan driver overload protector,
Safety Devices
Over current relay, Inverter overload protector Over current relay, Inverter overload protector
Capacity Control % 20-100 12-100
Refrigerant Name R410A R410A
Refrigerant Charge kg 8.1 11.3
Control Electronic expansion valve Electronic expansion valve
Refrigerator Oil Refer to the nameplate of compressor Refer to the nameplate of compressor
Installation manual, Operation manual, Connection pipes, Installation manual, Operation manual, Connection pipes,
Standard Accessories
Clamps Clamps
Specifications C: 3D111861 C: 3D111861
Drawing No.
Sound level — —

Notes:
Conversion formulae
1. Indoor temp.: 27°CDB, 19°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5 m, level difference: 0 m.
2. Anechoic chamber conversion value, measured at a point 1 m in front of the unit at a height of 1.5 m. kcal/h=kW×860
Btu/h=kW×3412
During actual operation, these values are normally somewhat higher as a result of ambient conditions. cfm=m³/min×35.3

26 RXUQ-A(M)
EDAMT341716 Specifications

Model Name RXUQ12AYM


3 phase,
RXUQ12AY14
3 phase,
RXUQ12AY1S
3 phase,
RXUQ14AYM
3 phase,
RXUQ14AY14
3 phase,
RXUQ14AY1S
3 phase,
2
Power Supply 380-415/380 V, 380-415 V, 380-415 V, 380-415/380 V, 380-415 V, 380-415 V,
50/60 Hz 50 Hz 50 Hz 50/60 Hz 50 Hz 50 Hz
kcal/h 28,800 34,400
1 Cooling Capacity Btu/h 114,000 136,000
kW 33.5 40.0
Casing Color Ivory white (5Y7.5/1) Ivory white (5Y7.5/1)
Dimensions: (H×W×D) mm 1,657×1,240×765 1,657×1,240×765
Heat Exchanger Cross fin coil Cross fin coil
Type Hermetically sealed scroll type Hermetically sealed scroll type
Motor Output×
Compressor kW (2.2×1)+(3.1×1) (3.6×1)+(3.1×1)
Number of Units
Starting Method Soft start Soft start
Type Propeller fan Propeller fan
Motor Output kW 0.75×2 0.75×2
Fan
Airflow Rate m³/min 213 218
Drive Direct drive Direct drive
Connecting Liquid Pipe mm 12.7 C1220T (Brazing connection) 12.7 C1220T (Brazing connection)
Pipes Gas Pipe mm 28.6 C1220T (Brazing connection) 28.6 C1220T (Brazing connection)
Mass kg 312 318
2 Sound pressure level dB(A) 60 60
High pressure switch, Fan driver overload protector, High pressure switch, Fan driver overload protector,
Safety Devices Over current relay, Inverter overload protector Over current relay, Inverter overload protector
Capacity Control % 12-100 11-100
Refrigerant Name R410A R410A
Refrigerant Charge kg 11.4 11.5
Control Electronic expansion valve Electronic expansion valve
Refrigerator Oil Refer to the nameplate of compressor Refer to the nameplate of compressor
Installation manual, Operation manual, Connection pipes, Installation manual, Operation manual, Connection pipes,
Standard Accessories
Clamps Clamps
Specifications C: 3D111861 C: 3D111861
Drawing No.
Sound level — —

Notes: Conversion formulae


1. Indoor temp.: 27°CDB, 19°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5 m, level difference: 0 m.
kcal/h=kW×860
2. Anechoic chamber conversion value, measured at a point 1 m in front of the unit at a height of 1.5 m. Btu/h=kW×3412
During actual operation, these values are normally somewhat higher as a result of ambient conditions. cfm=m³/min×35.3

RXUQ-A(M) 27
Specifications EDAMT341716

Model Name RXUQ16AYM RXUQ16AY14 RXUQ16AY1S


Power Supply 3 phase, 380-415/380 V, 50/60 Hz 3 phase, 380-415 V, 50 Hz 3 phase, 380-415 V, 50 Hz
kcal/h 38,700
1 Cooling Capacity Btu/h 154,000
kW 45.0
Casing Color Ivory white (5Y7.5/1)
Dimensions: (H×W×D) mm 1,657×1,240×765
Heat Exchanger Cross fin coil
Type Hermetically sealed scroll type
Motor Output×
Compressor kW (3.8×1)+(3.8×1)
Number of Units
Starting Method Soft start
Type Propeller fan
Motor Output kW 0.75×2
Fan
Airflow Rate m³/min 218
Drive Direct drive
Connecting Liquid Pipe mm 12.7 C1220T (Brazing connection)
Pipes Gas Pipe mm 28.6 C1220T (Brazing connection)
Mass kg 318
2 Sound pressure level dB(A) 61
High pressure switch, Fan driver overload protector,
Safety Devices
Over current relay, Inverter overload protector
Capacity Control % 9-100
Refrigerant Name R410A
Refrigerant Charge kg 11.7
Control Electronic expansion valve
Refrigerator Oil Refer to the nameplate of compressor
Standard Accessories Installation manual, Operation manual, Connection pipes, Clamps
Specifications C: 3D111861
Drawing No.
Sound level —

Notes: Conversion formulae


1. Indoor temp.: 27°CDB, 19°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5 m, level difference: 0 m.
kcal/h=kW×860
2. Anechoic chamber conversion value, measured at a point 1 m in front of the unit at a height of 1.5 m. Btu/h=kW×3412
During actual operation, these values are normally somewhat higher as a result of ambient conditions. cfm=m³/min×35.3

28 RXUQ-A(M)
EDAMT341716 Specifications

Model Name (Combination Unit) RXUQ18AYM RXUQ18AY14 RXUQ18AY1S RXUQ18AMYM


RXUQ8AYM+
RXUQ18AMY14
RXUQ8AY14+
RXUQ18AMY1S
RXUQ8AY1S+
2
Model Name (Independent Unit) — — —
RXUQ10AYM RXUQ10AY14 RXUQ10AY1S
3 phase, 3 phase, 3 phase, 3 phase, 3 phase, 3 phase,
Power Supply 380-415/380 V, 380-415 V, 380-415 V, 380-415/380 V, 380-415 V, 380-415 V,
50/60 Hz 50 Hz 50 Hz 50/60 Hz 50 Hz 50 Hz
kcal/h 43,000 43,300
1 Cooling Capacity Btu/h 171,000 172,000
kW 50.0 50.4
Casing Color Ivory white (5Y7.5/1) Ivory white (5Y7.5/1)
Dimensions: (H×W×D) mm 1,657×1,240×765 (1,657×1,240×765)+(1,657×1,240×765)
Heat Exchanger Cross fin coil Cross fin coil
Type Hermetically sealed scroll type Hermetically sealed scroll type
Motor Output×
Compressor kW (4.5×1)+(4.1×1) (1.8×1)+(1.7×1)+(1.7×1)+(2.8×1)
Number of Units
Starting Method Soft start Soft start
Type Propeller fan Propeller fan
Motor Output kW 0.75×2 (0.75×2)+(0.75×2)
Fan
Airflow Rate m³/min 268 163+192
Drive Direct drive Direct drive
Connecting Liquid Pipe mm 15.9 C1220T (Brazing connection) 15.9 C1220T (Brazing connection)
Pipes Gas Pipe mm 28.6 C1220T (Brazing connection) 28.6 C1220T (Brazing connection)
Mass kg 318 273+312
2 Sound pressure level dB(A) 65 59
High pressure switch, Fan driver overload protector, High pressure switch, Fan driver overload protector,
Safety Devices
Over current relay, Inverter overload protector Over current relay, Inverter overload protector
Capacity Control % 9-100 7-100
Refrigerant Name R410A R410A
Refrigerant Charge kg 11.7 8.1+11.3
Control Electronic expansion valve Electronic expansion valve
Refrigerator Oil Refer to the nameplate of compressor Refer to the nameplate of compressor
Installation manual, Operation manual, Connection pipes, Installation manual, Operation manual, Connection pipes,
Standard Accessories
Clamps Clamps
Specifications C: 3D111861 —
Drawing No.
Sound level — —

Notes:
Conversion formulae
1. Indoor temp.: 27°CDB, 19°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5 m, level difference: 0 m.
2. Anechoic chamber conversion value, measured at a point 1 m in front of the unit at a height of 1.5 m. kcal/h=kW×860
Btu/h=kW×3412
During actual operation, these values are normally somewhat higher as a result of ambient conditions. cfm=m³/min×35.3

RXUQ-A(M) 29
Specifications EDAMT341716

Model Name (Combination Unit) RXUQ20AYM RXUQ20AY14 RXUQ20AY1S RXUQ20AMYM RXUQ20AMY14 RXUQ20AMY1S
RXUQ8AYM+ RXUQ8AY14+ RXUQ8AY1S+
Model Name (Independent Unit) — — —
RXUQ12AYM RXUQ12AY14 RXUQ12AY1S
3 phase, 3 phase, 3 phase, 3 phase, 3 phase, 3 phase,
Power Supply 380-415/380 V, 380-415 V, 380-415 V, 380-415/380 V, 380-415 V, 380-415 V,
50/60 Hz 50 Hz 50 Hz 50/60 Hz 50 Hz 50 Hz
kcal/h 48,200 48,100
1 Cooling Capacity Btu/h 191,000 191,000
kW 56.0 55.9
Casing Color Ivory white (5Y7.5/1) Ivory white (5Y7.5/1)
Dimensions: (H×W×D) mm 1,657×1,240×765 (1,657×1,240×765)+(1,657×1,240×765)
Heat Exchanger Cross fin coil Cross fin coil
Type Hermetically sealed scroll type Hermetically sealed scroll type
Motor Output×
Compressor kW (5.1×1)+(5.0×1) (1.8×1)+(1.7×1)+(2.2×1)+(3.1×1)
Number of Units
Starting Method Soft start Soft start
Type Propeller fan Propeller fan
Motor Output kW 0.75×2 (0.75×2)+(0.75×2)
Fan
Airflow Rate m³/min 268 163+213
Drive Direct drive Direct drive
Connecting Liquid Pipe mm 15.9 C1220T (Brazing connection) 15.9 C1220T (Brazing connection)
Pipes Gas Pipe mm 28.6 C1220T (Brazing connection) 28.6 C1220T (Brazing connection)
Mass kg 318 273+312
2 Sound pressure level dB(A) 65 61
High pressure switch, Fan driver overload protector, High pressure switch, Fan driver overload protector,
Safety Devices
Over current relay, Inverter overload protector Over current relay, Inverter overload protector
Capacity Control % 7-100 7-100
Refrigerant Name R410A R410A
Refrigerant Charge kg 11.7 8.1+11.4
Control Electronic expansion valve Electronic expansion valve
Refrigerator Oil Refer to the nameplate of compressor Refer to the nameplate of compressor
Installation manual, Operation manual, Connection pipes, Installation manual, Operation manual, Connection pipes,
Standard Accessories
Clamps Clamps
Specifications C: 3D111861 —
Drawing No.
Sound level — —

Notes:
Conversion formulae
1. Indoor temp.: 27°CDB, 19°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5 m, level difference: 0 m.
2. Anechoic chamber conversion value, measured at a point 1 m in front of the unit at a height of 1.5 m. kcal/h=kW×860
Btu/h=kW×3412
During actual operation, these values are normally somewhat higher as a result of ambient conditions. cfm=m³/min×35.3

30 RXUQ-A(M)
EDAMT341716 Specifications

Model Name (Combination Unit) RXUQ22AMYM


RXUQ8AYM+
RXUQ22AMY14
RXUQ8AY14+
RXUQ22AMY1S
RXUQ8AY1S+
RXUQ24AMYM
RXUQ8AYM+
RXUQ24AMY14
RXUQ8AY14+
RXUQ24AMY1S
RXUQ8AY1S+
2
Model Name (Independent Unit)
RXUQ14AYM RXUQ14AY14 RXUQ14AY1S RXUQ16AYM RXUQ16AY14 RXUQ16AY1S
3 phase, 3 phase, 3 phase, 3 phase, 3 phase, 3 phase,
Power Supply 380-415/380 V, 380-415 V, 380-415 V, 380-415/380 V, 380-415 V, 380-415 V,
50/60 Hz 50 Hz 50 Hz 50/60 Hz 50 Hz 50 Hz
kcal/h 53,700 58,000
1 Cooling Capacity Btu/h 213,000 230,000
kW 62.4 67.4
Casing Color Ivory white (5Y7.5/1) Ivory white (5Y7.5/1)
Dimensions: (H×W×D) mm (1,657×1,240×765)+(1,657×1,240×765) (1,657×1,240×765)+(1,657×1,240×765)
Heat Exchanger Cross fin coil Cross fin coil
Type Hermetically sealed scroll type Hermetically sealed scroll type
Motor Output×
Compressor kW (1.8×1)+(1.7×1)+(3.6×1)+(3.1×1) (1.8×1)+(1.7×1)+(3.8×1)+(3.8×1)
Number of Units
Starting Method Soft start Soft start
Type Propeller fan Propeller fan
Motor Output kW (0.75×2)+(0.75×2) (0.75×2)+(0.75×2)
Fan
Airflow Rate m³/min 163+218 163+218
Drive Direct drive Direct drive
Connecting Liquid Pipe mm 15.9 C1220T (Brazing connection) 15.9 C1220T (Brazing connection)
Pipes Gas Pipe mm 28.6 C1220T (Brazing connection) 34.9 C1220T (Brazing connection)
Mass kg 273+318 273+318
2 Sound pressure level dB(A) 61 62
High pressure switch, Fan driver overload protector, High pressure switch, Fan driver overload protector,
Safety Devices
Over current relay, Inverter overload protector Over current relay, Inverter overload protector
Capacity Control % 7-100 6-100
Refrigerant Name R410A R410A
Refrigerant Charge kg 8.1+11.5 8.1+11.7
Control Electronic expansion valve Electronic expansion valve
Refrigerator Oil Refer to the nameplate of compressor Refer to the nameplate of compressor
Installation manual, Operation manual, Connection pipes, Installation manual, Operation manual, Connection pipes,
Standard Accessories
Clamps Clamps
Specifications — —
Drawing No.
Sound level — —

Notes:
Conversion formulae
1. Indoor temp.: 27°CDB, 19°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5 m, level difference: 0 m.
2. Anechoic chamber conversion value, measured at a point 1 m in front of the unit at a height of 1.5 m. kcal/h=kW×860
Btu/h=kW×3412
During actual operation, these values are normally somewhat higher as a result of ambient conditions. cfm=m³/min×35.3

RXUQ-A(M) 31
Specifications EDAMT341716

Model Name (Combination Unit) RXUQ26AMYM RXUQ26AMY14 RXUQ26AMY1S RXUQ28AMYM RXUQ28AMY14 RXUQ28AMY1S
RXUQ8AYM+ RXUQ8AY14+ RXUQ8AY1S+ RXUQ8AYM+ RXUQ8AY14+ RXUQ8AY1S+
Model Name (Independent Unit)
RXUQ18AYM RXUQ18AY14 RXUQ18AY1S RXUQ20AYM RXUQ20AY14 RXUQ20AY1S
3 phase, 3 phase, 3 phase, 3 phase, 3 phase, 3 phase,
Power Supply 380-415/380 V, 380-415 V, 380-415 V, 380-415/380 V, 380-415 V, 380-415 V,
50/60 Hz 50 Hz 50 Hz 50/60 Hz 50 Hz 50 Hz
kcal/h 62,300 67,400
1 Cooling Capacity Btu/h 247,000 268,000
kW 72.4 78.4
Casing Color Ivory white (5Y7.5/1) Ivory white (5Y7.5/1)
Dimensions: (H×W×D) mm (1,657×1,240×765)+(1,657×1,240×765) (1,657×1,240×765)+(1,657×1,240×765)
Heat Exchanger Cross fin coil Cross fin coil
Type Hermetically sealed scroll type Hermetically sealed scroll type
Motor Output×
Compressor kW (1.8×1)+(1.7×1)+(4.5×1)+(4.1×1) (1.8×1)+(1.7×1)+(5.1×1)+(5.0×1)
Number of Units
Starting Method Soft start Soft start
Type Propeller fan Propeller fan
Motor Output kW (0.75×2)+(0.75×2) (0.75×2)+(0.75×2)
Fan
Airflow Rate m³/min 163+268 163+268
Drive Direct drive Direct drive
Connecting Liquid Pipe mm 19.1 C1220T (Brazing connection) 19.1 C1220T (Brazing connection)
Pipes Gas Pipe mm 34.9 C1220T (Brazing connection) 34.9 C1220T (Brazing connection)
Mass kg 273+318 273+318
2 Sound pressure level dB(A) 65 65
High pressure switch, Fan driver overload protector, High pressure switch, Fan driver overload protector,
Safety Devices
Over current relay, Inverter overload protector Over current relay, Inverter overload protector
Capacity Control % 6-100 5-100
Refrigerant Name R410A R410A
Refrigerant Charge kg 8.1+11.7 8.1+11.7
Control Electronic expansion valve Electronic expansion valve
Refrigerator Oil Refer to the nameplate of compressor Refer to the nameplate of compressor
Installation manual, Operation manual, Connection pipes, Installation manual, Operation manual, Connection pipes,
Standard Accessories
Clamps Clamps
Specifications — —
Drawing No.
Sound level — —

Notes:
Conversion formulae
1. Indoor temp.: 27°CDB, 19°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5 m, level difference: 0 m.
2. Anechoic chamber conversion value, measured at a point 1 m in front of the unit at a height of 1.5 m. kcal/h=kW×860
Btu/h=kW×3412
During actual operation, these values are normally somewhat higher as a result of ambient conditions. cfm=m³/min×35.3

32 RXUQ-A(M)
EDAMT341716 Specifications

Model Name (Combination Unit) RXUQ30AMYM


RXUQ12AYM+
RXUQ30AMY14
RXUQ12AY14+
RXUQ30AMY1S
RXUQ12AY1S+
RXUQ32AMYM
RXUQ12AYM+
RXUQ32AMY14
RXUQ12AY14+
RXUQ32AMY1S
RXUQ12AY1S+
2
Model Name (Independent Unit)
RXUQ18AYM RXUQ18AY14 RXUQ18AY1S RXUQ20AYM RXUQ20AY14 RXUQ20AY1S
3 phase, 3 phase, 3 phase, 3 phase, 3 phase, 3 phase,
Power Supply 380-415/380 V, 380-415 V, 380-415 V, 380-415/380 V, 380-415 V, 380-415 V,
50/60 Hz 50 Hz 50 Hz 50/60 Hz 50 Hz 50 Hz
kcal/h 71,800 77,000
1 Cooling Capacity Btu/h 285,000 305,000
kW 83.5 89.5
Casing Color Ivory white (5Y7.5/1) Ivory white (5Y7.5/1)
Dimensions: (H×W×D) mm (1,657×1,240×765)+(1,657×1,240×765) (1,657×1,240×765)+(1,657×1,240×765)
Heat Exchanger Cross fin coil Cross fin coil
Type Hermetically sealed scroll type Hermetically sealed scroll type
Motor Output×
Compressor kW (2.2×1)+(3.1×1)+(4.5×1)+(4.1×1) (2.2×1)+(3.1×1)+(5.1×1)+(5.0×1)
Number of Units
Starting Method Soft start Soft start
Type Propeller fan Propeller fan
Motor Output kW (0.75×2)+(0.75×2) (0.75×2)+(0.75×2)
Fan
Airflow Rate m³/min 213+268 213+268
Drive Direct drive Direct drive
Connecting Liquid Pipe mm 19.1 C1220T (Brazing connection) 19.1 C1220T (Brazing connection)
Pipes Gas Pipe mm 34.9 C1220T (Brazing connection) 34.9 C1220T (Brazing connection)
Mass kg 312+318 312+318
2 Sound pressure level dB(A) 66 66
High pressure switch, Fan driver overload protector, High pressure switch, Fan driver overload protector,
Safety Devices
Over current relay, Inverter overload protector Over current relay, Inverter overload protector
Capacity Control % 5-100 4-100
Refrigerant Name R410A R410A
Refrigerant Charge kg 11.4+11.7 11.4+11.7
Control Electronic expansion valve Electronic expansion valve
Refrigerator Oil Refer to the nameplate of compressor Refer to the nameplate of compressor
Installation manual, Operation manual, Connection pipes, Installation manual, Operation manual, Connection pipes,
Standard Accessories
Clamps Clamps
Specifications — —
Drawing No.
Sound level — —

Notes:
Conversion formulae
1. Indoor temp.: 27°CDB, 19°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5 m, level difference: 0 m.
2. Anechoic chamber conversion value, measured at a point 1 m in front of the unit at a height of 1.5 m. kcal/h=kW×860
Btu/h=kW×3412
During actual operation, these values are normally somewhat higher as a result of ambient conditions. cfm=m³/min×35.3

RXUQ-A(M) 33
Specifications EDAMT341716

Model Name (Combination Unit) RXUQ34AMYM RXUQ34AMY14 RXUQ34AMY1S RXUQ36AMYM RXUQ36AMY14 RXUQ36AMY1S
RXUQ16AYM+ RXUQ16AY14+ RXUQ16AY1S+ RXUQ18AYM+ RXUQ18AY14+ RXUQ18AY1S+
Model Name (Independent Unit)
RXUQ18AYM RXUQ18AY14 RXUQ18AY1S RXUQ18AYM RXUQ18AY14 RXUQ18AY1S
3 phase, 3 phase, 3 phase, 3 phase, 3 phase, 3 phase,
Power Supply 380-415/380 V, 380-415 V, 380-415 V, 380-415/380 V, 380-415 V, 380-415 V,
50/60 Hz 50 Hz 50 Hz 50/60 Hz 50 Hz 50 Hz
kcal/h 81,700 86,000
1 Cooling Capacity Btu/h 324,000 341,000
kW 95.0 100
Casing Color Ivory white (5Y7.5/1) Ivory white (5Y7.5/1)
Dimensions: (H×W×D) mm (1,657×1,240×765)+(1,657×1,240×765) (1,657×1,240×765)+(1,657×1,240×765)
Heat Exchanger Cross fin coil Cross fin coil
Type Hermetically sealed scroll type Hermetically sealed scroll type
Motor Output×
Compressor kW (3.8×1)+(3.8×1)+(4.5×1)+(4.1×1) (4.5×1)+(4.1×1)+(4.5×1)+(4.1×1)
Number of Units
Starting Method Soft start Soft start
Type Propeller fan Propeller fan
Motor Output kW (0.75×2)+(0.75×2) (0.75×2)+(0.75×2)
Fan
Airflow Rate m³/min 218+268 268+268
Drive Direct drive Direct drive
Connecting Liquid Pipe mm 19.1 C1220T (Brazing connection) 19.1 C1220T (Brazing connection)
Pipes Gas Pipe mm 34.9 C1220T (Brazing connection) 41.3 C1220T (Brazing connection)
Mass kg 318+318 318+318
2 Sound pressure level dB(A) 66 68
High pressure switch, Fan driver overload protector, High pressure switch, Fan driver overload protector,
Safety Devices
Over current relay, Inverter overload protector Over current relay, Inverter overload protector
Capacity Control % 5-100 5-100
Refrigerant Name R410A R410A
Refrigerant Charge kg 11.7+11.7 11.7+11.7
Control Electronic expansion valve Electronic expansion valve
Refrigerator Oil Refer to the nameplate of compressor Refer to the nameplate of compressor
Installation manual, Operation manual, Connection pipes, Installation manual, Operation manual, Connection pipes,
Standard Accessories
Clamps Clamps
Specifications — —
Drawing No.
Sound level — —

Notes:
Conversion formulae
1. Indoor temp.: 27°CDB, 19°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5 m, level difference: 0 m.
2. Anechoic chamber conversion value, measured at a point 1 m in front of the unit at a height of 1.5 m. kcal/h=kW×860
Btu/h=kW×3412
During actual operation, these values are normally somewhat higher as a result of ambient conditions. cfm=m³/min×35.3

34 RXUQ-A(M)
EDAMT341716 Specifications

Model Name (Combination Unit) RXUQ38AMYM


RXUQ18AYM+
RXUQ38AMY14
RXUQ18AY14+
RXUQ38AMY1S
RXUQ18AY1S+
RXUQ40AMYM
RXUQ20AYM+
RXUQ40AMY14
RXUQ20AY14+
RXUQ40AMY1S
RXUQ20AY1S+
2
Model Name (Independent Unit)
RXUQ20AYM RXUQ20AY14 RXUQ20AY1S RXUQ20AYM RXUQ20AY14 RXUQ20AY1S
3 phase, 3 phase, 3 phase, 3 phase, 3 phase, 3 phase,
Power Supply 380-415/380 V, 380-415 V, 380-415 V, 380-415/380 V, 380-415 V, 380-415 V,
50/60 Hz 50 Hz 50 Hz 50/60 Hz 50 Hz 50 Hz
kcal/h 91,200 96,300
1 Cooling Capacity Btu/h 362,000 382,000
kW 106 112
Casing Color Ivory white (5Y7.5/1) Ivory white (5Y7.5/1)
Dimensions: (H×W×D) mm (1,657×1,240×765)+(1,657×1,240×765) (1,657×1,240×765)+(1,657×1,240×765)
Heat Exchanger Cross fin coil Cross fin coil
Type Hermetically sealed scroll type Hermetically sealed scroll type
Motor Output×
Compressor kW (4.5×1)+(4.1×1)+(5.1×1)+(5.0×1) (5.1×1)+(5.0×1)+(5.1×1)+(5.0×1)
Number of Units
Starting Method Soft start Soft start
Type Propeller fan Propeller fan
Motor Output kW (0.75×2)+(0.75×2) (0.75×2)+(0.75×2)
Fan
Airflow Rate m³/min 268+268 268+268
Drive Direct drive Direct drive
Connecting Liquid Pipe mm 19.1 C1220T (Brazing connection) 19.1 C1220T (Brazing connection)
Pipes Gas Pipe mm 41.3 C1220T (Brazing connection) 41.3 C1220T (Brazing connection)
Mass kg 318+318 318+318
2 Sound pressure level dB(A) 68 68
High pressure switch, Fan driver overload protector, High pressure switch, Fan driver overload protector,
Safety Devices
Over current relay, Inverter overload protector Over current relay, Inverter overload protector
Capacity Control % 4-100 4-100
Refrigerant Name R410A R410A
Refrigerant Charge kg 11.7+11.7 11.7+11.7
Control Electronic expansion valve Electronic expansion valve
Refrigerator Oil Refer to the nameplate of compressor Refer to the nameplate of compressor
Installation manual, Operation manual, Connection pipes, Installation manual, Operation manual, Connection pipes,
Standard Accessories
Clamps Clamps
Specifications — —
Drawing No.
Sound level — —

Notes:
Conversion formulae
1. Indoor temp.: 27°CDB, 19°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5 m, level difference: 0 m.
2. Anechoic chamber conversion value, measured at a point 1 m in front of the unit at a height of 1.5 m. kcal/h=kW×860
Btu/h=kW×3412
During actual operation, these values are normally somewhat higher as a result of ambient conditions. cfm=m³/min×35.3

RXUQ-A(M) 35
Specifications EDAMT341716

Model Name (Combination Unit) RXUQ42AMYM RXUQ42AMY14 RXUQ42AMY1S RXUQ44AMYM RXUQ44AMY14 RXUQ44AMY1S
RXUQ8AYM+ RXUQ8AY14+ RXUQ8AY1S+ RXUQ8AYM+ RXUQ8AY14+ RXUQ8AY1S+
Model Name (Independent Unit) RXUQ16AYM+ RXUQ16AY14+ RXUQ16AY1S+ RXUQ18AYM+ RXUQ18AY14+ RXUQ18AY1S+
RXUQ18AYM RXUQ18AY14 RXUQ18AY1S RXUQ18AYM RXUQ18AY14 RXUQ18AY1S
3 phase, 3 phase, 3 phase, 3 phase, 3 phase, 3 phase,
Power Supply 380-415/380 V, 380-415 V, 380-415 V, 380-415/380 V, 380-415 V, 380-415 V,
50/60 Hz 50 Hz 50 Hz 50/60 Hz 50 Hz 50 Hz
kcal/h 101,000 105,000
1 Cooling Capacity Btu/h 399,000 416,000
kW 117 122
Casing Color Ivory white (5Y7.5/1) Ivory white (5Y7.5/1)
Dimensions: (H×W×D) mm (1,657×1,240×765)+(1,657×1,240×765)+(1,657×1,240×765) (1,657×1,240×765)+(1,657×1,240×765)+(1,657×1,240×765)
Heat Exchanger Cross fin coil Cross fin coil
Type Hermetically sealed scroll type Hermetically sealed scroll type
Motor Output×
Compressor kW (1.8×1)+(1.7×1)+(3.8×1)+(3.8×1)+(4.5×1)+(4.1×1) (1.8×1)+(1.7×1)+(4.5×1)+(4.1×1)+(4.5×1)+(4.1×1)
Number of Units
Starting Method Soft start Soft start
Type Propeller fan Propeller fan
Motor Output kW (0.75×2)+(0.75×2)+(0.75×2) (0.75×2)+(0.75×2)+(0.75×2)
Fan
Airflow Rate m³/min 163+218+268 163+268+268
Drive Direct drive Direct drive
Connecting Liquid Pipe mm 19.1 C1220T (Brazing connection) 19.1 C1220T (Brazing connection)
Pipes Gas Pipe mm 41.3 C1220T (Brazing connection) 41.3 C1220T (Brazing connection)
Mass kg 273+318+318 273+318+318
2 Sound pressure level dB(A) 67 68
High pressure switch, Fan driver overload protector, High pressure switch, Fan driver overload protector,
Safety Devices
Over current relay, Inverter overload protector Over current relay, Inverter overload protector
Capacity Control % 4-100 4-100
Refrigerant Name R410A R410A
Refrigerant Charge kg 8.1+11.7+11.7 8.1+11.7+11.7
Control Electronic expansion valve Electronic expansion valve
Refrigerator Oil Refer to the nameplate of compressor Refer to the nameplate of compressor
Installation manual, Operation manual, Connection pipes, Installation manual, Operation manual, Connection pipes,
Standard Accessories
Clamps Clamps
Specifications — —
Drawing No.
Sound level — —

Notes:
Conversion formulae
1. Indoor temp.: 27°CDB, 19°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5 m, level difference: 0 m.
2. Anechoic chamber conversion value, measured at a point 1 m in front of the unit at a height of 1.5 m. kcal/h=kW×860
Btu/h=kW×3412
During actual operation, these values are normally somewhat higher as a result of ambient conditions. cfm=m³/min×35.3

36 RXUQ-A(M)
EDAMT341716 Specifications

Model Name (Combination Unit) RXUQ46AMYM


RXUQ8AYM+
RXUQ46AMY14
RXUQ8AY14+
RXUQ46AMY1S
RXUQ8AY1S+
RXUQ48AMYM
RXUQ8AYM+
RXUQ48AMY14
RXUQ8AY14+
RXUQ48AMY1S
RXUQ8AY1S+
2
Model Name (Independent Unit) RXUQ18AYM+ RXUQ18AY14+ RXUQ18AY1S+ RXUQ20AYM+ RXUQ20AY14+ RXUQ20AY1S+
RXUQ20AYM RXUQ20AY14 RXUQ20AY1S RXUQ20AYM RXUQ20AY14 RXUQ20AY1S
3 phase, 3 phase, 3 phase, 3 phase, 3 phase, 3 phase,
Power Supply 380-415/380 V, 380-415 V, 380-415 V, 380-415/380 V, 380-415 V, 380-415 V,
50/60 Hz 50 Hz 50 Hz 50/60 Hz 50 Hz 50 Hz
kcal/h 110,000 115,000
1 Cooling Capacity Btu/h 437,000 457,000
kW 128 134
Casing Color Ivory white (5Y7.5/1) Ivory white (5Y7.5/1)
Dimensions: (H×W×D) mm (1,657×1,240×765)+(1,657×1,240×765)+(1,657×1,240×765) (1,657×1,240×765)+(1,657×1,240×765)+(1,657×1,240×765)
Heat Exchanger Cross fin coil Cross fin coil
Type Hermetically sealed scroll type Hermetically sealed scroll type
Motor Output×
Compressor kW (1.8×1)+(1.7×1)+(4.5×1)+(4.1×1)+(5.1×1)+(5.0×1) (1.8×1)+(1.7×1)+(5.1×1)+(5.0×1)+(5.1×1)+(5.0×1)
Number of Units
Starting Method Soft start Soft start
Type Propeller fan Propeller fan
Motor Output kW (0.75×2)+(0.75×2)+(0.75×2) (0.75×2)+(0.75×2)+(0.75×2)
Fan
Airflow Rate m³/min 163+268+268 163+268+268
Drive Direct drive Direct drive
Connecting Liquid Pipe mm 19.1 C1220T (Brazing connection) 19.1 C1220T (Brazing connection)
Pipes Gas Pipe mm 41.3 C1220T (Brazing connection) 41.3 C1220T (Brazing connection)
Mass kg 273+318+318 273+318+318
2 Sound pressure level dB(A) 68 68
High pressure switch, Fan driver overload protector, High pressure switch, Fan driver overload protector,
Safety Devices
Over current relay, Inverter overload protector Over current relay, Inverter overload protector
Capacity Control % 3-100 3-100
Refrigerant Name R410A R410A
Refrigerant Charge kg 8.1+11.7+11.7 8.1+11.7+11.7
Control Electronic expansion valve Electronic expansion valve
Refrigerator Oil Refer to the nameplate of compressor Refer to the nameplate of compressor
Installation manual, Operation manual, Connection pipes, Installation manual, Operation manual, Connection pipes,
Standard Accessories
Clamps Clamps
Specifications — —
Drawing No.
Sound level — —

Notes:
Conversion formulae
1. Indoor temp.: 27°CDB, 19°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5 m, level difference: 0 m.
2. Anechoic chamber conversion value, measured at a point 1 m in front of the unit at a height of 1.5 m. kcal/h=kW×860
Btu/h=kW×3412
During actual operation, these values are normally somewhat higher as a result of ambient conditions. cfm=m³/min×35.3

RXUQ-A(M) 37
Specifications EDAMT341716

Model Name (Combination Unit) RXUQ50AMYM RXUQ50AMY14 RXUQ50AMY1S RXUQ52AMYM RXUQ52AMY14 RXUQ52AMY1S
RXUQ12AYM+ RXUQ12AY14+ RXUQ12AY1S+ RXUQ12AYM+ RXUQ12AY14+ RXUQ12AY1S+
Model Name (Independent Unit) RXUQ18AYM+ RXUQ18AY14+ RXUQ18AY1S+ RXUQ20AYM+ RXUQ20AY14+ RXUQ20AY1S+
RXUQ20AYM RXUQ20AY14 RXUQ20AY1S RXUQ20AYM RXUQ20AY14 RXUQ20AY1S
3 phase, 3 phase, 3 phase, 3 phase, 3 phase, 3 phase,
Power Supply 380-415/380 V, 380-415 V, 380-415 V, 380-415/380 V, 380-415 V, 380-415 V,
50/60 Hz 50 Hz 50 Hz 50/60 Hz 50 Hz 50 Hz
kcal/h 120,000 126,000
1 Cooling Capacity Btu/h 478,000 498,000
kW 140 146
Casing Color Ivory white (5Y7.5/1) Ivory white (5Y7.5/1)
Dimensions: (H×W×D) mm (1,657×1,240×765)+(1,657×1,240×765)+(1,657×1,240×765) (1,657×1,240×765)+(1,657×1,240×765)+(1,657×1,240×765)
Heat Exchanger Cross fin coil Cross fin coil
Type Hermetically sealed scroll type Hermetically sealed scroll type
Motor Output×
Compressor kW (2.2×1)+(3.1×1)+(4.5×1)+(4.1×1)+(5.1×1)+(5.0×1) (2.2×1)+(3.1×1)+(5.1×1)+(5.0×1)+(5.1×1)+(5.0×1)
Number of Units
Starting Method Soft start Soft start
Type Propeller fan Propeller fan
Motor Output kW (0.75×2)+(0.75×2)+(0.75×2) (0.75×2)+(0.75×2)+(0.75×2)
Fan
Airflow Rate m³/min 213+268+268 213+268+268
Drive Direct drive Direct drive
Connecting Liquid Pipe mm 19.1 C1220T (Brazing connection) 19.1 C1220T (Brazing connection)
Pipes Gas Pipe mm 41.3 C1220T (Brazing connection) 41.3 C1220T (Brazing connection)
Mass kg 312+318+318 312+318+318
2 Sound pressure level dB(A) 69 69
High pressure switch, Fan driver overload protector, High pressure switch, Fan driver overload protector,
Safety Devices
Over current relay, Inverter overload protector Over current relay, Inverter overload protector
Capacity Control % 3-100 3-100
Refrigerant Name R410A R410A
Refrigerant Charge kg 11.4+11.7+11.7 11.4+11.7+11.7
Control Electronic expansion valve Electronic expansion valve
Refrigerator Oil Refer to the nameplate of compressor Refer to the nameplate of compressor
Installation manual, Operation manual, Connection pipes, Installation manual, Operation manual, Connection pipes,
Standard Accessories
Clamps Clamps
Specifications — —
Drawing No.
Sound level — —

Notes:
Conversion formulae
1. Indoor temp.: 27°CDB, 19°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5 m, level difference: 0 m.
2. Anechoic chamber conversion value, measured at a point 1 m in front of the unit at a height of 1.5 m. kcal/h=kW×860
Btu/h=kW×3412
During actual operation, these values are normally somewhat higher as a result of ambient conditions. cfm=m³/min×35.3

38 RXUQ-A(M)
EDAMT341716 Specifications

Model Name (Combination Unit) RXUQ54AMYM


RXUQ18AYM+
RXUQ54AMY14
RXUQ18AY14+
RXUQ54AMY1S
RXUQ18AY1S+
RXUQ56AMYM
RXUQ18AYM+
RXUQ56AMY14
RXUQ18AY14+
RXUQ56AMY1S
RXUQ18AY1S+
2
Model Name (Independent Unit) RXUQ18AYM+ RXUQ18AY14+ RXUQ18AY1S+ RXUQ18AYM+ RXUQ18AY14+ RXUQ18AY1S+
RXUQ18AYM RXUQ18AY14 RXUQ18AY1S RXUQ20AYM RXUQ20AY14 RXUQ20AY1S
3 phase, 3 phase, 3 phase, 3 phase, 3 phase, 3 phase,
Power Supply 380-415/380 V, 380-415 V, 380-415 V, 380-415/380 V, 380-415 V, 380-415 V,
50/60 Hz 50 Hz 50 Hz 50/60 Hz 50 Hz 50 Hz
kcal/h 129,000 134,000
1 Cooling Capacity Btu/h 512,000 532,000
kW 150 156
Casing Color Ivory white (5Y7.5/1) Ivory white (5Y7.5/1)
Dimensions: (H×W×D) mm (1,657×1,240×765)+(1,657×1,240×765)+(1,657×1,240×765) (1,657×1,240×765)+(1,657×1,240×765)+(1,657×1,240×765)
Heat Exchanger Cross fin coil Cross fin coil
Type Hermetically sealed scroll type Hermetically sealed scroll type
Motor Output×
Compressor kW (4.5×1)+(4.1×1)+(4.5×1)+(4.1×1)+(4.5×1)+(4.1×1) (4.5×1)+(4.1×1)+(4.5×1)+(4.1×1)+(5.1×1)+(5.0×1)
Number of Units
Starting Method Soft start Soft start
Type Propeller fan Propeller fan
Motor Output kW (0.75×2)+(0.75×2)+(0.75×2) (0.75×2)+(0.75×2)+(0.75×2)
Fan
Airflow Rate m³/min 268+268+268 268+268+268
Drive Direct drive Direct drive
Connecting Liquid Pipe mm 19.1 C1220T (Brazing connection) 19.1 C1220T (Brazing connection)
Pipes Gas Pipe mm 41.3 C1220T (Brazing connection) 41.3 C1220T (Brazing connection)
Mass kg 318+318+318 318+318+318
2 Sound pressure level dB(A) 70 70
High pressure switch, Fan driver overload protector, High pressure switch, Fan driver overload protector,
Safety Devices
Over current relay, Inverter overload protector Over current relay, Inverter overload protector
Capacity Control % 3-100 3-100
Refrigerant Name R410A R410A
Refrigerant Charge kg 11.7+11.7+11.7 11.7+11.7+11.7
Control Electronic expansion valve Electronic expansion valve
Refrigerator Oil Refer to the nameplate of compressor Refer to the nameplate of compressor
Installation manual, Operation manual, Connection pipes, Installation manual, Operation manual, Connection pipes,
Standard Accessories
Clamps Clamps
Specifications — —
Drawing No.
Sound level — —

Notes:
Conversion formulae
1. Indoor temp.: 27°CDB, 19°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5 m, level difference: 0 m.
2. Anechoic chamber conversion value, measured at a point 1 m in front of the unit at a height of 1.5 m. kcal/h=kW×860
Btu/h=kW×3412
During actual operation, these values are normally somewhat higher as a result of ambient conditions. cfm=m³/min×35.3

RXUQ-A(M) 39
Specifications EDAMT341716

Model Name (Combination Unit) RXUQ58AMYM RXUQ58AMY14 RXUQ58AMY1S RXUQ60AMYM RXUQ60AMY14 RXUQ60AMY1S
RXUQ18AYM+ RXUQ18AY14+ RXUQ18AY1S+ RXUQ20AYM+ RXUQ20AY14+ RXUQ20AY1S+
Model Name (Independent Unit) RXUQ20AYM+ RXUQ20AY14+ RXUQ20AY1S+ RXUQ20AYM+ RXUQ20AY14+ RXUQ20AY1S+
RXUQ20AYM RXUQ20AY14 RXUQ20AY1S RXUQ20AYM RXUQ20AY14 RXUQ20AY1S
3 phase, 3 phase, 3 phase, 3 phase, 3 phase, 3 phase,
Power Supply 380-415/380 V, 380-415 V, 380-415 V, 380-415/380 V, 380-415 V, 380-415 V,
50/60 Hz 50 Hz 50 Hz 50/60 Hz 50 Hz 50 Hz
kcal/h 139,000 144,000
1 Cooling Capacity Btu/h 553,000 573,000
kW 162 168
Casing Color Ivory white (5Y7.5/1) Ivory white (5Y7.5/1)
Dimensions: (H×W×D) mm (1,657×1,240×765)+(1,657×1,240×765)+(1,657×1,240×765) (1,657×1,240×765)+(1,657×1,240×765)+(1,657×1,240×765)
Heat Exchanger Cross fin coil Cross fin coil
Type Hermetically sealed scroll type Hermetically sealed scroll type
Motor Output×
Compressor kW (4.5×1)+(4.1×1)+(5.1×1)+(5.0×1)+(5.1×1)+(5.0×1) (5.1×1)+(5.0×1)+(5.1×1)+(5.0×1)+(5.1×1)+(5.0×1)
Number of Units
Starting Method Soft start Soft start
Type Propeller fan Propeller fan
Motor Output kW (0.75×2)+(0.75×2)+(0.75×2) (0.75×2)+(0.75×2)+(0.75×2)
Fan
Airflow Rate m³/min 268+268+268 268+268+268
Drive Direct drive Direct drive
Connecting Liquid Pipe mm 19.1 C1220T (Brazing connection) 19.1 C1220T (Brazing connection)
Pipes Gas Pipe mm 41.3 C1220T (Brazing connection) 41.3 C1220T (Brazing connection)
Mass kg 318+318+318 318+318+318
2 Sound pressure level dB(A) 70 70
High pressure switch, Fan driver overload protector, High pressure switch, Fan driver overload protector,
Safety Devices
Over current relay, Inverter overload protector Over current relay, Inverter overload protector
Capacity Control % 3-100 2-100
Refrigerant Name R410A R410A
Refrigerant Charge kg 11.7+11.7+11.7 11.7+11.7+11.7
Control Electronic expansion valve Electronic expansion valve
Refrigerator Oil Refer to the nameplate of compressor Refer to the nameplate of compressor
Installation manual, Operation manual, Connection pipes, Installation manual, Operation manual, Connection pipes,
Standard Accessories
Clamps Clamps
Specifications — —
Drawing No.
Sound level — —

Notes:
Conversion formulae
1. Indoor temp.: 27°CDB, 19°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5 m, level difference: 0 m.
2. Anechoic chamber conversion value, measured at a point 1 m in front of the unit at a height of 1.5 m. kcal/h=kW×860
Btu/h=kW×3412
During actual operation, these values are normally somewhat higher as a result of ambient conditions. cfm=m³/min×35.3

40 RXUQ-A(M)
2.1
Unit: mm

RXUQ-A(M)
EDAMT341716

RXUQ20AY1S
1 4-15 x 22.5 Oblong holes
1076 (Foundation bolt hole)
2
(Pitch of foundation bolt holes)
393
3
134
125 8
2. Dimensions

112
107

271
Independent Unit

AA
722~737
70
100 71 10
160 AB

(Pitch of foundation bolt holes)


VIEW C
DETAIL A DETAIL B

11

Model AA AB
RX(Y)Q14, 16,18AY 171 106
9 RXUQ8, 10, 12, 14, 16, 18AY
RX(Y)Q20AY 161 101
RXUQ20AY
7

1657
4 No. Parts name Remark
1 Liquid pipe connection port See note 3.
6 2 Gas pipe connection port See note 3.
A 3 Refrigerant charge port
4 Power cord routing hole (side) φ65
5 Power cord routing hole (front) φ80
6 Power cord routing hole (front) φ65

122
7 Tranmistion wire routing hole (front) φ27
8 Power cord routing hole (bottom)

484
φ65
9 Pipe routing hole (front)
10 Pipe routing hole (bottom)

245
228
148
11 Grounding terminal Inside of switch box (M8)

94
NOTES:
66 66 B 97 107 1. DETAIL A AND DETAIL B INDICATE THE DIMENSIONS AFTER FIXING THE ATTACHED PIPING.
5 2. ITEM 4 TO 10 KNOCK OUT HOLE.
137 272 C 3. GAS PIPE :
765 328 φ19.1 BRAZING CONNECTION: RXUQ8AY
φ22.2 BRAZING CONNECTION: RXUQ10AY
373 φ28.6 BRAZING CONNECTION: RX(Y)Q14, 16, 18, 20AY, RXUQ12, 14, 16, 18, 20AY
1240 LIQUID PIPE:
φ9.5 BRAZING CONNECTION: RXUQ8, 10AY
RXUQ8AY1S / RXUQ10AY1S / RXUQ12AY1S / RXUQ14AY1S / RXUQ16AY1S / RXUQ18AY1S /

φ12.7 BRAZING CONNECTION: RX(Y)Q14, 16AY, RXUQ12, 14, 16AY


φ15.9 BRAZING CONNECTION: RX(Y)Q18, 20AY, RXUQ18, 20AY
RXUQ8AYM / RXUQ10AYM / RXUQ12AYM / RXUQ14AYM / RXUQ16AYM / RXUQ18AYM / RXUQ20AYM

3D111515

41
Dimensions

RXUQ8AY14 / RXUQ10AY14 / RXUQ12AY14 / RXUQ14AY14 / RXUQ16AY14 / RXUQ18AY14 / RXUQ20AY14


2
42
Unit: mm 2.2
Dimensions

4-15 x 22.5 Oblong hole 1076 1076 4-15 x 22.5 Oblong hole
(foundation bolt hole) (foundation bolt hole pitch) (foundation bolt hole pitch) (foundation bolt hole)
 The example of installation required space

300 or more

722 ~ 737
20 or more
10 or more 10 or more
Combination Unit

500
or more

(foundation bolt hole pitch)


FRONT SIDE
OUTDOOR UNIT 1 OUTDOOR UNIT 2
< Unit : mm >
Note: 1. For the wall height of the example for this installation required space area,
Fornt side: 1500 mm
Suction side: 500 mm
Lateral side: No height limitation
This installation required space example has the standard of cooling
operation at outdoor unit air temperature 35°C.
In case the temperature is over 35°C of designed outdoor air temperature,
or there is much heat load on all outdoor unit which its operation load
is over the maximum capacity, make sure to enlarge the suction side space
to be more than the value details which specified in drawing.
2. In case of it is over the wall height as specified, make sure to add each

1657
dimension h2/2, h1/2 or more to the front side, suction side space as
below diagram.
3. When installation, select the most suitable pattern of installation service
space adapt to field space by considering pathway, ventilation.
4. For front side space, make sure to install by considering the neccesary
space for refrigerant piping construction at the field.
h2

20 or more
1240 1240 765
SYSTEM NAME OUTDOOR UNIT1 DWG. No. OUTDOOR UNIT2 DWG. No.
h1

RX(Y)Q32AMY RX(Y)Q18AY 3D111515 RX(Y)Q14AY 3D111515


1500

RX(Y)Q34AMY RX(Y)Q18AY 3D111515 RX(Y)Q16AY 3D111515


RX(Y)Q36AMY RX(Y)Q18AY 3D111515 RX(Y)Q18AY 3D111515
FRONT SIDE
SUCTION SIDE

RX(Y)Q38AMY RX(Y)Q20AY 3D111515 RX(Y)Q18AY 3D111515


500

RX(Y)Q40AMY RX(Y)Q20AY 3D111515 RX(Y)Q20AY 3D111515


SYSTEM NAME OUTDOOR UNIT1 DWG. No. OUTDOOR UNIT2 DWG. No. SYSTEM NAME OUTDOOR UNIT1 DWG. No. OUTDOOR UNIT2 DWG. No.
RXUQ18AMY RXUQ10AY 3D111515 RXUQ8AY 3D111515 RXUQ30AMY RXUQ18AY 3D111515 RXUQ12AY 3D111515
RXUQ20AMY RXUQ12AY 3D111515 RXUQ8AY 3D111515 RXUQ32AMY RXUQ20AY 3D111515 RXUQ12AY 3D111515
RXUQ22AMY RXUQ14AY 3D111515 RXUQ8AY 3D111515 RXUQ34AMY RXUQ18AY 3D111515 RXUQ16AY 3D111515
RXUQ24AMY RXUQ16AY 3D111515 RXUQ8AY 3D111515 RXUQ36AMY RXUQ18AY 3D111515 RXUQ18AY 3D111515
RXUQ26AMY RXUQ18AY 3D111515 RXUQ8AY 3D111515 RXUQ38AMY RXUQ20AY 3D111515 RXUQ18AY 3D111515
RXUQ28AMY RXUQ20AY 3D111515 RXUQ8AY 3D111515 RXUQ40AMY RXUQ20AY 3D111515 RXUQ20AY 3D111515
RXUQ30AMYM / RXUQ32AMYM / RXUQ34AMYM / RXUQ36AMYM / RXUQ38AMYM / RXUQ40AMYM
RXUQ18AMYM / RXUQ20AMYM / RXUQ22AMYM / RXUQ24AMYM / RXUQ26AMYM / RXUQ28AMYM /

RXUQ30AMY14 / RXUQ32AMY14 / RXUQ34AMY14 / RXUQ36AMY14 / RXUQ38AMY14 / RXUQ40AMY14

3D111516
RXUQ18AMY14 / RXUQ20AMY14 / RXUQ22AMY14 / RXUQ24AMY14 / RXUQ26AMY14 / RXUQ28AMY14 /

RXUQ30AMY1S / RXUQ32AMY1S / RXUQ34AMY1S / RXUQ36AMY1S / RXUQ38AMY1S / RXUQ40AMY1S


RXUQ18AMY1S / RXUQ20AMY1S / RXUQ22AMY1S / RXUQ24AMY1S / RXUQ26AMY1S / RXUQ28AMY1S /

RXUQ-A(M)
EDAMT341716
Unit: mm

RXUQ-A(M)
4-15 x 22.5 Oblong hole 4-15 x 22.5 Oblong hole 4-15 x 22.5 Oblong hole
(foundation bolt hole)  The example of installation required space
(foundation bolt hole)
EDAMT341716

(foundation bolt hole)


1076 1076 1076
(foundation bolt hole pitch) (foundation bolt hole pitch) (foundation bolt hole pitch) 300 or more

10 or more 20 or more 10 or more


20 or more

500
or more

722 ~ 737
(foundation bolt hole pitch)
FRONT SIDE < Unit : mm >
Note:
OUTDOOR UNIT 1 OUTDOOR UNIT 2 OUTDOOR UNIT 3 1. For the wall height of the example for this
installation required space area,
Fornt side: 1500 mm
Suction side: 500 mm
Lateral side: No height limitation
This installation required space example has
the standard of cooling
operation at outdoor unit air temperature 35°C.
In case the temperature is over 35°C of designed
outdoor air temperature,or there is much heat load
on all outdoor unit which its operation load is over
the maximum capacity, make sure to enlarge the
suction side space to be more than the value details

1657
which specified in drawing.
2. In case of it is over the wall height as specified,
make sure to add each dimension h2/2, h1/2 or
more to the front side, suction side space as
below diagram.
3. When installation, select the most suitable pattern
of installation service space adapt to field space
by considering pathway, ventilation.
4. For front side space, make sure to install by
considering the neccesary space for refrigerant
RXUQ54AMYM / RXUQ56AMYM / RXUQ58AMYM / RXUQ60AMYM

piping construction at the field.


20 or more 20 or more
RXUQ54AMY14 / RXUQ56AMY14 / RXUQ58AMY14 / RXUQ60AMY14

1240 1240 1240


RXUQ54AMY1S / RXUQ56AMY1S / RXUQ58AMY1S / RXUQ60AMY1S

h2

SYSTEM NAME OUTDOOR UNIT1 DWG. No. OUTDOOR UNIT2 DWG. No. OUTDOOR UNIT3 DWG. No.
RX(Y)Q46AMY RX(Y)Q18AY 3D111515 RX(Y)Q14AY 3D111515 RX(Y)Q14AY 3D111515
RX(Y)Q48AMY RX(Y)Q18AY 3D111515 RX(Y)Q16AY 3D111515 RX(Y)Q14AY 3D111515
RX(Y)Q50AMY RX(Y)Q18AY 3D111515 RX(Y)Q18AY 3D111515 RX(Y)Q14AY 3D111515
RX(Y)Q52AMY RX(Y)Q18AY 3D111515 RX(Y)Q18AY 3D111515 RX(Y)Q16AY 3D111515
RX(Y)Q54AMY RX(Y)Q18AY 3D111515 RX(Y)Q18AY 3D111515 RX(Y)Q18AY 3D111515
h1

RX(Y)Q56AMY RX(Y)Q20AY 3D111515 RX(Y)Q18AY 3D111515 RX(Y)Q18AY 3D111515


1500

RX(Y)Q58AMY RX(Y)Q20AY 3D111515 RX(Y)Q20AY 3D111515 RX(Y)Q18AY 3D111515


RX(Y)Q60AMY RX(Y)Q20AY 3D111515 RX(Y)Q20AY 3D111515 RX(Y)Q20AY 3D111515
SYSTEM NAME OUTDOOR UNIT1 DWG. No. OUTDOOR UNIT2 DWG. No. OUTDOOR UNIT3 DWG. No.
FRONT SIDE
SUCTION SIDE

RXUQ42AMY RXUQ18AY 3D111515 RXUQ16AY 3D111515 RXUQ8AY 3D111515


500

RXUQ44AMY RXUQ18AY 3D111515 RXUQ18AY 3D111515 RXUQ8AY 3D111515


RXUQ46AMY RXUQ20AY 3D111515 RXUQ18AY 3D111515 RXUQ8AY 3D111515
RXUQ48AMY RXUQ20AY 3D111515 RXUQ20AY 3D111515 RXUQ8AY 3D111515
RXUQ50AMY RXUQ20AY 3D111515 RXUQ18AY 3D111515 RXUQ12AY 3D111515
RXUQ52AMY RXUQ20AY 3D111515 RXUQ20AY 3D111515 RXUQ12AY 3D111515
RXUQ54AMY RXUQ18AY 3D111515 RXUQ18AY 3D111515 RXUQ18AY 3D111515
RXUQ56AMY RXUQ20AY 3D111515 RXUQ18AY 3D111515 RXUQ18AY 3D111515
RXUQ58AMY RXUQ20AY 3D111515 RXUQ20AY 3D111515 RXUQ18AY 3D111515
RXUQ60AMY RXUQ20AY 3D111515 RXUQ20AY 3D111515 RXUQ20AY 3D111515
RXUQ42AMYM / RXUQ44AMYM / RXUQ46AMYM / RXUQ48AMYM / RXUQ50AMYM / RXUQ52AMYM /

3D111517
RXUQ42AMY14 / RXUQ44AMY14 / RXUQ46AMY14 / RXUQ48AMY14 / RXUQ50AMY14 / RXUQ52AMY14 /

RXUQ42AMY1S / RXUQ44AMY1S / RXUQ46AMY1S / RXUQ48AMY1S / RXUQ50AMY1S / RXUQ52AMY1S /

43
Dimensions

2
Service Space (Reference) EDAMT341716

3. Service Space (Reference)


RXUQ8AYM / RXUQ10AYM / RXUQ12AYM / RXUQ14AYM / RXUQ16AYM / RXUQ18AYM / RXUQ20AYM /
RXUQ18AMYM / RXUQ20AMYM / RXUQ22AMYM / RXUQ24AMYM / RXUQ26AMYM / RXUQ28AMYM /
RXUQ30AMYM / RXUQ32AMYM / RXUQ34AMYM / RXUQ36AMYM / RXUQ38AMYM / RXUQ40AMYM /
RXUQ42AMYM / RXUQ44AMYM / RXUQ46AMYM / RXUQ48AMYM / RXUQ50AMYM / RXUQ52AMYM /
RXUQ54AMYM / RXUQ56AMYM / RXUQ58AMYM / RXUQ60AMYM
RXUQ8AY14 / RXUQ10AY14 / RXUQ12AY14 / RXUQ14AY14 / RXUQ16AY14 / RXUQ18AY14 /
RXUQ20AY14 / RXUQ18AMY14 / RXUQ20AMY14 / RXUQ22AMY14 / RXUQ24AMY14 / RXUQ26AMY14 /
RXUQ28AMY14 / RXUQ30AMY14 / RXUQ32AMY14 / RXUQ34AMY14 / RXUQ36AMY14 / RXUQ38AMY14 /
RXUQ40AMY14 / RXUQ42AMY14 / RXUQ44AMY14 / RXUQ46AMY14 / RXUQ48AMY14 / RXUQ50AMY14 /
RXUQ52AMY14 / RXUQ54AMY14 / RXUQ56AMY14 / RXUQ58AMY14 / RXUQ60AMY14
RXUQ8AY1S / RXUQ10AY1S / RXUQ12AY1S / RXUQ14AY1S / RXUQ16AY1S / RXUQ18AY1S /
RXUQ20AY1S / RXUQ18AMY1S / RXUQ20AMY1S / RXUQ22AMY1S / RXUQ24AMY1S / RXUQ26AMY1S /
RXUQ28AMY1S / RXUQ30AMY1S / RXUQ32AMY1S / RXUQ34AMY1S / RXUQ36AMY1S / RXUQ38AMY1S /
RXUQ40AMY1S / RXUQ42AMY1S / RXUQ44AMY1S / RXUQ46AMY1S / RXUQ48AMY1S / RXUQ50AMY1S /
RXUQ52AMY1S / RXUQ54AMY1S / RXUQ56AMY1S / RXUQ58AMY1S / RXUQ60AMY1S
Unit: mm

44 RXUQ-A(M)
RXUQ-A(M)
Stop valve ( With service port on on-site piping side φ 7.9mm flare connection )
EDAMT341716

RXUQ20AY1S
Double tube
Heat Exchanger
R6T Electronic Expansion
Valve (main)
(Y1E)
R4T
Liquid
Pipe
Filter
R5T FILTER

FAN
4. Piping Diagrams

Electronic R1T
M1F M
Expansion Heat Exchanger
Heat sink PCB
Valve FAN
(Y2E)
M2F M

(S1NPH)
Pressure SENPH High pressure
sensor
Regulating
Valve

Check Valve Check Valve

Filter Filter

Electronic Expansion

Oil
Oil

(S2PH) (S1PH)
Valve High pressure High pressure
Separator
Separator

(Y4E) switch switch


Refrigerant HPS HPS
Filter
Auto charge Filter
port Filter
R22T R21T

Solenoid Solenoid
sv
sv

Compressor valve valve Compressor


R9T (Y4S) (Y3S) R8T
(S1NPL) INV2 INV1
Low pressure M2C Capillary
sensor tube
M1C

SENPL
Capillary
R3T tube
Gas
Pipe
Filter
RXUQ8AY1S / RXUQ10AY1S / RXUQ12AY1S / RXUQ14AY1S / RXUQ16AY1S / RXUQ18AY1S /
RXUQ8AYM / RXUQ10AYM / RXUQ12AYM / RXUQ14AYM / RXUQ16AYM / RXUQ18AYM / RXUQ20AYM

3D111854

45
Piping Diagrams

RXUQ8AY14 / RXUQ10AY14 / RXUQ12AY14 / RXUQ14AY14 / RXUQ16AY14 / RXUQ18AY14 / RXUQ20AY14


2
Wiring Diagrams (Reference) EDAMT341716

5. Wiring Diagrams (Reference)


RXUQ8AYM / RXUQ10AYM / RXUQ12AYM / RXUQ14AYM / RXUQ16AYM / RXUQ18AYM / RXUQ20AYM
RXUQ8AY14 / RXUQ10AY14 / RXUQ12AY14 / RXUQ14AY14 / RXUQ16AY14 / RXUQ18AY14 / RXUQ20AY14
RXUQ8AY1S / RXUQ10AY1S / RXUQ12AY1S / RXUQ14AY1S / RXUQ16AY1S / RXUQ18AY1S /
RXUQ20AY1S

46 RXUQ-A(M)
NOTES
1) ALL WIRING COMPONENTS AND MATERIALS TO BE PROCURED ON THE SITE MUST COMPLY WITH THE APPLICABLE LOCAL AND NATIONAL CODES.
2) USE COPPER CONDUCTORS ONLY.

RXUQ-A(M)
3) AS FOR DETAILS, SEE WIRING DIAGRAM.
4) INSTALL CIRCUIT BREAKER FOR SAFETY.
EDAMT341716

RXUQ20AY1S
5) ALL FIELD WIRING AND COMPONENTS MUST BE PROVIDED BY LICENSED ELECTRICIAN.
6) UNIT SHALL BE GROUNDED IN COMPLIANC WITH THE APPLICABLE LOCAL AND NATIONAL CODES.
7) WIRING SHOWN ARE GENERAL POINTS-OF-CONNECTION GUIDES ONLY AND ARE NOT INTENDED FOR OR TO INCLUDE ALL DETAILS FOR A SPECIFIC INSTALLATION.
8) FOR INDOOR UNITS, INSTALL ONE SWITCH AND ONE FUSE PER SYSTEM. (NOT PER INDOOR UNIT)
9) INSTALL THE MAIN SWITCH THAT CAN INTERRUPT ALL THE POWER SOURCES IN AN INTEGRATED MANNER BECAUSE THIS SYSTEM CONSISTS OF THE EQUIPMENT UTILIZING THE MULTIPLE POWER SOURCES.
10) MUST INSTALL EARTH LEAKAGE CIRCUIT BREAKER.
6. Field Wiring

POWER SUPPLY
L1 L2 L3 N

MAIN SWITCH

OUTDOOR UNITS
L1 L2 L3 N
SWITCH

FUSE

POWER SUPPLY
L N

MAIN SWITCH
FUSE

2 WIRES CABLE
(TRANSMISSION LINE)

2 WIRES CABLE 2 WIRES CABLE 2 WIRES CABLE


(TRANSMISSION LINE) (TRANSMISSION LINE) (TRANSMISSION LINE)
2 WIRES CABLE
(POWER LINE)

2 WIRES CABLE 2 WIRES CABLE 2 WIRES CABLE 2 WIRES CABLE


(POWER LINE) (POWER LINE) (POWER LINE) (POWER LINE)
RXUQ8AY1S / RXUQ10AY1S / RXUQ12AY1S / RXUQ14AY1S / RXUQ16AY1S / RXUQ18AY1S /

INDOOR UNITS
RXUQ8AYM / RXUQ10AYM / RXUQ12AYM / RXUQ14AYM / RXUQ16AYM / RXUQ18AYM / RXUQ20AYM

3D111511

47
RXUQ8AY14 / RXUQ10AY14 / RXUQ12AY14 / RXUQ14AY14 / RXUQ16AY14 / RXUQ18AY14 / RXUQ20AY14
Field Wiring

2
48
NOTES
1) ALL WIRING COMPONENTS AND MATERIALS TO BE PROCURED ON THE SITE MUST COMPLY WITH THE APPLICABLE LOCAL AND NATIONAL CODES.
Field Wiring

2) USE COPPER CONDUCTORS ONLY.


3) AS FOR DETAILS, SEE WIRING DIAGRAM.
4) INSTALL CIRCUIT BREAKER FOR SAFETY.
5) ALL FIELD WIRING AND COMPONENTS MUST BE PROVIDED BY LICENSED ELECTRICIAN.
6) UNIT SHALL BE GROUNDED IN COMPLIANC WITH THE APPLICABLE LOCAL AND NATIONAL CODES.
7) WIRING SHOWN ARE GENERAL POINTS-OF-CONNECTION GUIDES ONLY AND ARE NOT INTENDED FOR OR TO INCLUDE ALL DETAILS FOR A SPECIFIC INSTALLATION.
8) FOR INDOOR UNITS, INSTALL ONE SWITCH AND ONE FUSE PER SYSTEM. (NOT PER INDOOR UNIT)
9) INSTALL THE MAIN SWITCH THAT CAN INTERRUPT ALL THE POWER SOURCES IN AN INTEGRATED MANNER BECAUSE THIS SYSTEM CONSISTS OF THE EQUIPMENT UTILIZING THE MULTIPLE POWER SOURCES.
10) THE CAPACITY OF UNIT 1 MUST BE LARGER THAN UNIT 2 WHEN THE POWER SOURCE IS CONNECTED IN SERIES BETWEEN THE UNITS.
11) MUST INSTALL EARTH LEAKAGE CIRCUIT BREAKER.

WHEN THE POWER SOURCE IS SUPPLIED TO EACH OUTDOOR UNIT INDIVIDUALLY. WHEN THE POWER SOURCE IS CONNECTED IN SERIES BETWEEN THE UNITS.

POWER SUPPLY POWER SUPPLY


L1 L2 L3 N OUTDOOR UNITS L1 L2 L3 N OUTDOOR UNITS
MAIN SWITCH MAIN SWITCH

2 WIRES CABLE 2 WIRES CABLE


(TRANSMISSION LINE) (TRANSMISSION LINE)

[UNIT 1] [UNIT 2] [UNIT 1] [UNIT 2]


L1 L2 L3 N L1 L2 L3 N L1 L2 L3 N
SWITCH SWITCH SWITCH

FUSE FUSE FUSE

POWER SUPPLY POWER SUPPLY


L N L N

MAIN SWITCH MAIN SWITCH


FUSE FUSE
2 WIRES CABLE
2 WIRES CABLE (TRANSMISSION LINE)
(TRANSMISSION LINE)
2 WIRES CABLE 2 WIRES CABLE 2 WIRES CABLE 2 WIRES CABLE 2 WIRES CABLE 2 WIRES CABLE
2 WIRES CABLE (TRANSMISSION LINE) (TRANSMISSION LINE) (TRANSMISSION LINE) 2 WIRES CABLE (TRANSMISSION LINE) (TRANSMISSION LINE) (TRANSMISSION LINE)
(POWER LINE) (POWER LINE)

2 WIRES CABLE 2 WIRES CABLE


(POWER LINE) (POWER LINE)

2 WIRES CABLE 2 WIRES CABLE 2 WIRES CABLE 2 WIRES CABLE 2 WIRES CABLE 2 WIRES CABLE
(POWER LINE) (POWER LINE) (POWER LINE) (POWER LINE) (POWER LINE) (POWER LINE)

INDOOR UNITS INDOOR UNITS


RXUQ30AMYM / RXUQ32AMYM / RXUQ34AMYM / RXUQ36AMYM / RXUQ38AMYM / RXUQ40AMYM
RXUQ18AMYM / RXUQ20AMYM / RXUQ22AMYM / RXUQ24AMYM / RXUQ26AMYM / RXUQ28AMYM /

RXUQ30AMY14 / RXUQ32AMY14 / RXUQ34AMY14 / RXUQ36AMY14 / RXUQ38AMY14 / RXUQ40AMY14

3D111512
RXUQ18AMY14 / RXUQ20AMY14 / RXUQ22AMY14 / RXUQ24AMY14 / RXUQ26AMY14 / RXUQ28AMY14 /

RXUQ30AMY1S / RXUQ32AMY1S / RXUQ34AMY1S / RXUQ36AMY1S / RXUQ38AMY1S / RXUQ40AMY1S


RXUQ18AMY1S / RXUQ20AMY1S / RXUQ22AMY1S / RXUQ24AMY1S / RXUQ26AMY1S / RXUQ28AMY1S /

RXUQ-A(M)
EDAMT341716
RXUQ-A(M)
NOTES
1) ALL WIRING COMPONENTS AND MATERIALS TO BE PROCURED ON THE SITE MUST COMPLY WITH THE APPLICABLE LOCAL AND NATIONAL CODES.
EDAMT341716

2) USE COPPER CONDUCTORS ONLY.


3) AS FOR DETAILS, SEE WIRING DIAGRAM.
4) INSTALL CIRCUIT BREAKER FOR SAFETY.
5) ALL FIELD WIRING AND COMPONENTS MUST BE PROVIDED BY LICENSED ELECTRICIAN.
6) UNIT SHALL BE GROUNDED IN COMPLIANC WITH THE APPLICABLE LOCAL AND NATIONAL CODES.
7) WIRING SHOWN ARE GENERAL POINTS-OF-CONNECTION GUIDES ONLY AND ARE NOT INTENDED FOR OR TO INCLUDE ALL DETAILS FOR A SPECIFIC INSTALLATION.
8) FOR INDOOR UNITS, INSTALL ONE SWITCH AND ONE FUSE PER SYSTEM. (NOT PER INDOOR UNIT)
9) INSTALL THE MAIN SWITCH THAT CAN INTERRUPT ALL THE POWER SOURCES IN AN INTEGRATED MANNER BECAUSE THIS SYSTEM CONSISTS OF THE EQUIPMENT UTILIZING THE MULTIPLE POWER SOURCES.
10) THE CAPACITY OF UNIT 1 MUST BE LARGER THAN UNIT 2 AND UNIT 2 MUST BE LARGER THAN UNIT 3 WHEN THE POWER SOURCE IS CONNECTED IN SERIES BETWEEN THE UNITS.
11) MUST INSTALL EARTH LEAKAGE CIRCUIT BREAKER.

WHEN THE POWER SOURCE IS SUPPLIED TO EACH OUTDOOR UNIT INDIVIDUALLY. WHEN THE POWER SOURCE IS CONNECTED IN SERIES BETWEEN THE UNITS.

POWER SUPPLY POWER SUPPLY


L1 L2 L3 N OUTDOOR UNITS L1 L2 L3 N OUTDOOR UNITS
MAIN SWITCH MAIN SWITCH
2 WIRES CABLE 2 WIRES CABLE 2 WIRES CABLE 2 WIRES CABLE
(TRANSMISSION LINE) (TRANSMISSION LINE) (TRANSMISSION LINE) (TRANSMISSION LINE)

[UNIT 1] [UNIT 2] [UNIT 3] [UNIT 1] [UNIT 2] [UNIT 3]


L1 L2 L3 N L1 L2 L3 N L1 L2 L3 N L1 L2 L3 N
SWITCH SWITCH SWITCH SWITCH

FUSE FUSE FUSE FUSE

POWER SUPPLY POWER SUPPLY


L N L N
RXUQ54AMYM / RXUQ56AMYM / RXUQ58AMYM / RXUQ60AMYM

MAIN SWITCH MAIN SWITCH


RXUQ54AMY14 / RXUQ56AMY14 / RXUQ58AMY14 / RXUQ60AMY14

RXUQ54AMY1S / RXUQ56AMY1S / RXUQ58AMY1S / RXUQ60AMY1S

FUSE FUSE
2 WIRES CABLE
(TRANSMISSION LINE)

2 WIRES CABLE 2 WIRES CABLE 2 WIRES CABLE 2 WIRES CABLE 2 WIRES CABLE 2 WIRES CABLE 2 WIRES CABLE
(TRANSMISSION LINE) (TRANSMISSION LINE) (TRANSMISSION LINE) (TRANSMISSION LINE) (TRANSMISSION LINE) (TRANSMISSION LINE) (TRANSMISSION LINE)

2 WIRES CABLE 2 WIRES CABLE


(POWER LINE) (POWER LINE)

2 WIRES CABLE 2 WIRES CABLE


(POWER LINE) (POWER LINE)

2 WIRES CABLE 2 WIRES CABLE 2 WIRES CABLE 2 WIRES CABLE 2 WIRES CABLE 2 WIRES CABLE
(POWER LINE) (POWER LINE) (POWER LINE) (POWER LINE) (POWER LINE) (POWER LINE)

INDOOR UNITS INDOOR UNITS


RXUQ42AMYM / RXUQ44AMYM / RXUQ46AMYM / RXUQ48AMYM / RXUQ50AMYM / RXUQ52AMYM /

3D111513
RXUQ42AMY14 / RXUQ44AMY14 / RXUQ46AMY14 / RXUQ48AMY14 / RXUQ50AMY14 / RXUQ52AMY14 /

RXUQ42AMY1S / RXUQ44AMY1S / RXUQ46AMY1S / RXUQ48AMY1S / RXUQ50AMY1S / RXUQ52AMY1S /

49
Field Wiring

2
Operation Limits (Reference) EDAMT341716

7. Operation Limits (Reference)


RXUQ8AYM / RXUQ10AYM / RXUQ12AYM / RXUQ14AYM / RXUQ16AYM / RXUQ18AYM / RXUQ20AYM /
RXUQ18AMYM / RXUQ20AMYM / RXUQ22AMYM / RXUQ24AMYM / RXUQ26AMYM / RXUQ28AMYM /
RXUQ30AMYM / RXUQ32AMYM / RXUQ34AMYM / RXUQ36AMYM / RXUQ38AMYM / RXUQ40AMYM /
RXUQ42AMYM / RXUQ44AMYM / RXUQ46AMYM / RXUQ48AMYM / RXUQ50AMYM / RXUQ52AMYM /
RXUQ54AMYM / RXUQ56AMYM / RXUQ58AMYM / RXUQ60AMYM
RXUQ8AY14 / RXUQ10AY14 / RXUQ12AY14 / RXUQ14AY14 / RXUQ16AY14 / RXUQ18AY14 /
RXUQ20AY14 / RXUQ18AMY14 / RXUQ20AMY14 / RXUQ22AMY14 / RXUQ24AMY14 / RXUQ26AMY14 /
RXUQ28AMY14 / RXUQ30AMY14 / RXUQ32AMY14 / RXUQ34AMY14 / RXUQ36AMY14 / RXUQ38AMY14 /
RXUQ40AMY14 / RXUQ42AMY14 / RXUQ44AMY14 / RXUQ46AMY14 / RXUQ48AMY14 / RXUQ50AMY14 /
RXUQ52AMY14 / RXUQ54AMY14 / RXUQ56AMY14 / RXUQ58AMY14 / RXUQ60AMY14
RXUQ8AY1S / RXUQ10AY1S / RXUQ12AY1S / RXUQ14AY1S / RXUQ16AY1S / RXUQ18AY1S /
RXUQ20AY1S / RXUQ18AMY1S / RXUQ20AMY1S / RXUQ22AMY1S / RXUQ24AMY1S / RXUQ26AMY1S /
RXUQ28AMY1S / RXUQ30AMY1S / RXUQ32AMY1S / RXUQ34AMY1S / RXUQ36AMY1S / RXUQ38AMY1S /
RXUQ40AMY1S / RXUQ42AMY1S / RXUQ44AMY1S / RXUQ46AMY1S / RXUQ48AMY1S / RXUQ50AMY1S /
RXUQ52AMY1S / RXUQ54AMY1S / RXUQ56AMY1S / RXUQ58AMY1S / RXUQ60AMY1S

50 RXUQ-A(M)
EDAMT341716 Accessories

8. Accessories
8.1 Optional Accessories 2
Optional accessories RXUQ8AYM RXUQ8AY14 RXUQ8AY1S
RXUQ10AYM RXUQ10AY14 RXUQ10AY1S
KHRP26M22H, KHRP26M33H
Distributive REFNET header
(Max. 4 branch) (Max. 8 branch)
Piping
REFNET joint KHRP26A22T, KHRP26A33T
DIII-NET expand adaptor DTA109A51
Option PCB External control adaptor DTA104A61
Option plate for control adaptor BKS26A
3D111853

RXUQ12AYM RXUQ12AY14 RXUQ12AY1S


RXUQ14AYM RXUQ14AY14 RXUQ14AY1S
Optional accessories RXUQ16AYM RXUQ16AY14 RXUQ16AY1S
RXUQ18AYM RXUQ18AY14 RXUQ18AY1S
RXUQ20AYM RXUQ20AY14 RXUQ20AY1S
KHRP26M22H
(Max. 4 branch),
KHRP26M33H
Distributive REFNET header
(Max. 8 branch),
Piping KHRP26M72H
(Max. 8 branch)
REFNET joint KHRP26A22T, KHRP26A33T, KHRP26A72T
DIII-NET expand adaptor DTA109A51
Option PCB External control adaptor DTA104A61
Option plate for control adaptor BKS26A
3D111853

RXUQ18AMYM RXUQ18AMY14 RXUQ18AMY1S


Optional accessories RXUQ20AMYM RXUQ20AMY14 RXUQ20AMY1S
RXUQ22AMYM RXUQ22AMY14 RXUQ22AMY1S
KHRP26M22H, KHRP26M33H, KHRP26M72H
Distributive REFNET header (Max. 4 branch) (Max. 8 branch) (Max. 8 branch)
Piping
REFNET joint KHRP26A22T, KHRP26A33T, KHRP26A72T
Outdoor unit multi connection piping kit BHFP22P100
DIII-NET expand adaptor DTA109A51
Option PCB External control adaptor DTA104A61
Option plate for control adaptor BKS26A
3D111853

RXUQ24AMYM RXUQ24AMY14 RXUQ24AMY1S


RXUQ26AMYM RXUQ26AMY14 RXUQ26AMY1S
RXUQ28AMYM RXUQ28AMY14 RXUQ28AMY1S
RXUQ30AMYM RXUQ30AMY14 RXUQ30AMY1S
Optional accessories RXUQ32AMYM RXUQ32AMY14 RXUQ32AMY1S
RXUQ34AMYM RXUQ34AMY14 RXUQ34AMY1S
RXUQ36AMYM RXUQ36AMY14 RXUQ36AMY1S
RXUQ38AMYM RXUQ38AMY14 RXUQ38AMY1S
RXUQ40AMYM RXUQ40AMY14 RXUQ40AMY1S
REFNET header KHRP26M22H, KHRP26M33H, KHRP26M72H, KHRP26M73H
Distributive (Max. 4 branch) (Max. 8 branch) (Max. 8 branch) (Max. 8 branch)
Piping
REFNET joint KHRP26A22T, KHRP26A33T, KHRP26A72T, KHRP26A73T
Pipe size reducer KHRP26M73TP, KHRP26M73HP
Outdoor unit multi connection piping kit BHFP22P100
DIII-NET expand adaptor DTA109A51
Option PCB External control adaptor DTA104A61
Option plate for control adaptor BKS26A
3D111853

RXUQ42AMYM RXUQ42AMY14 RXUQ42AMY1S


RXUQ44AMYM RXUQ44AMY14 RXUQ44AMY1S
RXUQ46AMYM RXUQ46AMY14 RXUQ46AMY1S
RXUQ48AMYM RXUQ48AMY14 RXUQ48AMY1S
Optional accessories RXUQ50AMYM RXUQ50AMY14 RXUQ50AMY1S
RXUQ52AMYM RXUQ52AMY14 RXUQ52AMY1S
RXUQ54AMYM RXUQ54AMY14 RXUQ54AMY1S
RXUQ56AMYM RXUQ56AMY14 RXUQ56AMY1S
RXUQ58AMYM RXUQ58AMY14 RXUQ58AMY1S
RXUQ60AMYM RXUQ60AMY14 RXUQ60AMY1S
KHRP26M22H, KHRP26M33H, KHRP26M72H, KHRP26M73H
Distributive REFNET header
(Max. 4 branch) (Max. 8 branch) (Max. 8 branch) (Max. 8 branch)
Piping
REFNET joint KHRP26A22T, KHRP26A33T, KHRP26A72T, KHRP26A73T
Pipe size reducer KHRP26M73TP, KHRP26M73HP
Outdoor unit multi connection piping kit BHFP22P151
DIII-NET expand adaptor DTA109A51
Option PCB External control adaptor DTA104A61
Option plate for control adaptor BKS26A
3D111853

RXUQ-A(M) 51
Accessories EDAMT341716

52 RXUQ-A(M)
EDAMT341716

RXQ-A(M)
Cooling Only 50/60 Hz VRV A SERIES
3

1. Specifications ........................................................................................54
1.1 Cooling Only 50/60 Hz VRV A SERIES (RXQ-A(M)) .............................54
2. Dimensions ...........................................................................................69
2.1 Independent Unit ....................................................................................69
2.2 Combination Unit....................................................................................71
3. Service Space (Reference) ...................................................................76
4. Piping Diagrams....................................................................................77
5. Wiring Diagrams (Reference)................................................................80
6. Field Wiring ...........................................................................................84
7. Electric Characteristics..........................................................................87
8. Operation Limits (Reference) ................................................................91
9. Accessories...........................................................................................92
9.1 Optional Accessories..............................................................................92

RXQ-A(M) 53
Specifications EDAMT341716

1. Specifications
1.1 Cooling Only 50/60 Hz VRV A SERIES (RXQ-A(M))
Model Name RXQ6AYM RXQ6AY14 RXQ6AY1S RXQ8AYM RXQ8AY14 RXQ8AY1S
3 phase, 3 phase, 3 phase, 3 phase, 3 phase, 3 phase,
Power Supply 380-415/380 V, 380-415 V, 380-415 V, 380-415/380 V, 380-415 V, 380-415 V,
50/60 Hz 50 Hz 50 Hz 50/60 Hz 50 Hz 50 Hz
kcal/h 13,800 19,300
1 Cooling Capacity Btu/h 54,600 76,400
kW 16.0 22.4
Casing Color Ivory white (5Y7.5/1) Ivory white (5Y7.5/1)
Dimensions: (H×W×D) mm 1,657×930×765 1,657×930×765
Heat Exchanger Cross fin coil Cross fin coil
Type Hermetically sealed scroll type Hermetically sealed scroll type
Motor Output×
Compressor kW 2.3×1 3.4×1
Number of Units
Starting Method Soft start Soft start
Type Propeller fan Propeller fan
Motor Output kW 0.55×1 0.55×1
Fan
Airflow Rate m³/min 119 178
Drive Direct drive Direct drive
Connecting Liquid Pipe mm 9.5 C1220T (Brazing connection) 9.5 C1220T (Brazing connection)
Pipes Gas Pipe mm 19.1 C1220T (Brazing connection) 19.1 C1220T (Brazing connection)
Mass kg 175 175
2 Sound pressure level dB(A) 56 56
High pressure switch, Fan driver overload protector, High pressure switch, Fan driver overload protector,
Safety Devices
Over current relay, Inverter overload protector Over current relay, Inverter overload protector
Capacity Control % 25-100 20-100
Refrigerant Name R410A R410A
Refrigerant Charge kg 5.9 5.9
Control Electronic expansion valve Electronic expansion valve
Refrigerator Oil Refer to the nameplate of compressor Refer to the nameplate of compressor
Installation manual, Operation manual, Connection pipes, Installation manual, Operation manual, Connection pipes,
Standard Accessories
Clamps Clamps
Specifications C: 3D111543 C: 3D111543
Drawing No.
Sound level — —

Notes:
Conversion formulae
1. Indoor temp.: 27°CDB, 19°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5 m, level difference: 0 m.
2. Anechoic chamber conversion value, measured at a point 1 m in front of the unit at a height of 1.5 m. kcal/h=kW×860
Btu/h=kW×3412
During actual operation, these values are normally somewhat higher as a result of ambient conditions. cfm=m³/min×35.3

54 RXQ-A(M)
EDAMT341716 Specifications

Model Name RXQ10AYM RXQ10AY14 RXQ10AY1S RXQ12AYM RXQ12AY14 RXQ12AY1S


3 phase, 3 phase, 3 phase, 3 phase, 3 phase, 3 phase,
Power Supply 380-415/380 V, 380-415 V, 380-415 V, 380-415/380 V, 380-415 V, 380-415 V,
50/60 Hz 50 Hz 50 Hz 50/60 Hz 50 Hz 50 Hz
kcal/h 24,100 28,800 3
1 Cooling Capacity Btu/h 95,500 114,000
kW 28.0 33.5
Casing Color Ivory white (5Y7.5/1) Ivory white (5Y7.5/1)
Dimensions: (H×W×D) mm 1,657×930×765 1,657×930×765
Heat Exchanger Cross fin coil Cross fin coil
Type Hermetically sealed scroll type Hermetically sealed scroll type
Motor Output×
Compressor kW 4.5×1 5.6×1
Number of Units
Starting Method Soft start Soft start
Type Propeller fan Propeller fan
Motor Output kW 0.55×1 0.55×1
Fan
Airflow Rate m³/min 178 191
Drive Direct drive Direct drive
Connecting Liquid Pipe mm 9.5 C1220T (Brazing connection) 12.7 C1220T (Brazing connection)
Pipes Gas Pipe mm 22.2 C1220T (Brazing connection) 28.6 C1220T (Brazing connection)
Mass kg 185 185
2 Sound pressure level dB(A) 57 59
High pressure switch, Fan driver overload protector, High pressure switch, Fan driver overload protector,
Safety Devices Over current relay, Inverter overload protector Over current relay, Inverter overload protector
Capacity Control % 13-100 12-100
Refrigerant Name R410A R410A
Refrigerant Charge kg 6.7 6.8
Control Electronic expansion valve Electronic expansion valve
Refrigerator Oil Refer to the nameplate of compressor Refer to the nameplate of compressor
Installation manual, Operation manual, Connection pipes, Installation manual, Operation manual, Connection pipes,
Standard Accessories
Clamps Clamps
Specifications C: 3D111543 C: 3D111543
Drawing No.
Sound level — —

Notes:
Conversion formulae
1. Indoor temp.: 27°CDB, 19°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5 m, level difference: 0 m.
2. Anechoic chamber conversion value, measured at a point 1 m in front of the unit at a height of 1.5 m. kcal/h=kW×860
Btu/h=kW×3412
During actual operation, these values are normally somewhat higher as a result of ambient conditions. cfm=m³/min×35.3

RXQ-A(M) 55
Specifications EDAMT341716

Model Name RXQ14AYM RXQ14AY14 RXQ14AY1S RXQ16AYM RXQ16AY14 RXQ16AY1S


3 phase, 3 phase, 3 phase, 3 phase, 3 phase, 3 phase,
Power Supply 380-415/380 V, 380-415 V, 380-415 V, 380-415/380 V, 380-415 V, 380-415 V,
50/60 Hz 50 Hz 50 Hz 50/60 Hz 50 Hz 50 Hz
kcal/h 34,400 38,700
1 Cooling Capacity Btu/h 136,000 154,000
kW 40.0 45.0
Casing Color Ivory white (5Y7.5/1) Ivory white (5Y7.5/1)
Dimensions: (H×W×D) mm 1,657×1,240×765 1,657×1,240×765
Heat Exchanger Cross fin coil Cross fin coil
Type Hermetically sealed scroll type Hermetically sealed scroll type
Motor Output×
Compressor kW 6.4×1 (3.5×1)+(3.5×1)
Number of Units
Starting Method Soft start Soft start
Type Propeller fan Propeller fan
Motor Output kW 0.75×2 0.75×2
Fan
Airflow Rate m³/min 257 257
Drive Direct drive Direct drive
Connecting Liquid Pipe mm 12.7 C1220T (Brazing connection) 12.7 C1220T (Brazing connection)
Pipes Gas Pipe mm 28.6 C1220T (Brazing connection) 28.6 C1220T (Brazing connection)
Mass kg 233 276
2 Sound pressure level dB(A) 60 60
High pressure switch, Fan driver overload protector, High pressure switch, Fan driver overload protector,
Safety Devices Over current relay, Inverter overload protector Over current relay, Inverter overload protector
Capacity Control % 11-100 10-100
Refrigerant Name R410A R410A
Refrigerant Charge kg 7.4 8.2
Control Electronic expansion valve Electronic expansion valve
Refrigerator Oil Refer to the nameplate of compressor Refer to the nameplate of compressor
Installation manual, Operation manual, Connection pipes, Installation manual, Operation manual, Connection pipes,
Standard Accessories
Clamps Clamps
Specifications C: 3D111543 C: 3D111543
Drawing No.
Sound level — —

Notes:
Conversion formulae
1. Indoor temp.: 27°CDB, 19°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5 m, level difference: 0 m.
2. Anechoic chamber conversion value, measured at a point 1 m in front of the unit at a height of 1.5 m. kcal/h=kW×860
Btu/h=kW×3412
During actual operation, these values are normally somewhat higher as a result of ambient conditions. cfm=m³/min×35.3

56 RXQ-A(M)
EDAMT341716 Specifications

Model Name (Combination Unit) RXQ18AYM RXQ18AY14 RXQ18AY1S RXQ18AMYM RXQ18AMY14 RXQ18AMY1S

Model Name (Independent Unit) — — — RXQ8AYM+ RXQ8AY14+ RXQ8AY1S+


RXQ10AYM RXQ10AY14 RXQ10AY1S

Power Supply
3 phase,
380-415/380 V,
50/60 Hz
3 phase,
380-415 V,
50 Hz
3 phase,
380-415 V,
50 Hz
3 phase,
380-415/380 V,
50/60 Hz
3 phase,
380-415 V,
50 Hz
3 phase,
380-415 V,
50 Hz
3
kcal/h 43,000 43,300
1 Cooling Capacity Btu/h 171,000 172,000
kW 50.0 50.4
Casing Color Ivory white (5Y7.5/1) Ivory white (5Y7.5/1)
Dimensions: (H×W×D) mm 1,657×1,240×765 (1,657×930×765)+(1,657×930×765)
Heat Exchanger Cross fin coil Cross fin coil
Type Hermetically sealed scroll type Hermetically sealed scroll type
Motor Output×
Compressor kW (4.0×1)+(4.0×1) (3.4×1)+(4.5×1)
Number of Units
Starting Method Soft start Soft start
Type Propeller fan Propeller fan
Motor Output kW 0.75×2 (0.55×1)+(0.55×1)
Fan
Airflow Rate m³/min 257 178+178
Drive Direct drive Direct drive
Connecting Liquid Pipe mm 15.9 C1220T (Brazing connection) 15.9 C1220T (Brazing connection)
Pipes Gas Pipe mm 28.6 C1220T (Brazing connection) 28.6 C1220T (Brazing connection)
Mass kg 276 175+185
2 Sound pressure level dB(A) 61 60
High pressure switch, Fan driver overload protector, High pressure switch, Fan driver overload protector,
Safety Devices
Over current relay, Inverter overload protector Over current relay, Inverter overload protector
Capacity Control % 10-100 7-100
Refrigerant Name R410A R410A
Refrigerant Charge kg 8.4 5.9+6.7
Control Electronic expansion valve Electronic expansion valve
Refrigerator Oil Refer to the nameplate of compressor Refer to the nameplate of compressor
Installation manual, Operation manual, Connection pipes, Installation manual, Operation manual, Connection pipes,
Standard Accessories Clamps Clamps
Specifications C: 3D111543 —
Drawing No.
Sound level — —

Notes:
Conversion formulae
1. Indoor temp.: 27°CDB, 19°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5 m, level difference: 0 m.
2. Anechoic chamber conversion value, measured at a point 1 m in front of the unit at a height of 1.5 m. kcal/h=kW×860
Btu/h=kW×3412
During actual operation, these values are normally somewhat higher as a result of ambient conditions. cfm=m³/min×35.3

RXQ-A(M) 57
Specifications EDAMT341716

Model Name (Combination Unit) RXQ20AYM RXQ20AY14 RXQ20AY1S RXQ20AMYM RXQ20AMY14 RXQ20AMY1S

Model Name (Independent Unit) — — — RXQ8AYM+ RXQ8AY14+ RXQ8AY1S+


RXQ12AYM RXQ12AY14 RXQ12AY1S
3 phase, 3 phase, 3 phase, 3 phase, 3 phase, 3 phase,
Power Supply 380-415/380 V, 380-415 V, 380-415 V, 380-415/380 V, 380-415 V, 380-415 V,
50/60 Hz 50 Hz 50 Hz 50/60 Hz 50 Hz 50 Hz
kcal/h 48,200 48,100
1 Cooling Capacity Btu/h 191,000 191,000
kW 56.0 55.9
Casing Color Ivory white (5Y7.5/1) Ivory white (5Y7.5/1)
Dimensions: (H×W×D) mm 1,657×1,240×765 (1,657×930×765)+(1,657×930×765)
Heat Exchanger Cross fin coil Cross fin coil
Type Hermetically sealed scroll type Hermetically sealed scroll type
Motor Output×
Compressor kW (3.8×1)+(6.3×1) (3.4×1)+(5.6×1)
Number of Units
Starting Method Soft start Soft start
Type Propeller fan Propeller fan
Motor Output kW 0.75×2 (0.55×1)+(0.55×1)
Fan
Airflow Rate m³/min 297 178+191
Drive Direct drive Direct drive
Connecting Liquid Pipe mm 15.9 C1220T (Brazing connection) 15.9 C1220T (Brazing connection)
Pipes Gas Pipe mm 28.6 C1220T (Brazing connection) 28.6 C1220T (Brazing connection)
Mass kg 312 175+185
2 Sound pressure level dB(A) 65 61
High pressure switch, Fan driver overload protector, High pressure switch, Fan driver overload protector,
Safety Devices
Over current relay, Inverter overload protector Over current relay, Inverter overload protector
Capacity Control % 7-100 7-100
Refrigerant Name R410A R410A
Refrigerant Charge kg 11.8 5.9+6.8
Control Electronic expansion valve Electronic expansion valve
Refrigerator Oil Refer to the nameplate of compressor Refer to the nameplate of compressor
Installation manual, Operation manual, Connection pipes, Installation manual, Operation manual, Connection pipes,
Standard Accessories Clamps Clamps
Specifications C: 3D111543 —
Drawing No.
Sound level — —

Notes:
Conversion formulae
1. Indoor temp.: 27°CDB, 19°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5 m, level difference: 0 m.
2. Anechoic chamber conversion value, measured at a point 1 m in front of the unit at a height of 1.5 m. kcal/h=kW×860
Btu/h=kW×3412
During actual operation, these values are normally somewhat higher as a result of ambient conditions. cfm=m³/min×35.3

58 RXQ-A(M)
EDAMT341716 Specifications

Model Name (Combination Unit) RXQ22AMYM RXQ22AMY14 RXQ22AMY1S RXQ24AMYM RXQ24AMY14 RXQ24AMY1S

Model Name (Independent Unit) RXQ10AYM+ RXQ10AY14+ RXQ10AY1S+ RXQ12AYM+ RXQ12AY14+ RXQ12AY1S+
RXQ12AYM RXQ12AY14 RXQ12AY1S RXQ12AYM RXQ12AY14 RXQ12AY1S

Power Supply
3 phase,
380-415/380 V,
50/60 Hz
3 phase,
380-415 V,
50 Hz
3 phase,
380-415 V,
50 Hz
3 phase,
380-415/380 V,
50/60 Hz
3 phase,
380-415 V,
50 Hz
3 phase,
380-415 V,
50 Hz
3
kcal/h 52,900 57,600
1 Cooling Capacity Btu/h 210,000 229,000
kW 61.5 67.0
Casing Color Ivory white (5Y7.5/1) Ivory white (5Y7.5/1)
Dimensions: (H×W×D) mm (1,657×930×765)+(1,657×930×765) (1,657×930×765)+(1,657×930×765)
Heat Exchanger Cross fin coil Cross fin coil
Type Hermetically sealed scroll type Hermetically sealed scroll type
Motor Output×
Compressor kW (4.5×1)+(5.6×1) (5.6×1)+(5.6×1)
Number of Units
Starting Method Soft start Soft start
Type Propeller fan Propeller fan
Motor Output kW (0.55×1)+(0.55×1) (0.55×1)+(0.55×1)
Fan
Airflow Rate m³/min 178+191 191+191
Drive Direct drive Direct drive
Connecting Liquid Pipe mm 15.9 C1220T (Brazing connection) 15.9 C1220T (Brazing connection)
Pipes Gas Pipe mm 28.6 C1220T (Brazing connection) 34.9 C1220T (Brazing connection)
Mass kg 185+185 185+185
2 Sound pressure level dB(A) 61 62
High pressure switch, Fan driver overload protector, High pressure switch, Fan driver overload protector,
Safety Devices
Over current relay, Inverter overload protector Over current relay, Inverter overload protector
Capacity Control % 6-100 6-100
Refrigerant Name R410A R410A
Refrigerant Charge kg 6.7+6.8 6.8+6.8
Control Electronic expansion valve Electronic expansion valve
Refrigerator Oil Refer to the nameplate of compressor Refer to the nameplate of compressor
Installation manual, Operation manual, Connection pipes, Installation manual, Operation manual, Connection pipes,
Standard Accessories Clamps Clamps
Specifications — —
Drawing No.
Sound level — —

Notes:
Conversion formulae
1. Indoor temp.: 27°CDB, 19°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5 m, level difference: 0 m.
2. Anechoic chamber conversion value, measured at a point 1 m in front of the unit at a height of 1.5 m. kcal/h=kW×860
Btu/h=kW×3412
During actual operation, these values are normally somewhat higher as a result of ambient conditions. cfm=m³/min×35.3

RXQ-A(M) 59
Specifications EDAMT341716

Model Name (Combination Unit) RXQ26AMYM RXQ26AMY14 RXQ26AMY1S RXQ28AMYM RXQ28AMY14 RXQ28AMY1S

Model Name (Independent Unit) RXQ12AYM+ RXQ12AY14+ RXQ12AY1S+ RXQ12AYM+ RXQ12AY14+ RXQ12AY1S+
RXQ14AYM RXQ14AY14 RXQ14AY1S RXQ16AYM RXQ16AY14 RXQ16AY1S
3 phase, 3 phase, 3 phase, 3 phase, 3 phase, 3 phase,
Power Supply 380-415/380 V, 380-415 V, 380-415 V, 380-415/380 V, 380-415 V, 380-415 V,
50/60 Hz 50 Hz 50 Hz 50/60 Hz 50 Hz 50 Hz
kcal/h 63,200 67,500
1 Cooling Capacity Btu/h 251,000 268,000
kW 73.5 78.5
Casing Color Ivory white (5Y7.5/1) Ivory white (5Y7.5/1)
Dimensions: (H×W×D) mm (1,657×930×765)+(1,657×1,240×765) (1,657×930×765)+(1,657×1,240×765)
Heat Exchanger Cross fin coil Cross fin coil
Type Hermetically sealed scroll type Hermetically sealed scroll type
Motor Output×
Compressor kW (5.6×1)+(6.4×1) (5.6×1)+(3.5×1)+(3.5×1)
Number of Units
Starting Method Soft start Soft start
Type Propeller fan Propeller fan
Motor Output kW (0.55×1)+(0.75×2) (0.55×1)+(0.75×2)
Fan
Airflow Rate m³/min 191+257 191+257
Drive Direct drive Direct drive
Connecting Liquid Pipe mm 19.1 C1220T (Brazing connection) 19.1 C1220T (Brazing connection)
Pipes Gas Pipe mm 34.9 C1220T (Brazing connection) 34.9 C1220T (Brazing connection)
Mass kg 185+233 185+276
2 Sound pressure level dB(A) 63 63
High pressure switch, Fan driver overload protector, High pressure switch, Fan driver overload protector,
Safety Devices
Over current relay, Inverter overload protector Over current relay, Inverter overload protector
Capacity Control % 6-100 5-100
Refrigerant Name R410A R410A
Refrigerant Charge kg 6.8+7.4 6.8+8.2
Control Electronic expansion valve Electronic expansion valve
Refrigerator Oil Refer to the nameplate of compressor Refer to the nameplate of compressor
Installation manual, Operation manual, Connection pipes, Installation manual, Operation manual, Connection pipes,
Standard Accessories Clamps Clamps
Specifications — —
Drawing No.
Sound level — —

Notes:
Conversion formulae
1. Indoor temp.: 27°CDB, 19°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5 m, level difference: 0 m.
2. Anechoic chamber conversion value, measured at a point 1 m in front of the unit at a height of 1.5 m. kcal/h=kW×860
Btu/h=kW×3412
During actual operation, these values are normally somewhat higher as a result of ambient conditions. cfm=m³/min×35.3

60 RXQ-A(M)
EDAMT341716 Specifications

Model Name (Combination Unit) RXQ30AMYM RXQ30AMY14 RXQ30AMY1S RXQ32AMYM RXQ32AMY14 RXQ32AMY1S

Model Name (Independent Unit) RXQ12AYM+ RXQ12AY14+ RXQ12AY1S+ RXQ14AYM+ RXQ14AY14+ RXQ14AY1S+
RXQ18AYM RXQ18AY14 RXQ18AY1S RXQ18AYM RXQ18AY14 RXQ18AY1S

Power Supply
3 phase,
380-415/380 V,
50/60 Hz
3 phase,
380-415 V,
50 Hz
3 phase,
380-415 V,
50 Hz
3 phase,
380-415/380 V,
50/60 Hz
3 phase,
380-415 V,
50 Hz
3 phase,
380-415 V,
50 Hz
3
kcal/h 71,800 77,400
1 Cooling Capacity Btu/h 285,000 307,000
kW 83.5 90.0
Casing Color Ivory white (5Y7.5/1) Ivory white (5Y7.5/1)
Dimensions: (H×W×D) mm (1,657×930×765)+(1,657×1,240×765) (1,657×1,240×765)+(1,657×1,240×765)
Heat Exchanger Cross fin coil Cross fin coil
Type Hermetically sealed scroll type Hermetically sealed scroll type
Motor Output×
Compressor kW (5.6×1)+(4.0×1)+(4.0×1) (6.4×1)+(4.0×1)+(4.0×1)
Number of Units
Starting Method Soft start Soft start
Type Propeller fan Propeller fan
Motor Output kW (0.55×1)+(0.75×2) (0.75×2)+(0.75×2)
Fan
Airflow Rate m³/min 191+257 257+257
Drive Direct drive Direct drive
Connecting Liquid Pipe mm 19.1 C1220T (Brazing connection) 19.1 C1220T (Brazing connection)
Pipes Gas Pipe mm 34.9 C1220T (Brazing connection) 34.9 C1220T (Brazing connection)
Mass kg 185+276 233+276
2 Sound pressure level dB(A) 63 64
High pressure switch, Fan driver overload protector, High pressure switch, Fan driver overload protector,
Safety Devices
Over current relay, Inverter overload protector Over current relay, Inverter overload protector
Capacity Control % 5-100 5-100
Refrigerant Name R410A R410A
Refrigerant Charge kg 6.8+8.4 7.4+8.4
Control Electronic expansion valve Electronic expansion valve
Refrigerator Oil Refer to the nameplate of compressor Refer to the nameplate of compressor
Installation manual, Operation manual, Connection pipes, Installation manual, Operation manual, Connection pipes,
Standard Accessories Clamps Clamps
Specifications — —
Drawing No.
Sound level — —

Notes:
Conversion formulae
1. Indoor temp.: 27°CDB, 19°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5 m, level difference: 0 m.
2. Anechoic chamber conversion value, measured at a point 1 m in front of the unit at a height of 1.5 m. kcal/h=kW×860
Btu/h=kW×3412
During actual operation, these values are normally somewhat higher as a result of ambient conditions. cfm=m³/min×35.3

RXQ-A(M) 61
Specifications EDAMT341716

Model Name (Combination Unit) RXQ34AMYM RXQ34AMY14 RXQ34AMY1S RXQ36AMYM RXQ36AMY14 RXQ36AMY1S

Model Name (Independent Unit) RXQ16AYM+ RXQ16AY14+ RXQ16AY1S+ RXQ18AYM+ RXQ18AY14+ RXQ18AY1S+
RXQ18AYM RXQ18AY14 RXQ18AY1S RXQ18AYM RXQ18AY14 RXQ18AY1S
3 phase, 3 phase, 3 phase, 3 phase, 3 phase, 3 phase,
Power Supply 380-415/380 V, 380-415 V, 380-415 V, 380-415/380 V, 380-415 V, 380-415 V,
50/60 Hz 50 Hz 50 Hz 50/60 Hz 50 Hz 50 Hz
kcal/h 81,700 86,000
1 Cooling Capacity Btu/h 324,000 341,000
kW 95.0 100
Casing Color Ivory white (5Y7.5/1) Ivory white (5Y7.5/1)
Dimensions: (H×W×D) mm (1,657×1,240×765)+(1,657×1,240×765) (1,657×1,240×765)+(1,657×1,240×765)
Heat Exchanger Cross fin coil Cross fin coil
Type Hermetically sealed scroll type Hermetically sealed scroll type
Motor Output×
Compressor kW (3.5×1)+(3.5×1)+(4.0×1)+(4.0×1) (4.0×1)+(4.0×1)+(4.0×1)+(4.0×1)
Number of Units
Starting Method Soft start Soft start
Type Propeller fan Propeller fan
Motor Output kW (0.75×2)+(0.75×2) (0.75×2)+(0.75×2)
Fan
Airflow Rate m³/min 257+257 257+257
Drive Direct drive Direct drive
Connecting Liquid Pipe mm 19.1 C1220T (Brazing connection) 19.1 C1220T (Brazing connection)
Pipes Gas Pipe mm 34.9 C1220T (Brazing connection) 41.3 C1220T (Brazing connection)
Mass kg 276+276 276+276
2 Sound pressure level dB(A) 64 64
High pressure switch, Fan driver overload protector, High pressure switch, Fan driver overload protector,
Safety Devices
Over current relay, Inverter overload protector Over current relay, Inverter overload protector
Capacity Control % 5-100 5-100
Refrigerant Name R410A R410A
Refrigerant Charge kg 8.2+8.4 8.4+8.4
Control Electronic expansion valve Electronic expansion valve
Refrigerator Oil Refer to the nameplate of compressor Refer to the nameplate of compressor
Installation manual, Operation manual, Connection pipes, Installation manual, Operation manual, Connection pipes,
Standard Accessories Clamps Clamps
Specifications — —
Drawing No.
Sound level — —

Notes:
Conversion formulae
1. Indoor temp.: 27°CDB, 19°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5 m, level difference: 0 m.
2. Anechoic chamber conversion value, measured at a point 1 m in front of the unit at a height of 1.5 m. kcal/h=kW×860
Btu/h=kW×3412
During actual operation, these values are normally somewhat higher as a result of ambient conditions. cfm=m³/min×35.3

62 RXQ-A(M)
EDAMT341716 Specifications

Model Name (Combination Unit) RXQ38AMYM RXQ38AMY14 RXQ38AMY1S RXQ40AMYM RXQ40AMY14 RXQ40AMY1S

Model Name (Independent Unit) RXQ18AYM+ RXQ18AY14+ RXQ18AY1S+ RXQ20AYM+ RXQ20AY14+ RXQ20AY1S+
RXQ20AYM RXQ20AY14 RXQ20AY1S RXQ20AYM RXQ20AY14 RXQ20AY1S

Power Supply
3 phase,
380-415/380 V,
50/60 Hz
3 phase,
380-415 V,
50 Hz
3 phase,
380-415 V,
50 Hz
3 phase,
380-415/380 V,
50/60 Hz
3 phase,
380-415 V,
50 Hz
3 phase,
380-415 V,
50 Hz
3
kcal/h 91,200 96,300
1 Cooling Capacity Btu/h 362,000 382,000
kW 106 112
Casing Color Ivory white (5Y7.5/1) Ivory white (5Y7.5/1)
Dimensions: (H×W×D) mm (1,657×1,240×765)+(1,657×1,240×765) (1,657×1,240×765)+(1,657×1,240×765)
Heat Exchanger Cross fin coil Cross fin coil
Type Hermetically sealed scroll type Hermetically sealed scroll type
Motor Output×
Compressor kW (4.0×1)+(4.0×1)+(3.8×1)+(6.3×1) (3.8×1)+(6.3×1)+(3.8×1)+(6.3×1)
Number of Units
Starting Method Soft start Soft start
Type Propeller fan Propeller fan
Motor Output kW (0.75×2)+(0.75×2) (0.75×2)+(0.75×2)
Fan
Airflow Rate m³/min 257+297 297+297
Drive Direct drive Direct drive
Connecting Liquid Pipe mm 19.1 C1220T (Brazing connection) 19.1 C1220T (Brazing connection)
Pipes Gas Pipe mm 41.3 C1220T (Brazing connection) 41.3 C1220T (Brazing connection)
Mass kg 276+312 312+312
2 Sound pressure level dB(A) 66 68
High pressure switch, Fan driver overload protector, High pressure switch, Fan driver overload protector,
Safety Devices
Over current relay, Inverter overload protector Over current relay, Inverter overload protector
Capacity Control % 4-100 3-100
Refrigerant Name R410A R410A
Refrigerant Charge kg 8.4+11.8 11.8+11.8
Control Electronic expansion valve Electronic expansion valve
Refrigerator Oil Refer to the nameplate of compressor Refer to the nameplate of compressor
Installation manual, Operation manual, Connection pipes, Installation manual, Operation manual, Connection pipes,
Standard Accessories Clamps Clamps
Specifications — —
Drawing No.
Sound level — —

Notes:
Conversion formulae
1. Indoor temp.: 27°CDB, 19°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5 m, level difference: 0 m.
2. Anechoic chamber conversion value, measured at a point 1 m in front of the unit at a height of 1.5 m. kcal/h=kW×860
Btu/h=kW×3412
During actual operation, these values are normally somewhat higher as a result of ambient conditions. cfm=m³/min×35.3

RXQ-A(M) 63
Specifications EDAMT341716

Model Name (Combination Unit) RXQ42AMYM RXQ42AMY14 RXQ42AMY1S RXQ44AMYM RXQ44AMY14 RXQ44AMY1S
RXQ12AYM+ RXQ12AY14+ RXQ12AY1S+ RXQ12AYM+ RXQ12AY14+ RXQ12AY1S+
Model Name (Independent Unit) RXQ12AYM+ RXQ12AY14+ RXQ12AY1S+ RXQ12AYM+ RXQ12AY14+ RXQ12AY1S+
RXQ18AYM RXQ18AY14 RXQ18AY1S RXQ20AYM RXQ20AY14 RXQ20AY1S
3 phase, 3 phase, 3 phase, 3 phase, 3 phase, 3 phase,
Power Supply 380-415/380 V, 380-415 V, 380-415 V, 380-415/380 V, 380-415 V, 380-415 V,
50/60 Hz 50 Hz 50 Hz 50/60 Hz 50 Hz 50 Hz
kcal/h 101,000 106,000
1 Cooling Capacity Btu/h 339,000 420,000
kW 117 123
Casing Color Ivory white (5Y7.5/1) Ivory white (5Y7.5/1)
Dimensions: (H×W×D) mm (1,657×930×765)+(1,657×930×765)+(1,657×1,240×765) (1,657×930×765)+(1,657×930×765)+(1,657×1,240×765)
Heat Exchanger Cross fin coil Cross fin coil
Type Hermetically sealed scroll type Hermetically sealed scroll type
Motor Output×
Compressor kW (5.6×1)+(5.6×1)+(4.0×1)+(4.0×1) (5.6×1)+(5.6×1)+(3.8×1)+(6.3×1)
Number of Units
Starting Method Soft start Soft start
Type Propeller fan Propeller fan
Motor Output kW (0.55×1)+(0.55×1)+(0.75×2) (0.55×1)+(0.55×1)+(0.75×2)
Fan
Airflow Rate m³/min 191+191+257 191+191+297
Drive Direct drive Direct drive
Connecting Liquid Pipe mm 19.1 C1220T (Brazing connection) 19.1 C1220T (Brazing connection)
Pipes Gas Pipe mm 41.3 C1220T (Brazing connection) 41.3 C1220T (Brazing connection)
Mass kg 185+185+276 185+185+312
2 Sound pressure level dB(A) 65 67
High pressure switch, Fan driver overload protector, High pressure switch, Fan driver overload protector,
Safety Devices
Over current relay, Inverter overload protector Over current relay, Inverter overload protector
Capacity Control % 4-100 3-100
Refrigerant Name R410A R410A
Refrigerant Charge kg 6.8+6.8+8.4 6.8+6.8+11.8
Control Electronic expansion valve Electronic expansion valve
Refrigerator Oil Refer to the nameplate of compressor Refer to the nameplate of compressor

Standard Accessories Installation manual, Operation manual, Connection pipes, Installation manual, Operation manual, Connection pipes,
Clamps Clamps
Specifications — —
Drawing No.
Sound level — —

Notes:
Conversion formulae
1. Indoor temp.: 27°CDB, 19°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5 m, level difference: 0 m.
2. Anechoic chamber conversion value, measured at a point 1 m in front of the unit at a height of 1.5 m. kcal/h=kW×860
Btu/h=kW×3412
During actual operation, these values are normally somewhat higher as a result of ambient conditions. cfm=m³/min×35.3

64 RXQ-A(M)
EDAMT341716 Specifications

Model Name (Combination Unit) RXQ46AMYM RXQ46AMY14 RXQ46AMY1S RXQ48AMYM RXQ48AMY14 RXQ48AMY1S
RXQ14AYM+ RXQ14AY14+ RXQ14AY1S+ RXQ14AYM+ RXQ14AY14+ RXQ14AY1S+
Model Name (Independent Unit) RXQ14AYM+ RXQ14AY14+ RXQ14AY1S+ RXQ16AYM+ RXQ16AY14+ RXQ16AY1S+
RXQ18AYM RXQ18AY14 RXQ18AY1S RXQ18AYM RXQ18AY14 RXQ18AY1S

Power Supply
3 phase,
380-415/380 V,
3 phase,
380-415 V,
3 phase,
380-415 V,
3 phase,
380-415/380 V,
3 phase,
380-415 V,
3 phase,
380-415 V,
3
50/60 Hz 50 Hz 50 Hz 50/60 Hz 50 Hz 50 Hz
kcal/h 112,000 116,000
1 Cooling Capacity Btu/h 444,000 461,000
kW 130 135
Casing Color Ivory white (5Y7.5/1) Ivory white (5Y7.5/1)
Dimensions: (H×W×D) mm (1,657×1,240×765)+(1,657×1,240×765)+(1,657×1,240×765) (1,657×1,240×765)+(1,657×1,240×765)+(1,657×1,240×765)
Heat Exchanger Cross fin coil Cross fin coil
Type Hermetically sealed scroll type Hermetically sealed scroll type
Motor Output×
Compressor kW (6.4×1)+(6.4×1)+(4.0×1)+(4.0×1) (6.4×1)+(3.5×1)+(3.5×1)+(4.0×1)+(4.0×1)
Number of Units
Starting Method Soft start Soft start
Type Propeller fan Propeller fan
Motor Output kW (0.75×2)+(0.75×2)+(0.75×2) (0.75×2)+(0.75×2)+(0.75×2)
Fan
Airflow Rate m³/min 257+257+257 257+257+257
Drive Direct drive Direct drive
Connecting Liquid Pipe mm 19.1 C1220T (Brazing connection) 19.1 C1220T (Brazing connection)
Pipes Gas Pipe mm 41.3 C1220T (Brazing connection) 41.3 C1220T (Brazing connection)
Mass kg 233+233+276 233+276+276
2 Sound pressure level dB(A) 65 65
High pressure switch, Fan driver overload protector, High pressure switch, Fan driver overload protector,
Safety Devices
Over current relay, Inverter overload protector Over current relay, Inverter overload protector
Capacity Control % 3-100 3-100
Refrigerant Name R410A R410A
Refrigerant Charge kg 7.4+7.4+8.4 7.4+8.2+8.4
Control Electronic expansion valve Electronic expansion valve
Refrigerator Oil Refer to the nameplate of compressor Refer to the nameplate of compressor
Installation manual, Operation manual, Connection pipes, Installation manual, Operation manual, Connection pipes,
Standard Accessories
Clamps Clamps
Specifications — —
Drawing No.
Sound level — —

Notes: Conversion formulae


1. Indoor temp.: 27°CDB, 19°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5 m, level difference: 0 m.
kcal/h=kW×860
2. Anechoic chamber conversion value, measured at a point 1 m in front of the unit at a height of 1.5 m. Btu/h=kW×3412
During actual operation, these values are normally somewhat higher as a result of ambient conditions. cfm=m³/min×35.3

RXQ-A(M) 65
Specifications EDAMT341716

Model Name (Combination Unit) RXQ50AMYM RXQ50AMY14 RXQ50AMY1S RXQ52AMYM RXQ52AMY14 RXQ52AMY1S
RXQ14AYM+ RXQ14AY14+ RXQ14AY1S+ RXQ16AYM+ RXQ16AY14+ RXQ16AY1S+
Model Name (Independent Unit) RXQ18AYM+ RXQ18AY14+ RXQ18AY1S+ RXQ18AYM+ RXQ18AY14+ RXQ18AY1S+
RXQ18AYM RXQ18AY14 RXQ18AY1S RXQ18AYM RXQ18AY14 RXQ18AY1S
3 phase, 3 phase, 3 phase, 3 phase, 3 phase, 3 phase,
Power Supply 380-415/380 V, 380-415 V, 380-415 V, 380-415/380 V, 380-415 V, 380-415 V,
50/60 Hz 50 Hz 50 Hz 50/60 Hz 50 Hz 50 Hz
kcal/h 120,000 125,000
1 Cooling Capacity Btu/h 478,000 495,000
kW 140 145
Casing Color Ivory white (5Y7.5/1) Ivory white (5Y7.5/1)
Dimensions: (H×W×D) mm (1,657×1,240×765)+(1,657×1,240×765)+(1,657×1,240×765) (1,657×1,240×765)+(1,657×1,240×765)+(1,657×1,240×765)
Heat Exchanger Cross fin coil Cross fin coil
Type Hermetically sealed scroll type Hermetically sealed scroll type
Motor Output×
Compressor kW (6.4×1)+(4.0×1)+(4.0×1)+(4.0×1)+(4.0×1) (3.5×1)+(3.5×1)+(4.0×1)+(4.0×1)+(4.0×1)+(4.0×1)
Number of Units
Starting Method Soft start Soft start
Type Propeller fan Propeller fan
Motor Output kW (0.75×2)+(0.75×2)+(0.75×2) (0.75×2)+(0.75×2)+(0.75×2)
Fan
Airflow Rate m³/min 257+257+257 257+257+257
Drive Direct drive Direct drive
Connecting Liquid Pipe mm 19.1 C1220T (Brazing connection) 19.1 C1220T (Brazing connection)
Pipes Gas Pipe mm 41.3 C1220T (Brazing connection) 41.3 C1220T (Brazing connection)
Mass kg 233+276+276 276+276+276
2 Sound pressure level dB(A) 65 65
High pressure switch, Fan driver overload protector, High pressure switch, Fan driver overload protector,
Safety Devices
Over current relay, Inverter overload protector Over current relay, Inverter overload protector
Capacity Control % 3-100 3-100
Refrigerant Name R410A R410A
Refrigerant Charge kg 7.4+8.4+8.4 8.2+8.4+8.4
Control Electronic expansion valve Electronic expansion valve
Refrigerator Oil Refer to the nameplate of compressor Refer to the nameplate of compressor
Installation manual, Operation manual, Connection pipes, Installation manual, Operation manual, Connection pipes,
Standard Accessories
Clamps Clamps
Specifications — —
Drawing No.
Sound level — —

Notes:
Conversion formulae
1. Indoor temp.: 27°CDB, 19°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5 m, level difference: 0 m.
2. Anechoic chamber conversion value, measured at a point 1 m in front of the unit at a height of 1.5 m. kcal/h=kW×860
Btu/h=kW×3412
During actual operation, these values are normally somewhat higher as a result of ambient conditions. cfm=m³/min×35.3

66 RXQ-A(M)
EDAMT341716 Specifications

Model Name (Combination Unit) RXQ54AMYM RXQ54AMY14 RXQ54AMY1S RXQ56AMYM RXQ56AMY14 RXQ56AMY1S
RXQ18AYM+ RXQ18AY14+ RXQ18AY1S+ RXQ18AYM+ RXQ18AY14+ RXQ18AY1S+
Model Name (Independent Unit) RXQ18AYM+ RXQ18AY14+ RXQ18AY1S+ RXQ18AYM+ RXQ18AY14+ RXQ18AY1S+
RXQ18AYM RXQ18AY14 RXQ18AY1S RXQ20AYM RXQ20AY14 RXQ20AY1S

Power Supply
3 phase,
380-415/380 V,
3 phase,
380-415 V,
3 phase,
380-415 V,
3 phase,
380-415/380 V,
3 phase,
380-415 V,
3 phase,
380-415 V,
3
50/60 Hz 50 Hz 50 Hz 50/60 Hz 50 Hz 50 Hz
kcal/h 129,000 134,000
1 Cooling Capacity Btu/h 512,000 532,000
kW 150 156
Casing Color Ivory white (5Y7.5/1) Ivory white (5Y7.5/1)
Dimensions: (H×W×D) mm (1,657×1,240×765)+(1,657×1,240×765)+(1,657×1,240×765) (1,657×1,240×765)+(1,657×1,240×765)+(1,657×1,240×765)
Heat Exchanger Cross fin coil Cross fin coil
Type Hermetically sealed scroll type Hermetically sealed scroll type
Motor Output×
Compressor kW (4.0×1)+(4.0×1)+(4.0×1)+(4.0×1)+(4.0×1)+(4.0×1) (4.0×1)+(4.0×1)+(4.0×1)+(4.0×1)+(3.8×1)+(6.3×1)
Number of Units
Starting Method Soft start Soft start
Type Propeller fan Propeller fan
Motor Output kW (0.75×2)+(0.75×2)+(0.75×2) (0.75×2)+(0.75×2)+(0.75×2)
Fan
Airflow Rate m³/min 257+257+257 257+257+297
Drive Direct drive Direct drive
Connecting Liquid Pipe mm 19.1 C1220T (Brazing connection) 19.1 C1220T (Brazing connection)
Pipes Gas Pipe mm 41.3 C1220T (Brazing connection) 41.3 C1220T (Brazing connection)
Mass kg 276+276+276 276+276+312
2 Sound pressure level dB(A) 66 68
High pressure switch, Fan driver overload protector, High pressure switch, Fan driver overload protector,
Safety Devices
Over current relay, Inverter overload protector Over current relay, Inverter overload protector
Capacity Control % 3-100 3-100
Refrigerant Name R410A R410A
Refrigerant Charge kg 8.4+8.4+8.4 8.4+8.4+11.8
Control Electronic expansion valve Electronic expansion valve
Refrigerator Oil Refer to the nameplate of compressor Refer to the nameplate of compressor
Installation manual, Operation manual, Connection pipes, Installation manual, Operation manual, Connection pipes,
Standard Accessories
Clamps Clamps
Specifications — —
Drawing No.
Sound level — —

Notes:
Conversion formulae
1. Indoor temp.: 27°CDB, 19°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5 m, level difference: 0 m.
2. Anechoic chamber conversion value, measured at a point 1 m in front of the unit at a height of 1.5 m. kcal/h=kW×860
Btu/h=kW×3412
During actual operation, these values are normally somewhat higher as a result of ambient conditions. cfm=m³/min×35.3

RXQ-A(M) 67
Specifications EDAMT341716

Model Name (Combination Unit) RXQ58AMYM RXQ58AMY14 RXQ58AMY1S RXQ60AMYM RXQ60AMY14 RXQ60AMY1S
RXQ18AYM+ RXQ18AY14+ RXQ18AY1S+ RXQ20AYM+ RXQ20AY14+ RXQ20AY1S+
Model Name (Independent Unit) RXQ20AYM+ RXQ20AY14+ RXQ20AY1S+ RXQ20AYM+ RXQ20AY14+ RXQ20AY1S+
RXQ20AYM RXQ20AY14 RXQ20AY1S RXQ20AYM RXQ20AY14 RXQ20AY1S
3 phase, 3 phase, 3 phase, 3 phase, 3 phase, 3 phase,
Power Supply 380-415/380 V, 380-415 V, 380-415 V, 380-415/380 V, 380-415 V, 380-415 V,
50/60 Hz 50 Hz 50 Hz 50/60 Hz 50 Hz 50 Hz
kcal/h 139,000 144,000
1 Cooling Capacity Btu/h 553,000 573,000
kW 162 168
Casing Color Ivory white (5Y7.5/1) Ivory white (5Y7.5/1)
Dimensions: (H×W×D) mm (1,657×1,240×765)+(1,657×1,240×765)+(1,657×1,240×765) (1,657×1,240×765)+(1,657×1,240×765)+(1,657×1,240×765)
Heat Exchanger Cross fin coil Cross fin coil
Type Hermetically sealed scroll type Hermetically sealed scroll type
Motor Output×
Compressor kW (4.0×1)+(4.0×1)+(3.8×1)+(6.3×1)+(3.8×1)+(6.3×1) (3.8×1)+(6.3×1)+(3.8×1)+(6.3×1)+(3.8×1)+(6.3×1)
Number of Units
Starting Method Soft start Soft start
Type Propeller fan Propeller fan
Motor Output kW (0.75×2)+(0.75×2)+(0.75×2) (0.75×2)+(0.75×2)+(0.75×2)
Fan
Airflow Rate m³/min 257+297+297 297+297+297
Drive Direct drive Direct drive
Connecting Liquid Pipe mm 19.1 C1220T (Brazing connection) 19.1 C1220T (Brazing connection)
Pipes Gas Pipe mm 41.3 C1220T (Brazing connection) 41.3 C1220T (Brazing connection)
Mass kg 276+312+312 312+312+312
2 Sound pressure level dB(A) 69 70
High pressure switch, Fan driver overload protector, High pressure switch, Fan driver overload protector,
Safety Devices
Over current relay, Inverter overload protector Over current relay, Inverter overload protector
Capacity Control % 2-100 2-100
Refrigerant Name R410A R410A
Refrigerant Charge kg 8.4+11.8+11.8 11.8+11.8+11.8
Control Electronic expansion valve Electronic expansion valve
Refrigerator Oil Refer to the nameplate of compressor Refer to the nameplate of compressor
Installation manual, Operation manual, Connection pipes, Installation manual, Operation manual, Connection pipes,
Standard Accessories
Clamps Clamps
Specifications — —
Drawing No.
Sound level — —

Notes:
Conversion formulae
1. Indoor temp.: 27°CDB, 19°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5 m, level difference: 0 m.
2. Anechoic chamber conversion value, measured at a point 1 m in front of the unit at a height of 1.5 m. kcal/h=kW×860
Btu/h=kW×3412
During actual operation, these values are normally somewhat higher as a result of ambient conditions. cfm=m³/min×35.3

68 RXQ-A(M)
2.1
Unit: mm

RXQ-A(M)
1
766 352
2
EDAMT341716

(Pitch of foundation bolt holes)


135
8
3 124

296
105
112

AA
2. Dimensions

722 ~737
70
100 66
160 106
Independent Unit

10

(Pitch of foundation bolt holes)


DETAIL A DETAIL B 4-15 x 22.5mm Oblong holes VIEW C
(Foundation bolt hole)

11
RXQ6AYM / RXQ8AYM / RXQ10AYM / RXQ12AYM
RXQ6AY14 / RXQ8AY14 / RXQ10AY14 / RXQ12AY14
RXQ6AY1S / RXQ8AY1S / RXQ10AY1S / RXQ12AY1S

A Model AA

1657
4 7
RX(Y)Q6, 8,10AY 167
RX(Y)Q12AY 171

6 No. Parts name Remark


1 Liquid pipe connection port See note 3.
2 Gas pipe connection port See note 3.
3 Refrigerant charge port

122
4 Power cord routing hole (side) φ65
5 Power cord routing hole (front) φ80

484
6 Power cord routing hole (front) φ65
7 Transmistion wire routing hole (front) φ27

245
228
8 Power cord routing hole (bottom)

148
96
φ65
9 Pipe routing hole (front)
10 Pipe routing hole (bottom)
66 66 97 5 11 Grounding terminal Inside of switch box (M8)
137 107
765 B 272 C NOTES:
1. DETAIL A AND DETAIL B INDICATE THE DIMENSIONS AFTER FIXING THE ATTACHED PIPING.
328 2. ITEM 4 TO 10 KNOCK OUT HOLE.
3. GAS PIPE:
373
φ19.1 BRAZING CONNECTION: RX(Y)Q6, 8AY
930 φ22.2 BRAZING CONNECTION: RX(Y)Q10AY
φ28.6 BRAZING CONNECTION: RX(Y)Q12AY
LIQUID PIPE:
φ9.5 BRAZING CONNECTION: RX(Y)Q6, 8, 10AY
φ12.7 BRAZING CONNECTION: RX(Y)Q12AY

3D111514

69
Dimensions

3
70
Unit: mm
Dimensions

1 4-15 x 22.5 Oblong holes


1076 (Foundation bolt hole)
2
(Pitch of foundation bolt holes)
393
3
134
125 8

112
107

271
AA
722~737
70
100 71 10
160 AB

(Pitch of foundation bolt holes)


VIEW C
DETAIL A DETAIL B

11
RXQ14AYM / RXQ16AYM / RXQ18AYM / RXQ20AYM
RXQ14AY14 / RXQ16AY14 / RXQ18AY14 / RXQ20AY14
RXQ14AY1S / RXQ16AY1S / RXQ18AY1S / RXQ20AY1S

Model AA AB
RX(Y)Q14, 16,18AY 171 106
9 RXUQ8, 10, 12, 14, 16, 18AY
RX(Y)Q20AY 161 101
RXUQ20AY
7

1657
4 No. Parts name Remark
1 Liquid pipe connection port See note 3.
6 2 Gas pipe connection port See note 3.
A 3 Refrigerant charge port
4 Power cord routing hole (side) φ65
5 Power cord routing hole (front) φ80
6 Power cord routing hole (front) φ65

122
7 Tranmistion wire routing hole (front) φ27
8 Power cord routing hole (bottom)

484
φ65
9 Pipe routing hole (front)
10 Pipe routing hole (bottom)

245
228
148
11 Grounding terminal Inside of switch box (M8)

94
NOTES:
66 66 B 97 107 1. DETAIL A AND DETAIL B INDICATE THE DIMENSIONS AFTER FIXING THE ATTACHED PIPING.
5 2. ITEM 4 TO 10 KNOCK OUT HOLE.
137 272 C 3. GAS PIPE :
765 328 φ19.1 BRAZING CONNECTION: RXUQ8AY
φ22.2 BRAZING CONNECTION: RXUQ10AY
373 φ28.6 BRAZING CONNECTION: RX(Y)Q14, 16, 18, 20AY, RXUQ12, 14, 16, 18, 20AY
1240 LIQUID PIPE:
φ9.5 BRAZING CONNECTION: RXUQ8, 10AY
φ12.7 BRAZING CONNECTION: RX(Y)Q14, 16AY, RXUQ12, 14, 16AY
φ15.9 BRAZING CONNECTION: RX(Y)Q18, 20AY, RXUQ18, 20AY

3D111515

RXQ-A(M)
EDAMT341716
Unit: mm 2.2

RXQ-A(M)
EDAMT341716

 The example of installation required space

4-15 x 22.5 Oblong hole 300 or more


4-15 x 22.5 Oblong hole (foundation bolt hole)
(foundation bolt hole) 766 766
(Foundation bolt hole pitch) (Foundation bolt hole pitch)

10 or more 10 or more

20 or more

500 or more
Combination Unit

FRONT SIDE

722 ~737
< Unit : mm >
Note: 1. For the wall height of the example for this installation required space area,

(Foundation bolt hole pitch)


Fornt side: 1500 mm
Suction side: 500 mm
Lateral side: No height limitation
This installation required space example has the standard of cooling
operation at outdoor unit air temperature 35°C.
OUTDOOR UNIT 1 OUTDOOR UNIT 2 In case the temperature is over 35°C of designed outdoor air temperature,
or there is much heat load on all outdoor unit which its operation load
is over the maximum capacity, make sure to enlarge the suction side space
to be more than the value details which specified in drawing.
2. In case of it is over the wall height as specified, make sure to add each
dimension h2/2, h1/2 or more to the front side, suction side space as
below diagram.
3. When installation, select the most suitable pattern of installation service
space adapt to field space by considering pathway, ventilation.
RXQ18AMYM / RXQ20AMYM / RXQ22AMYM / RXQ24AMYM

4. For front side space, make sure to install by considering the neccesary
space for refrigerant piping construction at the field.
RXQ18AMY14 / RXQ20AMY14 / RXQ22AMY14 / RXQ24AMY14
RXQ18AMY1S / RXQ20AMY1S / RXQ22AMY1S / RXQ24AMY1S

h2

1657
h1

1500
FRONT SIDE
SUCTION SIDE
500

20 or more
930 930 765

SYSTEM NAME OUTDOOR UNIT1 DWG. No. OUTDOOR UNIT2 DWG. No.
RX(Y)Q18AMY RX(Y)Q10AY 3D111514 RX(Y)Q8AY 3D111514
RX(Y)Q20AMY RX(Y)Q12AY 3D111514 RX(Y)Q8AY 3D111514
RX(Y)Q22AMY RX(Y)Q12AY 3D111514 RX(Y)Q10AY 3D111514
RX(Y)Q24AMY RX(Y)Q12AY 3D111514 RX(Y)Q12AY 3D111514

3D111519

71
Dimensions

3
72
Unit: mm
Dimensions

4-15 x 22.5 Oblong hole 4-15 x 22.5 Oblong hole


1076 766  The example of installation required space
(foundation bolt hole) (foundation bolt hole)
(Foundation bolt hole pitch) (Foundation bolt hole pitch)

300 or more

722~737
10 or more 20 or more 10 or more

500
or more

(Foundation bolt hole pitch)


FRONT SIDE

OUTDOOR UNIT 1 OUTDOOR UNIT 2 < Unit : mm >


Note: 1. For the wall height of the example for this installation required space area,
Fornt side: 1500 mm
Suction side: 500 mm
RXQ26AMYM / RXQ28AMYM / RXQ30AMYM

Lateral side: No height limitation


RXQ26AMY14 / RXQ28AMY14 / RXQ30AMY14

This installation required space example has the standard of cooling


RXQ26AMY1S / RXQ28AMY1S / RXQ30AMY1S

operation at outdoor unit air temperature 35°C.


In case the temperature is over 35°C of designed outdoor air temperature,
or there is much heat load on all outdoor unit which its operation load
is over the maximum capacity, make sure to enlarge the suction side space
to be more than the value details which specified in drawing.
2. In case of it is over the wall height as specified, make sure to add each
dimension h2/2, h1/2 or more to the front side, suction side space as

1657
below diagram.
3. When installation, select the most suitable pattern of installation service
space adapt to field space by considering pathway, ventilation.
4. For front side space, make sure to install by considering the neccesary
space for refrigerant piping construction at the field.
h2

20 or more
h1

1240 930 765


1500
FRONT SIDE
SUCTION SIDE
500

SYSTEM NAME OUTDOOR UNIT1 DWG. No. OUTDOOR UNIT2 DWG. No.
RX(Y)Q26AMY RX(Y)Q14AY 3D111515 RX(Y)Q12AY 3D111514
RX(Y)Q28AMY RX(Y)Q16AY 3D111515 RX(Y)Q12AY 3D111514
RX(Y)Q30AMY RX(Y)Q18AY 3D111515 RX(Y)Q12AY 3D111514

3D111518

RXQ-A(M)
EDAMT341716
Unit: mm

RXQ-A(M)
4-15 x 22.5 Oblong hole 1076 1076 4-15 x 22.5 Oblong hole
EDAMT341716

(foundation bolt hole) (foundation bolt hole pitch) (foundation bolt hole pitch) (foundation bolt hole)
 The example of installation required space

300 or more

722 ~ 737
20 or more
10 or more 10 or more

500
or more

(foundation bolt hole pitch)


FRONT SIDE
OUTDOOR UNIT 1 OUTDOOR UNIT 2
< Unit : mm >
Note: 1. For the wall height of the example for this installation required space area,
Fornt side: 1500 mm
Suction side: 500 mm
Lateral side: No height limitation
This installation required space example has the standard of cooling
operation at outdoor unit air temperature 35°C.
In case the temperature is over 35°C of designed outdoor air temperature,
or there is much heat load on all outdoor unit which its operation load
is over the maximum capacity, make sure to enlarge the suction side space
to be more than the value details which specified in drawing.
2. In case of it is over the wall height as specified, make sure to add each

1657
dimension h2/2, h1/2 or more to the front side, suction side space as
below diagram.
3. When installation, select the most suitable pattern of installation service
space adapt to field space by considering pathway, ventilation.
4. For front side space, make sure to install by considering the neccesary
space for refrigerant piping construction at the field.
h2

20 or more
1240 1240 765
RXQ32AMYM / RXQ34AMYM / RXQ36AMYM / RXQ38AMYM / RXQ40AMYM

SYSTEM NAME OUTDOOR UNIT1 DWG. No. OUTDOOR UNIT2 DWG. No.
h1

RX(Y)Q32AMY RX(Y)Q18AY 3D111515 RX(Y)Q14AY 3D111515


1500
RXQ32AMY14 / RXQ34AMY14 / RXQ36AMY14 / RXQ38AMY14 / RXQ40AMY14

RX(Y)Q34AMY RX(Y)Q18AY 3D111515 RX(Y)Q16AY 3D111515


RXQ32AMY1S / RXQ34AMY1S / RXQ36AMY1S / RXQ38AMY1S / RXQ40AMY1S

RX(Y)Q36AMY RX(Y)Q18AY 3D111515 RX(Y)Q18AY 3D111515


FRONT SIDE
SUCTION SIDE

RX(Y)Q38AMY RX(Y)Q20AY 3D111515 RX(Y)Q18AY 3D111515


500

RX(Y)Q40AMY RX(Y)Q20AY 3D111515 RX(Y)Q20AY 3D111515


SYSTEM NAME OUTDOOR UNIT1 DWG. No. OUTDOOR UNIT2 DWG. No. SYSTEM NAME OUTDOOR UNIT1 DWG. No. OUTDOOR UNIT2 DWG. No.
RXUQ18AMY RXUQ10AY 3D111515 RXUQ8AY 3D111515 RXUQ30AMY RXUQ18AY 3D111515 RXUQ12AY 3D111515
RXUQ20AMY RXUQ12AY 3D111515 RXUQ8AY 3D111515 RXUQ32AMY RXUQ20AY 3D111515 RXUQ12AY 3D111515
RXUQ22AMY RXUQ14AY 3D111515 RXUQ8AY 3D111515 RXUQ34AMY RXUQ18AY 3D111515 RXUQ16AY 3D111515
RXUQ24AMY RXUQ16AY 3D111515 RXUQ8AY 3D111515 RXUQ36AMY RXUQ18AY 3D111515 RXUQ18AY 3D111515
RXUQ26AMY RXUQ18AY 3D111515 RXUQ8AY 3D111515 RXUQ38AMY RXUQ20AY 3D111515 RXUQ18AY 3D111515
RXUQ28AMY RXUQ20AY 3D111515 RXUQ8AY 3D111515 RXUQ40AMY RXUQ20AY 3D111515 RXUQ20AY 3D111515

3D111516

73
Dimensions

3
74
Unit: mm
Dimensions

 The example of installation required space


4-15 x 22.5 Oblong hole 4-15 x 22.5 Oblong hole 4-15 x 22.5 Oblong hole
(foundation bolt hole) (foundation bolt hole) (foundation bolt hole)
300 or more
1076 766 766
(foundation bolt hole pitch) (foundation bolt hole pitch) (foundation bolt hole pitch)

10 or more 20 or more 10 or more


RXQ42AMYM / RXQ44AMYM

500
20 or more
RXQ42AMY14 / RXQ44AMY14

or more
RXQ42AMY1S / RXQ44AMY1S

FRONT SIDE

722 ~737
< Unit : mm >

(foundation bolt hole pitch)


Note: 1. For the wall height of the example for this installation required
space area,
Fornt side: 1500 mm
Suction side: 500 mm
OUTDOOR UNIT 1 OUTDOOR UNIT 2 OUTDOOR UNIT 3 Lateral side: No height limitation
This installation required space example has the standard of cooling
operation at outdoor unit air temperature 35°C.
In case the temperature is over 35°C of designed outdoor air
temperature,or there is much heat load on all outdoor unit which
its operation load is over the maximum capacity, make sure to
enlarge the suction side space to be more than the value details
which specified in drawing.
2. In case of it is over the wall height as specified, make sure to add each
dimension h2/2, h1/2 or more to the front side, suction side space as
below diagram.
3. When installation, select the most suitable pattern of installation service
space adapt to field space by considering pathway, ventilation.
4. For front side space, make sure to install by considering the neccesary

1675
space for refrigerant piping construction at the field.
h2
h1

1500

20 or more 20 or more
FRONT SIDE
SUCTION SIDE

1240 930 930 765


500

SYSTEM NAME OUTDOOR UNIT1 DWG. No. OUTDOOR UNIT2 DWG. No. OUTDOOR UNIT3 DWG. No.
RX(Y)Q42AMY RX(Y)Q18AY 3D111515 RX(Y)Q12AY 3D111514 RX(Y)Q12AY 3D111514
RX(Y)Q44AMY RX(Y)Q20AY 3D111515 RX(Y)Q12AY 3D111514 RX(Y)Q12AY 3D111514

3D111520

RXQ-A(M)
EDAMT341716
Unit: mm

RXQ-A(M)
4-15 x 22.5 Oblong hole 4-15 x 22.5 Oblong hole 4-15 x 22.5 Oblong hole
 The example of installation required space
EDAMT341716

(foundation bolt hole) (foundation bolt hole) (foundation bolt hole)


1076 1076 1076
(foundation bolt hole pitch) (foundation bolt hole pitch) (foundation bolt hole pitch) 300 or more

10 or more 20 or more 10 or more


20 or more

500
or more

722 ~ 737
RXQ58AMYM / RXQ60AMYM

RXQ58AMY14 / RXQ60AMY14

RXQ58AMY1S / RXQ60AMY1S

(foundation bolt hole pitch)


FRONT SIDE < Unit : mm >
Note:
OUTDOOR UNIT 1 OUTDOOR UNIT 2 OUTDOOR UNIT 3 1. For the wall height of the example for this
installation required space area,
Fornt side: 1500 mm
Suction side: 500 mm
Lateral side: No height limitation
This installation required space example has
the standard of cooling
operation at outdoor unit air temperature 35°C.
In case the temperature is over 35°C of designed
outdoor air temperature,or there is much heat load
on all outdoor unit which its operation load is over
the maximum capacity, make sure to enlarge the
suction side space to be more than the value details

1657
which specified in drawing.
2. In case of it is over the wall height as specified,
make sure to add each dimension h2/2, h1/2 or
more to the front side, suction side space as
below diagram.
3. When installation, select the most suitable pattern
of installation service space adapt to field space
by considering pathway, ventilation.
4. For front side space, make sure to install by
considering the neccesary space for refrigerant
piping construction at the field.
20 or more 20 or more
1240 1240 1240
h2

SYSTEM NAME OUTDOOR UNIT1 DWG. No. OUTDOOR UNIT2 DWG. No. OUTDOOR UNIT3 DWG. No.
RX(Y)Q46AMY RX(Y)Q18AY 3D111515 RX(Y)Q14AY 3D111515 RX(Y)Q14AY 3D111515
RX(Y)Q48AMY RX(Y)Q18AY 3D111515 RX(Y)Q16AY 3D111515 RX(Y)Q14AY 3D111515
RX(Y)Q50AMY RX(Y)Q18AY 3D111515 RX(Y)Q18AY 3D111515 RX(Y)Q14AY 3D111515
RX(Y)Q52AMY RX(Y)Q18AY 3D111515 RX(Y)Q18AY 3D111515 RX(Y)Q16AY 3D111515
RX(Y)Q54AMY RX(Y)Q18AY 3D111515 RX(Y)Q18AY 3D111515 RX(Y)Q18AY 3D111515
h1

RX(Y)Q56AMY RX(Y)Q20AY 3D111515 RX(Y)Q18AY 3D111515 RX(Y)Q18AY 3D111515


1500

RX(Y)Q58AMY RX(Y)Q20AY 3D111515 RX(Y)Q20AY 3D111515 RX(Y)Q18AY 3D111515


RX(Y)Q60AMY RX(Y)Q20AY 3D111515 RX(Y)Q20AY 3D111515 RX(Y)Q20AY 3D111515
SYSTEM NAME OUTDOOR UNIT1 DWG. No. OUTDOOR UNIT2 DWG. No. OUTDOOR UNIT3 DWG. No.
FRONT SIDE
SUCTION SIDE

RXUQ42AMY RXUQ18AY 3D111515 RXUQ16AY 3D111515 RXUQ8AY 3D111515


500

RXUQ44AMY RXUQ18AY 3D111515 RXUQ18AY 3D111515 RXUQ8AY 3D111515


RXUQ46AMY RXUQ20AY 3D111515 RXUQ18AY 3D111515 RXUQ8AY 3D111515
RXUQ48AMY RXUQ20AY 3D111515 RXUQ20AY 3D111515 RXUQ8AY 3D111515
RXUQ50AMY RXUQ20AY 3D111515 RXUQ18AY 3D111515 RXUQ12AY 3D111515
RXUQ52AMY RXUQ20AY 3D111515 RXUQ20AY 3D111515 RXUQ12AY 3D111515
RXUQ54AMY RXUQ18AY 3D111515 RXUQ18AY 3D111515 RXUQ18AY 3D111515
RXQ46AMYM / RXQ48AMYM / RXQ50AMYM / RXQ52AMYM / RXQ54AMYM / RXQ56AMYM /

RXUQ56AMY RXUQ20AY 3D111515 RXUQ18AY 3D111515 RXUQ18AY 3D111515


RXUQ58AMY RXUQ20AY 3D111515 RXUQ20AY 3D111515 RXUQ18AY 3D111515
RXQ46AMY14 / RXQ48AMY14 / RXQ50AMY14 / RXQ52AMY14 / RXQ54AMY14 / RXQ56AMY14 /

RXUQ60AMY RXUQ20AY 3D111515 RXUQ20AY 3D111515 RXUQ20AY 3D111515


RXQ46AMY1S / RXQ48AMY1S / RXQ50AMY1S / RXQ52AMY1S / RXQ54AMY1S / RXQ56AMY1S /

3D111517

75
Dimensions

3
Service Space (Reference) EDAMT341716

3. Service Space (Reference)


RXQ6AYM / RXQ8AYM / RXQ10AYM / RXQ12AYM / RXQ14AYM / RXQ16AYM / RXQ18AYM / RXQ20AYM /
RXQ18AMYM / RXQ20AMYM / RXQ22AMYM / RXQ24AMYM / RXQ26AMYM / RXQ28AMYM / RXQ30AMYM /
RXQ32AMYM / RXQ34AMYM / RXQ36AMYM / RXQ38AMYM / RXQ40AMYM / RXQ42AMYM / RXQ44AMYM /
RXQ46AMYM / RXQ48AMYM / RXQ50AMYM / RXQ52AMYM / RXQ54AMYM / RXQ56AMYM / RXQ58AMYM /
RXQ60AMYM
RXQ6AY14 / RXQ8AY14 / RXQ10AY14 / RXQ12AY14 / RXQ14AY14 / RXQ16AY14 / RXQ18AY14 /
RXQ20AY14 / RXQ18AMY14 / RXQ20AMY14 / RXQ22AMY14 / RXQ24AMY14 / RXQ26AMY14 /
RXQ28AMY14 / RXQ30AMY14 / RXQ32AMY14 / RXQ34AMY14 / RXQ36AMY14 / RXQ38AMY14 /
RXQ40AMY14 / RXQ42AMY14 / RXQ44AMY14 / RXQ46AMY14 / RXQ48AMY14 / RXQ50AMY14 /
RXQ52AMY14 / RXQ54AMY14 / RXQ56AMY14 / RXQ58AMY14 / RXQ60AMY14
RXQ6AY1S / RXQ8AY1S / RXQ10AY1S / RXQ12AY1S / RXQ14AY1S / RXQ16AY1S / RXQ18AY1S /
RXQ20AY1S / RXQ18AMY1S / RXQ20AMY1S / RXQ22AMY1S / RXQ24AMY1S / RXQ26AMY1S /
RXQ28AMY1S / RXQ30AMY1S / RXQ32AMY1S / RXQ34AMY1S / RXQ36AMY1S / RXQ38AMY1S /
RXQ40AMY1S / RXQ42AMY1S / RXQ44AMY1S / RXQ46AMY1S / RXQ48AMY1S / RXQ50AMY1S /
RXQ52AMY1S / RXQ54AMY1S / RXQ56AMY1S / RXQ58AMY1S / RXQ60AMY1S
Unit: mm

76 RXQ-A(M)
RXQ-A(M)
Stop valve ( With service port on on-site piping side φ 7.9mm flare connection )
EDAMT341716

Double tube
Heat exchanger
R6T Electronic Expansion
valve (main)
R4T
Liquid
pipe
Filter R5T (Y1E) Filter

Heat sink PCB


4. Piping Diagrams

Fan R1T
Electronic expansion
valve
M Heat exchanger
(Y2E)
M1F

SENPH
(S1NPH)
RXQ6AYM / RXQ8AYM / RXQ10AYM / RXQ12AYM

Pressure
regulating High pressure
RXQ6AY14 / RXQ8AY14 / RXQ10AY14 / RXQ12AY14

valve sensor
RXQ6AY1S / RXQ8AY1S / RXQ10AY1S / RXQ12AY1S

Check valve

Filter
(S1PH)
High pressure
switch
Oil

HPS
Electronic expansion
Separator

valve
Refrigerant R21T
Auto charge
port Filter
Filter (Y4E)

Compressor
R8T
SV

(S1NPL) Solenoid valve (Y3S)


INV
Low pressure
sensor
M1C
SENPL

R3T
Gas
pipe Capillary tube
Filter

3D111780

77
Piping Diagrams

3
78
Stop valve ( With service port on on-site piping side φ 7.9mm flare connection )
RXQ14AYM
RXQ14AY14
RXQ14AY1S
Piping Diagrams

Double tube
Heat Exchanger
R6T Electronic expansion
Valve (main)
(Y1E)
R4T
Liquid
Pipe
Filter
R5T FILTER

FAN

Electronic R1T
M1F M
Expansion Heat Exchanger
Heat sink PCB
Valve FAN
(Y2E)
M2F M

(S1NPH)
Pressure SENPH High pressure
sensor
Regulating
Valve
Check valve

Filter
(S1PH)
Electronic Expansion High pressure
Valve switch
Oil

(Y4E) HPS
Separator

Refrigerant
Auto charge R21T
port
Filter
Filter

Compressor
(S1NPL) R8T
SV

INV Solenoid valve (Y3S)


Low pressure
sensor
M1C

SENPL
R3T
Gas
Pipe Capillary tube
Filter

3D111855

RXQ-A(M)
EDAMT341716
RXQ-A(M)
Stop valve ( With service port on on-site piping side φ 7.9mm flare connection )
EDAMT341716

Double tube
Heat Exchanger
R6T Electronic Expansion
Valve (main)
(Y1E)
R4T
Liquid
Pipe
Filter
R5T FILTER

FAN

Electronic R1T
M1F M
Expansion Heat Exchanger
Heat sink PCB
Valve FAN
RXQ16AYM / RXQ18AYM / RXQ20AYM

(Y2E)
RXQ16AY14 / RXQ18AY14 / RXQ20AY14

M2F M
RXQ16AY1S / RXQ18AY1S / RXQ20AY1S

(S1NPH)
Pressure SENPH High pressure
sensor
Regulating
Valve

Check Valve Check Valve

Filter Filter

Electronic Expansion
Oil
Oil

(S2PH) (S1PH)
Valve High pressure High pressure
Separator
Separator

(Y4E) switch switch


Refrigerant HPS HPS
Filter
Auto charge Filter
port Filter
R22T R21T

Solenoid Solenoid
sv
sv

Compressor valve valve Compressor


R9T (Y4S) (Y3S) R8T
(S1NPL) INV2 INV1
Low pressure M2C Capillary
sensor tube
M1C

SENPL
Capillary
R3T tube
Gas
Pipe
Filter

3D111854

79
Piping Diagrams

3
Wiring Diagrams (Reference) EDAMT341716

5. Wiring Diagrams (Reference)


RXQ6AYM / RXQ8AYM
RXQ6AY14 / RXQ8AY14
RXQ6AY1S / RXQ8AY1S

80 RXQ-A(M)
EDAMT341716 Wiring Diagrams (Reference)

RXQ10AYM / RXQ12AYM
RXQ10AY14 / RXQ12AY14
RXQ10AY1S / RXQ12AY1S
3

RXQ-A(M) 81
Wiring Diagrams (Reference) EDAMT341716

RXQ14AYM
RXQ14AY14
RXQ14AY1S

82 RXQ-A(M)
EDAMT341716 Wiring Diagrams (Reference)

RXQ16AYM / RXQ18AYM / RXQ20AYM


RXQ16AY14 / RXQ18AY14 / RXQ20AY14
RXQ16AY1S / RXQ18AY1S / RXQ20AY1S
3

RXQ-A(M) 83
84
NOTES
1) ALL WIRING COMPONENTS AND MATERIALS TO BE PROCURED ON THE SITE MUST COMPLY WITH THE APPLICABLE LOCAL AND NATIONAL CODES.
Field Wiring

2) USE COPPER CONDUCTORS ONLY.

RXQ20AY14

RXQ20AY1S
3) AS FOR DETAILS, SEE WIRING DIAGRAM.
4) INSTALL CIRCUIT BREAKER FOR SAFETY.
5) ALL FIELD WIRING AND COMPONENTS MUST BE PROVIDED BY LICENSED ELECTRICIAN.
6) UNIT SHALL BE GROUNDED IN COMPLIANC WITH THE APPLICABLE LOCAL AND NATIONAL CODES.
7) WIRING SHOWN ARE GENERAL POINTS-OF-CONNECTION GUIDES ONLY AND ARE NOT INTENDED FOR OR TO INCLUDE ALL DETAILS FOR A SPECIFIC INSTALLATION.
8) FOR INDOOR UNITS, INSTALL ONE SWITCH AND ONE FUSE PER SYSTEM. (NOT PER INDOOR UNIT)
9) INSTALL THE MAIN SWITCH THAT CAN INTERRUPT ALL THE POWER SOURCES IN AN INTEGRATED MANNER BECAUSE THIS SYSTEM CONSISTS OF THE EQUIPMENT UTILIZING THE MULTIPLE POWER SOURCES.
10) MUST INSTALL EARTH LEAKAGE CIRCUIT BREAKER.
6. Field Wiring

POWER SUPPLY
L1 L2 L3 N

MAIN SWITCH

OUTDOOR UNITS
L1 L2 L3 N
SWITCH

FUSE

POWER SUPPLY
L N

MAIN SWITCH
FUSE

2 WIRES CABLE
(TRANSMISSION LINE)

2 WIRES CABLE 2 WIRES CABLE 2 WIRES CABLE


(TRANSMISSION LINE) (TRANSMISSION LINE) (TRANSMISSION LINE)
2 WIRES CABLE
(POWER LINE)

2 WIRES CABLE 2 WIRES CABLE 2 WIRES CABLE 2 WIRES CABLE


(POWER LINE) (POWER LINE) (POWER LINE) (POWER LINE)
RXQ6AY14 / RXQ8AY14 / RXQ10AY14 / RXQ12AY14 / RXQ14AY14 / RXQ16AY14 / RXQ18AY14 /

RXQ6AY1S / RXQ8AY1S / RXQ10AY1S / RXQ12AY1S / RXQ14AY1S / RXQ16AY1S / RXQ18AY1S /

INDOOR UNITS
3D111511
RXQ6AYM / RXQ8AYM / RXQ10AYM / RXQ12AYM / RXQ14AYM / RXQ16AYM / RXQ18AYM / RXQ20AYM

RXQ-A(M)
EDAMT341716
RXQ-A(M)
NOTES
1) ALL WIRING COMPONENTS AND MATERIALS TO BE PROCURED ON THE SITE MUST COMPLY WITH THE APPLICABLE LOCAL AND NATIONAL CODES.
2) USE COPPER CONDUCTORS ONLY.
EDAMT341716

3) AS FOR DETAILS, SEE WIRING DIAGRAM.


4) INSTALL CIRCUIT BREAKER FOR SAFETY.
5) ALL FIELD WIRING AND COMPONENTS MUST BE PROVIDED BY LICENSED ELECTRICIAN.
6) UNIT SHALL BE GROUNDED IN COMPLIANC WITH THE APPLICABLE LOCAL AND NATIONAL CODES.
7) WIRING SHOWN ARE GENERAL POINTS-OF-CONNECTION GUIDES ONLY AND ARE NOT INTENDED FOR OR TO INCLUDE ALL DETAILS FOR A SPECIFIC INSTALLATION.
8) FOR INDOOR UNITS, INSTALL ONE SWITCH AND ONE FUSE PER SYSTEM. (NOT PER INDOOR UNIT)
9) INSTALL THE MAIN SWITCH THAT CAN INTERRUPT ALL THE POWER SOURCES IN AN INTEGRATED MANNER BECAUSE THIS SYSTEM CONSISTS OF THE EQUIPMENT UTILIZING THE MULTIPLE POWER SOURCES.
10) THE CAPACITY OF UNIT 1 MUST BE LARGER THAN UNIT 2 WHEN THE POWER SOURCE IS CONNECTED IN SERIES BETWEEN THE UNITS.
11) MUST INSTALL EARTH LEAKAGE CIRCUIT BREAKER.

WHEN THE POWER SOURCE IS SUPPLIED TO EACH OUTDOOR UNIT INDIVIDUALLY. WHEN THE POWER SOURCE IS CONNECTED IN SERIES BETWEEN THE UNITS.

POWER SUPPLY POWER SUPPLY


L1 L2 L3 N OUTDOOR UNITS L1 L2 L3 N OUTDOOR UNITS
MAIN SWITCH MAIN SWITCH

2 WIRES CABLE 2 WIRES CABLE


(TRANSMISSION LINE) (TRANSMISSION LINE)

[UNIT 1] [UNIT 2] [UNIT 1] [UNIT 2]


L1 L2 L3 N L1 L2 L3 N L1 L2 L3 N
SWITCH SWITCH SWITCH

FUSE FUSE FUSE

POWER SUPPLY POWER SUPPLY


L N L N

MAIN SWITCH MAIN SWITCH


FUSE FUSE
2 WIRES CABLE
2 WIRES CABLE (TRANSMISSION LINE)
(TRANSMISSION LINE)
RXQ32AMYM / RXQ34AMYM / RXQ36AMYM / RXQ38AMYM / RXQ40AMYM

2 WIRES CABLE 2 WIRES CABLE 2 WIRES CABLE 2 WIRES CABLE 2 WIRES CABLE 2 WIRES CABLE
2 WIRES CABLE (TRANSMISSION LINE) (TRANSMISSION LINE) (TRANSMISSION LINE) 2 WIRES CABLE (TRANSMISSION LINE) (TRANSMISSION LINE) (TRANSMISSION LINE)
(POWER LINE) (POWER LINE)

2 WIRES CABLE 2 WIRES CABLE


(POWER LINE) (POWER LINE)

2 WIRES CABLE 2 WIRES CABLE 2 WIRES CABLE 2 WIRES CABLE 2 WIRES CABLE 2 WIRES CABLE
(POWER LINE) (POWER LINE) (POWER LINE) (POWER LINE) (POWER LINE) (POWER LINE)
RXQ30AMY14 / RXQ32AMY14 / RXQ34AMY14 / RXQ36AMY14 / RXQ38AMY14 / RXQ40AMY14
RXQ18AMY14 / RXQ20AMY14 / RXQ22AMY14 / RXQ24AMY14 / RXQ26AMY14 / RXQ28AMY14 /

RXQ30AMY1S / RXQ32AMY1S / RXQ34AMY1S / RXQ36AMY1S / RXQ38AMY1S / RXQ40AMY1S


RXQ18AMY1S / RXQ20AMY1S / RXQ22AMY1S / RXQ24AMY1S / RXQ26AMY1S / RXQ28AMY1S /

INDOOR UNITS INDOOR UNITS

3D111512
RXQ18AMYM / RXQ20AMYM / RXQ22AMYM / RXQ24AMYM / RXQ26AMYM / RXQ28AMYM / RXQ30AMYM /

85
Field Wiring

3
86
Field Wiring

NOTES
1) ALL WIRING COMPONENTS AND MATERIALS TO BE PROCURED ON THE SITE MUST COMPLY WITH THE APPLICABLE LOCAL AND NATIONAL CODES.
2) USE COPPER CONDUCTORS ONLY.
3) AS FOR DETAILS, SEE WIRING DIAGRAM.
4) INSTALL CIRCUIT BREAKER FOR SAFETY.
5) ALL FIELD WIRING AND COMPONENTS MUST BE PROVIDED BY LICENSED ELECTRICIAN.
6) UNIT SHALL BE GROUNDED IN COMPLIANC WITH THE APPLICABLE LOCAL AND NATIONAL CODES.
7) WIRING SHOWN ARE GENERAL POINTS-OF-CONNECTION GUIDES ONLY AND ARE NOT INTENDED FOR OR TO INCLUDE ALL DETAILS FOR A SPECIFIC INSTALLATION.
8) FOR INDOOR UNITS, INSTALL ONE SWITCH AND ONE FUSE PER SYSTEM. (NOT PER INDOOR UNIT)
9) INSTALL THE MAIN SWITCH THAT CAN INTERRUPT ALL THE POWER SOURCES IN AN INTEGRATED MANNER BECAUSE THIS SYSTEM CONSISTS OF THE EQUIPMENT UTILIZING THE MULTIPLE POWER SOURCES.
10) THE CAPACITY OF UNIT 1 MUST BE LARGER THAN UNIT 2 AND UNIT 2 MUST BE LARGER THAN UNIT 3 WHEN THE POWER SOURCE IS CONNECTED IN SERIES BETWEEN THE UNITS.
11) MUST INSTALL EARTH LEAKAGE CIRCUIT BREAKER.

WHEN THE POWER SOURCE IS SUPPLIED TO EACH OUTDOOR UNIT INDIVIDUALLY. WHEN THE POWER SOURCE IS CONNECTED IN SERIES BETWEEN THE UNITS.

POWER SUPPLY POWER SUPPLY


RXQ56AMYM / RXQ58AMYM / RXQ60AMYM

L1 L2 L3 N OUTDOOR UNITS L1 L2 L3 N OUTDOOR UNITS


MAIN SWITCH MAIN SWITCH
2 WIRES CABLE 2 WIRES CABLE 2 WIRES CABLE 2 WIRES CABLE
(TRANSMISSION LINE) (TRANSMISSION LINE) (TRANSMISSION LINE) (TRANSMISSION LINE)

[UNIT 1] [UNIT 2] [UNIT 3] [UNIT 1] [UNIT 2] [UNIT 3]


L1 L2 L3 N L1 L2 L3 N L1 L2 L3 N L1 L2 L3 N
SWITCH SWITCH SWITCH SWITCH

FUSE FUSE FUSE FUSE


RXQ54AMY14 / RXQ56AMY14 / RXQ58AMY14 / RXQ60AMY14

RXQ54AMY1S / RXQ56AMY1S / RXQ58AMY1S / RXQ60AMY1S

POWER SUPPLY POWER SUPPLY


L N L N

MAIN SWITCH MAIN SWITCH


FUSE FUSE
2 WIRES CABLE
(TRANSMISSION LINE)

2 WIRES CABLE 2 WIRES CABLE 2 WIRES CABLE 2 WIRES CABLE 2 WIRES CABLE 2 WIRES CABLE 2 WIRES CABLE
(TRANSMISSION LINE) (TRANSMISSION LINE) (TRANSMISSION LINE) (TRANSMISSION LINE) (TRANSMISSION LINE) (TRANSMISSION LINE) (TRANSMISSION LINE)

2 WIRES CABLE 2 WIRES CABLE


(POWER LINE) (POWER LINE)

2 WIRES CABLE 2 WIRES CABLE


(POWER LINE) (POWER LINE)

2 WIRES CABLE 2 WIRES CABLE 2 WIRES CABLE 2 WIRES CABLE 2 WIRES CABLE 2 WIRES CABLE
(POWER LINE) (POWER LINE) (POWER LINE) (POWER LINE) (POWER LINE) (POWER LINE)
RXQ42AMY14 / RXQ44AMY14 / RXQ46AMY14 / RXQ48AMY14 / RXQ50AMY14 / RXQ52AMY14 /

INDOOR UNITS INDOOR UNITS


RXQ42AMY1S / RXQ44AMY1S / RXQ46AMY1S / RXQ48AMY1S / RXQ50AMY1S / RXQ52AMY1S /

3D111513
RXQ42AMYM / RXQ44AMYM / RXQ46AMYM / RXQ48AMYM / RXQ50AMYM / RXQ52AMYM / RXQ54AMYM /

RXQ-A(M)
EDAMT341716
RXQ-A(M)
Model name Units Power supply Compressor OFM

RXQ20AY14

RXQ20AY1S
Combination unit Independent Unit Hz Volts Min. Max. MCA TOCA MFA MSC RLA kW FLA
EDAMT341716

RXQ6AYM 380 – 4.7


50 400 342 456 – 4.5
RXQ6AY14 16.1 18.5 20 0.55 0.8
415 – 4.3
RXQ6AY1S 60 380 342 418 – 4.7
RXQ8AYM 380 – 7.4
50 400 342 456 – 7.0
RXQ8AY14 16.1 18.5 20 0.55 1.4
415 – 6.8
RXQ8AY1S 60 380 342 418 – 7.4
RXQ10AYM 380 – 9.7
50 400 342 456 – 9.2
RXQ10AY14 21.2 25.8 25 0.55 1.4
415 – 8.9
RXQ10AY1S 60 380 342 418 – 9.7
RXQ12AYM 380 – 13.2
50 400 342 456 – 12.6
RXQ12AY14 22.5 25.8 25 0.55 1.6
415 – 12.1
RXQ12AY1S 60 380 342 418 – 13.2
7. Electric Characteristics

RXQ14AYM 380 – 14.4


50 400 342 456 – 13.7
RXQ14AY14 26.9 28.5 30 0.75x2 1.1+1.2
415 – 13.2
RXQ14AY1S 60 380 342 418 – 14.4
RXQ16AYM 380 – 9.5 + 9.5
50 400 342 456 – 9.0 + 9.0
RXQ16AY14 30.2 37.4 35 0.75x2 1.1+1.2
415 – 8.7 + 8.7
RXQ16AY1S 60 380 342 418 – 9.5 + 9.5
RXQ18AYM 380 – 11.8 + 11.8
50 400 342 456 – 11.2 + 11.2
RXQ18AY14 30.2 37.4 35 0.75x2 1.1+1.2
415 – 10.8 + 10.8
RXQ18AY1S 60 380 342 418 – 11.8 + 11.8
RXQ20AYM 380 – 9.9 + 16.5
50 400 342 456 – 9.4 + 15.6
RXQ20AY14 38.9 48.2 45 0.75x2 1.4+1.9
415 – 9.1 + 15.1
RXQ20AY1S 60 380 342 418 – 9.9 + 16.5
Symbols : Notes :
MCA : Min. Circuit Amps. (A) 1. RLA is based on the following conditions.
TOCA : Total Over-current Amps. (A) Indoor temp. 27°CDB / 19°CWB
MFA : Max. Fuse Amps. (A) Outdoor temp. 35°CDB
MSC : Max. Starting current
RLA : Rated Load Amps. (A) 2. TOCA means the total value of each OC set.
OFM : Outdoor Fan motor 3. MSC means the Max. current during the starting of compressor.
FLA : Full load Amps. (A) 4. Voltage range
kW : Rated Motor Output (kW) Units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits.
5. Maximum allowable voltage variation between phases is 2%.
RXQ6AY14 / RXQ8AY14 / RXQ10AY14 / RXQ12AY14 / RXQ14AY14 / RXQ16AY14 / RXQ18AY14 /

6. Select wire size based on the value of MCA.


RXQ6AY1S / RXQ8AY1S / RXQ10AY1S / RXQ12AY1S / RXQ14AY1S / RXQ16AY1S / RXQ18AY1S /

7. MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker).
8. For Thailand and Indonesia, the power supply is 50 Hz.

C: 3D111598
RXQ6AYM / RXQ8AYM / RXQ10AYM / RXQ12AYM / RXQ14AYM / RXQ16AYM / RXQ18AYM / RXQ20AYM

87
Electric Characteristics

3
88
Model name Units Power supply Compressor OFM
Combination unit Independent Unit Hz Volts Min. Max. MCA TOCA MFA MSC RLA kW FLA
380 – 7.4 + 9.7
RXQ18AMYM RXQ8AYM RXQ10AYM
50 400 342 456 – 7.0 + 9.2
RXQ18AMY14 RXQ8AY14 RXQ10AY14 30.2 44.3 35 0.55 x 2 1.4 + 1.4
415 – 6.8 + 8.9
RXQ18AMY1S RXQ8AY1S RXQ10AY1S
60 380 342 418 – 7.4 + 9.7
Electric Characteristics

380 – 7.4 + 13.2


RXQ20AMYM RXQ8AYM RXQ12AYM
50 400 342 456 – 7.0 + 12.6
RXQ20AMY14 RXQ8AY14 RXQ12AY14 38.9 44.3 45 0.55 x 2 1.4 + 1.6
415 – 6.8 + 12.1
RXQ20AMY1S RXQ8AY1S RXQ12AY1S
60 380 342 418 – 7.4 + 13.2
RXQ30AMYM / RXQ32AMYM

380 – 9.7 + 13.2


RXQ30AMY14 / RXQ32AMY14

RXQ30AMY1S / RXQ32AMY1S

RXQ22AMYM RXQ10AYM RXQ12AYM


50 400 342 456 – 9.2 + 12.6
RXQ22AMY14 RXQ10AY14 RXQ12AY14 43.7 51.6 50 0.55 x 2 1.4 + 1.6
415 – 8.9 + 12.1
RXQ22AMY1S RXQ10AY1S RXQ12AY1S
60 380 342 418 – 9.7 + 13.2
380 – 13.2 x 2
RXQ24AMYM RXQ12AYM RXQ12AYM
50 400 342 456 – 12.6 x 2
RXQ24AMY14 RXQ12AY14 RXQ12AY14 45.0 51.6 50 0.55 x 2 1.6 x 2
415 – 12.1x 2
RXQ24AMY1S RXQ12AY1S RXQ12AY1S
60 380 342 418 – 13.2 x 2
380 – 13.2 + 14.4
RXQ26AMYM RXQ12AYM RXQ14AYM
50 400 342 456 – 12.6 + 13.7
RXQ26AMY14 RXQ12AY14 RXQ14AY14 49.4 54.3 60 0.55 + 0.75x2 1.6+(1.1+1.2)
415 – 12.1 + 13.2
RXQ26AMY1S RXQ12AY1S RXQ14AY1S
60 380 342 418 – 13.2 + 14.4
380 – 13.2 + 9.5 + 9.5
RXQ28AMYM RXQ12AYM RXQ16AYM
50 400 342 456 – 12.6 + 9.0 + 9.0
RXQ28AMY14 RXQ12AY14 RXQ16AY14 52.8 63.2 60 0.55 + 0.75x2 1.6+(1.1+1.2)
415 – 12.1 + 8.7 + 8.7
RXQ28AMY1S RXQ12AY1S RXQ16AY1S
60 380 342 418 – 13.2 + 9.5 + 9.5
380 – 13.2 + 11.8 + 11.8
RXQ30AMYM RXQ12AYM RXQ18AYM
50 400 342 456 – 12.6 + 11.2 + 11.2
RXQ30AMY14 RXQ12AY14 RXQ18AY14 52.8 63.2 60 0.55 + 0.75x2 1.6+(1.1+1.2)
415 – 12.1 + 10.8 + 10.8
RXQ30AMY1S RXQ12AY1S RXQ18AY1S
60 380 342 418 – 13.2 + 11.8 + 11.8
380 – 14.4 + 11.8 + 11.8
RXQ32AMYM RXQ14AYM RXQ18AYM
50 400 342 456 – 13.7 + 11.2 + 11.2
RXQ32AMY14 RXQ14AY14 RXQ18AY14 57.1 65.9 70 (0.75x2) x 2 (1.1+1.2) x 2
415 – 13.2 + 10.8 + 10.8
RXQ32AMY1S RXQ14AY1S RXQ18AY1S
60 380 342 418 – 14.4 + 11.8 + 11.8

Symbols : Notes :
MCA : Min. Circuit Amps. (A) 1. RLA is based on the following conditions.
TOCA : Total Over-current Amps. (A) Indoor temp. 27°CDB / 19°CWB
MFA : Max. Fuse Amps. (A) Outdoor temp. 35°CDB
MSC : Max. Starting current
RLA : Rated Load Amps. (A) 2. TOCA means the total value of each OC set.
OFM : Outdoor Fan motor 3. MSC means the Max. current during the starting of compressor.
RXQ18AMYM / RXQ20AMYM / RXQ22AMYM / RXQ24AMYM / RXQ26AMYM / RXQ28AMYM /

FLA : Full load Amps. (A) 4. Voltage range


kW : Rated Motor Output (kW) Units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits.
RXQ18AMY14 / RXQ20AMY14 / RXQ22AMY14 / RXQ24AMY14 / RXQ26AMY14 / RXQ28AMY14 /

5. Maximum allowable voltage variation between phases is 2%.


RXQ18AMY1S / RXQ20AMY1S / RXQ22AMY1S / RXQ24AMY1S / RXQ26AMY1S / RXQ28AMY1S /

6. Select wire size based on the value of MCA.


7. MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker).
8. For Thailand and Indonesia, the power supply is 50 Hz.

C: 3D111599

RXQ-A(M)
EDAMT341716
RXQ-A(M)
EDAMT341716

RXQ46AMYM

RXQ46AMY14

RXQ46AMY1S
Model name Units Power supply Compressor OFM
Combination unit Independent Unit Hz Volts Min. Max. MCA TOCA MFA MSC RLA kW FLA
380 – 9.5 + 9.5 + 11.8 + 11.8
RXQ34AMYM RXQ16AYM RXQ18AYM
50 400 342 456 – 9.0 + 9.0 + 11.2 + 11.2
RXQ34AMY14 RXQ16AY14 RXQ18AY14 60.5 74.8 70 (0.75 x 2) x 2 (1.1 + 1.2) x 2
415 – 8.7 + 8.7 + 10.8 + 10.8
RXQ34AMY1S RXQ16AY1S RXQ18AY1S
60 380 342 418 – 9.5 + 9.5 + 11.8 + 11.8
380 – (11.8 + 11.8) x 2
RXQ36AMYM RXQ18AYM RXQ18AYM
50 400 342 456 – (11.2 + 11.2) x 2
RXQ36AMY14 RXQ18AY14 RXQ18AY14 60.5 74.8 70 (0.75 x 2) x 2 (1.1 + 1.2) x 2
415 – (10.8 + 10.8) x 2
RXQ36AMY1S RXQ18AY1S RXQ18AY1S
60 380 342 418 – (11.8 + 11.8) x 2
380 – 11.8 + 11.8 + 9.9 + 16.5
RXQ38AMYM RXQ18AYM RXQ20AYM
50 400 342 456 – 11.2 + 11.2 + 9.4 + 15.6
RXQ38AMY14 RXQ18AY14 RXQ20AY14 69.1 85.6 80 (0.75 x 2) x 2 1.1 + 1.2 + 1.4 + 1.9
415 – 10.8 + 10.8 + 9.1 + 15.1
RXQ38AMY1S RXQ18AY1S RXQ20AY1S
60 380 342 418 – 11.8 + 11.8 + 9.9 + 16.5
380 – (9.9 + 16.5) x 2
RXQ40AMYM RXQ20AYM RXQ20AYM
50 400 342 456 – (9.4 + 15.6) x 2
RXQ40AMY14 RXQ20AY14 RXQ20AY14 77.7 96.4 90 (0.75 x 2) x 2 (1.4 + 1.9) x 2
415 – (9.1 + 15.1) x 2
RXQ40AMY1S RXQ20AY1S RXQ20AY1S
60 380 342 418 – (9.9 + 16.5) x 2
380 – 13.2 x 2 + 11.8 + 11.8
RXQ42AMYM RXQ12AYM RXQ12AYM RXQ18AYM
50 400 342 456 – 12.6 x 2 + 11.2 + 11.2
RXQ42AMY14 RXQ12AY14 RXQ12AY14 RXQ18AY14 75.3 89.0 90 (0.55) x 2 + 0.75 x 2 (1.6) x 2 + 1.1+1.2
415 – 12.1 x 2 + 10.8 + 10.8
RXQ42AMY1S RXQ12AY1S RXQ12AY1S RXQ18AY1S
60 380 342 418 – 13.2 x 2 + 11.8 + 11.8
380 – 13.2 x 2 + 9.9 + 16.5
RXQ44AMYM RXQ12AYM RXQ12AYM RXQ20AYM
50 400 342 456 – 12.6 x 2 + 9.4 + 15.6
RXQ44AMY14 RXQ12AY14 RXQ12AY14 RXQ20AY14 83.9 99.8 100 (0.55) x 2 + 0.75 x 2 (1.6) x 2 + 1.4+1.9
415 – 12.1 x 2 + 9.1 + 15.1
RXQ44AMY1S RXQ12AY1S RXQ12AY1S RXQ20AY1S
60 380 342 418 – 13.2 x 2 + 9.9 + 16.5
380 – (14.4) x 2 + 11.8 + 11.8
RXQ46AMYM RXQ14AYM RXQ14AYM RXQ18AYM
50 400 342 456 – (13.7) x 2 + 11.2 + 11.2
RXQ46AMY14 RXQ14AY14 RXQ14AY14 RXQ18AY14 84.0 94.4 100 (0.75 x 2) x 2 + 0.75 x 2 (1.1+1.2) x 2 + 1.1+1.2
415 – (13.2) x 2 +10.8 + 10.8
RXQ46AMY1S RXQ14AY1S RXQ14AY1S RXQ18AY1S
60 380 342 418 – (14.4) x 2 + 11.8 + 11.8

Symbols : Notes :
MCA : Min. Circuit Amps. (A) 1. RLA is based on the following conditions.
TOCA : Total Over-current Amps. (A) Indoor temp. 27°CDB / 19°CWB
MFA : Max. Fuse Amps. (A) Outdoor temp. 35°CDB
MSC : Max. Starting current
RLA : Rated Load Amps. (A) 2. TOCA means the total value of each OC set.
OFM : Outdoor Fan motor 3. MSC means the Max. current during the starting of compressor.
FLA : Full load Amps. (A) 4. Voltage range
kW : Rated Motor Output (kW) Units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits.
5. Maximum allowable voltage variation between phases is 2%.
6. Select wire size based on the value of MCA.
RXQ34AMYM / RXQ36AMYM / RXQ38AMYM / RXQ40AMYM / RXQ42AMYM / RXQ44AMYM /

7. MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker).
8. For Thailand and Indonesia, the power supply is 50 Hz.
RXQ34AMY14 / RXQ36AMY14 / RXQ38AMY14 / RXQ40AMY14 / RXQ42AMY14 / RXQ44AMY14 /

RXQ34AMY1S / RXQ36AMY1S / RXQ38AMY1S / RXQ40AMY1S / RXQ42AMY1S / RXQ44AMY1S /

C: 3D111600

89
Electric Characteristics

3
90
RXQ60AMYM

RXQ60AMY14

RXQ60AMY1S
Model name Units Power supply Compressor OFM
Electric Characteristics

Combination unit Independent Unit Hz Volts Min. Max. MCA TOCA MFA MSC RLA kW FLA
380 – 14.4 + 9.5 + 9.5 + 11.8 + 11.8
RXQ48AMYM RXQ14AYM RXQ16AYM RXQ18AYM
50 400 342 456 – 13.7 + 9.0 + 9.0 + 11.2 + 11.2
RXQ48AMY14 RXQ14AY14 RXQ16AY14 RXQ18AY14 87.4 103.3 100 (0.75 x 2) x 3 (1.1 + 1.2) x 3
415 – 13.2 + 8.7 + 8.7 + 10.8 + 10.8
RXQ48AMY1S RXQ14AY1S RXQ16AY1S RXQ18AY1S
60 380 342 418 – 14.4 + 9.5 + 9.5 + 11.8 + 11.8
380 – 14.4 + ( 11.8 + 11.8) x 2
RXQ50AMYM RXQ14AYM RXQ18AYM RXQ18AYM
50 400 342 456 – 13.7 + (11.2 + 11.2) x 2
RXQ50AMY14 RXQ14AY14 RXQ18AY14 RXQ18AY14 87.4 103.3 100 (0.75 x 2) x 3 (1.1 + 1.2) x 3
415 – 13.2 + (10.8 + 10.8) x 2
RXQ50AMY1S RXQ14AY1S RXQ18AY1S RXQ18AY1S
60 380 342 418 – 14.4 + ( 11.8 + 11.8) x 2
380 – 9.5 + 9.5 + (11.8 + 11.8) x 2
RXQ52AMYM RXQ16AYM RXQ18AYM RXQ18AYM
50 400 342 456 – 9.0 + 9.0 + (11.2 + 11.2) x 2
RXQ52AMY14 RXQ16AY14 RXQ18AY14 RXQ18AY14 90.7 112.2 100 (0.75 x 2) x 3 (1.1 + 1.2) x 3
415 – 8.7 + 8.7 + (10.8 + 10.8) x 2
RXQ52AMY1S RXQ16AY1S RXQ18AY1S RXQ18AY1S
60 380 342 418 – 9.5 + 9.5 + (11.8 + 11.8) x 2
380 – (11.8 + 11.8) x 3
RXQ54AMYM RXQ18AYM RXQ18AYM RXQ18AYM
50 400 342 456 – (11.2 + 11.2) x 3
RXQ54AMY14 RXQ18AY14 RXQ18AY14 RXQ18AY14 90.7 112.2 100 (0.75 x 2) x 3 (1.1 + 1.2) x 3
415 – (10.8 + 10.8) x 3
RXQ54AMY1S RXQ18AY1S RXQ18AY1S RXQ18AY1S
60 380 342 418 – (11.8 + 11.8) x 3
380 – (11.8 + 11.8) x 2 + 9.9 + 16.5
RXQ56AMYM RXQ18AYM RXQ18AYM RXQ20AYM
50 400 342 456 – (11.2 + 11.2) x 2 + 9.4 + 15.6
RXQ56AMY14 RXQ18AY14 RXQ18AY14 RXQ20AY14 99.4 123.0 110 (0.75 x 2) x 3 (1.1 + 1.2) x 2 + 1.4 + 1.9
415 – (10.8 + 10.8) x 2 + 9.1 + 15.1
RXQ56AMY1S RXQ18AY1S RXQ18AY1S RXQ20AY1S
60 380 342 418 – (11.8 + 11.8) x 2 + 9.9 + 16.5
380 – 11.8 + 11.8 + (9.9 + 16.5) x 2
RXQ58AMYM RXQ18AYM RXQ20AYM RXQ20AYM
50 400 342 456 – 11.2 + 11.2 + (9.4 + 15.6) x 2
RXQ58AMY14 RXQ18AY14 RXQ20AY14 RXQ20AY14 108.0 133.8 125 (0.75 x 2) x 3 1.1 + 1.2 + (1.4 + 1.9) x 2
415 – 10.8 + 10.8 + (9.1 + 15.1) x 2
RXQ58AMY1S RXQ18AY1S RXQ20AY1S RXQ20AY1S
60 380 342 418 – 11.8 + 11.8 + (9.9 + 16.5) x 2
380 – (9.9 + 16.5) x 3
RXQ60AMYM RXQ20AYM RXQ20AYM RXQ20AYM
50 400 342 456 – (9.4 + 15.6) x 3
RXQ60AMY14 RXQ20AY14 RXQ20AY14 RXQ20AY14 116.6 144.6 150 (0.75 x 2) x 3 (1.4 + 1.9) x 3
415 – (9.1 + 15.1) x 3
RXQ60AMY1S RXQ20AY1S RXQ20AY1S RXQ20AY1S
60 380 342 418 – (9.9 + 16.5) x 3

Symbols : Notes :
MCA : Min. Circuit Amps. (A) 1. RLA is based on the following conditions.
TOCA : Total Over-current Amps. (A) Indoor temp. 27°CDB / 19°CWB
MFA : Max. Fuse Amps. (A) Outdoor temp. 35°CDB
MSC : Max. Starting current
RLA : Rated Load Amps. (A) 2. TOCA means the total value of each OC set.
OFM : Outdoor Fan motor 3. MSC means the Max. current during the starting of compressor.
FLA : Full load Amps. (A) 4. Voltage range
kW : Rated Motor Output (kW) Units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits.
5. Maximum allowable voltage variation between phases is 2%.
6. Select wire size based on the value of MCA.
7. MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker).
RXQ48AMYM / RXQ50AMYM / RXQ52AMYM / RXQ54AMYM / RXQ56AMYM / RXQ58AMYM /

8. For Thailand and Indonesia, the power supply is 50 Hz.


RXQ48AMY14 / RXQ50AMY14 / RXQ52AMY14 / RXQ54AMY14 / RXQ56AMY14 / RXQ58AMY14 /

RXQ48AMY1S / RXQ50AMY1S / RXQ52AMY1S / RXQ54AMY1S / RXQ56AMY1S / RXQ58AMY1S /

C: 3D111601

RXQ-A(M)
EDAMT341716
EDAMT341716 Operation Limits (Reference)

8. Operation Limits (Reference)


RXQ6AYM / RXQ8AYM / RXQ10AYM / RXQ12AYM / RXQ14AYM / RXQ16AYM / RXQ18AYM / RXQ20AYM /
RXQ18AMYM / RXQ20AMYM / RXQ22AMYM / RXQ24AMYM / RXQ26AMYM / RXQ28AMYM / RXQ30AMYM / 3
RXQ32AMYM / RXQ34AMYM / RXQ36AMYM / RXQ38AMYM / RXQ40AMYM / RXQ42AMYM / RXQ44AMYM /
RXQ46AMYM / RXQ48AMYM / RXQ50AMYM / RXQ52AMYM / RXQ54AMYM / RXQ56AMYM / RXQ58AMYM /
RXQ60AMYM
RXQ6AY14 / RXQ8AY14 / RXQ10AY14 / RXQ12AY14 / RXQ14AY14 / RXQ16AY14 / RXQ18AY14 /
RXQ20AY14 / RXQ18AMY14 / RXQ20AMY14 / RXQ22AMY14 / RXQ24AMY14 / RXQ26AMY14 /
RXQ28AMY14 / RXQ30AMY14 / RXQ32AMY14 / RXQ34AMY14 / RXQ36AMY14 / RXQ38AMY14 /
RXQ40AMY14 / RXQ42AMY14 / RXQ44AMY14 / RXQ46AMY14 / RXQ48AMY14 / RXQ50AMY14 /
RXQ52AMY14 / RXQ54AMY14 / RXQ56AMY14 / RXQ58AMY14 / RXQ60AMY14
RXQ6AY1S / RXQ8AY1S / RXQ10AY1S / RXQ12AY1S / RXQ14AY1S / RXQ16AY1S / RXQ18AY1S /
RXQ20AY1S / RXQ18AMY1S / RXQ20AMY1S / RXQ22AMY1S / RXQ24AMY1S / RXQ26AMY1S /
RXQ28AMY1S / RXQ30AMY1S / RXQ32AMY1S / RXQ34AMY1S / RXQ36AMY1S / RXQ38AMY1S /
RXQ40AMY1S / RXQ42AMY1S / RXQ44AMY1S / RXQ46AMY1S / RXQ48AMY1S / RXQ50AMY1S /
RXQ52AMY1S / RXQ54AMY1S / RXQ56AMY1S / RXQ58AMY1S / RXQ60AMY1S

RXQ-A(M) 91
Accessories EDAMT341716

9. Accessories
9.1 Optional Accessories
RXQ6AYM RXQ6AY14 RXQ6AY1S
Optional accessories RXQ8AYM RXQ8AY14 RXQ8AY1S
RXQ10AYM RXQ10AY14 RXQ10AY1S
KHRP26M22H, KHRP26M33H
Distributive REFNET header
(Max. 4 branch) (Max. 8 branch)
Piping
REFNET joint KHRP26A22T, KHRP26A33T
DIII-NET expand adaptor DTA109A51
Option PCB
External control adaptor DTA104A61
3D111833

RXQ12AYM RXQ12AY14 RXQ12AY1S


RXQ14AYM RXQ14AY14 RXQ14AY1S
Optional accessories RXQ16AYM RXQ16AY14 RXQ16AY1S
RXQ18AYM RXQ18AY14 RXQ18AY1S
RXQ20AYM RXQ20AY14 RXQ20AY1S

REFNET header KHRP26M22H, KHRP26M33H, KHRP26M72H


Distributive (Max. 4 branch) (Max. 8 branch) (Max. 8 branch)
Piping
REFNET joint KHRP26A22T, KHRP26A33T, KHRP26A72T
DIII-NET expand adaptor DTA109A51
Option PCB External control adaptor DTA104A61
Option plate for control adaptor 1 — BKS26A
3D111833

RXQ18AMYM RXQ18AMY14 RXQ18AMY1S


Optional accessories RXQ20AMYM RXQ20AMY14 RXQ20AMY1S
RXQ22AMYM RXQ22AMY14 RXQ22AMY1S
KHRP26M22H, KHRP26M33H, KHRP26M72H
Distributive REFNET header (Max. 4 branch) (Max. 8 branch) (Max. 8 branch)
Piping
REFNET joint KHRP26A22T, KHRP26A33T, KHRP26A72T
Outdoor unit multi connection piping kit BHFP22P100
DIII-NET expand adaptor DTA109A51
Option PCB External control adaptor DTA104A61
Option plate for control adaptor 1 BKS26A
3D111833

RXQ24AMYM RXQ24AMY14 RXQ24AMY1S


RXQ26AMYM RXQ26AMY14 RXQ26AMY1S
RXQ28AMYM RXQ28AMY14 RXQ28AMY1S
RXQ30AMYM RXQ30AMY14 RXQ30AMY1S
Optional accessories RXQ32AMYM RXQ32AMY14 RXQ32AMY1S
RXQ34AMYM RXQ34AMY14 RXQ34AMY1S
RXQ36AMYM RXQ36AMY14 RXQ36AMY1S
RXQ38AMYM RXQ38AMY14 RXQ38AMY1S
RXQ40AMYM RXQ40AMY14 RXQ40AMY1S
KHRP26M22H, KHRP26M33H,
(Max. 4 branch) (Max. 8 branch)
Distributive REFNET header KHRP26M72H, KHRP26M73H
Piping (Max. 8 branch) (Max. 8 branch)
REFNET joint KHRP26A22T, KHRP26A33T, KHRP26A72T, KHRP26A73T
Pipe size reducer KHRP26M73TP, KHRP26M73HP
Outdoor unit multi connection piping kit BHFP22P100
DIII-NET expand adaptor DTA109A51
Option PCB External control adaptor DTA104A61
Option plate for control adaptor 1 BKS26A
3D111833

RXQ42AMYM RXQ42AMY14 RXQ42AMY1S


RXQ44AMYM RXQ44AMY14 RXQ44AMY1S
RXQ46AMYM RXQ46AMY14 RXQ46AMY1S
RXQ48AMYM RXQ48AMY14 RXQ48AMY1S
Optional accessories RXQ50AMYM RXQ50AMY14 RXQ50AMY1S
RXQ52AMYM RXQ52AMY14 RXQ52AMY1S
RXQ54AMYM RXQ54AMY14 RXQ54AMY1S
RXQ56AMYM RXQ56AMY14 RXQ56AMY1S
RXQ58AMYM RXQ58AMY14 RXQ58AMY1S
RXQ60AMYM RXQ60AMY14 RXQ60AMY1S
KHRP26M22H, KHRP26M33H, KHRP26M72H, KHRP26M73H
Distributive REFNET header
(Max. 4 branch) (Max. 8 branch) (Max. 8 branch) (Max. 8 branch)
Piping
REFNET joint KHRP26A22T, KHRP26A33T, KHRP26A72T, KHRP26A73T
Pipe size reducer KHRP26M73TP, KHRP26M73HP
Outdoor unit multi connection piping kit BHFP22P151
DIII-NET expand adaptor DTA109A51
Option PCB External control adaptor DTA104A61
Option plate for control adaptor 1 BKS26A
3D111833
1. This option is just for large casing, incase there are large casing used for outdoor multi combination. Neccessary to adopt
this option part.

92 RXQ-A(M)
Warning Ask a qualified installer or contractor to install this product. Do not try to install the product yourself.
Improper installation can result in water or refrigerant leakage, electrical shock, fire or explosion.
Use only those parts and accessories supplied or specified by Daikin. Ask a qualified installer or
contractor to install those parts and accessories. Use of unauthorised parts and accessories or
improper installation of parts and accessories can result in water or refrigerant leakage, electrical
shock, fire or explosion.
Read the user's manual carefully before using this product. The user's manual provides important
safety instructions and warnings. Be sure to follow these instructions and warnings.
If you have any enquiries, please contact your local importer, distributor and/or retailer.

Cautions on product corrosion


1. Air conditioners should not be installed in areas where corrosive gases, such as acid gas or alkaline gas, are produced.
2. If the outdoor unit is to be installed close to the sea shore, direct exposure to the sea breeze should be avoided. If you need to install
the outdoor unit close to the sea shore, contact your local distributor.

Specifications, designs and other content appearing in this brochure are current as of August 2017 but subject to change without notice.

c All rights reserved

AK

Potrebbero piacerti anche