2 GEGridSolutions.com
UR & URPlus Family
Family Overview
Transmission & Distribution (Continued) Industrial & Network
F60 T35 M60
Feeder Protection with Hi-Z Fault Detection Basic Transformer Protection, Multiple CTs Motor Protection
The F60 provides comprehensive feeder The T35 is a basic transformer protection The M60 offers comprehensive protection and
protection, control, advanced communications, system capable of protecting combined main control solutions for large-sized three-phase
monitoring and metering in an integrated, power transformers and up to five feeders motors. The M60 provides superior protection,
economical, and compact package and more. downstream. The T35 provides automatic or control, and diagnostics that includes thermal
user-definable magnitude reference winding model with RTD and current unbalance biasing,
F35 selection for CT ratio matching, automatic stator differential, reverse and low forward
phase shift compensation and allows users to power, external RRTD module, two-speed
Multiple Feeder Protection
enable removal of the zero-sequence current motors, reduced voltage starting, broken rotor
The F35 is a cost-effective device for primary even for delta connected transformer windings. bar detection, and more.
feeder protection. F35’s modular design allows
customers to protect groups of feeders as C90Plus N60
follows: independent current and voltage inputs,
Breaker Automation and Controller Network Stability and Synchrophasor
independent current and common voltage
Measurement
inputs or independent current inputs only. The C90 Plus is a powerful logic controller
designed to be used in substation environments The N60 is intended to be used on load shedding,
C70 and for the unique automation requirements remedial action, special protection and wide
of industrial and utility power systems. The area monitoring and control schemes. Like no
Capacitor Bank Protection
C90Plus provides unmatched logic processing one device before, the N60 shares real-time
The C70 is an integrated protection, control, and ability combined with a powerful math engine operational data to remote N60s so the system
monitoring device for shunt capacitor banks. with deterministic execution of logic equations can generate intelligent decisions to maintain
The current and voltage-based protection regardless of the configuration of the number of power system operation.
functions are designed to provide sensitive lines of logic.
protection for grounded, ungrounded single and
parallel capacitor banks and banks with taps. C60
Breaker Controller
T60
The C60 is a substation hardened controller that
Medium to Large Transformers
provides a complete integrated package for the
The T60 is a fully featured transformer protection protection, control, and monitoring of circuit
system suitable for power transformers of any breakers, supporting dual-breaker busbar
size that require current differential function. configurations, such as breaker-and-half or ring
The T60 provides automatic or user-definable bus schemes.
magnitude reference winding selection for CT
ratio matching, and performs automatic phase C30
shift compensation for all types of transformer
I/O Logic Controller
winding connections.
The C30 is designed to perform substation
control logic that can also expand the I/O
capability of protection devices and replace
existing Sequence of Events (SOE) recorders.
GEGridSolutions.com 3
UR & URPlus Family
The UR can be supplied in a variety of Digital I/O in the average protection relay. Each UR can be
configurations and is available as a 19-inch seamlessly integrated with other UR relays for
Up to 96 contact inputs (with utility voltage
rack horizontal mount unit or a reduced size complete system protection and control.
rating up to 250V), and up to 64 contact
(¾) vertical mount unit . The UR consists of
outputs, are available and can be used to
the following modules: power supply, CPU, FlexLogic
monitor and control a wide range of auxiliary
CT/VT input, digital input/output, transducer FlexLogic is the powerful UR-platform
equipment found within a substation or other
input/output , inter-relay communications, programming logic engine that provides the
protection application. Types of digital I/O
communication switch and IEC Process Bus. All ability to create customized protection and
cards include trip-rated Form-A, Form-C, Fast
hardware modules and software options can be control schemes, minimizing the need and
Form-C, latching and Solid State Relay (SSR),
specified at the time of ordering. associated costs of, auxiliary components and
with or without DC voltage, current monitoring
and isolated inputs (with auto burnish feature). wiring. With 1024 lines of FlexLogic, the UR
Protection and Control Mechanically latching outputs can be used to can be programmed to provide the required
develop secure interlocking applications and tripping logic along with custom scheme logic
The UR incorporates the most complete and
replace mechanical switches and lockout relays. for breaker control (including interlocking
unique protection algorithms to provide
Form-A digital outputs have activation speeds with external synchronizers), transfer tripping
unparalleled security and system uptime. The
of less than 4ms and both wet and dry contacts schemes for remote breakers and dynamic
UR selector guide (in the following pages) lists
are supported. setting group changes.
all the protection elements found in each relay.
Solid state output modules with high current Scalable Hardware
To support the protection and control functions
breaking capability, fast tripping and reset time
of the UR, various types and forms of I/O The UR is available with a multitude of I/O
are ideal for direct tripping applications.
are available (specific capabilities are model configurations to suit the most demanding
dependent). Supported I/Os include: application needs. The expandable modular design
Transducer I/O
allows for easy configuration and future upgrades.
CTs and VTs RTDs and DCmA cards are available to monitor
system parameters, such as temperature, • Multiple CT/VT configurations allow for the
Up to 24 analog current transformer (CT) implementation of many different schemes,
vibration, pressure, wind speed, and flow. Analog
and voltage transformer (VT) signals can be including concurrent split-phase and
outputs can be used for hardwired connections
configured to monitor AC power lines. Both 1 differential protection
from the controller to a SCADA system, to a
A and 5 A CTs are supported. Special function
programmable logic controller (PLC), or to other • Flexible, modular high density I/O covering
modules are available including: a CT module
user interface devices (eg. panel display). a broad range of input signals and tripping
with sensitive ground input to provide ground
schemes with trip rated Form-A for high density
fault protection on high-impedance grounded outputs and Trip rated Form A, SSR, Form-C and
systems, and a high-impedance fault detection Advanced Automation mechanically latched relays for normal outputs
module that provides fast and reliable detection
The UR incorporates advanced automation • Inter-relay communications module that
of faults caused by downed conductors.
features including powerful FlexLogic enables the sharing of digital status and
programmable logic, communication, and analog values between UR relays for control,
SCADA capabilities that far surpass what is found fast tripping or teleprotection applications
4 GEGridSolutions.com
UR & URPlus Family
Family Overview
Digital fault recorder summary with the latest information on the events, Control screen for the preconfigured bay with breaker & disconnect control in
faults, transients and disturbances. multiple pages using dedicated pushbuttons in the front panel.
• Types of digital outputs include trip-rated • Fault Reports A special feature of the synchrophasor
Form-A and SSR mechanically latching, and - Powerful summary report of pre-fault and implementation is the ability to apply magnitude
Form-C outputs fault values and phase angle correction on a per-phase basis
• Form-A and SSR outputs available with The very high sampling rate and large amounts for known CT and PT magnitude and phase errors.
optional circuit continuity monitoring and of storage space available for data recording in Selected UR devices can apply a phase correction
current detection to verify continuity and the UR allows for the capture of complex events on each phase of up to ±5° in increments of 0.05°.
health of the associated circuitry and can eliminate the need for installing costly They also provide the ability to adjust for delta-
• IEC 61850 Process Bus delivering advanced stand-alone recording equipment. wye phase angle shifts or polarity reversal in
protection and control capabilities while the synchrophasor reporting of the voltage and
providing significant savings on the total life Advanced Device Health Diagnostics current sequence components.
cost of electrical substations The UR performs comprehensive device health UR devices can stream PMU data through any
• RTDs and DCmA inputs are available to diagnostic tests at startup and continuously of its three Ethernet ports using either IEEE
monitor equipment parameters such as during run-time to test its own major functions C37.118 or IEC 61850-90-5 data formats. When
temperature and pressure and critical hardware. These diagnostic tests streaming PMU data through a single port, a
monitor for conditions that could impact security failover function can automatically switch the
and availability of protection, and present device
Monitoring and Metering status via SCADA communications and front
transmission over another Ethernet port.
The UR includes high accuracy metering panel display. Providing continuous monitoring Selected UR devices also support up to 16 user-
and recording for all AC signals. Voltage, and early detection of possible issues help definable command outputs via the command
current , and power metering are built into improve system uptime. frame defined in the IEEE C37.118 standard.
the relay as a standard feature. Current and
• Comprehensive device health diagnostic PMU recording
voltage parameters are available as total RMS
performed at startup
magnitude, and as fundamental frequency UR devices include high accuracy metering and
magnitude and angle. • Monitors the CT/VT input circuitry to validate
recording for all AC signals. Voltage, current,
the integrity of all signals
frequency, power and energy and demand
Fault and Disturbance Recording • Monitors internal DC voltage levels that metering are built into the relay as a standard
The advanced disturbance and event recording allows for proactive maintenance and feature. Current and voltage parameters are
increased uptime available as total RMS magnitude, and as
features within the UR can significantly reduce
the time needed for postmortem analysis fundamental frequency magnitude and angle.
of power system events and the creation of PMU - Synchrophasors UR devices have 12MB of synchrophasor
regulatory reports. Recording functions include: recording memory with multiple recording and
With the ability of having up to 6 PMU elements
triggering options. The PMU recorder can be
• Sequence of Event (SOE) in one device, UR devices provide simultaneous
triggered by an over/under frequency, over/
- 1024 time stamped events (UR Relays) data streams of up to four different clients.
under voltage, overcurrent, overpower, rate of
- 8192 time stamped events (URPlus)
UR devices exceed the IEEE C37.118 (2011) change of frequency condition, or by a user-
• Oscillography requirements for Total Vector Error (TVE) less specified condition, freely configured through
- Supports IEEE C37.111-1999/2013, IEC than 1% over a range of 40Hz to 70Hz, and are FlexLogic. The PMU status flag shows which of
60255-24 Ed 2.0 COMTRADE standard able to measure and report synchrophasors those functions triggered the PMU recorder.
- 64 digital & up to 40 analog channels over a frequency range from 30Hz to 90Hz with
- Events with up to 45s length little effect on TVE.
• Data Logger and Disturbance Recording
- 16 channels up to 1 sample/cycle/channel
GEGridSolutions.com 5
UR & URPlus Family
6 GEGridSolutions.com
UR & URPlus Family
Interoperability with Embedded IEC 61850 LAN Redundancy issues driving the labor required for protection
Ed. 1 and Ed. 2 Substation LAN redundancy has been traditionally
and control design, construction and testing:
Use the UR with integrated IEC 61850 to lower accomplished by reconfiguring the active network • Every substation is unique, making design and
costs associated with system protection, control topology in case of failure. Regardless of the type drafting a one-off solution for every station
and automation. GE Digital Energy’s leadership of LAN architecture (tree, mesh, etc), reconfiguring • Miles of copper wires need to be pulled,
in IEC 61850 comes from thousands of installed the active LAN requires time to switchover, during spliced and terminated
devices and follows on extensive development which the LAN is unavailable. UR devices deliver
• Time-consuming testing and troubleshooting
experience with UCA 2.0. redundancy as specified by PRP-IEC 62439-3,
of thousands of connections must be
Family Overview
which eliminates the dependency on LAN
• Backup wired signals or replace expensive performed by skilled personnel
reconfiguration and the associated switchover
copper wiring between devices with direct The HardFiber Process Bus System was designed
transfer of data from up to 64 remote device time. The UR becomes a dual attached node
that transmits data packets over both main and to address these challenges and reduce the
using GOOSE messaging.
redundant networks simultaneously, so in case overall labor associated with the tasks of
• Configure GE systems based on IEC 61850 designing, documenting, installing and testing
of failure, one of the data packets will reach the
and also monitor and troubleshoot them in protection and control systems. By specifically
receiving device with no time delay.
real-time with EnerVista Viewpoint Engineer targeting copper wiring and all of the labor it
• Multicast IEEE C37.118 synchrophasor Direct I/O Messaging requires, the HardFiber Process Bus System
data between PMU and PDC devices using allows for greater utilization and optimization of
Direct I/O allows for the sharing of analog or
IEC 61850-90-5 resources with the ultimate goal of reducing the
high-speed digital information between multiple
• R-GOOSE enable customer to send GOOSE total life cost (TLC) for protection and control.
UR relays via direct back-to-back connections or
messages beyond the substation, which multiplexed through a standard DS0 multiplexer
enables WAPC and more cost effective channel bank. Regardless of the connection Cyber Security - CyberSentry UR
communication architectures for wide area
method, direct I/O provides continuous
applications CyberSentry enables UR devices to deliver full
real-time channel monitoring that supplies
cyber security features that help customers to
• Implements, user selectable, Ed. 1 and Ed. 2 diagnostics information on channel health.
comply with NERC CIP and NIST® IR 7628 cyber
of the standard across the entire UR Family Direct I/O provides superior relay-to-relay
security requirements through supporting the
communications that can be used in advanced
following core features:
interlocking, generation rejection and other
special protection schemes. Password Complexity
• Communication with up to 16 UR relays Supporting up to 20 alpha- numeric or special
in single or redundant rings rather than characters, UR passwords exceed NERC
strictly limited to simplistic point-to-point CIP requirements for password complexity.
configurations between two devices Individual passwords per role are available.
• Connect to standard DS0 channel banks
through standard RS422, G.703 or IEEE AAA Server Support (Radius)
C37.94 interfaces or via direct fiber optic Enables integration with centrally managed
connections authentication and accounting of all user
• No external or handheld tester required to activities and uses modern industry best
provide channel diagnostic information practices and standards that meet and exceed
NERC CIP requirements for authentication and
Multi-Language password management.
UR devices support multiple languages: English,
French, Russian, Chinese, Turkish, German, Role Based Access Control (RBAC)
Polish and Japanese. These language options Efficiently administrate users and roles within
are available on the front panel, in the EnerVista UR devices. The new and advanced access
setup software, and in the product manuals. functions allow users to configure up to eight
Easily switch between English and an additional roles for up to eight configurable users with
language on the local displays without independent passwords. The standard “Remote
uploading new firmware. Authentication Dial In User Service” (Radius) is
used for authentication.
HardFiber IEC 61850 Process Bus
Event Recorder (Syslog for SEM)
The HardFiber Process Bus System represents
a true breakthrough in the installation and Capture all cyber security related events within
ownership of protection and control systems, a SOE element (login, logout, invalid password
by reducing the overall labor required for attempts, remote/local access, user in session,
IEC 61850 protocol enables high-speed trip and substation design, construction, and testing. settings change, FW update, etc), and then
control via the substation LAN without complex
This innovative solution addresses the three key serve and classify data by security level using
fixed wiring to many auxiliary devices.
GEGridSolutions.com 7
UR & URPlus Family
standard Syslog data format . This enables Viewpoint Monitoring • Device Health Report
UR devices to integrate with established SEM • Single-Click Fault Data Retreival
Viewpoint Monitoring is a simple-to-use and
(Security Event Management) systems.
full-featured monitoring and data recording
EnerVista Integrator
software package for small systems. Similar
EnerVista Software to small SCADA systems, Viewpoint Monitoring EnerVista Integrator is a toolkit that allows
provides a complete HMI package with the seamless integration of Multilin devices into
The EnerVista suite is an industry-leading set
following functionality: new or existing automation systems. Included in
of software programs that simplifies every
EnerVista Integrator is:
Family Overview
aspect of using the UR. The EnerVista suite • Plug-&-Play Device Monitoring
provides all the tools to monitor the status of • OPC/DDE Server
• System Single-Line Monitoring & Control
the protected asset, maintain the relay, and • GE Multilin Drivers
• Annunciator Alarm Screens
integrate information measured by the UR into
• Automatic Event Retrieval
DCS or SCADA monitoring systems. Convenient • Trending Reports
COMTRADE and SOE viewers are an integral part • Automatic Waveform Retrieval
• Automatic Event Retrieval
of the UR setup software included with every UR • Automatic Waveform Retrieval
relay, to carry out postmortem event analysis User Interface
and ensure proper protection system operation. Viewpoint UR Engineer The UR front panel provides extensive local
Viewpoint UR Engineer is a set of powerful HMI capabilities. The local display is used for
EnerVista Launchpad
tools that allows the configuration and testing monitoring, status messaging, fault diagnosis,
EnerVista Launchpad is a powerful software of GE relays at a system level in an easy-to- and device configuration. User-configurable
package that provides users with all of the use graphical drag-and-drop environment . messages that combine text with live data can
setup and support tools needed for configuring Viewpoint UR Engineer provides the following be displayed when user-defined conditions are
and maintaining GE Multilin products. The configuration and commissioning utilities: met. Configurable LEDs allows status and alarm
setup software within Launchpad allows for signaling (50 LEDs).
• Graphical Logic Designer (Substation)
the configuration of devices in real-time by
communicating using serial, Ethernet , or • Graphical System Designer The URPlus and UR optionally has a color graphic
modem connections, or offline by creating HMI that allows users to have customizable bay
• Graphical Logic Monitor
setting files to be sent to devices at a later time. diagrams with local monitoring of status, values
• Graphical System Monitor (Substation) and control functionality.
Included in Launchpad is a document archiving • IEC 61850 Configurator
and management system that ensures critical The alarm annunciator panel provides the
documentation is up-to-date and available when Viewpoint Maintenance configuration of up to 96 (UR) or 256 signals (URPlus)
needed. Documents made available include: (alarms and status) with full text description.
Viewpoint Maintenance provides tools that
• Manuals • Brochures will create reports on the operating status of A 7” color, graphic HMI is optionally available that
the relay, simplify the steps to download fault allows users to have customizable bay diagrams
• Application Notes • Wiring Diagrams
and event data, and reduce the work required with local monitoring of status, values and control
and Support • FAQ’s for cyber security compliance audits. Tools functionality. The alarm annunciator panel
Documents
• Service Bulletins available in Viewpoint Maintenance include: provides the configuration of up to 96 signals
• Guideform (alarms and status) with full text description.
Specifications • Settings Security Audit Report
Record the operation of the internal UR elements and external connected Analyze faults and disturbances using both analog and digital power
devices with 1ms time-stamped accuracy to identify the Sequence of system quantities.
Operation of station devices during faults and disturbances.
8 GEGridSolutions.com
UR & URPlus Family
Family Overview
High-speed local data synchrophasors over Ethernet
• Event record pages with dynamic updates
Transfer
15 14 13 11
SIZE DRAWING NO. REV SHEET
D GE Root Number A1 1
GE PROPRIETARY AND CONFIDENTIAL INFORMATION
REVISIONS
This document is the property of General Electric Company ("GE") and contains
proprietary information of GE. This document is loaned on the express condition
that neither it nor the information contained therein shall be disclosed to REV. DATE ECO# DWN APP DESCRIPTION
others without the express written consent of GE, and that the information shall
be used by the recipient only as approved expressly by GE. This document shall
Advanced Automation Controller 10 side screen pushbuttons 5 below screen tab and Menu navigation keys
be returned to GE upon its request. This document may be subject to certain
restrictions under U.S. export control laws and regulations.
© General Electric Company, GE CONFIDENTIAL UNPUBLISHED WORK
• Built-in programmable logic engine for bay control and additional 1 home pushbutton for
10 soft user programmable page recall
• Boolean and control operations pushbuttons D
[246,05]
9.687
[281,76]
11.093
UR Horizontal Dimensions
18 17 16 15 14 13 11
SIZE DRAWING NO. REV SHEET
D GE Root Number A1 1
GE PROPRIETARY AND CONFIDENTIAL INFORMATION
REVISIONS
This document is the property of General Electric Company ("GE") and contains
proprietary information of GE. This document is loaned on the express condition
that neither it nor the information contained therein shall be disclosed to REV. DATE ECO# DWN APP DESCRIPTION
C
others without the express written consent of GE, and that the information shall
be used by the recipient only as approved expressly by GE. This document shall
be returned to GE upon its request. This document may be subject to certain
restrictions under U.S. export control laws and regulations.
© General Electric Company, GE CONFIDENTIAL UNPUBLISHED WORK
D
D
[246,05]
9.687
B
[281,76]
11.093
[176,78]
6.960
C
C
18.974
[481,94]
SIGNATURES DATE
Grid Solutions
MODEL
Multilin
. .
DIMENSIONS ARE IN INCHES
DETAIL 650 MARKLAND ST. TEL: +1 905 927 7070 FAX: +1 905 927 5098
UNLESS OTHERWISE . .
MARKHAM, ON, CANADA L6C 0M1 INTERNET: http://www.gegridsolutions.com/multilin/
SPECIFIED IN DRAWING CHECKED
. .
TOLERANCE ON:
1 PL DECIMALS
2 PL DECIMALS
0.1
0.01
.
B
3 PL DECIMALS
ANGLES 1.0
0.005
WHERE USED:
.
SIZE DRAWING REV
FRACTIONS
FINISH
.
.
UR, Manual, Assy Pic.
DRAWING FILE: 862700 D GE Root Number A1 B
TITLE DWG No. FILE LOCATION: X:\DRAFTING\ProE Models\UR\UR_chassis2014\new_front_panel
CRITICAL TO QUALITY
SCALE: 0.750 PART No: . SHEET 1 OF 1
REFERENCE DRAWINGS CHARACTERISTIC SOFTWARE TOOL: Pro/ENGINEER
15 14 13 12 11
[177,67]
[176,78]
6.995
6.960
18.974
[481,94]
A
GEGridSolutions.com DIMENSIONS ARE IN INCHES
MODEL
SIGNATURES
.
DATE
.
Grid Solutions
Multilin
9
DETAIL 650 MARKLAND ST. TEL: +1 905 927 7070 FAX: +1 905 927 5098
UNLESS OTHERWISE . .
MARKHAM, ON, CANADA L6C 0M1 INTERNET: http://www.gegridsolutions.com/multilin/
SPECIFIED IN DRAWING CHECKED
. .
TOLERANCE ON:
1 PL DECIMALS
2 PL DECIMALS
0.1
0.01
.
3 PL DECIMALS
ANGLES 1.0
0.005
WHERE USED:
.
THIRD ANGLE PROJECTION
SIZE DRAWING REV
FRACTIONS . UR, Manual, Assy Pic.
FINISH . DRAWING FILE: 862700 GE Root Number A1
UR & URPlus Family
URPlus Front Panel with Large Color Display and Annunciator Panel
• Eliminates the need for separate • Local control and status indication of breakers • Local control and status indication of breakers
& disconnect switches & disconnect switches
annunciator
• Local/remote control • Local/remote control
(20 programmable buttons)
• Fault, event, disturbance and transient reports
Family Overview
URPlus Dimensions
9.80”
7.50” (249)
11.43”
(190) (290)
18.31” (465)
18.86” (479)
4 x 0.28” Dia
(7.1)
18.37” (466.6)
10 GEGridSolutions.com
7.13” 4.00”
(81.1) (101.6)
UR & URPlus Family
Secure Locking
Family Overview
Bright, Easy Labeling, LED Annunciator
UR Vertical Dimensions
7.482” 7.482”
(190) (190) 11.015” 11.015”
(279.781)
1.329” (279.781)
1.329”
(33.76) (33.76)
4.00” 4.00”
(101.6) (101.6) 9.780” 9.780”
(248.4) (248.4)
GEGridSolutions.com 11
UR & URPlus Family
UR Family
Selector Guide
Features ANSI B30 B90 B95Plus C30 C60 C70 C90Plus D30 D60 D90Plus
Protection
Family Overview
Disturbance Detector • • • • •
Mho Distance, Phase (No. of Zones) 21P 5 5 5
Mho Distance, Ground or Neutral Phase (No. of Zones) 21G/N 5 5 5
Quadrilateral Distance, Phase (No. of Zones) 21P 5 5 5
Quadrilateral Distance, Ground or Neutral (No. of Zones) 21G/N 5 5 5
Permissive Pilot Logic • •
Sub-Cycle Distance •
Overexcitation Protection (V/Hz) 24
Synchronism Check or Synchronizing 25 • • • • •
Undervoltage, Phase 27P • • • • • • • • •
Undervoltage, Auxiliary 27X • • • • •
Stator Ground (3rd Harmonic) 27TN
Sensitive Directional Power 32S • •
Loss of Excitation – Based on Reactive Power 40Q
Loss of Excitation – Based on Impedance Element 40
Current Unbalance 46
Broken Conductor Detection 46BC
IOC, Negative Sequence 46/50 • • • • •
TOC, Negative Sequence 46/51 • • • • •
Current Directional, Negative Sequence 46/67 • • • • •
Reverse Phase Sequence Voltage 47 •
Thermal Model 49
Inadvertent/Accidental Energization 50/27
End of Fault Protection • • •
Motor Mechanical Jam
Motor Start Supervision
Motor Acceleration Time
User Programmable Curves • • • • • • •
Breaker Failure 50BF • • • • • • Logic • •
IOC, Phase 50P • • • • • • • • •
IOC, Ground 50G • • • • • • •
IOC, Neutral 50N • • • • • • •
IOC, Sensitive Ground 50SG • • • •
High Impedance Fault Detection
TOC, Phase 51P • • • • • • • • •
TOC, Ground 51G • • • • • • •
TOC, Neutral 51N • • • • • • •
TOC, Sensitive Ground 51SG • • • •
TOC, Voltage Restrained 51V • • • • • • •
Overvoltage, Phase 59P • • • • •
Overvoltage, Auxiliary 59A • • • • • • •
Overvoltage, Neutral 59N • • • • • • •
Negative Sequence Overvoltage 59-2 • • • • •
100% Stator Ground Protection 64TN
Current Directional, Phase 67P • • • •
Current Directional, Neutral 67N • • • •
Current Directional, Negative Sequence 46/67 • • • •
Power Swing Blocking 68 • • •
Out-of-Step Tripping 78 • • •
AC Reclosing (No. of Shots) 79 4 4 4 4 •
Switch on to Fault (Line Pickup) SOTF • • •
Voltage Transformer Fuse Failure VTFF • • • • • •
Current Transformer Supervision 50/74 • • •
Load Encroachment Logic • • •
Underfrequency 81U • • •
Overfrequency 810 • • •
Anti-Islanding Protection/Frequency Rate of Change 81R • •
Lockout Functionality 86 • • • • • • • • • •
Bus Differential 87B 2 2 2
Line Current Differential 87L
Ground Differential 87G
Stator Differential 87S
Transformer Differential 87T
Line Phase Comparison 87PC
Voltage Differential •
Capacitor Bank Overvoltage •
Neutral Voltage Unbalance •
Automatic Voltage Regulation •
Time of Day Control •
Instantaneous Differential 50/87 • • •
Split Phase Protection
Line Current Differential Trip Logic
CT Failure • •
12 GEGridSolutions.com
UR & URPlus Family
Features F35 F60 G30 G60 L30 L60 L90 M60 N60 T35 T60
Protection
Family Overview
Disturbance Detector • • • • •
Mho Distance, Phase (No. of Zones) 3 3 5 5
Mho Distance, Ground or Neutral Phase (No. of Zones) 3 3 5
Quadrilateral Distance, Phase (No. of Zones) 3 3 5
Quadrilateral Distance, Ground or Neutral (No. of Zones) 3 3 5
Permissive Pilot Logic •
Sub-Cycle Distance
Overexcitation Protection (V/Hz) • • •
Synchronism Check or Synchronizing • • • • • • • •
Undervoltage, Phase • • • • • • • • • •
Undervoltage, Auxiliary • • • • • • • • •
Stator Ground (3rd Harmonic) • •
Sensitive Directional Power • • • • •
Loss of Excitation – Based on Reactive Power • • •
Loss of Excitation – Based on Impedance Element • •
Current Unbalance • • •
Broken Conductor Detection •
IOC, Negative Sequence • • • •
TOC, Negative Sequence • • • •
Current Directional, Negative Sequence • • • • •
Reverse Phase Sequence Voltage •
Thermal Model • • •
Inadvertent/Accidental Energization • •
End of Fault Protection
Motor Mechanical Jam •
Motor Start Supervision •
Motor Acceleration Time •
User Programmable Curves • • • • • • • • • • •
Breaker Failure Logic • Logic • • • • • Logic Logic Logic
IOC, Phase • • • • • • • • • •
IOC, Ground • • • • • • • • •
IOC, Neutral • • • • • • • • •
IOC, Sensitive Ground • • • • • • • • •
High Impedance Fault Detection •
TOC, Phase • • • • • • • • • •
TOC, Ground • • • • • • • • • •
TOC, Neutral • • • • • • • • •
TOC, Sensitive Ground • • • • • • • • •
TOC, Voltage Restrained • • • • • • • • •
Overvoltage, Phase • • • • • • • • •
Overvoltage, Auxiliary • • • • • • • • •
Overvoltage, Neutral • • • • • • • • •
Negative Sequence Overvoltage • • • •
100% Stator Ground Protection •
Current Directional, Phase • • • • • • •
Current Directional, Neutral • • • • • • •
Current Directional, Negative Sequence • • • • •
Power Swing Blocking • • • • •
Out-of-Step Tripping • • • • •
AC Reclosing (No. of Shots) 4 4 4 4 4
Switch on to Fault (Line Pickup) • •
Voltage Transformer Fuse Failure • • • • • • • • • •
Current Transformer Supervision • • •
Load Encroachment Logic • • • •
Underfrequency • • • • • • •
Overfrequency • • • • •
Anti-Islanding Protection/Frequency Rate of Change • • • • • •
Lockout Functionality • • • • • • • • • •
Bus Differential
Line Current Differential • •
Ground Differential • • • • • •
Stator Differential • • •
Transformer Differential • • •
Line Phase Comparison •
Voltage Differential
Capacitor Bank Overvoltage
Neutral Voltage Unbalance
Automatic Voltage Regulation
Time of Day Control
Instantaneous Differential • •
Split Phase Protection • •
Line Current Differential Trip Logic •
CT Failure • • • • • • • •
GEGridSolutions.com 13
UR & URPlus Family
UR Technical Specifications
PROTECTION PROTECTION PROTECTION
100% STATOR GROUND BREAKER FAILURE Timing accuracy: ±3% or 4 ms, whichever is greater
Operating quantity: V_neutral_3rd/(V_neutral_3rd + Mode: 1-pole, 3-pole Current supervision:
V_zero_3rd) Current supervision: phase, neutral current Level: neutral current (3I_0)
Pickup level: 0.000 to 0.250 pu in steps of 0.001 Current supv. 0.02 to 30.000 pu in steps of 0.001 Pickup: 0.050 to 30.000 pu in steps of 0.001
Dropout level: 97 to 98% of pickup pickup: Dropout: 97 to 98%
Level accuracy: ±2% of reading from 1 to 120 V Current supv. 97 to 98% of pickup Memory duration: 5 to 25 cycles in steps of 1
Pickup delay: 0 to 600.00 s in steps of 0.01 dropout: Voltage supervision 0 to 5.000 pu in steps of 0.001
3rd harmonic 0.0010 to 0.1000 pu in steps of 0.0001 Current supv. accuracy: pickup (series
supervision level: 0.1 to 2.0 × CT ±0.75% of reading or ±2% of rated compensation
Time accuracy: ±3% or ±20 ms, whichever is greater rating: (whichever is greater) applications):
above 2 × CT rating: ±2.5% of reading Operation time: 1 to 1.5 cycles (typical)
Family Overview
Pickup level: 0.02 to 3.000 pu in steps of 0.001 Level accuracy: ±0.5% or ±0.1% of rated, whichever 29
Level accuracy: ±0.5% of reading from 0.1 to 2.0 × Pickup delay: 0 to 65.535 s in steps of 0.001 26
14 GEGridSolutions.com
UR & URPlus Family
UR Technical Specifications
PROTECTION PROTECTION PROTECTION
MECHANICAL JAM OPEN POLE DETECTOR Memory duration: 5 to 25 cycles in steps of 1
Operating condition: Phase overcurrent Detects an open pole condition, monitoring breaker auxiliary VT location: all delta-wye and wye-delta
Arming condition: Motor not starting contacts, the current in each phase and optional voltages on transformers
Pickup level: 1.00 to 10.00 × FLA in steps of 0.01 the line CT location: all delta-wye and wye-delta
Dropout level: 97 to 98% of pickup Current pickup level: 0.02 to 30.000 pu in steps of 0.001 transformers
Level accuracy: at 0.1 to 2.0 × CT: ±0.5% of reading Line capacitive 300.0 to 9999.9 sec. W in steps of 0.1 Voltage supervision 0 to 5.000 pu in steps of 0.001
at > 2.0 × CT rating: ±1.5% of reading reactances (XC1, pickup (series
Pickup delay: 0.10 to 600.00 s in steps of 0.01 XC0): compensation
Reset delay: 0.00 to 600.00 s in steps of 0.01 Remote current 0.02 to 30.000 pu in steps of 0.001 applications):
Time accuracy: ±3% or ±20 ms, whichever is greater pickup level: PHASE DISTANCE OPERATING TIME CURVES
MOTOR START SUPERVISION Current dropout Pickup + 3%, not less than 0.05 pu The operating times are response times of a microprocessor
Family Overview
Maximum no. of 1 to 16 in steps of 1 level: part of the relay. See output contacts specifications for
starts: OVERFREQUENCY estimation of the total response time for a particular
Monitored time 1 to 300 minutes in steps of 1 Pickup level: 20.00 to 65.00 Hz in steps of 0.01 application. The operating times are average times including
interval: Dropout level: Pickup - 0.03 Hz variables such as fault inception angle or type of a voltage
Time between starts: 0 to 300 minutes in steps of 1 Level accuracy: ±0.01 Hz source (magnetic VTs and CVTs).
Restart delay: 0 to 50000seconds in steps of 1 Time delay: 0 to 65.535 s in steps of 0.001 30
NEGATIVE SEQUENCE DIRECTIONAL OC Timer accuracy: ±3% or 4 ms, whichever is greater 29
Restraint, K: 0.000 to 0.500 in steps of 0.001 I2 x Z - V2: 0.005 to 15.00 pu in steps of 0.01 18
SIR=20
Characteristic angle: 0 to 90° in steps of 1 dI2 / dt: 0.01 to 5.00 pu in steps of 0.01 17 SIR=30
SIR=60
dI1 / dt: 0.01 to 5.00 pu in steps of 0.01
16
Limit angle: 40 to 90° in steps of 1, independent for 15
Pickup level: 0.05 to 30.00 pu in steps of 0.01 I2 x Z - V2: 0.005 to 15.00 pu in steps of 0.01 10
0 20 40 60 70 80
Dropout level: 97 to 98% dI2 / dt: 0.01 to 5.00 pu in steps of 0.01 Fault Location (%)
Operation time: < 16 ms at 3 × Pickup at 60 Hz dI1 / dt: 0.01 to 5.00 pu in steps of 0.01
NEGATIVE SEQUENCE IOC Signal Symmetry PHASE/NEUTRAL/GROUND IOC
Current: Phasor Adjustment: -0.5 to 5.0 ms in steps of 0.1 Pickup level: 0.02 to 30.000 pu in steps of 0.001
Pickup level: 0.02 to 30.000 pu in steps of 0.001 Channel Delay 0.000 to 30.00 ms in steps of 0.001 Dropout level: 97 to 98% of pickup
Dropout level: 97 to 98% of Pickup Adjustment: Level accuracy:
Level accuracy: Channel channel delay and signal symmetry 0.1 to 2.0 × CT ±0.5% of reading or ±1% of rated
0.1 to 2.0 × CT ±0.5% of reading or ±1% of rated Adjustments: compensation rating: (whichever is greater)
rating: (whichever is greater)> 2.0 × CT rating: Operate Time 3/4 cycle for single phase comparison > 2.0 × CT rating: ±1.5% of reading
±1.5% of reading (Typical): Overreach: <2%
Overreach: < 2% Trip Security: First coincidence or enhanced Pickup delay: 0.00 to 600.00 s in steps of 0.01
Pickup delay: 0.00 to 600.00 s in steps of 0.01 Second Coincidence 10 to 200 ms in steps of 1 Reset delay: 0.00 to 600.00 s in steps of 0.01
Reset delay: 0.00 to 600.00 s in steps of 0.01 Timer: Operate time: <16ms at 3 × pickup at 60Hz (Phase/
Operate time: < 20 ms at 3 × Pickup at 60 Hz Enhanced Stability 40 to 180° in steps of 1 Ground IOC) <20ms at 3 × pickup at
Timing accuracy: Operate at 1.5 × Pickup ±3% or ± 4 ms Angle: 60Hz (Neutral IOC)
(whichever is greater) PHASE DIRECTIONAL OVERCURRENT Timing accuracy: Operate at 1.5 × Pickup ±3% or ±4 ms
NEGATIVE SEQUENCE OVERVOLTAGE Relay connection: 90° (quadrature) (whichever is greater)
Pickup level: 0.004 to 1.250 pu in steps of 0.001 Quadrature voltage: PHASE/NEUTRAL/GROUND TOC
Dropout level: 97 to 98% of Pickup ABC phase seq.: phase A (VBC), phase B (VCA), Current: Phasor or RMS
Level accuracy: ±0.5% of reading from 10 to 208 V phase C (VAB) Pickup level: 0.02 to 30.000 pu in steps of 0.001
Pickup delay: 0 to 600.00 s in steps of 0.01 ACB phase seq.: phase A (VCB), phase B (VAC), Dropout level: 97% to 98% of Pickup
Reset delay: 0 to 600.00 s in steps of 0.01 phase C (VBA) Level accuracy: for 0.1 to 2.0 × CT: ±0.5% of reading
Time accuracy: ±3% or ±20 ms, whichever is greater Polarizing voltage 0.004 to 3.000 pu in steps of 0.001 or ±1% of rated (whichever is greater)
Operate time: < 30 ms at 1.10 × Pickup at 60 Hz threshold: for > 2.0 × CT: ±1.5% of reading > 2.0
NEGATIVE SEQUENCE TOC Current sensitivity 0.05 pu × CT rating
Current: Phasor threshold: Curve shapes: IEEE Moderately/Very/Extremely
Pickup level: 0.02 to 30.000 pu in steps of 0.001 Characteristic angle: 0 to 359° in steps of 1 Inverse; IEC (and BS) A/B/C and Short
Dropout level: 97% to 98% of Pickup Angle accuracy: ±2° Inverse; GE IAC Inverse, Short/Very/
Operation time: (FlexLogic elements): Extremely Inverse; I2t; FlexCurves.
Level accuracy: ±0.5% of reading or ±1% of rated (programmable); Definite Time (0.01 s
(whichever is greater from 0.1 to 2.0 Tripping (reverse < 12 ms, typically
load, forward fault): base curve)
x CT rating ±1.5% of reading > 2.0 x
CT rating Blocking (forward < 8 ms, typically Curve multiplier: Time Dial = 0.00 to 600.00 in steps
load, reverse fault): of 0.01
Curve shapes: IEEE Moderately/Very/Extremely
Inverse; IEC (and BS) A/B/C and Short PHASE DISTANCE Reset type: Instantaneous/Timed (per IEEE)
Inverse; GE IAC Inverse, Short/Very/ Characteristic: Mho (memory polarized or offset) Timing accuracy: Operate at > 1.03 × actual Pickup
Extremely Inverse; I2t; FlexCurves. or Quad (memory polarized or non- ±3.5% of operate time or ±½ cycle
(programmable); Definite Time (0.01 s directional), selectable individually (whichever is greater)
base curve) per zone PHASE OVERVOLTAGE
Curve multiplier 0.00 to 600.00 in steps of 0.01 Number of zones: Up to 5 Voltage: Phasor only
(Time dial): Directionality: Forward, Reverse, or Non-Directional Pickup level: 0.004 to 3.000 pu in steps of 0.001
Reset type: Instantaneous/Timed (per IEEE) and per zone Dropout level: 97 to 98% of Pickup
L ear Reach (secondary W): 0.02 to 250.00 in steps of 0.01 Level accuracy: ±0.5% of reading from 10 to 208V
Timing accuracy: Operate at > 1.03 × Actual Pickup Reach accuracy: ±5% including the effect of CVT Pickup delay: 0.00 to 600.00 in steps of 0.01 s
±3.5% of operate time or ±½ cycle transients up to an SIR of 30 Operate time: < 30 ms at 1.10 × Pickup at 60 Hz
(whichever is greater) Distance: Timing accuracy: ±3% or ±4 ms (whichever is greater)
NEUTRAL DIRECTIONAL OVERCURRENT Characteristic angle: 30 to 90° in steps of 1 PHASE UNDERVOLTAGE
Directionality: Co-existing forward and reverse Comparator limit 30 to 90° in steps of 1 Voltage: Phasor only
Polarizing: Voltage, Current, Dual, Dual-I, Dual-V angle: Pickup level: 0.004 to 3.000 pu in steps of 0.001
Polarizing voltage: V_0 or VX Directional supervision: Dropout level: 102 to 103% of Pickup
Polarizing current: IG Characteristic angle: 30 to 90° in steps of 1 Level accuracy: ±0.5% of reading from 10 to 208V
Operating current: I_0 Limit angle: 30 to 90° in steps of 1 Curve shapes: GE IAV Inverse; Definite Time (0.1s
Level sensing: 3 × (|I_0| - K × |I_1|), IG Right blinder (Quad only): base curve)
Restraint, K: 0.000 to 0.500 in steps of 0.001 Reach: 0.02 to 500 in steps of 0.01 Curve multiplier: Time Dial = 0.00 to 600.00 in steps
Characteristic angle: -90 to 90° in steps of 1 Characteristic angle: 60 to 90° in steps of 1 of 0.01
Limit angle: 40 to 90° in steps of 1, independent for Left Blinder (Quad only): Timing accuracy: Operate at < 0.90 × Pickup ±3.5% of
forward and reverse Reach: 0.02 to 500 in steps of 0.01 operate time or ±4 ms (whichever is
Angle accuracy: ±2° Characteristic angle: 60 to 90° in steps of 1 greater)
Offset impedance: 0.00 to 250.00W in steps of 0.01 Time delay: 0.000 to 65.535 s in steps of 0.001 PILOT-AIDED SCHEMES
Pickup level: 0.05 to 30.00 pu in steps of 0.01 Timing accuracy: ±3% or 4 ms, whichever is greater Direct Underreaching Transfer Trip (DUTT)
Dropout level: 97 to 98% Current supervision: Permissive Underreaching Transfer Trip (PUTT)
Operation time: < 16 ms at 3 × Pickup at 60 Hz Level: line-to-line current Permissive Overreaching Transfer Trip (POTT)
NEUTRAL OVERVOLTAGE Pickup: 0.050 to 30.000 pu in steps of 0.001 Hybrid POTT Scheme
Pickup level: 0.004 to 3.000 pu in steps of 0.001 Dropout: 97 to 98% Directional Comparison Blocking Scheme
Polarizing: Voltage, Current, Dual, Dual-I, Dual-V Customizable version of the POTT and DCB schemes (POTT1
Level accuracy: ±0.5% of reading from 10 to 208 V and DCB1)
Pickup delay: 0.00 to 600.00 s in steps of 0.01
Reset delay: 0.00 to 600.00 s in steps of 0.01
Timing accuracy: ±3% or ±20 ms (whichever is greater)
Operate time: < 30 ms at 1.10 × Pickup at 60 Hz
GEGridSolutions.com 15
UR & URPlus Family
UR Technical Specifications
PROTECTION PROTECTION PROTECTION
POWER SWING DETECT THERMAL MODEL TRIP OUTPUT
Functions: Power swing block, Out-of-step trip Thermal overload Standard curve, FlexCurve, Collects trip and reclose input requests and issues outputs to
Characteristic: Mho or Quad curves: voltage dependent curve control tripping and reclosing.
Measured impedance: Positive-sequence Standard Curve Time 0.00 to 600.00 in steps of 0.01 Communications timer 0 to 65535 s in steps of 0.001
Blocking / tripping 2-step or 3-step Multiplier: delay:
mozes: Thermal Overload pu = overload factor x FLA Evolving fault timer: 0.000 to 65.535 s in steps of 0.001
Tripping mode: Early or Delayed Pickup: Timing accuracy: ±3% or 4 ms, whichever is greater
Current supervision: Overload (OF): 1.00 to 1.50 in steps of 0.001 UNDERFREQUENCY
Pickup level: 0.050 to 30.000 pu in steps of 0.001 Standard Overload Minimum signal: 0.10 to 1.25 pu in steps of 0.01
Dropout level: 97 to 98% of Pickup Curve: Pickup level: 20.00 to 65.00 Hz in steps of 0.01
Fwd / reverse reach 0.10 to 500.00W in steps of 0.01 trip time = Dropout level: Pickup + 0.03 Hz
Family Overview
16 GEGridSolutions.com
UR & URPlus Family
UR Technical Specifications
MONITORING USER-PROGRAMMABLE ELEMENTS INPUTS
PHASOR MEASUREMENT UNIT CONTROL PUSHBUTTONS AC CURRENT
Output format: per IEEE C37.118 standard Number of pushbuttons: 3 (standard), 16 (UR Enhanced CT rated primary: 1 to 50000 A
Number of channels: 14 synchrophasors, 16 analogs, 16 HMI) or 8 plus 10 soft CT rated secondary: 1 A or 5 A by connection
digitals pushbuttons (UR color HMI) Nominal frequency: 20 to 65 Hz
TVE (total vector error): <1% Operation: drive FlexLogic. operands Relay burden: < 0.2 VA at rated secondary
Triggering: frequency, voltage, current, power, FLEXCURVES Conversion range:
rate of change of frequency, user- Number: 4 (A through D) Standard CT: 0.02 to 46 × CT rating RMS
defined Reset points: 40 (0 through 1 of pickup) symmetrical
Reporting rate: 1, 2, 5, 10, 12, 15, 20, 25, 30, 50, 60 or Operate points: 80 (1 through 20 of pickup) Sensitive Ground/HI-Z CT module:
120 times per second Time delay: 0 to 65535 ms in steps of 1 0.002 to 4.6 × CT rating RMS
Number of clients: One over TCP/IP port, two over UDP/ FLEXLOGIC symmetrical
Family Overview
IP ports Programming language: Reverse Polish Notation with Current withstand: 20 ms at 250 times rated
TAC ranges: As indicated in appropriate graphical visualization (keypad 1 sec. at 100 times rated
specifications sections programmable) continuous at 3 times rated
Network reporting 16-bit integer or 32-bit IEEE floating Lines of code: 1024 continuous 4xInom; URs equipped
format: point numbers Internal variables: 64 with 24 CT inputs have a maximum
Network reporting Rectangular (real and imaginary) Supported operations: NOT, XOR, OR (2 to 16 inputs), operating temp. of 50°C
style: or polar (magnitude and angle) AND (2 AC VOLTAGE
coordinates to 16 inputs), NOR (2 to 16 VT rated secondary: 50.0 to 240.0 V
Filtering: P and M class inputs), VT ratio: 1.00 to 24000.00
Calibration: Angle ±5°, magnitude +/-5% per NAND (2 to 16 inputs), Latch Nominal frequency: 20 to 65 Hz For the L90, the nominal
phase (Reset Dominant), Edge system frequency should be chosen as
Compensation: -180 to 180° in steps of 30° (current Detectors, 50 Hz or 60 Hz only.
and voltage components) Timers Relay burden: < 0.25 VA at 120 V
Mode of operation: Normal and test Inputs: any logical variable, contact, or Conversion range: 1 to 275 V
PMU Recording: 46 configurable channels virtual input Voltage withstand: continuous at 260 V to neutral
(14 syncrophasor, 16 digital, Number of timers: 32 1 min./hr at 420 V to neutral
16 analogs) Pickup delay: 0 to 60000 (ms, sec., min.) in CONTACT INPUTS
METERING steps of 1 Dry contacts: 1000 W maximum
RMS CURRENT: PHASE, NEUTRAL, AND GROUND Dropout delay: 0 to 60000 (ms, sec., min.) in Wet contacts: 300 V DC maximum
Accuracy at: steps of 1 Selectable 17 V, 33 V, 84 V, 166 V
0.1 to 2.0 × CT rating: ±0.25% of reading or ±0.1% of rated FLEXELEMENTS thresholds:
(whichever is greater) Number of elements: 8 or 16 Tolerance: ±10%
> 2.0 × CT rating: ±1.0% of reading Operating signal: any analog actual value, or two Contacts Per 4
RMS VOLTAGE values in Differential mode Common Return:
Accuracy: ±0.5% of reading from 10 to 208 V Operating signal mode: Signed or Absolute Value Recognition time: < 1 ms
REAL POWER (WATTS) Operating mode: Level, Delta Debounce timer: 0.0 to 16.0 ms in steps of 0.5
Accuracy: ±1.0% of reading at -0.8 < PF < -1.0 Comparator direction: Over, Under Continuous Current 3mA (when energized)
and 0.8 < PF < 1.0 Pickup Level: -30.000 to 30.000 pu in steps Draw:
REACTIVE POWER (VARS) of 0.001 CONTACT INPUTS WITH AUTO-BURNISHING
Accuracy: ±1.0% of reading at -0.2 < PF < 0.2 Hysteresis: 0.1 to 50.0% in steps of 0.1 Dry contacts: 1000 W maximum
APPARENT POWER (VA) Delta dt: 20 ms to 60 days Wet contacts: 300 V DC maximum
Accuracy: ±1.0% of reading Pickup & dropout delay: 0.000 to 65.535 s in steps of Selectable 17 V, 33 V, 84 V, 166 V
WATT-HOURS (POSITIVE AND NEGATIVE) 0.001 thresholds:
Accuracy: ±2.0% of reading FLEXSTATES Tolerance: ±10%
Range: ±0 to 2 × 109 MWh Number: up to 256 logical variables Contacts Per 2
Parameters: 3-phase only grouped Common Return:
Update rate: 50 ms under 16 Modbus addresses Recognition time: < 1 ms
VAR-HOURS (POSITIVE AND NEGATIVE) Programmability: any logical variable, contact, or Debounce timer: 0.0 to 16.0 ms in steps of 0.5
Accuracy: ±2.0% of reading virtual input Continuous Current 3mA (when energized)
Range: ±0 to 2 × 109 Mvarh LED TEST Draw:
Parameters: 3-phase only Initiation: from any digital input or user- Auto-Burnish Impulse 50 to 70 mA
Update rate: 50 ms programmable condition Current:
CURRENT HARMONICS Number of tests: 3, interruptible at any time Duration of Auto- 25 to 50 ms
Harmonics: 2nd to 25th harmonic: per phase, Duration of full test: approximately 3 minutes Burnish Impulse:
displayed as a % of f1 (fundamental Test sequence 1: all LEDs on DCMA INPUTS
frequency phasor) THD: per phase, Test sequence 2: all LEDs off, one LED at a time Current input (mA 0 to -1, 0 to +1, -1 to +1, 0 to 5, 0 to 10,
displayed as a % of f1 on for 1 s DC): 0 to 20, 4 to 20 (programmable)
Accuracy: Test sequence 3: all LEDs on, one LED at a time Input impedance: 379 ±10%
Harmonics: 1. f1 > 0.4pu: (0.20% + 0.035% / off for 1 s Conversion range: -1 to + 20 mA DC
harmonic) of reading or 0.15% of NON-VOLATILE LATCHES Accuracy: ±0.2% of full scale
100%, whichever is greater Type: Set-dominant or Reset- Type: Passive
2. f1 < 0.4pu: as above plus %error dominant DIRECT INPUTS
of f1 Number: 16 (individually programmed) Number of input 32
THD: 1. f1 > 0.4pu: (0.25% + 0.035% / Output: Stored in non-volatile memory points:
harmonic) of reading or 0.20% of Execution sequence: As input prior to protection, No. of remote 16
100%, whichever is greater control, and FlexLogic. devices:
2. f1 < 0.4pu: as above plus %error SELECTOR SWITCH Default states on On, Off, Latest/Off, Latest/On
of f1 Number of elements: 2 loss of comms.:
DEMAND Upper position limit: 1 to 7 in steps of 1 Ring configuration: Yes, No
Measurements: Phases A, B, and C present and Selecting mode: Time-out or Acknowledge Data rate: 64 or 128 kbps
maximum measured currents Time-out timer: 3.0 to 60.0 s in steps of 0.1 CRC: 32-bit
3-Phase Power (P, Q, and S) present Control inputs: step-up and 3-bit CRC alarm:
and maximum measured currents Power-up mode: restore from non-volatile Responding to: Rate of messages failing the CRC
Accuracy: ±2.0% memory or synchronize to a Monitoring message 10 to 10000 in steps of 1
FREQUENCY 3-bit control input count:
Accuracy at ±0.01 Hz (when voltage signal is used USER-DEFINABLE DISPLAYS Alarm threshold: 1 to 1000 in steps of 1
V = 0.8 to 1.2 pu: for frequency measurement) Number of displays: 16 Unreturned message alarm:
I = 0.1 to 0.25 pu: ±0.05 Hz Lines of display: 2 × 20 alphanumeric characters Responding to: Rate of unreturned messages in the
I > 0.25 pu: ±0.02 Hz (when current signal is used Parameters: up to 5, any Modbus register ring configuration
for frequency measurement) addresses Monitoring message 10 to 10000 in steps of 1
VOLTAGE HARMONICS Invoking and scrolling: keypad, or any user- count:
Harmonics: 2nd to 25th harmonic: per phase, programmable condition, Alarm threshold: 1 to 1000 in steps of 1
displayed as a % of f1 (fundamental including pushbuttons IRIG-B INPUT
frequency phasor) THD: per phase, USER-PROGRAMMABLE LEDS Amplitude 1 to 10 V pk-pk
displayed as a % of f1 Number: 48 plus Trip and Alarm (UR modulation:
Accuracy: Enhanced HMI), 8 plus Trip and DC shift: TTL
Harmonics: 1. f1 > 0.4pu: (0.20% + 0.035% / Alarm (UR Color HMI) Input impedance: 22 kW
harmonic) of reading or 0.15% of Programmability: from any logical variable, Isolation: 2 kV
100%, whichever is greater contact, or virtual input REMOTE INPUTS (IEC 61850 GSSE)
2. f1 < 0.4pu: as above plus %error Reset mode: Self-reset or Latched Number of input 32, configured from 64 incoming bit
of f1 USER-PROGRAMMABLE PUSHBUTTONS (OPTIONAL) points: pairs
THD: 1. f1 > 0.4pu: (0.25% + 0.035% / Number of pushbuttons: 13 (standard), 16 (UR Enhanced Number of remote 16
harmonic) of reading or 0.20% of HMI) or 8 plus 10 soft devices:
100%, whichever is greater pushbuttons (UR color HMI) Default states on On, Off, Latest/Off, Latest/On
2. f1 < 0.4pu: as above plus %error Mode: Self-Reset, Latched loss of comms.:
of f1 Display message: 2 lines of 20 characters each RTD INPUTS
8-BIT SWITCH Types (3-wire): 100 W Platinum, 100 W &
Number of elements: 6 120 W Nickel, 10 W Copper
Input signals: two 8-bit integers via FlexLogic Sensing current: 5 mA
operands Range: -50 to +250°C
Control: any FlexLogic operand Accuracy: ±2°C
Response time: < 8 ms at 60 Hz, < 10 ms at Isolation: 36 V pk-pk
50 Hz
GEGridSolutions.com 17
UR Technical Specifications
OUTPUTS COMMUNICATIONS INTER-RELAY COMMUNICATIONS
CONTROL POWER EXTERNAL OUTPUT RS232 * Note: Typical distances listed are based on the following
(FOR DRY CONTACT INPUT) Front port: 19.2 kbps, Modbus® RTU, DNP 3.0 assumptions for system loss. Actual losses will vary from one
Capacity: 100 mA DC at 48 V DC RS485 installation to another, the distance covered by your system
Isolation: ±300 Vpk 1 or 2 rear ports: Up to 115 kbps, Modbus® RTU, DNP may vary.
DCMA OUTPUTS 3.0 isolated together at 36 Vpk CONNECTOR LOSSES (TOTAL OF BOTH ENDS)
Range: -1 to 1 mA, 0 to 1 mA, 4 to 20 mA Typical distance: 1200 m ST connector 2dB
Max. load resistance: 12 k for -1 to 1 mA range Isolation: 2 kV FIBER LOSSES
12 k for 0 to 1 mA range ETHERNET PORT 820 nm multimode 3 dB/km
600 for 4 to 20 mA range 10Base-F: 820 nm, multi-mode, supports 1300 nm mulimode 1 dB/km
Accuracy: half-duplex/full-duplex fiber optic 1300 nm singlemode 0.35 dB/km
±0.75% of full-scale for 0 to 1 mA with ST connector 1550 nm singlemode 0.25 dB/km
range Redundant 10Base-F: 820 nm, multi-mode, half-duplex/ Splice losses: One splice every 2 km, at 0.05 dB
±0.5% of full-scale for -1 to 1 mA full-duplex fiber optic with ST loss per splice
range connector SYSTEM MARGIN
±0.75% of full-scale for 0 to 20 mA 10Base-T: RJ45 connector 3 dB additional loss added to calculations to compensate for
range Power budget: 10 dB all other losses.
99% Settling time to a 100 ms Max optical input power: -7.6 dBm Compensate difference in transmitting and receiving (channel
step change: Max optical output asymmetry) channel delays using GPS satellite clock: 10 ms
Isolation: 1.5 kV power: -20 dBm
Driving signal: any FlexAnalog quantity Receiver sensitivity: -30 dBm POWER SUPPLY
Upper & lower limit for -90 to 90 pu in steps of 0.001 Typical distance: 1.65 km LOW RANGE
the driving signal: SNTP Clock (redundant) Nominal DC voltage: 24 to 48 V at 3 A
DIRECT OUTPUTS synchronization error: <10 ms (typical) Min/max DC voltage: 20 / 60 V
Output points: 32 PROTOCOLS * NOTE: Low range is DC only.
FORM-A CURRENT MONITOR HIGH RANGE
Threshold current: approx. 80 to 100 mA RS232 RS485 10BaseF 10BaseT 100BaseT
Nominal DC voltage: 125 to 250 V at 0.7 A
FORM-A RELAY IEC 61850 • • • Min/max DC voltage: 88 / 300 V
Make & carry for 0.2s: 30 A as per ANSI C37.90 DNP 3.0 • • • • • Nominal AC voltage: 100 to 240 V at 50/60 Hz, 0.7 A
Carry continuous: 6A Modbus • • • • • Min/max AC voltage: 88 / 265 V at 25 to 100 Hz
Break at L/R of 40 ms: 1 A DC max. at 24 V IEC104 • • • ALL RANGES
0.5 A DC max. at 48 V Volt withstand: 2 × Highest Nominal Voltage for 10 ms
0.3 A DC max. at 125 V EGD • • • Voltage loss hold-up: 50 ms duration at nominal
0.2 A DC max. at 250 V Power consumption: Typical = 15 VA; Max. = 30 VA
Operate time: < 4 ms INTER-RELAY COMMUNICATIONS INTERNAL FUSE
Contact material: Silver alloy SHIELDED TWISTED-PAIR INTERFACE OPTIONS RATINGS
FORM-A VOLTAGE MONITOR INTERFACE TYPE TYPICAL DISTANCE Low range power 8 A / 250 V
Applicable voltage: approx. 15 to 250 V DC RS422 1200m supply:
Trickle current: approx. 1 to 2.5 mA High range power 4 A / 250 V
G.703 100m
supply:
INPUT VOLTAGE IMPEDANCE INTERRUPTING CAPACITY
2W RESISTOR 1W RESISTOR * NOTE: RS422 distance is based on transmitter power and AC: 100 000 A RMS symmetrical
250 V DC 20 K 50K does not take into consideration the clock source provided DC: 10 000 A
by the user. Hold up time: 200 ms
120 V DC 5K 2K
48 V DC 2K 2K LINK POWER BUDGET TYPE TESTS
24 V DC 2K 2K EMITTER, TRANSMIT RECEIVED Electrical fast transient:ANSI/IEEE C37.90.1
POWER BUDGET
FIBER TYPE POWER SENSITIVITY IEC 61000-4-4
FORM-C AND CRITICAL FAILURE RELAY 820nm LED IEC 60255-22-4
Make & carry for 0.2 s: 30 A Multimode -20dBm -30dBm 10dB Oscillatory transient: ANSI/IEEE C37.90.1
Carry continuous: 8A 1300 nm LED IEC 61000-4-12
Break at L/R of 40 ms: 0.25 A DC max. at 48 V -21dBm -30dBm 9dB
Multimode Insulation resistance: IEC 60255-5
0.10 A DC max. at 125 V 1300 nm ELED Dielectric strength: IEC 60255-6
Operate time: < 8 ms -21dBm -30dBm 9dB
Multimode ANSI/IEEE C37.90
Contact material: Silver alloy 1300 nm Laser Electrostatic discharge: EN 61000-4-2
-1dBm -30dBm 29dB
FAST FORM-C RELAY Singlemode Surge immunity: EN 61000-4-5
Make & carry: 0.1 A max. (resistive load) 1550 nm Laser RFI susceptibility: ANSI/IEEE C37.90.2
+5dBm -30dBm 35dB
Minimum load impedance: Singlemode IEC 61000-4-3
Operate time: < 0.6 ms IEC 60255-22-3
Internal Limiting 100, 2 * NOTE: These power budgets are calculated from the Ontario Hydro C-5047-77
Resistor: manufacturers’ worst-case transmitter power and worst-case Conducted RFI: IEC 61000-4-6
IRIG-B OUTPUT receiver sensitivity. Voltage dips/interruptions/variations:
Amplitude: 10 V peak-peak RS485 level IEC 61000-4-11
Maximum load: 100 ohms MAXIMUM OPTICAL INPUT POWER
IEC 60255-11
Time delay: 1 ms for AM input EMITTED, FIBER TYPE MAX. OPTICAL INPUT POWER Power frequency magnetic field immunity:
40 µs for DC-shift input IEC 61000-4-8
Isolation: 2 kV 820 nm LED, Multimode -7.6 dBm Vibration test IEC 60255-21-1
LATCHING RELAY 1300 nm LED, Multimode -11 dBm (sinusoidal):
Make & carry for 0.2 s: 30 A as per ANSI C37.90 1300 nm ELED, Singlemode -14 dBm Shock and bump: IEC 60255-21-2
Carry continuous: 6A 1300 nm Laser, Singlemode -14 dBm * NOTE: Type test report available upon
Break at L/R of 40 ms: 0.25 A DC max. 1500 nm Laser, Singlemode -14 dBm request.
Operate time: < 4 ms
Contact material: Silver alloy TYPICAL LINK DISTANCE PRODUCTION TESTS
Control: separate operate and reset inputs THERMAL
Control mode: operate-dominant or reset- CONNECTOR
EMITTED TYPE FIBER TYPE TYPICAL DISTANCE Products go through an environmental test based upon an
dominant TYPE
accepted quality level (AQL) sampling process
REMOTE OUTPUTS (IEC 61850 GSSE) 820 nm LED Multimode -7.6 dBm 1.65 km ENVIRONMENTAL
Standard output points: 32 1300 nm LED Multimode -11 dBm 3.8 km OPERATING TEMPERATURES
User output points: 32 Cold: IEC 60028-2-1, 16 h at -40°C
SOLID-STATE OUTPUT RELAY 1300 nm ELED Singlemode -14 dBm 11.4 km Dry Heat: IEC 60028-2-2, 16 h at +85°C
Operate & release time: <100 µs 1300 nm Laser Singlemode -14 dBm 64 km OTHER
Maximum voltage: 265 V DC 1500 nm Laser Singlemode -14 dBm 105 km Humidity(noncondensing):
Maximum continuous 5 A at 45°C; 4 A at 65°C IEC 60068-2-30, 95%, Variant
current: 1,6days.
Make & carry for 0.2 s: as per ANSI C37.90 Altitude: Up to 2000 m
For 0.3s: 300 A Installation Category: II
Breaking capacity: APPROVALS
UTILITY UL Listed for the USA and Canada
IEC 647-5/UL508 APPLICATION INDUSTRIAL Manufactured under an ISO9000 registered system.
(AUTORECLOSE APPLICATION
SCHEME) LVD 73/23/EEC: IEC 1010-1
5000 ops 5 ops/
1 s-On, 9 s-Off .2 s-On, 10000 ops/
EMC 81/336/EEC: EN 50081-2, EN 50082-2
Operations/ 0.2 s-Off
interval 0.2 s-On,
1000 ops within 1 30 s-Off
0.5 s-On, 0.5 s-Of minute
3.2 A
Break L/R = 10 ms
capability 1.6 A 10 A 10 A IEC is a registered trademark of Commission Electrotechnique Internationale. IEEE is a registered
(0 to 250 VDC) L/R = 20 ms L/R = 40 ms L/R = 40 ms
0.8 A
trademark of the Institute of Electrical Electronics Engineers, Inc. Modbus is a registered trademark of
L/R = 40 ms Schneider Automation. NERC is a registered trademark of North American Electric Reliability Council.
NIST is a registered trademark of the National Institute of Standards and Technology.
GE, the GE monogram, Multilin, FlexLogic, EnerVista and CyberSentry are trademarks of General Electric
Company.
GE reserves the right to make changes to specifications of products described at any time without notice
and without obligation to notify any person of such changes.