Protection Settings
Voltage Above 110% of Nominal for 60 Seconds 635 V
Voltage Above 115% of Nominal for 2 Seconds 664 V
Voltage Above 120% of Nominal for 0.08 Seconds 692 V
Voltage Above 125% of Nominal for 0.005 Seconds 721 V
Voltage Below 90% of Nominal for 60 Seconds 519 V
Voltage Below 85% of Nominal for 11 Seconds 490 V
Frequency is Above [Hz] for 0.2 Seconds 53 Hz
Frequency is Below [Hz] for 0.2 Seconds 47 Hz
Table 9-5: Generator and converter disconnecting values.
NOTE * Over the turbine lifetime, grid drop-outs are to occur at an average of no more
than 20 times a year.
1500
1000
cos 0,4
500 cos 0,98
Q [kVar]
0
0 250 500 750 1000 1250 1500 1750 2000 2250 2500 2750 3000
-1000
-1500
P [kW]