Communication Specification for
Pakscan P3 and IIS Master Station

Publication S171E V1.1 Issue 11/2008


Pakscan P3 with P720 Module Modbus Interface Specification

As we are continually developing our products their design is subject to change without notice.

© The contents of this document are copyright and must not be reproduced without the written
permission of Rotork Controls Ltd.

The name Rotork is a registered trademark

Modbus is a registered trademark of Modbus-IDA

Centum is a registered trademark by Yokogawa Electric Corporation

EPLCG, SI gateway and TDC3000 are products of Honeywell Inc.

2 of 96 Publication S171E V1.1 Issue 11/2008


Contents

Contents

Glossary of Terms:............................................................................................................................5
Abbreviations: ...................................................................................................................................5

1 INTRODUCTION.................................................................................................7
1.1 General .....................................................................................................................................7
1.2 Serial communication to Pakscan master stations.............................................................8
1.2.1 Serial communication to a Pakscan IIS master station ........................................8
1.2.2 Serial communication to a Pakscan P3 master station ........................................9
1.2.3 Host communication connections for hot standby Pakscan P3 master stations10
1.2.4 Pakscan 3 master station – Port Function DIP switches....................................14
1.2.5 Pakscan 3 master station – RS485 termination .................................................14
1.2.6 Pakscan 3 master station – RS485 Cross Connection (Hot Standby Systems) 15
1.2.7 RS485 termination – Pakscan IIS master station...............................................15
1.3 Ethernet Communications to Pakscan master stations ...................................................16
1.3.1 Pakscan P3 Ethernet Connection ......................................................................16
1.3.2 Pakscan IIS Ethernet Connection ......................................................................17

2 DATA INTERPRETATION................................................................................19
2.1 Master station data ...............................................................................................................19
2.1.1 Data base segregation .......................................................................................19
2.1.2 Master station data description...........................................................................20
2.1.3 Alarm handling....................................................................................................21
2.1.4 Data relevant to hot standby systems ................................................................21
2.1.5 Additional data available using Generic / EPLCG Interface...............................21
2.1.6 Command description.........................................................................................22
2.2 Field unit data........................................................................................................................22
2.2.1 Digital status bits ................................................................................................23
2.2.2 Alarm data bits....................................................................................................23
2.2.3 Field unit commands ..........................................................................................24
2.2.4 Field unit analogue inputs...................................................................................25

3 MODBUS SPECIFICATION..............................................................................27
3.1 Electrical specification .........................................................................................................27
3.2 Outer protocol .......................................................................................................................27
3.3 Serial Data..............................................................................................................................27
3.4 Overview of the design.........................................................................................................27

4 GENERIC AND HONEYWELL EPLCG PROTOCOL INTERFACE


SPECIFICATION ..............................................................................................29
4.1 Modbus unit address (Generic and Honeywell EPLCG protocols)..................................29
4.2 Modbus function code support (Generic and Honeywell EPLCG protocols) .................31
4.3 Data base access (Generic and Honeywell EPLCG protocols)........................................34
4.3.1 Data Organisation...............................................................................................34
4.3.2 Data Read Requests ..........................................................................................34

Publication S171E V1.1 Issue 11/2008 3 of 96


Pakscan P3 with P720 Module Modbus Interface Specification

4.3.3 Register and Discrete Address Formulae ..........................................................35


4.4 Notes on the use of the Generic and EPLCG Modbus protocol.......................................38
4.4.1 Suggested Scan Cycle .......................................................................................38
4.4.2 Writing to Coils....................................................................................................38
4.4.3 Readback of Holding Registers ..........................................................................39
4.4.4 Alarm Handling ...................................................................................................39
4.4.5 Use of Alarm Bits ................................................................................................40
4.5 Master station data base (Generic and Honeywell EPLCG protocols)............................41
4.5.1 Master Station Read Only Data..........................................................................41
4.5.2 Master Station Write Only Data ..........................................................................44
4.6 Field unit data base (Generic and Honeywell EPLCG protocols) ....................................45
4.6.1 Field Unit Data Base Locations ..........................................................................46
4.7 Modbus messages examples (Generic and Honeywell EPLCG protocols) ....................54
4.7.1 Read Master Station Status................................................................................54
4.7.2 Write Master Station Alarm Accept ....................................................................54
4.7.3 Read Field Unit 12 Digital Status........................................................................54
4.7.4 Read Field Unit 62 Digital Status........................................................................55
4.7.5 Read Digital Status from 60 Field Units, Addresses 121 to 180 ........................55
4.7.6 Energise Command to OPEN relay of Field Unit 4 ............................................55
4.7.7 Write Desired Valve Position for FCU 26 to be 50% ..........................................55

5 YOKOGAWA AND HONEYWELL SI PROTOCOL INTERFACE


SPECIFICATION ..............................................................................................57
5.1 Modbus unit address (Yokogawa and Honeywell SI protocols) ......................................57
5.2 Modbus function code support (Yokogawa and Honeywell SI protocols)......................59
5.3 Data base access (Yokogawa and Honeywell SI protocols).............................................62
5.3.1 Data Organisation...............................................................................................62
5.3.2 Data Interchange Requests................................................................................62
5.4 Notes on the use of the Yokogawa and Honeywell SI Modbus protocol ........................62
5.4.1 Suggested Scan Cycle .......................................................................................63
5.4.2 Writing to Coils....................................................................................................63
5.4.3 Readback of Holding Registers ..........................................................................63
5.4.4 Alarm Handling ...................................................................................................64
5.4.5 Use of Alarm Bits ................................................................................................65
5.5 Master station data base (Yokogawa and Honeywell SI protocols) ................................66
5.5.1 Master Station Records ......................................................................................66
5.6 Field unit data base (Yokogawa and Honeywell SI protocols) .........................................67
5.6.1 Digital Inputs (Field Units) ..................................................................................67
5.6.2 Digital Outputs (Field Units)................................................................................73
5.6.3 Analogue Inputs (Field Units) .............................................................................75
5.6.4 Analogue Outputs (Field Units) ..........................................................................78
5.7 Field unit inputs and outputs available ..............................................................................79
5.7.1 Digital Inputs .......................................................................................................79
5.7.2 Digital Outputs ....................................................................................................81
5.7.3 Analogue Inputs..................................................................................................81
5.7.4 Analogue Outputs...............................................................................................81
5.8 Modbus message examples (Yokogawa and Honeywell SI protocols)...........................82
5.8.1 Read Field Unit Bit 5 from FCU 1 to 100............................................................82

4 of 96 Publication S171E V1.1 Issue 11/2008


Contents

5.8.2 Read Field Unit Bit 2 and 3 from FCU 1 to 120..................................................82


5.8.3 Read Valve Position from FCU 26......................................................................82
5.8.4 Energise Command to Open relay of Field Unit 104..........................................82
5.8.5 Write Desired Valve Position for FCU 26 to be 50% ..........................................83

6 FIELD UNIT BLOCK AND PARAMETER ALLOCATIONS..............................85


6.1 Block and parameter construction......................................................................................85
6.1.1 Digital inputs .......................................................................................................85
6.1.2 Alarm block .........................................................................................................85
6.1.3 Analogue and counter input data .......................................................................85
6.1.4 Outputs ...............................................................................................................86
6.2 Block and parameter usage .................................................................................................86

Glossary of Terms:
Block A master station data base entry covering 8 related parameters
Parameter A master station data base entry of 16 bits
Bit A master station data base discrete entry.
Modbus Address The 8 bit address to which a Modbus Slave responds when interrogated.
Register Address A data base start location within a Modbus address used to access at least
one parameter (16 bits).
Discrete Address A data base start location within a Modbus address used to access at least
one bit.
Field Unit A device connected to a master station that reports records into the master
station data base.
Master Station A Modbus slave containing a data base about itself and the connected field
units.
Slave A Modbus device containing data.
Host A Modbus master controlling all data transactions on the Data Highway.
Data Highway The mechanism along which the data flows; e.g. the RS 232, RS485 or
Ethernet connection between Host and master station(s).
Gateway The host device (PLC or DCS or other equipment) interface to the data
highway

Abbreviations:
Comms Communications
CRC Cyclic Redundancy Check
DIP Dual In-Line Package (chip)
FCU Field Unit
FU Field Unit
HW Hardware
MS Master Station
No Number
RAM Random Access Memory
ROM Read Only Memory
RTU Remote Terminal Unit
SW Software

Publication S171E V1.1 Issue 11/2008 5 of 96


Pakscan P3 with P720 Module Modbus Interface Specification

(This page is intentionally blank)

6 of 96 Publication S171E V1.1 Issue 11/2008


Serial Communications

This manual relates to Pakscan 3 Systems fitted with


PS720 Current Loop modules and Pakscan IIS systems

1 INTRODUCTION

This document provides information on the Modbus data base organisation and locations of
information inside Pakscan IIS and P3 Current Loop Option master stations. In addition, it provides an
overview for the connection of host systems to the Pakscan master stations.

‰ Supporting Documents:

Modbus-IDA documentation:

Protocol Documentation
Modbus Application Protocol Specification V1.1b December 2006

Implementation for Legacy Serial Systems


Modbus Protocol Reference Guide PI-MBUS-300 Rev J 1996

Implementation for New Serial Systems


Modbus over Serial Line Specification & Implementation Guide V1.02 December 2006

Implementation for Modbus TCP/IP systems


Modbus Messaging on TCP/IP Implementation Guide V1.0b October 2006

Rotork Documentation

Pakscan 3 Master Station System Manual Publication S720E


Pakscan IIS Master Station Technical Manual Publication S130E

‰ Supported Hardware:
Pakscan 3 Master Station (version 1.01.01) and PS720 module (version 1.0.2) or higher
Pakscan IIS Master Station with software reference 5222-020 version 1.5 or higher

All Pakscan master stations are RTU slaves on serial Modbus highways; they cannot act as masters.
On TCP/IP systems they are Servers and cannot act as Clients. Where a Pakscan IIS is being used
on a Modbus TCP/IP network a separate PS610 module is required.

1.1 General
All Pakscan master stations are supplied preconfigured with a standard, non-variable, data base
relating to the field units connected. The data is always as listed in this document and does not vary
between projects. Because various host systems have complexities and requirements that are slightly
different there are two basic data base maps, each with two variations on analogue register value
scaling.

Publication S171E V1.1 Issue 11/2008 7 of 96


Pakscan P3 with P720 Module Modbus Interface Specification

The data base organisation that is accessed is chosen by the user. It is selected from the list of four by
entering the choice into the system using the keypad and LCD screen on the master station. At any
time the choice can be amended and no additional re-programming of the unit is required.

P3 Pakscan P
3 P3 P3 P3 P3 P3 Pakscan
IIE Loop Keyswitch IIE Loop

Standby Standby

Port A Port A
Auto
A B

Port B Port B
Status Status
PS710 Pri/Stby PS720 PS730 PS720 PS710 Pri/Stby
Power Power
rotork Alarm rotork rotork rotork rotork rotork rotork Alarm
rotork

CPU/PSU Option 1 Option 2 Switch Option 2 Option 1 CPU/PSU


Port 1 Port 1
PS700

Port 2
CE A B
Port 2

Pakscan IIS

Fig 1: Pakscan P3 and Pakscan IIS master station

1.2 Serial communication to Pakscan master stations


All Pakscan master stations (both P3 and IIS), have two or more serial communication ports available
for connection to host systems. These may be either RS232 or RS485 depending on the options
specified when the unit was manufactured. It is possible to retrospectively change these ports after
delivery by altering the DIP switches on the backplane of either unit.

In all cases, the communication is half-duplex and in the case of RS485 it is 2 wire.

1.2.1 Serial communication to a Pakscan IIS master station

The Pakscan IIS has three communication ports. These may be individually set for either RS232 or
RS485. To change a port from RS232 to RS485, or vice versa, simply involves the fitting of jumper
links to the main board in the appropriate positions. On the RS485 ports, links for both pull-apart and
termination resistors can be selected for line termination. Full information on setting the ports is
contained in the Pakscan IIS Technical Manual.

Port 1 2 wire RS485 highway


or RS232 highway
Port 2 2 wire RS485 highway
Pakscan IIS
or RS232 highway

Fig 2: Pakscan IIS master station serial communications

8 of 96 Publication S171E V1.1 Issue 11/2008


Serial Communications

Single or redundant communications can be used on either multi-drop or dedicated highways. The
data base information remains the same whichever type of connection is used.

When redundant communications are employed such as shown in Fig. 2; the two data lines access
Port 1 and Port 2. The data behind these ports is designed to allow communication to two separate
host systems or a single host on redundant highways. The two ports are effectively handled by two
independent data bases each fed with information from the connected actuators. Care must then be
taken in the handling of alarms that will be latched in the master station data bases. Either link the two
ports by setting the ‘Alarms - Linked’ option for the Current Loop module Host Settings or ensure that
all alarms are accepted on both highways.

The alarm handling is independent of the protocol data base chosen for communication to the host
system.

The Pakscan IIS master station also has a unique capability to have two Modbus slave addresses to
which it will respond. Addresses above 127 are designed specifically for use with the Sequence
Programming Tools (Orbus SCT) available from Rotork. Regular data communication should be
limited to using slave addresses in the range 1 to 127.

1.2.2 Serial communication to a Pakscan P3 master station

The Pakscan P3 has two serial communication ports on each module. These may be individually set
for either RS232 or RS485. To change a port from RS232 to RS485 or vice versa simply involves
altering DIP switch settings on the rear chassis behind the main PS710 modules. When RS485 ports
are selected, line termination settings for both pull-apart and termination resistors can also be DIP
switch selected. With dual redundant P3 master stations in hot standby configuration there will be two
communication ports on each side, giving four in total. Full information on setting the ports is
contained in the Pakscan P3 Technical Manual.

Station A Station B
Station A Station B
Port 1 Port 2 Port 1 Port 2
P3 Pakscan P
3 P3 P3 P3 P3 P3 Pakscan
IIE Loop Keyswitch IIE Loop

RS232 RS232
Standby Standby

Port A Port A
Auto

Status
Pri/Stby
Port B
A B

Port B
Status
Pri/Stby
or or N/A N/A
PS710 PS720 PS730 PS720 PS710

rotork
Power
Alarm rotork rotork rotork rotork rotork rotork
Power
Alarm
RS485 RS485
rotork

CPU/PSU Option 1 Option 2 Switch Option 2 Option 1 CPU/PSU


Port 1 Port 1
PS700

Port 2
CE A B
Port 2

P3 Pakscan P
3 P3 P3 P3 P3 P3 Pakscan
IIE Loop Keyswitch IIE Loop

Standby Standby
RS232 RS232 RS232 RS232
Port A

Port B
A
Auto
B
Port A

Port B
or or or or
PS710

rotork
Status
Pri/Stby
Power
Alarm
PS720 PS730

rotork rotork rotork rotork rotork


PS720 PS710

rotork
Status
Pri/Stby
Power
Alarm
RS485 RS485 RS485 RS485
rotork

CPU/PSU Option 1 Option 2 Switch Option 2 Option 1 CPU/PSU


Port 1 Port 1
PS700

Port 2
CE A B
Port 2

Fig 3: Pakscan P3 master station serial communications

The communications may be organised in many ways. A single Pakscan P3 master may be linked to
the host system in the same way as the Pakscan IIS described previously. When a hot standby master
station is used, the variations are more complex.

Publication S171E V1.1 Issue 11/2008 9 of 96


Pakscan P3 with P720 Module Modbus Interface Specification

When redundant communications are used, the two data lines should access both the A and B master
stations. In a complex multi-drop redundancy, care is needed in alarm handling. Access is to Port 1
and Port 2 on both units A and B. The data behind these ports is designed to allow communication to
two separate host systems, or a single host on redundant highways. The two ports are effectively
handled by two independent data bases each fed with information from the connected actuators.
When they are both connected to the same host system it is recommended that the two ports are
linked for alarms by setting the ‘Alarms - Linked’ option for the Current Loop module Host Settings.
This ensures that all alarms are accepted on both ports if alarms are accepted on one only.

1.2.3 Host communication connections for hot standby Pakscan P3 master stations

The Pakscan P3 hot standby system has two master stations operating one field network or Pakscan
2 wire current loop. One master station PS710 module will be the main or primary unit controlling the
network and the other will be the standby unit monitoring the performance of the main unit. Either unit
can be in either mode although they cannot both be in the same mode, i.e. either master station A or
master station B can be the main or primary unit whilst the other is in standby mode.

Each module has two communication ports as described above. The configuration option for hot
standby mode includes a choice for host communications, i.e. ‘Active’ or ‘Passive’ when the module is
in Standby mode. This is a selection for the communications option of the PS710 module itself, rather
than the hot standby pair (the setting is located in the M/S Settings menu page). The choice
determines how the module responds to host communications when it is in standby mode, and each
module has a separate choice for both of its host ports. If the module is set to ‘Passive’, it will not
respond to messages from the host when it is the standby unit, however, it will reply when it is the
main unit. When the unit is the main module, it will always respond to all instructions.

When the module is set to ‘Active’, it will respond to messages from the host irrespective of whether it
is in main or standby mode. When ‘Active’ is selected, care must be taken to ensure that valve
commands are addressed to the module that is in main mode as the module in standby mode is
prevented from controlling the field network or Pakscan current loop.

It is also important to note how control passes from one module to the other. The command to change
master will reverse the mode of the two units and the instruction can be instigated either from the
keypad or via the serial communications link. Note that it is the only command actioned by a standby
unit which is set to ‘Passive’. (The keyswitch can also be used to make either station A or station B the
main module). A standby unit will change automatically to the main unit when it detects that its partner
has failed or that it no longer has control.

Station in Primary/Main Station in Standby Mode Station in Standby Mode


Mode Comms port set Active Comms port set Passive
Controls the field network Does not control the field Does not control the field network
and 2 wire current loop network and 2 wire current loop and 2 wire current loop
Responds to all host Responds to all host messages, Does not respond to any host
messages and actions all does not action any commands messages, only actions a change-
commands over command
May be remotely May be remotely commanded to May be remotely commanded to
commanded to change to change to main mode change to main mode
standby mode

10 of 96 Publication S171E V1.1 Issue 11/2008


Serial Communications

‰ Single host - RS485 (2 wire) communications


RS485 communications allow the user to multi-drop several devices on one data highway. One host
port can be connected to up to 32 master station RS485 ports, (more if repeaters are used). The ‘2
wire’ description refers to the communication highway using the same single pair of wires for both
transmitting and receiving data. The Pakscan P3 master station only supports 2 wire RS485
communications. The highway extension can be simplified by selecting the Cross Connect option on
the chassis DIP switches.

With this configuration, as all master station modules are connected on the same highway, both
station A and station B of each hot standby pair will receive data from the PLC. If both station A and
station B were to reply together the resultant data at the PLC would be unintelligible and therefore
rejected. To avoid this situation and have only either station A or station B replying both modules
should be set to ‘Passive’ on the serial port being used (Port 1 or Port 2).

If the module in main mode fails, the standby unit will take control automatically. However, if the
communication highway between PLC and the module in main mode fails, there will be no automatic
switch over. The PLC will be unable to command the change-over of main to standby and vice versa,
i.e. control any of the master stations beyond the failure point will not be possible.

RS485 2 wire highway


P3 Pakscan P
3 P3 P3 P
3 P3 P3 Pakscan
IIE Loop Keyswitch IIE Loop

Standby Standby

Port A Port A
Auto
A B

Port B Port B
Status Status
PS710 Pri/Stby PS720 PS730 PS720 PS710 Pri/Stby
Power Power
rotork Alarm rotork rotork rotork rotork rotork rotork Alarm
rotork

CPU/PSU Option 1 Option 2 Switch Option 2 Option 1 CPU/PSU


Port 1 Port 1
PS700

Port 2
CE A B
Port 2

Port 1 Cross Connect Port 1

P3 Pakscan P
3 P3 P3 P3 P3 P
3 Pakscan
IIE Loop Keyswitch IIE Loop

Standby Standby

Port A Port A
Auto
A B

Port B Port B
Status Status
PS710 Pri/Stby PS720 PS730 PS720 PS710 Pri/Stby
Power Power
rotork Alarm rotork rotork rotork rotork rotork rotork Alarm
rotork

CPU/PSU Option 1 Option 2 Switch Option 2 Option 1 CPU/PSU


Port 1 Port 1
PS700

Port 2
CE A B
Port 2

Port 1 Cross Connect Port 1

Fig 4: 2 wire RS485 single highway

‰ Twin host - RS485 (2 wire) communications


There are incidences when there are two host systems connected to one or more hot standby master
stations, e.g. PLC and In-Vision. This method offers redundancy of the host controller and the master
station units. In this case, two RS485 highways are needed, using both the stations’ communication
ports from each module. The Cross Connection DIP switches are used for highway extension.

Publication S171E V1.1 Issue 11/2008 11 of 96


Pakscan P3 with P720 Module Modbus Interface Specification

With this configuration both the ports (port 1 and port 2) on each station should be set to ‘Passive’ in
order to avoid the situation where two, (station A and station B), units reply at once. However, if a PLC
fails or the communication highway fails between one PLC and the master stations, that
communication will be lost. The second host (In-Vision) would continue without loss of master station
control. As each host requires full access to the alarms present, the port alarms should be set to
‘separate’ in this configuration.

Note that there is no prioritisation of control via the host communications ports, i.e. commands from
both PLC and In-Vision have equal weighting.

In-Vision

Highway 2
PLC highway In-Vision highway
Highway 1
P3 Pakscan P
3 P3 P3 P
3 P3 P3 Pakscan P3 Pakscan P
3 P3 P3 P
3 P3 P3 Pakscan
IIE Loop Keyswitch IIE Loop
IIE Loop Keyswitch IIE Loop

Standby Standby Standby Standby

Port A Port A Port A Port A


Auto Auto
A B A B

Port B Port B Port B Port B


Status Status Status Status
PS710 Pri/Stby PS720 PS730 PS720 PS710 Pri/Stby PS710 Pri/Stby PS720 PS730 PS720 PS710 Pri/Stby

Port 1 rotork
Power
Alarm rotork rotork rotork rotork rotork rotork
Power
Alarm
Port 1 Port 1 rotork
Power
Alarm rotork rotork rotork rotork rotork rotork
Power
Alarm
Port 1
rotork
rotork

CPU/PSU CPU/PSU Option 1 Option 2 Switch Option 2 Option 1 CPU/PSU


Option 1 Option 2 Switch Option 2 Option 1 CPU/PSU Port 1 Port 1 Port 1
Port 1

Port 2 Port 2 Port 2 Port 2


PS700
PS700

Port 2
CE A B
Port 2 Port 2
CE A B
Port 2

P3 Pakscan P
3 P3 P3 P3 P3 P
3 Pakscan P3 Pakscan P
3 P3 P3 P3 P3 P
3 Pakscan
IIE Loop Keyswitch IIE Loop
IIE Loop Keyswitch IIE Loop

Standby Standby
Standby Standby

Port A Port A
Auto Port A Port A
A B Auto
A B

Port B Port B
Status Status Port B Port B
Pri/Stby Pri/Stby Status Status
PS710 PS720 PS730 PS720 PS710
Power Power PS710 Pri/Stby PS720 PS730 PS720 PS710 Pri/Stby
rotork Alarm rotork rotork rotork rotork rotork rotork Alarm
rotork
Power
Alarm rotork rotork rotork rotork rotork rotork
Power
Alarm

Port 1
rotork

Port 1
rotork

CPU/PSU Option 1 Option 2 Switch Option 2 Option 1 CPU/PSU


Port 1 Port 1 CPU/PSU Option 1 Option 2 Switch Option 2 Option 1 CPU/PSU

Port 2
Port 1 Port 1

Port 2
PS700

CE
PS700

Port 2 Port 2
A B Port 2
CE A B
Port 2

In-Vision highway PLC highway Highway 2 Highway 1

Fig 5: Twin Host, single RS485 comms Fig 6: Single Host, dual redundant RS485 comms

‰ Single host - dual redundant RS485 (2 wire) communications


This configuration is similar to the dual system described above although in this case there is only one
host, which has two interfaces. This method offers true redundancy of the master stations, host
interface, and serial communications cabling. As before each module requires the ‘Passive’ option to
be selected. The alarm handling also requires the port alarms to be set to ‘Linked’ so that the host
system does not collect repeats of the alarms when changing the comms line in use.

12 of 96 Publication S171E V1.1 Issue 11/2008


Serial Communications

‰ Single host - dual RS232 communications


RS232 communications are a point to point means of communication; i.e. one port on the host system
will be connected to one port on the master station. Dual data highways from the host are required
when using RS232 communications to a hot standby master station. The two RS232 ports on the host
connect to one on master station A and one on master station B. This connection method can only be
used where there is a single field network or 2 wire current loop and master station to be supervised.
RS232 does not permit multi-drop communications to a number of master stations.

With this configuration, the PLC determines which of its output ports and highways it is using and
therefore which unit it is talking to, i.e. there are separate paths for station A and station B
communication links to the PLC. Consequently both modules should be set to ‘Active’, so that the PLC
always receives an answer irrespective of which highway it uses. Note that only the unit in main mode
will action any commands issued by the PLC, so the PLC needs to determine which of units A and B is
the main and which is the standby.

P3 Pakscan P
3 P3 P3 P
3 P3 P3 Pakscan
IIE Loop Keyswitch IIE Loop

Standby Standby

Port A Port A
Auto
A B

Port B Port B
Status Status
PS710 Pri/Stby PS720 PS730 PS720 PS710 Pri/Stby
Power Power
rotork Alarm rotork rotork rotork rotork rotork rotork Alarm
rotork

CPU/PSU Option 1 Option 2 Switch Option 2 Option 1 CPU/PSU


Port 1 Port 1
PS700

Port 2
CE A B
Port 2

Port 1 Port 1

Fig 7: Single Host, dual redundant RS232 comms


If the main mode unit fails, the standby unit will take control automatically. However, if the
communication highway between PLC and the main mode unit fails, there will be no automatic switch
over. The PLC should read the master station data to determine which side is in control and then issue
a suitable command the change over the main to standby if required.
Signal Common

Signal Common
Transmit Data

Recieve Data

Data +

(Female) 9 way D Type


Data -

5 4 3 2 1 5 4 3 2 1

9 8 7 6 9 8 7 6
RS232 Connections RS485 Connections

Fig 8: Pakscan 3 master station serial communications connections

Publication S171E V1.1 Issue 11/2008 13 of 96


Pakscan P3 with P720 Module Modbus Interface Specification

General guidance

1. Both station A and B must be set to the same options with regard to all
settings including the standby active/standby passive option.

2. When using an RS485 highway, care must be taken to ensure that it is


correctly terminated at both ends (and only at the ends).

3. If the host system wishes to change over control of the loop such that
master station A changes from main to standby or vice versa, it must do
so by sending the change over command to either the main unit or the
standby unit.

1.2.4 Pakscan 3 master station – Port Function DIP switches

The P3 master station chassis has DIP switches underneath the PS710 CPU module for setting the
type of serial port that is presented at the port connectors.

RS232 RS485
The two DIP switches allow each port to be selected between
Port 1 RS232 and RS485. For RS485 slide the appropriate Port switch
to the right, for RS232 they should be on the left.

Each of the two ports may be set independently.


Port 2

Fig 9: Port Function Switches shown in RS232 position

1.2.5 Pakscan 3 master station – RS485 termination

The master station chassis includes the DIP switches to select line termination and pull-apart resistors
on the comms lines. All RS485 highways should be terminated correctly and when two wire data
transmission is being used the possible errors in data that can occur during line turn around can be
overcome with pull-apart resistors. Care must be taken to fit these resistor networks on the ends of the
lines only; consequently the best location is at the PLC/DCS end of the multi-drop data highway. Prior
to dispatch from Rotork these switches are normally set ‘Off’ to disable the resistors.
+5V
120

Off On
Port Terminations Data +
Off 1 On
100
Off 2 On
Data -
Off On

120
Gnd
Fig 10: Port Termination Switches shown in Off position

14 of 96 Publication S171E V1.1 Issue 11/2008


Serial Communications

The two DIP switches are used to connect end of line termination resistors and biasing resistors to the
RS485 network. All RS485 network highways should be terminated at both ends of the highway.
Each port can be terminated independently.

1.2.6 Pakscan 3 master station – RS485 Cross Connection (Hot Standby Systems)

The cross connection DIP switches allow the serial ports on the two sides of the hot standby master
station to be connected together as a multi-drop pair. The port should only be cross connected when
either Port 1 and/or Port 2 are set to RS485. If a port is cross connected then its associated “A Only”
and “B Only” feedback switches must also be set to the Cross Connected position (moved to the
right). The feedback switches are used to inform the master station and modify the default set up
options for a cross coupled port to “standby passive”.
Port 1 A Side Master B Side Master
A Only
Port 2
Feedback Port 1 Feedback

B Only Port 1 Feedback Port 2 Feedback


Port 2

Data +
Port 1 Data -
Port 1 Data + Port 1
Port 1 Data -

Data +
Port 2 Data -
Port 2 Data + Port 2
Port 2 Data -

Not Cross Cross Cross Connect Switches


Connected Connected (Shown not cross connected)

Fig 11: Port Cross Connection and Feedback Switches shown in Not Cross Connected position

1.2.7 RS485 termination – Pakscan IIS master station

The Pakscan IIS master station has two configurable ports in which the mode of operation is changed
by links on the main board. There is provision for pull-apart resistors to be selected internally for each
port by setting the DIP switches in the correct positions. In these units, there are no termination
+ve

PORT 1
RS485 S1 1 3
1 TXA+ Data +
LK6 2 TXA- Data -
1 2 S2
A B 3 Common
J5 4
2 4
RS485 -ve
A B
CTSA J10 5
RTSA J6 6
7 COMA
8 GND

Fig 12: Pakscan IIS master station terminating resistors for RS485 2 wire highway

Publication S171E V1.1 Issue 11/2008 15 of 96


Pakscan P3 with P720 Module Modbus Interface Specification

resistors but the pull-apart 120 ohm resistors will provide good termination on their own. All highways
should contain at least one pair of pull-apart resistors. The diagram shows the settings for Port 1, Port
2 is similar; details of the connections are shown on the internal label of the master station.

1.3 Ethernet Communications to Pakscan master stations


The Pakscan 3 master station includes dual Ethernet ports for communication by Modbus TCP/IP or to
the internet. The Pakscan IIS can be used with a PS610 module(s) to convert one or both of the
RS485 ports to Ethernet.

1.3.1 Pakscan P3 Ethernet Connection

Pakscan 3 master stations have two Ethernet ports for connection to host DCS or PLC systems. A
third Ethernet port is also available for connection to a laptop computer for configuration purposes.
The master station is ready to use with Ethernet and Modbus TCP protocol for the DCS to access data
and control the actuators on the field network. The IP address is already set and can be changed
during setting up the master station

Pakscan 3 Master Station


P
3
Pakscan P
3
P
3
P3
P3
P
3 P3
Pakscan
IIE Loop Keyswitch IIE Loop

Standby Standby

Port A Port A
Auto
A B

Port B Port B
Status Status
PS710 Pri/Stby PS720 PS730 PS720 PS710 Pri/Stby
Power Power
rotork Alarm rotork rotork rotork rotork rotork rotork Alarm
rotork

CPU/PSU Option 1 Option 2 Switch Option 2 Option 1 CPU/PSU


Port 1 Port 1
PS700

Port 2
CE A B
Port 2

Port 3 Port 4 Port 3 Port 4


PLC

Switch* Switch*
Ethernet Highway 1
Ethernet Highway 2

Fig 13: Ethernet, dual highway, from hot standby P3 master station to PLC

* If Port 3 and Port 4 are being utilised at least one switch must be a managed switch and support
either Spanning Tree Protocol (STP) or Rapid Spanning Tree Protocol (RSTP).

‰ Setting-Up the Ethernet Comms


Ethernet connections require 10/100BaseT Ethernet Switches to connect the system together. Patch
cords connect the ports on the master (which are in the bottom of the PS710 module) to the Switches.
Independent highways are possible by using separate switches on each highway.

The Pakscan master station defaults to the same IP address on both the ports, and can use the same
address on the A and B master stations. It is possible to change the IP address on either master

16 of 96 Publication S171E V1.1 Issue 11/2008


Serial Communications

station, but the two ports always have the same address. When the A and B stations both use the
same IP address it is important to set the Standby Action to Passive.

The two Ethernet inputs are logically combined within the P3 master station. This means that Alarms
read over either highway are effectively read over both and there is only one alarm data base. It is not
recommended to use the two highways to access different host systems.

The recommended highway setup should follow these guidelines


ƒ Use two main data highway busses, both of which connects to all the master stations
ƒ The master is left with a Static DHCP port setting
ƒ Each hot standby pair has the same IP address on its port 3 and port 4
ƒ The Standby action is set to passive (default is active)
ƒ Keep the number of host connections below 10 (The master station can serve up to 10
simultaneous host connections).

With this arrangement either PLC port can always communicate with the master station in control of
the loop. Heartbeat data requests on the second highway will always be acknowledged with a
response.

DHCP Static
Default IP address 10 200 1 1
Subnet mask 255 255 255 0
Standby Action Set to Passive

1.3.2 Pakscan IIS Ethernet Connection

To obtain an Ethernet connection to a Pakscan IIS master station a PS610 converter module must be
used. The PS610 supports 10/100 Mbps Ethernet and up to 10 simultaneous users. It requires
configuration for address and user permissions during the system commissioning.

Pakscan IIS Master Station

PS610
Ethernet Bridge

PLC
Pakscan IIS

Switch
Ethernet Highway 1

Fig 14: Ethernet Highway from PLC to Pakscan IIS master station

Publication S171E V1.1 Issue 11/2008 17 of 96


Pakscan P3 with P720 Module Modbus Interface Specification

‰ Setting-Up the Ethernet Comms


Ethernet connections require 10/100BaseT Ethernet Switches to connect the system together. Patch
cords connect the ports on the PS610 Bridge to the Switches. Further Pakscan IIS master stations are
added by connecting to the switch. If a redundant highway is required then a second PS610 can be
connected to the Pakscan IIS master station.

ƒ The Ethernet bridge default I/P address is: 10.200.1.1.


ƒ The master station can serve up to 10 simultaneous host connections

DHCP Static
Default IP address 10 200 1 1
Subnet mask 255 255 255 0

18 of 96 Publication S171E V1.1 Issue 11/2008


Serial Communications

2 DATA INTERPRETATION

This section describes the data organisation and meaning of the various data bits found in the protocol
data for the Pakscan IIS and Pakscan P3 Current Loop option.

2.1 Master station data


The Pakscan 3 with Current Loop option and Pakscan IIS master stations perform various self-
checking routines and control the 2 wire current loop. The status of the master station itself is available
for interrogation by a host DCS over the serial interface. The relevant registers and the location of the
data within them, together with the methods for reading and writing to these registers is detailed later
in this document. The data is always related either to a field unit on the 2 wire current loop or to the
master station module or the Current Loop module.

This section provides the interpretation of the information reported by each data bit or register in the
master station area of the data base and the available registers to which system instructions may be
written. Note that the Pakscan IIS does not have hot standby capability and the data bits relating to
this feature are not applicable.

Information about the meaning of the information reported in the field unit area of the data base is
contained in the individual field unit instruction manuals. A brief overview of these data bit
interpretations follows later in this manual.

2.1.1 Data base segregation


Host Comms Link

Master Station Field Unit


Data Data
Data Base

2 wire loop data


Fig 15: Data base segregation

Whichever data base Interface is chosen it will contain at least two sections. One of these is termed
the Master Station Data Base, whilst the other is the Field Unit Data Base. The Field Unit Data Base
contains the information from the attached devices on the current loop network, whilst the Master
Station Data Base contains the system data.

‰ Logical and physical master stations


The Pakscan IIS master station has only one physical and one logical master station although a
special logical area exists that contains the sequencing data.

The physical Pakscan P3 master station (Current Loop access) may contain up to four logical master
stations as described in the Generic and EPLCG Interface section. The logical master stations each
have a different Modbus slave address and contain data about different groups of field units on the

Publication S171E V1.1 Issue 11/2008 19 of 96


Pakscan P3 with P720 Module Modbus Interface Specification

current loop. All of these logical master stations contain the same master station data. A command or
write instruction to one is equivalent to writing to them all and all transactions should take place using
the slave address of the base unit only. There is no need to read or write to more than one of them to
achieve a read or write for all of them.

In the case of the Yokogawa and APM-SI interfaces, there is both one logical and one physical master
station covering all the connected field units on the current loop for both the Pakscan P3 and IIS
master stations.

2.1.2 Master station data description

The available data depends on the interface chosen; this section describes all the data bits. When a
bit is present or asserted it will be a logical 1.

Auto-Loopback Occurred This bit is an alarm bit that is present if a fault is detected on the current loop
network and an automatic reconfiguration of the loop occurred.
Common Actuator alarm This data is an alarm bit that is present if any field unit on the loop has its MREL
data bit present. MREL is only available from Rotork actuator field units and is
the state of the ‘monitor relay’. It indicates that the actuator is not available for
control. (The actuator field unit ‘MREL’ bit is described in the actuator field unit
manual.)
Common Field Unit alarm This data is an alarm bit that is present if any field unit on the current loop
network has any of its alarm bits present, including those field units connected
to other logical master stations within this physical station. Thus, this alarm is
present whilst any one field unit is actually in alarm or if there is a field unit off
line and is therefore unable to communicate. (The field unit alarm bits are
described in the field unit manual.)
ESD Mode This bit is present if a contact input wired to the ESD terminals (4/5 on a P3 or
32/33 on a IIS) is open circuit and the remote contact input ESD facility is
enabled in the master station setup.
Loopback in Progress This could be named ‘reconfiguration in progress’ and is present whilst the
master station is in the process of reconfiguring the current loop network. It
provides an indication that the master station is ‘busy’ and the field unit data
may not be true during the reconfiguration time.
Loopback in Use This signal is present whenever the master station has found a loop fault and is
operating with Loopback asserted on the field cable. Note that under this
condition loop doubling is not available.
Power On Reset This bit is an alarm bit that is present if the system power has been lost and
restored.
RAM test fail This bit is an alarm bit that is present if the master station RAM test produces an
error. The memory is tested periodically.
ROM test fail This bit is an alarm bit that is present if the power up test of the EPROM in the
station fails.
Serial Control Enabled This bit is present if the master station can be controlled serially. (This signal is
always present.)
Watchdog fail This bit is an alarm bit that is present if the processor watchdog trips.

20 of 96 Publication S171E V1.1 Issue 11/2008


Serial Communications

2.1.3 Alarm handling

Some of the data bits are described as ‘alarm bits’. These represent information that can be
considered as an alarm. In each case the alarm bit is latched and it will not clear until the data has
been read by the host, a serial data alarm accept has been issued to the master station and the
source of the alarm has returned to normal.

2.1.4 Data relevant to hot standby systems

This data only has a true meaning for a Pakscan P3 master station with a hot standby fitted. The left
hand ‘A’ station is always the designated Main unit.

0 = A side, This bit indicates ‘A station / B station communicating’. It is used to determine if


1 = B side the communication is to the left hand or right hand station (A or B) of a standby
pair. The left hand ‘A’ unit is the designated ‘Main’ station. The data bit will be a
0 if the communication is to the ‘A’ station on the left-hand side. It is a 1 if the
communication is to the B station on the right hand side.
Master Station ‘A’ OK This bit is present if the Main, A side, left hand, unit is functioning correctly.
(main unit)
Master Station ‘B’ OK This bit is present if the Standby, B side, right hand unit is functioning correctly.
(standby unit)
1 = Primary, (In Use), This bit is used to indicate if the station that is currently communicating on the
0 = Standby, (Out of Use) serial link is in control of the current loop network or not. A ‘1’ indicates
communication to a station that is in Main mode, whilst a ‘0’ indicates it is in
Standby mode.

2.1.5 Additional data available using Generic / EPLCG Interface

FCU Failure Count This is a series of registers containing data showing the absolute number of
communication failures (including retries) for every connected field unit on the
current loop. The maximum count for a field unit is 256 failures after which its
counter rolls over to zero and starts again.
FCU Map This is a series of registers containing the field unit addresses in the order in
which they are connected on the 2 wire current loop
FCU on Loop to Scan Up This register contains a number equal to the master station setting for the
To highest FCU address to look for.
FCU’s Connected This register contains data to show the number of FCU’s communicating on
each of the current loop network ports. In normal circumstances all the FCU’s
will be connected to Port A. However, if there is a cable fault, then some will be
connected to Port A and some to Port B. The numbers indicate the position of
the cable fault.
Field Unit Address Fault This register holds data about the position and address number that is found to
be at fault during configuration.
Loop Baud Rate This register contains a number that may be decoded to give the loop baud rate
setting.
Loop Configuration This register changes its value as the master station proceeds through the
Process stages used in configuring the loop.
Loop Fault Information This register holds data indicating loop faults that may be present and
preventing complete loop configuration. Additionally it includes the last system
reconfiguration code and the loop fault type.

Publication S171E V1.1 Issue 11/2008 21 of 96


Pakscan P3 with P720 Module Modbus Interface Specification

PS720 Current Loop Card This register contains a number collected from the loop card EPROM to indicate
Software Version Number the software version that is in use.
Loop Test Result (%) This register holds a hex number for the result of the last loop test in percent.
Loop Test Speed The number in this register relates to the last Loop Test performed and the
speed at which it was done.
Command Filter Timeout This register contains the timeout setting for the command filter.
Master Station Type This register contains a number that identifies the type and capacity of the
Number master station.

2.1.6 Command description

It is possible to issue instructions to the system over the serial interface. These commands are
directed either at a particular field unit or at the system as a whole. The commands relating to the
system are as follows.

Alarm Accept Energise this coil to issue an alarm accept to any alarm in the data base (field
unit or master station) which has been read in a previous transaction. There is
only one ‘accept’ coil for alarms, though each serial port, the Ethernet ports and
the LCD on each station, have their own accept system and virtual data bases.
Any alarms will only clear from the data base if they are read over the serial link
or Ethernet link prior to being accepted and the alarm condition returns to
normal. Note that if the alarms are ‘linked’ then the Alarm Accept accepts all the
alarms on the linked the data bases
Change Main / Standby Energise this coil in either the Main unit or Standby unit to cause the system to
transfer control between units. A ‘Main’ unit may be switched to standby, or a
‘Standby’ unit may be switched to main.
Note that this command is operative even when sent to a unit in Standby Mode
that is set to ‘Standby Passive’. It is the only message obeyed by a unit in this
condition. ‘Standby Passive’ is the normal setting for a master station on a
multi-drop system.
ESD Command to Loop Energise this coil to cause a global emergency shut down instruction to be
issued over the 2 wire current loop to all the field units. (The command will only
be issued to the loop if the ESD facility is enabled in the master station setup.)
Reconfigure Loop Energise this coil to cause the PS720 or IIS to reconfigure the current loop.
This command can be used to reset the system after the repair of a cable fault.

2.2 Field unit data


Field unit data is made available from the master station. The master station collects the data
asynchronously from the connected field units in the actuators on the 2 wire current loop. The field
units vary depending on the actuator in which they are fitted and the data available to report.
ƒ IQ and IQT actuators contain IQ field units
ƒ IQ analogue field units can only be fitted to IQ or IQT actuators in addition to the IQ field unit
ƒ A, AQ and Q range actuators have Integral type field units
ƒ General Purpose field units are mounted away from the devices they control and can be set
to Actuator or General Purpose mode
ƒ Flowpak field units are used with pneumatic or hydraulic cylinder actuators
ƒ EH actuators contain EH field units, a derivative of the IQ field unit
ƒ Skilmatic SI actuators have SI field units, a derivative of the IQ field unit
ƒ ROMPAK actuators have a ROMPAK field unit similar to the Integral type field unit.

22 of 96 Publication S171E V1.1 Issue 11/2008


Serial Communications

In the interface sections that follow a series of abbreviations are used for the data bits. The information
on the exact reason for each data bit to be present is explained in the individual instruction manuals
for each field unit type. The list below provides a brief explanation of each of the major data bits listed.
Note that not all the bits are available from all the actuators and the list is a definition table only.

All data is present (1) when the state is true.

2.2.1 Digital status bits

ALARM There is an alarm present on this field unit


AUX 1 to AUX 4 Refers to the digital inputs available from an IQ/IQT actuator
BATT The IQ/IQT battery is low
DIN1 to DIN8 Digital inputs 1 to 8 on a general purpose field unit
EXT The external contact on an AQ or Q actuator is closed. This is not available if
the actuator has to report actual percentage position data
LBON Loopback on asserted on this field unit
MOVE IQ/IQT actuator centre column moving
MRO and MRC Motor running in the open (MRO) / close (MRC) direction
MRUN The actuator motor is running
NALARM There is a new, unread, alarm on this field unit
OAS and CAS The actuator open limit switch (OAS) and close limit switch (CAS) made
Remote Actuator local/remote selector in the remote position
STOP (reported data) Actuator stationary in mid position
TRO and TRC Actuator travelling towards the open (TRO) position or closed (TRC) position
Travelling Actuator in motion

2.2.2 Alarm data bits

AUXOR On an IQ/IQT actuator this indicates that one of the auxiliary inputs is active
CNA Actuator remote control not available because the local/local stop/remote
selector is not in the remote position
COMMS Communication failure between master station and field unit
EOT Actuator continues to run the motor beyond the end of travel limit switch
LOCAL IQ/IQT Actuator local/local stop/remote selector in the local position
Low Press Low hydraulic or pneumatic pressure on a Flowpak actuator
LSTOP Local/local stop/remote selector in the Local Stop position
MEMF Memory chip fault
MMOVE Manual movement of the valve detected
MOP and MCL Actuator has reached the open (MOP) or close (MCL) position due to manual
movement of the handwheel. MOP is manually opened, MCL is manually closed
MOPG and MCLG Actuator has left the close position (MOPG) or the open position (MCLG) due to
manual movement of the handwheel. MOPG is manual opening of the valve
and MCLG is manual closing of the valve

MREL Actuator monitor relay tripped. The monitor relay is a combination signal for the

Publication S171E V1.1 Issue 11/2008 23 of 96


Pakscan P3 with P720 Module Modbus Interface Specification

thermostat, local stop or local signals being present in electric actuators. In


hydraulic or pneumatic actuators the signal is a combination of loss of pressure
or local or off selected on the local/remote selector
OFF Local/off/remote selector on a Flowpak actuator in the ‘off’ position
POWR Field unit power on reset alarm
SFAIL Actuator fails to start or stop when expected to do so
THERM Actuator thermostat tripped
FAULT EH or SI actuator general fault indication
VJAM Valve jammed at end of travel causing a torque trip
VOBS Obstructed valve causing actuator to torque trip in mid travel
VTT On an IQ/IQT only this indicates valve travel time exceeded

2.2.3 Field unit commands

The actuators on the loop can be commanded to open, close, or stop by writing to the appropriate
location in the data base. In all cases, there is no requirement to cancel a command to remove it. A
new command will always remove any existing commands.

IQ and IQT actuators are capable of adopting an analogue position (0-100%). Note that A, AQ, Q and
ROMPAK actuators may require additional parts before they can provide this capability. Writing an
analogue position to the appropriate register cancels any existing command. Writing an
open/stop/close command will cancel any analogue setting previously made.

General purpose field units can have their relay outputs operated (energised or de-energised) and
additionally they have an analogue output signal. Similar to actuator commands, with the GPFCU
relays there is no requirement to cancel a command to remove it unless the relay outputs have been
set to ‘Maintained’ action within the field unit.

OPEN Causes the actuator to move to the open position


STOP Causes the actuator to stop
CLOSE Causes the actuator to move to the close position
ESD Causes the actuator to adopt the internally set Emergency Shut Down position
(which may be open. close or stay put)
Position Control Writing a value to the valve desired position causes the actuator to adopt the
desired position. This method of intermediate positioning must be used for
modulating duty. The use of a ‘move and stop’ type of control will not be
successful as the current loop network timing is not deterministic
RLY1 to RLY4 Writing to these locations causes the relay to energise or de-energise
depending on the data written. In general only a GPFCU will consider the
commands as operating relays. All other field units have logic outputs to the
actuator internal controls

‰ Pakscan P3 Command Filtering


The Pakscan 3 master station includes a command filter to reduce the replication of commands to a
field unit over the current loop interface. If a command sent over the serial or Ethernet links is
repeated within the time set in the filter, the second command will be discarded and only the first
command will be actioned. The effect is to remove unwanted field network commands from the system
and free up the maximum available time space for other valid commands or data retrieval from the
field.

24 of 96 Publication S171E V1.1 Issue 11/2008


Serial Communications

2.2.4 Field unit analogue inputs

There are several analogue inputs available from field units. Not all signals will be reported by all
actuators and the tables for each protocol indicate what is available from each type of actuator. In
particular A, AQ, Q and ROMPAK range actuators cannot report valve position unless they are fitted
with a potentiometer.

Valve position feedback Reports the actual valve position as a percentage of full travel
Pulse input This register from a GPFCU contains a counter value that increments on receipt
of inputs to DIN1
12-bit analogue input 1 On GPFCU’s and IQ Analogue field units there are two registers that report the
and 2 value of the analogue input connected. These are termed ‘12-bit’ since the input
signal is resolved to 12 bits (1 in 4096). The actual register value will vary in
accordance with the input signal over a range that depends on the protocol
selected
Historic torque profile On an IQ/IQT only, these registers have torque values measured at various
positions across the stroke of the valve
Instantaneous torque On an IQ/IQT only, this indicates the last torque value

Publication S171E V1.1 Issue 11/2008 25 of 96


Pakscan P3 with P720 Module Modbus Interface Specification

(This page is intentionally blank)

26 of 96 Publication S171E V1.1 Issue 11/2008


Modbus Specification

3 MODBUS SPECIFICATION

3.1 Electrical specification


Serial data Line Electrical Specification RS485 or RS232
Ethernet 10baseT

3.2 Outer protocol


Modbus Transmission Mode RTU (8-bit binary data)
Ethernet Modbus TCP/IP Server

3.3 Serial Data


Baud Rate
Pakscan IIS master station 2400, 4800, 9600, or 19200
Pakscan P3 master station 2400, 4800, 9600, 19200, 38400, 57600, or 115200
Number of bits per character:
start bits 1
data bits (LSB first) 8
parity (configurable) Odd, Even, None, Always 0
stop Bits 1

Error checking CRC

Modbus message turn round time


Minimum period between request and response 2400 16.00 mSec
(3.5 character period t3.5 according to the 4800 8.00 mSec
Modbus Serial Line Implementation Guide V1.02, 9600 4.00 mSec
fixed at 1.750 mSec above 19200) 19200 2.00 mSec
38400 1.75 mSec
57600 1.75 mSec
115200 1.75 mSec

Maximum period between request and response 100 00 mSec

The Modbus protocol supports two forms of data access Discrete (or Bit) and Register addressing.
The Function Code determines which form of addressing is to be used.

3.4 Overview of the design


Modbus commands may be transmitted to the Pakscan P3 or IIS master stations via Ethernet, RS232
or RS485 physical interfaces. Up to 32 master station modules may be linked on a single RS485
highway to one host port. Each Pakscan P3 master station Current Loop Interface permits up to 240
field units to be connected to it. The Pakscan IIS master station supports up to 32 field units

The master station responds as a MODBUS SLAVE or SERVER to messages from the host. The
serial ports can each use different data bases, whilst the two Ethernet ports must both use the same
data base and protocol. Within the master station the Modbus address that the master station will

Publication S171E V1.1 Issue 11/2008 27 of 96


Pakscan P3 with P720 Module Modbus Interface Specification

respond to is set using the front keypad or web pages and the protocol used on the particular port is
also set in the same way.

The master station maintains a sectioned data base covering all its connected field units, and the host
reads this data without the need to access field units directly. The master station main module
performs the functions of Data Concentrator and interface whilst the Current Loop module is the 2 wire
loop master.

Within the field units, data is organised into processing blocks. Each block performs a specific function
such as analogue scale and bias, characterised by a number of parameters. Modbus data locations
within the master station Current Loop module data base relating to itself or a field unit are calculated
by using the Block number, Parameter number, and field unit Address (see 4.3.3 Register and
Discrete Address Formulae).

Serial Port 1 Generic Data Base 1


EPLCG
Yokogawa
Honeywell SI
System
Generic Data Base 2 and
Serial Port 2 Network
EPLCG Data
Yokogawa
Honeywell SI
Ethernet Port 3
Generic Data Base 3
Ethernet Port 4 EPLCG
Yokogawa
Honeywell SI

Fig 16: Data base Connections

28 of 96 Publication S171E V1.1 Issue 11/2008


Generic and Honeywell EPLCG Protocols

4 GENERIC AND HONEYWELL EPLCG PROTOCOL INTERFACE


SPECIFICATION

This section describes the two protocols that allow access to the maximum amount of data within the
master station. The tables give locations for the data which may be read from either registers or
discrete locations, or in some cases, both. The Generic protocol has access to all the blocks and
parameters within the data base and is the most flexible choice. The Honeywell EPLCG protocol also
allows access to all the blocks and parameters and has been specially tailored to meet the
requirements of the Honeywell EPLCG gateway. Honeywell has approved this version as suitable for
connection to their gateway.

On the Pakscan IIS master station or the P3 Current Loop Option Module select 'GENERIC MODBUS'
for the Generic configuration of the data base or ‘HONEYWELL EPLCG’ for the EPLCG version of the
data base: the difference between these two choices is in the analogue data scaling only. Generic
uses 16-bit 2’s complement and EPLCG uses a 12-bit value in the register.

Care must be taken to ensure that the correct protocol is routed to the port being used for the
application concerned. Rotork’s own In-Vision system, for example, uses the Generic Modbus data
base. The Modbus address is used to gain access to the correct section of the data base for the field
unit whose data is to be collected. For a Pakscan IIS there is only one address to cover all its field
units, but with Pakscan 3 and the Current Loop module the Pakscan 2 base address does not cover
the whole range of field unit addresses. The lowest, or Base, Modbus address allows access to the
first 60 field units, the next address the next 60 field units and so on

4.1 Modbus unit address (Generic and Honeywell EPLCG protocols)


The first byte of all Modbus message frames is the Modbus Address byte. Modbus supports 248
addresses, of which value 0 is always allocated for Broadcast messages. This leaves 247 addresses
for use by connected devices on the Modbus data link. Each master station is configured with a
Modbus Base Address, which may be anywhere in the range 1 to 247.

Modbus Function Register or Number of Data CRC


Address Code Discrete Registers or Field Check
Address Bits

8 bits 8 bits 16 bits 16 bits N bits 16 bits

Fig 17: Modbus transaction format

The Pakscan IIS master station responds to the selected Modbus address. Each Pakscan P3 master
station Pakscan 2 Current Loop module will then respond to between 1 and 4 Modbus addresses
depending on how many field units it has been configured to support. Physically a P3 master station is
only one unit on the Modbus highway, but logically as far as the protocol is concerned it can appear to
be up to 4 units. Each logical unit supports up to 60 field units.

As far as Modbus is concerned, each unit behaves as an independent slave. Fig. 18 illustrates this
and Fig. 19 correlates the real field unit address with which logical master station unit it appears to be
attached. Users may find that when assigning Modbus addresses for use on the network, configuring

Publication S171E V1.1 Issue 11/2008 29 of 96


Pakscan P3 with P720 Module Modbus Interface Specification

the setting of the Base address of the master station using increments of 4 will ensure future
expansion space.
Physical arrangement
Modbus highway
P3 Pakscan P
3 P3 P3 P
3 P3 P3 Pakscan
IIE Loop Keyswitch IIE Loop

Master Standby Standby

Station Port A

Port B
A
Auto
B
Port A

Port B
Status Status
PS710 Pri/Stby PS720 PS730 PS720 PS710 Pri/Stby
Power Power
rotork Alarm rotork rotork rotork rotork rotork rotork Alarm

rotork
PS700
CPU/PSU
Port 1
Option 1 Option 2 Switch Option 2 Option 1 CPU/PSU Port 1

Port 2
CE A B
Port 2

Loop with up to
240 field units
Logical arrangement
Modbus highway

Master Station comms port

DATA BASE DATA BASE DATA BASE DATA BASE


Master Station Master Station Master Station Master Station
Base Address Base + 1 Base + 2 Base + 3
60 field units 60 field units 60 field units 60 field units

Data FCU 1 - 60 Data FCU 61 - 120 Data FCU 121 - 180 Data FCU 181 - 240

Loop with up to
240 field units
Fig 18: Pakscan P3 master station model – Generic and Honeywell EPLCG protocol

Field Unit Number of Modbus Addresses Modbus


Address Master Station Responds To Address

1 to 60 1 Base
61 to 120 2 Base + 1
121 to 180 3 Base + 2
181 to 240 4 Base + 3

Fig 19: Modbus address organisation


Examples:
Physical Field Unit address 10 is accessed as FCU No. 10 within Modbus Base address.
Physical Field Unit address 61 is accessed as FCU No. 1 within Modbus Base address +1.
Physical Field Unit address 165 is accessed as FCU No. 45 within Modbus Base address +2.

30 of 96 Publication S171E V1.1 Issue 11/2008


Generic and Honeywell EPLCG Protocols

4.2 Modbus function code support (Generic and Honeywell EPLCG protocols)
Details of Request and Reply formats are contained in the Modbus Reference Guide. The following
section deals with how Pakscan P3 and IIS master stations interpret the commands. Fig 20 lists the
supported Modbus commands.

Function Modbus Name Master Station Meaning Addressing


Code
01 Read coil status Read master station status Discrete
02 Read input status Read FCU status Discrete
03 Read holding registers Read master station status Register
04 Read input registers Read FCU status Register
05 Force single coil Discrete output Discrete
06 Preset single register Register output Register
08 Loopback diagnostic test
15 Force multiple coils Multiple discrete outputs Discrete
16 Preset multiple registers Multiple register outputs Register
17 Report slave ID

Error code Meaning

01 Illegal function code or incorrect message length


02 Illegal data address (Register address invalid)
06 Slave Device Busy (Pakscan P3 only)

Fig 20: Modbus function codes and error codes

To read data the function code to use will depend on whether the data is to be read as single bits or as
16 bit registers and also whether it is to be field unit or master station data. For example, code 01
reads master station data as discrete bits, whereas code 03 reads the same data as registers.
Discrete and Register access read the SAME data.

For Discrete access, the Discrete address field is interpreted as a Bit offset into the data base. For
Register access, the Register address field is interpreted as a Register location address in the data
base.

‰ Function Code 01 - Read Master Station Status (Bits)


Function code 01 is used to read discrete (bit) data from the data base to obtain information about the
master station itself.

Note: This function code is not generally supported for use in reading data from the data base for field
unit information. The exception is where the gateway is set up to read the data from the actuator
command open or close coils, for example prior to writing data, this is permitted by the master station.
However, the coils do not physically exist and the data read back by the host is the current status of

Publication S171E V1.1 Issue 11/2008 31 of 96


Pakscan P3 with P720 Module Modbus Interface Specification

the Open and Close limit switch in the actuator (OAS for an Open command and CAS for a Close
command). These signals may not reflect the state of the command coil. For example the actuator
may have been opened by a system command to the open coil and then closed manually. The coil for
open would be expected to be ‘on’, but the actuator will report the close coil as being ‘on’ since CAS
will be present, and the open coil as being ‘off’. In addition for actuator control all the write signals
become pulsed outputs at the field unit and the actuator responds to these pulse commands itself.

‰ Function Code 02 - Read FCU Status (Bits)


Within the master station, there are four sections of field unit data base, one for each group of 60 field
units. Access to each section is via a different Modbus slave address.

Function code 02 is used to read discrete (bit) data from the field unit data base to obtain information
about a field unit or group of field units. This function code is not supported for use in reading
information about the master station itself.

‰ Function Code 03 - Read Master Station Status and Read FCU Status (Registers)
Function code 03 is used to read register (16 bit) data from the data base to obtain information about
the master station itself. [This function code may also be used to read field unit data as Holding
Registers in the same way as function code 04.]

‰ Function Code 04 - Read FCU Status and Read Master Station Status (Registers
Within the master station, there are four sections of field unit data base, one for each group of 60 field
units. Access to each section is via a different Modbus slave address.

Function code 04 is used to read register (16 bit) data from the field unit data base to obtain
information about a field unit or group of field units. [This function code may also be used to read
master station data as Input Registers in the same way as function code 03.]

‰ Function Codes 05 and 06 - Write Single Coil or Register Outputs


Function codes 05 and 06 are used when data has to be written to the master station either for action
by a field unit (such as a command to open a valve) or by the master station itself (such as accept an
alarm).

Although function code 05 is legal for message transactions its effect is to write data in exactly the
same locations as function code 06 (all ‘outputs’ from the master station occupy a 16 bit location). The
calculation to determine the location for a data write using code 05 produces the same resultant
location as a calculation for a register write using code 06. There is no support for writing to discrete
data locations in the data base, all locations are registers.

If a Write request is to that part of the data base containing master station data, then the data is
written directly to that register.

32 of 96 Publication S171E V1.1 Issue 11/2008


Generic and Honeywell EPLCG Protocols

If the Write request is to that part of the data base relating to a field unit, then the information
contained in the message is translated into a command that a field unit understands and sent to the
field unit over the current loop network. The rate at which instructions are sent to the master station
should not exceed the rate at which they can be sent on to the field units.

The sequence of events is:


(1) - Write command received by the Master Station
(2) - Response sent back to Host
(3) - Write message sent to Field Unit

A good response to the Host indicates that the request was received correctly, the message length is
acceptable, and that the addressed field unit is on-line. It does not indicate that the write to the field
unit was successful. Confirmation of a successful write comes some time later when new data is
reported as a change in the main data base.

If commands are written at too high a rate then the current loop network is prevented from collecting
data from the field units and the system will appear to slow down. The Command Filter provides some
protection against too high a frequency of writing commands. It causes the system to ignore
duplicated commands to the same field unit if the duplicate is within the time setting for the filter.

‰ Function Code 08 - Loopback Diagnostic Test


The purpose of the Loopback Test is to test the communication system between the host and the
master station. Only Diagnostic sub-code 00 (Return Query Data) is supported.

‰ Function Code 15 and 16 - Write Multiple Outputs


Function codes 15 and 16 may be used when data has to be written to more than one register in the
master station either for action by a field unit (such as a command to open a valve) or by the master
station itself (such as accept an alarm).

Although function code 15 is legal for message transactions its effect is to write data in exactly the
same locations as function code 16 (all ‘outputs’ from the master station occupy a 16 bit location). The
calculation to determine the location for a data write using code 15 produces the same resultant
location as a calculation for a register write using code 16. As with single instructions there is no
support for writing data to discrete data locations, all locations are registers.

The master station is able to accept a single transaction multiple write message containing information
to be written to a maximum of 30 registers. These instructions are then passed to a queue for onward
transmission over the current loop network. The rate at which the data is written into the master station
must not exceed the rate at which it can be sent on to the field units. The command filter will remove
duplicated commands in the same way as for function code 01 writes.

In the case of actuator control there is never a need to write to turn a register or coil ‘off’ as the output
is always treated as a pulse. If commands to turn off registers are sent these will be obeyed by the
system with no actual result, the output already having turned off. The effect of sending these
unnecessary commands will be to congest the communication on the current loop network.

Publication S171E V1.1 Issue 11/2008 33 of 96


Pakscan P3 with P720 Module Modbus Interface Specification

‰ Function Code 17 - Report Slave ID


The response format is:
Byte count field -6
Slave ID field - 40
Runlight field - 255
Device dependent data (4 bytes) - HW version (16 bits)
- SW version (16 bits)

‰ Error Codes 01, 02 and 06


Error code 01 will be presented back to the host if the function code in the data message is not one of
those supported by the master station, or if the message length is incorrect.

Error code 02 will be presented back to the host if the Data Address is illegal; or if the write command
is a multiple write (code 15 or 16) where the number of coils or registers exceeds 30.

Error code 06 (02 in IIS) will also be sent back to the host if the master station has insufficient buffer
space to handle 30 coils or registers in a single transaction. Buffer space will become free as the
writes are issued to the loop and field units.

4.3 Data base access (Generic and Honeywell EPLCG protocols)


The total data base for the Pakscan system is distributed across all the connected master stations.
Each master station contains data base records relating to itself and the field units on the current loop
connected to it.

4.3.1 Data Organisation

The data base comprises a series of records organised into Blocks and Parameters. Each parameter
contains 16 bits of data. There are 32 Blocks each of 8 Parameters associated with data about the
master station itself and 32 Blocks each of 8 Parameters for each field unit on the current loop.

The data to be found in each record is listed in section 4.5 for master stations and in section 4.6 for
the field units.

4.3.2 Data Read Requests

If the request is for several registers, the address defines the start point for a group of Blocks and
Parameters. The contiguous records in these registers are either associated with the master station
itself, or with a GROUP of field units. This is particularly useful to collect, for example, the Alarm
information from all field units connected to one master station in a single Modbus transaction. The
alternative is to collect it with multiple transactions, one for each field unit address in use.

34 of 96 Publication S171E V1.1 Issue 11/2008


Generic and Honeywell EPLCG Protocols

4.3.3 Register and Discrete Address Formulae

The following formulae allow discrete and register addressing to be calculated. Section 3.5 and 3.6
should be referred to, to determine the meaning of particular bits and parameters.

To use these formulae, first decide which 'bits' and 'registers' of information need to be collected, and
which need to be written to. This will provide Field Unit, Block, Parameter, and Bit numbers that can be
used in the equations. Note that the Modbus address for the particular master station also has to be
known. (The FCU addresses will all be in the range 1-60 even if there are more than 60 field units
connected. The master station address increments for each successive group of 60 field units.) Next,
decide if register or discrete reads and writes are to be used and then determine the function code
applicable. Finally, calculate the relevant start point in the data base using the information below.

Modbus Slave Address = Master Station base address (for physical FU 1-60)

= Master Station base address + offset (for physical FU above 60)

‰ Function code 01: Read Master Station Status by Bits


Start Discrete = (128 x B) + (16 x P) + D see Note 1

‰ Function code 02: Read FCU Data by Bits – Only applies to Blocks 0 to 7
Start Discrete = (7680 x P) + (960 x B) + (16 x [N-1]) + D see Note 1

‰ Function code 03: Read Master Station Status by Register


Start Register = (8 x B) + P

‰ Function code 04: Read FCU Data by Register


Start Register = 256 + (480 x B) + (60 x P) + (N-1)

‰ Function code 05 or 15: Write Master Station Data by Single or Multiple Bits
Start Coil = (8 x B) + P see Note 2

‰ Function code 05 or 15: Write FCU Data by Single or Multiple Bits


Start Coil = 256 + (480 x B) + (60 x P) + (N-1) see Note 2

Publication S171E V1.1 Issue 11/2008 35 of 96


Pakscan P3 with P720 Module Modbus Interface Specification

‰ Function code 06 or 16: Write Master Station Data by Single or Multiple Register
Start Register = (8 x B) + P see Note 2

‰ Function code 06 or 16: Write FCU Data by Single or Multiple Register


Start Register = 256 + (480 x B) + (60 x P) + (N-1) see Note 2

In the formulae above, the following symbols are used:

N = FCU address (range 1 to 60)


B = Block number
P = Parameter number
D = Data bit number within parameter (register).

‰ Note 1 - Limited address range


This formula (reading discrete FCU data) has been carefully designed to allow for those Modbus hosts
that have a limited address range. Parameter 0 has the most useful data and is located near the top
end of the address field.

‰ Note 2 - Writing Data


The master station recognises write requests to both coils and registers. In the calculation of the
location of the coil or register to be written to, the start location is the same for both types of ‘write’.
The master station considers coils and registers to be the same; they are always a whole parameter.
There is no support for writing to an individual bit within a parameter.

Where multiple writes are used the maximum number that may be written in a single transaction is 30,
if the host attempts to write more than 30 or the internal buffer is full error code 02 is returned by the
master station and no action taken.

The rate at which data is written should not exceed the rate at which it can be transferred to the
current loop network.

‰ Note 3 - Address offsets

This table and the examples are for a typical Modbus implementation only. Check your system
documentation carefully.

The discrete and register addresses calculated in the formulae are those which should appear in the
messages as they are transmitted on the Modbus link to the master station. Some Modbus hosts
offset addresses as far as the user is concerned. In such cases, the address programmed by the user
into the host would be different from those calculated. Check Host system documentation carefully.

36 of 96 Publication S171E V1.1 Issue 11/2008


Generic and Honeywell EPLCG Protocols

Typical offsets are:

Function Offset to be added to


Code formulae result

1 1
2 10001
3 40001
4 30001
5 1
6 40001

Examples:

1) Calculate a field unit bit address to read as 1920. Use function code 02, so add 10,001
to get the number to programme into the Host system. The result is 11921.

2) Calculate a master station bit address to write to as 5. Use function code 05, so add 1.
The result, which is the number to be programmed into the host system, is 6.

‰ Note 4 - FCU number in formulae


In the formulae the FCU addresses are the offsets within each section of the virtual data base.
Remember that a Pakscan P3 master station appears as 4 independent slaves (4 logical units) from a
Modbus point of view. Table 1 indicates how to decide FCU addresses for the calculations.

‰ Note 5 - Discrete addressing range


A discrete address needs to be 16 times the register address to access the same parameter. Because
of the limited size of the discrete address field in the Modbus message, discrete addresses can only
reach parameters associated with low number registers.

Publication S171E V1.1 Issue 11/2008 37 of 96


Pakscan P3 with P720 Module Modbus Interface Specification

4.4 Notes on the use of the Generic and EPLCG Modbus protocol
Normally a Modbus host will be set up to cyclically read data representing key variables of the master
station and field units. It can do this using Read Register function codes (03 and 04), and Read
Discrete Status function codes (01 and 02).

Parameters may contain either digital (bit) information or analogue (register) information. For digital
records the Modbus discrete addressing commands are appropriate, whilst for analogue information
the Modbus register address commands should normally be used.

Register and Discrete addresses in this specification are the addresses that should be used within
messages on the Modbus data link. Modbus host software may need to be configured with addresses
that are 1 more than those which must appear on the link. This is due to the Host regarding addresses
as starting from 1, not 0.

Reading a group of registers in one transaction is more efficient than reading one register at a time.

Support for Modbus diagnostic code (function code 08) is provided, but it is not obligatory to use it.
.
The master station includes Alarm Accept logic with respect to field unit alarms. Alarms from field units
are automatically accepted by the master station (so the field unit can clear its alarm latches) and
latched within the master station. These alarms must be read by the Host and then accepted (with an
Alarm Accept write, to master station Block 0 Parameter 5), before they can clear.

4.4.1 Suggested Scan Cycle

The Host should be configured to scan data from the master station in the following order:

Read Alarm Status


Read Digital Status
Perform Alarm Accept
(Only strictly necessary if any new alarms have occurred)
Read Analogue Status
(If any analogue data is to be read)

Commands to field units may be fitted in as required.

In some applications it may be desirable to scan some items e.g. analogues, less frequently than
others. This is perfectly acceptable.

4.4.2 Writing to Coils

When writing to a coil the data field to turn off the coil has to be 0x0000. As the most common device
connected is an actuator whose action is controlled by a pulse output there is often no need to turn off
a coil that has previously been turned on. The output command from the DCS should, where possible,
use a pulse type output. When writing to a coil the data field to turn on the coil may be 0xFF00 or any
other non zero value.

38 of 96 Publication S171E V1.1 Issue 11/2008


Generic and Honeywell EPLCG Protocols

4.4.3 Readback of Holding Registers

The master station supports the reading of the data in the Holding Registers. This data may not
accurately reflect the state of the actuator as it could have been moved manually since the data was
written. The data is a 2’s complement 16 bit value (0x0000 – 0x7FFF in the case of the Generic
protocol or 0x0000 – 0x0FFF in the case of the Honeywell EPLCG). It is calculated from the actual
value used in the data transaction over the current loop network to the field unit. When ‘read back’ this
value may differ by 1 digit due to rounding errors in the calculation. The value sent to the field unit
when the register was written will be true. To establish the actual valve position the Input Register
relating to the field unit Measured Value should be read.

4.4.4 Alarm Handling

The serial communication ports on the master station are each served by their own independent data
base and alarm handling. The handling of alarms on one serial port does not reflect on the alarms of
any of the other serial ports unless the master station is set to Link the alarms. On a P3 system the
two Ethernet ports share another independent data base with its own alarm handling which is common
to both Ethernet ports.

In the data base there is a group of 16 bits of data defined as the 'Alarm Block' for each field unit, (for
example, 'COMMS' is an alarm bit). Similarly, there are System Alarms as listed in section 3.6, (for
example 'RAM test fail'). These data bits will all be latched by the master station if they should actually
occur. The master station will therefore capture a transient alarm and keep it in its data base ready for
the host to read it.

Any latched alarm from these data areas will only be reset on three subsequent conditions. Firstly the
alarm bit must be read by the host, secondly the alarm bit must be accepted by the host (this is done
by issuing an 'Alarm Accept'), and finally the source of the alarm itself must return to normal.

An example of the sequence would be:

Consider an Actuator Thermostat.

1. Thermostat gets hot and trips.


2. Host reads data bit for the thermostat for this actuator
3. Host issues Alarm Accept; this is registered by the system as applicable to the
Thermostat Trip alarm.
4. The data bit remains set until the actuator cools down.
5. Once cooled below the trip point the data bit returns to normal.

If the host does not read the Thermostat bit for this field unit then the bit will remain set for all time (in
this data base), even though the actuator cools down. Also if the host does not read this bit any Alarm
Accept will not allow the alarm to reset itself. Any alarm bit must be read before it is able to be
accepted.

If the alarms are read infrequently then the above procedure guarantees that the host will register any
and every alarm from the alarm block.

In addition to the alarm data for each field unit there is a 'Status Block'. These status locations also
contain information about the presence (or absence) of alarms in the Alarm Block.

Publication S171E V1.1 Issue 11/2008 39 of 96


Pakscan P3 with P720 Module Modbus Interface Specification

‰ 'Alarm' bit
For each field unit the 'Alarm' bit will be present if any of the source signals used to set bits in the
Alarm block are present. Notice that the Alarm bit is an OR function of any alarm before the latch for
that alarm. The 'Alarm' bit is latched and will not clear until it has been read, accepted and the source
of the alarm has returned to normal. In the example of the thermostat, the 'Alarm' bit will be set when
the thermostat is initially tripped.

‰ 'New Alarm' Bit


For each field unit 'New Alarm' will be present every time a new alarm is detected as occurring in the
field unit. However, every time an Alarm Accept is issued this data bit will be reset even if the alarm
itself is still present.

The purpose of this bit is to indicate to the Host that there is a new alarm to be read from the alarm
block.

‰ System Common Alarms


In the master station Block 0 Parameter 0, bit 2 will be set if any field unit has its own 'Alarm' bit set.
Thus the 'Common Field Unit Alarm' is set whilst any one field unit has an input actually in alarm, or if
there is a field unit off line that is therefore unable to communicate.

Block 0 Parameter 0, bit 3 contains a similar common data bit derived from the actuator 'Monitor
Relay' source signals.

4.4.5 Use of Alarm Bits

The host may be configured to read as many, or all, of the alarm block data bits as required. (Those
that are not being used will possibly fill up as alarms over the course of operating the Pakscan system;
this will not have any detrimental effect on the system.)

For the alarms that are used they will individually appear in the data locations being read, and by
means of the Alarm Accept process will transfer to the host. They will also reset themselves as they
return to normal providing they are read and accepted.

The 'Alarm' bit will inform the host that any alarm is present, even those not normally being identified
by the host as relevant. This bit may be used by the host as a flag that an alarm is currently present on
a field unit. The host must take care of latching these bits in its own alarm handling system. This bit is
analogous to a contact input that is self-resetting. As it is taken from before the internal latch, it is a
true statement of the current alarm situation on the field unit.

The 'New Alarm' bit may be used to indicate to the host that an alarm reading process is required, or
that an ‘Alarm Accept’ write is required. The New Alarm will by its very nature disappear once the
Accept is issued irrespective of the actual plant status as it has to be available for each new alarm.

40 of 96 Publication S171E V1.1 Issue 11/2008


Generic and Honeywell EPLCG Protocols

4.5 Master station data base (Generic and Honeywell EPLCG protocols)
The discrete and register numbers listed in the tables all start from '0', for example register
40000 would be referenced as 0000 in the serial transaction message and not as 0001.

4.5.1 Master Station Read Only Data

This set of registers exists in each of the four 'logical' master stations that exist within a single physical
master station. The Modbus address used in transactions must be the master station Base address.
Reading data from any one of the addresses is the same as any other as all four contain the same
data. All the location numbers listed in this appendix are decimal numbers and zero based.

BLOCK 0 – Read Only Data (accessed with Modbus function code 01, 03 or 04) Register
Location
Parameter 0 – System Status and Alarm 0
Discrete
Location
Bit 0 Loopback in Progress 0
Bit 1 Loopback in Use 1
Bit 2 Common Field Unit Alarm 2
Bit 3 Common Actuator Alarm 3
*= Bit 4 0 = A side, 1 = B Side 4
Bit 5 ESD Mode 5
Bit 6 Reserved 6
*= Bit 7 1 = Primary, (In Use), 0 = Standby, (Out of Use) 7
Bit 8 Failure On Start-up 8
Bit 9 Reserved 9
Bit 10 Power On Reset 10
Bit 11 Watchdog Fail 11
Bit 12 Auto-Loopback Occurred 12
= Bit 13 Field Unit in Comms Fail 13
*= Bit 14 P3 Master Station ‘A’ OK (main unit, left side) 14
*= Bit 15 P3 Master Station ‘B’ OK (standby unit, right side) 15
Register
Location
Parameter 1 - FCU on loop to Scan Up To 1
Data = XXXX, Highest FCU Address
Parameter 2 - Loop Baud Rate Code 2
1 = 110 Baud
2 = 300 Baud
3 = 600 Baud
4 = 1200 Baud
5 = 2400 Baud
6 = 4800 Baud
Parameter 3 - Loop Scan Count 3
Data = Counter Value

Note: Data bits marked * are not relevant to single Pakscan P3 master stations
= are not relevant to Pakscan IIS master stations

Publication S171E V1.1 Issue 11/2008 41 of 96


Pakscan P3 with P720 Module Modbus Interface Specification

BLOCK 0 – Read Only Data (accessed with Modbus function code 01, 03 or 04) Register
Location
Parameter 4 - Loop Fault Information 4
Bits 15-12 Loop Address Faults
Bit 15 0 = Port A, 1 = Port B
Bit 14 Duplicate Address found
Bit 13 Address Too High found
Bit 12 Zero Address found
Bit 11-8 Loop fault type
5 = Loop open circuit
6 = Loop short circuit
Bits 7-0 Reason why loop last configured
1 = Reset occurred
2 = FCU found at address zero
3 = FCU found at too high address
4 = Two FCU's at same address found
5 = Loop fault on outward wire (loop complete)
6 = Loop fault found on A side (LB's in use)
7 = Loop fault found on B side (LB's in use)
8 = Test of 'return' wire failed
9 = Loop configure command received
Parameter 5 - Field Unit Address Fault data 5
Bits 15-8 Loop position of address fault
Bits 7-0 Offending address
Parameter 6 - Loop Configuration Progress 6
1 = Wait for loopbacks 1
2 = Find FCU's on Port A
3 = Test loop
4 = Find FCU's on Port B
5 = Wait for loopbacks 2
6 = Loopbacks off on Port A
7 = Loopbacks off on Port B
8 = Program Baud Rate on Port A
9 = Program Baud Rate on Port B
Parameter 7 – Number of FCU’s found in Loop Configuration 7
Bits 8-15 Number of FCU’s on Port B
Bits 0-7 Number of FCU’s on Port A

BLOCK 1 to 15 – Read Only Data (accessed with function code 01, 03 or 04) Register
Location
Parameter 0-7 FCU Map 0008
240 8-bit fields with the address of each field unit connected in the order in which they to 0127
are connected, e.g.
Block 1 Parameter 0
Bits 8 to 15 Address of first FCU
Bits 0 to 7 Address of second FCU

42 of 96 Publication S171E V1.1 Issue 11/2008


Generic and Honeywell EPLCG Protocols

BLOCK 16 to 30 – Read Only Data (accessed with function code 01, 03 or 04) Register
Location
Parameter 0-7 FCU Failure Counts 0128
240 8-bit fields with the failure count for one FCU. Incremented on each comms failure. to 0247
e.g.
Block 16 Parameter 0
Bits 8 to 15 Failure count for FCU 1
Bits 0 to 7 Failure count for FCU 2

BLOCK 31 - Read Only Data (accessed with Modbus function code 01, 03 or 04) Register
Location
Parameter 0 – Command Filter timeout (seconds), default value depends on loop speed 248
Loop speed: 110 baud Filter Time: 60 seconds
300 30
600 15
1200 10
2400 5
Parameter 1 - Master Station Type 249
1 = Pakscan IIE
2 = Pakscan IIS
3 = Pakscan 3
Parameter 2 - Master Station Type 250
Identifies the number of channels and if unit is Hot Standby
Bits 8-15 1 = single unit, 2 = hot standby
Bits 0-7 0 = 32 channel
1 = 60 channel
2 = 120 channel
3 = 180 channel
4 = 240 channel
Parameter 3 - Loop Interface card Software Version Number (see note below) 251
Parameter 4 - FCU’s in Loopback at FCU (x) and FCU (y) [zero = none present] 252
Bits 0-7 = FCU (x)
Bits 8 - 15 = FCU (y)
Parameter 5 - Loop Test Speed 253
Bits 0-7 1 = 110 baud
2 = 300 baud
3 = 600 baud
4 = 1200 baud
5 = 2400 baud
Parameter 6 - Loop Test Result in Percent 0000-0x0064) 254
Parameter 7 - FCU Data Upload Progress 255
0 = FCU data upload not started
255 = FCU data upload complete
Other values indicate FCU currently being read

Publication S171E V1.1 Issue 11/2008 43 of 96


Pakscan P3 with P720 Module Modbus Interface Specification

Note on software version numbers:


Software version numbers should be interpreted as 4 digits stored within the register. Bits 15 to
8 contain the major release number and bits 7 to 0 contain the minor release number e.g.
0x0156 will be version 01.5.6

4.5.2 Master Station Write Only Data

Only a few addresses accept 'writes' from a Modbus host. All except those listed below return an error
code. The ‘written’ data may be any value (except zero) to achieve the desired action. The master
station considers all writes to be to registers, even when a ‘coil’ function code command is used.

BLOCK 0 - Write Only Data (accessed with Modbus function code 05, 15, 06 or 16) Register
Location
Parameter 3 - Reconfigure Loop 3
Data = any non-zero value to reconfigure
Parameter 4 - Change Main to Standby and vice versa * 4
Data = any non-zero value to change
Parameter 5 - Alarm Accept 5
Data = any non-zero value to Accept
Parameter 6 - Send ESD Command on Loop 6
Data = any non-zero value to send ESD

BLOCK 31 - Write Only Data (accessed with Modbus function code 05, 15, 06 or 16) Register
Location
Parameter 7 – Start FCU Data Upload 255
Data = any non-zero value to start upload

Attempting to read back from these locations will result in reading the ‘read only’ data and will not give
a value for these locations.

Writing a command to Parameter 4, marked *, is only applicable to a Pakscan P3 master station.

44 of 96 Publication S171E V1.1 Issue 11/2008


Generic and Honeywell EPLCG Protocols

4.6 Field unit data base (Generic and Honeywell EPLCG protocols)
Data within the Pakscan system is organised in Blocks and Parameters relating to specific functions or
activities within the FCU on the current loop (e.g. Digital inputs, Alarms, Position control). Each FCU
supports up to 32 blocks with each block containing eight 16-bit parameters though not all these
blocks contain relevant data. The master station maintains the data base for all the field units on the
current loop without the need for any action from the host. This section details the use of these blocks
and parameters in the transfer of data between the Master Station and Host computer.

Within the field unit data base certain areas are restricted to Read Only (RO), others to Write Only
(WO), and some that may be both Read and Write (R/W).

When reading data it is permissible to use either Function code 02 for single discrete bits (or multiple
bits), or Function code 04 for register (or multiple registers) for any data within the data base. It is
usual to use register reads where the data is an analogue value. A group of 16 bits in 1 parameter
may be read as a register.

When writing data all locations are treated as registers. Function codes 05, 15, 06, or 16 may be used
and the location to which data is written is always the register location. For relay outputs the data to
turn off a relay is always 0000h and any non-zero value will turn the relay on. For example values of
0001h, FF00h, or 00FFh will all energise the relay.

The registers are transmitted Most Significant Data Byte first.

‰ Digital Inputs
Each field unit has direct digital inputs from the connected actuator and the status is reported in the
Digital Input Block (Block 2 Parameter 0). The block also contains indication of any alarms present in
the Alarm block.

‰ Alarm Block
The Alarm Block holds data about alarms either directly connected to the field unit, or logically derived
from the status of all the inputs. These Alarms data bits are individually latched by the master station
and will not return to normal until both the source alarm condition is corrected and the alarm is both
'read' and 'accepted' by the host.

‰ Analogue and Counter Input Data


The field unit will report analogue or counter values to the master station only when the measurement
changes by an amount that exceeds the 'Deviation' setting by 1 digit, or the 'Update Timeout' period
has expired. These parameters are adjusted locally within the field unit itself, and included in the
system to ensure that analogue reporting only occurs when necessary. The host computer has access
to the last reported analogue value in the master station.

‰ Outputs
The master station transfers both digital and analogue outputs from the host computer directly to the
connected field unit. There are no registers holding output data present within the master station itself.

Publication S171E V1.1 Issue 11/2008 45 of 96


Pakscan P3 with P720 Module Modbus Interface Specification
‰ Field Unit Types Available
46 of 96

IQ/IQT Actuator IQ Actuator or IQT actuator


INTEGRAL Actuator control integral to the actuator
GPFCU (GP) General Purpose version of GPFCU
GPFCU (Act) Actuator Control version of GPFCU
Flowpak Integral Flowpak controlled pneumatic/hydraulic actuator
IQ Analogue Analogue input card for IQ’s only
EH EH actuator
Skil Skilmatic SI actuator

‰ Key to Symbols Used


RO Read Only
Publication S171E V1.1 Issue 11/2008

R/W Read / Write


WO Write Only
Y Item supported for this type of Field Unit
R Reserved for internal or future use
BLANK A Blank entry indicates that the item is not supported for that Field Unit type. Reads of that item generally
return zero.
Register Location The decimal number of the register for FCU address 1, 2 and 60, for the parameter indicated.
Discrete Location The decimal number of the discrete bit for FCU address 1, 2 and 60, for the parameter and bit indicated.

4.6.1 Field Unit Data Base Locations

Read
Write FCU Type Data Location
IQ/IQT A, AQ, Q, GPFCU GPFCU Flowpak EH SKIL IQ FCU 1 FCU 2 to FCU 60
Actuator ROMPAK (GP) (ACT) Integral Analogue

Block 0 - FCU Type Block


(accessed with Modbus function code 02, 03 or 04) Register Location
Parameter 0 - 7 - R R R R R R R R 256 257 - 735

Block 1 - FCU Block


(accessed with Modbus function code 02, 03 or 04) Register Location
Parameter 0 - 7 - R R R R R R R R 736 737 - 1215
Read
Write FCU Type Data Location
IQ/IQT A, AQ, Q, GPFCU GPFCU Flowpak EH SKIL IQ FCU 1 FCU 2 to FCU 60
Actuator Integral (GP) (ACT) Integral Analogue

Block 2 – Digital Input Block


(accessed with Modbus function code 02, 03 or 04) Register Location
Parameter 0 RO Y Y Y Y Y Y Y Y 1216 1217 - 1275
Discrete Location
Bit 0 RO AUX 1 R DIN 1 R R AUX 1 AUX 1 R 1920 1936 - 2864
Bit 1 RO AUX 2 R DIN 2 R R AUX 2 AUX 2 R 1921 1937 - 2865
Bit 2 RO OAS OAS DIN 3 OAS OAS OAS OAS R 1922 1938 - 2866
Bit 3 RO CAS CAS DIN 4 CAS CAS CAS CAS R 1923 1939 - 2867
Publication S171E V1.1 Issue 11/2008

Bit 4 RO STOP STOP DIN 5 STOP STOP STOP STOP R 1924 1940 - 2868
Bit 5 RO MOVE MRUN DIN 6 MRUN Travelling Travelling Travelling R 1925 1941 - 2869
Bit 6 RO MRO MRO DIN 7 MRO TRO TRO TRO R 1926 1942 - 2870
Bit 7 RO MRC MRC DIN 8 MRC TRC TRC TRC R 1927 1943 - 2871
Bit 8 RO AUX 3 EXT R EXT R AUX 3 AUX 3 R 1928 1944 - 2872
Bit 9 RO AUX 4 R R R R AUX 4 AUX 4 R 1929 1945 - 2873
Bit 10 RO LBON LBON LBON LBON LBON LBON LBON LBON 1930 1946 - 2874
Bit 11 RO NALRM NALRM NALRM NALRM NALRM NALRM NALRM NALRM 1931 1947 - 2875

Generic and Honeywell EPLCG Protocols


Bit 12 RO ALRM ALRM ALRM ALRM ALRM ALRM ALRM ALRM 1932 1948 - 2876
Bit 13 RO BATT R R R R R R R 1933 1949 - 2877
Bit 14 RO R R R R Remote R R R 1934 1950 - 2878
Bit 15 RO R R R R R R R R 1935 1951 - 2879
Register Location
Parameter 1 - 7 - R R R R R R R R 1276 1277 - 1695

Key to Digital Input Labels: Note: When using the GPFCU (GP) for pump
AUX 1-4 - Aux Input 1-4 TRO - Travelling open direction control the following arrangement is used:
OAS - Open limit switch TRC - Travelling close direction DIN1 - Represents Monitor2
CAS - Close limit switch DIN 1 to 8 - Digital inputs 1 to 8 DIN2 - Represents Monitor3
STOP - Actuator stopped in mid travel EXT - External contact input DIN3 - Represents Motor Running
MOVE - IQ/IQT valve moving LBON - Loopback on DIN4 - Not assigned
MRUN - Motor running NALM - New alarm flag DIN5 - Represents Motor Stopped
47 of 96

MRO - Motor running open direction ALARM - Any alarm present on this FCU DIN6 - Represents Monitor1
MRC - Motor running close direction BATT - Battery Low Indication DIN7 & 8 - Not assigned
Travelling - Actuator moving Remote - Flowpak control, remote selected all other allocations are unchanged
Pakscan P3 with P720 Module Modbus Interface Specification
Read
48 of 96

Write FCU Type Data Location


IQ/IQT A, AQ, Q, GPFCU GPFCU Flowpak EH SKIL IQ FCU 1 FCU 2 to FCU 60
Actuator Integral (GP) (ACT) Integral Analogue

Block 3 – Alarm Block


(accessed with Modbus function code 02, 03 or 04) Register Location
Parameter 0 RO Y Y Y Y Y Y Y Y 1696 1697 - 1755
Discrete Location
Bit 0 RO MEMF MEMF MEMF MEMF MEMF MEMF MEMF MEMF 2880 2896 - 3824
Bit 1 RO COMMS COMMS COMMS COMMS COMMS COMMS COMMS COMMS 2881 2897 - 3825
Bit 2 RO LOCAL CNA R CNA LOCAL LOCAL LOCAL LOCAL 2882 2898 - 3826
Bit 3 RO POWR POWR POWR POWR POWR POWR POWR POWR 2883 2899 - 3827
Publication S171E V1.1 Issue 11/2008

Bit 4 RO WDOG WDOG WDOG WDOG WDOG WDOG WDOG WDOG 2884 2900 - 3828
Bit 5 RO MREL MREL R MREL MREL MREL MREL R 2885 2901 - 3829
Bit 6 RO THERM THERM R THERM Low Press FAULT FAULT R 2886 2902 - 3830
Bit 7 RO LSTOP LSTOP R LSTOP OFF LSTOP LSTOP R 2887 2903 - 3831
Bit 8 RO SFAIL SFAIL R SFAIL SFAIL SFAIL SFAIL R 2888 2904 - 3832
Bit 9 RO VOBS VOBS R VOBS VOBS VOBS VOBS R 2889 2905 - 3833
Bit 10 RO VJAM VJAM R VJAM VJAM VJAM VJAM R 2890 2906 - 3834
Bit 11 RO AUXOR MOP R MOP MOP AUXOR AUXOR R 2891 2907 - 3835
Bit 12 RO VTT MCL R MCL MCL VTT VTT R 2892 2908 - 3836
Bit 13 RO R MOPG R MOPG R R R R 2893 2909 - 3837
Bit 14 RO MMOVE MCLG R MCLG MMOVE MMOVE MMOVE R 2894 2910 - 3838
Bit 15 RO EOT EOT R EOT R EOT EOT R 2895 2911 - 3839
Register Location
Parameter 1 - 7 - R R R R R R R R 1756 1757 - 2175

Key to Alarm Labels:


MEMF - RAM/ROM failure LSTOP - Local stop operated MCLG - Manual closing
COMMS - Comms fail OFF - Flowpak selected to Off EOT - Motor running end of travel
LOCAL - Actuator not in remote control SFAIL - Start/stop fail FAULT Fault relay, any fault present
CNA - Control not available VOBS - Valve obstructed
POWR - Power on reset VJAM - Valve jammed
WDOG - Watchdog fail MMOVE - Manual valve movement
MREL - Monitor relay MOP - Manual open
THERM - Thermostat trip MCL - Manual close
Low Press - Low pressure MOPG - Manual opening
Read
Write FCU Type Data Location
IQ/IQT A, AQ, Q, GPFCU GPFCU Flowpak EH SKIL IQ FCU 1 FCU 2 to FCU 60
Actuator Integral (GP) (ACT) Integral Analogue

Block 4 - Analogue Input Block - Valve Position Feedback


(accessed with Modbus function code 03 or 04) Register Location
Para’ 0 (MV) RO Y Y R Y Y Y Y R 2176 2177 - 2235
MV Range: Using Generic Protocol, 0x0000 = 0%, 0x7FFF = 100% position
Using EPLCG Protocol, 0x0000 = 0%, 0x0FFF = 100% position
Parameter 1 - 7 - R R R R R R R R 2236 2237 - 2655

Block 5 – Position Control Block – Valve Desired Position


Publication S171E V1.1 Issue 11/2008

(accessed with Modbus function code 03 or 04, writes with 06 or 16) Register Location
Parameter 0 - R R R R R R R R 2656 2657 - 2715
Para’ 1 (DV) R/W Y Y R Y Y Y Y R 2716 2717 - 2775
DV Range: Using Generic Protocol, 0x0000 = 0%, 0x7FFF = 100% Desired pos’n
Using EPLCG Protocol, 0x0000 = 0%, 0x0FFF = 100% Desired pos’n
Parameter 2 – 7 - R R R R R R R R 2776 2777 - 3135

Block 6 – Digital Output Block

Generic and Honeywell EPLCG Protocols


(accessed with Modbus function code 02, 03 or 04, writes with 05, 15, 06 or 16) Register Location
Parameter 0 RO R R Y R R R R R 3136 3137 - 3195
Discrete Location
Bit 0 RO - - RLY4 - - - - - 5760 5776 - 6720
Bit 1 RO - - RLY1 - - - - - 5761 5777 - 6721
Bit 2 RO - - RLY3 - - - - - 5762 5778 - 6722
Bit 3 RO - - RLY2 - - - - - 5763 5779 - 6723
Bit 4 RO - - 0 - - - - - 5764 5780 - 6724
Bit 5 RO - - 0 - - - - - 5765 5781 - 6725
Bit 6 RO - - 0 - - - - - 5766 5782 - 6726
Bit 7 RO - - ACT (1) - - - - - 5767 5783 - 6727
Bit 8 to 15 - - - R - - - - - 5768-75 5784-91 - 6728-35
(1) Key: ACT = Relay action, 0 = Fleeting, 1 = Maintained
49 of 96
Pakscan P3 with P720 Module Modbus Interface Specification
Read
50 of 96

Write FCU Type Data Location


IQ/IQT A, AQ, Q, GPFCU GPFCU Flowpak EH SKIL IQ FCU 1 FCU 2 to FCU 60
Actuator Integral (GP) (ACT) Integral Analogue

Block 6 – Digital Output Block (Continued)


(accessed with Modbus function code 02, 03 or 04, writes with 05, 15, 06 or 16) Register Location
Parameter 1 - WO Y Y Y Y Y Y Y N 3196 3197 - 3255
Open
‘OPEN’ (Relay 2) : 0x0000 = De-energise 0xFF00 or any non-zero value = Energise relay
Parameter 2 - WO Y Y Y Y Y Y Y N 3256 3257 - 3315
Stop
‘STOP’ (Relay 3) : 0x0000 = De-energise 0xFF00 or any non-zero value = Energise relay
Publication S171E V1.1 Issue 11/2008

Parameter 3 - WO Y Y Y Y Y Y Y N 3316 3317 - 3375


Close
‘CLOSE’ (Relay 1) : 0x0000 = De-energise 0xFF00 or any non-zero value = Energise relay
Parameter 4 - WO Y Y Y Y Y Y Y N 3376 3377 - 3435
ESD
‘ESD’ (Relay 4) : 0x0000 = De-energise 0xFF00 or any non-zero value = Energise relay
Parameter 5 - 7 - R R R R R R R N 3436 3437 - 3615

Block 7 – Pulse Input Block


(accessed with Modbus function code 03 or 04) Register Location
Parameter 0 RO - - - Y - - - - 3516 3517 - 3675
Range: 0x0000 to 0x270F = Counter value
Parameter 1 – 7 - R R R R R R R R 3676 3677 - 4095

Block 8 – Reserved
Register Location
Parameter 0 - 7 - R R R R R R R R 4096 4097 - 4575
Read
Write FCU Type Data Location
IQ/IQT A, AQ, Q, GPFCU GPFCU Flowpak EH SKIL IQ FCU 1 FCU 2 to FCU 60
Actuator Integral (GP) (ACT) Integral Analogue

Block 9 – 12 bit Analogue Input 1 Block


(accessed with Modbus function code 03 or 04) Register Location
Parameter 0 RO - - Y - - - - Y 4576 4577 - 4635
An Input 1 Range: Using Generic Protocol, 0x0000 = 0%, 0x7FFF = 100%
Using EPLCG Protocol, 0x0000 = 0%, 0x0FFF = 100%
Parameter 1 - 7 - R R R R R R R R 4636 4637 - 5055

Block 10 – 12 bit Analogue Input 2 Block


Publication S171E V1.1 Issue 11/2008

(accessed with Modbus function code 03 or 04) Register Location


Parameter 0 RO - - Y - - - - Y 5056 5057 - 5115
An Input 2 Range: Using Generic Protocol, 0x0000 = 0%, 0x7FFF = 100%
Using EPLCG Protocol, 0x0000 = 0%, 0x0FFF = 100%
Parameter 1 - 7 - R R R R R R R R 5116 5117 - 5535

Block 11 – 12 bit Analogue Output Block


(accessed with Modbus function code 03, 04, 06 or 16) Register Location

Generic and Honeywell EPLCG Protocols


Parameter 0 R/W - - Y - - - - - 5536 5537 - 5595
An Output Range: Using Generic Protocol, 0x0000 = 0%, 0x7FFF = 100%
Using EPLCG Protocol, 0x0000 = 0%, 0x0FFF = 100%
Parameter 1 - 7 - R R R R R R R R 5596 5597 - 6015
51 of 96
Pakscan P3 with P720 Module Modbus Interface Specification
Read
52 of 96

Write FCU Type Data Location


IQ/IQT A, AQ, Q, GPFCU GPFCU Flowpak EH SKIL IQ FCU 1 FCU 2 to FCU 60
Actuator Integral (GP) (ACT) Integral Analogue

Block 12 – Historical Torque Profile – Opening Direction


(accessed with Modbus function code 03 or 04) Register Location
The IQ/IQT Actuator is able to report 8 torque values related to valve position across the valve stroke. Position 0 and 100% are not used as these may
be set to full torque for a torque seating valve. Torque readings are available for 6%, 19%, 31%, 44%, 56%, 69%, 81%, and 94% positions. Parameters
1-7 contain this data for the OPENING direction of travel - note they only update if a complete stroke of the valve is made and contain the last profile.
All are ranged as : Using Generic Protocol, 0x0000 = 0% rated torque, 0x7FFF = 120% rated torque
Using EPLCG Protocol, 0x0000 = 0% rated torque, 0x0FFF = 120% rated torque
Para’ 0 - 6% RO Y - - - - - - - 6016 6017 - 6075
Publication S171E V1.1 Issue 11/2008

Para’ 1 - 19% RO Y - - - - - - - 6076 6077 - 6135


Para’ 2 - 31% RO Y - - - - - - - 6136 6137 - 6195
Para’ 3 - 44% RO Y - - - - - - - 6196 6197 - 6255
Para’ 4 - 56% RO Y - - - - - - - 6256 6257 - 6315
Para’ 5 - 69% RO Y - - - - - - - 6316 6317 - 6375
Para’ 6 - 81% RO Y - - - - - - - 6376 6377 - 6435
Para’ 7 - 94% RO Y - - - - - - - 6436 6437 - 6495

Block 13 – Historical Torque Profile – Closing Direction


(accessed with Modbus function code 03 or 04) Register Location
The IQ/IQT Actuator is able to report 8 torque values related to valve position across the valve stroke. Position 0 and 100% are not used as these may
be set to full torque for a torque seating valve. Torque readings are available for 6%, 19%, 31%, 44%, 56%, 69%, 81%, and 94% positions. Parameters
1-7 contain this data for the CLOSING direction of travel - note they only update if a complete stroke of the valve is made and contain the last profile.
All are ranged as : Using Generic Protocol, 0x0000 = 0% rated torque, 0x7FFF = 120% rated torque
Using EPLCG Protocol, 0x0000 = 0% rated torque, 0x0FFF = 120% rated torque
Para’ 0 - 6% RO Y - - - - - - - 6496 6497 - 6555
Para’ 1 - 19% RO Y - - - - - - - 6556 6557 - 6615
Para’ 2 - 31% RO Y - - - - - - - 6616 6617 - 6675
Para’ 3 - 44% RO Y - - - - - - - 6676 6677 - 6735
Para’ 4 - 56% RO Y - - - - - - - 6736 6737 - 6795
Para’ 5 - 69% RO Y - - - - - - - 6796 6797 - 6855
Para’ 6 - 81% RO Y - - - - - - - 6856 6857 - 6915
Para’ 7 - 94% RO Y - - - - - - - 6916 6917 - 6975
Read
Write FCU Type Data Location
IQ/IQT A, AQ, Q, GPFCU GPFCU Flowpak EH SKIL IQ FCU 1 FCU 2 to FCU 60
Actuator Integral (GP) (ACT) Integral Analogue

Block 14 – Instantaneous Torque


(accessed with Modbus function code 03 or 04) Register Location
Parameter 0 RO Y - - - - - - - 6976 6977 - 7035
Inst. Torque Range: Using Generic Protocol, 0x0000 = 0%, 0x7FFF = 120%
Using EPLCG Protocol, 0x0000 = 0%, 0x0FFF = 120%
Parameter 1 - 3 - R R R R R R R R 7036 7034 - 7215
Parameter 4 RO Y - - - - - - - 7216 7217 - 7275
Torque Profile Counters
Publication S171E V1.1 Issue 11/2008

Data Bits 8-15 = Opening Torque Profile count


Data Bits 0-7 = Closing Torque Profile count
Parameter 5 - 7 - R R R R R R R R 7276 7277 - 7455

Block 15 to 31 – Reserved
Register Location
Block 15 Para 0 - R R R R R R R R 7456 7457 - 15615
-

Generic and Honeywell EPLCG Protocols


Block 31 Para 7
53 of 96
Pakscan P3 with P720 Module Modbus Interface Specification

4.7 Modbus messages examples (Generic and Honeywell EPLCG protocols)


Examples are included here to clarify the use of the Modbus protocol. These examples assume that
the master station base address is 01. All data in the message tables is in hexadecimal notation.

The register and discrete locations calculated by the earlier formulae all have a start point of 0 (zero),
hence the Modbus message location is the same as that calculated by the formulae.

4.7.1 Read Master Station Status

Master Station Block 0 Parameter 0, register location is 0000 decimal, and may be read with function
code 03, discrete locations are 0000-0015 decimal and may be read with function code 01.

Using Function Code 01: Modbus Function Discrete Number of CRC Check
Address Code Address Discretes
01 01 00 00 00 10 CRC

Using Function Code 03: Modbus Function Register Number of CRC Check
Address Code Address Registers
01 03 00 00 00 01 CRC

4.7.2 Write Master Station Alarm Accept

Master Station Block 0 Parameter 5, location 0005 decimal. Note that this is identified as a ‘write’
instruction by the function code used, which may be 05, 15, 06, or 16. The data written may be any
value, including zero, to accept the alarm. There is no need to ‘cancel’ the accept with a zero write.

Using Function Code 05: Modbus Function Coil Data CRC Check
Address Code Address
01 05 00 05 FF 00 CRC

Using Function Code 16: (multiple is ‘1’)

Modbus Function Register Quantity Byte Data CRC Check


Address Code Address Count
01 10 00 05 00 01 02 FF 00 CRC

4.7.3 Read Field Unit 12 Digital Status

Field unit digital status is in Block 2, Parameter 0. For FCU 12, the register location is 1227 decimal
(= 0x04CB), or discrete locations 2096 to 2111 decimal (= 0x0830 to 0x083F). The data may be read
with Function Code 02 or 04.

Using Function Code 02: Modbus Function Discrete Number of CRC Check
Address Code Address Discretes
01 02 08 30 00 10 CRC

Using Function Code 04: Modbus Function Register Number of CRC Check
Address Code Address Registers
01 04 04 CB 00 01 CRC

54 of 96 Publication S171E V1.1 Issue 11/2008


Generic and Honeywell EPLCG Protocols

4.7.4 Read Field Unit 62 Digital Status

Field Unit 62 is found in Modbus Address Base + 1 = 02 as it is above number 60. The data is located
in Block 2, Parameter 0. For FCU 62 the register location is as for FCU 02, 1217 decimal (= 0x04C1),
and discrete locations 1936 to 1951 decimal (= 0x0790 to 0x079F).

Using Function Code 02: Modbus Function Discrete Number of CRC Check
Address Code Address Discretes
02 02 07 90 00 10 CRC

Using Function Code 04: Modbus Function Register Number of CRC Check
Address Code Address Registers
02 04 04 C1 00 01 CRC

4.7.5 Read Digital Status from 60 Field Units, Addresses 121 to 180

Modbus Address = Base + 2 = 03. Data is in Block 2 Parameter 0. FCU 1 data starts in register 1216
decimal (= 0x04C0).
Modbus Function Register Number of CRC Check
Using Function Code 04: Address Code Address Registers
03 04 04 C0 00 3C CRC

4.7.6 Energise Command to OPEN relay of Field Unit 4

The OPEN relay for FCU 4 is located in Block 6 Parameter 1, register location 3199 decimal
(= 0x0C7F). Either Function code 05 or 06 can be used, but the location to be written to is always the
register number.
Modbus Function Address Data CRC Check
Using Function Code 05: Address Code
01 05 0C 7F FF 00 CRC

Using Function Code 06: Modbus Function Address Data CRC Check
Address Code
01 06 0C 7F FF 00 CRC

4.7.7 Write Desired Valve Position for FCU 26 to be 50%

The DV data is written to Block 5 Parameter 1, register 2741 decimal (= 0x0AB5) for FCU 26.
With Generic Protocol, 50% is 0x3FFF and with EPLCG Protocol, 50% is 0x07FF.

Using Function Code 06 Modbus Function Address Data CRC Check


and Generic Protocol Address Code
01 06 0A B5 3F FF CRC

Using Function Code 06 Modbus Function Address Data CRC Check


and EPLCG Protocol Address Code
01 06 0A B5 07 FF CRC

Publication S171E V1.1 Issue 11/2008 55 of 96


Pakscan P3 with P720 Module Modbus Interface Specification

(This page is intentionally blank)

56 of 96 Publication S171E V1.1 Issue 11/2008


Yokogawa and Honeywell SI Protocols

5 YOKOGAWA AND HONEYWELL SI PROTOCOL INTERFACE


SPECIFICATION

This section describes the two protocols that pack the field unit data in the tightest way. This allows
the host system to minimise the data traffic to and from the master station. The tables give register
and discrete locations in the master station from which the data may be read.

The Yokogawa protocol is recommended when interfacing between a Pakscan master station and a
Yokogawa Centum CS and ACM11 interface card, Centum XL, EFCD gateway and RS4 cards, or
similar system where the data packing is suitable. The protocol has been tested by Yokogawa in
Japan, Holland, and Singapore and found to successfully connect the Pakscan and Yokogawa
systems together. The protocol allows a standard Yokogawa SI22 faceplate to be used for the screen
displays associated with motor operated valves.

The Honeywell SI protocol is recommended for connection between the Pakscan master station and
the Honeywell SI gateway. Honeywell has tested and approved the SI version for connecting the
Pakscan system to a Honeywell TDC 3000 with an Advanced Process Manager and Serial Interface
Gateway, or similar system where the data packing is suitable.

On the Pakscan IIS master station or the P3 Current Loop Option Module select 'YOKOGAWA' for the
Yokogawa configuration of the data base or ‘HONEYWELL SI’ for the SI version of the data base: the
difference between these two choices is in the analogue data scaling only. Yokogawa uses 16-bit 2’s
complement and Honeywell SI uses an integer value in the register, all locations for the data are
identical. Care must be taken to ensure that the correct protocol is selected for the application
concerned.

The master station responds as a Modbus Slave to messages from the host. Each master station
responds to a single Modbus address. The serial ports can each use different data bases, whilst the
two Ethernet ports must both use the same data base and protocol

The master station maintains a data base covering all its connected field units, and the host reads this
data without the need to access field units directly. The master station performs the functions of Data
Concentrator, Protocol Converter, and 2 wire current loop master. Within the field units data is
organised in blocks. The data base locations listed in this section are the spaces from which and to
which this data is moved.

5.1 Modbus unit address (Yokogawa and Honeywell SI protocols)


The first byte of all Modbus message frames is the Modbus Address byte. Modbus supports 248
addresses, of which value 0 is always allocated for Broadcast messages. This leaves 247 addresses
for use by connected devices on the Modbus data link.

Modbus Function Register or Number of Data CRC


Address Code Discrete Registers or Field Check
Address Bits

8 bits 8 bits 16 bits 16 bits N bits 16 bits

Fig 21: Modbus transaction format

Publication S171E V1.1 Issue 11/2008 57 of 96


Pakscan P3 with P720 Module Modbus Interface Specification

Modbus
Address

0 Broadcast message Master station


data base

1
P3/IIS Master station Master station
| and up to 240 field units data
247 on current loop
Field unit
data

Fig 22: Modbus unit address structure – Yokogawa and Honeywell SI protocol

Each P3 Current Loop Option Card and IIS master station occupies a single Modbus address in which
all the data relating to itself and the connected field units is located. Modbus 'Read' requests return
field unit data from the data base in the appropriate master station; Modbus 'Write' requests are
translated into write commands which are sent to the field unit concerned.

Modbus Address Responding Master Station Interpretation


0 All Modbus Broadcast
1 1 Data base access
2 2 Data base access
| | |
247 247 Data base access

Fig 23: Modbus addressing for master stations

58 of 96 Publication S171E V1.1 Issue 11/2008


Yokogawa and Honeywell SI Protocols

5.2 Modbus function code support (Yokogawa and Honeywell SI protocols)


Details of Request and Reply formats are contained in the Modbus Reference Guide. The following
section deals with how Pakscan P3 and IIS master stations interpret the commands. Fig 24 lists the
supported Modbus commands.

Function Modbus Name Addressing


Code
01 Read coil status Discrete
02 Read input status Discrete
03 Read holding registers Register
04 Read input registers Register
05 Force single coil Discrete
06 Preset single register Register
08 Loopback diagnostic test
15 Force multiple coils Discrete
16 Preset multiple registers Register

Error code Meaning


01 Illegal function code or incorrect message length
02 Illegal data address (Register address invalid)
06 Slave Device Busy (Pakscan P3 only)

Fig 24: Modbus function codes and error codes

Within the master station there is one data base associated with each serial comms port and one
shared between the two Ethernet ports. All data read commands access these data bases.

‰ Function Code 01 - Read Coil Status Requests


Where the gateway is set up to read the data from the open or close coils, for example prior to writing
data, this is permitted by the master station. However the coils do not physically exist and the data
read back by the host is the current status of the Open and Close limit switch in the actuator (OAS for
an Open command and CAS for a Close command). These signals may not reflect the state of the
command coil. For example the actuator may have been opened by a system command to the open
coil and then closed manually. The coil for open would be expected to be ‘on’, but the actuator will
report the close coil as being ‘on’ since CAS will be present, and the open coil as being ‘off’. In
addition for actuator control all the write signals become pulsed outputs at the field unit and the
actuator responds to these pulse commands itself.

Publication S171E V1.1 Issue 11/2008 59 of 96


Pakscan P3 with P720 Module Modbus Interface Specification

‰ Function Code 02 - Read Input Status Requests


Any Input Status data within the master station may be read with a Code 02 Read request. The
returned data will be valid for the discrete locations chosen.

‰ Function Code 03 - Read Holding Register Requests


Holding registers are used for the location of Output registers. In the case of Pakscan systems these
output registers are used either to position a valve or for setting an analogue output. Where the
gateway is set up to read the data in a Holding register, for example prior to writing data, the master
station permits this. However, the data read back by the host may not be true.

In the case of reading the state of an output (holding) register the master station may not directly
reflect the current position of the attached field unit or actuator since the actuator may have been
moved manually or by a digital command since the analogue position was last sent. The data read
may not be valid, though it will be the last state written.

‰ Function Code 04 - Read Input Register Requests


Any register data within the master station may be read with a Code 04 Read request. The returned
data will be valid for the discrete locations chosen.

‰ Function Code 05 and 06 - Force Single Coil, Preset Single Register


If a Write request is to a discrete coil or register associated with the master station, then data is written
directly to that coil or register.

If the Write request is to a discrete coil or register associated with a Field Unit, then the information
contained in the message is translated into a command that a field unit understands. The command is
then sent to the field unit over the current loop network. The rate at which instructions are sent must
not exceed the rate at which they can be sent on to the field units.

The sequence of events is:


(1) - Write command received by the master station.
(2) - Response sent back to Host
(3) - Write message sent to Field Unit

A good response to the Host indicates that the request was received correctly, the message length is
acceptable, and that the addressed Field Unit is on-line. It does not indicate that the Write to the Field
Unit was successful. A successful write is confirmed some time later when new data is reported as a
change in the main data base.

If commands are written at too high a rate then the current loop network is prevented from collecting
data from the field units and the system will appear to slow down. The Command Filter provides some
protection against too high a frequency of writing commands. It causes the system to ignore
duplicated commands to the same field unit if the duplicate is within the time setting for the filter.

60 of 96 Publication S171E V1.1 Issue 11/2008


Yokogawa and Honeywell SI Protocols

‰ Code 08 - Loopback Diagnostic Test


The purpose of the Loopback Test is to test the communication system between the master station
and the gateway. The master station supports this test when used with diagnostic code 00, Return
Query Data. No other diagnostic test codes are supported.

‰ Code 15 and 16 - Force Multiple Coils, Preset Multiple Registers


If a Write request is to discrete coils or registers associated with the master station, then data is written
directly to those coils or registers.

If the Write request is to discrete coils or registers associated with Field Units, then the information
contained in the message is translated into a commands that field units understand. The command is
then sent to the field unit over the current loop network. The master station is able to accept a single
transaction multiple write message containing information to be written to a maximum of 30 coils or
registers. These instructions are then passed to a queue for onward transmission over the current loop
network. The rate at which instructions are sent must not exceed the rate at which they can be sent on
to the field units.

If commands are written at too high a rate then the current loop network is prevented from collecting
data from the field units and the system will appear to slow down. The Command Filter provides some
protection against too high a frequency of writing commands. It causes the system to ignore
duplicated commands to the same field unit if the duplicate is within the time setting for the filter.

In the case of actuator control there is never a need to write to a coil to turn it off as the output is
always treated as a pulse. The DCS control should be arranged for the outputs to be pulse type. If this
is not done the communication on the current loop network will carry unnecessary control commands
to ‘turn off’ coils that are already off.

‰ Error Codes 01, 02 and 06


Error code 01 will be presented back to the host if the function code in the data message is not one of
those supported by the master station or the message length is not as expected.

Error code 02 will be presented back to the host if the Data Address is illegal, OR if the write command
is a multiple write (code 15 or 16) where the number of coils or registers written to exceed 30.

Error code 06 (02 in IIS) will also be sent back to the host if the master station has insufficient buffer
space to handle 30 coils or registers in a single transaction. Buffer space will become free as the
writes are issued to the loop and field units.

Publication S171E V1.1 Issue 11/2008 61 of 96


Pakscan P3 with P720 Module Modbus Interface Specification

5.3 Data base access (Yokogawa and Honeywell SI protocols)


The data base is accessed by use of the Modbus address structure using Register Numbers or
Discrete Numbers in accordance with the Modbus standard. The data base contains information
collected from field units and is the data actually in the master station. Data transfers to and from the
field units are under the control of the P3 master station option card or Pakscan IIS master station.

5.3.1 Data Organisation

The data base comprises a series of records organised in accordance with the Modbus
documentation. Messages with function codes 01 to 06, 15 and 16 indicate specifically which locations
in the data base are to be accessed.

Function Codes 01, 05, and 15 refer to coils 0XXXX


Function Code 02 refers to discrete inputs 1XXXX
Function Code 04 refers to read only registers 3XXXX
Function Codes 03, 06, and 16 refer to registers 4XXXX

Coils are used for digital outputs. The status of maintained digital outputs should be read from discrete
status inputs and not from the coil itself. Data read back from a coil may not be valid.

Registers are used for all multiple bit signals (analogues and counters). Some are protected and may
only be read. Data read back from a Holding register with code 03 will contain the last data written to
that coil. It may not reflect the actual status of the register in the field unit.

The data in each record is listed in the following sections for both master stations for field units.

5.3.2 Data Interchange Requests

Data may be interchanged between the host and the master station data base using Modbus Register
or Discrete Numbers.

5.4 Notes on the use of the Yokogawa and Honeywell SI Modbus protocol
Normally the Modbus host will be set up to cyclically read data representing key variables of the
master station and field units. It can do this using Read Input Register function code 04, and Read
Discrete Status function code 02. In addition the gateway may be set to use function code 01 to read
Output Coils prior to a write (05) or code 03 to read Holding Registers prior to a write (06).

Register and Discrete address numbers referred to in the standard Modbus documentation all start
from number 1, though the actual data request on the data link takes its start as 0. The Modbus host
software may need to be configured with addresses that are 1 less than those listed in the tables
following. This is due to the Host regarding addresses as starting from 0, not 1. The actual method
used by the gateway is specified in its documentation.

The discrete and register numbers listed in the tables all start from '1', register 40001 would be
referenced as 0000 in the serial transaction.

62 of 96 Publication S171E V1.1 Issue 11/2008


Yokogawa and Honeywell SI Protocols

The data base is arranged to provide maximum efficiency in the use of the gateway space available
and reading a group of registers in one transaction is more efficient than reading one register at a
time. The Honeywell SI, because of the link to the APM Arrays may be easily set to collect multiple
data in a transaction. The Yokogawa gateway should be organised to use efficient data transfer at all
times. Note that the discrete bits may be moved in a minimum of 16 bits to the card working space.

The master station includes Alarm Accept logic with respect to field unit alarms. Alarms from field units
are automatically accepted by the master station (so the field unit can clear its alarm latches) and
latched within the master station. These alarms must be read by the Host and then accepted (with an
Alarm Accept write to coil 32) before they can clear.

5.4.1 Suggested Scan Cycle

The Host should be configured to scan data from the master station in the following order:

Read Alarm Status


Read Digital Status
Perform Alarm Accept
(only strictly necessary if any New Alarms have occurred)
Read Analogue Status
(if any analogue data is to be read)

Commands to Field Units may be fitted in as required.

In some applications it may be desirable to scan some items e.g. analogues, less frequently than
others. This is perfectly acceptable.

Within the master station area of the data base there are common alarm bits for loop fault, field unit
fault and actuator fault. These may be used as a quick way of checking for new alarms.

5.4.2 Writing to Coils

When writing to a coil the data field to turn off the coil has to be 0x0000. As the most common device
connected is an actuator whose action is controlled by a pulse output there is often no need to turn off
a coil that has previously been turned on. The output command from the DCS should, where possible,
use a pulse type output. When writing to a coil the data field to turn on the coil may be 0xFF00 or any
other non zero value.

5.4.3 Readback of Holding Registers

The master station supports the reading of the data in the Holding Registers. This data may not
accurately reflect the state of the actuator as it could have been moved manually since the data was
written. The data is a 2’s complement 16 bit value (0x0000 – 0x7FFF) in the case of the Yokogawa
protocol or a signed integer value (0-0x0064) in the case of the Honeywell SI. It is calculated from the
actual value used in the data transaction over the current loop network to the field unit. When ‘read
back’ this value may differ by 1 digit due to rounding errors in the calculation. The value sent to the
field unit when the register was written will be true. To establish the actual valve position the Input
Register relating to the field unit Measured Value should be read.

Publication S171E V1.1 Issue 11/2008 63 of 96


Pakscan P3 with P720 Module Modbus Interface Specification

5.4.4 Alarm Handling

The two serial communication ports on the master station are each served by their own independent
data base and alarm handling. The two Ethernet ports share a third independent data base. The
handling of alarms on one port does not reflect on the alarms of any of the other port.

In the data base there is a group of 16 bits (bits 13 to 28) of data defined as the 'Alarm Block' for each
field unit (for example 'COMMS' is an alarm bit).

Similarly there are System Alarms as listed in the master station data section, for example 'RAM test
fail'.

These data bits will all be latched by the master station if they should actually occur. The master
station will therefore capture a transient alarm and keep it in its data base ready for the host to read it.

Any latched alarm from these data areas will only be reset on three subsequent conditions. Firstly the
alarm bit must read by the host, secondly the alarm bit must be accepted by the host (this is done by
issuing an 'Alarm Accept'), and finally the source of the alarm itself must return to normal.

An example of the sequence would be:

Consider an Actuator Thermostat.


1. Thermostat gets hot and trips.
2. Host reads data bit (bit 19) for the thermostat for this actuator
3. Host issues Alarm Accept; this is registered by the system as applicable to the
Thermostat Trip alarm.
4. The data bit remains set until the actuator cools down.
5. Once cooled below the trip point the data bit returns to normal.

If the host does not read the thermostat bit for this field unit then the bit will remain set for all time,
even after the actuator cools down. In addition, if the host does not read this bit any Alarm Accept will
not allow the alarm to reset itself. Any alarm bit must be read before it is able to be accepted.

Even if the alarms are read infrequently, the above procedure guarantees that any alarm from the
alarm block will be registered by the host.

In addition to the alarm data for each field unit there is a 'Status Block'. These status locations also
contain information about the presence (or absence) of alarms in the Alarm Block.

‰ ‘Alarm’ Bit (bit 12)


For each field unit the 'Alarm' bit will be present if any of the source signals used to set bits in the
Alarm block are present. Notice that the Alarm bit is an OR function of any alarm before the latch for
that alarm. The 'Alarm' bit is latched and will not clear until it has been read, accepted and the source
of the alarm has returned to normal. In the example of the thermostat, the 'Alarm' bit will be set when
the thermostat is initially tripped.

64 of 96 Publication S171E V1.1 Issue 11/2008


Yokogawa and Honeywell SI Protocols

‰ ‘New Alarm’ Bit (bit 11)


For each field unit, 'New Alarm' will be present every time a new alarm is detected as occurring in the
field unit. However, every time an Alarm Accept is issued this data bit will be reset even if the alarm
itself is still present.

The purpose of this bit is to indicate to the Host that there is a new alarm to be read from the alarm
block.

‰ System Common Alarms


In the master station bit 10250 will be set if any field unit has its own 'Alarm' bit set. Thus the 'Common
Field Unit Alarm' is set whilst any one field unit has an input actually in alarm.

Bit 10251 contains a similar common data bit derived from the actuator 'Monitor Relay' source signals.

5.4.5 Use of Alarm Bits

The host may be configured to read as many, or all, of the alarm block data bits as required. Those
that are not being used will probably 'fill up' as alarms over the course of operating the system.
For the alarms that are used they will individually appear in the data locations being read, and by
means of the Alarm Accept process will transfer to the host. They will also reset themselves as they
return to normal provided they are read and accepted.

The 'Alarm' bit will inform the host that any alarm is present, even those not normally being identified
by the host as relevant. This bit may be used by the host as a flag that an alarm is currently present on
a field unit.

The 'New Alarm' bit may be used to indicate to the host that an alarm reading process is required, or
that an alarm accept is required. The New Alarm will by its very nature disappear once the Accept is
issued irrespective of the actual plant status as it has to be available for each 'new' alarm.

Publication S171E V1.1 Issue 11/2008 65 of 96


Pakscan P3 with P720 Module Modbus Interface Specification

5.5 Master station data base (Yokogawa and Honeywell SI protocols)

5.5.1 Master Station Records

The discrete and register numbers listed in the tables all start from '1', for example discrete
input 10001 would be referenced as 0000 in the serial transaction and not 0001.

‰ Digital Inputs – Read Only Data (accessed with Modbus function code 02)
Individual Bits - Discrete Locations (1 bit per)

Location Description Location Description

System Alarms System status and flags


10001 to 10240 Reserved 10248 Loopback in progress
10241 RAM test fail 10249 Loopback in use
10242 ROM test fail 10250 Common Field Unit alarm
10243 Power On Reset 10251 Common Actuator alarm
10244 Watchdog fail 10252 Master station A (Main) ok
10245 Auto loopback 10253 Master station B (Standby) ok
10246 Reserved 10254 Communicating to:
0 = Master station A (Left),
1 = Master station B (Right)
10247 Reserved 10255 1 = Primary (In Use), 0 = Standby
(Out of Use)

‰ Digital Outputs – Write function (accessed with Modbus function code 05 and 15)
Individual Bits - Discrete Locations (1 bit per)

When writing to a location the data field should comply with the Modbus instructions, although writing
any value (including zero) to these locations will cause the action to occur.

Function Action Location Description


Global ESD Trigger write to trigger ESD 0001 ESD
Change Master write to change over 0015 Change Master
System reconfiguration write to trigger 0016 Reset Loop
System/Comms Alarm Accept write to accept 0032 Alarm Accept

66 of 96 Publication S171E V1.1 Issue 11/2008


Yokogawa and Honeywell SI Protocols

5.6 Field unit data base (Yokogawa and Honeywell SI protocols)


The field unit data base is organised to present the same information from each sequential field unit
address in adjacent record entries. This general rule is broken only by the signals indicating valve
open (OAS) and valve closed (CAS), and the commands to 'Open' and 'Close' the valves. These
records are located adjacent to one another in pairs for each field unit.

As the field units may be of differing types, a Bit No., Relay No. or register description identifier is
attached, together with its IQ actuator meaning for each record group. The different Bit No., Relay No.
and register meanings are also listed for the different field unit types at the end of this section.

5.6.1 Digital Inputs (Field Units)

The discrete and register numbers listed in the tables all start from '1', discrete input 10001
would be referenced as 0000 in the serial transaction and not 0001.

‰ Read Only Data (accessed with Modbus function code 02)


Status - Adjacent Bits per Field Unit - Discrete locations (1 bit per)

Location Description Location Description

10257 Bit 3 FCU 1 (CAS) 10258 Bit 2 FCU 1 (OAS)


10259 Bit 3 FCU 2 (CAS) 10260 Bit 2 FCU 2 (OAS)
10261 Bit 3 FCU 3 (CAS) 10262 Bit 2 FCU 3 (OAS)
10263 Bit 3 FCU 4 (CAS) 10264 Bit 2 FCU 4 (OAS)
10265 Bit 3 FCU 5 (CAS) 10266 Bit 2 FCU 5 (OAS)
10267 Bit 3 FCU 6 (CAS) 10268 Bit 2 FCU 6 (OAS)
10269 Bit 3 FCU 7 (CAS) 10270 Bit 2 FCU 7 (OAS)
10271 Bit 3 FCU 8 (CAS) 10272 Bit 2 FCU 8 (OAS)
| |
| FCU 'N' Bit 3 = 10256 + 2N - 1 | FCU 'N' Bit 2 = 10256 + 2N
| |
10723 Bit 3 FCU 234 (CAS) 10724 Bit 2 FCU 234 (OAS)
10725 Bit 3 FCU 235 (CAS) 10726 Bit 2 FCU 235 (OAS)
10727 Bit 3 FCU 236 (CAS) 10728 Bit 2 FCU 236 (OAS)
10729 Bit 3 FCU 237 (CAS) 10730 Bit 2 FCU 237 (OAS)
10731 Bit 3 FCU 238 (CAS) 10732 Bit 2 FCU 238 (OAS)
10733 Bit 3 FCU 239 (CAS) 10734 Bit 2 FCU 239 (OAS)
10735 Bit 3 FCU 240 (CAS) 10736 Bit 2 FCU 240 (OAS)

Note that the information in these locations is also mapped to alternate locations starting 11217 (OAS)
and 11457 (CAS)

N = field unit address number in the range 1 to 240

Publication S171E V1.1 Issue 11/2008 67 of 96


Pakscan P3 with P720 Module Modbus Interface Specification

‰ Read Only Data (accessed with Modbus function code 02)


Status bits - Individual Bits per Field Unit - Discrete Locations (1 bit per)

Location Description Location Description Location Description

Bit 0 - AUX 1 Bit 1 - AUX 2 Bit 2 - OAS


10737 Bit 0 FCU 1 10977 Bit 1 FCU 1 11217 Bit 2 FCU 1
10738 Bit 0 FCU 2 10978 Bit 1 FCU 2 11218 Bit 2 FCU 2
10739 Bit 0 FCU 3 10979 Bit 1 FCU 3 11219 Bit 2 FCU 3
10740 Bit 0 FCU 4 10980 Bit 1 FCU 4 11220 Bit 2 FCU 4
| | |
| FCU 'N' Bit 0 = 10736 + N | FCU 'N' Bit 1 = 10976 + N | FCU 'N' Bit 2 = 11216 + N
| | |
10974 Bit 0 FCU 238 11214 Bit 1 FCU 238 11454 Bit 2 FCU 238
10975 Bit 0 FCU 239 11215 Bit 1 FCU 239 11455 Bit 2 FCU 239
10976 Bit 0 FCU 240 11216 Bit 1 FCU 240 11456 Bit 2 FCU 240

Bit 3 - CAS Bit 4 - STOP Bit 5 - MOVE


11457 Bit 3 FCU 1 11697 Bit 4 FCU 1 11937 Bit 5 FCU 1
11458 Bit 3 FCU 2 11698 Bit 4 FCU 2 11938 Bit 5 FCU 2
11459 Bit 3 FCU 3 11699 Bit 4 FCU 3 11939 Bit 5 FCU 3
11460 Bit 3 FCU 4 11700 Bit 4 FCU 4 11940 Bit 5 FCU 4
| | |
| FCU 'N' Bit 3 = 11456 + N | FCU 'N' Bit 4 = 11696 + N | FCU 'N' Bit 5 = 11936 + N
| | |
11694 Bit 3 FCU 238 11934 Bit 4 FCU 238 12174 Bit 5 FCU 238
11695 Bit 3 FCU 239 11935 Bit 4 FCU 239 12175 Bit 5 FCU 239
11696 Bit 3 FCU 240 11936 Bit 4 FCU 240 12176 Bit 5 FCU 240

Bit 6 - MRO Bit 7 - MRC Bit 8 - AUX3


12177 Bit 6 FCU 1 12417 Bit 7 FCU 1 12657 Bit 8 FCU 1
12178 Bit 6 FCU 2 12418 Bit 7 FCU 2 12658 Bit 8 FCU 2
12179 Bit 6 FCU 3 12419 Bit 7 FCU 3 12659 Bit 8 FCU 3
12180 Bit 6 FCU 4 12420 Bit 7 FCU 4 12660 Bit 8 FCU 4
| | |
| FCU 'N' Bit 6 = 12176 + N | FCU 'N' Bit 7 = 12416 + N | FCU 'N' Bit 8 = 12656 + N
| | |
12414 Bit 6 FCU 238 12654 Bit 7 FCU 238 12894 Bit 8 FCU 238
12415 Bit 6 FCU 239 12655 Bit 7 FCU 239 12895 Bit 8 FCU 239
12416 Bit 6 FCU 240 12656 Bit 7 FCU 240 12896 Bit 8 FCU 240

68 of 96 Publication S171E V1.1 Issue 11/2008


Yokogawa and Honeywell SI Protocols

‰ Read Only Data (accessed with Modbus function code 02)


Status bits - Individual Bits per Field Unit - Discrete Locations (1 bit per)

Location Description Location Description Location Description

Bit 9 - AUX4 Bit 10 - LBON Bit 11 - NALM


12897 Bit 9 FCU 1 13137 Bit 10 FCU 1 13377 Bit 11 FCU 1
12898 Bit 9 FCU 2 13138 Bit 10 FCU 2 13378 Bit 11 FCU 2
12899 Bit 9 FCU 3 13139 Bit 10 FCU 3 13379 Bit 11 FCU 3
12900 Bit 9 FCU 4 13140 Bit 10 FCU 4 13380 Bit 11 FCU 4
| | |
| FCU 'N' Bit 9 = 12896 + N | FCU 'N' Bit 10 = 13136 + N | FCU 'N' Bit 11 = 13376 + N
| | |
13134 Bit 9 FCU 238 13374 Bit 10 FCU 238 13614 Bit 11 FCU 238
13135 Bit 9 FCU 239 13375 Bit 10 FCU 239 13615 Bit 11 FCU 239
13136 Bit 9 FCU 240 13376 Bit 10 FCU 240 13616 Bit 11 FCU 240

Bit 12 - ALARM
13617 Bit 12 FCU 1
13618 Bit 12 FCU 2
13619 Bit 12 FCU 3
13620 Bit 12 FCU 4
|
| FCU 'N' Bit 12 = 13616 + N
|
13854 Bit 12 FCU 238
13855 Bit 12 FCU 239
13856 Bit 12 FCU 240

N = field unit address number in the range 1 to 240

Publication S171E V1.1 Issue 11/2008 69 of 96


Pakscan P3 with P720 Module Modbus Interface Specification

‰ Read Only Data (accessed with Modbus function code 02)


Alarm bits - Individual Bits per Field Unit - Discrete Locations (1 bit per)

Location Description Location Description Location Description

Bit 13 - MEMF Bit 14 - COMMS Bit 15 - LOCAL


13857 Bit 13 FCU 1 14097 Bit 14 FCU 1 14337 Bit 15 FCU 1
13858 Bit 13 FCU 2 14098 Bit 14 FCU 2 14338 Bit 15 FCU 2
13859 Bit 13 FCU 3 14099 Bit 14 FCU 3 14339 Bit 15 FCU 3
13860 Bit 13 FCU 4 14100 Bit 14 FCU 4 14340 Bit 15 FCU 4
| | |
| FCU 'N' Bit 13 = 13856 + N | FCU 'N' Bit 14 = 14096 + N | FCU 'N' Bit 15 = 14336 + N
| | |
14094 Bit 13 FCU 238 14334 Bit 14 FCU 238 14574 Bit 15 FCU 238
14095 Bit 13 FCU 239 14335 Bit 14 FCU 239 14575 Bit 15 FCU 239
14096 Bit 13 FCU 240 14336 Bit 14 FCU 240 14576 Bit 15 FCU 240

Bit 16 - POWR Bit 17 - WDOG Bit 18 - MREL


14577 Bit 16 FCU 1 14817 Bit 17 FCU 1 15057 Bit 18 FCU 1
14578 Bit 16 FCU 2 14818 Bit 17 FCU 2 15058 Bit 18 FCU 2
14579 Bit 16 FCU 3 14819 Bit 17 FCU 3 15059 Bit 18 FCU 3
14580 Bit 16 FCU 4 14820 Bit 17 FCU 4 15060 Bit 18 FCU 4
| |
| FCU 'N' Bit 16 = 14576 + N | FCU 'N' Bit 17 = 14816 + N | FCU 'N' Bit 18 = 15056 + N
| | |
14814 Bit 16 FCU 238 15054 Bit 17 FCU 238 15294 Bit 18 FCU 238
14815 Bit 16 FCU 239 15055 Bit 17 FCU 239 15295 Bit 18 FCU 239
14816 Bit 16 FCU 240 15056 Bit 17 FCU 240 15296 Bit 18 FCU 240

Bit 19 - THERM Bit 20 - LSTOP Bit 21 - SFAIL


15297 Bit 19 FCU 1 15537 Bit 20 FCU 1 15777 Bit 21 FCU 1
15298 Bit 19 FCU 2 15538 Bit 20 FCU 2 15778 Bit 21 FCU 2
15299 Bit 19 FCU 3 15539 Bit 20 FCU 3 15779 Bit 21 FCU 3
15300 Bit 19 FCU 4 15540 Bit 20 FCU 4 15780 Bit 21 FCU 4
| | |
| FCU 'N' Bit 19 = 15296 + N | FCU 'N' Bit 20 = 15536 + N | FCU 'N' Bit 21 = 15776 + N
| | |
15534 Bit 19 FCU 238 15774 Bit 20 FCU 238 16014 Bit 21 FCU 238
15535 Bit 19 FCU 239 15775 Bit 20 FCU 239 16015 Bit 21 FCU 239
15536 Bit 19 FCU 240 15776 Bit 20 FCU 240 16016 Bit 21 FCU 240

70 of 96 Publication S171E V1.1 Issue 11/2008


Yokogawa and Honeywell SI Protocols

‰ Read Only Data (accessed with Modbus function code 02)


Alarm bits - Individual Bits per Field Unit - Discrete Locations (1 bit per)

Location Description Location Description Location Description

Bit 22 - VOBS Bit 23 - VJAM Bit 24 - AUXOR


16017 Bit 22 FCU 1 16257 Bit 23 FCU 1 16497 Bit 24 FCU 1
16018 Bit 22 FCU 2 16258 Bit 23 FCU 2 16498 Bit 24 FCU 2
16019 Bit 22 FCU 3 16259 Bit 23 FCU 3 16499 Bit 24 FCU 3
16020 Bit 22 FCU 4 16260 Bit 23 FCU 4 16500 Bit 24 FCU 4
| | |
| FCU 'N' Bit 22 = 16016 + N | FCU 'N' Bit 23 = 16256 + N | FCU 'N' Bit 24 = 16496 + N
| | |
16254 Bit 22 FCU 238 16494 Bit 23 FCU 238 16734 Bit 24 FCU 238
16255 Bit 22 FCU 239 16495 Bit 23 FCU 239 16735 Bit 24 FCU 239
16256 Bit 22 FCU 240 16496 Bit 23 FCU 240 16736 Bit 24 FCU 240

Bit 25 - VTT Bit 26 - R Bit 27 - MMOVE


16737 Bit 25 FCU 1 16977 Bit 26 FCU 1 17217 Bit 27 FCU 1
16738 Bit 25 FCU 2 16978 Bit 26 FCU 2 17218 Bit 27 FCU 2
16739 Bit 25 FCU 3 16979 Bit 26 FCU 3 17219 Bit 27 FCU 3
16740 Bit 25 FCU 4 16980 Bit 26 FCU 4 17220 Bit 27 FCU 4
| | |
| FCU 'N' Bit 25 = 16736 + N | FCU 'N' Bit 26 = 16976 + N | FCU 'N' Bit 27 = 17216 + N
| | |
16974 Bit 25 FCU 238 17214 Bit 26 FCU 238 17454 Bit 27 FCU 238
16975 Bit 25 FCU 239 17215 Bit 26 FCU 239 17455 Bit 27 FCU 239
16976 Bit 25 FCU 240 17216 Bit 26 FCU 240 17456 Bit 27 FCU 240

Bit 28 - EOT
17457 Bit 28 FCU 1
17458 Bit 28 FCU 2
17459 Bit 28 FCU 3
17460 Bit 28 FCU 4
|
| FCU 'N' Bit 28 = 17456 + N
|
17694 Bit 28 FCU 238
17695 Bit 28 FCU 239
17696 Bit 28 FCU 240 N = field unit address number in the range 1 to 240

Publication S171E V1.1 Issue 11/2008 71 of 96


Pakscan P3 with P720 Module Modbus Interface Specification

‰ Read Only Data (accessed with Modbus function code 02)


Digital Inputs (Field Units) – Relay Coil Status (Applies to General Purpose Field Units only)

The following data locations contain the status of the output relays in the General Purpose field units.
These may be considered as 'status signals'. The state of the coil may be examined by using Function
Code 02 on a discrete by discrete basis. For writing data to relay coils see later.

Location Description Location Description Location Description

Relay 4 Coil Relay 1 Coil Relay 3 Coil


17697 Rly 4 FCU 1 17937 Rly 1 FCU 1 18177 Rly 3 FCU 1
17698 Rly 4 FCU 2 17938 Rly 1 FCU 2 18178 Rly 3 FCU 2
17699 Rly 4 FCU 3 17939 Rly 1 FCU 3 18179 Rly 3 FCU 3
17670 Rly 4 FCU 4 17940 Rly 1 FCU 4 18180 Rly 3 FCU 4
| | |
| FCU 'N' Rly 4 = 17696 + N | FCU 'N' Rly 1 = 17936 + N | FCU 'N' Rly 3 = 18176 + N
| | |
17934 Rly 4 FCU 238 18174 Rly 1 FCU 238 18414 Rly 3 FCU 238
17935 Rly 4 FCU 239 18175 Rly 1 FCU 239 18415 Rly 3 FCU 239
17936 Rly 4 FCU 240 18176 Rly 1 FCU 240 18416 Rly 3 FCU 240

Relay 2 Coil
18417 Rly 2 FCU 1
18418 Rly 2 FCU 2
18419 Rly 2 FCU 3
18420 Rly 2 FCU 4
|
| FCU 'N' Rly 2 = 18416 + N
|
18654 Rly 2 FCU 238
18655 Rly 2 FCU 239
18656 Rly 2 FCU 240

N = field unit address number in the range 1 to 240

72 of 96 Publication S171E V1.1 Issue 11/2008


Yokogawa and Honeywell SI Protocols

5.6.2 Digital Outputs (Field Units)

‰ Write Data (accessed with Modbus function code 05 and 15)


When writing outputs to the field units, to assert the command (energise the coil) write 0xFF00 (or any
data other than 0x0000). To remove the command (de-energise the coil) write 0x0000. Actuator
control commands never require to be turned off, so there is no need to write a de-energise command.

Commands - Adjacent coils per Field Unit - Coil locations (1 bit per)

Location Description Location Description

00033 Rly 1 FCU 1 (Close Cmd) 00034 Rly 2 FCU 1 (Open Cmd)
00035 Rly 1 FCU 2 (Close Cmd) 00036 Rly 2 FCU 2 (Open Cmd)
00037 Rly 1 FCU 3 (Close Cmd) 00038 Rly 2 FCU 3 (Open Cmd)
00039 Rly 1 FCU 4 (Close Cmd) 00040 Rly 2 FCU 4 (Open Cmd)
00041 Rly 1 FCU 5 (Close Cmd) 00042 Rly 2 FCU 5 (Open Cmd)
00043 Rly 1 FCU 6 (Close Cmd) 00044 Rly 2 FCU 6 (Open Cmd)
00045 Rly 1 FCU 7 (Close Cmd) 00046 Rly 2 FCU 7 (Open Cmd)
00047 Rly 1 FCU 8 (Close Cmd) 00048 Rly 2 FCU 8 (Open Cmd)
00049 Rly 1 FCU 9 (Close Cmd) 00050 Rly 2 FCU 9 (Open Cmd)
00051 Rly 1 FCU 10 (Close Cmd) 00052 Rly 2 FCU 10 (Open Cmd)
00053 Rly 1 FCU 11 (Close Cmd) 00054 Rly 2 FCU 11 (Open Cmd)
00055 Rly 1 FCU 12 (Close Cmd) 00056 Rly 2 FCU 12 (Open Cmd)
00057 Rly 1 FCU 13 (Close Cmd) 00058 Rly 2 FCU 13 (Open Cmd)
00059 Rly 1 FCU 14 (Close Cmd) 00060 Rly 2 FCU 14 (Open Cmd)
00061 Rly 1 FCU 15 (Close Cmd) 00062 Rly 2 FCU 15 (Open Cmd)
00063 Rly 1 FCU 16 (Close Cmd) 00064 Rly 2 FCU 16 (Open Cmd)
| |
| FCU 'N' Rly 1 00032 + 2N - 1 | FCU 'N' Rly 2 = 00032 + 2N
| |
00501 Rly 1 FCU 234 (Close Cmd) 00502 Rly 2 FCU 234 (Open Cmd)
00503 Rly 1 FCU 235 (Close Cmd) 00504 Rly 2 FCU 235 (Open Cmd)
00505 Rly 1 FCU 236 (Close Cmd) 00506 Rly 2 FCU 236 (Open Cmd)
00507 Rly 1 FCU 237 (Close Cmd) 00508 Rly 2 FCU 238 (Open Cmd)
00509 Rly 1 FCU 239 (Close Cmd) 00510 Rly 2 FCU 239 (Open Cmd)
00511 Rly 1 FCU 240 (Close Cmd) 00512 Rly 2 FCU 240 (Open Cmd)

Note that the access to these coils is also mapped to alternate locations starting 00513 (Open
Command) through to 01472 (ESD Command, field unit 240)

N = field unit address number in the range 1 to 240

Publication S171E V1.1 Issue 11/2008 73 of 96


Pakscan P3 with P720 Module Modbus Interface Specification

‰ Write Data (accessed with Modbus function code 05 and 15)


Commands - Individual Coils per Field Unit - Coil Locations (1 bit per)

Location Description Location Description Location Description

Relay 2 - OPEN COMMAND Relay 3 - STOP COMMAND Relay 1 - CLOSE COMMAND


00513 Rly 2 FCU 1 00753 Rly 3 FCU 1 00993 Rly 1 FCU 1
00514 Rly 2 FCU 2 00754 Rly 3 FCU 2 00994 Rly 1 FCU 2
00515 Rly 2 FCU 3 00755 Rly 3 FCU 3 00995 Rly 1 FCU 3
00516 Rly 2 FCU 4 00756 Rly 3 FCU 4 00996 Rly 1 FCU 4
| | |
| FCU 'N' Rly 2 = 00512 + N | FCU 'N' Rly 3 = 00752 + N | FCU 'N' Rly 1 = 00992 + N
| | |
00750 Rly 2 FCU 238 00990 Rly 3 FCU 238 01230 Rly 1 FCU 238
00751 Rly 2 FCU 239 00991 Rly 3 FCU 239 01231 Rly 1 FCU 239
00752 Rly 2 FCU 240 00992 Rly 3 FCU 240 01232 Rly 1 FCU 240

Relay 4 - ESD COMMAND


01233 Rly 4 FCU 1
01234 Rly 4 FCU 2
01235 Rly 4 FCU 3
01236 Rly 4 FCU 4
|
| FCU 'N' Rly 4 = 01232 + N
|
01470 Rly 4 FCU 238
01471 Rly 4 FCU 239
01472 Rly 4 FCU 240

N = field unit address number in the range 1 to 240

74 of 96 Publication S171E V1.1 Issue 11/2008


Yokogawa and Honeywell SI Protocols

5.6.3 Analogue Inputs (Field Units)

‰ Read Only Data (accessed with Modbus function code 04)


Each suitably equipped Field Unit is able to collect Analogue data from various inputs. In the
Yokogawa protocol the registers each contain a 2's complement value for the measurement. In the
Honeywell SI protocol the registers each contain an integer value for the measurement.

Location Description Location Description

Applicable to Actuator Field Units only Applicable to General Purpose Field Units and IQ
Analogue Field Units only
Valve Position Analogue Input 1
Range: Yokogawa, 0x0000 = 0% 0x7FFF = 100% Range: Yokogawa, 0x0000 = 0% 0x7FFF = 100%
Honeywell SI, 0x0000 = 0% 0x0064 = 100% Honeywell SI, 0x0000 = 0% 0x0064 = 100%
30001 FCU 1 Position 30241 FCU 1 An 1 I/P
30002 FCU 2 Position 30242 FCU 2 An 1 I/P
30003 FCU 3 Position 30243 FCU 3 An 1 I/P
30004 FCU 4 Position 30244 FCU 4 An 1 I/P
| |
| FCU 'N' Position = 30000 + N | FCU 'N' An 1 I/P = 30240 + N
| |
30238 FCU 238 Position 30478 FCU 238 An 1 I/P
30239 FCU 239 Position 30479 FCU 239 An 1 I/P
30240 FCU 240 Position 30480 FCU 240 An 1 I/P

Applicable to General Purpose Field Units and IQ Applicable to General Purpose Field Units only
Analogue Field Units only
Analogue Input 2 Pulse Input
Range: Yokogawa, 0x0000 = 0% 0x7FFF = 100% Range: Yokogawa and Honeywell SI,
Honeywell SI, 0x0000 = 0% 0x0064 = 100% 0x0000 to 0x270F counter value
30481 FCU 1 An 2 I/P 30721 FCU 1 Pulse I/P
30482 FCU 2 An 2 I/P 30722 FCU 2 Pulse I/P
30483 FCU 3 An 2 I/P 30723 FCU 3 Pulse I/P
30484 30724 FCU 4 Pulse I/P
| |
| FCU 'N' An 2 I/P = 30480 + N | FCU 'N' Pulse I/P = 30720 + N
| |
30718 FCU 238 An 2 I/P 30958 FCU 238 Pulse I/P
30719 FCU 239 An 2 I/P 30959 FCU 239 Pulse I/P
30720 FCU 240 An 2 I/P 30960 FCU 240 Pulse I/P

N = field unit address number in the range 1 to 240

Publication S171E V1.1 Issue 11/2008 75 of 96


Pakscan P3 with P720 Module Modbus Interface Specification

‰ Read Only Data (accessed with Modbus function code 04)


Each IQ/IQT Actuator Field Unit is able to collect both Current and Historical Torque data from the
actuator. The following 16 bit register locations each contain a value relating to the actuator torque.

Location Description

Applicable to IQ/IQT Actuator Field Units only

Current Torque
Range: Yokogawa, 0x0000 = 0% 0x7FFF = 120%
Honeywell SI, 0x0000 = 0% 0x0078 = 120%
30961 FCU 1 Current Torque
30962 FCU 2 Current Torque
30963 FCU 3 Current Torque
30964 FCU 4 Current Torque
|
| FCU 'N' Position = 30960 + N
|
31198 FCU 238 Current Torque
31199 FCU 239 Current Torque
31200 FCU 240 Current Torque

Location Description Location Description

Applicable to IQ/IQT Actuator Field Units only

Historical Torque Profile


Range: Yokogawa, 0x0000 = 0% 0x7FFF = 120%
Honeywell SI, 0x0000 = 0% 0x0078 = 120%
The Torque value is related to the readings taken across the valve stroke, Position 0 and 100% are not used as
these may be set to full torque for a torque seating valve. Torque readings are available for 6%, 19%, 31%,
44%, 56%, 69%, 81%, and 94% positions. The data is stacked in pairs where an open torque is followed by a
close torque for each position, for each field unit.
The data is historical and only updated on completion of a full stroke of the valve from open to close, or from
close to open. Further the data is not reported from the actuator to the master station unless the Torque Data
Filter Factor is set to 0 (refer to the Field Unit manual for more information).
31201 6% Open Torque FCU 1 31202 6% Close Torque FCU 1
31203 6% Open Torque FCU 2 31204 6% Close Torque FCU 2
31205 6% Open Torque FCU 3 31206 6% Close Torque FCU 3
| |
| FCU ’N’ 6% Open Torque = 31200 + 2N -1 | FCU ‘N’ 6% Close Torque = 31200 + 2N
| |
31679 6% Open Torque FCU 240 31680 6% Close Torque FCU 240

76 of 96 Publication S171E V1.1 Issue 11/2008


Yokogawa and Honeywell SI Protocols

Location Description Location Description

31681 19% Open Torque FCU 1 31682 19% Close Torque FCU 1
| FCU ‘N’ 19% Open Torque = 31680 + 2N -1 | FCU ‘N’ 19% Close Torque = 31680 + 2N)
32159 19% Open Torque FCU 240 32160 19% Close Torque FCU 240

32161 31% Open Torque FCU 1 32162 31% Close Torque FCU 1
| FCU ‘N’ 31% Open Torque = 32160 + 2N -1 | FCU ‘N’ 31% Close Torque = 32160 + 2N
32639 31% Open Torque FCU 240 32640 31% Close Torque FCU 240

32641 44% Open Torque FCU 1 32642 44% Close Torque FCU 1
| FCU ‘N’ 44% Open Torque = 32640 + 2N -1 | FCU ‘N’ 44% Close Torque = 32640 + 2N
33119 44% Open Torque FCU 240 33120 44% Close Torque FCU 240

33121 56% Open Torque FCU 1 33122 56% Close Torque FCU 1
| FCU ‘N’ 56% Open Torque = 33120 + 2N -1 | FCU ‘N’ 56% Close Torque = 33120 + 2N
33599 56% Open Torque FCU 240 33600 56% Close Torque FCU 240

33601 69% Open Torque FCU 1 33602 69% Close Torque FCU 1
| FCU ‘N’ 69% Open Torque = 33600 + 2N -1 | FCU ‘N’ 69% Close Torque = 33600 + 2N
34079 69% Open Torque FCU 240 34080 69% Close Torque FCU 240

34081 81% Open Torque FCU 1 34082 81% Close Torque FCU 1
| FCU ‘N’ 81% Open Torque = 34080 + 2N -1 | FCU ‘N’ 81% Close Torque = 34080 + 2N
34559 81% Open Torque FCU 240 34560 81% Close Torque FCU 240

34561 94% Open Torque FCU 1 34562 94% Close Torque FCU 1
| FCU ‘N’ 94% Open Torque = 34560 + 2N -1 | FCU ‘N’ 94% Close Torque = 34560 + 2N
35039 94% Open Torque FCU 240 35040 94% Close Torque FCU 240
N = field unit address number in the range 1 to 240

Publication S171E V1.1 Issue 11/2008 77 of 96


Pakscan P3 with P720 Module Modbus Interface Specification

5.6.4 Analogue Outputs (Field Units)

‰ Write Data (accessed with Modbus function codes 03, 06, 16)

Particular Actuator Field Units are able to accept


Location Description
a Desired Position signal. The following 16 bit
register locations may be written to with a 2's
complement value (Yokogawa protocol), or Applicable to Actuator Field Units only
signed integer value (Honeywell SI protocol)
relating to the desired valve position. Valve Position Control
Range: Yokogawa, 0x0000 = 0% 0x7FFF = 100%
Honeywell SI, 0x0000 = 0% 0x0064 = 100%
40001 FCU 1 Position control
40002 FCU 2 Position control
40003 FCU 3 Position control
40004 FCU 4 Position control
|
| FCU 'N' Position = 40000 + N
|
40238 FCU 238 Position control
40239 FCU 239 Position control
40240 FCU 240 Position control

General Purpose Field Units are able to accept


Location Description
an 'Analogue Output' signal for connection to a
controller or positioner. The following 16 bit
register locations may be written to with a 2's Applicable to General Purpose Field Units only
complement value (Yokogawa protocol), or
signed integer value (Honeywell SI protocol) Analogue Output
relating to the setting of this output. Range: Yokogawa, 0x0000 = 0% 0x7FFF = 100%
Honeywell SI, 0x0000 = 0% 0x0064 = 100%
40241 FCU 1 Analogue output
40242 FCU 2 Analogue output
40243 FCU 3 Analogue output
40244 FCU 4 Analogue output
|
| FCU 'N' Position = 40240 + N
|
40478 FCU 238 Analogue output
40479 FCU 239 Analogue output
40480 FCU 240 Analogue output

78 of 96 Publication S171E V1.1 Issue 11/2008


5.7 Field unit inputs and outputs available
5.7.1 Digital Inputs

FCU Type
Data Bit or Register IQ/IQT A, AQ, Q, GPFCU (GP) GPFCU (ACT) Flowpak EH SKIL IQ Analogue
Actuator ROMPAK Integral
Bit 0 AUX 1 R DIN 1 R R AUX 1 AUX 1 R
Bit 1 AUX 2 R DIN 2 R R AUX 2 AUX 2 R
Bit 2 OAS OAS DIN 3 OAS OAS OAS OAS R
Bit 3 CAS CAS DIN 4 CAS CAS CAS CAS R
Bit 4 STOP STOP DIN 5 STOP STOP STOP STOP R
Publication S171E V1.1 Issue 11/2008

Bit 5 MOVE MRUN DIN 6 MRUN Travelling Travelling Travelling R


Bit 6 MRO MRO DIN 7 MRO TRO MRO MRO R
Bit 7 MRC MRC DIN 8 MRC TRC MRC MRC R
Bit 8 AUX 3 EXT R EXT R AUX 3 AUX 3 R
Bit 9 AUX 4 R R R R AUX 4 AUX 4 R
Bit 10 LBON LBON LBON LBON LBON LBON LBON LBON
Bit 11 NALRM NALRM NALRM NALRM NALRM NALRM NALRM NALRM
Bit 12 ALRM ALRM ALRM ALRM ALRM ALRM ALRM ALRM
Bit 13 MEMF MEMF MEMF MEMF MEMF MEMF MEMF MEMF
Bit 14 COMMS COMMS COMMS COMMS COMMS COMMS COMMS COMMS

Yokogawa and Honeywell SI Protocols


Bit 15 LOCAL CNA R CNA LOCAL LOCAL LOCAL R
Bit 16 POWR POWR POWR POWR POWR POWR POWR POWR
Bit 17 WDOG WDOG WDOG WDOG WDOG WDOG WDOG WDOG
Bit 18 MREL MREL R MREL MREL MREL MREL R
Bit 19 THERM THERM R THERM Low Press FAULT FAULT R
Bit 20 LSTOP LSTOP R LSTOP OFF LSTOP LSTOP R
Bit 21 SFAIL SFAIL R SFAIL SFAIL SFAIL SFAIL R
Bit 22 VOBS VOBS R VOBS VOBS VOBS VOBS R
Bit 23 VJAM VJAM R VJAM VJAM VJAM VJAM R
Bit 24 AUXOR MOP R MOP MOP AUXOR AUXOR R
Bit 25 VTT MCL R MCL MCL VTT VTT R
79 of 96

Bit 26 R MOPG R MOPG R R R R


Bit 27 MMOVE MCLG R MCLG MMOVE MMOVE MMOVE R
Pakscan P3 with P720 Module Modbus Interface Specification
80 of 96
FCU Type
Data Bit or Register IQ/IQT A, AQ, Q, GPFCU (GP) GPFCU (ACT) Flowpak EH SKIL IQ Analogue
Actuator ROMPAK Integral
Bit 28 EOT EOT R EOT EOT EOT EOT R

Relay 4 R 0 RL4 0 0 R R R
Relay 1 R 0 RL1 0 0 R R R
Relay 3 R 0 RL3 0 0 R R R
Relay 2 R 0 RL2 0 0 R R R
AUX1 - Aux. Input 1 MEMF - RAM/ROM failure
AUX2 - Aux Input 2 COMMS - Comms fail
OAS - Open limit switch LOCAL - Actuator not in remote control
Publication S171E V1.1 Issue 11/2008

CAS - Close limit switch CNA - Control not available


STOP - Actuator stopped in mid travel POWR - Power on reset
MOVE - IQ/IQT valve moving WDOG - Watchdog fail
MRUN - Motor running MREL - Monitor relay
MRO - Motor running open direction THERM - Thermostat trip
MRC - Motor running close direction FAULT - Actuator fault
AUX3 - Aux Input 3 LSTOP - Local stop operated
AUX4 - Aux Input 4 SFAIL - Start/stop fail
DIN 1 to 8 - Digital inputs 1 to 8 VOBS - Valve obstructed
EXT IP - External digital input VJAM - Valve jammed
LBON - Loopback on AUXOR - Aux I/P Override
NALM - New alarm present on this FCU VTT - Valve Travel Time
ALARM - Any alarm present on this FCU MOP - Manual open
R - Reserved MCL - Manual close
Travelling - Actuator in motion MMOVE - Manual valve movement
TRO - Travelling open direction MOPG - Manual opening
TRC - Travelling closed direction MCLG - Manual closing
Low Press - Low air/hydraulic pressure EOT - Motor running end of travel
OFF - Electrical control inhibited
5.7.2 Digital Outputs

FCU Type
Data Bit or Register IQ/IQT A, AQ, Q, GPFCU (GP) GPFCU (ACT) Flowpak EH SKIL IQ Analogue
Actuator ROMPAK Integral
Open (Relay 2) Y Y Y Y Y Y Y N
Stop (Relay 3) Y Y Y Y Y Y Y N
Close (Relay 1) Y Y Y Y Y Y Y N
ESD (Relay 4) Y Y Y Y Y Y Y N
Publication S171E V1.1 Issue 11/2008

5.7.3 Analogue Inputs

FCU Type
Data Bit or Register IQ/IQT A, AQ, Q, GPFCU (GP) GPFCU (ACT) Flowpak EH SKIL IQ Analogue
Actuator ROMPAK Integral
Valve Position Y Y N Y Y Y Y N
Current Torque Y N N N N N N N
Historical Torque Y N N N N N N N
Analogue Input 1 N N Y N N N N Y

Yokogawa and Honeywell SI Protocols


Analogue Input 2 N N Y N N N N Y
Pulse Input N N Y N N N N N

5.7.4 Analogue Outputs

FCU Type
Data Bit or Register IQ/IQT A, AQ, Q, GPFCU (GP) GPFCU (ACT) Flowpak EH SKIL IQ Analogue
Actuator ROMPAK Integral
Position Control Y Y N Y Y Y Y N
Analogue Output N N Y N N N N N
81 of 96
Pakscan P3 with P720 Module Modbus Interface Specification

5.8 Modbus message examples (Yokogawa and Honeywell SI protocols)


A few examples are included here to clarify the use of the Modbus protocol. These examples assume
that the master station address is set to 01. All data is in hexadecimal notation.

Remember that the address used in the Modbus message assumes start points of zero for coils,
registers etc. However the locations indicated in the tables above put the first register or coil etc. as
number 1. Therefore 1 must be deducted from the locations indicated when determining the Modbus
message location.

5.8.1 Read Field Unit Bit 5 from FCU 1 to 100

To determine which Actuator Modbus Function Discrete Number of CRC Check


motors are running. Bit 5 is Address Code Address Discretes
located in discrete areas 11937 01 02 07 90 00 64 CRC
to 12036 for actuators 1 to 100.

5.8.2 Read Field Unit Bit 2 and 3 from FCU 1 to 120

To use a single transaction by


Modbus Function Discrete Number of CRC Check
collecting the data from the 'two Address Code Address Discretes
bit' area. Bits 2 and 3 are located
01 02 01 00 00 F0 CRC
in discrete areas 10257 to 10496
for actuators 1 to 120.

5.8.3 Read Valve Position from FCU 26

Modbus Function Register Number of CRC Check


Register is located at 30026 Address Code Address Registers
01 04 00 19 00 01 CRC

5.8.4 Energise Command to Open relay of Field Unit 104

The coil is located at 00616 Modbus Function Coil Address Data CRC Check
To write a single coil the data Address Code
field must be FF00 01 05 02 68 FF 00 CRC

OR:

Using the 'two command area' Modbus Function Coil Address Data CRC Check
the coil is located at 00240 Address Code
To write a single coil the data
01 05 00 F0 FF 00 CRC
field must be FF00

82 of 96 Publication S171E V1.1 Issue 11/2008


Yokogawa and Honeywell SI Protocols

5.8.5 Write Desired Valve Position for FCU 26 to be 50%

Register is located at 40026.


With Yokogawa protocol, 50% is 3FFF and with Honeywell SI protocol, 50% is 0032

Modbus Function Register Data CRC Check


Using Yokogawa protocol Address Code Addess
01 06 00 19 3F FF CRC

Using Honeywell SI protocol Modbus Function Register Data CRC Check


Address Code Addess
01 06 00 19 00 32 CRC

Publication S171E V1.1 Issue 11/2008 83 of 96


Pakscan P3 with P720 Module Modbus Interface Specification

(This page is intentionally blank)

84 of 96 Publication S171E V1.1 Issue 11/2008


Field Unit Block and Parameter Allocations

6 FIELD UNIT BLOCK AND PARAMETER ALLOCATIONS

The Pakscan current loop system comprises a number of Field Control Units connected to a Master
Station via a 2 wire loop. The Master Station manages the loop, collects data from, and issues
instructions to, the Field Units. Data within the Pakscan system is organised in Blocks and Parameters
relating to specific functions or activities within the Field Control Units (e.g. Digital inputs, Alarms,
Position control). Each FCU supports up to 32 blocks with each block containing eight 16-bit
parameters.

This section details the use of these blocks and parameters in the transfer of data between the Field
Unit and Master Station. A subset of this data is then used in host computer communications when
using Modbus. The field unit blocks and parameters can be examined on a Pakscan IIS system from
the master station screens or with a Paktester hand held communicator connected directly to the
actuator in which the data is held. In some cases the data read with a Paktester may differ from that
read using the IIS master station screen because the data is manipulated by the master station.
Pakscan 3 master station show the same information on specific field unit screens.

The various types of Field Unit have different block and parameter allocations. The following sections
give details of all the allocations applicable to each actuator and field unit type.

6.1 Block and parameter construction


The FCU acts as a slave to the master station, responding only when interrogated, just as the master
station acts as a slave to the host computer system. The data base in the field unit comprises a series
of records organised into Blocks and Parameters. Each Parameter contains 16 data bits. There are 32
Blocks, each of 8 Parameters, allocated for every field unit on the system, though not all these Blocks
contain relevant data.

6.1.1 Digital inputs

Each field unit has direct digital inputs from the connected actuator or other device. The status of
these digital signals is reported in the Digital Input Block (Block 2 Parameter 0). The block also
contains indication of any alarms present in the Alarm block.

6.1.2 Alarm block

The Alarm Block holds data about alarms either directly connected to the field unit, or logically derived
from the status of all the inputs. Transient alarm data bits are individually latched by the master station
and automatically cleared from the field unit on successful transfer. Alarm conditions will not return to
normal until both the source of the alarm is corrected and the alarm is both 'read' and 'accepted' by the
master station.

6.1.3 Analogue and counter input data

The field unit will report analogue or counter values to the master station only when the measurement
changes by an amount that exceeds the 'Deviation' setting by 1 digit, or the 'Update Timeout' period

85 of 96 Publication S171E V1.1 Issue 11/2008


Pakscan P3 with P720 Module Modbus Interface Specification

has expired. These parameters are adjustable, and included in the system to ensure that analogue
reporting only occurs when necessary. The host computer has access to the last reported analogue
value in the master station.

6.1.4 Outputs

The master station transfers both digital and analogue outputs from the host computer directly to the
connected field unit. There are no registers holding output data present within the master station itself.

6.2 Block and parameter usage


The following lists show all the relevant Blocks and Parameters that may exist in FCU's. They also
show the meaning of parameters for each Field Unit type and which parameters are supported by the
particular Field Unit types. All parameters are 16 bit quantities although most have a limited range of
values. The Parameters are transmitted Most Significant Data Byte first.

Field Unit Types Available:


IQ/IQT - Dedicated to the IQ/IQT actuator
INTEGRAL - A, AQ and Q Actuator control integral to the actuator
GPFCU (GP) - General Purpose version of GPFCU
GPFCU (Act) - Actuator Control version of GPFCU
EH - Electro-hydraulic actuator version of IQ field unit
Skil - Skilmatic SI actuator version of IQ field unit
Flowpak - Pneumatic or hydraulic actuator controller
ROMPAK - Dedicated to the ROMPAK actuator
IQ Analogue - Additional analogue input card for IQ actuators already fitted with FCU

Key to Symbols Used:


RO - Read Only
R/W - Read / Write
WO - Write Only
Y - Item supported for this type of Field Unit
R - Reserved for internal or future use
BLANK - A Blank entry indicates that the item is not supported for that Field
Unit type. Reads of that item generally return zero.
M - Data indicated is as read with a Paktester, if it is read via a master
station screen using Block and Parameter reads the data will be
invalid.
‰ Notes:
a) Great care must be exercised in the writing of data to a field unit. In general this can only be
achieved if the field unit is in ‘loopback’.

b) The range display will differ when viewed with a master station block and parameter read compared
to a Paktester read. In general, the master station re-ranges the range to show 32767 as the 100%
value as a decimal whilst the Paktester will show 100% as 0xFFFF in hexadecimal. Writes from the
master station should use the master station range.

c) The ranges indicated in the tables are those seen with a Paktester directly connected to the field
unit.

86 of 96 Publication S171E V1.1 Issue 11/2008


Read
FCU Type
Write
IQ/IQT A, AQ, Q, GPFCU (GP) GPFCU Flowpak EH SKIL IQ Analogue
Actuator ROMPAK (ACT) Integral

Block 0 - FCU Type Block


Parameter 0 – FCU Type RO Y Y Y Y Y Y
Data: IQ = 0006 0002 0004 0003 0005 0009 000A 0007
IQT = 0008 ROMPAK =
000E
Parameter 1 – SW version RO Y Y Y Y Y Y Y Y
Parameter 2 R/W Y Y R Y Y Y Y R
Data: Tag string / Stall timer
Publication S171E V1.1 Issue 11/2008

Parameter 3 to 7 R R R R R R R R

Block 1 - FCU Block


Parameter 0 R R R R R R R R
Parameter 1 – Baud rate M Y Y Y Y Y Y Y Y
Data: 0000 = 110, 0001 = 300, 0002 = 600, 0003 = 1200, 0004 = 2400
Parameter 2 - Address M Y Y Y Y Y Y Y Y
Range: 0001 to 00F0

Field Unit Block and Parameter Allocations


Parameter 3 – Address in L/B M Y Y Y Y Y Y Y Y
Range: 0001 to 00F0
Parameter 4 to 7 R R R R R R R R
87 of 96
Pakscan P3 with P720 Module Modbus Interface Specification
Read FCU Type
88 of 96

Write
IQ/IQT A, AQ, Q, GPFCU (GP) GPFCU Flowpak EH SKIL IQ Analogue
Actuator ROMPAK (ACT) Integral

Block 2 – Digital Input Block


Parameter 0 – Digital I/P RO Y Y Y Y Y Y Y Y
Bit 0 RO AUX 1 R DIN 1 R R AUX 1 AUX 1 R
Bit 1 RO AUX 2 R DIN 2 R R AUX 2 AUX 2 R
Bit 2 RO OAS OAS DIN 3 OAS OAS OAS OAS R
Bit 3 RO CAS CAS DIN 4 CAS CAS CAS CAS R
Bit 4 RO STOP STOP DIN 5 STOP STOP STOP STOP R
Bit 5 RO MOVE MRUN DIN 6 MRUN Travelling Travelling Travelling R
Publication S171E V1.1 Issue 11/2008

Bit 6 RO MRO MRO DIN 7 MRO TRO MRO MRO R


Bit 7 RO MRC MRC DIN 8 MRC TRC MRC MRC R
Bit 8 RO AUX 3 EXT R EXT R AUX 3 AUX 3 R
Bit 9 RO AUX 4 R R R R AUX 4 AUX 4 R
Bit 10 RO LBON LBON LBON LBON LBON LBON LBON LBON
Bit 11 RO NALRM NALRM NALRM NALRM NALRM NALRM NALRM NALRM
Bit 12 RO ALRM ALRM ALRM ALRM ALRM ALRM ALRM ALRM
Bit 13 RO BATT R R R R R R R
Bit 14 RO R R R R Remote R R R
Bit 15 RO R R R R R R R R
Parameter 1 – Invert mask R/W R R Y R R R R R
Parameter 2 – Aux I/P config R/W Y R R R R Y Y R
Parameter 3 to 7 R R R R R R R R
Read FCU Type
Write
IQ/IQT A, AQ, Q, GPFCU (GP) GPFCU Flowpak EH SKIL IQ Analogue
Actuator ROMPAK (ACT) Integral

Block 3 – Alarm Block


Parameter 0 – Alarms RO Y Y Y Y Y Y Y Y
Bit 0 RO MEMF MEMF MEMF MEMF MEMF MEMF MEMF MEMF
Bit 1 RO COMMS COMMS COMMS COMMS COMMS COMMS COMMS COMMS
Bit 2 RO LOCAL CNA R CNA LOCAL LOCAL LOCAL LOCAL
Bit 3 RO POWR POWR POWR POWR POWR POWR POWR POWR
Bit 4 RO WDOG WDOG WDOG WDOG WDOG WDOG WDOG WDOG
Bit 5 RO MREL MREL R MREL MREL MREL MREL R
Publication S171E V1.1 Issue 11/2008

Bit 6 RO THERM THERM R THERM Low Press FAULT FAULT R


Bit 7 RO LSTOP LSTOP R LSTOP OFF LSTOP LSTOP R
Bit 8 RO SFAIL SFAIL R SFAIL SFAIL SFAIL SFAIL R
Bit 9 RO VOBS VOBS R VOBS VOBS VOBS VOBS R
Bit 10 RO VJAM VJAM R VJAM VJAM VJAM VJAM R
Bit 11 RO AUXOR MOP R MOP MOP AUXOR AUXOR R
Bit 12 RO VTT MCL R MCL MCL VTT VTT R
Bit 13 RO R MOPG R MOPG R R R R

Field Unit Block and Parameter Allocations


Bit 14 RO MMOVE MCLG R MCLG MMOVE MMOVE MMOVE R
Bit 15 RO EOT EOT R EOT R EOT EOT R
Parameter 1 – Alarm Accept R R R R R R R R
Para’ 2 – Valve Travel Time R/W Y R R R R Y Y R
Parameter 3 to 7 R R R R R R R R
89 of 96
Pakscan P3 with P720 Module Modbus Interface Specification
Read FCU Type
90 of 96

Write
IQ/IQT A, AQ, Q, GPFCU (GP) GPFCU Flowpak EH SKIL IQ Analogue
Actuator ROMPAK (ACT) Integral

Block 4 - 8 Bit Analogue Input Block - Valve Position Feedback


Parameter 0 – Position MV RO Y Y R Y Y Y Y R
Range: 0x0000 = 0% position, 0x00FF = 100% position
Para’1 – Deviation Threshold R/W Y Y R Y Y Y Y R
Range: 0x0000 = 0%, 0x00FF = 100%, (0 = disable)
Para’ 2 – Update Timeout R/W Y Y R Y Y Y Y R
Range: 0x0000 = 0 sec, 0x00FF = 255 sec, (0 = disable)
Publication S171E V1.1 Issue 11/2008

Para’ 3 – 0% calibration R/W Y R R R R Y Y R


Para’ 4 – 100% calibration R/W Y R R R R Y Y R
Para’ 5 – Raw Input RO Y Y R Y Y Y Y R
Para’ 6 – Motion detect timer R/W R R R R Y R R R
Range: 0x0000 = 0 sec, 0x00FF = 255 sec
Parameter 7 R R R R R R R R

Block 5 – Position Control Block (Valve Desired Position)


Parameter 0 R R R R R R R R
Parameter 1 – Desired value R/W Y Y R Y Y Y Y R
Range: 0x0000 = 0% Desired position, 0x00FF = 100% Desired position
Para’ 2 – Motion Inhibit Timer R/W Y Y R Y Y Y Y R
Range: 0x0000 = 0 sec, 0x00FF = 128 sec
Para’ 3 – Deadband Setting R/W Y Y R Y Y Y Y R
Range: 0x0000 = 0%, 0x00FF = 12%
Para’ 4 – Hysteresis R/W Y R R R R Y Y R
Parameter 5 to 7 R R R R R R R R
Read FCU Type
Write
IQ/IQT A, AQ, Q, GPFCU (GP) GPFCU Flowpak EH SKIL IQ Analogue
Actuator ROMPAK (ACT) Integral

Block 6 – Digital Output Block


Parameter 0 – Digital Output RO R R Y R R R R R
Bit 0 RO 0 0 RLY 4 0 0 0 0 0
Bit 1 RO 0 0 RLY 1 0 0 0 0 0
Bit 2 RO 0 0 RLY 3 0 0 0 0 0
Bit 3 RO 0 0 RLY 2 0 0 0 0 0
Bit 4 RO 0 0 0 0 0 0 0 0
Bit 5 RO 0 0 0 0 0 0 0 0
Publication S171E V1.1 Issue 11/2008

Bit 6 RO 0 0 0 0 0 0 0 0
Bit 7 RO 0 0 ACT 0 0 0 0 0
Bit 8 – 15 RO 0 0 0 0 0 0 0 0
Key: ACT = relay action, 0 = Fleeting, 1 = Maintained
Parameter 1 - Open WO Y Y Y Y Y Y Y R
‘OPEN’ (Relay 2) : 0x0000 = De-energise 0xFF00 or any non-zero value = Energise relay
Parameter 2 – Stop WO Y Y Y Y Y Y Y R

Field Unit Block and Parameter Allocations


‘STOP’ (Relay 3) : 0x0000 = De-energise 0Xff00 or any non-zero value = Energise relay
Parameter 3 - Close WO Y Y Y Y Y Y Y R
‘CLOSE’ (Relay 1) : 0x0000 = De-energise 0xFF00 or any non-zero value = Energise relay
Parameter 4 - ESD WO Y Y Y Y Y Y Y R
‘ESD’ (Relay 4) : 0x0000 = De-energise 0xFF00 or any non-zero value = Energise relay
Parameter 5 - 7 R R R R R R R R

Block 7 – Pulse Input Block


Parameter 0 – Counter Value RO R R Y R R R R R
Range: 0x0000 to 0x270F = 0 to 9999 decimal
Parameter 1 to 7 R R R R R R R R

Block 8 - Reserved
91 of 96

Parameter 0 to 7 R R R R R R
Pakscan P3 with P720 Module Modbus Interface Specification
Read FCU Type
92 of 96

Write
IQ/IQT A, AQ, Q, GPFCU (GP) GPFCU Flowpak EH SKIL IQ Analogue
Actuator ROMPAK (ACT) Integral

Block 9 – 12 bit Analogue Input 1 Block


Para’ 0 – Analogue Input 1 R/O R R Y R R R R Y
Range: 0x0000 = 0%, 0x0FFF = 100%
Para’ 1 – Deviation Threshold R/W R R Y R R R R Y
Range: 0x0000 = 0%, 0x00FF = 100%, (0 = disable)
Para’ 2 – Update Timeout R/W R R Y R R R R Y
Range: 0x0000 = 0 sec, 0x00FF = 255 sec (0 = disable)
Publication S171E V1.1 Issue 11/2008

Para’ 3 – AI 1 Min (0% input) R/W R R Y R R R R Y


Para’ 4 – AI 1 Max (100% i/p) R/W R R Y R R R R Y
Para; 5 – Raw An I/P 1 RO R R Y R R R R Y
Parameter 6 and 7 R R R R R R R R

Block 10 – 12 bit Analogue Input 2 Block


Para’ 0 – Analogue Input 2 R/O R R Y R R R R Y
Range: 0x0000 = 0%, 0x0FFF = 100%
Para’ 1 – Deviation Threshold R/W R R Y R R R R Y
Range: 0x0000 = 0%, 0x00FF = 100%, (0 = disable)
Para’ 2 – Update Timeout R/W R R Y R R R R Y
Range: 0x0000 = 0 sec, 0x00FF = 255 sec (0 = disable)
Para’ 3 – AI 2 Min (0% input) R/W R R Y R R R R Y
Para’ 4 – AI 2 Max (100% i/p) R/W R R Y R R R R Y
Para; 5 – Raw An I/P 2 RO R R Y R R R R Y
Parameter 6 and 7 R R R R R R R R
Read FCU Type
Write
IQ/IQT A, AQ, Q, GPFCU (GP) GPFCU Flowpak EH SKIL IQ Analogue
Actuator ROMPAK (ACT) Integral

Block 11 – 12 bit Analogue Output Block


Para’ 0 – Analogue Output R/W R R Y R R R R R
Range: 0x0000 = 0%, 0x0FFF = 100%
Para’ 1 – 0% Calibration R/W R R Y R R R R R
Range: 0x0000 to 0x0FFF = Value at 0%
Para’ 1 – 100% Calibration R/W R R Y R R R R R
Range: 0x0000 to 0x0FFF = Value at 100%
Publication S171E V1.1 Issue 11/2008

Parameter 3 to 7 R R R R R R R R

Block 12 – Historical Torque Profile – Opening Direction


The IQ/IQT Actuator is able to report 8 torque values related to valve position across the valve stroke. Position 0 and 100% are not used as these
may be set to full torque for a torque seating valve. Torque readings are available for 6%, 19%, 31%, 44%, 56%, 69%, 81%, and 94% positions. The
following parameters contain this data for the OPENING direction of travel - note that they only update if a complete stroke of the valve is made and
contain the last profile only.
Range: 0000 = 0% rated torque, 00FF = 120% rated torque

Field Unit Block and Parameter Allocations


Para’ 0 - 6% RO Y R R R R R R R
Para’ 1 - 19% RO Y R R R R R R R
Para’ 2 - 31% RO Y R R R R R R R
Para’ 3 - 44% RO Y R R R R R R R
Para’ 4 - 56% RO Y R R R R R R R
Para’ 5 - 69% RO Y R R R R R R R
Para’ 6 - 81% RO Y R R R R R R R
Para’ 7 - 94% RO Y R R R R R R R
93 of 96
Pakscan P3 with P720 Module Modbus Interface Specification
Read FCU Type
94 of 96

Write
IQ/IQT A, AQ, Q, GPFCU (GP) GPFCU Flowpak EH SKIL IQ Analogue
Actuator ROMPAK (ACT) Integral

Block 13 – Historical Torque Profile – Closing Direction


The IQ/IQT Actuator is able to report 8 torque values related to valve position across the valve stroke. Position 0 and 100% are not used as these
may be set to full torque for a torque seating valve. Torque readings are available for 6%, 19%, 31%, 44%, 56%, 69%, 81%, and 94% positions. The
following parameters contain this data for the CLOSING direction of travel - note that they only update if a complete stroke of the valve is made and
contain the last profile only.
Range: 0000 = 0% rated torque, 00FF = 120% rated torque
Para’ 0 - 6% RO Y R R R R R R R
Para’ 1 - 19% RO Y R R R R R R R
Publication S171E V1.1 Issue 11/2008

Para’ 2 - 31% RO Y R R R R R R R
Para’ 3 - 44% RO Y R R R R R R R
Para’ 4 - 56% RO Y R R R R R R R
Para’ 5 - 69% RO Y R R R R R R R
Para’ 6 - 81% RO Y R R R R R R R
Para’ 7 - 94% RO Y R R R R R R R

Block 14 – Historical Torque Profile – Closing Direction


Para’ 0 – Current Torque R/O Y R R R R R R R
Range: 0x0000 = 0%, 0x00FF = 120%
Para’ 1 – Deviation Threshold R/W Y R R R R R R R
Range: 0x0000 = 0%, 0x00FF = 100%,
Para’ 2 – Update Timeout R/W Y R R R R R R R
Range: 0x0001 = 1 minute, 0x00FF = 255 minutes (0 = disable)
Para’ 3 – Filter R/W Y R R R R R R R
Data: 0x0000 = Off, 0x00FF = On, Automatic torque reporting is only available with the filter Off
Para’ 4 – Profile Counters M R R R R R R R
Bits 8-15 = Open counter, Bits 7-0 = Close counter (available from the master station only)
Parameter 5 to 7 R R R R R R R R

Block 15 to 31 – Reserved
Block 15 - 31 Parameter 1 - 7 R R R R R R R R
Field Unit Block and Parameter Allocations

(This page is intentionally blank)

Publication S171E V1.1 Issue 11/2008 95 of 96


Pakscan P3 with P720 Module Modbus Interface Specification

UK Head Office USA Head Office

htpp://www.rotork.com Rotork Controls Ltd Rotork Controls Inc


Bath 675 Mile Crossing Blvd
England Rochester
BA1 3JQ New York 14624
USA
Rotork reserves the right to amend Tel: +44 (0) 1225 733 200
and change specifications without
prior notice. Fax: +44 (0) 1225 333 467 Tel: +1 585 247 2304
e-mail: mail@rotork.co.uk Fax: +1 585 247 2308
Published data may be subject to e-mail: info@rotork.com
change

96 of 96 Publication S171E V1.1 Issue 11/2008