Sei sulla pagina 1di 40

Tele.

& TV

Riser Cable No.Tele. Aver.Lengt


Tag Block
Description Size Qty. Length No.of TTB Points h

Basement 100 25 2 12 2 33 50
Ground 200 50 2 10 2 103 50
First 200 50 2 16 2 81 50
Second Floor 200 50 2 24 2 119 50
Third Floor 200 50 2 32 2 92 50
Fourth Floor 200 50 2 40 2 87 50
Fifth 200 50 2 48 2 72 50
Sixth 100 25 2 56 2 82 50
Total 16 16 669
20% Extra
Final Total
T.V (For Both Shaft)

MATV Network
No.of Tapoff Cond.-
Descriptrion T1 T2 T3 T4 TV point 25mm

Basement 4 80
Ground 7 140
First 9 180
Second Floor 60 1200
Third Floor 33 680
Fourth Floor 32 660
Fifth 31 660
Sixth 7 140
Total 3740
10% Extra 374
Final Total 183 4114

Nurse Call Point Conduit & wire length (Nursing station to ward room)
25mm con. wire 25mm con. wire (4X2.5) 25mm con. wire (Cat-5)
for 30 bed
For 1 ward Room 74 45 ward 219 409 198 340
For 118 ward
Room 8732 5310 for 19 ward 4161 7771 3762 6460
for ICUs,
gyne,Emer.
(6 nos.) 1314 2454 1188 2040
Total 8732 5310 5475 10225 4950 8500

Summary of Tele., TV & Nurse Call System

25mm Cond. Cat-5 wire RG-6 RG-11 Signal wire 20 pair (Nurse Call )
34842.14 #REF! 4622.2 2208.8 5310
.

Cable Tray
L.V Tray
Vertical Length
(Shaft)
From LV Shaft-1 300mm x 40
Basement 4 4
Ground 4
First 4
Second Floor 4
Third Floor 4
Fourth Floor 4
Fifth 4
Sixth 4
From LV Shaft-2
Basement 4
Ground 4
First 4
Second Floor 4
Third Floor 4
Fourth Floor 4
Fifth 4
Sixth 4
Total 64
Cat-5
Wire 25mm Cond.

1848 818.4
5768 2554.4
4536 2008.8
6664 2951.2
5152 2281.6
4872 2157.6
4032 1785.6
4592 2033.6
37464 16591.2
7492.8 3318.24
44956.8 19909.44
RG-6
cable RG-11 cable

88 125
154 288
198 288
1364 288
748 253
770 253
726 260
154 253
4202 2008
420.2 200.8
4622.2 2208.8

For 30bed ward (typ.)

20 pair (Nurse Call )


132 686.4
412 2142.4
324 1684.8
476 2475.2
368 1913.6
348 1809.6
288 1497.6
328 1705.6
Cond.-25mm

119
273
273
273
238
238
245
238
1897
189.7
2086.7
Submain

Ground Floor
(Panel-1)
No.of DBs/CablCable size Total Length Glands
Wing-A 1 4cx6 30 2
LDB 4 4cx10 120 8
4cx10 0 0
PDB 3 4cx16 6
4cx4 0 0
1 4cx6 30 2
1 4cx10 30 2
AHU 4cx16 0 0
1 4cx10 30 2
4cx16 0
3.5cx35 0
X-Ray 3.5cx50 0

Wing-C 4cx6 0 0
LDB 3 4cx10 60 6
2 4cx10 40 4
PDB 4cx16 0
4cx4 0 0
1 4cx6 20 2
1 4cx10 20 2
AHU 4cx16 0 0
LPDB-1 1 4cx6 20 2
LPDB-2 1 4cx6 20 2
X-Ray 4cx10 0 0
UPS DB 0 0

Wing-E 4cx6 0 0
LDB 2 4cx10 128 4
4cx10 0 0
PDB 2 4cx16 128 4
1 4cx4 64 2
4cx6 0 0
1 4cx10 64 2
AHU 4cx16 0 0
X-Ray 0 0
UPS DB 0 0

First Floor
(Panel-1)
No.of DBs Cable size Total Length
Wing-A 4cx6 0 0
LDB 3 4cx10 90 6
4cx10 0 0
PDB 1 4cx16 20 2
4cx4 0 0
2 4cx6 60 4
1 4cx10 30 2
AHU
AHU 4cx16 0 0
X-Ray 4cx10 0 0
UPS DB 4cx16 0 0
0
Wing-C 4cx6 0 0
LDB 2 4cx10 40 4
4cx10 0 0
PDB 2 4cx16 4
1 4cx4 20 2
1 4cx6 20 2
4cx10 0 0
AHU 4cx16 0 0
LPDB-1 4cx6 0 0
LPDB-2 4cx6 0 0
X-Ray 4cx10 0 0
UPS DB 0 0
0
Wing-E 4cx6 0 0
LDB 2 4cx10 128 4
4cx10 0 0
PDB 2 4cx16 128 4
1 4cx4 64 2
1 4cx6 64 2
4cx10 0 0
AHU 4cx16 0 0
X-Ray 0 0
UPS DB 0 0

Second Floor
(Panel-1)
No.of DBs/CablCable size Total Length
Wing-A 4cx6 0 0
LDB 4 4cx10 120 8
4 4cx10 80 8
PDB 3 4cx16 6
4cx4 0 0
1 4cx6 30 2
4cx10 0 0
AHU 1 4cx16 30 2
X-Ray 4cx10 0 0
UPS DB 4cx16 0 0
0
Wing-C 4cx6 0 0
LDB 2 4cx10 40 4
3 4cx10 60 6
PDB 4cx16 0
4cx4 0 0
1 4cx6 20 2
4cx10 0 0
AHU 4cx16 0 0
LPDB-1 4cx6 0 0
LPDB-2 4cx6 0 0
X-Ray 4cx10 0 0
UPS DB 0 0
0
Wing-E 4cx6 0 0
LDB 2 4cx10 128 4
1 4cx10 64 2
PDB 3 4cx16 192 6
4cx4 0 0
2 4cx6 128 4
4cx10 0 0
AHU 4cx16 0 0
X-Ray 0 0
UPS DB 0 0

Third Floor
(Panel-1)
No.of DBs Cable size Total Length
Wing-A 4cx6 0 0
LDB 1 4cx10 30 2
4cx10 0 0
PDB 2 4cx16 4
4cx4 0 0
1 4cx6 30 2
4cx10 0 0
AHU 4cx16 0 0
X-Ray 4cx10 0 0
UPS DB 4cx16 0 0
0
Wing-C 4cx6 0 0
LDB 2 4cx10 40 4
1 4cx10 20 2
PDB 1 4cx16 2
4cx4 0 0
1 4cx6 20 2
4cx10 0 0
AHU 4cx16 0 0
LPDB-1 4cx6 0 0
LPDB-2 4cx6 0 0
X-Ray 4cx10 0 0
UPS DB 0 0
0
Wing-E 4cx6 0 0
LDB 2 4cx10 128 4
4cx10 0 0
PDB 2 4cx16 128 4
4cx4 0 0
2 4cx6 128 4
4cx10 0 0
AHU 4cx16 0 0
X-Ray 0 0
UPS DB 0 0
Fourth Floor
(Panel-1)
No.of DBs Cable size Total Length
Wing-A 4cx6 0 0
LDB 1 4cx10 30 2
4cx10 0 0
PDB 2 4cx16 4
4cx4 0 0
1 4cx6 30 2
4cx10 0 0
AHU 4cx16 0 0
X-Ray 4cx10 0 0
UPS DB 4cx16 0 0
0
Wing-C 4cx6 0 0
LDB 2 4cx10 40 4
3 4cx10 60 6
PDB 4cx16 0
4cx4 0 0
2 4cx6 40 4
4cx10 0 0
AHU 4cx16 0 0
LPDB-1 4cx6 0 0
LPDB-2 4cx6 0 0
X-Ray 4cx10 0 0
UPS DB 0 0
0
Wing-E 4cx6 0 0
LDB 1 4cx10 64 2
2 4cx10 128 4
PDB 4cx16 0 0
4cx4 0 0
4cx6 0 0
1 4cx10 64 2
AHU 4cx16 0 0
X-Ray 0 0
UPS DB 0 0

Fifth Floor
(Panel-1)
No.of DBs Cable size Total Length
Wing-A 4cx6 0 0
LDB 2 4cx10 60 4
1 4cx10 20 2
PDB 2 4cx16 4
2 4cx4 60 4
4cx6 0 0
4cx10 0 0
AHU 4cx16 0 0
X-Ray 4cx10 0 0
UPS DB 4cx16 0 0
0
Wing-C 4cx6 0 0
LDB 2 4cx10 40 4
4cx10 0 0
PDB 2 4cx16 4
4cx4 0 0
1 4cx6 20 2
1 4cx10 20 2
AHU 4cx16 0 0
LPDB-1 4cx6 0 0
LPDB-2 4cx6 0 0
X-Ray 4cx10 0 0
UPS DB 0 0
0
Wing-E 4cx6 0 0
LDB 2 4cx10 128 4
4cx10 0 0
PDB 2 4cx16 128 4
1 4cx4 64 2
1 4cx6 64 2
4cx10 0 0
AHU 4cx16 0 0
X-Ray 0 0
UPS DB 0 0

Sixth Floor
(Panel-1)
No.of DBs Cable size Total Length
Wing-A 4cx6 0 0
LDB 2 4cx10 60 4
4cx10 0 0
PDB 2 4cx16 4
4cx4 0 0
4cx6 0 0
4cx10 0 0
AHU 4cx16 0 0
AHU Panel-1 1 3.5cx25 30 2
X-Ray 4cx10 0 0
UPS DB 4cx16 0 0
0
Wing-C 4cx6 0 0
LDB 1 4cx10 20 2
4cx10 0 0
PDB 1 4cx16 2
4cx4 0 0
4cx6 0 0
4cx10 0 0
AHU 4cx16 0 0
AHU Panel-2 1 3.5cx25 20 2
LPDB-1 4cx6 0 0
LPDB-2 4cx6 0 0
X-Ray 4cx10 0 0
UPS DB 0 0

Wing-E 4cx6 0 0
LDB 1 4cx10 64 2
4cx10 0 0
PDB 1 4cx16 64 2
4cx4 0 0
4cx6 0 0
4cx10 0 0
AHU 1 4cx16 64 2
X-Ray 0 0
UPS DB 0 0
264

Wing-A,C & E
Sl.No. Cable Size Length Gland
1 3.5cx25 sq mm 50 4
2 3.5cx35 sq mm 0 0
3 3.5cx50 sq mm 0 0
4 4cx4sq mm 272 12
5 4cx6sq mm 774 44
6 4cx10 sq mm 2288 134
7 4cx16 sq mm 882 70

From To Cable Size No.of Cable Length Gland


4 MDB Lift Panel-1 Lift Panel -WA 3.5cx95 1 125 2
2 Lift Panel-WC1 3.5cx35 1 50 2
3 Lift Panel-WC2 3.5cx70 1 30 2

Coupler 3.5cx185 1 120 2

2 Lift Panel-WF1 3.5cx35 1 140 2


1 MDB Lift Panel-2 Lift Panel-WF3 4cx16 1 135 2
2 Lift Panel-WF2 3.5cx35 1 155 2
2 Lift Panel-WD1 3.5cx35 1 65 2
1 Lift Panel-WD2 4cx16 1 45 2
1 Lift Panel-WD3 4cx16 1 60 2

Lift Panel-WD1
(Typical For-
WC1,WF1 & WF2)
lift-1 4cx10 4 160 8
lift-2 4cx10 4 160 8
LMR DB 2cx6 4 160 8
Lift Panel-WC2 lift-1 4cx10 4 40 8
lift-2 4cx10 4 40 8
lift-3 4cx10 4 40 8
LMR DB 4cx6 4 40 8
0
Lift Panel-WD2
(Typical For-
WD3,WF3 )
lift-1 4cx16 3 120 6
LMR DB 2cx6 3 120 6

Rising Main-1A Gr.Flr-1A & 2A 3.5cx185 4 40 8


Rising Main-2A 1st Flr-1A & 2A 3.5cx185 4 40 8
2nd Flr-1A & 2A 3.5cx185 4 40 8
3rd Flr-1A & 2A 3.5cx240 2 20 4
4th Flr-1A & 2A 3.5cx240 2 20 4
5th Flr-1A & 2A 3.5cx185 4 40 8
6th Flr-1A & 2A 3.5cx240 2 20 4

Rising Main-1D Gr.Flr-1D & 2D 3.5cx185 4 40 8


Rising Main-2D 1st Flr-1D & 2D 3.5cx185 4 40 8
2nd Flr-1D & 2D 3.5cx185 4 40 8
3rd Flr-1D & 2D 3.5cx185 4 40 8
4th Flr-1D & 2D 3.5cx185 4 40 8
5th Flr-1D & 2D 3.5cx150 4 40 8
6th Flr-1D & 2D 3.5cx185 4 40 8

Basement Vent
Panel SUMP 4cx6 2 60 4
SUMP 4cx6 2 60 4
SUMP 4cx6 2 60 4
SUMP 4cx6 2 60 4
Smoke Exhaust-3cx16 1 60 2
Smoke Exhaust-3cx16 1 60 2
Normal Exhaust 3cx16 1 60 2
Base.AHU+Vent 3.5cx70 1 60 2
Smoke Exhaust 3cx10 1 60 2
Smoke Exhaust 3cx10 1 60 2
Smoke Exhaust 3cx10 1 60 2
Noemal Exhaust3cx6 1 60 2
Noemal Exhaust3cx6 1 60 2
Noemal Exhaust3cx6 1 60 2
0
Base.AHU+Vent PaneAHU-1 4cx10 1 50 2
AHU-2 4cx10 1 50 2
AHU-3 4cx10 1 50 2
AHU-4 4cx6 1 50 2
Normal Exhaust 4cx16 1 50 2

Hospital Bsement
Panel Parking LPDB-1 4cx16 1 50 2
Parking LPDB-2 4cx16 1 50 2
Parking LPDB-3 4cx16 1 50 2
A/C Plant LPDB 4cx10 1 50 2
Wing-B LDB-1 4cx10 1 50 2
Wing-B LDB-2 4cx10 1 50 2
Wing-B PDB-1 4cx16 1 50 2
Wing-B PDB-2 4cx16 1 50 2

Wing-F LDB-1 4cx10 1 50 2


Wing-F LDB-2 4cx10 1 50 2
Wing-F LDB-3 4cx10 1 50 2
Wing-F LDB-4 4cx10 1 50 2

Wing-F PDB-1 4cx16 1 50 2


Wing-F PDB-2 4cx16 1 50 2
Wing-F PDB-3 4cx16 1 50 2
Wing-F PDB-4 4cx16 1 50 2

LDB 4cx10 1 50 2
PDB 4cx16 1 50 2
AHU Panel 3.5cx25 1 50 2
UPS 3.5cx35 1 50 2

MDB UPS-1 Server Room 4cx25 1 75 2


UPS GD1 4cx50 1 110 2
UPS 2A1. 4cx50 1 30 2
UPS 1A1 (Blood4cx70 1 25 2
UPS GA1 4cx25 1 20 2
UPS 5A1 4cx35 1 45 2
UPS 6D1 4cx50 1 140 2
UPS 6A1 4cx70 1 50 2
0
MDB UPS-2 UPS 2A2 4cx70 1 30 2
UPS 1A2 (Eye B4cx50 1 25 2
UPS GA2 4cx25 1 20 2
UPS 5A2 4cx35 1 45 2
UPS 6D2 4cx50 1 140 2
UPS 6A2 4cx70 1 50 2
UPS GD2 4cx50 1 110 2

UPS GD1(Typical
for 2A1) UPS Panel Grou4cx16 1 30 2
1 30 2
UPS Panel Sec 4cx16 1 30 2
UPS Panel Four 4cx10 1 30 2
UPS GD2(Typical
for 2A2) UPS Panel First 4cx16 1 30 2
UPS Panel Third4cx16 1 30 2
UPS Panel Fifth 4cx10 1 30 2

UPS Floor Panels UDBs 2cx6 20 1000 40


UDBs 2cx10 16 800 32
Isolation Panel 2cx10 12 600 24
2cx16 8 400 16

Pressurization
Panel-1 (Loc.-
Basement) Press.Fan-1 3cx6 1 50 2
Press.Fan-2 3cx6 1 50 2
Press.Fan-3 3cx6 1 50 2
Toilet Exhaust-1 3cx6 1 50 2
Toilet Exhaust-2 3cx6 1 50 2
Staircase Fan 3cx6 1 50 2
Pressurization
Panel-2 (Loc.-
Basement) Press.Fan-1 3cx6 1 50 2
Press.Fan-2 3cx6 1 50 2
Press.Fan-3 3cx6 1 50 2
Staircase Fan 3cx6 1 50 2

Pressurization
Panel-3 (Loc.-
Basement) Press.Fan-1 3cx6 1 50 2
Press.Fan-2 3cx6 1 50 2
Press.Fan-3 3cx6 1 50 2
Staircase Fan 3cx6 1 50 2

MDB-OT(6th Flr3.5cx120 1 255 2


MDB-ICU (6th F3.5cx120 1 190 2
MRI 3.5cx240 1 160 2
CT Scan 3.5cx185 1 155 2

MDB- Kitchen Kitchen Panel 3.5cx50 2 200 4


MDB- Kitchen KDBs 4cx16 6 240 12

Autoclave 3.5cx25 3 90 6
MDB-CSSD Autoclave 4cx16 3 90 6
other eqpts. 4cx10 3 90 6
4cx6 3 90 6
4cx4 3 90 6

Sub-main cable Length Lift ,UPS,Vent & Press..


Cable Size Length Gland
2cx4 0 0
2cx6 1280 54
2cx10 1400 56
2cx16 400 16
3cx4 0 0
3cx6 720 34
3cx10 180 6
3cx16 180 6
4cx4 90 6
4cx6 420 32
4cx10 1140 72
4cx16 1360 60
4cx25 115 6
4cx35 90 4
4cx50 555 12
4cx70 155 8
3.5cx35 460 10
3.5cx50 200 4
3.5cx25 140 8
3.5cx70 90 4
3.5cx95 125 2
3.5cx120 445 4
3.5cx150 40 8
3.5cx185 675 84
3.5cx240 220 14
3.5cx300 0 0
Summary of Cable Length

Cable Size Total Length 40% Extra Final Total Total Gland
3.5cx300 0 0 0 0
3.5cx240 220 110 330 14
3.5cx185 675 337.5 1013 84
3.5cx150 40 20 60 8
3.5cx120 445 222.5 668 4
3.5cx95 sq mm 125 62.5 188 2
3.5cx70 sq mm 90 45 135 4
3.5cx50 sq mm 555 277.5 833 6
3.5cx35 sq mm 460 230 690 14
3.5cx25 sq mm 280 140 420 16
4cx70 sq mm 155 77.5 233 8
4cx50 sq mm 555 277.5 833 12
4cx35 sq mm 90 45 135 4
4cx16 sq mm 4177 2088.5 6266 216
4cx10 sq mm 5768 2884 8652 310
4cx6sq mm 1959 979.5 2939 110
4cx4sq mm 497 248.5 746 24
3cx16sq mm 180 90 270 6
3cx10sq mm 180 90 270 6
3cx6sq mm 720 360 1080 34
3cx4 0 0 0 0
2cx16 400 200 600 16
2cx10 1400 700 2100 56
2cx6sq mm 1280 640 1920 54
2cx4 0 0 0 0
20251 30377 1008
40.18 60.27 504

8.37972414
Cable Tray Length

Length of Cable Tray in Mtr.


Location
150 mm. 300mm 600mm 900mm
Basement 210 130 280
Ground floor 131 74 90
First floor 169 67 80
Second floor 188 65 85
Third floor 153 42 96
Fourth Floor 87 43 100
Fifth Floor 121 49 115
Sixth Floor 128 59 77
vertical riser 18 158 72
AC Plant
LT Panel room
Total 0 1205 687 995

Main LT Panel Riser Main -1A High side 5 750


Riser Main -2A High side 5 750
Riser Main -1DHigh side 5 750
Riser Main -2DHigh side 5 750
MDB-UPS1 High side 2 300
MDB-UPS2 High side 2 300
MDB-Bas. High side 2 300
MDB-Misc. High side 0 0
Cap-1 High side 0 0
MDB-Lift-1 High side 2 300
MDB- Lift2 High side 2 300
MDB- Kitchen High side 2 300
MDB-1Bas. VenHigh side 2 300
MDB-2Bas. VenHigh side 2 300
Mortuary High side Bq
Incinerator High side Bq
36 5400 66.25
A.C. Plant High side Bq
Pump room High side Bq
Fire Pums High side Bq
Med. College High side Bq
Nursing CollegHigh side Bq
Library High side Bq
Admin Block High side Bq
Audi. High side Bq
No.of DBs/Cable Cable size Total Length Glands
4cx6 0 0
LDB 2 4cx10 90 4
4cx10 0 0
PDB 2 4cx16 90 4
4cx4 0 0
1 4cx6 45 2
1 4cx10 45 2
AHU 4cx16 0 0
4cx10 0 0
1 4cx16 45 2
2 3.5cx35 90 4
X-Ray 1 3.5cx50 45 2

4cx6 0 0
LDB 1 4cx10 45 2
4cx10 0 0
PDB 1 4cx16 45 2
4cx4 0 0
1 4cx6 45 2
4cx10 0 0
AHU 4cx16 0 0
X-Ray 4cx10 0 0
UPS DB 4cx16 0 0

4cx6 0 0
LDB 2 4cx10 90 4
4cx10 0 0
PDB 2 4cx16 90 4
1 4cx4 45 2
1 4cx6 45 2
4cx10 0 0
AHU 4cx16 0 0
X-Ray 4cx10 0 0
UPS DB 4cx16 0 0

No.of DBs Cable size Total Length


4cx6 0 0
LDB 2 4cx10 90 4
1 4cx10 45 2
PDB 3 4cx16 135 6
4cx4 0 0
1 4cx6 45 2
4cx10 0 0
AHU
AHU 4cx16 0 0
X-Ray 4cx10 0 0
UPS DB 4cx16 0 0
0
4cx6 0 0
LDB 1 4cx10 45 2
4cx10 0 0
PDB 2 4cx16 90 4
1 4cx4 45 2
4cx6 0 0
4cx10 0 0
AHU 4cx16 0 0
X-Ray 4cx10 0 0
UPS DB 4cx16 0 0
0
0
0
4cx6 0 0
LDB 2 4cx10 90 4
4cx10 0 0
PDB 2 4cx16 90 4
4cx4 0 0
1 4cx6 45 2
1 4cx10 45 2
AHU 4cx16 0 0
X-Ray 4cx10 0 0
UPS DB 4cx16 0 0

No.of DBs Cable size Total Length


4cx6 0 0
LDB 2 4cx10 90 4
1 4cx10 45 2
PDB 3 4cx16 135 6
4cx4 0 0
4cx6 0 0
4cx10 0 0
AHU 1 4cx16 45 2
X-Ray 4cx10 0 0
UPS DB 4cx16 0 0
0
4cx6 0 0
LDB 1 4cx10 45 2
2 4cx10 90 4
PDB 4cx16 0 0
4cx4 0 0
1 4cx6 45 2
4cx10 0 0
AHU 4cx16 0 0
X-Ray 4cx10 0 0
UPS DB 4cx16 0 0
0
0
0
4cx6 0 0
LDB 2 4cx10 90 4
1 4cx10 45 2
PDB 3 4cx16 135 6
4cx4 0 0
2 4cx6 90 4
4cx10 0 0
AHU 4cx16 0 0
X-Ray 4cx10 0 0
UPS DB 4cx16 0 0

No.of DBs Cable size Total Length


4cx6 0 0
LDB 2 4cx10 90 4
4cx10 0 0
PDB 4 4cx16 180 8
1 4cx4 45 2
4cx6 0 0
1 4cx10 45 2
AHU 4cx16 0 0
X-Ray 4cx10 0 0
UPS DB 4cx16 0 0
0
4cx6 0 0
LDB 1 4cx10 45 2
1 4cx10 45 2
PDB 1 4cx16 45 2
4cx4 0 0
1 4cx6 45 2
4cx10 0 0
AHU 4cx16 0 0
X-Ray 4cx10 0 0
UPS DB 4cx16 0 0
0
0
0
4cx6 0 0
LDB 2 4cx10 90 4
4cx10 0 0
PDB 3 4cx16 135 6
4cx4 0 0
1 4cx6 45 2
4cx10 0 0
AHU 4cx16 0 0
X-Ray 4cx10 0 0
UPS DB 4cx16 0 0
No.of DBs Cable size Total Length
4cx6 0 0
LDB 2 4cx10 90 4
4cx10 0 0
PDB 4 4cx16 180 8
4cx4 0 0
2 4cx6 90 4
4cx10 0 0
AHU 4cx16 0 0
X-Ray 4cx10 0 0
UPS DB 4cx16 0 0
0
4cx6 0 0
LDB 1 4cx10 45 2
2 4cx10 90 4
PDB 4cx16 0 0
4cx4 0 0
1 4cx6 45 2
4cx10 0 0
AHU 4cx16 0 0
X-Ray 4cx10 0 0
UPS DB 4cx16 0 0

4cx6 0 0
LDB 2 4cx10 90 4
4cx10 0 0
PDB 3 4cx16 135 6
4cx4 0 0
1 4cx6 45 2
4cx10 0 0
AHU 4cx16 0 0
X-Ray 4cx10 0 0
UPS DB 4cx16 0 0

No.of DBs Cable size Total Length


4cx6 0 0
LDB 2 4cx10 90 4
4 4cx10 180 8
PDB 4cx16 0 0
4cx4 0 0
1 4cx6 45 2
4cx10 0 0
AHU 4cx16 0 0
X-Ray 4cx10 0 0
UPS DB 4cx16 0 0
0
4cx6 0 0
LDB 1 4cx10 45 2
2 4cx10 90 4
PDB 4cx16 0 0
4cx4 0 0
4cx6 0 0
4cx10 0 0
AHU 4cx16 0 0
X-Ray 4cx10 0 0
UPS DB 4cx16 0 0

4cx6 0 0
LDB 2 4cx10 90 4
4cx10 0 0
PDB 3 4cx16 135 6
4cx4 0 0
2 4cx6 90 4
4cx10 0 0
AHU 4cx16 0 0
X-Ray 4cx10 0 0
UPS DB 4cx16 0 0

No.of DBs Cable size Total Length


4cx6 0 0
LDB 3 4cx10 135 6
4cx10 0 0
PDB 3 4cx16 135 6
4cx4 0 0
4cx6 0 0
4cx10 0 0
AHU 4cx16 0 0
AHU Panel-3 1 3.5cx25 45 2
X-Ray 4cx10 0 0
UPS DB 4cx16 0 0
0
4cx6 0 0
LDB 4cx10 0 0
4cx10 0 0
PDB 4cx16 0 0
4cx4 0 0
4cx6 0 0
4cx10 0 0
AHU 4cx16 0 0
AHU Panel-4 1 3.5cx25 45 2
X-Ray 4cx10 0 0
UPS DB 4cx16 0 0
0
0
0
4cx6 0 0
LDB 2 4cx10 90 4
4cx10 0 0
PDB 2 4cx16 90 4
4cx4 0 0
4cx6 0 0
4cx10 0 0
AHU 4cx16 0 0
X-Ray 4cx10 0 0
UPS DB 4cx16 0 0
240

Wing-B,D & F
Cable Size Length Gland
3.5cx25 sq m 90 4
3.5cx35 sq m 90 4
3.5cx50 sq m 45 2
4cx4sq mm 135 6
4cx6sq mm 765 34
4cx10 sq mm 2340 104
4cx16 sq mm 1935 86
396.492
DB Detail
Ligtht DB Power DB AHU
4way TPN 6way TPN 8way TPN 8way TPN 10way TPN 4way TPN
Basement 5 6 5 1
Ground Floor 9 4 13 1
First Floor 8 4 12 2
Second Floor 9 4 20 2
Third Floor 7 4 12 2
Fourth Floor 6 4 11 2
Fifth Floor 7 4 14 3
Sixth Floor 10 2 8 8
Total 0 61 32 95 21 0
AHU
6way TPN 8way TPN

0 0
Earthing Wire/Strip Detail

Copper Plate (In Sets)


Length of
No.of Cable
Sl.No. Description Panel/DBs tray/Riser 600mmx600mmx6.3mm
1 Floor Panel 12
2 Cable Tray (for Power Cables)
3 Cable Tray in Shaft only (L.V) 4700
4 Riser (In shaft) 80
5 DBs (Lights+Power) 147
6 17nos. Lifts (Horizontal Length) 220
7 MDB-Lift 1
8 Lift Panel-WD1
9 Lift Panel-WC1
10 Lift Panel-WF1
11 Lift Panel-WF2
12 Lift Panel-WC2
13 Lift Panel-WD2
14 Lift Panel-WD3
15 Lift Panel-WF3
16 Lift Panel-WA
7 AHU 80
8 AHU DBs 4
9 UPS Panel 1
10 UPS DBs 40
11 Equipment DBs 8
12 5 nos. LMR DBs 9
13 MDB (Kichen) 2
14 Panel (Kitchen) 1
15 Kichen DBs 6
16 MDB-CSSD
17 Pressurization Panel 3
18 Hospital Basement Panel
19 Ventilation Panel-1
20 AHU & Vent.Panel-2
21
22
Total
G.I Plate (In Sets) Copper Earthing Strip (mts) G.I Earthing Strip (mts)

300mmx300mmx6.15mm 25mm x 6mm 32mm x 6mm 25mm x 6mm 32mm x 6mm


12

9400
160

440

1
1
1
1
1
1
1
1
1

40

12 0 0 9840 160
hing Strip (mts) GI wire (mts)

40mm x 6mm 8 SWG 6 SWG

1470

800
40

400
80
90

0 2710 0
Hospital Inventory'

Proposed Electrical Points for each Flats for Proposed ESIC Hospital, Mandi, H.P.

S. N. Description MCB Control Mirror Light Fix Light Fix Light FixLight Fix Light Fix Light Fix Tube Tube Tube Tube BulkH Ceilin 6A NP Exhau UPS UPS2 6A Extra 16A G/w Com. Tele.P TV OTs Metal
Light 4x18 CFL Light Light Light Light ead g Fan sock st Fan 6A x6A Sock 2x6A Socket Bs-3 Point oint Point Light Clad
Primary Loop 1x11 CFL 2x18 2x18 CFL 2x36CFL 1x13 BSL (Rec.) 2x36w 2x40w 1x40w 1x36w Light et socke Socke et Sock
t t et on
BS-
Basement 2/3
Total 0 0 0 305 11 11 0 176 0 0 356 14 44 25 11 0 25 26 72 25 33 3 0 1
Ground Floor
Total 0 0 16 145 0 797 11 33 80 165 12 15 23 14 13 18 11 0 106 72 200 18 109 5 1 1
First Floor
Type-1 1 10 29 30 30 5 2 8 4 6 41 40 3 8 7 5
Type-2 1 6 26 15 5 4 5 6 5 5
Total (6*Type-2) 6 36 0 156 0 0 0 90 0 0 0 0 0 30 0 0 24 30 36 30 30 0 0 0
Total (2*Type-1) 2 0 20 58 0 60 60 10 0 4 16 0 8 12 0 0 0 82 80 6 16 14 0 10
Type-8 4 8 3 2 24 3 14 4 4 2
Blood Bank 52 10 8 6
Eye Bank 52 10 8 6
Unknown Area 52 5 5 10
Wing-D 13 44 28 35 8 6 1 5 11 11 8 9 2 3
Wing-C 7 40 15 5 11 7 2
Corridor 25 172 197
Total 25 172 32 128 20 494 0 60 60 241 0 12 61 8 23 47 0 0 24 163 159 44 81 16 3 10
Second Floor
Type-1 1 10 29 30 30 5 2 8 4 6 40 40 3 8 7 5
Total (8*Type-1) 8 0 80 232 0 240 240 40 0 16 64 0 32 48 0 0 0 320 320 24 64 56 40
Type-A1 2 2 35 11 52 10 8 21 14 23 26 21 24
Type-C 2 2 29 11 14 2 5 22 15 24 25 22 24
Type-6 6 57 9 6 3 1 5 9 8 5 7 4
Corridor 32 224 254
Total 32 224 18 4 80 607 0 240 262 115 0 22 79 0 46 96 0 0 29 376 379 72 119 60 0 40

Third Floor
Type-1 1 10 29 30 30 5 2 8 4 6 41 40 3 8 7 5
Type-3 2 2 14 13 1 4 16 3 10 10 11
Type-4 1 12 1 22 12 5 4 2 6 1 22 20 2 4 4 2
Total (3*Type-1) 3 0 30 87 0 90 90 15 0 6 24 0 12 18 0 0 0 123 120 9 24 21 15
Total (3*Type-3) 6 6 0 42 0 0 0 39 0 0 3 0 12 0 0 0 48 9 30 30 33 0
Total (2*Type-4) 2 24 2 44 0 24 0 10 0 0 8 0 4 12 2 0 0 44 40 4 8 8 0 4
Type-5 14 10 8 2 1 4 2
Type-6 6 57 9 6 3 1 5 9 8 5 7 4
Type-7 2 2 24 24 2 1 3 14 9 16 17 14 16
Type-8 4 8 3 2 24 3 14 4 4 2
Corridor 20 140 160
Total 20 140 23 40 32 431 0 114 90 109 0 14 71 3 48 49 2 0 57 206 223 62 92 33 0 19

Fourth Floor
Type-1 1 10 29 30 30 5 2 8 4 6 41 40 3 8 7 5
Type-3 2 2 14 13 1 4 16 3 10 10 11
Total (4*Type-1) 4 0 40 116 0 120 120 20 0 8 32 0 16 24 0 0 0 164 160 12 32 28 20
Total (2*Type-3) 4 4 0 28 0 0 0 26 0 0 2 0 8 0 0 0 32 6 20 20 22 0
Type-5 14 10 8 2 1 4 2
Type-6 6 57 9 6 3 1 5 9 8 5 7 4
Type-7 2 2 24 24 2 1 3 14 9 16 17 14 16
Type-8 4 8 3 2 24 3 14 4 4 2
Conference+waiting 2 23 32 12 4 4 8 9 4 6
+Dyp.Medical
Corridor 18 124 142
Total 18 124 20 16 40 407 0 120 152 103 0 20 70 3 44 47 0 0 41 208 222 55 87 32 0 20

Fifth Floor
Type-1 1 10 29 30 30 5 2 8 4 6 41 40 3 8 7 5
Type-11 4 7 12 8 1 4 6 8 4 5 2
Total (2*Type-1) 2 0 20 58 0 60 60 10 0 4 16 0 8 12 0 0 0 82 80 6 16 14 10
Total (2*Type-11) 0 8 0 14 0 0 0 24 0 0 16 0 2 8 0 0 0 12 16 8 10 4
Type-6 6 57 9 6 3 1 5 9 8 5 7 4
Type-7 2 2 24 24 2 1 3 14 16 17 14 16

SPC Engineers Pvt. Ltd. I - 34


Hospital Inventory'
S. N. Description MCB Control Mirror Light Fix Light Fix Light FixLight Fix Light Fix Light Fix Tube Tube Tube Tube BulkH Ceilin 6A NP Exhau UPS UPS2 6A Extra 16A G/w Com. Tele.P TV OTs Metal
Light 4x18 CFL Light Light Light Light ead g Fan sock st Fan 6A x6A Sock 2x6A Socket Bs-3 Point oint Point Light Clad
Primary Loop 1x11 CFL 2x18 2x18 CFL 2x36CFL 1x13 BSL (Rec.) 2x36w 2x40w 1x40w 1x36w Light et socke Socke et Sock
Type-9 8 8 4 8 t t 8 et on 8 8 8 8
4 2 28 8 18 18 BS- 1 2 16
Type-10 2/3

SPC Engineers Pvt. Ltd. I - 35


Hospital Inventory'
S. N. Description MCB Control Mirror Light Fix Light Fix Light FixLight Fix Light Fix Light Fix Tube Tube Tube Tube BulkH Ceilin 6A NP Exhau UPS UPS2 6A Extra 16A G/w Com. Tele.P TV OTs Metal
Light 4x18 CFL Light Light Light Light ead g Fan sock st Fan 6A x6A Sock 2x6A Socket Bs-3 Point oint Point Light Clad
Primary Loop 1x11 CFL 2x18 2x18 CFL 2x36CFL 1x13 BSL (Rec.) 2x36w 2x40w 1x40w 1x36w Light et socke Socke et Sock
Nisu+Nursury 4 66 16 8 8 5 2 t t2 9 et on 2 5 5
19 6 1 14 13 4 15 3 BS- 1 1 1
Septic +Ots/LC/CH 2/3
Corridor 33 264 297
Total 33 264 10 41 20 526 0 76 71 83 42 29 36 0 14 64 2 0 35 157 133 49 62 30 1 26

Sixth Floor
Type-9 8 8 4 8 8 8 8 8 8
Type-10 4 2 28 8 18 18 1 2 2 1 16
Type-11 4 7 12 8 1 4 6 8 4 5 2
Type-12 35 30 15 4 1 1 7 1 4 4 2
Total (3*Type-9) 0 24 0 0 0 0 0 24 0 12 0 0 0 24 0 0 0 24 24 24 24 24
Total (4*Type-10) 0 0 0 16 0 0 8 0 112 0 0 0 0 32 0 0 72 72 4 8 8 0 4 64
Total (2*Type-11) 0 8 0 14 0 0 0 24 0 0 16 0 2 8 0 0 0 12 16 8 10 4
Total (2*Type-12) 0 0 0 70 0 60 30 0 0 0 0 0 0 8 2 0 2 14 2 8 8 0 4
Type-3 2 2 14 13 1 4 16 3 10 10 11
Type-6 6 57 9 6 3 1 5 9 8 5 7 4
AHU+Pre.+Post 10 39 48 42 44 5 6 45 6 6 42 2 54 55 6 17 9
Area
OTS/CHS/LCS 1 52 3 4 25 1 2 7 1 1 1
Corridor 34 252 286
Total 34 252 9 96 39 508 0 102 82 79 112 49 65 0 13 84 44 0 92 190 126 70 86 42 4 68

Final Total 162 1176 128 470 231 4075 22 756 797 1071 166 161 761 42 245 430 70 0 203 409 789 609 1514 609 395 669 221 9 185
BS-1 (BS-3) 43 43 43 43
BS-2 94 # 188 94 94
BS-4 24 48 24
Grand Total 246 433 1219 840 1605 770
16A-1soc/ckt. 165
16A-2soc/ckt. 720
extra 16A switched socket 282

SPC Engineers Pvt. Ltd. I - 36


Hospital Inventory'
S. N. Description MCB Control Mirror Light Fix Light Fix Light FixLight Fix Light Fix Light Fix Tube Tube Tube Tube BulkH Ceilin 6A NP Exhau UPS UPS2 6A Extra 16A G/w Com. Tele.P TV OTs Metal
Light 4x18 CFL Light Light Light Light ead g Fan sock st Fan 6A x6A Sock 2x6A Socket Bs-3 Point oint Point Light Clad
Primary Loop 1x11 CFL 2x18 2x18 CFL 2x36CFL 1x13 BSL (Rec.) 2x36w 2x40w 1x40w 1x36w Light et socke Socke et Sock
Type-1 1 10 29 30 30 5 2 8 4 6 t t 40 et on 40 3 8 7
1 6 26 15 5 5 BS- 6 5 5
Type-2
2/3
Type-3 2 2 14 13 1 4 3 10.00 10 11
Type-4 1 12 1 22 12 5 4 2 6 1 22 20 2 4 4
Type-5 14 10 8 2 1 4 2
Type-6 6 57 9 6 3 1 5 9 8 5 7 4
Type-7 2 2 24 24 2 1 3 14 16 17 14 16
Type-8 4 8 3 2 24 3 14 4 4 2
Type-9 8 8 4 8 8 8 8 8 8
Type-10 4 2 28 8 18 1 2 2
Type-11 4 7 12 8 1 4 6 8 4 5 2
Type-12 35 30 15 4 1 7 1 4 5
Type-A1 2 2 35 11 52 10 8 21 23 26 21 24
Type-C 2 2 29 11 14 2 5 22 24 25 22 24

SPC Engineers Pvt. Ltd. I - 37


Hospital Inventory'

Electrical Points for each Flats for Proposed ESIC Hospital, Mandi, H.P. Proposed Electrical Points for each Flats fo

S. N. Description Primary Secondary


Point Point

Basement
Total 350 523
Ground Floor
Total 500 790
First Floor
Type-1 70 49
Type-2 21 27
Total (6*Type-2) 126 162
Total (2*Type-1) 140 98
Type-8 35 23
Blood Bank 12 36
Eye Bank 12 36
Unknown Area 14 34
Wing-D 55 79
Wing-C 38 35
Corridor
Total 432 503
Second Floor
Type-1 66 49
Total (8*Type-1) 528 392
Type-A1 32 80
Type-C 35 25
Type-6 49 38
Corridor
Total 644 535

Third Floor
Type-1 66 49
Type-3 22 10
Type-4 38 25
Total (3*Type-1) 198 147
Total (3*Type-3) 66 30
Total (2*Type-4) 76 50
Type-5 12 22
Type-6 49 37
Type-7 33 36
Type-8 21 23
Corridor
Total 455 345

Fourth Floor
Type-1 66 49
Type-3 26 10
Total (4*Type-1) 264 196
Total (2*Type-3) 52 20
Type-5 12 22
Type-6 50 37
Type-7 36 36
Type-8 35 23
Conference+waiting 22 51
+Dyp.Medical
Corridor
Total 471 385

Fifth Floor
Type-1 66 49
Type-11 21 11
Total (2*Type-1) 132 98
Total (2*Type-11) 42 22
Type-6 50 37
Type-7 36 36

SPC Engineers Pvt. Ltd. I - 38


Hospital Inventory'
S. N. Description Primary Secondary
Point Point

Type-9 18 2
Type-10 6 28

SPC Engineers Pvt. Ltd. I - 39


Hospital Inventory'
S. N. Description Primary Secondary
Point Point

Nisu+Nursury 35 67
Septic +Ots/LC/CH 15 38
Corridor
Total 334 328

Sixth Floor
Type-9 18 2
Type-10 6 28
Type-11 21 11
Type-12 20 60
Total (3*Type-9) 54 6
Total (4*Type-10) 24 112
Total (2*Type-11) 42 22
Total (2*Type-12) 40 120
Type-3 22 10
Type-6 50 37
AHU+Pre.+Post 64 175
Area
OTS/CHS/LCS 50 35
Corridor
Total 346 517

Final Total 3532 3926


BS-1 (BS-3)
BS-2
BS-4
Grand Total
16A-1soc/ckt.
16A-2soc/ckt.
extra 16A switched socket