perete cu vata 10 cm Exterior wall


created on 30.7.2018

Thermal protection Moisture proofing Heat protection


No condensate Temperature amplitude damping: >100
U = 0,18 W/(m²K) phase shift: non relevant
Thermal capacity inside: 183 kJ/m²K
EnEV Bestand*: U<0,24 W/(m²K)

excellent insufficient excellent insufficient excellent insufficient

outside
4 6
100 5
6
25 3 4
455

300 www.ubakus.de
2

Commercial use only with Plus-, PDF- or Profi-Option (from 2.99 € / month plus VAT).
20 1
inside
1 Cement screed (20 mm) 4 Baumit Starcontact XS (6 mm)
2 aerated concrete 500kg/m³ (300 mm) 5 Rock wool façade insulation (100 mm)
3 Cement screed (25 mm) 6 Baumit Starcontact XS (4 mm)

Impact of each layer and comparison to reference values


For the following figure, the thermal resistances of the individual layers were converted in millimeters insulation. The scale
refers to an insulation of thermal conductivity 0,035 W/mK.

aerated concrete 500kg/m³ Rock wool façade insulation Equivalent


insulation thickness
(WLS 035)

0 20 40 60 80 100 120 140 160 180 200 220 240 260 280 300 320 mm
8 i
0 95 eT
u 5
ba =0,2 d ,15 =0
,1
41 O ig u =0
DI
N tzV dr Ne U tan au =0,2 U
40 sU
ch
u nie 14 s ub au
s au
es nd V Be Ne 55 U n. -H KfW ivh
m sta EnE EV 16 fW aß
r
ite au s s
är Be En nEV K elm 3-L eub Pa
W V E ba u z
EnE u Ein N
Ne KfW

Inside air : 22,0°C / 60% Thickness: 45,5 cm


Outside air: -5,0°C / 80% sd-value: 2,9 m Weight: 264 kg/m²
Surface temperature.: 20,8°C / -4,8°C Heat capacity: 262 kJ/m²K

*Comparison to the maximum U-value according to the german EnEV 2014/2016 for first-time installation or renewal of Außenwänden (Anlage 3, Page 1
Tabelle 1, Zeile 1).
All statements without guarantee

perete cu vata 10 cm, U=0,18 W/(m²K)

Temperature profile
Temperature profile
Temperature
20 Dew point
1 2 3
4 5 6
15
1 Cement screed (20 mm)
Temperature [°C]

2 aerated concrete 500kg/m³ (300 mm)


10
3 Cement screed (25 mm)
5 4 Baumit Starcontact XS (6 mm)
5 Rock wool façade insulation (100 mm)
0 6 Baumit Starcontact XS (4 mm)

-5

0 50 100 150 200 250 300 350 400 450 500


Inside [mm]
0°C Outside

Commercial use only with Plus-, PDF- or Profi-Option (from 2.99 € / month plus VAT).
www.ubakus.de

Temperature and dew-point temperature in the component. The dew-point indicates the temperature, at which water vapour
condensates. As long as the temperature of the component is everywhere above the dew-point temperature, no
condensation occurs. If the curves have contact, condensation occurs at the corresponding position.

Layers (from inside to outside)


# Material λ R Temperatur [°C] Weight
[W/mK] [m²K/W] min max [kg/m²]
Thermal contact resistance* 0,130 20,8 22,0
1 2 cm Cement screed 1,400 0,014 20,7 20,8 40,0
2 30 cm aerated concrete 500kg/m³ 0,120 2,500 8,9 20,7 150,0
3 2,5 cm Cement screed 1,400 0,018 8,8 8,9 50,0
4 0,6 cm Baumit Starcontact XS 0,820 0,007 8,8 8,8 7,5
5 10 cm Rock wool façade insulation 0,035 2,857 -4,8 8,8 12,0
6 0,4 cm Baumit Starcontact XS 0,820 0,005 -4,8 -4,8 5,0
Thermal contact resistance* 0,040 -5,0 -4,8
45,5 cm Whole component 5,571 264,5
*Thermal contact resistances according to DIN 6946 for the U-value calculation. Rsi=0,25 and Rse=0,04 according to DIN
4108-3 were used for moisture proofing and temperature profile.

Surface temperature inside (min / average / max): 20,8°C 20,8°C 20,8°C


Surface temperature outside (min / average / max): -4,8°C -4,8°C -4,8°C

Page 2
All statements without guarantee

perete cu vata 10 cm, U=0,18 W/(m²K)

Moisture proofing
This calculation was carried out with a user-defined climate for the winter period, which deviates from DIN
4108-3.
This calculation: inside: 22°C 60% outside: -5°C 80%
Requested by DIN 4108-4: inside: 20°C 50% outside: -5°C 80%

This component is free of condensate under the given climate conditions.

# Material sd-value Condensate Weight


[m] [kg/m²] [Gew.-%] [kg/m²]
1 2 cm Cement screed 0,30 - 40,0
2 30 cm aerated concrete 500kg/m³ 1,50 - 150,0
3 2,5 cm Cement screed 0,88 - 50,0
4 0,6 cm Baumit Starcontact XS 0,06 - 7,5
5 10 cm Rock wool façade insulation 0,10 - 12,0
6 0,4 cm Baumit Starcontact XS 0,04 - 5,0
45,5 cm Whole component 2,88 264,5

Commercial use only with Plus-, PDF- or Profi-Option (from 2.99 € / month plus VAT).
Humidity
The temperature of the inside surface is 20,8 °C leading to a relative humidity on the surface of 65%.Mould formation is not
expected under these conditions.
The following figure show the relative humidity inside the component.

100 Relative humidity (%)


1 2 3 saturation point
90
4 5 6
80
Relative humidity (%)

1 Cement screed (20 mm)


70
2 aerated concrete 500kg/m³ (300 mm)
60
3 Cement screed (25 mm)
50 4 Baumit Starcontact XS (6 mm)
40 5 Rock wool façade insulation (100 mm)
30 6 Baumit Starcontact XS (4 mm)
20
10
0
0 50 100 150 200 250 300 350 400 450 500
Inside [mm]
0°C Outside
www.ubakus.de

Page 3
All statements without guarantee

perete cu vata 10 cm, U=0,18 W/(m²K)

Heat protection
For the analysis of the heat protection, the temperature changes within the component were simulated during a hot summer
day:

Temperature profile
This document has been generated by the U-value calculator on www.u-wert.net. If you are harmed by the free use of these contents, the service provider is only liable in case of

36 Temperature at 3pm, 11am and 7am


34 1 2 3 Temperature at 7pm, 11pm and 3am
intent and gross negligence on the part of the service provider. For further information, please refer to the terms and conditions at http://www.u-wert.net/agb

32 4 5 6
30 1 Cement screed (20 mm)
Temperature [°C]

28 2 aerated concrete 500kg/m³ (300 mm)


26 3 Cement screed (25 mm)
24 4 Baumit Starcontact XS (6 mm)
5 Rock wool façade insulation (100 mm)
22
6 Baumit Starcontact XS (4 mm)
20
18

Commercial use only with Plus-, PDF- or Profi-Option (from 2.99 € / month plus VAT).
16
14
0 50 100 150 200 250 300 350 400 450 500
Inside [mm]
www.ubakus.de Outside

[°C] The surface temperature during the day


36 Outside
34 Inside
32
30
28
26
24
22
20
18
16
14
12 13 14 15 16 17 18 19 20 21 22 23 24 1 2 3 4 5 6 7 8 9 10 11 12
[time of day]
Top:Temperature profile within the component at different times. From top to bottom, brown lines: at 3 pm, 11 am and 7 am
and red lines at 7 pm , 11 pm and 3 am.
Bottom:Temperature on the outer ( red ) and inner ( blue ) surface in the course of a day. The arrows indicate the location of
the temperature maximum values . The maximum of the inner surface temperature should preferably occur during the
second half of the night.

Phase shift* non relevant


Amplitude attenuation ** >100 Thermal fluctuation on exterior surface: 19,7°C
TAV *** 0,001 Temperature fluctuation on interior surface 0,0°C
* The phase shift is the time in hours after which the temperature peak of the afternoon reaches the component interior.
** The amplitude attenuation describes the attenuation of the temperature wave when passing through the component. A value of 10
means that the temperature on the outside varies 10x stronger than on the inside, e.g. outside 15-35 °C, inside 24-26 °C.
*** The temperature amplitude ratio TAV is the reciprocal of the attenuation: TAV = 1 / amplitude attenuation

Page 4

Powered by TCPDF (www.tcpdf.org)

Potrebbero piacerti anche