Ishikawajima-Harima Heavy Industries Co., Ltd.

Sharjah Cement Industrial Development Co. 6

Table -1
Design Base for Illumination System

No. Area Calculation Illumination Level (Lx) Maintenance Type of


Method Ave. Min. Factor Lighting Fixture
1 Limestone Crusher House A 100 50 0.65 S, F
2 Bag Filter P 50 20 0.65 F
3 Conveyor
Conveyor head
Wallk P 100 50 0.65 F
Way (Main Walk
4 Way)
Conveyor Wallk P 20 5 0.65 F
Way (Sub Walk
5 Way) P 5 2 - -
6 Siltstone Crusher House A 100 50 0.65 S, F
7 Bag Filter P 50 20 0.65 F
8 Conveyor
Conveyor head
Wallk P 100 50 0.65 F
Way (Main Walk
9 Way)
Conveyor Wallk P 20 5 0.65 F
Way (Sub Walk
10 Way) P 5 2 - -
11 Siltstone Screening Building P 100 50 0.65 F
12 Limestone Screening Building P 100 50 0.65 F
13 Compressor House for Crushing A 100 50 0.7 F
14 Raw Material Feed Bin A 100 50 0.65 F
15 Other Floor A 20 5 0.65 F
16 Raw Meal Grindi Conveyor P 20 5 0.65 F
17 Building A 100 50 0.65 S, F
18 Outside P 50 20 0.65 S
19 Raw Material Homogenizing Silo
20 Under A 100 50 0.65 F
21 Top P 50 20 0.65 S
22 Preheater Tower A 100 50 0.65 S, F
23 Kiln Walk Way P 50 20 0.65 F
24 Drive P 100 50 0.65 S
25 Main Bag House P 100 50 0.65 S, F
26 Bypass Bag House P 100 50 0.65 S, F
27 Clinker Cooler Conveyor Head P 100 50 0.65 F
28 Building A 100 50 0.65 S, F
Conveyor Wallk
Way (Main Walk
29 Way) P 20 5 0.65 F
Conveyor Wallk
Way (Sub Walk
30 Way) P 5 2 0.65 -
31 Clinker Silo Top P 50 20 0.65 S
32 Compressor House A 100 50 0.7 S, F

Illumination Calculation_R0 5031-060 B7100-1308 R0


Ishikawajima-Harima Heavy Industries Co., Ltd.
Sharjah Cement Industrial Development Co. 6

33 Road Lighting P 20 2 0.65 H


34
35

Note: Caculation Method A: Average Illumination Calculation


P: Point Illumination Calculation

Type of Lighting FixtureS: High Pressure Sodium Lamp


F: Fluorescent Lamp
H: High PressureSodium Lamp (High-way Type)

Illumination Calculation_R0 5031-060 B7100-1308 R0