Sei sulla pagina 1di 22

Chapter 3

Safety
This chapter was written by James N. sociated with emergency disaster opera- smallest size; a 5-pound capacity will meet
Woods, W7PUP, and includes additional tions are covered best by the agencies and most requirements in the home. ABC ex-
contributors as well. This chapter will organizations affected. tinguishers are also the best choice for
focus on how to avoid potential hazards as Although the RF, ac and dc voltages in kitchen fires (the most common location of
we explore Amateur Radio and its many most amateur stations pose a potentially home fires). One disadvantage of this type
facets. We need to learn as much as pos- grave threat to life and limb, common sense is the residue left behind that might cause
sible about what could go wrong so we can and knowledge of good safety practices corrosion in electrical connectors. Another
avoid factors that might result in acci- will help us avoid accidents. Building and type of fire extinguisher suitable for ener-
dents. Amateur Radio activities are not in- operating an Amateur Radio station can be, gized electrical equipment is the carbon
herently hazardous, but like many things and is for almost all amateurs, a perfectly dioxide unit. CO2 extinguishers require the
in modern life, it pays to be informed. safe pastime. Carelessness can lead to user to be much closer to the fire, are heavy
Stated another way, while we long to be severe injury, or even death, however. The and difficult to handle, and are relatively
creative and innovative, there is still the ideas presented here are only guidelines; it expensive. For obvious reasons, water ex-
need to act responsibly. Safety begins with would be impossible to cover all safety tinguishers are not suitable for fires in or
our attitude. Make it a habit to plan work precautions. Remember: There is no sub- near electronic equipment.
carefully. Don’t be the one to say, “I didn’t stitute for common sense. Involve your family in Amateur Radio.
think it could happen to me.” Fires in well-designed electronic equip- Having other people close by is always
Having a good attitude about safety is ment are not common but are known to beneficial in the event that you need im-
not enough, however. We must be knowl- occur. Proper use of a suitable fire extin- mediate assistance. Take the valuable step
edgeable about common safety guidelines guisher can make the difference between a of showing family members how to turn
and follow them faithfully. Safety guide- small fire with limited damage and loss of off the electrical power to your equipment
lines cannot possibly cover all situations, an entire home. Make sure you know the safely. Additionally, cardiopulmonary re-
but if we approach each task with a mea- limitations of your extinguisher and the suscitation (CPR) training can save lives
sure of common sense, we should be able importance of reporting the fire to your in the event of electrical shock. Classes
to work safely. local fire department immediately. are offered in most communities. Take the
This chapter will address some of the Several types of extinguishers are suit- time to plan with your family members
most popular ham radio activities: build- able for electrical fires. The multipurpose exactly what action should be taken in the
ing and erecting antennas, constructing dry chemical or “ABC” type units are rela- event of an emergency, such as electrical
radio equipment, and the testing and tively inexpensive and contain a solid pow- shock, equipment fire or power outage.
troubleshooting of our radios. Safety as- der that is nonconductive. Avoid buying the Practice your plan!

Antenna and Tower Safety


Since antennas are generally outdoors, The complete installation must comply (EIA) in Arlington, CA.
they are affected by such potentially haz- with all applicable structural and building To ensure structural safety and integ-
ardous weather as wind, ice and lightning. codes. Professional engineers design rity, you must demonstrate that your tower
Learning about the potential hazards of towers to withstand code loadings — that has been designed by a qualified engineer
towers and antennas and how to do is, dead weight, wind and ice loadings that to withstand EIA-222 loadings at your
antenna work safely will pay dividends. are applicable to the environment at your specific geographic area. Further, the
ARRL Technical Advisor Paul Krugh, particular location. The latest revision of tower, foundation, guys and anchors must
N2NS, reminds us to remember that put- the EIA-222 standard is the document be installed (and maintained) according to
ting up a tower has a set of responsibilities from which professional engineers work any drawings, instructions and specifica-
associated with it. Any heavy, large and to ensure that their tower designs are struc- tions supplied by the professional engi-
permanent structure that fails or collapses turally safe. For further information, con- neer. Remember: A properly designed,
can potentially hurt or even kill somebody. tact the Electronic Industries Alliance installed and maintained tower should be

Safety 3.1
as safe as a building or a bridge! of the tower. • After the tower is installed, keep the
It is not feasible to discuss each type of • Provisions must be made to keep chil- installation safe. Inspection and main-
antenna and tower in detail, so this section dren from climbing the support. tenance recommended by the tower’s
will include only highlights. For a full • Always write to the manufacturer of the manufacturer should be carefully fol-
understanding of the specific hardware tower before purchasing and ask for in- lowed.
you will be working with, consult the stallation specifications, including guy- • If making attachments to houses or in-
manufacturer or supplier. You should dis- ing data. stallations on roofs, have a qualified
cuss your antenna plans with a qualified • Soil conditions at the tower site should person determine that the method is ade-
engineer. The ARRL Volunteer Consult- be investigated. The footings need to be quate and the loading conditions are sat-
ing Engineer program can steer you to a designed around actual soil conditions, isfactory.
knowledgeable engineer. particularly on a rocky site. • Avoid metal ladders if there are any util-
In addition, your town or city will prob- ity lines in the vicinity. Assume that any
ably require that you obtain a building TOWER TIPS line is energized — including cable tele-
permit to erect a tower or antenna. This is • Beware of used towers. Have them pro- vision and telephone lines.
their way to help ensure that the installa- fessionally inspected and contact the
tion follows good practices and that the manufacturer for installation criteria. POWER LINES
installation is safe. Wise amateurs realize • Always follow manufacturer’s instruc- Hundreds of people have been killed or
that an independent review of drawings tions, using only parts that are designed seriously injured when attempting to in-
and site inspections are beneficial and can for the model you have. stall or dismantle antennas. In virtually all
result in fewer problems in the future. • Never rush into projects. Consult the cases, the victim was aware of the haz-
Towers must have a properly engineered most experienced amateurs in your ards, including the potential for serious
support, both for the tower sections them- community for assistance, especially if electrical shock, but did not take the nec-
selves as well as guy wire attachments. you are new to tower installation. essary steps to eliminate the risks. Never
Sometimes towers are braced to buildings • Check with your local building officials. install antennas, towers and masts near
for added support. The Antenna Supports • Liability may be increased with a tower power lines. How far away is considered
chapter of The ARRL Antenna Book covers installation. Check with your insurer to safe? Towers and masts should be in-
this subject in greater detail. Towers are ensure your coverage is adequate. stalled twice the height of the installation
available commercially in both guyed and • Consider your neighbors about any haz- away from power lines. Every electrical
self-supporting styles, and constructed of ards your antennas may present to them. wire must be considered dangerous. If the
both steel and aluminum materials. Masts • Don’t let your installation become an installation should contact power lines,
may be wood or metal. One popular and “attractive nuisance.” Take steps to in- you or those around you could be killed! If
inexpensive mast used to support small stall barriers so your tower cannot eas- you have any questions about power lines,
antennas is the tubular mast often sold for ily be climbed by others, particularly contact your electrical utility, city inspec-
TV antenna use. These come in telescoping adventurous children. tor or a qualified professional.
sections, in heights from 20 to 50 ft. • Use only the highest quality materials If, for some reason your tower or antenna
Aluminum extension ladders are some- in your system. structure begins to fall, get away from it
times used for temporary antenna sup- • Make sure you have all the tools needed immediately! If it contacts energized lines,
ports, such as at Field Day sites. One before starting. Some specialized tools it can become a lethal hazard if you are
problem with this approach is the diffi- (such as a gin pole) may be required. touching any part of the conductive struc-
culty in holding down the bottom section • Never erect an antenna, tower or rotor ture. If a coworker becomes energized, do
while “walking up” the ladder. Do not try during an electrical storm or rainstorm, not touch the person! The safest practice
to erect this type of support alone. or when lightning is a possibility. is to keep all others clear of the area, call
Trees are sometimes pressed into ser- • The assembly crew as well as those 911, and just wait for the power company
vice for holding one end of a wire antenna. climbing the tower during erection must and rescue team to arrive and assist the vic-
When using slingshots or arrows to string wear hard hats and use appropriate per- tim. At some greater risk, a well-insulated
up the antenna, be sure no one is in range sonal protective equipment including pole such as fiberglass or PVC pipe — as
before you launch. gloves, boots, climbing belt or harness. long as possible for safety — can be uti-
Don’t forget that lifelines are needed lized in an attempt to dislodge the live wire
FACTORS TO CONSIDER WHEN when the belt is unattached from the or collapsed metal structure from the vic-
SELECTING A TOWER tower while moving. tim (with moisture, etc., wood can be a poor
• Towers have design load limitations. • Be careful not to over-stress the tower insulator — especially at high voltages!).
Make very sure the tower you consider when it is being assembled. The tower If the victim can be well cleared of the haz-
has the capacity to safely handle the manufacturer can offer suggestions that ard and is not breathing, immediately start
antenna(s) you intend to install in the will avoid jeopardizing the tower. CPR procedures and seek emergency as-
kind of environment that is applicable • Install guy wires using the proper tools. sistance. Remember, use caution and un-
to your QTH. Care should be exercised especially when derstand that during such an accident,
• The antenna must be located in such a handling loose, un-terminated, and sharp the live conductor or live antenna struc-
position that it cannot possibly tangle guy wire ends! Avoid wrapping guy wire ture can further move (lurch) suddenly
with power lines, both during normal around your hands to pull it into place, and without warning. One accident is
operation or if the structure should fall. and instead use sufficient length to easily bad enough — there is no need to have
• Sufficient yard space must be available attach it to the anchors. Use tower-rated two victims! It is best to just seek quali-
to position a guyed tower properly. A turnbuckles or similar devices to adjust fied emergency help if you are unsure of
rule of thumb is that the guy anchors tension evenly around the tower. the situation-specific hazards.
should be between 60% and 80% of the • Assign someone in the erection crew to Further information about tower safety
tower height in distance from the base monitor the use of safety equipment. appears in The ARRL Antenna Book.

3.2 Chapter 3
Electrical Wiring Around the Shack
The standard power available from
commercial mains in the United States for
residential service is 120/240-V ac. The
“primary” voltages that feed transformers
in our neighborhoods may range from
2000 to about 10,000 V. Generally, the
responsibility for maintaining the power
distribution system belongs to a utility
company, electric cooperative or city. The
“ownership” of conductors usually trans-
fers from the electric utility supplier to the
homeowner where the power connects to
the meter or weatherhead. If you are
unsure where the division of responsibil-
ity falls in your community, a call to your
electrical utility will provide the answer. Fig 3.1 — Typical division of responsibility for maintenance of electrical power
Fig 3.1 shows the typical division of re- conductors and equipment. The meter is supplied by the utility company.
sponsibility between the utility company
and the homeowner.
There are two facets to success with
electrical power: safety and performance. What Does UL Listing
Since we are not professionals, we need to Mean?
pursue safety first and consult profession- CAUTION: Listing does not
als for alternative solutions if performance mean what most consumers
is unacceptable. expect it to mean! More often than
STATION CONCERNS not the listing does not relate to
the performance of the listed
The primary electrical power supplied
product. The listing simply indi-
to your radio equipment should be con-
cates that a sample of the device
trolled by one master switch so that it is
meets certain manufacturers’
easy to kill the power in an emergency.
One convenient means is a switched outlet construction criteria. Similar
strip, as used for computer equipment. The devices from the same or different
strip should be listed by a nationally rec- manufacturers may differ signifi-
cantly in overall construction and Fig 3.2 — If the switch box feeding
ognized testing laboratory such as Under- power to your shack is equipped with a
writers Lab and incorporate a circuit performance even though all are
lock-out hole, use it. With a lock
breaker. See “What Does UL Listing investigated and listed against the through the hole on the box, the power
Mean?” and “How Safe are Outlet Strips?” same UL product category cannot be accidentally turned back on.
for warnings about poor quality products. (Photo courtesy of American ED-CO)
It is poor practice to “daisy-chain” several
power strips. If you need more outlets than
are available on a strip, have additional
convenience outlets installed. jobs may require drawings of planned positive steps to ensure that others do not
Before adding equipment to your home, work. Often the permit fee pays for an in- restore the power while you are working.
be sure that it does not overload the circuit. spector to review the work. Considering (Fig 3.2 illustrates one way to ensure that
National and local codes set permissible the risk of injury or fire if critical mistakes power will be off until you want it turned
branch capacities according to a rather are left uncorrected, a permit and inspec- on.) Check the circuit with an ac voltmeter
complex process. Here’s a safe rule of tion are well worth the effort. Don’t take to be sure that it is “dead” each time you
thumb: consider adding a new circuit if the chances — seek assistance from the build- begin work. Before restoring power, check
total load is more than 80% of the circuit ing officials or an experienced electrician your work with an ohm meter: There should
breaker or fuse rating. (This assumes that if you have any questions or doubts about be good continuity between the neutral
the fuse or breaker is correct. If you have proper wiring techniques. conductor (white wire, “silver” screw) and
any doubts, have an electrician check it.) Ordinary 120-V circuits are the most the grounding conductor (green or bare
common source of fatal electrical acci- wire, green screw). An ohmmeter should
Do It Yourself Wiring? dents. Never use bare wire for exposed indicate a closed circuit between the con-
Amateurs sometimes “rewire” parts of circuits or open-chassis construction with ductors.
their homes to accommodate their hobby. exposed connections! Remember that There should be no continuity between
Most local codes do allow for modifica- high-current, low-voltage power sources the hot conductor (black wire, “brass”
tion of wiring (by building owners), so can be just as dangerous as high-voltage screw) and the grounding conductor or the
long as the electrical codes are met. Gen- sources. neutral conductor. An ohmmeter should
erally, the building owner must obtain an Never work on electrical wiring with the indicate an open circuit between the hot
electrical permit before beginning changes conductors energized! Switch off the cir- wire and either of the other two conduc-
or additions to permanent wiring. Some cuit breaker or remove the fuse and take tors.

Safety 3.3
A commercially available plug-in tester nonabsorbent insulating tubes or bush- tection purposes.) An acceptable alternative
is the best way to test regular three-wire ings, through an opening provided for the to lightning arrestor installation is a switch
receptacles. purpose that provides a clearance of at (capable of withstanding many kilovolts)
least 2 inches; or through a drilled win- that connects the lead-in to ground when the
NATIONAL ELECTRICAL CODE dowpane. All lead-in conductors to trans- transmitter is not in use.
Fortunately, much has been learned mitting equipment must be arranged so
about how to harness electrical energy that accidental contact is difficult. Ground Conductors
safely. This collective experience has Lightning arrestors — Transmitting sta- Grounding conductors may be made
been codified into the National Electrical tions are required to have a means of drain- from copper, aluminum, copper-clad steel,
Code, or NEC. The Code details safety re- ing static charges from the antenna system. bronze or similar erosion-resistant materi-
quirements for many kinds of electrical in- An antenna discharge unit (lightning arres- als. Insulation is not required. [Lightning
stallations. Compliance with the NEC tor) must be installed on each lead-in con- and high-voltage transient events may
provides an installation that is essentially ductor that is not protected by a permanently require much larger conductors. —Ed.]
free from hazard, but not necessarily effi- and effectively grounded metallic shield, The “protective grounding conductor”
cient, convenient or adequate for good unless the antenna itself is permanently and (main conductor running to the ground rod)
service (paraphrased from NEC Article effectively grounded. (The code exception must be as large as the antenna lead-in, but
90-1a and b). For example, the NEC re- for shielded lead-ins does not apply to coax, not smaller than #10. The “operating
quirements discussed here are not ade- but to shields such as thin-wall conduit. grounding conductor” (to bond equipment
quate for lightning protection and high Coaxial braid is neither “adequate” nor chassis together) must be at least #14. There
transient voltage events. Look at “Light- “effectively grounded” for lightning pro- is a “unified” grounding electrode require-
ning/Transient Protection” for more infor-
mation. While the NEC is national in
nature and sees wide application, it is not
universal.
Local building authorities set the codes
for their area of jurisdiction. They often
incorporate the NEC in some form, while
considering local issues. For example,
Washington State specifically exempts
telephone, telegraph, radio and television
wires and equipment from conformance
to electrical codes, rules and regulations.
However, some local jurisdictions (city,
county and so on) do impose a higher level
of installation criteria, including some of
the requirements exempted by the state.
Code interpretation is a complex sub-
ject, and untrained individuals should
steer clear of the NEC itself. The NEC is
not written to be understood by do-it-
yourselfers. Therefore, the best sources of
information about code compliance and
acceptable practices are local building
officials, engineers and practicing electri-
cians. With that said, let’s look at a few
NEC requirements for radio installations.
Antenna conductors — Transmitting
antennas using hard-drawn copper wire:
#14 for unsupported spans less than
150 ft, and #10 for longer spans. Copper-
clad steel, bronze or other high-strength
conductors must be #14 for spans less
than 150 ft and #12 for longer spans.
Open-wire transmission line conductors
must be at least as large as those speci-
fied for antennas.
Lead-ins — There are several NEC
requirements for antenna lead-in conduc-
tors. For transmitting stations, their size
must be equal to or greater than that of the
antenna. Lead-ins attached to buildings
must be firmly mounted at least 3 inches
clear of the surface of the building on non- Fig 3.3 — At A, proper bonding of all grounds to electrical service panel.
absorbent insulators. Lead-in conductors Installation shown at B is unsafe — the separate grounds are not bonded. This
must enter through rigid, noncombustible, could result in a serious accident or electrical fire.

3.4 Chapter 3
ment — it is necessary to bond all ground rectly bonding ground rods. (Note: The All conductors inside the building must be
rods to the electric service entrance ground. NEC requirements do not address effective at least 4 inches away from conductors of
All utilities, antennas and any separate RF grounds. See the EMI/Direction Find- any lighting or signaling circuit except
grounding rods used must be bonded to- ing chapter of this book for information when they are separated from other con-
gether. Fig 3.3 shows correct (A) and about RF grounding practices.) ductors by conduit or insulator. Transmit-
incorrect (B) ways to bond ground rods. Fig Additionally, the Code covers some ters must be enclosed in metal cabinets,
3.4 demonstrates the importance of cor- information on safety inside the station. and the cabinets must be grounded. All
metal handles and controls accessible by
the operator must be grounded. Access
How Safe are Outlet Strips? doors must be fitted with interlocks that
CAUTION: The switch in outlet strips is generally not rated for repetitive will automatically disconnect all voltages
load break duty. Early failure and fire hazard may result from using these above 350 when the door is opened.
devices to switch loads. Misapplications are common (another bit of bad
technique that has evolved from the use of personal computers), and Ground-Fault Circuit Interrupters
manufacturers are all too willing to accommodate the market with marginal GFCIs are devices that can be used with
products that are “cheap.” common 120-V circuits to reduce the
Nonindicating and poorly designed surge protection also add to the safety chance of electrocution when the path of
hazard of using power strips. Marginally rated MOVs often fail in a manner current flow leaves the branch circuit (say,
that could cause a fire hazard, especially in outlet strips that have nonmetal- through a person’s body to another branch
lic enclosures. or ground). The NEC requires GFCI outlets
A lockable disconnect switch or circuit breaker, as shown in Fig 3.2, is a in all wet or potentially wet locations, such
better and safer station master switch. as: bathrooms, kitchens, and any outdoor
outlet with ground-level access, garages
and unfinished basements. Any area with
bare concrete floors or concrete masonry
walls should be GFCI equipped. GFCIs are
available as portable units, duplex outlets
and as individual circuit breakers. Some
early units may have been sensitive to RF
radiation but this problem appears to have
been solved. Ham radio shacks in poten-
tially wet areas (basements, out buildings)
should be GFCI equipped. Fig 3.5 is a sim-
plified diagram of a GFCI.
LIGHTNING/TRANSIENT
PROTECTION
Nearly everyone recognizes the need to
protect themselves from lightning. From
miles away, the sight and sound of light-
ning boldly illustrates its destructive
potential. Many people don’t realize that
destructive transients from lightning and
other events can reach electronic equip-
ment from many sources, such as outside
antennas, power, telephone and cable TV
installations. Many hams don’t realize that
the standard protection scheme of several
decades, a ground rod and simple “light-
ning arrestor” is not adequate.
Lightning and transient high-voltage
protection follows a familiar communi-
cations scenario: identify the unwanted
signal, isolate it and dissipate it. The dif-
ference here is that the unwanted signal is
many megavolts at possibly 200,000 A.
What can we do?
Hams cannot expect to design or install
effective lightning protection systems, but
reasonably complete protection from
Fig 3.4 — These drawings show the importance of properly bonded ground rods. lightning is available in systems designed
In the system shown in A, the 20-A breaker will not trip. In the system in B, the by lightning protection professionals.
20-A circuit breaker trips instantly. There is an equipment internal short to ground Hams can easily follow some general
— the ground rod is properly bonded back to the power system ground. Of
course, the main protection should be in a circuit ground wire in the equipment
guidelines that will protect their stations
power cord itself! against high-voltage events that are in-

Safety 3.5
duced by nearby lightning strikes or that out what building codes apply in your area tion products may offer considerable help
arrive via utility lines. Let’s talk about and have someone explain the regulations to apply their products to specific installa-
where to find professionals first, and then about antenna installation and safety. For tions. One such source is PolyPhaser
consider construction guidelines. more help, look in your telephone yellow Corporation. Look under “Ground Refer-
pages for professional engineers, light- ences,” later in this chapter, for a partial
Professional Help ning protection suppliers and contractors. list of PolyPhaser’s publications.
Start with your local government. Find Companies that sell lightning-protec-
Construction Guidelines
Ground rods — Ground rods should be
either solid copper, copper-clad steel, hot-
dipped galvanized steel or stainless steel.
They should be at least 8 ft long by 1/2 inch
in diameter (5/8 inch diameter for iron or
steel).
Bonding Conductors — Copper strap-
ping (or flashing) comes in a number of
sizes; use 1 1/ 2 inches wide and 0.051
inches thick as a minimum for ground con-
nections. Copper strap is a better lightning
and RF ground than wire because straps
have less inductance than wires. On the
other hand, straps are more expensive than
wire and more difficult to find.
Use bare copper for buried ground wires.
Fig 3.5 — Simplified diagram of a 120-V ac ground fault circuit interrupter (GFCI). (There are some exceptions; seek an
When a stray current flows from the load (or outlet) side to ground, the toroidal
current becomes unbalanced allowing detection, amplification and relay actuation expert’s advice if your soil is corrosive.)
to immediately cut off power to the load (and to the stray path!) GFCI units require Exposed runs above ground that are sub-
a manual reset after tripping. GFCI’s are required in wet locations (near kitchen ject to physical damage may require addi-
sinks, in garages, in outdoor circuits and for construction work.) They are tional protection (a conduit) to meet code
available as portable units or combined with over-current circuit breakers for requirements. Wire size depends on the
installation in entrance panels.
application, but never use anything smaller
than #6 AWG for bonding conductors.
Local lightning-protection experts or
About the National Electrical Code building inspectors can recommend sizes
Exactly how does the National Electrical Code become a require- for each application.
ment? How is it enforced? Tower and Antennas
Cities and other political subdivisions have the responsibility to act for the
public safety and welfare. To address safety and fire hazards in buildings, Because a tower is usually the highest
regulations are adopted by local laws and ordinances usually including some metal object on the property, it is the most
form of permit and accompanying inspections. Because the technology for likely strike target. Proper tower ground-
the development of general construction, mechanical and electrical codes is ing is essential to lightning protection. The
beyond most city building departments, model codes are incorporated by goal is to establish short multiple paths to
reference. There are several general building code models used in the US: the Earth so that the strike energy is divided
Uniform, BOCA and Southern Building Codes are those most commonly and dissipated.
adopted. For electrical issues, the National Electrical Code is in effect in Connect each tower leg and each fan of
virtually every community. City building officials will serve as “the authority metal guy wires to a separate ground rod.
having jurisdiction” and interpret the provisions of the Code as they apply it Space rods at least 6 ft apart. Bond the leg
to specific cases. ground rods together with a #6 AWG or
Building codes differ from planning or zoning regulations: Building codes larger copper bonding conductor (form a
are directed only at safety, fire and health issues. Zoning regulations often
ring around the tower base, see Fig 3.6).
are aimed at preservation of property values and aesthetics.
The NEC is part of a series of reference codes published by the National
Connect a continuous bonding conductor
Fire Protection Association, a nonprofit organization. Published codes are between the tower ring ground and the
regularly kept up-to-date and are developed by a series of technical commit- entrance panel. Make all connections with
tees whose makeup represents a wide consensus of opinion. The NEC is fittings approved for grounding applica-
updated every three years. tions. Do not use solder for these connec-
Do I have to update my electrical wiring as code requirements are tions. Solder will be destroyed in the heat
updated or changed? of a lightning strike.
Generally, no. Codes are typically applied for new construction and for Unless the tower is also a shunt-fed
renovating existing structures. Room additions, for example, might not antenna, use grounded metal guys. For
directly trigger upgrades in the existing service panel unless the panel was crank-up or telescoping towers, connect
determined to be inadequate. However, the wiring of the new addition would the sections with strap jumpers. Because
be expected to meet current codes. Prudent homeowners, however, may galvanized steel (which has a zinc coat-
want to add safety features for their own value. Many homeowners, for ing) reacts with copper when combined
example, have added GFCI protection to bathroom and outdoor convenience with moisture, use stainless steel hardware
outlets. between the galvanized metal and the

3.6 Chapter 3
PolyPhaser.
Both balanced line and coax arrestors Suppliers of Lightning
should be mounted to a secure ground con- Protection Equipment
nection on the outside of the building. The For current vendor contact informa-
easiest way to do this is to install a large tion, use your favorite Internet
metal enclosure as a bulkhead and ground search tool.
block. This bulkhead serves as the last line • Alpha Delta Communications:
of lightning defense, so it’s critical that it Coax lightning arrestors, coax
be installed properly. You can home-brew switches with surge protectors.
a bulkhead panel from 1/8-inch copper • The Wireman: copper wire up to
sheet, bent into a box shape. Position the #4 AWG, 2-inch flat copper strap,
bulkhead on the building exterior, 4 to 6 8-ft copper clad ground rods and
inches (minimum) away from nearby com- 1 × 1/4-inch buss bar.
bustible materials. Install a separate • Industrial Communication Engi-
ground rod for this panel and connect it neers, Ltd (ICE): Coax lightning
to the bulkhead with a short, direct con- arrestors.
nection. Bond this ground rod to the rest • PolyPhaser Corporation: Many
Fig 3.6 — Schematic of a properly lightning protection products for
grounded tower. A bonding conductor of the ground system. Mount all protec-
connects each tower leg to a ground tive devices, switches and relay discon- feed lines, towers, equipment,
rod and a buried (1 ft deep) bare, tinned nects on the outside face wall of the and so on.
copper ring (dashed line), which is also bulkhead. • Rohn: Copper strap and other
connected to the station ground and tower grounding products.
then to the ac safety ground. Locate Lightning Arrestors • Zero Surge Inc: Power line surge
ground rods on the ring, as close as protector.
possible to their respective tower legs. Feed line lightning arrestors are avail-
All connectors should be compatible able for both coax cable and balanced line.
with the tower and conductor materials Most of the balanced line arrestors use a
to prevent corrosion. See text for simple spark gap arrangement, but a bal-
conductor sizes and details of lightning
anced line impulse suppresser is available grounding electrodes. As discussed later,
and voltage transient protection.
from Industrial Communication Engi- however, all grounding systems must
neers, Ltd (ICE), Indianapolis, IN. eventually be bonded together.
Coaxial Cable Arrestors — DC block- An effective safety ground system is
copper grounding materials. ing arrestors have a fixed frequency range. necessary for every amateur station. It pro-
To prevent strike energy from entering a They present a high-impedance to light- vides a common reference potential for all
shack via the feed line, ground the feed ning (less than 1 MHz) while offering a parts of the ac system and reduces the pos-
line outside the home. Ground the coax low impedance to RF. sibility of electrical shock by ensuring that
shield to the tower at the antenna and the DC continuity arrestors (gas tubes and all exposed conductors remain at that
base to keep the tower and line at the same spark gaps) can be used over a wider fre- (low) potential. Three-wire electrical sys-
potential. Several companies offer ground- quency range than those that block dc. tems effectively ground our equipment for
ing blocks that make this job easy. Where the coax carries supply voltages to dc and low frequencies. Unfortunately, an
All grounding media at the home must remote devices (such as a mast-mounted effective ground conductor at 60 Hz
be bonded together. This includes light- preamp or remote coax switch), dc-con- (5,000,000 m wavelength) may be an ex-
ning-protection conductors, electrical ser- tinuous arrestors must be used. cellent antenna for a 20 m signal.
vice, telephone, antenna system grounds When stray RF causes interference or
and underground metal pipes. Any ground GROUNDS other problems, we need another kind of
rods used for lightning protection or en- As hams we are concerned with three ground — a low-impedance path for RF to
trance-panel grounding must be spaced at kinds of ground, which are easily confused reach the earth or some other “ground” that
least 6 ft from each other and the electrical because we call each of them “ground.” dissipates, rather than radiates, the RF
service or other utility grounds and then The first is the power line ground, which energy. Let’s call this an RF ground.
bonded to the ac system ground as required is required by building codes to ensure the In most stations, dc ground and RF
by the NEC. safety of life and property surrounding ground are provided by the same system.
electrical systems. The NEC requires that If you install ground rods, however, bond
A Radio Entrance Panel all grounds be bonded together; this is a them to each other and to the safety ground
We want to control the flow of the energy very important safety feature as well as an at the electrical service entrance. In older
in a strike. Eliminate any possible paths for NEC requirement. Ground systems to pre- houses, water lines are sometimes used for
surges to enter the building. This involves vent shock hazards are generally referred the service entrance panel ground. It is a
routing the feed lines, rotator control cables, to as the dc ground by amateurs, although good idea to check that the pipes are elec-
and so on at least 6 ft away from other nearby safety ground is a more appropriate term. trically continuous from the panel to earth.
grounded metal objects. The previous section discussed some of (Consider that Teflon tape is often used to
Every conductor that enters the struc- the features of a lightning protection seal pipe joints in modern repairs.)
ture should have its own surge suppressor grounding system. Additional information For decades, amateurs have been ad-
including antenna system control lines at on lightning, surge and EMI grounding vised to bond all equipment cabinets to an
the Radio Entrance Panel and other ser- can be found in The ARRL Antenna Book. RF ground located near the station. That’s
vices where they connect to the ac system The National Electrical Code requires a good idea, but it’s not easily achieved.
ground. They are available from a number lightning protection ground rods to be “Near” in this use is 10 ft or less for HF
of manufacturers, including ICE and separate from the power line safety operation, even less for higher frequen-

Safety 3.7
effectiveness of the ground system.
Building cold water supply systems
were used as station grounds in years past.
Connection was made via a low-imped-
ance conductor from the station ground
bus to a convenient cold water pipe, pref-
erably somewhere near the point where the
main water supply enters the house. (Hot
water lines are unsuitable for grounding
conductors.) Increased used of plastic
plumbing both inside and outside houses
is reducing the availability of this option.
If you do use the cold water line, ensure
that it has a good electrical connection to
the earth and attach it outside the structure
to reduce EMI. As with ground rods,
ensure that the water line is also bonded to
the service entrance panel.
Fig 3.7 — An effective station ground bonds the chassis of all equipment together For some installations, especially those
with low-impedance conductors and ties into a good earth ground. Note that the located above the first floor, a conven-
ground bus is in turn bonded to the service entrance panel. This connection
should be made by a licensed electrician with #6 AWG (minimum size) copper wire. tional ground system such as that just de-
scribed will make a fine dc ground but will
not provide the necessary low-impedance
path to ground for RF. The length of the
cies. At some stations, it is very difficult diameter copper water pipe runs the entire conductor between the ground bus and the
to produce an effective RF ground. When length of the operating bench. A wide cop- ultimate ground point becomes a problem.
levels of unwanted RF are low, an RF per ground braid runs from each piece of For example, the ground wire may be
ground may not be needed. (See the EMI/ equipment to a stainless-steel clamp on the about 1/4 wavelength (or an odd multiple
Direction Finding chapter for more about pipe. of 1/4 wavelength) long on some amateur
RF grounds and interference.) Some think After the equipment is bonded to a com- band. A 1/4-wavelength wire acts as an im-
that RF grounds should be isolated from mon ground bus, the ground bus must be pedance inverter from one end to the other.
the safety ground system — that is not wired to a good earth ground. This run Since the grounded end is at a very low
true! All grounds, including safety, RF, should be made with a heavy conductor impedance, the equipment end will be at a
lightning protection and commercial com- (copper braid is a good choice again) and high impedance. The likely result is RF
munications, must be bonded together in should be as short and direct as possible. hot spots around the station while the
order to protect life and property. The earth ground usually takes one of two transmitter is in operation. In this case,
The first step in building an RF ground forms. this ground system may be worse (from an
system is to bond together the chassis of all In most cases, the best approach is to RF viewpoint) than no ground at all.
equipment in your station. Choose conduc- drive one or more ground rods into the
tors large enough to provide a low-imped- earth at the point where the conductor from Ground References
ance path. The NEC requires that grounding the station ground bus leaves the house. Federal Information Processing Standards
conductors be as large as the largest con- The best ground rods to use are those avail- (FIPS) publication 94: Guideline on
ductor in the primary power circuit (#14 able from an electrical supply house. Electrical Power for ADP Installations.
for a 15-A circuit, #12 for 20 A). Copper These rods are generally 8 ft long and FIPS are available from the National
strap, sold as “flashing copper,” is excel- made from steel with a heavy copper plat- Technical Information Service.
lent for this application. Coax braid is a ing. Do not depend on shorter, thinly IAEI: Soares’ Book on Grounding, avail-
popular choice; but it is not a good ground plated rods sold by some home electronics able from International Association of
conductor unless tinned, and then it’s no suppliers, as they can quickly rust and Electrical Inspectors (IAEI).
longer very flexible. It is best to use com- soon become worthless. IEEE Std 1100: Powering and Grounding
mercially made copper braid ground strap Once the ground rod is installed, clamp Sensitive Electronics Equipment.
that is tinned and ampacity rated — wider the conductor from the station ground bus to PolyPhaser: The Grounds for Lightning
straps make better RF grounds. Avoid solid it with a clamp that can be tightened securely and EMP Protection. PolyPhaser’s
conductors; they tend to break. and will not rust. Copper-plated clamps quarterly newsletter, Striking News,
Grounding straps can be run from equip- made specially for this purpose (and match- contains articles on Amateur Radio sta-
ment chassis to equipment chassis, but a ing the rods) are available from electrical tion lightning protection in the Febru-
more convenient approach is illustrated supply houses. Multiple ground rods reduce ary and May 1994 issues. Complimen-
in Fig 3.7. In this installation, a 1/2-inch- the electrical resistance and improve the tary copies of these issues are available
from PolyPhaser.

3.8 Chapter 3
AN EARTH-CONTINUITY TESTER
This project was first published by the household equipment, demand that the detector, no matter how large or small the
Radio Society of Great Britain (RSGB) resistance of the protective earth path be- output from the Wheatstone bridge. This is
and is reproduced here by permission. This tween an exposed metal part and the pro- important, as it means correct operation of
simple ground continuity tester deter- tective earth pin is less than 0.1 Ω. the circuit doesn’t depend on the voltage of
mines the quality of the ground (earth) The equipment needed for checking to the high-current battery, particularly as it is
connection in an Amateur Radio station this standard is specialized and expensive, a chemical type whose output voltage can
installation. In the context of this discus- but this simple project provides a low-cost fall dramatically when a high current is
sion, the terms ground and earth are syn- alternative that will check resistance at being drawn. The pass/fail voltage Vpf from
onymous. 2-3 A if good-quality batteries are used. the detector then passes to the output indi-
When using mains-powered electrical To simplify use, the circuit gives a pass/ cator circuit.
equipment, a good-quality protective fail indication instead of a resistance
earth system is very important for safety. value.
Good earth connections are additionally
important for radio operation, both for WHEATSTONE BRIDGE Table 3.1
protection against lightning strikes and The circuit can be considered in three Components List
also for the greater effectiveness of anten- parts; TEST, DETECTOR and OUTPUT Resistors
nas that use earth as one half of a dipole. In INDICATOR. See the diagram in Fig 3.9 and R1, 2 0.1 Ω, 2.5 W
situations where the earth path is a func- the components list in Table 3.1. The TEST R3, 4 10k Ω
tional earth as opposed to a protective part of the circuit is based on a Wheatstone R6, 7 24k Ω
earth, a simple low-voltage, low-current bridge, where the earth resistance path R5, 8 150 Ω
continuity tester or resistance meter is forms one of the resistance arms. See Fig R9, 10 330 Ω
All resistors metal oxide 0.4 W 1%, except
usually sufficient for checking earthing re- 3.10 for the principle behind a Wheatstone R1 & R2
sistance, but for a proper test of a protec- bridge. As a consequence of the values of
tive earth a high-current tester is needed, resistance chosen (the test leads are as- Semiconductors
as shown in Fig 3.8. This is because a sumed to have a resistance of 0.1 Ω), if the U1 LM324
deteriorating earth connection in the form earth resistance is less than 0.1 Ω, the volt- D1, 2 TLY114A yellow, or TLR114A red
and TLG114A green
of a stranded wire where many of the age between the midpoints of the two Q1 BC179 (general-purpose pnp)
strands are broken will still show a low halves of the Wheatstone bridge will be Q2 BC109C (general-purpose npn)
resistance to a low-current tester but, in a positive, and if it is less than 0.1 Ω, it will
fault situation when the earth path needs be negative. This is fed to the detector part Additional items
to pass a high current to ground and thus of the circuit. The DETECTOR is an op-amp B1 1 × AA Duracell
B2 PP3, 9V
trigger a protective device, the high cur- wired as a comparator. Connected in this S1 Double pole, momentary on,
rent causes the remaining strands to burn way, it has such a high gain that its output or push-to-make
out, i.e., go open-circuit, before the pro- is roughly equal to either the positive or S2 SPST
tective device has time to operate. The negative supply rail voltage, depending on Battery clips/holders
protection is then nonexistent! whether the PD between its non-inverting Stripboard
and inverting inputs is positive or negative. Plastic case*
SAFETY STANDARDS 2 × 4mm plugs & sockets*
It doesn’t matter whether the PD is large or 2 × alligator clips
Recognizing this situation, the British small — the output will always be at either
*Only required if you are building the
and European safety standards for electri- extreme. This means there will always be a project in a case.
cal safety, for example BS EN 60335-1 for definite pass or fail indication from the

Fig 3.8 — Inside a completed tester.


Note that in an enclosed project, the
LEDs are brought out to the front
panel. Fig 3.9 — Circuit diagram of the earth-continuity tester.

Safety 3.9
Fig 3.10 — In a conventional
Wheatstone bridge circuit, the value of
an unknown resistance (Rx) is
determined by adjusting a variable
resistor (RV) with a calibrated scale
until the reading on the voltmeter is
zero. At that point (Rx/R1) = (RV/R2) so
the value of Rx is then given by Rx =
(R1 × RV)/R2. The advantage of this
method is that, at the balance point, no
current flows through the voltmeter, so
the resistance of it doesn’t affect the
measurement. This is a sensitive
method for detecting small changes in
resistance, as a small change causes a
large meter reading. Fig 3.12 — Orientation (and pin-outs) of the batteries, U1, LEDs and transistors.

Fig 3.11 — Layout of the circuit on stripboard.

3.10 Chapter 3
The OUTPUT INDICATOR circuit consists the connection to the mains plug earth pin 120 V to get amperes. If the total current
of two LEDs, driven by transistors to pro- mentioned in the previous paragraph implies required for your station is near 12 (0.8 ×
vide sufficient current, which indicate ei- that the plug is free. — Ed 15 = 12 A), you need to install another
ther a pass or a fail for an earth path circuit. Keep in mind that other rooms may
resistance of less than or more than 0.1 Ω. STATION POWER be powered from the same branch of the
Q2 is an npn transistor that switches on Amateur Radio stations generally re- electrical system, so the power consump-
when its input is high, while Q1 is a pnp quire a 120-V ac power source. (In resi- tion of any equipment connected to other
type that switches on when its input is low. dential systems voltages from 110 V outlets on the branch must be taken into
A separate supply voltage is needed for through 125 V are considered equivalent, account. Whenever possible, power your
the op-amp and LED circuit, since the test as are those from 220 V through 250 V.) station from a separate, heavy-duty line
battery voltage will drop under a heavy 120-V ac is converted to the proper ac or run directly to the distribution panel
load current. dc levels required for the station equip- through a disconnect switch or circuit
Because the output of the op-amp does ment. Power supplies should accommo- breaker that can be locked in the off posi-
not swing completely to the positive and date the measured voltage range at each tion.
negative supply rails, measures need to be station. (The measured voltage usually If you decide to install a separate heavy-
taken to ensure that the LED driver tran- varies by hour, day, season and location.) duty 120-V line or a 240-V line, consult
sistors switch off correctly. Power supply theory is covered in the the power company for local require-
Power Supplies chapter. If your station is ments. In some areas, a licensed electri-
Construction located in a room with electrical outlets, cian must perform this work. Others may
A suitable stripboard layout is shown in you’re in luck. If your station is located in require a special building permit. Even if
Fig 3.11, and Fig 3.12 shows how to iden- the basement, an attic or other area with- you are allowed to do the work yourself, it
tify and orientate several of the compo- out a convenient 120-V source, you may might need inspection by a licensed elec-
nents. Use thick wire for the test leads! need to have a new line run to your oper- trician. Go through the system and get the
ating position. necessary permits and inspections! Faulty
How To Use It Stations with high-power amplifiers wiring can destroy your possessions and
Using flying leads with suitable connec- should have a 240-V ac power source in take away your loved ones. Many fire in-
tors, eg, alligator clips, connect the circuit addition to the 120-V supply. Some am- surance policies are void if there is unap-
to each end of the earth path to be tested. plifiers may be powered from 120 V, but proved wiring in the structure.
This would usually be the mains plug earth they require current levels that may If you decide to do the job yourself,
pin and any metal part meant to be earthed. exceed the limits of standard house wir- work closely with local building officials.
Then press the test button. Release the test ing. For safety, and for the best possible Most home-improvement centers sell
switch as soon as a pass/fail indicator lights voltage regulation in the equipment, it is books to guide do-it-yourself wiring
(certainly within 5 to 10 seconds, to advisable to install a separate 240 or projects. If you have any doubts about
lengthen battery life and prevent possible 120-V line with an appropriate current doing the work yourself, get a licensed
overheating of R1 and R2). rating if you use an amplifier. electrician to do the installation.
The usual line running to baseboard out-
Safety Notice lets is rated at 15 A, although 20-A outlets Three-Wire 120-V Power Cords
The project described here may be used to may be installed in newer houses. This Most metal-cased electrical tools and
test the resistance of appliance earth con- may or may not be enough current to appliances are equipped with three-con-
nections, but it is not intended to conform to power your station. To determine how ductor power cords. Two of the conduc-
any legal requirements for the testing of much current your station requires, check tors carry power to the device, while the
electrical safety. The RSGB, ARRL and the the ratings for each piece of gear. Usually, third conductor is connected to the case or
author accept no responsibility for any acci- the manufacturer will specify the required frame. Fig 3.13 shows two commonly used
dent or injury caused by its use. Never use on current at 120 V; if the power consump- connectors.
mains equipment plugged into the mains — tion is rated in watts, divide that rating by When both plug and receptacle are prop-

Fig 3.13 — 120-V ac chassis connector wiring.

Safety 3.11
FCC RF-Exposure Regulations
FCC regulations control the amount of RF exposure the minimum necessary power at all times
that can result from your station’s operation (§§97.13, (§97.311 [a]).
97.503, 1.1307 (b)(c)(d), 1.1310 and 2.1093). The
regulations set limits on the maximum permissible Environments
exposure (MPE) allowed from operation of transmitters in The FCC has defined two exposure environments
all radio services. They also require that certain types of — controlled and uncontrolled. A controlled environ-
stations be evaluated to determine if they are in compli- ment is one in which the people who are being
ance with the MPEs specified in the rules. The FCC has exposed are aware of that exposure and can take
also required that five questions on RF environmental steps to minimize that exposure, if appropriate. In an
safety practices be added to Novice, Technician and uncontrolled environment, the people being exposed
General license examinations. are not normally aware of the exposure. The uncon-
These rules went into effect on January 1, 1998 for trolled environment limits are more stringent than the
new stations or stations that file a 610 application with controlled environment limits.
the FCC. Other existing stations have until September 1, Although the controlled environment is usually
2000 to be in compliance with the rules. intended as an occupational environment, the FCC
has determined that it generally applies to amateur
THE RULES operators and members of their immediate house-
Maximum Permissible Exposure (MPE) holds. In most cases, controlled-environment limits
All radio stations regulated by the FCC must comply can be applied to your home and property to which
with the requirements for MPEs, even QRP stations you can control physical access. The uncontrolled
running only a few watts or less. The MPEs vary with environment is intended for areas that are accessible
frequency, as shown in Table A. MPE limits are specified by the general public, such as your neighbors’
in maximum electric and magnetic fields for frequencies properties.
below 30 MHz, in power density for frequencies above The MPE levels are based on average exposure.
300 MHz and all three ways for frequencies from 30 to An averaging time of 6 minutes is used for controlled
300 MHz. For compliance purposes, all of these limits exposure; an averaging period of 30 minutes is used
must be considered separately. If any one is exceeded, for uncontrolled exposure.
the station is not in compliance. Station Evaluations
The regulations control human exposure to RF fields,
not the strength of RF fields. There is no limit to how The FCC requires that certain amateur stations be
strong a field can be as long as no one is being exposed evaluated for compliance with the MPEs. Although an
to it, although FCC regulations require that amateurs use amateur can have someone else do the evaluation, it

Table A — (From §1.1310) Limits for Maximum Permissible Exposure (MPE)


(A) Limits for Occupational/Controlled Exposure
Frequency Electric Field Magnetic Field Power Density Averaging Time
Range Strength Strength (mW/cm 2) (minutes)
(MHz) (V/m) (A/m)
0.3-3.0 614 1.63 (100)* 6
3.0-30 1842/f 4.89/f (900/f 2)* 6
30-300 61.4 0.163 1.0 6
300-1500 — — f/300 6
1500-100,000 — — 5 6
f = frequency in MHz
* = Plane-wave equivalent power density (see Note 1).

(B) Limits for General Population/Uncontrolled Exposure


Frequency Electric Field Magnetic Field Power Density Averaging Time
Range Strength Strength (mW/cm 2) (minutes)
(MHz) (V/m) (A/m)
0.3-1.34 614 1.63 (100)* 30
1.34-30 824/f 2.19/f (180/f 2)* 30
30-300 27.5 0.073 0.2 30
300-1500 — — f/1500 30
1500-100,000 — — 1.0 30
f = frequency in MHz
* = Plane-wave equivalent power density (see Note 1).
Note 1: This means the equivalent far-field strength that would have the E or H-field component calculated or measured. It does not
apply well in the near field of an antenna. The equivalent far-field power density can be found in the near or far field regions from the
relationships: Pd = |Etotal|2 / 3770 mW/cm2 or from Pd = Htotal|2 × 37.7 mW/cm2.

3.12 Chapter 3
is not difficult for hams to evaluate their own stations. The
ARRL book RF Exposure and You contains extensive Table B — Power Thresholds for Routine Evalua-
information about the regulations and a large chapter of tion of Amateur Radio Stations
tables that show compliance distances for specific anten-
nas and power levels. Generally, hams will use these tables Wavelength Evaluation Required if
to evaluate their stations. Some of these tables have been Band Power* (watts) Exceeds:
included in the FCC’s information — OET Bulletin 65 and MF
its Supplement B. If hams choose, however, they can do 160 m 500
more extensive calculations, use a computer to model their HF
80 m 500
antenna and exposure, or make actual measurements. 75 m 500
Categorical Exemptions 40 m 500
30 m 425
Some types of amateur stations do not need to be 20 m 225
evaluated, but these stations must still comply with the 17 m 125
MPE limits. The station licensee remains responsible for 15 m 100
ensuring that the station meets these requirements. 12 m 75
The FCC has exempted these stations from the evalua- 10 m 50
tion requirement because their output power, operating
VHF (all bands) 50
mode and frequency are such that they are presumed to be UHF
in compliance with the rules. 70 cm 70
Stations using power equal to or less than the levels in 33 cm 150
Table B do not have to be evaluated. For the 100-W HF 23 cm 200
ham station, for example, an evaluation would be required 13 cm 250
only on 12 and 10 meters.
Hand-held radios and vehicle-mounted mobile radios that SHF (all bands) 250
operate using a push-to-talk (PTT) button are also categori-
cally exempt from performing the routine evaluation. EHF (all bands) 250
Repeater stations that use less than 500 W ERP or those Repeater stations non-building-mounted antennas :
with antennas not mounted on buildings, if the antenna is at (all bands) height above ground level to lowest
least 10 meters off the ground, also do not need to be point of antenna < 10 m and power
evaluated. > 500 W ERP building-mounted
antennas: power > 500 W ERP
Correcting Problems
*Transmitter power = Peak-envelope power input to antenna.
Most hams are already in compliance with the MPE For repeater stations only, power exclusion based on ERP
requirements. Some amateurs, especially those using (effective radiated power).
indoor antennas or high-power, high-duty-cycle modes such
as a RTTY bulletin station and specialized stations for
moonbounce operations and the like may need to make More Information
adjustments to their station or operation to be in compli- This discussion offers only an overview of this
ance. topic; additional information can be found in RF
The FCC permits amateurs considerable flexibility in Exposure and You and on ARRLWeb at
complying with these regulations. As an example, hams can www.arrl.org/news/rfsafety/. ARRLWeb has
adjust their operating frequency, mode or power to comply links to the FCC Web site, with OET Bulletin 65
with the MPE limits. They can also adjust their operating and Supplement B and links to software that hams
habits or control the direction their antenna is pointing. can use to evaluate their stations.

erly wired, the three-contact polarized connecting any new equipment, check for “double insulated” and fed with a two-
plug connects the equipment to the system continuity from case to ground pin with wire cord. Such equipment is safe because
ground. This grounds the chassis or frame an ohmmeter. If there is no continuity, both conductors are completely insulated
of the appliance and prevents the possibil- have the equipment repaired before use. from the user. Nonetheless, there is still a
ity of electrical shock to the user. Most Use such equipment only with properly hazard if, say, a double insulated drill were
commercially manufactured test equip- installed three-wire outlets. If your house used to drill an improperly grounded case
ment and ac-operated amateur equip- does not have such outlets, consult with of a transmitter that was still plugged in.
ment is supplied with these three-wire an electrician or local building officials to Remember, all insulation is prey to age,
cords. Unfortunately, the ground wire is learn about safe alternatives. damage and wear that may erode its initial
sometimes improperly installed. Before Equipment with plastic cases is often protection.

Safety 3.13
Safe Homebrewing
Since Amateur Radio began, building ways take care of your investment. Store dents may still occur from time to time.
equipment in home workshops has been a tools in a way to prevent damage or use by Ensure that everyone in your household
major part of an amateur’s activity. In untrained persons (young children, for knows basic first aid procedures and un-
fact, in the early days, building equipment example). Keep the cutting edges of saws, derstands how to summon help in an emer-
with your hands was the only option avail- chisels and drill bits sharp. Protect metal gency. They should also know where to
able. While times and interests change, surfaces from corrosion. Frequently in- find and how to safely shut down electri-
home construction of radio equipment and spect the cords and plugs of electrical cal power in your shack and shop. Keep
related accessories remains very popular equipment and make any necessary repairs. your shop neat and orderly, with every-
and enjoyable. Building your own gear If you find that your power cord is becom- thing in its place. Do not store an exces-
need not be hazardous if you become ing frayed, do not delay its repair. Often the sive amount of flammable materials. Keep
familiar with the hazards, learn how to best solution is to buy a replacement cord clutter off the floor so no one will trip or
perform the necessary functions and fol- with a molded connector already attached. lose their footing. Exemplary housekeep-
low some basic safe practices including Protect yourself. Use of drills, saws, ing is contagious — set a good example
the ones listed below. grinders and other wood- or metal-work- for everyone!
Consider your State of Mind...when ing equipment can release small fragments Soldering. Soldering requires a certain
working on projects or troubleshooting that could cause serious eye damage. Al- degree of practice and, of course, the right
(especially where high voltage is present). ways wear safety glasses or goggles when tools. What potential hazards are in-
Some activities require a lot of concentra- doing work that might present a flying volved?
tion. As we grow older, this may be a chal- object hazard. If you use hammers, wire- • Since the solder used for virtually all elec-
lenge for some of us. Put another way, if cutters, chisels and other hand tools, you tronic components is a lead-tin alloy, the
we aren’t able to be highly alert, we should will also need the protection that safety first thing in most people’s mind is lead,
put off doing hazardous work until we are eyewear offers. Dress appropriately — a well-known health hazard. There are
better able to focus on the hazards. loose clothing (or even hair) can be caught two primary ways lead might enter our
Read instructions carefully…and follow in exposed rotating equipment such as bodies when soldering: we could breathe
them. The manufacturers of tools are the drill presses. lead fumes into our lungs or we could
most knowledgeable about how to use their Take your time. If you hurry, not only ingest (swallow) lead or lead-contami-
products safely. Tap their knowledge by will you make more mistakes and possibly nated food. Inhalation of lead fumes is
carefully reading all operating instructions spoil the appearance of your new equip- extremely unlikely because the tempera-
and warnings. Avoiding injuries with ment, you won’t have time to think things tures ordinarily used in electronic solder-
power tools requires safe tool design as through. Always plan ahead. Do not work ing are far below those needed to vaporize
well as proper operation by the user. Keep with shop tools if you can’t concentrate on lead. But since lead is soft and we may
the instructions in a place where you can what you are doing. tend to handle it with our fingers, con-
refer to them in the future. Know what to do in an emergency. De- taminating our food is a real possibility.
Keep your tools in good condition. Al- spite your best efforts to be careful, acci- For this reason, wash your hands carefully
after any soldering (or touching of solder
connections).
• Generally, solder used for electronic
components contains a flux, often a rosin
RF Burns! material. When heated the flux flows
There’s a lot of talk about hazards of RF radiation, but most people don’t freely and emits a vapor in the form of a
think about RF burns. Happily, most ham shacks offer little exposure to RF light gray smoke-like plume. This flux
current. Transmitters are enclosed, coaxial cable is the most common feed vapor, which often contains aldehydes,
line, and antennas are located well out of reach. is a strong irritant and can cause poten-
Some people have experienced a mild tingling on their lips while operating tially serious problems to persons who
with a metal microphone — a gentle reminder of “RF in the shack.” When first may have respiratory sensitivity condi-
licensed in 1963, I learned a stronger lesson. Lightbulbs were often used as tions including those who suffer from
dummy loads then: they give a nice visual indication of output power, but asthma. In most cases it is relatively easy
provide a poor load for the transmitter (not 50 Ω). Also, you can work a lot of to use a small fan to move the flux vapor
people on such a “dummy” antenna. (Don’t try this with a modern solid-state away from your eyes and face. Open a
transmitter; the mismatch could be fatal to the radio!) window, if there is one, to provide addi-
While tuning my Viking Adventurer one day, I bumped the lit bulb and it fell tional air exchange. In extreme cases use
off the table. I prevented a broken lightbulb by catching it — with my finger an organic vapor cartridge respirator.
across the cable ends that were soldered to the bulb. 50-W of RF went
• Although it is fairly obvious, be careful
through my finger tip and cauterized a path about 3/16 × 1/8 inch. It was an
when soldering not to burn yourself. A
extremely painful burn; I would rather have broken the bulb. To avoid RF
burns, insulate or enclose any exposed RF conductors and keep your soldering iron stand is helpful.
antennas out of reach. Ground mounted vertical antennas that carry more • Solvents are often used to remove ex-
than a few watts should be enclosed by an insulator such as a PVC pipe cess flux after the parts have cooled to
slipped over the radiator or an 8-ft-high fence around the antenna base. room temperature. Minimize skin con-
— Bob Schetgen, KU7G, QEX Managing Editor tact with solvents by wearing molded
gloves that are resistant to the solvent.

3.14 Chapter 3
RF Radiation and Electromagnetic Field Safety
Amateur Radio is basically a safe ac- low to cause heating. These functions will experience a safe SAR.
tivity. In recent years, however, there has return to normal when the field is re- Nevertheless, thermal effects of RF en-
been considerable discussion and con- moved. Although research is ongoing, no ergy should not be a major concern for
cern about the possible hazards of elec- harmful health consequences have been most radio amateurs, because of the power
tromagnetic radiation (EMR), including linked to these changes. levels we normally use and the intermit-
both RF energy and power-frequency In addition to the ongoing research, tent nature of most amateur transmissions.
(50-60 Hz) electromagnetic (EM) fields. much else has been done to address this Amateurs spend more time listening than
FCC regulations set limits on the maxi- issue. For example, FCC regulations set transmitting, and many amateur transmis-
mum permissible exposure (MPE) al- limits on exposure from radio transmitters. sions such as CW and SSB use low-duty-
lowed from the operation of radio The Institute of Electrical and Electronics cycle modes. (With FM or RTTY, though,
transmitters. These regulations do not Engineers, the American National Stan- the RF is present continuously at its maxi-
take the place of RF-safety practices, dards Institute and the National Council for mum level during each transmission.) In
however. This section deals with the Radiation Protection and Measurement, any event, it is rare for radio amateurs to
topic of RF safety. among others, have recommended volun- be subjected to RF fields strong enough to
This section was prepared by members tary guidelines to limit human exposure to produce thermal effects, unless they are
of the ARRL RF Safety Committee RF energy. The ARRL has established the close to an energized antenna or un-
and coordinated by Dr. Robert E. Gold, RF Safety Committee, consisting of con- shielded power amplifier. Specific sug-
WBØKIZ. It summarizes what is now cerned medical doctors and scientists, serv- gestions for avoiding excessive exposure
known and offers safety precautions based ing voluntarily to monitor scientific are offered later in this chapter.
on the research to date. research in the fields and to recommend
All life on Earth has adapted to survive safe practices for radio amateurs. ATHERMAL EFFECTS OF EMR
in an environment of weak, natural, low- Research about possible health effects
frequency electromagnetic fields (in addi- THERMAL EFFECTS OF RF resulting from exposure to the lower level
tion to the Earth’s static geomagnetic ENERGY energy fields, the athermal effects, has
field). Natural low-frequency EM fields Body tissues that are subjected to very been of two basic types: epidemiological
come from two main sources: the sun, and high levels of RF energy may suffer seri- research and laboratory research.
thunderstorm activity. But in the last 100 ous heat damage. These effects depend on Scientists conduct laboratory research
years, man-made fields at much higher the frequency of the energy, the power into biological mechanisms by which EMR
intensities and with a very different spec- density of the RF field that strikes the body may affect animals including humans. Epi-
tral distribution have altered this natural and factors such as the polarization of the demiologists look at the health patterns of
EM background in ways that are not yet wave. large groups of people using statistical
fully understood. Researchers continue to At frequencies near the body’s natural methods. These epidemiological studies
look at the effects of RF exposure over a resonant frequency, RF energy is absorbed have been inconclusive. By their basic de-
wide range of frequencies and levels. more efficiently, and an increase in heat- sign, these studies do not demonstrate
Both RF and 60-Hz fields are classified ing occurs. In adults, this frequency usu- cause and effect, nor do they postulate
as nonionizing radiation, because the fre- ally is about 35 MHz if the person is mechanisms of disease. Instead, epidemi-
quency is too low for there to be enough grounded, and about 70 MHz if insulated ologists look for associations between an
photon energy to ionize atoms. (Ionizing from the ground. Individual body parts environmental factor and an observed pat-
radiation, such as X-rays, gamma rays and may be resonant at different frequencies. tern of illness. For example, in the earliest
even some ultraviolet radiation has enough The adult head, for example, is resonant research on malaria, epidemiologists ob-
energy to knock electrons loose from their around 400 MHz, while a baby’s smaller served the association between populations
atoms. When this happens, positive and head resonates near 700 MHz. Body size with high prevalence of the disease and the
negative ions are formed.) Still, at suffi- thus determines the frequency at which proximity of mosquito infested swamp-
ciently high power densities, EMR poses most RF energy is absorbed. As the fre- lands. It was left to the biological and medi-
certain health hazards. It has been known quency is moved farther from resonance, cal scientists to isolate the organism
since the early days of radio that RF energy less RF heating generally occurs. Specific causing malaria in the blood of those with
can cause injuries by heating body tissue. absorption rate (SAR) is a term that de- the disease, and identify the same organ-
(Anyone who has ever touched an improp- scribes the rate at which RF energy is ab- isms in the mosquito population.
erly grounded radio chassis or energized sorbed in tissue. In the case of athermal effects, some
antenna and received an RF burn will agree Maximum permissible exposure (MPE) studies have identified a weak association
that this type of injury can be quite pain- limits are based on whole-body SAR val- between exposure to EMF at home or at
ful.) In extreme cases, RF-induced heating ues, with additional safety factors in- work and various malignant conditions
in the eye can result in cataract formation, cluded as part of the standards and including leukemia and brain cancer. A
and can even cause blindness. Excessive regulations. This helps explain why these larger number of equally well-designed
RF heating of the reproductive organs can safe exposure limits vary with frequency. and performed studies, however, have
cause sterility. Other health problems also The MPE limits define the maximum elec- found no association. A risk ratio of be-
can result from RF heating. These heat- tric and magnetic field strengths or the tween 1.5 and 2.0 has been observed in
related health hazards are called thermal plane-wave equivalent power densities as- positive studies (the number of observed
effects. A microwave oven is a positive ap- sociated with these fields, that a person cases of malignancy being 1.5 to 2.0 times
plication of this thermal effect. may be exposed to without harmful effect the “expected” number in the population).
There also have been observations of — and with an acceptable safety factor. Epidemiologists generally regard a risk
changes in physiological function in the The regulations assume that a person ex- ratio of 4.0 or greater to be indicative of a
presence of RF energy levels that are too posed to a specified (safe) MPE level also strong association between the cause and

Safety 3.15
effect under study. For example, men who nisms for the systematic initiation or pro- reflect the current research. The new IEEE
smoke one pack of cigarettes per day in- motion of cancer by these extremely weak standard was adopted by ANSI in 1992.
crease their risk for lung cancer tenfold 60-Hz fields have been identified. The IEEE standard recommends fre-
compared to nonsmokers, and two packs 3. While it is impossible to prove that no quency-dependent and time-dependent
per day increases the risk to more than 25 deleterious health effects occur from expo- maximum permissible exposure levels.
times the nonsmokers’ risk. sure to any environmental factor, it is neces- Unlike earlier versions of the standard, the
Epidemiological research by itself is sary to demonstrate a consistent, significant, 1991 standard recommends different RF
rarely conclusive, however. Epidemiol- and causal relationship before one can con- exposure limits in controlled environ-
ogy only identifies health patterns in clude that such effects do occur. ments (that is, where energy levels can be
groups — it does not ordinarily determine In a report dated October 31, 1996, a accurately determined and everyone on
their cause. And there are often confound- committee of the National Research Coun- the premises is aware of the presence of
ing factors: Most of us are exposed to cil of the National Academy of Sciences EM fields) and in uncontrolled environ-
many different environmental hazards that has concluded that no clear, convincing ments (where energy levels are not known
may affect our health in various ways. evidence exists to show that residential or where people may not be aware of the
Moreover, not all studies of persons likely exposures to electric and magnetic fields presence of EM fields). FCC regulations
to be exposed to high levels of EMR have (EMFs) are a threat to human health. also include controlled/occupational and
yielded the same results. A National Cancer Institute epidemio- uncontrolled/general population exposure
There also has been considerable labo- logical study of residential exposure to environments.
ratory research about the biological magnetic fields and acute lymphoblastic The graph in Fig 3.14 depicts the 1991
effects of EMR in recent years. For ex- leukemia in children was published in the IEEE standard. It is necessarily a complex
ample, some separate studies have indi- New England Journal of Medicine in July graph, because the standards differ not only
cated that even fairly low levels of EMR 1997. The exhaustive, seven-year study for controlled and uncontrolled environ-
might alter the human body’s circadian concludes that if there is any link at all, it ments but also for electric (E) fields and
rhythms, affect the manner in which T is far too weak to be concerned about. magnetic (H) fields. Basically, the lowest
lymphocytes function in the immune sys- Readers may want to follow this topic E-field exposure limits occur at frequencies
tem and alter the nature of the electrical as further studies are reported. Amateurs between 30 and 300 MHz. The lowest
and chemical signals communicated should be aware that exposure to RF and H-field exposure levels occur at 100-
through the cell membrane and between ELF (60 Hz) electromagnetic fields at all 300 MHz. The ANSI standard sets the maxi-
cells, among other things. Although these power levels and frequencies has not been mum E-field limits between 30 and 300 MHz
studies are intriguing, they do not demon- fully studied under all circumstances. at a power density of 1 mW/cm2 (61.4 V/m)
strate any effect of these low-level fields “Prudent avoidance” of any avoidable in controlled environments — but at one-
on the overall organism. EMR is always a good idea. Prudent avoid- fifth that level (0.2 mW/cm2 or 27.5 V/m) in
Much of this research has focused on ance doesn’t mean that amateurs should uncontrolled environments. The H-field
low-frequency magnetic fields, or on RF be fearful of using their equipment. Most limit drops to 1 mW/cm2 (0.163 A/m) at
fields that are keyed, pulsed or modulated amateur operations are well within the 100-300 MHz in controlled environments
at a low audio frequency (often below MPE limits. If any risk does exist, it will and 0.2 mW/cm2 (0.0728 A/m) in uncon-
100 Hz). Several studies suggested that almost surely fall well down on the list of trolled environments. Higher power den-
humans and animals could adapt to the causes that may be harmful to your health sities are permitted at frequencies below
presence of a steady RF carrier more (on the other end of the list from your auto- 30 MHz (below 100 MHz for H fields) and
readily than to an intermittent, keyed or mobile). It does mean, however, that hams above 300 MHz, based on the concept
modulated energy source. should be aware of the potential for expo- that the body will not be resonant at those
The results of studies in this area, plus sure from their stations, and take what- frequencies and will therefore absorb less
speculations concerning the effect of vari- ever reasonable steps they can take to energy.
ous types of modulation, were and have minimize their own exposure and the ex- In general, the 1991 IEEE standard re-
remained somewhat controversial. None posure of those around them. quires averaging the power level over time
of the research to date has demonstrated periods ranging from 6 to 30 minutes for
that low-level EMR causes adverse health Safe Exposure Levels power-density calculations, depending on
effects. How much EM energy is safe? Scien- the frequency and other variables. The
Given the fact that there is a great deal of tists and regulators have devoted a great ANSI exposure limits for uncontrolled
ongoing research to examine the health deal of effort to deciding upon safe RF- environments are lower than those for con-
consequences of exposure to EMF, the exposure limits. This is a very complex trolled environments, but to compensate
American Physical Society (a national problem, involving difficult public health for that the standard allows exposure lev-
group of highly respected scientists) issued and economic considerations. The recom- els in those environments to be averaged
a statement in May 1995 based on its review mended safe levels have been revised over much longer time periods (generally
of available data pertaining to the possible downward several times over the years — 30 minutes). This long averaging time
connections of cancer to 60-Hz EMF expo- and not all scientific bodies agree on this means that an intermittently operating RF
sure. This report is exhaustive and should question even today. An Institute of Elec- source (such as an Amateur Radio trans-
be reviewed by anyone with a serious inter- trical and Electronics Engineers (IEEE) mitter) will show a much lower power
est in the field. Among its general conclu- standard for recommended EM exposure density than a continuous-duty station —
sions were the following: limits was published in 1991 (see Bibliog- for a given power level and antenna con-
1. The scientific literature and the re- raphy). It replaced a 1982 American figuration.
ports of reviews by other panels show no National Standards Institute (ANSI) stan- Time averaging is based on the concept
consistent, significant link between cancer dard. In the new standard, most of the per- that the human body can withstand
and power line fields. mitted exposure levels were revised a greater rate of body heating (and thus,
2. No plausible biophysical mecha- downward (made more stringent), to better a higher level of RF energy) for a short

3.16 Chapter 3
Fig 3.14 — 1991 RF protection guidelines for body exposure of humans. It is known officially as the “IEEE Standard for Safety
Levels with Respect to Human Exposure to Radio Frequency Electromagnetic Fields, 3 kHz to 300 GHz.”

time than for a longer period. Time aver- recommendations of the National Council modern (dual chamber) pacemaker in and
aging may not be appropriate, however, for Radiation Protection and Measure- around an Amateur Radio station. The
when considering nonthermal effects of ment (NCRP). The MPE limits under the pacemaker generator has circuits that
RF energy. regulations are slightly different than the receive and process electrical signals pro-
The IEEE standard excludes any trans- IEEE/ANSI limits. Note that the MPE lev- duced by the heart, and also generate
mitter with an output below 7 W because els apply to the FCC rules put into effect electrical signals that stimulate (pace) the
such low-power transmitters would not be for radio amateurs on January 1, 1998. heart. In one series of experiments, the
able to produce significant whole-body These MPE requirements do not reflect pacemaker was connected to a heart simu-
heating. (Recent studies show that hand- and include all the assumptions and exclu- lator. The system was placed on top of the
held transceivers often produce power sions of the IEEE/ANSI standard. cabinet of a 1-kW HF linear amplifier dur-
densities in excess of the IEEE standard ing SSB and CW operation. In another test,
within the head.) Cardiac Pacemakers and RF the system was placed in close proximity to
There is disagreement within the scien- Safety several 1 to 5-W 2-meter hand-held trans-
tific community about these RF exposure It is a widely held belief that cardiac ceivers. The test pacemaker was connected
guidelines. The IEEE standard is still pacemakers may be adversely affected in to the heart simulator in a third test, and
intended primarily to deal with thermal their function by exposure to electromag- then placed on the ground 9 meters below
effects, not exposure to energy at lower netic fields. Amateurs with pacemakers and 5 meters in front of a three-element
levels. A small but significant number of may ask whether their operating might Yagi HF antenna. No interference with
researchers now believe athermal effects endanger themselves or visitors to their pacemaker function was observed in these
also should be taken into consideration. shacks who have a pacemaker. Because of experiments.
Several European countries and localities this, and similar concerns regarding other Although the possibility of interference
in the United States have adopted stricter sources of electromagnetic fields, pace- cannot be entirely ruled out by these few
standards than the recently updated IEEE maker manufacturers apply design meth- observations, these tests represent more
standard. ods that for the most part shield the severe exposure to EM fields than would
Another national body in the United pacemaker circuitry from even relatively ordinarily be encountered by an amateur
States, the National Council for Radiation high EM field strengths. — with an average amount of common
Protection and Measurement (NCRP), also It is recommended that any amateur who sense. Of course prudence dictates that
has adopted recommended exposure guide- has a pacemaker, or is being considered amateurs with pacemakers, who use hand-
lines. NCRP urges a limit of 0.2 mW/cm2 for one, discuss this matter with his or her held VHF transceivers, keep the antenna
for nonoccupational exposure in the 30- physician. The physician will probably put as far as possible from the site of the im-
300 MHz range. The NCRP guideline dif- the amateur into contact with the technical planted pacemaker generator. They also
fers from IEEE in two notable ways: It takes representative of the pacemaker manufac- should use the lowest transmitter output
into account the effects of modulation on turer. These representatives are generally required for adequate communication. For
an RF carrier, and it does not exempt trans- excellent resources, and may have data high power HF transmission, the antenna
mitters with outputs below 7 W. from laboratory or “in the field” studies should be as far as possible from the oper-
The FCC MPE regulations are based on with specific model pacemakers. ating position, and all equipment should
parts of the 1992 IEEE/ANSI standard and One study examined the function of a be properly grounded.

Safety 3.17
LOW-FREQUENCY FIELDS be determined by simple arithmetic. In the far pected, due to reflections from nearby ob-
Although the FCC doesn’t regulate field, conditions become easier to predict jects. In addition, “nearby objects” often
60-Hz fields, some recent concern about with simple calculations. change or vary with weather or the season,
EMR has focused on low-frequency The boundary between the near field and so the model so laboriously crafted may not
energy rather than RF. Amateur Radio the far field depends on the wavelength of be representative of the actual situation, by
equipment can be a significant source of the transmitted signal and the physical size the time it is running on the computer.
low-frequency magnetic fields, although and configuration of the antenna. The Intensely elevated but localized fields
there are many other sources of this kind boundary between the near field and the far often can be detected by professional mea-
of energy in the typical home. Magnetic field of an antenna can be as much as sev- suring instruments. These “hot spots” are
fields can be measured relatively accu- eral wavelengths from the antenna. often found near wiring in the shack, and
rately with inexpensive 60-Hz meters that Computer antenna-modeling programs metal objects such as antenna masts or
are made by several manufacturers. are another approach you can use. MININEC equipment cabinets. But even with the best
Table 3.2 shows typical magnetic field or other codes derived from NEC (Numeri- instrumentation, these measurements also
intensities of Amateur Radio equipment cal Electromagnetics Code) are suitable for may be misleading in the near field.
and various household items. Because estimating RF magnetic and electric fields One need not make precise measure-
these fields dissipate rapidly with dis- around amateur antenna systems. ments or model the exact antenna system,
tance, “prudent avoidance” would mean These models have limitations. Ground however, to develop some idea of the rela-
staying perhaps 12 to 18 inches away from interactions must be considered in estimat- tive fields around an antenna. Computer
most Amateur Radio equipment (and 24 ing near-field power densities, and the modeling using close approximations of
inches from power supplies with 1-kW RF “correct ground” must be modeled. Com- the geometry and power input of the
amplifiers). puter modeling is generally not sophisti- antenna will generally suffice. Those who
cated enough to predict “hot spots” in the are familiar with MININEC can estimate
DETERMINING RF POWER near field — places where the field inten- their power densities by computer model-
DENSITY sity may be far higher than would be ex- ing, and those who have access to profes-
Unfortunately, determining the power
density of the RF fields generated by an
amateur station is not as simple as measur- Table 3.2
ing low-frequency magnetic fields. Al- Typical 60-Hz Magnetic Fields Near Amateur Radio Equipment and
though sophisticated instruments can be AC-Powered Household Appliances
used to measure RF power densities quite
Values are in milligauss.
accurately, they are costly and require fre-
quent recalibration. Most amateurs don’t Item Field Distance
have access to such equipment, and the Electric blanket 30-90 Surface
inexpensive field-strength meters that we Microwave oven 10-100 Surface
do have are not suitable for measuring RF 1-10 12"
IBM personal computer 5-10 Atop monitor
power density. 0-1 15" from screen
Table 3.3 shows a sampling of measure- Electric drill 500-2000 At handle
ments made at Amateur Radio stations by Hair dryer 200-2000 At handle
the Federal Communications Commission HF transceiver 10-100 Atop cabinet
and the Environmental Protection Agency 1-5 15" from front
1-kW RF amplifier 80-1000 Atop cabinet
in 1990. As this table indicates, a good
1-25 15" from front
antenna well removed from inhabited areas (Source: measurements made by members of the ARRL RF Safety Committee)
poses no hazard under any of the IEEE/
ANSI guidelines. However, the FCC/EPA
survey also indicates that amateurs must be
careful about using indoor or attic-mounted Table 3.3
antennas, mobile antennas, low directional Typical RF Field Strengths Near Amateur Radio Antennas
arrays or any other antenna that is close to
A sampling of values as measured by the Federal Communications Commission and
inhabited areas, especially when moderate Environmental Protection Agency, 1990
to high power is used.
Ideally, before using any antenna that is Antenna Type Freq Power E Field
(MHz) (W) (V/m) Location
in close proximity to an inhabited area, you
should measure the RF power density. If Dipole in attic 14.15 100 7-100 In home
Discone in attic 146.5 250 10-27 In home
that is not feasible, the next best option is Half sloper 21.5 1000 50 1 m from base
make the installation as safe as possible by Dipole at 7-13 ft 7.14 120 8-150 1-2 m from earth
observing the safety suggestions listed in Vertical 3.8 800 180 0.5 m from base
Table 3.4. 5-element Yagi at 60 ft 21.2 1000 10-20 In shack
It also is possible, of course, to calculate 14 12 m from base
3-element Yagi at 25 ft 28.5 425 8-12 12 m from base
the probable power density near an antenna Inverted V at 22-46 ft 7.23 1400 5-27 Below antenna
using simple equations. Such calculations Vertical on roof 14.11 140 6-9 In house
have many pitfalls. For one, most of the situ- 35-100 At antenna tuner
ations where the power density would be high Whip on auto roof 146.5 100 22-75 2 m antenna
enough to be of concern are in the near field. 15-30 In vehicle
In the near field, ground interactions and other 90 Rear seat
5-element Yagi at 20 ft 50.1 500 37-50 10 m antenna
variables produce power densities that cannot

3.18 Chapter 3
sional power-density meters can make
Table 3.4
useful measurements.
RF Awareness Guidelines While our primary concern is ordinarily
These guidelines were developed by the ARRL RF Safety Committee, based on the the intensity of the signal radiated by an
FCC/EPA measurements of Table 3.2 and other data. antenna, we also should remember that
there are other potential energy sources to
• Although antennas on towers (well away from people) pose no exposure problem,
make certain that the RF radiation is confined to the antennas’ radiating elements
be considered. You also can be exposed to
themselves. Provide a single, good station ground (earth), and eliminate radiation RF radiation directly from a power ampli-
from transmission lines. Use good coaxial cable or other feed line properly. Avoid fier if it is operated without proper shield-
serious imbalance in your antenna system and feed line. For high-powered installa- ing. Transmission lines also may radiate a
tions, avoid end-fed antennas that come directly into the transmitter area near the significant amount of energy under some
operator. conditions. Poor microwave waveguide
• No person should ever be near any transmitting antenna while it is in use. This is joints or improperly assembled connectors
especially true for mobile or ground-mounted vertical antennas. Avoid transmitting are another source of incidental radiation.
with more than 25 W in a VHF mobile installation unless it is possible to first
measure the RF fields inside the vehicle. At the 1-kW level, both HF and VHF FURTHER RF EXPOSURE
directional antennas should be at least 35 ft above inhabited areas. Avoid using
SUGGESTIONS
indoor and attic-mounted antennas if at all possible. If open-wire feeders are used,
ensure that it is not possible for people (or animals) to come into accidental contact Potential exposure situations should be
with the feed line. taken seriously. Based on the FCC/EPA
• Don’t operate high-power amplifiers with the covers removed, especially at VHF/ measurements and other data, the “RF
UHF. awareness” guidelines of Table 3.4 were
• In the UHF/SHF region, never look into the open end of an activated length of developed by the ARRL RF Safety Commit-
waveguide or microwave feed-horn antenna or point it toward anyone. (If you do, tee. A longer version of these guidelines,
you may be exposing your eyes to more than the maximum permissible exposure along with a complete list of references,
level of RF radiation.) Never point a high-gain, narrow-bandwidth antenna (a appeared in a QST article by Ivan Shulman,
paraboloid, for instance) toward people. Use caution in aiming an EME
(moonbounce) array toward the horizon; EME arrays may deliver an effective
MD, WC2S (“Is Amateur Radio Hazardous
radiated power of 250,000 W or more. to Our Health?” QST, Oct 1989, pp 31-34).
In addition, the ARRL has published
• With hand-held transceivers, keep the antenna away from your head and use the
lowest power possible to maintain communications. Use a separate microphone and a book, RF Exposure and You, that is
hold the rig as far away from you as possible. This will reduce your exposure to the helping hams comply with the FCC’s
RF energy. RF-exposure regulations. The ARRL also
• Don’t work on antennas that have RF power applied. maintains an RF-exposure news page on
• Don’t stand or sit close to a power supply or linear amplifier when the ac power is its Web site. See www.arrl.org/news/
turned on. Stay at least 24 inches away from power transformers, electrical fans and rfsafety. This site contains reprints of
other sources of high-level 60-Hz magnetic fields. selected QST articles on RF exposure and
links to the FCC and other useful sites.

Other Hazards in the Ham Shack


CHEMICALS trained persons will not gain access. original containers. Oil-filled capacitors
We can’t seem to live without the use of • Always keep containers labeled so there and transformers were once commonly
chemicals, even in the electronics age. A is no confusion about the contents. Use filled with oil containing PCB’s. Never
number of substances are used everyday the container in which the chemical was dispose of any such items that may con-
by amateurs without causing ill effects. A purchased. tain PCB’s in landfills.
sensible approach is to become knowl- • Handle chemicals carefully to avoid • Always use recommended personal pro-
edgeable of the hazards associated with spills. tective equipment (such as gloves, face
the chemicals we use in our shack and then • Clean up any spills or leaks promptly but shield, splash goggles and aprons).
treat them with respect. don’t overexpose yourself in the process. • If corrosives (acids or caustics) are
A few key suggestions: Never dispose of chemicals in household splashed on you immediately rinse with
• Read the information that accompanies sinks or drains. Instead, contact your cold water for a minimum of 15 minutes
the chemical and follow the manu- local waste plant operator or fire depart- to flush the skin thoroughly. If splashed
facturer’s recommended safety prac- ment to determine the proper disposal pro- in the eyes, direct a gentle stream of cold
tices. If you would like more informa- cedures for your area. Many communities water into the eyes for at least 15 min-
tion than is printed on the label, ask for have household hazardous waste collec- utes. Gently lift the eyelids so trapped
a material safety data sheet. tion programs. Of course, the best solu- liquids can be flushed completely. Start
• Store chemicals properly away from tion is to only buy the amount of chemical flushing before removing contaminated
sunlight and sources of heat. Provide that you will need, and use it all if pos- clothing. Seek professional medical as-
security so they won’t fall off the shelf. sible. Always label any waste chemicals, sistance. It is unwise to work alone since
Secure them so that children and un- especially if they are no longer in their people splashed with chemicals need

Safety 3.19
the calm influence of another person. “fitting the work to the person.” If tools periods of time spent in unnatural posi-
• Food and chemicals don’t mix. Keep and equipment are designed about what tions can lead to repetitive-motion illness.
food, drinks and cigarettes away from people can accommodate, the results will Much of this attention has been focused
areas where chemicals are used and be much more satisfactory. For example, on people whose job tasks have required
don’t bring your chemicals to places in the 1930s research was done in tele- them to operate video display terminals
where you eat. phone equipment manufacturing plants (VDTs). While most Amateur Radio oper-
Table 3.5 summarizes the uses and haz- because use of long-nosed pliers for wir- ators do not devote as much time to their
ards of chemicals used in the ham shack. It ing switchboards required considerable hobby as they might in a full-time job, it
includes preventive measures that can force at the end of the hand’s range of does make sense to consider comfort and
minimize risk. motion. A simple tool redesign resolved flexibility when choosing furniture and
this issue. Considerable attention has been arranging it in the shack or workshop.
ERGONOMICS focused on ergonomics in recent years Adjustable height chairs are available with
Ergonomics is a term that loosely means because we have come to realize that long air cylinders to serve as a shock absorber.

Table 3.5
Properties and Hazards of Chemicals often used in the Shack or Workshop
Generic Chemical Name Purpose or Use Hazards Ways to Minimize Risks
Lead-tin solder Bonding electrical • Lead exposure • Always wash hands after
components (mostly from hand contact) soldering or touching solder.
• Flux exposure (inhalation) • Use good ventilation.
Isopropyl alcohol Flux remover • Dermatitis (skin rash) • Wear molded gloves suitable for
solvents.
• Vapor inhalation • Use good ventilation and avoid
aerosol generation.
• Fire hazard • Use good ventilation, limit use to
small amounts, keep ignition sources
away, dispose of rags only in tightly
sealed metal cans.
Freons Circuit cooling and • Vapor inhalation • Use adequate ventilation.
general solvent • Dermatitis • Wear molded gloves suitable for
solvents.
Phenols and Enameled wire/ • Strong skin corrosive • Avoid skin contact; wear
methylene chloride paint stripper suitable molded gloves; use adequate
ventilation.
Beryllium oxide Ceramic insulator which • Toxic when in fine dust • Avoid grinding, sawing or
can conduct heat well form and inhaled reducing to dust form.
Beryllium metal Lightweight metal, • Same as beryllium oxide • Avoid grinding, sawing,
alloyed with copper. welding, or often reducing to dust.
Contact supplier for special
procedures.
Various paints Finishing • Exposures to solvents • Adequate ventilation; use respirator
when spraying.
• Exposures to sensitizers • Adequate ventilation and
(especially urethane paint) use respirator. Contact supplier for
more info.
• Exposure to toxic metals • Adequate ventilation and
(lead, cadmium, chrome, use respirator. Contact
and so on) in pigments supplier for more info.
• Fire hazard (especially • Adequate ventilation;
when spray painting) control of residues; eliminate ignition
sources.
Ferric chloride Printed circuit • Skin and eye contact • Use suitable containers;
board etchant wear splash goggles and molded
gloves suitable for acids.
Ammonium persulphate Printed circuit • Skin and eye contact • Use suitable containers;
and mercuric chloride board etchants wear splash goggles and molded
gloves suitable for acids.
Epoxy resins General purpose • Dermatitis and possible • Avoid skin contact. Mix
cement or paint sensitizer only amount needed.
Sulfuric acid Electrolyte in •Strong corrosive when •Always wear splash goggles and
lead-acid batteries on skin or eyes. molded plastic gloves (PVC) when
•Will release hydrogen handling. Keep ignition sources away
when charging (fire, from battery when charging. Provide
explosion hazard). adequate ventilation.

3.20 Chapter 3
Footrests might come in handy if the chair
is so high that your feet cannot support High-Voltage Hazards
your lower leg weight. The height of tables What happens when someone receives an electrical shock?
and keyboards often is not adjustable. Electrocutions (fatal electric shocks) usually are caused by the heart
Placement of VDT screens should take ceasing to beat in its normal rhythm. This condition, called ventricular
into consideration the reflected light com- fibrillation, causes the heart muscles to quiver and stop working in a coordi-
ing from windows. It is always wise to nated pattern, in turn preventing the heart from pumping blood.
build into your sitting sessions time to The current flow that results in ventricular fibrillation varies between
walk around and stimulate blood circula- individuals but may be in the range of 100 mA to 500 mA. At higher current
tion. Your muscles are less likely to levels the heart may have less tendency to fibrillate but serious damage
stiffen, while the flexibility in your joints would be expected. Studies have shown 60-Hz alternating current to be
can be enhanced by moving around. more hazardous than dc currents. Emphasis is placed on application of
Selection of hand tools is another area cardiopulmonary resuscitation (CPR), as this technique can provide
where there are choices to make that may mechanical flow of some blood until paramedics can “restart” the heart’s
affect how comfortable you will be while normal beating pattern. Defibrillators actually apply a carefully controlled dc
working in your shack. Look for screw- voltage to “shock” the heart back into a normal heartbeat. It doesn’t always
drivers with pliable grips. Take into work but it’s the best procedure available.
account how heavy things are before pick- What are the most important factors associated with severe shocks?
ing them up — your back will thank you.
You may have heard that the current that flows through the body is the
ENERGIZED CIRCUITS most important factor, and this is generally true. The path that current takes
through the body affects the outcome to a large degree. While simple
Working with energized circuits can be application of Ohm’s Law tells us that the higher the voltage applied with a
very hazardous since our senses cannot fixed resistance, the greater the current that will flow. Most electrical shocks
directly detect dangerous voltages. The involve skin contact. Skin, with its layer of dead cells and often fatty tissues,
first thing we should ask ourselves when is a fair insulator. Nonetheless, as voltage increases the skin will reach a
faced with troubleshooting, aligning or point where it breaks down. Then the lowered resistance of deeper tissues
other “live” procedures is, “Is there a way allows a greater current to flow. This is why electrical codes refer to the term
to reduce the hazard of electrical shock?” “high voltage” as a voltage above 600 V.
Here are some ways of doing just that.
How little a voltage can be lethal?
1. If at all possible, troubleshoot with
an ohmmeter. With a reliable schematic This depends entirely on the resistance of the two contact points in the
diagram and careful consideration of how circuit, the internal resistance of the body, and the path the current travels
various circuit conditions may reflect re- through the body. Historically, reports of fatal shocks suggest that as little as
sistance readings, it will often be unneces- 24 V could be fatal under extremely adverse conditions. To add some
perspective, one standard used to prevent serious electrical shock in
sary to do live testing.
hospital operating rooms limits leakage flow from electronic instruments to
2. Keep a fair distance from energized only 50 μA due to the use of electrical devices and related conductors inside
circuits. What is considered “good prac- the patient’s body.
tice” in terms of distance? The National
Electrical Code specifies minimum work-
ing space about electric equipment in Sec-
tions 110-16 and 110-34, depending on the
voltage level. The principle here is that a moved and disconnected use a “shorting manufacturer for suggested procedures.
person doing live work needs adequate stick” to ground all exposed conductors 10. Ground-fault circuit interrupters
space so they are not forced to be danger- and ensure that voltage is not present. can offer additional protection for stray
ously close to energized equipment. Avoid using screwdrivers, as this brings currents that flow through the ground on
3. If you need to measure the voltage of the amateur too close to the circuit and 120-V circuits. Know their limitations.
a circuit, install the voltmeter with the could ruin the screwdriver’s blade. They cannot offer protection for the plate
power safely off, back up, and only then 6. If you must hold a probe to take a supply voltages in linear amplifiers, for
energize the circuit. Remove the power measurement, always keep one hand in example.
before disconnecting the meter. your pocket. As mentioned in the sidebar 11. Older radio equipment containing
4. If you are building equipment that on the effects of high voltages, the worst ac/dc power supplies have their own haz-
has hinged or easily removable covers that path current could take through your body ards. If working on these live, use an iso-
could expose someone to an energized cir- is from hand to hand since the flow would lation transformer, as the chassis may be
cuit, install interlock switches that safely pass through the chest cavity. connected directly to the hot or neutral
remove power in the event that the enclo- 7. Make sure someone is in the room with power conductor.
sure was opened with the power still on. you and that they know how to remove the 12. Be aware of electrolytic capacitors
Interlock switches are generally not used power safely. If they grab you with the that might fail if used outside their in-
if tools are required to open the enclosure. power still on they will be shocked as well. tended applications.
5. Never assume that a circuit is at zero 8. Test equipment probes and their leads 13. Replace fuses only with those having
potential even if the power is switched off must be in very good condition and rated proper ratings.
and the power cable disconnected. Capaci- for the conditions they will encounter.
tors can retain a charge for a considerable 9. Be wary of the hazards of “floating” SUMMARY
period of time. Bleeder resistors should be (ungrounded) test equipment. A number The ideas presented in this chapter are
installed, but don’t assume they have bled of options are available to avoid this intended to reinforce the concept that
off the voltage. Instead, after power is re- hazard. Contact your test equipment ham radio, like many other activities in

Safety 3.21
modern life, does have certain risks. But expectations. Code and NEC are registered trade-
by understanding the hazards and how to marks of the National Fire Protection
deal effectively with them, the risk can BIBLIOGRAPHY Association, Inc, Quincy, MA 02269.
be minimized. Common-sense measures Source material and more extended dis- R. P. Haviland, “Amateur Use of Telescop-
can go a long way to help us prevent ac- cussion of topics covered in this chapter ing Masts,” QST, May 1994, pp 41-45.
cidents. Traditionally, amateurs are in- can be found in the references given below. For more information about soldering haz-
Lightning Protection Code, NFPA ards, symptoms, and protection, see
ventors, and experimenting is a major
“Making Soldering Safer,” by Bryan P.
part of our nature. But reckless chance- 780,National Fire Protection Associa-
Bergeron, MD, NU1N (Mar 1991 QST,
taking is never wise, especially when our tion, Quincy, MA, 1992.
pp 28-30) and “More on Safer Solder-
health and well-being is involved. A National Electrical Code, NFPA 70, Na- ing,” by Gary E. Myers, K9CZB (Aug
healthy attitude toward doing things the tional Fire Protection Association, 1991 QST, p 42).
right way will help us meet our goals and Quincy, MA, 1993. National Electrical

3.22 Chapter 3

Potrebbero piacerti anche