incl. SSP for STARTER
General conditions and function limitations, notes for configuration and operation
SINAMICS_S110_V41_Restrictions.pdf 17.12.2008
SIEMENS SINAMICS S110 V4.1
incl. SSP for STARTER
p0010 = 4
p0400 = 9999
p0405.2 = 1
p0010 = 0
AP00719118 The configuration of the motor If during the STARTER commissioning, the brake of a drive with SMI p1215 can be set directly to the desired value
holding brake p1215 is changed after components is set to "Motor holding brake always open" (see p1215), the after the download.
the parameter download for drives value is reset to "Motor holding brake acc. to sequential control" in the drive
with SMI components. after the parameter download.
AP00748394 When using asynchronous motors, When using asynchronous motors, current controller gain may be too large Considering the existing motor data
current controller gain may be too considering the existing motor data identification. identification of asynchronous motors, the
large considering the existing motor current controller gain (p1715) must be
data identification. checked and corrected if need be. For
checking, the reference frequency response
must be taken over for the current controller.
SINAMICS_SW - Safety Integrated
AP00731197 Very sporadically alarm Very sporadically alarms F1711 and F30711 with fault value 58 occur when The error can be completely avoided with the
F1711/30711 when selecting SS1 selecting the extended safety function SS1. The error occurs at the time following measures: 1.) Trigger an STO in
when, because of a time condition (p9556) or the speed/velocity attained good time before the transition time from SS1
(p9560), the STO response is triggered. The error can be acknowledged via to STO expires (p9556, p9356) 2.) Use SS2
the safe acknowledgement (PROFIsafe: Internal event acknowledge, and switch to STO after the feedback message
TM54F: p10006). In SW V02.50.xx.xx this acknowledgement must be SOS active 3.) Use the SS1 function of the
performed before the deselection of SS1. basic safety functions
AP00737515 Re-parameterization of parameters in Re-parameterization of parameters in the range 10100 - 10199 is not Perform the parameterization exclusively via
the range 10100 - 10199 is not permitted via the expert list. This results in alarm 30680 (SI motion MM: the STARTER screens.
permitted via the expert list. Checksum error, safety monitoring functions).
AP00744909 After error parameterization p9500 If p9500 (SI Motion Monitoring Cycle Control Unit) unequal p9300 (SI If error message F30665 is output with error
unequal to p9300 and after parameter Motion Monitoring Cycle Motor Module) is set due to incorrect message F30711 (cross-checking error) and if
reset on the CU (p972 = 1) or after a parameterization, then error message F30711 as well as the incorrect error parameterization p9500 is unequal to p9300 or
power OFF/ON, error message message F30665 (SI MM: System Defect) will be ouput after a parameter (p9511/p9311..), then the parameterization in
F30711 is output together with the reset on the control unit with p972 = 1 or after a power OFF/ON. The same p9500 and p9300 or (p9511/p9311..) must be
invalid error message F30665. The also applies to other parameters (p9511/p9311..) of the Safety screen corrected in such a way that the monitoring
same also applies to other parameters form?Configuration? cycle settings match the cycle settings. Error
(p9511/p9311..) of the Safety screen message F30665 can be ignored in this case.
form?Configuration?
SINAMICS_S110_V41_Restrictions.pdf 17.12.2008
SIEMENS SINAMICS S110 V4.1
incl. SSP for STARTER
SINAMICS_S110_V41_Restrictions.pdf 17.12.2008