SIEMENS SINAMICS S110 V4.

1
incl. SSP for STARTER

General conditions and function limitations, notes for configuration and operation

These notes take precedence over statements contained in other documents.


Because these notes contain important information for the installation and use of the software, please read them carefully.

SINAMICS S110 V4.1 incl. SSP for STARTER


ARTSPlusRQ Brief description Description Possible work-around
SINAMICS_SW - General
AP00316750 Changing the motor in the expert list Another motor may only be selected via the drive wizard. Changing the ---
motor code in the expert list can result in inconsistencies in the STARTER
displays.
AP00325763 The information for rated current and The information for rated current and rated power of the PM340 power Select the power module by MLFB when using
rated power of the PM340 power module in the drive wizard can deviate from the catalog data in some cases. the drive wizard for commissioning
module in the drive wizard can
deviate from the catalog data in some
cases.
AP00330263 The information for the power unit The information for the power unit duty cycles in indices 1 to 4 of none
duty cycles in indices 1 to 4 of parameters r0206, r0207 und r0209 in the expert list are not displayed
parameters r0206, r0207 und r0209 correctly in some cases. The value in index 0 is applicable.
in the expert list are not displayed
correctly in some cases. The value in
index 0 is applicable.
AP00394976 When a PM340 power module is When a PM340 power module is inserted onto another CU305, the runtime None
inserted onto another CU305, the meter of the power unit fan is reset to 0.
runtime meter of the power unit fan
is reset to 0.
AP00490745 The number of permissible places With scripts, it is possible to write a parameter with more places after the Take the number of permissible places after the
after the decimal point is not taken decimal point than permitted or displayed in the screens. This can result in decimal point into account in the script. See
into account for scripting. an inconsistency between the actual value set in the drive and the display in expert list.
STARTER. These differences cannot be displayed through a comparison of
lists.
AP00718943 Saving is rejected directly after 1) The topology error A:1420 (Topology: Comparison: One component Acknowledge the message and wait until r002
correcting warning A:1420 different) is present during ramp-up. = 0. Then save.
(Topology: Comparison: One
component different). 2) After correction of A:1420 and while the system is still ramping up (r002
<> 0), STARTER immediately attempts to save. A message appears that the
saving operation has failed.

3) The system continues to ramp up. Saving can be performed after


completion of the ramp-up (r002 = 0).
AP00729186 Alarms on the control unit that do not Alarms on the control unit that do not result in a shutdown response, are not The alarms can be viewed in the alarm history
result in a shutdown response, are not visible when the first servo or vector DO has been deactivated via p105. r945 to r949.
visible when the first servo or vector
DO has been deactivated via p105.
AP00748695 When using a SafeBrake relay, and in When using a SafeBrake relay, and in the case of automatic configuration The motor holding brake must be manually
the case of automatic configuration and reset to factory setting, the motor holding brake may not be detected configured via parameter p1215 = 1.
and reset to factory setting, the motor from time to time. This means that, when switching on the drive, the brake
holding brake may not be detected remains locked. For this reason, parameter p1215 = 0 "Motor Holding Brake
from time to time. Configuration" remains and error message F7935 "Drive: Motor Holding
Brake Detected" is not triggered.
SINAMICS_SW - EPOS
AP00517160 Modulo rotary axis in MDI Modulo rotary axis in MDI operation, absolute, edge-triggered positioning Only specify a new starting edge after the
operation, absolute, edge-triggered with direction specification: If several starting edges are specified during the feedback message "Target position reached"
positioning with direction braking phase, the axis turns an extra modulo revolution after reaching the r2684.10 = 1.
specification: If several starting target position.
edges are specified during the
braking phase, the axis turns an extra
modulo revolution after reaching the
target position.
AP00734501 If the "Basic positioner" function If the "Basic positioner" function module is used on the S110, the number of During simultaneous use of the "Basic
module is used on the S110, the blocks that can be used is restricted when using the "Free function blocks" positioner" and the "Free function blocks"
number of blocks that can be used is function module. The reason is that there is less residual computation time. function modules, 23 blocks (one of each block
restricted when using the "Free type) can be calculated in 16 ms. 23 blocks can
function blocks" function module. be calculated in 4 ms when the "Basic
positioner" function module is not activated. If
a shorter sampling time is set, this reduces the
remaining computation time, so that, e.g. only
3 blocks can be calculated in 2 ms with "Basic
positioner". When the remaining computation
time is not sufficient, F1205 is triggered.
SINAMICS_SW - General communication
AP00524709 For a BICO interconnection with For a BICO interconnection with p2050 "CO: IF1 PROFIdrive PZD received Do not transfer process data via drive object 1.
p2050 to drive object 1, there is no word" to DO 1 (CU), there is no normalizing of the received process data to
normalizing of the received process 4000h. This occurs, for example, for an interconnection to the torque limits
data to 4000h. p1522 and p1523:

If p1522 or p1523 of the drive is interconnected to p2050 of the drive, there


is a normalizing to 4000h during the determination of the torque.

If p1522 or p1523 of the drive is interconnected to p2050 of the CU, there is


no normalizing to 4000h during the determination of the torque
(normalizing: 1 corresponds to 100% torque).

There is no explicit information about this varying behavior in the


STARTER dialog boxes.

SINAMICS_S110_V41_Restrictions.pdf 17.12.2008
SIEMENS SINAMICS S110 V4.1
incl. SSP for STARTER

ARTSPlusRQ Brief description Description Possible work-around


SINAMICS_SW - CAN communication
AP00326015 CAN command "Restore" does not In contrast to the CANopen specification, the "Restore all parameters" or If the SINAMICS is to ramp up with its default
conform with CANopen. "Restore communication parameters" command is executed as follows for values after Power OFF/ON or "Reset", the
the SINAMICS: After writing object 0x1011, subindex 1 or 2, the default values must be saved to the CF card via
corresponding objects are set to their default values directly in the RAM. If object 0x1011 after writing object 0x1010. If it
the "Reset node" or "Reset communication parameters" is transmitted, the is sufficient to have the default values only in
values of the objects still saved on the CF card are loaded to the RAM again. the RAM, only object 0x1011 has to be
The SINAMICS is now configured again as it was before the Restore written. After a reconfiguration has been
commands. performed, the values can be written to the CF
card with object 0x1010.
AP00703561 The CANopen status word displays The CU305CAN is in the CANopen drive state "Operation enable". The Delay the "OPERATIONAL" command after
error F8701 shortly after the NMT motor turns. The NMT command "Reset communication" is issued. After the the "Reset communication" command for three
command "Reset communication" boot-up message, there is an immediate change to the NMT status CAN cycles or ignore the error bit in the first
although it has been automatically "OPERATIONAL". The error bit of the CANopen status word still displays cycle after switching to OPERATIONAL.
acknowledged. error F8701 for one cycle although this has been automatically
acknowledged.
SINAMICS_SW - PROFIBUS communication
AP00334540 Diagnostics display for message PZD MDI_vel and MDI_decc are missing in the diagnostics display for ---
frame 110 incomplete. PROFIBUS message frame 110.
AP00744750 During an interruption of the During an interruption of the PROFIBUS connection between the control Error message F30662 (error with internal
PROFIBUS connection between the unit (PROFIBUS master) and the drive unit (unplug DP plug from control communications) can be acknowledged only
control unit (PROFIBUS master) and unit) and simultaneous (online) link with the STARTER, error message through a power ON of the control unit.
the drive unit (unplug DP plug from F30662 (error with internal communications) is sporadiacally output.
control unit) and simultaneous
(online) link with the STARTER,
error message F30662 (error with
internal communications) is
sporadiacally output.
AP00744833 STARTER (online) link hardly STARTER (online) link hardly possible if the configured PROFIsafe Switch off or disconnect PROFIsafe master
possible if configured PROFIsafe addresses of PROFIsafe master and drive unit do not match. until PROFIsafe addresses have been corrected
address not correct. in the drive. The PROFIsafe addresses
(p9610/9810) in the drive must match the
address parametrized in the PROFIsafe master.
AP00745858 The functionality "Differentiating In the case of integrated encoder evaluation for the control unit CU305 and None.
encoder errors via PROFIBUS" is not SMC30 (MLFB: 6SL3055-0AA00-5CA2), the functionality "Differentiating
supported. encoder errors via PROFIBUS" is not supported. In parameter r483 "CO:
The actual encoder position value Gn_XIST2 / Geb Gn_XIST2" is,
therefore, always shown as an error code with value 1 = encoder error if an
error message is reported.
SINAMICS_SW - Closed-loop control
AP00522164 When using a synchronous motor When using a synchronous motor with selected pole position identification The fine synchronization must be manually
with selected pole position and incremental encoder with zero mark, but without absolute position configured with the following sequence: p0010
identification and incremental (without C/D track, not EnDat encoder), the 'commutation with zero mark' = 4 (encoder commissioning) p0400 = 9999
encoder with zero mark, but without (fine synchronization) is not automatically activated via p404.15. (user-defined) p0404.15 = 1 (commutation
absolute position (without C/D track, with zero mark)
not EnDat encoder), the
'commutation with zero mark' (fine
synchronization) is not automatically
activated via p404.15.
AP00660609 No track monitoring with listed TTL In the selection of a TTL encoder from the encoder list (e.g. p0400 = 3002), The track monitoring can be subsequently
encoders the track monitoring (p0405 bit 2) is switched off. switched on with

p0010 = 4
p0400 = 9999
p0405.2 = 1
p0010 = 0
AP00719118 The configuration of the motor If during the STARTER commissioning, the brake of a drive with SMI p1215 can be set directly to the desired value
holding brake p1215 is changed after components is set to "Motor holding brake always open" (see p1215), the after the download.
the parameter download for drives value is reset to "Motor holding brake acc. to sequential control" in the drive
with SMI components. after the parameter download.
AP00748394 When using asynchronous motors, When using asynchronous motors, current controller gain may be too large Considering the existing motor data
current controller gain may be too considering the existing motor data identification. identification of asynchronous motors, the
large considering the existing motor current controller gain (p1715) must be
data identification. checked and corrected if need be. For
checking, the reference frequency response
must be taken over for the current controller.
SINAMICS_SW - Safety Integrated
AP00731197 Very sporadically alarm Very sporadically alarms F1711 and F30711 with fault value 58 occur when The error can be completely avoided with the
F1711/30711 when selecting SS1 selecting the extended safety function SS1. The error occurs at the time following measures: 1.) Trigger an STO in
when, because of a time condition (p9556) or the speed/velocity attained good time before the transition time from SS1
(p9560), the STO response is triggered. The error can be acknowledged via to STO expires (p9556, p9356) 2.) Use SS2
the safe acknowledgement (PROFIsafe: Internal event acknowledge, and switch to STO after the feedback message
TM54F: p10006). In SW V02.50.xx.xx this acknowledgement must be SOS active 3.) Use the SS1 function of the
performed before the deselection of SS1. basic safety functions
AP00737515 Re-parameterization of parameters in Re-parameterization of parameters in the range 10100 - 10199 is not Perform the parameterization exclusively via
the range 10100 - 10199 is not permitted via the expert list. This results in alarm 30680 (SI motion MM: the STARTER screens.
permitted via the expert list. Checksum error, safety monitoring functions).
AP00744909 After error parameterization p9500 If p9500 (SI Motion Monitoring Cycle Control Unit) unequal p9300 (SI If error message F30665 is output with error
unequal to p9300 and after parameter Motion Monitoring Cycle Motor Module) is set due to incorrect message F30711 (cross-checking error) and if
reset on the CU (p972 = 1) or after a parameterization, then error message F30711 as well as the incorrect error parameterization p9500 is unequal to p9300 or
power OFF/ON, error message message F30665 (SI MM: System Defect) will be ouput after a parameter (p9511/p9311..), then the parameterization in
F30711 is output together with the reset on the control unit with p972 = 1 or after a power OFF/ON. The same p9500 and p9300 or (p9511/p9311..) must be
invalid error message F30665. The also applies to other parameters (p9511/p9311..) of the Safety screen corrected in such a way that the monitoring
same also applies to other parameters form?Configuration? cycle settings match the cycle settings. Error
(p9511/p9311..) of the Safety screen message F30665 can be ignored in this case.
form?Configuration?

SINAMICS_S110_V41_Restrictions.pdf 17.12.2008
SIEMENS SINAMICS S110 V4.1
incl. SSP for STARTER

ARTSPlusRQ Brief description Description Possible work-around


SINAMICS_SW - Safety Integrated
AP00745163 After changing P10106 (SI After first commissioning or after changing P10106 (SI Acknowledgement Switch OFF/ON.
Acknowledgement Internal Event Internal Event Input Terminal (2nd channel)) a present discrepancy error
Input Terminal (2nd channel)) a C30770 cannot be acknowledged any longer with safe acknowledgement.
present discrepancy error C30770 After power ON the new parameterization becomes effective and is
cannot be acknowledged any longer functioning. In the event of an error, the respective FDI remains in a safe
with safe acknowledgement. After state.
power ON the new parameterization
becomes effective and is functioning.
In the event of an error, the
respective FDI remains in a safe
state.
AP00747957 Error messages C01712 and C30712 If error messages C01770 SI "Motion CU: Discrepency error of the failsafe Fault output requires corresponding
are not output with a fault value 10 inputs or outputs" C30770 "SI Motion MM: Discrepency error of the failsafe interpretation.
and, as from fault value 11, output inputs or outputs" are reported, then bugfixing may show that different
with a value one less than output. settings of the parameters p10039 "SI Safe State Signal Selection / SI Safe
State Selection" and p10139 "SI Safe State Signal Selection (2nd channel) /
SI Safe State Selection" are responsible. The error messages C01712 and
C30712 with fault value 10, as expected, are, however, not output.

In the case of error messages C01712 SI "Motion CU: Defect in F-IO


processing" or C30712 "SI Motion MM: Defect in F-IO processing", the
fault value is output with a value one less than output as from fault value 11.
SINAMICS_SW - Topology
AP00486766 After replacement of the SMI motor, After replacement of the SMI motor, fault F1840 (SMI: Component with Open expert list of drive object 1 (device) and
fault F1840 (SMI: Component with changed data found) occurs. change the value of parameter p9906 to 2.
changed data found) occurs. Then save and switch off and on again.
AP00667805 Some errors cannot be acknowledged Some errors cannot be acknowledged after the deactivation or parking of Acknowledge errors before the deactivation or
after the deactivation or parking of some SMI/SME components. This only applies when the errors have not parking. Perform restart after activation or
some SMI/SME components. been acknowledged before the deactivation or parking. termination of parking.

SINAMICS_S110_V41_Restrictions.pdf 17.12.2008