HAZEL INTERNATIONAL STORAGE TANK INSPECTION CHECK

TANK NO:
SL.NO. List of Items R
1 Foundation
1.1 Any crack observed in tank apron / concrete ring
1.2 Any settlement around perimeter of tank
1.3 Any dripping/sweating is observed in foundation
1.4 Are there any chances of water stagnation at the bottom curb area
Any cavity observed under foundation and vegetation against bottom of
1.5
tank
2 Shell
2.1 Any pitting, corrosion and failure in painting on shell area
Any corrosion / thinning of plate in the bottom curb angle joint around the
2.2
tank
2.3 Any corrosion / damage of wind girder and staircase of the tank
2.4 Are there any buckling or bulging in the shell plates
2.5 Are there any signs on the shell surface of any leaks
3 Shell appurtenances
3.1 Any cracks or signs of leakage on weld joints at nozzles and manways

3.2 Tank inlet line from common manifold to tank/valve/ blinds/etc

3.3 Tank out let line from tank to pump house valve/blinds/etc
Are valve glands and gaskets free from evidence of leaks and are stems
3.4
lubricated and in good condition
Whether the TRV Expansion line valve is properly secured and
3.5
functioning
Whether fire fighting lines (sprinkler and foam system) are properly
3.6
supported
3.7 Whether earth strips are properly tightened to the tank shell
4 Roof
Any crack, pitting, corrosion and failure in painting on roof plates and
4.1
welding joints
Any leakage of air or product vapour through nozzles flange joint or roof
4.2
plate welded joints
5 Roof appurtenances
Whether dip hatch/ temp.hatch/ other nozzles are properly functioning and
5.1
closed. Condition of hatch seals
5.2 Is PV valve/goose neck is functioning properly. Condition of mesh
5.3 Electrical ligting and JB's
5.4 Whether the Radar and its fitting are properly secured
Whether IFR seal in good condition without any cracks. This can be
5.5
checked by opening roof dome covers provided on tank roof
5.6 Any corrosion / damage of roof hand rails of the tank
6 General
6.1 Are the dyke outlet valves in operation and normally closed
6.2 Any unwanted materials around the tank
Whether aluminium clamp is fixed to all joints of expansion line and
6.3
pipelines from tank to loading arm
6.4 Whether Silica gel breather is functioning properly. Condition of silica gel
Insulated tank - Is the cladding in good condition and is there any
6.5
evidence of insulation degradation
Are the shell and roof nozzles full bolted ( All the bolts holes are with
6.6
bolts)
6.7 Are the electrical equipment connected to the tank properly secured
Comments:

Inspected by Maintenance In-charge

Signature:

Name:
NSPECTION CHECKLIST
DATE OF INSPECTION:
Remarks
Maintenance In-charge Terminal In-charge