Sei sulla pagina 1di 23

LP 1 (LIGHTING PANEL 1)

BRANCH SIZE & TYPE OF


LOAD TOTAL CURRENT CB RATING SIZE OF CONDUIT
CIRCUIT VOLTAGE FEEDER
DESCRIPTION VA
NO. AB BC CA 3Ø AT AF POLE NO. 𝑚𝑚2 TYPE NO. mmØ TYPE
1 LP -13 230 1345.5 5.85 30 50 2 2 3.5 THHN 1 15 RCP
2 LP -21 230 2173.5 9.45 30 50 2 2 3.5 THHN 1 15 RCP
3 LP -16 230 1656 7.2 30 50 2 2 3.5 THHN 1 15 RCP
4 LP -20 230 2070 9 30 50 2 2 3.5 THHN 1 15 RCP
5 LP -17 230 1759.5 7.65 30 50 2 2 3.5 THHN 1 15 RCP
6 LP -23 230 2380.5 10.35 30 50 2 2 3.5 THHN 1 15 RCP
7 LP -23 230 2380.5 10.35 30 50 2 2 3.5 THHN 1 15 RCP
8 LP -23 230 2380.5 10.35 30 50 2 2 3.5 THHN 1 15 RCP
9 LP -24 230 2484 10.8 30 50 2 2 3.5 THHN 1 15 RCP
10 LP -14 230 1449 6.3 30 50 2 2 3.5 THHN 1 15 RCP
11 LP -16 230 1656 7.2 30 50 2 2 3.5 THHN 1 15 RCP
12 LP -24 230 2484 10.8 30 50 2 2 3.5 THHN 1 15 RCP
13 LP -25 230 2587.5 11.25 30 50 2 2 3.5 THHN 1 15 RCP
14 LP -20 230 2070 9 30 50 2 2 3.5 THHN 1 15 RCP
15 LP -24 230 2484 10.8 30 50 2 2 3.5 THHN 1 15 RCP
16 LP -22 230 2277 9.9 30 50 2 2 3.5 THHN 1 15 RCP
17 LP -22 230 2277 9.9 30 50 2 2 3.5 THHN 1 15 RCP
18 LP -24 230 2484 10.8 30 50 2 2 3.5 THHN 1 15 RCP
19 SPARE 230 3450’ 15 30 50 2 2 3.5 THHN 1 15 RCP
20 SPARE 230 3450 15 30 50 2 2 3.5 THHN 1 15 RCP
21 SPARE 230 3450 15 30 50 2 2 3.5 THHN 1 15 RCP
TOTAL 48748.5 70.8 70.35 70.8

𝑰𝟑Ø = (√𝟑)(𝟕𝟎. 𝟖) = 𝟏𝟐𝟐. 𝟔𝟑 𝑨 RATING OF FEEDER CB

MINIMUM AMPERE 175 AT, 225 AF, 2P, 230V MOLDED CASE TYPE

𝑰𝑴𝑰𝑵𝑰𝑴𝑼𝑴 = (𝟏𝟐𝟐. 𝟔𝟑)(𝟏. 𝟐𝟓) = 𝟏𝟓𝟑. 𝟐𝟗 𝑨 SIZE OF GROUNDING

SIZE OF FEEDER CONDUCTOR 1 - 14 𝒎𝒎𝟐 COPPER CONDUCTOR

2 - 60 𝒎𝒎𝟐 THHN COPPER WIRE (AMPACITY = 170 A)


REQUIRED SIZE OF RACEWAY
1 - 32 mmØ METALLIC RCP
LP 2 (LIGHTING PANEL 2)

BRANCH SIZE & TYPE OF


LOAD TOTAL CURRENT CB RATING SIZE OF CONDUIT
CIRCUIT VOLTAGE FEEDER
DESCRIPTION VA
NO. AB BC CA 3Ø AT AF POLE NO. 𝑚𝑚2 TYPE NO. mmØ TYPE
1 LP – 24 230 2484 10.8 30 50 2 2 3.5 THHN 1 15 RCP
2 LP -20 230 2070 9 30 50 2 2 3.5 THHN 1 15 RCP
3 LP -25 230 2587.5 11.25 30 50 2 2 3.5 THHN 1 15 RCP
4 LP -25 230 2587.5 11.25 30 50 2 2 3.5 THHN 1 15 RCP
5 LP -21 230 2173.5 9.45 30 50 2 2 3.5 THHN 1 15 RCP
6 LP -26 230 2691 11.7 30 50 2 2 3.5 THHN 1 15 RCP
7 LP -26 230 2691 11.7 30 50 2 2 3.5 THHN 1 15 RCP
8 LP -20 230 2070 9 30 50 2 2 3.5 THHN 1 15 RCP
9 LP -22 230 2277 9.9 30 50 2 2 3.5 THHN 1 15 RCP
10 LP -20 230 2070 9 30 50 2 2 3.5 THHN 1 15 RCP
11 LP -21 230 2173.5 9.45 30 50 2 2 3.5 THHN 1 15 RCP
12 LP -21 230 2173.5 9.45 30 50 2 2 3.5 THHN 1 15 RCP
13 LP -18 230 1863 8.1 30 50 2 2 3.5 THHN 1 15 RCP
14 LP -20 230 2070 9 30 50 2 2 3.5 THHN 1 15 RCP
15 LP -24 230 2484 10.8 30 50 2 2 3.5 THHN 1 15 RCP
16 SPARE 230 3450 15 30 50 2 2 3.5 THHN 1 15 RCP
17 SPARE 230 3450 15 30 50 2 2 3.5 THHN 1 15 RCP
18 SPARE 230 3450 15 30 50 2 2 3.5 THHN 1 15 RCP
TOTAL 44818.5 64.95 65.4 64.5

𝑰𝟑Ø = (√𝟑)(𝟔𝟓. 𝟒) = 𝟏𝟏𝟑. 𝟐𝟖 𝑨 REQUIRED SIZE OF RACEWAY

MINIMUM AMPERE 1 - 32 mmØ METALLIC RCP

𝑰𝑴𝑰𝑵𝑰𝑴𝑼𝑴 = (𝟏𝟏𝟑. 𝟐𝟖)(𝟏. 𝟐𝟓) = 𝟏𝟒𝟏. 𝟔 𝑨 RATING OF FEEDER CB

SIZE OF FEEDER CONDUCTOR 150 AT, 225 AF, 2P, 230V MOLDED CASE TYPE

2 - 50 𝒎𝒎𝟐 THHN COPPER WIRE (AMPACITY = 150 A) SIZE OF GROUNDING

1 - 14 𝒎𝒎𝟐 COPPER CONDUCTOR


LP 3 (LIGHTING WITH CONVENIENCE OUTLET PANEL 3)

BRANCH SIZE & TYPE OF


LOAD TOTAL CURRENT CB RATING SIZE OF CONDUIT
CIRCUIT VOLTAGE FEEDER
DESCRIPTION VA
NO. AB BC CA 3Ø AT AF POLE NO. 𝑚𝑚2 TYPE NO. mmØ TYPE
1 LP -15 230 1552.5 6.75 30 50 2 2 3.5 THHN 1 15 RCP
2 LP -22 230 2277 9.9 30 50 2 2 3.5 THHN 1 15 RCP
3 LP -20 230 2070 9 30 50 2 2 3.5 THHN 1 15 RCP
4 LP -20 230 2070 9 30 50 2 2 3.5 THHN 1 15 RCP
5 LP -20 230 2070 9 30 50 2 2 3.5 THHN 1 15 RCP
6 LP -19 230 1966.5 8.55 30 50 2 2 3.5 THHN 1 15 RCP
7 PP -28 230 5040 21.91 30 50 2 2 3.5 THHN 1 15 RCP
8 PP -38 230 6840 29.74 30 50 2 2 5.5 THHN 1 15 RCP
9 PP -20 230 3600 15.65 30 50 2 2 3.5 THHN 1 15 RCP
10 PP -21 230 3780 16.43 30 50 2 2 3.5 THHN 1 15 RCP
11 PP -20 230 3600 15.65 30 50 2 2 3.5 THHN 1 15 RCP
12 PP -6 230 1080 4.7 30 50 2 2 3.5 THHN 1 15 RCP
13 SPARE 230 5750 25 30 50 2 2 3.5 THHN 1 15 RCP
14 SPARE 230 5750 25 30 50 2 2 3.5 THHN 1 15 RCP
15 SPARE 230 5750 25 30 50 2 2 3.5 THHN 1 15 RCP
TOTAL 53196 76.65 76.75 77.88

𝑰𝟑Ø = (√𝟑)(𝟕𝟕. 𝟖𝟖) = 𝟏𝟑𝟒. 𝟖𝟗 𝑨 REQUIRED SIZE OF RACEWAY

MINIMUM AMPERE 1 - 32 mmØ METALLIC RCP

𝑰𝑴𝑰𝑵𝑰𝑴𝑼𝑴 = (𝟏𝟑𝟒. 𝟖𝟗)(𝟏. 𝟐𝟓) = 𝟏𝟔𝟖. 𝟔𝟏 𝑨 RATING OF FEEDER CB

SIZE OF FEEDER CONDUCTOR 170 AT, 225 AF, 2P, 230V MOLDED CASE TYPE

2 - 60 𝒎𝒎𝟐 THHN COPPER WIRE (AMPACITY = 170 A) SIZE OF GROUNDING

1 - 14 𝒎𝒎𝟐 COPPER CONDUCTOR


LDP (LIGHTING DISTRIBUTION PANEL)

BRANCH SIZE & TYPE OF


LOAD TOTAL CURRENT CB RATING SIZE OF CONDUIT
CIRCUIT VOLTAGE FEEDER
DESCRIPTION VA
NO. AB BC CA 3Ø AT AF POLE NO. 𝑚𝑚2 TYPE NO. mmØ TYPE
1 LP1 230 48748.5 70.8 70.35 70.8 175 225 2 2 60 THHN 1 32 RCP
2 LP2 230 44818.5 64.95 65.4 64.5 150 225 2 2 38 THHN 1 32 RCP
3 LP3 230 53196 76.65 76.75 77.88 175 225 2 2 60 THHN 1 32 RCP
TOTAL 146763 212.4 212.5 213.18

𝑰𝟑Ø = (√𝟑)(𝟐𝟏𝟑. 𝟏𝟖) = 𝟑𝟔𝟗. 𝟐𝟒 𝑨 REQUIRED SIZE OF RACEWAY

MINIMUM AMPERE 1 - 65 mmØ METALLIC RCP

𝑰𝑴𝑰𝑵𝑰𝑴𝑼𝑴 = (𝟑𝟔𝟗. 𝟐𝟒)(𝟏. 𝟐𝟓) = 𝟒𝟔𝟏. 𝟓𝟓 𝑨 RATING OF FEEDER CB

SIZE OF FEEDER CONDUCTOR 500 AT, 500 AF, 2P, 230V MOLDED CASE TYPE

2 - 325 𝒎𝒎𝟐 THHN COPPER WIRE (AMPACITY = 470 A) SIZE OF GROUNDING

1 - 30 𝒎𝒎𝟐 COPPER CONDUCTOR


PPU 1 (POWER PANEL UNIT 1) (FAN COIL UNIT GROUND FLOOR)

BRANCH SIZE & TYPE OF


LOAD TOTAL CURRENT CB RATING SIZE OF CONDUIT
CIRCUIT HP VOLTAGE FEEDER
DESCRIPTION VA
NO. AB BC CA 3Ø AT AF POLE NO. 𝑚𝑚2 TYPE NO. mmØ TYPE
1 FCU 3 230 3910 17 30 50 2 2 3.5 THHN 1 15 RCP
2 FCU 2 230 2760 12 30 50 2 2 3.5 THHN 1 15 RCP
3 FCU 2 230 2760 12 30 50 2 2 3.5 THHN 1 15 RCP
4 FCU 2 230 2760 12 30 50 2 2 3.5 THHN 1 15 RCP
5 FCU 7.5 230 9200 40 45 50 2 2 8 THHN 1 15 RCP
6 FCU 5 230 6440 28 40 50 2 2 5.5 THHN 1 15 RCP
7 FCU 5 230 6440 28 40 50 2 2 5.5 THHN 1 15 RCP
8 FCU 5 230 6440 28 40 50 2 2 5.5 THHN 1 15 RCP
9 FCU 5 230 6440 28 40 50 2 2 5.5 THHN 1 15 RCP
10 FCU 5 230 6440 28 40 50 2 2 5.5 THHN 1 15 RCP
11 FCU 5 230 6440 28 40 50 2 2 5.5 THHN 1 15 RCP
12 FCU 5 230 6440 28 40 50 2 2 5.5 THHN 1 15 RCP
13 FCU 5 230 6440 28 40 50 2 2 5.5 THHN 1 15 RCP
14 FCU 5 230 6440 28 40 50 2 2 5.5 THHN 1 15 RCP
15 FCU 5 230 6440 28 40 50 2 2 5.5 THHN 1 15 RCP
16 SPARE 5 230 6440 28 40 50 2 2 5.5 THHN 1 15 RCP
17 SPARE 5 230 6440 28 40 50 2 2 5.5 THHN 1 15 RCP
18 SPARE 5’ 230 6440 28 40 50 2 2 5.5 THHN 1 15 RCP
TOTAL 105110 153 152 152

𝑰𝟑Ø = (√𝟑)(𝟏𝟓𝟑) = 𝟐𝟔𝟓 𝑨 REQUIRED SIZE OF RACEWAY

MINIMUM AMPERE 1 - 65 mmØ METALLIC RCP

𝑰𝑴𝑰𝑵𝑰𝑴𝑼𝑴 = 𝟐𝟔𝟓 + (𝟎. 𝟐𝟓)(𝟒𝟎) = 𝟐𝟕𝟓 𝑨 RATING OF FEEDER CB

MAXIMUM AMPERE 400 AT, 400 AF, 2P, 230V MOLDED CASE TYPE

𝑰𝑴𝑨𝑿𝑰𝑴𝑼𝑴 = 𝟐𝟔𝟓 + (𝟏)(𝟒𝟎) = 𝟑𝟎𝟓 𝑨 SIZE OF GROUNDING

SIZE OF FEEDER CONDUCTOR 1 - 30 𝒎𝒎𝟐 COPPER CONDUCTOR

2 - 200 𝒎𝒎𝟐 THHN COPPER WIRE (AMPACITY = 355 A)


PPU 2 (POWER PANEL UNIT 2) (FAN COIL UNIT SECOND FLOOR)
BRANCH SIZE & TYPE OF
LOAD TOTAL CURRENT CB RATING SIZE OF CONDUIT
CIRCUIT HP VOLTAGE FEEDER
DESCRIPTION VA
NO. AB BC CA 3Ø AT AF POLE NO. 𝑚𝑚2 TYPE NO. mmØ TYPE
1 FCU 5 230 6440 28 40 50 2 2 5.5 THHN 1 15 RCP
2 FCU 5 230 6440 28 40 50 2 2 5.5 THHN 1 15 RCP
3 FCU 5 230 6440 28 40 50 2 2 5.5 THHN 1 15 RCP
4 FCU 5 230 6440 28 40 50 2 2 5.5 THHN 1 15 RCP
5 FCU 5 230 6440 28 40 50 2 2 5.5 THHN 1 15 RCP
6 FCU 5 230 6440 28 40 50 2 2 5.5 THHN 1 15 RCP
7 FCU 5 230 6440 28 40 50 2 2 5.5 THHN 1 15 RCP
8 FCU 5 230 6440 28 40 50 2 2 5.5 THHN 1 15 RCP
9 FCU 5 230 6440 28 40 50 2 2 5.5 THHN 1 15 RCP
10 FCU 5 230 6440 28 40 50 2 2 5.5 THHN 1 15 RCP
11 FCU 3 230 3910 17 30 50 2 2 3.5 THHN 1 15 RCP
12 FCU 3 230 3910 17 30 50 2 2 3.5 THHN 1 15 RCP
13 FCU 3 230 3910 17 30 50 2 2 3.5 THHN 1 15 RCP
14 FCU 2 230 2760 12 30 50 2 2 3.5 THHN 1 15 RCP
15 FCU 7.5 230 9200 40 45 50 2 2 8 THHN 1 15 RCP
16 FCU 7.5 230 9200 40 45 50 2 2 8 THHN 1 15 RCP
17 SPARE 230 9200 40 45 50 2 2 8 THHN 1 15 RCP
18 SPARE 230 9200 40 45 50 2 2 8 THHN 1 15 RCP
19 SPARE 230 9200 40 45 50 2 2 8 THHN 1 15 RCP
TOTAL 124890 181 181 181

𝑰𝟑Ø = (√𝟑)(𝟏𝟖𝟏) = 𝟑𝟏𝟑. 𝟓 𝑨 REQUIRED SIZE OF RACEWAY

MINIMUM AMPERE 1 - 65 mmØ METALLIC RCP

𝑰𝑴𝑰𝑵𝑰𝑴𝑼𝑴 = 𝟑𝟏𝟑. 𝟓 + (𝟎. 𝟐𝟓)(𝟒𝟎) = 𝟑𝟐𝟑. 𝟓 𝑨 RATING OF FEEDER CB

MAXIMUM AMPERE 400 AT, 400 AF, 2P, 230V MOLDED CASE TYPE

𝑰𝑴𝑨𝑿𝑰𝑴𝑼𝑴 = 𝟑𝟏𝟑. 𝟓 + (𝟏)(𝟒𝟎) = 𝟑𝟓𝟑. 𝟓 𝑨 SIZE OF GROUNDING

SIZE OF FEEDER CONDUCTOR 1 - 30 𝒎𝒎𝟐 COPPER CONDUCTOR

2 - 250 𝒎𝒎𝟐 THHN COPPER WIRE (AMPACITY = 400 A)


PPU 3 (POWER PANEL UNIT 3) (AIR HANDLING UNIT GROUND FLOOR)

BRANCH SIZE & TYPE OF


LOAD TOTAL CURRENT CB RATING SIZE OF CONDUIT
CIRCUIT HP VOLTAGE FEEDER
DESCRIPTION VA
NO. AB BC CA 3Ø AT AF POLE NO. 𝑚𝑚2 TYPE NO. mmØ TYPE
1 AHU 15 230 9660 42 90 100 3 3 22 THHN 1 25 RCP
2 AHU 15 230 9660 42 90 100 3 3 22 THHN 1 25 RCP
3 AHU 15 230 9660 42 90 100 3 3 22 THHN 1 25 RCP
4 AHU 15 230 9660 42 90 100 3 3 22 THHN 1 25 RCP
5 AHU 15 230 9660 42 90 100 3 3 22 THHN 1 25 RCP
6 AHU 15 230 9660 42 90 100 3 3 22 THHN 1 25 RCP
7 AHU 15 230 9660 42 90 100 3 3 22 THHN 1 25 RCP
8 AHU 15 230 9660 42 90 100 3 3 22 THHN 1 25 RCP
9 AHU 15 230 9660 42 90 100 3 3 22 THHN 1 25 RCP
10 AHU 15 230 9660 42 90 100 3 3 22 THHN 1 25 RCP
11 SPARE 230 9660 42 90 100 3 3 22 THHN 1 25 RCP
12 SPARE 230 9660 42 90 100 3 3 22 THHN 1 25 RCP
13 SPARE 230 9660 42 90 100 3 3 22 THHN 1 25 RCP
TOTAL 125580 546

𝑰𝟑Ø = 𝟓𝟒𝟔 𝑨 REQUIRED SIZE OF RACEWAY

MINIMUM AMPERE 1 - 80 mmØ METALLIC RCP

𝑰𝑴𝑰𝑵𝑰𝑴𝑼𝑴 = 𝟓𝟒𝟔 + (𝟒𝟐)(𝟎. 𝟐𝟓) = 𝟓𝟓𝟔. 𝟓 𝑨 RATING OF FEEDER CB


MAXIMUM AMPERE 1000 AT, 1000 AF, 3P, 230V MOLDED CASE TYPE
𝑰𝑴𝑨𝑿𝑰𝑴𝑼𝑴 = 𝟓𝟒𝟔 + (𝟒𝟐)(𝟏) = 𝟓𝟖𝟖 𝑨 SIZE OF GROUNDING
SIZE OF FEEDER CONDUCTOR 1 - 50 𝒎𝒎𝟐 COPPER CONDUCTOR
2 SETS - 3 - 200 𝒎𝒎𝟐 THHN COPPER WIRE (AMPACITY=710 A)
PPU 4 (POWER PANEL UNIT 4) (AIR HANDLING UNIT SECOND FLOOR)

BRANCH SIZE & TYPE OF


LOAD TOTAL CURRENT CB RATING SIZE OF CONDUIT
CIRCUIT HP VOLTAGE FEEDER
DESCRIPTION VA
NO. AB BC CA 3Ø AT AF POLE NO. 𝑚𝑚2 TYPE NO. mmØ TYPE
1 AHU 15 230 9660 42 90 100 3 3 22 THHN 1 25 RCP
2 AHU 15 230 9660 42 90 100 3 3 22 THHN 1 25 RCP
3 AHU 15 230 9660 42 90 100 3 3 22 THHN 1 25 RCP
4 AHU 15 230 9660 42 90 100 3 3 22 THHN 1 25 RCP
5 AHU 15 230 9660 42 90 100 3 3 22 THHN 1 25 RCP
6 AHU 15 230 9660 42 90 100 3 3 22 THHN 1 25 RCP
7 AHU 15 230 9660 42 90 100 3 3 22 THHN 1 25 RCP
8 AHU 15 230 9660 42 90 100 3 3 22 THHN 1 25 RCP
9 AHU 15 230 9660 42 90 100 3 3 22 THHN 1 25 RCP
10 SPARE 230 9660 42 90 100 3 3 22 THHN 1 25 RCP
11 SPARE 230 9660 42 90 100 3 3 22 THHN 1 25 RCP
12 SPARE 230 9660 42 90 100 3 3 22 THHN 1 25 RCP
TOTAL 115920 504

𝑰𝟑Ø = 𝟓𝟎𝟒 𝑨 REQUIRED SIZE OF RACEWAY

MINIMUM AMPERE 1 - 80 mmØ METALLIC RCP

𝑰𝑴𝑰𝑵𝑰𝑴𝑼𝑴 = 𝟓𝟎𝟒 + (𝟒𝟐)(𝟎. 𝟐𝟓) = 𝟓𝟏𝟒. 𝟓 𝑨 RATING OF FEEDER CB


MAXIMUM AMPERE 1000 AT, 1000 AF, 3P, 230V MOLDED CASE TYPE
𝑰𝑴𝑨𝑿𝑰𝑴𝑼𝑴 = 𝟓𝟎𝟒 + (𝟒𝟐)(𝟏) = 𝟓𝟒𝟔 𝑨 SIZE OF GROUNDING
SIZE OF FEEDER CONDUCTOR 1 - 50 𝒎𝒎𝟐 COPPER CONDUCTOR
2 SETS - 3 - 200 𝒎𝒎𝟐 THHN COPPER WIRE (AMPACITY = 710 A)
PPU 5 (POWER PANEL UNIT 5)
BRANCH SIZE & TYPE OF
LOAD TOTAL CURRENT CB RATING SIZE OF CONDUIT
CIRCUIT HP VOLTAGE FEEDER
DESCRIPTION VA
NO. AB BC CA 3Ø AT AF POLE NO. 𝑚𝑚2 TYPE NO. mmØ TYPE
1 DX -21 2 230 57960 252 300 400 2 2 125 THHN 1 50 RCP
2 ACCU 1 -17 1/3 230 14076 61.2 100 100 2 2 14 THHN 1 20 RCP
3 ACCU 2 -17 1/3 230 14076 61.2 100 100 2 2 14 THHN 1 20 RCP
1
4 PACU -6 230 13800 60 100 100 2 2 14 THHN 1 20 RCP
1/2
5 CT -3 1/2 230 3381 14.7 30 50 2 2 3.5 THHN 1 15 RCP
6 CCTVS - 148 1/6 230 74888 325.6 400 400 2 2 200 THHN 2 32
7 SPEAKERS - 70 1/4 230 46690 203 300 400 2 2 80 THHN 1 40 RCP
8 SPARE 230 74888 325.6 400 400 2 2 200 THHN 2 32 RCP
9 SPARE 230 74888 325.6 400 400 2 2 200 THHN 2 32 RCP
11 SPARE 230 74888 325.6 400 400 2 2 200 THHN 2 32 RCP
TOTAL 449535 651.2 651 652.3

𝑰𝟑Ø = (√𝟑)(𝟔𝟓𝟐. 𝟑) = 𝟏𝟏𝟐𝟗. 𝟖𝟐 𝑨 REQUIRED SIZE OF RACEWAY

MINIMUM AMPERE 4 - 80 mmØ RCP

𝑰𝑴𝑰𝑵𝑰𝑴𝑼𝑴 = 𝟏𝟏𝟐𝟗. 𝟖𝟐 + (𝟑𝟐𝟓. 𝟔)(𝟎. 𝟐𝟓) = 𝟏𝟐𝟏𝟏. 𝟐𝟐 𝑨 RATING OF FEEDER CB

MAXIMUM AMPERE 2000 AT, 2000 AF, 3P, 230V MOLDED CASE TYPE

𝑰𝑴𝑨𝑿𝑰𝑴𝑼𝑴 = 𝟏𝟏𝟐𝟗. 𝟖𝟐 + (𝟑𝟐𝟓. 𝟔)(𝟏) = 𝟏𝟒𝟓𝟓. 𝟒𝟐 𝑨 SIZE OF GROUNDING

SIZE OF FEEDER CONDUCTOR 1 - 125 𝒎𝒎𝟐 COPPER CONDUCTOR

4 SETS - 3 - 325 𝒎𝒎𝟐 THHN COPPER WIRE (AMPACITY = 1880 A)


MDP 3 (MAIN DISTRIBUTION PANEL 3)

‘BRANCH SIZE & TYPE OF


LOAD TOTAL CURRENT CB RATING SIZE OF CONDUIT
CIRCUIT VOLTAGE FEEDER
DESCRIPTION VA
NO. AB BC CA 3Ø AT AF POLE NO. 𝑚𝑚2 TYPE NO. mmØ TYPE
1 PPU1 230 105110 153 152 152 400 400 2 2 200 THHN 1 65 RCP
2 PPU2 230 124890 181 181 181 400 400 2 2 250 THHN 1 65 RCP
3 PPU3 230 125580 546 1000 1000 3 6 200 THHN 1 80 RCP
4 PPU4 230 115920 504 1000 1000 3 6 200 THHN 1 80 RCP
5 PPU5 230 449535 651.2 651 652.3 2000 2000 3 12 325 THHN 4 80 RCP
TOTAL 921035 985.2 984 985.3 1050

𝑰𝟑Ø = (√𝟑)(𝟗𝟖𝟓. 𝟑 + 𝟗𝟖𝟒 + 𝟗𝟖𝟓. 𝟑) + 𝟏𝟎𝟓𝟎 = 𝟒𝟎𝟎𝟒. 𝟔 𝑨 MAXIMUM AMPERE

MINIMUM AMPACITY 𝑰𝑴𝑨𝑿𝑰𝑴𝑼𝑴 = 𝟒𝟎𝟎𝟒. 𝟔 + (𝟓𝟒𝟔)(𝟏) = 𝟒𝟓𝟓𝟎. 𝟔 𝑨

𝑰𝑴𝑰𝑵𝑰𝑴𝑼𝑴 = 𝟒𝟎𝟎𝟒. 𝟔 + (𝟓𝟒𝟔)(𝟎. 𝟐𝟓) = 𝟒𝟏𝟒𝟏. 𝟏 𝑨 RATING OF FEEDER CB

SIZE OF FEEDER CONDUCTOR 10000 AT, 10000 AF, 3P, 230V MOLDED CASE TYPE

“10 SETS - 3 - 500 𝒎𝒎𝟐 THHN COPPER WIRE (AMPACITY = 5800 A) SIZE OF GROUNDING

REQUIRED SIZE OF RACEWAY 1 - 400 𝒎𝒎𝟐 COPPER CONDUCTOR

10 - 90 mmØ METALLIC RCP


PPS 1 (POWER PANEL ALL DAY SUPER MARKET)
BRANCH SIZE & TYPE OF
LOAD TOTAL CURRENT CB RATING SIZE OF CONDUIT
CIRCUIT VOLTAGE FEEDER
DESCRIPTION VA
NO. AB BC CA 3Ø AT AF POLE NO. 𝑚𝑚2 TYPE NO. mmØ TYPE
1 230 2208 9.6 30 50 3 3 3.5 THHN 1 15 RCP
2 230 3450 15 30 50 2 2 3.5 THHN 1 15 RCP
3 230 1656 7.2 30 50 2 2 3.5 THHN 1 15 RCP
4 230 7504.9 32.63 70 100 3 3 5.5 THHN 1 15 RCP
5 230 3187.8 13.86 30 50 2 2 3.5 THHN 1 15 RCP
6 230 1656 7.2 30 50 2 2 3.5 THHN 1 15 RCP
7 SPARE 230 3450 15 “ 30 50 2 2 3.5 THHN 1 15 RCP
8 SPARE 230 3450 15 “ 30 50 2 2 3.5 THHN 1 15 RCP
9 SPARE 230 3450 15 “ 30 50 2 2 3.5 THHN 1 15 RCP
10 SPARE 230 7504.9 ’32.63” 70 100 3 3 5.5 THHN 1 15 RCP
TOTAL 37517.6 30 29.4 28.86 74.86

𝑰𝟑Ø = (√𝟑)(𝟑𝟎) + 𝟕𝟒. 𝟖𝟔 = 𝟏𝟐𝟔. 𝟖𝟐 𝑨 3 - 80 𝒎𝒎𝟐 THHN COPPER WIRE (AMPACITY = 205 A)

MINIMUM AMPERE REQUIRED SIZE OF RACEWAY

𝑰𝑴𝑰𝑵𝑰𝑴𝑼𝑴 = 𝟏𝟐𝟔. 𝟖𝟐 + (𝟑𝟐. 𝟔𝟑)(𝟎. 𝟐𝟓) = 𝟏𝟑𝟒. 𝟗𝟖 𝑨 1 - 40 mmØ METALLIC RCP

MAXIMUM AMPERE RATING OF FEEDER CB

𝑰𝑴𝑨𝑿𝑰𝑴𝑼𝑴 = 𝟏𝟐𝟔. 𝟖𝟐 + (𝟑𝟐. 𝟔𝟑)(𝟏) = 𝟏𝟓𝟗. 𝟒𝟓 𝑨 300 AT, 400 AF, 3P, 230V MOLDED CASE TYPE

SIZE OF FEEDER CONDUCTOR SIZE OF GROUNDING

1 - 22 𝒎𝒎𝟐 COPPER CONDUCTOR


PPS 2 (POWER PANEL RETAIL STORES)
BRANCH CURRENT CB RATING SIZE & TYPE OF FEEDER SIZE OF CONDUIT
LOAD TOTAL
CIRCUIT VOLTAGE 2
DESCRIPTION VA AB BC CA 3Ø AT AF POLE NO. 𝑚𝑚 TYPE NO. mmØ TYPE
NO.
1 R1 230 4600 20 40 50 3 3 3.5 THHN 1 15 RCP
2 R2 230 4600 20 40 50 3 3 3.5 THHN 1 15 RCP
3 R3 230 4600 20 40 50 3 3 3.5 THHN 1 15 RCP
4 R4 230 4600 20 40 50 3 3 3.5 THHN 1 15 RCP
5 R5 230 4600 20 40 50 3 3 3.5 THHN 1 15 RCP
6 R6 230 4600 20 40 50 3 3 3.5 THHN 1 15 RCP
7 R7 230 4600 20 40 50 3 3 3.5 THHN 1 15 RCP
8 R8 230 4600 20 40 50 3 3 3.5 THHN 1 15 RCP
9 R9 230 4600 20 40 50 3 3 3.5 THHN 1 15 RCP
10 R 10 230 4600 20 40 50 3 3 3.5 THHN 1 15 RCP
11 R 11 230 4600 20 40 50 3 3 3.5 THHN 1 15 RCP
12 R 12 230 4600 20 40 50 3 3 3.5 THHN 1 15 RCP
13 SPARE 230 4600 20 40 50 3 3 3.5 THHN 1 15 RCP
14 SPARE 230 4600 20 40 50 3 3 3.5 THHN 1 15 RCP
15 SPARE 230 4600 20 40 50 3 3 3.5 THHN 1 15 RCP
TOTAL 69000 300

𝑰𝟑Ø = 𝟑𝟎𝟎 𝑨 REQUIRED SIZE OF RACEWAY

MINIMUM AMPERE 1 - 80 mmØ METALLIC RCP

𝑰𝑴𝑰𝑵𝑰𝑴𝑼𝑴 = 𝟑𝟎𝟎 + (𝟐𝟎)(𝟎. 𝟐𝟓) = 𝟑𝟎𝟓 𝑨 RATING OF FEEDER CB


MAXIMUM AMPERE 600 AT, 1000 AF, 3P, 230V MOLDED CASE TYPE
𝑰𝑴𝑨𝑿𝑰𝑴𝑼𝑴 = 𝟑𝟎𝟎 + (𝟐𝟎)(𝟏. 𝟓) = 𝟑𝟑𝟎 𝑨 SIZE OF GROUNDING
SIZE OF FEEDER CONDUCTOR 1 - 30 𝒎𝒎𝟐 COPPER CONDUCTOR
3 - 325 𝒎𝒎𝟐 THHN COPPER WIRE (AMPACITY = 470 A)
PDPS (POWER ISTRIBUTION PANEL STORES)
BRANCH SIZE & TYPE OF
LOAD TOTAL CURRENT CB RATING SIZE OF CONDUIT
CIRCUIT VOLTAGE FEEDER
DESCRIPTION VA
NO. AB BC CA 3Ø AT AF POLE NO. 𝑚𝑚2 TYPE NO. mmØ TYPE
1 PPS 1 230 37517.6 30 29.4 28.86 74.86 300 400 3 3 80 THHN 1 40 RCP
2 PP2S 230 69000 300 600 1000 3 3 325 THHN 1 80 RCP
TOTAL 106517.6 30 29.4 28.86 374.86

𝑰𝟑Ø = (√𝟑)(𝟑𝟎) + 𝟑𝟕𝟒. 𝟖𝟔 = 𝟒𝟐𝟔. 𝟖𝟐 𝑨 REQUIRED SIZE OF RACEWAY

MINIMUM AMPERE 3 - 65 mmØ METALLIC RCP

𝑰𝑴𝑰𝑵𝑰𝑴𝑼𝑴 = 𝟒𝟐𝟔. 𝟖𝟐 + (𝟑𝟎𝟎)(𝟎. 𝟐𝟓) = 𝟓𝟎𝟏. 𝟖𝟐 𝑨 RATING OF FEEDER CB

MAXIMUM AMPERE 1500 AT, 1500 AF, 3P, 230V MOLDED CASE TYPE

𝑰𝑴𝑨𝑿𝑰𝑴𝑼𝑴 = 𝟒𝟐𝟔. 𝟖𝟐 + (𝟑𝟎𝟎)(𝟏) = 𝟕𝟐𝟔. 𝟖𝟐 𝑨 SIZE OF GROUNDING

SIZE OF FEEDER CONDUCTOR 1 - 60 𝒎𝒎𝟐 COPPER CONDUCTOR

2 SETS - 3 - 325 𝒎𝒎𝟐 THHN COPPER WIRE (AMPACITY = 940 A)


PPC 1 (POWER PANEL CINEMA 1)
BRANCH SIZE & TYPE OF
LOAD TOTAL CURRENT CB RATING SIZE OF CONDUIT
CIRCUIT VOLTAGE FEEDER
DESCRIPTION VA
NO. AB BC CA 3Ø AT AF POLE NO. 𝑚𝑚2 TYPE NO. mmØ TYPE
EQUIPMENT
1 230 48300 210 450 500 3 3 125 THHN 1 50 RCP
PROJECTOR
CINEMA
2 230 37202.5 161.75 400 500 3 3 80 THHN 1 40 RCP
EQUIPMENTS
3 SPARE 230 48300 210 450 500 3 3 125 THHN 1 50 RCP
4 SPARE 230 48300 210 450 500 3 3 125 THHN 1 50 RCP
5’ SPARE 230 48300 210 450 500 3 3 125 THHN 1 50 RCP
TOTAL 230402.5 1001.75

𝑰𝟑Ø = 𝟏𝟎𝟎𝟏. 𝟕𝟓 𝑨 REQUIRED SIZE OF RACEWAY

MINIMUM AMPERE 3 - 90 mmØ METALLIC RCP

𝑰𝑴𝑰𝑵𝑰𝑴𝑼𝑴 = 𝟏𝟎𝟎𝟏. 𝟕𝟓 + (𝟐𝟏𝟎)(𝟎. 𝟐𝟓) = 𝟏𝟎𝟓𝟒. 𝟐𝟓 𝑨 RATING OF FEEDER CB


MAXIMUM AMPERE 2500 AT, 2500 AF, 3P, 230V MOLDED CASE TYPE
𝑰𝑴𝑨𝑿𝑰𝑴𝑼𝑴 = 𝟏𝟎𝟎𝟏. 𝟕𝟓 + (𝟐𝟏𝟎)(𝟏) = 𝟏𝟐𝟏𝟏. 𝟕𝟓 𝑨 SIZE OF GROUNDING
SIZE OF FEEDER CONDUCTOR 1 - 125 𝒎𝒎𝟐 COPPER CONDUCTOR
3 SETS - 3 - 500 𝒎𝒎𝟐 THHN COPPER WIRE (AMPACITY = 1740 A)
PPC 2 (POWER PANEL CINEMA 2)
BRANCH SIZE & TYPE OF
LOAD TOTAL CURRENT CB RATING SIZE OF CONDUIT
CIRCUIT VOLTAGE FEEDER
DESCRIPTION VA
NO. AB BC CA 3Ø AT AF POLE NO. 𝑚𝑚2 TYPE NO. mmØ TYPE
EQUIPMENT
1 230 42977.8 186.86 400 400 3 3 125 THHN 1 50 RCP
PROJECTOR
CINEMA
2 230 37202.5 161.75 400 400 3 3 125 THHN 1 50 RCP
EQUIPMENTS
3 SPARE 230 42977.8 186.86 400 400 3 3 125 THHN 1 50 RCP
4 SPARE 230 42977.8 186.86 400 400 3 3 125 THHN 1 50 RCP
5 SPARE 230 42977.8 186.86 400 400 3 3 125 THHN 1 50 RCP
TOTAL 209113.7 909.19

𝑰𝟑Ø = 𝟗𝟎𝟗. 𝟏𝟗 𝑨 REQUIRED SIZE OF RACEWAY

MINIMUM AMPERE 3 - 80 mmØ METALLIC RCP

𝑰𝑴𝑰𝑵𝑰𝑴𝑼𝑴 = 𝟗𝟎𝟗. 𝟏𝟗 + (𝟏𝟖𝟔. 𝟖𝟔)(𝟎. 𝟐𝟓) = 𝟗𝟓𝟓. 𝟗𝟏 𝑨 RATING OF FEEDER CB


MAXIMUM AMPERE 2000 AT, 2000 AF, 3P, 230V MOLDED CASE TYPE
𝑰𝑴𝑨𝑿𝑰𝑴𝑼𝑴 = 𝟗𝟎𝟗. 𝟏𝟗 + (𝟏𝟖𝟔. 𝟖𝟔)(𝟏) = 𝟏𝟎𝟗𝟔. 𝟎𝟓 𝑨 SIZE OF GROUNDING
SIZE OF FEEDER CONDUCTOR 1 - 125 𝒎𝒎𝟐 COPPER CONDUCTOR
3 SETS - 3 - 400 𝒎𝒎𝟐 THHN COPPER WIRE (AMPACITY = 1545 A)

PPC 3 (POWER PANEL CINEMA 3)


BRANCH SIZE & TYPE OF
LOAD TOTAL CURRENT CB RATING SIZE OF CONDUIT
CIRCUIT VOLTAGE FEEDER
DESCRIPTION VA
NO. AB BC CA 3Ø AT AF POLE NO. 𝑚𝑚2 TYPE NO. mmØ TYPE
EQUIPMENT
1 230 42977.8 186.86 400 400 3 3 125 THHN 1 50 RCP
PROJECTOR
CINEMA
2 230 37202.5 161.75 400 400 3 3 125 THHN 1 50 RCP
EQUIPMENTS
3 SPARE 230 42977.8 186.86 400 400 3 3 125 THHN 1 50 RCP
4 SPARE 230 42977.8 186.86 400 400 3 3 125 THHN 1 50 RCP
5 SPARE 230 42977.8 186.86 400 400 3 3 125 THHN 1 50 RCP
TOTAL 209113.7 909.19
𝑰𝟑Ø = 𝟗𝟎𝟗. 𝟏𝟗 𝑨 REQUIRED SIZE OF RACEWAY

MINIMUM AMPERE 3 - 80 mmØ METALLIC RCP

𝑰𝑴𝑰𝑵𝑰𝑴𝑼𝑴 = 𝟗𝟎𝟗. 𝟏𝟗 + (𝟏𝟖𝟔. 𝟖𝟔)(𝟎. 𝟐𝟓) = 𝟗𝟓𝟓. 𝟗𝟏 𝑨 RATING OF FEEDER CB


MAXIMUM AMPERE 2000 AT, 2000 AF, 3P, 230V MOLDED CASE TYPE
𝑰𝑴𝑨𝑿𝑰𝑴𝑼𝑴 = 𝟗𝟎𝟗. 𝟏𝟗 + (𝟏𝟖𝟔. 𝟖𝟔)(𝟏) = 𝟏𝟎𝟗𝟔. 𝟎𝟓 𝑨 SIZE OF GROUNDING
SIZE OF FEEDER CONDUCTOR 1 - 125 𝒎𝒎𝟐 COPPER CONDUCTOR
3 SETS - 3 - 400 𝒎𝒎𝟐 THHN COPPER WIRE (AMPACITY = 1545 A)

PPC 4 (POWER PANEL CINEMA 4)


BRANCH SIZE & TYPE OF
LOAD TOTAL CURRENT CB RATING SIZE OF CONDUIT
CIRCUIT VOLTAGE FEEDER
DESCRIPTION VA
NO. AB BC CA 3Ø AT AF POLE NO. 𝑚𝑚2 TYPE NO. mmØ TYPE
EQUIPMENT
1 230 35077.3 152.51 350 400 3 3 80 THHN 1 40 RCP
PROJECTOR
CINEMA
2 230 37202.5 161.75 350 400 3 3 80 THHN 1 40 RCP
EQUIPMENTS
3 SPARE 230 37202.5 161.75 350 400 3 3 80 THHN 1 40 RCP
4 SPARE 230 37202.5 161.75 350 400 3 3 80 THHN 1 40 RCP
5 SPARE 230 37202.5 161.75 350 400 3 3 80 THHN 1 40 RCP
TOTAL 183887.3 799.51

𝑰𝟑Ø = 𝟕𝟗𝟗. 𝟓𝟏 𝑨 REQUIRED SIZE OF RACEWAY

MINIMUM AMPERE 3 - 80 mmØ METALLIC RCP

𝑰𝑴𝑰𝑵𝑰𝑴𝑼𝑴 = 𝟕𝟗𝟗. 𝟓𝟏 + (𝟏𝟔𝟏. 𝟕𝟓)(𝟎. 𝟐𝟓) = 𝟖𝟑𝟗. 𝟗𝟓 𝑨 RATING OF FEEDER CB


MAXIMUM AMPERE 2000 AT, 2000 AF, 3P, 230V MOLDED CASE TYPE
𝑰𝑴𝑨𝑿𝑰𝑴𝑼𝑴 = 𝟕𝟗𝟗. 𝟓𝟏 + (𝟏𝟔𝟏. 𝟕𝟓)(𝟏) = 𝟗𝟔𝟏. 𝟐𝟔 𝑨 SIZE OF GROUNDING
SIZE OF FEEDER CONDUCTOR 1 - 125 𝒎𝒎𝟐 COPPER CONDUCTOR
3 SETS - 3 - 400 𝒎𝒎𝟐 THHN COPPER WIRE (AMPACITY = 1545 A)
PPC 5 (POWER PANEL CINEMA 5)
BRANCH SIZE & TYPE OF
LOAD TOTAL CURRENT CB RATING SIZE OF CONDUIT
CIRCUIT VOLTAGE FEEDER
DESCRIPTION VA
NO. AB BC CA 3Ø AT AF POLE NO. 𝑚𝑚2 TYPE NO. mmØ TYPE
EQUIPMENT
1 230 35077.3 152.51 350 400 3 3 80 THHN 1 40 RCP
PROJECTOR
CINEMA
2 230 37202.5 161.75 350 400 3 3 80 THHN 1 40 RCP
EQUIPMENTS
3 SPARE 230 37202.5 161.75 350 400 3 3 80 THHN 1 40 RCP
4 SPARE 230 37202.5 161.75 350 400 3 3 80 THHN 1 40 RCP
5 SPARE 230 37202.5 161.75 350 400 3 3 80 THHN 1 40 RCP
TOTAL 183887.3 799.51

𝑰𝟑Ø = 𝟕𝟗𝟗. 𝟓𝟏 𝑨 REQUIRED SIZE OF RACEWAY

MINIMUM AMPERE 3 - 80 mmØ METALLIC RCP

𝑰𝑴𝑰𝑵𝑰𝑴𝑼𝑴 = 𝟕𝟗𝟗. 𝟓𝟏 + (𝟏𝟔𝟏. 𝟕𝟓)(𝟎. 𝟐𝟓) = 𝟖𝟑𝟗. 𝟗𝟓 𝑨 RATING OF FEEDER CB


MAXIMUM AMPERE 2000 AT, 2000 AF, 3P, 230V MOLDED CASE TYPE
𝑰𝑴𝑨𝑿𝑰𝑴𝑼𝑴 = 𝟕𝟗𝟗. 𝟓𝟏 + (𝟏𝟔𝟏. 𝟕𝟓)(𝟏) = 𝟗𝟔𝟏. 𝟐𝟔 𝑨 SIZE OF GROUNDING
SIZE OF FEEDER CONDUCTOR 1 - 125 𝒎𝒎𝟐 COPPER CONDUCTOR
3 SETS - 3 - 400 𝒎𝒎𝟐 THHN COPPER WIRE (AMPACITY = 1545 A)
PPC 6 (POWER PANEL CINEMA 6)
BRANCH SIZE & TYPE OF
LOAD TOTAL CURRENT CB RATING SIZE OF CONDUIT
CIRCUIT VOLTAGE FEEDER
DESCRIPTION VA
NO. AB BC CA 3Ø AT AF POLE NO. 𝑚𝑚2 TYPE NO. mmØ TYPE
EQUIPMENT
1 230 34617.3 150.51 350 400 3 3 80 THHN 1 40 RCP
PROJECTOR
CINEMA
2 230 37202.5 161.75 350 400 3 3 80 THHN 1 40 RCP
EQUIPMENTS
3 SPARE 230 37202.5 161.75 350 400 3 3 80 THHN 1 40 RCP
4 SPARE 230 37202.5 161.75 350 400 3 3 80 THHN 1 40 RCP
5 SPARE 230 37202.5 161.75 350 400 3 3 80 THHN 1 40 RCP
TOTAL 183427.3 797.51

𝑰𝟑Ø = 𝟕𝟗𝟕. 𝟓𝟏 𝑨 REQUIRED SIZE OF RACEWAY

MINIMUM AMPERE 3 - 80 mmØ METALLIC RCP

𝑰𝑴𝑰𝑵𝑰𝑴𝑼𝑴 = 𝟕𝟗𝟕. 𝟓𝟏 + (𝟏𝟔𝟏. 𝟕𝟓)(𝟎. 𝟐𝟓) = 𝟖𝟑𝟕. 𝟗𝟓 𝑨 RATING OF FEEDER CB


MAXIMUM AMPERE 2000 AT, 2000 AF, 3P, 230V MOLDED CASE TYPE
𝑰𝑴𝑨𝑿𝑰𝑴𝑼𝑴 = 𝟕𝟗𝟕. 𝟓𝟏 + (𝟏𝟔𝟏. 𝟕𝟓)(𝟏) = 𝟗𝟓𝟗. 𝟐𝟔 𝑨 SIZE OF GROUNDING
SIZE OF FEEDER CONDUCTOR 1 - 125 𝒎𝒎𝟐 COPPER CONDUCTOR
3 SETS - 3 - 400 𝒎𝒎𝟐 THHN COPPER WIRE (AMPACITY = 1545 A)

MDP 4 (MAIN DISTRIBUTION PANEL 4)


BRANCH SIZE & TYPE OF
LOAD TOTAL CURRENT CB RATING SIZE OF CONDUIT
CIRCUIT VOLTAGE FEEDER
DESCRIPTION VA
NO. AB BC CA 3Ø AT AF POLE NO. 𝑚𝑚2 TYPE NO. mmØ TYPE
1 PPC 1 230 230402.5 1001.75 2500 2500 3 9 500 THHN 3 90 RCP
2 PPC 2 230 209113.7 909.19 2000 2000 3 9 400 THHN 3 80 RCP
3 PPC 3 230 209113.7 909.19 2000 2000 3 9 400 THHN 3 80 RCP
4 PPC 4 230 183887.3 799.51 2000 2000 3 9 400 THHN 3 80 RCP
5 PPC 5 230 183887.3 799.51 2000 2000 3 9 400 THHN 3 80 RCP
6 PPC 6 230 183427.3 797.51 2000 2000 3 9 400 THHN 3 80 RCP
TOTAL 1199831.8 5216.66
𝑰𝟑Ø = 𝟓𝟐𝟏𝟔. 𝟔𝟔 𝑨 MAXIMUM AMPERE

MINIMUM AMPACITY 𝑰𝑴𝑨𝑿𝑰𝑴𝑼𝑴 = 𝟓𝟐𝟏𝟔. 𝟔𝟔 + (𝟏𝟎𝟎𝟏. 𝟕𝟓)(𝟏) = 𝟔𝟐𝟏𝟖. 𝟒𝟏 𝑨

𝑰𝑴𝑰𝑵𝑰𝑴𝑼𝑴 = 𝟓𝟐𝟏𝟔. 𝟔𝟔 + (𝟏𝟎𝟎𝟏. 𝟕𝟓)(𝟎. 𝟐𝟓) = 𝟓𝟒𝟔𝟕. 𝟏 𝑨 RATING OF FEEDER CB

SIZE OF FEEDER CONDUCTOR 13000 AT, 13000 AF, 3P, 230V MOLDED CASE TYPE

14 SETS - 3 - 𝟓𝟎𝟎 𝒎𝒎𝟐 THHN COPPER WIRE (AMPACITY = 8120 A) SIZE OF GROUNDING

REQUIRED SIZE OF RACEWAY 1 - 𝟒𝟎𝟎 𝒎𝒎𝟐 COPPER CONDUCTOR

14 - 90 mmØ METALLIC RCP

PPEL MAIN (POWER PANEL ELEVATOR MAIN)


BRANCH SIZE & TYPE OF
LOAD TOTAL CURRENT CB RATING SIZE OF CONDUIT
CIRCUIT HP VOLTAGE FEEDER
DESCRIPTION VA
NO. AB BC CA 3Ø AT AF POLE NO. 𝑚𝑚2 TYPE NO. mmØ TYPE
1 PPEL 1 25 230 15640 68 150 225 3 3 22 THHN 1 25 RCP
2 PPEL 2 25 230 15640 68 150 225 3 3 22 THHN 1 25 RCP
3 PPEL 3 25 230 15640 68 150 225 3 3 22 THHN 1 25 RCP
4 SPARE 25 230 15640 68 150 225 3 3 22 THHN 1 25 RCP
5 SPARE 25 230 15640 68 150 225 3 3 22 THHN 1 25 RCP
6 SPARE 25 230 15640 68 150 225 3 3 22 THHN 1 25 RCP
TOTAL 93840 408

𝑰𝟑Ø = 𝟒𝟎𝟖 𝑨 REQUIRED SIZE OF RACEWAY

MINIMUM AMPERE 1 - 80 mmØ METALLIC RCP

𝑰𝑴𝑰𝑵𝑰𝑴𝑼𝑴 = 𝟒𝟎𝟖 + (𝟔𝟖)(𝟎. 𝟐𝟓) = 𝟒𝟐𝟓 𝑨 RATING OF FEEDER CB


MAXIMUM AMPERE 1000 AT, 1000 AF, 3P, 230V MOLDED CASE TYPE
𝑰𝑴𝑨𝑿𝑰𝑴𝑼𝑴 = 𝟒𝟎𝟖 + (𝟔𝟖)(𝟏) = 𝟒𝟕𝟔 𝑨 SIZE OF GROUNDING
SIZE OF FEEDER CONDUCTOR 1 - 60 𝒎𝒎𝟐 COPPER CONDUCTOR
2 SETS - 3 - 200 𝒎𝒎𝟐 THHN COPPER WIRE (AMPACITY = 710 A)
PPES MAIN (POWER PANEL ESCALATOR MAIN)
BRANCH SIZE & TYPE OF
LOAD TOTAL CURRENT CB RATING SIZE OF CONDUIT
CIRCUIT HP VOLTAGE FEEDER
DESCRIPTION VA
NO. AB BC CA 3Ø AT AF POLE NO. 𝑚𝑚2 TYPE NO. mmØ TYPE
1 PPES 1 7 1/2 230 5060 22 50 100 3 3 5.5 THHN 1 15 RCP
2 PPES 2 7 1/2 230 5060 22 50 100 3 3 5.5 THHN 1 15 RCP
3 PPES 3 7 1/2 230 5060 22 50 100 3 3 5.5 THHN 1 15 RCP
4 PPES 4 7 1/2 230 5060 22 50 100 3 3 5.5 THHN 1 15 RCP
5 PPES 5 7 1/2 230 5060 22 50 100 3 3 5.5 THHN 1 15 RCP
6 PPES 6 7 1/2 230 5060 22 50 100 3 3 5.5 THHN 1 15 RCP
7 PPES 7 7 1/2 230 5060 22 50 100 3 3 5.5 THHN 1 15 RCP
8 PPES 8 7 1/2 230 5060 22 50 100 3 3 5.5 THHN 1 15 RCP
9 SPARE 7 1/2 230 5060 22 50 100 3 3 5.5 THHN 1 15 RCP
10 SPARE 7 1/2 230 5060 22 50 100 3 3 5.5 THHN 1 15 RCP
11 SPARE 7 1/2 230 5060 22 50 100 3 3 5.5 THHN 1 15 RCP
TOTAL 55660 242

“𝑰𝟑Ø = 𝟐𝟒𝟐 𝑨 REQUIRED SIZE OF RACEWAY

MINIMUM AMPERE 1 - 65 mmØ METALLIC RCP

𝑰𝑴𝑰𝑵𝑰𝑴𝑼𝑴 = 𝟐𝟒𝟐 + (𝟐𝟐)(𝟎. 𝟐𝟓) = 𝟐𝟒𝟕. 𝟓 𝑨 RATING OF FEEDER CB


MAXIMUM AMPERE 600 AT, 1000 AF, 3P, 230V MOLDED CASE TYPE
𝑰𝑴𝑨𝑿𝑰𝑴𝑼𝑴 = 𝟐𝟒𝟐 + (𝟐𝟐)(𝟏. 𝟓) = 𝟐𝟕𝟓 𝑨 SIZE OF GROUNDING
SIZE OF FEEDER CONDUCTOR 1 - 38 𝒎𝒎𝟐 COPPER CONDUCTOR
3 - 200 𝒎𝒎𝟐 THHN COPPER WIRE (AMPACITY = 355 A)
MDP 1 (MAIN DISTRIBUTION PANEL 1)
BRANCH SIZE & TYPE OF
LOAD TOTAL CURRENT CB RATING SIZE OF CONDUIT
CIRCUIT VOLTAGE FEEDER
DESCRIPTION VA
NO. AB BC CA 3Ø AT AF POLE NO. 𝑚𝑚2 TYPE NO. mmØ TYPE
1 LDP 230 146763 212.4 212.5 213.18 500 500 2 2 325 THHN 1 65 RCP
2’ PPEL 230 93840 408 1000 1000 3 6 200 THHN 1 80 RCP
TOTAL 240603 212.4 212.5 213.18 408
3 - 100 mmØ METALLIC RCP

𝑰𝟑Ø = (√𝟑)(𝟐𝟏𝟐. 𝟒 + 𝟐𝟏𝟐. 𝟓 + 𝟐𝟏𝟑. 𝟏𝟖) + 𝟒𝟎𝟖 = 𝟏𝟓𝟏𝟑. 𝟏𝟗 A MAXIMUM AMPERE

MINIMUM AMPACITY 𝑰𝑴𝑨𝑿𝑰𝑴𝑼𝑴 = 𝟏𝟓𝟏𝟑. 𝟏𝟗 + (𝟏)(𝟒𝟎𝟖) = 𝟏𝟗𝟐𝟏. 𝟏𝟗 𝑨

𝑰𝑴𝑰𝑵𝑰𝑴𝑼𝑴 = 𝟏𝟓𝟏𝟑. 𝟏𝟗 + (𝟎. 𝟐𝟓)(𝟒𝟎𝟖) = 1615.19 A RATING OF FEEDER CB

SIZE OF FEEDER CONDUCTOR 4000 AT, 4000 AF, 3P, 230V MOLDED CASE TYPE

5 SETS OF 3 - 400 𝒎𝒎𝟐 THHN COPPER WIRE (AMPACITY = 2575 A) SIZE OF GROUNDING

REQUIRED SIZE OF RACEWAY 1 - 125 𝒎𝒎𝟐 COPPER CONDUCTOR


MDP 2 (MAIN DISTRIBUTION PANEL 2)
BRANCH SIZE & TYPE OF
LOAD TOTAL CURRENT CB RATING SIZE OF CONDUIT
CIRCUIT VOLTAGE FEEDER
DESCRIPTION VA
NO. AB BC CA 3Ø AT AF POLE NO. 𝑚𝑚2 TYPE NO. mmØ TYPE
1 PDPS 230 106517.6 30 29.4 28.86 374.86 1500 1500 3 6 325 THHN 3 65 RCP
2’ PPES 230 55660 242 600 1000 3 3 200 THHN 1 65 RCP
TOTAL 30 29.4 28.86 616.86

𝑰𝟑Ø = (√𝟑)(𝟑𝟎 + 𝟐𝟗. 𝟒 + 𝟐𝟖. 𝟖𝟔) + 𝟔𝟏𝟔. 𝟖𝟔 = 𝟕𝟔𝟗. 𝟕𝟑 A 3 - 80 mmØ METALLIC RCP

MINIMUM AMPACITY MAXIMUM AMPERE

𝑰𝑴𝑰𝑵𝑰𝑴𝑼𝑴 = 𝟕𝟔𝟗. 𝟕𝟑 + (𝟎. 𝟐𝟓)(𝟑𝟕𝟒. 𝟖𝟔) = 863.45 A 𝑰𝑴𝑨𝑿𝑰𝑴𝑼𝑴 = 𝟕𝟔𝟗. 𝟕𝟑 + (𝟏)(𝟑𝟕𝟒. 𝟖𝟔) = 𝟏𝟏𝟒𝟒. 𝟓𝟗 𝑨
RATING OF FEEDER CB
SIZE OF FEEDER CONDUCTOR
2500 AT, 2500 AF, 3P, 230V MOLDED CASE TYPE
3 SETS OF 3 - 400 𝒎𝒎𝟐 THHN COPPER WIRE (AMPACITY = 1545 A)
SIZE OF GROUNDING
REQUIRED SIZE OF RACEWAY
1 - 125 𝒎𝒎𝟐 COPPER CONDUCTOR

Potrebbero piacerti anche