Laboratorio de Sistema de Potencia 1

Tema:
Simulación de los tipos de líneas de transmisión:

NOMBRE ESTUDIANTE: Johnny Daniel Veloz R.

PROFESOR: Ing. Jimmy Córdova

FECHA DE LA PRÁCTICA: 3 de Agosto de 2018

FECHA ENTREGA DEL INFORME: 9 de Agosto de 2018

1T - 2018

1
TABLA DE CONTENIDO:

1. OBJETIVOS ................................................................... Error! Bookmark not defined.

2. MATERIALES DE EQUIPOS UTILIZADOS ............. Error! Bookmark not defined.

3. PROCEDIMIENTO ..................................................................................................... 4

4. DIAGRAMA DE CONECCIONES ............................................................................. 5

5. TABLAS ....................................................................................................................... 6

6. GRAFICOS................................................................................................................... 7

7. CALCULOS .................................................................................................................. 9

8. ANALISIS DE DATOS .............................................................................................. 15

9. CONCLUSIONES ...................................................................................................... 15

10. BIBLIOGRAFIA ...................................................................................................... 16

11. Anexos ………………………………………………………17

2
OBJETIVOS :

• Analizar la relación de voltajes y corrientes de los distintos tipos de líneas de


transmisión.

• Determinar la matriz de transmisión y el circuito equivalente de los diferentes


tipos de línea de transmisión.

• Analizar las gráficas de las líneas de transmisión con carga y sin carga

MATERIALES DE EQUIPOS UTILIZADOS

• Mesa de módulos para simulación de líneas de transmisión


• Cables Punta-gancho
• Variac
• Multímetro
• Gafas
• Guantes dieléctricos Tipo 1
• Reóstato

3
PROCEDIMIENTO:

A) Conexionado para la línea de transmisión corta:

1. Se procede a conecta una bornera a los respectivos módulos en forma lineal o en


serie, es decir de la parte media a la parte final de cada impedancia y luego se hace
un nodo general de las borneras del módulo a la bornera a tierra.

2. Se conecta la mesa de módulos a los voltajes del tablero de control de distribución


a los bornes del primer módulo y procedemos hacer el conexionado sin carga y luego
con carga (R=50 Ω).

3. Finalmente, con el Variac, regulamos el voltaje de envió y empezamos a tomar los


datos de voltaje de cada módulo hasta llegar al final y lo anotamos para simular los
parámetros de transmisión y su respectivo circuito equivalente.

B) Conexionado para la línea de transmisión media:

1. Se procede a conectar los respectivos módulos, pero en esta ocasión conectamos


las admitancias, una 𝑌2 en la parte media de la impedancia en serie, y otra 𝑌2 en la
parte final de cada módulo, y se hace un nodo general de las borneras de cada
módulo a la bornera tierra y queda en forma de Π.

2. Se conecta la mesa de módulos a los voltajes del tablero de control de distribución


a los bornes del primer módulo y procedemos hacer el conexionado sin carga y luego
con carga (R=50 Ω)
.
3. Finalmente, con el Variac, regulamos el voltaje de envió y empezamos a tomar los
datos de voltaje de cada módulo hasta llegar al final, para luego simular los
parámetros de transmisión y su respectivo circuito equivalente.

B) Conexionado para la línea de transmisión larga:

1. Se procede a conectar los respectivos módulos, pero en esta ocasión conectamos


las admitancias, una 𝑌1 en la parte media de la impedancia en serie, y otra 𝑌1 en la
parte final de cada módulo, y se hace un nodo general de las borneras de cada
módulo a la bornera tierra y queda en forma de Π.

2 Se conecta la mesa de módulos a los voltajes del tablero de control de distribución a


los bornes del primer módulo y procedemos hacer el conexionado sin carga y luego
con carga (R=50 Ω).

3. Finalmente, con el Variac, regulamos el voltaje de envió y empezamos a tomar los


datos de voltaje de cada módulo hasta llegar al final, para luego simular los
parámetros de transmisión y su respectivo circuito equivalente.

4
Diagrama de conexiones

Voltaje

Neutro

Fig.1.1 Conexiones para la línea transmisión corta.

Voltaje

Neutro

Fig.1.2 Conexiones para la línea transmisión media.

Voltaje

Neutro

Fig.1.3 Conexiones para la línea transmisión larga.

5
TABLA DE DATOS
LINEA CORTA
Voltaje sin carga [V] Voltaje con carga R=50 Ω [V]
Voltaje Inicial 120.24 120.01
Módulo 1 120.34 115.33
Módulo 2 120.25 110.99
Módulo 3 120.16 107.79
Módulo 4 120.08 105.78
Módulo 5 120.02 104.47
Tabla 1. Datos experimentales para la línea transmisión corta.

LINEA MEDIA
Voltaje sin carga [V] Voltaje con carga R=50 Ω [V]
Voltaje Inicial 120.21 119.82
Módulo 1 123.47 116.97
Módulo 2 126.21 114.59
Módulo 3 128.33 112.18
Módulo 4 129.21 111.09
Módulo 5 129.59 109.77
Tabla 2. Datos experimentales para la línea transmisión media
.

LINEA LARGA
Voltaje sin carga [V] Voltaje con carga R=50 Ω [V]
Voltaje Inicial 120.32 120.68
Módulo 1 120.68 115.76
Módulo 2 121.04 111.31
Módulo 3 121.43 107.82
Módulo 4 121.57 105.75
Módulo 5 121.57 104.63
Tabla 3. Datos experimentales para la línea transmisión larga.

6
Gráficos:

Fig. 1 Línea transmisión corta sin carga

Fig. 2 Línea transmisión corta con carga

Fig. 3 Línea transmisión


7 media sin carga
Fig. 4 Línea transmisión media con carga

Fig. 5 Línea transmisión larga sin carga

Fig. 6 Línea transmisión media con carga


8
CÁLCULOS TEÓRICOS

Datos Globales:

Resistencia=0.5 Ω/km

Inductancia=1.173mH/Km

𝑪𝒚𝟐 = 137 nF

𝑪𝒚𝟏 =961 nF

1. Parámetros para Línea de transmisión Corta


Sin carga:
Datos:
Z = 𝑅 + 𝑗𝑋𝐿 [Ω] ; R = 0.5 [Ω/𝐾𝑚] ; L=1.173 [𝑚𝐻] ; Longitud= 33km

XL = 2 π f L
XL = 2 ∗ π ∗ 6 ∗ 1.173
XL= 0.44221058 [Ω]

Zlinea = Z* L [Ω]
Zlinea = (0.5+j0.44221058) * (33) [Ω]
Zlinea = 16.5 + j14.59 [Ω]

En la línea de transmisión corta la corriente de envió 𝐼𝑠 = 𝐼𝑟 , por lo que no hay ramales


en paralelo, por eso no admitancia en paralelo se desprecia:
𝑍𝑌
A=D= 1+ 2 ; C=0; B= Zlinea
𝐴 𝐵 𝑉𝑟 𝑉𝑠
[ ] ∗ | |=| |
𝐶 𝐷 𝐼𝑟 𝐼𝑠
1 16.5 + j14.59 𝑉𝑟 𝑉𝑠
[ ] ∗ | |=| |
0 1 𝐼𝑟 𝐼𝑠
𝑉𝑠 = 𝑍𝑙𝑖𝑛𝑒𝑎 ∗ 𝐼𝑅 + 𝑉𝑅 [𝑉]
𝑉𝑆 = (16.5 + 𝑗14.59) ∗ (0) + 𝑉𝑅 [𝑉]

Vs = VR [𝑉]
VR = 120.23 [𝑉]

9
Con carga [50 Ω]:
Datos:
Z = 𝑅 + 𝑗𝑋𝐿 [Ω] ; R = 0.5 [Ω/𝐾𝑚] ; L=1.173 [𝑚𝐻] ; Longitud= 33km

Vs = 120.01 ≮ 0̊°[V]
XL = 2 π f L
XL = 2 ∗ π ∗ 6 ∗ 1.173
XL= 0.44221058 [Ω]

Zlinea = Z* L [Ω]
Zlinea = (0.5+j0.44221058) * (33) [Ω]
Zlinea = 16.5 + j14.59 [Ω]
𝑍𝑐𝑎𝑟𝑔𝑎 = 50 [𝛺]
𝑍𝑡𝑜𝑡𝑎𝑙 = 𝑍𝑙𝑖𝑛𝑒𝑎 + 𝑍𝑐𝑎𝑟𝑔𝑎 = 66.5 + 𝑗14.59 [𝛺]

Como no hay ramales en paralelo, por eso no admitancia en paralelo se desprecia:


𝑍𝑌
A=D= 1+ 2 ; C=0; B= Zlinea
A=1; B=Z=16.5 + j14.59 [𝛺] ; C=0 ; D=1

𝐴 𝐵 𝑉𝑟 𝑉𝑠
[ ] ∗ | |=| |
𝐶 𝐷 𝐼𝑟 𝐼𝑠
1 16.5 + j14.59 𝑉𝑟 𝑉𝑠
[ ] ∗ | |=| |
0 1 𝐼𝑟 𝐼𝑠
𝐼𝑠 = 𝐼𝑟

𝑉𝑠 = 𝑉𝑠 + 𝑍𝑡𝑜𝑡𝑎𝑙 ∗ 𝐼𝑠
𝑉𝑠
𝐼𝑠 =
(𝑍𝑡𝑜𝑡𝑎𝑙)
120.01 ≮ 0̊°
𝐼𝑠 =
(66.5 + 𝑗14.59)

𝐼𝑠 = 1.762 ≮ −12.37° [A]

𝑉𝑟 = 𝑉𝑠 − (𝑍𝑙𝑖𝑛𝑒𝑎) ∗ 𝐼𝑟
𝑉𝑟 =86.10≮ −12.37

10
2. Parámetros para Línea de transmisión media
Sin carga:
Datos:
Z = 𝑅 + 𝑗𝑋𝐿 [Ω] ; R = 0.5 [Ω/𝐾𝑚] ; L=1.173 [𝑚𝐻] ; Longitud= 125km

XL = 2 π f L
XL = 2 ∗ π ∗ 6 ∗ 1.173
XL= 0.44221058 [Ω]

Zlinea = Z* L [Ω]
Zlinea = (0.5+j0.44221058) * (125) [Ω]
Zlinea = 62.5 + j55.2763[Ω]

1
Xc = = j19361.915
137nF
2 ∗ π ∗ 60 ∗ Km
1
y = Xc

y = j51.647 ∗ 10−6 [℧/km]

Y =y∗l


Y = j51.647 ∗ 10−6 [ ] ∗ 125[Km] = j0.0064559[℧]
Km
Y
= j0.0032279(℧)
2
𝑍𝑌
A = D = 1+ 2
(62.5 + j55.2763 )∗(𝑗 0.0064559)
A = D = 1+ =0.8217 + j0.2015
2
B=Zlinea = 62.5 + j55.28 [𝛀]
𝑍𝑌
C= Y*(1+ 4 )= −0.000651 + j0.00587
𝐴 𝐵 𝑉𝑟 𝑉𝑠
[ ] ∗ | |=| |
𝐶 𝐷 𝐼𝑟 𝐼𝑠

0.8217 + j0.2015 62.5 + j55.28 𝑉𝑟 𝑉𝑠


[ ] ∗ | |=| |
−0.000651 + j0.00587 0.8217 + j0.2015 𝐼𝑟 𝐼𝑠
Y
Vs = (1 + ZLinea ∗ ) ∗ Vr
2
Vs = 120.21 ≮ 0
Vs
Vr =
A

Vr = 142.09 ≮′ − 13.78°[V]

11
Con Carga:

Usando los mismos parámetros anteriores:

𝐴 𝐵 𝑉𝑟 𝑉𝑠
[ ] ∗ | |=| |
𝐶 𝐷 𝐼𝑟 𝐼𝑠

0.8217 + j0.2015 62.5 + j55.28 𝑉𝑟 𝑉𝑠


[ ] ∗ | |=| |
−0.000651 + j0.00587 0.8217 + j0.2015 𝐼𝑟 𝐼𝑠

Vs = AVr + BIr
Vr
Donde Ir =
Zcarga

𝐵𝑉𝑟
𝑉𝑠 = 𝐴𝑉𝑟 +
𝑍𝑐𝑎𝑟𝑔𝑎

𝐵
𝑉𝑠 = (𝐴 + )𝑉𝑟
𝑍𝑐𝑎𝑟𝑔𝑎

𝑉𝑠
𝑉𝑟 =
𝐵
𝐴+
𝑍𝑐𝑎𝑟𝑔𝑎

119.82 ≮ 0º
𝑉𝑟 =
(62.5 + j55.28)
(0.8217 + j0.2015) +
50

𝑉𝑟 = 48.91 ≮ −32.249°

12
Parámetros para Línea de transmisión alta.
Sin carga:

Z = 𝑅 + 𝑗𝑋𝐿 [Ω] ; R = 0.5 [Ω/𝐾𝑚] ; L=1.173 [𝑚𝐻] ; Longitud= 275km

XL = 2 π f L
XL = 2 ∗ π ∗ 6 ∗ 1.173
XL= 0.44221058 [Ω]

Zp = Z [Ω/𝐾𝑚]
Zp = (0.5+j0.44221058) [Ω/𝐾𝑚]
Zp = 0.6674 ≮ 41.49º [Ω/𝐾𝑚]

1
Xc = 961nF = j2760.2314
2∗π∗60∗
Km
1
Yp =
Xc
Yp = j362.28 ∗ 10−6 [℧/km]
Yp = j362.68 ∗ 10−6 ≮ 90º [℧/km]

ƴL= √Zp ∗ Yp ∗ L
ƴL = 27 √0.6674 ∗ 362.68 ∗ 10−6 ≮⁄(41.49+90) /2
ƴL= 5.36≮65.74º
ƴL= α + β = 2.20 + j4.78

Zp 0.6674
Zc= √ =√ ≮⁄(41.49 −90) /2
Yp 362.68∗10−6

Zc=42.8974≮ − 24. 25º

1
Cosh(ƴL)= (𝑒 α ≮ β + 𝑒 −α ≮- β)
2
1
Cosh(ƴL)= (𝑒 2.20 ≮ 273.89 º + 𝑒 −2.20 ≮- 273.89º)
2
Cosh(ƴL)= 4.5125 ≮ 273.89 º + 0.0554≮-273.89º
Cosh(ƴL)= −0.8451885 + j0.338343335

1
Sinh(ƴL)= (𝑒 α ≮ β - 𝑒 −α ≮- β)
2
1
Sinh(ƴL)= (𝑒 2.20 ≮ 273.89 º - 𝑒 −2.20 ≮- 273.89º)
2
Sinh(ƴL)= 4.5125 ≮ 273.89 º - 0.0554≮-273.89º
Sinh(ƴL) = 4.567 ≮ −86.204º

A=Cosh(ƴL) ; B=Zc ∗ Sinh(ƴL) ; C =1/Zc ∗ (Sinh(ƴL); D=Cosh(ƴL)

13
𝐴 𝐵 𝑉𝑟 𝑉𝑠
[ ] ∗ | |=| |
𝐶 𝐷 𝐼𝑟 𝐼𝑠

−0.8451885 + j0.338343335 195.91 ≮ −110.45 𝑉𝑟 𝑉𝑠


[ ] ∗ | |=| |
−0.001686 + 0.00964𝑗 −0.8451885 + j0.338343335 𝐼𝑟 𝐼𝑠
𝑉𝑠 = 120.32 𝑉 ≮ 0°
𝑉𝑠 = 𝐴𝑉𝑟

𝑉𝑟 = 𝑉𝑠/𝐶𝑜𝑠ℎ(𝛾𝑙)

𝑉𝑟 = 120.32/ ((−0.8451885 + j0.338343335º)

𝑉𝑟 = 134.17 𝑉 ≮ −158.08° [𝑉]

Con carga
𝑉𝑠 = 𝐴𝑉𝑟 + 𝐵𝐼𝑟

Vr
Ir =
Zcarga

𝑉𝑠 = 120.68 𝑉 ≮ 0°

𝐵𝑉𝑟
𝑉𝑠 = 𝐴𝑉𝑟 +
𝑍𝑐𝑎𝑟𝑔𝑎

𝐵
𝑉𝑠 = (𝐴 + )𝑉𝑟
𝑍𝑐𝑎𝑟𝑔𝑎

𝑉𝑠
𝑉𝑟 =
𝐵
𝐴 + 𝑍𝑐𝑎𝑟𝑔𝑎

120.68
𝑉𝑟 =
−3.429 + 𝑗57.995
−0.8451885 + j0.338343335 +
222.5 + 𝑗152.56558

𝑉𝑟 = 137.85 𝑉 ≮ −126.12° [𝑉]

14
ANALISIS DE DATOS

• Nos pudimos dar cuenta en la Fig.1 que las conecciones de la linea de transmision
corta sin carga , tanto como el Voltaje de envio Vs y el Voltaje de resivo Vr son
iguales por lo que se deberia mantener casi constante y tambien por que no hay
ni admitancias en paralelo ni corrientes de envio Is ni corrientes de resivo Ir, por
lo que no caida tension.

• En la linea de transmision corta con carga , Podemos ver Fig.2 que el voltaje de
resivo decae mucho por lo que caida tension en los terminales y esto se debe a
que hay mas perdidas de voltajes de resivo Vr.

• En la linea de transmision media sin carga se puede observar en la Fig. 3 que el


voltaje tiende a aumentar, esto se debe que a que no hay carga ni caida de
tension en los terminales , entonces lo unicos que produce estas subida de voltaje
son las admitancias en paralelo .

• Podemos ver en la Fig.4 que en la transmision media con carga , el voltaje tiende
a decaer , debido a las caídas de tensión en las líneas que existe en la Zserie y
Yparalelo.

• Podemos ver en las Fig.5 que son las líneas de longitud larga sin carga el voltaje
que sale Vs, tiende a subir a medida que recorre por la linea , debido a las Yp que
nos ayudan a inyectar mas voltaje , pero a la final ,llega con el mismo Vinicial ,
eso quiero decir que varia describe pequeña parabola.

• Podemos ver en la Fig.6 que en la transmision media con carga , el voltaje tiende
a decaer , debido a las caídas de tensión , pero para esto existen los Yp que nos
ayudan a regular el voltaje y compensar dichas perdidas de energia que se
pierden en el camino.

. CONCLUSIONES

• Antes de todos, revisar tener los equipos de proteccion electrica a la mano, para
no sufrir calamidades ni daños al momento de energizar la mesa de simulacion.
• Al momento de hacer cambios en la mesa, debemos apagar el panel de control el
breaker y asi cuando ya hallamos terminado de hacer los cambios, podemos
energizar la mesa.
• Se pudo realizar las simulaciónes de los distintos tipos de líneas de transmision ,
para asi poder determinar los parámetros y ver los voltajes de envio y de resivo
como varian con respecto a la distancia y a la configuración que se conectan .
• Cuando las líneas se conectan a una carga, la diferencia de potencial llegan a un
punto máximo y por ende empiezan a decrecer.
• Cuando ingresan las admitancias en las distintas configuraciones de los sistemas,
estos ayudan a compensar el voltaje de envío y entregan reactivos, para asi
regular el voltaje inyectado a la red .
• Pudimos descubrir para cada instante de módulos los valores de tensión, a una
distancia del origen para así comprobar que la progresión de los parámetros.
15
BIBLIOGRAFIA

✓ Stevenson, W. D., & Grainger, J. Análisis de sistemas de potencia. Mexico :


McGraw-Hill.

✓ Gonen, T. Modern Power System Analysis . New York: CRC Press.

16
ANEXOS:
Codigo de Matlab de las graficas de cada linea de transmision
figure(1)
close all
clc;
Modules=[0 1 2 3 4 5];
Vres=[120.24 120.21 120.20 120.16 120.08 120.02];
plot(Modules,Vres,'b')
xlim ([ 1 5])
ylim ([120.2 120.5])
xlabel('Distancia[Km]')
ylabel('Voltaje [V]')
title('Línea de transmisión Corta Sin Carga')
grid
hold on

figure(2)

Modules=[0 1 2 3 4 5];
Vres=[120.01 115.33 110.99 107.79 105.78 104.47];
plot(Modules,Vres,'b')
xlabel('Distancia[Km]')
ylabel('Voltaje [V]')
title('Línea de transmisión Corta Con Carga')
grid
hold on

figure(3)

Modules=[0 1 2 3 4 5];
Vres=[120.21 123.47 126.21 128.33 129.21 129.59];
plot(Modules,Vres,'b')
xlabel('Distancia[Km]')
ylabel('Voltaje [V]')
title('Línea de transmisión Media Sin Carga')
grid
hold on

figure(4)

Modules=[0 1 2 3 4 5];
Vres=[119.82 116.97 114.59 112.18 111.09 109.77];
plot(Modules,Vres,'b')
xlabel('Distancia[Km]')
ylabel('Voltaje [V]')
title('Línea Media Con Carga')
grid
hold on

figure(5)
Modules=[0 1 2 3 4 5];
Vres=[120.32 120.68 121.04 121.43 121.57 121.57];
plot(Modules,Vres,'b')
xlabel('Distancia[Km]')
ylabel('Voltaje [V]')
title('Linea de transmisión Larga Sin Carga')
grid
hold on

figure(6)
Modules=[0 1 2 3 4 5];
Vres=[120.68 115.76 111.31 107.82 105.75 104.63];
plot(Modules,Vres,'b')
xlabel('Distancia[Km]')
ylabel('Voltaje [V]')
title('Línea de transmisión Larga Con Carga')
grid
hold on