1. Basic Data
1.1 The description
We would like to use the reinforced concrete pipe(NP3 900mm ) as the service duct embedded under the DK0+037 level
crossing to cross through the water pipes, electrical line, telecom line at the captioned level crossing.
According to the formula mentioned in the BS-EN-1295 NA.4.1, the Soil Load Wc should be calculated as the follow:
W'c=Cc x x Bc2 1)
Where:
W'c - The soil load per unit length of pipe in embankment and wide trench conditions.
Cc - The soil load coefficient in embankment condition.
- Unit weight of soil
Bc - Outside diameter of the pipe.
Cc= 1 2)
Cc= +( 3)
As per the indication in the BS-EN-1295-1998 Clouse NA.4.3.1 the soil properties
The value of the Ku = 0.19
The value of the = 19.6 Kn/m3
Further
Scenario 1
Assume the cover depth to top of the pipe is H1= 1.5 m actual 1.69m
According to the pipe testing report, the pipe's outside diameter is
Bc= 0.96 m
0.8m+0.08+0.08
1
Cc1= = 2.13 1a
By using the formula 3, as per indicated in the BS-EN-1295 Clouse NA.4.1.1, the Cc can be obtained from the table NA.2
as shown below
As shown in the table NA.2, the Cc equation is determined by the combination value of rsd and p
Where:
rsd-Settlement deflection ratio
p- Projection ratio
As per the indication in the BS-EN-1295 mentioned in NA.4.3.3, the recommended combination value of rsd and p is 0.7
Hence
After comparing the Cc values from the formula 2 and 3, the lower value is taken
Cc1= 2.13
As per the indication in the BS-EN-1295 Clouse NA.4.1.4, the value of the Ps can be obtained from the figure NA.6.
Where:
Fm-Bedding Factor
Fse-The safety factor for rigid pipe material (External load design)
Wt-Crushing strength of rigid pipe (Maximum load for concrete pipe)
According to the table NA.5 Minimum safety factor of Fse and Fsi as shown below:
According to the pipe testing report, the Maximum load applied of the NP3 pipe is 85.1 Kn/m
Wt= 85.1 Kn/m
By using formula 8
The bedding type can be obtained by check the table NA.7 Rigid Pipe Embeddments as shown below, for the secnario1, the Fm
values are 1.84, the embedment type are "B". Based on the BS-EN-1295 and Design Manual for Roads and Bridges Volume 4
Section 2, the sketch of the rigid pipe bedding.
The relevant pipe bedding drawing please refer to the attachment