Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
injections inside R. The reduced network is the same as It follows from (2) that
the area R with respect to the border buses, so there is no
change in the electrical properties. Pab = 1
into
+ PaR ) − (Pbinto + PbR )
2 (Pa (3)
into
In the reduced network, the border buses Ma are connected = 1
2 (Pa − Pbinto ) + 12 (PaR − PbR ) (4)
to the border buses Mb by equivalent lines. Since removing
these equivalent lines separates the buses Ma from the Mb , Equation (3) relates Pab to the difference of the power flows
these equivalent lines form a cutset of the reduced network, injected at buses Ma and Mb . Equation (4) splits Pab into
and we can apply the cutset angle concept of [1] to define two parts. One part is related to the difference of the ex-
the angle θ̂ab across the cutset. The cutset angle θ̂ab obeys ternal power flows injected at buses Ma and Mb . The other
circuit laws and can be understood as the angle across an part is related to the difference of the power flows equivalent
equivalent single line joining bus a to bus b. Bus a corre- to the power flows internal to area R.
sponds to the set of buses Ma and bus b corresponds to the
set of buses Mb . Following through this reduction process Painto + PaR
in Figure 1, we see that the angle θ̂ab is the angle across
the area R from the Ma buses to the Mb buses. We can
also use the equivalent quantities of the single line to de-
a θ̂ab is angle across line.
fine the susceptance bab of the area R and the equivalent
power flow Pab through the area R. Since circuit laws apply bab is line susceptance.
throughout the reduction, we have
Pbinto + PbR
R
The area angle θ̂ab is a weighted linear combination of the stress on area R. In particular, θ̂ab only depends on the
border bus angles θm : power injections inside area R and the lines in service in-
side R.
θ̂ab = w θm = w1 θm1 + w2 θm2 + · · · + wnb θmnb . (6)
R
Now we discuss how the internal stress angle θ̂ab can be
The weights in the row vector w are determined by the obtained from phasor measurements. We assume that the
susceptances of lines in service in R using a DC load flow lines in service inside R are known so that the area sus-
model of R (see (48)). Therefore, if we place phasor angle ceptance bab can be calculated. The power flowing into a
measurements at all the border buses of R and know the bus can be determined from phasor measurements if the
status of lines in R, we can easily determine the angle θ̂ab currents in the tie lines and the bus voltage are both mea-
across the area R. The area susceptance bab is also easy to sured. If the external tie line power entering each bus in Ma
evaluate given the DC load flow model of R and the status is known from these measurements, these can be summed
of the lines. to obtain the total power Painto entering into the area R
through Ma . The total power Pbinto entering into the area
Combining (1) and (3) gives
R through Mb can be obtained similarly. Then we can de-
into R
1 into termine θ̂ab using (10) and then determine θ̂ab using
(Pa + PaR ) − (Pbinto + PbR )
θ̂ab = (7)
2bab
R into
θ̂ab = θ̂ab − θ̂ab . (12)
That is, the area angle θ̂ab results from the difference in
the powers injected at the Ma border buses and the powers
injected at the Mb border buses. In terms of the single line Changes ∆θ̂ab R
in the internal stress angle can be related to
equivalent shown in Figure 2, θ̂ab arises from the difference changes inside the area R such as line outages. In particu-
in the powers injected at the a bus and the powers injected R
lar, ∆θ̂ab is proportional to the pre-outage power flow and
at the b bus. angle on the line. If it is known by other methods which
line inside R has outaged, then the angle across the line
Combining (1) and (4) gives
after the line is outaged is given by
Painto − Pbinto P R − PbR
θ̂ab = + a (8) bab
2bab 2bab θ̂kafter = R
∆θ̂ab . (13)
into R
bk ρ R
abrs
= θ̂ab + θ̂ab (9)
line to outage
+100MW
-100MW +100MW
line to outage
R
Various angles and flows are shown in Table 1 for the base
case and for some examples of transfers and line outages.
Fig. 3: Area R shown as the black buses for a 225 bus The transfers and line outages are shown in Figure 4. The
model of the Western USA. Gray buses are outside area base case area stress is θ̂ab = 10.85 degree and the equiva-
R. The border buses with phasor measurements are the lent power flow west through the area is Pab = 1734 MW.
labelled black triangles. The area susceptance is bab = 91.62 per unit on a 100 MW
base. The transfer inside area R increases the westward
power flow and increases the stress θ̂ab . The transfer out-
side area R also increases the westward power flow and the
2.3 A simple example of an area and its angles stress θ̂ab . Both of the line outages also increase the overall
stress on area R.
We illustrate the concepts using the model of the WECC
system shown in Figure 3. The model has 225 buses and The area stress can be decomposed into external and inter-
into R
is a reduced representation of the higher voltage WECC nal stress as θ̂ab = θ̂ab + θ̂ab . All the changes affect the
into
transmission system. The network layout is roughly geo- power flows into area R and the external stress θ̂ab . How-
graphic so that Canadian buses are at the top, Southern ever, it can be seen from Table 1 that the internal stress
R
California is at the bottom left and New Mexico is at the θ̂ab only changes when the transfer or line outage is inside
lower right. area R.
We choose the area R that includes the black buses When the line inside area R outages, the internal stress
R
shown in Figure 3 as a simple example. The three angle θ̂ab increases from 1.070 degrees to 3.702 degrees, so
R
border buses labelled by black triangles are Ma = that ∆θ̂ab = 2.632 degrees. Then evaluating (13) shows
{ELDORADO, PALOVRDE} and Mb = {VINCENT}. For that the angle across the outaged line after the outage is
the purpose of illustration, we assume phasor measurements θ̂kafter = 21.49 degrees. This information is useful in deter-
at the three border buses. mining whether the line can be safely reclosed.
a
Ma
R1 R3
Mb Mc
R2 c
b
Fig. 5: Reduction of a three area power system to a three node equivalent
Area angles can be applied to several areas in a power sys- Tate and Overbye [9] give an algorithm for detecting which
tem. For example, consider the power system with the lines have outaged using phasor measurements. Their anal-
three areas R1 , R2 , R3 shown in the left hand of Figure 5. ysis also exploits, among other methods, the standard net-
Border buses are shown as black dots. Areas R1 and R2 work reduction of DC load flow and participation factors
have border buses Mb in common, areas R2 and R3 have to represent line outages. Tate and Overbye [9] should also
border buses Mc in common, and areas R3 and R1 have be read for more information about the signal processing of
border buses Ma in common. Although two border buses the phasor measurements and the practical availability of
are shown in Figure 5 for each common border, there could the DC load flow models since these useful topics are not
be any number of border buses on each common border. treated in this paper.
We can proceed with the network reduction process for all Previous work by others on monitoring power system stress
three areas at once. The first step is to replace each area by with phasor measurements has focused on the angle differ-
an equivalent network joining the border buses and with ad- ence between two buses. Simulations of the grid before the
ditional power injections at each border bus that are equiv- August 2003 Northeastern blackout show increasing angle
alent to the power injections inside the area. The result differences between Cleveland and West Michigan, suggest-
of the first step is shown in the middle of Figure 5. The ing that large angle differences could be a blackout risk pre-
second step is to apply the cutset angle concept to each of cursor [4]. A recent simulation study [8] of potential pha-
the equivalent subnetworks to define the area angles θ̂ab , sor measurements on the 39 bus New England test system
θ̂bc , θ̂ca , the area susceptances bab , bbc , bca , and the power shows that, of several phasor measurements, angle differ-
flows Pab , Pbc , Pca . The effect is to reduce the three area ences were the best in discriminating alert and emergency
power system to the three bus power system shown in the states. A large angle difference between two buses does
right hand of Figure 5. indicate, in some general sense, a stressed power system.
However, this angle difference it is generally affected by
Area angles are applied to multiple cutset areas of a power changes throughout the entire grid, and it is difficult to in-
system in [2]. terpret the reason for changes in the angle difference or set
thresholds. The angle across an area is a generalization of
the angle difference between two buses (see subsection 5.5)
3 Previous work and gives specific information about the area.
A cutset of lines is a set of lines that cuts the Consider the example network in Figure 6 with buses 1,2,3
network into separate networks when that set of in Ma and buses 4,5 in Mb . The buses in Ma are separated
lines is removed from the network. from the buses in Mb by the cutset of lines 1,2,3,4,5,6 that
is indicated by the dashed line. Write θi for the voltage
angle at bus number i and θ̂j for the angle difference across
Let θ be the vector of bus angles and P be the vector of
line number j. The susceptance of line number j is bj .
bus power injections. The DC load flow equations of the
base case grid are The power flowing from Ma to Mb along line j of the cutset
P = Bθ (15) is bj θ̂j . For this illustration, it is convenient to assume that
where the angle difference θ̂j on line j is defined so that θ̂j is
B = AΛAT (16) positive for positive power flowing on line j from Ma to
and Λ is the diagonal matrix of line susceptances Mb . The power Pab flowing through the cutset is the sum
of the powers flowing in each line of the cutset:
Λ = diag{b1 , b2 , · · · , bnline }
Pab = b1 θ̂1 + b2 θ̂2 + b3 θ̂3 + b4 θ̂4 + b5 θ̂5 + b6 θ̂6 . (19)
and A is the incidence matrix
The cutset susceptance is
1
bus i is sending bus of line j
Aij = −1 bus i is receiving bus of line j (17) bab = b1 + b2 + b3 + b4 + b5 + b6 . (20)
0 otherwise.
Following [1], we define the angle across the cutset as
The transpose of the incidence matrix A relates the bus b1 b2 b3 b4 b5 b6
θ̂ab = θ̂1 + θ̂2 + θ̂3 + θ̂4 + θ̂5 + θ̂6 , (21)
angles θ to the line angle differences θ̂: bab bab bab bab bab bab
θ̂ = AT θ (18) which is a linear combination of the cutset line angle differ-
ences, weighted according to the line susceptances. Then
To streamline the notation, we often do not indicate the (19), (20), and (21) imply that
length of a row or column vector and this length must be Pab = bab θ̂ab , (22)
deduced from the context.
which expresses the power flowing through the cutset as the
product of the cutset susceptance and the angle across the
4.2 Angle across a cutset cutset. Equation (21) can be rewritten in terms of the bus
angles as
We derive the angle across a cutset in an example to briefly
b1 + b2 b3 + b4 b5 + b6
explain the concept and establish notation. A more thor- θ̂ab = θ1 + θ2 + θ3
ough explanation of cutset angle can be found in [1]. bab bab bab
1 Some authors define a cutset to be a minimal set of buses or lines
b1 + b3 + b5 b2 + b4 + b6
− θ4 − θ5 (23)
that separate the network, but we do not require this here. bab bab
For practical calculations, it is better to use vector and that a “North to South” angle across an area is different
matrix notation. The buses 1,2,3 in Ma are defined by the than an “East to West” angle across the area.
ones in
σa = (1, 1, 1, 0, 0) (24) We will assume phasor measurements at all the border
buses M . Some of the buses in N may also have phasor
The bus angles are measurements, but we will not make use of them.
θm = (θ1 , θ2 , θ3 , θ4 , θ5 )T (25) The row vector σr defines the buses in R by
eq
Let Bmm be the 5 × 5 susceptance matrix of the network
(
eq
1 bus i in R
in Figure 6. The entries of the first 3 rows of Bmm are σri = (28)
0 bus i not in R.
b1 + b2 + b7 −b7 0 −b1 −b2
Then the lines that join R to the rest of the network are
−b7 b3 + b4 + b7 + b8 −b8 −b3 −b4
indicated by the row vector
0 −b 8 b5 + b 6 + b8 −b5 −b6
. . . . . cr = σr A (29)
. . . . .
Since R is a proper subnetwork, the lines joining R to the
Now it can be easily verified that (20) can be written as rest of the network form a cutset. And
eq
bab = σa Bmm σaT (26) 1
line j in cutset has sending bus in R
crj = −1 line j in cutset has receiving bus in R (30)
and (23) can be written as
0 line j not in cutset.
eq
σa Bmm θm
θ̂ab = . (27)
bab Write Am for the rows of A corresponding to the buses in
M . Define the matrix τ by
4.3 Angle between sets of buses and across an area τmr = Am ⊗ |cr | (31)
where ⊗ is element by element multiplication of each row
We explain how to obtain the angle θ̂ab between a set of
of Am with the row vector |cr |. |cr | is the row vector of
buses Ma and set of buses Mb and across an area or region
absolute values of the components of cr .
R of the network. We will also define the power flow Pab
from Ma to Mb through the area and the susceptance bab of Then
the area from Ma to Mb . The sets Ma and Mb areSassumed
to have no buses in common. We write M = Ma Mb . M
1 bus i in M is the sending bus of line j
will be the border buses of area R. joining bus i to a bus not in R
−1 bus i in M is the receiving bus of line j
We assume that the border buses M are a nodal cutset. τmrij =
joining bus i to a bus not in R
0 bus i in M not joined by line j
This assumption formalizes the concept that the M is all
to a bus not in R
the buses along the border of the area R to be chosen below.
The assumption that M is a nodal cutset holds throughout (32)
the paper, except that section 5.5 briefly considers the case
that M is not a nodal cutset. Since M is a nodal cutset, Each bus i that is a border bus in M has lines not in R
if the buses in M are removed from network, then the re- entering bus i. We write Piinto for the total power entering
into
maining network has several connected components, each into bus i along all the lines not in R. We write Pm =
into
of which is a proper subset of the network. One of these {Pi , i ∈ M } for the column vector of powers entering
connected components N is chosen and augmented with into buses in M along the lines not in R. Then
Sthe
buses in M to form the area or subnetwork R = M N . into
Pm = −τmr ΛAT θ. (33)
The buses in M are called the border buses for the area
R, and the buses in N are called the interior buses of R. We write Pm for the vector of powers injected at the buses
The quantities θ̂ab , Pab , and bab will be defined across or in M due to load or generation at these buses. Then the
through the area R from the border buses Ma to the border combined effect of the lines outside R and any load or gener-
buses Mb . ation at the border buses in M is given by power injections
into
of Pm + Pm at the border buses.
For a given area R with border buses M , there are usually
multiple ways to divide the border buses into the buses It is now convenient to focus on the subnetwork R. The
into
Ma and Mb . Each choice of Ma and Mb gives different power injections Pm at the border buses account for the
quantities θab , Pab , and bab . For example, it is reasonable effect of the rest of the network on area R.
The next step is to reduce area R to an equivalent network. The angle across the cutset will be the area angle, the sus-
The border buses M are retained and the interior buses N ceptance of the cutset will be the area susceptance and
are equivalenced out. Write column vectors θm and Pm for the power flow through the cutset will be the power flow
the angle and power injected at the border buses and θn through the area from Ma to Mb . This applies the cutset
and Pn for the angle and power injected at buses N inside angle concept indicated in section 4.2.
the area R. Order the buses in R so that the border buses
come first. Then The row vector σa defines the buses in Ma by
into (
θm Pm + Pm 1 bus i in Ma
θr = and Pr = . σai = (40)
θn Pn
0 otherwise
Then the DC load flow equations for area R are
Define the equivalent power flow Pab through area R from
Ma to Mb as the cutset power flow
into R
Pm + Pm θm Bmm Bmn θm
= BR = .
Pn θn Bnm Bnn θn eq into R
(34) Pab = σa Pm = σa (Pm + Pm ) = Painto + PaR , (41)
Here B R is the susceptance matrix for the subnetwork R.
where the total power flowing into Ma from lines outside R
(Note that B R is not identical to the submatrix Brr of the
R is
susceptance matrix B for the entire network. Bmm is the
R
submatrix of B corresponding to the buses in M . The Painto = σa Pm
into
(42)
R
diagonal entries of Bmm are different than the submatrix and the total power injected into Ma that accounts for
Bmm of the susceptance matrix B for the entire network, power injections in buses of R is
because they do not include the susceptances of the lines
outside R that are joined to buses in M .) PaR = σa Pm
R
(43)
Eliminating θn from (34) in the usual way gives Define the susceptance bab of area R from Ma to Mb as the
cutset susceptance
into −1 R −1
Pm + Pm − Bmn Bnn Pn = (Bmm − Bmn Bnn Bnm ) θm
eq
bab = σa Bmm σaT (44)
and, letting
eq into −1 Define the angle θ̂ab across area R from Ma to Mb as the
Pm = Pm + Pm − Bmn Bnn Pn (35)
the cutset angle
and eq
σa Bmm θm
θ̂ab = eq (45)
eq
Bmm R
= Bmm −1
− Bmn Bnn Bnm , (36) σa Bmm σaT
eq
σa Bmm θm
= (46)
we obtain a reduced grid electrically equivalent to R with bab
the DC load flow equations = w θm , (47)
eq eq
Pm = Bmm θm . (37) where the row vector of weights is
The reduced grid electrically equivalent to R is the border eq
σa Bmm
buses M joined by equivalent transmission lines and with w= . (48)
bab
additional power injections.
Then
eq
From (35), the equivalent power injections Pm at buses in eq
M have two parts eq eq σa Bmm θm
Pab = σa Pm = σa Bmm θm = bab = bab θ̂ab (49)
bab
eq into R
Pm = Pm + Pm , (38)
where Pminto
is the external powers entering into buses in M It is important to note that Bnn only depends on the net-
T
from lines outside R and work in the interior of R. Bnm = Bmn only depends on the
eq
lines connecting M to the interior of R. Therefore Bmm
R −1 only depends on lines in R. It follows that bab only depends
Pm = Pm − Bmn Bnn Pn (39)
on the lines in service in R and that θ̂ab only depends on
is the internal powers entering into buses in M that account the lines in service in R and the border bus angles θm .
for power injections in buses at R.
Given the status of lines within R, one can compute the
The reduced network has the border buses Ma separated susceptance bab of R. If the border bus angles θm are also
from the border buses Mb by a cutset of equivalent lines. measured, then one can compute the angle θ̂ab across R.
4.4 Internal and external area power flows and angles The standard property 1B R = 0 implies 1Bmn +1Bnn = 0.
Therefore
The total power entering into R through the buses in Ma −1
is 1PmR = 1(Pm − Bmn Bnn Pn ) = 1Pm + 1Pn = −P into .
(60)
Painto = σa Pm
into
= −σa τmr ΛAT θ (50)
Another way to express the total power Painto entering into Hence
R through the buses in Ma is to define the lines entering R
P into = −1Pm
R R
= −(σa + σb )Pm = −PaR − PbR . (61)
through buses in Ma with a row vector ca with
In summary,
1
line j has sending bus in Ma
and receiving bus not in R P into = Painto + Pbinto = −PaR − PbR .
(62)
−1 line j has receiving bus in Ma
caj = (51)
and sending bus not in R
From (41), and using (62),
0 line j does not have a bus in Ma
or line j has one bus in N . Pab = Painto + PaR
Pba = −Pab (57) We recall, based on [11], the modeling of line outages with
power injections and the standard line outage distribution
factors. It is convenient to write ek for the column vector of
We state several formulas for the total power P into entering all zeros except that the kth component is one. The length
into area R. By definition, of the vector ek varies with context.
P into = 1Pm
into into
= (σa + σb )Pm = Painto + Pbinto (58) The power transfer distribution factor ρkrs is the increase
into in power flow in line k joining u to v due to a unit injection
Moreover, since M is a nodal cutset, the total power P
of power at bus r and a unit decrement of power injected
entering into area R is also the total power consumed inside
at bus s:
R:
Pm ρkrs = eTk ΛAT B −1 (er − es )
into
P = −1 (59)
Pn = bk (eTu − eTv )B −1 (er − es ) (67)
Suppose line k joining bus r to bus s has power flow Pkline . can be computed as the change in PaR due to a unit in-
Assume that the outage of line k does not island the net- jection of power at bus r and a unit decrement of power
work. Then the effect of outage of line k on the rest of the injected at bus s. That is, from (43) and (39),
network is equivalent to preserving the network structure
and injecting power Pkoutage at bus r and injecting −Pkoutage ρR
abrs = f (r) − f (s) (75)
at bus s, where
where
Pkline
Pkoutage = (68) −1
1 − ρkrs
−σa Bmn Bnn er , bus r in N
1 bus r in Ma
The power flow on the line k after the power injections is f (r) = (76)
0 bus r in Mb
Pkline +ρkrs Pkoutage = Pkoutage , and it is this fact that implies
0 bus r not in R
that the injections have the same effect on the rest of the
network as outaging line k [11]. It also follows that the
angle across line k after it is outaged is ρR
abrs only depends on the area R.
Pkoutage θ̂k The case of islanding and the case in which one of the buses
θ̂kafter = = , (69) r and s is in R and the other bus is not in R are not treated
bk 1 − ρkrs
here.
where θ̂k is the angle across line k before it outaged.
5.3 Monitoring line outages
5.2 Effect of power transfers on area angle
The objective is to monitor line outages by changes in the
Consider the power transfer in which power P inject
is in- angles across area R and changes in power Painto entering
jected at bus r and −P inject is injected at bus s. This power into area R. It is necessary that the status of lines in R
transfer may be an actual power transfer or may represent before the line outage is known. (The line status is required
eq
the effect of a line outage. so that Bmm can be evaluated.)
It is useful to generalize power transfer distribution fac- There is an important choice to be made when using area
tors to the incremental effect of the transfer on the internal angles to monitor line outages. When the line outage occurs
power flow 12 (PaR − PbR ) across the area (see (63)). In par- inside area R, the bus angles and line power flows change
ticular, define the power transfer distribution factor ρR throughout the network and the line status changes inside
abrs
to be the change in 21 (PaR − PbR ) due to a unit injection of R. The change in line status implies that the definitions of
power at bus r and a unit decrement of power injected at area angles, susceptances, power flows, and power transfer
bus s. Let ∆Painto and ∆Pbinto be the respective changes in distribution factors all change. That is, when the line out-
Painto and Pbinto due to the transfer. Then age occurs, both the bus angles and line power flows change
and the definitions of the area quantities we are using to
∆Pab = 21 (∆Painto − ∆Pbinto ) + ρR
abrs P
inject
(70) monitor the system change. One can either monitor the
system after the line outage using the old area quantities
We consider the cases in which either buses r and s are both that apply before the line outage, or one can update the def-
in R or are both outside R. Then the total power entering initions of the area quantities and monitor the system using
into R does not change, so that ∆P into = 0. It follows from the new area quantities after the line outage. A disadvan-
(62) that tage of updating the definitions of the area quantities when
the line outage occurs is that one needs to know which line
∆Painto = −∆Pbinto (71)
outaged to calculate the new definitions. In this paper we
and choose to monitor the system after the line outage occurs
using the old area quantities that were defined before the
∆PaR = −∆PbR . (72) line outage. (In a more developed application of the area
angles, one could make this same choice retaining the old
Then area quantities just after the line outage occurs for the pur-
pose of detecting and quantifying the line outage, and then
∆Pab = ∆Painto + ∆PaR = ∆Painto + ρR
abrs P
inject
(73)
update the definitions to reflect the line outage after the
A formula for ∆Painto is line outaged is identified in order to be better positioned
for further line outages.)
∆Painto = −ca ΛAT B −1 (er − es )P inject , (74)
We make phasor measurements at the border buses in M
but our intention is to determine ∆Painto from phasor mea- of the angles θm and the powers Pminto
entering into the
surements. Moreover, since 21 (∆PaR − ∆PbR ) = ∆PaR , ρR
abrs border buses. Then, given a DC load flow model of R, we
can compute θ̂ab , bab , Painto , and Pbinto . We monitor the 5.4 Cutset areas and areas with Ma or Mb a cutset
changes in these quantities and compute the change in the
internal area angle A useful special case is that the buses in M contain two
nodal cutsets and in particular that the buses Ma is one
R ∆Painto − ∆Pbinto
∆θ̂ab = ∆θ̂ab − (77) nodal cutset and Mb is another nodal cutset. Then the
2bab area between Ma and Mb is called a cutset area [2]. In this
R
and monitor the changes ∆θ̂ab . In some cases, only one of subsection, we consider a case slightly more general than a
into
∆Pa and ∆Pb into
need be monitored. cutset area in which at least one of Ma or Mb is a nodal
cutset. Without loss of generality, suppose that Ma is a
Suppose that the power system is not islanded by the line nodal cutset. We continue to assume that M is a nodal
outage. In this case, the effect of the outage of line k is cutset.
equivalent to retaining the current line statuses and inject-
ing powers ±Pkoutage determined by (68) at the ends of the If Ma is a nodal cutset, there is a nice simplification for
line. Then, if the outaged line has no buses in R, the power monitoring line outages. Suppose that the line buses are
injections inside R do not change and both in R or are both outside R. Then the equal and op-
posite power injections representing the effect of the line
R outage do not change total power entering into R, so that
∆θ̂ab = 0. (78)
∆P into = 0. Moreover, since Ma is a nodal cutset, the total
On the other hand, if the outaged line is within R, then power entering Ma does not change so that ∆Painto = 0.
Then we can use (62) and ∆P into = 0 to deduce that
R ∆PaR
∆θ̂ab = (79) ∆Pbinto = 0. Thus ∆Painto = ∆Pbinto = ∆P into = 0 and the
bab change in the external area stress always vanishes. Then
outage
ρR
abrs Pk the phasor measurements of the current or powers entering
= (80)
bab the area are not needed to monitor the line outages with
ρR changes in the stress angle. Several examples of monitoring
= abrs
P line (81) a cutset area in this way are given in [2].
bab (1 − ρkrs ) k
bk ρRabrs
= θ̂k (82)
bab (1 − ρkrs ) 5.5 Border buses not a cutset
bk ρRabrs after
= θ̂k (83) All of the paper, except this subsection, assumes that the
bab
border buses M are a nodal cutset. If the border buses M
R are not a nodal cutset, then Section 4 applies with minor
Equations (81) and (82) show that θ̂ab is proportional to
line modifications and in particular one can still define the angle
the power flow Pk through the line before the outage and
the angle θ̂k across the line before the outage. Equation between Ma and Mb across the area R. However, following
(83) shows that θ̂abR
is proportional to angle θ̂kafter across the procedure in subsection 4.3, the area R is necessarily
the line after the outage. Rearranging (83) gives the entire network. There are no external powers entering
into R
the network, so θ̂ab = 0 and θ̂ab = θ̂ab . We speculate
bab that having the area R be the entire network does not seem
θ̂kafter = R
∆θ̂ab (84)
bk ρ R
abrs advantageous for applications to large power grids because
the specificity of the area is lost.
If it is known which line outaged so that bk ρR abrs can be
after
calculated, (84) determines the angle θ̂k across the line One extreme example of both a cutset area (see [2]) and a
after the outage from the phasor measurements. case with M not a nodal cutset can often arise in the case of
Ma a single bus and Mb a single bus. In this case, the angle
In this section, we analyze the simplest case of line outages θ̂ab across the entire network is simply the angle difference
in which the line buses are either both in R or both not in R between the two buses.
and in which the line outage does not cause islanding. If the
line outage islands the power system, any power redispatch
caused by the islanding should be taken into account. We 5.6 Area angles with other network variables
expect that the methods of the paper can be extended to
this case as long as the redispatch of the power imbalance The ingredients required to get area angles, power flows,
caused by the islanding is specified. It is not essential to and susceptances to work are an “across” circuit quantity
analyze the case of line trips in which one of the line buses (angle difference), a “through” circuit quantity (power flow)
is a border bus and the other bus is outside area R. Our and an admittance-like quantity (susceptance), that are re-
proposed monitoring already measures the current or power lated together by an Ohm’s law such as (1). For developing
flowing in such lines and the line outage can be directly applications of area angles such as model reduction, it is
detected from these measurements. important to note that one can substitute into the circuit
theory derivations of this paper any three corresponding reduction. It is easy to define other circuit quantities re-
across, through and admittance network quantities and all lated to areas such as the complex phasor voltage across
the statements remain valid. an area and the complex admittance of an area since the
theory is exactly parallel and can be obtained by simply
For example, let the “across” circuit quantity be the com- substituting corresponding variables.
plex phasor voltage difference V , the “through” circuit
quantity be complex current I, and the admittance-like One disadvantage of the area angles is that a DC load flow
quantity be complex admittance Y . The DC load flow equa- model of the area and a knowledge or assumption of the
tions (15) are rewritten as I = Y V . Then, in an exactly line status in the area is required. The DC load flow ap-
similar way as (14) we can define the complex voltage pha- proximation is expected to be practical, but has only been
sor V̂ab across area R as a weighted average of the complex tested against AC load flow results for the special case of
phasor voltages at the border buses: cutset area angles [2]. It is an open question what level of
y1 y2 network detail in the DC load flow model is needed. It is
V̂ab = VELDORADO + VPALOVRDE − VVINCENT possible that measurements at border buses only connected
yab yab
to high impedance or low voltage lines may be neglected,
where y1 and y2 are the complex admittances of the 2 lines but this has not yet been determined.
in the cutset separating Ma = {ELDORADO, PALOVRDE}
from Mb = {VINCENT} in the reduced network of the 3 The area angles respond to line outages and larger changes
border buses. The complex admittance of the area is yab = in area angles correspond to outages of lines with larger
y1 + y2 . Moreover, power flows in accordance with circuit laws. The area an-
gles also respond proportionally to power redispatches. It
Iab = yab V̂ab , (85) is useful that the internal area stress angle does not re-
spond to line outages and power redispatches outside the
where Iab is the effective phasor current through the area. area. Changes in the internal stress angle across the area
can detect line outages inside the area. If, in addition, it is
known which line is outaged, then the angle across the out-
6 Conclusions aged line after it outages can be computed from the change
in the internal stress angle. This could be helpful in as-
We define new angles across a power system area to be able sessing whether it safe to reclose the line. We suggest that
to monitor the total stress of the area, as well as the parts the method of Tate and Overbye [9] could be used to de-
of the stress that are related to the power flows internal termine which line in the area is outaged. The monitoring
and external to the area. The new angles can be easily cal- of line outages in an area simplifies if the area is a cutset
culated from phasor measurements at all the buses along area, because then only the border bus voltages, and not
the border of the area using a DC load flow model of the any currents, need to be monitored.
area and knowledge of which lines in the area are in service.
The new angles generalize the cutset area angles of [1, 2] The paper shows the valuable information about an area
and their calculation uses the new cutset angle concept in- that can be obtained by placing phasor measurements at
troduced in [1]. all the buses along the border of the area. It is natural
to have already placed phasor measurements at major area
Previous approaches to measuring stress with phasor mea- tie lines, so these could be systematically augmented to ob-
surements have used the difference of angles at two buses or tain phasor measurements at all the buses along the border.
searched for patterns in angles from many buses. The new More generally, the method of the paper suggests that pha-
area angles have some advantages over these approaches. sor measurements be placed along nodal cutsets. Instead
The area angles give stress information specific to an area of fixing the areas and asking where phasor measurements
of the power system. This corresponds with the way large should be added, one can ask what areas are implied by the
power systems are operated, and information that describes current or planned phasor measurement locations. All the
specific properties of a specific area of a large power system possible areas can be obtained by considering the network
is more actionable. Since the new area angles obey circuit formed by removing all the buses with phasor measure-
laws, they are more meaningful than an arbitrary combina- ments. Then the possible areas are all the islands (compo-
tion of angles and should provide quantities summarizing nents) of this network, or combinations of these islands.
the power system condition that will behave in ways con-
sistent with the intuition of operators and engineers about The new area angles are very promising quantities for mon-
power flows. itoring area stress and extracting more value from phasor
measurements. We look forward to finding and developing
The area angles may also be useful in summarizing and their practical applications.
communicating the state of large power systems when the
angles and power flows are known from state estimation.
The area angles could also be applied to problems of model
Acknowledgments
References
[1] I. Dobson, M. Parashar, C. Carter, Combining phasor mea-
surements to monitor cutset angles, 43rd Hawaii Interna-
tional Conference on System Sciences, Kauai HI, Jan. 2010.
[2] I. Dobson, M. Parashar, A cutset area concept for phasor
monitoring, IEEE PES General Meeting, Minneapolis, MN
July 2010.
[3] B. Bhargava, A. Salazar, Synchronized phasor measure-
ment system (SPMS) for monitoring transmission system
at SCE, presentation at NASPI Meeting, Carson, CA, May
2007.
[4] R. W. Cummings, Predicting cascading failures, presenta-
tion at NSF/EPRI Workshop on Understanding and Pre-
venting Cascading Failures in Power Systems, Westminster
CO, October 2005.
[5] Z. Huang, J. Dagle, Synchrophasor measurements: Sys-
tem architecture and performance evaluation in supporting
wide-area applications, IEEE Power and Energy Society
General Meeting, Pittsburgh PA, July 2008.
[6] M. Parashar, W. Zhou, D. Trudnowski, Y. Makarov,
I. Dobson, Phasor technology applications feasibility
assessment and research results, DOE/CERTS report,
http://certs.lbl.gov/pdf/phasor-feasibility-2008.pdf, June
2008.
[7] A.G. Phadke, J.S. Thorp, Synchronized Phasor Measure-
ments and Their Applications, Springer NY, 2008.
[8] V. Venkatasubramanian, Y. X. Yue, G. Liu, M. Sherwood,
Q. Zhang, Wide-area monitoring and control algorithms
for large power systems using synchrophasors, IEEE Power
Systems Conference and Exposition, Seattle WA, March
2009.
[9] J. E. Tate, T. J. Overbye, Line outage detection using
phasor angle measurements, IEEE Trans. Power Systems,
vol. 23, no. 4, Nov. 2008, pp. 1644-1652.
[10] C. W. Taylor, D. C. Erickson, K. E. Martin, R. E. Wilson,
V. Venkatasubramanian, WACS–Wide-area stability and
voltage control system: R&D and online demonstration,
Proceedings of the IEEE, vol. 93, no. 5, May 2005, pp.
892-906.
[11] A. Wood and B. Wollenberg, Power Generation, Operation,
and Control. New York: Wiley, 1984.