Lot Detail

Lot No. : e-TENDER CDAsqt23


Construction of 18 storied & 19 storied residential building with basement pile capMat foundation underground basement Water
Lot Description : tank Septic tank Super structuredeep tube-wells Internal Sanitary and plumbing workWater Supply Gas Connection internal
electrification work Firefighting & protection work etc.

Bill of Quantities (Civil)

Table
Bill of Quantities
Name :
Unit Total Total
Item Unit Price Price Price Price
Item Code Measurement Quantity
Group Description of Item
no. (if Unit In In In
In figures (BDT)
any) Words Figures Words
(BDT) (BDT) (BDT)
1.a Civil N/A Erection and maintenance of site L.S 1
office and removal the same after
completion of work in accordance
with the conditions of contract. In
addition to the office required for his
own use, the Contractor shall provide
and maintain furnished field office for
the use of the Engineer and his staff.
The field office is to have a concrete
floor, adequate foundation, brick
walls, false ceiling of hard board with
seasoned Garjan wood frame and
painted, and all windows are to be
glazed and provided with steel grill.
Outside and inside wall surface are to
be painted on plaster acceptable to
the Engineer. The field office shall be
maintained in a secure and watertight
condition by the Contractor until the
completion of the contract and shall
be provided with electricity, running
water and sewerage. All doors shall
be fitted with approved locks and
windows shall be provided with
screen/blinds. Before construction the
Contractor shall submit plans and
drawings showing proposed details
and location for the field office,
including foundations, access roads,
shades, layout of electrical and water
supply and hard standings thereto for
the approval of the engineer. The
Engineer may require revision of first
occupies the site.the plans prior to
giving approval for construction. The
Contractor shall also submit details
proposed furniture, fittings and other
items of equipment and plant to the
engineer for approval. These items
shall be of the standard quality
suitable for site. The office, complete
with furnishings, fittings, access roads
and hard standings shall be ready for
occupation by the Engineer within 28
days of the date when the
Contractor.The Contractor will
provide day and night guards and a
tea boy for the field office. At the end
of the project all materials, equipment
and plant, furniture, fittings recovered
from dismantling the office and
removing access road will be the
property of the Contractor. No interim
payment shall be certified unless
Engineer's office with required
facilities are constructed and
accepted by the Engineer. (This is a
time related item. Proportionate
payment for this item shall be made
distributing in each bill on the basis of
percentage progress of the whole
works under contract) a) Engineer's
site office of minimum 38 sqm plinth
area with providing security fencing, 5
Kva stand-bye generator, IBM
compatible PC with monitor,
uninterruptible power supply (UPS),
Laserjet printer (minimum 25 ppm),
photocopier, 6 cft. Freeze, furniture,
first aid-box, safety helmet,
level/theodolite/EDM, consumables,
stationeries etc.
1.b Civil N/A Erection and maintenance of site Month 24
office and removal the same after
completion of work in accordance
with the conditions of contract. In
addition to the office required for his
own use, the Contractor shall provide
and maintain furnished field office for
the use of the Engineer and his staff.
The field office is to have a concrete
floor, adequate foundation, brick
walls, false ceiling of hard board with
seasoned Garjan wood frame and
painted, and all windows are to be
glazed and provided with steel grill.
Outside and inside wall surface are to
be painted on plaster acceptable to
the Engineer. The field office shall be
maintained in a secure and watertight
condition by the Contractor until the
completion of the contract and shall
be provided with electricity, running
water and sewerage. All doors shall
be fitted with approved locks and
windows shall be provided with
screen/blinds. Before construction the
Contractor shall submit plans and
drawings showing proposed details
and location for the field office,
including foundations, access roads,
shades, layout of electrical and water
supply and hard standings thereto for
the approval of the engineer. The
Engineer may require revision of first
occupies the site.the plans prior to
giving approval for construction. The
Contractor shall also submit details
proposed furniture, fittings and other
items of equipment and plant to the
engineer for approval. These items
shall be of the standard quality
suitable for site. The office, complete
with furnishings, fittings, access roads
and hard standings shall be ready for
occupation by the Engineer within 28
days of the date when the
Contractor.The Contractor will
provide day and night guards and a
tea boy for the field office. At the end
of the project all materials, equipment
and plant, furniture, fittings recovered
from dismantling the office and
removing access road will be the
property of the Contractor. No interim
payment shall be certified unless
Engineer's office with required
facilities are constructed and
accepted by the Engineer. (This is a
time related item. Proportionate
payment for this item shall be made
distributing in each bill on the basis of
percentage progress of the whole
works under contract) a) Engineer's
site office of minimum 38 sqm plinth
area with providing security fencing, 5
Kva stand-bye generator, IBM
compatible PC with monitor,
uninterruptible power supply (UPS),
Laserjet printer (minimum 25 ppm),
photocopier, 6 cft. Freeze, furniture,
first aid-box, safety helmet,
level/theodolite/EDM, consumables,
stationeries etc. Provide Material
Testing Laboratory including
equipment, furniture and maintenance
with all supplies and consumable.
(Contractor Property)
2 Civil N/A Providing and maintenance window Each 1
type 1800 BTU AC (Air-Cooler) for
Engineer's office and remove after
completion of contract.
3 Civil N/A Providing 3 sets as-built Drawings per tender 1
subject to Engineer's approval
produced in AutoCAD software in
23.38? x 16.54? (A-2 size) standard
drawing paper, and operating and
maintenance manual of the equipment
and plant incorporated in the works, if
any, in original by the date stated in
the Particular Conditions of Contract
(PCC). If the Contractor does not
supply the as-built drawings and
operating and maintenance manuals
by the date stated in the Particular
Conditions of Contract (PCC), or
they do not receive the Engineer's
approval, the Engineer shall withhold
the amount stated in the PCC from
the payments due to the
Contractor.The as-built drawings
must show the permanent works as
actually constructed and reflect the
revision of Tender Drawings and
Drawings supplied to the Contractor
during the Contract as well as
revisions of drawings supplied by the
Contractor during the Contract. (One
set of as-built drawings shall be
considered for measurement and
payment)
4 Civil N/A Providing additional copy of as-built Sqm 116
drawing produced in Auto CAD
software in 23.38" x 16.54" (A-2)
standard drawing paper accepted by
the Engineer.
5 Civil N/A Providing minimum ten (10) copies Month 30
coloured post-card size progress
photograph of ?works under
contract? taken by professional
photographer which record the
progress of the Works.
6 Civil N/A Preparation & submission of L.S 1
implementation schedule to the
Engineer for approval prior ground
breaking showing the events (works)
and successive sub-events of works
including all the management &
control parameters like Earliest Start
Time (EST), Earliest Finish Time
(EFT), float events on critical path,
resource allocation etc. with
description of general method of
works, in orderly manner all in the
form network diagram prepared in
computer software like MS project
and presenting in Displayable hard
and soft copy minimum 3 (three) sets.
(This is a time related item.
Proportionate payment for this item
shall be made istributing in each bill
on the basis of percentage progress
of the whole works under contract)
7 Civil N/A Updating the Implementation Month 36
Schedule and submission to the
Engineer at intervals no longer than
28 days showing actual physical and
financial progress achieved, on each
activity and the effect of the progress
on the timing of the remaining work,
including any changes to the
sequence of the activities.However,
Engineer's approval of the
Programme shall not alter the
Contractor's obligations. The
Contractor may revise the
Programme and submit it to the
Engineer again at any time. A revised
programme shall show the Variations
and Events related to change of
contract price.
8 Civil N/A Providing all necessary logistic Month 36
support to frame ?monthly progress
meeting? between
Contractor/Contractor's
representatives and Employer /
Employer's representatives at the
Engineer's office at site.
9 Civil N/A Providing layout and carry over PWD Sqm. 2688.89
Bench-Mark (BM) at site from nearby
BM pillar, Property lines, existing
ground level (EGL), formation ground
level (FGL), highest flood levels
(HFL), plinth levels (PL), mean sea
level (MSL), setting and marking all
pillars, marker, pegs etc. showing
and maintaining reduced levels (RL's)
including locating, establishing,
protecting all public utilities within the
premise of work and finally all to be
presented in black and white.
10 Civil N/A Mobilization and cleaning site before Sqm. 3226.67
commencing actual physical work and
during contract period and
demobilization after completion of the
Works under contract accepted by
Engineer. This work shall also covers
clayey cleaning and clearing, cutting
or filling, dressing the project area on
and in the ground to an extent that all
the events of works of the project
can be executed smoothly in a
working environment with a particular
attention on safety and security in all.
11 Civil N/A Provide operate and maintain New Month 24.00
microbus 1 Numbers for Engineer
and consultant for use in site.
12.a Civil N/A Earth work in excavation in all kinds Sqm. 2062.91
of soil for foundation trenches
including. layout, providing center
lines, local bench-mark pillars,
leveling, ramming and preparing the
base, fixing bamboo spikes and
marking layout with chalk powder,
providing necessary tools and plants,
protecting and maintaining the trench
dry etc., stacking, cleaning the
excavated earth at a safe distance
out of the area enclosed by the layout
etc. all complete and accepted by the
Engineer, subject to submit method
statement of carrying out excavation
work to the Engineer for approval.
However, Engineer's approval shall
not relieve the contractor of his
responsibilities and obligations under
the contract a). Layout and marking
for earthwork in excavation in
foundation accepted by the Engineer.
[Plinth area of the structure shall be
considered for measurement.
12.b Civil N/A Earth work in excavation in all kinds Cum 2974.61
of soil for foundation trenches
including. layout, providing center
lines, local bench-mark pillars,
leveling, ramming and preparing the
base, fixing bamboo spikes and
marking layout with chalk powder,
providing necessary tools and plants,
protecting and maintaining the trench
dry etc., stacking, cleaning the
excavated earth at a safe distance
out of the area enclosed by the layout
etc. all complete and accepted by the
Engineer, subject to submit method
statement of carrying out excavation
work to the Engineer for approval.
However, Engineer's approval shall
not relieve the contractor of his
responsibilities and obligations under
the contract b). Earthwork in
excavation in foundation trenches up
to 1.5 m depth and maximum 10 m
lead: in medium stiff clayey soil
12.c Civil N/A Earth work in excavation in all kinds Cum 991.54
of soil for foundation trenches
including. layout, providing center
lines, local bench-mark pillars,
leveling, ramming and preparing the
base, fixing bamboo spikes and
marking layout with chalk powder,
providing necessary tools and plants,
protecting and maintaining the trench
dry etc., stacking, cleaning the
excavated earth at a safe distance
out of the area enclosed by the layout
etc. all complete and accepted by the
Engineer, subject to submit method
statement of carrying out excavation
work to the Engineer for approval.
However, Engineer's approval shall
not relieve the contractor of his
responsibilities and obligations under
the contract c). Earthwork in
excavation in foundation trenches
from 1.5 m to 2.0 m depth and
maximum 10 m lead: in medium stiff
clayey soil
12.d Civil N/A Earth work in excavation in all kinds Cum 693.87
of soil for foundation trenches
including. layout, providing center
lines, local bench-mark pillars,
leveling, ramming and preparing the
base, fixing bamboo spikes and
marking layout with chalk powder,
providing necessary tools and plants,
protecting and maintaining the trench
dry etc., stacking, cleaning the
excavated earth at a safe distance
out of the area enclosed by the layout
etc. all complete and accepted by the
Engineer, subject to submit method
statement of carrying out excavation
work to the Engineer for approval.
However, Engineer's approval shall
not relieve the contractor of his
responsibilities and obligations under
the contract d) Earthwork in
excavation in foundation trenches
from 2.0 m to 2.5 m depth and
maximum 10 m lead: in medium stiff
clayey soil
12.e Civil N/A Earth work in excavation in all kinds Cum 493.20
of soil for foundation trenches
including. layout, providing center
lines, local bench-mark pillars,
leveling, ramming and preparing the
base, fixing bamboo spikes and
marking layout with chalk powder,
providing necessary tools and plants,
protecting and maintaining the trench
dry etc., stacking, cleaning the
excavated earth at a safe distance
out of the area enclosed by the layout
etc. all complete and accepted by the
Engineer, subject to submit method
statement of carrying out excavation
work to the Engineer for approval.
However, Engineer's approval shall
not relieve the contractor of his
responsibilities and obligations under
the contract e) Earthwork in
excavation in foundation trenches
from 2.5 m to 3.0 m depth and
maximum 10 m lead: in medium stiff
clayey soil
13 Civil N/A Bailing out trapped water caused by Hour 500.00
inundation or rain, by pump from
foundation trenches
14 Civil N/A Shore protection work during Sqm. 275.51
excavation in foundation trenches up
to 1.5 m depth, to protect loss due to
damage of property by Palisading
accepted by the Engineer. [the rate is
including cost of vertical post]
15 Civil N/A Sand filling in foundation trenches and Cum 426.84
plinth with sand having F.M. 0.5 to
0.8 in 150mm layers including
leveling, watering and compaction to
achieve minimum dry density of 90%
with optimum moisture content
(Modified proctor test) by ramming
each layer up to finished level as per
design supplied by the design office
only etc. all complete and accepted
by the Engineer.
16 Civil N/A Sand filling in foundation trenches and Cum 763.96
plinth with coarse sand having min.
F.M. 1.2 in 150mm in layers including
leveling, watering and compaction to
achieve minimum dry density of 90%
with optimum moisture content
(Modified proctor test) by ramming
each layer up to finished level as per
design supplied by the design office
only etc. all complete and accepted
by the Engineer.
17 Civil N/A Earth filling in foundation trenches and Cum 500.00
plinth in 150 mm layer with earth
available within 90 m of the building
site minimum dry density of 90% with
optimum moisture content (Modified
proctor test) including carrying
watering, leveling, dressing and
compacting to a specified percentage
each layer up to finished level etc. all
complete and accepted by the
Engineer.
18 Civil N/A Clearing and disposing of excavated Cum 4115.25
earth from the construction site by
truck or any other means to a place
within 30 km radius of the city or
town area including loading, unloading
at both ends, leveling and dressing
the carried earth etc. complete
accepted by the Engineer.
19 Civil N/A Site Development/Improvement by Cum 700.00
carted/dredged earth or sand (free
from any organic, foreign,
environmental hazard substances)
carried by head or truck or any other
meansl in/c cost of cutting/dredging
of earth/sand, carrying, placing the
earth/sand in the designated area,
maintaining slopes, breaking lumps,
levelling and dressing in layers up to
finished level etc. all complete as per
direction and accepted by the
engineer in charge.
20 Civil N/A One layer of brick flat soling in Sqm. 350.00
foundation or in floor with first class
or picked jhama bricks including
preparation of bed and filling the
interstices with local sand, leveling
etc. complete and accepted by the
Engineer.
21.a Civil N/A Mass concrete (1:2:4) in foundation Cum 62.00
or floor with cement, sand (F.M. 1.2)
and picked jhama chips including
breaking chips, screening, mixing,
laying, compacting to levels and
curing for at least 7 days including the
supply of water, electricity and other
charges and costs of tools and plants
etc. all complete and accepted by the
Engineer. (Cement: CEM-II/A-M) a)
Mass concrete in floor (1:2:4) with
brick chips and local sand of F.M. 1.2
21.b Civil N/A Mass concrete (1:2:4) in foundation Cum 62.00
or floor with cement, sand (F.M. 1.2)
and picked jhama chips including
breaking chips, screening, mixing,
laying, compacting to levels and
curing for at least 7 days including the
supply of water, electricity and other
charges and costs of tools and plants
etc. all complete and accepted by the
Engineer. (Cement: CEM-II/A-M) b)
Mass concrete in floor (1:3:6) with
brick chips and local sand of F.M. 1.2
22 Civil N/A Damp proof course (DPC) (1:1.5:3) Sqm. 20.00
in cement concrete with cement, sand
(F.M. 1.2) and picked jhama or stone
chips including breaking chips,
screening, centering, shuttering,
casting, curing and finished with a
coat of bitumen including the supply
of water, electricity and other
charges and costs of tools and plants
etc. all complete and accepted by the
Engineer. (Cement: CEM-II/A-M) a)
75 mm or 3" thick damp proof course
(1:1.5:3) with Sylhet sand (F.M. 2.2)
and stone chips.
23-a Civil N/A Supplying and laying of single layer Sqm. 6779.29
polythene sheet weighing one
kilogram per 6.5 square meter in floor
or any where below cement concrete
complete in all respect and accepted
by the Engineer.
23.b Civil N/A Supplying, fitting and fixing Ribbed Rm 3000.00
with center bulb PVC water stopper
of width apporx. 250mm and approx
9mm thick, for movable (working or
expansion joints) RCC joints, having
minimum tensile strength 8.27MP a
(approx. 1200psi) min ultimate
elongation 350% approximate
hardness 50, minimum tear
resistance 0.0175kn/mm
(100Ibs/inch) at RCC construction
green joints in basements, approved
and inconsultation with design
office,providing 1.5''*2.5'' wooden
batten at the top and bottom of water
stopper, holding inposition and
keeping the water stopper in true
horizontal or vertical by approprate
means as where necessary
etc.allcomplete and accepted by the
Engineer.
24.a Civil N/A a. Brick works with first class bricks Cum 91.62
in cement sand (F.M. of sand 1.2)
mortar (1:6) in foundation and plinth,
filling the joints/interstices fully with
mortar, racking out the joints, cleaning
and soaking the bricks at least for 24
hours before use and curing at least
for 7 days etc. all complete including
cost of water, electricity and other
charges and accepted by the
Engineer.(Cement: CEM-II/A-M).
24.b Civil N/A b. 125 mm brick works with first class Sq m 1046.61
bricks in cement sand (F.M. 1.2)
mortar (1:4) in foundation and making
bond with connected walls including
necessary scaffolding, raking out
joints, cleaning and soaking the bricks
for at least 24 hours before use and
washing of sand curing at least for 7
days in all floors including cost of
water, electricity and other charges
etc. all complete and accepted by the
Engineer.(Cement: CEM-II/A-M).
25.a Civil N/A Brick works of width one brick or one Cum 125.14
and a half brick length with first class
bricks in cement sand (F.M. 1.2)
mortar (1:6) in superstructure
including raking out joints, filling the
interstices with mortar, cleaning and
soaking the bricks at least for 24
hours before use and washing of
sand, necessary scaffolding, curing at
least for 7 days etc. all complete
(measurement to given as 250 mm
width for one brick length and 375
mm for one brick and a half brick
length) and accepted by the
Engineer.(Cement: CEM-II/A-M) a)
in Ground & Basement Floor
25.b Civil N/A Brick works of width one brick or one Cum 63.16
and a half brick length with first class
bricks in cement sand (F.M. 1.2)
mortar (1:6) in superstructure
including raking out joints, filling the
interstices with mortar, cleaning and
soaking the bricks at least for 24
hours before use and washing of
sand, necessary scaffolding, curing at
least for 7 days etc. all complete
(measurement to given as 250 mm
width for one brick length and 375
mm for one brick and a half brick
length) and accepted by the
Engineer.(Cement: CEM-II/A-M) b)
in 1st Floor
25.c Civil N/A Brick works of width one brick or one Cum 78.95
and a half brick length with first class
bricks in cement sand (F.M. 1.2)
mortar (1:6) in superstructure
including raking out joints, filling the
interstices with mortar, cleaning and
soaking the bricks at least for 24
hours before use and washing of
sand, necessary scaffolding, curing at
least for 7 days etc. all complete
(measurement to given as 250 mm
width for one brick length and 375
mm for one brick and a half brick
length) and accepted by the
Engineer.(Cement: CEM-II/A-M) c)
in 2nd Floor
25.d Civil N/A Brick works of width one brick or one Cum 78.95
and a half brick length with first class
bricks in cement sand (F.M. 1.2)
mortar (1:6) in superstructure
including raking out joints, filling the
interstices with mortar, cleaning and
soaking the bricks at least for 24
hours before use and washing of
sand, necessary scaffolding, curing at
least for 7 days etc. all complete
(measurement to given as 250 mm
width for one brick length and 375
mm for one brick and a half brick
length) and accepted by the
Engineer.(Cement: CEM-II/A-M) d)
in 3rd Floor
25.e Civil N/A Brick works of width one brick or one Cum 78.95
and a half brick length with first class
bricks in cement sand (F.M. 1.2)
mortar (1:6) in superstructure
including raking out joints, filling the
interstices with mortar, cleaning and
soaking the bricks at least for 24
hours before use and washing of
sand, necessary scaffolding, curing at
least for 7 days etc. all complete
(measurement to given as 250 mm
width for one brick length and 375
mm for one brick and a half brick
length) and accepted by the
Engineer.(Cement: CEM-II/A-M) e)
in 4th Floor
25.f Civil N/A Brick works of width one brick or one Cum 78.95
and a half brick length with first class
bricks in cement sand (F.M. 1.2)
mortar (1:6) in superstructure
including raking out joints, filling the
interstices with mortar, cleaning and
soaking the bricks at least for 24
hours before use and washing of
sand, necessary scaffolding, curing at
least for 7 days etc. all complete
(measurement to given as 250 mm
width for one brick length and 375
mm for one brick and a half brick
length) and accepted by the
Engineer.(Cement: CEM-II/A-M) f) in
5th Floor
25.g Civil N/A Brick works of width one brick or one Cum 78.95
and a half brick length with first class
bricks in cement sand (F.M. 1.2)
mortar (1:6) in superstructure
including raking out joints, filling the
interstices with mortar, cleaning and
soaking the bricks at least for 24
hours before use and washing of
sand, necessary scaffolding, curing at
least for 7 days etc. all complete
(measurement to given as 250 mm
width for one brick length and 375
mm for one brick and a half brick
length) and accepted by the
Engineer.(Cement: CEM-II/A-M) g)
in 6th Floor
25.h Civil N/A Brick works of width one brick or one Cum 78.95
and a half brick length with first class
bricks in cement sand (F.M. 1.2)
mortar (1:6) in superstructure
including raking out joints, filling the
interstices with mortar, cleaning and
soaking the bricks at least for 24
hours before use and washing of
sand, necessary scaffolding, curing at
least for 7 days etc. all complete
(measurement to given as 250 mm
width for one brick length and 375
mm for one brick and a half brick
length) and accepted by the
Engineer.(Cement: CEM-II/A-M) h)
in 7th Floor
25.i Civil N/A Brick works of width one brick or one Cum 78.95
and a half brick length with first class
bricks in cement sand (F.M. 1.2)
mortar (1:6) in superstructure
including raking out joints, filling the
interstices with mortar, cleaning and
soaking the bricks at least for 24
hours before use and washing of
sand, necessary scaffolding, curing at
least for 7 days etc. all complete
(measurement to given as 250 mm
width for one brick length and 375
mm for one brick and a half brick
length) and accepted by the
Engineer.(Cement: CEM-II/A-M) i) in
8th Floor
25.j Civil N/A Brick works of width one brick or one Cum 78.95
and a half brick length with first class
bricks in cement sand (F.M. 1.2)
mortar (1:6) in superstructure
including raking out joints, filling the
interstices with mortar, cleaning and
soaking the bricks at least for 24
hours before use and washing of
sand, necessary scaffolding, curing at
least for 7 days etc. all complete
(measurement to given as 250 mm
width for one brick length and 375
mm for one brick and a half brick
length) and accepted by the
Engineer.(Cement: CEM-II/A-M) j) in
9th Floor
25.k Civil N/A Brick works of width one brick or one Cum 78.95
and a half brick length with first class
bricks in cement sand (F.M. 1.2)
mortar (1:6) in superstructure
including raking out joints, filling the
interstices with mortar, cleaning and
soaking the bricks at least for 24
hours before use and washing of
sand, necessary scaffolding, curing at
least for 7 days etc. all complete
(measurement to given as 250 mm
width for one brick length and 375
mm for one brick and a half brick
length) and accepted by the
Engineer.(Cement: CEM-II/A-M) k)
in 10th Floor
25.l Civil N/A Brick works of width one brick or one Cum 78.95
and a half brick length with first class
bricks in cement sand (F.M. 1.2)
mortar (1:6) in superstructure
including raking out joints, filling the
interstices with mortar, cleaning and
soaking the bricks at least for 24
hours before use and washing of
sand, necessary scaffolding, curing at
least for 7 days etc. all complete
(measurement to given as 250 mm
width for one brick length and 375
mm for one brick and a half brick
length) and accepted by the
Engineer.(Cement: CEM-II/A-M) l) in
11th Floor
25.m Civil N/A Brick works of width one brick or one Cum 78.95
and a half brick length with first class
bricks in cement sand (F.M. 1.2)
mortar (1:6) in superstructure
including raking out joints, filling the
interstices with mortar, cleaning and
soaking the bricks at least for 24
hours before use and washing of
sand, necessary scaffolding, curing at
least for 7 days etc. all complete
(measurement to given as 250 mm
width for one brick length and 375
mm for one brick and a half brick
length) and accepted by the
Engineer.(Cement: CEM-II/A-M) m)
in 12th Floor
25.n Civil N/A Brick works of width one brick or one Cum 78.95
and a half brick length with first class
bricks in cement sand (F.M. 1.2)
mortar (1:6) in superstructure
including raking out joints, filling the
interstices with mortar, cleaning and
soaking the bricks at least for 24
hours before use and washing of
sand, necessary scaffolding, curing at
least for 7 days etc. all complete
(measurement to given as 250 mm
width for one brick length and 375
mm for one brick and a half brick
length) and accepted by the
Engineer.(Cement: CEM-II/A-M) n)
in 13th Floor
25.o Civil N/A Brick works of width one brick or one Cum 78.95
and a half brick length with first class
bricks in cement sand (F.M. 1.2)
mortar (1:6) in superstructure
including raking out joints, filling the
interstices with mortar, cleaning and
soaking the bricks at least for 24
hours before use and washing of
sand, necessary scaffolding, curing at
least for 7 days etc. all complete
(measurement to given as 250 mm
width for one brick length and 375
mm for one brick and a half brick
length) and accepted by the
Engineer.(Cement: CEM-II/A-M) o)
in 14th Floor
25.p Civil N/A Brick works of width one brick or one Cum 78.95
and a half brick length with first class
bricks in cement sand (F.M. 1.2)
mortar (1:6) in superstructure
including raking out joints, filling the
interstices with mortar, cleaning and
soaking the bricks at least for 24
hours before use and washing of
sand, necessary scaffolding, curing at
least for 7 days etc. all complete
(measurement to given as 250 mm
width for one brick length and 375
mm for one brick and a half brick
length) and accepted by the
Engineer.(Cement: CEM-II/A-M) p)
in 15th Floor
25.q Civil N/A Brick works of width one brick or one Cum 78.95
and a half brick length with first class
bricks in cement sand (F.M. 1.2)
mortar (1:6) in superstructure
including raking out joints, filling the
interstices with mortar, cleaning and
soaking the bricks at least for 24
hours before use and washing of
sand, necessary scaffolding, curing at
least for 7 days etc. all complete
(measurement to given as 250 mm
width for one brick length and 375
mm for one brick and a half brick
length) and accepted by the
Engineer.(Cement: CEM-II/A-M) q)
in 16th Floor
25.r Civil N/A Brick works of width one brick or one Cum 45.01
and a half brick length with first class
bricks in cement sand (F.M. 1.2)
mortar (1:6) in superstructure
including raking out joints, filling the
interstices with mortar, cleaning and
soaking the bricks at least for 24
hours before use and washing of
sand, necessary scaffolding, curing at
least for 7 days etc. all complete
(measurement to given as 250 mm
width for one brick length and 375
mm for one brick and a half brick
length) and accepted by the
Engineer.(Cement: CEM-II/A-M) r) in
17th Floor (Chilakota & lift machine
room)
25.s Civil N/A Brick works of width one brick or one Cum 6.02
and a half brick length with first class
bricks in cement sand (F.M. 1.2)
mortar (1:6) in superstructure
including raking out joints, filling the
interstices with mortar, cleaning and
soaking the bricks at least for 24
hours before use and washing of
sand, necessary scaffolding, curing at
least for 7 days etc. all complete
(measurement to given as 250 mm
width for one brick length and 375
mm for one brick and a half brick
length) and accepted by the
Engineer.(Cement: CEM-II/A-M) s)in
18th Floor
26.a Civil N/A 125 mm brick works with first class Sqm. 423.43
bricks in cement sand (F.M. 1.2)
mortar (1:4) and making bond with
connected walls including necessary
scaffolding, raking out joints, cleaning
and soaking the bricks for at least 24
hours before use and washing of
sand curing at least for 7 days in all
floors including cost of water,
electricity and other charges etc. all
complete and accepted by the
Engineer.(Cement: CEM-II/A-M). a)
in Ground & Basement Floor
26.b Civil N/A 125 mm brick works with first class Sqm. 332.66
bricks in cement sand (F.M. 1.2)
mortar (1:4) and making bond with
connected walls including necessary
scaffolding, raking out joints, cleaning
and soaking the bricks for at least 24
hours before use and washing of
sand curing at least for 7 days in all
floors including cost of water,
electricity and other charges etc. all
complete and accepted by the
Engineer.(Cement: CEM-II/A-M). b)
in 1st Floor
26.c Civil N/A 125 mm brick works with first class Sqm. 1093.63
bricks in cement sand (F.M. 1.2)
mortar (1:4) and making bond with
connected walls including necessary
scaffolding, raking out joints, cleaning
and soaking the bricks for at least 24
hours before use and washing of
sand curing at least for 7 days in all
floors including cost of water,
electricity and other charges etc. all
complete and accepted by the
Engineer.(Cement: CEM-II/A-M). c)
in 2nd Floor
26.d Civil N/A 125 mm brick works with first class Sqm. 1093.63
bricks in cement sand (F.M. 1.2)
mortar (1:4) and making bond with
connected walls including necessary
scaffolding, raking out joints, cleaning
and soaking the bricks for at least 24
hours before use and washing of
sand curing at least for 7 days in all
floors including cost of water,
electricity and other charges etc. all
complete and accepted by the
Engineer.(Cement: CEM-II/A-M). d)
in 3rd Floor
26.e Civil N/A 125 mm brick works with first class Sqm. 1093.63
bricks in cement sand (F.M. 1.2)
mortar (1:4) and making bond with
connected walls including necessary
scaffolding, raking out joints, cleaning
and soaking the bricks for at least 24
hours before use and washing of
sand curing at least for 7 days in all
floors including cost of water,
electricity and other charges etc. all
complete and accepted by the
Engineer.(Cement: CEM-II/A-M). e)
in 4th Floor
26.f Civil N/A 125 mm brick works with first class Sqm. 1093.63
bricks in cement sand (F.M. 1.2)
mortar (1:4) and making bond with
connected walls including necessary
scaffolding, raking out joints, cleaning
and soaking the bricks for at least 24
hours before use and washing of
sand curing at least for 7 days in all
floors including cost of water,
electricity and other charges etc. all
complete and accepted by the
Engineer.(Cement: CEM-II/A-M). f)
in 5th Floor
26.g Civil N/A 125 mm brick works with first class Sqm. 1093.63
bricks in cement sand (F.M. 1.2)
mortar (1:4) and making bond with
connected walls including necessary
scaffolding, raking out joints, cleaning
and soaking the bricks for at least 24
hours before use and washing of
sand curing at least for 7 days in all
floors including cost of water,
electricity and other charges etc. all
complete and accepted by the
Engineer.(Cement: CEM-II/A-M). g)
in 6th Floor
26.h Civil N/A 125 mm brick works with first class Sqm. 1093.63
bricks in cement sand (F.M. 1.2)
mortar (1:4) and making bond with
connected walls including necessary
scaffolding, raking out joints, cleaning
and soaking the bricks for at least 24
hours before use and washing of
sand curing at least for 7 days in all
floors including cost of water,
electricity and other charges etc. all
complete and accepted by the
Engineer.(Cement: CEM-II/A-M). h)
in 7th Floor
26.i Civil N/A 125 mm brick works with first class Sqm. 1093.63
bricks in cement sand (F.M. 1.2)
mortar (1:4) and making bond with
connected walls including necessary
scaffolding, raking out joints, cleaning
and soaking the bricks for at least 24
hours before use and washing of
sand curing at least for 7 days in all
floors including cost of water,
electricity and other charges etc. all
complete and accepted by the
Engineer.(Cement: CEM-II/A-M). i)
in 8th Floor
26.j Civil N/A 125 mm brick works with first class Sqm. 1093.63
bricks in cement sand (F.M. 1.2)
mortar (1:4) and making bond with
connected walls including necessary
scaffolding, raking out joints, cleaning
and soaking the bricks for at least 24
hours before use and washing of
sand curing at least for 7 days in all
floors including cost of water,
electricity and other charges etc. all
complete and accepted by the
Engineer.(Cement: CEM-II/A-M). j)
in 9th Floor
26.k Civil N/A 125 mm brick works with first class Sqm. 1093.63
bricks in cement sand (F.M. 1.2)
mortar (1:4) and making bond with
connected walls including necessary
scaffolding, raking out joints, cleaning
and soaking the bricks for at least 24
hours before use and washing of
sand curing at least for 7 days in all
floors including cost of water,
electricity and other charges etc. all
complete and accepted by the
Engineer.(Cement: CEM-II/A-M). k)
in 10th Floor
26.l Civil N/A 125 mm brick works with first class Sqm. 1093.63
bricks in cement sand (F.M. 1.2)
mortar (1:4) and making bond with
connected walls including necessary
scaffolding, raking out joints, cleaning
and soaking the bricks for at least 24
hours before use and washing of
sand curing at least for 7 days in all
floors including cost of water,
electricity and other charges etc. all
complete and accepted by the
Engineer.(Cement: CEM-II/A-M). l)
in 11th Floor
26.m Civil N/A 125 mm brick works with first class Sqm. 1093.63
bricks in cement sand (F.M. 1.2)
mortar (1:4) and making bond with
connected walls including necessary
scaffolding, raking out joints, cleaning
and soaking the bricks for at least 24
hours before use and washing of
sand curing at least for 7 days in all
floors including cost of water,
electricity and other charges etc. all
complete and accepted by the
Engineer.(Cement: CEM-II/A-M). m)
in 12th Floor
26.n Civil N/A 125 mm brick works with first class Sqm. 1093.63
bricks in cement sand (F.M. 1.2)
mortar (1:4) and making bond with
connected walls including necessary
scaffolding, raking out joints, cleaning
and soaking the bricks for at least 24
hours before use and washing of
sand curing at least for 7 days in all
floors including cost of water,
electricity and other charges etc. all
complete and accepted by the
Engineer.(Cement: CEM-II/A-M). n)
in 13th Floor
26.o Civil N/A 125 mm brick works with first class Sqm. 1093.63
bricks in cement sand (F.M. 1.2)
mortar (1:4) and making bond with
connected walls including necessary
scaffolding, raking out joints, cleaning
and soaking the bricks for at least 24
hours before use and washing of
sand curing at least for 7 days in all
floors including cost of water,
electricity and other charges etc. all
complete and accepted by the
Engineer.(Cement: CEM-II/A-M). o)
in 14th Floor
26.p Civil N/A 125 mm brick works with first class Sqm. 1093.63
bricks in cement sand (F.M. 1.2)
mortar (1:4) and making bond with
connected walls including necessary
scaffolding, raking out joints, cleaning
and soaking the bricks for at least 24
hours before use and washing of
sand curing at least for 7 days in all
floors including cost of water,
electricity and other charges etc. all
complete and accepted by the
Engineer.(Cement: CEM-II/A-M).p)
in 15th Floor
26.q Civil N/A 125 mm brick works with first class Sqm. 1093.63
bricks in cement sand (F.M. 1.2)
mortar (1:4) and making bond with
connected walls including necessary
scaffolding, raking out joints, cleaning
and soaking the bricks for at least 24
hours before use and washing of
sand curing at least for 7 days in all
floors including cost of water,
electricity and other charges etc. all
complete and accepted by the
Engineer.(Cement: CEM-II/A-M). q)
in 16th Floor
26.r Civil N/A 125 mm brick works with first class Sqm. 278.40
bricks in cement sand (F.M. 1.2)
mortar (1:4) and making bond with
connected walls including necessary
scaffolding, raking out joints, cleaning
and soaking the bricks for at least 24
hours before use and washing of
sand curing at least for 7 days in all
floors including cost of water,
electricity and other charges etc. all
complete and accepted by the
Engineer.(Cement: CEM-II/A-M). r)
in Chillachota & lift machine room
in17th Floor
26.s Civil N/A 125 mm brick works with first class Sqm. 79.09
bricks in cement sand (F.M. 1.2)
mortar (1:4) and making bond with
connected walls including necessary
scaffolding, raking out joints, cleaning
and soaking the bricks for at least 24
hours before use and washing of
sand curing at least for 7 days in all
floors including cost of water,
electricity and other charges etc. all
complete and accepted by the
Engineer.(Cement: CEM-II/A-M).
s)in 18th Floor
27 Civil N/A 38 mm thick artificial patent stone Sqm. 1300.00
(1:1.5:3) flooring with cement, best
quality coarse sand (50% quantity of
Sylhet sand or coarse sand of
equivalent F.M. 2.2 and 50% best
local sand of FM 1.2) and 12 mm
down well graded stone chips, laying
the concrete in alternate panels,
compacting and finishing the top with
neat cement and curing at least 7
days in all floors including cost of
water, electricity and other charges
etc. all complete and accepted by the
Engineer. (Cement: CEM-II/A-M) r)
in 17th Floor (roof)
28.a Civil N/A Marble stone/ Granite flooring with Sqm. 227.23
18mm thick Italian coloured/ grey
marble stone of approved quality,
texture and size over 25 mm thick
cement sand (F.M. 1.2) mortar (1:2)
including. placing cement slurry below
the stone, cutting the marble stone to
desired size, grinding and finishing the
edges, setting in position in proper
level filling the gaps with white
cement and colouring pigments
including supplying all necessary
equipments/materials and finishing the
top by pumic stone and necessary
auxiliary materials and water,
electricity and other charges
complete in all respect accepted by
the Engineer.(Cement: CEM-II/A-M)
In ground floor. a) Marble stone a)
Marble stone
28.b Civil N/A Marble stone/ Granite flooring with Sqm. 227.23
18mm thick Italian coloured/ grey
marble stone of approved quality,
texture and size over 25 mm thick
cement sand (F.M. 1.2) mortar (1:2)
including. placing cement slurry below
the stone, cutting the marble stone to
desired size, grinding and finishing the
edges, setting in position in proper
level filling the gaps with white
cement and colouring pigments
including supplying all necessary
equipments/materials and finishing the
top by pumic stone and necessary
auxiliary materials and water,
electricity and other charges
complete in all respect accepted by
the Engineer.(Cement: CEM-II/A-M)
In ground floor. a) Marble stone b)
Granite
29 Civil N/A Labour Cost for making moulding in Sqm. 304.55
marble/granite stone as per
Architectural drawing including
cutting, grinding, finishing, supplying
necessary equipment etc. complete in
all respect as per direction of the
Engineer in Charge. (Cement: CEM-
II/A-M) for 18 mm thick marble stone
30.a Civil N/A Supplying, fitting and fixing glazed Sqm. 70.00
wall tiles (local/equivalent foreign
made) with on 20 mm thick cement
sand (F.M. 1.2) mortar (1:3) base
and raking out the joints with white
cement including cutting, laying and
hire charge of machine and finishing
with care etc. including water,
electricity and other charges
complete all respect accepted by the
Engineer. (Cement: CEM-II/A-M)
Coloured glazed wall tiles of different
sizes (Sample approved by the
engineer in charge))e and accepted
by the Engineer.(Cement: CEM-II/A-
M). (More than 250x330 & less than
250x400 or equivalent). a) in Ground
& Basement Floor
30.b Civil N/A Supplying, fitting and fixing glazed Sqm. 405.00
wall tiles (local/equivalent foreign
made) with on 20 mm thick cement
sand (F.M. 1.2) mortar (1:3) base
and raking out the joints with white
cement including cutting, laying and
hire charge of machine and finishing
with care etc. including water,
electricity and other charges
complete all respect accepted by the
Engineer. (Cement: CEM-II/A-M)
Coloured glazed wall tiles of different
sizes (Sample approved by the
engineer in charge))e and accepted
by the Engineer.(Cement: CEM-II/A-
M). (More than 250x330 & less than
250x400 or equivalent). b) in 1st
Floor
30.c Civil N/A Supplying, fitting and fixing glazed Sqm. 490.77
wall tiles (local/equivalent foreign
made) with on 20 mm thick cement
sand (F.M. 1.2) mortar (1:3) base
and raking out the joints with white
cement including cutting, laying and
hire charge of machine and finishing
with care etc. including water,
electricity and other charges
complete all respect accepted by the
Engineer. (Cement: CEM-II/A-M)
Coloured glazed wall tiles of different
sizes (Sample approved by the
engineer in charge))e and accepted
by the Engineer.(Cement: CEM-II/A-
M). (More than 250x330 & less than
250x400 or equivalent). c) in 2nd
Floor
30.d Civil N/A Supplying, fitting and fixing glazed Sqm. 490.77
wall tiles (local/equivalent foreign
made) with on 20 mm thick cement
sand (F.M. 1.2) mortar (1:3) base
and raking out the joints with white
cement including cutting, laying and
hire charge of machine and finishing
with care etc. including water,
electricity and other charges
complete all respect accepted by the
Engineer. (Cement: CEM-II/A-M)
Coloured glazed wall tiles of different
sizes (Sample approved by the
engineer in charge))e and accepted
by the Engineer.(Cement: CEM-II/A-
M). (More than 250x330 & less than
250x400 or equivalent).d) in 3rd Floor
30.e Civil N/A Supplying, fitting and fixing glazed Sqm. 490.77
wall tiles (local/equivalent foreign
made) with on 20 mm thick cement
sand (F.M. 1.2) mortar (1:3) base
and raking out the joints with white
cement including cutting, laying and
hire charge of machine and finishing
with care etc. including water,
electricity and other charges
complete all respect accepted by the
Engineer. (Cement: CEM-II/A-M)
Coloured glazed wall tiles of different
sizes (Sample approved by the
engineer in charge))e and accepted
by the Engineer.(Cement: CEM-II/A-
M). (More than 250x330 & less than
250x400 or equivalent).e) in 4th Floor
30.f Civil N/A Supplying, fitting and fixing glazed Sqm. 490.77
wall tiles (local/equivalent foreign
made) with on 20 mm thick cement
sand (F.M. 1.2) mortar (1:3) base
and raking out the joints with white
cement including cutting, laying and
hire charge of machine and finishing
with care etc. including water,
electricity and other charges
complete all respect accepted by the
Engineer. (Cement: CEM-II/A-M)
Coloured glazed wall tiles of different
sizes (Sample approved by the
engineer in charge))e and accepted
by the Engineer.(Cement: CEM-II/A-
M). (More than 250x330 & less than
250x400 or equivalent).f) in 5th Floor
30.g Civil N/A Supplying, fitting and fixing glazed Sqm. 490.77
wall tiles (local/equivalent foreign
made) with on 20 mm thick cement
sand (F.M. 1.2) mortar (1:3) base
and raking out the joints with white
cement including cutting, laying and
hire charge of machine and finishing
with care etc. including water,
electricity and other charges
complete all respect accepted by the
Engineer. (Cement: CEM-II/A-M)
Coloured glazed wall tiles of different
sizes (Sample approved by the
engineer in charge))e and accepted
by the Engineer.(Cement: CEM-II/A-
M). (More than 250x330 & less than
250x400 or equivalent).g) in 6th Floor
30.h Civil N/A Supplying, fitting and fixing glazed Sqm. 490.77
wall tiles (local/equivalent foreign
made) with on 20 mm thick cement
sand (F.M. 1.2) mortar (1:3) base
and raking out the joints with white
cement including cutting, laying and
hire charge of machine and finishing
with care etc. including water,
electricity and other charges
complete all respect accepted by the
Engineer. (Cement: CEM-II/A-M)
Coloured glazed wall tiles of different
sizes (Sample approved by the
engineer in charge))e and accepted
by the Engineer.(Cement: CEM-II/A-
M). (More than 250x330 & less than
250x400 or equivalent).h) in 7th Floor
30.i Civil N/A Supplying, fitting and fixing glazed Sqm. 490.77
wall tiles (local/equivalent foreign
made) with on 20 mm thick cement
sand (F.M. 1.2) mortar (1:3) base
and raking out the joints with white
cement including cutting, laying and
hire charge of machine and finishing
with care etc. including water,
electricity and other charges
complete all respect accepted by the
Engineer. (Cement: CEM-II/A-M)
Coloured glazed wall tiles of different
sizes (Sample approved by the
engineer in charge))e and accepted
by the Engineer.(Cement: CEM-II/A-
M). (More than 250x330 & less than
250x400 or equivalent).i) in 8th Floor
30.j Civil N/A Supplying, fitting and fixing glazed Sqm. 490.77
wall tiles (local/equivalent foreign
made) with on 20 mm thick cement
sand (F.M. 1.2) mortar (1:3) base
and raking out the joints with white
cement including cutting, laying and
hire charge of machine and finishing
with care etc. including water,
electricity and other charges
complete all respect accepted by the
Engineer. (Cement: CEM-II/A-M)
Coloured glazed wall tiles of different
sizes (Sample approved by the
engineer in charge))e and accepted
by the Engineer.(Cement: CEM-II/A-
M). (More than 250x330 & less than
250x400 or equivalent).j) in 9th Floor
30.k Civil N/A Supplying, fitting and fixing glazed Sqm. 490.77
wall tiles (local/equivalent foreign
made) with on 20 mm thick cement
sand (F.M. 1.2) mortar (1:3) base
and raking out the joints with white
cement including cutting, laying and
hire charge of machine and finishing
with care etc. including water,
electricity and other charges
complete all respect accepted by the
Engineer. (Cement: CEM-II/A-M)
Coloured glazed wall tiles of different
sizes (Sample approved by the
engineer in charge))e and accepted
by the Engineer.(Cement: CEM-II/A-
M). (More than 250x330 & less than
250x400 or equivalent).k) in 10th
Floor
30.l Civil N/A Supplying, fitting and fixing glazed Sqm. 490.77
wall tiles (local/equivalent foreign
made) with on 20 mm thick cement
sand (F.M. 1.2) mortar (1:3) base
and raking out the joints with white
cement including cutting, laying and
hire charge of machine and finishing
with care etc. including water,
electricity and other charges
complete all respect accepted by the
Engineer. (Cement: CEM-II/A-M)
Coloured glazed wall tiles of different
sizes (Sample approved by the
engineer in charge))e and accepted
by the Engineer.(Cement: CEM-II/A-
M). (More than 250x330 & less than
250x400 or equivalent).l) in 11th Floor
30.m Civil N/A Supplying, fitting and fixing glazed Sqm. 490.77
wall tiles (local/equivalent foreign
made) with on 20 mm thick cement
sand (F.M. 1.2) mortar (1:3) base
and raking out the joints with white
cement including cutting, laying and
hire charge of machine and finishing
with care etc. including water,
electricity and other charges
complete all respect accepted by the
Engineer. (Cement: CEM-II/A-M)
Coloured glazed wall tiles of different
sizes (Sample approved by the
engineer in charge))e and accepted
by the Engineer.(Cement: CEM-II/A-
M). (More than 250x330 & less than
250x400 or equivalent).m) in 12th
Floor
30.n Civil N/A Supplying, fitting and fixing glazed Sqm. 490.77
wall tiles (local/equivalent foreign
made) with on 20 mm thick cement
sand (F.M. 1.2) mortar (1:3) base
and raking out the joints with white
cement including cutting, laying and
hire charge of machine and finishing
with care etc. including water,
electricity and other charges
complete all respect accepted by the
Engineer. (Cement: CEM-II/A-M)
Coloured glazed wall tiles of different
sizes (Sample approved by the
engineer in charge))e and accepted
by the Engineer.(Cement: CEM-II/A-
M). (More than 250x330 & less than
250x400 or equivalent).n) in 13th
Floor
30.o Civil N/A Supplying, fitting and fixing glazed Sqm. 490.77
wall tiles (local/equivalent foreign
made) with on 20 mm thick cement
sand (F.M. 1.2) mortar (1:3) base
and raking out the joints with white
cement including cutting, laying and
hire charge of machine and finishing
with care etc. including water,
electricity and other charges
complete all respect accepted by the
Engineer. (Cement: CEM-II/A-M)
Coloured glazed wall tiles of different
sizes (Sample approved by the
engineer in charge))e and accepted
by the Engineer.(Cement: CEM-II/A-
M). (More than 250x330 & less than
250x400 or equivalent).o) in 14th
Floor
30.p Civil N/A Supplying, fitting and fixing glazed Sqm. 490.77
wall tiles (local/equivalent foreign
made) with on 20 mm thick cement
sand (F.M. 1.2) mortar (1:3) base
and raking out the joints with white
cement including cutting, laying and
hire charge of machine and finishing
with care etc. including water,
electricity and other charges
complete all respect accepted by the
Engineer. (Cement: CEM-II/A-M)
Coloured glazed wall tiles of different
sizes (Sample approved by the
engineer in charge))e and accepted
by the Engineer.(Cement: CEM-II/A-
M). (More than 250x330 & less than
250x400 or equivalent).p) in 15th
Floor
30.q Civil N/A Supplying, fitting and fixing glazed Sqm. 490.77
wall tiles (local/equivalent foreign
made) with on 20 mm thick cement
sand (F.M. 1.2) mortar (1:3) base
and raking out the joints with white
cement including cutting, laying and
hire charge of machine and finishing
with care etc. including water,
electricity and other charges
complete all respect accepted by the
Engineer. (Cement: CEM-II/A-M)
Coloured glazed wall tiles of different
sizes (Sample approved by the
engineer in charge))e and accepted
by the Engineer.(Cement: CEM-II/A-
M). (More than 250x330 & less than
250x400 or equivalent).q) in 16th
Floor
30.r Civil N/A Supplying, fitting and fixing glazed Sqm. 35.00
wall tiles (local/equivalent foreign
made) with on 20 mm thick cement
sand (F.M. 1.2) mortar (1:3) base
and raking out the joints with white
cement including cutting, laying and
hire charge of machine and finishing
with care etc. including water,
electricity and other charges
complete all respect accepted by the
Engineer. (Cement: CEM-II/A-M)
Coloured glazed wall tiles of different
sizes (Sample approved by the
engineer in charge))e and accepted
by the Engineer.(Cement: CEM-II/A-
M). (More than 250x330 & less than
250x400 or equivalent).r) in 17th
Floor
31.a Civil N/A Supplying, fitting and fixing Unglazed Sqm. 10.00
homogeneous Toilet floor tiles
(local/equivalent foreign made) with
cement sand (F.M. 1.2) mortar (1:4)
base and raking out the joints with
white cement including cutting and
laying the tiles in proper way and
finishing with care etc. all complete
and accepted by the Engineer.
(Cement: CEM-II/A-M). GP
(homogeneous) 300 x 300 mm floor
tiles (Sample approved by the
engineer in charge) and accepted by
the Engineer.(Cement: CEM-II/A-
M).a) in Ground & Basement Floor
31.b Civil N/A Supplying, fitting and fixing Unglazed Sqm. 30.00
homogeneous Toilet floor tiles
(local/equivalent foreign made) with
cement sand (F.M. 1.2) mortar (1:4)
base and raking out the joints with
white cement including cutting and
laying the tiles in proper way and
finishing with care etc. all complete
and accepted by the Engineer.
(Cement: CEM-II/A-M). GP
(homogeneous) 300 x 300 mm floor
tiles (Sample approved by the
engineer in charge) and accepted by
the Engineer.(Cement: CEM-II/A-
M).b) in 1st Floor
31.c Civil N/A Supplying, fitting and fixing Unglazed Sqm. 76.82
homogeneous Toilet floor tiles
(local/equivalent foreign made) with
cement sand (F.M. 1.2) mortar (1:4)
base and raking out the joints with
white cement including cutting and
laying the tiles in proper way and
finishing with care etc. all complete
and accepted by the Engineer.
(Cement: CEM-II/A-M). GP
(homogeneous) 300 x 300 mm floor
tiles (Sample approved by the
engineer in charge) and accepted by
the Engineer.(Cement: CEM-II/A-
M).c) in 2nd Floor
31.d Civil N/A Supplying, fitting and fixing Unglazed Sqm. 76.82
homogeneous Toilet floor tiles
(local/equivalent foreign made) with
cement sand (F.M. 1.2) mortar (1:4)
base and raking out the joints with
white cement including cutting and
laying the tiles in proper way and
finishing with care etc. all complete
and accepted by the Engineer.
(Cement: CEM-II/A-M). GP
(homogeneous) 300 x 300 mm floor
tiles (Sample approved by the
engineer in charge) and accepted by
the Engineer.(Cement: CEM-II/A-
M).d) in 3rd Floor
31.e Civil N/A Supplying, fitting and fixing Unglazed Sqm. 76.82
homogeneous Toilet floor tiles
(local/equivalent foreign made) with
cement sand (F.M. 1.2) mortar (1:4)
base and raking out the joints with
white cement including cutting and
laying the tiles in proper way and
finishing with care etc. all complete
and accepted by the Engineer.
(Cement: CEM-II/A-M). GP
(homogeneous) 300 x 300 mm floor
tiles (Sample approved by the
engineer in charge) and accepted by
the Engineer.(Cement: CEM-II/A-
M).e) in 4th Floor
31.f Civil N/A Supplying, fitting and fixing Unglazed Sqm. 76.82
homogeneous Toilet floor tiles
(local/equivalent foreign made) with
cement sand (F.M. 1.2) mortar (1:4)
base and raking out the joints with
white cement including cutting and
laying the tiles in proper way and
finishing with care etc. all complete
and accepted by the Engineer.
(Cement: CEM-II/A-M). GP
(homogeneous) 300 x 300 mm floor
tiles (Sample approved by the
engineer in charge) and accepted by
the Engineer.(Cement: CEM-II/A-
M).f) in 5th Floor
31.g Civil N/A Supplying, fitting and fixing Unglazed Sqm. 76.82
homogeneous Toilet floor tiles
(local/equivalent foreign made) with
cement sand (F.M. 1.2) mortar (1:4)
base and raking out the joints with
white cement including cutting and
laying the tiles in proper way and
finishing with care etc. all complete
and accepted by the Engineer.
(Cement: CEM-II/A-M). GP
(homogeneous) 300 x 300 mm floor
tiles (Sample approved by the
engineer in charge) and accepted by
the Engineer.(Cement: CEM-II/A-
M).g) in 6th Floor
31.h Civil N/A Supplying, fitting and fixing Unglazed Sqm. 76.82
homogeneous Toilet floor tiles
(local/equivalent foreign made) with
cement sand (F.M. 1.2) mortar (1:4)
base and raking out the joints with
white cement including cutting and
laying the tiles in proper way and
finishing with care etc. all complete
and accepted by the Engineer.
(Cement: CEM-II/A-M). GP
(homogeneous) 300 x 300 mm floor
tiles (Sample approved by the
engineer in charge) and accepted by
the Engineer.(Cement: CEM-II/A-
M).h) in 7th Floor
31.i Civil N/A Supplying, fitting and fixing Unglazed Sqm. 76.82
homogeneous Toilet floor tiles
(local/equivalent foreign made) with
cement sand (F.M. 1.2) mortar (1:4)
base and raking out the joints with
white cement including cutting and
laying the tiles in proper way and
finishing with care etc. all complete
and accepted by the Engineer.
(Cement: CEM-II/A-M). GP
(homogeneous) 300 x 300 mm floor
tiles (Sample approved by the
engineer in charge) and accepted by
the Engineer.(Cement: CEM-II/A-
M).i) in 8th Floor
31.j Civil N/A Supplying, fitting and fixing Unglazed Sqm. 76.82
homogeneous Toilet floor tiles
(local/equivalent foreign made) with
cement sand (F.M. 1.2) mortar (1:4)
base and raking out the joints with
white cement including cutting and
laying the tiles in proper way and
finishing with care etc. all complete
and accepted by the Engineer.
(Cement: CEM-II/A-M). GP
(homogeneous) 300 x 300 mm floor
tiles (Sample approved by the
engineer in charge) and accepted by
the Engineer.(Cement: CEM-II/A-
M).j) in 9th Floor
31.k Civil N/A Supplying, fitting and fixing Unglazed Sqm. 76.82
homogeneous Toilet floor tiles
(local/equivalent foreign made) with
cement sand (F.M. 1.2) mortar (1:4)
base and raking out the joints with
white cement including cutting and
laying the tiles in proper way and
finishing with care etc. all complete
and accepted by the Engineer.
(Cement: CEM-II/A-M). GP
(homogeneous) 300 x 300 mm floor
tiles (Sample approved by the
engineer in charge) and accepted by
the Engineer.(Cement: CEM-II/A-
M).k) in 10th Floor
31.l Civil N/A Supplying, fitting and fixing Unglazed Sqm. 76.82
homogeneous Toilet floor tiles
(local/equivalent foreign made) with
cement sand (F.M. 1.2) mortar (1:4)
base and raking out the joints with
white cement including cutting and
laying the tiles in proper way and
finishing with care etc. all complete
and accepted by the Engineer.
(Cement: CEM-II/A-M). GP
(homogeneous) 300 x 300 mm floor
tiles (Sample approved by the
engineer in charge) and accepted by
the Engineer.(Cement: CEM-II/A-
M).l) in 11th Floor
31.m Civil N/A Supplying, fitting and fixing Unglazed Sqm. 76.82
homogeneous Toilet floor tiles
(local/equivalent foreign made) with
cement sand (F.M. 1.2) mortar (1:4)
base and raking out the joints with
white cement including cutting and
laying the tiles in proper way and
finishing with care etc. all complete
and accepted by the Engineer.
(Cement: CEM-II/A-M). GP
(homogeneous) 300 x 300 mm floor
tiles (Sample approved by the
engineer in charge) and accepted by
the Engineer.(Cement: CEM-II/A-
M).m) in 12th Floor
31.n Civil N/A Supplying, fitting and fixing Unglazed Sqm. 76.82
homogeneous Toilet floor tiles
(local/equivalent foreign made) with
cement sand (F.M. 1.2) mortar (1:4)
base and raking out the joints with
white cement including cutting and
laying the tiles in proper way and
finishing with care etc. all complete
and accepted by the Engineer.
(Cement: CEM-II/A-M). GP
(homogeneous) 300 x 300 mm floor
tiles (Sample approved by the
engineer in charge) and accepted by
the Engineer.(Cement: CEM-II/A-
M).n) in 13th Floor
31.o Civil N/A Supplying, fitting and fixing Unglazed Sqm. 76.82
homogeneous Toilet floor tiles
(local/equivalent foreign made) with
cement sand (F.M. 1.2) mortar (1:4)
base and raking out the joints with
white cement including cutting and
laying the tiles in proper way and
finishing with care etc. all complete
and accepted by the Engineer.
(Cement: CEM-II/A-M). GP
(homogeneous) 300 x 300 mm floor
tiles (Sample approved by the
engineer in charge) and accepted by
the Engineer.(Cement: CEM-II/A-
M).o) in 14th Floor
31.p Civil N/A Supplying, fitting and fixing Unglazed Sqm. 76.82
homogeneous Toilet floor tiles
(local/equivalent foreign made) with
cement sand (F.M. 1.2) mortar (1:4)
base and raking out the joints with
white cement including cutting and
laying the tiles in proper way and
finishing with care etc. all complete
and accepted by the Engineer.
(Cement: CEM-II/A-M). GP
(homogeneous) 300 x 300 mm floor
tiles (Sample approved by the
engineer in charge) and accepted by
the Engineer.(Cement: CEM-II/A-
M).p) in 15th Floor
31.q Civil N/A Supplying, fitting and fixing Unglazed Sqm. 76.82
homogeneous Toilet floor tiles
(local/equivalent foreign made) with
cement sand (F.M. 1.2) mortar (1:4)
base and raking out the joints with
white cement including cutting and
laying the tiles in proper way and
finishing with care etc. all complete
and accepted by the Engineer.
(Cement: CEM-II/A-M). GP
(homogeneous) 300 x 300 mm floor
tiles (Sample approved by the
engineer in charge) and accepted by
the Engineer.(Cement: CEM-II/A-
M).q) in 16th Floor
31.r Civil N/A Supplying, fitting and fixing Unglazed Sqm. 99.76
homogeneous Toilet floor tiles
(local/equivalent foreign made) with
cement sand (F.M. 1.2) mortar (1:4)
base and raking out the joints with
white cement including cutting and
laying the tiles in proper way and
finishing with care etc. all complete
and accepted by the Engineer.
(Cement: CEM-II/A-M). GP
(homogeneous) 300 x 300 mm floor
tiles (Sample approved by the
engineer in charge) and accepted by
the Engineer.(Cement: CEM-II/A-
M).r) in 17th Floor (in chilakota)
32.a Civil N/A Supplying, fitting and fixing glazed Sqm. 15.00
homogeneous Kitchen floor tiles
(local/equivalent foreign made) with
cement sand (F.M. 1.2) mortar (1:4)
base and raking out the joints with
white cement including cutting and
laying the tiles in proper way and
finishing with care etc. all complete
and accepted by the Engineer.
(Cement: CEM-II/A-M). GP
(homogeneous) 400x400 floor tiles
(Sample approved by the engineer in
charge).a) in Ground & Basement
Floor
32.b Civil N/A Supplying, fitting and fixing glazed Sqm. 45.00
homogeneous Kitchen floor tiles
(local/equivalent foreign made) with
cement sand (F.M. 1.2) mortar (1:4)
base and raking out the joints with
white cement including cutting and
laying the tiles in proper way and
finishing with care etc. all complete
and accepted by the Engineer.
(Cement: CEM-II/A-M). GP
(homogeneous) 400x400 floor tiles
(Sample approved by the engineer in
charge).b) in 1st Floor
32.c Civil N/A Supplying, fitting and fixing glazed Sqm. 61.57
homogeneous Kitchen floor tiles
(local/equivalent foreign made) with
cement sand (F.M. 1.2) mortar (1:4)
base and raking out the joints with
white cement including cutting and
laying the tiles in proper way and
finishing with care etc. all complete
and accepted by the Engineer.
(Cement: CEM-II/A-M). GP
(homogeneous) 400x400 floor tiles
(Sample approved by the engineer in
charge).c) in 2nd Floor
32.d Civil N/A Supplying, fitting and fixing glazed Sqm. 61.57
homogeneous Kitchen floor tiles
(local/equivalent foreign made) with
cement sand (F.M. 1.2) mortar (1:4)
base and raking out the joints with
white cement including cutting and
laying the tiles in proper way and
finishing with care etc. all complete
and accepted by the Engineer.
(Cement: CEM-II/A-M). GP
(homogeneous) 400x400 floor tiles
(Sample approved by the engineer in
charge).d) in 3rd Floor
32.e Civil N/A Supplying, fitting and fixing glazed Sqm. 61.57
homogeneous Kitchen floor tiles
(local/equivalent foreign made) with
cement sand (F.M. 1.2) mortar (1:4)
base and raking out the joints with
white cement including cutting and
laying the tiles in proper way and
finishing with care etc. all complete
and accepted by the Engineer.
(Cement: CEM-II/A-M). GP
(homogeneous) 400x400 floor tiles
(Sample approved by the engineer in
charge).e) in 4th Floor
32.f Civil N/A Supplying, fitting and fixing glazed Sqm. 61.57
homogeneous Kitchen floor tiles
(local/equivalent foreign made) with
cement sand (F.M. 1.2) mortar (1:4)
base and raking out the joints with
white cement including cutting and
laying the tiles in proper way and
finishing with care etc. all complete
and accepted by the Engineer.
(Cement: CEM-II/A-M). GP
(homogeneous) 400x400 floor tiles
(Sample approved by the engineer in
charge). f) in 5th Floor
32.g Civil N/A Supplying, fitting and fixing glazed Sqm. 61.57
homogeneous Kitchen floor tiles
(local/equivalent foreign made) with
cement sand (F.M. 1.2) mortar (1:4)
base and raking out the joints with
white cement including cutting and
laying the tiles in proper way and
finishing with care etc. all complete
and accepted by the Engineer.
(Cement: CEM-II/A-M). GP
(homogeneous) 400x400 floor tiles
(Sample approved by the engineer in
charge).g) in 6th Floor
32.h Civil N/A Supplying, fitting and fixing glazed Sqm. 61.57
homogeneous Kitchen floor tiles
(local/equivalent foreign made) with
cement sand (F.M. 1.2) mortar (1:4)
base and raking out the joints with
white cement including cutting and
laying the tiles in proper way and
finishing with care etc. all complete
and accepted by the Engineer.
(Cement: CEM-II/A-M). GP
(homogeneous) 400x400 floor tiles
(Sample approved by the engineer in
charge).h) in 7th Floor
32.i Civil N/A Supplying, fitting and fixing glazed Sqm. 61.57
homogeneous Kitchen floor tiles
(local/equivalent foreign made) with
cement sand (F.M. 1.2) mortar (1:4)
base and raking out the joints with
white cement including cutting and
laying the tiles in proper way and
finishing with care etc. all complete
and accepted by the Engineer.
(Cement: CEM-II/A-M). GP
(homogeneous) 400x400 floor tiles
(Sample approved by the engineer in
charge).i) in 8th Floor
32.j Civil N/A Supplying, fitting and fixing glazed Sqm. 61.57
homogeneous Kitchen floor tiles
(local/equivalent foreign made) with
cement sand (F.M. 1.2) mortar (1:4)
base and raking out the joints with
white cement including cutting and
laying the tiles in proper way and
finishing with care etc. all complete
and accepted by the Engineer.
(Cement: CEM-II/A-M). GP
(homogeneous) 400x400 floor tiles
(Sample approved by the engineer in
charge).j) in 9th Floor
32.k Civil N/A Supplying, fitting and fixing glazed Sqm. 61.57
homogeneous Kitchen floor tiles
(local/equivalent foreign made) with
cement sand (F.M. 1.2) mortar (1:4)
base and raking out the joints with
white cement including cutting and
laying the tiles in proper way and
finishing with care etc. all complete
and accepted by the Engineer.
(Cement: CEM-II/A-M). GP
(homogeneous) 400x400 floor tiles
(Sample approved by the engineer in
charge).k) in 10th Floor
32.l Civil N/A Supplying, fitting and fixing glazed Sqm. 61.57
homogeneous Kitchen floor tiles
(local/equivalent foreign made) with
cement sand (F.M. 1.2) mortar (1:4)
base and raking out the joints with
white cement including cutting and
laying the tiles in proper way and
finishing with care etc. all complete
and accepted by the Engineer.
(Cement: CEM-II/A-M). GP
(homogeneous) 400x400 floor tiles
(Sample approved by the engineer in
charge).l) in 11th Floor
32.m Civil N/A Supplying, fitting and fixing glazed Sqm. 61.57
homogeneous Kitchen floor tiles
(local/equivalent foreign made) with
cement sand (F.M. 1.2) mortar (1:4)
base and raking out the joints with
white cement including cutting and
laying the tiles in proper way and
finishing with care etc. all complete
and accepted by the Engineer.
(Cement: CEM-II/A-M). GP
(homogeneous) 400x400 floor tiles
(Sample approved by the engineer in
charge).m) in 12th Floor
32.n Civil N/A Supplying, fitting and fixing glazed Sqm. 61.57
homogeneous Kitchen floor tiles
(local/equivalent foreign made) with
cement sand (F.M. 1.2) mortar (1:4)
base and raking out the joints with
white cement including cutting and
laying the tiles in proper way and
finishing with care etc. all complete
and accepted by the Engineer.
(Cement: CEM-II/A-M). GP
(homogeneous) 400x400 floor tiles
(Sample approved by the engineer in
charge).n) in 13th Floor
32.o Civil N/A Supplying, fitting and fixing glazed Sqm. 61.57
homogeneous Kitchen floor tiles
(local/equivalent foreign made) with
cement sand (F.M. 1.2) mortar (1:4)
base and raking out the joints with
white cement including cutting and
laying the tiles in proper way and
finishing with care etc. all complete
and accepted by the Engineer.
(Cement: CEM-II/A-M). GP
(homogeneous) 400x400 floor tiles
(Sample approved by the engineer in
charge).o) in 14th Floor
32.p Civil N/A Supplying, fitting and fixing glazed Sqm. 61.57
homogeneous Kitchen floor tiles
(local/equivalent foreign made) with
cement sand (F.M. 1.2) mortar (1:4)
base and raking out the joints with
white cement including cutting and
laying the tiles in proper way and
finishing with care etc. all complete
and accepted by the Engineer.
(Cement: CEM-II/A-M). GP
(homogeneous) 400x400 floor tiles
(Sample approved by the engineer in
charge).p) in 15th Floor
32.q Civil N/A Supplying, fitting and fixing glazed Sqm. 61.57
homogeneous Kitchen floor tiles
(local/equivalent foreign made) with
cement sand (F.M. 1.2) mortar (1:4)
base and raking out the joints with
white cement including cutting and
laying the tiles in proper way and
finishing with care etc. all complete
and accepted by the Engineer.
(Cement: CEM-II/A-M). GP
(homogeneous) 400x400 floor tiles
(Sample approved by the engineer in
charge).q) in 16th Floor
32.r Civil N/A Supplying, fitting and fixing glazed Sqm. 39.87
homogeneous Kitchen floor tiles
(local/equivalent foreign made) with
cement sand (F.M. 1.2) mortar (1:4)
base and raking out the joints with
white cement including cutting and
laying the tiles in proper way and
finishing with care etc. all complete
and accepted by the Engineer.
(Cement: CEM-II/A-M). GP
(homogeneous) 400x400 floor tiles
(Sample approved by the engineer in
charge).r) in 17th Floor
33.a Civil N/A Supplying, fitting and fixing mirror Sqm. 35.00
polished homogeneous floor tiles
(local/equivalent foreign made) with
cement sand (F.M. 1.2) mortar (1:4)
base and raking out the joints with
white cement including cutting and
laying the tiles in proper way and
finishing with care etc. all complete
and accepted by the Engineer.
(Cement: CEM-II/A-M). GP (mirror
polished) 300 x 300 mm floor tiles
(Sample approved by the engineer in
charge)a) in Ground & Basement
Floor
33.b Civil N/A Supplying, fitting and fixing mirror Sqm. 25.00
polished homogeneous floor tiles
(local/equivalent foreign made) with
cement sand (F.M. 1.2) mortar (1:4)
base and raking out the joints with
white cement including cutting and
laying the tiles in proper way and
finishing with care etc. all complete
and accepted by the Engineer.
(Cement: CEM-II/A-M). GP (mirror
polished) 300 x 300 mm floor tiles
(Sample approved by the engineer in
charge) b) in 1st Floor
33.c Civil N/A Supplying, fitting and fixing mirror Sqm. 106.32
polished homogeneous floor tiles
(local/equivalent foreign made) with
cement sand (F.M. 1.2) mortar (1:4)
base and raking out the joints with
white cement including cutting and
laying the tiles in proper way and
finishing with care etc. all complete
and accepted by the Engineer.
(Cement: CEM-II/A-M). GP (mirror
polished) 300 x 300 mm floor tiles
(Sample approved by the engineer in
charge) c) in 2nd Floor
33.d Civil N/A Supplying, fitting and fixing mirror Sqm. 106.32
polished homogeneous floor tiles
(local/equivalent foreign made) with
cement sand (F.M. 1.2) mortar (1:4)
base and raking out the joints with
white cement including cutting and
laying the tiles in proper way and
finishing with care etc. all complete
and accepted by the Engineer.
(Cement: CEM-II/A-M). GP (mirror
polished) 300 x 300 mm floor tiles
(Sample approved by the engineer in
charge)d) in 3rd Floor
33.e Civil N/A Supplying, fitting and fixing mirror Sqm. 106.32
polished homogeneous floor tiles
(local/equivalent foreign made) with
cement sand (F.M. 1.2) mortar (1:4)
base and raking out the joints with
white cement including cutting and
laying the tiles in proper way and
finishing with care etc. all complete
and accepted by the Engineer.
(Cement: CEM-II/A-M). GP (mirror
polished) 300 x 300 mm floor tiles
(Sample approved by the engineer in
charge)e) in 4th Floor
33.f Civil N/A Supplying, fitting and fixing mirror Sqm. 106.32
polished homogeneous floor tiles
(local/equivalent foreign made) with
cement sand (F.M. 1.2) mortar (1:4)
base and raking out the joints with
white cement including cutting and
laying the tiles in proper way and
finishing with care etc. all complete
and accepted by the Engineer.
(Cement: CEM-II/A-M). GP (mirror
polished) 300 x 300 mm floor tiles
(Sample approved by the engineer in
charge)f) in 5th Floor
33.g Civil N/A Supplying, fitting and fixing mirror Sqm. 106.32
polished homogeneous floor tiles
(local/equivalent foreign made) with
cement sand (F.M. 1.2) mortar (1:4)
base and raking out the joints with
white cement including cutting and
laying the tiles in proper way and
finishing with care etc. all complete
and accepted by the Engineer.
(Cement: CEM-II/A-M). GP (mirror
polished) 300 x 300 mm floor tiles
(Sample approved by the engineer in
charge) g) in 6th Floor
33.h Civil N/A Supplying, fitting and fixing mirror Sqm. 106.32
polished homogeneous floor tiles
(local/equivalent foreign made) with
cement sand (F.M. 1.2) mortar (1:4)
base and raking out the joints with
white cement including cutting and
laying the tiles in proper way and
finishing with care etc. all complete
and accepted by the Engineer.
(Cement: CEM-II/A-M). GP (mirror
polished) 300 x 300 mm floor tiles
(Sample approved by the engineer in
charge) h) in 7th Floor
33.i Civil N/A Supplying, fitting and fixing mirror Sqm. 106.32
polished homogeneous floor tiles
(local/equivalent foreign made) with
cement sand (F.M. 1.2) mortar (1:4)
base and raking out the joints with
white cement including cutting and
laying the tiles in proper way and
finishing with care etc. all complete
and accepted by the Engineer.
(Cement: CEM-II/A-M). GP (mirror
polished) 300 x 300 mm floor tiles
(Sample approved by the engineer in
charge) i) in 8th Floor
33.j Civil N/A Supplying, fitting and fixing mirror Sqm. 106.32
polished homogeneous floor tiles
(local/equivalent foreign made) with
cement sand (F.M. 1.2) mortar (1:4)
base and raking out the joints with
white cement including cutting and
laying the tiles in proper way and
finishing with care etc. all complete
and accepted by the Engineer.
(Cement: CEM-II/A-M). GP (mirror
polished) 300 x 300 mm floor tiles
(Sample approved by the engineer in
charge) j) in 9th Floor
33.k Civil N/A Supplying, fitting and fixing mirror Sqm. 106.32
polished homogeneous floor tiles
(local/equivalent foreign made) with
cement sand (F.M. 1.2) mortar (1:4)
base and raking out the joints with
white cement including cutting and
laying the tiles in proper way and
finishing with care etc. all complete
and accepted by the Engineer.
(Cement: CEM-II/A-M). GP (mirror
polished) 300 x 300 mm floor tiles
(Sample approved by the engineer in
charge) k) in 10th Floor
33.l Civil N/A Supplying, fitting and fixing mirror Sqm. 106.32
polished homogeneous floor tiles
(local/equivalent foreign made) with
cement sand (F.M. 1.2) mortar (1:4)
base and raking out the joints with
white cement including cutting and
laying the tiles in proper way and
finishing with care etc. all complete
and accepted by the Engineer.
(Cement: CEM-II/A-M). GP (mirror
polished) 300 x 300 mm floor tiles
(Sample approved by the engineer in
charge) l) in 11th Floor
33.m Civil N/A Supplying, fitting and fixing mirror Sqm. 106.32
polished homogeneous floor tiles
(local/equivalent foreign made) with
cement sand (F.M. 1.2) mortar (1:4)
base and raking out the joints with
white cement including cutting and
laying the tiles in proper way and
finishing with care etc. all complete
and accepted by the Engineer.
(Cement: CEM-II/A-M). GP (mirror
polished) 300 x 300 mm floor tiles
(Sample approved by the engineer in
charge) m) in 12th Floor
33.n Civil N/A Supplying, fitting and fixing mirror Sqm. 106.32
polished homogeneous floor tiles
(local/equivalent foreign made) with
cement sand (F.M. 1.2) mortar (1:4)
base and raking out the joints with
white cement including cutting and
laying the tiles in proper way and
finishing with care etc. all complete
and accepted by the Engineer.
(Cement: CEM-II/A-M). GP (mirror
polished) 300 x 300 mm floor tiles
(Sample approved by the engineer in
charge) n) in 13th Floor
33.o Civil N/A Supplying, fitting and fixing mirror Sqm. 106.32
polished homogeneous floor tiles
(local/equivalent foreign made) with
cement sand (F.M. 1.2) mortar (1:4)
base and raking out the joints with
white cement including cutting and
laying the tiles in proper way and
finishing with care etc. all complete
and accepted by the Engineer.
(Cement: CEM-II/A-M). GP (mirror
polished) 300 x 300 mm floor tiles
(Sample approved by the engineer in
charge) o) in 14th Floor
33.p Civil N/A Supplying, fitting and fixing mirror Sqm. 106.32
polished homogeneous floor tiles
(local/equivalent foreign made) with
cement sand (F.M. 1.2) mortar (1:4)
base and raking out the joints with
white cement including cutting and
laying the tiles in proper way and
finishing with care etc. all complete
and accepted by the Engineer.
(Cement: CEM-II/A-M). GP (mirror
polished) 300 x 300 mm floor tiles
(Sample approved by the engineer in
charge) p) in 15th Floor
33.q Civil N/A Supplying, fitting and fixing mirror Sqm. 106.32
polished homogeneous floor tiles
(local/equivalent foreign made) with
cement sand (F.M. 1.2) mortar (1:4)
base and raking out the joints with
white cement including cutting and
laying the tiles in proper way and
finishing with care etc. all complete
and accepted by the Engineer.
(Cement: CEM-II/A-M). GP (mirror
polished) 300 x 300 mm floor tiles
(Sample approved by the engineer in
charge) q) in 16th Floor
33.r Civil N/A Supplying, fitting and fixing mirror Sqm. 56.32
polished homogeneous floor tiles
(local/equivalent foreign made) with
cement sand (F.M. 1.2) mortar (1:4)
base and raking out the joints with
white cement including cutting and
laying the tiles in proper way and
finishing with care etc. all complete
and accepted by the Engineer.
(Cement: CEM-II/A-M). GP (mirror
polished) 300 x 300 mm floor tiles
(Sample approved by the engineer in
charge) r) in 17th Floor
34.a Civil N/A Supplying, fitting and fixing mirror Sqm. 50.00
polished homogeneous floor tiles
(local/equivalent foreign made) with
cement sand (F.M. 1.2) mortar (1:4)
base and raking out the joints with
white cement including cutting and
laying the tiles in proper way and
finishing with care etc. all complete
and accepted by the Engineer.
(Cement: CEM-II/A-M). GP (mirror
polished) 400 x 400 mm floor tiles
(Sample approved by the engineer in
charge) a) in Ground & Basement
Floor
34.b Civil N/A Supplying, fitting and fixing mirror Sqm. 40.00
polished homogeneous floor tiles
(local/equivalent foreign made) with
cement sand (F.M. 1.2) mortar (1:4)
base and raking out the joints with
white cement including cutting and
laying the tiles in proper way and
finishing with care etc. all complete
and accepted by the Engineer.
(Cement: CEM-II/A-M). GP (mirror
polished) 400 x 400 mm floor tiles
(Sample approved by the engineer in
charge) b) in 1st Floor
34.c Civil N/A Supplying, fitting and fixing mirror Sqm. 423.88
polished homogeneous floor tiles
(local/equivalent foreign made) with
cement sand (F.M. 1.2) mortar (1:4)
base and raking out the joints with
white cement including cutting and
laying the tiles in proper way and
finishing with care etc. all complete
and accepted by the Engineer.
(Cement: CEM-II/A-M). GP (mirror
polished) 400 x 400 mm floor tiles
(Sample approved by the engineer in
charge) c) in 2nd Floor
34.d Civil N/A Supplying, fitting and fixing mirror Sqm. 423.88
polished homogeneous floor tiles
(local/equivalent foreign made) with
cement sand (F.M. 1.2) mortar (1:4)
base and raking out the joints with
white cement including cutting and
laying the tiles in proper way and
finishing with care etc. all complete
and accepted by the Engineer.
(Cement: CEM-II/A-M). GP (mirror
polished) 400 x 400 mm floor tiles
(Sample approved by the engineer in
charge) d) in 3rd Floor
34.e Civil N/A Supplying, fitting and fixing mirror Sqm. 423.88
polished homogeneous floor tiles
(local/equivalent foreign made) with
cement sand (F.M. 1.2) mortar (1:4)
base and raking out the joints with
white cement including cutting and
laying the tiles in proper way and
finishing with care etc. all complete
and accepted by the Engineer.
(Cement: CEM-II/A-M). GP (mirror
polished) 400 x 400 mm floor tiles
(Sample approved by the engineer in
charge) e) in 4th Floor
34.f Civil N/A Supplying, fitting and fixing mirror Sqm. 423.88
polished homogeneous floor tiles
(local/equivalent foreign made) with
cement sand (F.M. 1.2) mortar (1:4)
base and raking out the joints with
white cement including cutting and
laying the tiles in proper way and
finishing with care etc. all complete
and accepted by the Engineer.
(Cement: CEM-II/A-M). GP (mirror
polished) 400 x 400 mm floor tiles
(Sample approved by the engineer in
charge) f) in 5th Floor
34.g Civil N/A Supplying, fitting and fixing mirror Sqm. 423.88
polished homogeneous floor tiles
(local/equivalent foreign made) with
cement sand (F.M. 1.2) mortar (1:4)
base and raking out the joints with
white cement including cutting and
laying the tiles in proper way and
finishing with care etc. all complete
and accepted by the Engineer.
(Cement: CEM-II/A-M). GP (mirror
polished) 400 x 400 mm floor tiles
(Sample approved by the engineer in
charge) g) in 6th Floor
34.h Civil N/A Supplying, fitting and fixing mirror Sqm. 423.88
polished homogeneous floor tiles
(local/equivalent foreign made) with
cement sand (F.M. 1.2) mortar (1:4)
base and raking out the joints with
white cement including cutting and
laying the tiles in proper way and
finishing with care etc. all complete
and accepted by the Engineer.
(Cement: CEM-II/A-M). GP (mirror
polished) 400 x 400 mm floor tiles
(Sample approved by the engineer in
charge) h) in 7th Floor
34.i Civil N/A Supplying, fitting and fixing mirror Sqm. 423.88
polished homogeneous floor tiles
(local/equivalent foreign made) with
cement sand (F.M. 1.2) mortar (1:4)
base and raking out the joints with
white cement including cutting and
laying the tiles in proper way and
finishing with care etc. all complete
and accepted by the Engineer.
(Cement: CEM-II/A-M). GP (mirror
polished) 400 x 400 mm floor tiles
(Sample approved by the engineer in
charge) i) in 8th Floor
34.j Civil N/A Supplying, fitting and fixing mirror Sqm. 423.88
polished homogeneous floor tiles
(local/equivalent foreign made) with
cement sand (F.M. 1.2) mortar (1:4)
base and raking out the joints with
white cement including cutting and
laying the tiles in proper way and
finishing with care etc. all complete
and accepted by the Engineer.
(Cement: CEM-II/A-M). GP (mirror
polished) 400 x 400 mm floor tiles
(Sample approved by the engineer in
charge) j) in 9th Floor
34.k Civil N/A Supplying, fitting and fixing mirror Sqm. 423.88
polished homogeneous floor tiles
(local/equivalent foreign made) with
cement sand (F.M. 1.2) mortar (1:4)
base and raking out the joints with
white cement including cutting and
laying the tiles in proper way and
finishing with care etc. all complete
and accepted by the Engineer.
(Cement: CEM-II/A-M). GP (mirror
polished) 400 x 400 mm floor tiles
(Sample approved by the engineer in
charge) k) in 10th Floor
34.l Civil N/A Supplying, fitting and fixing mirror Sqm. 423.88
polished homogeneous floor tiles
(local/equivalent foreign made) with
cement sand (F.M. 1.2) mortar (1:4)
base and raking out the joints with
white cement including cutting and
laying the tiles in proper way and
finishing with care etc. all complete
and accepted by the Engineer.
(Cement: CEM-II/A-M). GP (mirror
polished) 400 x 400 mm floor tiles
(Sample approved by the engineer in
charge) l) in 11th Floor
34.m Civil N/A Supplying, fitting and fixing mirror Sqm. 423.88
polished homogeneous floor tiles
(local/equivalent foreign made) with
cement sand (F.M. 1.2) mortar (1:4)
base and raking out the joints with
white cement including cutting and
laying the tiles in proper way and
finishing with care etc. all complete
and accepted by the Engineer.
(Cement: CEM-II/A-M). GP (mirror
polished) 400 x 400 mm floor tiles
(Sample approved by the engineer in
charge) m) in 12th Floor
34.n Civil N/A Supplying, fitting and fixing mirror Sqm. 423.88
polished homogeneous floor tiles
(local/equivalent foreign made) with
cement sand (F.M. 1.2) mortar (1:4)
base and raking out the joints with
white cement including cutting and
laying the tiles in proper way and
finishing with care etc. all complete
and accepted by the Engineer.
(Cement: CEM-II/A-M). GP (mirror
polished) 400 x 400 mm floor tiles
(Sample approved by the engineer in
charge) n) in 13th Floor
34.o Civil N/A Supplying, fitting and fixing mirror Sqm. 423.88
polished homogeneous floor tiles
(local/equivalent foreign made) with
cement sand (F.M. 1.2) mortar (1:4)
base and raking out the joints with
white cement including cutting and
laying the tiles in proper way and
finishing with care etc. all complete
and accepted by the Engineer.
(Cement: CEM-II/A-M). GP (mirror
polished) 400 x 400 mm floor tiles
(Sample approved by the engineer in
charge) o) in 14th Floor
34.p Civil N/A Supplying, fitting and fixing mirror Sqm. 423.88
polished homogeneous floor tiles
(local/equivalent foreign made) with
cement sand (F.M. 1.2) mortar (1:4)
base and raking out the joints with
white cement including cutting and
laying the tiles in proper way and
finishing with care etc. all complete
and accepted by the Engineer.
(Cement: CEM-II/A-M). GP (mirror
polished) 400 x 400 mm floor tiles
(Sample approved by the engineer in
charge) p) in 15th Floor
34.q Civil N/A Supplying, fitting and fixing mirror Sqm. 423.88
polished homogeneous floor tiles
(local/equivalent foreign made) with
cement sand (F.M. 1.2) mortar (1:4)
base and raking out the joints with
white cement including cutting and
laying the tiles in proper way and
finishing with care etc. all complete
and accepted by the Engineer.
(Cement: CEM-II/A-M). GP (mirror
polished) 400 x 400 mm floor tiles
(Sample approved by the engineer in
charge) q) in 16th Floor
34.r Civil N/A Supplying, fitting and fixing mirror Sqm. 191.99
polished homogeneous floor tiles
(local/equivalent foreign made) with
cement sand (F.M. 1.2) mortar (1:4)
base and raking out the joints with
white cement including cutting and
laying the tiles in proper way and
finishing with care etc. all complete
and accepted by the Engineer.
(Cement: CEM-II/A-M). GP (mirror
polished) 400 x 400 mm floor tiles
(Sample approved by the engineer in
charge) r) in 17th Floor
35.a Civil N/A Supplying, fitting and fixing mirror Sqm. 30.00
polished homogeneous floor tiles
(local/equivalent foreign made) with
cement sand (F.M. 1.2) mortar (1:4)
base and raking out the joints with
white cement including cutting and
laying the tiles in proper way and
finishing with care etc. all complete
and accepted by the Engineer.
(Cement: CEM-II/A-M). GP (mirror
polished) 600 x 600 mm floor tiles
(Sample approved by the engineer in
charge) a) in Ground & Basement
Floor
35.b Civil N/A Supplying, fitting and fixing mirror Sqm. 70.00
polished homogeneous floor tiles
(local/equivalent foreign made) with
cement sand (F.M. 1.2) mortar (1:4)
base and raking out the joints with
white cement including cutting and
laying the tiles in proper way and
finishing with care etc. all complete
and accepted by the Engineer.
(Cement: CEM-II/A-M). GP (mirror
polished) 600 x 600 mm floor tiles
(Sample approved by the engineer in
charge) b) in 1st Floor
35.c Civil N/A Supplying, fitting and fixing mirror Sqm. 423.88
polished homogeneous floor tiles
(local/equivalent foreign made) with
cement sand (F.M. 1.2) mortar (1:4)
base and raking out the joints with
white cement including cutting and
laying the tiles in proper way and
finishing with care etc. all complete
and accepted by the Engineer.
(Cement: CEM-II/A-M). GP (mirror
polished) 600 x 600 mm floor tiles
(Sample approved by the engineer in
charge) c) in 2nd Floor
35.d Civil N/A Supplying, fitting and fixing mirror Sqm. 423.88
polished homogeneous floor tiles
(local/equivalent foreign made) with
cement sand (F.M. 1.2) mortar (1:4)
base and raking out the joints with
white cement including cutting and
laying the tiles in proper way and
finishing with care etc. all complete
and accepted by the Engineer.
(Cement: CEM-II/A-M). GP (mirror
polished) 600 x 600 mm floor tiles
(Sample approved by the engineer in
charge) d) in 3rd Floor
35.e Civil N/A Supplying, fitting and fixing mirror Sqm. 423.88
polished homogeneous floor tiles
(local/equivalent foreign made) with
cement sand (F.M. 1.2) mortar (1:4)
base and raking out the joints with
white cement including cutting and
laying the tiles in proper way and
finishing with care etc. all complete
and accepted by the Engineer.
(Cement: CEM-II/A-M). GP (mirror
polished) 600 x 600 mm floor tiles
(Sample approved by the engineer in
charge) e) in 4th Floor
35.f Civil N/A Supplying, fitting and fixing mirror Sqm. 423.88
polished homogeneous floor tiles
(local/equivalent foreign made) with
cement sand (F.M. 1.2) mortar (1:4)
base and raking out the joints with
white cement including cutting and
laying the tiles in proper way and
finishing with care etc. all complete
and accepted by the Engineer.
(Cement: CEM-II/A-M). GP (mirror
polished) 600 x 600 mm floor tiles
(Sample approved by the engineer in
charge) f) in 5th Floor
35.g Civil N/A Supplying, fitting and fixing mirror Sqm. 423.88
polished homogeneous floor tiles
(local/equivalent foreign made) with
cement sand (F.M. 1.2) mortar (1:4)
base and raking out the joints with
white cement including cutting and
laying the tiles in proper way and
finishing with care etc. all complete
and accepted by the Engineer.
(Cement: CEM-II/A-M). GP (mirror
polished) 600 x 600 mm floor tiles
(Sample approved by the engineer in
charge) g) in 6th Floor
35.h Civil N/A Supplying, fitting and fixing mirror Sqm. 423.88
polished homogeneous floor tiles
(local/equivalent foreign made) with
cement sand (F.M. 1.2) mortar (1:4)
base and raking out the joints with
white cement including cutting and
laying the tiles in proper way and
finishing with care etc. all complete
and accepted by the Engineer.
(Cement: CEM-II/A-M). GP (mirror
polished) 600 x 600 mm floor tiles
(Sample approved by the engineer in
charge) h) in 7th Floor
35.i Civil N/A Supplying, fitting and fixing mirror Sqm. 423.88
polished homogeneous floor tiles
(local/equivalent foreign made) with
cement sand (F.M. 1.2) mortar (1:4)
base and raking out the joints with
white cement including cutting and
laying the tiles in proper way and
finishing with care etc. all complete
and accepted by the Engineer.
(Cement: CEM-II/A-M). GP (mirror
polished) 600 x 600 mm floor tiles
(Sample approved by the engineer in
charge) i) in 8th Floor
35.j Civil N/A Supplying, fitting and fixing mirror Sqm. 423.88
polished homogeneous floor tiles
(local/equivalent foreign made) with
cement sand (F.M. 1.2) mortar (1:4)
base and raking out the joints with
white cement including cutting and
laying the tiles in proper way and
finishing with care etc. all complete
and accepted by the Engineer.
(Cement: CEM-II/A-M). GP (mirror
polished) 600 x 600 mm floor tiles
(Sample approved by the engineer in
charge) j) in 9th Floor
35.k Civil N/A Supplying, fitting and fixing mirror Sqm. 423.88
polished homogeneous floor tiles
(local/equivalent foreign made) with
cement sand (F.M. 1.2) mortar (1:4)
base and raking out the joints with
white cement including cutting and
laying the tiles in proper way and
finishing with care etc. all complete
and accepted by the Engineer.
(Cement: CEM-II/A-M). GP (mirror
polished) 600 x 600 mm floor tiles
(Sample approved by the engineer in
charge) k) in 10th Floor
35.l Civil N/A Supplying, fitting and fixing mirror Sqm. 423.88
polished homogeneous floor tiles
(local/equivalent foreign made) with
cement sand (F.M. 1.2) mortar (1:4)
base and raking out the joints with
white cement including cutting and
laying the tiles in proper way and
finishing with care etc. all complete
and accepted by the Engineer.
(Cement: CEM-II/A-M). GP (mirror
polished) 600 x 600 mm floor tiles
(Sample approved by the engineer in
charge) l) in 11th Floor
35.m Civil N/A Supplying, fitting and fixing mirror Sqm. 423.88
polished homogeneous floor tiles
(local/equivalent foreign made) with
cement sand (F.M. 1.2) mortar (1:4)
base and raking out the joints with
white cement including cutting and
laying the tiles in proper way and
finishing with care etc. all complete
and accepted by the Engineer.
(Cement: CEM-II/A-M). GP (mirror
polished) 600 x 600 mm floor tiles
(Sample approved by the engineer in
charge) m) in 12th Floor
35.n Civil N/A Supplying, fitting and fixing mirror Sqm. 423.88
polished homogeneous floor tiles
(local/equivalent foreign made) with
cement sand (F.M. 1.2) mortar (1:4)
base and raking out the joints with
white cement including cutting and
laying the tiles in proper way and
finishing with care etc. all complete
and accepted by the Engineer.
(Cement: CEM-II/A-M). GP (mirror
polished) 600 x 600 mm floor tiles
(Sample approved by the engineer in
charge) n) in 13th Floor
35.o Civil N/A Supplying, fitting and fixing mirror Sqm. 423.88
polished homogeneous floor tiles
(local/equivalent foreign made) with
cement sand (F.M. 1.2) mortar (1:4)
base and raking out the joints with
white cement including cutting and
laying the tiles in proper way and
finishing with care etc. all complete
and accepted by the Engineer.
(Cement: CEM-II/A-M). GP (mirror
polished) 600 x 600 mm floor tiles
(Sample approved by the engineer in
charge) o) in 14th Floor
35.p Civil N/A Supplying, fitting and fixing mirror Sqm. 423.88
polished homogeneous floor tiles
(local/equivalent foreign made) with
cement sand (F.M. 1.2) mortar (1:4)
base and raking out the joints with
white cement including cutting and
laying the tiles in proper way and
finishing with care etc. all complete
and accepted by the Engineer.
(Cement: CEM-II/A-M). GP (mirror
polished) 600 x 600 mm floor tiles
(Sample approved by the engineer in
charge) p) in 15th Floor
35.q Civil N/A Supplying, fitting and fixing mirror Sqm. 423.88
polished homogeneous floor tiles
(local/equivalent foreign made) with
cement sand (F.M. 1.2) mortar (1:4)
base and raking out the joints with
white cement including cutting and
laying the tiles in proper way and
finishing with care etc. all complete
and accepted by the Engineer.
(Cement: CEM-II/A-M). GP (mirror
polished) 600 x 600 mm floor tiles
(Sample approved by the engineer in
charge) q) in 16th Floor
35.r Civil N/A Supplying, fitting and fixing mirror Sqm. 191.99
polished homogeneous floor tiles
(local/equivalent foreign made) with
cement sand (F.M. 1.2) mortar (1:4)
base and raking out the joints with
white cement including cutting and
laying the tiles in proper way and
finishing with care etc. all complete
and accepted by the Engineer.
(Cement: CEM-II/A-M). GP (mirror
polished) 600 x 600 mm floor tiles
(Sample approved by the engineer in
charge) r) in 17th Floor
36.a Civil N/A Supplying, fitting and fixing GP Sqm. 112.25
homogeneous stair tiles
(local/equivalent foreign made) with
cement sand (F.M. 1.2) mortar (1:4)
base and raking out the joints with
white cement including cutting and
laying the tiles in proper way and
finishing with care etc. all complete
and accepted by the Engineer.
(Cement: CEM-II/A-M). (Sample
approved by the engineer in charge)
a) in Ground & Basement Floor
36.b Civil N/A Supplying, fitting and fixing GP Sqm. 78.14
homogeneous stair tiles
(local/equivalent foreign made) with
cement sand (F.M. 1.2) mortar (1:4)
base and raking out the joints with
white cement including cutting and
laying the tiles in proper way and
finishing with care etc. all complete
and accepted by the Engineer.
(Cement: CEM-II/A-M). (Sample
approved by the engineer in charge)
b) in 1st Floor
36.c Civil N/A Supplying, fitting and fixing GP Sqm. 73.19
homogeneous stair tiles
(local/equivalent foreign made) with
cement sand (F.M. 1.2) mortar (1:4)
base and raking out the joints with
white cement including cutting and
laying the tiles in proper way and
finishing with care etc. all complete
and accepted by the Engineer.
(Cement: CEM-II/A-M). (Sample
approved by the engineer in charge)
c) in 2nd Floor
36.d Civil N/A Supplying, fitting and fixing GP Sqm. 73.19
homogeneous stair tiles
(local/equivalent foreign made) with
cement sand (F.M. 1.2) mortar (1:4)
base and raking out the joints with
white cement including cutting and
laying the tiles in proper way and
finishing with care etc. all complete
and accepted by the Engineer.
(Cement: CEM-II/A-M). (Sample
approved by the engineer in charge)
d) in 3rd Floor
36.e Civil N/A Supplying, fitting and fixing GP Sqm. 73.19
homogeneous stair tiles
(local/equivalent foreign made) with
cement sand (F.M. 1.2) mortar (1:4)
base and raking out the joints with
white cement including cutting and
laying the tiles in proper way and
finishing with care etc. all complete
and accepted by the Engineer.
(Cement: CEM-II/A-M). (Sample
approved by the engineer in charge)
e) in 4th Floor
36.f Civil N/A Supplying, fitting and fixing GP Sqm. 73.19
homogeneous stair tiles
(local/equivalent foreign made) with
cement sand (F.M. 1.2) mortar (1:4)
base and raking out the joints with
white cement including cutting and
laying the tiles in proper way and
finishing with care etc. all complete
and accepted by the Engineer.
(Cement: CEM-II/A-M). (Sample
approved by the engineer in charge)
f) in 5th Floor
36.g Civil N/A Supplying, fitting and fixing GP Sqm. 73.19
homogeneous stair tiles
(local/equivalent foreign made) with
cement sand (F.M. 1.2) mortar (1:4)
base and raking out the joints with
white cement including cutting and
laying the tiles in proper way and
finishing with care etc. all complete
and accepted by the Engineer.
(Cement: CEM-II/A-M). (Sample
approved by the engineer in charge)
g) in 6th Floor
36.h Civil N/A Supplying, fitting and fixing GP Sqm. 73.19
homogeneous stair tiles
(local/equivalent foreign made) with
cement sand (F.M. 1.2) mortar (1:4)
base and raking out the joints with
white cement including cutting and
laying the tiles in proper way and
finishing with care etc. all complete
and accepted by the Engineer.
(Cement: CEM-II/A-M). (Sample
approved by the engineer in charge)
h) in 7th Floor
36.i Civil N/A Supplying, fitting and fixing GP Sqm. 73.19
homogeneous stair tiles
(local/equivalent foreign made) with
cement sand (F.M. 1.2) mortar (1:4)
base and raking out the joints with
white cement including cutting and
laying the tiles in proper way and
finishing with care etc. all complete
and accepted by the Engineer.
(Cement: CEM-II/A-M). (Sample
approved by the engineer in charge)
i) in 8th Floor
36.j Civil N/A Supplying, fitting and fixing GP Sqm. 73.19
homogeneous stair tiles
(local/equivalent foreign made) with
cement sand (F.M. 1.2) mortar (1:4)
base and raking out the joints with
white cement including cutting and
laying the tiles in proper way and
finishing with care etc. all complete
and accepted by the Engineer.
(Cement: CEM-II/A-M). (Sample
approved by the engineer in charge)
j) in 9th Floor
36.k Civil N/A Supplying, fitting and fixing GP Sqm. 73.19
homogeneous stair tiles
(local/equivalent foreign made) with
cement sand (F.M. 1.2) mortar (1:4)
base and raking out the joints with
white cement including cutting and
laying the tiles in proper way and
finishing with care etc. all complete
and accepted by the Engineer.
(Cement: CEM-II/A-M). (Sample
approved by the engineer in charge)
k) in 10th Floor
36.l Civil N/A Supplying, fitting and fixing GP Sqm. 73.19
homogeneous stair tiles
(local/equivalent foreign made) with
cement sand (F.M. 1.2) mortar (1:4)
base and raking out the joints with
white cement including cutting and
laying the tiles in proper way and
finishing with care etc. all complete
and accepted by the Engineer.
(Cement: CEM-II/A-M). (Sample
approved by the engineer in charge)
l) in 11th Floor
36.m Civil N/A Supplying, fitting and fixing GP Sqm. 73.19
homogeneous stair tiles
(local/equivalent foreign made) with
cement sand (F.M. 1.2) mortar (1:4)
base and raking out the joints with
white cement including cutting and
laying the tiles in proper way and
finishing with care etc. all complete
and accepted by the Engineer.
(Cement: CEM-II/A-M). (Sample
approved by the engineer in charge)
m) in 12th Floor
36.n Civil N/A Supplying, fitting and fixing GP Sqm. 73.19
homogeneous stair tiles
(local/equivalent foreign made) with
cement sand (F.M. 1.2) mortar (1:4)
base and raking out the joints with
white cement including cutting and
laying the tiles in proper way and
finishing with care etc. all complete
and accepted by the Engineer.
(Cement: CEM-II/A-M). (Sample
approved by the engineer in charge)
n) in 13th Floor
36.o Civil N/A Supplying, fitting and fixing GP Sqm. 73.19
homogeneous stair tiles
(local/equivalent foreign made) with
cement sand (F.M. 1.2) mortar (1:4)
base and raking out the joints with
white cement including cutting and
laying the tiles in proper way and
finishing with care etc. all complete
and accepted by the Engineer.
(Cement: CEM-II/A-M). (Sample
approved by the engineer in charge)
o) in 14th Floor
36.p Civil N/A Supplying, fitting and fixing GP Sqm. 73.19
homogeneous stair tiles
(local/equivalent foreign made) with
cement sand (F.M. 1.2) mortar (1:4)
base and raking out the joints with
white cement including cutting and
laying the tiles in proper way and
finishing with care etc. all complete
and accepted by the Engineer.
(Cement: CEM-II/A-M). (Sample
approved by the engineer in charge)
p) in 15th Floor
36.q Civil N/A Supplying, fitting and fixing GP Sqm. 73.19
homogeneous stair tiles
(local/equivalent foreign made) with
cement sand (F.M. 1.2) mortar (1:4)
base and raking out the joints with
white cement including cutting and
laying the tiles in proper way and
finishing with care etc. all complete
and accepted by the Engineer.
(Cement: CEM-II/A-M). (Sample
approved by the engineer in charge)
q) in 16th Floor
36.r Civil N/A Supplying, fitting and fixing GP Sqm. 39.32
homogeneous stair tiles
(local/equivalent foreign made) with
cement sand (F.M. 1.2) mortar (1:4)
base and raking out the joints with
white cement including cutting and
laying the tiles in proper way and
finishing with care etc. all complete
and accepted by the Engineer.
(Cement: CEM-II/A-M). (Sample
approved by the engineer in charge)
r) in 17th Floor
37- Civil N/A Reinforced cement concrete works Cum 2.00
A.1 using wooden shutter with minimum
cement content relates to mix ratio
1:2:4 having minimum f'cr = 27 Mpa,
and satisfying a specified
compressive strength f?c = 22 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1- CEM
1 (32.5 to 52.5 N) / ASTM-C 150
Type ? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site.(Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and placing)Tie
beam and lintels a-i) Ground floor &
Basement Floor, Concrete
37- Civil N/A Reinforced cement concrete works Sqm. 18.91
A.2 using wooden shutter with minimum
cement content relates to mix ratio
1:2:4 having minimum f'cr = 27 Mpa,
and satisfying a specified
compressive strength f?c = 22 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1- CEM
1 (32.5 to 52.5 N) / ASTM-C 150
Type ? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site.(Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and placing)Tie
beam and lintels. a-ii) Ground floor &
Basement Floor
Formwork/shuttering, prop and
necessary supports etc. (wooden)
37- Civil N/A Reinforced cement concrete works Cum 2.00
A.3 using wooden shutter with minimum
cement content relates to mix ratio
1:2:4 having minimum f'cr = 27 Mpa,
and satisfying a specified
compressive strength f?c = 22 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1- CEM
1 (32.5 to 52.5 N) / ASTM-C 150
Type ? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site.(Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and placing)Tie
beam and lintels. b-i) 1st floor
Concrete
37- Civil N/A Reinforced cement concrete works Sqm 13.00
A.4 using wooden shutter with minimum
cement content relates to mix ratio
1:2:4 having minimum f'cr = 27 Mpa,
and satisfying a specified
compressive strength f?c = 22 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1- CEM
1 (32.5 to 52.5 N) / ASTM-C 150
Type ? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site.(Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and placing)Tie
beam and lintels. b-ii) 1st floor
Formwork/shuttering, prop and
necessary supports etc. (wooden)
37- Civil N/A Reinforced cement concrete works Cum 9.50
A.5 using wooden shutter with minimum
cement content relates to mix ratio
1:2:4 having minimum f'cr = 27 Mpa,
and satisfying a specified
compressive strength f?c = 22 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1- CEM
1 (32.5 to 52.5 N) / ASTM-C 150
Type ? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site.(Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and placing)Tie
beam and lintels. c-i) 2nd Floor,
Concrete
37- Civil N/A Reinforced cement concrete works Sqm 141.37
A.6 using wooden shutter with minimum
cement content relates to mix ratio
1:2:4 having minimum f'cr = 27 Mpa,
and satisfying a specified
compressive strength f?c = 22 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1- CEM
1 (32.5 to 52.5 N) / ASTM-C 150
Type ? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site.(Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and placing)Tie
beam and lintels. c-ii) 2nd Floor
Formwork/shuttering, prop and
necessary supports etc. (wooden)
37- Civil N/A Reinforced cement concrete works Cum 9.50
A.7 using wooden shutter with minimum
cement content relates to mix ratio
1:2:4 having minimum f'cr = 27 Mpa,
and satisfying a specified
compressive strength f?c = 22 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1- CEM
1 (32.5 to 52.5 N) / ASTM-C 150
Type ? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site.(Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and placing)Tie
beam and lintels. d-i) 3rd Floor,
Concrete
37- Civil N/A Reinforced cement concrete works Sqm 141.37
A.8 using wooden shutter with minimum
cement content relates to mix ratio
1:2:4 having minimum f'cr = 27 Mpa,
and satisfying a specified
compressive strength f?c = 22 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1- CEM
1 (32.5 to 52.5 N) / ASTM-C 150
Type ? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site.(Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and placing)Tie
beam and lintels. d-ii) 3rd Floor
Formwork/shuttering, prop and
necessary supports etc. (wooden)
37- Civil N/A Reinforced cement concrete works Cum 9.50
A.9 using wooden shutter with minimum
cement content relates to mix ratio
1:2:4 having minimum f'cr = 27 Mpa,
and satisfying a specified
compressive strength f?c = 22 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1- CEM
1 (32.5 to 52.5 N) / ASTM-C 150
Type ? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site.(Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and placing)Tie
beam and lintels. e-i) 4th Floor,
Concrete
37- Civil N/A Reinforced cement concrete works Sqm 141.37
A.10 using wooden shutter with minimum
cement content relates to mix ratio
1:2:4 having minimum f'cr = 27 Mpa,
and satisfying a specified
compressive strength f?c = 22 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1- CEM
1 (32.5 to 52.5 N) / ASTM-C 150
Type ? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site.(Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and placing)Tie
beam and lintels. e-ii) 4th Floor
Formwork/shuttering, prop and
necessary supports etc. (wooden)
37- Civil N/A Reinforced cement concrete works Cum 9.50
A.11 using wooden shutter with minimum
cement content relates to mix ratio
1:2:4 having minimum f'cr = 27 Mpa,
and satisfying a specified
compressive strength f?c = 22 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1- CEM
1 (32.5 to 52.5 N) / ASTM-C 150
Type ? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site.(Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and placing)Tie
beam and lintels. f-i) 5th Floor,
Concrete
37- Civil N/A Reinforced cement concrete works Sqm 141.37
A.12 using wooden shutter with minimum
cement content relates to mix ratio
1:2:4 having minimum f'cr = 27 Mpa,
and satisfying a specified
compressive strength f?c = 22 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1- CEM
1 (32.5 to 52.5 N) / ASTM-C 150
Type ? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site.(Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and placing)Tie
beam and lintels. f-ii) 5th Floor
Formwork/shuttering, prop and
necessary supports etc. (wooden)
37- Civil N/A Reinforced cement concrete works Cum 9.50
A.13 using wooden shutter with minimum
cement content relates to mix ratio
1:2:4 having minimum f'cr = 27 Mpa,
and satisfying a specified
compressive strength f?c = 22 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1- CEM
1 (32.5 to 52.5 N) / ASTM-C 150
Type ? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site.(Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and placing)Tie
beam and lintels. g-i) 6th Floor,
Concrete
37- Civil N/A Reinforced cement concrete works Sqm 141.37
A.14 using wooden shutter with minimum
cement content relates to mix ratio
1:2:4 having minimum f'cr = 27 Mpa,
and satisfying a specified
compressive strength f?c = 22 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1- CEM
1 (32.5 to 52.5 N) / ASTM-C 150
Type ? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site.(Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and placing)Tie
beam and lintels. g-ii) 6th Floor
Formwork/shuttering, prop and
necessary supports etc. (wooden)
37- Civil N/A Reinforced cement concrete works Cum 9.50
A.15 using wooden shutter with minimum
cement content relates to mix ratio
1:2:4 having minimum f'cr = 27 Mpa,
and satisfying a specified
compressive strength f?c = 22 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1- CEM
1 (32.5 to 52.5 N) / ASTM-C 150
Type ? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site.(Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and placing)Tie
beam and lintels. h-i) 7th Floor,
Concrete
37- Civil N/A Reinforced cement concrete works Sqm 141.37
A.16 using wooden shutter with minimum
cement content relates to mix ratio
1:2:4 having minimum f'cr = 27 Mpa,
and satisfying a specified
compressive strength f?c = 22 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1- CEM
1 (32.5 to 52.5 N) / ASTM-C 150
Type ? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site.(Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and placing)Tie
beam and lintels. h-ii) 7th Floor
Formwork/shuttering, prop and
necessary supports etc. (wooden)
37- Civil N/A Reinforced cement concrete works Cum 9.50
A.17 using wooden shutter with minimum
cement content relates to mix ratio
1:2:4 having minimum f'cr = 27 Mpa,
and satisfying a specified
compressive strength f?c = 22 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1- CEM
1 (32.5 to 52.5 N) / ASTM-C 150
Type ? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site.(Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and placing)Tie
beam and lintels. i-i) 8th Floor,
Concrete
37- Civil N/A Reinforced cement concrete works Sqm 141.37
A.18 using wooden shutter with minimum
cement content relates to mix ratio
1:2:4 having minimum f'cr = 27 Mpa,
and satisfying a specified
compressive strength f?c = 22 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1- CEM
1 (32.5 to 52.5 N) / ASTM-C 150
Type ? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site.(Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and placing)Tie
beam and lintels. i-ii) 8th Floor
Formwork/shuttering, prop and
necessary supports etc. (wooden)
37- Civil N/A Reinforced cement concrete works Cum 9.50
A.19 using wooden shutter with minimum
cement content relates to mix ratio
1:2:4 having minimum f'cr = 27 Mpa,
and satisfying a specified
compressive strength f?c = 22 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1- CEM
1 (32.5 to 52.5 N) / ASTM-C 150
Type ? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site.(Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and placing)Tie
beam and lintels. j-i) 9th Floor,
Concrete
37- Civil N/A Reinforced cement concrete works Sqm 141.37
A.20 using wooden shutter with minimum
cement content relates to mix ratio
1:2:4 having minimum f'cr = 27 Mpa,
and satisfying a specified
compressive strength f?c = 22 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1- CEM
1 (32.5 to 52.5 N) / ASTM-C 150
Type ? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site.(Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and placing)Tie
beam and lintels. j-ii) 9th Floor
Formwork/shuttering, prop and
necessary supports etc. (wooden)
37- Civil N/A Reinforced cement concrete works Cum 9.50
A.21 using wooden shutter with minimum
cement content relates to mix ratio
1:2:4 having minimum f'cr = 27 Mpa,
and satisfying a specified
compressive strength f?c = 22 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1- CEM
1 (32.5 to 52.5 N) / ASTM-C 150
Type ? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site.(Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and placing)Tie
beam and lintels. k-i) 10th Floor,
Concrete
37- Civil N/A Reinforced cement concrete works Sqm 141.37
A.22 using wooden shutter with minimum
cement content relates to mix ratio
1:2:4 having minimum f'cr = 27 Mpa,
and satisfying a specified
compressive strength f?c = 22 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1- CEM
1 (32.5 to 52.5 N) / ASTM-C 150
Type ? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site.(Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and placing)Tie
beam and lintels. k-ii) 10th Floor
Formwork/shuttering, prop and
necessary supports etc. (wooden)
37- Civil N/A Reinforced cement concrete works Cum 9.50
A.23 using wooden shutter with minimum
cement content relates to mix ratio
1:2:4 having minimum f'cr = 27 Mpa,
and satisfying a specified
compressive strength f?c = 22 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1- CEM
1 (32.5 to 52.5 N) / ASTM-C 150
Type ? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site.(Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and placing)Tie
beam and lintels. l-i) 11th Floor,
Concrete
37- Civil N/A Reinforced cement concrete works Sqm 141.37
A.24 using wooden shutter with minimum
cement content relates to mix ratio
1:2:4 having minimum f'cr = 27 Mpa,
and satisfying a specified
compressive strength f?c = 22 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1- CEM
1 (32.5 to 52.5 N) / ASTM-C 150
Type ? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site.(Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and placing)Tie
beam and lintels. l-ii) 11th Floor
Formwork/shuttering, prop and
necessary supports etc. (wooden)
37- Civil N/A Reinforced cement concrete works Cum 9.50
A.25 using wooden shutter with minimum
cement content relates to mix ratio
1:2:4 having minimum f'cr = 27 Mpa,
and satisfying a specified
compressive strength f?c = 22 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1- CEM
1 (32.5 to 52.5 N) / ASTM-C 150
Type ? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site.(Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and placing)Tie
beam and lintels. m-i) 12th Floor,
Concrete
37- Civil N/A Reinforced cement concrete works Sqm 141.37
A.26 using wooden shutter with minimum
cement content relates to mix ratio
1:2:4 having minimum f'cr = 27 Mpa,
and satisfying a specified
compressive strength f?c = 22 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1- CEM
1 (32.5 to 52.5 N) / ASTM-C 150
Type ? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site.(Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and placing)Tie
beam and lintels. m-ii) 12th Floor
Formwork/shuttering, prop and
necessary supports etc. (wooden)
37- Civil N/A Reinforced cement concrete works Cum 9.50
A.27 using wooden shutter with minimum
cement content relates to mix ratio
1:2:4 having minimum f'cr = 27 Mpa,
and satisfying a specified
compressive strength f?c = 22 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1- CEM
1 (32.5 to 52.5 N) / ASTM-C 150
Type ? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site.(Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and placing)Tie
beam and lintels. n-i) 13th Floor,
Concrete
37- Civil N/A Reinforced cement concrete works Sqm 141.37
A.28 using wooden shutter with minimum
cement content relates to mix ratio
1:2:4 having minimum f'cr = 27 Mpa,
and satisfying a specified
compressive strength f?c = 22 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1- CEM
1 (32.5 to 52.5 N) / ASTM-C 150
Type ? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site.(Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and placing)Tie
beam and lintels. n-ii) 13th Floor
Formwork/shuttering, prop and
necessary supports etc. (wooden)
37- Civil N/A Reinforced cement concrete works Cum 9.50
A.29 using wooden shutter with minimum
cement content relates to mix ratio
1:2:4 having minimum f'cr = 27 Mpa,
and satisfying a specified
compressive strength f?c = 22 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1- CEM
1 (32.5 to 52.5 N) / ASTM-C 150
Type ? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site.(Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and placing)Tie
beam and lintels. o-i) 14th Floor,
Concrete
37- Civil N/A Reinforced cement concrete works Sqm 141.37
A.30 using wooden shutter with minimum
cement content relates to mix ratio
1:2:4 having minimum f'cr = 27 Mpa,
and satisfying a specified
compressive strength f?c = 22 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1- CEM
1 (32.5 to 52.5 N) / ASTM-C 150
Type ? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site.(Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and placing)Tie
beam and lintels. o-ii) 14th Floor
Formwork/shuttering, prop and
necessary supports etc. (wooden)
37- Civil N/A Reinforced cement concrete works Cum 9.50
A.31 using wooden shutter with minimum
cement content relates to mix ratio
1:2:4 having minimum f'cr = 27 Mpa,
and satisfying a specified
compressive strength f?c = 22 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1- CEM
1 (32.5 to 52.5 N) / ASTM-C 150
Type ? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site.(Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and placing)Tie
beam and lintels. p-i) 15th Floor,
Concrete
37- Civil N/A Reinforced cement concrete works Sqm 141.37
A.32 using wooden shutter with minimum
cement content relates to mix ratio
1:2:4 having minimum f'cr = 27 Mpa,
and satisfying a specified
compressive strength f?c = 22 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1- CEM
1 (32.5 to 52.5 N) / ASTM-C 150
Type ? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site.(Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and placing)Tie
beam and lintels. p-ii) 15th Floor
Formwork/shuttering, prop and
necessary supports etc. (wooden)
37- Civil N/A Reinforced cement concrete works Cum 9.50
A.33 using wooden shutter with minimum
cement content relates to mix ratio
1:2:4 having minimum f'cr = 27 Mpa,
and satisfying a specified
compressive strength f?c = 22 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1- CEM
1 (32.5 to 52.5 N) / ASTM-C 150
Type ? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site.(Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and placing)Tie
beam and lintels. q-i) 16th Floor,
Concrete
37- Civil N/A Reinforced cement concrete works Sqm 141.37
A.34 using wooden shutter with minimum
cement content relates to mix ratio
1:2:4 having minimum f'cr = 27 Mpa,
and satisfying a specified
compressive strength f?c = 22 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1- CEM
1 (32.5 to 52.5 N) / ASTM-C 150
Type ? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site.(Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and placing)Tie
beam and lintels. q-ii) 16th Floor
Formwork/shuttering, prop and
necessary supports etc. (wooden)
37- Civil N/A Reinforced cement concrete works Cum 2.50
A.35 using wooden shutter with minimum
cement content relates to mix ratio
1:2:4 having minimum f'cr = 27 Mpa,
and satisfying a specified
compressive strength f?c = 22 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1- CEM
1 (32.5 to 52.5 N) / ASTM-C 150
Type ? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site.(Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and placing)Tie
beam and lintels. r-i) 17th Floor,
Concrete (Chilakota)
37- Civil N/A Reinforced cement concrete works Sqm 25.00
A.36 using wooden shutter with minimum
cement content relates to mix ratio
1:2:4 having minimum f'cr = 27 Mpa,
and satisfying a specified
compressive strength f?c = 22 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1- CEM
1 (32.5 to 52.5 N) / ASTM-C 150
Type ? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site.(Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and placing)Tie
beam and lintels. r-ii) 17th Floor
Formwork/shuttering, prop and
necessary supports etc. (wooden)
37- Civil N/A Reinforced cement concrete works Cum 0.50
A.37 using wooden shutter with minimum
cement content relates to mix ratio
1:2:4 having minimum f'cr = 27 Mpa,
and satisfying a specified
compressive strength f?c = 22 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1- CEM
1 (32.5 to 52.5 N) / ASTM-C 150
Type ? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site.(Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and placing)Tie
beam and lintels. s-1) 18th Floor
Concrete
37- Civil N/A Reinforced cement concrete works Sqm 5.00
A.38 using wooden shutter with minimum
cement content relates to mix ratio
1:2:4 having minimum f'cr = 27 Mpa,
and satisfying a specified
compressive strength f?c = 22 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1- CEM
1 (32.5 to 52.5 N) / ASTM-C 150
Type ? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site.(Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and placing)Tie
beam and lintels. s-1) 18th Floor
Formwork
37- Civil N/A Reinforced cement concrete works Cum 5.32
B.1 using wooden shutter with minimum
cement content relates to mix ratio
1:2:4 having minimum f'cr = 27 Mpa,
and satisfying a specified
compressive strength f?c = 22 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1- CEM
1 (32.5 to 52.5 N) / ASTM-C 150
Type ? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site.(Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and placing)Cornice,
railing, drop walls, louver, fins etc. a-i)
Ground floor & Basement Floor,
Concrete
37- Civil N/A Reinforced cement concrete works Sqm 128.24
B.2 using wooden shutter with minimum
cement content relates to mix ratio
1:2:4 having minimum f'cr = 27 Mpa,
and satisfying a specified
compressive strength f?c = 22 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1- CEM
1 (32.5 to 52.5 N) / ASTM-C 150
Type ? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site.(Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and placing)Cornice,
railing, drop walls, louver, fins etc. a-
ii) Ground floor & Basement Floor
Formwork/shuttering, prop and
necessary supports etc. (wooden)
37- Civil N/A Reinforced cement concrete works Cum 5.32
B.3 using wooden shutter with minimum
cement content relates to mix ratio
1:2:4 having minimum f'cr = 27 Mpa,
and satisfying a specified
compressive strength f?c = 22 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1- CEM
1 (32.5 to 52.5 N) / ASTM-C 150
Type ? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site.(Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and placing)Cornice,
railing, drop walls, louver, fins etc. b-i)
1st floor Concrete
37- Civil N/A Reinforced cement concrete works Sqm 128.24
B.4 using wooden shutter with minimum
cement content relates to mix ratio
1:2:4 having minimum f'cr = 27 Mpa,
and satisfying a specified
compressive strength f?c = 22 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1- CEM
1 (32.5 to 52.5 N) / ASTM-C 150
Type ? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site.(Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and placing)Cornice,
railing, drop walls, louver, fins etc. b-
ii) 1st floor Formwork/shuttering, prop
and necessary supports etc.
(wooden)
37- Civil N/A Reinforced cement concrete works Cum 6.47
B.5 using wooden shutter with minimum
cement content relates to mix ratio
1:2:4 having minimum f'cr = 27 Mpa,
and satisfying a specified
compressive strength f?c = 22 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1- CEM
1 (32.5 to 52.5 N) / ASTM-C 150
Type ? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site.(Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and placing)Cornice,
railing, drop walls, louver, fins etc. c-i)
2nd Floor, Concrete
37- Civil N/A Reinforced cement concrete works Sqm 169.32
B.6 using wooden shutter with minimum
cement content relates to mix ratio
1:2:4 having minimum f'cr = 27 Mpa,
and satisfying a specified
compressive strength f?c = 22 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1- CEM
1 (32.5 to 52.5 N) / ASTM-C 150
Type ? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site.(Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and placing)Cornice,
railing, drop walls, louver, fins etc. c-
ii) 2nd Floor Formwork/shuttering,
prop and necessary supports etc.
(wooden)
37- Civil N/A Reinforced cement concrete works Cum 6.94
B.7 using wooden shutter with minimum
cement content relates to mix ratio
1:2:4 having minimum f'cr = 27 Mpa,
and satisfying a specified
compressive strength f?c = 22 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1- CEM
1 (32.5 to 52.5 N) / ASTM-C 150
Type ? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site.(Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and placing)Cornice,
railing, drop walls, louver, fins etc. d-i)
3rd Floor, Concrete
37- Civil N/A Reinforced cement concrete works Sqm 169.32
B.8 using wooden shutter with minimum
cement content relates to mix ratio
1:2:4 having minimum f'cr = 27 Mpa,
and satisfying a specified
compressive strength f?c = 22 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1- CEM
1 (32.5 to 52.5 N) / ASTM-C 150
Type ? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site.(Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and placing)Cornice,
railing, drop walls, louver, fins etc. d-
ii) 3rd Floor Formwork/shuttering,
prop and necessary supports etc.
(wooden)
37- Civil N/A Reinforced cement concrete works Cum 6.94
B.9 using wooden shutter with minimum
cement content relates to mix ratio
1:2:4 having minimum f'cr = 27 Mpa,
and satisfying a specified
compressive strength f?c = 22 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1- CEM
1 (32.5 to 52.5 N) / ASTM-C 150
Type ? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site.(Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and placing)Cornice,
railing, drop walls, louver, fins etc. e-i)
4th Floor, Concrete
37- Civil N/A Reinforced cement concrete works Sqm 169.32
B.10 using wooden shutter with minimum
cement content relates to mix ratio
1:2:4 having minimum f'cr = 27 Mpa,
and satisfying a specified
compressive strength f?c = 22 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1- CEM
1 (32.5 to 52.5 N) / ASTM-C 150
Type ? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site.(Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and placing)Cornice,
railing, drop walls, louver, fins etc. e-
ii) 4th Floor Formwork/shuttering,
prop and necessary supports etc.
(wooden)
37- Civil N/A Reinforced cement concrete works Cum 6.94
B.11 using wooden shutter with minimum
cement content relates to mix ratio
1:2:4 having minimum f'cr = 27 Mpa,
and satisfying a specified
compressive strength f?c = 22 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1- CEM
1 (32.5 to 52.5 N) / ASTM-C 150
Type ? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site.(Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and placing)Cornice,
railing, drop walls, louver, fins etc. f-i)
5th Floor, Concrete
37- Civil N/A Reinforced cement concrete works Sqm 169.32
B.12 using wooden shutter with minimum
cement content relates to mix ratio
1:2:4 having minimum f'cr = 27 Mpa,
and satisfying a specified
compressive strength f?c = 22 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1- CEM
1 (32.5 to 52.5 N) / ASTM-C 150
Type ? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site.(Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and placing)Cornice,
railing, drop walls, louver, fins etc. f-ii)
5th Floor Formwork/shuttering, prop
and necessary supports etc.
(wooden)
37- Civil N/A Reinforced cement concrete works Cum 6.94
B.13 using wooden shutter with minimum
cement content relates to mix ratio
1:2:4 having minimum f'cr = 27 Mpa,
and satisfying a specified
compressive strength f?c = 22 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1- CEM
1 (32.5 to 52.5 N) / ASTM-C 150
Type ? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site.(Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and placing)Cornice,
railing, drop walls, louver, fins etc. g-i)
6th Floor, Concrete
37- Civil N/A Reinforced cement concrete works Sqm 169.32
B.14 using wooden shutter with minimum
cement content relates to mix ratio
1:2:4 having minimum f'cr = 27 Mpa,
and satisfying a specified
compressive strength f?c = 22 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1- CEM
1 (32.5 to 52.5 N) / ASTM-C 150
Type ? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site.(Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and placing)Cornice,
railing, drop walls, louver, fins etc.g-ii)
6th Floor Formwork/shuttering, prop
and necessary supports etc.
(wooden)
37- Civil N/A Reinforced cement concrete works Cum 6.94
B.15 using wooden shutter with minimum
cement content relates to mix ratio
1:2:4 having minimum f'cr = 27 Mpa,
and satisfying a specified
compressive strength f?c = 22 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1- CEM
1 (32.5 to 52.5 N) / ASTM-C 150
Type ? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site.(Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and placing)Cornice,
railing, drop walls, louver, fins etc. h-i)
7th Floor, Concrete
37- Civil N/A Reinforced cement concrete works Sqm 169.32
B.16 using wooden shutter with minimum
cement content relates to mix ratio
1:2:4 having minimum f'cr = 27 Mpa,
and satisfying a specified
compressive strength f?c = 22 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1- CEM
1 (32.5 to 52.5 N) / ASTM-C 150
Type ? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site.(Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and placing)Cornice,
railing, drop walls, louver, fins etc. h-
ii) 7th Floor Formwork/shuttering,
prop and necessary supports etc.
(wooden)
37- Civil N/A Reinforced cement concrete works Cum 6.94
B.17 using wooden shutter with minimum
cement content relates to mix ratio
1:2:4 having minimum f'cr = 27 Mpa,
and satisfying a specified
compressive strength f?c = 22 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1- CEM
1 (32.5 to 52.5 N) / ASTM-C 150
Type ? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site.(Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and placing)Cornice,
railing, drop walls, louver, fins etc. i-i)
8th Floor, Concrete
37- Civil N/A Reinforced cement concrete works Sqm 169.32
B.18 using wooden shutter with minimum
cement content relates to mix ratio
1:2:4 having minimum f'cr = 27 Mpa,
and satisfying a specified
compressive strength f?c = 22 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1- CEM
1 (32.5 to 52.5 N) / ASTM-C 150
Type ? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site.(Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and placing)Cornice,
railing, drop walls, louver, fins etc. i-ii)
8th Floor Formwork/shuttering, prop
and necessary supports etc.
(wooden)
37- Civil N/A Reinforced cement concrete works Cum 6.94
B.19 using wooden shutter with minimum
cement content relates to mix ratio
1:2:4 having minimum f'cr = 27 Mpa,
and satisfying a specified
compressive strength f?c = 22 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1- CEM
1 (32.5 to 52.5 N) / ASTM-C 150
Type ? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site.(Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and placing)Cornice,
railing, drop walls, louver, fins etc. j-i)
9th Floor, Concrete
37- Civil N/A Reinforced cement concrete works Sqm 169.32
B.20 using wooden shutter with minimum
cement content relates to mix ratio
1:2:4 having minimum f'cr = 27 Mpa,
and satisfying a specified
compressive strength f?c = 22 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1- CEM
1 (32.5 to 52.5 N) / ASTM-C 150
Type ? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site.(Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and placing)Cornice,
railing, drop walls, louver, fins etc. j-ii)
9th Floor Formwork/shuttering, prop
and necessary supports etc.
(wooden)
37- Civil N/A Reinforced cement concrete works Cum 6.94
B.21 using wooden shutter with minimum
cement content relates to mix ratio
1:2:4 having minimum f'cr = 27 Mpa,
and satisfying a specified
compressive strength f?c = 22 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1- CEM
1 (32.5 to 52.5 N) / ASTM-C 150
Type ? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site.(Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and placing)Cornice,
railing, drop walls, louver, fins etc. k-i)
10th Floor, Concrete
37- Civil N/A Reinforced cement concrete works Sqm 169.32
B.22 using wooden shutter with minimum
cement content relates to mix ratio
1:2:4 having minimum f'cr = 27 Mpa,
and satisfying a specified
compressive strength f?c = 22 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1- CEM
1 (32.5 to 52.5 N) / ASTM-C 150
Type ? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site.(Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and placing)Cornice,
railing, drop walls, louver, fins etc. k-
ii) 10th Floor Formwork/shuttering,
prop and necessary supports etc.
(wooden)
37- Civil N/A Reinforced cement concrete works Cum 6.94
B.23 using wooden shutter with minimum
cement content relates to mix ratio
1:2:4 having minimum f'cr = 27 Mpa,
and satisfying a specified
compressive strength f?c = 22 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1- CEM
1 (32.5 to 52.5 N) / ASTM-C 150
Type ? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site.(Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and placing)Cornice,
railing, drop walls, louver, fins etc. l-i)
11th Floor, Concrete
37- Civil N/A Reinforced cement concrete works Sqm 169.32
B.24 using wooden shutter with minimum
cement content relates to mix ratio
1:2:4 having minimum f'cr = 27 Mpa,
and satisfying a specified
compressive strength f?c = 22 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1- CEM
1 (32.5 to 52.5 N) / ASTM-C 150
Type ? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site.(Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and placing)Cornice,
railing, drop walls, louver, fins etc. l-ii)
11th Floor Formwork/shuttering, prop
and necessary supports etc.
(wooden)
37- Civil N/A Reinforced cement concrete works Cum 6.94
B.25 using wooden shutter with minimum
cement content relates to mix ratio
1:2:4 having minimum f'cr = 27 Mpa,
and satisfying a specified
compressive strength f?c = 22 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1- CEM
1 (32.5 to 52.5 N) / ASTM-C 150
Type ? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site.(Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and placing)Cornice,
railing, drop walls, louver, fins etc. m-
i) 12th Floor, Concrete
37- Civil N/A Reinforced cement concrete works Sqm 169.32
B.26 using wooden shutter with minimum
cement content relates to mix ratio
1:2:4 having minimum f'cr = 27 Mpa,
and satisfying a specified
compressive strength f?c = 22 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1- CEM
1 (32.5 to 52.5 N) / ASTM-C 150
Type ? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site.(Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and placing)Cornice,
railing, drop walls, louver, fins etc. m-
ii) 12th Floor Formwork/shuttering,
prop and necessary supports etc.
(wooden)
37- Civil N/A Reinforced cement concrete works Cum 6.94
B.27 using wooden shutter with minimum
cement content relates to mix ratio
1:2:4 having minimum f'cr = 27 Mpa,
and satisfying a specified
compressive strength f?c = 22 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1- CEM
1 (32.5 to 52.5 N) / ASTM-C 150
Type ? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site.(Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and placing)Cornice,
railing, drop walls, louver, fins etc. n-i)
13th Floor, Concrete
37- Civil N/A Reinforced cement concrete works Sqm 169.32
B.28 using wooden shutter with minimum
cement content relates to mix ratio
1:2:4 having minimum f'cr = 27 Mpa,
and satisfying a specified
compressive strength f?c = 22 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1- CEM
1 (32.5 to 52.5 N) / ASTM-C 150
Type ? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site.(Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and placing)Cornice,
railing, drop walls, louver, fins etc. n-
ii) 13th Floor Formwork/shuttering,
prop and necessary supports etc.
(wooden)
37- Civil N/A Reinforced cement concrete works Cum 6.94
B.29 using wooden shutter with minimum
cement content relates to mix ratio
1:2:4 having minimum f'cr = 27 Mpa,
and satisfying a specified
compressive strength f?c = 22 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1- CEM
1 (32.5 to 52.5 N) / ASTM-C 150
Type ? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site.(Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and placing)Cornice,
railing, drop walls, louver, fins etc. o-i)
14th Floor, Concrete
37- Civil N/A Reinforced cement concrete works Sqm 169.32
B.30 using wooden shutter with minimum
cement content relates to mix ratio
1:2:4 having minimum f'cr = 27 Mpa,
and satisfying a specified
compressive strength f?c = 22 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1- CEM
1 (32.5 to 52.5 N) / ASTM-C 150
Type ? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site.(Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and placing)Cornice,
railing, drop walls, louver, fins etc. o-
ii) 14th Floor Formwork/shuttering,
prop and necessary supports etc.
(wooden)
37- Civil N/A Reinforced cement concrete works Cum 6.94
B.31 using wooden shutter with minimum
cement content relates to mix ratio
1:2:4 having minimum f'cr = 27 Mpa,
and satisfying a specified
compressive strength f?c = 22 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1- CEM
1 (32.5 to 52.5 N) / ASTM-C 150
Type ? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site.(Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and placing)Cornice,
railing, drop walls, louver, fins etc. p-i)
15th Floor, Concrete
37- Civil N/A Reinforced cement concrete works Sqm 169.32
B.32 using wooden shutter with minimum
cement content relates to mix ratio
1:2:4 having minimum f'cr = 27 Mpa,
and satisfying a specified
compressive strength f?c = 22 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1- CEM
1 (32.5 to 52.5 N) / ASTM-C 150
Type ? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site.(Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and placing)Cornice,
railing, drop walls, louver, fins etc. p-
ii) 15th Floor Formwork/shuttering,
prop and necessary supports etc.
(wooden)
37- Civil N/A Reinforced cement concrete works Cum 6.94
B.33 using wooden shutter with minimum
cement content relates to mix ratio
1:2:4 having minimum f'cr = 27 Mpa,
and satisfying a specified
compressive strength f?c = 22 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1- CEM
1 (32.5 to 52.5 N) / ASTM-C 150
Type ? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site.(Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and placing)Cornice,
railing, drop walls, louver, fins etc. q-i)
16th Floor, Concrete
37- Civil N/A Reinforced cement concrete works Sqm 169.32
B.34 using wooden shutter with minimum
cement content relates to mix ratio
1:2:4 having minimum f'cr = 27 Mpa,
and satisfying a specified
compressive strength f?c = 22 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1- CEM
1 (32.5 to 52.5 N) / ASTM-C 150
Type ? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site.(Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and placing)Cornice,
railing, drop walls, louver, fins etc. q-
ii) 16th Floor Formwork/shuttering,
prop and necessary supports etc.
(wooden)
37- Civil N/A Reinforced cement concrete works Cum 6.94
B.35 using wooden shutter with minimum
cement content relates to mix ratio
1:2:4 having minimum f'cr = 27 Mpa,
and satisfying a specified
compressive strength f?c = 22 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1- CEM
1 (32.5 to 52.5 N) / ASTM-C 150
Type ? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site.(Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and placing)Cornice,
railing, drop walls, louver, fins etc. r-i)
17th Floor, Concrete (roof)
37- Civil N/A Reinforced cement concrete works Sqm 169.32
B.36 using wooden shutter with minimum
cement content relates to mix ratio
1:2:4 having minimum f'cr = 27 Mpa,
and satisfying a specified
compressive strength f?c = 22 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1- CEM
1 (32.5 to 52.5 N) / ASTM-C 150
Type ? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site.(Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and placing)Cornice,
railing, drop walls, louver, fins etc. r-ii)
17th Floor Formwork/shuttering, prop
and necessary supports etc.
(wooden)
37- Civil N/A Reinforced cement concrete works Cum 1.50
B.37 using wooden shutter with minimum
cement content relates to mix ratio
1:2:4 having minimum f'cr = 27 Mpa,
and satisfying a specified
compressive strength f?c = 22 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1- CEM
1 (32.5 to 52.5 N) / ASTM-C 150
Type ? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site.(Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and placing)Cornice,
railing, drop walls, louver, fins etc. s-i)
18th Floor, Concrete (machine room)
37- Civil N/A Reinforced cement concrete works Sqm 25.00
B.38 using wooden shutter with minimum
cement content relates to mix ratio
1:2:4 having minimum f'cr = 27 Mpa,
and satisfying a specified
compressive strength f?c = 22 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1- CEM
1 (32.5 to 52.5 N) / ASTM-C 150
Type ? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site.(Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and placing)Cornice,
railing, drop walls, louver, fins etc. s-
ii) 18th Floor Formwork/shuttering,
prop and necessary supports etc.
(wooden)
37- Civil N/A Reinforced cement concrete works Cum 2.00
C.1 using wooden shutter with minimum
cement content relates to mix ratio
1:2:4 having minimum f'cr = 27 Mpa,
and satisfying a specified
compressive strength f?c = 22 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1- CEM
1 (32.5 to 52.5 N) / ASTM-C 150
Type ? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site.(Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and
placing)Sunshade, false ceiling:a-i)
Ground floor & Basement Floor,
Concrete
37- Civil N/A Reinforced cement concrete works Sqm 20.00
C.2 using wooden shutter with minimum
cement content relates to mix ratio
1:2:4 having minimum f'cr = 27 Mpa,
and satisfying a specified
compressive strength f?c = 22 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1- CEM
1 (32.5 to 52.5 N) / ASTM-C 150
Type ? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site.(Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and
placing)Sunshade, false ceiling:a-ii)
Ground floor & Basement Floor
Formwork/shuttering, prop and
necessary supports etc. (wooden)
37- Civil N/A Reinforced cement concrete works Cum 2.00
C.3 using wooden shutter with minimum
cement content relates to mix ratio
1:2:4 having minimum f'cr = 27 Mpa,
and satisfying a specified
compressive strength f?c = 22 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1- CEM
1 (32.5 to 52.5 N) / ASTM-C 150
Type ? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site.(Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and
placing)Sunshade, false ceiling:b-i)
1st floor Concrete
37- Civil N/A Reinforced cement concrete works Sqm 20.00
C.4 using wooden shutter with minimum
cement content relates to mix ratio
1:2:4 having minimum f'cr = 27 Mpa,
and satisfying a specified
compressive strength f?c = 22 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1- CEM
1 (32.5 to 52.5 N) / ASTM-C 150
Type ? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site.(Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and
placing)Sunshade, false ceiling:b-ii)
1st floor Formwork/shuttering, prop
and necessary supports etc.
(wooden)
37- Civil N/A Reinforced cement concrete works Cum 12.36
C.5 using wooden shutter with minimum
cement content relates to mix ratio
1:2:4 having minimum f'cr = 27 Mpa,
and satisfying a specified
compressive strength f?c = 22 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1- CEM
1 (32.5 to 52.5 N) / ASTM-C 150
Type ? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site.(Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and
placing)Sunshade, false ceiling:c-i)
2nd Floor, Concrete
37- Civil N/A Reinforced cement concrete works Sqm 162.35
C.6 using wooden shutter with minimum
cement content relates to mix ratio
1:2:4 having minimum f'cr = 27 Mpa,
and satisfying a specified
compressive strength f?c = 22 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1- CEM
1 (32.5 to 52.5 N) / ASTM-C 150
Type ? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site.(Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and
placing)Sunshade, false ceiling:c-ii)
2nd Floor Formwork/shuttering, prop
and necessary supports etc.
(wooden)
37- Civil N/A Reinforced cement concrete works Cum 12.36
C.7 using wooden shutter with minimum
cement content relates to mix ratio
1:2:4 having minimum f'cr = 27 Mpa,
and satisfying a specified
compressive strength f?c = 22 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1- CEM
1 (32.5 to 52.5 N) / ASTM-C 150
Type ? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site.(Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and
placing)Sunshade, false ceiling:d-i)
3rd Floor, Concrete
37- Civil N/A Reinforced cement concrete works Sqm 162.35
C.8 using wooden shutter with minimum
cement content relates to mix ratio
1:2:4 having minimum f'cr = 27 Mpa,
and satisfying a specified
compressive strength f?c = 22 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1- CEM
1 (32.5 to 52.5 N) / ASTM-C 150
Type ? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site.(Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and
placing)Sunshade, false ceiling:d-ii)
3rd Floor Formwork/shuttering, prop
and necessary supports etc.
(wooden)
37- Civil N/A Reinforced cement concrete works Cum 12.36
C.9 using wooden shutter with minimum
cement content relates to mix ratio
1:2:4 having minimum f'cr = 27 Mpa,
and satisfying a specified
compressive strength f?c = 22 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1- CEM
1 (32.5 to 52.5 N) / ASTM-C 150
Type ? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site.(Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and
placing)Sunshade, false ceiling:e-i)
4th Floor, Concrete
37- Civil N/A Reinforced cement concrete works Sqm 162.35
C.10 using wooden shutter with minimum
cement content relates to mix ratio
1:2:4 having minimum f'cr = 27 Mpa,
and satisfying a specified
compressive strength f?c = 22 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1- CEM
1 (32.5 to 52.5 N) / ASTM-C 150
Type ? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site.(Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and
placing)Sunshade, false ceiling:e-ii)
4th Floor Formwork/shuttering, prop
and necessary supports etc.
(wooden)
37- Civil N/A Reinforced cement concrete works Cum 12.36
C.11 using wooden shutter with minimum
cement content relates to mix ratio
1:2:4 having minimum f'cr = 27 Mpa,
and satisfying a specified
compressive strength f?c = 22 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1- CEM
1 (32.5 to 52.5 N) / ASTM-C 150
Type ? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site.(Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and
placing)Sunshade, false ceiling:f-i) 5th
Floor, Concrete
37- Civil N/A Reinforced cement concrete works Sqm 162.35
C.12 using wooden shutter with minimum
cement content relates to mix ratio
1:2:4 having minimum f'cr = 27 Mpa,
and satisfying a specified
compressive strength f?c = 22 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1- CEM
1 (32.5 to 52.5 N) / ASTM-C 150
Type ? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site.(Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and
placing)Sunshade, false ceiling:f-ii)
5th Floor Formwork/shuttering, prop
and necessary supports etc.
(wooden)
37- Civil N/A Reinforced cement concrete works Cum 12.36
C.13 using wooden shutter with minimum
cement content relates to mix ratio
1:2:4 having minimum f'cr = 27 Mpa,
and satisfying a specified
compressive strength f?c = 22 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1- CEM
1 (32.5 to 52.5 N) / ASTM-C 150
Type ? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site.(Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and
placing)Sunshade, false ceiling:g-i)
6th Floor, Concrete
37- Civil N/A Reinforced cement concrete works Sqm 162.35
C.14 using wooden shutter with minimum
cement content relates to mix ratio
1:2:4 having minimum f'cr = 27 Mpa,
and satisfying a specified
compressive strength f?c = 22 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1- CEM
1 (32.5 to 52.5 N) / ASTM-C 150
Type ? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site.(Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and
placing)Sunshade, false ceiling:g-ii)
6th Floor Formwork/shuttering, prop
and necessary supports etc.
(wooden)
37- Civil N/A Reinforced cement concrete works Cum 12.36
C.15 using wooden shutter with minimum
cement content relates to mix ratio
1:2:4 having minimum f'cr = 27 Mpa,
and satisfying a specified
compressive strength f?c = 22 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1- CEM
1 (32.5 to 52.5 N) / ASTM-C 150
Type ? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site.(Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and
placing)Sunshade, false ceiling:h-i)
7th Floor, Concrete
37- Civil N/A Reinforced cement concrete works Sqm 162.35
C.16 using wooden shutter with minimum
cement content relates to mix ratio
1:2:4 having minimum f'cr = 27 Mpa,
and satisfying a specified
compressive strength f?c = 22 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1- CEM
1 (32.5 to 52.5 N) / ASTM-C 150
Type ? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site.(Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and
placing)Sunshade, false ceiling:h-ii)
7th Floor Formwork/shuttering, prop
and necessary supports etc.
(wooden)
37- Civil N/A Reinforced cement concrete works Cum 12.36
C.17 using wooden shutter with minimum
cement content relates to mix ratio
1:2:4 having minimum f'cr = 27 Mpa,
and satisfying a specified
compressive strength f?c = 22 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1- CEM
1 (32.5 to 52.5 N) / ASTM-C 150
Type ? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site.(Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and
placing)Sunshade, false ceiling:i-i) 8th
Floor, Concrete
37- Civil N/A Reinforced cement concrete works Sqm 162.35
C.18 using wooden shutter with minimum
cement content relates to mix ratio
1:2:4 having minimum f'cr = 27 Mpa,
and satisfying a specified
compressive strength f?c = 22 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1- CEM
1 (32.5 to 52.5 N) / ASTM-C 150
Type ? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site.(Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and
placing)Sunshade, false ceiling:i-ii)
8th Floor Formwork/shuttering, prop
and necessary supports etc.
(wooden)
37- Civil N/A Reinforced cement concrete works Cum 12.36
C.19 using wooden shutter with minimum
cement content relates to mix ratio
1:2:4 having minimum f'cr = 27 Mpa,
and satisfying a specified
compressive strength f?c = 22 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1- CEM
1 (32.5 to 52.5 N) / ASTM-C 150
Type ? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site.(Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and
placing)Sunshade, false ceiling:j-i) 9th
Floor, Concrete
37- Civil N/A Reinforced cement concrete works Sqm 162.35
C.20 using wooden shutter with minimum
cement content relates to mix ratio
1:2:4 having minimum f'cr = 27 Mpa,
and satisfying a specified
compressive strength f?c = 22 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1- CEM
1 (32.5 to 52.5 N) / ASTM-C 150
Type ? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site.(Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and
placing)Sunshade, false ceiling:j-ii)
9th Floor Formwork/shuttering, prop
and necessary supports etc.
(wooden)
37- Civil N/A Reinforced cement concrete works Cum 12.36
C.21 using wooden shutter with minimum
cement content relates to mix ratio
1:2:4 having minimum f'cr = 27 Mpa,
and satisfying a specified
compressive strength f?c = 22 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1- CEM
1 (32.5 to 52.5 N) / ASTM-C 150
Type ? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site.(Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and
placing)Sunshade, false ceiling:k-i)
10th Floor, Concrete
37- Civil N/A Reinforced cement concrete works Sqm 162.35
C.22 using wooden shutter with minimum
cement content relates to mix ratio
1:2:4 having minimum f'cr = 27 Mpa,
and satisfying a specified
compressive strength f?c = 22 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1- CEM
1 (32.5 to 52.5 N) / ASTM-C 150
Type ? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site.(Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and
placing)Sunshade, false ceiling:k-ii)
10th Floor Formwork/shuttering, prop
and necessary supports etc.
(wooden)
37- Civil N/A Reinforced cement concrete works Cum 12.36
C.23 using wooden shutter with minimum
cement content relates to mix ratio
1:2:4 having minimum f'cr = 27 Mpa,
and satisfying a specified
compressive strength f?c = 22 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1- CEM
1 (32.5 to 52.5 N) / ASTM-C 150
Type ? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site.(Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and
placing)Sunshade, false ceiling:l-i)
11th Floor, Concrete
37- Civil N/A Reinforced cement concrete works Sqm 162.35
C.24 using wooden shutter with minimum
cement content relates to mix ratio
1:2:4 having minimum f'cr = 27 Mpa,
and satisfying a specified
compressive strength f?c = 22 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1- CEM
1 (32.5 to 52.5 N) / ASTM-C 150
Type ? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site.(Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and
placing)Sunshade, false ceiling:l-ii)
11th Floor Formwork/shuttering, prop
and necessary supports etc.
(wooden)
37- Civil N/A Reinforced cement concrete works Cum 12.36
C.25 using wooden shutter with minimum
cement content relates to mix ratio
1:2:4 having minimum f'cr = 27 Mpa,
and satisfying a specified
compressive strength f?c = 22 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1- CEM
1 (32.5 to 52.5 N) / ASTM-C 150
Type ? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site.(Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and
placing)Sunshade, false ceiling:m-i)
12th Floor, Concrete
37- Civil N/A Reinforced cement concrete works Sqm 162.35
C.26 using wooden shutter with minimum
cement content relates to mix ratio
1:2:4 having minimum f'cr = 27 Mpa,
and satisfying a specified
compressive strength f?c = 22 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1- CEM
1 (32.5 to 52.5 N) / ASTM-C 150
Type ? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site.(Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and
placing)Sunshade, false ceiling:m-ii)
12th Floor Formwork/shuttering, prop
and necessary supports etc.
(wooden)
37- Civil N/A Reinforced cement concrete works Cum 12.36
C.27 using wooden shutter with minimum
cement content relates to mix ratio
1:2:4 having minimum f'cr = 27 Mpa,
and satisfying a specified
compressive strength f?c = 22 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1- CEM
1 (32.5 to 52.5 N) / ASTM-C 150
Type ? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site.(Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and
placing)Sunshade, false ceiling:n-i)
13th Floor, Concrete
37- Civil N/A Reinforced cement concrete works Sqm 162.35
C.28 using wooden shutter with minimum
cement content relates to mix ratio
1:2:4 having minimum f'cr = 27 Mpa,
and satisfying a specified
compressive strength f?c = 22 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1- CEM
1 (32.5 to 52.5 N) / ASTM-C 150
Type ? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site.(Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and
placing)Sunshade, false ceiling:n-ii)
13th Floor Formwork/shuttering, prop
and necessary supports etc.
(wooden)
37- Civil N/A Reinforced cement concrete works Cum 12.36
C.29 using wooden shutter with minimum
cement content relates to mix ratio
1:2:4 having minimum f'cr = 27 Mpa,
and satisfying a specified
compressive strength f?c = 22 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1- CEM
1 (32.5 to 52.5 N) / ASTM-C 150
Type ? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site.(Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and
placing)Sunshade, false ceiling:o-i)
14th Floor, Concrete
37- Civil N/A Reinforced cement concrete works Sqm 162.35
C.30 using wooden shutter with minimum
cement content relates to mix ratio
1:2:4 having minimum f'cr = 27 Mpa,
and satisfying a specified
compressive strength f?c = 22 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1- CEM
1 (32.5 to 52.5 N) / ASTM-C 150
Type ? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site.(Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and
placing)Sunshade, false ceiling:o-ii)
14th Floor Formwork/shuttering, prop
and necessary supports etc.
(wooden)
37- Civil N/A Reinforced cement concrete works Cum 12.36
C.31 using wooden shutter with minimum
cement content relates to mix ratio
1:2:4 having minimum f'cr = 27 Mpa,
and satisfying a specified
compressive strength f?c = 22 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1- CEM
1 (32.5 to 52.5 N) / ASTM-C 150
Type ? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site.(Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and
placing)Sunshade, false ceiling:p-i)
15th Floor, Concrete
37- Civil N/A Reinforced cement concrete works Sqm 162.35
C.32 using wooden shutter with minimum
cement content relates to mix ratio
1:2:4 having minimum f'cr = 27 Mpa,
and satisfying a specified
compressive strength f?c = 22 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1- CEM
1 (32.5 to 52.5 N) / ASTM-C 150
Type ? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site.(Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and
placing)Sunshade, false ceiling:p-ii)
15th Floor Formwork/shuttering, prop
and necessary supports etc.
(wooden)
37- Civil N/A Reinforced cement concrete works Cum 12.36
C.33 using wooden shutter with minimum
cement content relates to mix ratio
1:2:4 having minimum f'cr = 27 Mpa,
and satisfying a specified
compressive strength f?c = 22 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1- CEM
1 (32.5 to 52.5 N) / ASTM-C 150
Type ? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site.(Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and
placing)Sunshade, false ceiling:q-i)
16th Floor, Concrete
37- Civil N/A Reinforced cement concrete works Sqm 162.35
C.34 using wooden shutter with minimum
cement content relates to mix ratio
1:2:4 having minimum f'cr = 27 Mpa,
and satisfying a specified
compressive strength f?c = 22 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1- CEM
1 (32.5 to 52.5 N) / ASTM-C 150
Type ? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site.(Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and
placing)Sunshade, false ceiling:q-ii)
16th Floor Formwork/shuttering, prop
and necessary supports etc.
(wooden)
37- Civil N/A Reinforced cement concrete works Cum 6.69
C.35 using wooden shutter with minimum
cement content relates to mix ratio
1:2:4 having minimum f'cr = 27 Mpa,
and satisfying a specified
compressive strength f?c = 22 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1- CEM
1 (32.5 to 52.5 N) / ASTM-C 150
Type ? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site.(Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and
placing)Sunshade, false ceiling:r-1)
17th Floor Concrete
37- Civil N/A Reinforced cement concrete works Sqm 87.85
C.36 using wooden shutter with minimum
cement content relates to mix ratio
1:2:4 having minimum f'cr = 27 Mpa,
and satisfying a specified
compressive strength f?c = 22 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1- CEM
1 (32.5 to 52.5 N) / ASTM-C 150
Type ? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site.(Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and
placing)Sunshade, false ceiling:r-2)
17th Floor Fromwork
37- Civil N/A Reinforced cement concrete works Cum 0.50
C.37 using wooden shutter with minimum
cement content relates to mix ratio
1:2:4 having minimum f'cr = 27 Mpa,
and satisfying a specified
compressive strength f?c = 22 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1- CEM
1 (32.5 to 52.5 N) / ASTM-C 150
Type ? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site.(Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and
placing)Sunshade, false ceiling:s-1)
18th Floor Concrete
37- Civil N/A Reinforced cement concrete works Sqm 5.00
C.38 using wooden shutter with minimum
cement content relates to mix ratio
1:2:4 having minimum f'cr = 27 Mpa,
and satisfying a specified
compressive strength f?c = 22 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1- CEM
1 (32.5 to 52.5 N) / ASTM-C 150
Type ? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site.(Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and
placing)Sunshade, false ceiling:s-2)
18th Floor Fromwork
38- Civil N/A Reinforced cement concrete works Cum 1082.00
A.1 using steel shutter with minimum
cement content relates to mix ratio
1:1.5:3 having minimum f'cr = 30
Mpa, and satisfying a specified
compressive strength f?c = 25 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1-CEM 1
(32.5 to 52.5 N) / ASTM-C 150 Type
? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site. (Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and placing). Should
be RMC)Raft or Mat a-i) Concrete
38- Civil N/A Reinforced cement concrete works Sqm 746.64
A.2 using steel shutter with minimum
cement content relates to mix ratio
1:1.5:3 having minimum f'cr = 30
Mpa, and satisfying a specified
compressive strength f?c = 25 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1-CEM 1
(32.5 to 52.5 N) / ASTM-C 150 Type
? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site. (Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and placing). Should
be RMC)Raft or Mat a-ii)
Formwork/shuttering, prop and
necessary supports etc. (steel)
38- Civil N/A Reinforced cement concrete works Cum 1.00
B.1 using steel shutter with minimum
cement content relates to mix ratio
1:1.5:3 having minimum f'cr = 30
Mpa, and satisfying a specified
compressive strength f?c = 25 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1-CEM 1
(32.5 to 52.5 N) / ASTM-C 150 Type
? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site. (Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and placing). Should
be RMC)Foundation beam: a-i)
Concrete
38- Civil N/A Reinforced cement concrete works Sqm 10.00
B.2 using steel shutter with minimum
cement content relates to mix ratio
1:1.5:3 having minimum f'cr = 30
Mpa, and satisfying a specified
compressive strength f?c = 25 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1-CEM 1
(32.5 to 52.5 N) / ASTM-C 150 Type
? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site. (Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and placing). Should
be RMC)Foundation beam: a-ii)
Formwork/shuttering, prop and
necessary supports etc. (steel)
38- Civil N/A Reinforced cement concrete works Cum 102.00
C.1 using steel shutter with minimum
cement content relates to mix ratio
1:1.5:3 having minimum f'cr = 30
Mpa, and satisfying a specified
compressive strength f?c = 25 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1-CEM 1
(32.5 to 52.5 N) / ASTM-C 150 Type
? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site. (Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and placing). Should
be RMC) Tee beams, Ell beams and
Rectangular beams etca-i) Concrete
Ground floor
38- Civil N/A Reinforced cement concrete works Sqm 863.46
C.2 using steel shutter with minimum
cement content relates to mix ratio
1:1.5:3 having minimum f'cr = 30
Mpa, and satisfying a specified
compressive strength f?c = 25 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1-CEM 1
(32.5 to 52.5 N) / ASTM-C 150 Type
? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site. (Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and placing). Should
be RMC) Tee beams, Ell beams and
Rectangular beams etca-ii)
Formwork/shuttering, prop and
necessary supports etc. (steel)
38- Civil N/A Reinforced cement concrete works Cum 100.00
C.3 using steel shutter with minimum
cement content relates to mix ratio
1:1.5:3 having minimum f'cr = 30
Mpa, and satisfying a specified
compressive strength f?c = 25 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1-CEM 1
(32.5 to 52.5 N) / ASTM-C 150 Type
? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site. (Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and placing). Should
be RMC) Tee beams, Ell beams and
Rectangular beams etcb. Tee beams,
Ell beams and Rectangular beams
etc in 1st Floor:b-i) Concrete
38- Civil N/A Reinforced cement concrete works Sqm 792.40
C.4 using steel shutter with minimum
cement content relates to mix ratio
1:1.5:3 having minimum f'cr = 30
Mpa, and satisfying a specified
compressive strength f?c = 25 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1-CEM 1
(32.5 to 52.5 N) / ASTM-C 150 Type
? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site. (Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and placing). Should
be RMC) Tee beams, Ell beams and
Rectangular beams etcb. Tee beams,
Ell beams and Rectangular beams
etc in 1st Floor:b-ii)
Formwork/shuttering, prop and
necessary supports etc. (steel)
38- Civil N/A Reinforced cement concrete works Cum 92.00
C.5 using steel shutter with minimum
cement content relates to mix ratio
1:1.5:3 having minimum f'cr = 30
Mpa, and satisfying a specified
compressive strength f?c = 25 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1-CEM 1
(32.5 to 52.5 N) / ASTM-C 150 Type
? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site. (Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and placing). Should
be RMC) Tee beams, Ell beams and
Rectangular beams etcc. Tee beams,
Ell beams and Rectangular beams
etc in 2nd Floor:c-i) Concrete
38- Civil N/A Reinforced cement concrete works Sqm 792.00
C.6 using steel shutter with minimum
cement content relates to mix ratio
1:1.5:3 having minimum f'cr = 30
Mpa, and satisfying a specified
compressive strength f?c = 25 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1-CEM 1
(32.5 to 52.5 N) / ASTM-C 150 Type
? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site. (Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and placing). Should
be RMC) Tee beams, Ell beams and
Rectangular beams etcc. Tee beams,
Ell beams and Rectangular beams
etc in 2nd Floor:c-ii)
Formwork/shuttering, prop and
necessary supports etc. (steel)
38- Civil N/A Reinforced cement concrete works Cum 92.00
C.7 using steel shutter with minimum
cement content relates to mix ratio
1:1.5:3 having minimum f'cr = 30
Mpa, and satisfying a specified
compressive strength f?c = 25 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1-CEM 1
(32.5 to 52.5 N) / ASTM-C 150 Type
? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site. (Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and placing). Should
be RMC) Tee beams, Ell beams and
Rectangular beams etcd. Tee beams,
Ell beams and Rectangular beams
etc in 3rd Floord-i) Concrete
38- Civil N/A Reinforced cement concrete works Sqm 792.00
C.8 using steel shutter with minimum
cement content relates to mix ratio
1:1.5:3 having minimum f'cr = 30
Mpa, and satisfying a specified
compressive strength f?c = 25 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1-CEM 1
(32.5 to 52.5 N) / ASTM-C 150 Type
? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site. (Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and placing). Should
be RMC) Tee beams, Ell beams and
Rectangular beams etcd. Tee beams,
Ell beams and Rectangular beams
etc in 3rd Floord-ii)
Formwork/shuttering, prop and
necessary supports etc. (steel)
38- Civil N/A Reinforced cement concrete works Cum 92.00
C.9 using steel shutter with minimum
cement content relates to mix ratio
1:1.5:3 having minimum f'cr = 30
Mpa, and satisfying a specified
compressive strength f?c = 25 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1-CEM 1
(32.5 to 52.5 N) / ASTM-C 150 Type
? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site. (Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and placing). Should
be RMC)e. Tee beams, Ell beams
and Rectangular beams etc in 4th
Floore-i) Concrete
38- Civil N/A Reinforced cement concrete works Sqm 792.00
C.10 using steel shutter with minimum
cement content relates to mix ratio
1:1.5:3 having minimum f'cr = 30
Mpa, and satisfying a specified
compressive strength f?c = 25 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1-CEM 1
(32.5 to 52.5 N) / ASTM-C 150 Type
? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site. (Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and placing). Should
be RMC)e. Tee beams, Ell beams
and Rectangular beams etc in 4th
Floore-ii) Formwork/shuttering, prop
and necessary supports etc. (steel)
38- Civil N/A Reinforced cement concrete works Cum 92.00
C.11 using steel shutter with minimum
cement content relates to mix ratio
1:1.5:3 having minimum f'cr = 30
Mpa, and satisfying a specified
compressive strength f?c = 25 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1-CEM 1
(32.5 to 52.5 N) / ASTM-C 150 Type
? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site. (Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and placing). Should
be RMC)f. Tee beams, Ell beams
and Rectangular beams etc in 5th
Floor:f-i) Concrete
38- Civil N/A Reinforced cement concrete works Sqm 792.00
C.12 using steel shutter with minimum
cement content relates to mix ratio
1:1.5:3 having minimum f'cr = 30
Mpa, and satisfying a specified
compressive strength f?c = 25 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1-CEM 1
(32.5 to 52.5 N) / ASTM-C 150 Type
? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site. (Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and placing). Should
be RMC)f. Tee beams, Ell beams
and Rectangular beams etc in 5th
Floor:f-ii) Formwork/shuttering, prop
and necessary supports etc. (steel)
38- Civil N/A Reinforced cement concrete works Cum 92.00
C.13 using steel shutter with minimum
cement content relates to mix ratio
1:1.5:3 having minimum f'cr = 30
Mpa, and satisfying a specified
compressive strength f?c = 25 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1-CEM 1
(32.5 to 52.5 N) / ASTM-C 150 Type
? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site. (Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and placing). Should
be RMC)g. Tee beams, Ell beams
and Rectangular beams etc in 6th
Floor:g-i) Concrete
38- Civil N/A Reinforced cement concrete works Sqm 792.00
C.14 using steel shutter with minimum
cement content relates to mix ratio
1:1.5:3 having minimum f'cr = 30
Mpa, and satisfying a specified
compressive strength f?c = 25 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1-CEM 1
(32.5 to 52.5 N) / ASTM-C 150 Type
? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site. (Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and placing). Should
be RMC)g. Tee beams, Ell beams
and Rectangular beams etc in 6th
Floor:g-ii) Formwork/shuttering, prop
and necessary supports etc. (steel)
38- Civil N/A Reinforced cement concrete works Cum 92.00
C.15 using steel shutter with minimum
cement content relates to mix ratio
1:1.5:3 having minimum f'cr = 30
Mpa, and satisfying a specified
compressive strength f?c = 25 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1-CEM 1
(32.5 to 52.5 N) / ASTM-C 150 Type
? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site. (Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and placing). Should
be RMC)Tee beams, Ell beams and
Rectangular beams etc in 7th Floor:
h-i) Concrete
38- Civil N/A Reinforced cement concrete works Sqm 792.00
C.16 using steel shutter with minimum
cement content relates to mix ratio
1:1.5:3 having minimum f'cr = 30
Mpa, and satisfying a specified
compressive strength f?c = 25 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1-CEM 1
(32.5 to 52.5 N) / ASTM-C 150 Type
? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site. (Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and placing). Should
be RMC)Tee beams, Ell beams and
Rectangular beams etc in 7th Floor:
h-ii) Formwork/shuttering, prop and
necessary supports etc. (steel)
38- Civil N/A Reinforced cement concrete works Cum 92.00
C.17 using steel shutter with minimum
cement content relates to mix ratio
1:1.5:3 having minimum f'cr = 30
Mpa, and satisfying a specified
compressive strength f?c = 25 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1-CEM 1
(32.5 to 52.5 N) / ASTM-C 150 Type
? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site. (Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and placing). Should
be RMC)Tee beams, Ell beams and
Rectangular beams etc in 8th Floor: i-
i) Concrete
38- Civil N/A Reinforced cement concrete works Sqm 792.00
C.18 using steel shutter with minimum
cement content relates to mix ratio
1:1.5:3 having minimum f'cr = 30
Mpa, and satisfying a specified
compressive strength f?c = 25 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1-CEM 1
(32.5 to 52.5 N) / ASTM-C 150 Type
? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site. (Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and placing). Should
be RMC)Tee beams, Ell beams and
Rectangular beams etc in 8th Floor:i-
ii) Formwork/shuttering, prop and
necessary supports etc. (steel)
38- Civil N/A Reinforced cement concrete works Cum 92.00
C.19 using steel shutter with minimum
cement content relates to mix ratio
1:1.5:3 having minimum f'cr = 30
Mpa, and satisfying a specified
compressive strength f?c = 25 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1-CEM 1
(32.5 to 52.5 N) / ASTM-C 150 Type
? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site. (Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and placing). Should
be RMC)Tee beams, Ell beams and
Rectangular beams etc in 9th Floor: j-
i) Concrete
38- Civil N/A Reinforced cement concrete works Sqm 792.00
C.20 using steel shutter with minimum
cement content relates to mix ratio
1:1.5:3 having minimum f'cr = 30
Mpa, and satisfying a specified
compressive strength f?c = 25 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1-CEM 1
(32.5 to 52.5 N) / ASTM-C 150 Type
? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site. (Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and placing). Should
be RMC)Tee beams, Ell beams and
Rectangular beams etc in 9th Floor:j-
ii) Formwork/shuttering, prop and
necessary supports etc. (steel)
38- Civil N/A Reinforced cement concrete works Cum 92.00
C.21 using steel shutter with minimum
cement content relates to mix ratio
1:1.5:3 having minimum f'cr = 30
Mpa, and satisfying a specified
compressive strength f?c = 25 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1-CEM 1
(32.5 to 52.5 N) / ASTM-C 150 Type
? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site. (Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and placing). Should
be RMC)Tee beams, Ell beams and
Rectangular beams etc in 10th
Floor:k-i) Concrete
38- Civil N/A Reinforced cement concrete works Sqm 792.00
C.22 using steel shutter with minimum
cement content relates to mix ratio
1:1.5:3 having minimum f'cr = 30
Mpa, and satisfying a specified
compressive strength f?c = 25 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1-CEM 1
(32.5 to 52.5 N) / ASTM-C 150 Type
? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site. (Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and placing). Should
be RMC)Tee beams, Ell beams and
Rectangular beams etc in 10th Floor:
k-ii) Formwork/shuttering, prop and
necessary supports etc. (steel)
38- Civil N/A Reinforced cement concrete works Cum 92.00
C.23 using steel shutter with minimum
cement content relates to mix ratio
1:1.5:3 having minimum f'cr = 30
Mpa, and satisfying a specified
compressive strength f?c = 25 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1-CEM 1
(32.5 to 52.5 N) / ASTM-C 150 Type
? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site. (Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and placing). Should
be RMC)Tee beams, Ell beams and
Rectangular beams etc in 11th Floor:
l-i) Concrete
38- Civil N/A Reinforced cement concrete works Sqm 792.00
C.24 using steel shutter with minimum
cement content relates to mix ratio
1:1.5:3 having minimum f'cr = 30
Mpa, and satisfying a specified
compressive strength f?c = 25 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1-CEM 1
(32.5 to 52.5 N) / ASTM-C 150 Type
? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site. (Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and placing). Should
be RMC)Tee beams, Ell beams and
Rectangular beams etc in 11th Floor:
l-ii) Formwork/shuttering, prop and
necessary supports etc. (steel)
38- Civil N/A Reinforced cement concrete works Cum 92.00
C.25 using steel shutter with minimum
cement content relates to mix ratio
1:1.5:3 having minimum f'cr = 30
Mpa, and satisfying a specified
compressive strength f?c = 25 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1-CEM 1
(32.5 to 52.5 N) / ASTM-C 150 Type
? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site. (Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and placing). Should
be RMC)Tee beams, Ell beams and
Rectangular beams etc in 12th Floor:
m-i) Concrete
38- Civil N/A Reinforced cement concrete works Sqm 792.00
C.26 using steel shutter with minimum
cement content relates to mix ratio
1:1.5:3 having minimum f'cr = 30
Mpa, and satisfying a specified
compressive strength f?c = 25 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1-CEM 1
(32.5 to 52.5 N) / ASTM-C 150 Type
? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site. (Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and placing). Should
be RMC)Tee beams, Ell beams and
Rectangular beams etc in 12th Floor:
m-ii) Formwork/shuttering, prop and
necessary supports etc. (steel)
38- Civil N/A Reinforced cement concrete works Cum 92.00
C.27 using steel shutter with minimum
cement content relates to mix ratio
1:1.5:3 having minimum f'cr = 30
Mpa, and satisfying a specified
compressive strength f?c = 25 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1-CEM 1
(32.5 to 52.5 N) / ASTM-C 150 Type
? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site. (Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and placing). Should
be RMC)Tee beams, Ell beams and
Rectangular beams etc in 13th Floor:
n-i) Concrete
38- Civil N/A Reinforced cement concrete works Sqm 792.00
C.28 using steel shutter with minimum
cement content relates to mix ratio
1:1.5:3 having minimum f'cr = 30
Mpa, and satisfying a specified
compressive strength f?c = 25 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1-CEM 1
(32.5 to 52.5 N) / ASTM-C 150 Type
? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site. (Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and placing). Should
be RMC)Tee beams, Ell beams and
Rectangular beams etc in 13th Floor:
n-ii) Formwork/shuttering, prop and
necessary supports etc. (steel)
38- Civil N/A Reinforced cement concrete works Cum 92.00
C.29 using steel shutter with minimum
cement content relates to mix ratio
1:1.5:3 having minimum f'cr = 30
Mpa, and satisfying a specified
compressive strength f?c = 25 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1-CEM 1
(32.5 to 52.5 N) / ASTM-C 150 Type
? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site. (Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and placing). Should
be RMC)Tee beams, Ell beams and
Rectangular beams etc in 14th Floor:
o-i) Concrete
38- Civil N/A Reinforced cement concrete works Sqm 792.00
C.30 using steel shutter with minimum
cement content relates to mix ratio
1:1.5:3 having minimum f'cr = 30
Mpa, and satisfying a specified
compressive strength f?c = 25 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1-CEM 1
(32.5 to 52.5 N) / ASTM-C 150 Type
? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site. (Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and placing). Should
be RMC)Tee beams, Ell beams and
Rectangular beams etc in 14th
Floor:o-ii) Formwork/shuttering, prop
and necessary supports etc. (steel)
38- Civil N/A Reinforced cement concrete works Cum 92.00
C.31 using steel shutter with minimum
cement content relates to mix ratio
1:1.5:3 having minimum f'cr = 30
Mpa, and satisfying a specified
compressive strength f?c = 25 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1-CEM 1
(32.5 to 52.5 N) / ASTM-C 150 Type
? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site. (Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and placing). Should
be RMC)Tee beams, Ell beams and
Rectangular beams etc in 15th Floor:
p-i) Concrete
38- Civil N/A Reinforced cement concrete works Sqm 792.00
C.32 using steel shutter with minimum
cement content relates to mix ratio
1:1.5:3 having minimum f'cr = 30
Mpa, and satisfying a specified
compressive strength f?c = 25 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1-CEM 1
(32.5 to 52.5 N) / ASTM-C 150 Type
? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site. (Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and placing). Should
be RMC)Tee beams, Ell beams and
Rectangular beams etc in 15th
Floor:p-ii) Formwork/shuttering, prop
and necessary supports etc. (steel)
38- Civil N/A Reinforced cement concrete works Cum 92.00
C.33 using steel shutter with minimum
cement content relates to mix ratio
1:1.5:3 having minimum f'cr = 30
Mpa, and satisfying a specified
compressive strength f?c = 25 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1-CEM 1
(32.5 to 52.5 N) / ASTM-C 150 Type
? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site. (Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and placing). Should
be RMC)Tee beams, Ell beams and
Rectangular beams etc in 16th Floor:
q-i) Concrete
38- Civil N/A Reinforced cement concrete works Sqm 792.00
C.34 using steel shutter with minimum
cement content relates to mix ratio
1:1.5:3 having minimum f'cr = 30
Mpa, and satisfying a specified
compressive strength f?c = 25 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1-CEM 1
(32.5 to 52.5 N) / ASTM-C 150 Type
? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site. (Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and placing). Should
be RMC)Tee beams, Ell beams and
Rectangular beams etc in 16th
Floor:q-ii) Formwork/shuttering, prop
and necessary supports etc. (steel)
38- Civil N/A Reinforced cement concrete works Cum 92.00
C.35 using steel shutter with minimum
cement content relates to mix ratio
1:1.5:3 having minimum f'cr = 30
Mpa, and satisfying a specified
compressive strength f?c = 25 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1-CEM 1
(32.5 to 52.5 N) / ASTM-C 150 Type
? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site. (Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and placing). Should
be RMC)Tee beams, Ell beams and
Rectangular beams etc in 17th Floor:
r-i) Concrete
38- Civil N/A Reinforced cement concrete works Sqm 792.00
C.36 using steel shutter with minimum
cement content relates to mix ratio
1:1.5:3 having minimum f'cr = 30
Mpa, and satisfying a specified
compressive strength f?c = 25 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1-CEM 1
(32.5 to 52.5 N) / ASTM-C 150 Type
? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site. (Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and placing). Should
be RMC)Tee beams, Ell beams and
Rectangular beams etc in 17th
Floor:r-ii) Formwork/shuttering, prop
and necessary supports etc. (steel)
38- Civil N/A Reinforced cement concrete works Cum 51.68
C.37 using steel shutter with minimum
cement content relates to mix ratio
1:1.5:3 having minimum f'cr = 30
Mpa, and satisfying a specified
compressive strength f?c = 25 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1-CEM 1
(32.5 to 52.5 N) / ASTM-C 150 Type
? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site. (Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and placing). Should
be RMC)Tee beams, Ell beams and
Rectangular beams etc. in 18th floor
(Chilakota)s-i) Concrete
38- Civil N/A Reinforced cement concrete works Sqm 451.86
C.38 using steel shutter with minimum
cement content relates to mix ratio
1:1.5:3 having minimum f'cr = 30
Mpa, and satisfying a specified
compressive strength f?c = 25 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1-CEM 1
(32.5 to 52.5 N) / ASTM-C 150 Type
? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site. (Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and placing). Should
be RMC)Tee beams, Ell beams and
Rectangular beams etc. in 18th floor
(Chilakota)s-ii) Formwork/shuttering,
prop and necessary supports etc.
(steel)
38- Civil N/A Reinforced cement concrete works Cum 6.41
C.39 using steel shutter with minimum
cement content relates to mix ratio
1:1.5:3 having minimum f'cr = 30
Mpa, and satisfying a specified
compressive strength f?c = 25 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1-CEM 1
(32.5 to 52.5 N) / ASTM-C 150 Type
? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site. (Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and placing). Should
be RMC)Tee beams, Ell beams and
Rectangular beams etc. in 18th floor
(Chilakota)t-1) Concrete
38- Civil N/A Reinforced cement concrete works Sqm 85.74
C.40 using steel shutter with minimum
cement content relates to mix ratio
1:1.5:3 having minimum f'cr = 30
Mpa, and satisfying a specified
compressive strength f?c = 25 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1-CEM 1
(32.5 to 52.5 N) / ASTM-C 150 Type
? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site. (Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and placing). Should
be RMC)Tee beams, Ell beams and
Rectangular beams etc. in 18th floor
(Chilakota)t-2) Fromwork
38- Civil N/A Reinforced cement concrete works Cum 218.00
D.1 using steel shutter with minimum
cement content relates to mix ratio
1:1.5:3 having minimum f'cr = 30
Mpa, and satisfying a specified
compressive strength f?c = 25 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1-CEM 1
(32.5 to 52.5 N) / ASTM-C 150 Type
? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site. (Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and placing). Should
be RMC)Floor and roof slab:Ground
floor a-i) Concrete Ground floor
38- Civil N/A Reinforced cement concrete works Sqm 1491.24
D.2 using steel shutter with minimum
cement content relates to mix ratio
1:1.5:3 having minimum f'cr = 30
Mpa, and satisfying a specified
compressive strength f?c = 25 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1-CEM 1
(32.5 to 52.5 N) / ASTM-C 150 Type
? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site. (Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and placing). Should
be RMC)Floor and roof slab:Ground
floor a-ii) Formwork/shuttering, prop
and necessary supports etc. (steel)
38- Civil N/A Reinforced cement concrete works Cum 227.60
D.3 using steel shutter with minimum
cement content relates to mix ratio
1:1.5:3 having minimum f'cr = 30
Mpa, and satisfying a specified
compressive strength f?c = 25 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1-CEM 1
(32.5 to 52.5 N) / ASTM-C 150 Type
? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site. (Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and placing). Should
be RMC)Floor and roof slab:Floor
and roof slab in 1st Floor b-i)
Concrete Ground floor
38- Civil N/A Reinforced cement concrete works Sqm 1544.73
D.4 using steel shutter with minimum
cement content relates to mix ratio
1:1.5:3 having minimum f'cr = 30
Mpa, and satisfying a specified
compressive strength f?c = 25 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1-CEM 1
(32.5 to 52.5 N) / ASTM-C 150 Type
? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site. (Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and placing). Should
be RMC)Floor and roof slab:Floor
and roof slab in 1st Floor b-ii)
Formwork/shuttering, prop and
necessary supports etc. (steel)
38- Civil N/A Reinforced cement concrete works Cum 177.00
D.5 using steel shutter with minimum
cement content relates to mix ratio
1:1.5:3 having minimum f'cr = 30
Mpa, and satisfying a specified
compressive strength f?c = 25 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1-CEM 1
(32.5 to 52.5 N) / ASTM-C 150 Type
? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site. (Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and placing). Should
be RMC)Floor and roof slab:Floor
and roof slab in 2nd Floor c-i)
Concrete
38- Civil N/A Reinforced cement concrete works Sqm 1261.58
D.6 using steel shutter with minimum
cement content relates to mix ratio
1:1.5:3 having minimum f'cr = 30
Mpa, and satisfying a specified
compressive strength f?c = 25 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1-CEM 1
(32.5 to 52.5 N) / ASTM-C 150 Type
? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site. (Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and placing). Should
be RMC)Floor and roof slab:Floor
and roof slab in 2nd Floor c-ii)
Formwork/shuttering, prop and
necessary supports etc. (steel)
38- Civil N/A Reinforced cement concrete works Cum 157.00
D.7 using steel shutter with minimum
cement content relates to mix ratio
1:1.5:3 having minimum f'cr = 30
Mpa, and satisfying a specified
compressive strength f?c = 25 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1-CEM 1
(32.5 to 52.5 N) / ASTM-C 150 Type
? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site. (Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and placing). Should
be RMC)Floor and roof slab:Floor
and roof slab in 3rd Floor d-i)
Concrete
38- Civil N/A Reinforced cement concrete works Sqm 1232.08
D.8 using steel shutter with minimum
cement content relates to mix ratio
1:1.5:3 having minimum f'cr = 30
Mpa, and satisfying a specified
compressive strength f?c = 25 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1-CEM 1
(32.5 to 52.5 N) / ASTM-C 150 Type
? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site. (Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and placing). Should
be RMC)Floor and roof slab:Floor
and roof slab in 3rd Floord-ii)
Formwork/shuttering, prop and
necessary supports etc. (steel)
38- Civil N/A Reinforced cement concrete works Cum 157.00
D.9 using steel shutter with minimum
cement content relates to mix ratio
1:1.5:3 having minimum f'cr = 30
Mpa, and satisfying a specified
compressive strength f?c = 25 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1-CEM 1
(32.5 to 52.5 N) / ASTM-C 150 Type
? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site. (Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and placing). Should
be RMC)Floor and roof slab:Floor
and roof slab in 4th Floor e-i)
Concrete
38- Civil N/A Reinforced cement concrete works Sqm 1232.08
D.10 using steel shutter with minimum
cement content relates to mix ratio
1:1.5:3 having minimum f'cr = 30
Mpa, and satisfying a specified
compressive strength f?c = 25 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1-CEM 1
(32.5 to 52.5 N) / ASTM-C 150 Type
? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site. (Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and placing). Should
be RMC)Floor and roof slab:Floor
and roof slab in 4th Floor e-ii)
Formwork/shuttering, prop and
necessary supports etc. (steel)
38- Civil N/A Reinforced cement concrete works Cum 157.00
D.11 using steel shutter with minimum
cement content relates to mix ratio
1:1.5:3 having minimum f'cr = 30
Mpa, and satisfying a specified
compressive strength f?c = 25 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1-CEM 1
(32.5 to 52.5 N) / ASTM-C 150 Type
? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site. (Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and placing). Should
be RMC)Floor and roof slab:Floor
and roof slab in 5th Floor f-i)
Concrete
38- Civil N/A Reinforced cement concrete works Sqm 1232.08
D.12 using steel shutter with minimum
cement content relates to mix ratio
1:1.5:3 having minimum f'cr = 30
Mpa, and satisfying a specified
compressive strength f?c = 25 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1-CEM 1
(32.5 to 52.5 N) / ASTM-C 150 Type
? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site. (Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and placing). Should
be RMC)Floor and roof slab:Floor
and roof slab in 5th Floor f-ii)
Formwork/shuttering, prop and
necessary supports etc. (steel)
38- Civil N/A Reinforced cement concrete works Cum 157.00
D.13 using steel shutter with minimum
cement content relates to mix ratio
1:1.5:3 having minimum f'cr = 30
Mpa, and satisfying a specified
compressive strength f?c = 25 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1-CEM 1
(32.5 to 52.5 N) / ASTM-C 150 Type
? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site. (Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and placing). Should
be RMC)Floor and roof slab:Floor
and roof slab in 6th Floor g-i)
Concrete
38- Civil N/A Reinforced cement concrete works Sqm 1232.08
D.14 using steel shutter with minimum
cement content relates to mix ratio
1:1.5:3 having minimum f'cr = 30
Mpa, and satisfying a specified
compressive strength f?c = 25 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1-CEM 1
(32.5 to 52.5 N) / ASTM-C 150 Type
? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site. (Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and placing). Should
be RMC)Floor and roof slab:Floor
and roof slab in 6th Floor g-ii)
Formwork/shuttering, prop and
necessary supports etc. (steel)
38- Civil N/A Reinforced cement concrete works Cum 157.00
D.15 using steel shutter with minimum
cement content relates to mix ratio
1:1.5:3 having minimum f'cr = 30
Mpa, and satisfying a specified
compressive strength f?c = 25 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1-CEM 1
(32.5 to 52.5 N) / ASTM-C 150 Type
? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site. (Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and placing). Should
be RMC)Floor and roof slab:Floor
and roof slab in 7th Floor h-i)
Concrete
38- Civil N/A Reinforced cement concrete works Sqm 1232.08
D.16 using steel shutter with minimum
cement content relates to mix ratio
1:1.5:3 having minimum f'cr = 30
Mpa, and satisfying a specified
compressive strength f?c = 25 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1-CEM 1
(32.5 to 52.5 N) / ASTM-C 150 Type
? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site. (Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and placing). Should
be RMC)Floor and roof slab:Floor
and roof slab in 7th Floor h-ii)
Formwork/shuttering, prop and
necessary supports etc. (steel)
38- Civil N/A Reinforced cement concrete works Cum 157.00
D.17 using steel shutter with minimum
cement content relates to mix ratio
1:1.5:3 having minimum f'cr = 30
Mpa, and satisfying a specified
compressive strength f?c = 25 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1-CEM 1
(32.5 to 52.5 N) / ASTM-C 150 Type
? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site. (Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and placing). Should
be RMC)Floor and roof slab:Floor
and roof slab in 8th Floor: i-i)
Concrete
38- Civil N/A Reinforced cement concrete works Sqm 1232.08
D.18 using steel shutter with minimum
cement content relates to mix ratio
1:1.5:3 having minimum f'cr = 30
Mpa, and satisfying a specified
compressive strength f?c = 25 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1-CEM 1
(32.5 to 52.5 N) / ASTM-C 150 Type
? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site. (Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and placing). Should
be RMC)Floor and roof slab:Floor
and roof slab in 8th Floor: i-ii)
Formwork/shuttering, prop and
necessary supports etc. (steel)
38- Civil N/A Reinforced cement concrete works Cum 157.00
D.19 using steel shutter with minimum
cement content relates to mix ratio
1:1.5:3 having minimum f'cr = 30
Mpa, and satisfying a specified
compressive strength f?c = 25 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1-CEM 1
(32.5 to 52.5 N) / ASTM-C 150 Type
? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site. (Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and placing). Should
be RMC)Floor and roof slab:Floor
and roof slab in 9th Floor: j-i)
Concrete
38- Civil N/A Reinforced cement concrete works Sqm 1232.08
D.20 using steel shutter with minimum
cement content relates to mix ratio
1:1.5:3 having minimum f'cr = 30
Mpa, and satisfying a specified
compressive strength f?c = 25 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1-CEM 1
(32.5 to 52.5 N) / ASTM-C 150 Type
? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site. (Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and placing). Should
be RMC)Floor and roof slab:Floor
and roof slab in 9th Floor: j-ii)
Formwork/shuttering, prop and
necessary supports etc. (steel)
38- Civil N/A Reinforced cement concrete works Cum 157.00
D.21 using steel shutter with minimum
cement content relates to mix ratio
1:1.5:3 having minimum f'cr = 30
Mpa, and satisfying a specified
compressive strength f?c = 25 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1-CEM 1
(32.5 to 52.5 N) / ASTM-C 150 Type
? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site. (Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and placing). Should
be RMC)Floor and roof slab:Floor
and roof slab in 10th Floor: k-i)
Concrete
38- Civil N/A Reinforced cement concrete works Sqm 1232.08
D.22 using steel shutter with minimum
cement content relates to mix ratio
1:1.5:3 having minimum f'cr = 30
Mpa, and satisfying a specified
compressive strength f?c = 25 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1-CEM 1
(32.5 to 52.5 N) / ASTM-C 150 Type
? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site. (Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and placing). Should
be RMC)Floor and roof slab:Floor
and roof slab in 10th Floor: k-ii)
Formwork/shuttering, prop and
necessary supports etc. (steel)
38- Civil N/A Reinforced cement concrete works Cum 157.00
D.23 using steel shutter with minimum
cement content relates to mix ratio
1:1.5:3 having minimum f'cr = 30
Mpa, and satisfying a specified
compressive strength f?c = 25 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1-CEM 1
(32.5 to 52.5 N) / ASTM-C 150 Type
? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site. (Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and placing). Should
be RMC)Floor and roof slab:Floor
and roof slab in 11th Floor l-i)
Concrete
38- Civil N/A Reinforced cement concrete works Sqm 1232.08
D.24 using steel shutter with minimum
cement content relates to mix ratio
1:1.5:3 having minimum f'cr = 30
Mpa, and satisfying a specified
compressive strength f?c = 25 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1-CEM 1
(32.5 to 52.5 N) / ASTM-C 150 Type
? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site. (Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and placing). Should
be RMC)Floor and roof slab:Floor
and roof slab in 11th Floor l-ii)
Formwork/shuttering, prop and
necessary supports etc. (steel)
38- Civil N/A Reinforced cement concrete works Cum 157.00
D.25 using steel shutter with minimum
cement content relates to mix ratio
1:1.5:3 having minimum f'cr = 30
Mpa, and satisfying a specified
compressive strength f?c = 25 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1-CEM 1
(32.5 to 52.5 N) / ASTM-C 150 Type
? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site. (Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and placing). Should
be RMC)Floor and roof slab:Floor
and roof slab in 12th Floor m-i)
Concrete
38- Civil N/A Reinforced cement concrete works Sqm 1232.08
D.26 using steel shutter with minimum
cement content relates to mix ratio
1:1.5:3 having minimum f'cr = 30
Mpa, and satisfying a specified
compressive strength f?c = 25 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1-CEM 1
(32.5 to 52.5 N) / ASTM-C 150 Type
? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site. (Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and placing). Should
be RMC)Floor and roof slab:Floor
and roof slab in 12th Floor m-ii)
Formwork/shuttering, prop and
necessary supports etc. (steel)
38- Civil N/A Reinforced cement concrete works Cum 157.00
D.27 using steel shutter with minimum
cement content relates to mix ratio
1:1.5:3 having minimum f'cr = 30
Mpa, and satisfying a specified
compressive strength f?c = 25 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1-CEM 1
(32.5 to 52.5 N) / ASTM-C 150 Type
? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site. (Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and placing). Should
be RMC)Floor and roof slab:Floor
and roof slab in 13th Floor: n-i)
Concrete
38- Civil N/A Reinforced cement concrete works Sqm 1232.08
D.28 using steel shutter with minimum
cement content relates to mix ratio
1:1.5:3 having minimum f'cr = 30
Mpa, and satisfying a specified
compressive strength f?c = 25 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1-CEM 1
(32.5 to 52.5 N) / ASTM-C 150 Type
? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site. (Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and placing). Should
be RMC)Floor and roof slab:Floor
and roof slab in 13th Floor: n-ii)
Formwork/shuttering, prop and
necessary supports etc. (steel)
38- Civil N/A Reinforced cement concrete works Cum 157.00
D.29 using steel shutter with minimum
cement content relates to mix ratio
1:1.5:3 having minimum f'cr = 30
Mpa, and satisfying a specified
compressive strength f?c = 25 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1-CEM 1
(32.5 to 52.5 N) / ASTM-C 150 Type
? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site. (Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and placing). Should
be RMC)Floor and roof slab:Floor
and roof slab in 14th Floor: o-i)
Concrete
38- Civil N/A Reinforced cement concrete works Sqm 1232.08
D.30 using steel shutter with minimum
cement content relates to mix ratio
1:1.5:3 having minimum f'cr = 30
Mpa, and satisfying a specified
compressive strength f?c = 25 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1-CEM 1
(32.5 to 52.5 N) / ASTM-C 150 Type
? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site. (Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and placing). Should
be RMC)Floor and roof slab:Floor
and roof slab in 14th Floor: o-ii)
Formwork/shuttering, prop and
necessary supports etc. (steel)
38- Civil N/A Reinforced cement concrete works Cum 157.00
D.31 using steel shutter with minimum
cement content relates to mix ratio
1:1.5:3 having minimum f'cr = 30
Mpa, and satisfying a specified
compressive strength f?c = 25 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1-CEM 1
(32.5 to 52.5 N) / ASTM-C 150 Type
? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site. (Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and placing). Should
be RMC)Floor and roof slab:Floor
and roof slab in 15th Floor: p-i)
Concrete
38- Civil N/A Reinforced cement concrete works Sqm 1232.08
D.32 using steel shutter with minimum
cement content relates to mix ratio
1:1.5:3 having minimum f'cr = 30
Mpa, and satisfying a specified
compressive strength f?c = 25 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1-CEM 1
(32.5 to 52.5 N) / ASTM-C 150 Type
? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site. (Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and placing). Should
be RMC)Floor and roof slab:Floor
and roof slab in 15th Floor: p-ii)
Formwork/shuttering, prop and
necessary supports etc. (steel)
38- Civil N/A Reinforced cement concrete works Cum 157.00
D.33 using steel shutter with minimum
cement content relates to mix ratio
1:1.5:3 having minimum f'cr = 30
Mpa, and satisfying a specified
compressive strength f?c = 25 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1-CEM 1
(32.5 to 52.5 N) / ASTM-C 150 Type
? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site. (Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and placing). Should
be RMC)Floor and roof slab:Floor
and roof slab in 16th Floor: q-i)
Concrete
38- Civil N/A Reinforced cement concrete works Sqm 1232.08
D.34 using steel shutter with minimum
cement content relates to mix ratio
1:1.5:3 having minimum f'cr = 30
Mpa, and satisfying a specified
compressive strength f?c = 25 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1-CEM 1
(32.5 to 52.5 N) / ASTM-C 150 Type
? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site. (Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and placing). Should
be RMC)Floor and roof slab:Floor
and roof slab in 16th Floor: q-ii)
Formwork/shuttering, prop and
necessary supports etc. (steel)
38- Civil N/A Reinforced cement concrete works Cum 157.00
D.35 using steel shutter with minimum
cement content relates to mix ratio
1:1.5:3 having minimum f'cr = 30
Mpa, and satisfying a specified
compressive strength f?c = 25 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1-CEM 1
(32.5 to 52.5 N) / ASTM-C 150 Type
? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site. (Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and placing). Should
be RMC)Floor and roof slab:Floor
and roof slab in 17th Floor (Roof
slab) r-i) Concrete
38- Civil N/A Reinforced cement concrete works Sqm 1232.08
D.36 using steel shutter with minimum
cement content relates to mix ratio
1:1.5:3 having minimum f'cr = 30
Mpa, and satisfying a specified
compressive strength f?c = 25 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1-CEM 1
(32.5 to 52.5 N) / ASTM-C 150 Type
? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site. (Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and placing). Should
be RMC)Floor and roof slab:Floor
and roof slab in 17th Floor (Roof
slab) r-ii) Formwork/shuttering, prop
and necessary supports etc. (steel)
38- Civil N/A Reinforced cement concrete works Cum 81.95
D.37 using steel shutter with minimum
cement content relates to mix ratio
1:1.5:3 having minimum f'cr = 30
Mpa, and satisfying a specified
compressive strength f?c = 25 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1-CEM 1
(32.5 to 52.5 N) / ASTM-C 150 Type
? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site. (Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and placing). Should
be RMC)Floor and roof slab:Floor
and roof slab in 18th Floor (Chilakota
& machine room): s-i) Concrete
38- Civil N/A Reinforced cement concrete works Sqm 605.74
D.38 using steel shutter with minimum
cement content relates to mix ratio
1:1.5:3 having minimum f'cr = 30
Mpa, and satisfying a specified
compressive strength f?c = 25 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1-CEM 1
(32.5 to 52.5 N) / ASTM-C 150 Type
? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site. (Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and placing). Should
be RMC)Floor and roof slab:Floor
and roof slab in 18th Floor (Chilakota
& machine room): s-ii)
Formwork/shuttering, prop and
necessary supports etc. (steel)
38- Civil N/A Reinforced cement concrete works Cum 29.40
D.39 using steel shutter with minimum
cement content relates to mix ratio
1:1.5:3 having minimum f'cr = 30
Mpa, and satisfying a specified
compressive strength f?c = 25 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1-CEM 1
(32.5 to 52.5 N) / ASTM-C 150 Type
? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site. (Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and placing). Should
be RMC)Floor and roof slab:19th
Floor (Chilakota & machine room) t-
1) Concrete
38- Civil N/A Reinforced cement concrete works Sqm 159.55
D.40 using steel shutter with minimum
cement content relates to mix ratio
1:1.5:3 having minimum f'cr = 30
Mpa, and satisfying a specified
compressive strength f?c = 25 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1-CEM 1
(32.5 to 52.5 N) / ASTM-C 150 Type
? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site. (Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and placing). Should
be RMC)Floor and roof slab:19th
Floor (Chilakota & machine room) t-
2) Fromwork
38- Civil N/A Reinforced cement concrete works Cum 37.31
E.1 using steel shutter with minimum
cement content relates to mix ratio
1:1.5:3 having minimum f'cr = 30
Mpa, and satisfying a specified
compressive strength f?c = 25 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1-CEM 1
(32.5 to 52.5 N) / ASTM-C 150 Type
? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site. (Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and placing). Should
be RMC)Stair case slab, steps &
ramps a-i) Concrete Ground floor
38- Civil N/A Reinforced cement concrete works Sqm 239.55
E.2 using steel shutter with minimum
cement content relates to mix ratio
1:1.5:3 having minimum f'cr = 30
Mpa, and satisfying a specified
compressive strength f?c = 25 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1-CEM 1
(32.5 to 52.5 N) / ASTM-C 150 Type
? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site. (Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and placing). Should
be RMC)Stair case slab, steps &
ramps a-ii) Formwork/shuttering,
prop and necessary supports etc.
(steel)
38- Civil N/A Reinforced cement concrete works Cum 11.60
E.3 using steel shutter with minimum
cement content relates to mix ratio
1:1.5:3 having minimum f'cr = 30
Mpa, and satisfying a specified
compressive strength f?c = 25 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1-CEM 1
(32.5 to 52.5 N) / ASTM-C 150 Type
? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site. (Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and placing). Should
be RMC)Stair case slab and steps in
1st Floorb-i) Concrete
38- Civil N/A Reinforced cement concrete works Sqm 90.77
E.4 using steel shutter with minimum
cement content relates to mix ratio
1:1.5:3 having minimum f'cr = 30
Mpa, and satisfying a specified
compressive strength f?c = 25 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1-CEM 1
(32.5 to 52.5 N) / ASTM-C 150 Type
? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site. (Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and placing). Should
be RMC)Stair case slab and steps in
1st Floorb-ii) Formwork/shuttering,
prop and necessary supports etc.
(steel)
38- Civil N/A Reinforced cement concrete works Cum 11.60
E.5 using steel shutter with minimum
cement content relates to mix ratio
1:1.5:3 having minimum f'cr = 30
Mpa, and satisfying a specified
compressive strength f?c = 25 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1-CEM 1
(32.5 to 52.5 N) / ASTM-C 150 Type
? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site. (Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and placing). Should
be RMC)Stair case slab and steps in
2nd Floorc-i) Concrete
38- Civil N/A Reinforced cement concrete works Sqm 90.77
E.6 using steel shutter with minimum
cement content relates to mix ratio
1:1.5:3 having minimum f'cr = 30
Mpa, and satisfying a specified
compressive strength f?c = 25 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1-CEM 1
(32.5 to 52.5 N) / ASTM-C 150 Type
? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site. (Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and placing). Should
be RMC)Stair case slab and steps in
2nd Floorc-ii) Formwork/shuttering,
prop and necessary supports etc.
(steel)
38- Civil N/A Reinforced cement concrete works Cum 11.60
E.7 using steel shutter with minimum
cement content relates to mix ratio
1:1.5:3 having minimum f'cr = 30
Mpa, and satisfying a specified
compressive strength f?c = 25 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1-CEM 1
(32.5 to 52.5 N) / ASTM-C 150 Type
? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site. (Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and placing). Should
be RMC)Stair case slab and steps in
3rd Floord-i) Concrete
38- Civil N/A Reinforced cement concrete works Sqm 90.77
E.8 using steel shutter with minimum
cement content relates to mix ratio
1:1.5:3 having minimum f'cr = 30
Mpa, and satisfying a specified
compressive strength f?c = 25 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1-CEM 1
(32.5 to 52.5 N) / ASTM-C 150 Type
? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site. (Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and placing). Should
be RMC)Stair case slab and steps in
3rd Floord-ii) Formwork/shuttering,
prop and necessary supports etc.
(steel)
38- Civil N/A Reinforced cement concrete works Cum 11.60
E.9 using steel shutter with minimum
cement content relates to mix ratio
1:1.5:3 having minimum f'cr = 30
Mpa, and satisfying a specified
compressive strength f?c = 25 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1-CEM 1
(32.5 to 52.5 N) / ASTM-C 150 Type
? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site. (Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and placing). Should
be RMC)Stair case slab and steps in
4th Floore-i) Concrete
38- Civil N/A Reinforced cement concrete works Sqm 90.77
E.10 using steel shutter with minimum
cement content relates to mix ratio
1:1.5:3 having minimum f'cr = 30
Mpa, and satisfying a specified
compressive strength f?c = 25 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1-CEM 1
(32.5 to 52.5 N) / ASTM-C 150 Type
? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site. (Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and placing). Should
be RMC)Stair case slab and steps in
4th Floore-ii) Formwork/shuttering,
prop and necessary supports etc.
(steel)
38- Civil N/A Reinforced cement concrete works Cum 11.60
E.11 using steel shutter with minimum
cement content relates to mix ratio
1:1.5:3 having minimum f'cr = 30
Mpa, and satisfying a specified
compressive strength f?c = 25 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1-CEM 1
(32.5 to 52.5 N) / ASTM-C 150 Type
? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site. (Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and placing). Should
be RMC)Stair case slab and steps in
5th Floor:f-i) Concrete
38- Civil N/A Reinforced cement concrete works Sqm 90.77
E.12 using steel shutter with minimum
cement content relates to mix ratio
1:1.5:3 having minimum f'cr = 30
Mpa, and satisfying a specified
compressive strength f?c = 25 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1-CEM 1
(32.5 to 52.5 N) / ASTM-C 150 Type
? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site. (Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and placing). Should
be RMC)Stair case slab and steps in
5th Floor:f-ii) Formwork/shuttering,
prop and necessary supports etc.
(steel)
38- Civil N/A Reinforced cement concrete works Cum 11.60
E.13 using steel shutter with minimum
cement content relates to mix ratio
1:1.5:3 having minimum f'cr = 30
Mpa, and satisfying a specified
compressive strength f?c = 25 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1-CEM 1
(32.5 to 52.5 N) / ASTM-C 150 Type
? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site. (Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and placing). Should
be RMC)Stair case slab and steps in
6th Floor:g-i) Concrete
38- Civil N/A Reinforced cement concrete works Sqm 90.77
E.14 using steel shutter with minimum
cement content relates to mix ratio
1:1.5:3 having minimum f'cr = 30
Mpa, and satisfying a specified
compressive strength f?c = 25 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1-CEM 1
(32.5 to 52.5 N) / ASTM-C 150 Type
? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site. (Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and placing). Should
be RMC)Stair case slab and steps in
6th Floor:g-ii) Formwork/shuttering,
prop and necessary supports etc.
(steel)
38- Civil N/A Reinforced cement concrete works Cum 11.60
E.15 using steel shutter with minimum
cement content relates to mix ratio
1:1.5:3 having minimum f'cr = 30
Mpa, and satisfying a specified
compressive strength f?c = 25 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1-CEM 1
(32.5 to 52.5 N) / ASTM-C 150 Type
? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site. (Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and placing). Should
be RMC) Stair case slab and steps
in 7th Floor:h-i) Concrete
38- Civil N/A Reinforced cement concrete works Sqm 90.77
E.16 using steel shutter with minimum
cement content relates to mix ratio
1:1.5:3 having minimum f'cr = 30
Mpa, and satisfying a specified
compressive strength f?c = 25 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1-CEM 1
(32.5 to 52.5 N) / ASTM-C 150 Type
? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site. (Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and placing). Should
be RMC) Stair case slab and steps
in 7th Floor:h-ii) Formwork/shuttering,
prop and necessary supports etc.
(steel)
38- Civil N/A Reinforced cement concrete works Cum 11.60
E.17 using steel shutter with minimum
cement content relates to mix ratio
1:1.5:3 having minimum f'cr = 30
Mpa, and satisfying a specified
compressive strength f?c = 25 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1-CEM 1
(32.5 to 52.5 N) / ASTM-C 150 Type
? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site. (Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and placing). Should
be RMC) Stair case slab and steps
in 8th Floor:i-i) Concrete
38- Civil N/A Reinforced cement concrete works Sqm 90.77
E.18 using steel shutter with minimum
cement content relates to mix ratio
1:1.5:3 having minimum f'cr = 30
Mpa, and satisfying a specified
compressive strength f?c = 25 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1-CEM 1
(32.5 to 52.5 N) / ASTM-C 150 Type
? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site. (Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and placing). Should
be RMC) Stair case slab and steps
in 8th Floor:i-ii) Formwork/shuttering,
prop and necessary supports etc.
(steel)
38- Civil N/A Reinforced cement concrete works Cum 11.60
E.19 using steel shutter with minimum
cement content relates to mix ratio
1:1.5:3 having minimum f'cr = 30
Mpa, and satisfying a specified
compressive strength f?c = 25 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1-CEM 1
(32.5 to 52.5 N) / ASTM-C 150 Type
? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site. (Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and placing). Should
be RMC) Stair case slab and stepsin
9th Floor:j-i) Concrete
38- Civil N/A Reinforced cement concrete works Sqm 90.77
E.20 using steel shutter with minimum
cement content relates to mix ratio
1:1.5:3 having minimum f'cr = 30
Mpa, and satisfying a specified
compressive strength f?c = 25 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1-CEM 1
(32.5 to 52.5 N) / ASTM-C 150 Type
? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site. (Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and placing). Should
be RMC) Stair case slab and stepsin
9th Floor:j-ii) Formwork/shuttering,
prop and necessary supports etc.
(steel)
38- Civil N/A Reinforced cement concrete works Cum 11.60
E.21 using steel shutter with minimum
cement content relates to mix ratio
1:1.5:3 having minimum f'cr = 30
Mpa, and satisfying a specified
compressive strength f?c = 25 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1-CEM 1
(32.5 to 52.5 N) / ASTM-C 150 Type
? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site. (Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and placing). Should
be RMC) Stair case slab and steps
in 10th Floor:k-i) Concrete
38- Civil N/A Reinforced cement concrete works Sqm 90.77
E.22 using steel shutter with minimum
cement content relates to mix ratio
1:1.5:3 having minimum f'cr = 30
Mpa, and satisfying a specified
compressive strength f?c = 25 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1-CEM 1
(32.5 to 52.5 N) / ASTM-C 150 Type
? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site. (Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and placing). Should
be RMC) Stair case slab and steps
in 10th Floor:k-ii)
Formwork/shuttering, prop and
necessary supports etc. (steel)
38- Civil N/A Reinforced cement concrete works Cum 11.60
E.23 using steel shutter with minimum
cement content relates to mix ratio
1:1.5:3 having minimum f'cr = 30
Mpa, and satisfying a specified
compressive strength f?c = 25 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1-CEM 1
(32.5 to 52.5 N) / ASTM-C 150 Type
? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site. (Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and placing). Should
be RMC) Stair case slab and steps
in 11th Floor:l-i) Concrete
38- Civil N/A Reinforced cement concrete works Sqm 90.77
E.24 using steel shutter with minimum
cement content relates to mix ratio
1:1.5:3 having minimum f'cr = 30
Mpa, and satisfying a specified
compressive strength f?c = 25 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1-CEM 1
(32.5 to 52.5 N) / ASTM-C 150 Type
? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site. (Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and placing). Should
be RMC) Stair case slab and steps
in 11th Floor:l-ii)
Formwork/shuttering, prop and
necessary supports etc. (steel)
38- Civil N/A Reinforced cement concrete works Cum 11.60
E.25 using steel shutter with minimum
cement content relates to mix ratio
1:1.5:3 having minimum f'cr = 30
Mpa, and satisfying a specified
compressive strength f?c = 25 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1-CEM 1
(32.5 to 52.5 N) / ASTM-C 150 Type
? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site. (Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and placing). Should
be RMC) Stair case slab and steps
in 12th Floor:m-i) Concrete
38- Civil N/A Reinforced cement concrete works Sqm 90.77
E.26 using steel shutter with minimum
cement content relates to mix ratio
1:1.5:3 having minimum f'cr = 30
Mpa, and satisfying a specified
compressive strength f?c = 25 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1-CEM 1
(32.5 to 52.5 N) / ASTM-C 150 Type
? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site. (Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and placing). Should
be RMC) Stair case slab and steps
in 12th Floor:m-ii)
Formwork/shuttering, prop and
necessary supports etc. (steel)
38- Civil N/A Reinforced cement concrete works Cum 11.60
E.27 using steel shutter with minimum
cement content relates to mix ratio
1:1.5:3 having minimum f'cr = 30
Mpa, and satisfying a specified
compressive strength f?c = 25 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1-CEM 1
(32.5 to 52.5 N) / ASTM-C 150 Type
? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site. (Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and placing). Should
be RMC) Stair case slab and steps
in 13th Floor:n-i) Concrete
38- Civil N/A Reinforced cement concrete works Sqm 90.77
E.28 using steel shutter with minimum
cement content relates to mix ratio
1:1.5:3 having minimum f'cr = 30
Mpa, and satisfying a specified
compressive strength f?c = 25 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1-CEM 1
(32.5 to 52.5 N) / ASTM-C 150 Type
? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site. (Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and placing). Should
be RMC) Stair case slab and steps
in 13th Floor:n-ii)
Formwork/shuttering, prop and
necessary supports etc. (steel)
38- Civil N/A Reinforced cement concrete works Cum 11.60
E.29 using steel shutter with minimum
cement content relates to mix ratio
1:1.5:3 having minimum f'cr = 30
Mpa, and satisfying a specified
compressive strength f?c = 25 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1-CEM 1
(32.5 to 52.5 N) / ASTM-C 150 Type
? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site. (Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and placing). Should
be RMC) Stair case slab and steps
in 14th Floor:o-i) Concrete
38- Civil N/A Reinforced cement concrete works Sqm 90.77
E.30 using steel shutter with minimum
cement content relates to mix ratio
1:1.5:3 having minimum f'cr = 30
Mpa, and satisfying a specified
compressive strength f?c = 25 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1-CEM 1
(32.5 to 52.5 N) / ASTM-C 150 Type
? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site. (Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and placing). Should
be RMC) Stair case slab and steps
in 14th Floor:o-ii)
Formwork/shuttering, prop and
necessary supports etc. (steel)
38- Civil N/A Reinforced cement concrete works Cum 11.60
E.31 using steel shutter with minimum
cement content relates to mix ratio
1:1.5:3 having minimum f'cr = 30
Mpa, and satisfying a specified
compressive strength f?c = 25 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1-CEM 1
(32.5 to 52.5 N) / ASTM-C 150 Type
? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site. (Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and placing). Should
be RMC) Stair case slab and steps
in 15th Floor:p-i) Concrete
38- Civil N/A Reinforced cement concrete works Sqm 90.77
E.32 using steel shutter with minimum
cement content relates to mix ratio
1:1.5:3 having minimum f'cr = 30
Mpa, and satisfying a specified
compressive strength f?c = 25 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1-CEM 1
(32.5 to 52.5 N) / ASTM-C 150 Type
? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site. (Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and placing). Should
be RMC) Stair case slab and steps
in 15th Floor:p-ii)
Formwork/shuttering, prop and
necessary supports etc. (steel)
38- Civil N/A Reinforced cement concrete works Cum 11.60
E.33 using steel shutter with minimum
cement content relates to mix ratio
1:1.5:3 having minimum f'cr = 30
Mpa, and satisfying a specified
compressive strength f?c = 25 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1-CEM 1
(32.5 to 52.5 N) / ASTM-C 150 Type
? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site. (Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and placing). Should
be RMC) Stair case slab and steps
in 16th Floor:q-i) Concrete
38- Civil N/A Reinforced cement concrete works Sqm 90.77
E.34 using steel shutter with minimum
cement content relates to mix ratio
1:1.5:3 having minimum f'cr = 30
Mpa, and satisfying a specified
compressive strength f?c = 25 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1-CEM 1
(32.5 to 52.5 N) / ASTM-C 150 Type
? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site. (Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and placing). Should
be RMC) Stair case slab and steps
in 16th Floor:q-ii)
Formwork/shuttering, prop and
necessary supports etc. (steel)
38- Civil N/A Reinforced cement concrete works Cum 6.10
E.35 using steel shutter with minimum
cement content relates to mix ratio
1:1.5:3 having minimum f'cr = 30
Mpa, and satisfying a specified
compressive strength f?c = 25 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1-CEM 1
(32.5 to 52.5 N) / ASTM-C 150 Type
? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site. (Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and placing). Should
be RMC) Stair case slab and steps
in 17th Floor:r-i) Concrete
38- Civil N/A Reinforced cement concrete works Sqm 42.77
E.36 using steel shutter with minimum
cement content relates to mix ratio
1:1.5:3 having minimum f'cr = 30
Mpa, and satisfying a specified
compressive strength f?c = 25 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1-CEM 1
(32.5 to 52.5 N) / ASTM-C 150 Type
? I, best quality Sylhet sand or
coarse sand of equivalent F.M. 2.2
and 20 mm down well graded stone
chips conforming to ASTM C-33,
making, placing shutter in position and
maintaining true to plumb, making
shutter water-tight properly, placing
reinforcement in position; RMC
mixing , casting in forms, compacting
by vibrator machine and curing at
least for 28 days, removing centering-
shuttering including cost of water,
electricity, testing and other charges
etc. all complete approved and
accepted by the Engineer and making
all type of concrete mixture with the
help of automatic batching plant at
site. (Rate is excluding the cost of
reinforcement and its fabrication,
binding, welding and placing). Should
be RMC) Stair case slab and steps
in 17th Floor:r-ii)
Formwork/shuttering, prop and
necessary supports etc. (steel)
39.1 Civil N/A Reinforced cement concrete works Cum 562.73
using steel shutter with minimum
cement content relates to mix ratio
1:1.25:2.5 having minimum f'cr = 40
Mpa, and satisfying a specified
compressive strength f?c = 32 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1-CEM 1
(32.5 to 52.5 N) / ASTM-C 150 Type
? I, with approved high range
admixture, best quality coarse sand
[Sylhet sand or coarse sand of
equivalent F.M. 2.2], 20 mm down
well graded crushed stone chips
conforming to ASTM C-33, including
breaking chips and screening through
proper sieves, making and placing
shutter in position and maintaining
true to plumb, making shutter water-
tight properly, placing reinforcement
in position; mixing with standard mixer
machine with hoper and fed by
standard measuring boxes, casting in
forms, compacting by vibrator
machine and curing at least for 28
days, removing centering-shuttering
including cost of water, electricity,
testing and other charges etc. and
making all type of concrete mixture
with the help of automatic batching
plant at site all complete.Pedestals,
column, column capitals, lift walls and
walls in Basement & G Floor. a-i)
Concrete
39.2 Civil N/A Reinforced cement concrete works Sqm 4198.00
using steel shutter with minimum
cement content relates to mix ratio
1:1.25:2.5 having minimum f'cr = 40
Mpa, and satisfying a specified
compressive strength f?c = 32 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1-CEM 1
(32.5 to 52.5 N) / ASTM-C 150 Type
? I, with approved high range
admixture, best quality coarse sand
[Sylhet sand or coarse sand of
equivalent F.M. 2.2], 20 mm down
well graded crushed stone chips
conforming to ASTM C-33, including
breaking chips and screening through
proper sieves, making and placing
shutter in position and maintaining
true to plumb, making shutter water-
tight properly, placing reinforcement
in position; mixing with standard mixer
machine with hoper and fed by
standard measuring boxes, casting in
forms, compacting by vibrator
machine and curing at least for 28
days, removing centering-shuttering
including cost of water, electricity,
testing and other charges etc. and
making all type of concrete mixture
with the help of automatic batching
plant at site all complete.Pedestals,
column, column capitals, lift walls and
walls in Basement & G Floor. a-ii)
Formwork/shuttering, prop and
necessary supports etc. (steel)
39.3 Civil N/A Reinforced cement concrete works Cum 144.00
using steel shutter with minimum
cement content relates to mix ratio
1:1.25:2.5 having minimum f'cr = 40
Mpa, and satisfying a specified
compressive strength f?c = 32 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1-CEM 1
(32.5 to 52.5 N) / ASTM-C 150 Type
? I, with approved high range
admixture, best quality coarse sand
[Sylhet sand or coarse sand of
equivalent F.M. 2.2], 20 mm down
well graded crushed stone chips
conforming to ASTM C-33, including
breaking chips and screening through
proper sieves, making and placing
shutter in position and maintaining
true to plumb, making shutter water-
tight properly, placing reinforcement
in position; mixing with standard mixer
machine with hoper and fed by
standard measuring boxes, casting in
forms, compacting by vibrator
machine and curing at least for 28
days, removing centering-shuttering
including cost of water, electricity,
testing and other charges etc. and
making all type of concrete mixture
with the help of automatic batching
plant at site all complete.Pedestals,
column, column capitals, lift walls and
walls in Basement & G Floor.
Pedestals, column, column capitals,
lift walls and walls in 1st Floorb-i)
Concrete
39.4 Civil N/A Reinforced cement concrete works Sqm 1025.00
using steel shutter with minimum
cement content relates to mix ratio
1:1.25:2.5 having minimum f'cr = 40
Mpa, and satisfying a specified
compressive strength f?c = 32 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1-CEM 1
(32.5 to 52.5 N) / ASTM-C 150 Type
? I, with approved high range
admixture, best quality coarse sand
[Sylhet sand or coarse sand of
equivalent F.M. 2.2], 20 mm down
well graded crushed stone chips
conforming to ASTM C-33, including
breaking chips and screening through
proper sieves, making and placing
shutter in position and maintaining
true to plumb, making shutter water-
tight properly, placing reinforcement
in position; mixing with standard mixer
machine with hoper and fed by
standard measuring boxes, casting in
forms, compacting by vibrator
machine and curing at least for 28
days, removing centering-shuttering
including cost of water, electricity,
testing and other charges etc. and
making all type of concrete mixture
with the help of automatic batching
plant at site all complete.Pedestals,
column, column capitals, lift walls and
walls in Basement & G Floor.
Pedestals, column, column capitals,
lift walls and walls in 1st Floorb-ii)
Formwork/shuttering, prop and
necessary supports etc. (steel)
39.5 Civil N/A Reinforced cement concrete works Cum 114.61
using steel shutter with minimum
cement content relates to mix ratio
1:1.25:2.5 having minimum f'cr = 40
Mpa, and satisfying a specified
compressive strength f?c = 32 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1-CEM 1
(32.5 to 52.5 N) / ASTM-C 150 Type
? I, with approved high range
admixture, best quality coarse sand
[Sylhet sand or coarse sand of
equivalent F.M. 2.2], 20 mm down
well graded crushed stone chips
conforming to ASTM C-33, including
breaking chips and screening through
proper sieves, making and placing
shutter in position and maintaining
true to plumb, making shutter water-
tight properly, placing reinforcement
in position; mixing with standard mixer
machine with hoper and fed by
standard measuring boxes, casting in
forms, compacting by vibrator
machine and curing at least for 28
days, removing centering-shuttering
including cost of water, electricity,
testing and other charges etc. and
making all type of concrete mixture
with the help of automatic batching
plant at site all complete.Pedestals,
column, column capitals, lift walls and
walls in Basement & G Floor.
Pedestals, column, column capitals,
lift walls and walls in 2nd Floorc-i)
Concrete
39.6 Civil N/A Reinforced cement concrete works Sqm 717.00
using steel shutter with minimum
cement content relates to mix ratio
1:1.25:2.5 having minimum f'cr = 40
Mpa, and satisfying a specified
compressive strength f?c = 32 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1-CEM 1
(32.5 to 52.5 N) / ASTM-C 150 Type
? I, with approved high range
admixture, best quality coarse sand
[Sylhet sand or coarse sand of
equivalent F.M. 2.2], 20 mm down
well graded crushed stone chips
conforming to ASTM C-33, including
breaking chips and screening through
proper sieves, making and placing
shutter in position and maintaining
true to plumb, making shutter water-
tight properly, placing reinforcement
in position; mixing with standard mixer
machine with hoper and fed by
standard measuring boxes, casting in
forms, compacting by vibrator
machine and curing at least for 28
days, removing centering-shuttering
including cost of water, electricity,
testing and other charges etc. and
making all type of concrete mixture
with the help of automatic batching
plant at site all complete.Pedestals,
column, column capitals, lift walls and
walls in Basement & G Floor.
Pedestals, column, column capitals,
lift walls and walls in 2nd Floorc-ii)
Formwork/shuttering, prop and
necessary supports etc. (steel)
39.7 Civil N/A Reinforced cement concrete works Cum 98.00
using steel shutter with minimum
cement content relates to mix ratio
1:1.25:2.5 having minimum f'cr = 40
Mpa, and satisfying a specified
compressive strength f?c = 32 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1-CEM 1
(32.5 to 52.5 N) / ASTM-C 150 Type
? I, with approved high range
admixture, best quality coarse sand
[Sylhet sand or coarse sand of
equivalent F.M. 2.2], 20 mm down
well graded crushed stone chips
conforming to ASTM C-33, including
breaking chips and screening through
proper sieves, making and placing
shutter in position and maintaining
true to plumb, making shutter water-
tight properly, placing reinforcement
in position; mixing with standard mixer
machine with hoper and fed by
standard measuring boxes, casting in
forms, compacting by vibrator
machine and curing at least for 28
days, removing centering-shuttering
including cost of water, electricity,
testing and other charges etc. and
making all type of concrete mixture
with the help of automatic batching
plant at site all complete.Pedestals,
column, column capitals, lift walls and
walls in Basement & G Floor.
Pedestals, column, column capitals,
lift walls and walls in 3rd Floord-i)
Concrete
39.8 Civil N/A Reinforced cement concrete works Sqm 697.00
using steel shutter with minimum
cement content relates to mix ratio
1:1.25:2.5 having minimum f'cr = 40
Mpa, and satisfying a specified
compressive strength f?c = 32 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1-CEM 1
(32.5 to 52.5 N) / ASTM-C 150 Type
? I, with approved high range
admixture, best quality coarse sand
[Sylhet sand or coarse sand of
equivalent F.M. 2.2], 20 mm down
well graded crushed stone chips
conforming to ASTM C-33, including
breaking chips and screening through
proper sieves, making and placing
shutter in position and maintaining
true to plumb, making shutter water-
tight properly, placing reinforcement
in position; mixing with standard mixer
machine with hoper and fed by
standard measuring boxes, casting in
forms, compacting by vibrator
machine and curing at least for 28
days, removing centering-shuttering
including cost of water, electricity,
testing and other charges etc. and
making all type of concrete mixture
with the help of automatic batching
plant at site all complete.Pedestals,
column, column capitals, lift walls and
walls in Basement & G Floor.
Pedestals, column, column capitals,
lift walls and walls in 3rd Floord-ii)
Formwork/shuttering, prop and
necessary supports etc. (steel)
39.9 Civil N/A Reinforced cement concrete works Cum 98.00
using steel shutter with minimum
cement content relates to mix ratio
1:1.25:2.5 having minimum f'cr = 40
Mpa, and satisfying a specified
compressive strength f?c = 32 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1-CEM 1
(32.5 to 52.5 N) / ASTM-C 150 Type
? I, with approved high range
admixture, best quality coarse sand
[Sylhet sand or coarse sand of
equivalent F.M. 2.2], 20 mm down
well graded crushed stone chips
conforming to ASTM C-33, including
breaking chips and screening through
proper sieves, making and placing
shutter in position and maintaining
true to plumb, making shutter water-
tight properly, placing reinforcement
in position; mixing with standard mixer
machine with hoper and fed by
standard measuring boxes, casting in
forms, compacting by vibrator
machine and curing at least for 28
days, removing centering-shuttering
including cost of water, electricity,
testing and other charges etc. and
making all type of concrete mixture
with the help of automatic batching
plant at site all complete.Pedestals,
column, column capitals, lift walls and
walls in Basement & G Floor.
Pedestals, column, column capitals,
lift walls and walls in 4th Floore-i)
Concrete
39.10 Civil N/A Reinforced cement concrete works Sqm 697.00
using steel shutter with minimum
cement content relates to mix ratio
1:1.25:2.5 having minimum f'cr = 40
Mpa, and satisfying a specified
compressive strength f?c = 32 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1-CEM 1
(32.5 to 52.5 N) / ASTM-C 150 Type
? I, with approved high range
admixture, best quality coarse sand
[Sylhet sand or coarse sand of
equivalent F.M. 2.2], 20 mm down
well graded crushed stone chips
conforming to ASTM C-33, including
breaking chips and screening through
proper sieves, making and placing
shutter in position and maintaining
true to plumb, making shutter water-
tight properly, placing reinforcement
in position; mixing with standard mixer
machine with hoper and fed by
standard measuring boxes, casting in
forms, compacting by vibrator
machine and curing at least for 28
days, removing centering-shuttering
including cost of water, electricity,
testing and other charges etc. and
making all type of concrete mixture
with the help of automatic batching
plant at site all complete.Pedestals,
column, column capitals, lift walls and
walls in Basement & G Floor.
Pedestals, column, column capitals,
lift walls and walls in 4th Floore-ii)
Formwork/shuttering, prop and
necessary supports etc. (steel)
39.11 Civil N/A Reinforced cement concrete works Cum 98.00
using steel shutter with minimum
cement content relates to mix ratio
1:1.25:2.5 having minimum f'cr = 40
Mpa, and satisfying a specified
compressive strength f?c = 32 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1-CEM 1
(32.5 to 52.5 N) / ASTM-C 150 Type
? I, with approved high range
admixture, best quality coarse sand
[Sylhet sand or coarse sand of
equivalent F.M. 2.2], 20 mm down
well graded crushed stone chips
conforming to ASTM C-33, including
breaking chips and screening through
proper sieves, making and placing
shutter in position and maintaining
true to plumb, making shutter water-
tight properly, placing reinforcement
in position; mixing with standard mixer
machine with hoper and fed by
standard measuring boxes, casting in
forms, compacting by vibrator
machine and curing at least for 28
days, removing centering-shuttering
including cost of water, electricity,
testing and other charges etc. and
making all type of concrete mixture
with the help of automatic batching
plant at site all complete.Pedestals,
column, column capitals, lift walls and
walls in Basement & G Floor.
Pedestals, column, column capitals,
lift walls and walls in 5th Floor:f-i)
Concrete
39.12 Civil N/A Reinforced cement concrete works Sqm 697.00
using steel shutter with minimum
cement content relates to mix ratio
1:1.25:2.5 having minimum f'cr = 40
Mpa, and satisfying a specified
compressive strength f?c = 32 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1-CEM 1
(32.5 to 52.5 N) / ASTM-C 150 Type
? I, with approved high range
admixture, best quality coarse sand
[Sylhet sand or coarse sand of
equivalent F.M. 2.2], 20 mm down
well graded crushed stone chips
conforming to ASTM C-33, including
breaking chips and screening through
proper sieves, making and placing
shutter in position and maintaining
true to plumb, making shutter water-
tight properly, placing reinforcement
in position; mixing with standard mixer
machine with hoper and fed by
standard measuring boxes, casting in
forms, compacting by vibrator
machine and curing at least for 28
days, removing centering-shuttering
including cost of water, electricity,
testing and other charges etc. and
making all type of concrete mixture
with the help of automatic batching
plant at site all complete.Pedestals,
column, column capitals, lift walls and
walls in Basement & G Floor.
Pedestals, column, column capitals,
lift walls and walls in 5th Floor:f-ii)
Formwork/shuttering, prop and
necessary supports etc. (steel)
39.13 Civil N/A Reinforced cement concrete works Cum 98.00
using steel shutter with minimum
cement content relates to mix ratio
1:1.25:2.5 having minimum f'cr = 40
Mpa, and satisfying a specified
compressive strength f?c = 32 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1-CEM 1
(32.5 to 52.5 N) / ASTM-C 150 Type
? I, with approved high range
admixture, best quality coarse sand
[Sylhet sand or coarse sand of
equivalent F.M. 2.2], 20 mm down
well graded crushed stone chips
conforming to ASTM C-33, including
breaking chips and screening through
proper sieves, making and placing
shutter in position and maintaining
true to plumb, making shutter water-
tight properly, placing reinforcement
in position; mixing with standard mixer
machine with hoper and fed by
standard measuring boxes, casting in
forms, compacting by vibrator
machine and curing at least for 28
days, removing centering-shuttering
including cost of water, electricity,
testing and other charges etc. and
making all type of concrete mixture
with the help of automatic batching
plant at site all complete.Pedestals,
column, column capitals, lift walls and
walls in Basement & G Floor.
Pedestals, column, column capitals,
lift walls and walls in 6th Floor:g-i)
Concrete
39.14 Civil N/A Reinforced cement concrete works Sqm 697.00
using steel shutter with minimum
cement content relates to mix ratio
1:1.25:2.5 having minimum f'cr = 40
Mpa, and satisfying a specified
compressive strength f?c = 32 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1-CEM 1
(32.5 to 52.5 N) / ASTM-C 150 Type
? I, with approved high range
admixture, best quality coarse sand
[Sylhet sand or coarse sand of
equivalent F.M. 2.2], 20 mm down
well graded crushed stone chips
conforming to ASTM C-33, including
breaking chips and screening through
proper sieves, making and placing
shutter in position and maintaining
true to plumb, making shutter water-
tight properly, placing reinforcement
in position; mixing with standard mixer
machine with hoper and fed by
standard measuring boxes, casting in
forms, compacting by vibrator
machine and curing at least for 28
days, removing centering-shuttering
including cost of water, electricity,
testing and other charges etc. and
making all type of concrete mixture
with the help of automatic batching
plant at site all complete.Pedestals,
column, column capitals, lift walls and
walls in Basement & G Floor.
Pedestals, column, column capitals,
lift walls and walls in 6th Floor:g-ii)
Formwork/shuttering, prop and
necessary supports etc. (steel)
39.15 Civil N/A Reinforced cement concrete works Cum 98.00
using steel shutter with minimum
cement content relates to mix ratio
1:1.25:2.5 having minimum f'cr = 40
Mpa, and satisfying a specified
compressive strength f?c = 32 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1-CEM 1
(32.5 to 52.5 N) / ASTM-C 150 Type
? I, with approved high range
admixture, best quality coarse sand
[Sylhet sand or coarse sand of
equivalent F.M. 2.2], 20 mm down
well graded crushed stone chips
conforming to ASTM C-33, including
breaking chips and screening through
proper sieves, making and placing
shutter in position and maintaining
true to plumb, making shutter water-
tight properly, placing reinforcement
in position; mixing with standard mixer
machine with hoper and fed by
standard measuring boxes, casting in
forms, compacting by vibrator
machine and curing at least for 28
days, removing centering-shuttering
including cost of water, electricity,
testing and other charges etc. and
making all type of concrete mixture
with the help of automatic batching
plant at site all complete.Pedestals,
column, column capitals, lift walls and
walls in Basement & G Floor.
Pedestals, column, column capitals,
lift walls and walls in 7th Floor:h-i)
Concrete
39.16 Civil N/A Reinforced cement concrete works Sqm 697.00
using steel shutter with minimum
cement content relates to mix ratio
1:1.25:2.5 having minimum f'cr = 40
Mpa, and satisfying a specified
compressive strength f?c = 32 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1-CEM 1
(32.5 to 52.5 N) / ASTM-C 150 Type
? I, with approved high range
admixture, best quality coarse sand
[Sylhet sand or coarse sand of
equivalent F.M. 2.2], 20 mm down
well graded crushed stone chips
conforming to ASTM C-33, including
breaking chips and screening through
proper sieves, making and placing
shutter in position and maintaining
true to plumb, making shutter water-
tight properly, placing reinforcement
in position; mixing with standard mixer
machine with hoper and fed by
standard measuring boxes, casting in
forms, compacting by vibrator
machine and curing at least for 28
days, removing centering-shuttering
including cost of water, electricity,
testing and other charges etc. and
making all type of concrete mixture
with the help of automatic batching
plant at site all complete.Pedestals,
column, column capitals, lift walls and
walls in Basement & G Floor.
Pedestals, column, column capitals,
lift walls and walls in 7th Floor:h-ii)
Formwork/shuttering, prop and
necessary supports etc. (steel)
39.17 Civil N/A Reinforced cement concrete works Cum 98.00
using steel shutter with minimum
cement content relates to mix ratio
1:1.25:2.5 having minimum f'cr = 40
Mpa, and satisfying a specified
compressive strength f?c = 32 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1-CEM 1
(32.5 to 52.5 N) / ASTM-C 150 Type
? I, with approved high range
admixture, best quality coarse sand
[Sylhet sand or coarse sand of
equivalent F.M. 2.2], 20 mm down
well graded crushed stone chips
conforming to ASTM C-33, including
breaking chips and screening through
proper sieves, making and placing
shutter in position and maintaining
true to plumb, making shutter water-
tight properly, placing reinforcement
in position; mixing with standard mixer
machine with hoper and fed by
standard measuring boxes, casting in
forms, compacting by vibrator
machine and curing at least for 28
days, removing centering-shuttering
including cost of water, electricity,
testing and other charges etc. and
making all type of concrete mixture
with the help of automatic batching
plant at site all complete.Pedestals,
column, column capitals, lift walls and
walls in Basement & G Floor.
Pedestals, column, column capitals,
lift walls and walls in 8th Floor:i-i)
Concrete
39.18 Civil N/A Reinforced cement concrete works Sqm 697.00
using steel shutter with minimum
cement content relates to mix ratio
1:1.25:2.5 having minimum f'cr = 40
Mpa, and satisfying a specified
compressive strength f?c = 32 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1-CEM 1
(32.5 to 52.5 N) / ASTM-C 150 Type
? I, with approved high range
admixture, best quality coarse sand
[Sylhet sand or coarse sand of
equivalent F.M. 2.2], 20 mm down
well graded crushed stone chips
conforming to ASTM C-33, including
breaking chips and screening through
proper sieves, making and placing
shutter in position and maintaining
true to plumb, making shutter water-
tight properly, placing reinforcement
in position; mixing with standard mixer
machine with hoper and fed by
standard measuring boxes, casting in
forms, compacting by vibrator
machine and curing at least for 28
days, removing centering-shuttering
including cost of water, electricity,
testing and other charges etc. and
making all type of concrete mixture
with the help of automatic batching
plant at site all complete.Pedestals,
column, column capitals, lift walls and
walls in Basement & G Floor.
Pedestals, column, column capitals,
lift walls and walls in 8th Floor:i-ii)
Formwork/shuttering, prop and
necessary supports etc. (steel)
39.19 Civil N/A Reinforced cement concrete works Cum 98.00
using steel shutter with minimum
cement content relates to mix ratio
1:1.25:2.5 having minimum f'cr = 40
Mpa, and satisfying a specified
compressive strength f?c = 32 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1-CEM 1
(32.5 to 52.5 N) / ASTM-C 150 Type
? I, with approved high range
admixture, best quality coarse sand
[Sylhet sand or coarse sand of
equivalent F.M. 2.2], 20 mm down
well graded crushed stone chips
conforming to ASTM C-33, including
breaking chips and screening through
proper sieves, making and placing
shutter in position and maintaining
true to plumb, making shutter water-
tight properly, placing reinforcement
in position; mixing with standard mixer
machine with hoper and fed by
standard measuring boxes, casting in
forms, compacting by vibrator
machine and curing at least for 28
days, removing centering-shuttering
including cost of water, electricity,
testing and other charges etc. and
making all type of concrete mixture
with the help of automatic batching
plant at site all complete.Pedestals,
column, column capitals, lift walls and
walls in Basement & G Floor.
Pedestals, column, column capitals,
lift walls and walls in 9th Floor:j-i)
Concrete
39.20 Civil N/A Reinforced cement concrete works Sqm 697.00
using steel shutter with minimum
cement content relates to mix ratio
1:1.25:2.5 having minimum f'cr = 40
Mpa, and satisfying a specified
compressive strength f?c = 32 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1-CEM 1
(32.5 to 52.5 N) / ASTM-C 150 Type
? I, with approved high range
admixture, best quality coarse sand
[Sylhet sand or coarse sand of
equivalent F.M. 2.2], 20 mm down
well graded crushed stone chips
conforming to ASTM C-33, including
breaking chips and screening through
proper sieves, making and placing
shutter in position and maintaining
true to plumb, making shutter water-
tight properly, placing reinforcement
in position; mixing with standard mixer
machine with hoper and fed by
standard measuring boxes, casting in
forms, compacting by vibrator
machine and curing at least for 28
days, removing centering-shuttering
including cost of water, electricity,
testing and other charges etc. and
making all type of concrete mixture
with the help of automatic batching
plant at site all complete.Pedestals,
column, column capitals, lift walls and
walls in Basement & G Floor.
Pedestals, column, column capitals,
lift walls and walls in 9th Floor:j-ii)
Formwork/shuttering, prop and
necessary supports etc. (steel)
39.21 Civil N/A Reinforced cement concrete works Cum 98.00
using steel shutter with minimum
cement content relates to mix ratio
1:1.25:2.5 having minimum f'cr = 40
Mpa, and satisfying a specified
compressive strength f?c = 32 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1-CEM 1
(32.5 to 52.5 N) / ASTM-C 150 Type
? I, with approved high range
admixture, best quality coarse sand
[Sylhet sand or coarse sand of
equivalent F.M. 2.2], 20 mm down
well graded crushed stone chips
conforming to ASTM C-33, including
breaking chips and screening through
proper sieves, making and placing
shutter in position and maintaining
true to plumb, making shutter water-
tight properly, placing reinforcement
in position; mixing with standard mixer
machine with hoper and fed by
standard measuring boxes, casting in
forms, compacting by vibrator
machine and curing at least for 28
days, removing centering-shuttering
including cost of water, electricity,
testing and other charges etc. and
making all type of concrete mixture
with the help of automatic batching
plant at site all complete.Pedestals,
column, column capitals, lift walls and
walls in Basement & G Floor.
Pedestals, column, column capitals,
lift walls and walls in 10th Floor:k-i)
Concrete
39.22 Civil N/A Reinforced cement concrete works Sqm 697.00
using steel shutter with minimum
cement content relates to mix ratio
1:1.25:2.5 having minimum f'cr = 40
Mpa, and satisfying a specified
compressive strength f?c = 32 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1-CEM 1
(32.5 to 52.5 N) / ASTM-C 150 Type
? I, with approved high range
admixture, best quality coarse sand
[Sylhet sand or coarse sand of
equivalent F.M. 2.2], 20 mm down
well graded crushed stone chips
conforming to ASTM C-33, including
breaking chips and screening through
proper sieves, making and placing
shutter in position and maintaining
true to plumb, making shutter water-
tight properly, placing reinforcement
in position; mixing with standard mixer
machine with hoper and fed by
standard measuring boxes, casting in
forms, compacting by vibrator
machine and curing at least for 28
days, removing centering-shuttering
including cost of water, electricity,
testing and other charges etc. and
making all type of concrete mixture
with the help of automatic batching
plant at site all complete.Pedestals,
column, column capitals, lift walls and
walls in Basement & G Floor.
Pedestals, column, column capitals,
lift walls and walls in 10th Floor:k-ii)
Formwork/shuttering, prop and
necessary supports etc. (steel)
39.23 Civil N/A Reinforced cement concrete works Cum 98.00
using steel shutter with minimum
cement content relates to mix ratio
1:1.25:2.5 having minimum f'cr = 40
Mpa, and satisfying a specified
compressive strength f?c = 32 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1-CEM 1
(32.5 to 52.5 N) / ASTM-C 150 Type
? I, with approved high range
admixture, best quality coarse sand
[Sylhet sand or coarse sand of
equivalent F.M. 2.2], 20 mm down
well graded crushed stone chips
conforming to ASTM C-33, including
breaking chips and screening through
proper sieves, making and placing
shutter in position and maintaining
true to plumb, making shutter water-
tight properly, placing reinforcement
in position; mixing with standard mixer
machine with hoper and fed by
standard measuring boxes, casting in
forms, compacting by vibrator
machine and curing at least for 28
days, removing centering-shuttering
including cost of water, electricity,
testing and other charges etc. and
making all type of concrete mixture
with the help of automatic batching
plant at site all complete.Pedestals,
column, column capitals, lift walls and
walls in Basement & G Floor.
Pedestals, column, column capitals,
lift walls and walls in 11th Floor:l-i)
Concrete
39.24 Civil N/A Reinforced cement concrete works Sqm 697.00
using steel shutter with minimum
cement content relates to mix ratio
1:1.25:2.5 having minimum f'cr = 40
Mpa, and satisfying a specified
compressive strength f?c = 32 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1-CEM 1
(32.5 to 52.5 N) / ASTM-C 150 Type
? I, with approved high range
admixture, best quality coarse sand
[Sylhet sand or coarse sand of
equivalent F.M. 2.2], 20 mm down
well graded crushed stone chips
conforming to ASTM C-33, including
breaking chips and screening through
proper sieves, making and placing
shutter in position and maintaining
true to plumb, making shutter water-
tight properly, placing reinforcement
in position; mixing with standard mixer
machine with hoper and fed by
standard measuring boxes, casting in
forms, compacting by vibrator
machine and curing at least for 28
days, removing centering-shuttering
including cost of water, electricity,
testing and other charges etc. and
making all type of concrete mixture
with the help of automatic batching
plant at site all complete.Pedestals,
column, column capitals, lift walls and
walls in Basement & G Floor.
Pedestals, column, column capitals,
lift walls and walls in 11th Floor:l-ii)
Formwork/shuttering, prop and
necessary supports etc. (steel)
39.25 Civil N/A Reinforced cement concrete works Cum 98.00
using steel shutter with minimum
cement content relates to mix ratio
1:1.25:2.5 having minimum f'cr = 40
Mpa, and satisfying a specified
compressive strength f?c = 32 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1-CEM 1
(32.5 to 52.5 N) / ASTM-C 150 Type
? I, with approved high range
admixture, best quality coarse sand
[Sylhet sand or coarse sand of
equivalent F.M. 2.2], 20 mm down
well graded crushed stone chips
conforming to ASTM C-33, including
breaking chips and screening through
proper sieves, making and placing
shutter in position and maintaining
true to plumb, making shutter water-
tight properly, placing reinforcement
in position; mixing with standard mixer
machine with hoper and fed by
standard measuring boxes, casting in
forms, compacting by vibrator
machine and curing at least for 28
days, removing centering-shuttering
including cost of water, electricity,
testing and other charges etc. and
making all type of concrete mixture
with the help of automatic batching
plant at site all complete.Pedestals,
column, column capitals, lift walls and
walls in Basement & G Floor.
Pedestals, column, column capitals,
lift walls and walls in 12th Floor:m-i)
Concrete
39.26 Civil N/A Reinforced cement concrete works Sqm 697.00
using steel shutter with minimum
cement content relates to mix ratio
1:1.25:2.5 having minimum f'cr = 40
Mpa, and satisfying a specified
compressive strength f?c = 32 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1-CEM 1
(32.5 to 52.5 N) / ASTM-C 150 Type
? I, with approved high range
admixture, best quality coarse sand
[Sylhet sand or coarse sand of
equivalent F.M. 2.2], 20 mm down
well graded crushed stone chips
conforming to ASTM C-33, including
breaking chips and screening through
proper sieves, making and placing
shutter in position and maintaining
true to plumb, making shutter water-
tight properly, placing reinforcement
in position; mixing with standard mixer
machine with hoper and fed by
standard measuring boxes, casting in
forms, compacting by vibrator
machine and curing at least for 28
days, removing centering-shuttering
including cost of water, electricity,
testing and other charges etc. and
making all type of concrete mixture
with the help of automatic batching
plant at site all complete.Pedestals,
column, column capitals, lift walls and
walls in Basement & G Floor.
Pedestals, column, column capitals,
lift walls and walls in 12th Floor:m-ii)
Formwork/shuttering, prop and
necessary supports etc. (steel)
39.27 Civil N/A Reinforced cement concrete works Cum 98.00
using steel shutter with minimum
cement content relates to mix ratio
1:1.25:2.5 having minimum f'cr = 40
Mpa, and satisfying a specified
compressive strength f?c = 32 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1-CEM 1
(32.5 to 52.5 N) / ASTM-C 150 Type
? I, with approved high range
admixture, best quality coarse sand
[Sylhet sand or coarse sand of
equivalent F.M. 2.2], 20 mm down
well graded crushed stone chips
conforming to ASTM C-33, including
breaking chips and screening through
proper sieves, making and placing
shutter in position and maintaining
true to plumb, making shutter water-
tight properly, placing reinforcement
in position; mixing with standard mixer
machine with hoper and fed by
standard measuring boxes, casting in
forms, compacting by vibrator
machine and curing at least for 28
days, removing centering-shuttering
including cost of water, electricity,
testing and other charges etc. and
making all type of concrete mixture
with the help of automatic batching
plant at site all complete.Pedestals,
column, column capitals, lift walls and
walls in Basement & G Floor.
Pedestals, column, column capitals,
lift walls and walls in 13th Floor:n-i)
Concrete
39.28 Civil N/A Reinforced cement concrete works Sqm 697.00
using steel shutter with minimum
cement content relates to mix ratio
1:1.25:2.5 having minimum f'cr = 40
Mpa, and satisfying a specified
compressive strength f?c = 32 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1-CEM 1
(32.5 to 52.5 N) / ASTM-C 150 Type
? I, with approved high range
admixture, best quality coarse sand
[Sylhet sand or coarse sand of
equivalent F.M. 2.2], 20 mm down
well graded crushed stone chips
conforming to ASTM C-33, including
breaking chips and screening through
proper sieves, making and placing
shutter in position and maintaining
true to plumb, making shutter water-
tight properly, placing reinforcement
in position; mixing with standard mixer
machine with hoper and fed by
standard measuring boxes, casting in
forms, compacting by vibrator
machine and curing at least for 28
days, removing centering-shuttering
including cost of water, electricity,
testing and other charges etc. and
making all type of concrete mixture
with the help of automatic batching
plant at site all complete.Pedestals,
column, column capitals, lift walls and
walls in Basement & G Floor.
Pedestals, column, column capitals,
lift walls and walls in 13th Floor:n-ii)
Formwork/shuttering, prop and
necessary supports etc. (steel)
39.29 Civil N/A Reinforced cement concrete works Cum 98.00
using steel shutter with minimum
cement content relates to mix ratio
1:1.25:2.5 having minimum f'cr = 40
Mpa, and satisfying a specified
compressive strength f?c = 32 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1-CEM 1
(32.5 to 52.5 N) / ASTM-C 150 Type
? I, with approved high range
admixture, best quality coarse sand
[Sylhet sand or coarse sand of
equivalent F.M. 2.2], 20 mm down
well graded crushed stone chips
conforming to ASTM C-33, including
breaking chips and screening through
proper sieves, making and placing
shutter in position and maintaining
true to plumb, making shutter water-
tight properly, placing reinforcement
in position; mixing with standard mixer
machine with hoper and fed by
standard measuring boxes, casting in
forms, compacting by vibrator
machine and curing at least for 28
days, removing centering-shuttering
including cost of water, electricity,
testing and other charges etc. and
making all type of concrete mixture
with the help of automatic batching
plant at site all complete.Pedestals,
column, column capitals, lift walls and
walls in Basement & G Floor.
Pedestals, column, column capitals,
lift walls and walls in 14th Floor:o-i)
Concrete
39.30 Civil N/A Reinforced cement concrete works Sqm 697.00
using steel shutter with minimum
cement content relates to mix ratio
1:1.25:2.5 having minimum f'cr = 40
Mpa, and satisfying a specified
compressive strength f?c = 32 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1-CEM 1
(32.5 to 52.5 N) / ASTM-C 150 Type
? I, with approved high range
admixture, best quality coarse sand
[Sylhet sand or coarse sand of
equivalent F.M. 2.2], 20 mm down
well graded crushed stone chips
conforming to ASTM C-33, including
breaking chips and screening through
proper sieves, making and placing
shutter in position and maintaining
true to plumb, making shutter water-
tight properly, placing reinforcement
in position; mixing with standard mixer
machine with hoper and fed by
standard measuring boxes, casting in
forms, compacting by vibrator
machine and curing at least for 28
days, removing centering-shuttering
including cost of water, electricity,
testing and other charges etc. and
making all type of concrete mixture
with the help of automatic batching
plant at site all complete.Pedestals,
column, column capitals, lift walls and
walls in Basement & G Floor.
Pedestals, column, column capitals,
lift walls and walls in 14th Floor:o-ii)
Formwork/shuttering, prop and
necessary supports etc. (steel)
39.31 Civil N/A Reinforced cement concrete works Cum 98.00
using steel shutter with minimum
cement content relates to mix ratio
1:1.25:2.5 having minimum f'cr = 40
Mpa, and satisfying a specified
compressive strength f?c = 32 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1-CEM 1
(32.5 to 52.5 N) / ASTM-C 150 Type
? I, with approved high range
admixture, best quality coarse sand
[Sylhet sand or coarse sand of
equivalent F.M. 2.2], 20 mm down
well graded crushed stone chips
conforming to ASTM C-33, including
breaking chips and screening through
proper sieves, making and placing
shutter in position and maintaining
true to plumb, making shutter water-
tight properly, placing reinforcement
in position; mixing with standard mixer
machine with hoper and fed by
standard measuring boxes, casting in
forms, compacting by vibrator
machine and curing at least for 28
days, removing centering-shuttering
including cost of water, electricity,
testing and other charges etc. and
making all type of concrete mixture
with the help of automatic batching
plant at site all complete.Pedestals,
column, column capitals, lift walls and
walls in Basement & G Floor.
Pedestals, column, column capitals,
lift walls and walls in 15th Floor:p-i)
Concrete
39.32 Civil N/A Reinforced cement concrete works Sqm 697.00
using steel shutter with minimum
cement content relates to mix ratio
1:1.25:2.5 having minimum f'cr = 40
Mpa, and satisfying a specified
compressive strength f?c = 32 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1-CEM 1
(32.5 to 52.5 N) / ASTM-C 150 Type
? I, with approved high range
admixture, best quality coarse sand
[Sylhet sand or coarse sand of
equivalent F.M. 2.2], 20 mm down
well graded crushed stone chips
conforming to ASTM C-33, including
breaking chips and screening through
proper sieves, making and placing
shutter in position and maintaining
true to plumb, making shutter water-
tight properly, placing reinforcement
in position; mixing with standard mixer
machine with hoper and fed by
standard measuring boxes, casting in
forms, compacting by vibrator
machine and curing at least for 28
days, removing centering-shuttering
including cost of water, electricity,
testing and other charges etc. and
making all type of concrete mixture
with the help of automatic batching
plant at site all complete.Pedestals,
column, column capitals, lift walls and
walls in Basement & G Floor.
Pedestals, column, column capitals,
lift walls and walls in 15th Floor:p-ii)
Formwork/shuttering, prop and
necessary supports etc. (steel)
39.33 Civil N/A Reinforced cement concrete works Cum 98.00
using steel shutter with minimum
cement content relates to mix ratio
1:1.25:2.5 having minimum f'cr = 40
Mpa, and satisfying a specified
compressive strength f?c = 32 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1-CEM 1
(32.5 to 52.5 N) / ASTM-C 150 Type
? I, with approved high range
admixture, best quality coarse sand
[Sylhet sand or coarse sand of
equivalent F.M. 2.2], 20 mm down
well graded crushed stone chips
conforming to ASTM C-33, including
breaking chips and screening through
proper sieves, making and placing
shutter in position and maintaining
true to plumb, making shutter water-
tight properly, placing reinforcement
in position; mixing with standard mixer
machine with hoper and fed by
standard measuring boxes, casting in
forms, compacting by vibrator
machine and curing at least for 28
days, removing centering-shuttering
including cost of water, electricity,
testing and other charges etc. and
making all type of concrete mixture
with the help of automatic batching
plant at site all complete.Pedestals,
column, column capitals, lift walls and
walls in Basement & G Floor.
Pedestals, column, column capitals,
lift walls and walls in 16th Floor:q-i)
Concrete
39.34 Civil N/A Reinforced cement concrete works Sqm 697.00
using steel shutter with minimum
cement content relates to mix ratio
1:1.25:2.5 having minimum f'cr = 40
Mpa, and satisfying a specified
compressive strength f?c = 32 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1-CEM 1
(32.5 to 52.5 N) / ASTM-C 150 Type
? I, with approved high range
admixture, best quality coarse sand
[Sylhet sand or coarse sand of
equivalent F.M. 2.2], 20 mm down
well graded crushed stone chips
conforming to ASTM C-33, including
breaking chips and screening through
proper sieves, making and placing
shutter in position and maintaining
true to plumb, making shutter water-
tight properly, placing reinforcement
in position; mixing with standard mixer
machine with hoper and fed by
standard measuring boxes, casting in
forms, compacting by vibrator
machine and curing at least for 28
days, removing centering-shuttering
including cost of water, electricity,
testing and other charges etc. and
making all type of concrete mixture
with the help of automatic batching
plant at site all complete.Pedestals,
column, column capitals, lift walls and
walls in Basement & G Floor.
Pedestals, column, column capitals,
lift walls and walls in 16th Floor:q-ii)
Formwork/shuttering, prop and
necessary supports etc. (steel)
39.35 Civil N/A Reinforced cement concrete works Cum 122.24
using steel shutter with minimum
cement content relates to mix ratio
1:1.25:2.5 having minimum f'cr = 40
Mpa, and satisfying a specified
compressive strength f?c = 32 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1-CEM 1
(32.5 to 52.5 N) / ASTM-C 150 Type
? I, with approved high range
admixture, best quality coarse sand
[Sylhet sand or coarse sand of
equivalent F.M. 2.2], 20 mm down
well graded crushed stone chips
conforming to ASTM C-33, including
breaking chips and screening through
proper sieves, making and placing
shutter in position and maintaining
true to plumb, making shutter water-
tight properly, placing reinforcement
in position; mixing with standard mixer
machine with hoper and fed by
standard measuring boxes, casting in
forms, compacting by vibrator
machine and curing at least for 28
days, removing centering-shuttering
including cost of water, electricity,
testing and other charges etc. and
making all type of concrete mixture
with the help of automatic batching
plant at site all complete.Pedestals,
column, column capitals, lift walls and
walls in Basement & G Floor.
Pedestals, column, column capitals,
lift walls, tank wall, parapet walls in
17th Floor:r-i) Concrete
39.36 Civil N/A Reinforced cement concrete works Sqm 1118.80
using steel shutter with minimum
cement content relates to mix ratio
1:1.25:2.5 having minimum f'cr = 40
Mpa, and satisfying a specified
compressive strength f?c = 32 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1-CEM 1
(32.5 to 52.5 N) / ASTM-C 150 Type
? I, with approved high range
admixture, best quality coarse sand
[Sylhet sand or coarse sand of
equivalent F.M. 2.2], 20 mm down
well graded crushed stone chips
conforming to ASTM C-33, including
breaking chips and screening through
proper sieves, making and placing
shutter in position and maintaining
true to plumb, making shutter water-
tight properly, placing reinforcement
in position; mixing with standard mixer
machine with hoper and fed by
standard measuring boxes, casting in
forms, compacting by vibrator
machine and curing at least for 28
days, removing centering-shuttering
including cost of water, electricity,
testing and other charges etc. and
making all type of concrete mixture
with the help of automatic batching
plant at site all complete.Pedestals,
column, column capitals, lift walls and
walls in Basement & G Floor.
Pedestals, column, column capitals,
lift walls, tank wall, parapet walls in
17th Floor:r-ii) Formwork/shuttering,
prop and necessary supports etc.
(steel)
39.37 Civil N/A Reinforced cement concrete works Cum 58.95
using steel shutter with minimum
cement content relates to mix ratio
1:1.25:2.5 having minimum f'cr = 40
Mpa, and satisfying a specified
compressive strength f?c = 32 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1-CEM 1
(32.5 to 52.5 N) / ASTM-C 150 Type
? I, with approved high range
admixture, best quality coarse sand
[Sylhet sand or coarse sand of
equivalent F.M. 2.2], 20 mm down
well graded crushed stone chips
conforming to ASTM C-33, including
breaking chips and screening through
proper sieves, making and placing
shutter in position and maintaining
true to plumb, making shutter water-
tight properly, placing reinforcement
in position; mixing with standard mixer
machine with hoper and fed by
standard measuring boxes, casting in
forms, compacting by vibrator
machine and curing at least for 28
days, removing centering-shuttering
including cost of water, electricity,
testing and other charges etc. and
making all type of concrete mixture
with the help of automatic batching
plant at site all complete.Pedestals,
column, column capitals, lift walls and
walls in Basement & G Floor.
Pedestals, column, column capitals,
lift walls, tank wall, parapet walls in
18th Floor:s-i) Concrete
39.38 Civil N/A Reinforced cement concrete works Sqm 500.00
using steel shutter with minimum
cement content relates to mix ratio
1:1.25:2.5 having minimum f'cr = 40
Mpa, and satisfying a specified
compressive strength f?c = 32 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1-CEM 1
(32.5 to 52.5 N) / ASTM-C 150 Type
? I, with approved high range
admixture, best quality coarse sand
[Sylhet sand or coarse sand of
equivalent F.M. 2.2], 20 mm down
well graded crushed stone chips
conforming to ASTM C-33, including
breaking chips and screening through
proper sieves, making and placing
shutter in position and maintaining
true to plumb, making shutter water-
tight properly, placing reinforcement
in position; mixing with standard mixer
machine with hoper and fed by
standard measuring boxes, casting in
forms, compacting by vibrator
machine and curing at least for 28
days, removing centering-shuttering
including cost of water, electricity,
testing and other charges etc. and
making all type of concrete mixture
with the help of automatic batching
plant at site all complete.Pedestals,
column, column capitals, lift walls and
walls in Basement & G Floor.
Pedestals, column, column capitals,
lift walls, tank wall, parapet walls in
18th Floor:s-ii) Formwork/shuttering,
prop and necessary supports etc.
(steel)
40.1 Civil N/A "Reinforced cement concrete works Cum 2.00
using steel shutter with minimum
cement content relates to mix ratio
1:1.25:2.5 having minimum f'cr = 40
Mpa, and satisfying a specified
compressive strength f?c = 32 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1-CEM 1
(32.5 to 52.5 N) / ASTM-C 150 Type
? I, with approved high range
admixture, best quality coarse sand
[Sylhet sand or coarse sand of
equivalent F.M. 2.2], 20 mm down
well graded crushed stone chips
conforming to ASTM C-33, including
breaking chips and screening through
proper sieves, making and placing
shutter in position and maintaining
true to plumb, making shutter water-
tight properly, placing reinforcement
in position; mixing with standard mixer
machine with hoper and fed by
standard measuring boxes, casting in
forms, compacting by vibrator
machine and curing at least for 28
days, removing centering-shuttering
including cost of water, electricity,
testing and other charges etc. and
making all type of concrete mixture
with the help of automatic batching
plant at site. all comp
Rate for the RCC (materials,
consumables and laying/placing
concrete) works in columns, capitals,
liftwalls & walls where the free height
of the structure exceeds 4 meter
[rate is considered for the height of
each additional 4 (four) meter or
part]a) From 4.0m to 8.0m Height "
40.2 Civil N/A "Reinforced cement concrete works Cum 2.00
using steel shutter with minimum
cement content relates to mix ratio
1:1.25:2.5 having minimum f'cr = 40
Mpa, and satisfying a specified
compressive strength f?c = 32 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1-CEM 1
(32.5 to 52.5 N) / ASTM-C 150 Type
? I, with approved high range
admixture, best quality coarse sand
[Sylhet sand or coarse sand of
equivalent F.M. 2.2], 20 mm down
well graded crushed stone chips
conforming to ASTM C-33, including
breaking chips and screening through
proper sieves, making and placing
shutter in position and maintaining
true to plumb, making shutter water-
tight properly, placing reinforcement
in position; mixing with standard mixer
machine with hoper and fed by
standard measuring boxes, casting in
forms, compacting by vibrator
machine and curing at least for 28
days, removing centering-shuttering
including cost of water, electricity,
testing and other charges etc. and
making all type of concrete mixture
with the help of automatic batching
plant at site. all comp
Rate for the RCC (materials,
consumables and laying/placing
concrete) works in columns, capitals,
liftwalls & walls where the free height
of the structure exceeds 4 meter
[rate is considered for the height of
each additional 4 (four) meter or
part]b) From 8.0m to 12.0m Height "
40.3 Civil N/A "Reinforced cement concrete works Cum 2.00
using steel shutter with minimum
cement content relates to mix ratio
1:1.25:2.5 having minimum f'cr = 40
Mpa, and satisfying a specified
compressive strength f?c = 32 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1-CEM 1
(32.5 to 52.5 N) / ASTM-C 150 Type
? I, with approved high range
admixture, best quality coarse sand
[Sylhet sand or coarse sand of
equivalent F.M. 2.2], 20 mm down
well graded crushed stone chips
conforming to ASTM C-33, including
breaking chips and screening through
proper sieves, making and placing
shutter in position and maintaining
true to plumb, making shutter water-
tight properly, placing reinforcement
in position; mixing with standard mixer
machine with hoper and fed by
standard measuring boxes, casting in
forms, compacting by vibrator
machine and curing at least for 28
days, removing centering-shuttering
including cost of water, electricity,
testing and other charges etc. and
making all type of concrete mixture
with the help of automatic batching
plant at site. all comp
Rate for the RCC (materials,
consumables and laying/placing
concrete) works in columns, capitals,
liftwalls & walls where the free height
of the structure exceeds 4 meter
[rate is considered for the height of
each additional 4 (four) meter or
part]c) From 12.0m to 16.0m Hight "
40.4 Civil N/A "Reinforced cement concrete works Cum 2.00
using steel shutter with minimum
cement content relates to mix ratio
1:1.25:2.5 having minimum f'cr = 40
Mpa, and satisfying a specified
compressive strength f?c = 32 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1-CEM 1
(32.5 to 52.5 N) / ASTM-C 150 Type
? I, with approved high range
admixture, best quality coarse sand
[Sylhet sand or coarse sand of
equivalent F.M. 2.2], 20 mm down
well graded crushed stone chips
conforming to ASTM C-33, including
breaking chips and screening through
proper sieves, making and placing
shutter in position and maintaining
true to plumb, making shutter water-
tight properly, placing reinforcement
in position; mixing with standard mixer
machine with hoper and fed by
standard measuring boxes, casting in
forms, compacting by vibrator
machine and curing at least for 28
days, removing centering-shuttering
including cost of water, electricity,
testing and other charges etc. and
making all type of concrete mixture
with the help of automatic batching
plant at site. all comp
Rate for the RCC (materials,
consumables and laying/placing
concrete) works in columns, capitals,
liftwalls & walls where the free height
of the structure exceeds 4 meter
[rate is considered for the height of
each additional 4 (four) meter or
part]d) From 16.0m to 20.0m Hight "
40.5 Civil N/A "Reinforced cement concrete works Cum 2.00
using steel shutter with minimum
cement content relates to mix ratio
1:1.25:2.5 having minimum f'cr = 40
Mpa, and satisfying a specified
compressive strength f?c = 32 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1-CEM 1
(32.5 to 52.5 N) / ASTM-C 150 Type
? I, with approved high range
admixture, best quality coarse sand
[Sylhet sand or coarse sand of
equivalent F.M. 2.2], 20 mm down
well graded crushed stone chips
conforming to ASTM C-33, including
breaking chips and screening through
proper sieves, making and placing
shutter in position and maintaining
true to plumb, making shutter water-
tight properly, placing reinforcement
in position; mixing with standard mixer
machine with hoper and fed by
standard measuring boxes, casting in
forms, compacting by vibrator
machine and curing at least for 28
days, removing centering-shuttering
including cost of water, electricity,
testing and other charges etc. and
making all type of concrete mixture
with the help of automatic batching
plant at site. all comp
Rate for the RCC (materials,
consumables and laying/placing
concrete) works in columns, capitals,
liftwalls & walls where the free height
of the structure exceeds 4 meter
[rate is considered for the height of
each additional 4 (four) meter or
part]e) From 20.0m to 24.0m Hight "
40.6 Civil N/A "Reinforced cement concrete works Cum 2.00
using steel shutter with minimum
cement content relates to mix ratio
1:1.25:2.5 having minimum f'cr = 40
Mpa, and satisfying a specified
compressive strength f?c = 32 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1-CEM 1
(32.5 to 52.5 N) / ASTM-C 150 Type
? I, with approved high range
admixture, best quality coarse sand
[Sylhet sand or coarse sand of
equivalent F.M. 2.2], 20 mm down
well graded crushed stone chips
conforming to ASTM C-33, including
breaking chips and screening through
proper sieves, making and placing
shutter in position and maintaining
true to plumb, making shutter water-
tight properly, placing reinforcement
in position; mixing with standard mixer
machine with hoper and fed by
standard measuring boxes, casting in
forms, compacting by vibrator
machine and curing at least for 28
days, removing centering-shuttering
including cost of water, electricity,
testing and other charges etc. and
making all type of concrete mixture
with the help of automatic batching
plant at site. all comp
Rate for the RCC (materials,
consumables and laying/placing
concrete) works in columns, capitals,
liftwalls & walls where the free height
of the structure exceeds 4 meter
[rate is considered for the height of
each additional 4 (four) meter or
part]f) From 24.0m to 28.0m Hight "
40.7 Civil N/A "Reinforced cement concrete works Cum 2.00
using steel shutter with minimum
cement content relates to mix ratio
1:1.25:2.5 having minimum f'cr = 40
Mpa, and satisfying a specified
compressive strength f?c = 32 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1-CEM 1
(32.5 to 52.5 N) / ASTM-C 150 Type
? I, with approved high range
admixture, best quality coarse sand
[Sylhet sand or coarse sand of
equivalent F.M. 2.2], 20 mm down
well graded crushed stone chips
conforming to ASTM C-33, including
breaking chips and screening through
proper sieves, making and placing
shutter in position and maintaining
true to plumb, making shutter water-
tight properly, placing reinforcement
in position; mixing with standard mixer
machine with hoper and fed by
standard measuring boxes, casting in
forms, compacting by vibrator
machine and curing at least for 28
days, removing centering-shuttering
including cost of water, electricity,
testing and other charges etc. and
making all type of concrete mixture
with the help of automatic batching
plant at site. all comp
Rate for the RCC (materials,
consumables and laying/placing
concrete) works in columns, capitals,
liftwalls & walls where the free height
of the structure exceeds 4 meter
[rate is considered for the height of
each additional 4 (four) meter or
part]g) From 28.0m to 32.0m Hight "
40.8 Civil N/A "Reinforced cement concrete works Cum 2.00
using steel shutter with minimum
cement content relates to mix ratio
1:1.25:2.5 having minimum f'cr = 40
Mpa, and satisfying a specified
compressive strength f?c = 32 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1-CEM 1
(32.5 to 52.5 N) / ASTM-C 150 Type
? I, with approved high range
admixture, best quality coarse sand
[Sylhet sand or coarse sand of
equivalent F.M. 2.2], 20 mm down
well graded crushed stone chips
conforming to ASTM C-33, including
breaking chips and screening through
proper sieves, making and placing
shutter in position and maintaining
true to plumb, making shutter water-
tight properly, placing reinforcement
in position; mixing with standard mixer
machine with hoper and fed by
standard measuring boxes, casting in
forms, compacting by vibrator
machine and curing at least for 28
days, removing centering-shuttering
including cost of water, electricity,
testing and other charges etc. and
making all type of concrete mixture
with the help of automatic batching
plant at site. all comp
Rate for the RCC (materials,
consumables and laying/placing
concrete) works in columns, capitals,
liftwalls & walls where the free height
of the structure exceeds 4 meter
[rate is considered for the height of
each additional 4 (four) meter or
part]h) From 32.0m to 36.0m Hight "
40.9 Civil N/A "Reinforced cement concrete works Cum 2.00
using steel shutter with minimum
cement content relates to mix ratio
1:1.25:2.5 having minimum f'cr = 40
Mpa, and satisfying a specified
compressive strength f?c = 32 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1-CEM 1
(32.5 to 52.5 N) / ASTM-C 150 Type
? I, with approved high range
admixture, best quality coarse sand
[Sylhet sand or coarse sand of
equivalent F.M. 2.2], 20 mm down
well graded crushed stone chips
conforming to ASTM C-33, including
breaking chips and screening through
proper sieves, making and placing
shutter in position and maintaining
true to plumb, making shutter water-
tight properly, placing reinforcement
in position; mixing with standard mixer
machine with hoper and fed by
standard measuring boxes, casting in
forms, compacting by vibrator
machine and curing at least for 28
days, removing centering-shuttering
including cost of water, electricity,
testing and other charges etc. and
making all type of concrete mixture
with the help of automatic batching
plant at site. all comp
Rate for the RCC (materials,
consumables and laying/placing
concrete) works in columns, capitals,
liftwalls & walls where the free height
of the structure exceeds 4 meter
[rate is considered for the height of
each additional 4 (four) meter or
part]i) From 36.0m to 40.0m Hight "
40.10 Civil N/A "Reinforced cement concrete works Cum 2.00
using steel shutter with minimum
cement content relates to mix ratio
1:1.25:2.5 having minimum f'cr = 40
Mpa, and satisfying a specified
compressive strength f?c = 32 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1-CEM 1
(32.5 to 52.5 N) / ASTM-C 150 Type
? I, with approved high range
admixture, best quality coarse sand
[Sylhet sand or coarse sand of
equivalent F.M. 2.2], 20 mm down
well graded crushed stone chips
conforming to ASTM C-33, including
breaking chips and screening through
proper sieves, making and placing
shutter in position and maintaining
true to plumb, making shutter water-
tight properly, placing reinforcement
in position; mixing with standard mixer
machine with hoper and fed by
standard measuring boxes, casting in
forms, compacting by vibrator
machine and curing at least for 28
days, removing centering-shuttering
including cost of water, electricity,
testing and other charges etc. and
making all type of concrete mixture
with the help of automatic batching
plant at site. all comp
Rate for the RCC (materials,
consumables and laying/placing
concrete) works in columns, capitals,
liftwalls & walls where the free height
of the structure exceeds 4 meter
[rate is considered for the height of
each additional 4 (four) meter or
part]j) From 40.0m to 44.0m Hight "
40.11 Civil N/A "Reinforced cement concrete works Cum 2.00
using steel shutter with minimum
cement content relates to mix ratio
1:1.25:2.5 having minimum f'cr = 40
Mpa, and satisfying a specified
compressive strength f?c = 32 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1-CEM 1
(32.5 to 52.5 N) / ASTM-C 150 Type
? I, with approved high range
admixture, best quality coarse sand
[Sylhet sand or coarse sand of
equivalent F.M. 2.2], 20 mm down
well graded crushed stone chips
conforming to ASTM C-33, including
breaking chips and screening through
proper sieves, making and placing
shutter in position and maintaining
true to plumb, making shutter water-
tight properly, placing reinforcement
in position; mixing with standard mixer
machine with hoper and fed by
standard measuring boxes, casting in
forms, compacting by vibrator
machine and curing at least for 28
days, removing centering-shuttering
including cost of water, electricity,
testing and other charges etc. and
making all type of concrete mixture
with the help of automatic batching
plant at site. all comp
Rate for the RCC (materials,
consumables and laying/placing
concrete) works in columns, capitals,
liftwalls & walls where the free height
of the structure exceeds 4 meter
[rate is considered for the height of
each additional 4 (four) meter or
part]k) From 44.0m to 48.0m Hight "
40.12 Civil N/A "Reinforced cement concrete works Cum 2.00
using steel shutter with minimum
cement content relates to mix ratio
1:1.25:2.5 having minimum f'cr = 40
Mpa, and satisfying a specified
compressive strength f?c = 32 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1-CEM 1
(32.5 to 52.5 N) / ASTM-C 150 Type
? I, with approved high range
admixture, best quality coarse sand
[Sylhet sand or coarse sand of
equivalent F.M. 2.2], 20 mm down
well graded crushed stone chips
conforming to ASTM C-33, including
breaking chips and screening through
proper sieves, making and placing
shutter in position and maintaining
true to plumb, making shutter water-
tight properly, placing reinforcement
in position; mixing with standard mixer
machine with hoper and fed by
standard measuring boxes, casting in
forms, compacting by vibrator
machine and curing at least for 28
days, removing centering-shuttering
including cost of water, electricity,
testing and other charges etc. and
making all type of concrete mixture
with the help of automatic batching
plant at site. all comp
Rate for the RCC (materials,
consumables and laying/placing
concrete) works in columns, capitals,
liftwalls & walls where the free height
of the structure exceeds 4 meter
[rate is considered for the height of
each additional 4 (four) meter or
part]l) From 48.0m to 52.0m Hight "
40.13 Civil N/A "Reinforced cement concrete works Cum 2.00
using steel shutter with minimum
cement content relates to mix ratio
1:1.25:2.5 having minimum f'cr = 40
Mpa, and satisfying a specified
compressive strength f?c = 32 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1-CEM 1
(32.5 to 52.5 N) / ASTM-C 150 Type
? I, with approved high range
admixture, best quality coarse sand
[Sylhet sand or coarse sand of
equivalent F.M. 2.2], 20 mm down
well graded crushed stone chips
conforming to ASTM C-33, including
breaking chips and screening through
proper sieves, making and placing
shutter in position and maintaining
true to plumb, making shutter water-
tight properly, placing reinforcement
in position; mixing with standard mixer
machine with hoper and fed by
standard measuring boxes, casting in
forms, compacting by vibrator
machine and curing at least for 28
days, removing centering-shuttering
including cost of water, electricity,
testing and other charges etc. and
making all type of concrete mixture
with the help of automatic batching
plant at site. all comp
Rate for the RCC (materials,
consumables and laying/placing
concrete) works in columns, capitals,
liftwalls & walls where the free height
of the structure exceeds 4 meter
[rate is considered for the height of
each additional 4 (four) meter or
part]m) From 52.0m to 56.0m Hight "
40.14 Civil N/A "Reinforced cement concrete works Cum 2.00
using steel shutter with minimum
cement content relates to mix ratio
1:1.25:2.5 having minimum f'cr = 40
Mpa, and satisfying a specified
compressive strength f?c = 32 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1-CEM 1
(32.5 to 52.5 N) / ASTM-C 150 Type
? I, with approved high range
admixture, best quality coarse sand
[Sylhet sand or coarse sand of
equivalent F.M. 2.2], 20 mm down
well graded crushed stone chips
conforming to ASTM C-33, including
breaking chips and screening through
proper sieves, making and placing
shutter in position and maintaining
true to plumb, making shutter water-
tight properly, placing reinforcement
in position; mixing with standard mixer
machine with hoper and fed by
standard measuring boxes, casting in
forms, compacting by vibrator
machine and curing at least for 28
days, removing centering-shuttering
including cost of water, electricity,
testing and other charges etc. and
making all type of concrete mixture
with the help of automatic batching
plant at site. all comp
Rate for the RCC (materials,
consumables and laying/placing
concrete) works in columns, capitals,
liftwalls & walls where the free height
of the structure exceeds 4 meter
[rate is considered for the height of
each additional 4 (four) meter or
part]n) From 56.0m to 60.0m Hight "
40.15 Civil N/A "Reinforced cement concrete works Cum 2.00
using steel shutter with minimum
cement content relates to mix ratio
1:1.25:2.5 having minimum f'cr = 40
Mpa, and satisfying a specified
compressive strength f?c = 32 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1-CEM 1
(32.5 to 52.5 N) / ASTM-C 150 Type
? I, with approved high range
admixture, best quality coarse sand
[Sylhet sand or coarse sand of
equivalent F.M. 2.2], 20 mm down
well graded crushed stone chips
conforming to ASTM C-33, including
breaking chips and screening through
proper sieves, making and placing
shutter in position and maintaining
true to plumb, making shutter water-
tight properly, placing reinforcement
in position; mixing with standard mixer
machine with hoper and fed by
standard measuring boxes, casting in
forms, compacting by vibrator
machine and curing at least for 28
days, removing centering-shuttering
including cost of water, electricity,
testing and other charges etc. and
making all type of concrete mixture
with the help of automatic batching
plant at site. all comp
Rate for the RCC (materials,
consumables and laying/placing
concrete) works in columns, capitals,
liftwalls & walls where the free height
of the structure exceeds 4 meter
[rate is considered for the height of
each additional 4 (four) meter or
part]o) From 60.0m to 64.0m Hight "
41.1 Civil N/A Rate for the form work/shuttering Sqm 6.00
(steel) of RCC works in columns,
capitals, liftwalls & walls where the
free height of the structure exceeds 4
meter [rate is considered for the
height of each addl. 4 (four) meter or
part] a) From 4.0m to 8.0m Hight
41.2 Civil N/A Rate for the form work/shuttering Sqm 6.00
(steel) of RCC works in columns,
capitals, liftwalls & walls where the
free height of the structure exceeds 4
meter [rate is considered for the
height of each addl. 4 (four) meter or
part] b) From 8.0m to 12.0m Hight
41.3 Civil N/A Rate for the form work/shuttering Sqm 6.00
(steel) of RCC works in columns,
capitals, liftwalls & walls where the
free height of the structure exceeds 4
meter [rate is considered for the
height of each addl. 4 (four) meter or
part] c) From 12.0m to 16.0m Hight
41.4 Civil N/A Rate for the form work/shuttering Sqm 6.00
(steel) of RCC works in columns,
capitals, liftwalls & walls where the
free height of the structure exceeds 4
meter [rate is considered for the
height of each addl. 4 (four) meter or
part] d) From 16.0m to 20.0m Hight
41.5 Civil N/A Rate for the form work/shuttering Sqm 6.00
(steel) of RCC works in columns,
capitals, liftwalls & walls where the
free height of the structure exceeds 4
meter [rate is considered for the
height of each addl. 4 (four) meter or
part] e) From 20.0m to 24.0m Hight
41.6 Civil N/A Rate for the form work/shuttering Sqm 6.00
(steel) of RCC works in columns,
capitals, liftwalls & walls where the
free height of the structure exceeds 4
meter [rate is considered for the
height of each addl. 4 (four) meter or
part] f) From 24.0m to 28.0m Hight
41.7 Civil N/A Rate for the form work/shuttering Sqm 6.00
(steel) of RCC works in columns,
capitals, liftwalls & walls where the
free height of the structure exceeds 4
meter [rate is considered for the
height of each addl. 4 (four) meter or
part] g) From 28.0m to 32.0m Hight
41.8 Civil N/A Rate for the form work/shuttering Sqm 6.00
(steel) of RCC works in columns,
capitals, liftwalls & walls where the
free height of the structure exceeds 4
meter [rate is considered for the
height of each addl. 4 (four) meter or
part] h) From 32.0m to 36.0m Hight
41.9 Civil N/A Rate for the form work/shuttering Sqm 6.00
(steel) of RCC works in columns,
capitals, liftwalls & walls where the
free height of the structure exceeds 4
meter [rate is considered for the
height of each addl. 4 (four) meter or
part] i) From 36.0m to 40.0m Hight
41.10 Civil N/A Rate for the form work/shuttering Sqm 6.00
(steel) of RCC works in columns,
capitals, liftwalls & walls where the
free height of the structure exceeds 4
meter [rate is considered for the
height of each addl. 4 (four) meter or
part] j) From 40.0m to 44.0m Hight
41.11 Civil N/A Rate for the form work/shuttering Sqm 6.00
(steel) of RCC works in columns,
capitals, liftwalls & walls where the
free height of the structure exceeds 4
meter [rate is considered for the
height of each addl. 4 (four) meter or
part] k) From 44.0m to 48.0m Hight
41.12 Civil N/A Rate for the form work/shuttering Sqm 6.00
(steel) of RCC works in columns,
capitals, liftwalls & walls where the
free height of the structure exceeds 4
meter [rate is considered for the
height of each addl. 4 (four) meter or
part] l) From 48.0m to 52.0m Hight
41.13 Civil N/A Rate for the form work/shuttering Sqm 6.00
(steel) of RCC works in columns,
capitals, liftwalls & walls where the
free height of the structure exceeds 4
meter [rate is considered for the
height of each addl. 4 (four) meter or
part] m) From 52.0m to 56.0m Hight
41.14 Civil N/A Rate for the form work/shuttering Sqm 6.00
(steel) of RCC works in columns,
capitals, liftwalls & walls where the
free height of the structure exceeds 4
meter [rate is considered for the
height of each addl. 4 (four) meter or
part] n) From 56.0m to 60.0m Hight
41.15 Civil N/A Rate for the form work/shuttering Sqm 6.00
(steel) of RCC works in columns,
capitals, liftwalls & walls where the
free height of the structure exceeds 4
meter [rate is considered for the
height of each addl. 4 (four) meter or
part] o) From 60.0m to 64.0m Hight
42 Civil N/A Reinforced cement concrete works Cum 1.00
using steel shutter with minimum
cement content relates to mix ratio
1:1.25:2.5 having minimum f'cr = 40
Mpa, and satisfying a specified
compressive strength f?c = 32 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1-CEM 1
(32.5 to 52.5 N) / ASTM-C 150 Type
? I, with approved high range
admixture, best quality coarse sand
[Sylhet sand or coarse sand of
equivalent F.M. 2.2], 20 mm down
well graded crushed stone chips
conforming to ASTM C-33, including
breaking chips and screening through
proper sieves, making and placing
shutter in position and maintaining
true to plumb, making shutter water-
tight properly, placing reinforcement
in position; mixing with standard mixer
machine with hoper and fed by
standard measuring boxes, casting in
forms, compacting by vibrator
machine and curing at least for 28
days, removing centering-shuttering
including cost of water, electricity,
testing and other charges etc. and
making all type of concrete mixture
with the help of automatic batching
plant at site all complete. Rate for the
RCC (materials, consumables and
laying/placing concrete) works in Tee
beams, Ell beams and rectangular
beams where the free height of the
structure exceeds 4 meter (rate is
considered for each addl. meter
height) a) From 6.0m to 7.0m Height
43 Civil N/A Rate for the form work / shuttering Sqm 2.00
(steel) of RCC works in Tee beams,
Ell beams and rectangular beams
where the free height of the structure
exceeds 4 meter (rate is considered
for each addl. meter height)a) From
6.0m to 7.0m Height
44 Civil N/A Reinforced cement concrete works Cum 2.00
using steel shutter with minimum
cement content relates to mix ratio
1:1.25:2.5 having minimum f'cr = 40
Mpa, and satisfying a specified
compressive strength f?c = 32 Mpa
at 28 days on standard cylinders as
per standard practice of Code
ACI/BNBC/ASTM & Cement
conforming to BDS EN-197-1-CEM 1
(32.5 to 52.5 N) / ASTM-C 150 Type
? I, with approved high range
admixture, best quality coarse sand
[Sylhet sand or coarse sand of
equivalent F.M. 2.2], 20 mm down
well graded crushed stone chips
conforming to ASTM C-33, including
breaking chips and screening through
proper sieves, making and placing
shutter in position and maintaining
true to plumb, making shutter water-
tight properly, placing reinforcement
in position; mixing with standard mixer
machine with hoper and fed by
standard measuring boxes, casting in
forms, compacting by vibrator
machine and curing at least for 28
days, removing centering-shuttering
including cost of water, electricity,
testing and other charges etc. and
making all type of concrete mixture
with the help of automatic batching
plant at site all complete. Rate for the
RCC (materials, consumables and
laying/placing concrete) works in floor
/ roof slab, cantilever slab, waffle
slab and drop panels where the free
height of the structure exceeds 4
meter (rate is considered for each
addl. meter height) a) From 6.0m to
7.0m Height
45 Civil N/A Rate for the form work / shuttering Sqm 2.00
(steel) for RCC works in floor / roof
slab, cantilever slab, waffle slab and
drop panels where the free height of
the structure exceeds 4 meter (rate is
considered for each addl. meter
height)a). From 6.0m to 7.0m Hight
46 Civil N/A Supplying and mixing specified type Liter 7000.00
chemical admixture delivered from an
authorized local agent or
manufacturer, comply with the ASTM
C-494 requirements, confirming the
current compliance of the admixture
to specification requirements like
physical properties, uniformity and
equivalence in composition etc.,
performance (water content, fresh
concrete setting time and
compressive strength) requirements,
delivered in sealed water-tight
containers having and confirming
plainly marked the proprietary name
of the admixture type under this
specification, net weight and /or
volume, manufacturing and expiry
date, non aggressiveness to
environment, aggregates and metals
in concrete etc. and mixing the
admixture in non pre-stressed cement
concrete mixture in the field under the
strict accordance with manufacturers
recommendation and instruction,
providing safety provisions in all
respects etc. all complete as per
instruction and approved by the
Engineer. Dose (quantity in milliliters
per 50 kg bag cement) and
brand/origin/ manufacturer with
respect to particular brand of cement
and particular stock of aggregates
and method of use to be determined
by mix design / trial mix at the cost
borne by the Contractor and
approved by the Engineer. (Use of
admixture is subject to prior approval
of Design Office of Public Works
Department) a) Supply and use of
water reducing chemical admixture
ASTM C-494 Type - A of approved
brand/origin/manufacturer in concrete:
The admixture to reduce quantity of
mixing water required for normal
workability and to maintain low water-
cement (W/C) ratio for improved
concrete.
47-a Civil N/A "Supplying, best quality pliable, cold Sqm 118.00
applied pre-formed self adhesive
rubberized/ bituminous water proofing
membrane of approved brand / origin
/ manufacturer from an authorized
local agent or manufacturer having
minimum thickness 1.5 mm, lined with
2 ply cross laminated high density
polyethylene film performances and
properties all conforming to ASTM
standards and laying, placing, fixing
on made up firm and dry surfaces
free from hollows, sharp protrusions,
contaminates etc. laid over-lap by at
least 75 mm along the edges and 125
mm at ends ensuring good initial bond
with the surfaces all complete under
the strict accordance with the
manufacturer recommendations and
instructions providing all safety
provisions in all respects and
accepted by the Engineer.a) Water-
proofing membrane on external
surface of primed vertical or inclined
wall /on plastered and primed back-
wall and concrete cast against
membrane.
(Excluding cost of back fill/brick wall
on back/plaster when membrane laid
on back-wall and concrete cast
against membrane which to be paid
as per corresponding items in this
schedule)"
47-b Civil N/A Supplying, best quality pliable, cold Sqm 1663.12
applied pre-formed self adhesive
rubberized/ bituminous water proofing
membrane of approved brand / origin
/ manufacturer from an authorized
local agent or manufacturer having
minimum thickness 1.5 mm, lined with
2 ply cross laminated high density
polyethylene film performances and
properties all conforming to ASTM
standards and laying, placing, fixing
on made up firm and dry surfaces
free from hollows, sharp protrusions,
contaminates etc. laid over-lap by at
least 75 mm along the edges and 125
mm at ends ensuring good initial bond
with the surfaces all complete under
the strict accordance with the
manufacturer recommendations and
instructions providing all safety
provisions in all respects and
accepted by the Engineer.b) Water-
proofing membrane on made up
surface below the floor or below the
horizontal surfaces with temporary
protective cover using
polysterene/1.5" thick sand-cement
mortar in 4:1 /or by equally effective
alternative. (Rate is excluding the
cost of protective cover which to be
paid as per corresponding items in
this schedule)
48 Civil N/A Supplying, fabrication and fixing to Qtl. 16150.00
details as per design deformed bar
reinforcement in concrete in
accordance with BDS 1313 : 1991
standard including straightening and
cleaning rust, if any, bending and
binding in position including supply of
G.I. wires etc. complete in all
respects and accepted by the
Engineer.a. 60-grade deformed bar
with minimum fy = 415 MPa.: for
Basement & 18th floor
49 Civil N/A "Labour for breaking head of Cum 85.00
hardened cast in situ bored pile/pre-
cast pile up to a required length by
any means but without damaging the
rest and removing the dismantled
materials such as concrete to a safe
distance including scraps and
cleaning concrete from steel/M.S.
rods, straightening and bending of
pile bars, preparation and making
platform where necessary, carrying,
all sorts of handling, stacking the
same properly after clearing, leveling
and dressing the situ and clearing the
bed etc. complete in all respects and
accepted by the Engineer.
(Measurement will be given for the
actual pile head volume to be
broken)"
50 Civil N/A Supplying, fitting and fixing 1.5 mm sqm 20.00
thick fiber glass sheet roofing fitted
and fixed on M.S. sections with 'J'
hook or wooden purlin with screws,
limpet washers and putty etc. all
complete and accepted by the
Engineer.
51 Civil N/A Supplying and making door and Cum 37.57
window frames (Chowkat) for all
floors with matured natural seasoned
wood of required size including
painting two coats of coal tar to the
surface in contact with wall, fitting
and fixing in position etc. complete
and accepted by the Engineera) Teak
Chambal
52 Civil N/A Supplying, fitting and fixing M.S. flat Each 3726.00
bar clamp of 225 x 38 x 6 mm size
having bifurcated ends to door and
window frames with necessary
screws and encasing inside the wall
with cement concrete (1:2:4) etc.
complete and accepted by the
Engineer.
53 Civil N/A Supplying, fitting and fixing 38 mm sqm 277.72
finished well matured, natural
seasoned (min 10" wide plank)
wooden ornamental special design
(equivalent hatil) both sides single
panel flush door shutter with top and
middle rail 150 mm x 38mm bottom
rail 225 mm x 38 mm and style 125
mm x 38 mm, having vertical panels
175 mm x 38 mm in./c minimum 12
mm lap to each panel providing 4 nos,
best quality 100 mm brass hinges, 12
mm dia best quality 200 mm & 300
mm brass socket and tower bolts
2(two) now heavy type best quality
brass handle hinges cleats, wooden
buffer blocks in/c supply of necessary
nails and screws finished by making
design by machine finished etc. all
complete in all floors and accepted by
the Engineer (Ctg./Burma Teak
Wood).
54 Civil N/A Supplying, fitting and fixing 38 mm sqm 526.00
finished thick well matured, natural
seasoned (min. 10? wide plank)
wooden grooved single panel flush
door shutters with top and middle rail
100 mm x 38 mm, bottom rail 225
mm x 38 mm and style 100 mm x 38
mm, having vertical panels 100 x 38
mm including keeping 6 mm x 12 mm
even groove all around and minimum
12 mm grooved lap to each panel.
Providing 4 Nos. best quality 100 mm
iron hinges, 12 mm dia best quality
200 mm and 300 mm iron socket and
tower bolts, 2 (two) Nos. heavy type
best quality nickel plated handle
hinged cleats, wooden buffer blocks
including supply of necessary nails
and screws, finished by sand
papering etc. complete in all respect
in all floors as per drawing and as per
standard practice and accepted by
the Engineer. (All sizes of wood are
finished).a) Chittagong/Burma Teak
55 Civil N/A Supplying, fitting and fixing 36 mm sqm 540.00
thick and having density 400 kg/cum
solid particle board single leaf flush
door for all floors for internal use
made of well matured mechanical
seasoned Rubber (Malaysian timber)
or other approved wooden frame
having finished size 35 x 50 mm
around upon which 1.4 mm thick
veneer (total two Nos. of veneers one
of 0.7 mm horizontally and another of
0.7 mm vertically made of Burma
Teak or Champa or Chapalish or
Garjan wood) with necessary screws
are pested on each side by
mechanized process and provided
with best quality 4 Nos. 100 mm iron
hinges, 2 Nos. best quality 12 mm
iron dia 300 mm and 225 mm long
iron tower and socket bolts, 2 (two)
Nos. heavy type nickel plated
handles, hinged cleats, buffer blocks
etc. complete and accepted by the
Engineer. a) Burma Teak veneered
56 Civil N/A Supplying, fitting and fixing M.S. door sqm 21.81
shutter made with 1.5? x 1.5? x ¼?
angle outer frame, inner member 1? x
¼? F.I. bar, cladding with 16 BWG
M.S. sheet, hinged with 2? x 2? x ¼?
M.S. angle Chowkat.
57 Civil N/A Extra cost for using brass/ SS fittings Each 1000.00
in place of iron fittings in doors &
windows for all floors (super quality
local).a) Brass fittings of door
58 Civil N/A Supplying, fitting and fixing Each 130.00
MORTICE door lock approved and
accepted by the Engineer.
59 Civil N/A Supplying, fitting and fixing Rim/ Each 563.00
round door lock approved and
accepted by the Engineer.
60 Civil N/A Supplying, fitting and fixing of best Each 613.00
quality magnetic door shock absorber
including all necessary tools and
accessories etc. all complete
approved and accepted by the
Engineer
61 Civil N/A Supplying, fitting and fixing best Each 451.00
quality heavy type 19 mm dia and to
300 mm long brass hasp bolt
including cutting grooves in door
shutter and frames, screws etc. all
complete approved and accepted by
the Engineer.
62 Civil N/A Supplying, fitting and fixing sqm 650.00
window/verandha grills of any design
made with 20 x 5 mm F.I. bar
including fabricating, welding cost of
electricity and tools and plants etc.
complete for all floors accepted by
the Engineer. (Total weight per sqm
should be min 24.25 kg. and add or
deduct. @ Tk. 35.00 for each kg.
excess or less respectively)
63 Civil N/A Supplying, fitting and fixing sqm 3541.00
window/verandha grill made of 12mm
x 12mm M.S. solid bar/flat bar 5.5?
c/c with outer frame of 1.5? x ¼? F.I.
bar as per design approved and
accepted by the Engineer. for all
Floors
64-a Civil N/A "Supplying, fitting and fixing of sqm 2570.10
Aluminium sliding composite window
with mosquito mesh as per the U.S.
Architectural Aluminium
Manufacturer's Association (AAMA)
standard specification having 1.2 mm
thick outer bottom (size 95.00 mm,
38 mm, 0.870 kg/m), 1.2 mm thick
outer top (size 95.00 mm, 28.50 mm,
0.97kg/m), 1.2 mm thick shutter top
(size 33 mm, 26.80 mm, 22 mm,
0.536 kg/m), 1.2 mm thick shutter
bottom (size 60 mm, 24.40 mm,
0.736 kg/m), 1.2 mm thick outer side
(size 95.00 mm, 19.50 mm, 0.738
kg/m), 1.2 mm thick shutter lock (size
49.20 mm, 26.2 mm, 0.661 kg/m),
1.2 mm thick shutter lock (size 34.40
mm, 32.10 mm, 0.665 kg/m), 1.2 mm
thick mesh section (size 42.20 mm,
13.20 mm 0.460 kg/m), all aluminium
members (total weight 12.79 kg) will
be anodized to aluminium
bronze/silver colour with a coat not
less than 15 micron in thickness and
density of 4 mg per square cm etc.
including all accessories like sliding
door key lock, sliding door wheel,
sliding door mohiar, sliding door
neoprene, bolts and nuts including
sealants, keeping provision for fitting
fiber mesh including labour charge for
fitting of accessories, making grooves
and mending good damages,
carriage, and electricity. complete in
all respect as per drawing and
accepted by the Engineer.
a) S.S colour/as per archtict design"
64-b Civil N/A "Supplying, fitting and fixing of sqm 1445.06
Aluminium sliding doors as per the
U.S. Architectural Aluminium
Manufacturer's Association (AAMA)
standard specification having 1.2 mm
thick outer bottom (size 75.50 mm,
17.79 mm, 0.528 kg/m), 1.2 mm thick
outer top (size 75.50 mm, 26.80 mm,
0.78 kg/m) 1.2 mm thick shutter top
(size 33 mm, 26.80 mm, 0.536 kg/m),
1.2 mm shutter bottom (size 60 mm,
24 mm, 0.736 kg/m), 1.2 mm thick
outer side(size 75.50 mm, 19.90 mm,
0.616 kg/m) 1.5 mm thick shutter lock
(size 49.20 mm, 26.20 mm, 0.661
kg/m), 1.2 mm thick inter lock (size
34.40 mm, 32.10 mm, 0.665 kg/m),
1.2 mm thick shutter divider (size
31.75 mm, 0.535 kg/m) sections all
aluminium members (Total weight
14.789 kg) will be anodized to
aluminium bronze/silver colour with a
coat not less than 15 microns in
thickness and density of 4 mg per
square cm etc. including all
accessories like handle, sliding door
key lock , sliding door wheel, sliding
door mohiar, sliding door neoprene,
bolts and nuts including sealants,
keeping provision for fitting 5mm thick
glass including labour charge for
fitting of accessories, making grooves
and mending good damages,
carriage, and electricity complete in
all respect as per drawing and
accepted by the Engineer.
Size up to: 2100 mm x 2100 mm
a) S.S colour/as per archtict design"
65 Civil N/A "Supplying fitting and fixing of sqm 70.00
Aluminium fixed fan light as per the
U.S. Architectural Aluminium
Manufacturer's Association (AAMA)
standard specification mm, 0.313
kg/m) 1.2 mm thick bottom cover
(size 76.2 mm, 38.10 mm, 0.76 kg/m)
and 2.5 mm thick grouve cover
section (size 57.15mm, 15.80 mm,
0.425 kg/m) and 1.2 thick top and
side section (76.20 mm, 16 mm,
38.10 mm, 0.961 kg/m) fixed with
above mentioned frames and all
aluminium members (Total weight
5.365kg) will be anodized to
aluminium bronze/silver colour with a
coat not less than 15 micron in
thickness and density of 4 mg per
square cm etc. including all
accessories, neoprene, sealant, nut
and bolt etc. complete in all respect
as per drawing and accepted by the
Engineer.

a) S.S colour/as per archtict design"


66-a Civil N/A "Supplying, fitting and fixing in Sqm 2616.73
Aluminium door frames, windows,
partitions and curtain wall distortion
free glass of approved quality and
shade including cost of fitting fixing all
necessary accessories etc. complete
in all respect as per drawing and
accepted by the Engineer.
a) 5 mm thick tinted glass"
66-b Civil N/A Supplying, fitting and fixing in Sqm 1448.43
Aluminium door frames, windows,
partitions and curtain wall distortion
free glass of approved quality and
shade including cost of fitting fixing all
necessary accessories etc. complete
in all respect as per drawing and
accepted by the Engineer.b) 6 mm
thick tempered glass
67 Civil N/A Minimum 12 mm thick cement sand Sqm 100.00
(F.M. 1.2) plaster with neat cement
finishing to dado (1:4) with cement up
to 150 mm below ground level with
neat cement finishing including
washing of sand, finishing the edges
and corners and curing at least for 7
days, cost of water, electricity and
other charges etc. all complete in all
respect as per drawing and accepted
by the Engineer. (Cement: CEM-II/A-
M) Ground floor.
68-a Civil N/A Minimum 12 mm thick cement sand Sqm 1538.00
(F.M. 1.2) plaster (1:4) having with
fresh cement to wall both inner-and
outer surface, finishing the corner and
edges including washing of sand
cleaning the surface, scaffolding and
curing at least for 7 days, cost of
water, electricity and other charges
etc. all complete in all respect as per
drawing and accepted by the
Engineer. (Cement: CEM-II/A-M) a)
Basement & Ground Floor
68-b Civil N/A Minimum 12 mm thick cement sand Sqm 1018.38
(F.M. 1.2) plaster (1:4) having with
fresh cement to wall both inner-and
outer surface, finishing the corner and
edges including washing of sand
cleaning the surface, scaffolding and
curing at least for 7 days, cost of
water, electricity and other charges
etc. all complete in all respect as per
drawing and accepted by the
Engineer. (Cement: CEM-II/A-M) b)
1st Floor
68-c Civil N/A Minimum 12 mm thick cement sand Sqm 2606.10
(F.M. 1.2) plaster (1:4) having with
fresh cement to wall both inner-and
outer surface, finishing the corner and
edges including washing of sand
cleaning the surface, scaffolding and
curing at least for 7 days, cost of
water, electricity and other charges
etc. all complete in all respect as per
drawing and accepted by the
Engineer. (Cement: CEM-II/A-M) c)
2nd Floor
68-d Civil N/A Minimum 12 mm thick cement sand Sqm 2606.10
(F.M. 1.2) plaster (1:4) having with
fresh cement to wall both inner-and
outer surface, finishing the corner and
edges including washing of sand
cleaning the surface, scaffolding and
curing at least for 7 days, cost of
water, electricity and other charges
etc. all complete in all respect as per
drawing and accepted by the
Engineer. (Cement: CEM-II/A-M) d)
3rd Floor
68-e Civil N/A Minimum 12 mm thick cement sand Sqm 2606.10
(F.M. 1.2) plaster (1:4) having with
fresh cement to wall both inner-and
outer surface, finishing the corner and
edges including washing of sand
cleaning the surface, scaffolding and
curing at least for 7 days, cost of
water, electricity and other charges
etc. all complete in all respect as per
drawing and accepted by the
Engineer. (Cement: CEM-II/A-M) e)
4th Floor
68-f Civil N/A Minimum 12 mm thick cement sand Sqm 2606.10
(F.M. 1.2) plaster (1:4) having with
fresh cement to wall both inner-and
outer surface, finishing the corner and
edges including washing of sand
cleaning the surface, scaffolding and
curing at least for 7 days, cost of
water, electricity and other charges
etc. all complete in all respect as per
drawing and accepted by the
Engineer. (Cement: CEM-II/A-M) f)
5th Floor
68-g Civil N/A Minimum 12 mm thick cement sand Sqm 2606.10
(F.M. 1.2) plaster (1:4) having with
fresh cement to wall both inner-and
outer surface, finishing the corner and
edges including washing of sand
cleaning the surface, scaffolding and
curing at least for 7 days, cost of
water, electricity and other charges
etc. all complete in all respect as per
drawing and accepted by the
Engineer. (Cement: CEM-II/A-M) g)
6th Floor
68-h Civil N/A Minimum 12 mm thick cement sand Sqm 2606.10
(F.M. 1.2) plaster (1:4) having with
fresh cement to wall both inner-and
outer surface, finishing the corner and
edges including washing of sand
cleaning the surface, scaffolding and
curing at least for 7 days, cost of
water, electricity and other charges
etc. all complete in all respect as per
drawing and accepted by the
Engineer. (Cement: CEM-II/A-M) h)
7th Floor
68-i Civil N/A Minimum 12 mm thick cement sand Sqm 2606.10
(F.M. 1.2) plaster (1:4) having with
fresh cement to wall both inner-and
outer surface, finishing the corner and
edges including washing of sand
cleaning the surface, scaffolding and
curing at least for 7 days, cost of
water, electricity and other charges
etc. all complete in all respect as per
drawing and accepted by the
Engineer. (Cement: CEM-II/A-M) i)
8th Floor
68-j Civil N/A Minimum 12 mm thick cement sand Sqm 2606.10
(F.M. 1.2) plaster (1:4) having with
fresh cement to wall both inner-and
outer surface, finishing the corner and
edges including washing of sand
cleaning the surface, scaffolding and
curing at least for 7 days, cost of
water, electricity and other charges
etc. all complete in all respect as per
drawing and accepted by the
Engineer. (Cement: CEM-II/A-M) j)
9th Floor
68-k Civil N/A Minimum 12 mm thick cement sand Sqm 2606.10
(F.M. 1.2) plaster (1:4) having with
fresh cement to wall both inner-and
outer surface, finishing the corner and
edges including washing of sand
cleaning the surface, scaffolding and
curing at least for 7 days, cost of
water, electricity and other charges
etc. all complete in all respect as per
drawing and accepted by the
Engineer. (Cement: CEM-II/A-M) k)
10th Floor
68-l Civil N/A Minimum 12 mm thick cement sand Sqm 2606.10
(F.M. 1.2) plaster (1:4) having with
fresh cement to wall both inner-and
outer surface, finishing the corner and
edges including washing of sand
cleaning the surface, scaffolding and
curing at least for 7 days, cost of
water, electricity and other charges
etc. all complete in all respect as per
drawing and accepted by the
Engineer. (Cement: CEM-II/A-M) l)
11th Floor
68-m Civil N/A Minimum 12 mm thick cement sand Sqm 2606.10
(F.M. 1.2) plaster (1:4) having with
fresh cement to wall both inner-and
outer surface, finishing the corner and
edges including washing of sand
cleaning the surface, scaffolding and
curing at least for 7 days, cost of
water, electricity and other charges
etc. all complete in all respect as per
drawing and accepted by the
Engineer. (Cement: CEM-II/A-M) m)
12th Floor
68-n Civil N/A Minimum 12 mm thick cement sand Sqm 2606.10
(F.M. 1.2) plaster (1:4) having with
fresh cement to wall both inner-and
outer surface, finishing the corner and
edges including washing of sand
cleaning the surface, scaffolding and
curing at least for 7 days, cost of
water, electricity and other charges
etc. all complete in all respect as per
drawing and accepted by the
Engineer. (Cement: CEM-II/A-M) n)
13th Floor
68-o Civil N/A Minimum 12 mm thick cement sand Sqm 2606.10
(F.M. 1.2) plaster (1:4) having with
fresh cement to wall both inner-and
outer surface, finishing the corner and
edges including washing of sand
cleaning the surface, scaffolding and
curing at least for 7 days, cost of
water, electricity and other charges
etc. all complete in all respect as per
drawing and accepted by the
Engineer. (Cement: CEM-II/A-M) o)
14th Floor
68-p Civil N/A Minimum 12 mm thick cement sand Sqm 2606.10
(F.M. 1.2) plaster (1:4) having with
fresh cement to wall both inner-and
outer surface, finishing the corner and
edges including washing of sand
cleaning the surface, scaffolding and
curing at least for 7 days, cost of
water, electricity and other charges
etc. all complete in all respect as per
drawing and accepted by the
Engineer. (Cement: CEM-II/A-M) p)
15th Floor
68-q Civil N/A Minimum 12 mm thick cement sand Sqm 2606.10
(F.M. 1.2) plaster (1:4) having with
fresh cement to wall both inner-and
outer surface, finishing the corner and
edges including washing of sand
cleaning the surface, scaffolding and
curing at least for 7 days, cost of
water, electricity and other charges
etc. all complete in all respect as per
drawing and accepted by the
Engineer. (Cement: CEM-II/A-M) q)
16th Floor
68-r Civil N/A Minimum 12 mm thick cement sand Sqm 812.95
(F.M. 1.2) plaster (1:4) having with
fresh cement to wall both inner-and
outer surface, finishing the corner and
edges including washing of sand
cleaning the surface, scaffolding and
curing at least for 7 days, cost of
water, electricity and other charges
etc. all complete in all respect as per
drawing and accepted by the
Engineer. (Cement: CEM-II/A-M) r)
17th Floor
68-s Civil N/A Minimum 12 mm thick cement sand Sqm 197.68
(F.M. 1.2) plaster (1:4) having with
fresh cement to wall both inner-and
outer surface, finishing the corner and
edges including washing of sand
cleaning the surface, scaffolding and
curing at least for 7 days, cost of
water, electricity and other charges
etc. all complete in all respect as per
drawing and accepted by the
Engineer. (Cement: CEM-II/A-M) s)
18th Floor
69-a Civil N/A Minimum 6 mm thick cement sand Sqm 7412.41
(F.M. 1.2) plaster (1:4) with fresh
cement to ceiling R.C.C. columns,
beams, surface of stair case,
sunshades, cornices, railings, drop
wall, louvers, fins and finishing the
corners and edges including washing
of sand cleaning the surface,
scaffolding and curing at least for 7
days, cost of water, electricity and
other charges etc. all complete in all
respect as per drawing and accepted
by the Engineer. (Cement: CEM-II/A-
M) Ground floor.a) Basement &
Ground Floor
69-b Civil N/A Minimum 6 mm thick cement sand Sqm 3310.27
(F.M. 1.2) plaster (1:4) with fresh
cement to ceiling R.C.C. columns,
beams, surface of stair case,
sunshades, cornices, railings, drop
wall, louvers, fins and finishing the
corners and edges including washing
of sand cleaning the surface,
scaffolding and curing at least for 7
days, cost of water, electricity and
other charges etc. all complete in all
respect as per drawing and accepted
by the Engineer. (Cement: CEM-II/A-
M) Ground floor.b) 1st Floor
69-c Civil N/A Minimum 6 mm thick cement sand Sqm 2839.88
(F.M. 1.2) plaster (1:4) with fresh
cement to ceiling R.C.C. columns,
beams, surface of stair case,
sunshades, cornices, railings, drop
wall, louvers, fins and finishing the
corners and edges including washing
of sand cleaning the surface,
scaffolding and curing at least for 7
days, cost of water, electricity and
other charges etc. all complete in all
respect as per drawing and accepted
by the Engineer. (Cement: CEM-II/A-
M) Ground floor.c) 2nd Floor
69-d Civil N/A Minimum 6 mm thick cement sand Sqm 2839.88
(F.M. 1.2) plaster (1:4) with fresh
cement to ceiling R.C.C. columns,
beams, surface of stair case,
sunshades, cornices, railings, drop
wall, louvers, fins and finishing the
corners and edges including washing
of sand cleaning the surface,
scaffolding and curing at least for 7
days, cost of water, electricity and
other charges etc. all complete in all
respect as per drawing and accepted
by the Engineer. (Cement: CEM-II/A-
M) Ground floor.d) 3rd Floor
69-e Civil N/A Minimum 6 mm thick cement sand Sqm 2839.88
(F.M. 1.2) plaster (1:4) with fresh
cement to ceiling R.C.C. columns,
beams, surface of stair case,
sunshades, cornices, railings, drop
wall, louvers, fins and finishing the
corners and edges including washing
of sand cleaning the surface,
scaffolding and curing at least for 7
days, cost of water, electricity and
other charges etc. all complete in all
respect as per drawing and accepted
by the Engineer. (Cement: CEM-II/A-
M) Ground floor.e) 4th Floor
69-f Civil N/A Minimum 6 mm thick cement sand Sqm 2839.88
(F.M. 1.2) plaster (1:4) with fresh
cement to ceiling R.C.C. columns,
beams, surface of stair case,
sunshades, cornices, railings, drop
wall, louvers, fins and finishing the
corners and edges including washing
of sand cleaning the surface,
scaffolding and curing at least for 7
days, cost of water, electricity and
other charges etc. all complete in all
respect as per drawing and accepted
by the Engineer. (Cement: CEM-II/A-
M) Ground floor.f) 5th Floor
69-g Civil N/A Minimum 6 mm thick cement sand Sqm 2839.88
(F.M. 1.2) plaster (1:4) with fresh
cement to ceiling R.C.C. columns,
beams, surface of stair case,
sunshades, cornices, railings, drop
wall, louvers, fins and finishing the
corners and edges including washing
of sand cleaning the surface,
scaffolding and curing at least for 7
days, cost of water, electricity and
other charges etc. all complete in all
respect as per drawing and accepted
by the Engineer. (Cement: CEM-II/A-
M) Ground floor.g) 6th Floor
69-h Civil N/A Minimum 6 mm thick cement sand Sqm 2839.88
(F.M. 1.2) plaster (1:4) with fresh
cement to ceiling R.C.C. columns,
beams, surface of stair case,
sunshades, cornices, railings, drop
wall, louvers, fins and finishing the
corners and edges including washing
of sand cleaning the surface,
scaffolding and curing at least for 7
days, cost of water, electricity and
other charges etc. all complete in all
respect as per drawing and accepted
by the Engineer. (Cement: CEM-II/A-
M) Ground floor.h) 7th Floor
69-i Civil N/A Minimum 6 mm thick cement sand Sqm 2839.88
(F.M. 1.2) plaster (1:4) with fresh
cement to ceiling R.C.C. columns,
beams, surface of stair case,
sunshades, cornices, railings, drop
wall, louvers, fins and finishing the
corners and edges including washing
of sand cleaning the surface,
scaffolding and curing at least for 7
days, cost of water, electricity and
other charges etc. all complete in all
respect as per drawing and accepted
by the Engineer. (Cement: CEM-II/A-
M) Ground floor.i) 8th Floor
69-j Civil N/A Minimum 6 mm thick cement sand Sqm 2839.88
(F.M. 1.2) plaster (1:4) with fresh
cement to ceiling R.C.C. columns,
beams, surface of stair case,
sunshades, cornices, railings, drop
wall, louvers, fins and finishing the
corners and edges including washing
of sand cleaning the surface,
scaffolding and curing at least for 7
days, cost of water, electricity and
other charges etc. all complete in all
respect as per drawing and accepted
by the Engineer. (Cement: CEM-II/A-
M) Ground floor.j) 9th Floor
69-k Civil N/A Minimum 6 mm thick cement sand Sqm 2839.88
(F.M. 1.2) plaster (1:4) with fresh
cement to ceiling R.C.C. columns,
beams, surface of stair case,
sunshades, cornices, railings, drop
wall, louvers, fins and finishing the
corners and edges including washing
of sand cleaning the surface,
scaffolding and curing at least for 7
days, cost of water, electricity and
other charges etc. all complete in all
respect as per drawing and accepted
by the Engineer. (Cement: CEM-II/A-
M) Ground floor.k) 10th Floor
69-l Civil N/A Minimum 6 mm thick cement sand Sqm 2839.88
(F.M. 1.2) plaster (1:4) with fresh
cement to ceiling R.C.C. columns,
beams, surface of stair case,
sunshades, cornices, railings, drop
wall, louvers, fins and finishing the
corners and edges including washing
of sand cleaning the surface,
scaffolding and curing at least for 7
days, cost of water, electricity and
other charges etc. all complete in all
respect as per drawing and accepted
by the Engineer. (Cement: CEM-II/A-
M) Ground floor.l) 11th Floor
69-m Civil N/A Minimum 6 mm thick cement sand Sqm 2839.88
(F.M. 1.2) plaster (1:4) with fresh
cement to ceiling R.C.C. columns,
beams, surface of stair case,
sunshades, cornices, railings, drop
wall, louvers, fins and finishing the
corners and edges including washing
of sand cleaning the surface,
scaffolding and curing at least for 7
days, cost of water, electricity and
other charges etc. all complete in all
respect as per drawing and accepted
by the Engineer. (Cement: CEM-II/A-
M) Ground floor.m) 12th Floor
69-n Civil N/A Minimum 6 mm thick cement sand Sqm 2839.88
(F.M. 1.2) plaster (1:4) with fresh
cement to ceiling R.C.C. columns,
beams, surface of stair case,
sunshades, cornices, railings, drop
wall, louvers, fins and finishing the
corners and edges including washing
of sand cleaning the surface,
scaffolding and curing at least for 7
days, cost of water, electricity and
other charges etc. all complete in all
respect as per drawing and accepted
by the Engineer. (Cement: CEM-II/A-
M) Ground floor.n) 13th Floor
69-o Civil N/A Minimum 6 mm thick cement sand Sqm 2839.88
(F.M. 1.2) plaster (1:4) with fresh
cement to ceiling R.C.C. columns,
beams, surface of stair case,
sunshades, cornices, railings, drop
wall, louvers, fins and finishing the
corners and edges including washing
of sand cleaning the surface,
scaffolding and curing at least for 7
days, cost of water, electricity and
other charges etc. all complete in all
respect as per drawing and accepted
by the Engineer. (Cement: CEM-II/A-
M) Ground floor.o) 14th Floor
69-p Civil N/A Minimum 6 mm thick cement sand Sqm 2839.88
(F.M. 1.2) plaster (1:4) with fresh
cement to ceiling R.C.C. columns,
beams, surface of stair case,
sunshades, cornices, railings, drop
wall, louvers, fins and finishing the
corners and edges including washing
of sand cleaning the surface,
scaffolding and curing at least for 7
days, cost of water, electricity and
other charges etc. all complete in all
respect as per drawing and accepted
by the Engineer. (Cement: CEM-II/A-
M) Ground floor.p) 15th Floor
69-q Civil N/A Minimum 6 mm thick cement sand Sqm 2839.88
(F.M. 1.2) plaster (1:4) with fresh
cement to ceiling R.C.C. columns,
beams, surface of stair case,
sunshades, cornices, railings, drop
wall, louvers, fins and finishing the
corners and edges including washing
of sand cleaning the surface,
scaffolding and curing at least for 7
days, cost of water, electricity and
other charges etc. all complete in all
respect as per drawing and accepted
by the Engineer. (Cement: CEM-II/A-
M) Ground floor.q) 16th Floor
69-r Civil N/A Minimum 6 mm thick cement sand Sqm 1540.06
(F.M. 1.2) plaster (1:4) with fresh
cement to ceiling R.C.C. columns,
beams, surface of stair case,
sunshades, cornices, railings, drop
wall, louvers, fins and finishing the
corners and edges including washing
of sand cleaning the surface,
scaffolding and curing at least for 7
days, cost of water, electricity and
other charges etc. all complete in all
respect as per drawing and accepted
by the Engineer. (Cement: CEM-II/A-
M) Ground floor.r) 17th Floor
69-s Civil N/A Minimum 6 mm thick cement sand Sqm 1444.45
(F.M. 1.2) plaster (1:4) with fresh
cement to ceiling R.C.C. columns,
beams, surface of stair case,
sunshades, cornices, railings, drop
wall, louvers, fins and finishing the
corners and edges including washing
of sand cleaning the surface,
scaffolding and curing at least for 7
days, cost of water, electricity and
other charges etc. all complete in all
respect as per drawing and accepted
by the Engineer. (Cement: CEM-II/A-
M) Ground floor.s) 18th Floor
69-t Civil N/A Minimum 6 mm thick cement sand Sqm 840.19
(F.M. 1.2) plaster (1:4) with fresh
cement to ceiling R.C.C. columns,
beams, surface of stair case,
sunshades, cornices, railings, drop
wall, louvers, fins and finishing the
corners and edges including washing
of sand cleaning the surface,
scaffolding and curing at least for 7
days, cost of water, electricity and
other charges etc. all complete in all
respect as per drawing and accepted
by the Engineer. (Cement: CEM-II/A-
M) Ground floor.t) 19th Floor
70-a Civil N/A Minimum 12 mm thick cement sand Sqm 400.00
(F.M. 1.2) ornamental plaster (1:4)
having with fresh cement to wall both
inner-and outer surface, finishing the
corner and edges including washing
of sand cleaning the surface,
scaffolding and curing at least for 7
days, cost of water, electricity and
other charges etc. all complete in all
respect as per drawing and accepted
by the Engineer. (Cement: CEM-II/A-
M) a) Basement & Ground Floor
70-b Civil N/A Minimum 12 mm thick cement sand Sqm 200.00
(F.M. 1.2) ornamental plaster (1:4)
having with fresh cement to wall both
inner-and outer surface, finishing the
corner and edges including washing
of sand cleaning the surface,
scaffolding and curing at least for 7
days, cost of water, electricity and
other charges etc. all complete in all
respect as per drawing and accepted
by the Engineer. (Cement: CEM-II/A-
M) b) 1st Floor
70-c Civil N/A Minimum 12 mm thick cement sand Sqm 250.00
(F.M. 1.2) ornamental plaster (1:4)
having with fresh cement to wall both
inner-and outer surface, finishing the
corner and edges including washing
of sand cleaning the surface,
scaffolding and curing at least for 7
days, cost of water, electricity and
other charges etc. all complete in all
respect as per drawing and accepted
by the Engineer. (Cement: CEM-II/A-
M) c) 2nd Floor
70-d Civil N/A Minimum 12 mm thick cement sand Sqm 250.00
(F.M. 1.2) ornamental plaster (1:4)
having with fresh cement to wall both
inner-and outer surface, finishing the
corner and edges including washing
of sand cleaning the surface,
scaffolding and curing at least for 7
days, cost of water, electricity and
other charges etc. all complete in all
respect as per drawing and accepted
by the Engineer. (Cement: CEM-II/A-
M) d) 3rd Floor
70-e Civil N/A Minimum 12 mm thick cement sand Sqm 250.00
(F.M. 1.2) ornamental plaster (1:4)
having with fresh cement to wall both
inner-and outer surface, finishing the
corner and edges including washing
of sand cleaning the surface,
scaffolding and curing at least for 7
days, cost of water, electricity and
other charges etc. all complete in all
respect as per drawing and accepted
by the Engineer. (Cement: CEM-II/A-
M) e) 4th Floor
70-f Civil N/A Minimum 12 mm thick cement sand Sqm 250.00
(F.M. 1.2) ornamental plaster (1:4)
having with fresh cement to wall both
inner-and outer surface, finishing the
corner and edges including washing
of sand cleaning the surface,
scaffolding and curing at least for 7
days, cost of water, electricity and
other charges etc. all complete in all
respect as per drawing and accepted
by the Engineer. (Cement: CEM-II/A-
M) f) 5th Floor
70-g Civil N/A Minimum 12 mm thick cement sand Sqm 250.00
(F.M. 1.2) ornamental plaster (1:4)
having with fresh cement to wall both
inner-and outer surface, finishing the
corner and edges including washing
of sand cleaning the surface,
scaffolding and curing at least for 7
days, cost of water, electricity and
other charges etc. all complete in all
respect as per drawing and accepted
by the Engineer. (Cement: CEM-II/A-
M) g) 6th Floor
70-h Civil N/A Minimum 12 mm thick cement sand Sqm 250.00
(F.M. 1.2) ornamental plaster (1:4)
having with fresh cement to wall both
inner-and outer surface, finishing the
corner and edges including washing
of sand cleaning the surface,
scaffolding and curing at least for 7
days, cost of water, electricity and
other charges etc. all complete in all
respect as per drawing and accepted
by the Engineer. (Cement: CEM-II/A-
M) h) 7th Floor
70-i Civil N/A Minimum 12 mm thick cement sand Sqm 250.00
(F.M. 1.2) ornamental plaster (1:4)
having with fresh cement to wall both
inner-and outer surface, finishing the
corner and edges including washing
of sand cleaning the surface,
scaffolding and curing at least for 7
days, cost of water, electricity and
other charges etc. all complete in all
respect as per drawing and accepted
by the Engineer. (Cement: CEM-II/A-
M) i) 8th Floor
70-j Civil N/A Minimum 12 mm thick cement sand Sqm 250.00
(F.M. 1.2) ornamental plaster (1:4)
having with fresh cement to wall both
inner-and outer surface, finishing the
corner and edges including washing
of sand cleaning the surface,
scaffolding and curing at least for 7
days, cost of water, electricity and
other charges etc. all complete in all
respect as per drawing and accepted
by the Engineer. (Cement: CEM-II/A-
M) j) 9th Floor
70-k Civil N/A Minimum 12 mm thick cement sand Sqm 250.00
(F.M. 1.2) ornamental plaster (1:4)
having with fresh cement to wall both
inner-and outer surface, finishing the
corner and edges including washing
of sand cleaning the surface,
scaffolding and curing at least for 7
days, cost of water, electricity and
other charges etc. all complete in all
respect as per drawing and accepted
by the Engineer. (Cement: CEM-II/A-
M) k) 10th Floor
70-l Civil N/A Minimum 12 mm thick cement sand Sqm 250.00
(F.M. 1.2) ornamental plaster (1:4)
having with fresh cement to wall both
inner-and outer surface, finishing the
corner and edges including washing
of sand cleaning the surface,
scaffolding and curing at least for 7
days, cost of water, electricity and
other charges etc. all complete in all
respect as per drawing and accepted
by the Engineer. (Cement: CEM-II/A-
M) l) 11th Floor
70-m Civil N/A Minimum 12 mm thick cement sand Sqm 250.00
(F.M. 1.2) ornamental plaster (1:4)
having with fresh cement to wall both
inner-and outer surface, finishing the
corner and edges including washing
of sand cleaning the surface,
scaffolding and curing at least for 7
days, cost of water, electricity and
other charges etc. all complete in all
respect as per drawing and accepted
by the Engineer. (Cement: CEM-II/A-
M) m) 12th Floor
70-n Civil N/A Minimum 12 mm thick cement sand Sqm 250.00
(F.M. 1.2) ornamental plaster (1:4)
having with fresh cement to wall both
inner-and outer surface, finishing the
corner and edges including washing
of sand cleaning the surface,
scaffolding and curing at least for 7
days, cost of water, electricity and
other charges etc. all complete in all
respect as per drawing and accepted
by the Engineer. (Cement: CEM-II/A-
M) n) 13th Floor
70-o Civil N/A Minimum 12 mm thick cement sand Sqm 250.00
(F.M. 1.2) ornamental plaster (1:4)
having with fresh cement to wall both
inner-and outer surface, finishing the
corner and edges including washing
of sand cleaning the surface,
scaffolding and curing at least for 7
days, cost of water, electricity and
other charges etc. all complete in all
respect as per drawing and accepted
by the Engineer. (Cement: CEM-II/A-
M) o) 14th Floor
70-p Civil N/A Minimum 12 mm thick cement sand Sqm 250.00
(F.M. 1.2) ornamental plaster (1:4)
having with fresh cement to wall both
inner-and outer surface, finishing the
corner and edges including washing
of sand cleaning the surface,
scaffolding and curing at least for 7
days, cost of water, electricity and
other charges etc. all complete in all
respect as per drawing and accepted
by the Engineer. (Cement: CEM-II/A-
M) p) 15th Floor
70-q Civil N/A Minimum 12 mm thick cement sand Sqm 250.00
(F.M. 1.2) ornamental plaster (1:4)
having with fresh cement to wall both
inner-and outer surface, finishing the
corner and edges including washing
of sand cleaning the surface,
scaffolding and curing at least for 7
days, cost of water, electricity and
other charges etc. all complete in all
respect as per drawing and accepted
by the Engineer. (Cement: CEM-II/A-
M) q) 16th Floor
70-r Civil N/A Minimum 12 mm thick cement sand Sqm 160.00
(F.M. 1.2) ornamental plaster (1:4)
having with fresh cement to wall both
inner-and outer surface, finishing the
corner and edges including washing
of sand cleaning the surface,
scaffolding and curing at least for 7
days, cost of water, electricity and
other charges etc. all complete in all
respect as per drawing and accepted
by the Engineer. (Cement: CEM-II/A-
M) r) 17th Floor
70-s Civil N/A Minimum 12 mm thick cement sand Sqm 150.00
(F.M. 1.2) ornamental plaster (1:4)
having with fresh cement to wall both
inner-and outer surface, finishing the
corner and edges including washing
of sand cleaning the surface,
scaffolding and curing at least for 7
days, cost of water, electricity and
other charges etc. all complete in all
respect as per drawing and accepted
by the Engineer. (Cement: CEM-II/A-
M) s) 18th Floor
70-t Civil N/A Minimum 12 mm thick cement sand Sqm 150.00
(F.M. 1.2) ornamental plaster (1:4)
having with fresh cement to wall both
inner-and outer surface, finishing the
corner and edges including washing
of sand cleaning the surface,
scaffolding and curing at least for 7
days, cost of water, electricity and
other charges etc. all complete in all
respect as per drawing and accepted
by the Engineer. (Cement: CEM-II/A-
M) t) 19th Floor
71 Civil N/A "Providing drip course or Nosing at Rm 7118.65
the edge of sunshade or cornice with
cement sand (F.M. 1.2) mortar (1:2)
with fresh cement including
scaffolding, curing at least for 7 days,
cost of water, electricity and other
charges etc. all complete in all
respect as per drawing and accepted
by the Engineer. (Cement: CEM-II/A-
M)
a) Basement , Ground Floor & 1st
Floor to 19th Floor"
72-a Civil N/A Making groove in plaster on outside Rm 357.00
wall upto 50mm x 6mm size including
scaffolding, curing etc. complete as
per drawing and accepted by the
Engineer.a) Basement & Ground
Floor
72-b Civil N/A Making groove in plaster on outside Rm 357.00
wall upto 50mm x 6mm size including
scaffolding, curing etc. complete as
per drawing and accepted by the
Engineer.b) 1st Floor
72-c Civil N/A Making groove in plaster on outside Rm 357.00
wall upto 50mm x 6mm size including
scaffolding, curing etc. complete as
per drawing and accepted by the
Engineer.c) 2nd Floor
72-d Civil N/A Making groove in plaster on outside Rm 357.00
wall upto 50mm x 6mm size including
scaffolding, curing etc. complete as
per drawing and accepted by the
Engineer.d) 3rd Floor
72-e Civil N/A Making groove in plaster on outside Rm 357.00
wall upto 50mm x 6mm size including
scaffolding, curing etc. complete as
per drawing and accepted by the
Engineer.e) 4th Floor
72-f Civil N/A Making groove in plaster on outside Rm 357.00
wall upto 50mm x 6mm size including
scaffolding, curing etc. complete as
per drawing and accepted by the
Engineer.f) 5th Floor
72-g Civil N/A Making groove in plaster on outside Rm 357.00
wall upto 50mm x 6mm size including
scaffolding, curing etc. complete as
per drawing and accepted by the
Engineer.g) 6th Floor
72-h Civil N/A Making groove in plaster on outside Rm 357.00
wall upto 50mm x 6mm size including
scaffolding, curing etc. complete as
per drawing and accepted by the
Engineer.h) 7th Floor
72-i Civil N/A Making groove in plaster on outside Rm 357.00
wall upto 50mm x 6mm size including
scaffolding, curing etc. complete as
per drawing and accepted by the
Engineer.i) 8th Floor
72-j Civil N/A Making groove in plaster on outside Rm 357.00
wall upto 50mm x 6mm size including
scaffolding, curing etc. complete as
per drawing and accepted by the
Engineer.j) 9th Floor
72-k Civil N/A Making groove in plaster on outside Rm 357.00
wall upto 50mm x 6mm size including
scaffolding, curing etc. complete as
per drawing and accepted by the
Engineer.k) 10th Floor
72-l Civil N/A Making groove in plaster on outside Rm 357.00
wall upto 50mm x 6mm size including
scaffolding, curing etc. complete as
per drawing and accepted by the
Engineer.l) 11th Floor
72-m Civil N/A Making groove in plaster on outside Rm 357.00
wall upto 50mm x 6mm size including
scaffolding, curing etc. complete as
per drawing and accepted by the
Engineer.m) 12th Floor
72-n Civil N/A Making groove in plaster on outside Rm 357.00
wall upto 50mm x 6mm size including
scaffolding, curing etc. complete as
per drawing and accepted by the
Engineer.n) 13th Floor
72-o Civil N/A Making groove in plaster on outside Rm 357.00
wall upto 50mm x 6mm size including
scaffolding, curing etc. complete as
per drawing and accepted by the
Engineer.o) 14th Floor
72-p Civil N/A Making groove in plaster on outside Rm 357.00
wall upto 50mm x 6mm size including
scaffolding, curing etc. complete as
per drawing and accepted by the
Engineer.p) 15th Floor
72-q Civil N/A Making groove in plaster on outside Rm 357.00
wall upto 50mm x 6mm size including
scaffolding, curing etc. complete as
per drawing and accepted by the
Engineer.q) 16th Floor
72-r Civil N/A Making groove in plaster on outside Rm 357.00
wall upto 50mm x 6mm size including
scaffolding, curing etc. complete as
per drawing and accepted by the
Engineer.r) 17th Floor
72-s Civil N/A Making groove in plaster on outside Rm 357.00
wall upto 50mm x 6mm size including
scaffolding, curing etc. complete as
per drawing and accepted by the
Engineer.s) 18th Floor
72-t Civil N/A Making groove in plaster on outside Rm 357.00
wall upto 50mm x 6mm size including
scaffolding, curing etc. complete as
per drawing and accepted by the
Engineer.t) 19th Floor
73 Civil N/A On exterior surface applying as per Sqm 18040.50
manufacturer instructions 3 coat of
weather coat of approved quality and
colour delivered from authorized local
agent of the manufacturer in a sealed
container complete in all respect in all
floors and accepted by the Engineer.
74 Civil N/A Painting to door and window frames Sqm 5782.50
and shutters in two coats with
approved best quality and colour of
synthetic enamel paint delivered from
authorized local agent of the
manufacturer in a sealed container,
having highly water resistant, high
bondibilty, flexible, using specific
brand thinner applied by
brass/roller/spray over a coat of
priming elapsing time for drying
including surface cleaning from dust,
oil or dirt, smoothening, finishing and
polishing with sand paper and
necessary tools, scaffolding, testing
charges etc. all complete in all floors
approved and accepted by the
Engineer.
75 Civil N/A Plastic emulsion paint of approved Sqm 70680.00
best quality and colour delivered from
authorized local agent of the
manufacturer in a sealed container,
applying to wall and ceiling in two
coats over lime putty of special
applied on primer or sealer elapsing
specified time for drying or recoating
including cleaning drying, making free
from dirt, grease, wax, removing all
chalked and scaled materials, fungus,
mending good the surface defects,
sand papering the surface and
necessary scaffolding, spreading by
brush/ roller/spray etc. all complete in
all floors accepted by the Engineer.
76 Civil N/A French polishing to door and window Sqm 4502.35
frames and shutters three coats over
a coat of priming including putty,
cleaning finishing and polishing with
sand paper etc. all complete in all
floors accepted by the Engineer.
77 Civil N/A Constructing surface drain of 300 mm Rm 300.00
clear width and depth up to 300 mm
in brick masonry with 125 mm thick
check wall in cement sand (F.M. 1.2)
mortar (1:6) over av. 75 mm thick
cement concrete base (1:3:6) over
one layer of brick flat soling. The
surface having minimum 12 mm thick
cement sand (F.M. 1.2) plaster (1:3)
and neat cement finishing with cement
curing at least for 7 days including
excavation in all kinds of soil, back
filling with fine sand (F.M. 0.8),
consolidating and dressing, cost of
water, electricity, other charges etc.
complete and accepted by the
Engineer. (Cement: CEM-II/A-M).
78 Civil N/A Providing apron with 50 mm thick Sqm 250.00
cement concrete (1:2:4) with cement,
coarse sand and picked jhama chips
including breaking chips and one layer
brick flat soling at bottom with first
class or picked jhama bricks including
cutting earth for preparation of bed
and filling the interstices with local
sand (F.M. 0.8) including finishing,
dressing, curing at least for 7 days
etc. all complete, including cost of
water, electricity, other charges
accepted by the Engineer. (Cement:
CEM-II/A-M)
79 Civil N/A Supplying, laying, fitting and best Rm 100.00
quality fixing 225 mm dia (internal)
machine made R.C.C. pipe over 100
mm thick cement concrete (1:3:6) at
base and sides including single brick
flat soling and gasket with cement
mortar (1:4) joints, cutting and filling
trenches up to required depth
including excavation of soil etc. all
complete in all respects as per type
plan and accepted by the Engineer
(average depth of trench is 3'-
6").(Cement: CEM-II/A-M) a) with
300 mm dia (internal) R.C.C. pipe.
80 Civil N/A Manufacturing, supplying, fitting and Sqm 62.00
fixing collapsible gate of any design
and shape made of 3/4" x 3/4" x 1/8"
channel placed @ 112 mm c/c
vertically and connecting the same
with each other by 20 x 3 mm M.S
flat bar scissors 525 mm/ 600 mm
long provided in 3 rows including
cutting the different M.S. members to
required sizes, fabricating, welding,
riveting with required size rivets,
providing required size wheels, pulling
handles on both sides, suitable
locking arrangement, electrodes,
grease and finally placing the same in
position in between 2 (two) Nos. 50 x
50 x 6 mm M.S. Tee rail made by
welding 2 Nos. 50 x 6 mm M.S. flat
bar fitted and fixed at top and bottom
with R.C.C. lintel/roof slab, floors and
side wall with required Nos. 150 mm
to 225 mm long 38 x 6 mm M.S. flat
bar clamps one end welded with the
gate member and the other end
bifurcated and embedded in C.C. at
the respective point including cutting
holes and mending good the
damages by pouring concrete (1:2:4)
into the holes and finishing, etc
complete, painting 2 (two) coats with
approved best quality synthetic
enamel paint over a coat of
anticorrosive painting, both end
carriage, including greasing,
electrodes, curing etc. complete as
per drawing and design and accepted
by the Engineer. (Rate is excluding
the cost of paint).a) Collapsible gate
made of 1" x 1" x 1/8" M.S. angle as
vertical member and 1" x 1/8" F.I bar
as scissors.
81 Civil N/A Supplying, fitting, fixing and Sqm 56.00
installation ordinary type M.S. gate
(double leaf) of any design and shape
with 38 x 38 x 6 mm M.S. angle box
(made by welding 2 Nos. 38 x 38 x 6
mm angle) outer frame having 25 x 50
x 25 x 5 mm M.S. channel (made by
welding 2 Nos. of angle) placed part
diagonally after cutting and shaping
as per requirement part horizontally
@ 75 mm C/C the two part of each
leaf being separated by a vertical
member of 38 x 38 x 6 M.S. box and
welded the each ends of diagonal
and horizontal members properly with
the box frame as per architectural
drawing providing full locking
arrangement on 3 mm thick M.S.
plates providing 38 x 38 x 6 mm M.S.
angle clamps, fitting fixing with the
outer frame of the gate the clamp
being embedded in R.C.C. pillars
with cement concrete (1:2:4)
including. cutting holes and mending
good the damages, finishing, curing
and where necessary painting two
coats with approved quality of
synthetic enamel paint over a coat of
priming of anticorrosive paint etc. all
complete including making and
providing 50 x 6 mm M.S. rail and 38
mm wheel for smooth movement of
the gate etc. all complete as per
drawing, design and accepted by the
Engineer. [Rate is excluding the cost
of painting]
82 Civil N/A Manufacturing, supplying, fitting and Sqm 20.00
fixing stair railing of standard height
of any design and shape with square
box (2 No. box in each tread) made
by thorough welding of 2 Nos. 25 x
25 x 5 mm M.S. angle, engraving
each box 150 mm in the concrete by
50 x 50 x 6 mm anchor plate at base
welding 50 x 50 x 6 mm F.I. bar in
inclined plain with the top of the box
fit in the grooved wooden rail and 2
Nos. 225 x 25 mm finished section of
wooden strip fitted and fixed at mid
height of railing at both side of M.S.
angle box in inclined plain parallel to
the hand rail etc. fitted and fixed by
necessary screws, nails including
cutting grooves in concrete mending
good the damages with cement
concrete (1:2:4) applying 1st class
French polish to wooden hand rail
and inclined wooden strip and painting
to F.I bar and square box with 2
(two) coats of synthetic enamel paint
of approved quality and colour over a
prime coat etc. complete in all
respect for all floors and accepted by
the Engineer. (Exposed area of
railing will be considered for
measurement, rate is excluding cost
of polishing and painting).
83 Civil N/A Supplying, fitting and fixing stainless Sqm 493.69
steel (SS) stair railing of standard
height with 2 mm thick 2.5? dia pipe
for hand-rail as per drawing and
accepted by the Engineer.
84 Civil N/A Supplying, fitting and fixing verandah Sqm 1295.00
railing with 2mm thick 50 mm, 25 mm
and 20 mm diameter stainless steel
pipes as per approved design and
accepted by the Engineer.
85 Civil N/A Supplying, fitting and fixing of 20mm Rm 2189.00
dia foreign made aluminium pipe
curtain rail for door and window
including cutting and fitting fixing as
per required measurement and
supplying necessary screws, electric
drill and rowel plug including charge
of electricity etc. complete and
accepted by the Engineer.
86 Civil N/A Supplying fitting, fixing of uPVC Rm 2317.00
plastic door or window frame having
specific gravity 1.35 - 1.45, and other
physical, chemical, thermal, fire
resistivity properties etc. as per BSTI
approved manufacturer standards or
ASTM, BS/ISO/IS standards fitted
and fixed in brick wall/ R.C.C wall
with 6 Nos. GI clamp, 4Nos inner
joint GI clamp, 2 Nos. outer GI joint
clamp, 16 Nos. rivet making
necessary grooves and mending
good the damages, finishing, curing,
carriage etc complete in all respect
accepted by the Engineer.
87 Civil N/A Supplying, fitting, fixing of uPVC Each 465.00
hollow or solid plastic door shutter
having specific gravity 1.35 ? 1.45,
thickness 1.7 mm-2.2 mm, and other
physical, chemical, thermal, fire
resistivity properties etc. as per BSTI
approved manufacturer standards or
ASTM, BS/ISO/IS standards of
different sizes fitted fixed with uPVC
plastic door frame weighing 5.82
kg/m2 with at least 3 Nos. SS hinges
by min 64 Nos. Ø 3.17 mm and 3.97
mm 12.7 mm long rivets, 12 Nos.
25.4 mm SS screws, Ø 9.38 mm,
150 mm long SS tower bolts 2 Nos.,
146 mm SS handle by rivet 2 Nos.,
G.I inner joint 234.95 mm x 127 mm
clamp, 76.2 mm x 57.15 mm, 25 mm
dia 1 no SS haspbolt, special type
round lock, carrying the same to the
site and local carriage etc. complete
in all respect accepted by the
Engineer a) 760 mm x 2130 mm
uPVC plastic shutter (solid).
88-a Civil N/A Manufacturing, Supply, fixing of SS Sqm 3.00
door for all rooms inside the switch
according as per out specification
(panel thickness =40mm, using 16
gauge SS sheet for door frame & 18
gauge SS sheet for door shutter, all
types of door accessories like hatch
bolt, door handle, tower bolt etc.
should be of SS based materials).
88-b Civil N/A Supplying, fitting and fixing ?Column Sqm 273.00
Guard? around the columns at
basement and ground floor parking
area by welding to the previously
embedded clamps (embedded 3? in
the floor/ basement/ slab) using four
vertical M.S. angles (38mm X 38mm
X 6mm) of 36? height above finished
parking level, at four corners of the
column keeping maximum 20mm
clearance from the column finished
surface and bracing by welding four
tops of the vertical M.S. angles with
four 38mm X 38mm X 6mm M.S
angles to the required size and
shape. Placing and welding 25mm X
6mm M.S flat bar at the middle of the
vertical angles all around the column
including necessary cleaning, finishing
and painting all complete as per
direction of the Engineer?in-Charge.
(Rate shall be inclusive supplying and
embedding 3? M.S clamps ):
89-a Civil N/A Supplying and placing of coloured Sqm 3781.99
engraved cement concrete tiles (300
x 300 mm) in size having minimum
thickness 24 mm over 12 mm sand
cement mortar (4:1) each at a
distance of 6 mm apart and filling the
joints with cement sand mortar (1:4)
including raking out joints and cutting
the tiles to required sizes wherever
necessary with high class recessed
pointing, cleaning and washing of
sand, curing for min 3 (three) days on
mortar joints by jute /brush in wet,
followed by impervious /wet covering
for another 4 (four) days etc. all
complete and accepted by the
Engineer. a) in Ground & Basement
Floor
89-b Civil N/A Supplying and placing of coloured Sqm 1280.86
engraved cement concrete tiles (300
x 300 mm) in size having minimum
thickness 24 mm over 12 mm sand
cement mortar (4:1) each at a
distance of 6 mm apart and filling the
joints with cement sand mortar (1:4)
including raking out joints and cutting
the tiles to required sizes wherever
necessary with high class recessed
pointing, cleaning and washing of
sand, curing for min 3 (three) days on
mortar joints by jute /brush in wet,
followed by impervious /wet covering
for another 4 (four) days etc. all
complete and accepted by the
Engineer. b) in roof slab
90-a Civil N/A Exposed brick works (for exterior Cum 15.00
wall without outside plaster) with
automatic machine made first class
bricks, very carefully laid in cement
sand (F.M. 1.2) mortar (1:4) in
superstructure with uniform width and
depth joints, ture to vertical and
horizontal lines including raking out
joints scaffolding, soaking the bricks
at least for 24 hours before use,
washing and screening of sand,
Curing at least for 7 days and high
class flush pointing with cement and
(F.M.1.2) mortar (1:1) including cost
of water, electricity and other
charges etc. all complete and
accepted by the Engineer.a)
Basement & Ground Floor
90-b Civil N/A Exposed brick works (for exterior Cum 45.00
wall without outside plaster) with
automatic machine made first class
bricks, very carefully laid in cement
sand (F.M. 1.2) mortar (1:4) in
superstructure with uniform width and
depth joints, ture to vertical and
horizontal lines including raking out
joints scaffolding, soaking the bricks
at least for 24 hours before use,
washing and screening of sand,
Curing at least for 7 days and high
class flush pointing with cement and
(F.M.1.2) mortar (1:1) including cost
of water, electricity and other
charges etc. all complete and
accepted by the Engineer.b) 1st
Floor
90-c Civil N/A Exposed brick works (for exterior Cum 62.00
wall without outside plaster) with
automatic machine made first class
bricks, very carefully laid in cement
sand (F.M. 1.2) mortar (1:4) in
superstructure with uniform width and
depth joints, ture to vertical and
horizontal lines including raking out
joints scaffolding, soaking the bricks
at least for 24 hours before use,
washing and screening of sand,
Curing at least for 7 days and high
class flush pointing with cement and
(F.M.1.2) mortar (1:1) including cost
of water, electricity and other
charges etc. all complete and
accepted by the Engineer.c) 2nd
Floor
90-d Civil N/A Exposed brick works (for exterior Cum 62.00
wall without outside plaster) with
automatic machine made first class
bricks, very carefully laid in cement
sand (F.M. 1.2) mortar (1:4) in
superstructure with uniform width and
depth joints, ture to vertical and
horizontal lines including raking out
joints scaffolding, soaking the bricks
at least for 24 hours before use,
washing and screening of sand,
Curing at least for 7 days and high
class flush pointing with cement and
(F.M.1.2) mortar (1:1) including cost
of water, electricity and other
charges etc. all complete and
accepted by the Engineer.d) 3rd
Floor
90-e Civil N/A Exposed brick works (for exterior Cum 62.00
wall without outside plaster) with
automatic machine made first class
bricks, very carefully laid in cement
sand (F.M. 1.2) mortar (1:4) in
superstructure with uniform width and
depth joints, ture to vertical and
horizontal lines including raking out
joints scaffolding, soaking the bricks
at least for 24 hours before use,
washing and screening of sand,
Curing at least for 7 days and high
class flush pointing with cement and
(F.M.1.2) mortar (1:1) including cost
of water, electricity and other
charges etc. all complete and
accepted by the Engineer.e) 4th
Floor
90-f Civil N/A Exposed brick works (for exterior Cum 62.00
wall without outside plaster) with
automatic machine made first class
bricks, very carefully laid in cement
sand (F.M. 1.2) mortar (1:4) in
superstructure with uniform width and
depth joints, ture to vertical and
horizontal lines including raking out
joints scaffolding, soaking the bricks
at least for 24 hours before use,
washing and screening of sand,
Curing at least for 7 days and high
class flush pointing with cement and
(F.M.1.2) mortar (1:1) including cost
of water, electricity and other
charges etc. all complete and
accepted by the Engineer.f) 5th Floor
90-g Civil N/A Exposed brick works (for exterior Cum 62.00
wall without outside plaster) with
automatic machine made first class
bricks, very carefully laid in cement
sand (F.M. 1.2) mortar (1:4) in
superstructure with uniform width and
depth joints, ture to vertical and
horizontal lines including raking out
joints scaffolding, soaking the bricks
at least for 24 hours before use,
washing and screening of sand,
Curing at least for 7 days and high
class flush pointing with cement and
(F.M.1.2) mortar (1:1) including cost
of water, electricity and other
charges etc. all complete and
accepted by the Engineer.g) 6th
Floor
90-h Civil N/A Exposed brick works (for exterior Cum 62.00
wall without outside plaster) with
automatic machine made first class
bricks, very carefully laid in cement
sand (F.M. 1.2) mortar (1:4) in
superstructure with uniform width and
depth joints, ture to vertical and
horizontal lines including raking out
joints scaffolding, soaking the bricks
at least for 24 hours before use,
washing and screening of sand,
Curing at least for 7 days and high
class flush pointing with cement and
(F.M.1.2) mortar (1:1) including cost
of water, electricity and other
charges etc. all complete and
accepted by the Engineer.h) 7th Floor
90-i Civil N/A Exposed brick works (for exterior Cum 62.00
wall without outside plaster) with
automatic machine made first class
bricks, very carefully laid in cement
sand (F.M. 1.2) mortar (1:4) in
superstructure with uniform width and
depth joints, ture to vertical and
horizontal lines including raking out
joints scaffolding, soaking the bricks
at least for 24 hours before use,
washing and screening of sand,
Curing at least for 7 days and high
class flush pointing with cement and
(F.M.1.2) mortar (1:1) including cost
of water, electricity and other
charges etc. all complete and
accepted by the Engineer.i) 8th Floor
90-j Civil N/A Exposed brick works (for exterior Cum 62.00
wall without outside plaster) with
automatic machine made first class
bricks, very carefully laid in cement
sand (F.M. 1.2) mortar (1:4) in
superstructure with uniform width and
depth joints, ture to vertical and
horizontal lines including raking out
joints scaffolding, soaking the bricks
at least for 24 hours before use,
washing and screening of sand,
Curing at least for 7 days and high
class flush pointing with cement and
(F.M.1.2) mortar (1:1) including cost
of water, electricity and other
charges etc. all complete and
accepted by the Engineer.j) 9th Floor
90-k Civil N/A Exposed brick works (for exterior Cum 62.00
wall without outside plaster) with
automatic machine made first class
bricks, very carefully laid in cement
sand (F.M. 1.2) mortar (1:4) in
superstructure with uniform width and
depth joints, ture to vertical and
horizontal lines including raking out
joints scaffolding, soaking the bricks
at least for 24 hours before use,
washing and screening of sand,
Curing at least for 7 days and high
class flush pointing with cement and
(F.M.1.2) mortar (1:1) including cost
of water, electricity and other
charges etc. all complete and
accepted by the Engineer.k) 10th
Floor
90-l Civil N/A Exposed brick works (for exterior Cum 62.00
wall without outside plaster) with
automatic machine made first class
bricks, very carefully laid in cement
sand (F.M. 1.2) mortar (1:4) in
superstructure with uniform width and
depth joints, ture to vertical and
horizontal lines including raking out
joints scaffolding, soaking the bricks
at least for 24 hours before use,
washing and screening of sand,
Curing at least for 7 days and high
class flush pointing with cement and
(F.M.1.2) mortar (1:1) including cost
of water, electricity and other
charges etc. all complete and
accepted by the Engineer.l) 11th
Floor
90-m Civil N/A Exposed brick works (for exterior Cum 62.00
wall without outside plaster) with
automatic machine made first class
bricks, very carefully laid in cement
sand (F.M. 1.2) mortar (1:4) in
superstructure with uniform width and
depth joints, ture to vertical and
horizontal lines including raking out
joints scaffolding, soaking the bricks
at least for 24 hours before use,
washing and screening of sand,
Curing at least for 7 days and high
class flush pointing with cement and
(F.M.1.2) mortar (1:1) including cost
of water, electricity and other
charges etc. all complete and
accepted by the Engineer.m) 12th
Floor
90-n Civil N/A Exposed brick works (for exterior Cum 62.00
wall without outside plaster) with
automatic machine made first class
bricks, very carefully laid in cement
sand (F.M. 1.2) mortar (1:4) in
superstructure with uniform width and
depth joints, ture to vertical and
horizontal lines including raking out
joints scaffolding, soaking the bricks
at least for 24 hours before use,
washing and screening of sand,
Curing at least for 7 days and high
class flush pointing with cement and
(F.M.1.2) mortar (1:1) including cost
of water, electricity and other
charges etc. all complete and
accepted by the Engineer.n) 13th
Floor
90-o Civil N/A Exposed brick works (for exterior Cum 62.00
wall without outside plaster) with
automatic machine made first class
bricks, very carefully laid in cement
sand (F.M. 1.2) mortar (1:4) in
superstructure with uniform width and
depth joints, ture to vertical and
horizontal lines including raking out
joints scaffolding, soaking the bricks
at least for 24 hours before use,
washing and screening of sand,
Curing at least for 7 days and high
class flush pointing with cement and
(F.M.1.2) mortar (1:1) including cost
of water, electricity and other
charges etc. all complete and
accepted by the Engineer.o) 14th
Floor
90-p Civil N/A Exposed brick works (for exterior Cum 62.00
wall without outside plaster) with
automatic machine made first class
bricks, very carefully laid in cement
sand (F.M. 1.2) mortar (1:4) in
superstructure with uniform width and
depth joints, ture to vertical and
horizontal lines including raking out
joints scaffolding, soaking the bricks
at least for 24 hours before use,
washing and screening of sand,
Curing at least for 7 days and high
class flush pointing with cement and
(F.M.1.2) mortar (1:1) including cost
of water, electricity and other
charges etc. all complete and
accepted by the Engineer.p) 15th
Floor
90-q Civil N/A Exposed brick works (for exterior Cum 62.00
wall without outside plaster) with
automatic machine made first class
bricks, very carefully laid in cement
sand (F.M. 1.2) mortar (1:4) in
superstructure with uniform width and
depth joints, ture to vertical and
horizontal lines including raking out
joints scaffolding, soaking the bricks
at least for 24 hours before use,
washing and screening of sand,
Curing at least for 7 days and high
class flush pointing with cement and
(F.M.1.2) mortar (1:1) including cost
of water, electricity and other
charges etc. all complete and
accepted by the Engineer.q) 16th
Floor
90-r Civil N/A Exposed brick works (for exterior Cum 62.00
wall without outside plaster) with
automatic machine made first class
bricks, very carefully laid in cement
sand (F.M. 1.2) mortar (1:4) in
superstructure with uniform width and
depth joints, ture to vertical and
horizontal lines including raking out
joints scaffolding, soaking the bricks
at least for 24 hours before use,
washing and screening of sand,
Curing at least for 7 days and high
class flush pointing with cement and
(F.M.1.2) mortar (1:1) including cost
of water, electricity and other
charges etc. all complete and
accepted by the Engineer.r) 17th
Floor
90-s Civil N/A Exposed brick works (for exterior Cum 62.00
wall without outside plaster) with
automatic machine made first class
bricks, very carefully laid in cement
sand (F.M. 1.2) mortar (1:4) in
superstructure with uniform width and
depth joints, ture to vertical and
horizontal lines including raking out
joints scaffolding, soaking the bricks
at least for 24 hours before use,
washing and screening of sand,
Curing at least for 7 days and high
class flush pointing with cement and
(F.M.1.2) mortar (1:1) including cost
of water, electricity and other
charges etc. all complete and
accepted by the Engineer.s) 18th
Floor
90-t Civil N/A Exposed brick works (for exterior Cum 62.00
wall without outside plaster) with
automatic machine made first class
bricks, very carefully laid in cement
sand (F.M. 1.2) mortar (1:4) in
superstructure with uniform width and
depth joints, ture to vertical and
horizontal lines including raking out
joints scaffolding, soaking the bricks
at least for 24 hours before use,
washing and screening of sand,
Curing at least for 7 days and high
class flush pointing with cement and
(F.M.1.2) mortar (1:1) including cost
of water, electricity and other
charges etc. all complete and
accepted by the Engineer.t) 19th
Floor
91-a Civil N/A Providing brick works for 200x100mm Sqm 374.00
facing in superstructure with
200x100x50 mm machine made
clinker hard pressed facing bricks of
approved quality in cement sand
(F.M. 1.2) including racking out joints,
cutting the bricks to required size
wherever necessary including high
class recessed pointing, cleaning and
soaking the bricks at least for 24
hours before use and washing and
screening of sand, necessary,
scaffolding, curing at least for 7 days
for all floors up to 4th floor including
cost of water, electricity and other
charges etc. All complete and
accepted by the Engineer. (100x200
mm face should be placed for
facing)a) Basement & Ground Floor
91-b Civil N/A Providing brick works for 200x100mm Sqm 366.00
facing in superstructure with
200x100x50 mm machine made
clinker hard pressed facing bricks of
approved quality in cement sand
(F.M. 1.2) including racking out joints,
cutting the bricks to required size
wherever necessary including high
class recessed pointing, cleaning and
soaking the bricks at least for 24
hours before use and washing and
screening of sand, necessary,
scaffolding, curing at least for 7 days
for all floors up to 4th floor including
cost of water, electricity and other
charges etc. All complete and
accepted by the Engineer. (100x200
mm face should be placed for
facing)b) 1st Floor
91-c Civil N/A Providing brick works for 200x100mm Sqm 156.00
facing in superstructure with
200x100x50 mm machine made
clinker hard pressed facing bricks of
approved quality in cement sand
(F.M. 1.2) including racking out joints,
cutting the bricks to required size
wherever necessary including high
class recessed pointing, cleaning and
soaking the bricks at least for 24
hours before use and washing and
screening of sand, necessary,
scaffolding, curing at least for 7 days
for all floors up to 4th floor including
cost of water, electricity and other
charges etc. All complete and
accepted by the Engineer. (100x200
mm face should be placed for
facing)c) 2nd Floor
92 Civil N/A Supplying fitting and fixing of Sqm 454.00
Aluminum fixed louver as per the U.S.
Architectural aluminum Manufacture's
Association (AAMA) standard
specification having 1.2mm thick wall
frame (size 76.2mm, 38.10mm,
0.707kg/m), 5mm thick louver section
(size 55.02mm, 37.39mm, 0.22kg/m)
and 2.50mm thick louver outer section
(size 39.67mm, 15.06mm,
0.265kg/m) and all aluminum
members (Total weight 7.992
kg/sqm) will be anodized to aluminum
bronze/silver colour with a coat not
less than 15 micron in thickness and
density of 4 mg per square cm etc.
including all accessories, neoprene,
sealant, nut and bolt etc. complete in
all respect as per drawing and
accepted by the Engineer. Silver
Colour
93 Civil N/A Supplying, fitting and fixing Rastic Sqm 500.00
wall tiles (foreign made) with on 20
mm thick cement sand (F.M. 1.2)
mortar (1:3) base and raking out the
joints with white cement including
cutting, laying and hire charge of
machine and finishing with care etc.
including water, electricity and other
charges complete all respect
accepted by the Engineer. (Cement:
CEM-II/A-M) Coloured glazed wall
tiles of different sizes (Sample
approved by the engineer in
charge))e and accepted by the
Engineer.(Cement: CEM-II/A-M).
300mm x 600mm or equivalent).
1.1 Sanitary N/A Supply, fitting and fixing of Extra Rm. 120
heavy uPVC pipe shall be made
uPVC as per BS4514/ISO4422/
SS213 standard. Pipe shall be bell
end socket type. Approved type of
solvent sealant shall be used to install
pipe and jointing the pipe with uPVC
pipe fittings such as bends, tees, Y-
joints, socket, reducers, U-trap, S-
trap, drain strainer, elbows, offset
bends etc. made of uPVC having
minimum thickness as specified in
uPVC pipe and shall be complete
with threaded service door with cover
etc. Pipefittings. Joint shall be
watertight. In brick wall pipe shall be
surrounded by concrete in 1: 3.5: 5.5
and shall be clamped to wall properly
at an interval of not more than 1200
mm. Pipe laying shall have the
following gradient unless otherwise
specified. Nominal dia of pipe with
thickness shall be as follows. Product
shall be of Partex/ Bangale/ NPL/
RFL from Bangladesh. a)150 mm dia
1: 60 soil, 1: 90 for waste. b)100 mm
dia 1: 40 for soil, 1: 60 for waste. c)
80 mm dia 1: 25 for soil, 1: 40 for
waste.350 mm dia, 9.8mm thick.
1.2 Sanitary N/A Supply, fitting and fixing of Extra Rm. 160
heavy uPVC pipe shall be made
uPVC as per BS4514/ISO4422/
SS213 standard. Pipe shall be bell
end socket type. Approved type of
solvent sealant shall be used to install
pipe and jointing the pipe with uPVC
pipe fittings such as bends, tees, Y-
joints, socket, reducers, U-trap, S-
trap, drain strainer, elbows, offset
bends etc. made of uPVC having
minimum thickness as specified in
uPVC pipe and shall be complete
with threaded service door with cover
etc. Pipefittings. Joint shall be
watertight. In brick wall pipe shall be
surrounded by concrete in 1: 3.5: 5.5
and shall be clamped to wall properly
at an interval of not more than 1200
mm. Pipe laying shall have the
following gradient unless otherwise
specified. Nominal dia of pipe with
thickness shall be as follows. Product
shall be of Partex/ Bangale/ NPL/
RFL from Bangladesh. a)150 mm dia
1: 60 soil, 1: 90 for waste. b)100 mm
dia 1: 40 for soil, 1: 60 for waste. c)
80 mm dia 1: 25 for soil, 1: 40 for
waste.300 mm dia, 7.8mm thick.
1.3 Sanitary N/A Supply, fitting and fixing of Extra Rm. 140
heavy uPVC pipe shall be made
uPVC as per BS4514/ISO4422/
SS213 standard. Pipe shall be bell
end socket type. Approved type of
solvent sealant shall be used to install
pipe and jointing the pipe with uPVC
pipe fittings such as bends, tees, Y-
joints, socket, reducers, U-trap, S-
trap, drain strainer, elbows, offset
bends etc. made of uPVC having
minimum thickness as specified in
uPVC pipe and shall be complete
with threaded service door with cover
etc. Pipefittings. Joint shall be
watertight. In brick wall pipe shall be
surrounded by concrete in 1: 3.5: 5.5
and shall be clamped to wall properly
at an interval of not more than 1200
mm. Pipe laying shall have the
following gradient unless otherwise
specified. Nominal dia of pipe with
thickness shall be as follows. Product
shall be of Partex/ Bangale/ NPL/
RFL from Bangladesh. a)150 mm dia
1: 60 soil, 1: 90 for waste. b)100 mm
dia 1: 40 for soil, 1: 60 for waste. c)
80 mm dia 1: 25 for soil, 1: 40 for
waste.250 mm dia, 6.6mm thick.
1.4 Sanitary N/A Supply, fitting and fixing of Extra Rm. 90
heavy uPVC pipe shall be made
uPVC as per BS4514/ISO4422/
SS213 standard. Pipe shall be bell
end socket type. Approved type of
solvent sealant shall be used to install
pipe and jointing the pipe with uPVC
pipe fittings such as bends, tees, Y-
joints, socket, reducers, U-trap, S-
trap, drain strainer, elbows, offset
bends etc. made of uPVC having
minimum thickness as specified in
uPVC pipe and shall be complete
with threaded service door with cover
etc. Pipefittings. Joint shall be
watertight. In brick wall pipe shall be
surrounded by concrete in 1: 3.5: 5.5
and shall be clamped to wall properly
at an interval of not more than 1200
mm. Pipe laying shall have the
following gradient unless otherwise
specified. Nominal dia of pipe with
thickness shall be as follows. Product
shall be of Partex/ Bangale/ NPL/
RFL from Bangladesh. a)150 mm dia
1: 60 soil, 1: 90 for waste. b)100 mm
dia 1: 40 for soil, 1: 60 for waste. c)
80 mm dia 1: 25 for soil, 1: 40 for
waste.200 mm dia, 5.3mm thick.
1.5 Sanitary N/A Supply, fitting and fixing of Extra Rm. 280
heavy uPVC pipe shall be made
uPVC as per BS4514/ISO4422/
SS213 standard. Pipe shall be bell
end socket type. Approved type of
solvent sealant shall be used to install
pipe and jointing the pipe with uPVC
pipe fittings such as bends, tees, Y-
joints, socket, reducers, U-trap, S-
trap, drain strainer, elbows, offset
bends etc. made of uPVC having
minimum thickness as specified in
uPVC pipe and shall be complete
with threaded service door with cover
etc. Pipefittings. Joint shall be
watertight. In brick wall pipe shall be
surrounded by concrete in 1: 3.5: 5.5
and shall be clamped to wall properly
at an interval of not more than 1200
mm. Pipe laying shall have the
following gradient unless otherwise
specified. Nominal dia of pipe with
thickness shall be as follows. Product
shall be of Partex/ Bangale/ NPL/
RFL from Bangladesh. a)150 mm dia
1: 60 soil, 1: 90 for waste. b)100 mm
dia 1: 40 for soil, 1: 60 for waste. c)
80 mm dia 1: 25 for soil, 1: 40 for
waste.150 mm dia, 4.5 mm thick.
1.6 Sanitary N/A Supply, fitting and fixing of Extra Rm. 5650
heavy uPVC pipe shall be made
uPVC as per BS4514/ISO4422/
SS213 standard. Pipe shall be bell
end socket type. Approved type of
solvent sealant shall be used to install
pipe and jointing the pipe with uPVC
pipe fittings such as bends, tees, Y-
joints, socket, reducers, U-trap, S-
trap, drain strainer, elbows, offset
bends etc. made of uPVC having
minimum thickness as specified in
uPVC pipe and shall be complete
with threaded service door with cover
etc. Pipefittings. Joint shall be
watertight. In brick wall pipe shall be
surrounded by concrete in 1: 3.5: 5.5
and shall be clamped to wall properly
at an interval of not more than 1200
mm. Pipe laying shall have the
following gradient unless otherwise
specified. Nominal dia of pipe with
thickness shall be as follows. Product
shall be of Partex/ Bangale/ NPL/
RFL from Bangladesh. a)150 mm dia
1: 60 soil, 1: 90 for waste. b)100 mm
dia 1: 40 for soil, 1: 60 for waste. c)
80 mm dia 1: 25 for soil, 1: 40 for
waste.100 mm dia, 3.4 mm thick
1.7 Sanitary N/A Supply, fitting and fixing of Extra Rm. 80
heavy uPVC pipe shall be made
uPVC as per BS4514/ISO4422/
SS213 standard. Pipe shall be bell
end socket type. Approved type of
solvent sealant shall be used to install
pipe and jointing the pipe with uPVC
pipe fittings such as bends, tees, Y-
joints, socket, reducers, U-trap, S-
trap, drain strainer, elbows, offset
bends etc. made of uPVC having
minimum thickness as specified in
uPVC pipe and shall be complete
with threaded service door with cover
etc. Pipefittings. Joint shall be
watertight. In brick wall pipe shall be
surrounded by concrete in 1: 3.5: 5.5
and shall be clamped to wall properly
at an interval of not more than 1200
mm. Pipe laying shall have the
following gradient unless otherwise
specified. Nominal dia of pipe with
thickness shall be as follows. Product
shall be of Partex/ Bangale/ NPL/
RFL from Bangladesh. a)150 mm dia
1: 60 soil, 1: 90 for waste. b)100 mm
dia 1: 40 for soil, 1: 60 for waste. c)
80 mm dia 1: 25 for soil, 1: 40 for
waste.80 mm dia, 3 mm thick.
1.8 Sanitary N/A Supply, fitting and fixing of Extra Rm. 450
heavy uPVC pipe shall be made
uPVC as per BS4514/ISO4422/
SS213 standard. Pipe shall be bell
end socket type. Approved type of
solvent sealant shall be used to install
pipe and jointing the pipe with uPVC
pipe fittings such as bends, tees, Y-
joints, socket, reducers, U-trap, S-
trap, drain strainer, elbows, offset
bends etc. made of uPVC having
minimum thickness as specified in
uPVC pipe and shall be complete
with threaded service door with cover
etc. Pipefittings. Joint shall be
watertight. In brick wall pipe shall be
surrounded by concrete in 1: 3.5: 5.5
and shall be clamped to wall properly
at an interval of not more than 1200
mm. Pipe laying shall have the
following gradient unless otherwise
specified. Nominal dia of pipe with
thickness shall be as follows. Product
shall be of Partex/ Bangale/ NPL/
RFL from Bangladesh. a)150 mm dia
1: 60 soil, 1: 90 for waste. b)100 mm
dia 1: 40 for soil, 1: 60 for waste. c)
80 mm dia 1: 25 for soil, 1: 40 for
waste.50 mm dia, 2.4 mm thick
1.9 Sanitary N/A Supply, fitting and fixing of Extra Rm. 120
heavy uPVC pipe shall be made
uPVC as per BS4514/ISO4422/
SS213 standard. Pipe shall be bell
end socket type. Approved type of
solvent sealant shall be used to install
pipe and jointing the pipe with uPVC
pipe fittings such as bends, tees, Y-
joints, socket, reducers, U-trap, S-
trap, drain strainer, elbows, offset
bends etc. made of uPVC having
minimum thickness as specified in
uPVC pipe and shall be complete
with threaded service door with cover
etc. Pipefittings. Joint shall be
watertight. In brick wall pipe shall be
surrounded by concrete in 1: 3.5: 5.5
and shall be clamped to wall properly
at an interval of not more than 1200
mm. Pipe laying shall have the
following gradient unless otherwise
specified. Nominal dia of pipe with
thickness shall be as follows. Product
shall be of Partex/ Bangale/ NPL/
RFL from Bangladesh. a)150 mm dia
1: 60 soil, 1: 90 for waste. b)100 mm
dia 1: 40 for soil, 1: 60 for waste. c)
80 mm dia 1: 25 for soil, 1: 40 for
waste.40 mm dia, 2 mm thick.
1.10 Sanitary N/A Supply, fitting and fixing of Extra Rm. 120
heavy uPVC pipe shall be made
uPVC as per BS4514/ISO4422/
SS213 standard. Pipe shall be bell
end socket type. Approved type of
solvent sealant shall be used to install
pipe and jointing the pipe with uPVC
pipe fittings such as bends, tees, Y-
joints, socket, reducers, U-trap, S-
trap, drain strainer, elbows, offset
bends etc. made of uPVC having
minimum thickness as specified in
uPVC pipe and shall be complete
with threaded service door with cover
etc. Pipefittings. Joint shall be
watertight. In brick wall pipe shall be
surrounded by concrete in 1: 3.5: 5.5
and shall be clamped to wall properly
at an interval of not more than 1200
mm. Pipe laying shall have the
following gradient unless otherwise
specified. Nominal dia of pipe with
thickness shall be as follows. Product
shall be of Partex/ Bangale/ NPL/
RFL from Bangladesh. a)150 mm dia
1: 60 soil, 1: 90 for waste. b)100 mm
dia 1: 40 for soil, 1: 60 for waste. c)
80 mm dia 1: 25 for soil, 1: 40 for
waste.32 mm dia, 1.7 mm thick.
2.1 Sanitary N/A Supply, fitting and fixing of uPVC pipe Nos. 850
fittings such as P-trap, S-trap, Bell
Mouth Roof Drain etc. made of
uPVC having minimum thickness as
specified in uPVC pipe and shall be
complete with threaded service door
with cover etc. Fittings shall be bell
and spigot type to adopt pipes.
Product shall be as per
BS4515/BS5255/ISO4422/ISO3633.
Fittings shall be installed as per
drawing and direction and shall be
properly plumbed and fixed. The
fittings shall be of Bangal/ Partex/
NPL from Bangladesh. uPVC P-Trap
100mm dia :Supply, fitting and fixing
of 100 mm dia uPVC P-trap with
50mm vent and shall have minimum
50mm water seal. 100mm dia
2.2 Sanitary N/A Supply, fitting and fixing of uPVC pipe Nos. 20
fittings such as P-trap, S-trap, Bell
Mouth Roof Drain etc. made of
uPVC having minimum thickness as
specified in uPVC pipe and shall be
complete with threaded service door
with cover etc. Fittings shall be bell
and spigot type to adopt pipes.
Product shall be as per
BS4515/BS5255/ISO4422/ISO3633.
Fittings shall be installed as per
drawing and direction and shall be
properly plumbed and fixed. The
fittings shall be of Bangal/ Partex/
NPL from Bangladesh. uPVC S-
TRAP : Supply, fitting and fixing of
uPVC 100 mm dia uPVC S Trap with
50mm vent and shall have 50mm
water seal. 100mm dia
2.3.a Sanitary N/A Supply, fitting and fixing of uPVC pipe Nos. 4
fittings such as P-trap, S-trap, Bell
Mouth Roof Drain etc. made of
uPVC having minimum thickness as
specified in uPVC pipe and shall be
complete with threaded service door
with cover etc. Fittings shall be bell
and spigot type to adopt pipes.
Product shall be as per
BS4515/BS5255/ISO4422/ISO3633.
Fittings shall be installed as per
drawing and direction and shall be
properly plumbed and fixed. The
fittings shall be of Bangal/ Partex/
NPL from Bangladesh. HCI Bell
Mouth Roof Drain :Supply, fitting and
fixing of HCI Bell Mouth Roof Drain
shall be 200mm x 200mm & 150mm x
150mm size to adopt upvc pipe two
pieces with socket. 150 mm dia
2.3.b Sanitary N/A Supply, fitting and fixing of uPVC pipe Nos. 30
fittings such as P-trap, S-trap, Bell
Mouth Roof Drain etc. made of
uPVC having minimum thickness as
specified in uPVC pipe and shall be
complete with threaded service door
with cover etc. Fittings shall be bell
and spigot type to adopt pipes.
Product shall be as per
BS4515/BS5255/ISO4422/ISO3633.
Fittings shall be installed as per
drawing and direction and shall be
properly plumbed and fixed. The
fittings shall be of Bangal/ Partex/
NPL from Bangladesh. HCI Bell
Mouth Roof Drain :Supply, fitting and
fixing of HCI Bell Mouth Roof Drain
shall be 200mm x 200mm & 150mm x
150mm size to adopt upvc pipe two
pieces with socket. 100 mm dia
3.1 Sanitary N/A Supply, fitting, fixing and laying of Rm 6
R.C.C. pipe over 100 mm and 75 mm
thick cement concrete (6:3:1) at base
over a brick flat soling with proper
gradient in trenches, making collar
joints with gasket and cement mortar
(1:1) including cutting trenches and
refilling the same upto the required
depth as per direction of the
Engineer/Consultant.350 mm dia pipe
3.2 Sanitary N/A Supply, fitting, fixing and laying of Rm 6
R.C.C. pipe over 100 mm and 75 mm
thick cement concrete (6:3:1) at base
over a brick flat soling with proper
gradient in trenches, making collar
joints with gasket and cement mortar
(1:1) including cutting trenches and
refilling the same upto the required
depth as per direction of the
Engineer/Consultant. 300 mm dia
pipe
4.1.a Sanitary N/A WATER SUPPLY PIPE : GI PIPE : Rm 210
Supply, fittings, fixing and laying of GI
Pipe. Pipe work of Standard
thickness as specified in group-ka or
approved equivalent shall be
complete with bends, tees, elbows,
socket, union, reducers, hanger,
bracket, clamp etc. complete.
Approved type of sealant shall be
used on thread to make it leak proof.
All the pipe work shall be tested at
680 kpa for 24 hours in presence of
the representative of the
Owner/counsultants. All MS & GI
Materials used in pipe work shall be
painted with two coats of prime cote
of approved quality. Product shall be
of NTL/ Bashundhara (Ruby)
Bangladesh. 100mm dia, 3.65mm
thick
4.1.b Sanitary N/A WATER SUPPLY PIPE : GI PIPE : Rm 90
Supply, fittings, fixing and laying of GI
Pipe. Pipe work of Standard
thickness as specified in group-ka or
approved equivalent shall be
complete with bends, tees, elbows,
socket, union, reducers, hanger,
bracket, clamp etc. complete.
Approved type of sealant shall be
used on thread to make it leak proof.
All the pipe work shall be tested at
680 kpa for 24 hours in presence of
the representative of the
Owner/counsultants. All MS & GI
Materials used in pipe work shall be
painted with two coats of prime cote
of approved quality. Product shall be
of NTL/ Bashundhara (Ruby)
Bangladesh. 80mm dia, 3.25mm thick
4.1.c Sanitary N/A WATER SUPPLY PIPE : GI PIPE : Rm 20
Supply, fittings, fixing and laying of GI
Pipe. Pipe work of Standard
thickness as specified in group-ka or
approved equivalent shall be
complete with bends, tees, elbows,
socket, union, reducers, hanger,
bracket, clamp etc. complete.
Approved type of sealant shall be
used on thread to make it leak proof.
All the pipe work shall be tested at
680 kpa for 24 hours in presence of
the representative of the
Owner/counsultants. All MS & GI
Materials used in pipe work shall be
painted with two coats of prime cote
of approved quality. Product shall be
of NTL/ Bashundhara (Ruby)
Bangladesh. 65mm dia, 3.25mm thick
4.1.d Sanitary N/A WATER SUPPLY PIPE : GI PIPE : Rm 310
Supply, fittings, fixing and laying of GI
Pipe. Pipe work of Standard
thickness as specified in group-ka or
approved equivalent shall be
complete with bends, tees, elbows,
socket, union, reducers, hanger,
bracket, clamp etc. complete.
Approved type of sealant shall be
used on thread to make it leak proof.
All the pipe work shall be tested at
680 kpa for 24 hours in presence of
the representative of the
Owner/counsultants. All MS & GI
Materials used in pipe work shall be
painted with two coats of prime cote
of approved quality. Product shall be
of NTL/ Bashundhara (Ruby)
Bangladesh. 50mm dia, 2.90mm thick
4.1.e Sanitary N/A WATER SUPPLY PIPE : GI PIPE : Rm 330
Supply, fittings, fixing and laying of GI
Pipe. Pipe work of Standard
thickness as specified in group-ka or
approved equivalent shall be
complete with bends, tees, elbows,
socket, union, reducers, hanger,
bracket, clamp etc. complete.
Approved type of sealant shall be
used on thread to make it leak proof.
All the pipe work shall be tested at
680 kpa for 24 hours in presence of
the representative of the
Owner/counsultants. All MS & GI
Materials used in pipe work shall be
painted with two coats of prime cote
of approved quality. Product shall be
of NTL/ Bashundhara (Ruby)
Bangladesh. 40mm dia, 2.90mm thick
4.1.f Sanitary N/A WATER SUPPLY PIPE : GI PIPE : Rm 30
Supply, fittings, fixing and laying of GI
Pipe. Pipe work of Standard
thickness as specified in group-ka or
approved equivalent shall be
complete with bends, tees, elbows,
socket, union, reducers, hanger,
bracket, clamp etc. complete.
Approved type of sealant shall be
used on thread to make it leak proof.
All the pipe work shall be tested at
680 kpa for 24 hours in presence of
the representative of the
Owner/counsultants. All MS & GI
Materials used in pipe work shall be
painted with two coats of prime cote
of approved quality. Product shall be
of NTL/ Bashundhara (Ruby)
Bangladesh. 35mm dia, 2.65mm thick
4.1.g Sanitary N/A WATER SUPPLY PIPE : GI PIPE : Rm 1050
Supply, fittings, fixing and laying of GI
Pipe. Pipe work of Standard
thickness as specified in group-ka or
approved equivalent shall be
complete with bends, tees, elbows,
socket, union, reducers, hanger,
bracket, clamp etc. complete.
Approved type of sealant shall be
used on thread to make it leak proof.
All the pipe work shall be tested at
680 kpa for 24 hours in presence of
the representative of the
Owner/counsultants. All MS & GI
Materials used in pipe work shall be
painted with two coats of prime cote
of approved quality. Product shall be
of NTL/ Bashundhara (Ruby)
Bangladesh. 25mm dia, 2.65mm thick
4.1.h Sanitary N/A WATER SUPPLY PIPE : GI PIPE : Rm 50
Supply, fittings, fixing and laying of GI
Pipe. Pipe work of Standard
thickness as specified in group-ka or
approved equivalent shall be
complete with bends, tees, elbows,
socket, union, reducers, hanger,
bracket, clamp etc. complete.
Approved type of sealant shall be
used on thread to make it leak proof.
All the pipe work shall be tested at
680 kpa for 24 hours in presence of
the representative of the
Owner/counsultants. All MS & GI
Materials used in pipe work shall be
painted with two coats of prime cote
of approved quality. Product shall be
of NTL/ Bashundhara (Ruby)
Bangladesh. 20mm dia, 2.35mm thick
4.1.i Sanitary N/A WATER SUPPLY PIPE : GI PIPE : Rm 1100
Supply, fittings, fixing and laying of GI
Pipe. Pipe work of Standard
thickness as specified in group-ka or
approved equivalent shall be
complete with bends, tees, elbows,
socket, union, reducers, hanger,
bracket, clamp etc. complete.
Approved type of sealant shall be
used on thread to make it leak proof.
All the pipe work shall be tested at
680 kpa for 24 hours in presence of
the representative of the
Owner/counsultants. All MS & GI
Materials used in pipe work shall be
painted with two coats of prime cote
of approved quality. Product shall be
of NTL/ Bashundhara (Ruby)
Bangladesh. 15mm dia, 2.00mm thick
4.2.a Sanitary N/A WATER SUPPLY PIPE : CPVC Rm 120
PIPE : Supply, fittings, fixing and
laying of CPVC Pipe.Pipe work shall
be complete with bends, tees,
elbows, socket, union, reducers,
hanger, bracket, clamp etc. All joints
shall be Hot-melt, 100% Approved
type & sealant shall be used
secondary on thread to make it leak
proof. All the pipe work shall be
tested at 1.6Mpa for 24 hours in
presence of the representative of the
Consultants. All MS & GI Materials
used in pipe work shall be painted
with two coats of prime coat of
approved quality by the
Engineer/Consultants.The product
shall be Ajay /Astral at India or NPL/
RFL Equivalent. 100mm dia, 7.65mm
thick
4.2.b Sanitary N/A WATER SUPPLY PIPE : CPVC Rm 201
PIPE : Supply, fittings, fixing and
laying of CPVC Pipe.Pipe work shall
be complete with bends, tees,
elbows, socket, union, reducers,
hanger, bracket, clamp etc. All joints
shall be Hot-melt, 100% Approved
type & sealant shall be used
secondary on thread to make it leak
proof. All the pipe work shall be
tested at 1.6Mpa for 24 hours in
presence of the representative of the
Consultants. All MS & GI Materials
used in pipe work shall be painted
with two coats of prime coat of
approved quality by the
Engineer/Consultants.The product
shall be Ajay /Astral at India or NPL/
RFL Equivalent. 80mm dia, 6.85mm
thick
4.2.c Sanitary N/A WATER SUPPLY PIPE : CPVC Rm 120
PIPE : Supply, fittings, fixing and
laying of CPVC Pipe.Pipe work shall
be complete with bends, tees,
elbows, socket, union, reducers,
hanger, bracket, clamp etc. All joints
shall be Hot-melt, 100% Approved
type & sealant shall be used
secondary on thread to make it leak
proof. All the pipe work shall be
tested at 1.6Mpa for 24 hours in
presence of the representative of the
Consultants. All MS & GI Materials
used in pipe work shall be painted
with two coats of prime coat of
approved quality by the
Engineer/Consultants.The product
shall be Ajay /Astral at India or NPL/
RFL Equivalent. 65mm dia, 6.5mm
thick
4.2.d Sanitary N/A WATER SUPPLY PIPE : CPVC Rm 610
PIPE : Supply, fittings, fixing and
laying of CPVC Pipe.Pipe work shall
be complete with bends, tees,
elbows, socket, union, reducers,
hanger, bracket, clamp etc. All joints
shall be Hot-melt, 100% Approved
type & sealant shall be used
secondary on thread to make it leak
proof. All the pipe work shall be
tested at 1.6Mpa for 24 hours in
presence of the representative of the
Consultants. All MS & GI Materials
used in pipe work shall be painted
with two coats of prime coat of
approved quality by the
Engineer/Consultants.The product
shall be Ajay /Astral at India or NPL/
RFL Equivalent. 50mm dia, 5.60mm
thick
4.2.e Sanitary N/A WATER SUPPLY PIPE : CPVC Rm 1950
PIPE : Supply, fittings, fixing and
laying of CPVC Pipe.Pipe work shall
be complete with bends, tees,
elbows, socket, union, reducers,
hanger, bracket, clamp etc. All joints
shall be Hot-melt, 100% Approved
type & sealant shall be used
secondary on thread to make it leak
proof. All the pipe work shall be
tested at 1.6Mpa for 24 hours in
presence of the representative of the
Consultants. All MS & GI Materials
used in pipe work shall be painted
with two coats of prime coat of
approved quality by the
Engineer/Consultants.The product
shall be Ajay /Astral at India or NPL/
RFL Equivalent. 40mm dia, 4.50mm
thick
4.2.f Sanitary N/A WATER SUPPLY PIPE : CPVC Rm 300
PIPE : Supply, fittings, fixing and
laying of CPVC Pipe.Pipe work shall
be complete with bends, tees,
elbows, socket, union, reducers,
hanger, bracket, clamp etc. All joints
shall be Hot-melt, 100% Approved
type & sealant shall be used
secondary on thread to make it leak
proof. All the pipe work shall be
tested at 1.6Mpa for 24 hours in
presence of the representative of the
Consultants. All MS & GI Materials
used in pipe work shall be painted
with two coats of prime coat of
approved quality by the
Engineer/Consultants.The product
shall be Ajay /Astral at India or NPL/
RFL Equivalent. 32mm dia, 3.90mm
thick
4.2.g Sanitary N/A WATER SUPPLY PIPE : CPVC Rm 2850
PIPE : Supply, fittings, fixing and
laying of CPVC Pipe.Pipe work shall
be complete with bends, tees,
elbows, socket, union, reducers,
hanger, bracket, clamp etc. All joints
shall be Hot-melt, 100% Approved
type & sealant shall be used
secondary on thread to make it leak
proof. All the pipe work shall be
tested at 1.6Mpa for 24 hours in
presence of the representative of the
Consultants. All MS & GI Materials
used in pipe work shall be painted
with two coats of prime coat of
approved quality by the
Engineer/Consultants.The product
shall be Ajay /Astral at India or NPL/
RFL Equivalent. 25mm dia, 3.85mm
thick
4.2.h Sanitary N/A WATER SUPPLY PIPE : CPVC Rm 950
PIPE : Supply, fittings, fixing and
laying of CPVC Pipe.Pipe work shall
be complete with bends, tees,
elbows, socket, union, reducers,
hanger, bracket, clamp etc. All joints
shall be Hot-melt, 100% Approved
type & sealant shall be used
secondary on thread to make it leak
proof. All the pipe work shall be
tested at 1.6Mpa for 24 hours in
presence of the representative of the
Consultants. All MS & GI Materials
used in pipe work shall be painted
with two coats of prime coat of
approved quality by the
Engineer/Consultants.The product
shall be Ajay /Astral at India or NPL/
RFL Equivalent. 20mm dia, 2.30mm
thick
4.2.i Sanitary N/A WATER SUPPLY PIPE : CPVC Rm 5950
PIPE : Supply, fittings, fixing and
laying of CPVC Pipe.Pipe work shall
be complete with bends, tees,
elbows, socket, union, reducers,
hanger, bracket, clamp etc. All joints
shall be Hot-melt, 100% Approved
type & sealant shall be used
secondary on thread to make it leak
proof. All the pipe work shall be
tested at 1.6Mpa for 24 hours in
presence of the representative of the
Consultants. All MS & GI Materials
used in pipe work shall be painted
with two coats of prime coat of
approved quality by the
Engineer/Consultants.The product
shall be Ajay /Astral at India or NPL/
RFL Equivalent. 15mm dia, 2.00mm
thick
5.1 Sanitary N/A Supply, Fitting & 'Fixing of Toilet Nos. 422
fittings in Toilets with all hardwares
and consumables (SS Bush, SS
Screw, SS fancy Bush, Nut bolt,
Taflon, Solvent Cement, white
Cement, Gasket etc) required for
complete installation and function of
the fittings.Stop Cock : Supply, fitting
and fixing of CP oval type Stop Cock
of dia 13 mm with brass rising stem
screwed bonnet, solid wedge and
screwed end type. Stop cock shall be
suitable to withstand a pressure of
344 kPa. and shall be installed at
location shown in the drawing and as
per direction of the Engineer-in-
charge/Consultant. Product shall be
Model No. HDA0609MR2 HUIDA/
DOFINY, China or Equivalent Nazma
or Sharif from Bangladesh.
5.2 Sanitary N/A Supply, Fitting & 'Fixing of Toilet Nos. 1690
fittings in Toilets with all hardwares
and consumables (SS Bush, SS
Screw, SS fancy Bush, Nut bolt,
Taflon, Solvent Cement, white
Cement, Gasket etc) required for
complete installation and function of
the fittings.Angle Stop Cock :Supply,
fitting and fixing of CP oval type
Angle Stop Cock of dia 12 mm with
brass rising stem screwed bonnet,
solid wedge and screwed end type.
Angle Stop cock shall be suitable to
withstand a pressure of 344 kPa. and
shall be installed at location shown in
the drawing and as per direction of
the Engineer-in-
charge/Consultant.Supply, fitting and
fixing of Angle Stop Cock/ Valve,
Product shall be Model No. J855
HUIDA/ DOFINY, China or
Equivalent Nazma or Sharif from
Bangladesh.
5.3 Sanitary N/A Supply, Fitting & 'Fixing of Toilet Nos. 320
fittings in Toilets with all hardwares
and consumables (SS Bush, SS
Screw, SS fancy Bush, Nut bolt,
Taflon, Solvent Cement, white
Cement, Gasket etc) required for
complete installation and function of
the fittings.WC Shower Rose (Push
Shower): Supply, fitting and fixing of
Wc Shower Rose(with angle stop
cock) complete in all respect as per
drawing and direction of the
Engineer/Consultant. Product shall be
Model No. SP74021 HUIDA/
DOFINY, China or Equivalent Nazma
or Sharif from Bangladesh.
5.4 Sanitary N/A Supply, Fitting & 'Fixing of Toilet Nos. 210
fittings in Toilets with all hardwares
and consumables (SS Bush, SS
Screw, SS fancy Bush, Nut bolt,
Taflon, Solvent Cement, white
Cement, Gasket etc) required for
complete installation and function of
the fittings. Two in One Bib Cock :
Supply, Fitting and fixing of Two in
one bib Cock shall be constructed
with bronze and shall have rising stem
screwed bonnet, disc. and screwed
end type. Valve shall be installed at
location shown in the drawing and as
per direction of Consultant. Threaded
joint shall be made properly sealed.
Product shall be Model No.
HDA5270B HUIDA/ DOFINY, China
or Equivalent Nazma or Sharif from
Bangladesh.
5.5 Sanitary N/A Supply, Fitting & 'Fixing of Toilet Nos. 560
fittings in Toilets with all hardwares
and consumables (SS Bush, SS
Screw, SS fancy Bush, Nut bolt,
Taflon, Solvent Cement, white
Cement, Gasket etc) required for
complete installation and function of
the fittings.Open Tap/Bib Cock
:Supply, fitting and fixing of 12 mm
dia CP Open Tap complete in all
respect as per drawing and direction
of the Engineer/Consultant. Product
shall be Model No. HDA0604B
HUIDA/ DOFINY, China or
Equivalent Nazma or Sharif from
Bangladesh.
5.6 Sanitary N/A Supply, Fitting & 'Fixing of Toilet Nos. 150
fittings in Toilets with all hardwares
and consumables (SS Bush, SS
Screw, SS fancy Bush, Nut bolt,
Taflon, Solvent Cement, white
Cement, Gasket etc) required for
complete installation and function of
the fittings.Basin Pillar Cock :Supply,
fitting and fixing of 12 mm dia CP
Medal Headed Heavy deluxe body
Basin Pillar Cock shall be constructed
with brass rising stem screwed
bonnet, solid wedge and screwed
end type and shall be suitable to
withstand a pressure of 344 kPa. Pill
cock shall be installed at location
shown in the drawing and as per
direction of the Engineer-in-
charge/Consultant.Supply, fitting and
fixing of Basin Pillar Cock. Product
shall be Model No. HDA0608M
HUIDA/ DOFINY, China or
Equivalent Nazma or Sharif from
Bangladesh.
5.7 Sanitary N/A Supply, Fitting & 'Fixing of Toilet Nos. 361
fittings in Toilets with all hardwares
and consumables (SS Bush, SS
Screw, SS fancy Bush, Nut bolt,
Taflon, Solvent Cement, white
Cement, Gasket etc) required for
complete installation and function of
the fittings.Basin Mixture :Supply,
fitting fixing of 13 mm dia CP Basin
Mixture complete in all respect as per
drawing and direction of the
Engineer/Consultant. Basin Mixture,
Faucet with popup waste, Product
shall be Model No. HDA1811M
HUIDA/ DOFINY, China or
Equivalent Nazma or Sharif from
Bangladesh.
5.8 Sanitary N/A Supply, Fitting & 'Fixing of Toilet Nos. 126
fittings in Toilets with all hardwares
and consumables (SS Bush, SS
Screw, SS fancy Bush, Nut bolt,
Taflon, Solvent Cement, white
Cement, Gasket etc) required for
complete installation and function of
the fittings.Kitchen Mixture Cock
:Supply, fitting and fixing of 12 mm
dia CP Sink Mixture shall be
constructed with brass rising stem
(Nozzle type), solid wedge and
screwed end type. Valves shall be
capable to withstand a pressure of
344 kPa. Sink cock shall be installed
at location shown in the drawing and
as per direction of the Engineer-in-
charge/Consultant. Product shall be
Model No. HDA1304XH HUIDA/
DOFINY, China or Equivalent Nazma
or Sharif from Bangladesh.
5.9 Sanitary N/A Supply, Fitting & 'Fixing of Toilet Nos. 570
fittings in Toilets with all hardwares
and consumables (SS Bush, SS
Screw, SS fancy Bush, Nut bolt,
Taflon, Solvent Cement, white
Cement, Gasket etc) required for
complete installation and function of
the fittings.Bottle Trap :Supply, fitting
and fixing of Bottle Trap complete in
all respect as per drawing and
direction of the Engineer/Consultant.
Product shall be Model No. GD1002
HUIDA/ DOFINY, China or
Equivalent Nazma or Sharif from
Bangladesh.
6.1.a Sanitary N/A Supply, fitting and fixing of Toilet Nos. 390
fixtures of approved colour with all
hardwares and consumables required
for complete installation and function
of the fixtures.Washing Hand
BasinSupply, fitting and fixing of
Special coloured washing hand basin
with Angale stop cock, piller cock,
SS Connection pipe, CI wall
Brackets, SS Screw, SS Bush,
Solvent cement, thread tap, white
cement, Gasket etc. including making
holes and fitting in walls and mending
good the damages etc. complete in
all respect as per drawing and
direction of the Engineer/Consultant.
Wash Basin with Pedestal, Model no.
WB 30002, DOFINY/ HUIDA China
or Equivalent RAK /BISF from
Bangladesh.
6.1.b Sanitary N/A Supply, fitting and fixing of Toilet Nos. 120
fixtures of approved colour with all
hardwares and consumables required
for complete installation and function
of the fixtures.Washing Hand
BasinSupply, fitting and fixing of
Special coloured washing hand basin
with Angale stop cock, piller cock,
SS Connection pipe, CI wall
Brackets, SS Screw, SS Bush,
Solvent cement, thread tap, white
cement, Gasket etc. including making
holes and fitting in walls and mending
good the damages etc. complete in
all respect as per drawing and
direction of the Engineer/Consultant.
Counter Top Wash Basin, Model no.
WB 34003, DOFINY/ HUIDA China
or Equivalent RAK /BISF from
Bangladesh.
6.2 Sanitary N/A Supply, fitting and fixing of Toilet Nos. 126
fixtures of approved colour with all
hardwares and consumables required
for complete installation and function
of the fixtures.Kitchen Sink (Single
Bowl Single Tray)Supply, Fitting and
fixing of Super quality Stainless Steel
Kitchen Sink in position with heavy
type CI wall brackets, SS Screw,
Solvent cement, thread tap, white
cement, Gasket including making
holes in walls and fitting with CI wall
brackets and mending good the
damages etc. complete as per
direction of the Consultant. Kitchen
Sink (Single Bowl Single Tray) (
Model No. HDSC8706E of DOFINY/
HUIDA China or Equivalent Thailand.
6.3 Sanitary N/A Supply, fitting and fixing of Toilet Nos. 1310
fixtures of approved colour with all
hardwares and consumables required
for complete installation and function
of the fixtures.Steel Flexible
ConnectionSupply, fitting and fixing of
Steel connecting pipe of 12 mm dia
and 600 mm length with SS flare nut,
SS Bush, SS Fancy Bussh PVC
taflon and Socket on both end to
adapt 13 mm dia threaded G.I. Pipe
etc. complete in all respect as per
drawing and direction of the
Engineer/Consultant.Product shall be
of Model no. P23600SN, of
DOFINY/ HUIDA China or
Equivalent Nazma or Sharif from
Bangladesh
6.4.a Sanitary N/A Supply, fitting and fixing of Toilet Nos. 200
fixtures of approved colour with all
hardwares and consumables required
for complete installation and function
of the fixtures.Combi Closet
:Supplying, fitting and fixing Euroepan
type glazed Combi Closet,
700x410x795 mm size, approx. 34.5
kg weight, plastic seat cover and
preparing the base with cement
concrete and with wire mesh or rods
if necessary, in all floors including
making holes wherever required and
mending good the damages and
fitting, fixing, finishing complete with
all necessary fittings and connection
approved and accepted by the
Engineer.Combi Closet White (with
Low Down) Product shall be of
Model TL 10015A of DOFINY/
HUIDA China, China or Equivalent
RAK /BISF in Bangladesh.
6.4.b Sanitary N/A Supply, fitting and fixing of Toilet Nos. 120
fixtures of approved colour with all
hardwares and consumables required
for complete installation and function
of the fixtures.Combi Closet
:Supplying, fitting and fixing Euroepan
type glazed Combi Closet,
700x410x795 mm size, approx. 34.5
kg weight, plastic seat cover and
preparing the base with cement
concrete and with wire mesh or rods
if necessary, in all floors including
making holes wherever required and
mending good the damages and
fitting, fixing, finishing complete with
all necessary fittings and connection
approved and accepted by the
Engineer.Combi Closet White (with
Low down) Product shall be of Model
TL 10201C of DOFINY/ HUIDA
China or Equivalent RAK /BISF in
Bangladesh.
6.5 Sanitary N/A Supply, fitting and fixing of Toilet Nos. 121
fixtures of approved colour with all
hardwares and consumables required
for complete installation and function
of the fixtures.Long PanSupplying,
fitting and fixing Bangladesh patern,
570x445x290 mm long pan with foot-
rest inlclucing plastic low-down,
approx. 12kg by weight, made of
Vitreous China and preparing the
base of pan with cement mortar (1:4)
and with wire mesh or rods, if
necessary, in all floors including
making holes wherever required and
mending good the damages and
fitting, fixing, finishing etc. complete
with all necessary fittings and
connection approved and accepted
by the Engineer.Long pan White (with
Low down) Product shall be of Model
SP50031+CT40003 of DOFINY/
HUIDA China or Equivalent RAK
/BISF in Bangladesh.
6.6 Sanitary N/A Supply, fitting and fixing of Toilet Set 1
fixtures of approved colour with all
hardwares and consumables required
for complete installation and function
of the fixtures.UrinalSupply, fitting and
fixing of Integrated SenSor Standing
Urinal with heavy duty waste pipe
wherever required CI wall brackets,
SS Screw, Solvent cement, thread
tap, white cement, gasket including
making holes in wall and fitting
mending good the damages etc.
complete in all respect as per
drawing and direction of the
Engineer/Consultant. Product shall be
of DOFINY/ HUIDA China or
Equivalent RAK /BISF in
Bangladesh.
6.7.a Sanitary N/A Supply, fitting and fixing of Toilet Set 361
fixtures of approved colour with all
hardwares and consumables required
for complete installation and function
of the fixtures.Shower Assembly
Supply, Fitting and fixing of C.P.
Shower head complete with all
standard accessories and fittings.
Shower assembly shall be fitted to
pipe end by using approved sealing
compound to make the joint water
tight as per drawing and direction of
the Engineer/Consultant.Supply,
fitting and fixing of Concealed
Shower Mixture with Spout and
Shower Head, Model HD1814YR2,
of DOFINY/ HUIDA, China or
Equivalent Nazma or Sharif from
Bangladesh.
6.7.b Sanitary N/A Supply, fitting and fixing of Toilet Set 180
fixtures of approved colour with all
hardwares and consumables required
for complete installation and function
of the fixtures.Shower Assembly
Supply, Fitting and fixing of C.P.
Shower head complete with all
standard accessories and fittings.
Shower assembly shall be fitted to
pipe end by using approved sealing
compound to make the joint water
tight as per drawing and direction of
the Engineer/Consultant.Supply,
fitting and fixing of Fixed Shower
Head Product shall be of Model
HDDP2075 of DOFINY/ HUIDA,
China or Equivalent Nazma or Sharif
from Bangladesh.
6.8 Sanitary N/A Supply, fitting and fixing of Toilet Nos. 510
fixtures of approved colour with all
hardwares and consumables required
for complete installation and function
of the fixtures.Glass MirrorSupply,
Fitting and fixing of Beveled edge
plate glass mirror (Oval Glass Mirror)
fitted in wall with screws including
plastic plug, damp protection on back
etc. and shall be completed as per
direction of the Consultant.Product
shall be (Local Made of Size (500 X
900mm)
6.9 Sanitary N/A Supply, fitting and fixing of Toilet Nos. 510
fixtures of approved colour with all
hardwares and consumables required
for complete installation and function
of the fixtures.Glass Shelf Supply,
Fitting and fixing of super quality
600x125 mm coloured glass (plate)
shelf having 5mm thickness with
fancy C.P. brackets, screws and
frames including making holes in walls
and mending good the damages with
cement mortar (1:4) etc. all complete
as per direction of the Consultant.
Product shall be Glass Shel, Model
HDC 1802 of DOFINY, China, or
Equivalent .
6.10.a Sanitary N/A Supply, fitting and fixing of Toilet Nos. 430
fixtures of approved colour with all
hardwares and consumables required
for complete installation and function
of the fixtures.Towel Bar / Towel Ring
/ Towel Shelf Supply, fitting, fixing of
CP towel bar respectively complete
with CP wall bracket fitted on wall
plastic plug and screws as per
drawing and direction of the
Engineer-in-charge/Consultant.
Supply, fitting, fixing of CP Towel
Bar, Model HDC 1803 of DOFINY,
China or Equivalent Nazma or Sharif
from Bangladesh.
6.10.b Sanitary N/A Supply, fitting and fixing of Toilet Nos. 140
fixtures of approved colour with all
hardwares and consumables required
for complete installation and function
of the fixtures.Towel Bar / Towel Ring
/ Towel Shelf Supply, fitting, fixing of
CP towel bar respectively complete
with CP wall bracket fitted on wall
plastic plug and screws as per
drawing and direction of the
Engineer-in-charge/Consultant.
Supply, fitting, fixing of Towel Ring,
Model No. HDC 1807 of DOFINY,
China or Equivalent Nazma or Sharif
from Bangladesh.
6.11 Sanitary N/A Supply, fitting and fixing of Toilet Nos. 460
fixtures of approved colour with all
hardwares and consumables required
for complete installation and function
of the fixtures.Soap Case Supply,
fitting, fixing of S.S Soap Tray Model
HDC 1009 of DOFINY, China or
Equivalent Nazma or Sharif from
Bangladesh.
6.12 Sanitary N/A Supply, fitting and fixing of Toilet Nos. 440
fixtures of approved colour with all
hardwares and consumables required
for complete installation and function
of the fixtures.Toilet Paper Holder
Supply, fitting, fixing of S.S Toilet
Paper Holder, Model HDC 7008 of
DOFINY, China or Equivalent Nazma
or Sharif from Bangladesh
6.13 Sanitary N/A Supply, fitting and fixing of Toilet Nos. 130
fixtures of approved colour with all
hardwares and consumables required
for complete installation and function
of the fixtures.CP Coat HookSupply,
fitting, fixing of S.S Coat Hook
Complete with S.S bracket. shall be
fixed to the wall by using plastic bolt
and screws and as per direction of
the Engineer-in-charge /Consultant.
Product shall be of Robe Hook,
Model HDC 1810 of DOFINY, China
or Equivalent Nazma or Sharif from
Bangladesh
6.14.a Sanitary N/A Supply, fitting and fixing of Toilet Nos. 642
fixtures of approved colour with all
hardwares and consumables required
for complete installation and function
of the fixtures.SQUARE SHAPED
GRATING FLOOR DRAIN :Supply,
fitting and fixing of SS Square
Gratings shall be four piece type-
frame, perorated cover, strainer and
water seal cover. Grating cove shall
be hinge type. Floor Drain Model
HDFD 8821 of DOFINY,
China100mm dia SS Square Grating
Model HDFD 8821 of DOFINY,
China or Equivalent.
6.14.b Sanitary N/A Supply, fitting and fixing of Toilet Nos. 378
fixtures of approved colour with all
hardwares and consumables required
for complete installation and function
of the fixtures.SQUARE SHAPED
GRATING FLOOR DRAIN :Supply,
fitting and fixing of SS Square
Gratings shall be four piece type-
frame, perorated cover, strainer and
water seal cover. Grating cove shall
be hinge type. Floor Drain Model
HDFD 8821 of DOFINY, China50mm
dia SS Square Grating Model HDFD
8821 of DOFINY, China or
Equivalent.
6.15 Sanitary N/A Supply, fitting and fixing of Toilet Nos. 1
fixtures of approved colour with all
hardwares and consumables required
for complete installation and function
of the fixtures.Safety Accessories for
Disable ToiletSupply, fitting, fixing of
Safety Accessories for Disable Toilet
Handicap Bar Complete with all
goods shall be fixed to the wall by
using plastic bolt and screws and as
per direction of the Engineer-in-
charge /Consultant. Product shall be
of Model No. CT751, CT753, CT754
(3Nos) of COTTO, Thailand or
Equivalent.
6.16 Sanitary N/A Supply, fitting and fixing of Toilet Nos. 4
fixtures of approved colour with all
hardwares and consumables required
for complete installation and function
of the fixtures.Automatic Soap
DispenserSupply, fitting, fixing of
Soap dispenser complete with all
goods shall be fixed to the wall by
using plastic bolt and screws and as
per direction of the Engineer-in-
charge /Consultant. Product shall be
of Model No. HDC6014 of DOFINY,
China or Equivalent.
6.17 Sanitary N/A Supply, fitting and fixing of Toilet Nos. 4
fixtures of approved colour with all
hardwares and consumables required
for complete installation and function
of the fixtures. Automatic Hand Dryer
Supply, fitting, fixing of Automatic
Hand Dryer, Complete with all goods
shall be fixed to the wall by using
plastic bolt and screws and as per
direction of the Engineer-in-charge
/Consultant. Product shall be of
Model No. Model- HD 342 AC of
DOFINY, China or Equivalent.
7.a Sanitary N/A Automatic Water Heater : Supply, Nos. 1
Instalation of Electric or Gas fired
water heater be made of stainless
steel sheet inside container with
seamless welding pressure tested to
leaks. Outside jackets shall be
sprayed with scratch and rust proof
high gloss backed enamel paint. The
heater shall be complete with
adjustable Thermostat (30°C to
80°C) and automatic pressure
release valve and all other required
accessories. The Water Heater shall
be of 'IEGA brand, Bangladesh 5
Gallon (Horizontal type)
7.b Sanitary N/A Automatic Water Heater : Supply, Nos. 1
Instalation of Electric or Gas fired
water heater be made of stainless
steel sheet inside container with
seamless welding pressure tested to
leaks. Outside jackets shall be
sprayed with scratch and rust proof
high gloss backed enamel paint. The
heater shall be complete with
adjustable Thermostat (30°C to
80°C) and automatic pressure
release valve and all other required
accessories. The Water Heater shall
be of 'IEGA brand, Bangladesh 10
Gallon (Horizontal type)
8 Sanitary N/A CATCH PIT : Construction of Nos. 16
masonry Catch pits, inside
measurement (450 mm x 450 mm x
600 mm) with 250 mm thick brick
work in cement mortar (4:1) 100 mm
thick R.C.C. top (4:2:1) with the
necessary reinforcement.450mm x
450mm x 600mm
9.a Sanitary N/A INSPECTION PIT: Construction of Nos. 60
masonry Inspection pits, inside
measurement (600 mm x 600 mm x
550 mm) with 250 mm thick brick
work in cement mortar (4:1) 100 mm
thick R.C.C. top (4:2:1) with the
necessary reinforcement.
9.b Sanitary N/A INSPECTION PIT: Construction of Nos. 12
masonry Inspection pits, inside
measurement (760 mm x 760 mm x
760 mm) with 250 mm thick brick
work in cement mortar (4:1) 100 mm
thick R.C.C. top (4:2:1) with the
necessary reinforcement.
9.c Sanitary N/A INSPECTION PIT: Construction of Nos. 4
masonry Inspection pits, inside
measurement (900 mm x 900 mm x
900 mm) with 250 mm thick brick
work in cement mortar (4:1) 100 mm
thick R.C.C. top (4:2:1) with the
necessary reinforcement.
10 Sanitary N/A C.I. COVER: Supply and installation Nos. 76
of heavy duty C.I. manhole covers of
550mm/600mm Clear opening with
frames (Havy type Minimum weight
of Cover to be 22kg to 28Kg) lock
type in top slab of inspection pits all
complete as per drawing and
direction of the Consultant. Product
shall be Manco / equivalent Brand.
11 Sanitary N/A WATER DISTRIBUTION PUMP Set 4
Supply, Installation, Testing and
Commissioning of single stage water
supply distribution system having a
capacity to handle 290 Gpm of water
against a head of 80 meter of wg.
The pump shall be complete with
coupled motor, coupling, motor guard
etc. Pump shall not be less than 60%
efficient. Pump motor shall be
capable to handle 30% to 120% of
rated flow. Supply shall be 400V/3
phase/50Hz. Pump shall be of USA/
UK/ JAPAN/ Germany/ Australia/
korea origin.
12 Sanitary N/A SUMP PUMP Supply, installation, Set 6
testing and commissioning of single
stage sump pump having a capacity
to handle 25 Gpm of water against a
head of 15 meter of wg. The pump
shall be complete with coupled motor,
coupling, motor guard etc. Pump shall
not be less than 60% efficient. Pump
motor shall be capable to handle 30%
to 120% of rated flow. Supply shall
be 400V/3 phase/50Hz. Pump shall
be of USA/ UK/ JAPAN/ Germany/
Australia/ korea origin.
13.1.a Sanitary N/A GATE VALVE Supply, fitting and Nos. 6
fixing of Gate valve of 40mm dia shall
be bronze body and valve of 150mm
dia shall be iron body to withstand a
water pressure of 200 PSIG. Valves
shall be installed at location as shown
on the drawing complete with
consumable, materials etc. Valves
shall be of USA/UK/Japan origin.
100mm dia
13.1.b Sanitary N/A GATE VALVE Supply, fitting and Nos. 8
fixing of Gate valve of 40mm dia shall
be bronze body and valve of 150mm
dia shall be iron body to withstand a
water pressure of 200 PSIG. Valves
shall be installed at location as shown
on the drawing complete with
consumable, materials etc. Valves
shall be of USA/UK/Japan origin.
80mm dia
13.1.c Sanitary N/A GATE VALVE Supply, fitting and Nos. 12
fixing of Gate valve of 40mm dia shall
be bronze body and valve of 150mm
dia shall be iron body to withstand a
water pressure of 200 PSIG. Valves
shall be installed at location as shown
on the drawing complete with
consumable, materials etc. Valves
shall be of USA/UK/Japan origin.
65mm dia
13.1.d Sanitary N/A GATE VALVE Supply, fitting and Nos. 60
fixing of Gate valve of 40mm dia shall
be bronze body and valve of 150mm
dia shall be iron body to withstand a
water pressure of 200 PSIG. Valves
shall be installed at location as shown
on the drawing complete with
consumable, materials etc. Valves
shall be of USA/UK/Japan origin.
50mm dia
13.1.e Sanitary N/A GATE VALVE Supply, fitting and Nos. 180
fixing of Gate valve of 40mm dia shall
be bronze body and valve of 150mm
dia shall be iron body to withstand a
water pressure of 200 PSIG. Valves
shall be installed at location as shown
on the drawing complete with
consumable, materials etc. Valves
shall be of USA/UK/Japan
origin.40mm dia
13.1.f Sanitary N/A GATE VALVE Supply, fitting and Nos. 6
fixing of Gate valve of 40mm dia shall
be bronze body and valve of 150mm
dia shall be iron body to withstand a
water pressure of 200 PSIG. Valves
shall be installed at location as shown
on the drawing complete with
consumable, materials etc. Valves
shall be of USA/UK/Japan origin.
32mm dia
13.1.g Sanitary N/A GATE VALVE Supply, fitting and Nos. 290
fixing of Gate valve of 40mm dia shall
be bronze body and valve of 150mm
dia shall be iron body to withstand a
water pressure of 200 PSIG. Valves
shall be installed at location as shown
on the drawing complete with
consumable, materials etc. Valves
shall be of USA/UK/Japan origin.
25mm dia
13.1.h Sanitary N/A GATE VALVE Supply, fitting and Nos. 160
fixing of Gate valve of 40mm dia shall
be bronze body and valve of 150mm
dia shall be iron body to withstand a
water pressure of 200 PSIG. Valves
shall be installed at location as shown
on the drawing complete with
consumable, materials etc. Valves
shall be of USA/UK/Japan origin.
20mm dia
13.1.i Sanitary N/A GATE VALVE Supply, fitting and Nos. 20
fixing of Gate valve of 40mm dia shall
be bronze body and valve of 150mm
dia shall be iron body to withstand a
water pressure of 200 PSIG. Valves
shall be installed at location as shown
on the drawing complete with
consumable, materials etc. Valves
shall be of USA/UK/Japan origin.
15mm dia Ball Valve
13.1.j Sanitary N/A GATE VALVE Supply, fitting and No 6
fixing of Gate valve of 40mm dia shall
be bronze body and valve of 150mm
dia shall be iron body to withstand a
water pressure of 200 PSIG. Valves
shall be installed at location as shown
on the drawing complete with
consumable, materials etc. Valves
shall be of USA/UK/Japan origin.
20mm dia air relief valve
13.2.a Sanitary N/A GLOBE VALVE : Supply, fitting and Nos. 6
fixing of Globe valve of 40mm dia
shall be bronze body and 150mm dia
shall be iron body to withstand a
water pressure of 200 PSIG, valve
shall be installed at location as shown
on the drawing complete with
consumable, accessories etc.Valves
shall be of USA/UK/Japan origin.100
mm dia
13.2.b Sanitary N/A GLOBE VALVE : Supply, fitting and Nos. 12
fixing of Globe valve of 40mm dia
shall be bronze body and 150mm dia
shall be iron body to withstand a
water pressure of 200 PSIG, valve
shall be installed at location as shown
on the drawing complete with
consumable, accessories etc.Valves
shall be of USA/UK/Japan origin.50
mm dia
13.2.c Sanitary N/A GLOBE VALVE : Supply, fitting and Nos. 50
fixing of Globe valve of 40mm dia
shall be bronze body and 150mm dia
shall be iron body to withstand a
water pressure of 200 PSIG, valve
shall be installed at location as shown
on the drawing complete with
consumable, accessories etc.Valves
shall be of USA/UK/Japan origin.40
mm dia
13.3 Sanitary N/A STRAINER : Supply, fitting and fixing Nos. 4
of Strainer shall be cast iron body
flanged end type assembly complete
with internal stainless steel net,
companion flange, nut bolt, gasket, all
consumable and materials.Strainer
shall be of USA/UK/Japan origin.
100mm dia
13.4 Sanitary N/A CHECK VALVE : Supply, fitting and Nos. 4
fixing of Check valve of iron body
shall flanged end lift check type
complete companion flange, nut bolt,
gasket, all consumable and
materials.Valves shall be of
USA/UK/Japan origin.100mm dia
13.5 Sanitary N/A FOOT VALVE : Supply, fitting and Nos. 4
fixing of Foot valve shall be flanged
end/screwed end type with non-return
valve & strainer. Valves shall be of
USA/UK/Japan origin. 100mm dia
13.6 Sanitary N/A FLEXIBLE JOINT : Supply, fitting Nos. 8
and fixing of Flexible joints shall be of
moulded neoprene shall be capable
and suitable to absorb shock and
system hammering at the line water
pressure of 200 psig complete with
flanged end, companion flanges,
adjustable screw etc. flexible joint
shall be installed at suction and
discharge side of pump or as shown
on the & shall be tested upto
satisfaction of the Consultant.
Flexible Joint shall be of
USA/UK/Japan origin. 100mm dia
13.7 Sanitary N/A FLOAT ASSEMBLY : Supply, fitting Nos. 2
and fixing of float assembly suitable
to install on 65 mm dia supply pipe.
Float assembly shall be complete
with float valve, float etc.
complete.Float Assembly shall be of
USA/UK/Japan 100mm dia
13.8.a Sanitary N/A PRESSURE REDUCING VALVE : Nos. 10
Supply, fitting and fixing of pressure
reducing valve on size 50 mm dia.
Pressure reducing valve shall be
suitable to deliver water at a pressure
of 7.5 psig (minimum) irrespective of
inlet pressure. (Inlet pressure shall be
80 to 60 psig) PRV Valves shall be of
USA/UK/Japan origin.50mm dia
13.8.b Sanitary N/A PRESSURE REDUCING VALVE : Nos. 40
Supply, fitting and fixing of pressure
reducing valve on size 50 mm dia.
Pressure reducing valve shall be
suitable to deliver water at a pressure
of 7.5 psig (minimum) irrespective of
inlet pressure. (Inlet pressure shall be
80 to 60 psig) PRV Valves shall be of
USA/UK/Japan origin. 40mm dia
13.9 Sanitary N/A PRESSURE GAUGESupply, fitting No. 4
and fixing of Pressure gauge shall be
100mm dial type complete with
adapter, pet cock, pressure snowbar
etc.
14.a Sanitary N/A PUMP PANEL Supply, fitting, fixing Nos. 2
of totally insulated (IP65) pump panel
complete with MCCB for pump,
ON/OFF push button, bus bar, run-
stop lamp, dry operation protection,
phase monitoring rules all complete.
Power panel shall house all incoming
and outgoing MCCB, MCB, bus-bar,
insulator, internal wiring etc.
complete. Panel shall be painted with
two coats of epoxy paint of approved
red colour over a coat of primer. All
electrical components shall be from
Siemens/Moellir. Water Supply Pump
Panel
14.b Sanitary N/A PUMP PANEL Supply, fitting, fixing Nos. 4
of totally insulated (IP65) pump panel
complete with MCCB for pump,
ON/OFF push button, bus bar, run-
stop lamp, dry operation protection,
phase monitoring rules all complete.
Power panel shall house all incoming
and outgoing MCCB, MCB, bus-bar,
insulator, internal wiring etc.
complete. Panel shall be painted with
two coats of epoxy paint of approved
red colour over a coat of primer. All
electrical components shall be from
Siemens/Moellir. Sump Pump Panel
15 Sanitary N/A WATER LEVEL CONTROLLER Set 8
Supply, installation, testing and
commissioning of water level
controller suitable to operate the
pumps on demand of water in over
head tank. Level controller will also
resist dry operation of the pump
when there is no water in under
ground water reservoir. water level
control electric cabel standard quality
supplied.
16 Sanitary N/A ELECTRICAL CABLE WORKS Job 2
Electrical works shall be complete
with supply and installation of all
cables, conduit, distribution board
etc. as per direction and drawing by
the consultant. Product shall be of
BBS or BRB Cable from Bangladesh
17 Sanitary N/A SEPTIC TANK 200 Users Septic Nos. 2
Tank
18 Sanitary N/A SOAK WELL Construction of Soak Nos. 2
Well of different sizes with 250mm
thick solid brick work and 250mm
honey comb brick work with cement
mortar (1:6) as per design and
drawings over RCC (1:2:4) well curb
with 1.5% reinforcement including
supplying and fixing 600mm dia water
sealed heavy type C.I. manhole cover
with locking arrangement filling the
well upto the required depth with
graded khoa and sand including
supplying and fabricating MS Rod
casting curing including necessary
earth work in excavation, side filling
and bailing out water including cost of
all materials etc. all complete as per
drawing, design and direction of the
Engineer/Consultant. 200 Users Soak
Well
19 Sanitary N/A "WASA CONNECTION Job 2
Arrangement of Wasa Connection
from the WASA Header to Building
Premises complete with Water Meter
with Inspection Pit or surface drain
for rain water line and all other
required accessories as per drawings
and direction of the Client/Consultant
and as per approval of the Wasa
Authority. All required formalities to
WASA shall be done by the
Contractor.
"
20 Sanitary N/A "TESTING & COMMISSIONING Job 2
After complete installation the system
shall be tested and commissioned as
per recommendation of the
manufacturer and standard. Piping
system shall be tested with pressure
in presence of the Client/Consultant.
All testing of electrical system shall
be done as per direction. Test
certification shall be taken from the
Engineer.
"
1.a Electrifical N/A "Concealed conduit wiring for EACH 599
following point looping at the switch
board with earth terminal including
circuit wiring with IC-2x1.5 sq.mm
PVC insulated and sheathed
stranded cable (BYM) & 1.5 sq.mm
PVC insulated green/white coloured
ECC wire (BYA) through PVC
conduit (Lira brand or equivalent
product of other reputed
manufacturer) of minimum 25 mm dia
& 1.5 mm wall thickness complete
with 18 SWG GP sheet, pull box with
3mm thick ebonite sheet cover, ceiling
rose, fixing materials etc.(without
switch & switchboard) as required
including mending the damages good
(all electrical contacts shall be of
brass/copper)
Cables manufactured by
Citizen/SQ/Paradise or equivalent
approved by the Engineer-in-Charge.
CL- CEILING LIGHT Point"
1.b Electrifical N/A "Concealed conduit wiring for EACH 1570
following point looping at the switch
board with earth terminal including
circuit wiring with IC-2x1.5 sq.mm
PVC insulated and sheathed
stranded cable (BYM) & 1.5 sq.mm
PVC insulated green/white coloured
ECC wire (BYA) through PVC
conduit (Lira brand or equivalent
product of other reputed
manufacturer) of minimum 25 mm dia
& 1.5 mm wall thickness complete
with 18 SWG GP sheet, pull box with
3mm thick ebonite sheet cover, ceiling
rose, fixing materials etc.(without
switch & switchboard) as required
including mending the damages good
(all electrical contacts shall be of
brass/copper)
Cables manufactured by
Citizen/SQ/Paradise or equivalent
approved by the Engineer-in-Charge.
WL- WALL LIGHT Point"
1.c Electrifical N/A "Concealed conduit wiring for EACH 745
following point looping at the switch
board with earth terminal including
circuit wiring with IC-2x1.5 sq.mm
PVC insulated and sheathed
stranded cable (BYM) & 1.5 sq.mm
PVC insulated green/white coloured
ECC wire (BYA) through PVC
conduit (Lira brand or equivalent
product of other reputed
manufacturer) of minimum 25 mm dia
& 1.5 mm wall thickness complete
with 18 SWG GP sheet, pull box with
3mm thick ebonite sheet cover, ceiling
rose, fixing materials etc.(without
switch & switchboard) as required
including mending the damages good
(all electrical contacts shall be of
brass/copper)
Cables manufactured by
Citizen/SQ/Paradise or equivalent
approved by the Engineer-in-Charge.
CF- CEILING FAN POINTS"
1.d Electrifical N/A "Concealed conduit wiring for EACH 799
following point looping at the switch
board with earth terminal including
circuit wiring with IC-2x1.5 sq.mm
PVC insulated and sheathed
stranded cable (BYM) & 1.5 sq.mm
PVC insulated green/white coloured
ECC wire (BYA) through PVC
conduit (Lira brand or equivalent
product of other reputed
manufacturer) of minimum 25 mm dia
& 1.5 mm wall thickness complete
with 18 SWG GP sheet, pull box with
3mm thick ebonite sheet cover, ceiling
rose, fixing materials etc.(without
switch & switchboard) as required
including mending the damages good
(all electrical contacts shall be of
brass/copper)
Cables manufactured by
Citizen/SQ/Paradise or equivalent
approved by the Engineer-in-
Charge.CFC- CIRCULAR BOX
FOR CEILING"
1.e Electrifical N/A "Concealed conduit wiring for EACH 476
following point looping at the switch
board with earth terminal including
circuit wiring with IC-2x1.5 sq.mm
PVC insulated and sheathed
stranded cable (BYM) & 1.5 sq.mm
PVC insulated green/white coloured
ECC wire (BYA) through PVC
conduit (Lira brand or equivalent
product of other reputed
manufacturer) of minimum 25 mm dia
& 1.5 mm wall thickness complete
with 18 SWG GP sheet, pull box with
3mm thick ebonite sheet cover, ceiling
rose, fixing materials etc.(without
switch & switchboard) as required
including mending the damages good
(all electrical contacts shall be of
brass/copper)
Cables manufactured by
Citizen/SQ/Paradise or equivalent
approved by the Engineer-in-
Charge.TL- TUBE LIGHT POINTS"
1.f Electrifical N/A "Concealed conduit wiring for EACH 560
following point looping at the switch
board with earth terminal including
circuit wiring with IC-2x1.5 sq.mm
PVC insulated and sheathed
stranded cable (BYM) & 1.5 sq.mm
PVC insulated green/white coloured
ECC wire (BYA) through PVC
conduit (Lira brand or equivalent
product of other reputed
manufacturer) of minimum 25 mm dia
& 1.5 mm wall thickness complete
with 18 SWG GP sheet, pull box with
3mm thick ebonite sheet cover, ceiling
rose, fixing materials etc.(without
switch & switchboard) as required
including mending the damages good
(all electrical contacts shall be of
brass/copper)
Cables manufactured by
Citizen/SQ/Paradise or equivalent
approved by the Engineer-in-
Charge.ML- MIRROR LIGHT
POINTS"
1.g Electrifical N/A "Concealed conduit wiring for EACH 490
following point looping at the switch
board with earth terminal including
circuit wiring with IC-2x1.5 sq.mm
PVC insulated and sheathed
stranded cable (BYM) & 1.5 sq.mm
PVC insulated green/white coloured
ECC wire (BYA) through PVC
conduit (Lira brand or equivalent
product of other reputed
manufacturer) of minimum 25 mm dia
& 1.5 mm wall thickness complete
with 18 SWG GP sheet, pull box with
3mm thick ebonite sheet cover, ceiling
rose, fixing materials etc.(without
switch & switchboard) as required
including mending the damages good
(all electrical contacts shall be of
brass/copper)
Cables manufactured by
Citizen/SQ/Paradise or equivalent
approved by the Engineer-in-
Charge.EXF- EXHAUST FAN
POINTS"
1.h Electrifical N/A "Concealed conduit wiring for EACH 745
following point looping at the switch
board with earth terminal including
circuit wiring with IC-2x1.5 sq.mm
PVC insulated and sheathed
stranded cable (BYM) & 1.5 sq.mm
PVC insulated green/white coloured
ECC wire (BYA) through PVC
conduit (Lira brand or equivalent
product of other reputed
manufacturer) of minimum 25 mm dia
& 1.5 mm wall thickness complete
with 18 SWG GP sheet, pull box with
3mm thick ebonite sheet cover, ceiling
rose, fixing materials etc.(without
switch & switchboard) as required
including mending the damages good
(all electrical contacts shall be of
brass/copper)
Cables manufactured by
Citizen/SQ/Paradise or equivalent
approved by the Engineer-in-
Charge.FAN COVER (7x7) "
1.i Electrifical N/A "Concealed conduit wiring for EACH 387
following point looping at the switch
board with earth terminal including
circuit wiring with IC-2x1.5 sq.mm
PVC insulated and sheathed
stranded cable (BYM) & 1.5 sq.mm
PVC insulated green/white coloured
ECC wire (BYA) through PVC
conduit (Lira brand or equivalent
product of other reputed
manufacturer) of minimum 25 mm dia
& 1.5 mm wall thickness complete
with 18 SWG GP sheet, pull box with
3mm thick ebonite sheet cover, ceiling
rose, fixing materials etc.(without
switch & switchboard) as required
including mending the damages good
(all electrical contacts shall be of
brass/copper)
Cables manufactured by
Citizen/SQ/Paradise or equivalent
approved by the Engineer-in-
Charge.WCL- CEILING LIGHT
POINTS AT WET LOCATION "
1.j Electrifical N/A "Concealed conduit wiring for EACH 745
following point looping at the switch
board with earth terminal including
circuit wiring with IC-2x1.5 sq.mm
PVC insulated and sheathed
stranded cable (BYM) & 1.5 sq.mm
PVC insulated green/white coloured
ECC wire (BYA) through PVC
conduit (Lira brand or equivalent
product of other reputed
manufacturer) of minimum 25 mm dia
& 1.5 mm wall thickness complete
with 18 SWG GP sheet, pull box with
3mm thick ebonite sheet cover, ceiling
rose, fixing materials etc.(without
switch & switchboard) as required
including mending the damages good
(all electrical contacts shall be of
brass/copper)
Cables manufactured by
Citizen/SQ/Paradise or equivalent
approved by the Engineer-in-
Charge.CEILING FAN "
2.a Electrifical N/A "Providing & fixing 250 volts. 5/6 EACH 853
amps. (minimum) concealed type
following switch / switch socket
mounted on required size 18 SWG
galvanized plain sheet board of 76.2
mm. (3"") depth all electrical contacts
shall be of brass/copper gang switch
Of following brand & country of
origin.
(MK England/HEGAR or equivalent
product of GERMANY / USA / UK /
FRANCE / JAPAN / ITALY /
SWEDEN / SWITZERLAND )or
equivalent approved by the Engineer-
in-Charge QS- 3PIN-15A SOCKET
AT SKIRTING LEVEL OR 10""
HEIGHT FROM FINISHED
FLOOR"
2.b Electrifical N/A "Providing & fixing 250 volts. 5/6 EACH 369
amps. (minimum) concealed type
following switch / switch socket
mounted on required size 18 SWG
galvanized plain sheet board of 76.2
mm. (3"") depth all electrical contacts
shall be of brass/copper gang switch
Of following brand & country of
origin.
(MK England/HEGAR or equivalent
product of GERMANY / USA / UK /
FRANCE / JAPAN / ITALY /
SWEDEN / SWITZERLAND )or
equivalent approved by the Engineer-
in-ChargeRS- 3PIN-13A SOCKET
AT 48"" HEIGHT FROM FINISHED
FLOOR"
2.c Electrifical N/A "Providing & fixing 250 volts. 5/6 EACH 495
amps. (minimum) concealed type
following switch / switch socket
mounted on required size 18 SWG
galvanized plain sheet board of 76.2
mm. (3"") depth all electrical contacts
shall be of brass/copper gang switch
Of following brand & country of
origin.
(MK England/HEGAR or equivalent
product of GERMANY / USA / UK /
FRANCE / JAPAN / ITALY /
SWEDEN / SWITZERLAND )or
equivalent approved by the Engineer-
in-Charge QL- 3PIN-15A SOCKET
AT LENTEL LEVEL HEIGHT"
2.d Electrifical N/A "Providing & fixing 250 volts. 5/6 EACH 145
amps. (minimum) concealed type
following switch / switch socket
mounted on required size 18 SWG
galvanized plain sheet board of 76.2
mm. (3"") depth all electrical contacts
shall be of brass/copper gang switch
Of following brand & country of
origin.
(MK England/HEGAR or equivalent
product of GERMANY / USA / UK /
FRANCE / JAPAN / ITALY /
SWEDEN / SWITZERLAND )or
equivalent approved by the Engineer-
in-Charge RY- 3PIN-13A SOCKET
AT 3'8"" HEIGHT FROM FINISHED
FLOOR"
2.e Electrifical N/A "Providing & fixing 250 volts. 5/6 EACH 590
amps. (minimum) concealed type
following switch / switch socket
mounted on required size 18 SWG
galvanized plain sheet board of 76.2
mm. (3"") depth all electrical contacts
shall be of brass/copper gang switch
Of following brand & country of
origin.
(MK England/HEGAR or equivalent
product of GERMANY / USA / UK /
FRANCE / JAPAN / ITALY /
SWEDEN / SWITZERLAND )or
equivalent approved by the Engineer-
in-Charge AS-DISH ANTENNA
SOCKET AT 3'8"" HEIGHT FROM
FINISHED FLOOR"
2.f Electrifical N/A "Providing & fixing 250 volts. 5/6 EACH 498
amps. (minimum) concealed type
following switch / switch socket
mounted on required size 18 SWG
galvanized plain sheet board of 76.2
mm. (3"") depth all electrical contacts
shall be of brass/copper gang switch
Of following brand & country of
origin.
(MK England/HEGAR or equivalent
product of GERMANY / USA / UK /
FRANCE / JAPAN / ITALY /
SWEDEN / SWITZERLAND )or
equivalent approved by the Engineer-
in-Charge TS- TELEPHONE
SOCKET AT 10"" HEIGHT FROM
FINISHED FLOOR"
2.g Electrifical N/A "Providing & fixing 250 volts. 5/6 EACH 267
amps. (minimum) concealed type
following switch / switch socket
mounted on required size 18 SWG
galvanized plain sheet board of 76.2
mm. (3"") depth all electrical contacts
shall be of brass/copper gang switch
Of following brand & country of
origin.
(MK England/HEGAR or equivalent
product of GERMANY / USA / UK /
FRANCE / JAPAN / ITALY /
SWEDEN / SWITZERLAND )or
equivalent approved by the Engineer-
in-ChargeNS- INTERNET SOCKET
AT 10"" HEIGHT FROM FINISHED
FLOOR"
2.h Electrifical N/A "Providing & fixing 250 volts. 5/6 EACH 139
amps. (minimum) concealed type
following switch / switch socket
mounted on required size 18 SWG
galvanized plain sheet board of 76.2
mm. (3"") depth all electrical contacts
shall be of brass/copper gang switch
Of following brand & country of
origin.
(MK England/HEGAR or equivalent
product of GERMANY / USA / UK /
FRANCE / JAPAN / ITALY /
SWEDEN / SWITZERLAND )or
equivalent approved by the Engineer-
in-Charge IC- INTERCOM
SOCKET AT 10"" HEIGHT FROM
FINISHED FLOOR"
2.i Electrifical N/A "Providing & fixing 250 volts. 5/6 EACH 459
amps. (minimum) concealed type
following switch / switch socket
mounted on required size 18 SWG
galvanized plain sheet board of 76.2
mm. (3"") depth all electrical contacts
shall be of brass/copper gang switch
Of following brand & country of
origin.
(MK England/HEGAR or equivalent
product of GERMANY / USA / UK /
FRANCE / JAPAN / ITALY /
SWEDEN / SWITZERLAND )or
equivalent approved by the Engineer-
in-ChargeGEYSER DP SWITCH
(20A) "
2.j Electrifical N/A "Providing & fixing 250 volts. 5/6 EACH 765
amps. (minimum) concealed type
following switch / switch socket
mounted on required size 18 SWG
galvanized plain sheet board of 76.2
mm. (3"") depth all electrical contacts
shall be of brass/copper gang switch
Of following brand & country of
origin.
(MK England/HEGAR or equivalent
product of GERMANY / USA / UK /
FRANCE / JAPAN / ITALY /
SWEDEN / SWITZERLAND )or
equivalent approved by the Engineer-
in-Charge CFR- CEILING FAN
DIMMER"
2.k Electrifical N/A "Providing & fixing 250 volts. 5/6 EACH 726
amps. (minimum) concealed type
following switch / switch socket
mounted on required size 18 SWG
galvanized plain sheet board of 76.2
mm. (3"") depth all electrical contacts
shall be of brass/copper gang switch
Of following brand & country of
origin.
(MK England/HEGAR or equivalent
product of GERMANY / USA / UK /
FRANCE / JAPAN / ITALY /
SWEDEN / SWITZERLAND )or
equivalent approved by the Engineer-
in-Charge 1 GANG SWITCH
BOARD"
2.l Electrifical N/A "Providing & fixing 250 volts. 5/6 EACH 661
amps. (minimum) concealed type
following switch / switch socket
mounted on required size 18 SWG
galvanized plain sheet board of 76.2
mm. (3"") depth all electrical contacts
shall be of brass/copper gang switch
Of following brand & country of
origin.
(MK England/HEGAR or equivalent
product of GERMANY / USA / UK /
FRANCE / JAPAN / ITALY /
SWEDEN / SWITZERLAND )or
equivalent approved by the Engineer-
in-Charge 2 GANG SWITCH
BOARD"
2.m Electrifical N/A "Providing & fixing 250 volts. 5/6 EACH 1093
amps. (minimum) concealed type
following switch / switch socket
mounted on required size 18 SWG
galvanized plain sheet board of 76.2
mm. (3"") depth all electrical contacts
shall be of brass/copper gang switch
Of following brand & country of
origin.
(MK England/HEGAR or equivalent
product of GERMANY / USA / UK /
FRANCE / JAPAN / ITALY /
SWEDEN / SWITZERLAND )or
equivalent approved by the Engineer-
in-Charge 3 GANG SWITCH
BOARD"
2.n Electrifical N/A "Providing & fixing 250 volts. 5/6 EACH 49
amps. (minimum) concealed type
following switch / switch socket
mounted on required size 18 SWG
galvanized plain sheet board of 76.2
mm. (3"") depth all electrical contacts
shall be of brass/copper gang switch
Of following brand & country of
origin.
(MK England/HEGAR or equivalent
product of GERMANY / USA / UK /
FRANCE / JAPAN / ITALY /
SWEDEN / SWITZERLAND )or
equivalent approved by the Engineer-
in-Charge 4 GANG SWITCH
BOARD"
2.o Electrifical N/A "Providing & fixing 250 volts. 5/6 EACH 37
amps. (minimum) concealed type
following switch / switch socket
mounted on required size 18 SWG
galvanized plain sheet board of 76.2
mm. (3"") depth all electrical contacts
shall be of brass/copper gang switch
Of following brand & country of
origin.
(MK England/HEGAR or equivalent
product of GERMANY / USA / UK /
FRANCE / JAPAN / ITALY /
SWEDEN / SWITZERLAND )or
equivalent approved by the Engineer-
in-Charge NJB- NETWORK
JUNCTION BOX"
2.p Electrifical N/A "Providing & fixing 250 volts. 5/6 EACH 37
amps. (minimum) concealed type
following switch / switch socket
mounted on required size 18 SWG
galvanized plain sheet board of 76.2
mm. (3"") depth all electrical contacts
shall be of brass/copper gang switch
Of following brand & country of
origin.
(MK England/HEGAR or equivalent
product of GERMANY / USA / UK /
FRANCE / JAPAN / ITALY /
SWEDEN / SWITZERLAND )or
equivalent approved by the Engineer-
in-Charge TJB- TELEPHONE
JUNCTION BOX"
2.q Electrifical N/A "Providing & fixing 250 volts. 5/6 EACH 37
amps. (minimum) concealed type
following switch / switch socket
mounted on required size 18 SWG
galvanized plain sheet board of 76.2
mm. (3"") depth all electrical contacts
shall be of brass/copper gang switch
Of following brand & country of
origin.
(MK England/HEGAR or equivalent
product of GERMANY / USA / UK /
FRANCE / JAPAN / ITALY /
SWEDEN / SWITZERLAND )or
equivalent approved by the Engineer-
in-Charge IJB- INTERCOM
JUNCTION BOX"
2.r Electrifical N/A "Providing & fixing 250 volts. 5/6 EACH 37
amps. (minimum) concealed type
following switch / switch socket
mounted on required size 18 SWG
galvanized plain sheet board of 76.2
mm. (3"") depth all electrical contacts
shall be of brass/copper gang switch
Of following brand & country of
origin.
(MK England/HEGAR or equivalent
product of GERMANY / USA / UK /
FRANCE / JAPAN / ITALY /
SWEDEN / SWITZERLAND )or
equivalent approved by the Engineer-
in-Charge AJB- ANTENA
JUNCTION BOX "
3.a Electrifical N/A "Providing & fixing 250V, 50 Hz grade EACH 2
following concealed type sub-
distribution board & floor distribution
board made of 18-SWG MS sheet
complete with hinged type door, built-
in type locking arrangement, one no.
60 A capacity bus-bar with required
no. of holes thereon on insulators at
both ends, copper blocks for neutral
and earth terminal, SPMCBs having
minimum breaking capacity 6/10-KA
with thermal over current and
instantaneous electromagnetic short
ckt. release, necessary arrangement
for fixing of MCBs by keeping its
knobs out on the top cover of the
board in/c stove enamel/gray hammer
painting of board etc.
With SPMCBS of AEG (Germany),
Dorman Smith (England), MEM
(UK), Siemens (USA/Germany) or
equivalent approved by the Engineer-
in-Charge. Main Distribution Board"
3.b Electrifical N/A "Providing & fixing 250V, 50 Hz grade EACH 40
following concealed type sub-
distribution board & floor distribution
board made of 18-SWG MS sheet
complete with hinged type door, built-
in type locking arrangement, one no.
60 A capacity bus-bar with required
no. of holes thereon on insulators at
both ends, copper blocks for neutral
and earth terminal, SPMCBs having
minimum breaking capacity 6/10-KA
with thermal over current and
instantaneous electromagnetic short
ckt. release, necessary arrangement
for fixing of MCBs by keeping its
knobs out on the top cover of the
board in/c stove enamel/gray hammer
painting of board etc.
With SPMCBS of AEG (Germany),
Dorman Smith (England), MEM
(UK), Siemens (USA/Germany) or
equivalent approved by the Engineer-
in-Charge. FDB- FLOOR
DISTRIBUTION BOARD "
3.c Electrifical N/A "Providing & fixing 250V, 50 Hz grade EACH 148
following concealed type sub-
distribution board & floor distribution
board made of 18-SWG MS sheet
complete with hinged type door, built-
in type locking arrangement, one no.
60 A capacity bus-bar with required
no. of holes thereon on insulators at
both ends, copper blocks for neutral
and earth terminal, SPMCBs having
minimum breaking capacity 6/10-KA
with thermal over current and
instantaneous electromagnetic short
ckt. release, necessary arrangement
for fixing of MCBs by keeping its
knobs out on the top cover of the
board in/c stove enamel/gray hammer
painting of board etc.
With SPMCBS of AEG (Germany),
Dorman Smith (England), MEM
(UK), Siemens (USA/Germany) or
equivalent approved by the Engineer-
in-Charge. SDB-SUB
DISTRIBUTION BOARD"
4.a Electrifical N/A "Providing & fixing on a prepared EACH 2012
board 220 volt grade following Single-
pole Miniature Circuit Breaker
(SPMCB) and 500 volt Triple-pole
moulded case Circuit Breaker
(TPMCCB) with thermal over-current
and instantaneous electromagnetic
short circuit release provision.
Brand and Country of origin of SP
MCB & TPMCCB are ABB (Italy),
LEGRAND (France/Italy), MEM
(UK), or equivalent approved by the
Engineering-in-Charge. 10 APMS SP
MCB (6kA)"
4.b Electrifical N/A "Providing & fixing on a prepared EACH 711
board 220 volt grade following Single-
pole Miniature Circuit Breaker
(SPMCB) and 500 volt Triple-pole
moulded case Circuit Breaker
(TPMCCB) with thermal over-current
and instantaneous electromagnetic
short circuit release provision.
Brand and Country of origin of SP
MCB & TPMCCB are ABB (Italy),
LEGRAND (France/Italy), MEM
(UK), or equivalent approved by the
Engineering-in-Charge. 16 APMS SP
MCB (6kA)"
4.c Electrifical N/A "Providing & fixing on a prepared EACH 498
board 220 volt grade following Single-
pole Miniature Circuit Breaker
(SPMCB) and 500 volt Triple-pole
moulded case Circuit Breaker
(TPMCCB) with thermal over-current
and instantaneous electromagnetic
short circuit release provision.
Brand and Country of origin of SP
MCB & TPMCCB are ABB (Italy),
LEGRAND (France/Italy), MEM
(UK), or equivalent approved by the
Engineering-in-Charge. 25 APMS DP
MCB (6kA)"
4.d Electrifical N/A "Providing & fixing on a prepared EACH 294
board 220 volt grade following Single-
pole Miniature Circuit Breaker
(SPMCB) and 500 volt Triple-pole
moulded case Circuit Breaker
(TPMCCB) with thermal over-current
and instantaneous electromagnetic
short circuit release provision.
Brand and Country of origin of SP
MCB & TPMCCB are ABB (Italy),
LEGRAND (France/Italy), MEM
(UK), or equivalent approved by the
Engineering-in-Charge. 63 APMS DP
MCB (6kA)"
4.e Electrifical N/A "Providing & fixing on a prepared EACH 45
board 220 volt grade following Single-
pole Miniature Circuit Breaker
(SPMCB) and 500 volt Triple-pole
moulded case Circuit Breaker
(TPMCCB) with thermal over-current
and instantaneous electromagnetic
short circuit release provision.
Brand and Country of origin of SP
MCB & TPMCCB are ABB (Italy),
LEGRAND (France/Italy), MEM
(UK), or equivalent approved by the
Engineering-in-Charge. 80 APMS TP
MCCB (18kA) "
Grand
Total :

Schedule of Day works

Table
.
Name :
Unit Total
Item Unit Total Total
Price Price
Item Code Description Measurement Nominal Unit Price in Figures Price in
no. Group (if of Item Unit Quantity (BDT) in Figures in
Words Words
any) (BDT)
(BDT) (BDT)
NA NA NA NA NA 1

Grand
Total :

Unconditional Discount Form

Table
Unconditional Discount
Name :
Discount in Percentage (%)[In figure] Discount in Percentage (%) [In word]

Bill of Quantities (Sanitary)

Table
Bill of Quantities
Name :
Unit Total Total
Item Price Price Price
Unit Price
Item Code Measurement
Group Description of Item Quantity
no. (if Unit In figures (BDT) In In In
any) Words Figures Words
(BDT) (BDT) (BDT)
1.1 Sanitary N/A Supply, fitting and fixing of Extra Rm. 120
heavy uPVC pipe shall be made
uPVC as per BS4514/ISO4422/
SS213 standard. Pipe shall be bell
end socket type. Approved type of
solvent sealant shall be used to install
pipe and jointing the pipe with uPVC
pipe fittings such as bends, tees, Y-
joints, socket, reducers, U-trap, S-
trap, drain strainer, elbows, offset
bends etc. made of uPVC having
minimum thickness as specified in
uPVC pipe and shall be complete
with threaded service door with cover
etc. Pipefittings. Joint shall be
watertight. In brick wall pipe shall be
surrounded by concrete in 1: 3.5: 5.5
and shall be clamped to wall properly
at an interval of not more than 1200
mm. Pipe laying shall have the
following gradient unless otherwise
specified. Nominal dia of pipe with
thickness shall be as follows. Product
shall be of Partex/ Bangale/ NPL/
RFL from Bangladesh. a)150 mm dia
1: 60 soil, 1: 90 for waste. b)100 mm
dia 1: 40 for soil, 1: 60 for waste. c)
80 mm dia 1: 25 for soil, 1: 40 for
waste.350 mm dia, 9.8mm thick.
1.2 Sanitary N/A Supply, fitting and fixing of Extra Rm 160
heavy uPVC pipe shall be made
uPVC as per BS4514/ISO4422/
SS213 standard. Pipe shall be bell
end socket type. Approved type of
solvent sealant shall be used to install
pipe and jointing the pipe with uPVC
pipe fittings such as bends, tees, Y-
joints, socket, reducers, U-trap, S-
trap, drain strainer, elbows, offset
bends etc. made of uPVC having
minimum thickness as specified in
uPVC pipe and shall be complete
with threaded service door with cover
etc. Pipefittings. Joint shall be
watertight. In brick wall pipe shall be
surrounded by concrete in 1: 3.5: 5.5
and shall be clamped to wall properly
at an interval of not more than 1200
mm. Pipe laying shall have the
following gradient unless otherwise
specified. Nominal dia of pipe with
thickness shall be as follows. Product
shall be of Partex/ Bangale/ NPL/
RFL from Bangladesh. a)150 mm dia
1: 60 soil, 1: 90 for waste. b)100 mm
dia 1: 40 for soil, 1: 60 for waste. c)
80 mm dia 1: 25 for soil, 1: 40 for
waste.300 mm dia, 7.8mm thick.
1.3 Sanitary N/A Supply, fitting and fixing of Extra Rm 140
heavy uPVC pipe shall be made
uPVC as per BS4514/ISO4422/
SS213 standard. Pipe shall be bell
end socket type. Approved type of
solvent sealant shall be used to install
pipe and jointing the pipe with uPVC
pipe fittings such as bends, tees, Y-
joints, socket, reducers, U-trap, S-
trap, drain strainer, elbows, offset
bends etc. made of uPVC having
minimum thickness as specified in
uPVC pipe and shall be complete
with threaded service door with cover
etc. Pipefittings. Joint shall be
watertight. In brick wall pipe shall be
surrounded by concrete in 1: 3.5: 5.5
and shall be clamped to wall properly
at an interval of not more than 1200
mm. Pipe laying shall have the
following gradient unless otherwise
specified. Nominal dia of pipe with
thickness shall be as follows. Product
shall be of Partex/ Bangale/ NPL/
RFL from Bangladesh. a)150 mm dia
1: 60 soil, 1: 90 for waste. b)100 mm
dia 1: 40 for soil, 1: 60 for waste. c)
80 mm dia 1: 25 for soil, 1: 40 for
waste.250 mm dia, 6.6mm thick.
1.4 Sanitary N/A Supply, fitting and fixing of Extra Rm 90
heavy uPVC pipe shall be made
uPVC as per BS4514/ISO4422/
SS213 standard. Pipe shall be bell
end socket type. Approved type of
solvent sealant shall be used to install
pipe and jointing the pipe with uPVC
pipe fittings such as bends, tees, Y-
joints, socket, reducers, U-trap, S-
trap, drain strainer, elbows, offset
bends etc. made of uPVC having
minimum thickness as specified in
uPVC pipe and shall be complete
with threaded service door with cover
etc. Pipefittings. Joint shall be
watertight. In brick wall pipe shall be
surrounded by concrete in 1: 3.5: 5.5
and shall be clamped to wall properly
at an interval of not more than 1200
mm. Pipe laying shall have the
following gradient unless otherwise
specified. Nominal dia of pipe with
thickness shall be as follows. Product
shall be of Partex/ Bangale/ NPL/
RFL from Bangladesh. a)150 mm dia
1: 60 soil, 1: 90 for waste. b)100 mm
dia 1: 40 for soil, 1: 60 for waste. c)
80 mm dia 1: 25 for soil, 1: 40 for
waste.200 mm dia, 5.3mm thick.
1.5 Sanitary N/A Supply, fitting and fixing of Extra Rm 280
heavy uPVC pipe shall be made
uPVC as per BS4514/ISO4422/
SS213 standard. Pipe shall be bell
end socket type. Approved type of
solvent sealant shall be used to install
pipe and jointing the pipe with uPVC
pipe fittings such as bends, tees, Y-
joints, socket, reducers, U-trap, S-
trap, drain strainer, elbows, offset
bends etc. made of uPVC having
minimum thickness as specified in
uPVC pipe and shall be complete
with threaded service door with cover
etc. Pipefittings. Joint shall be
watertight. In brick wall pipe shall be
surrounded by concrete in 1: 3.5: 5.5
and shall be clamped to wall properly
at an interval of not more than 1200
mm. Pipe laying shall have the
following gradient unless otherwise
specified. Nominal dia of pipe with
thickness shall be as follows. Product
shall be of Partex/ Bangale/ NPL/
RFL from Bangladesh. a)150 mm dia
1: 60 soil, 1: 90 for waste. b)100 mm
dia 1: 40 for soil, 1: 60 for waste. c)
80 mm dia 1: 25 for soil, 1: 40 for
waste.150 mm dia, 4.5 mm thick.
1.6 Sanitary N/A Supply, fitting and fixing of Extra Rm 5650
heavy uPVC pipe shall be made
uPVC as per BS4514/ISO4422/
SS213 standard. Pipe shall be bell
end socket type. Approved type of
solvent sealant shall be used to install
pipe and jointing the pipe with uPVC
pipe fittings such as bends, tees, Y-
joints, socket, reducers, U-trap, S-
trap, drain strainer, elbows, offset
bends etc. made of uPVC having
minimum thickness as specified in
uPVC pipe and shall be complete
with threaded service door with cover
etc. Pipefittings. Joint shall be
watertight. In brick wall pipe shall be
surrounded by concrete in 1: 3.5: 5.5
and shall be clamped to wall properly
at an interval of not more than 1200
mm. Pipe laying shall have the
following gradient unless otherwise
specified. Nominal dia of pipe with
thickness shall be as follows. Product
shall be of Partex/ Bangale/ NPL/
RFL from Bangladesh. a)150 mm dia
1: 60 soil, 1: 90 for waste. b)100 mm
dia 1: 40 for soil, 1: 60 for waste. c)
80 mm dia 1: 25 for soil, 1: 40 for
waste.100 mm dia, 3.4 mm thick
1.7 Sanitary N/A Supply, fitting and fixing of Extra Rm 80
heavy uPVC pipe shall be made
uPVC as per BS4514/ISO4422/
SS213 standard. Pipe shall be bell
end socket type. Approved type of
solvent sealant shall be used to install
pipe and jointing the pipe with uPVC
pipe fittings such as bends, tees, Y-
joints, socket, reducers, U-trap, S-
trap, drain strainer, elbows, offset
bends etc. made of uPVC having
minimum thickness as specified in
uPVC pipe and shall be complete
with threaded service door with cover
etc. Pipefittings. Joint shall be
watertight. In brick wall pipe shall be
surrounded by concrete in 1: 3.5: 5.5
and shall be clamped to wall properly
at an interval of not more than 1200
mm. Pipe laying shall have the
following gradient unless otherwise
specified. Nominal dia of pipe with
thickness shall be as follows. Product
shall be of Partex/ Bangale/ NPL/
RFL from Bangladesh. a)150 mm dia
1: 60 soil, 1: 90 for waste. b)100 mm
dia 1: 40 for soil, 1: 60 for waste. c)
80 mm dia 1: 25 for soil, 1: 40 for
waste.80 mm dia, 3 mm thick.
1.8 Sanitary N/A Supply, fitting and fixing of Extra Rm 450
heavy uPVC pipe shall be made
uPVC as per BS4514/ISO4422/
SS213 standard. Pipe shall be bell
end socket type. Approved type of
solvent sealant shall be used to install
pipe and jointing the pipe with uPVC
pipe fittings such as bends, tees, Y-
joints, socket, reducers, U-trap, S-
trap, drain strainer, elbows, offset
bends etc. made of uPVC having
minimum thickness as specified in
uPVC pipe and shall be complete
with threaded service door with cover
etc. Pipefittings. Joint shall be
watertight. In brick wall pipe shall be
surrounded by concrete in 1: 3.5: 5.5
and shall be clamped to wall properly
at an interval of not more than 1200
mm. Pipe laying shall have the
following gradient unless otherwise
specified. Nominal dia of pipe with
thickness shall be as follows. Product
shall be of Partex/ Bangale/ NPL/
RFL from Bangladesh. a)150 mm dia
1: 60 soil, 1: 90 for waste. b)100 mm
dia 1: 40 for soil, 1: 60 for waste. c)
80 mm dia 1: 25 for soil, 1: 40 for
waste.50 mm dia, 2.4 mm thick
1.9 Sanitary N/A Supply, fitting and fixing of Extra Rm 120
heavy uPVC pipe shall be made
uPVC as per BS4514/ISO4422/
SS213 standard. Pipe shall be bell
end socket type. Approved type of
solvent sealant shall be used to install
pipe and jointing the pipe with uPVC
pipe fittings such as bends, tees, Y-
joints, socket, reducers, U-trap, S-
trap, drain strainer, elbows, offset
bends etc. made of uPVC having
minimum thickness as specified in
uPVC pipe and shall be complete
with threaded service door with cover
etc. Pipefittings. Joint shall be
watertight. In brick wall pipe shall be
surrounded by concrete in 1: 3.5: 5.5
and shall be clamped to wall properly
at an interval of not more than 1200
mm. Pipe laying shall have the
following gradient unless otherwise
specified. Nominal dia of pipe with
thickness shall be as follows. Product
shall be of Partex/ Bangale/ NPL/
RFL from Bangladesh. a)150 mm dia
1: 60 soil, 1: 90 for waste. b)100 mm
dia 1: 40 for soil, 1: 60 for waste. c)
80 mm dia 1: 25 for soil, 1: 40 for
waste.40 mm dia, 2 mm thick.
1.10 Sanitary N/A Supply, fitting and fixing of Extra Rm 120
heavy uPVC pipe shall be made
uPVC as per BS4514/ISO4422/
SS213 standard. Pipe shall be bell
end socket type. Approved type of
solvent sealant shall be used to install
pipe and jointing the pipe with uPVC
pipe fittings such as bends, tees, Y-
joints, socket, reducers, U-trap, S-
trap, drain strainer, elbows, offset
bends etc. made of uPVC having
minimum thickness as specified in
uPVC pipe and shall be complete
with threaded service door with cover
etc. Pipefittings. Joint shall be
watertight. In brick wall pipe shall be
surrounded by concrete in 1: 3.5: 5.5
and shall be clamped to wall properly
at an interval of not more than 1200
mm. Pipe laying shall have the
following gradient unless otherwise
specified. Nominal dia of pipe with
thickness shall be as follows. Product
shall be of Partex/ Bangale/ NPL/
RFL from Bangladesh. a)150 mm dia
1: 60 soil, 1: 90 for waste. b)100 mm
dia 1: 40 for soil, 1: 60 for waste. c)
80 mm dia 1: 25 for soil, 1: 40 for
waste.32 mm dia, 1.7 mm thick.
2.1 Sanitary N/A Supply, fitting and fixing of uPVC pipe Nos. 850
fittings such as P-trap, S-trap, Bell
Mouth Roof Drain etc. made of
uPVC having minimum thickness as
specified in uPVC pipe and shall be
complete with threaded service door
with cover etc. Fittings shall be bell
and spigot type to adopt pipes.
Product shall be as per
BS4515/BS5255/ISO4422/ISO3633.
Fittings shall be installed as per
drawing and direction and shall be
properly plumbed and fixed. The
fittings shall be of Bangal/ Partex/
NPL from Bangladesh. uPVC P-Trap
100mm dia :Supply, fitting and fixing
of 100 mm dia uPVC P-trap with
50mm vent and shall have minimum
50mm water seal. 100mm dia
2.2 Sanitary N/A Supply, fitting and fixing of uPVC pipe Nos. 20
fittings such as P-trap, S-trap, Bell
Mouth Roof Drain etc. made of
uPVC having minimum thickness as
specified in uPVC pipe and shall be
complete with threaded service door
with cover etc. Fittings shall be bell
and spigot type to adopt pipes.
Product shall be as per
BS4515/BS5255/ISO4422/ISO3633.
Fittings shall be installed as per
drawing and direction and shall be
properly plumbed and fixed. The
fittings shall be of Bangal/ Partex/
NPL from Bangladesh. uPVC S-
TRAP : Supply, fitting and fixing of
uPVC 100 mm dia uPVC S Trap with
50mm vent and shall have 50mm
water seal. 100mm dia
2.3.a Sanitary N/A Supply, fitting and fixing of uPVC pipe Nos. 4
fittings such as P-trap, S-trap, Bell
Mouth Roof Drain etc. made of
uPVC having minimum thickness as
specified in uPVC pipe and shall be
complete with threaded service door
with cover etc. Fittings shall be bell
and spigot type to adopt pipes.
Product shall be as per
BS4515/BS5255/ISO4422/ISO3633.
Fittings shall be installed as per
drawing and direction and shall be
properly plumbed and fixed. The
fittings shall be of Bangal/ Partex/
NPL from Bangladesh. HCI Bell
Mouth Roof Drain :Supply, fitting and
fixing of HCI Bell Mouth Roof Drain
shall be 200mm x 200mm & 150mm x
150mm size to adopt upvc pipe two
pieces with socket. 150 mm dia
2.3.b Sanitary N/A Supply, fitting and fixing of uPVC pipe Nos. 30
fittings such as P-trap, S-trap, Bell
Mouth Roof Drain etc. made of
uPVC having minimum thickness as
specified in uPVC pipe and shall be
complete with threaded service door
with cover etc. Fittings shall be bell
and spigot type to adopt pipes.
Product shall be as per
BS4515/BS5255/ISO4422/ISO3633.
Fittings shall be installed as per
drawing and direction and shall be
properly plumbed and fixed. The
fittings shall be of Bangal/ Partex/
NPL from Bangladesh. HCI Bell
Mouth Roof Drain :Supply, fitting and
fixing of HCI Bell Mouth Roof Drain
shall be 200mm x 200mm & 150mm x
150mm size to adopt upvc pipe two
pieces with socket. 100 mm dia
3.1 Sanitary N/A Supply, fitting, fixing and laying of Rm 6
R.C.C. pipe over 100 mm and 75 mm
thick cement concrete (6:3:1) at base
over a brick flat soling with proper
gradient in trenches, making collar
joints with gasket and cement mortar
(1:1) including cutting trenches and
refilling the same upto the required
depth as per direction of the
Engineer/Consultant.350 mm dia pipe
3.2 Sanitary N/A Supply, fitting, fixing and laying of Rm 6
R.C.C. pipe over 100 mm and 75 mm
thick cement concrete (6:3:1) at base
over a brick flat soling with proper
gradient in trenches, making collar
joints with gasket and cement mortar
(1:1) including cutting trenches and
refilling the same upto the required
depth as per direction of the
Engineer/Consultant. 300 mm dia
pipe
4.1.a Sanitary N/A WATER SUPPLY PIPE : GI PIPE : Rm 210
Supply, fittings, fixing and laying of GI
Pipe. Pipe work of Standard
thickness as specified in group-ka or
approved equivalent shall be
complete with bends, tees, elbows,
socket, union, reducers, hanger,
bracket, clamp etc. complete.
Approved type of sealant shall be
used on thread to make it leak proof.
All the pipe work shall be tested at
680 kpa for 24 hours in presence of
the representative of the
Owner/counsultants. All MS & GI
Materials used in pipe work shall be
painted with two coats of prime cote
of approved quality. Product shall be
of NTL/ Bashundhara (Ruby)
Bangladesh. 100mm dia, 3.65mm
thick
4.1.b Sanitary N/A WATER SUPPLY PIPE : GI PIPE : Rm 90
Supply, fittings, fixing and laying of GI
Pipe. Pipe work of Standard
thickness as specified in group-ka or
approved equivalent shall be
complete with bends, tees, elbows,
socket, union, reducers, hanger,
bracket, clamp etc. complete.
Approved type of sealant shall be
used on thread to make it leak proof.
All the pipe work shall be tested at
680 kpa for 24 hours in presence of
the representative of the
Owner/counsultants. All MS & GI
Materials used in pipe work shall be
painted with two coats of prime cote
of approved quality. Product shall be
of NTL/ Bashundhara (Ruby)
Bangladesh. 80mm dia, 3.25mm thick
4.1.c Sanitary N/A WATER SUPPLY PIPE : GI PIPE : Rm 20
Supply, fittings, fixing and laying of GI
Pipe. Pipe work of Standard
thickness as specified in group-ka or
approved equivalent shall be
complete with bends, tees, elbows,
socket, union, reducers, hanger,
bracket, clamp etc. complete.
Approved type of sealant shall be
used on thread to make it leak proof.
All the pipe work shall be tested at
680 kpa for 24 hours in presence of
the representative of the
Owner/counsultants. All MS & GI
Materials used in pipe work shall be
painted with two coats of prime cote
of approved quality. Product shall be
of NTL/ Bashundhara (Ruby)
Bangladesh. 65mm dia, 3.25mm thick
4.1.d Sanitary N/A WATER SUPPLY PIPE : GI PIPE : Rm 310
Supply, fittings, fixing and laying of GI
Pipe. Pipe work of Standard
thickness as specified in group-ka or
approved equivalent shall be
complete with bends, tees, elbows,
socket, union, reducers, hanger,
bracket, clamp etc. complete.
Approved type of sealant shall be
used on thread to make it leak proof.
All the pipe work shall be tested at
680 kpa for 24 hours in presence of
the representative of the
Owner/counsultants. All MS & GI
Materials used in pipe work shall be
painted with two coats of prime cote
of approved quality. Product shall be
of NTL/ Bashundhara (Ruby)
Bangladesh. 50mm dia, 2.90mm thick
4.1.e Sanitary N/A WATER SUPPLY PIPE : GI PIPE : Rm 330
Supply, fittings, fixing and laying of GI
Pipe. Pipe work of Standard
thickness as specified in group-ka or
approved equivalent shall be
complete with bends, tees, elbows,
socket, union, reducers, hanger,
bracket, clamp etc. complete.
Approved type of sealant shall be
used on thread to make it leak proof.
All the pipe work shall be tested at
680 kpa for 24 hours in presence of
the representative of the
Owner/counsultants. All MS & GI
Materials used in pipe work shall be
painted with two coats of prime cote
of approved quality. Product shall be
of NTL/ Bashundhara (Ruby)
Bangladesh. 40mm dia, 2.90mm thick
4.1.f Sanitary N/A WATER SUPPLY PIPE : GI PIPE : Rm 30
Supply, fittings, fixing and laying of GI
Pipe. Pipe work of Standard
thickness as specified in group-ka or
approved equivalent shall be
complete with bends, tees, elbows,
socket, union, reducers, hanger,
bracket, clamp etc. complete.
Approved type of sealant shall be
used on thread to make it leak proof.
All the pipe work shall be tested at
680 kpa for 24 hours in presence of
the representative of the
Owner/counsultants. All MS & GI
Materials used in pipe work shall be
painted with two coats of prime cote
of approved quality. Product shall be
of NTL/ Bashundhara (Ruby)
Bangladesh. 35mm dia, 2.65mm thick
4.1.g Sanitary N/A WATER SUPPLY PIPE : GI PIPE : Rm 1050
Supply, fittings, fixing and laying of GI
Pipe. Pipe work of Standard
thickness as specified in group-ka or
approved equivalent shall be
complete with bends, tees, elbows,
socket, union, reducers, hanger,
bracket, clamp etc. complete.
Approved type of sealant shall be
used on thread to make it leak proof.
All the pipe work shall be tested at
680 kpa for 24 hours in presence of
the representative of the
Owner/counsultants. All MS & GI
Materials used in pipe work shall be
painted with two coats of prime cote
of approved quality. Product shall be
of NTL/ Bashundhara (Ruby)
Bangladesh. 25mm dia, 2.65mm thick
4.1.h Sanitary N/A WATER SUPPLY PIPE : GI PIPE : Rm 50
Supply, fittings, fixing and laying of GI
Pipe. Pipe work of Standard
thickness as specified in group-ka or
approved equivalent shall be
complete with bends, tees, elbows,
socket, union, reducers, hanger,
bracket, clamp etc. complete.
Approved type of sealant shall be
used on thread to make it leak proof.
All the pipe work shall be tested at
680 kpa for 24 hours in presence of
the representative of the
Owner/counsultants. All MS & GI
Materials used in pipe work shall be
painted with two coats of prime cote
of approved quality. Product shall be
of NTL/ Bashundhara (Ruby)
Bangladesh. 20mm dia, 2.35mm thick
4.1.i Sanitary N/A WATER SUPPLY PIPE : GI PIPE : Rm 1100
Supply, fittings, fixing and laying of GI
Pipe. Pipe work of Standard
thickness as specified in group-ka or
approved equivalent shall be
complete with bends, tees, elbows,
socket, union, reducers, hanger,
bracket, clamp etc. complete.
Approved type of sealant shall be
used on thread to make it leak proof.
All the pipe work shall be tested at
680 kpa for 24 hours in presence of
the representative of the
Owner/counsultants. All MS & GI
Materials used in pipe work shall be
painted with two coats of prime cote
of approved quality. Product shall be
of NTL/ Bashundhara (Ruby)
Bangladesh. 15mm dia, 2.00mm thick
4.2.a Sanitary N/A WATER SUPPLY PIPE : CPVC Rm 120
PIPE : Supply, fittings, fixing and
laying of CPVC Pipe.Pipe work shall
be complete with bends, tees,
elbows, socket, union, reducers,
hanger, bracket, clamp etc. All joints
shall be Hot-melt, 100% Approved
type & sealant shall be used
secondary on thread to make it leak
proof. All the pipe work shall be
tested at 1.6Mpa for 24 hours in
presence of the representative of the
Consultants. All MS & GI Materials
used in pipe work shall be painted
with two coats of prime coat of
approved quality by the
Engineer/Consultants.The product
shall be Ajay /Astral at India or NPL/
RFL Equivalent. 100mm dia, 7.65mm
thick
4.2.b Sanitary N/A WATER SUPPLY PIPE : CPVC Rm 201
PIPE : Supply, fittings, fixing and
laying of CPVC Pipe.Pipe work shall
be complete with bends, tees,
elbows, socket, union, reducers,
hanger, bracket, clamp etc. All joints
shall be Hot-melt, 100% Approved
type & sealant shall be used
secondary on thread to make it leak
proof. All the pipe work shall be
tested at 1.6Mpa for 24 hours in
presence of the representative of the
Consultants. All MS & GI Materials
used in pipe work shall be painted
with two coats of prime coat of
approved quality by the
Engineer/Consultants.The product
shall be Ajay /Astral at India or NPL/
RFL Equivalent. 80mm dia, 6.85mm
thick
4.2.c Sanitary N/A WATER SUPPLY PIPE : CPVC Rm 120
PIPE : Supply, fittings, fixing and
laying of CPVC Pipe.Pipe work shall
be complete with bends, tees,
elbows, socket, union, reducers,
hanger, bracket, clamp etc. All joints
shall be Hot-melt, 100% Approved
type & sealant shall be used
secondary on thread to make it leak
proof. All the pipe work shall be
tested at 1.6Mpa for 24 hours in
presence of the representative of the
Consultants. All MS & GI Materials
used in pipe work shall be painted
with two coats of prime coat of
approved quality by the
Engineer/Consultants.The product
shall be Ajay /Astral at India or NPL/
RFL Equivalent. 65mm dia, 6.5mm
thick
4.2.d Sanitary N/A WATER SUPPLY PIPE : CPVC Rm 610
PIPE : Supply, fittings, fixing and
laying of CPVC Pipe.Pipe work shall
be complete with bends, tees,
elbows, socket, union, reducers,
hanger, bracket, clamp etc. All joints
shall be Hot-melt, 100% Approved
type & sealant shall be used
secondary on thread to make it leak
proof. All the pipe work shall be
tested at 1.6Mpa for 24 hours in
presence of the representative of the
Consultants. All MS & GI Materials
used in pipe work shall be painted
with two coats of prime coat of
approved quality by the
Engineer/Consultants.The product
shall be Ajay /Astral at India or NPL/
RFL Equivalent. 50mm dia, 5.60mm
thick
4.2.e Sanitary N/A WATER SUPPLY PIPE : CPVC Rm 1950
PIPE : Supply, fittings, fixing and
laying of CPVC Pipe.Pipe work shall
be complete with bends, tees,
elbows, socket, union, reducers,
hanger, bracket, clamp etc. All joints
shall be Hot-melt, 100% Approved
type & sealant shall be used
secondary on thread to make it leak
proof. All the pipe work shall be
tested at 1.6Mpa for 24 hours in
presence of the representative of the
Consultants. All MS & GI Materials
used in pipe work shall be painted
with two coats of prime coat of
approved quality by the
Engineer/Consultants.The product
shall be Ajay /Astral at India or NPL/
RFL Equivalent. 40mm dia, 4.50mm
thick
4.2.f Sanitary N/A WATER SUPPLY PIPE : CPVC Rm 300
PIPE : Supply, fittings, fixing and
laying of CPVC Pipe.Pipe work shall
be complete with bends, tees,
elbows, socket, union, reducers,
hanger, bracket, clamp etc. All joints
shall be Hot-melt, 100% Approved
type & sealant shall be used
secondary on thread to make it leak
proof. All the pipe work shall be
tested at 1.6Mpa for 24 hours in
presence of the representative of the
Consultants. All MS & GI Materials
used in pipe work shall be painted
with two coats of prime coat of
approved quality by the
Engineer/Consultants.The product
shall be Ajay /Astral at India or NPL/
RFL Equivalent. 32mm dia, 3.90mm
thick
4.2.g Sanitary N/A WATER SUPPLY PIPE : CPVC Rm 2850
PIPE : Supply, fittings, fixing and
laying of CPVC Pipe.Pipe work shall
be complete with bends, tees,
elbows, socket, union, reducers,
hanger, bracket, clamp etc. All joints
shall be Hot-melt, 100% Approved
type & sealant shall be used
secondary on thread to make it leak
proof. All the pipe work shall be
tested at 1.6Mpa for 24 hours in
presence of the representative of the
Consultants. All MS & GI Materials
used in pipe work shall be painted
with two coats of prime coat of
approved quality by the
Engineer/Consultants.The product
shall be Ajay /Astral at India or NPL/
RFL Equivalent. 25mm dia, 3.85mm
thick
4.2.h Sanitary N/A WATER SUPPLY PIPE : CPVC Rm 950
PIPE : Supply, fittings, fixing and
laying of CPVC Pipe.Pipe work shall
be complete with bends, tees,
elbows, socket, union, reducers,
hanger, bracket, clamp etc. All joints
shall be Hot-melt, 100% Approved
type & sealant shall be used
secondary on thread to make it leak
proof. All the pipe work shall be
tested at 1.6Mpa for 24 hours in
presence of the representative of the
Consultants. All MS & GI Materials
used in pipe work shall be painted
with two coats of prime coat of
approved quality by the
Engineer/Consultants.The product
shall be Ajay /Astral at India or NPL/
RFL Equivalent. 20mm dia, 2.30mm
thick
4.2.i Sanitary N/A WATER SUPPLY PIPE : CPVC Rm 5950
PIPE : Supply, fittings, fixing and
laying of CPVC Pipe.Pipe work shall
be complete with bends, tees,
elbows, socket, union, reducers,
hanger, bracket, clamp etc. All joints
shall be Hot-melt, 100% Approved
type & sealant shall be used
secondary on thread to make it leak
proof. All the pipe work shall be
tested at 1.6Mpa for 24 hours in
presence of the representative of the
Consultants. All MS & GI Materials
used in pipe work shall be painted
with two coats of prime coat of
approved quality by the
Engineer/Consultants.The product
shall be Ajay /Astral at India or NPL/
RFL Equivalent. 15mm dia, 2.00mm
thick
5.1 Sanitary N/A Supply, Fitting & 'Fixing of Toilet Nos. 422
fittings in Toilets with all hardwares
and consumables (SS Bush, SS
Screw, SS fancy Bush, Nut bolt,
Taflon, Solvent Cement, white
Cement, Gasket etc) required for
complete installation and function of
the fittings.Stop Cock : Supply, fitting
and fixing of CP oval type Stop Cock
of dia 13 mm with brass rising stem
screwed bonnet, solid wedge and
screwed end type. Stop cock shall be
suitable to withstand a pressure of
344 kPa. and shall be installed at
location shown in the drawing and as
per direction of the Engineer-in-
charge/Consultant. Product shall be
Model No. HDA0609MR2 HUIDA/
DOFINY, China or Equivalent Nazma
or Sharif from Bangladesh.
5.2 Sanitary N/A Supply, Fitting & 'Fixing of Toilet Nos. 1690
fittings in Toilets with all hardwares
and consumables (SS Bush, SS
Screw, SS fancy Bush, Nut bolt,
Taflon, Solvent Cement, white
Cement, Gasket etc) required for
complete installation and function of
the fittings.Angle Stop Cock :Supply,
fitting and fixing of CP oval type
Angle Stop Cock of dia 12 mm with
brass rising stem screwed bonnet,
solid wedge and screwed end type.
Angle Stop cock shall be suitable to
withstand a pressure of 344 kPa. and
shall be installed at location shown in
the drawing and as per direction of
the Engineer-in-
charge/Consultant.Supply, fitting and
fixing of Angle Stop Cock/ Valve,
Product shall be Model No. J855
HUIDA/ DOFINY, China or
Equivalent Nazma or Sharif from
Bangladesh.
5.3 Sanitary N/A Supply, Fitting & 'Fixing of Toilet Nos. 320
fittings in Toilets with all hardwares
and consumables (SS Bush, SS
Screw, SS fancy Bush, Nut bolt,
Taflon, Solvent Cement, white
Cement, Gasket etc) required for
complete installation and function of
the fittings.WC Shower Rose (Push
Shower): Supply, fitting and fixing of
Wc Shower Rose(with angle stop
cock) complete in all respect as per
drawing and direction of the
Engineer/Consultant. Product shall be
Model No. SP74021 HUIDA/
DOFINY, China or Equivalent Nazma
or Sharif from Bangladesh.
5.4 Sanitary N/A Supply, Fitting & 'Fixing of Toilet Nos. 210
fittings in Toilets with all hardwares
and consumables (SS Bush, SS
Screw, SS fancy Bush, Nut bolt,
Taflon, Solvent Cement, white
Cement, Gasket etc) required for
complete installation and function of
the fittings. Two in One Bib Cock :
Supply, Fitting and fixing of Two in
one bib Cock shall be constructed
with bronze and shall have rising stem
screwed bonnet, disc. and screwed
end type. Valve shall be installed at
location shown in the drawing and as
per direction of Consultant. Threaded
joint shall be made properly sealed.
Product shall be Model No.
HDA5270B HUIDA/ DOFINY, China
or Equivalent Nazma or Sharif from
Bangladesh.
5.5 Sanitary N/A Supply, Fitting & 'Fixing of Toilet Nos. 560
fittings in Toilets with all hardwares
and consumables (SS Bush, SS
Screw, SS fancy Bush, Nut bolt,
Taflon, Solvent Cement, white
Cement, Gasket etc) required for
complete installation and function of
the fittings.Open Tap/Bib Cock
:Supply, fitting and fixing of 12 mm
dia CP Open Tap complete in all
respect as per drawing and direction
of the Engineer/Consultant. Product
shall be Model No. HDA0604B
HUIDA/ DOFINY, China or
Equivalent Nazma or Sharif from
Bangladesh.
5.6 Sanitary N/A Supply, Fitting & 'Fixing of Toilet Nos. 150
fittings in Toilets with all hardwares
and consumables (SS Bush, SS
Screw, SS fancy Bush, Nut bolt,
Taflon, Solvent Cement, white
Cement, Gasket etc) required for
complete installation and function of
the fittings.Basin Pillar Cock :Supply,
fitting and fixing of 12 mm dia CP
Medal Headed Heavy deluxe body
Basin Pillar Cock shall be constructed
with brass rising stem screwed
bonnet, solid wedge and screwed
end type and shall be suitable to
withstand a pressure of 344 kPa. Pill
cock shall be installed at location
shown in the drawing and as per
direction of the Engineer-in-
charge/Consultant.Supply, fitting and
fixing of Basin Pillar Cock. Product
shall be Model No. HDA0608M
HUIDA/ DOFINY, China or
Equivalent Nazma or Sharif from
Bangladesh.
5.7 Sanitary N/A Supply, Fitting & 'Fixing of Toilet Nos. 361
fittings in Toilets with all hardwares
and consumables (SS Bush, SS
Screw, SS fancy Bush, Nut bolt,
Taflon, Solvent Cement, white
Cement, Gasket etc) required for
complete installation and function of
the fittings.Basin Mixture :Supply,
fitting fixing of 13 mm dia CP Basin
Mixture complete in all respect as per
drawing and direction of the
Engineer/Consultant. Basin Mixture,
Faucet with popup waste, Product
shall be Model No. HDA1811M
HUIDA/ DOFINY, China or
Equivalent Nazma or Sharif from
Bangladesh.
5.8 Sanitary N/A Supply, Fitting & 'Fixing of Toilet Nos. 126
fittings in Toilets with all hardwares
and consumables (SS Bush, SS
Screw, SS fancy Bush, Nut bolt,
Taflon, Solvent Cement, white
Cement, Gasket etc) required for
complete installation and function of
the fittings.Kitchen Mixture Cock
:Supply, fitting and fixing of 12 mm
dia CP Sink Mixture shall be
constructed with brass rising stem
(Nozzle type), solid wedge and
screwed end type. Valves shall be
capable to withstand a pressure of
344 kPa. Sink cock shall be installed
at location shown in the drawing and
as per direction of the Engineer-in-
charge/Consultant. Product shall be
Model No. HDA1304XH HUIDA/
DOFINY, China or Equivalent Nazma
or Sharif from Bangladesh.
5.9 Sanitary N/A Supply, Fitting & 'Fixing of Toilet Nos. 570
fittings in Toilets with all hardwares
and consumables (SS Bush, SS
Screw, SS fancy Bush, Nut bolt,
Taflon, Solvent Cement, white
Cement, Gasket etc) required for
complete installation and function of
the fittings.Bottle Trap :Supply, fitting
and fixing of Bottle Trap complete in
all respect as per drawing and
direction of the Engineer/Consultant.
Product shall be Model No. GD1002
HUIDA/ DOFINY, China or
Equivalent Nazma or Sharif from
Bangladesh.
6.1.a Sanitary N/A Supply, fitting and fixing of Toilet Nos. 390
fixtures of approved colour with all
hardwares and consumables required
for complete installation and function
of the fixtures.Washing Hand
BasinSupply, fitting and fixing of
Special coloured washing hand basin
with Angale stop cock, piller cock,
SS Connection pipe, CI wall
Brackets, SS Screw, SS Bush,
Solvent cement, thread tap, white
cement, Gasket etc. including making
holes and fitting in walls and mending
good the damages etc. complete in
all respect as per drawing and
direction of the Engineer/Consultant.
Wash Basin with Pedestal, Model no.
WB 30002, DOFINY/ HUIDA China
or Equivalent RAK /BISF from
Bangladesh.
6.1.b Sanitary N/A Supply, fitting and fixing of Toilet Nos. 120
fixtures of approved colour with all
hardwares and consumables required
for complete installation and function
of the fixtures.Washing Hand
BasinSupply, fitting and fixing of
Special coloured washing hand basin
with Angale stop cock, piller cock,
SS Connection pipe, CI wall
Brackets, SS Screw, SS Bush,
Solvent cement, thread tap, white
cement, Gasket etc. including making
holes and fitting in walls and mending
good the damages etc. complete in
all respect as per drawing and
direction of the Engineer/Consultant.
Counter Top Wash Basin, Model no.
WB 34003, DOFINY/ HUIDA China
or Equivalent RAK /BISF from
Bangladesh.
6.2 Sanitary N/A Supply, fitting and fixing of Toilet Nos. 126
fixtures of approved colour with all
hardwares and consumables required
for complete installation and function
of the fixtures.Kitchen Sink (Single
Bowl Single Tray)Supply, Fitting and
fixing of Super quality Stainless Steel
Kitchen Sink in position with heavy
type CI wall brackets, SS Screw,
Solvent cement, thread tap, white
cement, Gasket including making
holes in walls and fitting with CI wall
brackets and mending good the
damages etc. complete as per
direction of the Consultant. Kitchen
Sink (Single Bowl Single Tray) (
Model No. HDSC8706E of DOFINY/
HUIDA China or Equivalent Thailand.
6.3 Sanitary N/A Supply, fitting and fixing of Toilet Nos. 1310
fixtures of approved colour with all
hardwares and consumables required
for complete installation and function
of the fixtures.Steel Flexible
ConnectionSupply, fitting and fixing of
Steel connecting pipe of 12 mm dia
and 600 mm length with SS flare nut,
SS Bush, SS Fancy Bussh PVC
taflon and Socket on both end to
adapt 13 mm dia threaded G.I. Pipe
etc. complete in all respect as per
drawing and direction of the
Engineer/Consultant.Product shall be
of Model no. P23600SN, of
DOFINY/ HUIDA China or
Equivalent Nazma or Sharif from
Bangladesh
6.4.a Sanitary N/A Supply, fitting and fixing of Toilet Nos. 200
fixtures of approved colour with all
hardwares and consumables required
for complete installation and function
of the fixtures.Combi Closet
:Supplying, fitting and fixing Euroepan
type glazed Combi Closet,
700x410x795 mm size, approx. 34.5
kg weight, plastic seat cover and
preparing the base with cement
concrete and with wire mesh or rods
if necessary, in all floors including
making holes wherever required and
mending good the damages and
fitting, fixing, finishing complete with
all necessary fittings and connection
approved and accepted by the
Engineer.Combi Closet White (with
Low Down) Product shall be of
Model TL 10015A of DOFINY/
HUIDA China, China or Equivalent
RAK /BISF in Bangladesh.
6.4.b Sanitary N/A Supply, fitting and fixing of Toilet Nos. 120
fixtures of approved colour with all
hardwares and consumables required
for complete installation and function
of the fixtures.Combi Closet
:Supplying, fitting and fixing Euroepan
type glazed Combi Closet,
700x410x795 mm size, approx. 34.5
kg weight, plastic seat cover and
preparing the base with cement
concrete and with wire mesh or rods
if necessary, in all floors including
making holes wherever required and
mending good the damages and
fitting, fixing, finishing complete with
all necessary fittings and connection
approved and accepted by the
Engineer.Combi Closet White (with
Low down) Product shall be of Model
TL 10201C of DOFINY/ HUIDA
China or Equivalent RAK /BISF in
Bangladesh.
6.5 Sanitary N/A Supply, fitting and fixing of Toilet Nos. 121
fixtures of approved colour with all
hardwares and consumables required
for complete installation and function
of the fixtures.Long PanSupplying,
fitting and fixing Bangladesh patern,
570x445x290 mm long pan with foot-
rest inlclucing plastic low-down,
approx. 12kg by weight, made of
Vitreous China and preparing the
base of pan with cement mortar (1:4)
and with wire mesh or rods, if
necessary, in all floors including
making holes wherever required and
mending good the damages and
fitting, fixing, finishing etc. complete
with all necessary fittings and
connection approved and accepted
by the Engineer.Long pan White (with
Low down) Product shall be of Model
SP50031+CT40003 of DOFINY/
HUIDA China or Equivalent RAK
/BISF in Bangladesh.
6.6 Sanitary N/A Supply, fitting and fixing of Toilet Set 1
fixtures of approved colour with all
hardwares and consumables required
for complete installation and function
of the fixtures.UrinalSupply, fitting and
fixing of Integrated SenSor Standing
Urinal with heavy duty waste pipe
wherever required CI wall brackets,
SS Screw, Solvent cement, thread
tap, white cement, gasket including
making holes in wall and fitting
mending good the damages etc.
complete in all respect as per
drawing and direction of the
Engineer/Consultant. Product shall be
of DOFINY/ HUIDA China or
Equivalent RAK /BISF in
Bangladesh.
6.7.a Sanitary N/A Supply, fitting and fixing of Toilet Set 361
fixtures of approved colour with all
hardwares and consumables required
for complete installation and function
of the fixtures.Shower Assembly
Supply, Fitting and fixing of C.P.
Shower head complete with all
standard accessories and fittings.
Shower assembly shall be fitted to
pipe end by using approved sealing
compound to make the joint water
tight as per drawing and direction of
the Engineer/Consultant.Supply,
fitting and fixing of Concealed
Shower Mixture with Spout and
Shower Head, Model HD1814YR2,
of DOFINY/ HUIDA, China or
Equivalent Nazma or Sharif from
Bangladesh.
6.7.b Sanitary N/A Supply, fitting and fixing of Toilet Set 180
fixtures of approved colour with all
hardwares and consumables required
for complete installation and function
of the fixtures.Shower Assembly
Supply, Fitting and fixing of C.P.
Shower head complete with all
standard accessories and fittings.
Shower assembly shall be fitted to
pipe end by using approved sealing
compound to make the joint water
tight as per drawing and direction of
the Engineer/Consultant.Supply,
fitting and fixing of Fixed Shower
Head Product shall be of Model
HDDP2075 of DOFINY/ HUIDA,
China or Equivalent Nazma or Sharif
from Bangladesh.
6.8 Sanitary N/A Supply, fitting and fixing of Toilet Nos. 510
fixtures of approved colour with all
hardwares and consumables required
for complete installation and function
of the fixtures.Glass MirrorSupply,
Fitting and fixing of Beveled edge
plate glass mirror (Oval Glass Mirror)
fitted in wall with screws including
plastic plug, damp protection on back
etc. and shall be completed as per
direction of the Consultant.Product
shall be (Local Made of Size (500 X
900mm)
6.9 Sanitary N/A Supply, fitting and fixing of Toilet Nos. 510
fixtures of approved colour with all
hardwares and consumables required
for complete installation and function
of the fixtures.Glass Shelf Supply,
Fitting and fixing of super quality
600x125 mm coloured glass (plate)
shelf having 5mm thickness with
fancy C.P. brackets, screws and
frames including making holes in walls
and mending good the damages with
cement mortar (1:4) etc. all complete
as per direction of the Consultant.
Product shall be Glass Shel, Model
HDC 1802 of DOFINY, China, or
Equivalent .
6.10.a Sanitary N/A Supply, fitting and fixing of Toilet Nos. 430
fixtures of approved colour with all
hardwares and consumables required
for complete installation and function
of the fixtures.Towel Bar / Towel Ring
/ Towel Shelf Supply, fitting, fixing of
CP towel bar respectively complete
with CP wall bracket fitted on wall
plastic plug and screws as per
drawing and direction of the
Engineer-in-charge/Consultant.
Supply, fitting, fixing of CP Towel
Bar, Model HDC 1803 of DOFINY,
China or Equivalent Nazma or Sharif
from Bangladesh.
6.10.b Sanitary N/A Supply, fitting and fixing of Toilet Nos. 140
fixtures of approved colour with all
hardwares and consumables required
for complete installation and function
of the fixtures.Towel Bar / Towel Ring
/ Towel Shelf Supply, fitting, fixing of
CP towel bar respectively complete
with CP wall bracket fitted on wall
plastic plug and screws as per
drawing and direction of the
Engineer-in-charge/Consultant.
Supply, fitting, fixing of Towel Ring,
Model No. HDC 1807 of DOFINY,
China or Equivalent Nazma or Sharif
from Bangladesh.
6.11 Sanitary N/A Supply, fitting and fixing of Toilet Nos. 460
fixtures of approved colour with all
hardwares and consumables required
for complete installation and function
of the fixtures.Soap Case Supply,
fitting, fixing of S.S Soap Tray Model
HDC 1009 of DOFINY, China or
Equivalent Nazma or Sharif from
Bangladesh.
6.12 Sanitary N/A Supply, fitting and fixing of Toilet Nos. 440
fixtures of approved colour with all
hardwares and consumables required
for complete installation and function
of the fixtures.Toilet Paper Holder
Supply, fitting, fixing of S.S Toilet
Paper Holder, Model HDC 7008 of
DOFINY, China or Equivalent Nazma
or Sharif from Bangladesh
6.13 Sanitary N/A Supply, fitting and fixing of Toilet Nos. 130
fixtures of approved colour with all
hardwares and consumables required
for complete installation and function
of the fixtures.CP Coat HookSupply,
fitting, fixing of S.S Coat Hook
Complete with S.S bracket. shall be
fixed to the wall by using plastic bolt
and screws and as per direction of
the Engineer-in-charge /Consultant.
Product shall be of Robe Hook,
Model HDC 1810 of DOFINY, China
or Equivalent Nazma or Sharif from
Bangladesh
6.14.a Sanitary N/A Supply, fitting and fixing of Toilet Nos. 642
fixtures of approved colour with all
hardwares and consumables required
for complete installation and function
of the fixtures.SQUARE SHAPED
GRATING FLOOR DRAIN :Supply,
fitting and fixing of SS Square
Gratings shall be four piece type-
frame, perorated cover, strainer and
water seal cover. Grating cove shall
be hinge type. Floor Drain Model
HDFD 8821 of DOFINY,
China100mm dia SS Square Grating
Model HDFD 8821 of DOFINY,
China or Equivalent.
6.14.b Sanitary N/A Supply, fitting and fixing of Toilet Nos. 378
fixtures of approved colour with all
hardwares and consumables required
for complete installation and function
of the fixtures.SQUARE SHAPED
GRATING FLOOR DRAIN :Supply,
fitting and fixing of SS Square
Gratings shall be four piece type-
frame, perorated cover, strainer and
water seal cover. Grating cove shall
be hinge type. Floor Drain Model
HDFD 8821 of DOFINY, China50mm
dia SS Square Grating Model HDFD
8821 of DOFINY, China or
Equivalent.
6.15 Sanitary N/A Supply, fitting and fixing of Toilet Nos. 1
fixtures of approved colour with all
hardwares and consumables required
for complete installation and function
of the fixtures.Safety Accessories for
Disable ToiletSupply, fitting, fixing of
Safety Accessories for Disable Toilet
Handicap Bar Complete with all
goods shall be fixed to the wall by
using plastic bolt and screws and as
per direction of the Engineer-in-
charge /Consultant. Product shall be
of Model No. CT751, CT753, CT754
(3Nos) of COTTO, Thailand or
Equivalent.
6.16 Sanitary N/A Supply, fitting and fixing of Toilet Nos. 4
fixtures of approved colour with all
hardwares and consumables required
for complete installation and function
of the fixtures.Automatic Soap
DispenserSupply, fitting, fixing of
Soap dispenser complete with all
goods shall be fixed to the wall by
using plastic bolt and screws and as
per direction of the Engineer-in-
charge /Consultant. Product shall be
of Model No. HDC6014 of DOFINY,
China or Equivalent.
6.17 Sanitary N/A Supply, fitting and fixing of Toilet Nos. 4
fixtures of approved colour with all
hardwares and consumables required
for complete installation and function
of the fixtures. Automatic Hand Dryer
Supply, fitting, fixing of Automatic
Hand Dryer, Complete with all goods
shall be fixed to the wall by using
plastic bolt and screws and as per
direction of the Engineer-in-charge
/Consultant. Product shall be of
Model No. Model- HD 342 AC of
DOFINY, China or Equivalent.
7.1 Sanitary N/A Automatic Water Heater : Supply, Nos. 1
Instalation of Electric or Gas fired
water heater be made of stainless
steel sheet inside container with
seamless welding pressure tested to
leaks. Outside jackets shall be
sprayed with scratch and rust proof
high gloss backed enamel paint. The
heater shall be complete with
adjustable Thermostat (30°C to
80°C) and automatic pressure
release valve and all other required
accessories. The Water Heater shall
be of 'IEGA brand, Bangladesh 5
Gallon (Horizontal type)
7.2 Sanitary N/A Automatic Water Heater : Supply, Nos. 1
Instalation of Electric or Gas fired
water heater be made of stainless
steel sheet inside container with
seamless welding pressure tested to
leaks. Outside jackets shall be
sprayed with scratch and rust proof
high gloss backed enamel paint. The
heater shall be complete with
adjustable Thermostat (30°C to
80°C) and automatic pressure
release valve and all other required
accessories. The Water Heater shall
be of 'IEGA brand, Bangladesh 10
Gallon (Horizontal type)
8 Sanitary N/A CATCH PIT : Construction of Nos. 16
masonry Catch pits, inside
measurement (450 mm x 450 mm x
600 mm) with 250 mm thick brick
work in cement mortar (4:1) 100 mm
thick R.C.C. top (4:2:1) with the
necessary reinforcement.450mm x
450mm x 600mm
9.1 Sanitary N/A INSPECTION PIT: Construction of Nos. 60
masonry Inspection pits, inside
measurement (600 mm x 600 mm x
550 mm) with 250 mm thick brick
work in cement mortar (4:1) 100 mm
thick R.C.C. top (4:2:1) with the
necessary reinforcement.
9.2 Sanitary N/A INSPECTION PIT: Construction of Nos. 12
masonry Inspection pits, inside
measurement (760 mm x 760 mm x
760 mm) with 250 mm thick brick
work in cement mortar (4:1) 100 mm
thick R.C.C. top (4:2:1) with the
necessary reinforcement.
9.3 Sanitary N/A INSPECTION PIT: Construction of Nos. 4
masonry Inspection pits, inside
measurement (900 mm x 900 mm x
900 mm) with 250 mm thick brick
work in cement mortar (4:1) 100 mm
thick R.C.C. top (4:2:1) with the
necessary reinforcement.
10 Sanitary N/A C.I. COVER: Supply and installation Nos. 76
of heavy duty C.I. manhole covers of
550mm/600mm Clear opening with
frames (Havy type Minimum weight
of Cover to be 22kg to 28Kg) lock
type in top slab of inspection pits all
complete as per drawing and
direction of the Consultant. Product
shall be Manco / equivalent Brand.
11 Sanitary N/A WATER DISTRIBUTION PUMP Set 4
Supply, Installation, Testing and
Commissioning of single stage water
supply distribution system having a
capacity to handle 290 Gpm of water
against a head of 80 meter of wg.
The pump shall be complete with
coupled motor, coupling, motor guard
etc. Pump shall not be less than 60%
efficient. Pump motor shall be
capable to handle 30% to 120% of
rated flow. Supply shall be 400V/3
phase/50Hz. Pump shall be of USA/
UK/ JAPAN/ Germany/ Australia/
korea origin.
12 Sanitary N/A SUMP PUMP Supply, installation, Set 6
testing and commissioning of single
stage sump pump having a capacity
to handle 25 Gpm of water against a
head of 15 meter of wg. The pump
shall be complete with coupled motor,
coupling, motor guard etc. Pump shall
not be less than 60% efficient. Pump
motor shall be capable to handle 30%
to 120% of rated flow. Supply shall
be 400V/3 phase/50Hz. Pump shall
be of USA/ UK/ JAPAN/ Germany/
Australia/ korea origin.
13.1.a Sanitary N/A VALVES & FITTINGS: Supply, fitting Nos. 6
and fixing of Gate valve of 40mm dia
shall be bronze body and valve of
150mm dia shall be iron body to
withstand a water pressure of 200
PSIG. Valves shall be installed at
location as shown on the drawing
complete with consumable, materials
etc. Valves shall be of
USA/UK/Japan origin. 100mm dia
13.1.b Sanitary N/A VALVES & FITTINGS: Supply, fitting Nos. 8
and fixing of Gate valve of 40mm dia
shall be bronze body and valve of
150mm dia shall be iron body to
withstand a water pressure of 200
PSIG. Valves shall be installed at
location as shown on the drawing
complete with consumable, materials
etc. Valves shall be of
USA/UK/Japan origin. 80mm dia
13.1.c Sanitary N/A VALVES & FITTINGS: Supply, fitting Nos. 12
and fixing of Gate valve of 40mm dia
shall be bronze body and valve of
150mm dia shall be iron body to
withstand a water pressure of 200
PSIG. Valves shall be installed at
location as shown on the drawing
complete with consumable, materials
etc. Valves shall be of
USA/UK/Japan origin. 65mm dia
13.1.d Sanitary N/A VALVES & FITTINGS: Supply, fitting Nos. 60
and fixing of Gate valve of 40mm dia
shall be bronze body and valve of
150mm dia shall be iron body to
withstand a water pressure of 200
PSIG. Valves shall be installed at
location as shown on the drawing
complete with consumable, materials
etc. Valves shall be of
USA/UK/Japan origin. 50mm dia
13.1.e Sanitary N/A VALVES & FITTINGS: Supply, fitting Nos. 180
and fixing of Gate valve of 40mm dia
shall be bronze body and valve of
150mm dia shall be iron body to
withstand a water pressure of 200
PSIG. Valves shall be installed at
location as shown on the drawing
complete with consumable, materials
etc. Valves shall be of
USA/UK/Japan origin.40mm dia
13.1.f Sanitary N/A VALVES & FITTINGS: Supply, fitting Nos. 6
and fixing of Gate valve of 40mm dia
shall be bronze body and valve of
150mm dia shall be iron body to
withstand a water pressure of 200
PSIG. Valves shall be installed at
location as shown on the drawing
complete with consumable, materials
etc. Valves shall be of
USA/UK/Japan origin. 32mm dia
13.1.g Sanitary N/A VALVES & FITTINGS: Supply, fitting Nos. 290
and fixing of Gate valve of 40mm dia
shall be bronze body and valve of
150mm dia shall be iron body to
withstand a water pressure of 200
PSIG. Valves shall be installed at
location as shown on the drawing
complete with consumable, materials
etc. Valves shall be of
USA/UK/Japan origin. 25mm dia
13.1.h Sanitary N/A VALVES & FITTINGS: Supply, fitting Nos 160
and fixing of Gate valve of 40mm dia
shall be bronze body and valve of
150mm dia shall be iron body to
withstand a water pressure of 200
PSIG. Valves shall be installed at
location as shown on the drawing
complete with consumable, materials
etc. Valves shall be of
USA/UK/Japan origin. 20mm dia
13.1.i Sanitary N/A VALVES & FITTINGS: Supply, fitting Nos 20
and fixing of Gate valve of 40mm dia
shall be bronze body and valve of
150mm dia shall be iron body to
withstand a water pressure of 200
PSIG. Valves shall be installed at
location as shown on the drawing
complete with consumable, materials
etc. Valves shall be of
USA/UK/Japan origin. 15mm dia Ball
Valve
13.1.j Sanitary N/A VALVES & FITTINGS: Supply, fitting Nos 6
and fixing of Gate valve of 40mm dia
shall be bronze body and valve of
150mm dia shall be iron body to
withstand a water pressure of 200
PSIG. Valves shall be installed at
location as shown on the drawing
complete with consumable, materials
etc. Valves shall be of
USA/UK/Japan origin. 20mm dia air
relief valve
13.2.a Sanitary N/A GLOBE VALVE : Supply, fitting and Nos 6
fixing of Globe valve of 40mm dia
shall be bronze body and 150mm dia
shall be iron body to withstand a
water pressure of 200 PSIG, valve
shall be installed at location as shown
on the drawing complete with
consumable, accessories etc.Valves
shall be of USA/UK/Japan origin.100
mm dia
13.2.b Sanitary N/A GLOBE VALVE : Supply, fitting and Nos 12
fixing of Globe valve of 40mm dia
shall be bronze body and 150mm dia
shall be iron body to withstand a
water pressure of 200 PSIG, valve
shall be installed at location as shown
on the drawing complete with
consumable, accessories etc.Valves
shall be of USA/UK/Japan origin.50
mm dia
13.2.c Sanitary N/A GLOBE VALVE : Supply, fitting and Nos 50
fixing of Globe valve of 40mm dia
shall be bronze body and 150mm dia
shall be iron body to withstand a
water pressure of 200 PSIG, valve
shall be installed at location as shown
on the drawing complete with
consumable, accessories etc.Valves
shall be of USA/UK/Japan origin.40
mm dia
13.3 Sanitary N/A STRAINER : Supply, fitting and fixing Nos 4
of Strainer shall be cast iron body
flanged end type assembly complete
with internal stainless steel net,
companion flange, nut bolt, gasket, all
consumable and materials.Strainer
shall be of USA/UK/Japan origin.
100mm dia
13.4 Sanitary N/A CHECK VALVE : Supply, fitting and Nos 4
fixing of Check valve of iron body
shall flanged end lift check type
complete companion flange, nut bolt,
gasket, all consumable and
materials.Valves shall be of
USA/UK/Japan origin.100mm dia
13.5 Sanitary N/A FOOT VALVE : Supply, fitting and Nos 4
fixing of Foot valve shall be flanged
end/screwed end type with non-return
valve & strainer. Valves shall be of
USA/UK/Japan origin. 100mm dia
13.6 Sanitary N/A FLEXIBLE JOINT : Supply, fitting Nos 8
and fixing of Flexible joints shall be of
moulded neoprene shall be capable
and suitable to absorb shock and
system hammering at the line water
pressure of 200 psig complete with
flanged end, companion flanges,
adjustable screw etc. flexible joint
shall be installed at suction and
discharge side of pump or as shown
on the & shall be tested upto
satisfaction of the Consultant.
Flexible Joint shall be of
USA/UK/Japan origin. 100mm dia
13.7 Sanitary N/A FLOAT ASSEMBLY : Supply, fitting Nos 2
and fixing of float assembly suitable
to install on 65 mm dia supply pipe.
Float assembly shall be complete
with float valve, float etc.
complete.Float Assembly shall be of
USA/UK/Japan 100mm dia
13.8.a Sanitary N/A PRESSURE REDUCING VALVE : Nos 10
Supply, fitting and fixing of pressure
reducing valve on size 50 mm dia.
Pressure reducing valve shall be
suitable to deliver water at a pressure
of 7.5 psig (minimum) irrespective of
inlet pressure. (Inlet pressure shall be
80 to 60 psig) PRV Valves shall be of
USA/UK/Japan origin.50mm dia
13.8.b Sanitary N/A PRESSURE REDUCING VALVE : Nos 40
Supply, fitting and fixing of pressure
reducing valve on size 50 mm dia.
Pressure reducing valve shall be
suitable to deliver water at a pressure
of 7.5 psig (minimum) irrespective of
inlet pressure. (Inlet pressure shall be
80 to 60 psig) PRV Valves shall be of
USA/UK/Japan origin. 40mm dia
13.9 Sanitary N/A PRESSURE GAUGESupply, fitting Nos 4
and fixing of Pressure gauge shall be
100mm dial type complete with
adapter, pet cock, pressure snowbar
etc.
14.1 Sanitary N/A PUMP PANEL Supply, fitting, fixing Nos 2
of totally insulated (IP65) pump panel
complete with MCCB for pump,
ON/OFF push button, bus bar, run-
stop lamp, dry operation protection,
phase monitoring rules all complete.
Power panel shall house all incoming
and outgoing MCCB, MCB, bus-bar,
insulator, internal wiring etc.
complete. Panel shall be painted with
two coats of epoxy paint of approved
red colour over a coat of primer. All
electrical components shall be from
Siemens/Moellir. Water Supply Pump
Panel
14.2 Sanitary N/A PUMP PANEL Supply, fitting, fixing Nos 4
of totally insulated (IP65) pump panel
complete with MCCB for pump,
ON/OFF push button, bus bar, run-
stop lamp, dry operation protection,
phase monitoring rules all complete.
Power panel shall house all incoming
and outgoing MCCB, MCB, bus-bar,
insulator, internal wiring etc.
complete. Panel shall be painted with
two coats of epoxy paint of approved
red colour over a coat of primer. All
electrical components shall be from
Siemens/Moellir. Sump Pump Panel
15 Sanitary N/A WATER LEVEL CONTROLLER Set 8
Supply, installation, testing and
commissioning of water level
controller suitable to operate the
pumps on demand of water in over
head tank. Level controller will also
resist dry operation of the pump
when there is no water in under
ground water reservoir. water level
control electric cabel standard quality
supplied.
16 Sanitary N/A ELECTRICAL CABLE WORKS Job 2
Electrical works shall be complete
with supply and installation of all
cables, conduit, distribution board
etc. as per direction and drawing by
the consultant. Product shall be of
BBS or BRB Cable from Bangladesh
17 Sanitary N/A SEPTIC TANK 200 Users Septic Nos 2
Tank
18 Sanitary N/A SOAK WELL Construction of Soak Nos 2
Well of different sizes with 250mm
thick solid brick work and 250mm
honey comb brick work with cement
mortar (1:6) as per design and
drawings over RCC (1:2:4) well curb
with 1.5% reinforcement including
supplying and fixing 600mm dia water
sealed heavy type C.I. manhole cover
with locking arrangement filling the
well upto the required depth with
graded khoa and sand including
supplying and fabricating MS Rod
casting curing including necessary
earth work in excavation, side filling
and bailing out water including cost of
all materials etc. all complete as per
drawing, design and direction of the
Engineer/Consultant. 200 Users Soak
Well
19 Sanitary N/A "WASA CONNECTION Job 2
Arrangement of Wasa Connection
from the WASA Header to Building
Premises complete with Water Meter
with Inspection Pit or surface drain
for rain water line and all other
required accessories as per drawings
and direction of the Client/Consultant
and as per approval of the Wasa
Authority. All required formalities to
WASA shall be done by the
Contractor.
"
20 Sanitary N/A "TESTING & COMMISSIONING Job 2
After complete installation the system
shall be tested and commissioned as
per recommendation of the
manufacturer and standard. Piping
system shall be tested with pressure
in presence of the Client/Consultant.
All testing of electrical system shall
be done as per direction. Test
certification shall be taken from the
Engineer.
"
Grand
Total :

Bill of Quantities (Electrifical)

Table
Bill of Quantities
Name :
Unit Total Total
Item Unit Price Price Price Price
Item Code Measurement
Item Code Measurement
Group Description of Item Quantity
no. (if Unit In figures (BDT) In In In
any) Words Figures Words
(BDT) (BDT) (BDT)
1.a Electrifical N/A "Concealed conduit wiring for EACH 599
following point looping at the
switch board with earth terminal
including circuit wiring with IC-
2x1.5 sq.mm PVC insulated and
sheathed stranded cable (BYM) &
1.5 sq.mm PVC insulated
green/white coloured ECC wire
(BYA) through PVC conduit (Lira
brand or equivalent product of
other reputed manufacturer) of
minimum 25 mm dia & 1.5 mm wall
thickness complete with 18 SWG
GP sheet, pull box with 3mm thick
ebonite sheet cover, ceiling rose,
fixing materials etc.(without switch
& switchboard) as required
including mending the damages
good (all electrical contacts shall
be of brass/copper)
Cables manufactured by
Citizen/SQ/Paradise or equivalent
approved by the Engineer-in-
Charge. CL- CEILING LIGHT
Point"
1.b Electrifical N/A "Concealed conduit wiring for EACH 1570
following point looping at the
switch board with earth terminal
including circuit wiring with IC-
2x1.5 sq.mm PVC insulated and
sheathed stranded cable (BYM) &
1.5 sq.mm PVC insulated
green/white coloured ECC wire
(BYA) through PVC conduit (Lira
brand or equivalent product of
other reputed manufacturer) of
minimum 25 mm dia & 1.5 mm wall
thickness complete with 18 SWG
GP sheet, pull box with 3mm thick
ebonite sheet cover, ceiling rose,
fixing materials etc.(without switch
& switchboard) as required
including mending the damages
good (all electrical contacts shall
be of brass/copper)
Cables manufactured by
Citizen/SQ/Paradise or equivalent
approved by the Engineer-in-
Charge. WL- WALL LIGHT Point"
1.c Electrifical N/A "Concealed conduit wiring for EACH 745
following point looping at the
switch board with earth terminal
including circuit wiring with IC-
2x1.5 sq.mm PVC insulated and
sheathed stranded cable (BYM) &
1.5 sq.mm PVC insulated
green/white coloured ECC wire
(BYA) through PVC conduit (Lira
brand or equivalent product of
other reputed manufacturer) of
minimum 25 mm dia & 1.5 mm wall
thickness complete with 18 SWG
GP sheet, pull box with 3mm thick
ebonite sheet cover, ceiling rose,
fixing materials etc.(without switch
& switchboard) as required
including mending the damages
good (all electrical contacts shall
be of brass/copper)
Cables manufactured by
Citizen/SQ/Paradise or equivalent
approved by the Engineer-in-
Charge. CF- CEILING FAN
POINTS"
1.d Electrifical N/A "Concealed conduit wiring for EACH 799
following point looping at the
switch board with earth terminal
including circuit wiring with IC-
2x1.5 sq.mm PVC insulated and
sheathed stranded cable (BYM) &
1.5 sq.mm PVC insulated
green/white coloured ECC wire
(BYA) through PVC conduit (Lira
brand or equivalent product of
other reputed manufacturer) of
minimum 25 mm dia & 1.5 mm wall
thickness complete with 18 SWG
GP sheet, pull box with 3mm thick
ebonite sheet cover, ceiling rose,
fixing materials etc.(without switch
& switchboard) as required
including mending the damages
good (all electrical contacts shall
be of brass/copper)
Cables manufactured by
Citizen/SQ/Paradise or equivalent
approved by the Engineer-in-
Charge.CFC- CIRCULAR BOX
FOR CEILING"
1.e Electrifical N/A "Concealed conduit wiring for EACH 476
following point looping at the
switch board with earth terminal
including circuit wiring with IC-
2x1.5 sq.mm PVC insulated and
sheathed stranded cable (BYM) &
1.5 sq.mm PVC insulated
green/white coloured ECC wire
(BYA) through PVC conduit (Lira
brand or equivalent product of
other reputed manufacturer) of
minimum 25 mm dia & 1.5 mm wall
thickness complete with 18 SWG
GP sheet, pull box with 3mm thick
ebonite sheet cover, ceiling rose,
fixing materials etc.(without switch
& switchboard) as required
including mending the damages
good (all electrical contacts shall
be of brass/copper)
Cables manufactured by
Citizen/SQ/Paradise or equivalent
approved by the Engineer-in-
Charge.TL- TUBE LIGHT
POINTS"
1.f Electrifical N/A "Concealed conduit wiring for EACH 560
following point looping at the
switch board with earth terminal
including circuit wiring with IC-
2x1.5 sq.mm PVC insulated and
sheathed stranded cable (BYM) &
1.5 sq.mm PVC insulated
green/white coloured ECC wire
(BYA) through PVC conduit (Lira
brand or equivalent product of
other reputed manufacturer) of
minimum 25 mm dia & 1.5 mm wall
thickness complete with 18 SWG
GP sheet, pull box with 3mm thick
ebonite sheet cover, ceiling rose,
fixing materials etc.(without switch
& switchboard) as required
including mending the damages
good (all electrical contacts shall
be of brass/copper)
Cables manufactured by
Citizen/SQ/Paradise or equivalent
approved by the Engineer-in-
Charge.ML- MIRROR LIGHT
POINTS"
1.g Electrifical N/A "Concealed conduit wiring for EACH 490
following point looping at the
switch board with earth terminal
including circuit wiring with IC-
2x1.5 sq.mm PVC insulated and
sheathed stranded cable (BYM) &
1.5 sq.mm PVC insulated
green/white coloured ECC wire
(BYA) through PVC conduit (Lira
brand or equivalent product of
other reputed manufacturer) of
minimum 25 mm dia & 1.5 mm wall
thickness complete with 18 SWG
GP sheet, pull box with 3mm thick
ebonite sheet cover, ceiling rose,
fixing materials etc.(without switch
& switchboard) as required
including mending the damages
good (all electrical contacts shall
be of brass/copper)
Cables manufactured by
Citizen/SQ/Paradise or equivalent
approved by the Engineer-in-
Charge.EXF- EXHAUST FAN
POINTS"
1.h Electrifical N/A "Concealed conduit wiring for EACH 745
following point looping at the
switch board with earth terminal
including circuit wiring with IC-
2x1.5 sq.mm PVC insulated and
sheathed stranded cable (BYM) &
1.5 sq.mm PVC insulated
green/white coloured ECC wire
(BYA) through PVC conduit (Lira
brand or equivalent product of
other reputed manufacturer) of
minimum 25 mm dia & 1.5 mm wall
thickness complete with 18 SWG
GP sheet, pull box with 3mm thick
ebonite sheet cover, ceiling rose,
fixing materials etc.(without switch
& switchboard) as required
including mending the damages
good (all electrical contacts shall
be of brass/copper)
Cables manufactured by
Citizen/SQ/Paradise or equivalent
approved by the Engineer-in-
Charge.FAN COVER (7x7) "
1.i Electrifical N/A "Concealed conduit wiring for EACH 387
following point looping at the
switch board with earth terminal
including circuit wiring with IC-
2x1.5 sq.mm PVC insulated and
sheathed stranded cable (BYM) &
1.5 sq.mm PVC insulated
green/white coloured ECC wire
(BYA) through PVC conduit (Lira
brand or equivalent product of
other reputed manufacturer) of
minimum 25 mm dia & 1.5 mm wall
thickness complete with 18 SWG
GP sheet, pull box with 3mm thick
ebonite sheet cover, ceiling rose,
fixing materials etc.(without switch
& switchboard) as required
including mending the damages
good (all electrical contacts shall
be of brass/copper)
Cables manufactured by
Citizen/SQ/Paradise or equivalent
approved by the Engineer-in-
Charge.WCL- CEILING LIGHT
POINTS AT WET LOCATION "
1.j Electrifical N/A "Concealed conduit wiring for EACH 745
following point looping at the
switch board with earth terminal
including circuit wiring with IC-
2x1.5 sq.mm PVC insulated and
sheathed stranded cable (BYM) &
1.5 sq.mm PVC insulated
green/white coloured ECC wire
(BYA) through PVC conduit (Lira
brand or equivalent product of
other reputed manufacturer) of
minimum 25 mm dia & 1.5 mm wall
thickness complete with 18 SWG
GP sheet, pull box with 3mm thick
ebonite sheet cover, ceiling rose,
fixing materials etc.(without switch
& switchboard) as required
including mending the damages
good (all electrical contacts shall
be of brass/copper)
Cables manufactured by
Citizen/SQ/Paradise or equivalent
approved by the Engineer-in-
Charge.CEILING FAN "
2.a Electrifical N/A "Providing & fixing 250 volts. 5/6 EACH 853
amps. (minimum) concealed type
following switch / switch socket
mounted on required size 18 SWG
galvanized plain sheet board of
76.2 mm. (3"") depth all electrical
contacts shall be of brass/copper
gang switch Of following brand &
country of origin.
(MK England/HEGAR or
equivalent product of GERMANY
/ USA / UK / FRANCE / JAPAN /
ITALY / SWEDEN /
SWITZERLAND )or equivalent
approved by the Engineer-in-
Charge QS- 3PIN-15A SOCKET
AT SKIRTING LEVEL OR 10""
HEIGHT FROM FINISHED
FLOOR"
2.b Electrifical N/A "Providing & fixing 250 volts. 5/6 EACH 369
amps. (minimum) concealed type
following switch / switch socket
mounted on required size 18 SWG
galvanized plain sheet board of
76.2 mm. (3"") depth all electrical
contacts shall be of brass/copper
gang switch Of following brand &
country of origin.
(MK England/HEGAR or
equivalent product of GERMANY
/ USA / UK / FRANCE / JAPAN /
ITALY / SWEDEN /
SWITZERLAND )or equivalent
approved by the Engineer-in-
ChargeRS- 3PIN-13A SOCKET
AT 48"" HEIGHT FROM
FINISHED FLOOR"
2.c Electrifical N/A "Providing & fixing 250 volts. 5/6 EACH 495
amps. (minimum) concealed type
following switch / switch socket
mounted on required size 18 SWG
galvanized plain sheet board of
76.2 mm. (3"") depth all electrical
contacts shall be of brass/copper
gang switch Of following brand &
country of origin.
(MK England/HEGAR or
equivalent product of GERMANY
/ USA / UK / FRANCE / JAPAN /
ITALY / SWEDEN /
SWITZERLAND )or equivalent
approved by the Engineer-in-
Charge QL- 3PIN-15A SOCKET
AT LENTEL LEVEL HEIGHT"
2.d Electrifical N/A "Providing & fixing 250 volts. 5/6 EACH 145
amps. (minimum) concealed type
following switch / switch socket
mounted on required size 18 SWG
galvanized plain sheet board of
76.2 mm. (3"") depth all electrical
contacts shall be of brass/copper
gang switch Of following brand &
country of origin.
(MK England/HEGAR or
equivalent product of GERMANY
/ USA / UK / FRANCE / JAPAN /
ITALY / SWEDEN /
SWITZERLAND )or equivalent
approved by the Engineer-in-
Charge RY- 3PIN-13A SOCKET
AT 3'8"" HEIGHT FROM
FINISHED FLOOR"
2.e Electrifical N/A "Providing & fixing 250 volts. 5/6 EACH 590
amps. (minimum) concealed type
following switch / switch socket
mounted on required size 18 SWG
galvanized plain sheet board of
76.2 mm. (3"") depth all electrical
contacts shall be of brass/copper
gang switch Of following brand &
country of origin.
(MK England/HEGAR or
equivalent product of GERMANY
/ USA / UK / FRANCE / JAPAN /
ITALY / SWEDEN /
SWITZERLAND )or equivalent
approved by the Engineer-in-
Charge AS-DISH ANTENNA
SOCKET AT 3'8"" HEIGHT
FROM FINISHED FLOOR"
2.f Electrifical N/A "Providing & fixing 250 volts. 5/6 EACH 498
amps. (minimum) concealed type
following switch / switch socket
mounted on required size 18 SWG
galvanized plain sheet board of
76.2 mm. (3"") depth all electrical
contacts shall be of brass/copper
gang switch Of following brand &
country of origin.
(MK England/HEGAR or
equivalent product of GERMANY
/ USA / UK / FRANCE / JAPAN /
ITALY / SWEDEN /
SWITZERLAND )or equivalent
approved by the Engineer-in-
Charge TS- TELEPHONE
SOCKET AT 10"" HEIGHT
FROM FINISHED FLOOR"
2.g Electrifical N/A "Providing & fixing 250 volts. 5/6 EACH 267
amps. (minimum) concealed type
following switch / switch socket
mounted on required size 18 SWG
galvanized plain sheet board of
76.2 mm. (3"") depth all electrical
contacts shall be of brass/copper
gang switch Of following brand &
country of origin.
(MK England/HEGAR or
equivalent product of GERMANY
/ USA / UK / FRANCE / JAPAN /
ITALY / SWEDEN /
SWITZERLAND )or equivalent
approved by the Engineer-in-
ChargeNS- INTERNET SOCKET
AT 10"" HEIGHT FROM
FINISHED FLOOR"
2.h Electrifical N/A "Providing & fixing 250 volts. 5/6 EACH 139
amps. (minimum) concealed type
following switch / switch socket
mounted on required size 18 SWG
galvanized plain sheet board of
76.2 mm. (3"") depth all electrical
contacts shall be of brass/copper
gang switch Of following brand &
country of origin.
(MK England/HEGAR or
equivalent product of GERMANY
/ USA / UK / FRANCE / JAPAN /
ITALY / SWEDEN /
SWITZERLAND )or equivalent
approved by the Engineer-in-
Charge IC- INTERCOM
SOCKET AT 10"" HEIGHT
FROM FINISHED FLOOR"
2.i Electrifical N/A "Providing & fixing 250 volts. 5/6 EACH 459
amps. (minimum) concealed type
following switch / switch socket
mounted on required size 18 SWG
galvanized plain sheet board of
76.2 mm. (3"") depth all electrical
contacts shall be of brass/copper
gang switch Of following brand &
country of origin.
(MK England/HEGAR or
equivalent product of GERMANY
/ USA / UK / FRANCE / JAPAN /
ITALY / SWEDEN /
SWITZERLAND )or equivalent
approved by the Engineer-in-
ChargeGEYSER DP SWITCH
(20A) "
2.j Electrifical N/A "Providing & fixing 250 volts. 5/6 EACH 765
amps. (minimum) concealed type
following switch / switch socket
mounted on required size 18 SWG
galvanized plain sheet board of
76.2 mm. (3"") depth all electrical
contacts shall be of brass/copper
gang switch Of following brand &
country of origin.
(MK England/HEGAR or
equivalent product of GERMANY
/ USA / UK / FRANCE / JAPAN /
ITALY / SWEDEN /
SWITZERLAND )or equivalent
approved by the Engineer-in-
Charge CFR- CEILING FAN
DIMMER"
2.k Electrifical N/A "Providing & fixing 250 volts. 5/6 EACH 726
amps. (minimum) concealed type
following switch / switch socket
mounted on required size 18 SWG
galvanized plain sheet board of
76.2 mm. (3"") depth all electrical
contacts shall be of brass/copper
gang switch Of following brand &
country of origin.
(MK England/HEGAR or
equivalent product of GERMANY
/ USA / UK / FRANCE / JAPAN /
ITALY / SWEDEN /
SWITZERLAND )or equivalent
approved by the Engineer-in-
Charge 1 GANG SWITCH
BOARD"
2.l Electrifical N/A "Providing & fixing 250 volts. 5/6 EACH 661
amps. (minimum) concealed type
following switch / switch socket
mounted on required size 18 SWG
galvanized plain sheet board of
76.2 mm. (3"") depth all electrical
contacts shall be of brass/copper
gang switch Of following brand &
country of origin.
(MK England/HEGAR or
equivalent product of GERMANY
/ USA / UK / FRANCE / JAPAN /
ITALY / SWEDEN /
SWITZERLAND )or equivalent
approved by the Engineer-in-
Charge 2 GANG SWITCH
BOARD"
2.m Electrifical N/A "Providing & fixing 250 volts. 5/6 EACH 1093
amps. (minimum) concealed type
following switch / switch socket
mounted on required size 18 SWG
galvanized plain sheet board of
76.2 mm. (3"") depth all electrical
contacts shall be of brass/copper
gang switch Of following brand &
country of origin.
(MK England/HEGAR or
equivalent product of GERMANY
/ USA / UK / FRANCE / JAPAN /
ITALY / SWEDEN /
SWITZERLAND )or equivalent
approved by the Engineer-in-
Charge 3 GANG SWITCH
BOARD"
2.n Electrifical N/A "Providing & fixing 250 volts. 5/6 EACH 49
amps. (minimum) concealed type
following switch / switch socket
mounted on required size 18 SWG
galvanized plain sheet board of
76.2 mm. (3"") depth all electrical
contacts shall be of brass/copper
gang switch Of following brand &
country of origin.
(MK England/HEGAR or
equivalent product of GERMANY
/ USA / UK / FRANCE / JAPAN /
ITALY / SWEDEN /
SWITZERLAND )or equivalent
approved by the Engineer-in-
Charge 4 GANG SWITCH
BOARD"
2.o Electrifical N/A "Providing & fixing 250 volts. 5/6 EACH 37
amps. (minimum) concealed type
following switch / switch socket
mounted on required size 18 SWG
galvanized plain sheet board of
76.2 mm. (3"") depth all electrical
contacts shall be of brass/copper
gang switch Of following brand &
country of origin.
(MK England/HEGAR or
equivalent product of GERMANY
/ USA / UK / FRANCE / JAPAN /
ITALY / SWEDEN /
SWITZERLAND )or equivalent
approved by the Engineer-in-
Charge NJB- NETWORK
JUNCTION BOX"
2.p Electrifical N/A "Providing & fixing 250 volts. 5/6 EACH 37
amps. (minimum) concealed type
following switch / switch socket
mounted on required size 18 SWG
galvanized plain sheet board of
76.2 mm. (3"") depth all electrical
contacts shall be of brass/copper
gang switch Of following brand &
country of origin.
(MK England/HEGAR or
equivalent product of GERMANY
/ USA / UK / FRANCE / JAPAN /
ITALY / SWEDEN /
SWITZERLAND )or equivalent
approved by the Engineer-in-
Charge TJB- TELEPHONE
JUNCTION BOX"
2.q Electrifical N/A "Providing & fixing 250 volts. 5/6 EACH 37
amps. (minimum) concealed type
following switch / switch socket
mounted on required size 18 SWG
galvanized plain sheet board of
76.2 mm. (3"") depth all electrical
contacts shall be of brass/copper
gang switch Of following brand &
country of origin.
(MK England/HEGAR or
equivalent product of GERMANY
/ USA / UK / FRANCE / JAPAN /
ITALY / SWEDEN /
SWITZERLAND )or equivalent
approved by the Engineer-in-
Charge IJB- INTERCOM
JUNCTION BOX"
2.r Electrifical N/A "Providing & fixing 250 volts. 5/6 EACH 37
amps. (minimum) concealed type
following switch / switch socket
mounted on required size 18 SWG
galvanized plain sheet board of
76.2 mm. (3"") depth all electrical
contacts shall be of brass/copper
gang switch Of following brand &
country of origin.
(MK England/HEGAR or
equivalent product of GERMANY
/ USA / UK / FRANCE / JAPAN /
ITALY / SWEDEN /
SWITZERLAND )or equivalent
approved by the Engineer-in-
Charge AJB- ANTENA
JUNCTION BOX "
3.a Electrifical N/A "Providing & fixing 250V, 50 Hz EACH 2
grade following concealed type
sub-distribution board & floor
distribution board made of 18-
SWG MS sheet complete with
hinged type door, built-in type
locking arrangement, one no. 60 A
capacity bus-bar with required no.
of holes thereon on insulators at
both ends, copper blocks for
neutral and earth terminal,
SPMCBs having minimum
breaking capacity 6/10-KA with
thermal over current and
instantaneous electromagnetic
short ckt. release, necessary
arrangement for fixing of MCBs by
keeping its knobs out on the top
cover of the board in/c stove
enamel/gray hammer painting of
board etc.
With SPMCBS of AEG
(Germany), Dorman Smith
(England), MEM (UK), Siemens
(USA/Germany) or equivalent
approved by the Engineer-in-
Charge. Main Distribution Board"
3.b Electrifical N/A "Providing & fixing 250V, 50 Hz EACH 40
grade following concealed type
sub-distribution board & floor
distribution board made of 18-
SWG MS sheet complete with
hinged type door, built-in type
locking arrangement, one no. 60 A
capacity bus-bar with required no.
of holes thereon on insulators at
both ends, copper blocks for
neutral and earth terminal,
SPMCBs having minimum
breaking capacity 6/10-KA with
thermal over current and
instantaneous electromagnetic
short ckt. release, necessary
arrangement for fixing of MCBs by
keeping its knobs out on the top
cover of the board in/c stove
enamel/gray hammer painting of
board etc.
With SPMCBS of AEG
(Germany), Dorman Smith
(England), MEM (UK), Siemens
(USA/Germany) or equivalent
approved by the Engineer-in-
Charge. FDB- FLOOR
DISTRIBUTION BOARD "
3.c Electrifical N/A "Providing & fixing 250V, 50 Hz EACH 148
grade following concealed type
sub-distribution board & floor
distribution board made of 18-
SWG MS sheet complete with
hinged type door, built-in type
locking arrangement, one no. 60 A
capacity bus-bar with required no.
of holes thereon on insulators at
both ends, copper blocks for
neutral and earth terminal,
SPMCBs having minimum
breaking capacity 6/10-KA with
thermal over current and
instantaneous electromagnetic
short ckt. release, necessary
arrangement for fixing of MCBs by
keeping its knobs out on the top
cover of the board in/c stove
enamel/gray hammer painting of
board etc.
With SPMCBS of AEG
(Germany), Dorman Smith
(England), MEM (UK), Siemens
(USA/Germany) or equivalent
approved by the Engineer-in-
Charge. SDB-SUB
DISTRIBUTION BOARD"
4.a Electrifical N/A "Providing & fixing on a prepared EACH 2012
board 220 volt grade following
Single-pole Miniature Circuit
Breaker (SPMCB) and 500 volt
Triple-pole moulded case Circuit
Breaker (TPMCCB) with thermal
over-current and instantaneous
electromagnetic short circuit
release provision.
Brand and Country of origin of SP
MCB & TPMCCB are ABB (Italy),
LEGRAND (France/Italy), MEM
(UK), or equivalent approved by
the Engineering-in-Charge. 10
APMS SP MCB (6kA)"
4.b Electrifical N/A "Providing & fixing on a prepared EACH 711
board 220 volt grade following
Single-pole Miniature Circuit
Breaker (SPMCB) and 500 volt
Triple-pole moulded case Circuit
Breaker (TPMCCB) with thermal
over-current and instantaneous
electromagnetic short circuit
release provision.
Brand and Country of origin of SP
MCB & TPMCCB are ABB (Italy),
LEGRAND (France/Italy), MEM
(UK), or equivalent approved by
the Engineering-in-Charge. 16
APMS SP MCB (6kA)"
4.c Electrifical N/A "Providing & fixing on a prepared EACH 498
board 220 volt grade following
Single-pole Miniature Circuit
Breaker (SPMCB) and 500 volt
Triple-pole moulded case Circuit
Breaker (TPMCCB) with thermal
over-current and instantaneous
electromagnetic short circuit
release provision.
Brand and Country of origin of SP
MCB & TPMCCB are ABB (Italy),
LEGRAND (France/Italy), MEM
(UK), or equivalent approved by
the Engineering-in-Charge. 25
APMS DP MCB (6kA)"
4.d Electrifical N/A "Providing & fixing on a prepared EACH 294
board 220 volt grade following
Single-pole Miniature Circuit
Breaker (SPMCB) and 500 volt
Triple-pole moulded case Circuit
Breaker (TPMCCB) with thermal
over-current and instantaneous
electromagnetic short circuit
release provision.
Brand and Country of origin of SP
MCB & TPMCCB are ABB (Italy),
LEGRAND (France/Italy), MEM
(UK), or equivalent approved by
the Engineering-in-Charge. 63
APMS DP MCB (6kA)"
4.e Electrifical N/A "Providing & fixing on a prepared EACH 45
board 220 volt grade following
Single-pole Miniature Circuit
Breaker (SPMCB) and 500 volt
Triple-pole moulded case Circuit
Breaker (TPMCCB) with thermal
over-current and instantaneous
electromagnetic short circuit
release provision.
Brand and Country of origin of SP
MCB & TPMCCB are ABB (Italy),
LEGRAND (France/Italy), MEM
(UK), or equivalent approved by
the Engineering-in-Charge. 80
APMS TP MCCB (18kA) "
5.a Electrifical N/A "Concealed conduit wiring with RFT 89702.4
following PVC insulated and
sheathed stranded cable (BYM) &
PVC insulated green/white
coloured ECC wire (BYA) through
PVC conduit of reputed
manufacturer complete with 18
SWG GP sheet and pull box with
3mm thick ebonite sheet cover,
fixing materials etc. as required
including mending the damages
good. All electrical contacts shall
be of brass/copper connected
through connector or soldering ( no
twisting shall be allowed) and
cables shall be manufactured and
tested according to relavent
IEC/BDS/BS/VDE standards and
as per detailed specification
mentioned in Annexure-A. The
work shall be carried out as per
direction/approval/acceptance of
the Engineer:
Cables manufactured by
Citizen/SQ/Paradise or equivalent
approved by the Engineering-in-
Charge. BYA 1CX1X1.5 mm2
RED LIGHTING LIVE CABLE "
5.b Electrifical N/A "Concealed conduit wiring with RFT 89702.4
following PVC insulated and
sheathed stranded cable (BYM) &
PVC insulated green/white
coloured ECC wire (BYA) through
PVC conduit of reputed
manufacturer complete with 18
SWG GP sheet and pull box with
3mm thick ebonite sheet cover,
fixing materials etc. as required
including mending the damages
good. All electrical contacts shall
be of brass/copper connected
through connector or soldering ( no
twisting shall be allowed) and
cables shall be manufactured and
tested according to relavent
IEC/BDS/BS/VDE standards and
as per detailed specification
mentioned in Annexure-A. The
work shall be carried out as per
direction/approval/acceptance of
the Engineer:
Cables manufactured by
Citizen/SQ/Paradise or equivalent
approved by the Engineering-in-
Charge. BYA 1CX1X1.5 mm2
BLACK LIGHTING NEUTRAL
CABLE "
5.c Electrifical N/A "Concealed conduit wiring with RFT 39031.68
following PVC insulated and
sheathed stranded cable (BYM) &
PVC insulated green/white
coloured ECC wire (BYA) through
PVC conduit of reputed
manufacturer complete with 18
SWG GP sheet and pull box with
3mm thick ebonite sheet cover,
fixing materials etc. as required
including mending the damages
good. All electrical contacts shall
be of brass/copper connected
through connector or soldering ( no
twisting shall be allowed) and
cables shall be manufactured and
tested according to relavent
IEC/BDS/BS/VDE standards and
as per detailed specification
mentioned in Annexure-A. The
work shall be carried out as per
direction/approval/acceptance of
the Engineer:
Cables manufactured by
Citizen/SQ/Paradise or equivalent
approved by the Engineering-in-
Charge. BYA 1CX1X2.5 mm2
RED POWER LIVE CABLE "
5.d Electrifical N/A "Concealed conduit wiring with RFT 39031.68
following PVC insulated and
sheathed stranded cable (BYM) &
PVC insulated green/white
coloured ECC wire (BYA) through
PVC conduit of reputed
manufacturer complete with 18
SWG GP sheet and pull box with
3mm thick ebonite sheet cover,
fixing materials etc. as required
including mending the damages
good. All electrical contacts shall
be of brass/copper connected
through connector or soldering ( no
twisting shall be allowed) and
cables shall be manufactured and
tested according to relavent
IEC/BDS/BS/VDE standards and
as per detailed specification
mentioned in Annexure-A. The
work shall be carried out as per
direction/approval/acceptance of
the Engineer:
Cables manufactured by
Citizen/SQ/Paradise or equivalent
approved by the Engineering-in-
Charge. BYA 1CX1X2.5 mm2
BLACK NEUTRAL CABLE "
5.e Electrifical N/A "Concealed conduit wiring with RFT 39515.8
following PVC insulated and
sheathed stranded cable (BYM) &
PVC insulated green/white
coloured ECC wire (BYA) through
PVC conduit of reputed
manufacturer complete with 18
SWG GP sheet and pull box with
3mm thick ebonite sheet cover,
fixing materials etc. as required
including mending the damages
good. All electrical contacts shall
be of brass/copper connected
through connector or soldering ( no
twisting shall be allowed) and
cables shall be manufactured and
tested according to relavent
IEC/BDS/BS/VDE standards and
as per detailed specification
mentioned in Annexure-A. The
work shall be carried out as per
direction/approval/acceptance of
the Engineer:
Cables manufactured by
Citizen/SQ/Paradise or equivalent
approved by the Engineering-in-
Charge. BYA 1CX1X4 mm2
GREEN ECC CABLE "
5.f Electrifical N/A "Concealed conduit wiring with RFT 39770.9
following PVC insulated and
sheathed stranded cable (BYM) &
PVC insulated green/white
coloured ECC wire (BYA) through
PVC conduit of reputed
manufacturer complete with 18
SWG GP sheet and pull box with
3mm thick ebonite sheet cover,
fixing materials etc. as required
including mending the damages
good. All electrical contacts shall
be of brass/copper connected
through connector or soldering ( no
twisting shall be allowed) and
cables shall be manufactured and
tested according to relavent
IEC/BDS/BS/VDE standards and
as per detailed specification
mentioned in Annexure-A. The
work shall be carried out as per
direction/approval/acceptance of
the Engineer:
Cables manufactured by
Citizen/SQ/Paradise or equivalent
approved by the Engineering-in-
Charge. BYA 1CX1X10 mm2
RED ECC CABLE "
5.g Electrifical N/A "Concealed conduit wiring with RFT 38770.9
following PVC insulated and
sheathed stranded cable (BYM) &
PVC insulated green/white
coloured ECC wire (BYA) through
PVC conduit of reputed
manufacturer complete with 18
SWG GP sheet and pull box with
3mm thick ebonite sheet cover,
fixing materials etc. as required
including mending the damages
good. All electrical contacts shall
be of brass/copper connected
through connector or soldering ( no
twisting shall be allowed) and
cables shall be manufactured and
tested according to relavent
IEC/BDS/BS/VDE standards and
as per detailed specification
mentioned in Annexure-A. The
work shall be carried out as per
direction/approval/acceptance of
the Engineer:
Cables manufactured by
Citizen/SQ/Paradise or equivalent
approved by the Engineering-in-
Charge. BYA 1CX1X10 mm2
GREEN ECC CABLE "
5.h Electrifical N/A "Concealed conduit wiring with RFT 38770.9
following PVC insulated and
sheathed stranded cable (BYM) &
PVC insulated green/white
coloured ECC wire (BYA) through
PVC conduit of reputed
manufacturer complete with 18
SWG GP sheet and pull box with
3mm thick ebonite sheet cover,
fixing materials etc. as required
including mending the damages
good. All electrical contacts shall
be of brass/copper connected
through connector or soldering ( no
twisting shall be allowed) and
cables shall be manufactured and
tested according to relavent
IEC/BDS/BS/VDE standards and
as per detailed specification
mentioned in Annexure-A. The
work shall be carried out as per
direction/approval/acceptance of
the Engineer:
Cables manufactured by
Citizen/SQ/Paradise or equivalent
approved by the Engineering-in-
Charge. BYA 1CX1X10 mm2
BLACK ECC CABLE "
6.a Electrifical N/A "Supply, Installation, Testing & EACH 80
Commissioning all type of Security
System Digital PABX Systems,
PA Systems,CCTV, Cat-6 Cable,
Rj-6 Co-axial Cable including all
typr of accessories.
Country of origin: Thailand/Japan/
UK/Taiwan/Spain or equivalent
approved by the Engineer-in-
Charge. PA SYSTEM WALL
MOUNTED "
6.b Electrifical N/A "Supply, Installation, Testing & EACH 8
Commissioning all type of Security
System Digital PABX Systems,
PA Systems,CCTV, Cat-6 Cable,
Rj-6 Co-axial Cable including all
typr of accessories.
Country of origin: Thailand/Japan/
UK/Taiwan/Spain or equivalent
approved by the Engineer-in-
Charge. PABX (24 LINE)"
6.c Electrifical N/A "Supply, Installation, Testing & EACH 128
Commissioning all type of Security
System Digital PABX Systems,
PA Systems,CCTV, Cat-6 Cable,
Rj-6 Co-axial Cable including all
typr of accessories.
Country of origin: Thailand/Japan/
UK/Taiwan/Spain or equivalent
approved by the Engineer-in-
Charge. BULLET TYPE
CAMERA 1 MP "
6.d Electrifical N/A "Supply, Installation, Testing & EACH 12
Commissioning all type of Security
System Digital PABX Systems,
PA Systems,CCTV, Cat-6 Cable,
Rj-6 Co-axial Cable including all
typr of accessories.
Country of origin: Thailand/Japan/
UK/Taiwan/Spain or equivalent
approved by the Engineer-in-
Charge. DVR (16 CHANNEL)"
6.e Electrifical N/A "Supply, Installation, Testing & METER 66876
Commissioning all type of Security
System Digital PABX Systems,
PA Systems,CCTV, Cat-6 Cable,
Rj-6 Co-axial Cable including all
typr of accessories.
Country of origin: Thailand/Japan/
UK/Taiwan/Spain or equivalent
approved by the Engineer-in-
Charge. RJ6 Co-axial CABLE
(For Dish)"
6.f Electrifical N/A "Supply, Installation, Testing & METER 31765.8
Commissioning all type of Security
System Digital PABX Systems,
PA Systems,CCTV, Cat-6 Cable,
Rj-6 Co-axial Cable including all
typr of accessories.
Country of origin: Thailand/Japan/
UK/Taiwan/Spain or equivalent
approved by the Engineer-in-
Charge. CAT 6 CABLE FOR
CAMERA"
7 Electrifical N/A "Supply and fixing of ENERGY EACH 1570
SAVINGS LAMP (CFL)
(230V/250V, 50Hz) (Osram/
Philips /Energypac/
Corona/Havells/ GE Edision/
MEP/ Metro / Harmonics (China)
or Equivalent approved by the
Engineer-in-Charge.)
a) 23 watt Spiral type lamps B-22"
8.a Electrifical N/A Providing & fixing the Double lamp EACH 599
bath-room light fitting of following
manufacturers (as per picture
No.4.3) consisting of oxidized
/golden or chromium plated brass
bracket/ base and carrier,
cylindrical glass shade of minimum
dia 80mm ( minimum total length of
fitting 350mm), brass holder, earth
terminal, necessary wiring with 2 x
0.4 sq.mm stranded PVC
insulated flexible FRcable etc.
complete (except lamp) of
following model & as per sample
approved by the Engineer.
CEILING LIGHT (LED)
8.b Electrifical N/A Providing & fixing fancy single EACH 250
bracket light fitting of the following
manufacturers consisting of
designed pitcher type fancy glass
shade, oxidized or chromium
plated or golden decorative and
designed brass bracket, brass
holder, earth terminal, necessary
wiring with 2 x 0.4 sq.mm stranded
PVC insulated flexible cable etc.
complete (except lamp) of
following model & as per sample
approved by the Engineer-in-
charge.Asha ACS BS-3277-G-
2577 P or Crescent cat. No. CB-
443-675P or Gloria cat. No.
GWB-2667-1847 or Shwash cat.
No. SCS-180 DT 749 or
equivalent approved by the
Engineering-in-Charge.
9.a Electrifical N/A Providing and Laying of following FEET 38000
PVC pipe, socket, tap,band, srew,
royal bolt, royal plug(Lira brand or
equivalent product of other reputed
manufacturer) embedded in wall/
column/ceiling/floor etc. with all
accessories, 18 SWG G.P sheet
pull box with 3mm thick ebonite
sheet cover, fixing materials etc.
as required including mending the
damages good. PVC PIPE (3/4
FEET)
9.b Electrifical N/A Providing and Laying of following DOZEN 500
PVC pipe, socket, tap,band, srew,
royal bolt, royal plug(Lira brand or
equivalent product of other reputed
manufacturer) embedded in wall/
column/ceiling/floor etc. with all
accessories, 18 SWG G.P sheet
pull box with 3mm thick ebonite
sheet cover, fixing materials etc.
as required including mending the
damages good. ROYAL PLUG
9.c Electrifical N/A Providing and Laying of following DOZEN 600
PVC pipe, socket, tap,band, srew,
royal bolt, royal plug(Lira brand or
equivalent product of other reputed
manufacturer) embedded in wall/
column/ceiling/floor etc. with all
accessories, 18 SWG G.P sheet
pull box with 3mm thick ebonite
sheet cover, fixing materials etc.
as required including mending the
damages good. PVC SOCKET
9.d Electrifical N/A Providing and Laying of following FEET 6500
PVC pipe, socket, tap,band, srew,
royal bolt, royal plug(Lira brand or
equivalent product of other reputed
manufacturer) embedded in wall/
column/ceiling/floor etc. with all
accessories, 18 SWG G.P sheet
pull box with 3mm thick ebonite
sheet cover, fixing materials etc.
as required including mending the
damages good. PVC PIPE (1
FEET)
9.e Electrifical N/A Providing and Laying of following DOZEN 700
PVC pipe, socket, tap,band, srew,
royal bolt, royal plug(Lira brand or
equivalent product of other reputed
manufacturer) embedded in wall/
column/ceiling/floor etc. with all
accessories, 18 SWG G.P sheet
pull box with 3mm thick ebonite
sheet cover, fixing materials etc.
as required including mending the
damages good. PVC BAND (1
INCH)
9.f Electrifical N/A Providing and Laying of following DOZEN 400
PVC pipe, socket, tap,band, srew,
royal bolt, royal plug(Lira brand or
equivalent product of other reputed
manufacturer) embedded in wall/
column/ceiling/floor etc. with all
accessories, 18 SWG G.P sheet
pull box with 3mm thick ebonite
sheet cover, fixing materials etc.
as required including mending the
damages good. PVC BAND (3/4
INCH)
9.g Electrifical N/A Providing and Laying of following EACH 1570
PVC pipe, socket, tap,band, srew,
royal bolt, royal plug(Lira brand or
equivalent product of other reputed
manufacturer) embedded in wall/
column/ceiling/floor etc. with all
accessories, 18 SWG G.P sheet
pull box with 3mm thick ebonite
sheet cover, fixing materials etc.
as required including mending the
damages good. ROYAL BOLT
9.h Electrifical N/A Providing and Laying of following EACH 2500
PVC pipe, socket, tap,band, srew,
royal bolt, royal plug(Lira brand or
equivalent product of other reputed
manufacturer) embedded in wall/
column/ceiling/floor etc. with all
accessories, 18 SWG G.P sheet
pull box with 3mm thick ebonite
sheet cover, fixing materials etc.
as required including mending the
damages good. ALL SCREW
9.i Electrifical N/A Providing and Laying of following DOZEN 700
PVC pipe, socket, tap,band, srew,
royal bolt, royal plug(Lira brand or
equivalent product of other reputed
manufacturer) embedded in wall/
column/ceiling/floor etc. with all
accessories, 18 SWG G.P sheet
pull box with 3mm thick ebonite
sheet cover, fixing materials etc.
as required including mending the
damages good. PVC TAP
(RED+YELLOW+BLUE+BLACK)
10 Electrifical N/A SUB ELECTRIC METER EACH 272

11 Electrifical N/A Supply and fixing 4'-40 watt EACH 238


FLUORESCENT LAMP
(230V/250V, 50Hz)(Eastern/GE/
Philips/ Osram/ Rangs/Transtec or
Equivalent approved by the
Engineer-in-Charge)
12 Electrifical N/A Providing & Installation of EACH 270
Standard Telephone set for
Intercom with push button, redial,
volume control, incoming indicator,
tone/plus switch and memory,
dialing key etc. complete as
required (Country of origin
Thailand/Japan/UK/ Taiwan/Spain
or any EU Countries sample
approved by the Engineer-in-
Charge.
Grand
Total :

Bill of Quantities (SUPPLY, INSTALLATION, TESTING & COMMISSIONING OF FIRE DETECTION AND ALARM SYSTEM)

Table
Bill of Quantities
Name :
Unit Total Total
Item Unit Price Price Price Price
Item Code Measurement
Group Description of Item Quantity
no. (if Unit In In In
In figures (BDT)
any) Words Figures Words
(BDT) (BDT) (BDT)
1 SUPPLY, N/A FIRE ALARM Set 2
INSTALLATION, CONTROL PANEL :
TESTING & Import, Supply,
COMMISSIONING Installation, Testing &
OF FIRE ommissioning of
DETECTION AND Intelligent Addressable
ALARM SYSTEM Micro processor Based
modular and
expandable Fire Alarm
Control Panel with
voice Evacutation
system and heavy
gauged sheet steel
painted with red color
as fire code approved.
The control and
indicating panel shall be
wall-mounted type with
front panel displays and
controls. The
Addressable panel shall
be capable to handle
200 devices per loop.
Presently but future
provision shall be
expandable upto 1500
devices. complete
network having
addressable detection
and alarm system. The
panel shall have LED
indicator for fire, fault
indicator, power-supply
unit, alarm silence,
Liquid Crystal Display.
The panel shall be
complete with battery
with trickle charger.
Battery shall be suitable
to provide power for the
total system for at least
30 minute after an
interruption of 24 hours.
Product shall be
Johsnson Control,
Honeywell, Simplex,
Nittan, Notifire, of UL,
ULC, FM listed. Origin
USA/UK/Canada/Japan
/Maxico. Or their
globally Located
Manufacturing
UnitsInstallation of Fire
Alarm Master Panel
shall be at location
shown in the drawing
and shall be as per
recommendation of the
manufacturer
2 SUPPLY, N/A REPEATER PANEL : Sets 2
INSTALLATION, Import and Supply of
TESTING & Repeater panel shall be
COMMISSIONING suitable to indicate
OF FIRE location of fire as
DETECTION AND recorded in the Fire
ALARM SYSTEM Alarm Master panel at
a remote location. The
repeater panel shall
also be complete with
hooter. Product shall be
UL, ULC, FM listed &
Origin USA/UK/Canada
/Mexico. Installation of
Repeater panel shall be
at location shown in the
drawing and shall be as
per recommendation of
the manufacturer
3 SUPPLY, N/A Smoke Detector Import Nos. 20
INSTALLATION, and Supply of
TESTING & Intelligent Addressable
COMMISSIONING Smoke Detector with
OF FIRE standard base
DETECTION AND photoelectric Smoke
ALARM SYSTEM Detector of two wire
system suitable to
mount Wall or Ceiling
and shall be complete
with detector base and
all mountings. The unit
shall be capable of
rapid detection of
visible and invisible
smoke and shall have
two chambers to
eliminate false alarms
and shall have latching
LED. Power supply
shall be 24V DC. Unit
shall be complete with
mounting base & EOL
resistor and shall be
suitable for 2-wire
installation. Product
shall be UL, ULC, FM
listed & Origin :
USA/UK/Canada
/Mexico/ Taiwan. or
their global locations.
4 SUPPLY, N/A Heat Detector Import Nos. 120
INSTALLATION, and Supply of
TESTING & Intelligent Addressable
COMMISSIONING Heat Detector with
OF FIRE standard base of two-
DETECTION AND wire system suitable to
ALARM SYSTEM mount on ceiling/wall
surface and shall be
complete with detector
base, visual indication,
All mountings.
Construction shall be
with self-extinguishing
thermo-plastic rated at
105°C and shall be
extremely strong. Wall
mounted heat detectors
shall be at a height of
7? from the floor level.
The detector shall
respond fire when rate
of rise of temperature
is above 8°C per
minute. Power supply
shall be 24V DC.
Product shall be UL,
ULC, FM listed &
Origin :
USA/UK/Canada
/Mexico/ Taiwan. or
their global locations
5 SUPPLY, N/A Multi-Sensor Detector : Nos. 12
INSTALLATION, Import and Supply of
TESTING & Intelligent Addressable
COMMISSIONING Multi-Sensor Detector
OF FIRE with standard base
DETECTION AND photoelectric Detector
ALARM SYSTEM of two wire system
suitable to mount Wall
or Ceiling and shall be
complete with detector
base and all mountings.
The unit shall be
capable of rapid
detection of visible and
invisible Multi-Sensor
Detector and shall have
two chambers to
eliminate false alarms
and shall have latching
LED. Power supply
shall be 24V DC. Unit
shall be complete with
mounting base & EOL
resistor and shall be
suitable for 2-wire
installation. Product
shall be UL, ULC, FM
listed & Origin :
USA/UK/Canada
/Mexico/ Taiwan. or
their global locations.
6.1 SUPPLY, N/A Surface mounted type Nos. 46
INSTALLATION, Electronic Horn Strobe
TESTING & Light shall be suitable
COMMISSIONING to produce 90dB of
OF FIRE sound at a distance of
DETECTION AND 1 meter. Bell shall be
ALARM SYSTEM pressed steel gong with
robust striker
mechanism complete
monitor module and all
other accessories.
Power supply shall be
24V DC. Product shall
be UL, ULC, FM listed
& Origin :
USA/UK/Canada
/Mexico/ Taiwan/
Korea/ Singapore. i)
Electronic Horn with
Strobe Light
6.2 SUPPLY, N/A Surface mounted type Nos. 4
INSTALLATION, Electronic Horn Strobe
TESTING & Light shall be suitable
COMMISSIONING to produce 90dB of
OF FIRE sound at a distance of
DETECTION AND 1 meter. Bell shall be
ALARM SYSTEM pressed steel gong with
robust striker
mechanism complete
monitor module and all
other accessories.
Power supply shall be
24V DC. Product shall
be UL, ULC, FM listed
& Origin :
USA/UK/Canada
/Mexico/ Taiwan/
Korea/ Singapore. ii)
Electronic Horn Strobe
7 SUPPLY, N/A Manual Pull Station Nos. 44
INSTALLATION, Import and Supply of
TESTING & Intelligent Addressable
COMMISSIONING Manual Pull Station of
OF FIRE Surface mounted type
DETECTION AND Manual Pull Station
ALARM SYSTEM shall be metal
construction, easy to
operate and shall be
with monitor module.
Power supply shall be
24V DC. Product shall
be UL, ULC, FM listed
& Origin :
USA/UK/Canada
/Mexico/ Taiwan/
Korea/ Singapore.
8 SUPPLY, N/A Control Modules Import Nos. 8
INSTALLATION, and Supply of
TESTING & Intelligent Addressable
COMMISSIONING Control Moduls Product
OF FIRE shall be UL, ULC, FM
DETECTION AND listed & Origin :
ALARM SYSTEM USA/UK/Canada
/Mexico/ Taiwan/
Korea/ Singapore.
9 SUPPLY, N/A Monitor Modules Nos. 8
INSTALLATION, Import and Supply of
TESTING & Intelligent Addressable
COMMISSIONING Monitor Modules
OF FIRE Product shall be UL,
DETECTION AND ULC, FM listed &
ALARM SYSTEM Origin :
USA/UK/Canada
/Mexico/ Taiwan/
Korea/ Singapore.
10 SUPPLY, N/A Fault Isolator Modules Nos. 8
INSTALLATION, Import and Supply,
TESTING & installation, testing and
COMMISSIONING commissioning of
OF FIRE Intelligent Addressable
DETECTION AND Fault Isolator Modules.
ALARM SYSTEM Product shall be UL,
ULC, FM listed &
Origin :
USA/UK/Canada
/Mexico/ Taiwan/
Korea/ Singapore.
11 SUPPLY, N/A Siren Import and Nos. 2
INSTALLATION, Supply & Installation of
TESTING & Wall/Ceiling Mounted
COMMISSIONING siren of 50 watts
OF FIRE capacity. Siren shall be
DETECTION AND industrial type suitable
ALARM SYSTEM to produce shirk sound.
Siren shall be all
accessories including
power supply unit
Rechargeable battery
etc. Product shall be
USA/UK/Canada
/Mexico/ Taiwan/
Korea/ Singapore.
12 SUPPLY, N/A Exit Light : Import and Nos. 82
INSTALLATION, Supply & Installation of
TESTING & Exit Light of 12 V
COMMISSIONING complete with
OF FIRE rechargeable battery
DETECTION AND and charger. Light shall
ALARM SYSTEM be suitable for AC/DC.
Power supply shall be
220V/ single phase.
Product shall be UL,
USA/UK/Canada
/Mexico/ Taiwan/
Korea/ Singapore.
13 SUPPLY, N/A "Fire Resistance Cable Rm 2600
INSTALLATION, : Import and Supply
TESTING & and Installation of
COMMISSIONING (FRLS) Fire resistant
OF FIRE type single/ multi core
DETECTION AND PVC insulated, PVC
ALARM SYSTEM sheathed electrical
cable of copper
conductor of required
size as per drawing and
direction. Cable shall be
complete with supply &
return lope .The work
shall be complete with
water grade PVC
conduit, conduit bends,
tees, junction box, pull
box etc. complete as
per direction and
standard.
Termination and cable
jointing shall be done as
per standard practice.
Cable work shall be
done as per drawing
and direction. The
Authority shall supply
required power up to
panel. The shall be able
to with stand at 400ºc.
Installation of Fire
resistance Cable shall
be at location shown in
the drawing and shall
be as per
recommendation of the
manufacturer. Approved
type of uPVC type shall
be used.
"
14 SUPPLY, N/A EMT Conduit : Supply, Rm 1050
INSTALLATION, installation, Testing,
TESTING & commissioning of 20mm
COMMISSIONING dia PVC Conduit With
OF FIRE all accessories.
DETECTION AND
ALARM SYSTEM
15 SUPPLY, N/A Testing, commissioning Lot 1
INSTALLATION, and Fire Drill After
TESTING & complete installation,
COMMISSIONING Testing, commissioning
OF FIRE and Fire Drill of the
DETECTION AND system shall be done
ALARM SYSTEM as per recommendation
of the Manufacturer
and as per NFPA. Pipe
system shall be tested
at 250psig pressure. All
the individual items shall
be tested separately
upto the satisfaction of
the Consultant.
Grand
Total :

Bill of Quantities (FIRE PROTECTION & SPRIKLER SYSTEM BUILDING Tower-2 & 3)

Table
Bill of Quantities
Name :
Unit Total Total
Item Price Price Price
Unit Price
Item Group Code Description of Item Measurement Quantity
no. (if Unit In In In
In figures (BDT)
any) Words Figures Words
(BDT) (BDT) (BDT)
1.1 FIRE N/A FIRE WATER PUMP : Set. 1
PROTECTION Supply & Installation of
& SPRIKLER Pump for Fire Fighting
SYSTEM System use shall be
BUILDING complete with
(Tower-2 & 3) mounting, coupled
motor etc. complete.
The pump shall be
minimum 60% efficient.
Impeller speed shall
not be more than 2,900
rpm. Power supply
shall be 400 V/3
phase/50Hz. The pump
shall have a capacity to
handle 750US GPM of
water against a head
of 120 meter of water.
Pump shall be
operated on pressure
signal from pressure
switch. Engine Driven
Pump shall be UL, FM,
ULC Listed.Checking,
carrying and
Installation of fire pump
shall be as per drawing
and direction and
recommendation of
manufacturer.
Foundation works shall
be done by for other
contractor as per
direction. Suction and
delivery connection to
the pumps shall be with
proper size of adapter.
Water, electrical and
control wiring shall be
done as per
recommendation and
drawing. Pump
assembly shall be
properly aligned. Base
shall be provided with
drain.
Electric Motor Driven
Complete with Control
Panel: Import, Supply
& Installation of
Electrical driven fire
pump shall be complete
with motor, starter,
base plate, coupling, all
other accessories etc.
as per specification
and drawing. Country
of Origin : USA/ UK/
Japan/ Canada. Type :
End Suction/ Split
Case Vertical
Discharge Discharge:
750 US. Gpm Head:
120 M of w.g.
1.2 FIRE N/A Supply & Installation of Set. 1
PROTECTION Pump for Fire Fighting
& SPRIKLER System use shall be
SYSTEM complete with
BUILDING mounting, coupled
(Tower-2 & 3) motor etc. complete.
The pump shall be
minimum 60% efficient.
Impeller speed shall
not be more than 2,900
rpm. Power supply
shall be 400 V/3
phase/50Hz. The pump
shall have a capacity to
handle 750US GPM of
water against a head
of 120 meter of water.
Pump shall be
operated on pressure
signal from pressure
switch. Engine Driven
Pump shall be UL, FM,
ULC Listed.Checking,
carrying and
Installation of fire pump
shall be as per drawing
and direction and
recommendation of
manufacturer.
Foundation works shall
be done by for other
contractor as per
direction. Suction and
delivery connection to
the pumps shall be with
proper size of adapter.
Water, electrical and
control wiring shall be
done as per
recommendation and
drawing. Pump
assembly shall be
properly aligned. Base
shall be provided with
drain. Diesel Engine
Driven Complete with
Control Panel: Import,
Supply & Installation of
Engine driven fire pump
shall be complete with
direct coupled diesel
engine, pump, all
controls and
accessories, diesel
tank etc. as per
specification and
drawing. Country of
Origin : USA/ UK/
Japan / Canada. Type
: End Suction/ Split
Case Vertical
Discharge Discharge:
750 US. Gpm Head:
120 M of w.g.
1.3 FIRE N/A Supply & Installation of Set. 1
PROTECTION Pump for Fire Fighting
& SPRIKLER System use shall be
SYSTEM complete with
BUILDING mounting, coupled
(Tower-2 & 3) motor etc. complete.
The pump shall be
minimum 60% efficient.
Impeller speed shall
not be more than 2,900
rpm. Power supply
shall be 400 V/3
phase/50Hz. The pump
shall have a capacity to
handle 750US GPM of
water against a head
of 120 meter of water.
Pump shall be
operated on pressure
signal from pressure
switch. Engine Driven
Pump shall be UL, FM,
ULC Listed.Checking,
carrying and
Installation of fire pump
shall be as per drawing
and direction and
recommendation of
manufacturer.
Foundation works shall
be done by for other
contractor as per
direction. Suction and
delivery connection to
the pumps shall be with
proper size of adapter.
Water, electrical and
control wiring shall be
done as per
recommendation and
drawing. Pump
assembly shall be
properly aligned. Base
shall be provided with
drain.
JOCKEY PUMP:
Supply, Installation,
Testing &
Commissioning of
Multistage vertical type
Jockey pump for fire
fighting hydrant system
to keep a certain
pressure in water
distribution system.
Pump shall be
complete with pressure
switch, pump motor,
starter, base plate etc.
Capacity of the pump
shall be 25 GPM
against a head of 125
meter of water.Power
supply shall be
400V/50Hz, 3 phase.
Country of Origin :
USA/ UK/ Japan/
Germaney/ Australia.
Type: Multi-stage
Vertical turbine
Discharge: 25 US.Gpm
Head: 125 M of w.g.
2.1 FIRE N/A FIRE HOSE Nos 44
PROTECTION STATION RACK AND
& SPRIKLER ACCESSORIES:
SYSTEM Supply and installation
BUILDING of 40mm dia Hose reel
(Tower-2 & 3) within single fire
Hydrant unit shall be
complete with jet/spray
nozzle, 30 Meter long
heavy duty hose of
40mm dia. The hose
shall be suitable to
withstand working
pressure of 250 psi ,
brass made male-
female coupling, steel
encloser of standard
size, the encloser shall
be made with 16 SWG
sheet steel, Landing
valve & hose shall be
UL,ULC,FM listed.
Country of Origin :
USA/ UK/ Japan/
Singapure/ Malaysia.
HOSE CABINET:
Type: Wall mounted
recessed type Cabinet
Double compartment
Material: Mild steel
sheet of 1.5mm thick
Operation: Manual
type swing type
rack/cradle
Capacity: To
accommodate 1 no.
40mm dia oblique type
Landing valve, 1 no. 65
mm dia oblique type
Landing valve, (for
firemen) 1 no. 65 mm
dia Ball valve, 1 no. 65
mm dia Pressure
Reducing valve and
40mm dia 30M Long
collapsible type hose
with Two Nos fire
Extinguisher i.e
Co2+DCP 5KG each.
Country of Origin :
USA/UK/Canada
/Japan/ Mexico/
Taiwan/ Korea/
Singapore/
Malaysia.Finishing:
Epoxy powder red
paint.
2.2 FIRE N/A FIRE HOSE Sets 40
PROTECTION STATION RACK AND
& SPRIKLER ACCESSORIES:
SYSTEM Supply and installation
BUILDING of 40mm dia Hose reel
(Tower-2 & 3) within single fire
Hydrant unit shall be
complete with jet/spray
nozzle, 30 Meter long
heavy duty hose of
40mm dia. The hose
shall be suitable to
withstand working
pressure of 250 psi ,
brass made male-
female coupling, steel
encloser of standard
size, the encloser shall
be made with 16 SWG
sheet steel, Landing
valve & hose shall be
UL,ULC,FM listed.
Country of Origin :
USA/ UK/ Japan/
Singapure/ Malaysia.
HOSE PIPE (Internal)
: Type: Collapsible
Material: Fire resistant
synthetic twill
Diameter: 40mm
Length: 30m Hose
Pipe shall be UL, FM,
ULC Listed.
Accessories: Adopter,
Coupling etc.
2.3 FIRE N/A FIRE HOSE Sets 4
PROTECTION STATION RACK AND
& SPRIKLER ACCESSORIES:
SYSTEM Supply and installation
BUILDING of 40mm dia Hose reel
(Tower-2 & 3) within single fire
Hydrant unit shall be
complete with jet/spray
nozzle, 30 Meter long
heavy duty hose of
40mm dia. The hose
shall be suitable to
withstand working
pressure of 250 psi ,
brass made male-
female coupling, steel
encloser of standard
size, the encloser shall
be made with 16 SWG
sheet steel, Landing
valve & hose shall be
UL,ULC,FM listed.
Country of Origin :
USA/ UK/ Japan/
Singapure/ Malaysia.
HOSE PIPE (External)
: Type: Collapsible
Material: Fire resistant
synthetic twill
Diameter: 65mm
Length: 30m Hose
Pipe shall be UL, FM,
ULC Listed.
Accessories: Adopter,
Coupling etc.
2.4 FIRE N/A FIRE HOSE Sets 40
PROTECTION STATION RACK AND
& SPRIKLER ACCESSORIES:
SYSTEM Supply and installation
BUILDING of 40mm dia Hose reel
(Tower-2 & 3) within single fire
Hydrant unit shall be
complete with jet/spray
nozzle, 30 Meter long
heavy duty hose of
40mm dia. The hose
shall be suitable to
withstand working
pressure of 250 psi ,
brass made male-
female coupling, steel
encloser of standard
size, the encloser shall
be made with 16 SWG
sheet steel, Landing
valve & hose shall be
UL,ULC,FM listed.
Country of Origin :
USA/ UK/ Japan/
Singapure/ Malaysia.
NOZZLE (Internal) :
Type: Adjustable spray
/ jet Material : Copper
alloy/Gun metal 40mm
dia Nozzle
2.5 FIRE N/A FIRE HOSE Sets 4
PROTECTION STATION RACK AND
& SPRIKLER ACCESSORIES:
SYSTEM Supply and installation
BUILDING of 40mm dia Hose reel
(Tower-2 & 3) within single fire
Hydrant unit shall be
complete with jet/spray
nozzle, 30 Meter long
heavy duty hose of
40mm dia. The hose
shall be suitable to
withstand working
pressure of 250 psi ,
brass made male-
female coupling, steel
encloser of standard
size, the encloser shall
be made with 16 SWG
sheet steel, Landing
valve & hose shall be
UL,ULC,FM listed.
Country of Origin :
USA/ UK/ Japan/
Singapure/ Malaysia.
NOZZLE (External):
Type: Adjustable spray
/ jet Material : Copper
alloy/Gun metal 65mm
dia Nozzle
2.6.a FIRE N/A FIRE HOSE Sets 42
PROTECTION STATION RACK AND
& SPRIKLER ACCESSORIES:
SYSTEM Supply and installation
BUILDING of 40mm dia Hose reel
(Tower-2 & 3) within single fire
Hydrant unit shall be
complete with jet/spray
nozzle, 30 Meter long
heavy duty hose of
40mm dia. The hose
shall be suitable to
withstand working
pressure of 250 psi ,
brass made male-
female coupling, steel
encloser of standard
size, the encloser shall
be made with 16 SWG
sheet steel, Landing
valve & hose shall be
UL,ULC,FM listed.
Country of Origin :
USA/ UK/ Japan/
Singapure/
Malaysia.LANDING
VALVE: Landing Valve
shall be UL, FM, ULC
Listed. 65mm dia
Landing Valve
2.6.b FIRE N/A FIRE HOSE Sets 40
PROTECTION STATION RACK AND
& SPRIKLER ACCESSORIES:
SYSTEM Supply and installation
BUILDING of 40mm dia Hose reel
(Tower-2 & 3) within single fire
Hydrant unit shall be
complete with jet/spray
nozzle, 30 Meter long
heavy duty hose of
40mm dia. The hose
shall be suitable to
withstand working
pressure of 250 psi ,
brass made male-
female coupling, steel
encloser of standard
size, the encloser shall
be made with 16 SWG
sheet steel, Landing
valve & hose shall be
UL,ULC,FM listed.
Country of Origin :
USA/ UK/ Japan/
Singapure/
Malaysia.LANDING
VALVE: Landing Valve
shall be UL, FM, ULC
Listed. 40mm dia
Landing Valve
2.7 FIRE N/A FIRE HOSE Sets 2
PROTECTION STATION RACK AND
& SPRIKLER ACCESSORIES:
SYSTEM Supply and installation
BUILDING of 40mm dia Hose reel
(Tower-2 & 3) within single fire
Hydrant unit shall be
complete with jet/spray
nozzle, 30 Meter long
heavy duty hose of
40mm dia. The hose
shall be suitable to
withstand working
pressure of 250 psi ,
brass made male-
female coupling, steel
encloser of standard
size, the encloser shall
be made with 16 SWG
sheet steel, Landing
valve & hose shall be
UL,ULC,FM listed.
Country of Origin :
USA/ UK/ Japan/
Singapure/ Malaysia.
2-Way Double Headed
Pillar Hydrant : Import,
supply & installation of
100mm dia Double
Headed Pillar Hydrant
and outlet point of
65mm dia for external
fire hydrant hose of fire
man uses.
3.1 FIRE N/A Sprinkler Head (Upright Nos 250
PROTECTION Type): Import, Supply
& SPRIKLER and installation of
SYSTEM Upright Type Sprinkler
BUILDING head shall be exposed
(Tower-2 & 3) type, 15mm dia, 155°F
as per specification
and drawing. Sprinkler
shall be used in All Car
Parking Level.
Sprinkler head shall be
complete with spare
sprinkler head with
Escutcheon plate as
per specification and
drawing. The sprinkler
head shall be UL, FM,
ULC Listed. Country
Origin :
USA/UK/Canada
/Japan.
3.2 FIRE N/A Sprinkler Head Nos 260
PROTECTION (Pendant Type):
& SPRIKLER Import, Supply and
SYSTEM installation of Pendent
BUILDING Type Sprinkler head
(Tower-2 & 3) shall be exposed type,
15mm dia, 155°F as
per specification and
drawing. Sprinkler shall
be used in All Car
Parking Level.
Sprinkler head shall be
complete with spare
sprinkler head with box
as per specification
and drawing. The
sprinkler head shall be
UL, FM, ULC Listed.
Country of Origin :
USA/UK/Canada
/Japan.
3.3 FIRE N/A SPRINKLER HEAD : Nos 5
PROTECTION Sprinkler Flexible
& SPRIKLER Hose: Import, Supply
SYSTEM and Installation of
BUILDING (Pendant Type/Upright
(Tower-2 & 3) Type) to Sprinkler
Flexible Hose as per
as per following
specifications and
drawing. The sprinkler
head shall be UL, FM,
ULC Listed. Country of
Origin :
USA/UK/Canada
/Japan/ Mexico/
Taiwan/ Korea/
Singapore/ Malaysia.
4.1 FIRE N/A Sight Glass: Import Nos 2
PROTECTION and Supply of Sight
& SPRIKLER glass shall be installed
SYSTEM on release by pass line
BUILDING to see the water flow.
(Tower-2 & 3) Country of Origin :
USA/UK/Canada
/Japan/ Mexico/
Taiwan/ Korea/
Singapore/ Malaysia.
50mm Sight glass
4.2 FIRE N/A Sight Glass: Import Nos 4
PROTECTION and Supply of Sight
& SPRIKLER glass shall be installed
SYSTEM on release by pass line
BUILDING to see the water flow.
(Tower-2 & 3) Country of Origin :
USA/UK/Canada
/Japan/ Mexico/
Taiwan/ Korea/
Singapore/ Malaysia.
40mm Sight glass
5.1 FIRE N/A Water Flow Switch: Nos 6
PROTECTION Import and Supply of
& SPRIKLER Leaf type flow switch
SYSTEM with supervisory switch
BUILDING shall be suitable to
(Tower-2 & 3) send the signal on flow
water. Country of
Origin :
USA/UK/Canada
/Japan/ Mexico/
Taiwan/ Korea/
Singapore/ Malaysia.
100mm dia Water flow
switch
5.2 FIRE N/A Water Flow Switch: Nos 2
PROTECTION Import and Supply of
& SPRIKLER Leaf type flow switch
SYSTEM with supervisory switch
BUILDING shall be suitable to
(Tower-2 & 3) send the signal on flow
water. Country of
Origin :
USA/UK/Canada
/Japan/ Mexico/
Taiwan/ Korea/
Singapore/ Malaysia.
65mm dia Water flow
switch
6.1 FIRE N/A BLACK STEEL PIPE m 18
PROTECTION WORKS :Supply and
& SPRIKLER Installation of Black
SYSTEM Steel Pipe of schedule
BUILDING 40(S) suitable to
(Tower-2 & 3) withstand a test
pressure 15 kg of
water complete with
bends, tees, elbows,
reducers, socket, union
etc. as per drawing
and direction.Cutting of
pipe welding, threading
and sealing the thread
with proper type of
sealing compound shall
be done leak proof.
Pipe work along with
fittings shall be suitable
to withstand a test
pressure of 15 Kg/cm².
Required flanges shall
be provided in main
pipe as per direction All
Pipe including M/S.
materials including
outside of Black steel
pipe work shall be
provided with two
coats of cold
galvanisation after
proper cleaning. All
underground pipes shall
be protected with black
tape wrapping. Earth
cutting, filling with sand
cc pipe support at an
interval of 3 meter shall
be done for out door
underground pipe
work.All pipe work
shall be completed with
support, bracket etc.
complete as per
drawing and direction.
For underground pipes,
brick / CC suports shall
be done by the owner /
others. Pipe Country of
Origin : Malaysia/
Germeny/ Korea/
Vietnam.Type:
Seamless Material:
Black Steel Schedule
no: 40SImport, Supply
& Installation of 200
mm dia
6.2 FIRE N/A BLACK STEEL PIPE m 190
PROTECTION WORKS :Supply and
& SPRIKLER Installation of Black
SYSTEM Steel Pipe of schedule
BUILDING 40(S) suitable to
(Tower-2 & 3) withstand a test
pressure 15 kg of
water complete with
bends, tees, elbows,
reducers, socket, union
etc. as per drawing
and direction.Cutting of
pipe welding, threading
and sealing the thread
with proper type of
sealing compound shall
be done leak proof.
Pipe work along with
fittings shall be suitable
to withstand a test
pressure of 15 Kg/cm².
Required flanges shall
be provided in main
pipe as per direction All
Pipe including M/S.
materials including
outside of Black steel
pipe work shall be
provided with two
coats of cold
galvanisation after
proper cleaning. All
underground pipes shall
be protected with black
tape wrapping. Earth
cutting, filling with sand
cc pipe support at an
interval of 3 meter shall
be done for out door
underground pipe
work.All pipe work
shall be completed with
support, bracket etc.
complete as per
drawing and direction.
For underground pipes,
brick / CC suports shall
be done by the owner /
others. Pipe Country of
Origin : Malaysia/
Germeny/ Korea/
Vietnam.Type:
Seamless Material:
Black Steel Schedule
no: 40SImport, Supply
& Installation of 150
mm dia
6.3 FIRE N/A BLACK STEEL PIPE m 45
PROTECTION WORKS :Supply and
& SPRIKLER Installation of Black
SYSTEM Steel Pipe of schedule
BUILDING 40(S) suitable to
(Tower-2 & 3) withstand a test
pressure 15 kg of
water complete with
bends, tees, elbows,
reducers, socket, union
etc. as per drawing
and direction.Cutting of
pipe welding, threading
and sealing the thread
with proper type of
sealing compound shall
be done leak proof.
Pipe work along with
fittings shall be suitable
to withstand a test
pressure of 15 Kg/cm².
Required flanges shall
be provided in main
pipe as per direction All
Pipe including M/S.
materials including
outside of Black steel
pipe work shall be
provided with two
coats of cold
galvanisation after
proper cleaning. All
underground pipes shall
be protected with black
tape wrapping. Earth
cutting, filling with sand
cc pipe support at an
interval of 3 meter shall
be done for out door
underground pipe
work.All pipe work
shall be completed with
support, bracket etc.
complete as per
drawing and direction.
For underground pipes,
brick / CC suports shall
be done by the owner /
others. Pipe Country of
Origin : Malaysia/
Germeny/ Korea/
Vietnam.Type:
Seamless Material:
Black Steel Schedule
no: 40SImport, Supply
& Installation of 100
mm dia
6.4 FIRE N/A BLACK STEEL PIPE m 110
PROTECTION WORKS :Supply and
& SPRIKLER Installation of Black
SYSTEM Steel Pipe of schedule
BUILDING 40(S) suitable to
(Tower-2 & 3) withstand a test
pressure 15 kg of
water complete with
bends, tees, elbows,
reducers, socket, union
etc. as per drawing
and direction.Cutting of
pipe welding, threading
and sealing the thread
with proper type of
sealing compound shall
be done leak proof.
Pipe work along with
fittings shall be suitable
to withstand a test
pressure of 15 Kg/cm².
Required flanges shall
be provided in main
pipe as per direction All
Pipe including M/S.
materials including
outside of Black steel
pipe work shall be
provided with two
coats of cold
galvanisation after
proper cleaning. All
underground pipes shall
be protected with black
tape wrapping. Earth
cutting, filling with sand
cc pipe support at an
interval of 3 meter shall
be done for out door
underground pipe
work.All pipe work
shall be completed with
support, bracket etc.
complete as per
drawing and direction.
For underground pipes,
brick / CC suports shall
be done by the owner /
others. Pipe Country of
Origin : Malaysia/
Germeny/ Korea/
Vietnam.Type:
Seamless Material:
Black Steel Schedule
no: 40SImport, Supply
& Installation of 80mm
dia
6.5 FIRE N/A BLACK STEEL PIPE m 175
PROTECTION WORKS :Supply and
& SPRIKLER Installation of Black
SYSTEM Steel Pipe of schedule
BUILDING 40(S) suitable to
(Tower-2 & 3) withstand a test
pressure 15 kg of
water complete with
bends, tees, elbows,
reducers, socket, union
etc. as per drawing
and direction.Cutting of
pipe welding, threading
and sealing the thread
with proper type of
sealing compound shall
be done leak proof.
Pipe work along with
fittings shall be suitable
to withstand a test
pressure of 15 Kg/cm².
Required flanges shall
be provided in main
pipe as per direction All
Pipe including M/S.
materials including
outside of Black steel
pipe work shall be
provided with two
coats of cold
galvanisation after
proper cleaning. All
underground pipes shall
be protected with black
tape wrapping. Earth
cutting, filling with sand
cc pipe support at an
interval of 3 meter shall
be done for out door
underground pipe
work.All pipe work
shall be completed with
support, bracket etc.
complete as per
drawing and direction.
For underground pipes,
brick / CC suports shall
be done by the owner /
others. Pipe Country of
Origin : Malaysia/
Germeny/ Korea/
Vietnam.Type:
Seamless Material:
Black Steel Schedule
no: 40SImport, Supply
& Installation of 65mm
dia
6.6 FIRE N/A BLACK STEEL PIPE m 280
PROTECTION WORKS :Supply and
& SPRIKLER Installation of Black
SYSTEM Steel Pipe of schedule
BUILDING 40(S) suitable to
(Tower-2 & 3) withstand a test
pressure 15 kg of
water complete with
bends, tees, elbows,
reducers, socket, union
etc. as per drawing
and direction.Cutting of
pipe welding, threading
and sealing the thread
with proper type of
sealing compound shall
be done leak proof.
Pipe work along with
fittings shall be suitable
to withstand a test
pressure of 15 Kg/cm².
Required flanges shall
be provided in main
pipe as per direction All
Pipe including M/S.
materials including
outside of Black steel
pipe work shall be
provided with two
coats of cold
galvanisation after
proper cleaning. All
underground pipes shall
be protected with black
tape wrapping. Earth
cutting, filling with sand
cc pipe support at an
interval of 3 meter shall
be done for out door
underground pipe
work.All pipe work
shall be completed with
support, bracket etc.
complete as per
drawing and direction.
For underground pipes,
brick / CC suports shall
be done by the owner /
others. Pipe Country of
Origin : Malaysia/
Germeny/ Korea/
Vietnam.Type:
Seamless Material:
Black Steel Schedule
no: 40SImport, Supply
& Installation of 50 mm
dia
6.7 FIRE N/A BLACK STEEL PIPE m 120
PROTECTION WORKS :Supply and
& SPRIKLER Installation of Black
SYSTEM Steel Pipe of schedule
BUILDING 40(S) suitable to
(Tower-2 & 3) withstand a test
pressure 15 kg of
water complete with
bends, tees, elbows,
reducers, socket, union
etc. as per drawing
and direction.Cutting of
pipe welding, threading
and sealing the thread
with proper type of
sealing compound shall
be done leak proof.
Pipe work along with
fittings shall be suitable
to withstand a test
pressure of 15 Kg/cm².
Required flanges shall
be provided in main
pipe as per direction All
Pipe including M/S.
materials including
outside of Black steel
pipe work shall be
provided with two
coats of cold
galvanisation after
proper cleaning. All
underground pipes shall
be protected with black
tape wrapping. Earth
cutting, filling with sand
cc pipe support at an
interval of 3 meter shall
be done for out door
underground pipe
work.All pipe work
shall be completed with
support, bracket etc.
complete as per
drawing and direction.
For underground pipes,
brick / CC suports shall
be done by the owner /
others. Pipe Country of
Origin : Malaysia/
Germeny/ Korea/
Vietnam.Type:
Seamless Material:
Black Steel Schedule
no: 40SImport, Supply
& Installation of 40 mm
dia
6.8 FIRE N/A BLACK STEEL PIPE m 60
PROTECTION WORKS :Supply and
& SPRIKLER Installation of Black
SYSTEM Steel Pipe of schedule
BUILDING 40(S) suitable to
(Tower-2 & 3) withstand a test
pressure 15 kg of
water complete with
bends, tees, elbows,
reducers, socket, union
etc. as per drawing
and direction.Cutting of
pipe welding, threading
and sealing the thread
with proper type of
sealing compound shall
be done leak proof.
Pipe work along with
fittings shall be suitable
to withstand a test
pressure of 15 Kg/cm².
Required flanges shall
be provided in main
pipe as per direction All
Pipe including M/S.
materials including
outside of Black steel
pipe work shall be
provided with two
coats of cold
galvanisation after
proper cleaning. All
underground pipes shall
be protected with black
tape wrapping. Earth
cutting, filling with sand
cc pipe support at an
interval of 3 meter shall
be done for out door
underground pipe
work.All pipe work
shall be completed with
support, bracket etc.
complete as per
drawing and direction.
For underground pipes,
brick / CC suports shall
be done by the owner /
others. Pipe Country of
Origin : Malaysia/
Germeny/ Korea/
Vietnam.Type:
Seamless Material:
Black Steel Schedule
no: 40SImport, Supply
& Installation of 32 mm
dia
6.9 FIRE N/A BLACK STEEL PIPE m 1450
PROTECTION WORKS :Supply and
& SPRIKLER Installation of Black
SYSTEM Steel Pipe of schedule
BUILDING 40(S) suitable to
(Tower-2 & 3) withstand a test
pressure 15 kg of
water complete with
bends, tees, elbows,
reducers, socket, union
etc. as per drawing
and direction.Cutting of
pipe welding, threading
and sealing the thread
with proper type of
sealing compound shall
be done leak proof.
Pipe work along with
fittings shall be suitable
to withstand a test
pressure of 15 Kg/cm².
Required flanges shall
be provided in main
pipe as per direction All
Pipe including M/S.
materials including
outside of Black steel
pipe work shall be
provided with two
coats of cold
galvanisation after
proper cleaning. All
underground pipes shall
be protected with black
tape wrapping. Earth
cutting, filling with sand
cc pipe support at an
interval of 3 meter shall
be done for out door
underground pipe
work.All pipe work
shall be completed with
support, bracket etc.
complete as per
drawing and direction.
For underground pipes,
brick / CC suports shall
be done by the owner /
others. Pipe Country of
Origin : Malaysia/
Germeny/ Korea/
Vietnam.Type:
Seamless Material:
Black Steel Schedule
no: 40SImport, Supply
& Installation of 25 mm
dia
6.10 FIRE N/A BLACK STEEL PIPE m 18
PROTECTION WORKS :Supply and
& SPRIKLER Installation of Black
SYSTEM Steel Pipe of schedule
BUILDING 40(S) suitable to
(Tower-2 & 3) withstand a test
pressure 15 kg of
water complete with
bends, tees, elbows,
reducers, socket, union
etc. as per drawing
and direction.Cutting of
pipe welding, threading
and sealing the thread
with proper type of
sealing compound shall
be done leak proof.
Pipe work along with
fittings shall be suitable
to withstand a test
pressure of 15 Kg/cm².
Required flanges shall
be provided in main
pipe as per direction All
Pipe including M/S.
materials including
outside of Black steel
pipe work shall be
provided with two
coats of cold
galvanisation after
proper cleaning. All
underground pipes shall
be protected with black
tape wrapping. Earth
cutting, filling with sand
cc pipe support at an
interval of 3 meter shall
be done for out door
underground pipe
work.All pipe work
shall be completed with
support, bracket etc.
complete as per
drawing and direction.
For underground pipes,
brick / CC suports shall
be done by the owner /
others. Pipe Country of
Origin : Malaysia/
Germeny/ Korea/
Vietnam.Type:
Seamless Material:
Black Steel Schedule
no: 40SImport, Supply
& Installation of 20 mm
dia
6.11 FIRE N/A BLACK STEEL PIPE m 24
PROTECTION WORKS :Supply and
& SPRIKLER Installation of Black
SYSTEM Steel Pipe of schedule
BUILDING 40(S) suitable to
(Tower-2 & 3) withstand a test
pressure 15 kg of
water complete with
bends, tees, elbows,
reducers, socket, union
etc. as per drawing
and direction.Cutting of
pipe welding, threading
and sealing the thread
with proper type of
sealing compound shall
be done leak proof.
Pipe work along with
fittings shall be suitable
to withstand a test
pressure of 15 Kg/cm².
Required flanges shall
be provided in main
pipe as per direction All
Pipe including M/S.
materials including
outside of Black steel
pipe work shall be
provided with two
coats of cold
galvanisation after
proper cleaning. All
underground pipes shall
be protected with black
tape wrapping. Earth
cutting, filling with sand
cc pipe support at an
interval of 3 meter shall
be done for out door
underground pipe
work.All pipe work
shall be completed with
support, bracket etc.
complete as per
drawing and direction.
For underground pipes,
brick / CC suports shall
be done by the owner /
others. Pipe Country of
Origin : Malaysia/
Germeny/ Korea/
Vietnam.Type:
Seamless Material:
Black Steel Schedule
no: 40SImport, Supply
& Installation of 15 mm
dia
7.1 FIRE N/A DRAIN GI PIPE m 45
PROTECTION Supply and Installation
& SPRIKLER of Drain pipe of
SYSTEM schedule 20(S) suitable
BUILDING to withstand a test
(Tower-2 & 3) pressure 6 kg of water
complete with bends,
tees, elbows, reducers,
socket, union etc. as
per drawing and
direction.GI pipes for
drain line of following
diameter (NTL/
Bashundhara-Ruby) 50
mm dia
7.2 FIRE N/A DRAIN GI PIPE m 30
PROTECTION Supply and Installation
& SPRIKLER of Drain pipe of
SYSTEM schedule 20(S) suitable
BUILDING to withstand a test
(Tower-2 & 3) pressure 6 kg of water
complete with bends,
tees, elbows, reducers,
socket, union etc. as
per drawing and
direction.GI pipes for
drain line of following
diameter (NTL/
Bashundhara-Ruby) 40
mm dia
8 FIRE N/A PIPE FITTINGS Lot 1
PROTECTION Supply, installation and
& SPRIKLER testing of local made
SYSTEM pipe fittings of following
BUILDING types made of
(Tower-2 & 3) malleable steel as per
drawing
9.1.a FIRE N/A VALVE AND Nos 1
PROTECTION ACCESSORIES
& SPRIKLER Import, Supply &
SYSTEM Installation of Pipe
BUILDING accessories such as
(Tower-2 & 3) Gate Valves, Globe
Valves, Check Valves,
Strainer, Expansion
Joint etc. Pipe
accessories shall be
suitable to with stand a
pressure of 250 psig.
Valves above 65mm
dia shall be of cast iron
body, flanged end type
complete with
companion Flanges,
Gaskets, Nuts Bolts
etc. Country of Origin :
USA/UK/Canada
/Japan/ Mexico/
Taiwan/ Korea/
Singapore/ Malaysia/
Germeny/ Italy.GATE
VALVE: Import, Supply
& Installation of Gate
Valve 50 mm dia and
smaller shall be bronze
body, screwed bonnet,
rising stem, swivel disc
and valve 65 mm dia
and larger shall be iron
body, bolted bonnet,
outside screw and
yoke, rising stem,
bevelled wedge disc
and flanged end type
complete with
companion flanges with
nut-bolt, gasket
etc.Origin :
USA/UK/Canada
/Japan/ Mexico/
Taiwan/ Korea/
Singapore/
Malaysia.Type: O, S &
Y Material: Bronze
(upto 65mm), cast
steel (above 65 mm)
Pressure rating: PN-16
minimum) Joints:
Threaded (upto
65mm), flagged (above
65mm). Stem: Rising
200 mm dia
9.1.b FIRE N/A VALVE AND Nos 6
PROTECTION ACCESSORIES
& SPRIKLER Import, Supply &
SYSTEM Installation of Pipe
BUILDING accessories such as
(Tower-2 & 3) Gate Valves, Globe
Valves, Check Valves,
Strainer, Expansion
Joint etc. Pipe
accessories shall be
suitable to with stand a
pressure of 250 psig.
Valves above 65mm
dia shall be of cast iron
body, flanged end type
complete with
companion Flanges,
Gaskets, Nuts Bolts
etc. Country of Origin :
USA/UK/Canada
/Japan/ Mexico/
Taiwan/ Korea/
Singapore/ Malaysia/
Germeny/ Italy.GATE
VALVE: Import, Supply
& Installation of Gate
Valve 50 mm dia and
smaller shall be bronze
body, screwed bonnet,
rising stem, swivel disc
and valve 65 mm dia
and larger shall be iron
body, bolted bonnet,
outside screw and
yoke, rising stem,
bevelled wedge disc
and flanged end type
complete with
companion flanges with
nut-bolt, gasket
etc.Origin :
USA/UK/Canada
/Japan/ Mexico/
Taiwan/ Korea/
Singapore/
Malaysia.Type: O, S &
Y Material: Bronze
(upto 65mm), cast
steel (above 65 mm)
Pressure rating: PN-16
minimum) Joints:
Threaded (upto
65mm), flagged (above
65mm). Stem: Rising
150 mm dia
9.1.c FIRE N/A VALVE AND Nos 2
PROTECTION ACCESSORIES
& SPRIKLER Import, Supply &
SYSTEM Installation of Pipe
BUILDING accessories such as
(Tower-2 & 3) Gate Valves, Globe
Valves, Check Valves,
Strainer, Expansion
Joint etc. Pipe
accessories shall be
suitable to with stand a
pressure of 250 psig.
Valves above 65mm
dia shall be of cast iron
body, flanged end type
complete with
companion Flanges,
Gaskets, Nuts Bolts
etc. Country of Origin :
USA/UK/Canada
/Japan/ Mexico/
Taiwan/ Korea/
Singapore/ Malaysia/
Germeny/ Italy.GATE
VALVE: Import, Supply
& Installation of Gate
Valve 50 mm dia and
smaller shall be bronze
body, screwed bonnet,
rising stem, swivel disc
and valve 65 mm dia
and larger shall be iron
body, bolted bonnet,
outside screw and
yoke, rising stem,
bevelled wedge disc
and flanged end type
complete with
companion flanges with
nut-bolt, gasket
etc.Origin :
USA/UK/Canada
/Japan/ Mexico/
Taiwan/ Korea/
Singapore/
Malaysia.Type: O, S &
Y Material: Bronze
(upto 65mm), cast
steel (above 65 mm)
Pressure rating: PN-16
minimum) Joints:
Threaded (upto
65mm), flagged (above
65mm). Stem: Rising
100 mm dia (Butter fly
type)
9.1.d FIRE N/A VALVE AND Nos 6
PROTECTION ACCESSORIES
& SPRIKLER Import, Supply &
SYSTEM Installation of Pipe
BUILDING accessories such as
(Tower-2 & 3) Gate Valves, Globe
Valves, Check Valves,
Strainer, Expansion
Joint etc. Pipe
accessories shall be
suitable to with stand a
pressure of 250 psig.
Valves above 65mm
dia shall be of cast iron
body, flanged end type
complete with
companion Flanges,
Gaskets, Nuts Bolts
etc. Country of Origin :
USA/UK/Canada
/Japan/ Mexico/
Taiwan/ Korea/
Singapore/ Malaysia/
Germeny/ Italy.GATE
VALVE: Import, Supply
& Installation of Gate
Valve 50 mm dia and
smaller shall be bronze
body, screwed bonnet,
rising stem, swivel disc
and valve 65 mm dia
and larger shall be iron
body, bolted bonnet,
outside screw and
yoke, rising stem,
bevelled wedge disc
and flanged end type
complete with
companion flanges with
nut-bolt, gasket
etc.Origin :
USA/UK/Canada
/Japan/ Mexico/
Taiwan/ Korea/
Singapore/
Malaysia.Type: O, S &
Y Material: Bronze
(upto 65mm), cast
steel (above 65 mm)
Pressure rating: PN-16
minimum) Joints:
Threaded (upto
65mm), flagged (above
65mm). Stem: Rising
80 mm dia (Butter fly
type with electric
supervisory switch)
9.1.e FIRE N/A VALVE AND Nos 1
PROTECTION ACCESSORIES
& SPRIKLER Import, Supply &
SYSTEM Installation of Pipe
BUILDING accessories such as
(Tower-2 & 3) Gate Valves, Globe
Valves, Check Valves,
Strainer, Expansion
Joint etc. Pipe
accessories shall be
suitable to with stand a
pressure of 250 psig.
Valves above 65mm
dia shall be of cast iron
body, flanged end type
complete with
companion Flanges,
Gaskets, Nuts Bolts
etc. Country of Origin :
USA/UK/Canada
/Japan/ Mexico/
Taiwan/ Korea/
Singapore/ Malaysia/
Germeny/ Italy.GATE
VALVE: Import, Supply
& Installation of Gate
Valve 50 mm dia and
smaller shall be bronze
body, screwed bonnet,
rising stem, swivel disc
and valve 65 mm dia
and larger shall be iron
body, bolted bonnet,
outside screw and
yoke, rising stem,
bevelled wedge disc
and flanged end type
complete with
companion flanges with
nut-bolt, gasket
etc.Origin :
USA/UK/Canada
/Japan/ Mexico/
Taiwan/ Korea/
Singapore/
Malaysia.Type: O, S &
Y Material: Bronze
(upto 65mm), cast
steel (above 65 mm)
Pressure rating: PN-16
minimum) Joints:
Threaded (upto
65mm), flagged (above
65mm). Stem: Rising
65 mm dia (Butter fly
type with electric
supervisory switch)
9.1.f FIRE N/A VALVE AND Nos 44
PROTECTION ACCESSORIES
& SPRIKLER Import, Supply &
SYSTEM Installation of Pipe
BUILDING accessories such as
(Tower-2 & 3) Gate Valves, Globe
Valves, Check Valves,
Strainer, Expansion
Joint etc. Pipe
accessories shall be
suitable to with stand a
pressure of 250 psig.
Valves above 65mm
dia shall be of cast iron
body, flanged end type
complete with
companion Flanges,
Gaskets, Nuts Bolts
etc. Country of Origin :
USA/UK/Canada
/Japan/ Mexico/
Taiwan/ Korea/
Singapore/ Malaysia/
Germeny/ Italy.GATE
VALVE: Import, Supply
& Installation of Gate
Valve 50 mm dia and
smaller shall be bronze
body, screwed bonnet,
rising stem, swivel disc
and valve 65 mm dia
and larger shall be iron
body, bolted bonnet,
outside screw and
yoke, rising stem,
bevelled wedge disc
and flanged end type
complete with
companion flanges with
nut-bolt, gasket
etc.Origin :
USA/UK/Canada
/Japan/ Mexico/
Taiwan/ Korea/
Singapore/
Malaysia.Type: O, S &
Y Material: Bronze
(upto 65mm), cast
steel (above 65 mm)
Pressure rating: PN-16
minimum) Joints:
Threaded (upto
65mm), flagged (above
65mm). Stem: Rising
Import & Supply of 65
mm dia (Ball Type)
9.1.g FIRE N/A VALVE AND Nos 2
PROTECTION ACCESSORIES
& SPRIKLER Import, Supply &
SYSTEM Installation of Pipe
BUILDING accessories such as
(Tower-2 & 3) Gate Valves, Globe
Valves, Check Valves,
Strainer, Expansion
Joint etc. Pipe
accessories shall be
suitable to with stand a
pressure of 250 psig.
Valves above 65mm
dia shall be of cast iron
body, flanged end type
complete with
companion Flanges,
Gaskets, Nuts Bolts
etc. Country of Origin :
USA/UK/Canada
/Japan/ Mexico/
Taiwan/ Korea/
Singapore/ Malaysia/
Germeny/ Italy.GATE
VALVE: Import, Supply
& Installation of Gate
Valve 50 mm dia and
smaller shall be bronze
body, screwed bonnet,
rising stem, swivel disc
and valve 65 mm dia
and larger shall be iron
body, bolted bonnet,
outside screw and
yoke, rising stem,
bevelled wedge disc
and flanged end type
complete with
companion flanges with
nut-bolt, gasket
etc.Origin :
USA/UK/Canada
/Japan/ Mexico/
Taiwan/ Korea/
Singapore/
Malaysia.Type: O, S &
Y Material: Bronze
(upto 65mm), cast
steel (above 65 mm)
Pressure rating: PN-16
minimum) Joints:
Threaded (upto
65mm), flagged (above
65mm). Stem: Rising
Import & Supply of 50
mm dia (Ball Type)
9.1.h FIRE N/A VALVE AND Nos 12
PROTECTION ACCESSORIES
& SPRIKLER Import, Supply &
SYSTEM Installation of Pipe
BUILDING accessories such as
(Tower-2 & 3) Gate Valves, Globe
Valves, Check Valves,
Strainer, Expansion
Joint etc. Pipe
accessories shall be
suitable to with stand a
pressure of 250 psig.
Valves above 65mm
dia shall be of cast iron
body, flanged end type
complete with
companion Flanges,
Gaskets, Nuts Bolts
etc. Country of Origin :
USA/UK/Canada
/Japan/ Mexico/
Taiwan/ Korea/
Singapore/ Malaysia/
Germeny/ Italy.GATE
VALVE: Import, Supply
& Installation of Gate
Valve 50 mm dia and
smaller shall be bronze
body, screwed bonnet,
rising stem, swivel disc
and valve 65 mm dia
and larger shall be iron
body, bolted bonnet,
outside screw and
yoke, rising stem,
bevelled wedge disc
and flanged end type
complete with
companion flanges with
nut-bolt, gasket
etc.Origin :
USA/UK/Canada
/Japan/ Mexico/
Taiwan/ Korea/
Singapore/
Malaysia.Type: O, S &
Y Material: Bronze
(upto 65mm), cast
steel (above 65 mm)
Pressure rating: PN-16
minimum) Joints:
Threaded (upto
65mm), flagged (above
65mm). Stem: Rising
Import & Supply of 40
mm dia (Ball Type)
9.1.i FIRE N/A VALVE AND Nos 8
PROTECTION ACCESSORIES
& SPRIKLER Import, Supply &
SYSTEM Installation of Pipe
BUILDING accessories such as
(Tower-2 & 3) Gate Valves, Globe
Valves, Check Valves,
Strainer, Expansion
Joint etc. Pipe
accessories shall be
suitable to with stand a
pressure of 250 psig.
Valves above 65mm
dia shall be of cast iron
body, flanged end type
complete with
companion Flanges,
Gaskets, Nuts Bolts
etc. Country of Origin :
USA/UK/Canada
/Japan/ Mexico/
Taiwan/ Korea/
Singapore/ Malaysia/
Germeny/ Italy.GATE
VALVE: Import, Supply
& Installation of Gate
Valve 50 mm dia and
smaller shall be bronze
body, screwed bonnet,
rising stem, swivel disc
and valve 65 mm dia
and larger shall be iron
body, bolted bonnet,
outside screw and
yoke, rising stem,
bevelled wedge disc
and flanged end type
complete with
companion flanges with
nut-bolt, gasket
etc.Origin :
USA/UK/Canada
/Japan/ Mexico/
Taiwan/ Korea/
Singapore/
Malaysia.Type: O, S &
Y Material: Bronze
(upto 65mm), cast
steel (above 65 mm)
Pressure rating: PN-16
minimum) Joints:
Threaded (upto
65mm), flagged (above
65mm). Stem: Rising
Import & Supply of 25
mm dia (Ball Type)
9.1.j FIRE N/A VALVE AND Nos 2
PROTECTION ACCESSORIES
& SPRIKLER Import, Supply &
SYSTEM Installation of Pipe
BUILDING accessories such as
(Tower-2 & 3) Gate Valves, Globe
Valves, Check Valves,
Strainer, Expansion
Joint etc. Pipe
accessories shall be
suitable to with stand a
pressure of 250 psig.
Valves above 65mm
dia shall be of cast iron
body, flanged end type
complete with
companion Flanges,
Gaskets, Nuts Bolts
etc. Country of Origin :
USA/UK/Canada
/Japan/ Mexico/
Taiwan/ Korea/
Singapore/ Malaysia/
Germeny/ Italy.GATE
VALVE: Import, Supply
& Installation of Gate
Valve 50 mm dia and
smaller shall be bronze
body, screwed bonnet,
rising stem, swivel disc
and valve 65 mm dia
and larger shall be iron
body, bolted bonnet,
outside screw and
yoke, rising stem,
bevelled wedge disc
and flanged end type
complete with
companion flanges with
nut-bolt, gasket
etc.Origin :
USA/UK/Canada
/Japan/ Mexico/
Taiwan/ Korea/
Singapore/
Malaysia.Type: O, S &
Y Material: Bronze
(upto 65mm), cast
steel (above 65 mm)
Pressure rating: PN-16
minimum) Joints:
Threaded (upto
65mm), flagged (above
65mm). Stem: Rising
Import & Supply of 20
mm dia (Ball Type)
9.1.k FIRE N/A VALVE AND Nos 4
PROTECTION ACCESSORIES
& SPRIKLER Import, Supply &
SYSTEM Installation of Pipe
BUILDING accessories such as
(Tower-2 & 3) Gate Valves, Globe
Valves, Check Valves,
Strainer, Expansion
Joint etc. Pipe
accessories shall be
suitable to with stand a
pressure of 250 psig.
Valves above 65mm
dia shall be of cast iron
body, flanged end type
complete with
companion Flanges,
Gaskets, Nuts Bolts
etc. Country of Origin :
USA/UK/Canada
/Japan/ Mexico/
Taiwan/ Korea/
Singapore/ Malaysia/
Germeny/ Italy.GATE
VALVE: Import, Supply
& Installation of Gate
Valve 50 mm dia and
smaller shall be bronze
body, screwed bonnet,
rising stem, swivel disc
and valve 65 mm dia
and larger shall be iron
body, bolted bonnet,
outside screw and
yoke, rising stem,
bevelled wedge disc
and flanged end type
complete with
companion flanges with
nut-bolt, gasket
etc.Origin :
USA/UK/Canada
/Japan/ Mexico/
Taiwan/ Korea/
Singapore/
Malaysia.Type: O, S &
Y Material: Bronze
(upto 65mm), cast
steel (above 65 mm)
Pressure rating: PN-16
minimum) Joints:
Threaded (upto
65mm), flagged (above
65mm). Stem: Rising
Import & Supply of 15
mm dia (Ball Type)
9.2.a FIRE N/A VALVE AND Nos 2
PROTECTION ACCESSORIES
& SPRIKLER Import, Supply &
SYSTEM Installation of Pipe
BUILDING accessories such as
(Tower-2 & 3) Gate Valves, Globe
Valves, Check Valves,
Strainer, Expansion
Joint etc. Pipe
accessories shall be
suitable to with stand a
pressure of 250 psig.
Valves above 65mm
dia shall be of cast iron
body, flanged end type
complete with
companion Flanges,
Gaskets, Nuts Bolts
etc. Country of Origin :
USA/UK/Canada
/Japan/ Mexico/
Taiwan/ Korea/
Singapore/ Malaysia/
Germeny/
Italy.GLOBE VALVE
Import, Supply &
Installation of Globe
valve 50 mm dia and
smaller shall be bronze
body, screwed bonnet,
rising stem, swivel disc
and valve 65 mm dia
and larger shall be iron
body, bolted bonnet,
outside screw and
yoke, rising stem,
bevelled wedge disc
and flanged end type
complete with
companion flanges with
nut-bolt, gasket
etc.Origin :
USA/UK/Canada
/Japan/ Mexico/
Taiwan/ Korea/
Singapore/ Malaysia/
Germeny.Type: Ball-
Type Material: Bronze
(for upto 65mm) Cast
iron (for above 65mm)
Pressure rating: PN-16
(minimum) Joints:
Threaded (upto
65mm), flagged (above
65mm) Import &
Supply of 150 mm dia
9.2.b FIRE N/A VALVE AND Nos 1
PROTECTION ACCESSORIES
& SPRIKLER Import, Supply &
SYSTEM Installation of Pipe
BUILDING accessories such as
(Tower-2 & 3) Gate Valves, Globe
Valves, Check Valves,
Strainer, Expansion
Joint etc. Pipe
accessories shall be
suitable to with stand a
pressure of 250 psig.
Valves above 65mm
dia shall be of cast iron
body, flanged end type
complete with
companion Flanges,
Gaskets, Nuts Bolts
etc. Country of Origin :
USA/UK/Canada
/Japan/ Mexico/
Taiwan/ Korea/
Singapore/ Malaysia/
Germeny/
Italy.GLOBE VALVE
Import, Supply &
Installation of Globe
valve 50 mm dia and
smaller shall be bronze
body, screwed bonnet,
rising stem, swivel disc
and valve 65 mm dia
and larger shall be iron
body, bolted bonnet,
outside screw and
yoke, rising stem,
bevelled wedge disc
and flanged end type
complete with
companion flanges with
nut-bolt, gasket
etc.Origin :
USA/UK/Canada
/Japan/ Mexico/
Taiwan/ Korea/
Singapore/ Malaysia/
Germeny.Type: Ball-
Type Material: Bronze
(for upto 65mm) Cast
iron (for above 65mm)
Pressure rating: PN-16
(minimum) Joints:
Threaded (upto
65mm), flagged (above
65mm) Import &
Supply of 50 mm dia
9.3.a FIRE N/A VALVE AND Nos 2
PROTECTION ACCESSORIES
& SPRIKLER Import, Supply &
SYSTEM Installation of Pipe
BUILDING accessories such as
(Tower-2 & 3) Gate Valves, Globe
Valves, Check Valves,
Strainer, Expansion
Joint etc. Pipe
accessories shall be
suitable to with stand a
pressure of 250 psig.
Valves above 65mm
dia shall be of cast iron
body, flanged end type
complete with
companion Flanges,
Gaskets, Nuts Bolts
etc. Country of Origin :
USA/UK/Canada
/Japan/ Mexico/
Taiwan/ Korea/
Singapore/ Malaysia/
Germeny/
Italy.CHECK VALVE/
NON RETURN VALVE
: Import, Supply &
Installation of Non-
Return valves shall be
re-grind able seat,
screwed cap, lift type
disc, integral seal and
flanges end type.
Origin :
USA/UK/Canada
/Japan/ Mexico/
Taiwan/ Korea/
Singapore/ Malaysia/
Germeny.Type: Swing
check. Lift check (for
jockey pump) Material:
Bronze (for upto
65mm) Cast iron (for
above 65mm) Pressure
rating: PN-16
(minimum)Joints:
Threaded (upto 65mm)
flagged (above 65mm)
Import & Supply of 150
mm dia
9.3.b FIRE N/A VALVE AND Nos 6
PROTECTION ACCESSORIES
& SPRIKLER Import, Supply &
SYSTEM Installation of Pipe
BUILDING accessories such as
(Tower-2 & 3) Gate Valves, Globe
Valves, Check Valves,
Strainer, Expansion
Joint etc. Pipe
accessories shall be
suitable to with stand a
pressure of 250 psig.
Valves above 65mm
dia shall be of cast iron
body, flanged end type
complete with
companion Flanges,
Gaskets, Nuts Bolts
etc. Country of Origin :
USA/UK/Canada
/Japan/ Mexico/
Taiwan/ Korea/
Singapore/ Malaysia/
Germeny/
Italy.CHECK VALVE/
NON RETURN VALVE
: Import, Supply &
Installation of Non-
Return valves shall be
re-grind able seat,
screwed cap, lift type
disc, integral seal and
flanges end type.
Origin :
USA/UK/Canada
/Japan/ Mexico/
Taiwan/ Korea/
Singapore/ Malaysia/
Germeny.Type: Swing
check. Lift check (for
jockey pump) Material:
Bronze (for upto
65mm) Cast iron (for
above 65mm) Pressure
rating: PN-16
(minimum)Joints:
Threaded (upto 65mm)
flagged (above 65mm)
Import & Supply of 80
mm dia
9.3.c FIRE N/A VALVE AND Nos 1
PROTECTION ACCESSORIES
& SPRIKLER Import, Supply &
SYSTEM Installation of Pipe
BUILDING accessories such as
(Tower-2 & 3) Gate Valves, Globe
Valves, Check Valves,
Strainer, Expansion
Joint etc. Pipe
accessories shall be
suitable to with stand a
pressure of 250 psig.
Valves above 65mm
dia shall be of cast iron
body, flanged end type
complete with
companion Flanges,
Gaskets, Nuts Bolts
etc. Country of Origin :
USA/UK/Canada
/Japan/ Mexico/
Taiwan/ Korea/
Singapore/ Malaysia/
Germeny/
Italy.CHECK VALVE/
NON RETURN VALVE
: Import, Supply &
Installation of Non-
Return valves shall be
re-grind able seat,
screwed cap, lift type
disc, integral seal and
flanges end type.
Origin :
USA/UK/Canada
/Japan/ Mexico/
Taiwan/ Korea/
Singapore/ Malaysia/
Germeny.Type: Swing
check. Lift check (for
jockey pump) Material:
Bronze (for upto
65mm) Cast iron (for
above 65mm) Pressure
rating: PN-16
(minimum)Joints:
Threaded (upto 65mm)
flagged (above 65mm)
Import & Supply of 65
mm dia
9.3.d FIRE N/A VALVE AND Nos 1
PROTECTION ACCESSORIES
& SPRIKLER Import, Supply &
SYSTEM Installation of Pipe
BUILDING accessories such as
(Tower-2 & 3) Gate Valves, Globe
Valves, Check Valves,
Strainer, Expansion
Joint etc. Pipe
accessories shall be
suitable to with stand a
pressure of 250 psig.
Valves above 65mm
dia shall be of cast iron
body, flanged end type
complete with
companion Flanges,
Gaskets, Nuts Bolts
etc. Country of Origin :
USA/UK/Canada
/Japan/ Mexico/
Taiwan/ Korea/
Singapore/ Malaysia/
Germeny/
Italy.CHECK VALVE/
NON RETURN VALVE
: Import, Supply &
Installation of Non-
Return valves shall be
re-grind able seat,
screwed cap, lift type
disc, integral seal and
flanges end type.
Origin :
USA/UK/Canada
/Japan/ Mexico/
Taiwan/ Korea/
Singapore/ Malaysia/
Germeny.Type: Swing
check. Lift check (for
jockey pump) Material:
Bronze (for upto
65mm) Cast iron (for
above 65mm) Pressure
rating: PN-16
(minimum)Joints:
Threaded (upto 65mm)
flagged (above 65mm)
Import & Supply of 50
mm dia
9.4.a FIRE N/A VALVE AND Nos 2
PROTECTION ACCESSORIES
& SPRIKLER Import, Supply &
SYSTEM Installation of Pipe
BUILDING accessories such as
(Tower-2 & 3) Gate Valves, Globe
Valves, Check Valves,
Strainer, Expansion
Joint etc. Pipe
accessories shall be
suitable to with stand a
pressure of 250 psig.
Valves above 65mm
dia shall be of cast iron
body, flanged end type
complete with
companion Flanges,
Gaskets, Nuts Bolts
etc. Country of Origin :
USA/UK/Canada
/Japan/ Mexico/
Taiwan/ Korea/
Singapore/ Malaysia/
Germeny/ Italy.Y-
STRAINER Import,
Supply and Installation
of the Y-strainer as per
following capacities.
Country of Origin
Taiwan/Malaysia/Korea
/ Vietnam/Italy
/Germeny.Type: Y-
Type Material: Bronze
(for upto 65mm) Cast
iron (for above 65mm)
Pressure rating: PN-16
(minimum) Joints:
Threaded (upto
65mm), flagged (above
65mm) Import &
Supply of 150 mm dia
9.4.b FIRE N/A VALVE AND Nos 1
PROTECTION ACCESSORIES
& SPRIKLER Import, Supply &
SYSTEM Installation of Pipe
BUILDING accessories such as
(Tower-2 & 3) Gate Valves, Globe
Valves, Check Valves,
Strainer, Expansion
Joint etc. Pipe
accessories shall be
suitable to with stand a
pressure of 250 psig.
Valves above 65mm
dia shall be of cast iron
body, flanged end type
complete with
companion Flanges,
Gaskets, Nuts Bolts
etc. Country of Origin :
USA/UK/Canada
/Japan/ Mexico/
Taiwan/ Korea/
Singapore/ Malaysia/
Germeny/ Italy.Y-
STRAINER Import,
Supply and Installation
of the Y-strainer as per
following capacities.
Country of Origin
Taiwan/Malaysia/Korea
/ Vietnam/Italy
/Germeny.Type: Y-
Type Material: Bronze
(for upto 65mm) Cast
iron (for above 65mm)
Pressure rating: PN-16
(minimum) Joints:
Threaded (upto
65mm), flagged (above
65mm) Import &
Supply of 50 mm dia
9.5.a FIRE N/A VALVE AND Nos 2
PROTECTION ACCESSORIES
& SPRIKLER Import, Supply &
SYSTEM Installation of Pipe
BUILDING accessories such as
(Tower-2 & 3) Gate Valves, Globe
Valves, Check Valves,
Strainer, Expansion
Joint etc. Pipe
accessories shall be
suitable to with stand a
pressure of 250 psig.
Valves above 65mm
dia shall be of cast iron
body, flanged end type
complete with
companion Flanges,
Gaskets, Nuts Bolts
etc. Country of Origin :
USA/UK/Canada
/Japan/ Mexico/
Taiwan/ Korea/
Singapore/ Malaysia/
Germeny/ Italy.FOOT
VALVE: Import, Supply
and Installation of the
Foot Valve as per
following capacities.
Country of Origin
Taiwan/Malaysia/Korea
/ Vietnam/Italy
/Germeny.Type: Lift
check Material:
Malleable steel
Pressure rating: PN-16
(minimum) Joints:
Threaded (upto
65mm), flagged (above
65mm) Import &
Supply of 150 mm dia
9.5.b FIRE N/A VALVE AND Nos 1
PROTECTION ACCESSORIES
& SPRIKLER Import, Supply &
SYSTEM Installation of Pipe
BUILDING accessories such as
(Tower-2 & 3) Gate Valves, Globe
Valves, Check Valves,
Strainer, Expansion
Joint etc. Pipe
accessories shall be
suitable to with stand a
pressure of 250 psig.
Valves above 65mm
dia shall be of cast iron
body, flanged end type
complete with
companion Flanges,
Gaskets, Nuts Bolts
etc. Country of Origin :
USA/UK/Canada
/Japan/ Mexico/
Taiwan/ Korea/
Singapore/ Malaysia/
Germeny/ Italy.FOOT
VALVE: Import, Supply
and Installation of the
Foot Valve as per
following capacities.
Country of Origin
Taiwan/Malaysia/Korea
/ Vietnam/Italy
/Germeny.Type: Lift
check Material:
Malleable steel
Pressure rating: PN-16
(minimum) Joints:
Threaded (upto
65mm), flagged (above
65mm) Import &
Supply of 50 mm dia
9.6.a FIRE N/A VALVE AND Nos 4
PROTECTION ACCESSORIES
& SPRIKLER Import, Supply &
SYSTEM Installation of Pipe
BUILDING accessories such as
(Tower-2 & 3) Gate Valves, Globe
Valves, Check Valves,
Strainer, Expansion
Joint etc. Pipe
accessories shall be
suitable to with stand a
pressure of 250 psig.
Valves above 65mm
dia shall be of cast iron
body, flanged end type
complete with
companion Flanges,
Gaskets, Nuts Bolts
etc. Country of Origin :
USA/UK/Canada
/Japan/ Mexico/
Taiwan/ Korea/
Singapore/ Malaysia/
Germeny/ Italy.
FLEXIBLE JOINT:
Import, Supply and
Installation of the
Flexible Joint as per
following capacities.
Country of Origin
Taiwan/Malaysia/Korea
/ Vietnam/Italy
/Germeny. Type:
Spherical Material:
Butyl or neoprene
Pressure rating: PN-16
(minimum) Joints:
Threaded (upto
65mm), flagged (above
65mm) Import &
Supply of 150 mm dia
9.6.b FIRE N/A VALVE AND Nos 2
PROTECTION ACCESSORIES
& SPRIKLER Import, Supply &
SYSTEM Installation of Pipe
BUILDING accessories such as
(Tower-2 & 3) Gate Valves, Globe
Valves, Check Valves,
Strainer, Expansion
Joint etc. Pipe
accessories shall be
suitable to with stand a
pressure of 250 psig.
Valves above 65mm
dia shall be of cast iron
body, flanged end type
complete with
companion Flanges,
Gaskets, Nuts Bolts
etc. Country of Origin :
USA/UK/Canada
/Japan/ Mexico/
Taiwan/ Korea/
Singapore/ Malaysia/
Germeny/ Italy.
FLEXIBLE JOINT:
Import, Supply and
Installation of the
Flexible Joint as per
following capacities.
Country of Origin
Taiwan/Malaysia/Korea
/ Vietnam/Italy
/Germeny. Type:
Spherical Material:
Butyl or neoprene
Pressure rating: PN-16
(minimum) Joints:
Threaded (upto
65mm), flagged (above
65mm)Import & Supply
of 50 mm dia
9.7 FIRE N/A VALVE AND Nos 8
PROTECTION ACCESSORIES
& SPRIKLER Import, Supply &
SYSTEM Installation of Pipe
BUILDING accessories such as
(Tower-2 & 3) Gate Valves, Globe
Valves, Check Valves,
Strainer, Expansion
Joint etc. Pipe
accessories shall be
suitable to with stand a
pressure of 250 psig.
Valves above 65mm
dia shall be of cast iron
body, flanged end type
complete with
companion Flanges,
Gaskets, Nuts Bolts
etc. Country of Origin :
USA/UK/Canada
/Japan/ Mexico/
Taiwan/ Korea/
Singapore/ Malaysia/
Germeny/ Italy. AUTO
AIR VENT VALVE :
Import, Supply and
Installation of the Vent
Valve as per following
capacities. Country of
Origin
Taiwan/Malaysia/Korea
/ Vietnam/Italy
/Germeny. Type: Free
floating automatic
Material: Cast steel
Accessories: Pad
cock, mounting
accessories Import &
Supply of 25 mm dia
9.8 FIRE N/A VALVE AND Nos 1
PROTECTION ACCESSORIES
& SPRIKLER Import, Supply &
SYSTEM Installation of Pipe
BUILDING accessories such as
(Tower-2 & 3) Gate Valves, Globe
Valves, Check Valves,
Strainer, Expansion
Joint etc. Pipe
accessories shall be
suitable to with stand a
pressure of 250 psig.
Valves above 65mm
dia shall be of cast iron
body, flanged end type
complete with
companion Flanges,
Gaskets, Nuts Bolts
etc. Country of Origin :
USA/UK/Canada
/Japan/ Mexico/
Taiwan/ Korea/
Singapore/ Malaysia/
Germeny/ Italy.
PRESSURE RELIEF
VALVE: Import, Supply
and Installation of the
Pressure Relief Valve
as per following
capacities. Country of
Origin
Taiwan/Malaysia/Korea
/ Vietnam/Italy
/Germeny.Type:
Hydraulically operated
disphram type
Material: Cast
iron/steel Pressure
rating: PN-16
(minimum) Import &
Supply of 100 mm dia
9.9 FIRE N/A VALVE AND Nos 12
PROTECTION ACCESSORIES
& SPRIKLER Import, Supply &
SYSTEM Installation of Pipe
BUILDING accessories such as
(Tower-2 & 3) Gate Valves, Globe
Valves, Check Valves,
Strainer, Expansion
Joint etc. Pipe
accessories shall be
suitable to with stand a
pressure of 250 psig.
Valves above 65mm
dia shall be of cast iron
body, flanged end type
complete with
companion Flanges,
Gaskets, Nuts Bolts
etc. Country of Origin :
USA/UK/Canada
/Japan/ Mexico/
Taiwan/ Korea/
Singapore/ Malaysia/
Germeny/ Italy.
PRESSURE
REDUCING VALVE:
Import, Supply and
Installation of the
Pressure Reducing
Valve on size 50 mm
dia. Pressure reducing
valve shall be suitable
to deliver water at a
pressure of 7.5 psig
(minimum) irrespective
of inlet pressure. (Inlet
pressure shall be 80 to
60 psig) as per
following capacities
and Origin :
USA/UK/Canada
/Japan/ Mexico/
Taiwan/ Korea/
Singapore/ Malaysia/
Germeny/ Italy.Type:
Hydraulically operated
disphram type
Material: Cast
iron/steel Pressure
rating: PN-16
(minimum) Import &
Supply of 65 mm dia
10 FIRE N/A Alarm Check Valve : Nos 1
PROTECTION Import, Supply &
& SPRIKLER Installation of 150mm
SYSTEM dia Alarm valve shall be
BUILDING of the vertical or
(Tower-2 & 3) horizontal type as
incluted all of suitable
to send the signal on
sprinkler heads. The
Alarm Check valve
shall be UL, FM, ULC
Listed. Country Origin :
USA/UK/Canada
/Japan/ Mexico/
Taiwan/ Korea/
Singapore/ Malaysia/
Germeny.
11 FIRE N/A PRESSURE GAUGE Nos 4
PROTECTION Import, Supply &
& SPRIKLER Installation of Pressure
SYSTEM gauge shall be of dial
BUILDING type of 100mm dia
(Tower-2 & 3) suitable to read 0 to 20
Kg pressure. Pressure
gauge shall be
completed with
petcock, pressure
snowbar, nipple etc.
Origin :
USA/UK/Canada
/Japan/ Mexico/
Taiwan/ Korea/
Singapore/ Malaysia/
Germeny.Type: Direct
reading dial type
Capacity range: 0-35
bar Dial size: 100 mm
12 FIRE N/A PRESSURE SWITCH Nos 1
PROTECTION Import and Supply,
& SPRIKLER testing &
SYSTEM commissioning of
BUILDING Pressure Switch
(Tower-2 & 3) complete with sensing
element, enclosure
material, 15mm NPT
pressure connection,
direct mounting
electrical connection.
The switch shall sense
pressure of water in
pipe and operate pump
motor. Origin :
USA/UK/Canada
/Japan/ Mexico/
Taiwan/ Korea/
Singapore/ Malaysia/
Germeny/
Denmark.Type:
Adjustable Capacity
range: 0-16 bar
Operation: Cut-in &
Cut-out
13 FIRE N/A FIRE BRIGADE Nos 1
PROTECTION CONNECTION
& SPRIKLER Import, Supply &
SYSTEM Installation of Fire
BUILDING Brigade Connection of
(Tower-2 & 3) 150mm dia with 4-way
connections of 65mm
dia each and shall be
completed with non-
return valve, valve cap,
chain, purging valve
etc. Fire Brigade
Connection shall be
done on stand pipe
suitable to operate by
Fire service people.
Country of Origin :
USA/UK/Canada
/Japan/ Mexico/
Taiwan/ Korea/
Singapore/ Malaysia/
Germeny Or
equivalent.Type: 4-way
Material: Copper alloy
Inlet size: 65mm
Coupling type: Quick
coupling type Finishing:
Bright powder epoxy
paint finish.
14 FIRE N/A FIRE PUMP Nos 1
PROTECTION CONTROL
& SPRIKLER CONSOLE The
SYSTEM control console shall be
BUILDING complete with all
(Tower-2 & 3) required components
and meters such as
MCCB CT, busbar,
voltmeter, ammeter,
auto to manual change
switch, manual on-off
switch, power isolation
circuiting for auto
operation.Import and
Supply of Control
console for stand pipe
system
15 FIRE N/A WATER LEVEL nos 1
PROTECTION LIMIT SWITCH
& SPRIKLER Import, Supply &
SYSTEM installation of local
BUILDING made water level limit
(Tower-2 & 3) switch with all
components. The
switch shall be able to
protect dry run of fire
pumps. The switch
shall be Origin :
USA/UK/Canada
/Japan/ Mexico/
Taiwan/ Korea/
Singapore/ Malaysia/
Germeny. Import and
Supply water level limit
switch with all
components.
16.1.a FIRE N/A ELECTRICAL m 10
PROTECTION WORKS GI Conduit
& SPRIKLER Supply and laying of
SYSTEM following diameter local
BUILDING made GI conduit for
(Tower-2 & 3) running electrical
cables from control
console to pumps for
operation of the pumps
65 mm dia
16.1.b FIRE N/A ELECTRICAL m 10
PROTECTION WORKS GI Conduit
& SPRIKLER Supply and laying of
SYSTEM following diameter local
BUILDING made GI conduit for
(Tower-2 & 3) running electrical
cables from control
console to pumps for
operation of the pumps
40 mm dia
16.2.a FIRE N/A ELECTRICAL m 20
PROTECTION WIRING: Supply,
& SPRIKLER drawing, cable
SYSTEM termination and testing
BUILDING of local made PVC
(Tower-2 & 3) sheathed PVC
insulated single core
cable of following sizes
as per specification.
Complete with PVC
conduit 1 x 1c x70 sqm
cable
16.2.b FIRE N/A ELECTRICAL m 15
PROTECTION WIRING: Supply,
& SPRIKLER drawing, cable
SYSTEM termination and testing
BUILDING of local made PVC
(Tower-2 & 3) sheathed PVC
insulated single core
cable of following sizes
as per specification.
Complete with PVC
conduit1 x 1c x 4.0 sqm
cable
16.2.c FIRE N/A ELECTRICAL m 15
PROTECTION WIRING: Supply,
& SPRIKLER drawing, cable
SYSTEM termination and testing
BUILDING of local made PVC
(Tower-2 & 3) sheathed PVC
insulated single core
cable of following sizes
as per specification.
Complete with PVC
conduit 1 x 1c x 1.5sqm
cable
17 FIRE N/A "Trolly Mounted Foam set 1
PROTECTION Type Fire Extinguisher
& SPRIKLER : Supply of Trolley
SYSTEM mounted Foam Type
BUILDING Extinguisher shall be
(Tower-2 & 3) complete with 45 Litre
( 10 gallon ) Capacity
Cylinder, Discharge
Nozzle, fixed on strong
steel chasis with solid
rubber tyres for easy
movement. The
extinguisher shall be
suitable for class A & B
risks, shall be filled with
highly effective AFFF
(Aqueous Film Forming
Foam).
"
18 FIRE N/A Trolly Mounted CO2 set 1
PROTECTION Type Fire Extinguisher
& SPRIKLER : Supply Trolley mount
SYSTEM CO2 type Extinguisher
BUILDING shall be complete with
(Tower-2 & 3) 25 Kg Capacity
Cylinder, Discharge
Nozzle and all other
accessories, fixed on
strong steel chasis with
solid rubber tyres for
easy movement.
19.1 FIRE N/A PORTABLE FIRE Nos 10
PROTECTION EXTINGUISHER
& SPRIKLER Import, Supply &
SYSTEM Installation of portable
BUILDING and hand held ABC
(Tower-2 & 3) and CO2 Type Dry
Powder fire
extinguisher of 5.0kg.
Leavy duty metal steel
cylinder with red
enamel finish, rugged
valves and siphon
tubes with all
accessories and
consumables.etc. i)
(ABC)Dry Chemical
Powder Type 5kg Fire
Extinguisher
19.2 FIRE N/A PORTABLE FIRE Nos 12
PROTECTION EXTINGUISHER
& SPRIKLER Import, Supply &
SYSTEM Installation of portable
BUILDING and hand held ABC
(Tower-2 & 3) and CO2 Type Dry
Powder fire
extinguisher of 5.0kg.
Leavy duty metal steel
cylinder with red
enamel finish, rugged
valves and siphon
tubes with all
accessories and
consumables.etc. ii)
(CO2) Carbon-di-
Oxide Type 5kg Fire
Extinguisher
20 FIRE N/A Testing, commissioning Job 1
PROTECTION trial run and balancing
& SPRIKLER of the fire protection
SYSTEM system shall be carried
BUILDING out as per specification
(Tower-2 & 3) and recommendation of
the manufacturer
equipment and
accessories.
Grand
Total :

Bill of Quantities ( SUPPLY, INSTALLATION, TESTING AND COMMISSIONING OF GAS CONNECTION WORKS)

Table
Bill of Quantities
Name :
Unit Total Total
Item Unit Price Price Price Price
Item Code Measurement
Group Description of Item Quantity
no. (if Unit In In In
In figures (BDT)
any) Words Figures Words
(BDT) (BDT) (BDT)
1.1 SUPPLY, N/A Supply, fitting and rm 190
INSTALLATION, fixing of API 5L,
TESTING AND Grade-B. ERW. pipe
COMMISSIONING for TITAS Gas line
OF GAS of Product shall be
CONNECTION titas gas approved
WORKS quality. Pipe work
shall be complete
with bends, tees,
elbows, socket,
union, reducers,
hanger, bracket,
clamp black taping
etc. complete as per
site requirement.
Approved type of
sealant shall be used
for threaded
connection. All pipe
shall be cleaned and
provided with 30
micron film
galvanization coat on
outer surface for
corrosion protection.
Before galvanization
the pipe surface shall
be properly cleaned.
Pipe work shall be
suitable to withstand
a pressure test of 80
psig. All Pipe work
shall be done by
"TITAS Approved
Contractor". 50mm
N.D
1.2 SUPPLY, N/A Supply, fitting and rm 110
INSTALLATION, fixing of API 5L,
TESTING AND Grade-B. ERW. pipe
COMMISSIONING for TITAS Gas line
OF GAS of Product shall be
CONNECTION titas gas approved
WORKS quality. Pipe work
shall be complete
with bends, tees,
elbows, socket,
union, reducers,
hanger, bracket,
clamp black taping
etc. complete as per
site requirement.
Approved type of
sealant shall be used
for threaded
connection. All pipe
shall be cleaned and
provided with 30
micron film
galvanization coat on
outer surface for
corrosion protection.
Before galvanization
the pipe surface shall
be properly cleaned.
Pipe work shall be
suitable to withstand
a pressure test of 80
psig. All Pipe work
shall be done by
"TITAS Approved
Contractor". 25mm
N.D
1.3 SUPPLY, N/A Supply, fitting and rm 440
INSTALLATION, fixing of API 5L,
TESTING AND Grade-B. ERW. pipe
COMMISSIONING for TITAS Gas line
OF GAS of Product shall be
CONNECTION titas gas approved
WORKS quality. Pipe work
shall be complete
with bends, tees,
elbows, socket,
union, reducers,
hanger, bracket,
clamp black taping
etc. complete as per
site requirement.
Approved type of
sealant shall be used
for threaded
connection. All pipe
shall be cleaned and
provided with 30
micron film
galvanization coat on
outer surface for
corrosion protection.
Before galvanization
the pipe surface shall
be properly cleaned.
Pipe work shall be
suitable to withstand
a pressure test of 80
psig. All Pipe work
shall be done by
"TITAS Approved
Contractor". 20mm
N.D
2 SUPPLY, N/A Back filling the cum 100
INSTALLATION, trenches with sand
TESTING AND (F M. 08 ) in 150 mm
COMMISSIONING layer , watering &
OF GAS consolidating each
CONNECTION layer up to finished
WORKS level.
3.1 SUPPLY, N/A BUTT WELDING Nos. 98
INSTALLATION, Providing butt
TESTING AND welded joints to
COMMISSIONING pipes. tees, elbows
OF GAS etc. made above or
CONNECTION below ground etc. all
WORKS complete in all
respects as per
specifications of
Titas Gas (T &
D)Co. Ltd. & as per
direction of the
Engineer. Before
welding end of the
pipe shall be properly
beveled and cleaned.
Measurement shall
be done on per joint
of welding. 50mm
N.D
3.2 SUPPLY, N/A BUTT WELDING Nos. 110
INSTALLATION, Providing butt
TESTING AND welded joints to
COMMISSIONING pipes. tees, elbows
OF GAS etc. made above or
CONNECTION below ground etc. all
WORKS complete in all
respects as per
specifications of
Titas Gas (T &
D)Co. Ltd. & as per
direction of the
Engineer. Before
welding end of the
pipe shall be properly
beveled and cleaned.
Measurement shall
be done on per joint
of welding. 25mm
N.D
3.3 SUPPLY, N/A BUTT WELDING Nos. 360
INSTALLATION, Providing butt
TESTING AND welded joints to
COMMISSIONING pipes. tees, elbows
OF GAS etc. made above or
CONNECTION below ground etc. all
WORKS complete in all
respects as per
specifications of
Titas Gas (T &
D)Co. Ltd. & as per
direction of the
Engineer. Before
welding end of the
pipe shall be properly
beveled and cleaned.
Measurement shall
be done on per joint
of welding. 20mm
N.D
4.1 SUPPLY, N/A VALVES & Nos. 1
INSTALLATION, FITTINGS : Supply,
TESTING AND fitting & fixing of the
COMMISSIONING different sizes valve
OF GAS Tee, Service Tee,
CONNECTION flanges, nut-bolt to
WORKS connect the pipe
lines with the Titas
Gas Main pipe line
etc. all complete in
all respects as per
specification of Titas
Gas(T&D) Co Ltd. &
as per direction of
the Engineer 50mm
N.D Tee valve
4.2 SUPPLY, N/A VALVES & Nos. 2
INSTALLATION, FITTINGS : Supply,
TESTING AND fitting & fixing of the
COMMISSIONING different sizes valve
OF GAS Tee, Service Tee,
CONNECTION flanges, nut-bolt to
WORKS connect the pipe
lines with the Titas
Gas Main pipe line
etc. all complete in
all respects as per
specification of Titas
Gas(T&D) Co Ltd. &
as per direction of
the Engineer 25mm
N.D Tee valve.
4.3 SUPPLY, N/A VALVES & Nos. 126
INSTALLATION, FITTINGS : Supply,
TESTING AND fitting & fixing of the
COMMISSIONING different sizes valve
OF GAS Tee, Service Tee,
CONNECTION flanges, nut-bolt to
WORKS connect the pipe
lines with the Titas
Gas Main pipe line
etc. all complete in
all respects as per
specification of Titas
Gas(T&D) Co Ltd. &
as per direction of
the Engineer 20mm
N.D Tee valve.
4.4 SUPPLY, N/A VALVES & Nos. 126
INSTALLATION, FITTINGS : Supply,
TESTING AND fitting & fixing of the
COMMISSIONING different sizes valve
OF GAS Tee, Service Tee,
CONNECTION flanges, nut-bolt to
WORKS connect the pipe
lines with the Titas
Gas Main pipe line
etc. all complete in
all respects as per
specification of Titas
Gas(T&D) Co Ltd. &
as per direction of
the Engineer MS
pipe Nipple,20mmdia
5 SUPPLY, N/A INSULATION Nos. 1
INSTALLATION, FLANGE : Supplying
TESTING AND fitting & fixing in
COMMISSIONING position of different
OF GAS dia Insulation Flange
CONNECTION with accessories all
WORKS complete as
recommended by
Titas Gas (T&D) Co
Ltd. & direction of
the Engineer 50mm
ND Insulation Flange
6 SUPPLY, N/A VALVE PIT : Nos. 1
INSTALLATION, Construction of
TESTING AND standard size high
COMMISSIONING pressure valve pit
OF GAS with standard M.S
CONNECTION sheet valve pit cover
WORKS as per drawing ,
specifications of
Titas Gas (T&D)Co.
Ltd. etc. all complete
in all respects & as
per direction of the
Engineer. Valve pit
shall be
1000x1000x2400mm.
7 SUPPLY, N/A Testing and Purging rm 4300
INSTALLATION, the pipe lines
TESTING AND properly as per
COMMISSIONING Specifications of
OF GAS Titas Gas (T&D)Co.
CONNECTION Ltd. etc. all complete
WORKS in all respects &
direction of the
Engineer.
8 SUPPLY, N/A GAS REGULATOR Nos. 126
INSTALLATION, Supplying fitting &
TESTING AND fixing standard
COMMISSIONING Regulator approved
OF GAS by Titas Gas
CONNECTION (T&D)Co Ltd.
WORKS including supplying of
necessary fittings
such as union socket,
Elbow, Nipple etc.
complete in all
respects as per
specification of Titas
Gas (T&D) Co. Ltd
& direction of the
Engineer. 20mm dia
low pressure
(Regulator)
9 SUPPLY, N/A LOCK WING Nos. 126
INSTALLATION, COCK: Supplying
TESTING AND fitting & fixing
COMMISSIONING 20mmx20mm (local)
OF GAS lock wing cock
CONNECTION complete in all
WORKS respects as per
specification Titas
Gas (T&D)Co Ltd.
and as per direction
of the Engineer.
20mm N.D
10 SUPPLY, N/A ROAD CUTTING sqm 55
INSTALLATION, (Bituminous Road)
TESTING AND Cutting and
COMMISSIONING permanent re-
OF GAS installment of the
CONNECTION pucca (Rigid /
WORKS flexible) road and
mending good the
damages in all
respects as per
specification Titas
Gas (T&D)Co Ltd.
and as per direction
of the Engineer.
Bituminous Road
11 SUPPLY, N/A GI PIPE Supply and rm 4250
INSTALLATION, Installation of
TESTING AND Commercial House
COMMISSIONING GI pipe for supplying
OF GAS Titas Gas including
CONNECTION supplying fitting &
WORKS fixing in position of
different dia best
quality fittings &
accessories, cutting
trenches, walls,
floors etc. and back
filling the trenches,
restoring walls, black
taping and floors etc.
all complete in all
respect as per
specification of Titas
Gas (T&D) Ltd. and
drawing and direction
of the Engineer .
20mm N.D.
12 SUPPLY, N/A LINE VALVES Nos. 126
INSTALLATION, (20mm N.D) Supply,
TESTING AND fitting and fixing in
COMMISSIONING position different dia
OF GAS one way brass stop
CONNECTION gas cock of best
WORKS quality & heavy duty
type complete in all
respect as per Titas
Gas (T&D) Co. Ltd.
and direction of the
Engineer . 20mm
N.D.
13 SUPPLY, N/A GAS BURNER Nos. 126
INSTALLATION, Supply, fitting and
TESTING AND fixing of best quality
COMMISSIONING Machine Gas Burner
OF GAS for Kitchen including
CONNECTION all Fittings & fixtures
WORKS complete as per
drawing and direction
of the Engineer.
Residacial Double
Gas Bener
14 SUPPLY, N/A TESTING AND job 1
INSTALLATION, COMMISSIONING:
TESTING AND After complete
COMMISSIONING installation the
OF GAS system shall be
CONNECTION tested and
WORKS commissioned as per
recommendation of
the manufacturer and
standard. Piping
system shall be
tested with pressure
in presence of the
Client/Consultant. All
testing of electrical
system shall be done
as per direction. Test
certification shall be
taken from the
Client/Consultant.
Grand
Total :