For Clearing Alarm LED Go to Menu Operation Sub menu Control &Testing
Under this MT_RC then Press Down Key then the Facia will Display Reset
Record USER value 1 or some Value (if there is any Defective),then press Enter
the Facia will display Eight Stars( ********),then Pressing Password with LEFT,
RIGHT,UP, DOWN & ENTER KEYS,then display shows don’t execute, by
pressing Down Key make it Execute & press Enter Key, then it will start
Rebooting & found the Value become Zero, if the value does not becomes Zero
then move to Menu Operation sub menu Operating Data recording under this
MT_RC then to Mon.Signal record by Pressing Down key we will find the
defects in the Relay.
Operation
↓
Control &Testing
↓
MT_RC
↓
Reset Record USER
(enter)
********
◄►▲▼ (enter)
Don’t Execute
▼
Execute
(enter)
The Relay will Start Rebooting & Alarm LED will Turned OFF.
If found Alarm LED got not Resetted Move to the below shown Path and check
the Defects
Operation
↓
Operating Data recording
↓
MT_RC
↓
Mon.Signal record
↓
Defects
Procedure for Clearing Out of Service LED
Parameter
↓
Function Parameter
↓
Global
↓
MAIN
↓
Protection Enabled NO ( = OFF )
(enter)
********
◄►▲▼ ( enter)
Protection Enabled NO ( = OFF )
▼
Protection Enabled YES ( = ON )