Procedure for Clearing Out of Service LED & Alarm LED

Procedure for Clearing Alarm LED

For Clearing Alarm LED Go to Menu Operation Sub menu Control &Testing
Under this MT_RC then Press Down Key then the Facia will Display Reset
Record USER value 1 or some Value (if there is any Defective),then press Enter
the Facia will display Eight Stars( ********),then Pressing Password with LEFT,
RIGHT,UP, DOWN & ENTER KEYS,then display shows don’t execute, by
pressing Down Key make it Execute & press Enter Key, then it will start
Rebooting & found the Value become Zero, if the value does not becomes Zero
then move to Menu Operation sub menu Operating Data recording under this
MT_RC then to Mon.Signal record by Pressing Down key we will find the
defects in the Relay.

Operation

Control &Testing

MT_RC

Reset Record USER

(enter)

********
◄►▲▼ (enter)
Don’t Execute

Execute
(enter)

The Relay will Start Rebooting & Alarm LED will Turned OFF.
If found Alarm LED got not Resetted Move to the below shown Path and check
the Defects

Operation

Operating Data recording

MT_RC

Mon.Signal record

Defects
Procedure for Clearing Out of Service LED

For Clearing Out of Service LED, move to Menu Parameter, submenu


Function Parameter then Global then MAIN then by Pressing Down Key ,Facia
will Display Protection Enabled NO ( = OFF ), then press Enter the Facia will
display Eight Stars( ********),then Pressing Password with LEFT, RIGHT,UP,
DOWN & ENTER KEYS,then display shows don’t execute, by pressing Down
Key make it Execute & press Enter Key,then it Protection Enabled Becomes
Protection Enabled Yes ( = ON )

Parameter

Function Parameter

Global

MAIN

Protection Enabled NO ( = OFF )

(enter)

********
◄►▲▼ ( enter)
Protection Enabled NO ( = OFF )

Protection Enabled YES ( = ON )

( enter) Then Out of Service LED will turned OFF