Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
Contents
Medium voltage
fuses
BUSSMANN SERIES FULL LINE CATALOG 1007 — JUNE 2017 Eaton.com/bussmannseries 7-1
7 — Medium voltage fuses
Introduction E- and R-Rated fuses
7-2 BUSSMANN SERIES FULL LINE CATALOG 1007 — JUNE 2017 Eaton.com/bussmannseries
Medium voltage fuses — 7
2.75 kV E-Rated medium voltage ferrule fuses Dimensions — in (mm)
Catalog symbols C
•• 2CLE-_E
B
•• JCX-_E
Ratings
•• Volts 2.75 kV
•• Amps 10 to 450 A
3.31
•• Interrupting ratings (84.1)
•• 50 kA RMS Sym. (2CLE-_E) B
•• 40 kA RMS Sym. (JCX-_E)
A
Agency information
Recommended fuseclips
Description Fuse dia. — in (mm) Catalog no.
2 (51) A3354710*
Enclosed fuseclip
A3354730*
Open fuseclip 3 (76) 1A0065
Medium voltage
Spring loaded open fuseclip 9078A67G04
fuses
* For single barrel applications only. Not sold in pairs.
Catalog symbols C
•• General purpose B
•• 5CLE-_E-D (10-25 A)
•• 5CLE-_E (10-1350 A)
•• 5HLE-_E (10-450 A)
•• JCY-_E (1-25 A)
•• Full range (per ANSI C37.40) 3.31
(84.1)
•• MV055F_ (10-450 A)
B
Ratings*
A
•• Volts 5.5 kV
•• Amps 1 to 1350 A
•• Interrupting ratings 40 to 63 kA RMS Sym.
* See catalog number tables for voltages, ampacities and interrupting ratings by
catalog number.
Agency information
Medium voltage
1100E and 4.0 (101.6) N/A N/A — — — —
1350E Consult factory —
fuses
Four barrel
HLE
10E-D–250E Non-disconnect 5HLE-PNM-D 5HLE-GNM-D CLE-NL-D —
Single barrel Disconnect 5HLE-PDM-D 5HLE-GDM-D CLE-DL-D CLE-DF-D
60 3.0 (76.2) 12.0 (304.8) 15.9 (403.9)
300E–450E Non-disconnect 5HLE-PNM-E 5HLE-GNM-E CLE-NL-E —
Double barrel Disconnect 5HLE-PDM-E 5HLE-GDM-E CLE-DL-E CLE-DF-E
* Including live parts and end fittings, end fittings supplied only when required.
† Disconnect mountings provide a means for fuse extraction only. Do not use a
disconnect mounting for load switching or fuse removal while energized.
Medium voltage
* For single barrel applications only. Not sold in pairs.
fuses
Agency information
B C
A
Indicator to be
located here
14.50 1.75
3.31
(84.1)
B C
2.12
(53.8) A
16.00
Indicator to be
located here
3.31 9.29
(84.1)
1.19
3.31
(84.1)
B C 18.38
2.12
(53.8) A
Medium voltage
200 5HCL-200E†
fuses
250 5HCL-250E†
300 5HCL-300E†
400 22.8 (579) 5HCL-400E†
450 2 5HCL-450E†
500 5HCL-500E
600 5HCL-600E
† UL Listed, Guide JEEG, File E240398.
Catalog symbols C
•• 8CLE-_E-D (10-25 A)
B
•• 8CLE-_E (10-350 A)
•• 8HLE-_E (10-350 A)
Ratings*
•• Volts 8.3 kV
3.31
•• Amps 10 to 350 A (84.1)
•• IR 50 kA RMS Sym. B
* See catalog number tables for voltages, ampacities and interrupting ratings by
catalog number.
A
Agency information
Medium voltage
Description Fuse dia. — in (mm) Catalog no.
fuses
2 (51) A3354710*
Enclosed fuseclip
A3354730*
Open fuseclip 3 (76) 1A0065
Spring loaded open fuseclip 9078A67G04
Ratings*
•• Volts 8.3 kV
•• Amps 10 to 350 A
•• Interrupting rating 50 kA RMS Sym.
* See catalog number tables for voltages, ampacities and interrupting ratings by
catalog number.
Agency information
B 2.12
(53.8)
0.44 x 0.91
Slots 0.44 (11.2) Dia. Hole A
(11.2 x 23.1) Indicator
C 0.5 (12.7)
B C 0.25
(6.4)
A
4.31 (109.5) 4.31 (109.5)
1.25 1.25
Indicator to be
(31.8) (31.8) B
located here
Medium voltage
3.31
(84.1)
fuses
7.94 (201.7)
7.94 (201.7)
B C
2.12
(53.8) A
0.5 (12.7)
Indicator to be
located here 11.62 (295.1)
11.62 (295.1) 0.38
(9.7)
3.31
(84.1)
Indicator 3.00
3.31
(76.2)
(84.1)
* Flush with surface in untripped position, trip force is 2 lb (0.9kg)
B C
2.12
(53.8) Data sheet no. 10352
A
BUSSMANN SERIES FULL LINE CATALOG 1007 — JUNE 2017 Eaton.com/bussmannseries 7-13
7 — Medium voltage fuses
AHLE Type fuses
Special dimension fuses for use with 7.2 kV rated, 800 amp AMPGARD motor starting assemblies.
Catalog symbols C
•• General purpose
B
•• 15CLE-_E-D (long construction, 10-25 A)
•• 15CLE-_E (long construction, 15-300 A)
•• 15HLE-_E (short construction, 10-250 A)
•• 15LHLE-_E (intermediate construction, 65-300 A)
•• Full range (per ANSI C37.40) 3.31
•• MV155F_ (84.1)
B
Ratings*
•• Volts 15.5 kV A
•• Amps 10 to 300 A
•• Interrupting ratings 31.5 to 63 kA RMS Sym.
* See catalog number tables for voltages, ampacities and interrupting ratings by
catalog number.
Agency information
Medium voltage
175E–300E Non-disconnect 110 15CLE-PNM-E — CLE-NL-E —
Double barrel Disconnect† 110 15CLE-PDM-E — CLE-DL-E CLE-DF-E
fuses
HLE
10E-125E Non-disconnect 95 15HLE-PNM-D 15HLE-GNM-D CLE-NL-D —
Single barrel Disconnect† 95 15HLE-PDM-D 15HLE-GDM-D CLE-DL-D CLE-DF-D
3 (76) 15 (381) 18.9 (480)
150E–250E Non-disconnect 95 15HLE-PNM-E — CLE-NL-E —
Double barrel Disconnect† 95 15HLE-PDM-E — CLE-DL-E CLE-DF-E
LHLE
65E–150E Non-disconnect — CLE-NL-D —
Single barrel Disconnect† — CLE-DL-D CLE-DF-D
3 (76) 18 (457) 20.53 (521) Not available Not available
175E–300E Non-disconnect — CLE-NL-E —
Double barrel Disconnect† — CLE-DL-E CLE-DF-E
* Including live parts and end fittings, end fittings supplied only when required.
† Disconnect mountings provide a means for fuse extraction only. Do not use a
disconnect mounting for load switching or fuse removal while energized.
Medium voltage
fuses
Ratings*
•• Volts 15.5 kV
•• Amps 10 to 300 A
•• Interrupting ratings 50 to 63 kA RMS Sym.
* See catalog number tables for voltages, ampacities and interrupting ratings by
catalog number.
Agency information
Dimensions — in (mm)
A X.XX (XX.X)
BHLE HCL
B 2.12
(53.8)
0.44 x 0.91
Slots 0.44 (11.2) Dia. Hole A
(11.2 x 23.1) Indicator
C 0.5 (12.7)
B C 0.25
(6.4)
A
4.31 (109.5) 4.31 (109.5)
1.25 1.25
Indicator to be
(31.8) (31.8) B
located here
3.31
(84.1)
7.94 (201.7)
7.94 (201.7)
B C
2.12
(53.8) A
0.5 (12.7)
Indicator to be
located here
11.62 (295.1) 0.38 11.62 (295.1)
(9.7)
3.31
(84.1)
3.31 Indicator 3.00
(84.1) (76.2)
B C
2.12
(53.8) A
Medium voltage
fuses
Ratings
•• Volts 5.5 - 38 kV
•• Amps 10 - 450 A
•• Interrupting ratings 25 to 65 kA
Agency information
Striker force
•• 50 N (11 lbs)
Recommended fuseclips
Features
Typical applications
Dimensions — in (mm)
1.77 0.59
Diameter
(45) (15)
1.34 1.02
Length
(34) (26)
See catalog numbers tables for diameter and length values.
Medium voltage
25.8 kV
258GDQSJ10E 10
fuses
258GDQSJ15E 15
258GDQSJ20E 20 21.1 (537) 2 (51)
258GDQSJ25E 25
258GDQSJ30E 30
25
258GXQSJ40E 40
258GXQSJ50E 50 21.1 (537) 3.5 (89)
258GXQSJ65E 65
258GXZSJ80E 80
28.3 (718) 3.5 (89)
258GXZSJ100E 100
38 kV
38GFZSJ10E 10
38GFZSJ15E 15
38GFZSJ20E 20 25 28.3 (718) 3 (76)
38GFZSJ25E 25
38GFZSJ30E 30
•• Volts
•• 2.4 kV (nominal) Gripping tab
for Hookeye
•• 2.54 kV (max design) constructions Indicator
D
•• Amps 25-450 A C
•• Interrupting ratings
B
•• 50 kA Sym. A
•• 80 kA Asym.
Agency information
Bolt-on
•• UL Recognized: Guide MSSS2, File E96676 EFGHI
R 0.23 [5.81] Typ.
E = 3 [76.2]
F = 2.5 [63.5]
Recommended fuse holders for standard constructions G = 2.04 [51.81
H = 0.96 [24.4]
I = 0.5 [12.7]
D
Amps Description Catalog no. Indicator
Fuseclips C
2.12
25-230A 3” Enclosed fuseclip* A3354730 [53.8]
Fuse holders
Non-disconnect holder, porcelain 2CLE-PNM-D
25-230A Non-disconnect holder, glass polyester 2CLE-GNM-D
Single barrel Disconnect holder, porcelain 2CLE-PDM-D
Disconnect holder, glass polyester 2CLE-GDM-E
Non-disconnect holder, porcelain 2CLE-PNM-E
390-450A Non-disconnect holder, glass polyester 2CLE-GNM-E
Double
barrel Disconnect holder, porcelain 2CLE-PDM-E
Disconnect holder, glass polyester 2CLE-GDM-E
* Single barrel only, not sold in pairs.
F = 2.5 [63.5]
G = 2.04 [51.81
H = 0.96 [24.4]
•• UL Recognized, Guide MSSS2, File E96676 (JCL-_R [2R-12R] and I = 0.5 [12.7]
D
JCL-A-_R [2R-12R]) Indicator
C
2.12
Recommended fuse holders for standard constructions [53.8]
B
BIL 3.0
[76.2]
3.0
[76.2] A
Amps Description (kV) Catalog no.
Bolt-on — 5MCLS-_R-A
Fuseclips 2 SLOTS (0.38X0.5)
17.7 (striker not extended)
30-230A 3” Enclosed fuseclip* A3354730 0.25 C
0.25
16.5
0.25
3” Open fuseclip — 1A0065
30-450A
3” Spring loaded open fuseclip 9078A67G04
Fuse holders for CLS / JCL / 5HCLS
Non-disconnect holder, porcelain 5HLE-PNM-D D
Medium voltage
7.75 3.1
30-230A Non-disconnect holder, glass polyester 5HLE-GNM-D
Single
Disconnect holder, porcelain 5HLE-PDM-D
fuses
barrel Ø3.0 (REF)
2.25
5CLS, JCL, JCL-A, 5ACLS, 5HCLS and 5LCLS Type mountings - in (mm)
Hole centers BIL
Catalog no. A B Overall length C Hole inset D Hole ctr. E Contact hgt. F Overall hgt. G (kV)
Disconnect single barrel†
5CLE-GDM-D
15.24 (387.1) 25 (647.7)
5CLE-PDM-D
6 (152.4) 0.62 (15.7) 1.75 (44.4) 4.5 (114.3) 11.72 (297.7) 60
5HLE-PDM-D
16.25 (412.8) 23 (584.2)
5HLE-GDM-D
Disconnect double barrel†
5CLE-GDM-E
15.24 (387.1) 25 (647.7)
5CLE-PDM-E
6 (152.4) 0.62 (15.7) 1.75 (44.4) 4.5 (114.3) 15.28 (388.1) 60
5HLE-GDM-E
16.25 (412.8) 23 (584.2)
5HLE-PDM-E
Non-disconnect single barrel
5CLE-GNM-D
15.24 (387.1) 25 (635.0)
5CLE-PNM-D
6 (152.4) 0.62 (15.7) 1.75 (44.4) 4.5 (114.3) 8.79 (223.3) 60
5HLE-GNM-D
16.25 (412.7) 23 (584.2)
5HLE-PNM-D
Non-disconnect double barrel
5HLE-PNM-E
16.25 (412.7) 6 (152.4) 25 (635.0) 0.62 (15.7)\ 1.75 (44.4) 4.5 (114.3) 12.48 (317.0) 60
5HLE-GNM-E
•• Volts
Gripping tab
•• 7.2 kV (nominal) for Hookeye
constructions Indicator
•• 8.3 kV (max design 70-170 A standard and AMPGARD Hookeye) D
•• 7.2 kV (max design 200-450 A standard and AMPGARD C
Hookeye)
•• 7.2 kV (max design 70-800 A bolt-on) B
A
•• Amps 70-800 A
•• Interrupting ratings Bolt-on
•• 50 kA Sym. R 0.23 [5.81] Typ.
EFGHI
•• 80 kA Asym. E = 3 [76.2]
F = 2.5 [63.5]
G = 2.04 [51.81
H = 0.96 [24.4]
Recommended fuse holders for standard constructions I = 0.5 [12.7]
D Indicator
Amps Description BIL (kV) Cat. No.
C
Fuseclips 2.12
[53.8]
70-230 3” Enclosed fuseclip* A3354730
3” Open fuseclip — 1A0065 B
70-450 3.0 3.0
A
3” Spring loaded open fuseclip 9078A67G04 [76.2] [76.2]
Medium voltage
Disconnect holder, glass polyester 8HLE-GDM-E
fuses
7.2 kV R-Rated fuse catalog numbers
Mounting style (minimum interrupting rating in amps)
Amps “R” Designation Standard AMPGARD Hookeye Bolt-on No. of barrels
70 2R 8CLS-2R (160) 8ACLS-2R (160) 7BCLS-2R (160)
100 3R 8CLS-3R (250) 8ACLS-3R (250) 7BCLS-3R (250)
130 4R 8CLS-4R (325) 8ACLS-4R (325) 7BCLS-4R (325)
150 5R 8CLS-5R (390) 8ACLS-5R (390) 7BCLS-5R (390) 1
170 6R 8CLS-6R (500) 8ACLS-6R (500) 7BCLS-6R (500)
200 9R 7CLS-9R (750) 7ACLS-9R (750) 7BCLS-9R (750)
230 12R 7CLS-12R (1000) 7ACLS-12R (1000) 7BCLS-12R (1000)
390 18R 7CLS-18R (1450) 7ACLS-18R (1450) 7BCLS-18R (1450)
450 24R 7CLS-24R (2500) 7ACLS-24R (2500) 7BCLS-24R (2500) 2
800 44R — — 7BCLS-44R (3250)
Catalog symbols (by maximum voltage rating) Recommended fuseclip and fuse block
•• 2.475 kV •• 12 kV Description Catalog no.
•• 2NCLPT-_ •• 12ABCNA_ Open fuseclip for 0.8 (20 mm) dia. fuses 1A1837
Single-pole open fuse block with #10-32 phil-slot
•• 3.6 kV •• 12CAV_ screw terminals rated 2500 V, 5 A maximum and PTFB-2500-JCD
•• 3.6ABCNA_ •• 15.5 kV 63 kA withstand rating
•• 3.6ABWNA_ •• 15CLPT-_E
•• 3.6CAV_ •• 15NCLPT-_E-A
•• 5.5 kV •• 15NCLPT-_E-B
•• JCW-_ •• 15.5CAV_E
•• 5CLPT-_E •• 15.5CAVH_E
•• 5NCLPT-_E •• 17.5 kV
•• 5NCLPT-_E-A •• 17.5ABGNA_
•• 5.5ABWNA_E •• 17.5CAV_
•• 5.5AMWNA_E •• 24 kV
•• 5.5CAV_E •• 24ABGNA_
•• 5.5CAVH_E •• 24CAV_
•• 7.2 kV •• 25.5 kV
•• 7.2ABWNA_ •• 25CLPT-_E
•• 7.2ABCNA_ •• 36 kV
•• 7.2AMWNA_E •• 36ABGNA_
•• 7.2CAV_ •• 36CAV_
•• 8.3 kV •• 38 kV
•• 8CLPT-_E-A •• 38CAV_E
•• CLPT-_E-B •• 38CAVH_E
•• 8NCLPT-_E •• 38CLPT-_E
•• 8NCLPT-_E-A
•• 8NCLPT-_E-B
Ratings*
•• Volts 2.4 kV to 38 kV
•• Amps 0.25 to 15 A
•• Interrupting ratings 25 to 80 kA RMS Sym.
* See catalog number tables for voltages, ampacities and interrupting ratings by
catalog number.
Agency information
Medium voltage
4 5.6 (142) 0.8 (20) 4.8 (122) — 5.5AMWNA4.0E (50) 1A1837
fuses
5 9.5 (241) 1.6 (41) 8.1 (206) 5CLPT-5E (50) 5NCLPT-5E-A (50) 1A0835
5 1 (25) 4.4 (112) — 5.5ABWNA5E (50) A3354705
5.6 (142)
5 0.8 (20) 4.8 (122) — 5.5AMWNA5.0E (50) 1A1837
5 7.3 (185) 5.9 (150) — JCW-5E (40)
10 9.5 (241) 1.6 (41) 8.1 (206) 5CLPT-10E (50) 5NCLPT-10E (50) 1A0835
15 7.4 (188) 6.2 (157) — 5.5CAV15E (50)
† Due to manufacturing variations, this fuse does not comply with ANSI C37.46 for "E" rating.
Catalog no.
Mounting (including live parts, end fittings)**
Fuse mounting BIL Live parts End fittings
Amps type* (kV) Porcelain insulator Glass-polyester insulator (including end fittings)*** (disconnect only)
5.5 kV maximum (4.8 kV nominal)†
Non-disconnect 5CLPT-PNM-A 5CLPT-GNM-A CLPT-NL —
0.5–10 60
Disconnect†† 5CLPT-PDM-A 5CLPT-GDM-A CLPT-DL CLPT-DF
8.3 kV maximum (7.2 kV nominal)†
Non-disconnect 8CLPT-PNM-A 8CLPT-GNM-A CLPT-NL —
0.5–2
Disconnect†† 8CLPT-PDM-A 8CLPT-GDM-A CLPT-DL CLPT-DF
75
Non-disconnect 8CLPT-PNM-B 8CLPT-GNM-B CLPT-NL —
3–10
Disconnect†† 8CLPT-PDM-B 8CLPT-GDM-B CLPT-DL CLPT-DF
15.5 kV maximum (14.4 kV nominal)
Medium voltage
Non-disconnect 15CLPT-PNM-A 15CLPT-GNM-A CLPT-NL —
0.5–2
fuses
Disconnect ††
15CLPT-PDM-A 15CLPT-GDM-A CLPT-DL CLPT-DF
95
Non-disconnect 15CLPT-PNM-B 15CLPT-GNM-B CLPT-NL CLPT-DF
3–10
Disconnect†† 15CLPT-PDM-B 15CLPT-GDM-B CLPT-DL —
25.5 kV Maximum (23 kV Nominal)
Non-disconnect 25CLPT-PNM-A 25CLPT-NL —
0.5–1 150 —
Disconnect ††
25CLPT-PDM-A 25CLPT-DL CLPT-DF
38 kV Maximum (34.5 kV Nominal)
Disconnect†† Not applicable CLPT-NL CLPT-DF
0.5 N/A Not applicable
Non-disconnect 38CLPT-PNM-A CLPT-DL —
* See page 7-35 for dimensions and diagrams of typical mountings.
** End fittings supplied only when required.
† Refers to 5CLPT, 5NCLPT, 8CLPT and 8NCLPT-A or -B fuses only.
†† Disconnect mountings provide a means for fuse extraction only. Do not use a disconnect mounting for load switching or fuse removal while energized.
Ratings*
•• Volts 1-10 kV
•• Amps 1/16-10 A
* See catalog number table for possible volt/amp combinations.
Features
Typical applications
Test specifications
Dimensions — in (mm)
Catalog symbol kV Amps Max. IR (amps) Diameter Length
HVA 1 1/16, 1/10, 1/8, 2/10, 1/4, 3/8, 1/2, 3/4, 1, 1-1/2, 2, 3, 4, 6, 10 20 DC / 30 AC 3 (76)
0.4 (10)
HVB 2.5 1/2, 3/4, 1, 1-1/2, 2, 3 8 DC / 12 AC 4.5 (114)
HVJ 5 1/16, 1/8, 1/4, 1/2, 3/4, 1, 1-1/2, 2, 4, 6* 4 DC / 6 AC 5 (126.9)
0.8 (21)
HVL 10 1/16, 1/8, 1/4, 1/2, 1, 1-1/2, 2, 3* 2 DC / 3 AC 10 (254)
HVR 1 1/2, 1, 2, 3, 4, 5 500 AC 3 (76)
HVW 1.2 1, 2, 3, 4, 5, 8 4 DC / 167 AC 0.4 (10) 2.3 (57)
HVT 2.5 1/2, 1, 2, 3, 5 500 AC 4.5 (114)
HVU 5 1/2, 1, 2, 3, 4, 5 500 AC 5 (127)
0.8 (20)
HVX 10 1/2, 1, 3, 5 1200 AC 10 (254)
* AC only.
Medium voltage
fuses
BUSSMANN SERIES FULL LINE CATALOG 1007 — JUNE 2017 Eaton.com/bussmannseries 7-31
7 — Medium voltage fuses
DIN dimensioned IEC fuses for transformer
protection
DIN dimension fuses to Specification DIN 43625 covering current-
limiting fuses with performance in compliance with IEC 60282-1.
These are in accordance with the R10 and, in some cases, the R20 Typical applications
series of preferred numbers.
•• Medium voltage IEC designed equipment
Ratings*
Recommended fuseclips
•• Volts 3.6-36 kV
•• Amps 6.3-100 A •• Catalog numbers 270303, A3354745, see page 7-36.
•• Interrupting ratings 20-50 kA
* See catalog number table for possible volt/amp combinations. Dimensions — in (mm)
Striker -in
Agency information operated position
0.59
Diameter
(15)
•• Compliant with DIN dimensional standard DIN 43625, VDE 0670 1.77
(45)
part 4, VDE 0670 part 40Z and with IEC 60282-1 (2005)
Features
Length 1.34 1.02
(34) (26)
For diameter and length values, see catalog number table.
•• DIN dimensioned for retrofitting in existing hardware
•• Open fuse indicator for ease in troubleshooting
•• Designed for use in IEC equipment
7-32 BUSSMANN SERIES FULL LINE CATALOG 1007 — JUNE 2017 Eaton.com/bussmannseries
Medium voltage fuses — 7
Expulsion fuse links for use in high voltage Typical applications
distribution cut-outs •• Primary side transformer protection
Expulsion fuse links available in •• Feeder protection
a wide range of options from •• Capacitor bank protection
15 to 72 kV in ANSI Type T and
K characteristics. Expulsion Fuse label color coding
fuse link current ratings should
be selected on the basis of Type Color Type Color
maximum expected transient
no-damage currents rather than XA Pink T Green
on full load current. In addition, K Yellow S —
the selection of higher current
ratings will reduce the possibility Dimensions — mm (in)
of supply interruption due to
transient surges such as those A
125 (4.92)
due to lightning strikes.
Double tail
Links should be handled with a reasonable degree of care when Ø10 (0.39)
installing. Excessively rough handling may damage the element.
Universal
It is normal, under certain fault conditions, for arc extinguishing
material and/or metal particles to be expelled from the fuse Button head
assembly. It is therefore recommended that reasonable precautions
be taken to prevent the installation being approached by Ø7.5 (0.29)
unauthorized persons. Ø19 (0.75) Removeable button head
Medium voltage
Features
fuses
•• Wide range of options available from 15 kV to 72 kV in ANSI T and
K characteristics.
•• Extra rapid option also available.
BUSSMANN SERIES FULL LINE CATALOG 1007 — JUNE 2017 Eaton.com/bussmannseries 7-33
7 — Medium voltage fuses
FL — Type H, and EEI-NEMA Type K and T fuses Type H (high-surge), K and T universal tin element cutout
fuses rated to 27 kV
Medium voltage fuses: Type H (high surge), EEI-NEMA Type K (fast-
acting), EEI-NEMA Type T (time-delay). Catalog no.
7-34 BUSSMANN SERIES FULL LINE CATALOG 1007 — JUNE 2017 Eaton.com/bussmannseries
Medium voltage fuses — 7
PT fuse mountings — in (mm)
Catalog no. Hole ctrs. A Hole ctrs. B Overall length C Hole Inset D Hole ctrs. E Contact hgt. F Overall hgt. G BIL (kV)
5.5 kV Disconnect†
5CLPT-GDM-A
9.37 (238) 6 (152.4) 18.63 (473.2) 0.75 (19) 1.75 (44.4) 4.5 (114.3) 9.56 (242.8) 60
5CLPT-PDM-A
5.5 kV Non-disconnect
5CLPT-GNM-A
9.37 (238) 6 (152.4) 18.63 (473.2) 0.75 (19) 1.75 (44.4) 4.5 (114.3) 6.94 (176.2) 60
5CLPT-PNM-A
8.3 kV Disconnect†
8CLPT-GDM-A
8CLPT-GDM-B 9.37 (238) 18.63 (473.2)
6 (152.4) 0.75 (19) 1.75 (44.4) 7 (177.8) 12.06 (306.3) 75
8CLPT-PDM-A
8CLPT-PDM-B 12.74 (323.6) 22 (558.8)
8.3 kV Non-disconnect
8CLPT-GNM-A
9.37 (238) 18.63 (473.2)
8CLPT-PNM-A
6 (152.4) 0.75 (19) 1.75 (44.4) 7 (177.8) 9.44 (239.8) 75
8CLPT-GNM-B
12.75 (323.8) 22 (558.8)
8CLPT-PNM-B
15.5 kV Disconnect†
15CLPT-GDM-A
12.74 (323.6) 22 (558.8)
15CLPT-PDM-A
6 (152.4) 0.75 (19) 1.75 (44.4) 7 (177.8) 12.06 (306.3) 95
15CLPT-GDM-B
17.46 (443.5) 26.63 (676.4)
15CLPT-PDM-B
15.5 kV Non-disconnect
15CLPT-GNM-A
12.74 (323.6) 22 (558.8)
15CLPT-PNM-A
6 (152.4) 0.75 (19) 1.75 (44.4) 7 (177.8) 9.44 (239.8) 95
15CLPT-GNM-B
17.46 (443.5) 26.63 (676.4)
15CLPT-PNM-B
25.5 kV Disconnect†
25CLPT-PDM-A 19.12 (485.6) 7 (177.8) 26.63 (676.4) 0.75 (19) 1.75 (44.4) 12 (304.8) 17.06 (433.3) 150
25.5 kV Non-disconnect
25CLPT-PNM-A 26.63 (676.4) 7 (177.8) 26.63 (676.4) 0.75 (19) 1.75 (44.4) 12 (304.8) 14.75 (374.6) 150
† Disconnect mountings provide a means for fuse extraction only. Do not use a disconnect mounting for load switching or fuse removal while energized.
E E
Medium voltage
fuses
A C A C
E E
D B
D B
BUSSMANN SERIES FULL LINE CATALOG 1007 — JUNE 2017 Eaton.com/bussmannseries 7-35
7 — Medium voltage fuses
Recommended fuseclips
Figure 1 Figure 2
ØC
A
D
B
26.5
6.5
Figure 3 Figure 4
7-36 BUSSMANN SERIES FULL LINE CATALOG 1007 — JUNE 2017 Eaton.com/bussmannseries