Temperature Switch
Thermophant® T TTR31
Temperature switch for the safe measurement, monitoring and
control of process temperatures
Application
Temperature switch for the monitoring, display and
control of process temperatures in a range from
-50 to 200°C (-58 to 392°F):
Thermophant® T TTR31
− with thread connections or coupling
• May not be used in moisture latent environments
• Electronic versions
– one PNP switch output
– two PNP switch outputs
– 2 x PNP switch outputs or one PNP switch output
and 4 to 20 mA output (active)
Benefits at a glance
This compact temperature switch impresses with the
latest in technology being used:
• Integrated switching electronics for decentral and
economic process monitoring and control
• Quick and flexible process connection thanks to
modular connections
• High reproducibility and long-term stability
• Function check and information onsite thanks to LEDs
and digital display
• Long-term stable temperature sensor made of
platinum (Pt100 class A as per IEC 60751)
• High accuracy across the entire ambient temperature
range and short response time
• Operation and visualization also with PC and
ReadWin® 2000 configuration software
• Upper part of housing can be rotated by 310°
• DESINA-compliant
4â
TI105R/24/ae
Function and system design
Measuring principle Electronic recording and conversion of input signals in industrial temperature measurement. A platinum sensor
located at the measuring tip changes its resistance value depending on the temperature. This resistance value
is recorded electronically. The relation of the measured resistance value and temperature is defined by the
international standard IEC 60751.
Thermophant® TTR31
T09-TTR31xxx-14-xx-xx-xx-000
2
DC voltage version
PNP switch output of electronics.
Power supply e.g. with a power supply unit.
Preferably in conjunction with programmable logic controllers (PLC) or for controlling a relay.
A B
2 2
24V 13 24V 13
24V OV 24V OV
OV OV
Endress+Hauser
Endress+Hauser
1 1
RNB130
RNB130
T IN AC T IN AC
2 3
24V 13
24V OV
OV
Endress+Hauser
1
RNB130
T IN AC
T09-TTR31xxx-14-xx-xx-xx-001
3
Input
Measured variable Temperature (temperature-linear transmission behaviour)
Pt100 as per IEC 60751 -50 to 150 °C (-58 to 302 °F) 20 K (36 °F)
-50 to 200 °C (-58 to 392 °F) with neck
Output
Output signal DC voltage version: (short-circuit proof version)
• 1x PNP switch output
• 2x PNP switch outputs
• 2x PNP switch outputs or one PNP switch output and 4 to 20 mA output (active)
Signal on alarm • Analog output: ≤ 3.6 mA or ≥ 21.0 mA adjustable (if setting ≥ 21.0 mA the output is > 21.5 mA)
• Switch outputs: at safety condition (switch open)
Inductive load To prevent electrical interference, only operate an inductive load (relays, contactors, solenoid valves) when
directly connected to a protective circuit (free-wheeling diode or capacitor).
4
Power supply
Electrical connection Plug connection
A B
T09-TTR31xxx-04-00-xx-xx-000
A: M12x1 connector
B: M16x1.5 or NPT ½" valve plug
Device connection
• DC voltage version with M12x1 connector
A1 A2
L+ A2’ L+
2 1 2 1
3 4 R1 3 4
R1 1
L– L–
A3 A4
L+ A4’ L+
2 1 2 1
3 4 3 4
R1 4 to 20mA 4 to 20mA 1
L– L–
P01-PTx3xxxx-04-xx-xx-xx-002
A2’ 2x PNP switch output R1 and m (diagnosis/break contact with adjustment "DESINA") TTR31-A1B*******
A4’ 1x analog output (4 to 20 mA) and 1x PNP switch output m (diagnosis/break contact TTR31-A1C*******
with adjustment "DESINA")
B 1 L+
R 2
L–
P01-PTx3xxxx-04-xx-xx-xx-003
5
Supply voltage DC voltage version 12 to 30 V DC (reverse polarity protection)
Current consumption Without load < 60 mA, with reverse polarity protection
Performance characteristics
The percentage information in the "Performance characteristics" section refers to the sensor nominal value.
Sensor
• Tolerance class A as per IEC 60751, -50 to 200°C (-58 to 392°F)
• Maximum measured error in °C = ± 0.15 + 0.002 ⋅ ⏐T⏐
⏐T⏐ = Process temperature in °C without taking sign into account.
Total error
Total error = electronics error + sensor error, e.g. for process temperatures:
-50 to 75°C (-58 to 167°F) ≤ 0.5 K (0.9°F)
75 to 200°C (167 to 392°F) ≤ 0.75 K (1.35°F)
Long-term drift ≤ 0.1 K (0.18 °F) per year under reference operating conditions
Sensor response time Measured as per IEC 60751, in water flowing at 0.4 m/s (1.3 ft/s)
t50 t90
Long-term reliability Mean time between failure (MTBF) > 100 years
(calculated according to "British Telecom Handbook of Reliability Data No. 5")
Analog output • Maximum measured error = switch point error and display error + 0.1%
• Rise time T90: ≤ 200 ms
• Settling time T99: ≤ 500 ms
6
Operating conditions: Installation instructions
Installation instructions • Any orientation
• Housing can be rotated up to 310°
Degree of protection • With M16x1.5 or NPT ½" valve plug: IP 60 (similar to NEMA 3)
• With M12x1 connector: IP 60 (similar to NEMA 3)
Caution !
The electronics housing is rated at IP60 (similar to NEMA 3) only and can not be used for wash-down service.
Process temperature limits -50 to 150°C (-58 to 302°F) or -50 to 200°C (-58 to 392°F) with neck
Restrictions depending on process connection and ambient temperature:
• No restriction with coupling (see Accessories, order no. 51004751, 51004753) and neck tube length min.
20 mm (0.79")
• with process connection:
7
Process pressure limits Maximum permitted process pressure depending on the insertion length
a0008063-en
The diagram takes into consideration not only the overpressure but also the pressure load caused by the flow,
whereby a safety factor of 1.9 has been specified for operation with flow. The maximum permitted static
operating pressure is lower at greater insertion lengths due to the increased bending load caused by the flow.
The calculation assumes the maximum permitted medium velocity for the respective insertion length (see
diagram below).
Caution!
The maximum process pressure for the conical metal-metal process connection (Option MB) is 16 bar =
1.6 MPa (232 psi)!
a0008065-en
The permitted flow velocity is the minimum from resonance velocity (resonance distance 80%) and load or
buckling caused by flow, which would lead to failure of the thermometer tube or to exceedance of the safety
factor (1.9). Calculation was performed for the specified limit operating conditions of 200°C (392°F) and
≤10 MPa (1450 PSI) process pressure.
8
Mechanical construction
Design, dimensions Dimensions
2.05” 3.82”
(52) (97.1)
1.66”
(42.1)
1.38”
Æ 0.55” Æ 0.24” Æ 0.24” Æ 0.24”
(35)
(14) (6) (6) (6)
L L L
Æ 0.24”
(6)
T09-TTR31xxx-06-xx-x-en-000
Process connection
L L L
A B C
T09-TTR31xxx-17-xx-xx-en-000
A0008068-EN
9
Weight approx. 300 g (10.6 oz), depends on sensor length and process connection
Human interface
Operating elements Position of display and operating elements
Operating keys
E
Digital display
Illumination white = OK
Illumination red = error/fault
LED for status
Green = ok
Red = error/fault Yellow LEDs for switching states
LED on = switch closed
LED red/green blinking LED off = switch open
= warning
Communication jack
for personal computer
T09-TTR31xxx-19-xx-xx-en-001
Damping display value, output signal: anywhere between 0 to 40 s (in increments of 0.1 s)
Display:
−Display of measured value or of configured switch point
− Rotation of display by 180°
− Switching off of display
10
Function group Operating options
Switch-back point:
− Input value
− Acceptance of applied value
Switch-back point anywhere between 0 to 99.5 % URL (in increments of 0.1 %)
Delay of switch point and switch-back point: can be set anywhere between 0 to 99 s (in
increments of 0.1 s)
4-20 (configuration of Lower Range Value (LRV) and Upper Range Value (URV) of analog output:
analog output, only − Input value
for corresponding − Acceptance of applied value
electronic version)
Setting of error current: choice of ≤ 3.6 mA / ≥ 21.0 mA / last current value
Security locking
11
a b
T T
SP
SP
RSP RSP
t
t
1
0 4 1
1 3 0
0
2
1 1
0
T09-TTR31xxx-05-xx-xx-xx-001
Operation with PC
a0008072
In addition to the operating options listed in the previous "Local operation" section, the ReadWin® 2000 or
FieldCare configuration software provides further information on the Thermophant® T:
Device status/error
Order code
Hardware version
Software version
Device version
The configuration kit TXU10-AA is available as an accessory (see chap. ’accessories’). For the order of the
configuration kit FXA291 or software FieldCare please ask your E+H sales organization.
12
Certificates and approvals
CE-Mark The device meets the legal requirements of the EC directives. Endress+Hauser confirms that the device has
been successfully tested by applying the CE mark.
Other standards and • IEC 60529: Degree of protection provided by housing (IP-Code)
guidelines • IEC 61010: Safety requirements for electrical measurement, control and laboratory use.
• IEC 61326: Electromagnetic compatibility (EMC requirements)
• NAMUR: Standards working group for measurement and control technology in the chemical industry.
(www.namur.de)
UL listed for Canada and USA The device was examined by Underwriters Laboratories Inc. (UL) in accordance with the standards UL
61010B-1 and CSA C22.2 No. 1010.1-92 and listed under the number E225237 UL.
Ordering information
Thermophant® T TTR31
Product structure Approval:
A For non-hazardous areas
Electrical connection:
1 Plug M12x1, IP66
2 Valve plug M16x1.5, ISO4400, IP60
3 Valve plug NPT ½", ISO4400, IP60
Display:
1 Digital
Adjustment; Unit:
1 Factory setting; Unit °C (refer to Questionnaire)
2 Factory setting; Unit °F (refer to Questionnaire)
S Switch output 1, see Questionnaire
T Switch output 1+2, see Questionnaire
U Switch output + analog output, see Questionnaire
V Switch 1 + 2 DESINA-diag., see Questionnaire
W Analog output, switch DESINA-diag., see Questionnaire
Process connection:
AA Compr. fitting, L=>100 mm (3.94") Insertion length, 316L
AB Thread ISO228 G¼", 316L
AE Thread ISO 228 G½", 316L
DA Thread ANSI NPT ¼", 316L
DE Thread ANSI NPT ½", 316L
Version:
A Standard, documentation german
B Standard, documentation english
C Standard, documentation french
13
Questionnaire
R09-TTR31xxxx-16-06-xx-a2-001
Accessories
All dimensions in inches (mm).
EN10204-3.1 = Material certificate (melt analysis)
Welding boss with sealing Collar welding boss moveable with sealing taper and ø 0.24”
(6) G ½”
taper pressure screw; material of parts in contact with the
Af24
process: 316L SS, PEEK, max. process pressure 10 bar 1.42”
(145 psi) (36)
0.98”
Order number: 51004751 (25)
ø 1.18”
(30)
T09-TSM470AX-06-09-00-en-000
14
Collar welding boss Material of parts in contact with process: 316L SS ø 0.24” G ½”
(6)
Order no. 51004752
0.98”
(25)
ø 1.18”
(30)
T09-TSM470BX-06-09-00-en-000
a0006621
+1
(45 )
AF27
0.59”
(15)
G ½”
T09-TSM470AX-06-09-00-en-001
P01-PMP13xxx-00-xx-00-xx-003
0.58”
(14.8)
T09-TTR3xxxx-06-09-xx-en-000
Connecting cable PVC cable, 4 x 0.34 mm2 (22 AWG) with M12x1 1 (BN) +
coupling, elbowed, screw plug, length 5 m (16.4 ft), 1 2 2 (WH) R2
IP 60 4 3
3 (BU) -
Order number: 51005148 4 (BK) R1
Core colors:
- 1 = BN brown
- 2 = WH white
- 3 = BU blue
T09-TTR31xXX-00-00-xx-xx-002
- 4 = BK black
15
Connecting cable with LED PVC cable, 4 x 0.34 mm2 (22 AWG) with M12x1 coupling,
with LED, elbowed, 316L SS screw plug, length 5 m (16.4 ye 1
ft), specially for hygiene applications, IP 60
Order number: 52018763 ye 2 gn
Display:
−gn: device operational
−ye1: switch status 1
−ye2: switch status 2
Note!
Not for use at devices with "4 to 20 mA analog output"
option!
T09-TTR31xxx-00-00-xx-xx-001
Power supply • Power supply Easy Analog RNB130 by Endress+Hauser with nominal output current IΝ = 1.5 A.
Details see Technical information TI120R/24/ae.
• Process display RIA452 by Endress+Hauser with transmitter power supply,
max. output current I = 250 mA.
Details see Technical information TI113R/24/ae.
Documentation
Technical information • Process pressure switch Ceraphant T PTC31, PTP31: TI384P/24/ae
• Easy Analog RNB130: TI120R/24/ae
• Process display RIA452: TI113R/24/ae
• Multi Channel Recorder Ecograph T: TI115R/24/ae
• Data logger Minilog B: TI089R/24/ae
TI105R/24/ae/12.09
© 2009 Endress+Hauser, Inc.