Sei sulla pagina 1di 210

CLIENT M/S.

REFEX ENERGY LIMITED

DOCUMENT NO DATE
PROJECT SOLAR PV POWER PLANT OF 50MW AC
1617101-RFX-NLC-SWYD-F&C-018 06.03.18
DESIGNED CHECKED REV
TITLE: FOUNDATION & COLUMN DESIGN FOR CRB
GS SBK 0

CONTENTS

1 GENERAL

2 SUPPORT REACTION

3 DESIGN OF FOOTING

4 COLUMN DESIGN
CLIENT M/S. REFEX ENERGY LIMITED

DOCUMENT NO DATE
PROJECT SOLAR PV POWER PLANT OF 50MW AC
1617101-RFX-NLC-SWYD-F&C-018 06.03.18
DESIGNED CHECKED REV
TITLE: FOUNDATION & COLUMN DESIGN FOR CRB
PROJECT #REF!

TITLE #REF!

TABLE OF CONTENTS

SL.NO DESCRIPTION

1 GENERAL

2 REFERENCE CODES & BOOKS

3 LOAD CALCULATION

4 DESIGN OF ROOF SLAB

5 DESIGN OF FOOTING

6 STAAD INPUT/OUTPUT
PROJECT #REF!

TITLE #REF!
CLIENT M/S. REFEX ENERGY LIMITED

DOCUMENT NO DATE
PROJECT SOLAR PV POWER PLANT OF 50MW AC
1617101-RFX-NLC-SWYD-F&C-018 06.03.18
DESIGNED CHECKED REV
TITLE: FOUNDATION & COLUMN DESIGN FOR CRB
GS SBK 0

1.0 GENERAL

Design Ground Elevation

Finished Ground Level (FGL+0.00)

Concrete Grade

Grade of concrete for all RCC works shall be M25

Reinforcement Steel

Reinforcement for steel shall be HYSD conforming to various requirements of IS:1786 (High strength
deformed steel bars and wires for concrete reinforcement Grade Fe500)

Cover to Reinforcement

Clear cover to main reinforcement is as follows :

Top Bottom Sides


(mm) (mm) (mm)

Foundation 50 50 50

Column/Pedestal - - 40

Floor Beams 30 30 30

Slab/ Parapet 25 25 25

Net Safe Bearing capacity of Soil shall be as pr the soil report.


CLIENT M/S. REFEX ENERGY LIMITED

DOCUMENT NO DATE
PROJECT SOLAR PV POWER PLANT OF 50MW AC
1617101-RFX-NLC-SWYD-F&C-018 06.03.18
DESIGNED CHECKED REV
TITLE FOUNDATION & COLUMN DESIGN FOR CRB
GS KN 0

SUPPORT REACTIONS

Node L/C Force-X kN Force-Y kN Force-Z kN Moment-X Moment-Y Moment-Z


kN-m kN-m kN-m
1 101 DL+IL 3.447 139.36 3.3 2.476 0.223 -3.085
102 DL+WL (+X) -1.207 127.659 5.618 6.537 0.117 4.366
103 DL+WL (+X) 3.499 135.437 7.341 9.249 0.082 -3.14
104 DL+WL (+Z) 1.3 134.027 8.512 11.414 0.061 0.312
105 DL+WL (+Z) 0.12 126.759 3.359 2.575 0.146 2.353
106 DL+WL (-X) -1.209 127.659 5.786 6.65 0.126 4.369
107 DL+WL (-X) 3.503 135.436 7.038 9.045 0.065 -3.146
108 DL+WL (-Z) 1.473 134.046 8.516 11.42 0.014 0.154
109 DL+WL (+Z) -0.192 126.724 3.352 2.565 0.23 2.637
110 DL+EQ (+X) -2.971 119.8 3.365 2.587 0.232 7.331
111 DL+EQ (+Z) 3.455 121.95 -3.192 -8.876 0.271 -3.07
112 DL+EQ (-X) 9.959 142.896 3.246 2.387 0.139 -13.602
113 DL+EQ (-Z) 3.533 140.746 9.803 13.85 0.1 -3.202
114 DL+IL+WL (+X) -0.313 136.408 5.149 5.716 0.167 2.916
115 DL+IL+WL (+X) 3.461 141.029 6.529 7.888 0.132 -3.099
116 DL+IL+WL (+Z) 1.701 139.9 7.466 9.62 0.115 -0.337
117 DL+IL+WL (+Z) 0.758 134.086 3.343 2.548 0.183 1.295
118 DL+IL+WL (-X) -0.305 134.806 5.286 5.809 0.167 2.908
119 DL+IL+WL (-X) 3.464 141.028 6.287 7.725 0.119 -3.103
120 DL+IL+WL (-Z) 1.84 139.916 7.47 9.624 0.078 -0.463
121 DL+IL+WL (-Z) 0.508 134.058 3.338 2.541 0.25 1.523
122 DL+IL+EQ (+X) -1.716 128.519 3.348 2.559 0.253 5.278
123 DL+IL+EQ (+Z) 3.425 130.239 -1.897 -6.612 0.284 -3.043
124 DL+IL+EQ (-X) -1.716 128.519 3.348 2.559 0.253 5.278
125 DL+IL+EQ (-Z) 3.416 131.841 -1.898 -6.614 0.291 -3.033
126 DL+WL (+X) -1.556 114.524 5.287 6.288 0.098 4.68
127 DL+WL (+X) 3.15 122.303 7.011 9 0.063 -2.826
128 DL+WL (+Z) 0.95 120.892 8.182 11.166 0.042 0.626
129 DL+WL (+Z) -0.229 113.624 3.028 2.326 0.127 2.666
130 DL+WL (-X) -1.558 114.525 5.456 6.401 0.107 4.683
131 DL+WL (-X) 3.154 122.301 6.707 8.796 0.047 -2.832
132 DL+WL (-Z) 1.123 120.911 8.186 11.171 -0.004 0.468
133 DL+WL (-Z) -0.541 113.589 3.021 2.316 0.211 2.951
134 DL+EQ (+X) -3.321 106.666 3.035 2.339 0.214 7.645
135 DL+EQ (+Z) 3.105 108.815 -3.522 -9.125 0.253 -2.756
136 DL+EQ (-X) 9.609 129.761 2.916 2.138 0.121 -13.289
137 DL+EQ (-Z) 3.183 127.612 9.472 13.601 0.082 -2.888
2 101 DL+IL 12.186 180.324 -1.729 -1.495 0.173 -13.264
102 DL+WL (+X) 5.672 164.022 0.762 1.805 0.161 -1.627
103 DL+WL (+X) 11.584 172.393 2.261 3.809 0.118 -12.346
104 DL+WL (+Z) 9.21 169.859 3.646 5.639 0.139 -8.015
105 DL+WL (+Z) 6.643 164.487 -1.664 -1.412 0.141 -3.428
106 DL+WL (-X) 5.678 164.021 0.735 1.779 0.16 -1.637
107 DL+WL (-X) 11.574 172.394 2.309 3.855 0.119 -12.329
108 DL+WL (-Z) 8.68 170.108 3.65 5.644 0.109 -7.076
109 DL+WL (+Z) 7.596 164.039 -1.672 -1.421 0.195 -5.118
110 DL+EQ (+X) 3.197 157.605 -1.658 -1.403 0.197 2.575
111 DL+EQ (+Z) 11.513 163.204 -8.438 -10.533 0.151 -12.259
112 DL+EQ (-X) 19.871 181.894 -1.773 -1.557 0.091 -27.149
113 DL+EQ (-Z) 11.555 176.294 5.007 7.572 0.137 -12.314
114 DL+IL+WL (+X) 7.496 175.742 0.252 1.133 0.186 -4.736
CLIENT M/S. REFEX ENERGY LIMITED

DOCUMENT NO DATE
PROJECT SOLAR PV POWER PLANT OF 50MW AC
1617101-RFX-NLC-SWYD-F&C-018 06.03.18
DESIGNED CHECKED REV
TITLE FOUNDATION & COLUMN DESIGN FOR CRB
GS KN 0

115 DL+IL+WL (+X) 12.095 180.325 1.455 2.739 0.146 -13.116


116 DL+IL+WL (+Z) 10.196 178.297 2.562 4.203 0.162 -9.651
117 DL+IL+WL (+Z) 8.142 174 -1.686 -1.438 0.165 -5.982
118 DL+IL+WL (-X) 7.37 173.627 0.234 1.115 0.18 -4.549
119 DL+IL+WL (-X) 12.087 180.325 1.493 2.776 0.147 -13.102
120 DL+IL+WL (-Z) 9.772 178.496 2.565 4.207 0.139 -8.9
121 DL+IL+WL (-Z) 8.905 173.641 -1.692 -1.445 0.207 -7.333
122 DL+IL+EQ (+X) 5.386 168.494 -1.68 -1.43 0.209 -1.179
123 DL+IL+EQ (+Z) 12.038 172.973 -7.105 -8.734 0.172 -13.047
124 DL+IL+EQ (-X) 5.386 168.494 -1.68 -1.43 0.209 -1.179
125 DL+IL+EQ (-Z) 12.169 175.088 -7.108 -8.737 0.178 -13.242
126 DL+WL (+X) 4.519 147.047 0.933 1.953 0.146 -0.398
127 DL+WL (+X) 10.431 155.418 2.433 3.957 0.103 -11.118
128 DL+WL (+Z) 8.057 152.884 3.817 5.787 0.124 -6.786
129 DL+WL (+Z) 5.489 147.512 -1.493 -1.264 0.127 -2.199
130 DL+WL (-X) 4.525 147.046 0.906 1.927 0.146 -0.408
131 DL+WL (-X) 10.42 155.419 2.481 4.003 0.104 -11.1
132 DL+WL (-Z) 7.527 153.133 3.821 5.792 0.095 -5.848
133 DL+WL (-Z) 6.443 147.064 -1.5 -1.273 0.18 -3.889
134 DL+EQ (+X) 2.044 140.63 -1.486 -1.255 0.183 3.804
135 DL+EQ (+Z) 10.36 146.229 -8.267 -10.385 0.136 -11.031
136 DL+EQ (-X) 18.718 164.919 -1.602 -1.409 0.077 -25.92
137 DL+EQ (-Z) 10.402 159.319 5.179 7.72 0.123 -11.086
3 101 DL+IL 11.827 166.137 0.859 0.588 -0.247 -12.819
102 DL+WL (+X) 5.424 148.57 3.363 3.897 -0.196 -1.415
103 DL+WL (+X) 11.202 155.212 4.955 5.984 -0.232 -11.886
104 DL+WL (+Z) 8.826 151.302 6.32 7.793 -0.251 -7.586
105 DL+WL (+Z) 6.454 151.536 0.92 0.669 -0.147 -3.279
106 DL+WL (-X) 5.429 148.574 3.385 3.916 -0.196 -1.424
107 DL+WL (-X) 11.192 155.205 4.916 5.949 -0.232 -11.869
108 DL+WL (-Z) 8.341 151.539 6.325 7.799 -0.206 -6.723
109 DL+WL (+Z) 7.327 151.11 0.912 0.659 -0.228 -4.832
110 DL+EQ (+X) 2.975 144.719 0.925 0.676 -0.22 2.801
111 DL+EQ (+Z) 11.247 160.864 -5.984 -8.557 -0.2 -11.933
112 DL+EQ (-X) 19.481 168.818 0.807 0.521 -0.194 -26.62
113 DL+EQ (-Z) 11.209 152.674 7.716 9.754 -0.214 -11.886
114 DL+IL+WL (+X) 7.184 159.579 2.856 3.227 -0.239 -4.423
115 DL+IL+WL (+X) 11.687 163.018 4.132 4.898 -0.259 -12.618
116 DL+IL+WL (+Z) 9.786 159.89 5.223 6.346 -0.275 -9.178
117 DL+IL+WL (+Z) 7.888 160.078 0.903 0.647 -0.191 -5.733
118 DL+IL+WL (-X) 7.068 157.708 2.875 3.244 -0.231 -4.248
119 DL+IL+WL (-X) 11.678 163.013 4.1 4.871 -0.26 -12.605
120 DL+IL+WL (-Z) 9.398 160.08 5.227 6.35 -0.239 -8.488
121 DL+IL+WL (-Z) 8.587 159.737 0.897 0.638 -0.256 -6.975
122 DL+IL+EQ (+X) 5.105 154.624 0.907 0.653 -0.25 -0.868
123 DL+IL+EQ (+Z) 11.723 167.54 -4.62 -6.734 -0.234 -12.656
124 DL+IL+EQ (-X) 5.105 154.624 0.907 0.653 -0.25 -0.868
125 DL+IL+EQ (-Z) 11.842 169.414 -4.622 -6.736 -0.242 -12.838
126 DL+WL (+X) 4.301 132.893 3.276 3.837 -0.176 -0.224
127 DL+WL (+X) 10.079 139.535 4.869 5.924 -0.211 -10.695
128 DL+WL (+Z) 7.704 135.625 6.233 7.733 -0.231 -6.395
129 DL+WL (+Z) 5.331 135.859 0.833 0.609 -0.126 -2.088
130 DL+WL (-X) 4.306 132.897 3.299 3.856 -0.175 -0.233
131 DL+WL (-X) 10.069 139.528 4.829 5.889 -0.212 -10.678
CLIENT M/S. REFEX ENERGY LIMITED

DOCUMENT NO DATE
PROJECT SOLAR PV POWER PLANT OF 50MW AC
1617101-RFX-NLC-SWYD-F&C-018 06.03.18
DESIGNED CHECKED REV
TITLE FOUNDATION & COLUMN DESIGN FOR CRB
GS KN 0

132 DL+WL (-Z) 7.219 135.862 6.238 7.739 -0.185 -5.532


133 DL+WL (-Z) 6.204 135.433 0.825 0.599 -0.208 -3.641
134 DL+EQ (+X) 1.852 129.043 0.838 0.616 -0.199 3.992
135 DL+EQ (+Z) 10.124 145.187 -6.071 -8.617 -0.179 -10.742
136 DL+EQ (-X) 18.358 153.141 0.721 0.461 -0.173 -25.429
137 DL+EQ (-Z) 10.086 136.997 7.63 9.694 -0.193 -10.695
4 101 DL+IL 3.262 129.461 -2.749 -2.382 -0.284 -2.917
102 DL+WL (+X) -1.022 112.987 -0.153 1.883 -0.271 4.005
103 DL+WL (+X) 3.305 117.133 1.163 4.321 -0.346 -2.961
104 DL+WL (+Z) 1.266 112.587 2.693 6.74 -0.388 0.26
105 DL+WL (+Z) 0.224 117.687 -2.679 -2.271 -0.172 2.111
106 DL+WL (-X) -1.025 112.982 -0.321 1.764 -0.279 4.01
107 DL+WL (-X) 3.311 117.141 1.466 4.536 -0.332 -2.97
108 DL+WL (-Z) 1.438 112.634 2.702 6.751 -0.336 0.101
109 DL+WL (+Z) -0.086 117.602 -2.694 -2.291 -0.267 2.398
110 DL+EQ (+X) -2.724 110.753 -2.68 -2.268 -0.267 6.937
111 DL+EQ (+Z) 3.359 134.166 -9.529 -13.965 -0.161 -3.044
112 DL+EQ (-X) 9.368 133.87 -2.798 -2.464 -0.207 -12.898
113 DL+EQ (-Z) 3.285 110.456 4.051 9.233 -0.314 -2.917
114 DL+IL+WL (+X) -0.213 122.001 -0.68 1.018 -0.311 2.671
115 DL+IL+WL (+X) 3.26 123.888 0.375 2.971 -0.362 -2.915
116 DL+IL+WL (+Z) 1.629 120.251 1.599 4.906 -0.396 -0.337
117 DL+IL+WL (+Z) 0.795 124.331 -2.699 -2.303 -0.223 1.143
118 DL+IL+WL (-X) -0.204 120.567 -0.812 0.926 -0.308 2.663
119 DL+IL+WL (-X) 3.265 123.894 0.617 3.143 -0.35 -2.922
120 DL+IL+WL (-Z) 1.766 120.289 1.606 4.915 -0.354 -0.465
121 DL+IL+WL (-Z) 0.548 124.263 -2.711 -2.319 -0.299 1.373
122 DL+IL+EQ (+X) -1.563 118.784 -2.699 -2.3 -0.299 5.004
123 DL+IL+EQ (+Z) 3.303 137.515 -8.179 -11.658 -0.214 -2.981
124 DL+IL+EQ (-X) -1.563 118.784 -2.699 -2.3 -0.299 5.004
125 DL+IL+EQ (-Z) 3.291 138.945 -8.181 -11.661 -0.223 -2.968
126 DL+WL (+X) -1.354 100.756 0.121 2.12 -0.247 4.303
127 DL+WL (+X) 2.973 104.902 1.437 4.558 -0.322 -2.663
128 DL+WL (+Z) 0.933 100.356 2.967 6.976 -0.365 0.558
129 DL+WL (+Z) -0.109 105.456 -2.405 -2.035 -0.149 2.409
130 DL+WL (-X) -1.357 100.751 -0.047 2.001 -0.255 4.308
131 DL+WL (-X) 2.979 104.91 1.739 4.772 -0.308 -2.672
132 DL+WL (-Z) 1.105 100.403 2.976 6.987 -0.312 0.399
133 DL+WL (-Z) -0.418 105.371 -2.42 -2.055 -0.243 2.696
134 DL+EQ (+X) -3.056 98.522 -2.406 -2.031 -0.243 7.236
135 DL+EQ (+Z) 3.026 121.935 -9.255 -13.728 -0.137 -2.746
136 DL+EQ (-X) 9.035 121.638 -2.525 -2.228 -0.184 -12.6
137 DL+EQ (-Z) 2.953 98.225 4.325 9.47 -0.29 -2.619
5 101 DL+IL 2.688 266.636 3.669 2.901 0.286 -2.462
102 DL+WL (+X) -3.675 253.3 6.226 7.671 0.315 6.361
103 DL+WL (+X) 2.719 252.722 9.055 11.669 0.277 -2.5
104 DL+WL (+Z) -0.18 255.071 9.944 13.948 0.333 1.519
105 DL+WL (+Z) -2.036 250.279 3.831 3 0.242 4.089
106 DL+WL (-X) -3.677 253.435 6.93 8.167 0.318 6.365
107 DL+WL (-X) 2.724 252.48 7.789 10.775 0.272 -2.506
108 DL+WL (-Z) -0.132 255.069 9.936 13.94 0.286 1.453
109 DL+WL (+Z) -2.121 250.281 3.847 3.015 0.326 4.208
110 DL+EQ (+X) -5.834 252.976 3.844 3.013 0.3 9.651
111 DL+EQ (+Z) 2.667 239.142 -2.229 -8.269 0.204 -2.425
CLIENT M/S. REFEX ENERGY LIMITED

DOCUMENT NO DATE
PROJECT SOLAR PV POWER PLANT OF 50MW AC
1617101-RFX-NLC-SWYD-F&C-018 06.03.18
DESIGNED CHECKED REV
TITLE FOUNDATION & COLUMN DESIGN FOR CRB
GS KN 0

112 DL+EQ (-X) 11.271 243.952 3.857 3.039 0.188 -14.652


113 DL+EQ (-Z) 2.769 257.785 9.931 14.321 0.283 -2.576
114 DL+IL+WL (+X) -2.426 270.505 5.57 6.617 0.343 4.627
115 DL+IL+WL (+X) 2.695 266.408 7.869 9.84 0.304 -2.469
116 DL+IL+WL (+Z) 0.376 268.287 8.58 11.664 0.349 0.746
117 DL+IL+WL (+Z) -1.109 264.454 3.69 2.905 0.276 2.802
118 DL+IL+WL (-X) -2.422 266.979 6.169 7.039 0.337 4.623
119 DL+IL+WL (-X) 2.698 266.214 6.857 9.126 0.3 -2.474
120 DL+IL+WL (-Z) 0.414 268.286 8.574 11.657 0.311 0.693
121 DL+IL+WL (-Z) -1.178 264.456 3.703 2.917 0.344 2.897
122 DL+IL+EQ (+X) -4.148 266.611 3.7 2.916 0.322 7.251
123 DL+IL+EQ (+Z) 2.653 255.544 -1.158 -6.11 0.246 -2.41
124 DL+IL+EQ (-X) -4.148 266.611 3.7 2.916 0.322 7.251
125 DL+IL+EQ (-Z) 2.647 259.179 -1.195 -6.135 0.254 -2.402
126 DL+WL (+X) -3.947 228.454 5.841 7.368 0.29 6.612
127 DL+WL (+X) 2.447 227.876 8.67 11.366 0.253 -2.25
128 DL+WL (+Z) -0.452 230.224 9.559 13.646 0.309 1.769
129 DL+WL (+Z) -2.308 225.433 3.446 2.697 0.217 4.339
130 DL+WL (-X) -3.949 228.589 6.545 7.865 0.293 6.615
131 DL+WL (-X) 2.452 227.633 7.404 10.473 0.248 -2.256
132 DL+WL (-Z) -0.404 230.223 9.551 13.637 0.261 1.703
133 DL+WL (-Z) -2.393 225.435 3.462 2.713 0.302 4.458
134 DL+EQ (+X) -6.106 228.129 3.459 2.71 0.275 9.901
135 DL+EQ (+Z) 2.396 214.296 -2.615 -8.572 0.18 -2.175
136 DL+EQ (-X) 10.999 219.106 3.472 2.737 0.163 -14.402
137 DL+EQ (-Z) 2.498 232.939 9.546 14.019 0.259 -2.325
6 101 DL+IL -3.227 274.115 -1.711 -1.413 0.156 -1.003
102 DL+WL (+X) -10.63 257.259 1.398 2.675 0.135 11.315
103 DL+WL (+X) -3.681 251.3 3.375 5.323 0.088 -0.202
104 DL+WL (+Z) -6.256 255.302 5.233 7.712 0.1 4.284
105 DL+WL (+Z) -9.882 253.879 -1.831 -1.525 0.129 9.686
106 DL+WL (-X) -10.622 257.124 1.291 2.579 0.135 11.304
107 DL+WL (-X) -3.695 251.544 3.568 5.496 0.087 -0.181
108 DL+WL (-Z) -7.333 254.748 5.229 7.707 0.073 5.643
109 DL+WL (+Z) -7.944 254.876 -1.825 -1.516 0.178 7.24
110 DL+EQ (+X) -11.707 259.209 -1.824 -1.517 0.181 14.442
111 DL+EQ (+Z) -3.719 246.343 -8.745 -10.876 0.154 -0.138
112 DL+EQ (-X) 4.271 239.714 -1.816 -1.502 0.081 -14.744
113 DL+EQ (-Z) -3.718 252.58 5.105 7.857 0.108 -0.164
114 DL+IL+WL (+X) -8.757 280.354 0.864 1.935 0.158 8.17
115 DL+IL+WL (+X) -3.295 270.656 2.423 4.033 0.117 -0.873
116 DL+IL+WL (+Z) -5.356 273.857 3.91 5.945 0.126 2.715
117 DL+IL+WL (+Z) -8.256 272.718 -1.741 -1.445 0.149 7.037
118 DL+IL+WL (-X) -8.848 275.315 0.756 1.838 0.154 8.331
119 DL+IL+WL (-X) -3.307 270.85 2.578 4.172 0.115 -0.857
120 DL+IL+WL (-Z) -6.217 273.414 3.907 5.941 0.104 3.802
121 DL+IL+WL (-Z) -6.706 273.516 -1.736 -1.438 0.188 5.08
122 DL+IL+EQ (+X) -9.716 276.983 -1.736 -1.438 0.191 10.842
123 DL+IL+EQ (+Z) -3.326 266.69 -7.272 -8.926 0.169 -0.822
124 DL+IL+EQ (-X) -9.716 276.983 -1.736 -1.438 0.191 10.842
125 DL+IL+EQ (-Z) -3.227 271.621 -7.25 -8.906 0.174 -0.993
126 DL+WL (+X) -10.258 232.313 1.58 2.826 0.121 11.33
127 DL+WL (+X) -3.309 226.354 3.557 5.473 0.075 -0.187
128 DL+WL (+Z) -5.884 230.356 5.415 7.863 0.087 4.299
CLIENT M/S. REFEX ENERGY LIMITED

DOCUMENT NO DATE
PROJECT SOLAR PV POWER PLANT OF 50MW AC
1617101-RFX-NLC-SWYD-F&C-018 06.03.18
DESIGNED CHECKED REV
TITLE FOUNDATION & COLUMN DESIGN FOR CRB
GS KN 0

129 DL+WL (+Z) -9.51 228.933 -1.649 -1.374 0.116 9.701


130 DL+WL (-X) -10.25 232.178 1.473 2.73 0.122 11.319
131 DL+WL (-X) -3.323 226.598 3.75 5.647 0.074 -0.166
132 DL+WL (-Z) -6.961 229.802 5.411 7.858 0.06 5.658
133 DL+WL (-Z) -7.572 229.93 -1.643 -1.365 0.165 7.255
134 DL+EQ (+X) -11.335 234.263 -1.642 -1.366 0.168 14.457
135 DL+EQ (+Z) -3.347 221.397 -8.563 -10.725 0.141 -0.123
136 DL+EQ (-X) 4.642 214.768 -1.634 -1.351 0.068 -14.729
137 DL+EQ (-Z) -3.346 227.634 5.287 8.008 0.095 -0.149
7 101 DL+IL -3.338 250.748 1.118 0.869 -0.236 -0.751
102 DL+WL (+X) -10.575 234.789 4.331 5.033 -0.198 11.293
103 DL+WL (+X) -3.804 227.831 6.645 7.976 -0.241 0.058
104 DL+WL (+Z) -6.364 230.801 8.341 10.22 -0.264 4.501
105 DL+WL (+Z) -9.766 233.187 1.154 0.884 -0.142 9.597
106 DL+WL (-X) -10.567 234.645 4.434 5.123 -0.199 11.281
107 DL+WL (-X) -3.818 228.09 6.461 7.815 -0.239 0.078
108 DL+WL (-Z) -7.356 230.28 8.336 10.213 -0.222 5.754
109 DL+WL (+Z) -7.979 234.125 1.164 0.896 -0.217 7.342
110 DL+EQ (+X) -11.759 238.446 1.159 0.891 -0.209 14.535
111 DL+EQ (+Z) -3.806 229.659 -5.901 -8.581 -0.176 0.045
112 DL+EQ (-X) 4.162 219.269 1.187 0.921 -0.188 -14.435
113 DL+EQ (-Z) -3.792 228.056 8.248 10.393 -0.221 0.054
114 DL+IL+WL (+X) -8.759 255.493 3.645 4.171 -0.236 8.243
115 DL+IL+WL (+X) -3.435 245.549 5.507 6.533 -0.262 -0.584
116 DL+IL+WL (+Z) -5.482 247.925 6.864 8.328 -0.281 2.97
117 DL+IL+WL (+Z) -8.204 249.833 1.114 0.859 -0.183 7.047
118 DL+IL+WL (-X) -8.845 251 3.738 4.25 -0.229 8.395
119 DL+IL+WL (-X) -3.446 245.756 5.359 6.404 -0.261 -0.568
120 DL+IL+WL (-Z) -6.277 247.508 6.859 8.322 -0.247 3.972
121 DL+IL+WL (-Z) -6.775 250.584 1.122 0.868 -0.243 5.243
122 DL+IL+EQ (+X) -9.799 254.041 1.118 0.864 -0.237 10.997
123 DL+IL+EQ (+Z) -3.436 247.011 -4.53 -6.713 -0.21 -0.595
124 DL+IL+EQ (-X) -9.799 254.041 1.118 0.864 -0.237 10.997
125 DL+IL+EQ (-Z) -3.344 251.389 -4.541 -6.721 -0.218 -0.755
126 DL+WL (+X) -10.195 211.903 4.214 4.943 -0.179 11.288
127 DL+WL (+X) -3.424 204.946 6.528 7.886 -0.221 0.053
128 DL+WL (+Z) -5.984 207.916 8.224 10.129 -0.244 4.496
129 DL+WL (+Z) -9.386 210.301 1.037 0.793 -0.123 9.592
130 DL+WL (-X) -10.187 211.759 4.316 5.033 -0.179 11.276
131 DL+WL (-X) -3.439 205.204 6.343 7.724 -0.22 0.073
132 DL+WL (-Z) -6.977 207.395 8.218 10.123 -0.202 5.749
133 DL+WL (-Z) -7.599 211.239 1.047 0.805 -0.198 7.337
134 DL+EQ (+X) -11.379 215.56 1.042 0.8 -0.189 14.53
135 DL+EQ (+Z) -3.426 206.773 -6.019 -8.672 -0.156 0.04
136 DL+EQ (-X) 4.541 196.383 1.07 0.831 -0.168 -14.44
137 DL+EQ (-Z) -3.412 205.17 8.13 10.303 -0.201 0.049
8 101 DL+IL 2.443 251.755 -2.704 -2.23 -0.334 -2.239
102 DL+WL (+X) -3.44 234.753 0.337 2.877 -0.304 5.966
103 DL+WL (+X) 2.529 230.212 1.312 5.557 -0.266 -2.32
104 DL+WL (+Z) -0.198 229.567 3.525 8.788 -0.297 1.458
105 DL+WL (+Z) -1.875 237.244 -2.887 -2.396 -0.264 3.807
106 DL+WL (-X) -3.444 234.897 -0.351 2.382 -0.308 5.971
107 DL+WL (-X) 2.536 229.952 2.549 6.448 -0.259 -2.33
108 DL+WL (-Z) -0.121 229.53 3.52 8.779 -0.244 1.366
CLIENT M/S. REFEX ENERGY LIMITED

DOCUMENT NO DATE
PROJECT SOLAR PV POWER PLANT OF 50MW AC
1617101-RFX-NLC-SWYD-F&C-018 06.03.18
DESIGNED CHECKED REV
TITLE FOUNDATION & COLUMN DESIGN FOR CRB
GS KN 0

109 DL+WL (+Z) -2.014 237.311 -2.877 -2.379 -0.358 3.973


110 DL+EQ (+X) -5.618 240.145 -2.883 -2.387 -0.324 9.286
111 DL+EQ (+Z) 2.585 246.905 -9.277 -13.927 -0.315 -2.403
112 DL+EQ (-X) 10.696 230.413 -2.854 -2.352 -0.246 -13.951
113 DL+EQ (-Z) 2.493 223.654 3.541 9.188 -0.255 -2.262
114 DL+IL+WL (+X) -2.34 251.334 -0.14 1.967 -0.349 4.4
115 DL+IL+WL (+X) 2.454 244.406 0.607 4.084 -0.309 -2.248
116 DL+IL+WL (+Z) 0.272 243.89 2.378 6.668 -0.334 0.775
117 DL+IL+WL (+Z) -1.069 250.032 -2.752 -2.279 -0.307 2.654
118 DL+IL+WL (-X) -2.324 248.154 -0.723 1.543 -0.343 4.386
119 DL+IL+WL (-X) 2.46 244.198 1.597 4.796 -0.303 -2.255
120 DL+IL+WL (-Z) 0.334 243.86 2.373 6.661 -0.292 0.701
121 DL+IL+WL (-Z) -1.18 250.085 -2.744 -2.266 -0.383 2.787
122 DL+IL+EQ (+X) -4.063 252.353 -2.749 -2.272 -0.356 7.037
123 DL+IL+EQ (+Z) 2.499 257.76 -7.864 -11.504 -0.348 -2.314
124 DL+IL+EQ (-X) -4.063 252.353 -2.749 -2.272 -0.356 7.037
125 DL+IL+EQ (-Z) 2.48 261.056 -7.832 -11.476 -0.358 -2.295
126 DL+WL (+X) -3.694 211.225 0.624 3.114 -0.276 6.199
127 DL+WL (+X) 2.275 206.684 1.598 5.794 -0.238 -2.087
128 DL+WL (+Z) -0.452 206.039 3.812 9.025 -0.269 1.691
129 DL+WL (+Z) -2.128 213.716 -2.6 -2.159 -0.235 4.04
130 DL+WL (-X) -3.698 211.369 -0.064 2.619 -0.28 6.205
131 DL+WL (-X) 2.282 206.424 2.836 6.685 -0.23 -2.097
132 DL+WL (-Z) -0.375 206.002 3.807 9.016 -0.216 1.599
133 DL+WL (-Z) -2.268 213.783 -2.59 -2.142 -0.33 4.206
134 DL+EQ (+X) -5.872 216.618 -2.596 -2.15 -0.296 9.519
135 DL+EQ (+Z) 2.331 223.377 -8.991 -13.69 -0.286 -2.17
136 DL+EQ (-X) 10.442 206.886 -2.567 -2.115 -0.217 -13.718
137 DL+EQ (-Z) 2.239 200.126 3.828 9.425 -0.227 -2.029
9 101 DL+IL -7.355 180.925 3.671 2.555 -1.628 5.523
102 DL+WL (+X) -12.839 175.694 6.549 8.951 -1.58 15.49
103 DL+WL (+X) -7.363 173.375 8.864 13.57 -1.092 5.51
104 DL+WL (+Z) -9.75 176.191 10.343 17.088 -1.258 9.971
105 DL+WL (+Z) -11.607 172.69 3.652 2.461 -1.478 13.047
106 DL+WL (-X) -12.842 175.713 6.726 9.018 -1.593 15.494
107 DL+WL (-X) -7.358 173.341 8.544 13.449 -1.069 5.503
108 DL+WL (-Z) -9.898 176.174 10.342 17.087 -1.026 10.027
109 DL+WL (+Z) -11.34 172.721 3.654 2.463 -1.896 12.947
110 DL+EQ (+X) -14.615 176.961 3.633 2.421 -1.482 19.229
111 DL+EQ (+Z) -7.399 160.23 -6.168 -20.616 -1.72 5.585
112 DL+EQ (-X) -0.115 162.864 3.771 2.73 -1.328 -8.213
113 DL+EQ (-Z) -7.331 179.595 13.572 25.768 -1.09 5.431
114 DL+IL+WL (+X) -11.734 185.55 5.948 7.655 -1.768 13.508
115 DL+IL+WL (+X) -7.355 181.492 7.807 11.355 -1.333 5.522
116 DL+IL+WL (+Z) -9.265 183.746 8.99 14.169 -1.466 9.09
117 DL+IL+WL (+Z) -10.751 180.944 3.637 2.468 -1.642 11.551
118 DL+IL+WL (-X) -11.738 183.363 6.097 7.713 -1.734 13.509
119 DL+IL+WL (-X) -7.352 181.465 7.551 11.258 -1.315 5.516
120 DL+IL+WL (-Z) -9.384 183.732 8.989 14.168 -1.28 9.135
121 DL+IL+WL (-Z) -10.537 180.969 3.639 2.469 -1.976 11.471
122 DL+IL+EQ (+X) -13.157 184.362 3.622 2.436 -1.645 16.497
123 DL+IL+EQ (+Z) -7.384 170.976 -4.219 -15.994 -1.835 5.582
124 DL+IL+EQ (-X) -13.157 184.362 3.622 2.436 -1.645 16.497
125 DL+IL+EQ (-Z) -7.382 173.179 -4.225 -15.998 -1.88 5.585
CLIENT M/S. REFEX ENERGY LIMITED

DOCUMENT NO DATE
PROJECT SOLAR PV POWER PLANT OF 50MW AC
1617101-RFX-NLC-SWYD-F&C-018 06.03.18
DESIGNED CHECKED REV
TITLE FOUNDATION & COLUMN DESIGN FOR CRB
GS KN 0

126 DL+WL (+X) -12.103 158.703 6.178 8.693 -1.439 14.939


127 DL+WL (+X) -6.626 156.384 8.494 13.312 -0.952 4.959
128 DL+WL (+Z) -9.014 159.2 9.973 16.831 -1.117 9.42
129 DL+WL (+Z) -10.871 155.698 3.282 2.203 -1.338 12.497
130 DL+WL (-X) -12.105 158.722 6.356 8.76 -1.452 14.943
131 DL+WL (-X) -6.622 156.35 8.174 13.191 -0.928 4.952
132 DL+WL (-Z) -9.162 159.183 9.972 16.83 -0.885 9.476
133 DL+WL (-Z) -10.604 155.73 3.284 2.205 -1.755 12.396
134 DL+EQ (+X) -13.878 159.97 3.263 2.164 -1.341 18.678
135 DL+EQ (+Z) -6.662 143.239 -6.538 -20.874 -1.579 5.035
136 DL+EQ (-X) 0.622 145.872 3.401 2.472 -1.188 -8.763
137 DL+EQ (-Z) -6.594 162.604 13.202 25.51 -0.95 4.88
10 101 DL+IL -7.768 168.458 -1.45 -1.234 -0.784 14.419
102 DL+WL (+X) -11.908 156.139 -0.074 0.596 -0.823 24.397
103 DL+WL (+X) -6.583 155.945 0.876 1.865 -0.717 12.17
104 DL+WL (+Z) -9.69 156.684 1.651 2.894 -0.841 18.885
105 DL+WL (+Z) -9.272 155.274 -1.473 -1.265 -0.67 19.123
106 DL+WL (-X) -11.913 156.117 -0.087 0.581 -0.821 24.404
107 DL+WL (-X) -6.574 155.985 0.901 1.891 -0.721 12.159
108 DL+WL (-Z) -8.156 156.988 1.652 2.894 -0.735 16.3
109 DL+WL (+Z) -12.032 154.727 -1.474 -1.266 -0.861 23.774
110 DL+EQ (+X) -10.512 156.826 -1.482 -1.277 -0.649 24.165
111 DL+EQ (+Z) -6.8 149.62 -6.45 -7.973 -0.619 12.499
112 DL+EQ (-X) -2.858 151.999 -1.412 -1.185 -0.701 0.469
113 DL+EQ (-Z) -6.569 159.204 3.556 5.511 -0.732 12.135
114 DL+IL+WL (+X) -11.946 169.839 -0.351 0.228 -0.902 24.083
115 DL+IL+WL (+X) -7.47 166.875 0.409 1.244 -0.796 13.881
116 DL+IL+WL (+Z) -9.955 167.466 1.03 2.067 -0.895 19.253
117 DL+IL+WL (+Z) -9.621 166.338 -1.47 -1.26 -0.758 19.443
118 DL+IL+WL (-X) -11.734 167.013 -0.361 0.217 -0.879 23.668
119 DL+IL+WL (-X) -7.462 166.907 0.429 1.264 -0.799 13.872
120 DL+IL+WL (-Z) -8.729 167.709 1.03 2.067 -0.81 17.185
121 DL+IL+WL (-Z) -11.829 165.9 -1.47 -1.261 -0.911 23.164
122 DL+IL+EQ (+X) -10.613 167.579 -1.477 -1.27 -0.741 23.477
123 DL+IL+EQ (+Z) -7.644 161.815 -5.451 -6.627 -0.717 14.144
124 DL+IL+EQ (-X) -10.613 167.579 -1.477 -1.27 -0.741 23.477
125 DL+IL+EQ (-Z) -7.86 164.624 -5.452 -6.628 -0.739 14.565
126 DL+WL (+X) -11.239 140.698 0.071 0.719 -0.755 23.166
127 DL+WL (+X) -5.914 140.504 1.021 1.988 -0.65 10.939
128 DL+WL (+Z) -9.021 141.243 1.796 3.017 -0.774 17.653
129 DL+WL (+Z) -8.604 139.833 -1.328 -1.142 -0.602 17.891
130 DL+WL (-X) -11.244 140.676 0.057 0.704 -0.753 23.172
131 DL+WL (-X) -5.905 140.544 1.045 2.014 -0.654 10.927
132 DL+WL (-Z) -7.488 141.547 1.797 3.018 -0.667 15.069
133 DL+WL (-Z) -11.363 139.286 -1.329 -1.143 -0.794 22.543
134 DL+EQ (+X) -9.844 141.384 -1.337 -1.154 -0.582 22.933
135 DL+EQ (+Z) -6.132 134.179 -6.305 -7.85 -0.551 11.268
136 DL+EQ (-X) -2.189 136.558 -1.267 -1.062 -0.634 -0.763
137 DL+EQ (-Z) -5.901 143.763 3.701 5.634 -0.664 10.903
11 101 DL+IL -7.292 153.026 0.75 0.534 1.028 13.576
102 DL+WL (+X) -11.394 140.948 2.151 2.381 1.119 23.405
103 DL+WL (+X) -6.405 139.841 3.156 3.703 0.844 11.776
104 DL+WL (+Z) -9.417 139.898 3.927 4.723 1.023 18.294
105 DL+WL (+Z) -8.793 141.339 0.732 0.508 0.942 18.225
CLIENT M/S. REFEX ENERGY LIMITED

DOCUMENT NO DATE
PROJECT SOLAR PV POWER PLANT OF 50MW AC
1617101-RFX-NLC-SWYD-F&C-018 06.03.18
DESIGNED CHECKED REV
TITLE FOUNDATION & COLUMN DESIGN FOR CRB
GS KN 0

106 DL+WL (-X) -11.398 140.928 2.163 2.393 1.117 23.41


107 DL+WL (-X) -6.398 139.877 3.134 3.681 0.846 11.767
108 DL+WL (-Z) -8.004 140.182 3.927 4.724 0.873 15.899
109 DL+WL (+Z) -11.337 140.828 0.732 0.507 1.213 22.534
110 DL+EQ (+X) -10.063 142.875 0.726 0.498 0.929 23.282
111 DL+EQ (+Z) -6.156 142.536 -4.371 -6.303 0.936 11.396
112 DL+EQ (-X) -2.504 138.028 0.787 0.582 0.839 -0.081
113 DL+EQ (-Z) -6.411 138.367 5.884 7.384 0.833 11.805
114 DL+IL+WL (+X) -11.381 153.423 1.866 2.006 1.215 23.02
115 DL+IL+WL (+X) -7.188 150.022 2.671 3.065 0.966 13.322
116 DL+IL+WL (+Z) -9.598 150.068 3.287 3.881 1.11 18.536
117 DL+IL+WL (+Z) -9.099 151.221 0.732 0.509 1.045 18.48
118 DL+IL+WL (-X) -11.183 150.892 1.877 2.017 1.185 22.629
119 DL+IL+WL (-X) -7.183 150.052 2.653 3.048 0.969 13.314
120 DL+IL+WL (-Z) -8.467 150.296 3.288 3.882 0.99 16.62
121 DL+IL+WL (-Z) -11.133 150.812 0.732 0.508 1.262 21.928
122 DL+IL+EQ (+X) -10.114 152.45 0.727 0.501 1.035 22.527
123 DL+IL+EQ (+Z) -6.988 152.179 -3.351 -4.94 1.04 13.018
124 DL+IL+EQ (-X) -10.114 152.45 0.727 0.501 1.035 22.527
125 DL+IL+EQ (-Z) -7.19 154.694 -3.352 -4.941 1.069 13.413
126 DL+WL (+X) -10.766 126.903 2.075 2.327 1.031 22.245
127 DL+WL (+X) -5.777 125.795 3.08 3.649 0.755 10.616
128 DL+WL (+Z) -8.789 125.853 3.851 4.669 0.934 17.134
129 DL+WL (+Z) -8.165 127.294 0.656 0.453 0.854 17.064
130 DL+WL (-X) -10.77 126.883 2.088 2.339 1.029 22.25
131 DL+WL (-X) -5.77 125.832 3.058 3.627 0.758 10.607
132 DL+WL (-Z) -7.375 126.137 3.851 4.67 0.784 14.739
133 DL+WL (-Z) -10.709 126.783 0.656 0.453 1.124 21.374
134 DL+EQ (+X) -9.435 128.83 0.65 0.444 0.841 22.122
135 DL+EQ (+Z) -5.527 128.491 -4.447 -6.357 0.847 10.236
136 DL+EQ (-X) -1.876 123.983 0.711 0.528 0.751 -1.241
137 DL+EQ (-Z) -5.783 124.322 5.808 7.329 0.744 10.645
12 101 DL+IL -6.872 169.036 -3.025 -2.815 1.852 5.199
102 DL+WL (+X) -12.019 160.104 0.047 3.68 2.21 14.537
103 DL+WL (+X) -7.003 154.822 1.922 8.144 1.898 5.277
104 DL+WL (+Z) -9.175 154.934 3.771 11.83 2.314 9.41
105 DL+WL (+Z) -10.921 161.864 -3.114 -2.948 1.698 12.286
106 DL+WL (-X) -12.024 160.128 -0.136 3.597 2.218 14.544
107 DL+WL (-X) -6.996 154.779 2.251 8.294 1.884 5.265
108 DL+WL (-Z) -9.359 154.925 3.773 11.834 2.061 9.49
109 DL+WL (+Z) -10.59 161.881 -3.119 -2.955 2.155 12.141
110 DL+EQ (+X) -13.9 165.908 -3.125 -2.979 1.702 18.38
111 DL+EQ (+Z) -6.946 171.604 -13.245 -26.278 1.311 5.177
112 DL+EQ (-X) -0.07 152.508 -3.002 -2.683 1.489 -7.866
113 DL+EQ (-Z) -7.023 146.812 7.118 20.616 1.88 5.337
114 DL+IL+WL (+X) -10.9 169.752 -0.536 2.394 2.343 12.623
115 DL+IL+WL (+X) -6.909 163.562 0.956 5.962 2.042 5.227
116 DL+IL+WL (+Z) -8.647 163.651 2.435 8.911 2.375 8.533
117 DL+IL+WL (+Z) -10.044 169.195 -3.073 -2.911 1.883 10.834
118 DL+IL+WL (-X) -10.926 167.806 -0.69 2.324 2.298 12.64
119 DL+IL+WL (-X) -6.903 163.527 1.219 6.082 2.031 5.217
120 DL+IL+WL (-Z) -8.794 163.644 2.437 8.914 2.173 8.597
121 DL+IL+WL (-Z) -9.779 169.208 -3.076 -2.917 2.248 10.718
122 DL+IL+EQ (+X) -12.427 172.43 -3.081 -2.937 1.886 15.71
CLIENT M/S. REFEX ENERGY LIMITED

DOCUMENT NO DATE
PROJECT SOLAR PV POWER PLANT OF 50MW AC
1617101-RFX-NLC-SWYD-F&C-018 06.03.18
DESIGNED CHECKED REV
TITLE FOUNDATION & COLUMN DESIGN FOR CRB
GS KN 0

123 DL+IL+EQ (+Z) -6.864 176.987 -11.178 -21.575 1.573 5.147


124 DL+IL+EQ (-X) -12.427 172.43 -3.081 -2.937 1.886 15.71
125 DL+IL+EQ (-Z) -6.841 178.952 -11.17 -21.572 1.624 5.136
126 DL+WL (+X) -11.321 144.183 0.354 3.963 2.05 14.011
127 DL+WL (+X) -6.305 138.901 2.228 8.427 1.738 4.751
128 DL+WL (+Z) -8.477 139.013 4.077 12.113 2.154 8.884
129 DL+WL (+Z) -10.223 145.943 -2.808 -2.665 1.539 11.76
130 DL+WL (-X) -11.325 144.207 0.171 3.88 2.058 14.018
131 DL+WL (-X) -6.297 138.858 2.557 8.577 1.724 4.739
132 DL+WL (-Z) -8.661 139.004 4.08 12.117 1.901 8.964
133 DL+WL (-Z) -9.892 145.96 -2.812 -2.672 1.995 11.615
134 DL+EQ (+X) -13.201 149.987 -2.819 -2.696 1.543 17.855
135 DL+EQ (+Z) -6.248 155.683 -12.939 -25.995 1.152 4.652
136 DL+EQ (-X) 0.629 136.587 -2.696 -2.4 1.33 -8.392
137 DL+EQ (-Z) -6.325 130.891 7.424 20.899 1.721 4.811
CLIENT M/S. REFEX ENERGY LIMITED

DOCUMENT NO DATE
PROJECT SOLAR PV POWER PLANT OF 50MW AC
1617101-RFX-NLC-SWYD-F&C-018 06.03.18
DESIGNED CHECKED REV
TITLE FOUNDATION & COLUMN DESIGN FOR CRB
GS KN 0
3.1 DESIGN OF FOOTING -F1 (Load case 113) & (Node No 1)

DESIGN DATA:-
Depth of foundation from FGL = 2.00 m
Footing size = 1.50 m x 1.50 m
X-dir Z-dir
Thickness of footing at edge = 300 mm
Thickness of footing at face of column = 300 mm
Projection around column = ###
mm
Column size = 230 mm x 300 mm
X-dir Z-dir
MATERIAL PROPERTIES:-
Compressive Strength of Concrete = 25 N/mm2
Grade of steel = Fe 500
Density of concrete = 2.5 T/m3
Density of soil = 1.733 T/m3
Co efficient of friction = 0.50

FACTOR OF SAFETY:-
For strength design = 2.00
FX = 0.353 Ton.
FZ = 1.0 Ton
P = 14.1 Ton
Mx = 1.4 Ton.m
Mz = 0.3 Ton.m
FINAL VALUE FOR DESIGN
Vertical load P = 14.1 Ton
Bending Moment Z-direction Mx = 1.4 Ton.m
Bending Moment X-direction Mz = 0.3 Ton.m

CALCULATIONS
Volume of footing = 0.8 m3
Volume of soil = 3.7 m3
a) Wt of footing = 2 Ton
b) Wt of soil = 6.41 Ton
Total vertical load = 14.0746 + 2 + 6.41
= 22.48 Ton
Net SBC at 2 m depth = 17.95 T/m2
Gross SBC at 2 m depth = = 17.95x1.25+2x1.733 = 25.9035 T/m2

Bearing pressure = 22.48 / (1.5 x 1.5) ± 6 x 1.385 / (1.5 x 1.5^2)


± 6 x 0.3202 / (1.5 x 1.5^2)
= 9.99 ± 2.46 ± 0.57

Bearing pressure at footing P1 = 13.02 Ton./sqm OK < 25.9035 Ton./sqm


four corners P2 = 11.88 Ton./sqm
CLIENT M/S. REFEX ENERGY LIMITED

DOCUMENT NO DATE
PROJECT SOLAR PV POWER PLANT OF 50MW AC
1617101-RFX-NLC-SWYD-F&C-018 06.03.18
DESIGNED CHECKED REV
TITLE FOUNDATION & COLUMN DESIGN FOR CRB
GS KN 0
3.1 DESIGN OF FOOTING -F1 (Load case 113) & (Node No 1)
P3 = 8.1 Ton./sqm
P4 = 6.96 Ton./sqm

Pressure due to over burden soil and raft


( 0.30 + 0.30 )/ 2 x 2.5 +
( 1.70 + 1.70 )/ 2 x 1.733
= 3.6961
Net pmax = 9.3239 T/m2
Net pmin = 2.556 T/m2
0.23

0.23 FGL FGL


1.50

2.00
0.635 0.635

0.30 z

1.50 1.50 x
PLAN SECTION

CHECK FOR FLEXURE ABOUT Z DIRECTION


Net pressure at edge = 9.3239 t/m2

Thickness of footing at column face = 300 mm

Effective depth of footing at z direction, d = 300 - 50 - 6 = 244 mm

Cantilever span of slab from column face = (1.5 - 0.3) / 2 = 0.6 m

Moment (max) at face of column = 9.3239 x 0.6 ^ 2 / 2 = 1.68 tm

Mu/bd2 = (1.68 x 2 x 9.81x10^6) / (1000 x 244 ^2) = 0.55 N/mm2

pt = 0.130 % Ast = 0.13 x1000 x 244 / 100 = 317 mm2


Minimum pt = 0.12 % Ast = 0.12 x 1000 x 300 / 100 = 360 mm2
(Ref .Cl.No.26.5.2.1 in IS 456-2000)
PROVIDE 12 TOR @ 150 c/c at bottom , (Ast) = 754 mm2
SAFE
CHECK FOR FLEXURE ABOUT X DIRECTION
Cantilever span of slab from column face = (1.5 - 0.23) / 2 = 0.635 m

Moment (max) at face of column = 9.3239 x 0.635 ^ 2 / 2 = 1.88 tm


Effective depth of footing at x direction, d = 300 - 50 - 12 - 12/2 = 232 mm
Mu/bd2 = (1.88 x 2x 9.81 x 10^6) / (1000 x 232 ^2) = 0.69 N/mm2
CLIENT M/S. REFEX ENERGY LIMITED

DOCUMENT NO DATE
PROJECT SOLAR PV POWER PLANT OF 50MW AC
1617101-RFX-NLC-SWYD-F&C-018 06.03.18
DESIGNED CHECKED REV
TITLE FOUNDATION & COLUMN DESIGN FOR CRB
GS KN 0
3.1 DESIGN OF FOOTING -F1 (Load case 113) & (Node No 1)

pt = 0.164 % Ast = 0.164 x1000 x 232 / 100 = 380 mm2


Minimum pt = 0.12 % Ast = 0.12 x 1000 x 300 / 100 = 360 mm2
PROVIDE 12 TOR @ 150 c/c at bottom , (Ast = 754 mm2

(Ref .Cl.No.26.5.2.1 in IS 456-2000) SAFE


Provide nominal reinforcement @ top
Minimum pt = 0.06 % = 0.06 x 1000 x 300 / 100 = 180 mm2
PROVIDE 12 TOR @ 150 c/c bothways a, (Ast = 754 mm2
SAFE
CHECK AGAINST ONE WAY SHEAR @ Z DIRECTION
Depth of footing = 300 mm
Effective depth = 300 - 50 - 6 = 244 mm
Shear force at critical section, V = 9.3239 x 1x (0.6 - 0.244) = 3.32 ton
Cantilever length = 0.6 m
Critical section for shear is at a
distance 'd' from the face of the
pedestal = 0.6 - 0.244
= 0.356 m
Effective depth at critical sction d' = 0.244 m
(Ref .Cl.No.40.1 in IS 456-2000)
Nominal shear stress at critical section, tv = = V / (b' x d')
(3.32 x 2 x 9.81 x 10^3) / (1000 x 244) = 0.27 N/mm2

Percentage of reinforcement at critical section = [753.98 / ( 1000 x 244 )] x 100


= 0.310
Corresponding shear stress tc = 0.402 > 0.27 N/mm2
(Ref .Table 19. in IS 456-2000) Hence Safe
CHECK FOR TWO WAY SHEAR AT 'D/2' FROM THE PEDESTAL FACE
Maximum axial load on pedestal = 138.1 KN
Effective depth at critical section = 0.24 m
Area resisted by shear stress = 496784 mm2
Actual punching shear = 0.417
Permissible stress in two way shear = 0.25 × √25 = 1.250 N/mm²
(Ref .Cl.31.6.3. in IS 456-2000) Hence safe in two way shear

Check against one way shear @ X direction


Depth of footing D = 300 mm
Effective depth ( d' ) = 300 - 50 -12-6 = 232 mm

Shear force at critical section, V = 9.3239 x 1x (0.635 - 0.232) = 3.76 ton


Cantilever length = 0.635 m
CLIENT M/S. REFEX ENERGY LIMITED

DOCUMENT NO DATE
PROJECT SOLAR PV POWER PLANT OF 50MW AC
1617101-RFX-NLC-SWYD-F&C-018 06.03.18
DESIGNED CHECKED REV
TITLE FOUNDATION & COLUMN DESIGN FOR CRB
GS KN 0
3.1 DESIGN OF FOOTING -F1 (Load case 113) & (Node No 1)

Critical section for shear is at a distance 'd' from the face of the column = 0.635 - 0.232
= 0.403 m

Effective depth at critical sction d' = 0.232 m


(Ref .Cl.No.40.1 in IS 456-2000)
Nominal shear stress at critical section, tv = V / (b' x d')
(3.76 x 2 x 9.81 x 10^3) / (1000 x 232) = 0.32 N/mm2

Percentage of reinforcement at critical section = = [753.98 / ( 1000 x 232 )] x 100


= 0.320

Corresponding shear stress tc = 0.409 > 0.32 N/mm2


Hence Safe

Design Summary:-
Length of footing = 1500 mm
Breath of footing = 1500 mm
Thickness of footing = 300 mm
Reinforcement
Bottom of Footing:-
In Z-direction = 12 mm diameter @ 150 C/C (Bottom )
In X-direction = 12 mm diameter @ 150 C/C (Bottom )
Top of footing
CLIENT M/S. REFEX ENERGY LIMITED

DOCUMENT NO DATE
PROJECT SOLAR PV POWER PLANT OF 50MW AC
1617101-RFX-NLC-SWYD-F&C-018 06.03.18
DESIGNED CHECKED REV
TITLE FOUNDATION & COLUMN DESIGN FOR CRB
GS KN 0
3.1 DESIGN OF FOOTING -F1 (Load case 113) & (Node No 1)
M/S. REFEX ENERGY LIMITED
DOCUMENT NO DATE
PROJECT SOLAR PV POWER PLANT OF 50MW AC
1617101-RFX-NLC-SWYD-F&C-018 06.03.18
DESIGNED CHECKED REV
TITLE FOUNDATION & COLUMN DESIGN FOR CRB
GS KN 0.00
5.5 DESIGN OF FOOTING -F2 (Load case 124) & (Node No 28)
For Dry Condition
DESIGN DATA:-
Depth of foundation from FGL = 2.00 m
Footing size = 1.80 m x 1.80 m
X-dir Z-dir
Thickness of footing at edge = 400 mm
Thickness of footing at face of column = 400 mm
Projection around column = ###
mm
Column size = 300 mm x 450 mm
X-dir Z-dir
MATERIAL PROPERTIES:-
Compressive Strength of Concrete = 25 N/mm2
Grade of steel = Fe 415
Density of concrete = 2.5 T/m3
Density of soil = 1.87 T/m3
Co efficient of friction = 0.33
FACTOR OF SAFETY:-
For strength design = 2.00
From Staad Output (Maximum load among the nodes (18,20,22,28,29,30,31,32 & 34)
Design will be done for worst case i.e for (Load case 124) & (Node No28)
FX = 3.12 Ton.
FZ = 0.1 Ton
P = 38.1 Ton
Mx = 0.021 Ton.m
Mz = 3.81 Ton.m
FINAL VALUE FOR DESIGN
Vertical load P = 38.1 Ton
Bending Moment Z-direction Mx = 0.0206 Ton.m
Bending Moment X-direction Mz = 3.8091 Ton.m
CALCULATIONS
Volume of footing = 1.52 m3
Volume of soil = 4.96 m3
a) Wt of footing = 3.8 Ton
b) Wt of soil = 9.28 Ton
Total vertical load = 38.1 + 3.8 + 9.28
= 51.18 Ton
Net SBC at 2 m depth = 15.00 T/m2
Gross SBC at 1.5 m depth = = 15x1.25+2x1.87 = 22.49 T/m2

Bearing pressure = 51.18 / (1.8 x 1.8) ± 6 x 0.0206 / (1.8 x 1.8^2)


± 6 x 3.8091 / (1.8 x 1.8^2)
= 15.8 ± 0.02 ± 3.92
Bearing pressure at footing P1 = 19.74 Ton./sqm OK < 22.49 Ton./sqm
four corners P2 = 11.9 Ton./sqm
P3 = 19.7 Ton./sqm
P4 = 11.86 Ton./sqm
M/S. REFEX ENERGY LIMITED
DOCUMENT NO DATE
PROJECT SOLAR PV POWER PLANT OF 50MW AC
1617101-RFX-NLC-SWYD-F&C-018 06.03.18
DESIGNED CHECKED REV
TITLE FOUNDATION & COLUMN DESIGN FOR CRB
GS KN 0.00
5.5 DESIGN OF FOOTING -F2 (Load case 124) & (Node No 28)
M/S. REFEX ENERGY LIMITED
DOCUMENT NO DATE
PROJECT SOLAR PV POWER PLANT OF 50MW AC
1617101-RFX-NLC-SWYD-F&C-018 06.03.18
DESIGNED CHECKED REV
TITLE FOUNDATION & COLUMN DESIGN FOR CRB
GS KN 0.00
5.5 DESIGN OF FOOTING -F2 (Load case 124) & (Node No 28)

Pressure due to over burden soil and raft


( 0.40 + 0.40 )/ 2 x 2.5 +
( 1.60 + 1.60 )/ 2 x 1.87
= 3.992
Net pmax = 15.748 T/m2
Net pmin = -3.848 T/m2

0.3

0.3 FGL FGL


1.80

2.00
0.75 0.75

0.40 z

1.80 1.80 x

PLAN SECTION

CHECK FOR FLEXURE ABOUT Z DIRECTION


Net pressure at edge = 15.748 t/m2

Thickness of footing at column face = 400 mm

Effective depth of footing at z direction, d = 400 - 50 - 6 = 344 mm

Cantilever span of slab from column face = (1.8 - 0.45) / 2 = 0.675 m

Moment (max) at face of column = 15.748 x 0.675 ^ 2 / 2 = 3.59 tm

Mu/bd2 = (3.59 x 2 x 9.81x10^6) / (1000 x 344 ^2) = 0.60 N/mm2

pt = 0.171 % Ast = 0.171 x1000 x 344 / 100 = 588 mm2


Minimum pt = 0.12 % Ast = 0.12 x 1000 x 400 / 100 = 480 mm2
(Ref .Cl.No.26.5.2.1 in IS 456-2000)
PROVIDE 12 TOR @ 100 c/c at bottom, (Ast = 1131 mm2
SAFE
CHECK FOR FLEXURE ABOUT X DIRECTION
Cantilever span of slab from column face = (1.8 - 0.3) / 2 = 0.75 m
Moment (max) at face of column = 15.748 x 0.75 ^ 2 / 2 = 4.43 tm
Effective depth of footing at x direction, d = 400 - 50 - 12 - 12/2 = 332 mm
Mu/bd2 = (4.43 x 2 x 9.81 x 10^6) / (1000 x 332 ^2) = 0.79 N/mm2
M/S. REFEX ENERGY LIMITED
DOCUMENT NO DATE
PROJECT SOLAR PV POWER PLANT OF 50MW AC
1617101-RFX-NLC-SWYD-F&C-018 06.03.18
DESIGNED CHECKED REV
TITLE FOUNDATION & COLUMN DESIGN FOR CRB
GS KN 0.00
5.5 DESIGN OF FOOTING -F2 (Load case 124) & (Node No 28)

pt = 0.228 % Ast = 0.228 x1000 x 332 / 100 = 757 mm2


Minimum pt = 0.12 % Ast = 0.12 x 1000 x 400 / 100 = 480 mm2
PROVIDE 12 TOR @ 100 c/c at bottom, (Ast = 1131 mm2
(Ref .Cl.No.26.5.2.1 in IS 456-2000) SAFE
Provide nominal reinforcement @ top
Minimum pt = 0.06 % = 0.06 x 1000 x 400 / 100 = 240 mm2
PROVIDE 10 TOR @ 200 c/c bothways, (Ast = 393 mm2
SAFE
CHECK AGAINST ONE WAY SHEAR @ Z DIRECTION
Depth of footing = 400 mm
Effective depth = 400 - 50 - 6 = 344 mm
Shear force at critical section, V = 15.748 x 1x (0.675 - 0.344) = 5.21 ton
Cantilever length = 0.675 m
Critical section for shear is at a
distance 'd' from the face of the
pedestal = 0.675 - 0.344
= 0.331 m
Effective depth at critical sction d' = 0.344 m
(Ref .Cl.No.40.1 in IS 456-2000)
Nominal shear stress at critical section, tv = = V / (b' x d')
(5.21 x2 x 9.81 x 10^3) / (1000 x 344) = 0.30 N/mm2

Percentage of reinforcement at critical section = [1130.97 / ( 1000 x 344 )] x 100


= 0.330
Corresponding shear stress tc = 0.402 > 0.30 N/mm2
(Ref .Table 19. in IS 456-2000) Hence Safe

CHECK FOR TWO WAY SHEAR AT 'D/2' FROM THE PEDESTAL FACE
Maximum axial load on pedestal = 373.8 KN
Effective depth at critical section = 0.34 m

Area resisted by shear stress = 989344 mm2

Actual punching shear = 0.567


Permissible stress in two way shear = 0.25 × √25 = 1.250 N/mm²
(Ref .Cl.31.6.3. in IS 456-2000) Hence safe in two way shear
Check against one way shear @ X direction
Depth of footing D = 400 mm
Effective depth ( d' ) = 400 - 50 -12-6 = 332 mm

Shear force at critical section, V = 15.748 x 1x (0.75 - 0.332) = 6.58 ton


Cantilever length = 0.75 m
Critical section for shear is at a distance 'd' from the face of the column = 0.75 - 0.332
= 0.418 m
Effective depth at critical sction d' = 0.332 m
(Ref .Cl.No.40.1 in IS 456-2000)
M/S. REFEX ENERGY LIMITED
DOCUMENT NO DATE
PROJECT SOLAR PV POWER PLANT OF 50MW AC
1617101-RFX-NLC-SWYD-F&C-018 06.03.18
DESIGNED CHECKED REV
TITLE FOUNDATION & COLUMN DESIGN FOR CRB
GS KN 0.00
5.5 DESIGN OF FOOTING -F2 (Load case 124) & (Node No 28)
Nominal shear stress at critical section, tv = V / (b' x d')
(6.58 x 2 x 9.81 x 10^3) / (1000 x 332) = 0.39 N/mm2

Percentage of reinforcement at critical section = = [1130.97 / ( 1000 x 332 )] x 100


= 0.340

Corresponding shear stress tc = 0.41 > 0.39 N/mm2


Hence Safe

Design Summary:-
Length of footing = 1800 mm
Breath of footing = 1800 mm
Thickness of footing = 400 mm
Reinforcement
Bottom of Footing:-
In Z-direction = 12 mm diameter @ 100 C/C (Bottom )
In X-direction = 12 mm diameter @ 100 C/C (Bottom )
Top of footing
In Z-direction = 10 mm diameter @ 200 C/C (Top )
In X-direction = 10 mm diameter @ 200 C/C (Top )
M/S. REFEX ENERGY LIMITED
DOCUMENT NO DATE
PROJECT SOLAR PV POWER PLANT OF 50MW AC
1617101-RFX-NLC-SWYD-F&C-018 06.03.18
DESIGNED CHECKED REV
TITLE FOUNDATION & COLUMN DESIGN FOR CRB
GS KN 0.00
5.5 DESIGN OF FOOTING -F2 (Load case 124) & (Node No 28)
5 FOUNDATION DESIGN FOR CONTROL ROOM BUILDING

5.3 DESIGN OF FOOTING -F3 (FOR C3 COLUMNS)


DESIGN DATA:-
Depth of foundation from FGL = 2.00 m
Footing size = 2.20 m x 2.20 m
X-dir Z-dir
Thickness of footing at edge = 450 mm
Thickness of footing at face of column = 450 mm
Projection around column = ###
mm
Column size = 400 mm x 500 mm
X-dir Z-dir
MATERIAL PROPERTIES:-
Compressive Strength of Concrete = 25 N/mm2
Grade of steel = Fe 500
Density of concrete = 2.5 T/m3
Density of soil = 1.87 T/m3
Co efficient of friction = 0.33

FACTOR OF SAFETY:-
Factor of Safety for Overturning , Sliding = 1.40
For strength design = 1.50
From Staad Output (Maximum load among the nodes (14 &19)
Design will be done for worst case i.e for (Load case 101) & (Node No 14)
FX = 1.3 Ton. Node 14 ( Load Case 101)
FZ = 1.1 Ton Node 14 ( Load Case 101)
P = 43.4 Ton Node 14 ( Load Case 101)
Mx = 0.7 Ton.m Node 14 ( Load Case 101)
Mz = 0.89 Ton.m Node 14 ( Load Case 101)
FINAL VALUE FOR DESIGN
Vertical load P = 43.4 Ton
Bending Moment Z-direction Mx = 0.6959 Ton.m
Bending Moment X-direction Mz = 0.89 Ton.m

CALCULATIONS
Volume of footing = 2.18 m3
Volume of soil = 7.19 m3
a) Wt of footing = 5.45 Ton
b) Wt of soil = 13.45 Ton
Total vertical load = 43.3724 + 5.45 + 13.45
= 62.27 Ton
As per soil report, net SBC at 2.0 = 15.00 T/m2 (As per mail dated12.12.2013)
Gross SBC at 2.0m depth = = 15x1.25+2x1.87 = 22.490

Bearing pressure = 62.27 / (2.2 x 2.2) ± 6 x 0.6959 / (2.2 x 2.2^2)


± 6 x 0.89 / (2.2 x 2.2^2)
= 12.87 ± 0.39 ±
Bearing pressure at footing P1 = 13.76 Ton./sqm OK < 22.49 Ton./sqm
four corners P2 = 12.76 Ton./sqm
P3 = 12.98 Ton./sqm
5 FOUNDATION DESIGN FOR CONTROL ROOM BUILDING

5.3 DESIGN OF FOOTING -F3 (FOR C3 COLUMNS)


P4 = 11.98 Ton./sqm

Pressure due to over burden soil and raft


( 0.45 + 0.45 )/ 2 x 2.5 +
( 1.55 + 1.55 )/ 2 x 1.87
= 4.0235
Net pmax = 9.7365 T/m2
Net pmin = 3.024 T/m2
5 FOUNDATION DESIGN FOR CONTROL ROOM BUILDING

5.3 DESIGN OF FOOTING -F3 (FOR C3 COLUMNS)

0.4

0.4 FGL FGL


2.20

2.00
0.9 0.9

0.45 z

2.20 2.20 x

PLAN SECTION

CHECK FOR FLEXURE ABOUT Z DIRECTION


Net pressure at edge = 9.7365 t/m2

Thickness of footing at column face = 450 mm

Effective depth of footing at z direction, d = 450 - 50 - 6 = 394 mm

Cantilever span of slab from column face = (2.2 - 0.5) / 2 = 0.85 m

Moment (max) at face of column = 9.7365 x 0.85 ^ 2 / 2 = 3.52 tm

Mu/bd2 = (3.52 x 1.5 x 9.81x10^6) / (1000 x 394 ^2) = 0.33 N/mm2

pt = 0.077 % Ast = 0.077 x1000 x 394 / 100 = 303 mm2


Minimum pt = 0.12 % Ast = 0.12 x 1000 x 450 / 100 = 540 mm2
(Ref .Cl.No.26.5.2.1 in IS 456-2000)
PROVIDE 12 TOR @ 150 c/c at bottom, (Ast = 754 mm2
SAFE
CHECK FOR FLEXURE ABOUT X DIRECTION
Cantilever span of slab from column face = (2.2 - 0.4) / 2 = 0.9 m

Moment (max) at face of column = 9.7365 x 0.9 ^ 2 / 2 = 3.94 tm


Effective depth of footing at x direction, d = 450 - 50 - 12 - 12/2 = 382 mm
Mu/bd 2
= (3.94 x 1.5 x 9.81 x 10^6) / (1000 x 382 ^2) = 0.40 N/mm2

pt = 0.094 % Ast = 0.094 x1000 x 382 / 100 = 359 mm2


Minimum pt = 0.12 % Ast = 0.12 x 1000 x 450 / 100 = 540 mm2
PROVIDE 12 TOR @ 150 c/c at bottom, (Ast = 754 mm2
5 FOUNDATION DESIGN FOR CONTROL ROOM BUILDING

5.3 DESIGN OF FOOTING -F3 (FOR C3 COLUMNS)


(Ref .Cl.No.26.5.2.1 in IS 456-2000) SAFE
Provide nominal reinforcement @ top
Minimum pt = 0.06 % = 0.06 x 1000 x 450 / 100 = 270 mm2
PROVIDE 10 TOR @ 200 c/c bothways, (Ast = 393 mm2
SAFE
CHECK AGAINST ONE WAY SHEAR @ Z DIRECTION
Depth of footing = 450 mm
Effective depth = 450 - 50 - 6 = 394 mm
Shear force at critical section, V = 9.7365 x 1x (0.85 - 0.394) = 4.44 ton
Cantilever length = 0.85 m
5 FOUNDATION DESIGN FOR CONTROL ROOM BUILDING

5.3 DESIGN OF FOOTING -F3 (FOR C3 COLUMNS)


Critical section for shear is at a
distance 'd' from the face of the
pedestal = 0.85 -
= 0.456 m
Effective depth at critical sction d' = 0.394 m
(Ref .Cl.No.40.1 in IS 456-2000)
Nominal shear stress at critical section, tv = = V / (b' x d')
(4.44 x 1.5 x 9.81 x 10^3) / (1000 x 394) = 0.17 N/mm2

Percentage of reinforcement at critical section = [753.98 / ( 1000 x 394 )] x 100


= 0.190
Corresponding shear stress tc = 0.312 > 0.17 N/mm2
(Ref .Table 19. in IS 456-2000) Hence Safe

CHECK FOR TWO WAY SHEAR AT 'D/2' FROM THE PEDESTAL FACE
Maximum axial load on pedestal = 425.5 KN
Effective depth at critical section = 0.39 m

Area resisted by shear stress = 1330144 mm2

Actual punching shear = 0.48


Permissible stress in two way shear = 0.25 × √20 = 1.250 N/mm²
(Ref .Cl.31.6.3. in IS 456-2000) Hence safe in two way shear

Check against one way shear @ X direction


Depth of footing D = 450 mm
Effective depth ( d' ) = 450 - 50 -12-6 = 382 mm

Shear force at critical section, V = 9.7365 x 1x (0.9 - 0.382) = 5.04 ton


Cantilever length = 0.9 m

Critical section for shear is at a distance 'd' from the face of the column = 0.9 -
= 0.518 m
Effective depth at critical sction d' = 0.394 m
(Ref .Cl.No.40.1 in IS 456-2000)
Nominal shear stress at critical section, tv = V / (b' x d')
(5.04 x 1.5 x 9.81 x 10^3) / (1000 x 394) = 0.19 N/mm2

Percentage of reinforcement at critical section = = [753.98 / ( 1000 x 394 )] x 100


= 0.190

Corresponding shear stress tc = 0.312 > 0.19 N/mm2


Hence Safe

Design Summary:-
Length of footing = 2200 mm
Breath of footing = 2200 mm
5 FOUNDATION DESIGN FOR CONTROL ROOM BUILDING

5.3 DESIGN OF FOOTING -F3 (FOR C3 COLUMNS)


Thickness of footing = 450 mm
Reinforcement
Bottom of Footing:-
In Z-direction = 12 mm diameter @ 150 C/C (Bottom )
In X-direction = 12 mm diameter @ 150 C/C (Top )
Top of footing
In Z-direction = 10 mm diameter @ 200 C/C (Bottom )
In X-direction = 10 mm diameter @ 200 C/C (Top )
IGN FOR CONTROL ROOM BUILDING

OOTING -F3 (FOR C3 COLUMNS)

( Load Case 101)


( Load Case 101)
( Load Case 101)
( Load Case 101)
( Load Case 101)

(As per mail dated12.12.2013)


T/m2

0.5
OK < 22.49 Ton./sqm
IGN FOR CONTROL ROOM BUILDING

OOTING -F3 (FOR C3 COLUMNS)


IGN FOR CONTROL ROOM BUILDING

OOTING -F3 (FOR C3 COLUMNS)


IGN FOR CONTROL ROOM BUILDING

OOTING -F3 (FOR C3 COLUMNS)


IGN FOR CONTROL ROOM BUILDING

OOTING -F3 (FOR C3 COLUMNS)

0.394

[753.98 / ( 1000 x 394 )] x 100

0.382

[753.98 / ( 1000 x 394 )] x 100


IGN FOR CONTROL ROOM BUILDING

OOTING -F3 (FOR C3 COLUMNS)


M/S. REFEX ENERGY LIMITED
DOCUMENT NO DATE
PROJECT SOLAR PV POWER PLANT OF 50MW AC
1617101-RFX-NLC-SWYD-F&C-018 06.03.18
DESIGNED CHECKED REV
TITLE FOUNDATION & COLUMN DESIGN FOR CRB
GS KN 0.00
5.8 DESIGN OF FOOTING -F3 (Load case 124) & (Node No 26)
For Dry Condition
DESIGN DATA:-
Depth of foundation from FGL = 2.00 m
Footing size = 2.30 m x 2.30 m
X-dir Z-dir
Thickness of footing at edge = 500 mm
Thickness of footing at face of column = 500 mm
Projection around column = ###
mm
Column size = 300 mm x 450 mm
X-dir Z-dir
MATERIAL PROPERTIES:-
Compressive Strength of Concrete = 25 N/mm2
Grade of steel = Fe 415
Density of concrete = 2.5 T/m3
Density of soil = 1.87 T/m3
Co efficient of friction = 0.33

FACTOR OF SAFETY:-
For strength design = 2.00
From Staad Output (Maximum load among the nodes (24,25 & 26)
Design will be done for worst case i.e for (Load case 124) & (Node No 26)
FX = 3.610 Ton.
FZ = 1.0 Ton
P = 64.3 Ton
Mx = 0.8 Ton.m
Mz = 4.23 Ton.m
FINAL VALUE FOR DESIGN
Vertical load P = 64.3 Ton
Bending Moment Z-direction Mx = 0.7747 Ton.m
Bending Moment X-direction Mz = 4.2305 Ton.m

CALCULATIONS
Volume of footing = 2.85 m3
Volume of soil = 7.73 m3
a) Wt of footing = 7.125 Ton
b) Wt of soil = 14.46 Ton
Total vertical load = 64.3474 + 7.125 + 14.46
= 85.93 Ton
Net SBC at 2 m depth = 15.00 T/m2
Gross SBC at 2 m depth = = 15x1.25+2x1.87 = 22.49 T/m2

Bearing pressure = 85.93 / (2.3 x 2.3) ± 6 x 0.7747 / (2.3 x 2.3^2)


± 6 x 4.2305 / (2.3 x 2.3^2)
= 16.24 ± 0.38 ± 2.09
Bearing pressure at footing P1 = 18.71 Ton./sqm OK < 22.49 Ton./sqm
four corners P2 = 14.53 Ton./sqm
P3 = 17.95 Ton./sqm
P4 = 13.77 Ton./sqm
M/S. REFEX ENERGY LIMITED
DOCUMENT NO DATE
PROJECT SOLAR PV POWER PLANT OF 50MW AC
1617101-RFX-NLC-SWYD-F&C-018 06.03.18
DESIGNED CHECKED REV
TITLE FOUNDATION & COLUMN DESIGN FOR CRB
GS KN 0.00
5.8 DESIGN OF FOOTING -F3 (Load case 124) & (Node No 26)
Pressure due to over burden soil and raft
( 0.50 + 0.50 )/ 2 x 2.5 +
( 1.50 + 1.50 )/ 2 x 1.87
= 4.055
M/S. REFEX ENERGY LIMITED
DOCUMENT NO DATE
PROJECT SOLAR PV POWER PLANT OF 50MW AC
1617101-RFX-NLC-SWYD-F&C-018 06.03.18
DESIGNED CHECKED REV
TITLE FOUNDATION & COLUMN DESIGN FOR CRB
GS KN 0.00
5.8 DESIGN OF FOOTING -F3 (Load case 124) & (Node No 26)
Net pmax = 14.655 T/m2
Net pmin = -0.125 T/m2

0.3

0.3 FGL FGL


2.30

2.00
1 1

0.50 z

2.30 2.30 x

PLAN SECTION

CHECK FOR FLEXURE ABOUT Z DIRECTION


Net pressure at edge = 14.655 t/m2

Thickness of footing at column face = 500 mm

Effective depth of footing at z direction, d = 500 - 50 - 8 = 442 mm

Cantilever span of slab from column face = (2.3 - 0.45) / 2 = 0.925 m

Moment (max) at face of column = 14.655 x 0.925 ^ 2 / 2 = 6.27 tm

Mu/bd2 = (6.27 x 2 x 9.81x10^6) / (1000 x 442 ^2) = 0.63 N/mm2

pt = 0.180 % Ast = 0.18 x1000 x 442 / 100 = 796 mm2


Minimum pt = 0.12 % Ast = 0.12 x 1000 x 500 / 100 = 600 mm2
(Ref .Cl.No.26.5.2.1 in IS 456-2000)
PROVIDE 16 TOR @ 100 c/c at bottom , (Ast) = 2011 mm2
SAFE
CHECK FOR FLEXURE ABOUT X DIRECTION
Cantilever span of slab from column face = (2.3 - 0.3) / 2 = 1 m

Moment (max) at face of column = 14.655 x 1 ^ 2 / 2 = 7.33 tm


Effective depth of footing at x direction, d = 500 - 50 - 16 - 16/2 = 426 mm
Mu/bd2 = (7.33 x 2x 9.81 x 10^6) / (1000 x 426 ^2) = 0.79 N/mm2

pt = 0.228 % Ast = 0.228 x1000 x 426 / 100 = 971 mm2


Minimum pt = 0.12 % Ast = 0.12 x 1000 x 500 / 100 = 600 mm2
PROVIDE 16 TOR @ 100 c/c at bottom , (Ast = 2011 mm2
(Ref .Cl.No.26.5.2.1 in IS 456-2000) SAFE
M/S. REFEX ENERGY LIMITED
DOCUMENT NO DATE
PROJECT SOLAR PV POWER PLANT OF 50MW AC
1617101-RFX-NLC-SWYD-F&C-018 06.03.18
DESIGNED CHECKED REV
TITLE FOUNDATION & COLUMN DESIGN FOR CRB
GS KN 0.00
5.8 DESIGN OF FOOTING -F3 (Load case 124) & (Node No 26)
Provide nominal reinforcement @ top
Minimum pt = 0.06 % = 0.06 x 1000 x 500 / 100 = 300 mm2
PROVIDE 10 TOR @ 200 c/c bothways a, (Ast = 393 mm2
SAFE
M/S. REFEX ENERGY LIMITED
DOCUMENT NO DATE
PROJECT SOLAR PV POWER PLANT OF 50MW AC
1617101-RFX-NLC-SWYD-F&C-018 06.03.18
DESIGNED CHECKED REV
TITLE FOUNDATION & COLUMN DESIGN FOR CRB
GS KN 0.00
5.8 DESIGN OF FOOTING -F3 (Load case 124) & (Node No 26)
CHECK AGAINST ONE WAY SHEAR @ Z DIRECTION
Depth of footing = 500 mm
Effective depth = 500 - 50 - 8 = 442 mm
Shear force at critical section, V = 14.655 x 1x (0.925 - 0.442) = 7.08 ton
Cantilever length = 0.925 m
Critical section for shear is at a
distance 'd' from the face of the
pedestal = 0.925 - 0.442
= 0.483 m
Effective depth at critical sction d' = 0.442 m
(Ref .Cl.No.40.1 in IS 456-2000)
Nominal shear stress at critical section, tv = = V / (b' x d')
(7.08 x 2 x 9.81 x 10^3) / (1000 x 442) = 0.31 N/mm2

Percentage of reinforcement at critical section = [2010.62 / ( 1000 x 442 )] x 100


= 0.450
Corresponding shear stress tc = 0.464 > 0.31 N/mm2
(Ref .Table 19. in IS 456-2000) Hence Safe
CHECK FOR TWO WAY SHEAR AT 'D/2' FROM THE PEDESTAL FACE
Maximum axial load on pedestal = 631.2 KN
Effective depth at critical section = 0.44 m
Area resisted by shear stress = 1444456 mm2
Actual punching shear = 0.656
Permissible stress in two way shear = 0.25 × √25 = 1.250 N/mm²
(Ref .Cl.31.6.3. in IS 456-2000) Hence safe in two way shear

Check against one way shear @ X direction


Depth of footing D = 500 mm
Effective depth ( d' ) = 500 - 50 -16-8 = 426 mm

Shear force at critical section, V = 14.655 x 1x (1 - 0.426) = 8.41 ton


Cantilever length = 1m

Critical section for shear is at a distance 'd' from the face of the column = 1 - 0.426
= 0.574 m
Effective depth at critical sction d' = 0.426 m
(Ref .Cl.No.40.1 in IS 456-2000)
Nominal shear stress at critical section, tv = V / (b' x d')
(8.41 x 2 x 9.81 x 10^3) / (1000 x 426) = 0.39 N/mm2

Percentage of reinforcement at critical section = = [2010.62 / ( 1000 x 426 )] x 100


= 0.470

Corresponding shear stress tc = 0.474 > 0.39 N/mm2


Hence Safe
M/S. REFEX ENERGY LIMITED
DOCUMENT NO DATE
PROJECT SOLAR PV POWER PLANT OF 50MW AC
1617101-RFX-NLC-SWYD-F&C-018 06.03.18
DESIGNED CHECKED REV
TITLE FOUNDATION & COLUMN DESIGN FOR CRB
GS KN 0.00
5.8 DESIGN OF FOOTING -F3 (Load case 124) & (Node No 26)

Design Summary:-
Length of footing = 2300 mm
Breath of footing = 2300 mm
Thickness of footing = 500 mm
Reinforcement
Bottom of Footing:-
In Z-direction = 16 mm diameter @ 100 C/C (Bottom )
In X-direction = 16 mm diameter @ 100 C/C (Bottom)
Top of footing
In Z-direction = 10 mm diameter @ 200 C/C (Top )
In X-direction = 10 mm diameter @ 200 C/C (Top )
M/S. REFEX ENERGY LIMITED
DOCUMENT NO DATE
PROJECT SOLAR PV POWER PLANT OF 50MW AC
1617101-RFX-NLC-SWYD-F&C-018 06.03.18
DESIGNED CHECKED REV
TITLE FOUNDATION & COLUMN DESIGN FOR CRB
GS KN 0.00
5.8 DESIGN OF FOOTING -F3 (Load case 124) & (Node No 26)
COLUMN REINFORCEMRNT SUMMARY

Col.Length Breath Depth Reqd. Reinft


Cl.NO Node No. COLUMN No. Reinft
(m) (mm) (mm) (sq.mm)
1 1500 250 400 401.84 4
C1 1 2 1500 300 450 1091.6 NOS +
3 1500 300 450 1145.16 4

34 #N/A #N/A #N/A #N/A 4 +


35 #N/A #N/A #N/A #N/A NOS
C1 5
36 #N/A #N/A #N/A #N/A
37 #N/A #N/A #N/A #N/A 4

53 3000 250 400 809.69 4


54 3000 300 450 1085.75 NOS
C1 10 +
55 3000 300 450 1174.38
56 3000 300 450 1070.78 4

70 3000 250 400 826.11 4


C1 15 71 #N/A #N/A #N/A #N/A NOS +
72 #N/A #N/A #N/A #N/A 4

4 #N/A #N/A #N/A #N/A 4


C2 19 5 1500 300 450 611.3 NOS +
6 1500 300 450 1260.67 8

7 1500 250 400 325.87 8


8 1500 250 400 399.42 NOS
C3 29 +
9 1500 250 400 2929.53 4

10 1500 250 400 3068.7 4


11 1500 400 400 683.17 NOS
C2 39 +
12 1500 400 400 658.31
8

73 #N/A #N/A #N/A #N/A 4


C2 25 74 #N/A #N/A #N/A #N/A NOS +
75 #N/A #N/A #N/A #N/A 8

76 #N/A #N/A #N/A #N/A 8


77 #N/A #N/A #N/A #N/A NOS
C3 35 +
78 #N/A #N/A #N/A #N/A 4

79 #N/A #N/A #N/A #N/A 4


80 #N/A #N/A #N/A #N/A NOS
C2 45 +
81 #N/A #N/A #N/A #N/A 8

13 #N/A #N/A #N/A #N/A 4


C1 49 14 1500 250 400 564.32 NOS +
15 1500 250 400 1226.53 4

16 1500 250 400 365.4 4


C1 65 17 1500 250 400 549.03 NOS +
18 1500 250 400 524.06 4

19 1500 250 400 606.34 4


C1 79 +
COLUMN REINFORCEMRNT SUMMARY

Col.Length Breath Depth Reqd. Reinft


Cl.NO Node No. COLUMN No. Reinft
(m) (mm) (mm) (sq.mm)
20 1500 250 400 397.21 NOS
C1 79 +
21 #N/A #N/A #N/A #N/A
4

22 #N/A #N/A #N/A #N/A 4


C1 93 23 #N/A #N/A #N/A #N/A NOS +
24 #N/A #N/A #N/A #N/A 4

25 #N/A #N/A #N/A #N/A 4


26 #N/A #N/A #N/A #N/A NOS
C1 107 +
27 #N/A #N/A #N/A #N/A
4

28 #N/A #N/A #N/A #N/A 4


C4 121 28 #N/A #N/A #N/A #N/A NOS +
30 #N/A #N/A #N/A #N/A 4
COLUMN REINFORCEMRNT SUMMARY

Col.Length Breath Depth Reqd. Reinft


Cl.NO Node No. COLUMN No. Reinft
(m) (mm) (mm) (sq.mm)
31 #N/A #N/A #N/A #N/A 4
32 #N/A #N/A #N/A #N/A NOS
C5 128 +
33 #N/A #N/A #N/A #N/A
4

38 #N/A #N/A #N/A #N/A 4


C1 54 39 #N/A #N/A #N/A #N/A NOS +
4

40 #N/A #N/A #N/A #N/A 4


C1 69 41 #N/A #N/A #N/A #N/A NOS +
4

42 #N/A #N/A #N/A #N/A 4


C1 83 43 #N/A #N/A #N/A #N/A NOS +
4

44 #N/A #N/A #N/A #N/A 4


C1 97 45 #N/A #N/A #N/A #N/A NOS +
4

46 #N/A #N/A #N/A #N/A 4


C1 111 47 #N/A #N/A #N/A #N/A NOS +
4

48 #N/A #N/A #N/A #N/A 4


C1 125 49 #N/A #N/A #N/A #N/A NOS +
4

50 #N/A #N/A #N/A #N/A 4


C4 132 51 #N/A #N/A #N/A #N/A NOS +
52 #N/A #N/A #N/A #N/A 4

57 3000 300 450 1791.6 4


C1 57 58 3000 250 400 1014.19 NOS +
4

59 3000 250 400 1041.44 4


C1 72 60 3000 250 400 1659.32 NOS +
4

61 3000 250 400 2108.1 4


C1 86 62 3000 400 400 919.26 NOS +
4

63 3000 400 400 937.99 4


C1 100 64 3000 250 400 960.06 NOS +
4

65 3000 250 400 1593.28 4


C1 114 66 3000 250 400 1150.44 NOS +
4

67 3000 250 400 821.74 4


C4 136 68 3000 250 400 743.31 NOS +
COLUMN REINFORCEMRNT SUMMARY

Col.Length Breath Depth Reqd. Reinft


Cl.NO Node No. COLUMN No. Reinft
C4 136 (m) (mm) (mm) (sq.mm) +
69 3000 250 400 1734.61 4

82 #N/A #N/A #N/A #N/A 4


C1 61 83 #N/A #N/A #N/A #N/A NOS +
84 #N/A #N/A #N/A #N/A 4

85 #N/A #N/A #N/A #N/A 4


C1 75 86 #N/A #N/A #N/A #N/A NOS +
87 #N/A #N/A #N/A #N/A 4

88 #N/A #N/A #N/A #N/A 4


C1 89 89 #N/A #N/A #N/A #N/A NOS +
90 #N/A #N/A #N/A #N/A 4

91 #N/A #N/A #N/A #N/A 4


C1 103 92 #N/A #N/A #N/A #N/A NOS +
93 #N/A #N/A #N/A #N/A 4

94 #N/A #N/A #N/A #N/A 4


C4 117 95 #N/A #N/A #N/A #N/A NOS +
96 #N/A #N/A #N/A #N/A 4

97 #N/A #N/A #N/A #N/A 4


C6 140 98 #N/A #N/A #N/A #N/A NOS +
99 #N/A #N/A #N/A #N/A 4
NFORCEMRNT SUMMARY

Provided
Reinft
Reinft.(sq.mm)
12
DIA 904.78
12 REVISE

12 904.78
DIA #N/A

12

12
DIA 904.78

12 REVISE

12
DIA 904.78
12 #N/A

20
DIA 2865.13
16 #N/A

20
DIA 3769.91
20 OK

20
DIA 2865.13
REVISE
16

20
DIA 2865.13
16 #N/A

20
DIA 3769.91
20 #N/A

20
DIA 2865.13
16 #N/A

12
DIA 904.78
12 #N/A

12
DIA 904.78
12 OK

12
NFORCEMRNT SUMMARY

Provided
Reinft
Reinft.(sq.mm)
DIA 904.78
#N/A
12

12
DIA 904.78
12 #N/A

12
DIA 904.78

12 #N/A

16
DIA 1256.64
12 #N/A
NFORCEMRNT SUMMARY

Provided
Reinft
Reinft.(sq.mm)
20
DIA 2513.27

20 #N/A

12
DIA 904.78
12 #N/A

12
DIA 904.78
12 #N/A

12
DIA 904.78
12 #N/A

12
DIA 904.78
12 #N/A

12
DIA 904.78
12 #N/A

12
DIA 904.78
12 #N/A

16
DIA 1256.64
12 #N/A

12
DIA 904.78
12 REVISE

12
DIA 904.78
12 REVISE

12
DIA 904.78
12 REVISE

12
DIA 904.78
12 REVISE

12
DIA 904.78
12 REVISE

16
DIA 1256.64
NFORCEMRNT SUMMARY

Provided
Reinft
Reinft.(sq.mm)
12 REVISE

12
DIA 904.78
12 #N/A

12
DIA 904.78
12 #N/A

12
DIA 904.78
12 #N/A

12
DIA 904.78
12 #N/A

16
DIA 1256.64
12 #N/A

20
DIA 2060.88
16 #N/A
#REF!
WET CONDITION CHECK
#REF!
For Wet Condition
#REF!
Input data :
Depth of foundation from EGL = #REF! m
Distance between EGL & FGL = #REF! m
Depth of foundation from FGL = #REF! #REF! m
Footing size = #REF! m x #REF! m
X-dir Z-dir
Factor of Safety for Overturning , Sliding = #REF!
Co efficient of friction = #REF!
Thickness of footing at edge = #REF! mm
Thickness of footing at face of column = #REF! mm
Projection around column = #REF! mm
Column size = #REF! mm x #REF! mm
X-dir Z-dir
Concrete mix M #REF!
Grade of steel Fe #REF!
Density of concrete = 1.5 t/m3
Density of soil below EGL = 1 t/m3
Density of soil above EGL = #REF! t/m3
Volume of footing below EGL = #REF! m3
Volume of soil below EGL = #REF! m3
Volume of soil above EGL = #REF!
a) Wt of footing = #REF! ton
b) Wt of soil below EGL = #REF! ton
c) Wt of soil above EGL = #REF! ton

FX = #REF! ton
FZ = #REF! ton
P= #REF! ton As per STAAD output
Mx = #REF! tm
Mz = #REF! tm

Final value for design


P= #REF! ton
Z-dir Mx = #REF! tm
X-dir Mz = #REF! tm

Total vertical load = #REF! #REF! ton


As per soil report, net SBC at #REF! m depth = #REF! t/m2
Gross SBC at 2.5 m depth = #REF! #REF! t/m2
Bearing pressure = #REF! ± #REF!
± #REF!
#REF! ± #REF! ± #REF!
P1 #REF! t/sqm #REF!
P2 #REF! t/sqm
P3 #REF! t/sqm
P4 #REF! t/sqm

Pressure due to over burden soil and raft


#REF!
WET CONDITION CHECK
( #REF! + #REF! )/ 2 x 1.5 +
( #REF! + #REF! )/ 2 x 1 +
( #REF! + #REF! )/ 2 x #REF!
= #REF!
net pmax = #REF! t/m2
net pmin = #REF! t/m2
#REF!
WET CONDITION CHECK

#REF! #REF! #REF!


#REF!
#REF!

#REF!
#REF! #REF! Z
#REF!

#REF!
#REF!

Check for flexure about Z direction


Net pressure at edge = #REF! t/m2

Thickness of footing at column face = #REF! mm

Effective depth of footing at z direction, d = #REF! #REF! mm

Cantilever span of slab from column face = #REF! #REF! m

` Moment (max) at face of column = #REF! #REF! tm

Mu/bd2 = #REF! #REF! N/mm2

pt = #REF! % Ast = #REF! #REF! mm2


Minimum pt = 0.12 % Ast = #REF! #REF! mm2

PROVIDE 16 TOR @ #REF! at bottom , (Ast = #REF! mm2


#REF!
Check for flexure about X direction

Cantilever span of slab from column face = #REF! #REF! m


Moment (max) at face of column = #REF! #REF! tm
Effective depth of footing at x direction, d = #REF! #REF! mm
Mu/bd2 = #REF! #REF! N/mm2

pt = #REF! % Ast = #REF! #REF! mm2

Minimum pt = 0.12 % Ast = #REF! #REF! mm2


PROVIDE 16 TOR @ #REF! at bottom , (Ast = #REF! mm2
#REF!
Provide nominal reinforcement @ top
Minimum pt = 0.06 % #REF! = #REF! mm2
PROVIDE 10 TOR @ 200 c/c bothways at top , (Ast = 393 mm2
#REF!
#REF!
WET CONDITION CHECK

Check against one way shear @ Z direction

Depth of footing #REF! mm

Effective depth = #REF! #REF! mm

Shear force at critical section, V = #REF! #REF! ton

Cantilever length = #REF! m

Critical section for shear is at a


distance 'd3' from the face of the
pedestal = #REF! - #REF!
= #REF! m

Effective depth at critical sction d' #REF! m

#REF! +( #REF! x #REF! )- #REF! -

Nominal shear stress at critical section, tv = V / (b' x d') =


#REF!
= #REF! N/mm2

Percentage of reinforcement at critical section = #REF!

= #REF!

Corresponding shear stress tc = #REF!


#REF! #REF! N/mm2 #REF!

Check for Two way Shear at 'd/2' from the pedestal face
Maximum axial load on pedestal = #REF! KN
Effective depth at critical section = #REF! m

#REF! +( #REF! x #REF! ) #REF! -

#REF! /( #REF! - #REF! )

= #REF!
#REF! - #REF! /2
= #REF!

Area resisted by shear stress #REF! mm2

Actual punching shear #REF!


Permissible stress in two way shear = 0.25 × √20 = #REF! N/mm²
#REF!
#REF!
WET CONDITION CHECK
Check against one way shear @ X direction

Depth of footing #REF! mm

Effective depth = #REF! #REF! mm

Shear force at critical section, V = #REF! #REF! ton

Cantilever length = #REF! m

Critical section for shear is at a


distance 'd3' from the face of the
pedestal = #REF! - #REF!
= #REF! m

Effective depth at critical sction d' #REF! m

#REF! +( #REF! x #REF! )- #REF! -

Nominal shear stress at critical section, tv = V / (b' x d') =


#REF!
= #REF! N/mm2

Percentage of reinforcement at critical section = #REF!

= #REF!

Corresponding shear stress tc = #REF!


#REF! #REF! N/mm2 #REF!

CHECK FOR OVERTURNING:


Net Moments acting at Pad Level, Mxx = #REF! tm

Net Moments acting at Pad Level, Mzz = #REF! tm


Weight of pad = #REF! ton

Weight ofover burden earth = #REF! ton

Total downward Load = #REF! + #REF!


#REF!
= #REF! ton

Stabilizing moment `X ' Dir = #REF! x #REF!

= #REF! tm
Stabilizing moment `Z' Dir = #REF! x #REF!
#REF! tm

Actuating moment, Mxx = #REF! tm

Factor of Safety = #REF! / #REF!


#REF!
WET CONDITION CHECK
#REF! #REF! #REF!

#REF!
Actuating moment, Mzz = #REF! tm

Factor of Safety = #REF! / #REF!

#REF! #REF! #REF!


#REF!
#REF!
WET CONDITION CHECK
CHECK FOR SLIDING

Max. Shear Load At Pad level in X direction = #REF! ton

Resistance against Sliding = #REF! x #REF!

= #REF! ton

Factor of Safety = #REF! / #REF!

#REF! #REF! #REF!

#REF!

Max. Shear Load At Pad level in Z direction = #REF! ton

Resistance against Sliding = #REF! x #REF!

= #REF! ton

Factor of Safety = #REF! / #REF!

#REF! #REF! #REF!

#REF!
CHECK FOR UPLIFT
Base pressure on footing due to water pressure = 1 x #REF!
#REF! x #REF!

= #REF! ton

= #REF! / #REF!

#REF! #REF! 1.5

#REF!
#REF!
WET CONDITION CHECK
#REF!
#REF!
WET CONDITION CHECK
#REF!
WET CONDITION CHECK
#REF!
WET CONDITION CHECK

0.008

0.008
#REF!
WET CONDITION CHECK

0.008

/2

/2
#REF!
WET CONDITION CHECK
#REF!
WET CONDITION CHECK

x
#REF!
WET CONDITION CHECK
#REF!
For Wet Condition
#REF!
Input data :
Depth of foundation from EGL = #REF! m
Distance between EGL & FGL = #REF! m
Depth of foundation from FGL = #REF! #REF! m
Footing size = #REF! m x #REF! m
X-dir Z-dir
Factor of Safety for Overturning , Sliding = #REF!
Co efficient of friction = #REF!
Thickness of footing at edge = #REF! mm
Thickness of footing at face of column = #REF! mm
Projection around column = #REF! mm
Column size = #REF! mm x #REF! mm
X-dir Z-dir
Concrete mix M #REF!
Grade of steel Fe #REF!
Density of concrete = 1.5 t/m3
Density of soil below EGL = 1 t/m3
Density of soil above EGL = #REF! t/m3
Volume of footing below EGL = #REF! m3
Volume of soil below EGL = #REF! m3
Volume of soil above EGL = #REF!
a) Wt of footing = #REF! ton
b) Wt of soil below EGL = #REF! ton
c) Wt of soil above EGL = #REF! ton

FX = #REF! ton
FZ = #REF! ton
P= #REF! ton As per STAAD output
Mx = #REF! tm
Mz = #REF! tm

Final value for design


P= #REF! ton
Z-dir Mx = #REF! tm
X-dir Mz = #REF! tm

Total vertical load = #REF! #REF! ton


As per soil report, net SBC at #REF! m depth = #REF! t/m2
Gross SBC at 2.5 m depth = #REF! #REF! t/m2
Bearing pressure = #REF! ± #REF!
± #REF!
#REF! ± #REF! ± #REF!
P1 #REF! t/sqm #REF!
P2 #REF! t/sqm
P3 #REF! t/sqm
P4 #REF! t/sqm

Pressure due to over burden soil and raft


#REF!
WET CONDITION CHECK
( #REF! + #REF! )/ 2 x 1.5 +
( #REF! + #REF! )/ 2 x 1 +
( #REF! + #REF! )/ 2 x #REF!
= #REF!
net pmax = #REF! t/m2
net pmin = #REF! t/m2
#REF!
WET CONDITION CHECK

#REF! #REF! #REF!


#REF!
#REF!

#REF!
#REF! #REF! Z
#REF!

#REF!
#REF!

Check for flexure about Z direction


Net pressure at edge = #REF! t/m2

Thickness of footing at column face = #REF! mm

Effective depth of footing at z direction, d = #REF! #REF! mm

Cantilever span of slab from column face = #REF! #REF! m

Moment (max) at face of column = #REF! #REF! tm

Mu/bd2 = #REF! #REF! N/mm2

pt = #REF! % Ast = #REF! #REF! mm2


Minimum pt = 0.12 % Ast = #REF! #REF! mm2

PROVIDE #REF! TOR @ #REF! at bottom , (Ast = #REF! mm2


#REF!
Check for flexure about X direction

Cantilever span of slab from column face = #REF! #REF! m


Moment (max) at face of column = #REF! #REF! tm
Effective depth of footing at x direction, d = #REF! #REF! mm
Mu/bd2 = #REF! #REF! N/mm2

pt = #REF! % Ast = #REF! #REF! mm2


#REF!
Minimum pt = 0.12 % Ast = #REF! #REF! mm2
PROVIDE #REF! TOR @ #REF! at bottom , (Ast = #REF! mm2
#REF!
Provide nominal reinforcement @ top
Minimum pt = 0.06 % #REF! = #REF! mm2
PROVIDE 10 TOR @ #REF! bothways at top , (Ast = #REF! mm2
#REF!
#REF!
WET CONDITION CHECK

Check against one way shear @ Z direction

Depth of footing #REF! mm

Effective depth = #REF! #REF! mm

Shear force at critical section, V = #REF! #REF! ton

Cantilever length = #REF! m

Critical section for shear is at a


distance 'd3' from the face of the
pedestal = #REF! - #REF!
= #REF! m

Effective depth at critical sction d' #REF! m

#REF! +( #REF! x #REF! )- #REF! -

Nominal shear stress at critical section, tv = V / (b' x d') =


#REF!
= #REF! N/mm2

Percentage of reinforcement at critical section = #REF!

= #REF!

Corresponding shear stress tc = #REF!


#REF! #REF! N/mm2 #REF!

Check for Two way Shear at 'd/2' from the pedestal face
Maximum axial load on pedestal = #REF! KN
Effective depth at critical section = #REF! m

#REF! +( #REF! x #REF! ) #REF! -

#REF! /( #REF! - #REF! )

= #REF!
#REF! - #REF! /2
= #REF!

Area resisted by shear stress #REF! mm2

Actual punching shear #REF!


Permissible stress in two way shear = 0.25 × √20 = #REF! N/mm²
#REF!
#REF!
WET CONDITION CHECK
Check against one way shear @ X direction

Depth of footing #REF! mm

Effective depth = #REF! #REF! mm

Shear force at critical section, V = #REF! #REF! ton

Cantilever length = #REF! m

Critical section for shear is at a


distance 'd3' from the face of the
pedestal = #REF! - #REF!
= #REF! m

Effective depth at critical sction d' #REF! m

#REF! +( #REF! x #REF! )- #REF! -

Nominal shear stress at critical section, tv = V / (b' x d') =


#REF!
= #REF! N/mm2

Percentage of reinforcement at critical section = #REF!

= #REF!

Corresponding shear stress tc = #REF!


#REF! #REF! N/mm2 #REF!

CHECK FOR OVERTURNING:


Net Moments acting at Pad Level, Mxx = #REF! tm

Net Moments acting at Pad Level, Mzz = #REF! tm


Weight of pad = #REF! ton

Weight ofover burden earth = #REF! ton

Total downward Load = #REF! + #REF!


#REF!
= #REF! ton

Stabilizing moment `X ' Dir = #REF! x #REF!

= #REF! tm
Stabilizing moment `Z' Dir = #REF! x #REF!
#REF! tm

Actuating moment, Mxx = #REF! tm

Factor of Safety = #REF! / #REF!

#REF! #REF! #REF!


#REF!
WET CONDITION CHECK

#REF!
Actuating moment, Mzz = #REF! tm

Factor of Safety = #REF! / #REF!

#REF! #REF! #REF!


#REF!
#REF!
WET CONDITION CHECK
CHECK FOR SLIDING

Max. Shear Load At Pad level in X direction = #REF! ton

Resistance against Sliding = #REF! x #REF!

= #REF! ton

Factor of Safety = #REF! / #REF!

#REF! #REF! #REF!

#REF!

Max. Shear Load At Pad level in Z direction = #REF! ton

Resistance against Sliding = #REF! x #REF!

= #REF! ton

Factor of Safety = #REF! / #REF!

#REF! #REF! #REF!

#REF!
CHECK FOR UPLIFT
Base pressure on footing due to water pressure = 1 x #REF!
#REF! x #REF!

= #REF! ton

= #REF! / #REF!

#REF! #REF! 1.5

#REF!
#REF!
ET CONDITION CHECK
#REF!
#REF!
ET CONDITION CHECK
#REF!
ET CONDITION CHECK
#REF!
ET CONDITION CHECK

#REF!

#REF!
#REF!
ET CONDITION CHECK

#REF!

/2

/2
#REF!
ET CONDITION CHECK
#REF!
ET CONDITION CHECK

x
#REF!
WET CONDITION CHECK
#REF!
For Wet Condition
#REF!
Input data :
Depth of foundation from EGL = #REF! m
Distance between EGL & FGL = #REF! m
Depth of foundation from FGL = #REF! #REF! m
Footing size = #REF! m x #REF! m
X-dir Z-dir
Factor of Safety for Overturning , Sliding = #REF!
Co efficient of friction = #REF!
Thickness of footing at edge = #REF! mm
Thickness of footing at face of column = #REF! mm
Projection around column = #REF! mm
Column size = #REF! mm x #REF! mm
X-dir Z-dir
Concrete mix M #REF!
Grade of steel Fe #REF!
Density of concrete = 1.5 t/m3
Density of soil below EGL = 1 t/m3
Density of soil above EGL = #REF! t/m3
Volume of footing below EGL = #REF! m3
Volume of soil below EGL = #REF! m3
Volume of soil above EGL = #REF!
a) Wt of footing = #REF! ton
b) Wt of soil below EGL = #REF! ton
c) Wt of soil above EGL = #REF! ton

FX = #REF! ton
FZ = #REF! ton
P= #REF! ton As per STAAD output
Mx = #REF! tm
Mz = #REF! tm

Final value for design


P= #REF! ton
Z-dir Mx = #REF! tm
X-dir Mz = #REF! tm

Total vertical load = #REF! #REF! ton


As per soil report, net SBC at #REF! m depth = #REF! t/m2
Gross SBC at 2.5 m depth = #REF! #REF! t/m2
Bearing pressure = #REF! ± #REF!
± #REF!
#REF! ± #REF! ± #REF!
P1 #REF! t/sqm #REF!
P2 #REF! t/sqm
P3 #REF! t/sqm
P4 #REF! t/sqm

Pressure due to over burden soil and raft


#REF!
WET CONDITION CHECK
( #REF! + #REF! )/ 2 x 1.5 +
( #REF! + #REF! )/ 2 x 1 +
( #REF! + #REF! )/ 2 x #REF!
= #REF!
net pmax = #REF! t/m2
net pmin = #REF! t/m2
#REF!
WET CONDITION CHECK

#REF! #REF! #REF!


#REF!
#REF!

#REF!
#REF! #REF! Z
#REF!

#REF!
#REF!

Check for flexure about Z direction


Net pressure at edge = #REF! t/m2

Thickness of footing at column face = #REF! mm

Effective depth of footing at z direction, d = #REF! #REF! mm

Cantilever span of slab from column face = #REF! #REF! m

Moment (max) at face of column = #REF! #REF! tm

Mu/bd2 = #REF! #REF! N/mm2

pt = #REF! % Ast = #REF! #REF! mm2


Minimum pt = 0.12 % Ast = #REF! #REF! mm2

PROVIDE #REF! TOR @ #REF! at bottom , (Ast = #REF! mm2


#REF!
Check for flexure about X direction

Cantilever span of slab from column face = #REF! #REF! m


Moment (max) at face of column = #REF! #REF! tm
Effective depth of footing at x direction, d = #REF! #REF! mm
Mu/bd2 = #REF! #REF! N/mm2

pt = #REF! % Ast = #REF! #REF! mm2

Minimum pt = 0.12 % Ast = #REF! #REF! mm2


PROVIDE #REF! TOR @ #REF! at bottom , (Ast = #REF! mm2
#REF!
Provide nominal reinforcement @ top
Minimum pt = 0.06 % #REF! = #REF! mm2
PROVIDE 10 TOR @ #REF! bothways at top , (Ast = #REF! mm2
#REF!
#REF!
WET CONDITION CHECK

Check against one way shear @ Z direction

Depth of footing #REF! mm

Effective depth = #REF! #REF! mm

Shear force at critical section, V = #REF! #REF! ton

Cantilever length = #REF! m

Critical section for shear is at a


distance 'd3' from the face of the
pedestal = #REF! - #REF!
= #REF! m

Effective depth at critical sction d' #REF! m

#REF! +( #REF! x #REF! )- #REF! -

Nominal shear stress at critical section, tv = V / (b' x d') =


#REF!
= #REF! N/mm2

Percentage of reinforcement at critical section = #REF!

= #REF!

Corresponding shear stress tc = #REF!


#REF! #REF! #REF!

Check for Two way Shear at 'd/2' from the pedestal face
Maximum axial load on pedestal = #REF! KN
Effective depth at critical section = #REF! m

#REF! +( #REF! x #REF! ) #REF! -

#REF! /( #REF! - #REF! )

= #REF!
#REF! - #REF! /2
= #REF!

Area resisted by shear stress #REF! mm2

Actual punching shear #REF!


Permissible stress in two way shear = 0.25 × √20 = #REF! N/mm²
#REF!
#REF!
WET CONDITION CHECK
Check against one way shear @ X direction

Depth of footing #REF! mm

Effective depth = #REF! #REF! mm

Shear force at critical section, V = #REF! #REF! ton

Cantilever length = #REF! m

Critical section for shear is at a


distance 'd3' from the face of the
pedestal = #REF! - #REF!
= #REF! m

Effective depth at critical sction d' #REF! m

#REF! +( #REF! x #REF! )- #REF! -

Nominal shear stress at critical section, tv = V / (b' x d') =


#REF!
= #REF! N/mm2

Percentage of reinforcement at critical section = #REF!

= #REF!

Corresponding shear stress tc = #REF!


#REF! #REF! #REF!

CHECK FOR OVERTURNING:


Net Moments acting at Pad Level, Mxx = #REF! tm

Net Moments acting at Pad Level, Mzz = #REF! tm


Weight of pad = #REF! ton

Weight ofover burden earth = #REF! ton

Total downward Load = #REF! + #REF!


#REF!
= #REF! ton

Stabilizing moment `X ' Dir = #REF! x #REF!

= #REF! tm
Stabilizing moment `Z' Dir = #REF! x #REF!
#REF! tm

Actuating moment, Mxx = #REF! tm

Factor of Safety = #REF! / #REF!

#REF! #REF! #REF!


#REF!
WET CONDITION CHECK

#REF!
Actuating moment, Mzz = #REF! tm

Factor of Safety = #REF! / #REF!

#REF! #REF! #REF!


#REF!
#REF!
WET CONDITION CHECK
CHECK FOR SLIDING

Max. Shear Load At Pad level in X direction = #REF! ton

Resistance against Sliding = #REF! x #REF!

= #REF! ton

Factor of Safety = #REF! / #REF!

#REF! #REF! #REF!

#REF!

Max. Shear Load At Pad level in Z direction = #REF! ton

Resistance against Sliding = #REF! x #REF!

= #REF! ton

Factor of Safety = #REF! / #REF!

#REF! #REF! #REF!

#REF!
CHECK FOR UPLIFT
Base pressure on footing due to water pressure = 1 x #REF!
#REF! x #REF!

= #REF! ton

= #REF! / #REF!

#REF! #REF! 1.5

#REF!
#REF!
WET CONDITION CHECK
#REF!
#REF!
WET CONDITION CHECK
#REF!
WET CONDITION CHECK
#REF!
WET CONDITION CHECK

#REF!

#REF!
#REF!
WET CONDITION CHECK

#REF!

/2

/2
#REF!
WET CONDITION CHECK
#REF!
WET CONDITION CHECK

x
CLIENT M/S. REFEX ENERGY LIMITED
DOCUMENT NO DATE
PROJECT SOLAR PV POWER PLANT OF 50MW AC
1617101-RFX-NLC-SWYD-F&C-018 06.03.18
DESIGNED CHECKED REV
TITLE FOUNDATION & COLUMN DESIGN FOR CRB
GS KN 0
3.1 DESIGN OF FOOTING -F1 (Load case 136) & (Node No 3)

DESIGN DATA:-
Depth of foundation from FGL = 2.00 m
Footing size = 1.50 m x 1.50 m
X-dir Z-dir
Thickness of footing at edge = 300 mm
Thickness of footing at face of column = 300 mm
Projection around column = ###mm
Column size = 300 mm x 230 mm
X-dir Z-dir
MATERIAL PROPERTIES:-
Compressive Strength of Concrete = 25 N/mm2
Grade of steel = Fe 500
Density of concrete = 2.5 T/m3
Density of soil = 1.733 T/m3
Co efficient of friction = 0.50

FACTOR OF SAFETY:-
For strength design = 2.00
FX = 1.836 Ton.
FZ = 0.1 Ton
P = 15.3 Ton
Mx = 0.0 Ton.m
Mz = 2.5 Ton.m
FINAL VALUE FOR DESIGN
Vertical load P = 15.3 Ton
Bending Moment Z-direction Mx = 0.0 Ton.m
Bending Moment X-direction Mz = 2.5 Ton.m

CALCULATIONS
Volume of footing = 0.8 m3
Volume of soil = 3.7 m3
a) Wt of footing = 2 Ton
b) Wt of soil = 6.41 Ton
Total vertical load = 15.3141 + 2 + 6.41
= 23.72 Ton
Net SBC at 2 m depth = 17.95 T/m2
Gross SBC at 2 m depth = = 17.95x1.25+2x1.733 = 25.9035 T/m2

Bearing pressure = 23.72 / (1.5 x 1.5) ± 6 x 0.0461 / (1.5 x 1.5^2)


± 6 x 2.5429 / (1.5 x 1.5^2)
= 10.54 ± 0.08 ± 4.52

Bearing pressure at footing P1 = 15.14 Ton./sqm OK < 25.9035 Ton./sqm


four corners P2 = 6.1 Ton./sqm
P3 = 14.98 Ton./sqm
P4 = 5.94 Ton./sqm

Pressure due to over burden soil and raft


( 0.30 + 0.30 )/ 2 x 2.5 +
( 1.70 + 1.70 )/ 2 x 1.733
= 3.6961
Net pmax = 11.4439 T/m2
Net pmin = -5.344 T/m2
CLIENT M/S. REFEX ENERGY LIMITED
DOCUMENT NO DATE
PROJECT SOLAR PV POWER PLANT OF 50MW AC
1617101-RFX-NLC-SWYD-F&C-018 06.03.18
DESIGNED CHECKED REV
TITLE FOUNDATION & COLUMN DESIGN FOR CRB
GS KN 0

0.3

0.3 FGL FGL


1.50

2.00
0.6 0.6

0.30 z

1.50 1.50 x
PLAN SECTION

CHECK FOR FLEXURE ABOUT Z DIRECTION


Net pressure at edge = 11.4439 t/m2

Thickness of footing at column face = 300 mm

Effective depth of footing at z direction, d = 300 - 50 - 6 = 244 mm

Cantilever span of slab from column face = (1.5 - 0.23) / 2 = 0.635 m

Moment (max) at face of column = 11.4439 x 0.635 ^ 2 / 2 = 2.31 tm

Mu/bd2 = (2.31 x 2 x 9.81x10^6) / (1000 x 244 ^2) = 0.76 N/mm2

pt = 0.181 % Ast = 0.181 x1000 x 244 / 100 = 442 mm2


Minimum pt = 0.12 % Ast = 0.12 x 1000 x 300 / 100 = 360 mm2
(Ref .Cl.No.26.5.2.1 in IS 456-2000)
PROVIDE 12 TOR @ 150 c/c at bottom , (Ast) = 754 mm2
SAFE
CHECK FOR FLEXURE ABOUT X DIRECTION
Cantilever span of slab from column face = (1.5 - 0.3) / 2 = 0.6 m

Moment (max) at face of column = 11.4439 x 0.6 ^ 2 / 2 = 2.06 tm


Effective depth of footing at x direction, d = 300 - 50 - 12 - 12/2 = 232 mm
Mu/bd2 = (2.06 x 2x 9.81 x 10^6) / (1000 x 232 ^2) = 0.75 N/mm2

pt = 0.179 % Ast = 0.179 x1000 x 232 / 100 = 415 mm2


Minimum pt = 0.12 % Ast = 0.12 x 1000 x 300 / 100 = 360 mm2
PROVIDE 12 TOR @ 150 c/c at bottom , (Ast = 754 mm2
(Ref .Cl.No.26.5.2.1 in IS 456-2000) SAFE

Provide nominal reinforcement @ top


Minimum pt = 0.06 % = 0.06 x 1000 x 300 / 100 = 180 mm2
PROVIDE 12 TOR @ 150 c/c bothways a, (Ast = 754 mm2
SAFE

CHECK AGAINST ONE WAY SHEAR @ Z DIRECTION


Depth of footing = 300 mm
Effective depth = 300 - 50 - 6 = 244 mm
Shear force at critical section, V = 11.4439 x 1x (0.635 - 0.244) = 4.47 ton
Cantilever length = 0.635 m
CLIENT M/S. REFEX ENERGY LIMITED
DOCUMENT NO DATE
PROJECT SOLAR PV POWER PLANT OF 50MW AC
1617101-RFX-NLC-SWYD-F&C-018 06.03.18
DESIGNED CHECKED REV
TITLE FOUNDATION & COLUMN DESIGN FOR CRB
GS KN 0
Critical section for shear is at a
distance 'd' from the face of the
pedestal = 0.635 - 0.244
= 0.391 m

Effective depth at critical sction d' = 0.244 m


(Ref .Cl.No.40.1 in IS 456-2000)
Nominal shear stress at critical section, tv = = V / (b' x d')
(4.47 x 2 x 9.81 x 10^3) / (1000 x 244) = 0.36 N/mm2

Percentage of reinforcement at critical section = [753.98 / ( 1000 x 244 )] x 100


= 0.310
Corresponding shear stress = tc 0.402 > 0.36 N/mm2
(Ref .Table 19. in IS 456-2000) Hence Safe
CHECK FOR TWO WAY SHEAR AT 'D/2' FROM THE PEDESTAL FACE
Maximum axial load on pedestal = 150.2 KN
Effective depth at critical section = 0.24 m
Area resisted by shear stress = 496784 mm2
Actual punching shear = 0.454
Permissible stress in two way shear = 0.25 × √25 = 1.250 N/mm²
(Ref .Cl.31.6.3. in IS 456-2000) Hence safe in two way shear

Check against one way shear @ X direction


Depth of footing D = 300 mm
Effective depth ( d' ) = 300 - 50 -12-6 = 232 mm

Shear force at critical section, V = 11.4439 x 1x (0.6 - 0.232) = 4.21 ton


Cantilever length = 0.6 m

Critical section for shear is at a distance 'd' from the face of the column = 0.6 - 0.232
= 0.368 m
Effective depth at critical sction d' = 0.232 m
(Ref .Cl.No.40.1 in IS 456-2000)

Nominal shear stress at critical section, tv = V / (b' x d')


(4.21 x 2 x 9.81 x 10^3) / (1000 x 232) = 0.36 N/mm2

Percentage of reinforcement at critical section = = [753.98 / ( 1000 x 232 )] x 100


= 0.320

Corresponding shear stress tc = 0.409 > 0.36 N/mm2


Hence Safe

Design Summary:-
Length of footing = 1500 mm
Breath of footing = 1500 mm
Thickness of footing = 300 mm
Reinforcement
Bottom of Footing:-
In Z-direction = 12 mm diameter @ 150 C/C (Bottom )
In X-direction = 12 mm diameter @ 150 C/C (Bottom )
Top of footing
In Z-direction = 12 mm diameter @ 150 C/C (Top )
In X-direction = 12 mm diameter @ 150 C/C (Top )
CLIENT M/S. REFEX ENERGY LIMITED
DOCUMENT NO DATE
PROJECT SOLAR PV POWER PLANT OF 50MW AC
1617101-RFX-NLC-SWYD-F&C-018 06.03.18
DESIGNED CHECKED REV
TITLE FOUNDATION & COLUMN DESIGN FOR CRB
GS KN 0
CLIENT M/S. REFEX ENERGY LIMITED
DOCUMENT NO DATE
PROJECT SOLAR PV POWER PLANT OF 50MW AC
1617101-RFX-NLC-SWYD-F&C-018 06.03.18
DESIGNED CHECKED REV
TITLE FOUNDATION & COLUMN DESIGN FOR CRB
GS KN 0
3.1 DESIGN OF FOOTING -F1 (Load case 112) & (Node No 4)

DESIGN DATA:-
Depth of foundation from FGL = 2.00 m
Footing size = 1.50 m x 1.50 m
X-dir Z-dir
Thickness of footing at edge = 300 mm
Thickness of footing at face of column = 300 mm
Projection around column = ###mm
Column size = 230 mm x 300 mm
X-dir Z-dir
MATERIAL PROPERTIES:-
Compressive Strength of Concrete = 25 N/mm2
Grade of steel = Fe 500
Density of concrete = 2.5 T/m3
Density of soil = 1.733 T/m3
Co efficient of friction = 0.50

FACTOR OF SAFETY:-
For strength design = 2.00
FX = 0.937 Ton.
FZ = 0.3 Ton
P = 13.4 Ton
Mx = 0.2 Ton.m
Mz = 1.3 Ton.m
FINAL VALUE FOR DESIGN
Vertical load P = 13.4 Ton
Bending Moment Z-direction Mx = 0.2 Ton.m
Bending Moment X-direction Mz = 1.3 Ton.m

CALCULATIONS
Volume of footing = 0.8 m3
Volume of soil = 3.7 m3
a) Wt of footing = 2 Ton
b) Wt of soil = 6.41 Ton
Total vertical load = 13.387 + 2 + 6.41
= 21.80 Ton
Net SBC at 2 m depth = 17.95 T/m2
Gross SBC at 2 m depth = = 17.95x1.25+2x1.733 = 25.9035 T/m2

Bearing pressure = 21.8 / (1.5 x 1.5) ± 6 x 0.2464 / (1.5 x 1.5^2)


± 6 x 1.2898 / (1.5 x 1.5^2)
= 9.69 ± 0.44 ± 2.29

Bearing pressure at footing P1 = 12.42 Ton./sqm OK < 25.9035 Ton./sqm


four corners P2 = 7.84 Ton./sqm
P3 = 11.54 Ton./sqm
P4 = 6.96 Ton./sqm

Pressure due to over burden soil and raft


( 0.30 + 0.30 )/ 2 x 2.5 +
( 1.70 + 1.70 )/ 2 x 1.733
= 3.6961
Net pmax = 8.7239 T/m2
Net pmin = -0.884 T/m2
CLIENT M/S. REFEX ENERGY LIMITED
DOCUMENT NO DATE
PROJECT SOLAR PV POWER PLANT OF 50MW AC
1617101-RFX-NLC-SWYD-F&C-018 06.03.18
DESIGNED CHECKED REV
TITLE FOUNDATION & COLUMN DESIGN FOR CRB
GS KN 0

0.23

0.23 FGL FGL


1.50

2.00
0.635 0.635

0.30 z

1.50 1.50 x
PLAN SECTION

CHECK FOR FLEXURE ABOUT Z DIRECTION


Net pressure at edge = 8.7239 t/m2

Thickness of footing at column face = 300 mm

Effective depth of footing at z direction, d = 300 - 50 - 6 = 244 mm

Cantilever span of slab from column face = (1.5 - 0.3) / 2 = 0.6 m

Moment (max) at face of column = 8.7239 x 0.6 ^ 2 / 2 = 1.57 tm

Mu/bd2 = (1.57 x 2 x 9.81x10^6) / (1000 x 244 ^2) = 0.52 N/mm2

pt = 0.123 % Ast = 0.123 x1000 x 244 / 100 = 300 mm2


Minimum pt = 0.12 % Ast = 0.12 x 1000 x 300 / 100 = 360 mm2
(Ref .Cl.No.26.5.2.1 in IS 456-2000)
PROVIDE 12 TOR @ 150 c/c at bottom , (Ast) = 754 mm2
SAFE
CHECK FOR FLEXURE ABOUT X DIRECTION
Cantilever span of slab from column face = (1.5 - 0.23) / 2 = 0.635 m

Moment (max) at face of column = 8.7239 x 0.635 ^ 2 / 2 = 1.76 tm


Effective depth of footing at x direction, d = 300 - 50 - 12 - 12/2 = 232 mm
Mu/bd2 = (1.76 x 2x 9.81 x 10^6) / (1000 x 232 ^2) = 0.64 N/mm2

pt = 0.152 % Ast = 0.152 x1000 x 232 / 100 = 353 mm2


Minimum pt = 0.12 % Ast = 0.12 x 1000 x 300 / 100 = 360 mm2
PROVIDE 12 TOR @ 150 c/c at bottom , (Ast = 754 mm2
(Ref .Cl.No.26.5.2.1 in IS 456-2000) SAFE

Provide nominal reinforcement @ top


Minimum pt = 0.06 % = 0.06 x 1000 x 300 / 100 = 180 mm2
PROVIDE 12 TOR @ 150 c/c bothways a, (Ast = 754 mm2
SAFE

CHECK AGAINST ONE WAY SHEAR @ Z DIRECTION


Depth of footing = 300 mm
Effective depth = 300 - 50 - 6 = 244 mm
Shear force at critical section, V = 8.7239 x 1x (0.6 - 0.244) = 3.11 ton
Cantilever length = 0.6 m
CLIENT M/S. REFEX ENERGY LIMITED
DOCUMENT NO DATE
PROJECT SOLAR PV POWER PLANT OF 50MW AC
1617101-RFX-NLC-SWYD-F&C-018 06.03.18
DESIGNED CHECKED REV
TITLE FOUNDATION & COLUMN DESIGN FOR CRB
GS KN 0
Critical section for shear is at a
distance 'd' from the face of the
pedestal = 0.6 - 0.244
= 0.356 m

Effective depth at critical sction d' = 0.244 m


(Ref .Cl.No.40.1 in IS 456-2000)
Nominal shear stress at critical section, tv = = V / (b' x d')
(3.11 x 2 x 9.81 x 10^3) / (1000 x 244) = 0.25 N/mm2

Percentage of reinforcement at critical section = [753.98 / ( 1000 x 244 )] x 100


= 0.310
Corresponding shear stress = tc 0.402 > 0.25 N/mm2
(Ref .Table 19. in IS 456-2000) Hence Safe
CHECK FOR TWO WAY SHEAR AT 'D/2' FROM THE PEDESTAL FACE
Maximum axial load on pedestal = 131.3 KN
Effective depth at critical section = 0.24 m
Area resisted by shear stress = 496784 mm2
Actual punching shear = 0.397
Permissible stress in two way shear = 0.25 × √25 = 1.250 N/mm²
(Ref .Cl.31.6.3. in IS 456-2000) Hence safe in two way shear

Check against one way shear @ X direction


Depth of footing D = 300 mm
Effective depth ( d' ) = 300 - 50 -12-6 = 232 mm

Shear force at critical section, V = 8.7239 x 1x (0.635 - 0.232) = 3.52 ton


Cantilever length = 0.635 m

Critical section for shear is at a distance 'd' from the face of the column = 0.635 - 0.232
= 0.403 m
Effective depth at critical sction d' = 0.232 m
(Ref .Cl.No.40.1 in IS 456-2000)

Nominal shear stress at critical section, tv = V / (b' x d')


(3.52 x 2 x 9.81 x 10^3) / (1000 x 232) = 0.30 N/mm2

Percentage of reinforcement at critical section = = [753.98 / ( 1000 x 232 )] x 100


= 0.320

Corresponding shear stress tc = 0.409 > 0.30 N/mm2


Hence Safe

Design Summary:-
Length of footing = 1500 mm
Breath of footing = 1500 mm
Thickness of footing = 300 mm
Reinforcement
Bottom of Footing:-
In Z-direction = 12 mm diameter @ 150 C/C (Bottom )
In X-direction = 12 mm diameter @ 150 C/C (Bottom )
Top of footing
In Z-direction = 12 mm diameter @ 150 C/C (Top )
In X-direction = 12 mm diameter @ 150 C/C (Top )
CLIENT M/S. REFEX ENERGY LIMITED
DOCUMENT NO DATE
PROJECT SOLAR PV POWER PLANT OF 50MW AC
1617101-RFX-NLC-SWYD-F&C-018 06.03.18
DESIGNED CHECKED REV
TITLE FOUNDATION & COLUMN DESIGN FOR CRB
GS KN 0
CLIENT M/S. REFEX ENERGY LIMITED

DOCUMENT NO DATE
PROJECT SOLAR PV POWER PLANT OF 50MW AC
1617101-RFX-NLC-SWYD-F&C-018 06.03.18
DESIGNED CHECKED REV
TITLE FOUNDATION & COLUMN DESIGN FOR CRB
GS KN 0
3.2 DESIGN OF FOOTING -F2 (Load case 112) & (Node No 2)

DESIGN DATA:-
Depth of foundation from FGL = 2.00 m
Footing size = 1.75 m x 1.75 m
X-dir Z-dir
Thickness of footing at edge = 300 mm
Thickness of footing at face of column = 300 mm
Projection around column = ###
mm
Column size = 300 mm x 230 mm
X-dir Z-dir
MATERIAL PROPERTIES:-
Compressive Strength of Concrete = 25 N/mm2
Grade of steel = Fe 500
Density of concrete = 2.5 T/m3
Density of soil = 1.733 T/m3
Co efficient of friction = 0.50

FACTOR OF SAFETY:-
For strength design = 2.00
FX = 1.987 Ton.
FZ = 0.2 Ton
P = 18.2 Ton
Mx = 0.2 Ton.m
Mz = 2.7 Ton.m
FINAL VALUE FOR DESIGN
Vertical load P = 18.2 Ton
Bending Moment Z-direction Mx = 0.2 Ton.m
Bending Moment X-direction Mz = 2.7 Ton.m

CALCULATIONS
Volume of footing = 1.04 m3
Volume of soil = 5.09 m3
a) Wt of footing = 2.6 Ton
b) Wt of soil = 8.82 Ton
Total vertical load = 18.1894 + 2.6 + 8.82
= 29.61 Ton
Net SBC at 2 m depth = 17.95 T/m2
Gross SBC at 2 m depth = = 17.95x1.25+2x1.733 = 25.9035 T/m2

Bearing pressure = 29.61 / (1.75 x 1.75) ± 6 x 0.1557 / (1.75 x 1.75^2)


± 6 x 2.7149 / (1.75 x 1.75^2)
= 9.67 ± 0.17 ± 3.04

Bearing pressure at footing P1 = 12.88 Ton./sqm OK < 25.9035 Ton./sqm


four corners P2 = 6.8 Ton./sqm
CLIENT M/S. REFEX ENERGY LIMITED

DOCUMENT NO DATE
PROJECT SOLAR PV POWER PLANT OF 50MW AC
1617101-RFX-NLC-SWYD-F&C-018 06.03.18
DESIGNED CHECKED REV
TITLE FOUNDATION & COLUMN DESIGN FOR CRB
GS KN 0
3.2 DESIGN OF FOOTING -F2 (Load case 112) & (Node No 2)
P3 = 12.54 Ton./sqm
P4 = 6.46 Ton./sqm

Pressure due to over burden soil and raft


( 0.30 + 0.30 )/ 2 x 2.5 +
( 1.70 + 1.70 )/ 2 x 1.733
= 3.6961
Net pmax = 9.1839 T/m2
Net pmin = -2.384 T/m2
0.3

0.3 FGL FGL


1.75

2.00
0.725 0.725

0.30 z

1.75 1.75 x
PLAN SECTION

CHECK FOR FLEXURE ABOUT Z DIRECTION


Net pressure at edge = 9.1839 t/m2

Thickness of footing at column face = 300 mm

Effective depth of footing at z direction, d = 300 - 50 - 6 = 244 mm

Cantilever span of slab from column face = (1.75 - 0.23) / 2 = 0.76 m

Moment (max) at face of column = 9.1839 x 0.76 ^ 2 / 2 = 2.65 tm

Mu/bd2 = (2.65 x 2 x 9.81x10^6) / (1000 x 244 ^2) = 0.87 N/mm2

pt = 0.209 % Ast = 0.209 x1000 x 244 / 100 = 510 mm2


Minimum pt = 0.12 % Ast = 0.12 x 1000 x 300 / 100 = 360 mm2
(Ref .Cl.No.26.5.2.1 in IS 456-2000)
PROVIDE 12 TOR @ 150 c/c at bottom , (Ast) = 754 mm2
SAFE
CHECK FOR FLEXURE ABOUT X DIRECTION
Cantilever span of slab from column face = (1.75 - 0.3) / 2 = 0.725 m

Moment (max) at face of column = 9.1839 x 0.725 ^ 2 / 2 = 2.41 tm


Effective depth of footing at x direction, d = 300 - 50 - 12 - 12/2 = 232 mm
CLIENT M/S. REFEX ENERGY LIMITED

DOCUMENT NO DATE
PROJECT SOLAR PV POWER PLANT OF 50MW AC
1617101-RFX-NLC-SWYD-F&C-018 06.03.18
DESIGNED CHECKED REV
TITLE FOUNDATION & COLUMN DESIGN FOR CRB
GS KN 0
3.2 DESIGN OF FOOTING -F2 (Load case 112) & (Node No 2)
Mu/bd2 = (2.41 x 2x 9.81 x 10^6) / (1000 x 232 ^2) = 0.88 N/mm2

pt = 0.211 % Ast = 0.211 x1000 x 232 / 100 = 490 mm2


Minimum pt = 0.12 % Ast = 0.12 x 1000 x 300 / 100 = 360 mm2
PROVIDE 12 TOR @ 150 c/c at bottom , (Ast = 754 mm2
(Ref .Cl.No.26.5.2.1 in IS 456-2000) SAFE

Provide nominal reinforcement @ top


Minimum pt = 0.06 % = 0.06 x 1000 x 300 / 100 = 180 mm2
PROVIDE 12 TOR @ 150 c/c bothways a, (Ast = 754 mm2
SAFE

CHECK AGAINST ONE WAY SHEAR @ Z DIRECTION


Depth of footing = 300 mm
Effective depth = 300 - 50 - 6 = 244 mm
Shear force at critical section, V = 9.1839 x 1x (0.76 - 0.244) = 4.74 ton
Cantilever length = 0.76 m
Critical section for shear is at a
distance 'd' from the face of the
pedestal = 0.76 - 0.244
= 0.516 m
Effective depth at critical sction d' = 0.244 m
(Ref .Cl.No.40.1 in IS 456-2000)
Nominal shear stress at critical section, tv = = V / (b' x d')
(4.74 x 2 x 9.81 x 10^3) / (1000 x 244) = 0.38 N/mm2

Percentage of reinforcement at critical section = [753.98 / ( 1000 x 244 )] x 100


= 0.310
Corresponding shear stress tc = 0.402 > 0.38 N/mm2
(Ref .Table 19. in IS 456-2000) Hence Safe
CHECK FOR TWO WAY SHEAR AT 'D/2' FROM THE PEDESTAL FACE
Maximum axial load on pedestal = 178.4 KN
Effective depth at critical section = 0.24 m
Area resisted by shear stress = 496784 mm2
Actual punching shear = 0.539
Permissible stress in two way shear = 0.25 × √25 = 1.250 N/mm²
(Ref .Cl.31.6.3. in IS 456-2000) Hence safe in two way shear

Check against one way shear @ X direction


Depth of footing D = 300 mm
Effective depth ( d' ) = 300 - 50 -12-6 = 232 mm

Shear force at critical section, V = 9.1839 x 1x (0.725 - 0.232) = 4.53 ton


CLIENT M/S. REFEX ENERGY LIMITED

DOCUMENT NO DATE
PROJECT SOLAR PV POWER PLANT OF 50MW AC
1617101-RFX-NLC-SWYD-F&C-018 06.03.18
DESIGNED CHECKED REV
TITLE FOUNDATION & COLUMN DESIGN FOR CRB
GS KN 0
3.2 DESIGN OF FOOTING -F2 (Load case 112) & (Node No 2)
Cantilever length = 0.725 m

Critical section for shear is at a distance 'd' from the face of the column = 0.725 - 0.232
= 0.493 m

Effective depth at critical sction d' = 0.232 m


(Ref .Cl.No.40.1 in IS 456-2000)
Nominal shear stress at critical section, tv = V / (b' x d')
(4.53 x 2 x 9.81 x 10^3) / (1000 x 232) = 0.38 N/mm2

Percentage of reinforcement at critical section = = [753.98 / ( 1000 x 232 )] x 100


= 0.320

Corresponding shear stress tc = 0.409 > 0.38 N/mm2


Hence Safe

Design Summary:-
Length of footing = 1750 mm
Breath of footing = 1750 mm
Thickness of footing = 300 mm
Reinforcement
Bottom of Footing:-
In Z-direction = 12 mm diameter @ 150 C/C (Bottom )
In X-direction = 12 mm diameter @ 150 C/C (Bottom )
Top of footing
In Z-direction = 12 mm diameter @ 150 C/C (Top )
In X-direction = 12 mm diameter @ 150 C/C (Top )
CLIENT M/S. REFEX ENERGY LIMITED

DOCUMENT NO DATE
PROJECT SOLAR PV POWER PLANT OF 50MW AC
1617101-RFX-NLC-SWYD-F&C-018 06.03.18
DESIGNED CHECKED REV
TITLE FOUNDATION & COLUMN DESIGN FOR CRB
GS KN 0
3.2 DESIGN OF FOOTING -F2 (Load case 112) & (Node No 2)
#REF! M/S. REFEX ENERGY LIMITED

DOCUMENT NO DATE
PROJECT SOLAR PV POWER PLANT OF 50MW AC
1617101-RFX-NLC-SWYD-F&C-018 06.03.18
DESIGNED CHECKED REV
TITLE FOUNDATION & COLUMN DESIGN FOR CRB
GS KN 0
3.2 DESIGN OF FOOTING -F2 (Load case 112) & (Node No 4)

DESIGN DATA:-
Depth of foundation from FGL = 3.00 m
Footing size = 1.75 m x 1.75 m
X-dir Z-dir
Thickness of footing at edge = 450 mm
Thickness of footing at face of column = 450 mm
Projection around column = ###
mm
Column size = 350 mm x 500 mm
X-dir Z-dir
MATERIAL PROPERTIES:-
Compressive Strength of Concrete = 25 N/mm2
Grade of steel = Fe 500
Density of concrete = 2.5 T/m3
Density of soil = 1.9 T/m3
Co efficient of friction = 0.50

FACTOR OF SAFETY:-
For strength design = 2.00
FX = 3.373 Ton.
FZ = 0.1 Ton
P = 36.8 Ton
Mx = 0.1 Ton.m
Mz = 10.2 Ton.m
FINAL VALUE FOR DESIGN
Vertical load P = 36.8 Ton
Bending Moment Z-direction Mx = 0.1 Ton.m
Bending Moment X-direction Mz = 10.2 Ton.m

CALCULATIONS
Volume of footing = 1.83 m3
Volume of soil = 7.36 m3
a) Wt of footing = 4.575 Ton
b) Wt of soil = 13.98 Ton
Total vertical load = 36.8231 + 4.575 + 13.98
= 55.38 Ton
Net SBC at 3 m depth = 17.50 T/m2
Gross SBC at 2 m depth = = 17.5x1.25+3x1.9 = 27.575 T/m2

Bearing pressure = 55.38 / (1.75 x 1.75) ± 6 x 0.0818 / (1.75 x 1.75^2)


± 6 x 10.2372 / (1.75 x 1.75^2)
= 18.08 ± 0.09 ± 11.46

Bearing pressure at footing P1 = 29.63 Ton./sqm not ok


four corners P2 = 6.71 Ton./sqm
#REF! M/S. REFEX ENERGY LIMITED

DOCUMENT NO DATE
PROJECT SOLAR PV POWER PLANT OF 50MW AC
1617101-RFX-NLC-SWYD-F&C-018 06.03.18
DESIGNED CHECKED REV
TITLE FOUNDATION & COLUMN DESIGN FOR CRB
GS KN 0
3.2 DESIGN OF FOOTING -F2 (Load case 112) & (Node No 4)
P3 = 29.45 Ton./sqm
P4 = 6.53 Ton./sqm
Pressure due to over burden soil and raft
( 0.45 + 0.45 )/ 2 x 2.5 +
( 2.55 + 2.55 )/ 2 x 1.9
= 5.97
Net pmax = 23.66 T/m2
Net pmin = -16.95 T/m2
0.35

0.35 FGL FGL


1.75

3.00
0.7 0.7

0.45 z

1.75 1.75 x
PLAN SECTION

CHECK FOR FLEXURE ABOUT Z DIRECTION


Net pressure at edge = 23.66 t/m2

Thickness of footing at column face = 450 mm

Effective depth of footing at z direction, d = 450 - 50 - 8 = 392 mm

Cantilever span of slab from column face = (1.75 - 0.5) / 2 = 0.625 m

Moment (max) at face of column = 23.66 x 0.625 ^ 2 / 2 = 4.62 tm

Mu/bd2 = (4.62 x 2 x 9.81x10^6) / (1000 x 392 ^2) = 0.59 N/mm2

pt = 0.140 % Ast = 0.14 x1000 x 392 / 100 = 549 mm2


Minimum pt = 0.12 % Ast = 0.12 x 1000 x 450 / 100 = 540 mm2
(Ref .Cl.No.26.5.2.1 in IS 456-2000)
PROVIDE 16 TOR @ 150 c/c at bottom , (Ast) = 1340 mm2
SAFE
CHECK FOR FLEXURE ABOUT X DIRECTION
Cantilever span of slab from column face = (1.75 - 0.35) / 2 = 0.7 m

Moment (max) at face of column = 23.66 x 0.7 ^ 2 / 2 = 5.8 tm


Effective depth of footing at x direction, d = 450 - 50 - 16 - 16/2 = 376 mm
Mu/bd2 = (5.8 x 2x 9.81 x 10^6) / (1000 x 376 ^2) = 0.80 N/mm2
#REF! M/S. REFEX ENERGY LIMITED

DOCUMENT NO DATE
PROJECT SOLAR PV POWER PLANT OF 50MW AC
1617101-RFX-NLC-SWYD-F&C-018 06.03.18
DESIGNED CHECKED REV
TITLE FOUNDATION & COLUMN DESIGN FOR CRB
GS KN 0
3.2 DESIGN OF FOOTING -F2 (Load case 112) & (Node No 4)
pt = 0.191 % Ast = 0.191 x1000 x 376 / 100 = 718 mm2
Minimum pt = 0.12 % Ast = 0.12 x 1000 x 450 / 100 = 540 mm2
PROVIDE 16 TOR @ 150 c/c at bottom , (Ast = 1340 mm2
(Ref .Cl.No.26.5.2.1 in IS 456-2000) SAFE
Provide nominal reinforcement @ top
Minimum pt = 0.06 % = 0.06 x 1000 x 450 / 100 = 270 mm2
PROVIDE 12 TOR @ 150 c/c bothways a, (Ast = 754 mm2
SAFE
CHECK AGAINST ONE WAY SHEAR @ Z DIRECTION
Depth of footing = 450 mm
Effective depth = 450 - 50 - 8 = 392 mm
Shear force at critical section, V = 23.66 x 1x (0.625 - 0.392) = 5.51 ton
Cantilever length = 0.625 m
Critical section for shear is at a
distance 'd' from the face of the
pedestal = 0.625 - 0.392
= 0.233 m
Effective depth at critical sction d' = 0.392 m
(Ref .Cl.No.40.1 in IS 456-2000)
Nominal shear stress at critical section, tv = = V / (b' x d')
(5.51 x 2 x 9.81 x 10^3) / (1000 x 392) = 0.28 N/mm2

Percentage of reinforcement at critical section = [1340.41 / ( 1000 x 392 )] x 100


= 0.340
Corresponding shear stress tc = 0.423 > 0.28 N/mm2
(Ref .Table 19. in IS 456-2000) Hence Safe
CHECK FOR TWO WAY SHEAR AT 'D/2' FROM THE PEDESTAL FACE
Maximum axial load on pedestal = 361.2 KN
Effective depth at critical section = 0.39 m
Area resisted by shear stress = 1281056 mm2
Actual punching shear = 0.423
Permissible stress in two way shear = 0.25 × √25 = 1.250 N/mm²
(Ref .Cl.31.6.3. in IS 456-2000) Hence safe in two way shear
Check against one way shear @ X direction
Depth of footing D = 450 mm
Effective depth ( d' ) = 450 - 50 -16-8 = 376 mm

Shear force at critical section, V = 23.66 x 1x (0.7 - 0.376) = 7.67 ton


Cantilever length = 0.7 m

Critical section for shear is at a distance 'd' from the face of the column = 0.7 - 0.376
= 0.324 m
Effective depth at critical sction d' = 0.376 m
(Ref .Cl.No.40.1 in IS 456-2000)
Nominal shear stress at critical section, tv = V / (b' x d')
(7.67 x 2 x 9.81 x 10^3) / (1000 x 376) = 0.40 N/mm2
#REF! M/S. REFEX ENERGY LIMITED

DOCUMENT NO DATE
PROJECT SOLAR PV POWER PLANT OF 50MW AC
1617101-RFX-NLC-SWYD-F&C-018 06.03.18
DESIGNED CHECKED REV
TITLE FOUNDATION & COLUMN DESIGN FOR CRB
GS KN 0
3.2 DESIGN OF FOOTING -F2 (Load case 112) & (Node No 4)

Percentage of reinforcement at critical section = = [1340.41 / ( 1000 x 376 )] x 100


= 0.360

Corresponding shear stress tc = 0.437 > 0.40 N/mm2


Hence Safe

Design Summary:-
Length of footing = 1750 mm
Breath of footing = 1750 mm
Thickness of footing = 450 mm
Reinforcement
Bottom of Footing:-
In Z-direction = 16 mm diameter @ 150 C/C (Bottom )
In X-direction = 16 mm diameter @ 150 C/C (Bottom )
Top of footing
In Z-direction = 12 mm diameter @ 150 C/C (Top )
In X-direction = 12 mm diameter @ 150 C/C (Top )
#REF! M/S. REFEX ENERGY LIMITED

DOCUMENT NO DATE
PROJECT SOLAR PV POWER PLANT OF 50MW AC
1617101-RFX-NLC-SWYD-F&C-018 06.03.18
DESIGNED CHECKED REV
TITLE FOUNDATION & COLUMN DESIGN FOR CRB
GS KN 0
3.2 DESIGN OF FOOTING -F2 (Load case 112) & (Node No 4)
#REF! M/S. REFEX ENERGY LIMITED
DOCUMENT NO DATE
PROJECT SOLAR PV POWER PLANT OF 50MW AC
1617101-RFX-NLC-SWYD-F&C-018 06.03.18
DESIGNED CHECKED REV
TITLE FOUNDATION & COLUMN DESIGN FOR CRB
GS KN 0
3.3 DESIGN OF FOOTING -F3 (Load case 110) & (Node No 5)

DESIGN DATA:-
Depth of foundation from FGL = 3.00 m
Footing size = 1.50 m x 2.50 m
X-dir Z-dir
Thickness of footing at edge = 600 mm
Thickness of footing at face of column = 600 mm
Projection around column = ###
mm
Column size = 350 mm x 500 mm
X-dir Z-dir
MATERIAL PROPERTIES:-
Compressive Strength of Concrete = 25 N/mm2
Grade of steel = Fe 500
Density of concrete = 2.5 T/m3
Density of soil = 1.9 T/m3
Co efficient of friction = 0.50

FACTOR OF SAFETY:-
For strength design = 2.00
FX = 2.139 Ton.
FZ = 0.0 Ton
P = 50.7 Ton
Mx = 0.6 Ton.m
Mz = 5.6 Ton.m
FINAL VALUE FOR DESIGN
Vertical load P = 50.7 Ton
Bending Moment Z-direction Mx = 0.6 Ton.m
Bending Moment X-direction Mz = 5.6 Ton.m

CALCULATIONS
Volume of footing = 2.67 m3
Volume of soil = 8.58 m3
a) Wt of footing = 6.675 Ton
b) Wt of soil = 16.3 Ton
Total vertical load = 50.7432 + 6.675 + 16.3
= 73.72 Ton
Net SBC at 3 m depth = 17.50 T/m2
Gross SBC at 2 m depth = = 17.5x1.25+3x1.9 = 27.575 T/m2

Bearing pressure = 73.72 / (1.5 x 2.5) ± 6 x 0.5726 / (1.5 x 2.5^2)


± 6 x 5.58 / (2.5 x 1.5^2)
= 19.66 ± 0.37 ± 5.95

Bearing pressure at footing P1 = 25.98 Ton./sqm OK < 27.575 Ton./sqm


four corners P2 = 14.08 Ton./sqm
P3 = 25.24 Ton./sqm
#REF! M/S. REFEX ENERGY LIMITED
DOCUMENT NO DATE
PROJECT SOLAR PV POWER PLANT OF 50MW AC
1617101-RFX-NLC-SWYD-F&C-018 06.03.18
DESIGNED CHECKED REV
TITLE FOUNDATION & COLUMN DESIGN FOR CRB
GS KN 0
3.3 DESIGN OF FOOTING -F3 (Load case 110) & (Node No 5)
P4 = 13.34 Ton./sqm

Pressure due to over burden soil and raft


( 0.60 + 0.60 )/ 2 x 2.5 +
( 2.40 + 2.40 )/ 2 x 1.9
= 6.06
Net pmax = 19.92 T/m2
Net pmin = -5.84 T/m2
0.35

0.35 FGL FGL


2.50

3.00
0.575 0.575

0.60 z

1.50 1.50 x
PLAN SECTION

CHECK FOR FLEXURE ABOUT Z DIRECTION


Net pressure at edge = 19.92 t/m2

Thickness of footing at column face = 600 mm

Effective depth of footing at z direction, d = 600 - 50 - 8 = 542 mm

Cantilever span of slab from column face = (2.5 - 0.5) / 2 = 1m

Moment (max) at face of column = 19.92 x 1 ^ 2 / 2 = 9.96 tm

Mu/bd2 = (9.96 x 2 x 9.81x10^6) / (1000 x 542 ^2) = 0.67 N/mm2

pt = 0.159 % Ast = 0.159 x1000 x 542 / 100 = 862 mm2


Minimum pt = 0.12 % Ast = 0.12 x 1000 x 600 / 100 = 720 mm2
(Ref .Cl.No.26.5.2.1 in IS 456-2000)
PROVIDE 16 TOR @ 150 c/c at bottom , (Ast) = 1340 mm2
SAFE
CHECK FOR FLEXURE ABOUT X DIRECTION
Cantilever span of slab from column face = (1.5 - 0.35) / 2 = 0.575 m

Moment (max) at face of column = 19.92 x 0.575 ^ 2 / 2 = 3.29 tm


Effective depth of footing at x direction, d = 600 - 50 - 16 - 16/2 = 526 mm
Mu/bd2 = (3.29 x 2x 9.81 x 10^6) / (1000 x 526 ^2) = 0.23 N/mm2
#REF! M/S. REFEX ENERGY LIMITED
DOCUMENT NO DATE
PROJECT SOLAR PV POWER PLANT OF 50MW AC
1617101-RFX-NLC-SWYD-F&C-018 06.03.18
DESIGNED CHECKED REV
TITLE FOUNDATION & COLUMN DESIGN FOR CRB
GS KN 0
3.3 DESIGN OF FOOTING -F3 (Load case 110) & (Node No 5)
pt = 0.053 % Ast = 0.053 x1000 x 526 / 100 = 279 mm2
Minimum pt = 0.12 % Ast = 0.12 x 1000 x 600 / 100 = 720 mm2
PROVIDE 16 TOR @ 150 c/c at bottom , (Ast = 1340 mm2
(Ref .Cl.No.26.5.2.1 in IS 456-2000) SAFE

Provide nominal reinforcement @ top


Minimum pt = 0.06 % = 0.06 x 1000 x 600 / 100 = 360 mm2
PROVIDE 12 TOR @ 150 c/c bothways a, (Ast = 754 mm2
SAFE
CHECK AGAINST ONE WAY SHEAR @ Z DIRECTION
Depth of footing = 600 mm
Effective depth = 600 - 50 - 8 = 542 mm
Shear force at critical section, V = 19.92 x 1x (1 - 0.542) = 9.12 ton
Cantilever length = 1m
Critical section for shear is at a
distance 'd' from the face of the
pedestal = 1 - 0.542
= 0.458 m
Effective depth at critical sction d' = 0.542 m
(Ref .Cl.No.40.1 in IS 456-2000)
Nominal shear stress at critical section, tv = = V / (b' x d')
(9.12 x 2 x 9.81 x 10^3) / (1000 x 542) = 0.33 N/mm2

Percentage of reinforcement at critical section = [1340.41 / ( 1000 x 542 )] x 100


= 0.250
Corresponding shear stress tc = 0.360 > 0.33 N/mm2
(Ref .Table 19. in IS 456-2000) Hence Safe
CHECK FOR TWO WAY SHEAR AT 'D/2' FROM THE PEDESTAL FACE
Maximum axial load on pedestal = 497.8 KN
Effective depth at critical section = 0.54 m
Area resisted by shear stress = 2096456 mm2
Actual punching shear = 0.356
Permissible stress in two way shear = 0.25 × √25 = 1.250 N/mm²
(Ref .Cl.31.6.3. in IS 456-2000) Hence safe in two way shear

Check against one way shear @ X direction


Depth of footing D = 600 mm
Effective depth ( d' ) = 600 - 50 -16-8 = 526 mm

Shear force at critical section, V = 19.92 x 1x (0.575 - 0.526) = 0.98 ton


Cantilever length = 0.575 m

Critical section for shear is at a distance 'd' from the face of the column = 0.575 - 0.526
= 0.049 m
Effective depth at critical sction d' = 0.526 m
(Ref .Cl.No.40.1 in IS 456-2000)
#REF! M/S. REFEX ENERGY LIMITED
DOCUMENT NO DATE
PROJECT SOLAR PV POWER PLANT OF 50MW AC
1617101-RFX-NLC-SWYD-F&C-018 06.03.18
DESIGNED CHECKED REV
TITLE FOUNDATION & COLUMN DESIGN FOR CRB
GS KN 0
3.3 DESIGN OF FOOTING -F3 (Load case 110) & (Node No 5)
Nominal shear stress at critical section, tv = V / (b' x d')
(0.98 x 2 x 9.81 x 10^3) / (1000 x 526) = 0.04 N/mm2

Percentage of reinforcement at critical section = = [1340.41 / ( 1000 x 526 )] x 100


= 0.250

Corresponding shear stress tc = 0.360 > 0.04 N/mm2


Hence Safe

Design Summary:-
Length of footing = 1500 mm
Breath of footing = 2500 mm
Thickness of footing = 600 mm
Reinforcement
Bottom of Footing:-
In Z-direction = 16 mm diameter @ 150 C/C (Bottom )
In X-direction = 16 mm diameter @ 150 C/C (Bottom )
Top of footing
In Z-direction = 12 mm diameter @ 150 C/C (Top )
In X-direction = 12 mm diameter @ 150 C/C (Top )
#REF! M/S. REFEX ENERGY LIMITED
DOCUMENT NO DATE
PROJECT SOLAR PV POWER PLANT OF 50MW AC
1617101-RFX-NLC-SWYD-F&C-018 06.03.18
DESIGNED CHECKED REV
TITLE FOUNDATION & COLUMN DESIGN FOR CRB
GS KN 0
3.3 DESIGN OF FOOTING -F3 (Load case 110) & (Node No 5)
#REF! M/S. REFEX ENERGY LIMITED
DOCUMENT NO DATE
PROJECT SOLAR PV POWER PLANT OF 50MW AC
1617101-RFX-NLC-SWYD-F&C-018 06.03.18
DESIGNED CHECKED REV
TITLE FOUNDATION & COLUMN DESIGN FOR CRB
GS KN 0
3.4 DESIGN OF FOOTING -F4 (Load case 112) & (Node No 6)

DESIGN DATA:-
Depth of foundation from FGL = 3.00 m
Footing size = 2.00 m x 2.00 m
X-dir Z-dir
Thickness of footing at edge = 450 mm
Thickness of footing at face of column = 450 mm
Projection around column = ###
mm
Column size = 300 mm x 450 mm
X-dir Z-dir
MATERIAL PROPERTIES:-
Compressive Strength of Concrete = 25 N/mm2
Grade of steel = Fe 500
Density of concrete = 2.5 T/m3
Density of soil = 1.9 T/m3
Co efficient of friction = 0.50

FACTOR OF SAFETY:-
For strength design = 2.00
FX = 1.430 Ton.
FZ = 0.2 Ton
P = 55.0 Ton
Mx = 0.1 Ton.m
Mz = 3.6 Ton.m
FINAL VALUE FOR DESIGN
Vertical load P = 55.0 Ton
Bending Moment Z-direction Mx = 0.1 Ton.m
Bending Moment X-direction Mz = 3.6 Ton.m

CALCULATIONS
Volume of footing = 2.15 m3
Volume of soil = 9.85 m3
a) Wt of footing = 5.375 Ton
b) Wt of soil = 18.72 Ton
Total vertical load = 54.9676 + 5.375 + 18.72
= 79.06 Ton
Net SBC at 3 m depth = 17.50 T/m2
Gross SBC at 2 m depth = = 17.5x1.25+3x1.9 = 27.575 T/m2

Bearing pressure = 79.06 / (2 x 2) ± 6 x 0.0817 / (2 x 2^2)


± 6 x 3.6392 / (2 x 2^2)
= 19.77 ± 0.06 ± 2.73

Bearing pressure at footing P1 = 22.56 Ton./sqm OK < 27.575 Ton./sqm


four corners P2 = 17.1 Ton./sqm
P3 = 22.44 Ton./sqm
#REF! M/S. REFEX ENERGY LIMITED
DOCUMENT NO DATE
PROJECT SOLAR PV POWER PLANT OF 50MW AC
1617101-RFX-NLC-SWYD-F&C-018 06.03.18
DESIGNED CHECKED REV
TITLE FOUNDATION & COLUMN DESIGN FOR CRB
GS KN 0
3.4 DESIGN OF FOOTING -F4 (Load case 112) & (Node No 6)
P4 = 16.98 Ton./sqm

Pressure due to over burden soil and raft


( 0.45 + 0.45 )/ 2 x 2.5 +
( 2.55 + 2.55 )/ 2 x 1.9
= 5.97
Net pmax = 16.59 T/m2
Net pmin = 0.51 T/m2
0.3

0.3 FGL FGL


2.00

3.00
0.85 0.85

0.45 z

2.00 2.00 x
PLAN SECTION

CHECK FOR FLEXURE ABOUT Z DIRECTION


Net pressure at edge = 16.59 t/m2

Thickness of footing at column face = 450 mm

Effective depth of footing at z direction, d = 450 - 50 - 8 = 392 mm

Cantilever span of slab from column face = (2 - 0.45) / 2 = 0.775 m

Moment (max) at face of column = 16.59 x 0.775 ^ 2 / 2 = 4.98 tm

Mu/bd2 = (4.98 x 2 x 9.81x10^6) / (1000 x 392 ^2) = 0.64 N/mm2

pt = 0.152 % Ast = 0.152 x1000 x 392 / 100 = 596 mm2


Minimum pt = 0.12 % Ast = 0.12 x 1000 x 450 / 100 = 540 mm2
(Ref .Cl.No.26.5.2.1 in IS 456-2000)
PROVIDE 16 TOR @ 150 c/c at bottom , (Ast) = 1340 mm2
SAFE
CHECK FOR FLEXURE ABOUT X DIRECTION
Cantilever span of slab from column face = (2 - 0.3) / 2 = 0.85 m

Moment (max) at face of column = 16.59 x 0.85 ^ 2 / 2 = 5.99 tm


Effective depth of footing at x direction, d = 450 - 50 - 16 - 16/2 = 376 mm
Mu/bd2 = (5.99 x 2x 9.81 x 10^6) / (1000 x 376 ^2) = 0.83 N/mm2
#REF! M/S. REFEX ENERGY LIMITED
DOCUMENT NO DATE
PROJECT SOLAR PV POWER PLANT OF 50MW AC
1617101-RFX-NLC-SWYD-F&C-018 06.03.18
DESIGNED CHECKED REV
TITLE FOUNDATION & COLUMN DESIGN FOR CRB
GS KN 0
3.4 DESIGN OF FOOTING -F4 (Load case 112) & (Node No 6)
pt = 0.199 % Ast = 0.199 x1000 x 376 / 100 = 748 mm2
Minimum pt = 0.12 % Ast = 0.12 x 1000 x 450 / 100 = 540 mm2

PROVIDE 16 TOR @ 150 c/c at bottom , (Ast = 1340 mm2


(Ref .Cl.No.26.5.2.1 in IS 456-2000) . SAFE

Provide nominal reinforcement @ top


Minimum pt = 0.06 % = 0.06 x 1000 x 450 / 100 = 270 mm2
PROVIDE 12 TOR @ 150 c/c bothways a, (Ast = 754 mm2
SAFE
CHECK AGAINST ONE WAY SHEAR @ Z DIRECTION
Depth of footing = 450 mm
Effective depth = 450 - 50 - 8 = 392 mm
Shear force at critical section, V = 16.59 x 1x (0.775 - 0.392) = 6.35 ton
Cantilever length = 0.775 m
Critical section for shear is at a
distance 'd' from the face of the
pedestal = 0.775 - 0.392
= 0.383 m
Effective depth at critical sction d' = 0.392 m
(Ref .Cl.No.40.1 in IS 456-2000)
Nominal shear stress at critical section, tv = = V / (b' x d')
(6.35 x 2 x 9.81 x 10^3) / (1000 x 392) = 0.32 N/mm2

Percentage of reinforcement at critical section = [1340.41 / ( 1000 x 392 )] x 100


= 0.340
Corresponding shear stress tc = 0.423 > 0.32 N/mm2
(Ref .Table 19. in IS 456-2000) Hence Safe
CHECK FOR TWO WAY SHEAR AT 'D/2' FROM THE PEDESTAL FACE
Maximum axial load on pedestal = 539.2 KN
Effective depth at critical section = 0.39 m
Area resisted by shear stress = 1202656 mm2
Actual punching shear = 0.673
Permissible stress in two way shear = 0.25 × √25 = 1.250 N/mm²
(Ref .Cl.31.6.3. in IS 456-2000) Hence safe in two way shear

Check against one way shear @ X direction


Depth of footing D = 450 mm
Effective depth ( d' ) = 450 - 50 -16-8 = 376 mm

Shear force at critical section, V = 16.59 x 1x (0.85 - 0.376) = 7.86 ton


Cantilever length = 0.85 m

Critical section for shear is at a distance 'd' from the face of the column = 0.85 - 0.376
= 0.474 m
Effective depth at critical sction d' = 0.376 m
(Ref .Cl.No.40.1 in IS 456-2000)
#REF! M/S. REFEX ENERGY LIMITED
DOCUMENT NO DATE
PROJECT SOLAR PV POWER PLANT OF 50MW AC
1617101-RFX-NLC-SWYD-F&C-018 06.03.18
DESIGNED CHECKED REV
TITLE FOUNDATION & COLUMN DESIGN FOR CRB
GS KN 0
3.4 DESIGN OF FOOTING -F4 (Load case 112) & (Node No 6)
Nominal shear stress at critical section, tv = V / (b' x d')
(7.86 x 2 x 9.81 x 10^3) / (1000 x 376) = 0.41 N/mm2

Percentage of reinforcement at critical section = = [1340.41 / ( 1000 x 376 )] x 100


= 0.360

Corresponding shear stress tc = 0.437 > 0.41 N/mm2


Hence Safe

Design Summary:-
Length of footing = 2000 mm
Breath of footing = 2000 mm
Thickness of footing = 450 mm
Reinforcement
Bottom of Footing:-
In Z-direction = 16 mm diameter @ 150 C/C (Bottom )
In X-direction = 16 mm diameter @ 150 C/C (Bottom )
Top of footing
In Z-direction = 12 mm diameter @ 150 C/C (Top )
In X-direction = 12 mm diameter @ 150 C/C (Top )
#REF! M/S. REFEX ENERGY LIMITED
DOCUMENT NO DATE
PROJECT SOLAR PV POWER PLANT OF 50MW AC
1617101-RFX-NLC-SWYD-F&C-018 06.03.18
DESIGNED CHECKED REV
TITLE FOUNDATION & COLUMN DESIGN FOR CRB
GS KN 0
3.4 DESIGN OF FOOTING -F4 (Load case 112) & (Node No 6)
#REF! M/S. REFEX ENERGY LIMITED
DOCUMENT NO DATE
PROJECT SOLAR PV POWER PLANT OF 50MW AC
1617101-RFX-NLC-SWYD-F&C-018 06.03.18
DESIGNED CHECKED REV
TITLE FOUNDATION & COLUMN DESIGN FOR CRB
GS KN 0
3.5 DESIGN OF FOOTING -F5 (Load case 122) & (Node No 7)

DESIGN DATA:-
Depth of foundation from FGL = 3.00 m
Footing size = 2.00 m x 2.00 m
X-dir Z-dir
Thickness of footing at edge = 500 mm
Thickness of footing at face of column = 500 mm
Projection around column = ###
mm
Column size = 300 mm x 450 mm
X-dir Z-dir
MATERIAL PROPERTIES:-
Compressive Strength of Concrete = 25 N/mm2
Grade of steel = Fe 500
Density of concrete = 2.5 T/m3
Density of soil = 1.9 T/m3
Co efficient of friction = 0.50

FACTOR OF SAFETY:-
For strength design = 2.00
FX = 2.379 Ton.
FZ = 0.0 Ton
P = 27.6 Ton
Mx = 0.1 Ton.m
Mz = 6.3 Ton.m
FINAL VALUE FOR DESIGN
Vertical load P = 27.6 Ton
Bending Moment Z-direction Mx = 0.1 Ton.m
Bending Moment X-direction Mz = 6.3 Ton.m

CALCULATIONS
Volume of footing = 2.34 m3
Volume of soil = 9.66 m3
a) Wt of footing = 5.85 Ton
b) Wt of soil = 18.35 Ton
Total vertical load = 27.6472 + 5.85 + 18.35
= 51.85 Ton
Net SBC at 3 m depth = 17.50 T/m2
Gross SBC at 2 m depth = = 17.5x1.25+3x1.9 = 27.575 T/m2

Bearing pressure = 51.85 / (2 x 2) ± 6 x 0.0696 / (2 x 2^2)


± 6 x 6.2873 / (2 x 2^2)
= 12.96 ± 0.05 ± 4.72

Bearing pressure at footing P1 = 17.73 Ton./sqm OK < 27.575 Ton./sqm


four corners P2 = 8.29 Ton./sqm
P3 = 17.63 Ton./sqm
#REF! M/S. REFEX ENERGY LIMITED
DOCUMENT NO DATE
PROJECT SOLAR PV POWER PLANT OF 50MW AC
1617101-RFX-NLC-SWYD-F&C-018 06.03.18
DESIGNED CHECKED REV
TITLE FOUNDATION & COLUMN DESIGN FOR CRB
GS KN 0
3.5 DESIGN OF FOOTING -F5 (Load case 122) & (Node No 7)
P4 = 8.19 Ton./sqm

Pressure due to over burden soil and raft


( 0.50 + 0.50 )/ 2 x 2.5 +
( 2.50 + 2.50 )/ 2 x 1.9
= 6
Net pmax = 11.73 T/m2
Net pmin = -3.44 T/m2
0.3

0.3 FGL FGL


2.00

3.00
0.85 0.85

0.50 z

2.00 2.00 x
PLAN SECTION

CHECK FOR FLEXURE ABOUT Z DIRECTION


Net pressure at edge = 11.73 t/m2

Thickness of footing at column face = 500 mm

Effective depth of footing at z direction, d = 500 - 50 - 6 = 444 mm

Cantilever span of slab from column face = (2 - 0.45) / 2 = 0.775 m

Moment (max) at face of column = 11.73 x 0.775 ^ 2 / 2 = 3.52 tm

Mu/bd2 = (3.52 x 2 x 9.81x10^6) / (1000 x 444 ^2) = 0.35 N/mm2

pt = 0.082 % Ast = 0.082 x1000 x 444 / 100 = 364 mm2


Minimum pt = 0.12 % Ast = 0.12 x 1000 x 500 / 100 = 600 mm2
(Ref .Cl.No.26.5.2.1 in IS 456-2000)
PROVIDE 12 TOR @ 150 c/c at bottom , (Ast) = 754 mm2
SAFE
CHECK FOR FLEXURE ABOUT X DIRECTION
Cantilever span of slab from column face = (2 - 0.3) / 2 = 0.85 m

Moment (max) at face of column = 11.73 x 0.85 ^ 2 / 2 = 4.24 tm


Effective depth of footing at x direction, d = 500 - 50 - 12 - 12/2 = 432 mm
Mu/bd2 = (4.24 x 2x 9.81 x 10^6) / (1000 x 432 ^2) = 0.45 N/mm2
#REF! M/S. REFEX ENERGY LIMITED
DOCUMENT NO DATE
PROJECT SOLAR PV POWER PLANT OF 50MW AC
1617101-RFX-NLC-SWYD-F&C-018 06.03.18
DESIGNED CHECKED REV
TITLE FOUNDATION & COLUMN DESIGN FOR CRB
GS KN 0
3.5 DESIGN OF FOOTING -F5 (Load case 122) & (Node No 7)
pt = 0.106 % Ast = 0.106 x1000 x 432 / 100 = 458 mm2
Minimum pt = 0.12 % Ast = 0.12 x 1000 x 500 / 100 = 600 mm2
PROVIDE 12 TOR @ 150 c/c at bottom , (Ast = 754 mm2
(Ref .Cl.No.26.5.2.1 in IS 456-2000) SAFE

Provide nominal reinforcement @ top


Minimum pt = 0.06 % = 0.06 x 1000 x 500 / 100 = 300 mm2
PROVIDE 12 TOR @ 150 c/c bothways a, (Ast = 754 mm2
SAFE
CHECK AGAINST ONE WAY SHEAR @ Z DIRECTION
Depth of footing = 500 mm
Effective depth = 500 - 50 - 6 = 444 mm
Shear force at critical section, V = 11.73 x 1x (0.775 - 0.444) = 3.88 ton
Cantilever length = 0.775 m
Critical section for shear is at a
distance 'd' from the face of the
pedestal = 0.775 - 0.444
= 0.331 m
Effective depth at critical sction d' = 0.444 m
(Ref .Cl.No.40.1 in IS 456-2000)
Nominal shear stress at critical section, tv = = V / (b' x d')
(3.88 x 2 x 9.81 x 10^3) / (1000 x 444) = 0.17 N/mm2

Percentage of reinforcement at critical section = [753.98 / ( 1000 x 444 )] x 100


= 0.170
Corresponding shear stress tc = 0.304 > 0.17 N/mm2
(Ref .Table 19. in IS 456-2000) Hence Safe
CHECK FOR TWO WAY SHEAR AT 'D/2' FROM THE PEDESTAL FACE
Maximum axial load on pedestal = 271.2 KN
Effective depth at critical section = 0.44 m
Area resisted by shear stress = 1454544 mm2
Actual punching shear = 0.28
Permissible stress in two way shear = 0.25 × √25 = 1.250 N/mm²
(Ref .Cl.31.6.3. in IS 456-2000) Hence safe in two way shear

Check against one way shear @ X direction


Depth of footing D = 500 mm
Effective depth ( d' ) = 500 - 50 -12-6 = 432 mm

Shear force at critical section, V = 11.73 x 1x (0.85 - 0.432) = 4.9 ton


Cantilever length = 0.85 m

Critical section for shear is at a distance 'd' from the face of the column = 0.85 - 0.432
= 0.418 m
Effective depth at critical sction d' = 0.432 m
(Ref .Cl.No.40.1 in IS 456-2000)
#REF! M/S. REFEX ENERGY LIMITED
DOCUMENT NO DATE
PROJECT SOLAR PV POWER PLANT OF 50MW AC
1617101-RFX-NLC-SWYD-F&C-018 06.03.18
DESIGNED CHECKED REV
TITLE FOUNDATION & COLUMN DESIGN FOR CRB
GS KN 0
3.5 DESIGN OF FOOTING -F5 (Load case 122) & (Node No 7)
Nominal shear stress at critical section, tv = V / (b' x d')
(4.9 x 2 x 9.81 x 10^3) / (1000 x 432) = 0.22 N/mm2

Percentage of reinforcement at critical section = = [753.98 / ( 1000 x 432 )] x 100


= 0.170

Corresponding shear stress tc = 0.304 > 0.22 N/mm2


Hence Safe

Design Summary:-
Length of footing = 2000 mm
Breath of footing = 2000 mm
Thickness of footing = 500 mm
Reinforcement
Bottom of Footing:-
In Z-direction = 12 mm diameter @ 150 C/C (Bottom )
In X-direction = 12 mm diameter @ 150 C/C (Bottom )
Top of footing
In Z-direction = 12 mm diameter @ 150 C/C (Top )
In X-direction = 12 mm diameter @ 150 C/C (Top )
#REF! M/S. REFEX ENERGY LIMITED
DOCUMENT NO DATE
PROJECT SOLAR PV POWER PLANT OF 50MW AC
1617101-RFX-NLC-SWYD-F&C-018 06.03.18
DESIGNED CHECKED REV
TITLE FOUNDATION & COLUMN DESIGN FOR CRB
GS KN 0
3.5 DESIGN OF FOOTING -F5 (Load case 122) & (Node No 7)
#REF! M/S. REFEX ENERGY LIMITED
DOCUMENT NO DATE
PROJECT SOLAR PV POWER PLANT OF 50MW AC
1617101-RFX-NLC-SWYD-F&C-018 06.03.18
DESIGNED CHECKED REV
TITLE FOUNDATION & COLUMN DESIGN FOR CRB
GS KN 0
3.5 DESIGN OF FOOTING -F5 (Load case 110) & (Node No 26)

DESIGN DATA:-
Depth of foundation from FGL = 3.00 m
Footing size = 2.00 m x 2.00 m
X-dir Z-dir
Thickness of footing at edge = 500 mm
Thickness of footing at face of column = 500 mm
Projection around column = ###
mm
Column size = 300 mm x 450 mm
X-dir Z-dir
MATERIAL PROPERTIES:-
Compressive Strength of Concrete = 25 N/mm2
Grade of steel = Fe 500
Density of concrete = 2.5 T/m3
Density of soil = 1.9 T/m3
Co efficient of friction = 0.50

FACTOR OF SAFETY:-
For strength design = 2.00
FX = 3.263 Ton.
FZ = 0.2 Ton
P = 32.0 Ton
Mx = 0.2 Ton.m
Mz = 8.3 Ton.m
FINAL VALUE FOR DESIGN
Vertical load P = 32.0 Ton
Bending Moment Z-direction Mx = 0.2 Ton.m
Bending Moment X-direction Mz = 8.3 Ton.m

CALCULATIONS
Volume of footing = 2.34 m3
Volume of soil = 9.66 m3
a) Wt of footing = 5.85 Ton
b) Wt of soil = 18.35 Ton
Total vertical load = 31.966 + 5.85 + 18.35
= 56.17 Ton
Net SBC at 3 m depth = 17.50 T/m2
Gross SBC at 2 m depth = = 17.5x1.25+3x1.9 = 27.575 T/m2

Bearing pressure = 56.17 / (2 x 2) ± 6 x 0.2114 / (2 x 2^2)


± 6 x 8.2878 / (2 x 2^2)
= 14.04 ± 0.16 ± 6.22

Bearing pressure at footing P1 = 20.42 Ton./sqm OK < 27.575 Ton./sqm


four corners P2 = 7.98 Ton./sqm
P3 = 20.1 Ton./sqm
#REF! M/S. REFEX ENERGY LIMITED
DOCUMENT NO DATE
PROJECT SOLAR PV POWER PLANT OF 50MW AC
1617101-RFX-NLC-SWYD-F&C-018 06.03.18
DESIGNED CHECKED REV
TITLE FOUNDATION & COLUMN DESIGN FOR CRB
GS KN 0
3.5 DESIGN OF FOOTING -F5 (Load case 110) & (Node No 26)
P4 = 7.66 Ton./sqm

Pressure due to over burden soil and raft


( 0.50 + 0.50 )/ 2 x 2.5 +
( 2.50 + 2.50 )/ 2 x 1.9
= 6
Net pmax = 14.42 T/m2
Net pmin = -6.44 T/m2
0.3

0.3 FGL FGL


2.00

3.00
0.85 0.85

0.50 z

2.00 2.00 x
PLAN SECTION

CHECK FOR FLEXURE ABOUT Z DIRECTION


Net pressure at edge = 14.42 t/m2

Thickness of footing at column face = 500 mm

Effective depth of footing at z direction, d = 500 - 50 - 6 = 444 mm

Cantilever span of slab from column face = (2 - 0.45) / 2 = 0.775 m

Moment (max) at face of column = 14.42 x 0.775 ^ 2 / 2 = 4.33 tm

Mu/bd2 = (4.33 x 2 x 9.81x10^6) / (1000 x 444 ^2) = 0.43 N/mm2

pt = 0.101 % Ast = 0.101 x1000 x 444 / 100 = 448 mm2


Minimum pt = 0.12 % Ast = 0.12 x 1000 x 500 / 100 = 600 mm2
(Ref .Cl.No.26.5.2.1 in IS 456-2000)
PROVIDE 12 TOR @ 150 c/c at bottom , (Ast) = 754 mm2
SAFE
CHECK FOR FLEXURE ABOUT X DIRECTION
Cantilever span of slab from column face = (2 - 0.3) / 2 = 0.85 m

Moment (max) at face of column = 14.42 x 0.85 ^ 2 / 2 = 5.21 tm


Effective depth of footing at x direction, d = 500 - 50 - 12 - 12/2 = 432 mm
Mu/bd2 = (5.21 x 2x 9.81 x 10^6) / (1000 x 432 ^2) = 0.55 N/mm2
#REF! M/S. REFEX ENERGY LIMITED
DOCUMENT NO DATE
PROJECT SOLAR PV POWER PLANT OF 50MW AC
1617101-RFX-NLC-SWYD-F&C-018 06.03.18
DESIGNED CHECKED REV
TITLE FOUNDATION & COLUMN DESIGN FOR CRB
GS KN 0
3.5 DESIGN OF FOOTING -F5 (Load case 110) & (Node No 26)
pt = 0.130 % Ast = 0.13 x1000 x 432 / 100 = 562 mm2
Minimum pt = 0.12 % Ast = 0.12 x 1000 x 500 / 100 = 600 mm2
PROVIDE 12 TOR @ 150 c/c at bottom , (Ast = 754 mm2
(Ref .Cl.No.26.5.2.1 in IS 456-2000) SAFE

Provide nominal reinforcement @ top


Minimum pt = 0.06 % = 0.06 x 1000 x 500 / 100 = 300 mm2
PROVIDE 12 TOR @ 150 c/c bothways a, (Ast = 754 mm2
SAFE
CHECK AGAINST ONE WAY SHEAR @ Z DIRECTION
Depth of footing = 500 mm
Effective depth = 500 - 50 - 6 = 444 mm
Shear force at critical section, V = 14.42 x 1x (0.775 - 0.444) = 4.77 ton
Cantilever length = 0.775 m
Critical section for shear is at a
distance 'd' from the face of the
pedestal = 0.775 - 0.444
= 0.331 m
Effective depth at critical sction d' = 0.444 m
(Ref .Cl.No.40.1 in IS 456-2000)
Nominal shear stress at critical section, tv = = V / (b' x d')
(4.77 x 2 x 9.81 x 10^3) / (1000 x 444) = 0.21 N/mm2

Percentage of reinforcement at critical section = [753.98 / ( 1000 x 444 )] x 100


= 0.170
Corresponding shear stress tc = 0.304 > 0.21 N/mm2
(Ref .Table 19. in IS 456-2000) Hence Safe
CHECK FOR TWO WAY SHEAR AT 'D/2' FROM THE PEDESTAL FACE
Maximum axial load on pedestal = 313.6 KN
Effective depth at critical section = 0.44 m
Area resisted by shear stress = 1454544 mm2
Actual punching shear = 0.323
Permissible stress in two way shear = 0.25 × √25 = 1.250 N/mm²
(Ref .Cl.31.6.3. in IS 456-2000) Hence safe in two way shear

Check against one way shear @ X direction


Depth of footing D = 500 mm
Effective depth ( d' ) = 500 - 50 -12-6 = 432 mm

Shear force at critical section, V = 14.42 x 1x (0.85 - 0.432) = 6.03 ton


Cantilever length = 0.85 m

Critical section for shear is at a distance 'd' from the face of the column = 0.85 - 0.432
= 0.418 m
Effective depth at critical sction d' = 0.432 m
(Ref .Cl.No.40.1 in IS 456-2000)
#REF! M/S. REFEX ENERGY LIMITED
DOCUMENT NO DATE
PROJECT SOLAR PV POWER PLANT OF 50MW AC
1617101-RFX-NLC-SWYD-F&C-018 06.03.18
DESIGNED CHECKED REV
TITLE FOUNDATION & COLUMN DESIGN FOR CRB
GS KN 0
3.5 DESIGN OF FOOTING -F5 (Load case 110) & (Node No 26)
Nominal shear stress at critical section, tv = V / (b' x d')
(6.03 x 2 x 9.81 x 10^3) / (1000 x 432) = 0.27 N/mm2

Percentage of reinforcement at critical section = = [753.98 / ( 1000 x 432 )] x 100


= 0.170

Corresponding shear stress tc = 0.304 > 0.27 N/mm2


Hence Safe

Design Summary:-
Length of footing = 2000 mm
Breath of footing = 2000 mm
Thickness of footing = 500 mm
Reinforcement
Bottom of Footing:-
In Z-direction = 12 mm diameter @ 150 C/C (Bottom )
In X-direction = 12 mm diameter @ 150 C/C (Bottom )
Top of footing
In Z-direction = 12 mm diameter @ 150 C/C (Top )
In X-direction = 12 mm diameter @ 150 C/C (Top )
#REF! M/S. REFEX ENERGY LIMITED
DOCUMENT NO DATE
PROJECT SOLAR PV POWER PLANT OF 50MW AC
1617101-RFX-NLC-SWYD-F&C-018 06.03.18
DESIGNED CHECKED REV
TITLE FOUNDATION & COLUMN DESIGN FOR CRB
GS KN 0
3.5 DESIGN OF FOOTING -F5 (Load case 110) & (Node No 26)
#REF! M/S. REFEX ENERGY LIMITED
DOCUMENT NO DATE
PROJECT SOLAR PV POWER PLANT OF 50MW AC
1617101-RFX-NLC-SWYD-F&C-018 06.03.18
DESIGNED CHECKED REV
TITLE FOUNDATION & COLUMN DESIGN FOR CRB
GS KN 0
3.9 DESIGN OF FOOTING -F9 (Load case 23) & (Node No 212)

DESIGN DATA:-
Depth of foundation from FGL = 3.00 m
Footing size = 1.75 m x 2.00 m
X-dir Z-dir
Thickness of footing at edge = 450 mm
Thickness of footing at face of column = 450 mm
Projection around column = ###
mm
Column size = 300 mm x 450 mm
X-dir Z-dir
MATERIAL PROPERTIES:-
Compressive Strength of Concrete = 25 N/mm2
Grade of steel = Fe 500
Density of concrete = 2.5 T/m3
Density of soil = 1.9 T/m3
Co efficient of friction = 0.50

FACTOR OF SAFETY:-
For strength design = 2.00
FX = 3.348 Ton.
FZ = 0.2 Ton
P = 37.4 Ton
Mx = 0.2 Ton.m
Mz = 8.4 Ton.m
FINAL VALUE FOR DESIGN
Vertical load P = 37.4 Ton
Bending Moment Z-direction Mx = 0.2 Ton.m
Bending Moment X-direction Mz = 8.4 Ton.m

CALCULATIONS
Volume of footing = 1.92 m3
Volume of soil = 8.58 m3
a) Wt of footing = 4.8 Ton
b) Wt of soil = 16.3 Ton
Total vertical load = 37.3796 + 4.8 + 16.3
= 58.48 Ton
Net SBC at 3 m depth = 17.50 T/m2
Gross SBC at 2 m depth = = 17.5x1.25+3x1.9 = 27.575 T/m2

Bearing pressure = 58.48 / (1.75 x 2) ± 6 x 0.2375 / (1.75 x 2^2)


± 6 x 8.4096 / (2 x 1.75^2)
= 16.71 ± 0.2 ± 8.24

Bearing pressure at footing P1 = 25.15 Ton./sqm OK < 27.575 Ton./sqm


four corners P2 = 8.67 Ton./sqm
P3 = 24.75 Ton./sqm
#REF! M/S. REFEX ENERGY LIMITED
DOCUMENT NO DATE
PROJECT SOLAR PV POWER PLANT OF 50MW AC
1617101-RFX-NLC-SWYD-F&C-018 06.03.18
DESIGNED CHECKED REV
TITLE FOUNDATION & COLUMN DESIGN FOR CRB
GS KN 0
3.9 DESIGN OF FOOTING -F9 (Load case 23) & (Node No 212)
P4 = 8.27 Ton./sqm

Pressure due to over burden soil and raft


( 0.45 + 0.45 )/ 2 x 2.5 +
( 2.55 + 2.55 )/ 2 x 1.9
= 5.97
Net pmax = 19.18 T/m2
Net pmin = -10.51 T/m2
0.3

0.3 FGL FGL


2.00

3.00
0.725 0.725

0.45 z

1.75 1.75 x
PLAN SECTION

CHECK FOR FLEXURE ABOUT Z DIRECTION


Net pressure at edge = 19.18 t/m2

Thickness of footing at column face = 450 mm

Effective depth of footing at z direction, d = 450 - 50 - 8 = 392 mm

Cantilever span of slab from column face = (2 - 0.45) / 2 = 0.775 m

Moment (max) at face of column = 19.18 x 0.775 ^ 2 / 2 = 5.76 tm

Mu/bd2 = (5.76 x 2 x 9.81x10^6) / (1000 x 392 ^2) = 0.74 N/mm2

pt = 0.176 % Ast = 0.176 x1000 x 392 / 100 = 690 mm2


Minimum pt = 0.12 % Ast = 0.12 x 1000 x 450 / 100 = 540 mm2
(Ref .Cl.No.26.5.2.1 in IS 456-2000)
PROVIDE 16 TOR @ 150 c/c at bottom , (Ast) = 1340 mm2
SAFE
CHECK FOR FLEXURE ABOUT X DIRECTION
Cantilever span of slab from column face = (1.75 - 0.3) / 2 = 0.725 m

Moment (max) at face of column = 19.18 x 0.725 ^ 2 / 2 = 5.04 tm


Effective depth of footing at x direction, d = 450 - 50 - 16 - 16/2 = 376 mm
Mu/bd2 = (5.04 x 2x 9.81 x 10^6) / (1000 x 376 ^2) = 0.70 N/mm2
#REF! M/S. REFEX ENERGY LIMITED
DOCUMENT NO DATE
PROJECT SOLAR PV POWER PLANT OF 50MW AC
1617101-RFX-NLC-SWYD-F&C-018 06.03.18
DESIGNED CHECKED REV
TITLE FOUNDATION & COLUMN DESIGN FOR CRB
GS KN 0
3.9 DESIGN OF FOOTING -F9 (Load case 23) & (Node No 212)
pt = 0.167 % Ast = 0.167 x1000 x 376 / 100 = 628 mm2
Minimum pt = 0.12 % Ast = 0.12 x 1000 x 450 / 100 = 540 mm2
PROVIDE 16 TOR @ 150 c/c at bottom , (Ast = 1340 mm2
(Ref .Cl.No.26.5.2.1 in IS 456-2000) SAFE

Provide nominal reinforcement @ top


Minimum pt = 0.06 % = 0.06 x 1000 x 450 / 100 = 270 mm2
PROVIDE 12 TOR @ 150 c/c bothways a, (Ast = 754 mm2
SAFE
CHECK AGAINST ONE WAY SHEAR @ Z DIRECTION
Depth of footing = 450 mm
Effective depth = 450 - 50 - 8 = 392 mm
Shear force at critical section, V = 19.18 x 1x (0.775 - 0.392) = 7.35 ton
Cantilever length = 0.775 m
Critical section for shear is at a
distance 'd' from the face of the
pedestal = 0.775 - 0.392
= 0.383 m
Effective depth at critical sction d' = 0.392 m
(Ref .Cl.No.40.1 in IS 456-2000)
Nominal shear stress at critical section, tv = = V / (b' x d')
(7.35 x 2 x 9.81 x 10^3) / (1000 x 392) = 0.37 N/mm2

Percentage of reinforcement at critical section = [1340.41 / ( 1000 x 392 )] x 100


= 0.340
Corresponding shear stress tc = 0.423 > 0.37 N/mm2
(Ref .Table 19. in IS 456-2000) Hence Safe
CHECK FOR TWO WAY SHEAR AT 'D/2' FROM THE PEDESTAL FACE
Maximum axial load on pedestal = 366.7 KN
Effective depth at critical section = 0.39 m
Area resisted by shear stress = 1202656 mm2
Actual punching shear = 0.457
Permissible stress in two way shear = 0.25 × √25 = 1.250 N/mm²
(Ref .Cl.31.6.3. in IS 456-2000) Hence safe in two way shear

Check against one way shear @ X direction


Depth of footing D = 450 mm
Effective depth ( d' ) = 450 - 50 -16-8 = 376 mm

Shear force at critical section, V = 19.18 x 1x (0.725 - 0.376) = 6.69 ton


Cantilever length = 0.725 m

Critical section for shear is at a distance 'd' from the face of the column = 0.725 - 0.376
= 0.349 m
Effective depth at critical sction d' = 0.376 m
(Ref .Cl.No.40.1 in IS 456-2000)
#REF! M/S. REFEX ENERGY LIMITED
DOCUMENT NO DATE
PROJECT SOLAR PV POWER PLANT OF 50MW AC
1617101-RFX-NLC-SWYD-F&C-018 06.03.18
DESIGNED CHECKED REV
TITLE FOUNDATION & COLUMN DESIGN FOR CRB
GS KN 0
3.9 DESIGN OF FOOTING -F9 (Load case 23) & (Node No 212)
Nominal shear stress at critical section, tv = V / (b' x d')
(6.69 x 2 x 9.81 x 10^3) / (1000 x 376) = 0.35 N/mm2

Percentage of reinforcement at critical section = = [1340.41 / ( 1000 x 376 )] x 100


= 0.360

Corresponding shear stress tc = 0.437 > 0.35 N/mm2


Hence Safe

Design Summary:-
Length of footing = 1750 mm
Breath of footing = 2000 mm
Thickness of footing = 450 mm
Reinforcement
Bottom of Footing:-
In Z-direction = 16 mm diameter @ 150 C/C (Bottom )
In X-direction = 16 mm diameter @ 150 C/C (Bottom )
Top of footing
In Z-direction = 12 mm diameter @ 150 C/C (Top )
In X-direction = 12 mm diameter @ 150 C/C (Top )
#REF! M/S. REFEX ENERGY LIMITED
DOCUMENT NO DATE
PROJECT SOLAR PV POWER PLANT OF 50MW AC
1617101-RFX-NLC-SWYD-F&C-018 06.03.18
DESIGNED CHECKED REV
TITLE FOUNDATION & COLUMN DESIGN FOR CRB
GS KN 0
3.9 DESIGN OF FOOTING -F9 (Load case 23) & (Node No 212)
#REF! M/S. REFEX ENERGY LIMITED
DOCUMENT NO DATE
PROJECT SOLAR PV POWER PLANT OF 50MW AC
1617101-RFX-NLC-SWYD-F&C-018 06.03.18
DESIGNED CHECKED REV
TITLE FOUNDATION & COLUMN DESIGN FOR CRB
GS KN 0
3.10 DESIGN OF FOOTING -F6 (Load case 110) & (Node No 24)

DESIGN DATA:-
Depth of foundation from FGL = 3.00 m
Footing size = 1.50 m x 2.50 m
X-dir Z-dir
Thickness of footing at edge = 550 mm
Thickness of footing at face of column = 550 mm
Projection around column = ###
mm
Column size = 300 mm x 450 mm
X-dir Z-dir
MATERIAL PROPERTIES:-
Compressive Strength of Concrete = 25 N/mm2
Grade of steel = Fe 500
Density of concrete = 2.5 T/m3
Density of soil = 1.9 T/m3
Co efficient of friction = 0.50

FACTOR OF SAFETY:-
For strength design = 2.00
FX = 1.103 Ton.
FZ = 0.3 Ton
P = 69.7 Ton
Mx = 0.3 Ton.m
Mz = 3.2 Ton.m
FINAL VALUE FOR DESIGN
Vertical load P = 69.7 Ton
Bending Moment Z-direction Mx = 0.3 Ton.m
Bending Moment X-direction Mz = 3.2 Ton.m

CALCULATIONS
Volume of footing = 2.4 m3
Volume of soil = 8.85 m3
a) Wt of footing = 6 Ton
b) Wt of soil = 16.82 Ton
Total vertical load = 69.6606 + 6 + 16.82
= 92.48 Ton
Net SBC at 3 m depth = 17.50 T/m2
Gross SBC at 2 m depth = = 17.5x1.25+3x1.9 = 27.575 T/m2

Bearing pressure = 92.48 / (1.5 x 2.5) ± 6 x 0.3482 / (1.5 x 2.5^2)


± 6 x 3.2391 / (2.5 x 1.5^2)
= 24.66 ± 0.22 ± 3.46

Bearing pressure at footing P1 = 28.34 Ton./sqm not ok


four corners P2 = 21.42 Ton./sqm
P3 = 27.9 Ton./sqm
P4 = 20.98 Ton./sqm
#REF! M/S. REFEX ENERGY LIMITED
DOCUMENT NO DATE
PROJECT SOLAR PV POWER PLANT OF 50MW AC
1617101-RFX-NLC-SWYD-F&C-018 06.03.18
DESIGNED CHECKED REV
TITLE FOUNDATION & COLUMN DESIGN FOR CRB
GS KN 0
3.10 DESIGN OF FOOTING -F6 (Load case 110) & (Node No 24)

Pressure due to over burden soil and raft


( 0.55 + 0.55 )/ 2 x 2.5 +
( 2.45 + 2.45 )/ 2 x 1.9
= 6.03
Net pmax = 22.31 T/m2
Net pmin = -0.89 T/m2
0.3

0.3 FGL FGL


2.50

3.00
0.6 0.6

0.55 z

1.50 1.50 x
PLAN SECTION

CHECK FOR FLEXURE ABOUT Z DIRECTION


Net pressure at edge = 22.31 t/m2

Thickness of footing at column face = 550 mm

Effective depth of footing at z direction, d = 550 - 50 - 8 = 492 mm

Cantilever span of slab from column face = (2.5 - 0.45) / 2 = 1.025 m

Moment (max) at face of column = 22.31 x 1.025 ^ 2 / 2 = 11.72 tm

Mu/bd2 = (11.72 x 2 x 9.81x10^6) / (1000 x 492 ^2) = 0.95 N/mm2

pt = 0.229 % Ast = 0.229 x1000 x 492 / 100 = 1127 mm2


Minimum pt = 0.12 % Ast = 0.12 x 1000 x 550 / 100 = 660 mm2
(Ref .Cl.No.26.5.2.1 in IS 456-2000)
PROVIDE 16 TOR @ 100 c/c at bottom , (Ast) = 2011 mm2
SAFE
CHECK FOR FLEXURE ABOUT X DIRECTION
Cantilever span of slab from column face = (1.5 - 0.3) / 2 = 0.6 m

Moment (max) at face of column = 22.31 x 0.6 ^ 2 / 2 = 4.02 tm


Effective depth of footing at x direction, d = 550 - 50 - 16 - 16/2 = 476 mm
Mu/bd2 = (4.02 x 2x 9.81 x 10^6) / (1000 x 476 ^2) = 0.35 N/mm2
#REF! M/S. REFEX ENERGY LIMITED
DOCUMENT NO DATE
PROJECT SOLAR PV POWER PLANT OF 50MW AC
1617101-RFX-NLC-SWYD-F&C-018 06.03.18
DESIGNED CHECKED REV
TITLE FOUNDATION & COLUMN DESIGN FOR CRB
GS KN 0
3.10 DESIGN OF FOOTING -F6 (Load case 110) & (Node No 24)
pt = 0.082 % Ast = 0.082 x1000 x 476 / 100 = 390 mm2
Minimum pt = 0.12 % Ast = 0.12 x 1000 x 550 / 100 = 660 mm2
PROVIDE 16 TOR @ 100 c/c at bottom , (Ast = 2011 mm2
(Ref .Cl.No.26.5.2.1 in IS 456-2000) SAFE
Provide nominal reinforcement @ top
Minimum pt = 0.06 % = 0.06 x 1000 x 550 / 100 = 330 mm2
PROVIDE 12 TOR @ 150 c/c bothways a, (Ast = 754 mm2
SAFE
CHECK AGAINST ONE WAY SHEAR @ Z DIRECTION
Depth of footing = 550 mm
Effective depth = 550 - 50 - 8 = 492 mm
Shear force at critical section, V = 22.31 x 1x (1.025 - 0.492) = 11.89 ton
Cantilever length = 1.025 m
Critical section for shear is at a
distance 'd' from the face of the
pedestal = 1.025 - 0.492
= 0.533 m
Effective depth at critical sction d' = 0.492 m
(Ref .Cl.No.40.1 in IS 456-2000)
Nominal shear stress at critical section, tv = = V / (b' x d')
(11.89 x 2 x 9.81 x 10^3) / (1000 x 492) = 0.47 N/mm2

Percentage of reinforcement at critical section = [2010.62 / ( 1000 x 492 )] x 100


= 0.410
Corresponding shear stress tc = 0.472 > 0.47 N/mm2
(Ref .Table 19. in IS 456-2000) Hence Safe
CHECK FOR TWO WAY SHEAR AT 'D/2' FROM THE PEDESTAL FACE
Maximum axial load on pedestal = 683.4 KN
Effective depth at critical section = 0.49 m
Area resisted by shear stress = 1706256 mm2
Actual punching shear = 0.601
Permissible stress in two way shear = 0.25 × √25 = 1.250 N/mm²
(Ref .Cl.31.6.3. in IS 456-2000) Hence safe in two way shear

Check against one way shear @ X direction


Depth of footing D = 550 mm
Effective depth ( d' ) = 550 - 50 -16-8 = 476 mm

Shear force at critical section, V = 22.31 x 1x (0.6 - 0.476) = 2.77 ton


Cantilever length = 0.6 m

Critical section for shear is at a distance 'd' from the face of the column = 0.6 - 0.476
= 0.124 m
Effective depth at critical sction d' = 0.476 m
(Ref .Cl.No.40.1 in IS 456-2000)
Nominal shear stress at critical section, tv = V / (b' x d')
(2.77 x 2 x 9.81 x 10^3) / (1000 x 476) = 0.11 N/mm2
#REF! M/S. REFEX ENERGY LIMITED
DOCUMENT NO DATE
PROJECT SOLAR PV POWER PLANT OF 50MW AC
1617101-RFX-NLC-SWYD-F&C-018 06.03.18
DESIGNED CHECKED REV
TITLE FOUNDATION & COLUMN DESIGN FOR CRB
GS KN 0
3.10 DESIGN OF FOOTING -F6 (Load case 110) & (Node No 24)
Percentage of reinforcement at critical section = = [2010.62 / ( 1000 x 476 )] x 100
= 0.420

Corresponding shear stress tc = 0.479 > 0.11 N/mm2


Hence Safe

Design Summary:-
Length of footing = 1500 mm
Breath of footing = 2500 mm
Thickness of footing = 550 mm
Reinforcement
Bottom of Footing:-
In Z-direction = 16 mm diameter @ 100 C/C (Bottom )
In X-direction = 16 mm diameter @ 100 C/C (Bottom )
Top of footing
In Z-direction = 12 mm diameter @ 150 C/C (Top )
In X-direction = 12 mm diameter @ 150 C/C (Top )
#REF! M/S. REFEX ENERGY LIMITED
DOCUMENT NO DATE
PROJECT SOLAR PV POWER PLANT OF 50MW AC
1617101-RFX-NLC-SWYD-F&C-018 06.03.18
DESIGNED CHECKED REV
TITLE FOUNDATION & COLUMN DESIGN FOR CRB
GS KN 0
3.10 DESIGN OF FOOTING -F6 (Load case 110) & (Node No 24)
#REF! M/S. REFEX ENERGY LIMITED
DOCUMENT NO DATE
PROJECT SOLAR PV POWER PLANT OF 50MW AC
1617101-RFX-NLC-SWYD-F&C-018 06.03.18
DESIGNED CHECKED REV
TITLE FOUNDATION & COLUMN DESIGN FOR CRB
GS KN 0
3.11 DESIGN OF FOOTING -F11 (Load case 112) & (Node No 25)

DESIGN DATA:-
Depth of foundation from FGL = 3.00 m
Footing size = 2.00 m x 2.00 m
X-dir Z-dir
Thickness of footing at edge = 400 mm
Thickness of footing at face of column = 400 mm
Projection around column = 0 mm
Column size = 300 mm x 450 mm
X-dir Z-dir
MATERIAL PROPERTIES:-
Compressive Strength of Concrete = 25 N/mm2
Grade of steel = Fe 500
Density of concrete = 2.5 T/m3
Density of soil = 1.9 T/m3
Co efficient of friction = 0.50

FACTOR OF SAFETY:-
For strength design = 2.00
FX = 1.113 Ton.
FZ = 0.2 Ton
P = 66.7 Ton
Mx = 0.0 Ton.m
Mz = 3.2 Ton.m
FINAL VALUE FOR DESIGN
Vertical load P = 66.7 Ton
Bending Moment Z-direction Mx = 0.0 Ton.m
Bending Moment X-direction Mz = 3.2 Ton.m

CALCULATIONS
Volume of footing = 1.96 m3
Volume of soil = 10.04 m3
a) Wt of footing = 4.9 Ton
b) Wt of soil = 19.08 Ton
Total vertical load = 66.7304 + 4.9 + 19.08
= 90.71 Ton
Net SBC at 3 m depth = 17.50 T/m2
Gross SBC at 2 m depth = = 17.5x1.25+3x1.9 = 27.575 T/m2

Bearing pressure = 90.71 / (2 x 2) ± 6 x 0.0489 / (2 x 2^2)


± 6 x 3.23 / (2 x 2^2)
= 22.68 ± 0.04 ± 2.42

Bearing pressure at footing P1 = 25.14 Ton./sqm OK < 27.575 Ton./sqm


four corners P2 = 20.3 Ton./sqm
P3 = 25.06 Ton./sqm
P4 = 20.22 Ton./sqm
#REF! M/S. REFEX ENERGY LIMITED
DOCUMENT NO DATE
PROJECT SOLAR PV POWER PLANT OF 50MW AC
1617101-RFX-NLC-SWYD-F&C-018 06.03.18
DESIGNED CHECKED REV
TITLE FOUNDATION & COLUMN DESIGN FOR CRB
GS KN 0
3.11 DESIGN OF FOOTING -F11 (Load case 112) & (Node No 25)

Pressure due to over burden soil and raft


( 0.40 + 0.40 )/ 2 x 2.5 +
( 2.60 + 2.60 )/ 2 x 1.9
= 5.94
Net pmax = 19.2 T/m2
Net pmin = 1.1 T/m2
0.3

0.3 FGL FGL


2.00

3.00
0.85 0.85

0.40 z

2.00 2.00 x
PLAN SECTION

CHECK FOR FLEXURE ABOUT Z DIRECTION


Net pressure at edge = 19.2 t/m2

Thickness of footing at column face = 400 mm

Effective depth of footing at z direction, d = 400 - 50 - 8 = 342 mm

Cantilever span of slab from column face = (2 - 0.45) / 2 = 0.775 m

Moment (max) at face of column = 19.2 x 0.775 ^ 2 / 2 = 5.77 tm

Mu/bd2 = (5.77 x 2 x 9.81x10^6) / (1000 x 342 ^2) = 0.97 N/mm2

pt = 0.234 % Ast = 0.234 x1000 x 342 / 100 = 800 mm2


Minimum pt = 0.12 % Ast = 0.12 x 1000 x 400 / 100 = 480 mm2
(Ref .Cl.No.26.5.2.1 in IS 456-2000)
PROVIDE 16 TOR @ 100 c/c at bottom , (Ast) = 2011 mm2
SAFE
CHECK FOR FLEXURE ABOUT X DIRECTION
Cantilever span of slab from column face = (2 - 0.3) / 2 = 0.85 m

Moment (max) at face of column = 19.2 x 0.85 ^ 2 / 2 = 6.94 tm


Effective depth of footing at x direction, d = 400 - 50 - 16 - 16/2 = 326 mm
Mu/bd2 = (6.94 x 2x 9.81 x 10^6) / (1000 x 326 ^2) = 1.28 N/mm2
#REF! M/S. REFEX ENERGY LIMITED
DOCUMENT NO DATE
PROJECT SOLAR PV POWER PLANT OF 50MW AC
1617101-RFX-NLC-SWYD-F&C-018 06.03.18
DESIGNED CHECKED REV
TITLE FOUNDATION & COLUMN DESIGN FOR CRB
GS KN 0
3.11 DESIGN OF FOOTING -F11 (Load case 112) & (Node No 25)
pt = 0.314 % Ast = 0.314 x1000 x 326 / 100 = 1024 mm2
Minimum pt = 0.12 % Ast = 0.12 x 1000 x 400 / 100 = 480 mm2
PROVIDE 16 TOR @ 100 c/c at bottom , (Ast = 2011 mm2
(Ref .Cl.No.26.5.2.1 in IS 456-2000) SAFE
Provide nominal reinforcement @ top
Minimum pt = 0.06 % = 0.06 x 1000 x 400 / 100 = 240 mm2
PROVIDE 12 TOR @ 150 c/c bothways at , (Ast = 754 mm2
SAFE
CHECK AGAINST ONE WAY SHEAR @ Z DIRECTION
Depth of footing = 400 mm
Effective depth = 400 - 50 - 8 = 342 mm
Shear force at critical section, V = 19.2 x 1x (0.775 - 0.342) = 8.31 ton
Cantilever length = 0.775 m
Critical section for shear is at a
distance 'd' from the face of the
pedestal = 0.775 - 0.342
= 0.433 m
Effective depth at critical sction d' = 0.342 m
(Ref .Cl.No.40.1 in IS 456-2000)
Nominal shear stress at critical section, tv = = V / (b' x d')
(8.31 x 2 x 9.81 x 10^3) / (1000 x 342) = 0.48 N/mm2

Percentage of reinforcement at critical section = [2010.62 / ( 1000 x 342 )] x 100


= 0.590
Corresponding shear stress tc = 0.598 > 0.48 N/mm2
(Ref .Table 19. in IS 456-2000) Hence Safe
CHECK FOR TWO WAY SHEAR AT 'D/2' FROM THE PEDESTAL FACE
Maximum axial load on pedestal = 654.6 KN
Effective depth at critical section = 0.34 m
Area resisted by shear stress = 980856 mm2
Actual punching shear = 1.001
Permissible stress in two way shear = 0.25 × √25 = 1.250 N/mm²
(Ref .Cl.31.6.3. in IS 456-2000) Hence safe in two way shear

Check against one way shear @ X direction


Depth of footing D = 400 mm
Effective depth ( d' ) = 400 - 50 -16-8 = 326 mm

Shear force at critical section, V = 19.2 x 1x (0.85 - 0.326) = 10.06 ton


Cantilever length = 0.85 m

Critical section for shear is at a distance 'd' from the face of the column = 0.85 - 0.326
= 0.524 m
Effective depth at critical sction d' = 0.326 m
(Ref .Cl.No.40.1 in IS 456-2000)
Nominal shear stress at critical section, tv = V / (b' x d')
(10.06 x 2 x 9.81 x 10^3) / (1000 x 326) = 0.61 N/mm2
#REF! M/S. REFEX ENERGY LIMITED
DOCUMENT NO DATE
PROJECT SOLAR PV POWER PLANT OF 50MW AC
1617101-RFX-NLC-SWYD-F&C-018 06.03.18
DESIGNED CHECKED REV
TITLE FOUNDATION & COLUMN DESIGN FOR CRB
GS KN 0
3.11 DESIGN OF FOOTING -F11 (Load case 112) & (Node No 25)
Percentage of reinforcement at critical section = = [2010.62 / ( 1000 x 326 )] x 100
= 0.620

Corresponding shear stress tc = 0.619 > 0.61 N/mm2


Hence Safe

Design Summary:-
Length of footing = 2000 mm
Breath of footing = 2000 mm
Thickness of footing = 400 mm
Reinforcement
Bottom of Footing:-
In Z-direction = 16 mm diameter @ 100 C/C (Bottom )
In X-direction = 16 mm diameter @ 100 C/C (Bottom )
Top of footing
In Z-direction = 12 mm diameter @ 150 C/C (Top )
In X-direction = 12 mm diameter @ 150 C/C (Top )
#REF! M/S. REFEX ENERGY LIMITED
DOCUMENT NO DATE
PROJECT SOLAR PV POWER PLANT OF 50MW AC
1617101-RFX-NLC-SWYD-F&C-018 06.03.18
DESIGNED CHECKED REV
TITLE FOUNDATION & COLUMN DESIGN FOR CRB
GS KN 0
3.11 DESIGN OF FOOTING -F11 (Load case 112) & (Node No 25)
CLIENT M/S. REFEX ENERGY LIMITED
DOCUMENT NO DATE
PROJECT SOLAR PV POWER PLANT OF 50MW AC
1617101-RFX-NLC-SWYD-F&C-018 06.03.18
DESIGNED CHECKED REV
TITLE FOUNDATION & COLUMN DESIGN FOR CRB
GS KN 0
3.2 DESIGN OF FOOTING -F2 (Load case 134) & (Node No 6)

DESIGN DATA:-
Depth of foundation from FGL = 2.00 m
Footing size = 1.75 m x 1.75 m
X-dir Z-dir
Thickness of footing at edge = 300 mm
Thickness of footing at face of column = 300 mm
Projection around column = ###mm
Column size = 300 mm x 230 mm
X-dir Z-dir
MATERIAL PROPERTIES:-
Compressive Strength of Concrete = 25 N/mm2
Grade of steel = Fe 500
Density of concrete = 2.5 T/m3
Density of soil = 1.733 T/m3
Co efficient of friction = 0.50

FACTOR OF SAFETY:-
For strength design = 2.00
FX = 1.134 Ton.
FZ = 0.2 Ton
P = 23.4 Ton
Mx = 0.1 Ton.m
Mz = 1.4 Ton.m
FINAL VALUE FOR DESIGN
Vertical load P = 23.4 Ton
Bending Moment Z-direction Mx = 0.1 Ton.m
Bending Moment X-direction Mz = 1.4 Ton.m

CALCULATIONS
Volume of footing = 1.04 m3
Volume of soil = 5.09 m3
a) Wt of footing = 2.6 Ton
b) Wt of soil = 8.82 Ton
Total vertical load = 23.4263 + 2.6 + 8.82
= 34.85 Ton
Net SBC at 2 m depth = 17.95 T/m2
Gross SBC at 2 m depth = = 17.95x1.25+2x1.733 = 25.9035 T/m2

Bearing pressure = 34.85 / (1.75 x 1.75) ± 6 x 0.1366 / (1.75 x 1.75^2)


± 6 x 1.4457 / (1.75 x 1.75^2)
= 11.38 ± 0.15 ± 1.62

Bearing pressure at footing P1 = 13.15 Ton./sqm OK < 25.9035 Ton./sqm


four corners P2 = 9.91 Ton./sqm
P3 = 12.85 Ton./sqm
P4 = 9.61 Ton./sqm

Pressure due to over burden soil and raft


( 0.30 + 0.30 )/ 2 x 2.5 +
( 1.70 + 1.70 )/ 2 x 1.733
= 3.6961
Net pmax = 9.4539 T/m2
Net pmin = 0.456 T/m2
CLIENT M/S. REFEX ENERGY LIMITED
DOCUMENT NO DATE
PROJECT SOLAR PV POWER PLANT OF 50MW AC
1617101-RFX-NLC-SWYD-F&C-018 06.03.18
DESIGNED CHECKED REV
TITLE FOUNDATION & COLUMN DESIGN FOR CRB
GS KN 0

0.3

0.3 FGL FGL


1.75

2.00
0.725 0.725

0.30 z

1.75 1.75 x
PLAN SECTION

CHECK FOR FLEXURE ABOUT Z DIRECTION


Net pressure at edge = 9.4539 t/m2

Thickness of footing at column face = 300 mm

Effective depth of footing at z direction, d = 300 - 50 - 6 = 244 mm

Cantilever span of slab from column face = (1.75 - 0.23) / 2 = 0.76 m

Moment (max) at face of column = 9.4539 x 0.76 ^ 2 / 2 = 2.73 tm

Mu/bd2 = (2.73 x 2 x 9.81x10^6) / (1000 x 244 ^2) = 0.90 N/mm2

pt = 0.216 % Ast = 0.216 x1000 x 244 / 100 = 527 mm2


Minimum pt = 0.12 % Ast = 0.12 x 1000 x 300 / 100 = 360 mm2
(Ref .Cl.No.26.5.2.1 in IS 456-2000)
PROVIDE 12 TOR @ 150 c/c at bottom , (Ast) = 754 mm2
SAFE
CHECK FOR FLEXURE ABOUT X DIRECTION
Cantilever span of slab from column face = (1.75 - 0.3) / 2 = 0.725 m

Moment (max) at face of column = 9.4539 x 0.725 ^ 2 / 2 = 2.48 tm


Effective depth of footing at x direction, d = 300 - 50 - 12 - 12/2 = 232 mm
Mu/bd2 = (2.48 x 2x 9.81 x 10^6) / (1000 x 232 ^2) = 0.90 N/mm2

pt = 0.216 % Ast = 0.216 x1000 x 232 / 100 = 501 mm2


Minimum pt = 0.12 % Ast = 0.12 x 1000 x 300 / 100 = 360 mm2
PROVIDE 12 TOR @ 150 c/c at bottom , (Ast = 754 mm2
(Ref .Cl.No.26.5.2.1 in IS 456-2000) SAFE

Provide nominal reinforcement @ top


Minimum pt = 0.06 % = 0.06 x 1000 x 300 / 100 = 180 mm2
PROVIDE 12 TOR @ 150 c/c bothways a, (Ast = 754 mm2
SAFE

CHECK AGAINST ONE WAY SHEAR @ Z DIRECTION


Depth of footing = 300 mm
Effective depth = 300 - 50 - 6 = 244 mm
Shear force at critical section, V = 9.4539 x 1x (0.76 - 0.244) = 4.88 ton
Cantilever length = 0.76 m
CLIENT M/S. REFEX ENERGY LIMITED
DOCUMENT NO DATE
PROJECT SOLAR PV POWER PLANT OF 50MW AC
1617101-RFX-NLC-SWYD-F&C-018 06.03.18
DESIGNED CHECKED REV
TITLE FOUNDATION & COLUMN DESIGN FOR CRB
GS KN 0
Critical section for shear is at a
distance 'd' from the face of the
pedestal = 0.76 - 0.244
= 0.516 m

Effective depth at critical sction d' = 0.244 m


(Ref .Cl.No.40.1 in IS 456-2000)
Nominal shear stress at critical section, tv = = V / (b' x d')
(4.88 x 2 x 9.81 x 10^3) / (1000 x 244) = 0.39 N/mm2

Percentage of reinforcement at critical section = [753.98 / ( 1000 x 244 )] x 100


= 0.310
Corresponding shear stress = tc 0.402 > 0.39 N/mm2
(Ref .Table 19. in IS 456-2000) Hence Safe
CHECK FOR TWO WAY SHEAR AT 'D/2' FROM THE PEDESTAL FACE
Maximum axial load on pedestal = 229.8 KN
Effective depth at critical section = 0.24 m
Area resisted by shear stress = 496784 mm2
Actual punching shear = 0.694
Permissible stress in two way shear = 0.25 × √25 = 1.250 N/mm²
(Ref .Cl.31.6.3. in IS 456-2000) Hence safe in two way shear

Check against one way shear @ X direction


Depth of footing D = 300 mm
Effective depth ( d' ) = 300 - 50 -12-6 = 232 mm

Shear force at critical section, V = 9.4539 x 1x (0.725 - 0.232) = 4.66 ton


Cantilever length = 0.725 m

Critical section for shear is at a distance 'd' from the face of the column = 0.725 - 0.232
= 0.493 m
Effective depth at critical sction d' = 0.232 m
(Ref .Cl.No.40.1 in IS 456-2000)

Nominal shear stress at critical section, tv = V / (b' x d')


(4.66 x 2 x 9.81 x 10^3) / (1000 x 232) = 0.39 N/mm2

Percentage of reinforcement at critical section = = [753.98 / ( 1000 x 232 )] x 100


= 0.320

Corresponding shear stress tc = 0.409 > 0.39 N/mm2


Hence Safe

Design Summary:-
Length of footing = 1750 mm
Breath of footing = 1750 mm
Thickness of footing = 300 mm
Reinforcement
Bottom of Footing:-
In Z-direction = 12 mm diameter @ 150 C/C (Bottom )
In X-direction = 12 mm diameter @ 150 C/C (Bottom )
Top of footing
In Z-direction = 12 mm diameter @ 150 C/C (Top )
In X-direction = 12 mm diameter @ 150 C/C (Top )
CLIENT M/S. REFEX ENERGY LIMITED
DOCUMENT NO DATE
PROJECT SOLAR PV POWER PLANT OF 50MW AC
1617101-RFX-NLC-SWYD-F&C-018 06.03.18
DESIGNED CHECKED REV
TITLE FOUNDATION & COLUMN DESIGN FOR CRB
GS KN 0
CLIENT M/S. REFEX ENERGY LIMITED
DOCUMENT NO DATE
PROJECT SOLAR PV POWER PLANT OF 50MW AC
1617101-RFX-NLC-SWYD-F&C-018 06.03.18
DESIGNED CHECKED REV
TITLE FOUNDATION & COLUMN DESIGN FOR CRB
GS KN 0
3.2 DESIGN OF FOOTING -F2 (Load case 110) & (Node No 7)

DESIGN DATA:-
Depth of foundation from FGL = 2.00 m
Footing size = 1.75 m x 1.75 m
X-dir Z-dir
Thickness of footing at edge = 300 mm
Thickness of footing at face of column = 300 mm
Projection around column = ###mm
Column size = 300 mm x 230 mm
X-dir Z-dir
MATERIAL PROPERTIES:-
Compressive Strength of Concrete = 25 N/mm2
Grade of steel = Fe 500
Density of concrete = 2.5 T/m3
Density of soil = 1.733 T/m3
Co efficient of friction = 0.50

FACTOR OF SAFETY:-
For strength design = 2.00
FX = 1.176 Ton.
FZ = 0.1 Ton
P = 23.8 Ton
Mx = 0.1 Ton.m
Mz = 1.5 Ton.m
FINAL VALUE FOR DESIGN
Vertical load P = 23.8 Ton
Bending Moment Z-direction Mx = 0.1 Ton.m
Bending Moment X-direction Mz = 1.5 Ton.m

CALCULATIONS
Volume of footing = 1.04 m3
Volume of soil = 5.09 m3
a) Wt of footing = 2.6 Ton
b) Wt of soil = 8.82 Ton
Total vertical load = 23.8446 + 2.6 + 8.82
= 35.26 Ton
Net SBC at 2 m depth = 17.95 T/m2
Gross SBC at 2 m depth = = 17.95x1.25+2x1.733 = 25.9035 T/m2

Bearing pressure = 35.26 / (1.75 x 1.75) ± 6 x 0.0891 / (1.75 x 1.75^2)


± 6 x 1.4535 / (1.75 x 1.75^2)
= 11.51 ± 0.1 ± 1.63

Bearing pressure at footing P1 = 13.24 Ton./sqm OK < 25.9035 Ton./sqm


four corners P2 = 9.98 Ton./sqm
P3 = 13.04 Ton./sqm
P4 = 9.78 Ton./sqm

Pressure due to over burden soil and raft


( 0.30 + 0.30 )/ 2 x 2.5 +
( 1.70 + 1.70 )/ 2 x 1.733
= 3.6961
Net pmax = 9.5439 T/m2
Net pmin = 0.436 T/m2
CLIENT M/S. REFEX ENERGY LIMITED
DOCUMENT NO DATE
PROJECT SOLAR PV POWER PLANT OF 50MW AC
1617101-RFX-NLC-SWYD-F&C-018 06.03.18
DESIGNED CHECKED REV
TITLE FOUNDATION & COLUMN DESIGN FOR CRB
GS KN 0

0.3

0.3 1.75 FGL FGL

2.00
0.725 0.725

0.30 z

1.75 1.75 x
PLAN SECTION

CHECK FOR FLEXURE ABOUT Z DIRECTION


Net pressure at edge = 9.5439 t/m2

Thickness of footing at column face = 300 mm

Effective depth of footing at z direction, d = 300 - 50 - 6 = 244 mm

Cantilever span of slab from column face = (1.75 - 0.23) / 2 = 0.76 m

Moment (max) at face of column = 9.5439 x 0.76 ^ 2 / 2 = 2.76 tm

Mu/bd2 = (2.76 x 2 x 9.81x10^6) / (1000 x 244 ^2) = 0.91 N/mm2

pt = 0.219 % Ast = 0.219 x1000 x 244 / 100 = 534 mm2


Minimum pt = 0.12 % Ast = 0.12 x 1000 x 300 / 100 = 360 mm2
(Ref .Cl.No.26.5.2.1 in IS 456-2000)
PROVIDE 12 TOR @ 150 c/c at bottom , (Ast) = 754 mm2
SAFE
CHECK FOR FLEXURE ABOUT X DIRECTION
Cantilever span of slab from column face = (1.75 - 0.3) / 2 = 0.725 m

Moment (max) at face of column = 9.5439 x 0.725 ^ 2 / 2 = 2.51 tm


Effective depth of footing at x direction, d = 300 - 50 - 12 - 12/2 = 232 mm
Mu/bd2 = (2.51 x 2x 9.81 x 10^6) / (1000 x 232 ^2) = 0.91 N/mm2

pt = 0.219 % Ast = 0.219 x1000 x 232 / 100 = 508 mm2


Minimum pt = 0.12 % Ast = 0.12 x 1000 x 300 / 100 = 360 mm2
PROVIDE 12 TOR @ 150 c/c at bottom , (Ast = 754 mm2
(Ref .Cl.No.26.5.2.1 in IS 456-2000) SAFE

Provide nominal reinforcement @ top


Minimum pt = 0.06 % = 0.06 x 1000 x 300 / 100 = 180 mm2
PROVIDE 12 TOR @ 150 c/c bothways a, (Ast = 754 mm2
SAFE

CHECK AGAINST ONE WAY SHEAR @ Z DIRECTION


Depth of footing = 300 mm
Effective depth = 300 - 50 - 6 = 244 mm
Shear force at critical section, V = 9.5439 x 1x (0.76 - 0.244) = 4.92 ton
Cantilever length = 0.76 m
Critical section for shear is at a
CLIENT M/S. REFEX ENERGY LIMITED
DOCUMENT NO DATE
PROJECT SOLAR PV POWER PLANT OF 50MW AC
1617101-RFX-NLC-SWYD-F&C-018 06.03.18
DESIGNED CHECKED REV
TITLE FOUNDATION & COLUMN DESIGN FOR CRB
GS KN 0
distance 'd' from the face of the
pedestal = 0.76 - 0.244
= 0.516 m

Effective depth at critical sction d' = 0.244 m


(Ref .Cl.No.40.1 in IS 456-2000)
Nominal shear stress at critical section, tv = = V / (b' x d')
(4.92 x 2 x 9.81 x 10^3) / (1000 x 244) = 0.40 N/mm2

Percentage of reinforcement at critical section = [753.98 / ( 1000 x 244 )] x 100


= 0.310
Corresponding shear stress = tc 0.402 > 0.40 N/mm2
(Ref .Table 19. in IS 456-2000) Hence Safe
CHECK FOR TWO WAY SHEAR AT 'D/2' FROM THE PEDESTAL FACE
Maximum axial load on pedestal = 233.9 KN
Effective depth at critical section = 0.24 m
Area resisted by shear stress = 496784 mm2
Actual punching shear = 0.706
Permissible stress in two way shear = 0.25 × √25 = 1.250 N/mm²
(Ref .Cl.31.6.3. in IS 456-2000) Hence safe in two way shear

Check against one way shear @ X direction


Depth of footing D = 300 mm
Effective depth ( d' ) = 300 - 50 -12-6 = 232 mm

Shear force at critical section, V = 9.5439 x 1x (0.725 - 0.232) = 4.71 ton


Cantilever length = 0.725 m

Critical section for shear is at a distance 'd' from the face of the column = 0.725 - 0.232
= 0.493 m
Effective depth at critical sction d' = 0.232 m
(Ref .Cl.No.40.1 in IS 456-2000)

Nominal shear stress at critical section, tv = V / (b' x d')


(4.71 x 2 x 9.81 x 10^3) / (1000 x 232) = 0.40 N/mm2

Percentage of reinforcement at critical section = = [753.98 / ( 1000 x 232 )] x 100


= 0.320

Corresponding shear stress tc = 0.409 > 0.40 N/mm2


Hence Safe

Design Summary:-
Length of footing = 1750 mm
Breath of footing = 1750 mm
Thickness of footing = 300 mm
Reinforcement
Bottom of Footing:-
In Z-direction = 12 mm diameter @ 150 C/C (Bottom )
In X-direction = 12 mm diameter @ 150 C/C (Bottom )
Top of footing
In Z-direction = 12 mm diameter @ 150 C/C (Top )
In X-direction = 12 mm diameter @ 150 C/C (Top )
CLIENT M/S. REFEX ENERGY LIMITED
DOCUMENT NO DATE
PROJECT SOLAR PV POWER PLANT OF 50MW AC
1617101-RFX-NLC-SWYD-F&C-018 06.03.18
DESIGNED CHECKED REV
TITLE FOUNDATION & COLUMN DESIGN FOR CRB
GS KN 0
CLIENT M/S. REFEX ENERGY LIMITED
DOCUMENT NO
PROJECT SOLAR PV POWER PLANT OF 50MW AC
1617101-RFX-NLC-SWYD-F&C-018
DESIGNED CHECKED
TITLE FOUNDATION & COLUMN DESIGN FOR CRB
GS KN
3.2 DESIGN OF FOOTING -F2 (Load case 114) & (Node No 10)

DESIGN DATA:-
Depth of foundation from FGL = 2.00 m
Footing size = 1.75 m x 1.75
X-dir Z-dir
Thickness of footing at edge = 300 mm
Thickness of footing at face of column = 300 mm
Projection around column = ###mm
Column size = 230 mm x 450
X-dir Z-dir
MATERIAL PROPERTIES:-
Compressive Strength of Concrete = 25 N/mm2
Grade of steel = Fe 500
Density of concrete = 2.5 T/m3
Density of soil = 1.733 T/m3
Co efficient of friction = 0.50

FACTOR OF SAFETY:-
For strength design = 2.00
FX = 1.195 Ton.
FZ = 0.0 Ton
P = 17.0 Ton
Mx = 0.0 Ton.m
Mz = 2.4 Ton.m
FINAL VALUE FOR DESIGN
Vertical load P = 17.0 Ton
Bending Moment Z-direction Mx = 0.0 Ton.m
Bending Moment X-direction Mz = 2.4 Ton.m

CALCULATIONS
Volume of footing = 1.1 m3
Volume of soil = 5.03 m3
a) Wt of footing = 2.75 Ton
b) Wt of soil = 8.72 Ton
Total vertical load = 16.9839 + 2.75 + 8.72
= 28.45 Ton
Net SBC at 2 m depth = 17.95 T/m2
Gross SBC at 2 m depth = = 17.95x1.25+2x1.733 =

Bearing pressure = 28.45 / (1.75 x 1.75) ± 6 x 0.0228 / (1.75 x 1.75^2)


± 6 x 2.4083 / (1.75 x 1.75^2)
= 9.29 ± 0.03

Bearing pressure at footing P1 = 12.02 Ton./sqm OK < 25.9035 Ton./s


four corners P2 = 6.62 Ton./sqm
P3 = 11.96 Ton./sqm
P4 = 6.56 Ton./sqm
CLIENT M/S. REFEX ENERGY LIMITED
DOCUMENT NO
PROJECT SOLAR PV POWER PLANT OF 50MW AC
1617101-RFX-NLC-SWYD-F&C-018
DESIGNED CHECKED
TITLE FOUNDATION & COLUMN DESIGN FOR CRB
GS KN
Pressure due to over burden soil and raft
( 0.30 + 0.30 )/ 2 x 2.5
( 1.70 + 1.70 )/ 2 x 1.733
= 3.6961
Net pmax = 8.3239 T/m2
Net pmin = -1.704 T/m2

0.23

0.23 FGL FGL


1.75

2.00
0.76 0.76

0.30

1.75 1.75
PLAN SECTION

CHECK FOR FLEXURE ABOUT Z DIRECTION


Net pressure at edge = 8.3239 t/m2

Thickness of footing at column face = 300 mm

Effective depth of footing at z direction, d = 300 - 50 - 6 = 244 mm

Cantilever span of slab from column face = (1.75 - 0.45) / 2 = 0.65 m

Moment (max) at face of column = 8.3239 x 0.65 ^ 2 / 2 = 1.76 tm

Mu/bd2 = (1.76 x 2 x 9.81x10^6) / (1000 x 244 ^2) = 0.58 N/mm2

pt = 0.137 % Ast = 0.137 x1000 x 244 / 100 = 334


Minimum pt = 0.12 % Ast = 0.12 x 1000 x 300 / 100 = 360
(Ref .Cl.No.26.5.2.1 in IS 456-2000)
PROVIDE 12 TOR @ 150 c/c at bottom , (Ast) = 754
SAFE
CHECK FOR FLEXURE ABOUT X DIRECTION
Cantilever span of slab from column face = (1.75 - 0.23) / 2 = 0.76
CLIENT M/S. REFEX ENERGY LIMITED
DOCUMENT NO
PROJECT SOLAR PV POWER PLANT OF 50MW AC
1617101-RFX-NLC-SWYD-F&C-018
DESIGNED CHECKED
TITLE FOUNDATION & COLUMN DESIGN FOR CRB
GS KN
Moment (max) at face of column = 8.3239 x 0.76 ^ 2 / 2 = 2.4
Effective depth of footing at x direction, d = 300 - 50 - 12 - 12/2 = 232
Mu/bd2 = (2.4 x 2x 9.81 x 10^6) / (1000 x 232 ^2) = 0.87

pt = 0.209 % Ast = 0.209 x1000 x 232 / 100 = 485


Minimum pt = 0.12 % Ast = 0.12 x 1000 x 300 / 100 = 360
PROVIDE 12 TOR @ 150 c/c at bottom , (Ast = 754
(Ref .Cl.No.26.5.2.1 in IS 456-2000) SAFE

Provide nominal reinforcement @ top


Minimum pt = 0.06 % = 0.06 x 1000 x 300 / 100 = 180
PROVIDE 12 TOR @ 150 c/c bothways a, (Ast = 754
SAFE

CHECK AGAINST ONE WAY SHEAR @ Z DIRECTION


Depth of footing = 300
Effective depth = 300 - 50 - 6 = 244
Shear force at critical section, V = 8.3239 x 1x (0.65 - 0.244) = 3.38
Cantilever length = 0.65
Critical section for shear is at a
distance 'd' from the face of the
pedestal = 0.65
= 0.406

Effective depth at critical sction d' = 0.244


(Ref .Cl.No.40.1 in IS 456-2000)
Nominal shear stress at critical section, tv = = V / (b' x d')
(3.38 x 2 x 9.81 x 10^3) / (1000 x 244) = 0.27

Percentage of reinforcement at critical section = [753.98 / ( 1000 x 244 )] x


= 0.310
Corresponding shear stress = tc 0.402 > 0.27
(Ref .Table 19. in IS 456-2000) Hence Safe
CHECK FOR TWO WAY SHEAR AT 'D/2' FROM THE PEDESTAL FACE
Maximum axial load on pedestal = 166.6
Effective depth at critical section = 0.24
Area resisted by shear stress = 569984
Actual punching shear = 0.438
Permissible stress in two way shear = 0.25 × √25 = 1.250
(Ref .Cl.31.6.3. in IS 456-2000) Hence safe in two way shear
CLIENT M/S. REFEX ENERGY LIMITED
DOCUMENT NO
PROJECT SOLAR PV POWER PLANT OF 50MW AC
1617101-RFX-NLC-SWYD-F&C-018
DESIGNED CHECKED
TITLE FOUNDATION & COLUMN DESIGN FOR CRB
GS KN
Check against one way shear @ X direction
Depth of footing D = 300
Effective depth ( d' ) = 300 - 50 -12-6 = 232

Shear force at critical section, V = 8.3239 x 1x (0.76 - 0.232) = 4.4


Cantilever length = 0.76

Critical section for shear is at a distance 'd' from the face of the column = 0.76
= 0.528
Effective depth at critical sction d' = 0.232
(Ref .Cl.No.40.1 in IS 456-2000)

Nominal shear stress at critical section, tv = V / (b' x d')


(4.4 x 2 x 9.81 x 10^3) / (1000 x 232) = 0.37

Percentage of reinforcement at critical section = = [753.98 / ( 1000 x 232 )] x 100


=

Corresponding shear stress tc = 0.409 > 0.37


Hence Safe

Design Summary:-
Length of footing = 1750 mm
Breath of footing = 1750 mm
Thickness of footing = 300 mm
Reinforcement
Bottom of Footing:-
In Z-direction = 12 mm diameter @ 150 C/C (Bottom )
In X-direction = 12 mm diameter @ 150 C/C (Bottom )
Top of footing
In Z-direction = 12 mm diameter @ 150 C/C (Top )
In X-direction = 12 mm diameter @ 150 C/C (Top )
CUMENT NO DATE
-NLC-SWYD-F&C-018 06.03.18
CHECKED REV
KN 0
10)

mm

25.9035 T/m2

x 0.0228 / (1.75 x 1.75^2)


x 2.4083 / (1.75 x 1.75^2)
± 2.7

K < 25.9035 Ton./sqm


CUMENT NO DATE
-NLC-SWYD-F&C-018 06.03.18
CHECKED REV
KN 0

mm2
mm2

mm2

m
CUMENT NO DATE
-NLC-SWYD-F&C-018 06.03.18
CHECKED REV
KN 0
tm
mm
N/mm2

mm2
mm2
mm2

mm2
mm2

mm
mm
ton
m

- 0.244
m

V / (b' x d')
N/mm2

[753.98 / ( 1000 x 244 )] x 100

N/mm2

KN
m
mm2

N/mm²
two way shear
CUMENT NO DATE
-NLC-SWYD-F&C-018 06.03.18
CHECKED REV
KN 0

mm
mm

ton
m

- 0.232
m
m

V / (b' x d')
N/mm2

53.98 / ( 1000 x 232 )] x 100


0.320

N/mm2
CLIENT M/S. REFEX ENERGY LIMITED
DOCUMENT NO
PROJECT SOLAR PV POWER PLANT OF 50MW AC
1617101-RFX-NLC-SWYD-F&C-018
DESIGNED CHECKED
TITLE FOUNDATION & COLUMN DESIGN FOR CRB
GS KN
3.2 DESIGN OF FOOTING -F2 (Load case 109) & (Node No 11)

DESIGN DATA:-
Depth of foundation from FGL = 2.00 m
Footing size = 1.75 m x 1.75
X-dir Z-dir
Thickness of footing at edge = 300 mm
Thickness of footing at face of column = 300 mm
Projection around column = ###mm
Column size = 230 mm x 450
X-dir Z-dir
MATERIAL PROPERTIES:-
Compressive Strength of Concrete = 25 N/mm2
Grade of steel = Fe 500
Density of concrete = 2.5 T/m3
Density of soil = 1.733 T/m3
Co efficient of friction = 0.50

FACTOR OF SAFETY:-
For strength design = 2.00
FX = 1.134 Ton.
FZ = 0.1 Ton
P = 14.1 Ton
Mx = 0.1 Ton.m
Mz = 2.3 Ton.m
FINAL VALUE FOR DESIGN
Vertical load P = 14.1 Ton
Bending Moment Z-direction Mx = 0.1 Ton.m
Bending Moment X-direction Mz = 2.3 Ton.m

CALCULATIONS
Volume of footing = 1.1 m3
Volume of soil = 5.03 m3
a) Wt of footing = 2.75 Ton
b) Wt of soil = 8.72 Ton
Total vertical load = 14.0828 + 2.75 + 8.72
= 25.55 Ton
Net SBC at 2 m depth = 17.95 T/m2
Gross SBC at 2 m depth = = 17.95x1.25+2x1.733 =

Bearing pressure = 25.55 / (1.75 x 1.75) ± 6 x 0.0507 / (1.75 x 1.75^2)


± 6 x 2.2534 / (1.75 x 1.75^2)
= 8.34 ± 0.06

Bearing pressure at footing P1 = 10.92 Ton./sqm OK < 25.9035 Ton./s


four corners P2 = 5.88 Ton./sqm
P3 = 10.8 Ton./sqm
P4 = 5.76 Ton./sqm
CLIENT M/S. REFEX ENERGY LIMITED
DOCUMENT NO
PROJECT SOLAR PV POWER PLANT OF 50MW AC
1617101-RFX-NLC-SWYD-F&C-018
DESIGNED CHECKED
TITLE FOUNDATION & COLUMN DESIGN FOR CRB
GS KN

Pressure due to over burden soil and raft


( 0.30 + 0.30 )/ 2 x 2.5
( 1.70 + 1.70 )/ 2 x 1.733
= 3.6961
Net pmax = 7.2239 T/m2
Net pmin = -1.344 T/m2

0.23

0.23 FGL FGL


1.75

2.00
0.76 0.76

0.30

1.75 1.75
PLAN SECTION

CHECK FOR FLEXURE ABOUT Z DIRECTION


Net pressure at edge = 7.2239 t/m2

Thickness of footing at column face = 300 mm

Effective depth of footing at z direction, d = 300 - 50 - 6 = 244 mm

Cantilever span of slab from column face = (1.75 - 0.45) / 2 = 0.65 m

Moment (max) at face of column = 7.2239 x 0.65 ^ 2 / 2 = 1.53 tm

Mu/bd2 = (1.53 x 2 x 9.81x10^6) / (1000 x 244 ^2) = 0.50 N/mm2

pt = 0.118 % Ast = 0.118 x1000 x 244 / 100 = 288


Minimum pt = 0.12 % Ast = 0.12 x 1000 x 300 / 100 = 360
(Ref .Cl.No.26.5.2.1 in IS 456-2000)
PROVIDE 12 TOR @ 150 c/c at bottom , (Ast) = 754
SAFE
CHECK FOR FLEXURE ABOUT X DIRECTION
Cantilever span of slab from column face = (1.75 - 0.23) / 2 = 0.76
CLIENT M/S. REFEX ENERGY LIMITED
DOCUMENT NO
PROJECT SOLAR PV POWER PLANT OF 50MW AC
1617101-RFX-NLC-SWYD-F&C-018
DESIGNED CHECKED
TITLE FOUNDATION & COLUMN DESIGN FOR CRB
GS KN
Moment (max) at face of column = 7.2239 x 0.76 ^ 2 / 2 = 2.09
Effective depth of footing at x direction, d = 300 - 50 - 12 - 12/2 = 232
Mu/bd2 = (2.09 x 2x 9.81 x 10^6) / (1000 x 232 ^2) = 0.76

pt = 0.181 % Ast = 0.181 x1000 x 232 / 100 = 420


Minimum pt = 0.12 % Ast = 0.12 x 1000 x 300 / 100 = 360
PROVIDE 12 TOR @ 150 c/c at bottom , (Ast = 754
(Ref .Cl.No.26.5.2.1 in IS 456-2000) SAFE

Provide nominal reinforcement @ top


Minimum pt = 0.06 % = 0.06 x 1000 x 300 / 100 = 180
PROVIDE 12 TOR @ 150 c/c bothways a, (Ast = 754
SAFE

CHECK AGAINST ONE WAY SHEAR @ Z DIRECTION


Depth of footing = 300
Effective depth = 300 - 50 - 6 = 244
Shear force at critical section, V = 7.2239 x 1x (0.65 - 0.244) = 2.93
Cantilever length = 0.65
Critical section for shear is at a
distance 'd' from the face of the
pedestal = 0.65
= 0.406

Effective depth at critical sction d' = 0.244


(Ref .Cl.No.40.1 in IS 456-2000)
Nominal shear stress at critical section, tv = = V / (b' x d')
(2.93 x 2 x 9.81 x 10^3) / (1000 x 244) = 0.24

Percentage of reinforcement at critical section = [753.98 / ( 1000 x 244 )] x


= 0.310
Corresponding shear stress = tc 0.402 > 0.24
(Ref .Table 19. in IS 456-2000) Hence Safe
CHECK FOR TWO WAY SHEAR AT 'D/2' FROM THE PEDESTAL FACE
Maximum axial load on pedestal = 138.2
Effective depth at critical section = 0.24
Area resisted by shear stress = 569984
Actual punching shear = 0.364
Permissible stress in two way shear = 0.25 × √25 = 1.250
(Ref .Cl.31.6.3. in IS 456-2000) Hence safe in two way shear
CLIENT M/S. REFEX ENERGY LIMITED
DOCUMENT NO
PROJECT SOLAR PV POWER PLANT OF 50MW AC
1617101-RFX-NLC-SWYD-F&C-018
DESIGNED CHECKED
TITLE FOUNDATION & COLUMN DESIGN FOR CRB
GS KN
Check against one way shear @ X direction
Depth of footing D = 300
Effective depth ( d' ) = 300 - 50 -12-6 = 232

Shear force at critical section, V = 7.2239 x 1x (0.76 - 0.232) = 3.81


Cantilever length = 0.76

Critical section for shear is at a distance 'd' from the face of the column = 0.76
= 0.528
Effective depth at critical sction d' = 0.232
(Ref .Cl.No.40.1 in IS 456-2000)

Nominal shear stress at critical section, tv = V / (b' x d')


(3.81 x 2 x 9.81 x 10^3) / (1000 x 232) = 0.32

Percentage of reinforcement at critical section = = [753.98 / ( 1000 x 232 )] x 100


=

Corresponding shear stress tc = 0.409 > 0.32


Hence Safe

Design Summary:-
Length of footing = 1750 mm
Breath of footing = 1750 mm
Thickness of footing = 300 mm
Reinforcement
Bottom of Footing:-
In Z-direction = 12 mm diameter @ 150 C/C (Bottom )
In X-direction = 12 mm diameter @ 150 C/C (Bottom )
Top of footing
In Z-direction = 12 mm diameter @ 150 C/C (Top )
In X-direction = 12 mm diameter @ 150 C/C (Top )
CUMENT NO DATE
-NLC-SWYD-F&C-018 06.03.18
CHECKED REV
KN 0
11)

mm

25.9035 T/m2

x 0.0507 / (1.75 x 1.75^2)


x 2.2534 / (1.75 x 1.75^2)
± 2.52

K < 25.9035 Ton./sqm


CUMENT NO DATE
-NLC-SWYD-F&C-018 06.03.18
CHECKED REV
KN 0

mm2
mm2

mm2

m
CUMENT NO DATE
-NLC-SWYD-F&C-018 06.03.18
CHECKED REV
KN 0
tm
mm
N/mm2

mm2
mm2
mm2

mm2
mm2

mm
mm
ton
m

- 0.244
m

V / (b' x d')
N/mm2

[753.98 / ( 1000 x 244 )] x 100

N/mm2

KN
m
mm2

N/mm²
two way shear
CUMENT NO DATE
-NLC-SWYD-F&C-018 06.03.18
CHECKED REV
KN 0

mm
mm

ton
m

- 0.232
m
m

V / (b' x d')
N/mm2

53.98 / ( 1000 x 232 )] x 100


0.320

N/mm2
CLIENT M/S. REFEX ENERGY LIMITED
DOCUMENT NO
PROJECT SOLAR PV POWER PLANT OF 50MW AC
1617101-RFX-NLC-SWYD-F&C-018
DESIGNED CHECKED
TITLE FOUNDATION & COLUMN DESIGN FOR CRB
GS KN
3.2 DESIGN OF FOOTING -F2 (Load case 110) & (Node No 9)

DESIGN DATA:-
Depth of foundation from FGL = 2.00 m
Footing size = 1.75 m x 1.75
X-dir Z-dir
Thickness of footing at edge = 300 mm
Thickness of footing at face of column = 300 mm
Projection around column = ###mm
Column size = 230 mm x 450
X-dir Z-dir
MATERIAL PROPERTIES:-
Compressive Strength of Concrete = 25 N/mm2
Grade of steel = Fe 500
Density of concrete = 2.5 T/m3
Density of soil = 1.733 T/m3
Co efficient of friction = 0.50

FACTOR OF SAFETY:-
For strength design = 2.00
FX = 1.462 Ton.
FZ = 0.4 Ton
P = 17.7 Ton
Mx = 0.2 Ton.m
Mz = 1.9 Ton.m
FINAL VALUE FOR DESIGN
Vertical load P = 17.7 Ton
Bending Moment Z-direction Mx = 0.2 Ton.m
Bending Moment X-direction Mz = 1.9 Ton.m

CALCULATIONS
Volume of footing = 1.1 m3
Volume of soil = 5.03 m3
a) Wt of footing = 2.75 Ton
b) Wt of soil = 8.72 Ton
Total vertical load = 17.6961 + 2.75 + 8.72
= 29.17 Ton
Net SBC at 2 m depth = 17.95 T/m2
Gross SBC at 2 m depth = = 17.95x1.25+2x1.733 =

Bearing pressure = 29.17 / (1.75 x 1.75) ± 6 x 0.2421 / (1.75 x 1.75^2)


± 6 x 1.9229 / (1.75 x 1.75^2)
= 9.52 ± 0.27

Bearing pressure at footing P1 = 11.94 Ton./sqm OK < 25.9035 Ton./s


four corners P2 = 7.64 Ton./sqm
P3 = 11.4 Ton./sqm
P4 = 7.1 Ton./sqm
CLIENT M/S. REFEX ENERGY LIMITED
DOCUMENT NO
PROJECT SOLAR PV POWER PLANT OF 50MW AC
1617101-RFX-NLC-SWYD-F&C-018
DESIGNED CHECKED
TITLE FOUNDATION & COLUMN DESIGN FOR CRB
GS KN

Pressure due to over burden soil and raft


( 0.30 + 0.30 )/ 2 x 2.5
( 1.70 + 1.70 )/ 2 x 1.733
= 3.6961
Net pmax = 8.2439 T/m2
Net pmin = -0.604 T/m2

0.23

0.23 FGL FGL


1.75

2.00
0.76 0.76

0.30

1.75 1.75
PLAN SECTION

CHECK FOR FLEXURE ABOUT Z DIRECTION


Net pressure at edge = 8.2439 t/m2

Thickness of footing at column face = 300 mm

Effective depth of footing at z direction, d = 300 - 50 - 6 = 244 mm

Cantilever span of slab from column face = (1.75 - 0.45) / 2 = 0.65 m

Moment (max) at face of column = 8.2439 x 0.65 ^ 2 / 2 = 1.74 tm

Mu/bd2 = (1.74 x 2 x 9.81x10^6) / (1000 x 244 ^2) = 0.57 N/mm2

pt = 0.135 % Ast = 0.135 x1000 x 244 / 100 = 329


Minimum pt = 0.12 % Ast = 0.12 x 1000 x 300 / 100 = 360
(Ref .Cl.No.26.5.2.1 in IS 456-2000)
PROVIDE 12 TOR @ 150 c/c at bottom , (Ast) = 754
SAFE
CHECK FOR FLEXURE ABOUT X DIRECTION
Cantilever span of slab from column face = (1.75 - 0.23) / 2 = 0.76
CLIENT M/S. REFEX ENERGY LIMITED
DOCUMENT NO
PROJECT SOLAR PV POWER PLANT OF 50MW AC
1617101-RFX-NLC-SWYD-F&C-018
DESIGNED CHECKED
TITLE FOUNDATION & COLUMN DESIGN FOR CRB
GS KN
Moment (max) at face of column = 8.2439 x 0.76 ^ 2 / 2 = 2.38
Effective depth of footing at x direction, d = 300 - 50 - 12 - 12/2 = 232
Mu/bd2 = (2.38 x 2x 9.81 x 10^6) / (1000 x 232 ^2) = 0.87

pt = 0.209 % Ast = 0.209 x1000 x 232 / 100 = 485


Minimum pt = 0.12 % Ast = 0.12 x 1000 x 300 / 100 = 360
PROVIDE 12 TOR @ 150 c/c at bottom , (Ast = 754
(Ref .Cl.No.26.5.2.1 in IS 456-2000) SAFE

Provide nominal reinforcement @ top


Minimum pt = 0.06 % = 0.06 x 1000 x 300 / 100 = 180
PROVIDE 12 TOR @ 150 c/c bothways a, (Ast = 754
SAFE

CHECK AGAINST ONE WAY SHEAR @ Z DIRECTION


Depth of footing = 300
Effective depth = 300 - 50 - 6 = 244
Shear force at critical section, V = 8.2439 x 1x (0.65 - 0.244) = 3.35
Cantilever length = 0.65
Critical section for shear is at a
distance 'd' from the face of the
pedestal = 0.65
= 0.406

Effective depth at critical sction d' = 0.244


(Ref .Cl.No.40.1 in IS 456-2000)
Nominal shear stress at critical section, tv = = V / (b' x d')
(3.35 x 2 x 9.81 x 10^3) / (1000 x 244) = 0.27

Percentage of reinforcement at critical section = [753.98 / ( 1000 x 244 )] x


= 0.310
Corresponding shear stress = tc 0.402 > 0.27
(Ref .Table 19. in IS 456-2000) Hence Safe
CHECK FOR TWO WAY SHEAR AT 'D/2' FROM THE PEDESTAL FACE
Maximum axial load on pedestal = 173.6
Effective depth at critical section = 0.24
Area resisted by shear stress = 569984
Actual punching shear = 0.457
Permissible stress in two way shear = 0.25 × √25 = 1.250
(Ref .Cl.31.6.3. in IS 456-2000) Hence safe in two way shear
CLIENT M/S. REFEX ENERGY LIMITED
DOCUMENT NO
PROJECT SOLAR PV POWER PLANT OF 50MW AC
1617101-RFX-NLC-SWYD-F&C-018
DESIGNED CHECKED
TITLE FOUNDATION & COLUMN DESIGN FOR CRB
GS KN
Check against one way shear @ X direction
Depth of footing D = 300
Effective depth ( d' ) = 300 - 50 -12-6 = 232

Shear force at critical section, V = 8.2439 x 1x (0.76 - 0.232) = 4.35


Cantilever length = 0.76

Critical section for shear is at a distance 'd' from the face of the column = 0.76
= 0.528

Effective depth at critical sction d' = 0.232


(Ref .Cl.No.40.1 in IS 456-2000)

Nominal shear stress at critical section, tv = V / (b' x d')


(4.35 x 2 x 9.81 x 10^3) / (1000 x 232) = 0.37

Percentage of reinforcement at critical section = = [753.98 / ( 1000 x 232 )] x 100


=

Corresponding shear stress tc = 0.409 > 0.37


Hence Safe

Design Summary:-
Length of footing = 1750 mm
Breath of footing = 1750 mm
Thickness of footing = 300 mm
Reinforcement
Bottom of Footing:-
In Z-direction = 12 mm diameter @ 150 C/C (Bottom )
In X-direction = 12 mm diameter @ 150 C/C (Bottom )
Top of footing
In Z-direction = 12 mm diameter @ 150 C/C (Top )
In X-direction = 12 mm diameter @ 150 C/C (Top )
CUMENT NO DATE
-NLC-SWYD-F&C-018 06.03.18
CHECKED REV
KN 0
9)

mm

25.9035 T/m2

x 0.2421 / (1.75 x 1.75^2)


x 1.9229 / (1.75 x 1.75^2)
± 2.15

K < 25.9035 Ton./sqm


CUMENT NO DATE
-NLC-SWYD-F&C-018 06.03.18
CHECKED REV
KN 0

mm2
mm2

mm2

m
CUMENT NO DATE
-NLC-SWYD-F&C-018 06.03.18
CHECKED REV
KN 0
tm
mm
N/mm2

mm2
mm2
mm2

mm2
mm2

mm
mm
ton
m

- 0.244
m

V / (b' x d')
N/mm2

[753.98 / ( 1000 x 244 )] x 100

N/mm2

KN
m
mm2

N/mm²
two way shear
CUMENT NO DATE
-NLC-SWYD-F&C-018 06.03.18
CHECKED REV
KN 0

mm
mm

ton
m

- 0.232
m

V / (b' x d')
N/mm2

53.98 / ( 1000 x 232 )] x 100


0.320

N/mm2
CLIENT M/S. REFEX ENERGY LIMITED
DOCUMENT NO
PROJECT SOLAR PV POWER PLANT OF 50MW AC
1617101-RFX-NLC-SWYD-F&C-018
DESIGNED CHECKED
TITLE FOUNDATION & COLUMN DESIGN FOR CRB
GS KN
3.2 DESIGN OF FOOTING -F2 (Load case 135) & (Node No 12)

DESIGN DATA:-
Depth of foundation from FGL = 2.00 m
Footing size = 1.75 m x 1.75
X-dir Z-dir
Thickness of footing at edge = 300 mm
Thickness of footing at face of column = 300 mm
Projection around column = ###mm
Column size = 230 mm x 450
X-dir Z-dir
MATERIAL PROPERTIES:-
Compressive Strength of Concrete = 25 N/mm2
Grade of steel = Fe 500
Density of concrete = 2.5 T/m3
Density of soil = 1.733 T/m3
Co efficient of friction = 0.50

FACTOR OF SAFETY:-
For strength design = 2.00
FX = 0.625 Ton.
FZ = 1.3 Ton
P = 15.6 Ton
Mx = 2.6 Ton.m
Mz = 0.5 Ton.m
FINAL VALUE FOR DESIGN
Vertical load P = 15.6 Ton
Bending Moment Z-direction Mx = 2.6 Ton.m
Bending Moment X-direction Mz = 0.5 Ton.m

CALCULATIONS
Volume of footing = 1.1 m3
Volume of soil = 5.03 m3
a) Wt of footing = 2.75 Ton
b) Wt of soil = 8.72 Ton
Total vertical load = 15.5683 + 2.75 + 8.72
= 27.04 Ton
Net SBC at 2 m depth = 17.95 T/m2
Gross SBC at 2 m depth = = 17.95x1.25+2x1.733 =

Bearing pressure = 27.04 / (1.75 x 1.75) ± 6 x 2.5995 / (1.75 x 1.75^2)


± 6 x 0.4652 / (1.75 x 1.75^2)
= 8.83 ± 2.91

Bearing pressure at footing P1 = 12.26 Ton./sqm OK < 25.9035 Ton./s


four corners P2 = 11.22 Ton./sqm
P3 = 6.44 Ton./sqm
P4 = 5.4 Ton./sqm
CLIENT M/S. REFEX ENERGY LIMITED
DOCUMENT NO
PROJECT SOLAR PV POWER PLANT OF 50MW AC
1617101-RFX-NLC-SWYD-F&C-018
DESIGNED CHECKED
TITLE FOUNDATION & COLUMN DESIGN FOR CRB
GS KN

Pressure due to over burden soil and raft


( 0.30 + 0.30 )/ 2 x 2.5
( 1.70 + 1.70 )/ 2 x 1.733
= 3.6961
Net pmax = 8.5639 T/m2
Net pmin = 2.656 T/m2

0.23

0.23 FGL FGL


1.75

2.00
0.76 0.76

0.30

1.75 1.75
PLAN SECTION

CHECK FOR FLEXURE ABOUT Z DIRECTION


Net pressure at edge = 8.5639 t/m2

Thickness of footing at column face = 300 mm

Effective depth of footing at z direction, d = 300 - 50 - 6 = 244 mm

Cantilever span of slab from column face = (1.75 - 0.45) / 2 = 0.65 m

Moment (max) at face of column = 8.5639 x 0.65 ^ 2 / 2 = 1.81 tm

Mu/bd2 = (1.81 x 2 x 9.81x10^6) / (1000 x 244 ^2) = 0.60 N/mm2

pt = 0.142 % Ast = 0.142 x1000 x 244 / 100 = 346


Minimum pt = 0.12 % Ast = 0.12 x 1000 x 300 / 100 = 360
(Ref .Cl.No.26.5.2.1 in IS 456-2000)
PROVIDE 12 TOR @ 150 c/c at bottom , (Ast) = 754
SAFE
CHECK FOR FLEXURE ABOUT X DIRECTION
Cantilever span of slab from column face = (1.75 - 0.23) / 2 = 0.76
CLIENT M/S. REFEX ENERGY LIMITED
DOCUMENT NO
PROJECT SOLAR PV POWER PLANT OF 50MW AC
1617101-RFX-NLC-SWYD-F&C-018
DESIGNED CHECKED
TITLE FOUNDATION & COLUMN DESIGN FOR CRB
GS KN
Moment (max) at face of column = 8.5639 x 0.76 ^ 2 / 2 = 2.47
Effective depth of footing at x direction, d = 300 - 50 - 12 - 12/2 = 232
Mu/bd2 = (2.47 x 2x 9.81 x 10^6) / (1000 x 232 ^2) = 0.90

pt = 0.216 % Ast = 0.216 x1000 x 232 / 100 = 501


Minimum pt = 0.12 % Ast = 0.12 x 1000 x 300 / 100 = 360
PROVIDE 12 TOR @ 150 c/c at bottom , (Ast = 754
(Ref .Cl.No.26.5.2.1 in IS 456-2000) SAFE

Provide nominal reinforcement @ top


Minimum pt = 0.06 % = 0.06 x 1000 x 300 / 100 = 180
PROVIDE 12 TOR @ 150 c/c bothways a, (Ast = 754
SAFE

CHECK AGAINST ONE WAY SHEAR @ Z DIRECTION


Depth of footing = 300
Effective depth = 300 - 50 - 6 = 244
Shear force at critical section, V = 8.5639 x 1x (0.65 - 0.244) = 3.48
Cantilever length = 0.65
Critical section for shear is at a
distance 'd' from the face of the
pedestal = 0.65
= 0.406

Effective depth at critical sction d' = 0.244


(Ref .Cl.No.40.1 in IS 456-2000)
Nominal shear stress at critical section, tv = = V / (b' x d')
(3.48 x 2 x 9.81 x 10^3) / (1000 x 244) = 0.28

Percentage of reinforcement at critical section = [753.98 / ( 1000 x 244 )] x


= 0.310
Corresponding shear stress = tc 0.402 > 0.28
(Ref .Table 19. in IS 456-2000) Hence Safe
CHECK FOR TWO WAY SHEAR AT 'D/2' FROM THE PEDESTAL FACE
Maximum axial load on pedestal = 152.7
Effective depth at critical section = 0.24
Area resisted by shear stress = 569984
Actual punching shear = 0.402
Permissible stress in two way shear = 0.25 × √25 = 1.250
(Ref .Cl.31.6.3. in IS 456-2000) Hence safe in two way shear
CLIENT M/S. REFEX ENERGY LIMITED
DOCUMENT NO
PROJECT SOLAR PV POWER PLANT OF 50MW AC
1617101-RFX-NLC-SWYD-F&C-018
DESIGNED CHECKED
TITLE FOUNDATION & COLUMN DESIGN FOR CRB
GS KN
Check against one way shear @ X direction
Depth of footing D = 300
Effective depth ( d' ) = 300 - 50 -12-6 = 232

Shear force at critical section, V = 8.5639 x 1x (0.76 - 0.232) = 4.52


Cantilever length = 0.76

Critical section for shear is at a distance 'd' from the face of the column = 0.76
= 0.528

Effective depth at critical sction d' = 0.232


(Ref .Cl.No.40.1 in IS 456-2000)

Nominal shear stress at critical section, tv = V / (b' x d')


(4.52 x 2 x 9.81 x 10^3) / (1000 x 232) = 0.38

Percentage of reinforcement at critical section = = [753.98 / ( 1000 x 232 )] x 100


=

Corresponding shear stress tc = 0.409 > 0.38


Hence Safe

Design Summary:-
Length of footing = 1750 mm
Breath of footing = 1750 mm
Thickness of footing = 300 mm
Reinforcement
Bottom of Footing:-
In Z-direction = 12 mm diameter @ 150 C/C (Bottom )
In X-direction = 12 mm diameter @ 150 C/C (Bottom )
Top of footing
In Z-direction = 12 mm diameter @ 150 C/C (Top )
In X-direction = 12 mm diameter @ 150 C/C (Top )
CUMENT NO DATE
-NLC-SWYD-F&C-018 06.03.18
CHECKED REV
KN 0
12)

mm

25.9035 T/m2

x 2.5995 / (1.75 x 1.75^2)


x 0.4652 / (1.75 x 1.75^2)
± 0.52

K < 25.9035 Ton./sqm


CUMENT NO DATE
-NLC-SWYD-F&C-018 06.03.18
CHECKED REV
KN 0

mm2
mm2

mm2

m
CUMENT NO DATE
-NLC-SWYD-F&C-018 06.03.18
CHECKED REV
KN 0
tm
mm
N/mm2

mm2
mm2
mm2

mm2
mm2

mm
mm
ton
m

- 0.244
m

V / (b' x d')
N/mm2

[753.98 / ( 1000 x 244 )] x 100

N/mm2

KN
m
mm2

N/mm²
two way shear
CUMENT NO DATE
-NLC-SWYD-F&C-018 06.03.18
CHECKED REV
KN 0

mm
mm

ton
m

- 0.232
m

V / (b' x d')
N/mm2

53.98 / ( 1000 x 232 )] x 100


0.320

N/mm2
CLIENT M/S. REFEX ENERGY LIMITED
DOCUMENT NO
PROJECT SOLAR PV POWER PLANT OF 50MW AC
1617101-RFX-NLC-SWYD-F&C-018
DESIGNED CHECKED
TITLE FOUNDATION & COLUMN DESIGN FOR CRB
GS KN
3.3 DESIGN OF FOOTING -F3 (Load case 112) & (Node No 5)

DESIGN DATA:-
Depth of foundation from FGL = 2.00 m
Footing size = 2.00 m x 2.00
X-dir Z-dir
Thickness of footing at edge = 300 mm
Thickness of footing at face of column = 300 mm
Projection around column = ###mm
Column size = 230 mm x 300
X-dir Z-dir
MATERIAL PROPERTIES:-
Compressive Strength of Concrete = 25 N/mm2
Grade of steel = Fe 500
Density of concrete = 2.5 T/m3
Density of soil = 1.733 T/m3
Co efficient of friction = 0.50

FACTOR OF SAFETY:-
For strength design = 2.00
FX = 1.127 Ton.
FZ = 0.4 Ton
P = 24.4 Ton
Mx = 0.3 Ton.m
Mz = 1.5 Ton.m
FINAL VALUE FOR DESIGN
Vertical load P = 24.4 Ton
Bending Moment Z-direction Mx = 0.3 Ton.m
Bending Moment X-direction Mz = 1.5 Ton.m

CALCULATIONS
Volume of footing = 1.32 m3
Volume of soil = 6.68 m3
a) Wt of footing = 3.3 Ton
b) Wt of soil = 11.58 Ton
Total vertical load = 24.3952 + 3.3 + 11.58
= 39.28 Ton
Net SBC at 2 m depth = 17.95 T/m2
Gross SBC at 2 m depth = = 17.95x1.25+2x1.733 =

Bearing pressure = 39.28 / (2 x 2) ± 6 x 0.3039 / (2 x 2^2)


± 6 x 1.4652 / (2 x 2^2)
= 9.82 ± 0.23

Bearing pressure at footing P1 = 11.15 Ton./sqm OK < 25.9035 Ton./s


four corners P2 = 8.95 Ton./sqm
P3 = 10.69 Ton./sqm
P4 = 8.49 Ton./sqm
CLIENT M/S. REFEX ENERGY LIMITED
DOCUMENT NO
PROJECT SOLAR PV POWER PLANT OF 50MW AC
1617101-RFX-NLC-SWYD-F&C-018
DESIGNED CHECKED
TITLE FOUNDATION & COLUMN DESIGN FOR CRB
GS KN

Pressure due to over burden soil and raft


( 0.30 + 0.30 )/ 2 x 2.5
( 1.70 + 1.70 )/ 2 x 1.733
= 3.6961
Net pmax = 7.4539 T/m2
Net pmin = 1.496 T/m2

0.23

0.23 FGL FGL


2.00

2.00
0.885 0.885

0.30

2.00 2.00
PLAN SECTION

CHECK FOR FLEXURE ABOUT Z DIRECTION


Net pressure at edge = 7.4539 t/m2

Thickness of footing at column face = 300 mm

Effective depth of footing at z direction, d = 300 - 50 - 6 = 244 mm

Cantilever span of slab from column face = (2 - 0.3) / 2 = 0.85 m

Moment (max) at face of column = 7.4539 x 0.85 ^ 2 / 2 = 2.69 tm

Mu/bd2 = (2.69 x 2 x 9.81x10^6) / (1000 x 244 ^2) = 0.89 N/mm2

pt = 0.214 % Ast = 0.214 x1000 x 244 / 100 = 522


Minimum pt = 0.12 % Ast = 0.12 x 1000 x 300 / 100 = 360
(Ref .Cl.No.26.5.2.1 in IS 456-2000)
PROVIDE 12 TOR @ 100 c/c at bottom , (Ast) = 1131
SAFE
CHECK FOR FLEXURE ABOUT X DIRECTION
Cantilever span of slab from column face = (2 - 0.23) / 2 = 0.885
CLIENT M/S. REFEX ENERGY LIMITED
DOCUMENT NO
PROJECT SOLAR PV POWER PLANT OF 50MW AC
1617101-RFX-NLC-SWYD-F&C-018
DESIGNED CHECKED
TITLE FOUNDATION & COLUMN DESIGN FOR CRB
GS KN
Moment (max) at face of column = 7.4539 x 0.885 ^ 2 / 2 = 2.92
Effective depth of footing at x direction, d = 300 - 50 - 12 - 12/2 = 232
Mu/bd2 = (2.92 x 2x 9.81 x 10^6) / (1000 x 232 ^2) = 1.06

pt = 0.257 % Ast = 0.257 x1000 x 232 / 100 = 596


Minimum pt = 0.12 % Ast = 0.12 x 1000 x 300 / 100 = 360
PROVIDE 12 TOR @ 100 c/c at bottom , (Ast = 1131
(Ref .Cl.No.26.5.2.1 in IS 456-2000) SAFE

Provide nominal reinforcement @ top


Minimum pt = 0.06 % = 0.06 x 1000 x 300 / 100 = 180
PROVIDE 12 TOR @ 100 c/c bothways a, (Ast = 1131
SAFE

CHECK AGAINST ONE WAY SHEAR @ Z DIRECTION


Depth of footing = 300
Effective depth = 300 - 50 - 6 = 244
Shear force at critical section, V = 7.4539 x 1x (0.85 - 0.244) = 4.52
Cantilever length = 0.85
Critical section for shear is at a
distance 'd' from the face of the
pedestal = 0.85
= 0.606

Effective depth at critical sction d' = 0.244


(Ref .Cl.No.40.1 in IS 456-2000)
Nominal shear stress at critical section, tv = = V / (b' x d')
(4.52 x 2 x 9.81 x 10^3) / (1000 x 244) = 0.36

Percentage of reinforcement at critical section = [1130.97 / ( 1000 x 244 )]


= 0.460
Corresponding shear stress = tc 0.507 > 0.36
(Ref .Table 19. in IS 456-2000) Hence Safe
CHECK FOR TWO WAY SHEAR AT 'D/2' FROM THE PEDESTAL FACE
Maximum axial load on pedestal = 239.3
Effective depth at critical section = 0.24
Area resisted by shear stress = 496784
Actual punching shear = 0.723
Permissible stress in two way shear = 0.25 × √25 = 1.250
(Ref .Cl.31.6.3. in IS 456-2000) Hence safe in two way shear
CLIENT M/S. REFEX ENERGY LIMITED
DOCUMENT NO
PROJECT SOLAR PV POWER PLANT OF 50MW AC
1617101-RFX-NLC-SWYD-F&C-018
DESIGNED CHECKED
TITLE FOUNDATION & COLUMN DESIGN FOR CRB
GS KN
Check against one way shear @ X direction
Depth of footing D = 300
Effective depth ( d' ) = 300 - 50 -12-6 = 232

Shear force at critical section, V = 7.4539 x 1x (0.885 - 0.232) = 4.87


Cantilever length = 0.885

Critical section for shear is at a distance 'd' from the face of the column = 0.885
= 0.653
Effective depth at critical sction d' = 0.232
(Ref .Cl.No.40.1 in IS 456-2000)

Nominal shear stress at critical section, tv = V / (b' x d')


(4.87 x 2 x 9.81 x 10^3) / (1000 x 232) = 0.41

Percentage of reinforcement at critical section = = [1130.97 / ( 1000 x 232 )] x 10


=

Corresponding shear stress tc = 0.528 > 0.41


Hence Safe

Design Summary:-
Length of footing = 2000 mm
Breath of footing = 2000 mm
Thickness of footing = 300 mm
Reinforcement
Bottom of Footing:-
In Z-direction = 12 mm diameter @ 100 C/C (Bottom )
In X-direction = 12 mm diameter @ 100 C/C (Bottom )
Top of footing
In Z-direction = 12 mm diameter @ 100 C/C (Top )
In X-direction = 12 mm diameter @ 100 C/C (Top )
CUMENT NO DATE
-NLC-SWYD-F&C-018 06.03.18
CHECKED REV
KN 0
5)

mm

25.9035 T/m2

x 0.3039 / (2 x 2^2)
x 1.4652 / (2 x 2^2)
± 1.1

K < 25.9035 Ton./sqm


CUMENT NO DATE
-NLC-SWYD-F&C-018 06.03.18
CHECKED REV
KN 0

mm2
mm2

mm2

m
CUMENT NO DATE
-NLC-SWYD-F&C-018 06.03.18
CHECKED REV
KN 0
tm
mm
N/mm2

mm2
mm2
mm2

mm2
mm2

mm
mm
ton
m

- 0.244
m

V / (b' x d')
N/mm2

[1130.97 / ( 1000 x 244 )] x 100

N/mm2

KN
m
mm2

N/mm²
two way shear
CUMENT NO DATE
-NLC-SWYD-F&C-018 06.03.18
CHECKED REV
KN 0

mm
mm

ton
m

- 0.232
m
m

V / (b' x d')
N/mm2

130.97 / ( 1000 x 232 )] x 100


0.490

N/mm2
CLIENT M/S. REFEX ENERGY LIMITED
DOCUMENT NO
PROJECT SOLAR PV POWER PLANT OF 50MW AC
1617101-RFX-NLC-SWYD-F&C-018
DESIGNED CHECKED
TITLE FOUNDATION & COLUMN DESIGN FOR CRB
GS KN
3.3 DESIGN OF FOOTING -F3 (Load case 112) & (Node No 8)

DESIGN DATA:-
Depth of foundation from FGL = 2.00 m
Footing size = 2.00 m x 2.00
X-dir Z-dir
Thickness of footing at edge = 300 mm
Thickness of footing at face of column = 300 mm
Projection around column = ###mm
Column size = 230 mm x 300
X-dir Z-dir
MATERIAL PROPERTIES:-
Compressive Strength of Concrete = 25 N/mm2
Grade of steel = Fe 500
Density of concrete = 2.5 T/m3
Density of soil = 1.733 T/m3
Co efficient of friction = 0.50

FACTOR OF SAFETY:-
For strength design = 2.00
FX = 1.070 Ton.
FZ = 0.3 Ton
P = 23.0 Ton
Mx = 0.2 Ton.m
Mz = 1.4 Ton.m
FINAL VALUE FOR DESIGN
Vertical load P = 23.0 Ton
Bending Moment Z-direction Mx = 0.2 Ton.m
Bending Moment X-direction Mz = 1.4 Ton.m

CALCULATIONS
Volume of footing = 1.32 m3
Volume of soil = 6.68 m3
a) Wt of footing = 3.3 Ton
b) Wt of soil = 11.58 Ton
Total vertical load = 23.0413 + 3.3 + 11.58
= 37.92 Ton
Net SBC at 2 m depth = 17.95 T/m2
Gross SBC at 2 m depth = = 17.95x1.25+2x1.733 =

Bearing pressure = 37.92 / (2 x 2) ± 6 x 0.2352 / (2 x 2^2)


± 6 x 1.3951 / (2 x 2^2)
= 9.48 ± 0.18

Bearing pressure at footing P1 = 10.71 Ton./sqm OK < 25.9035 Ton./s


four corners P2 = 8.61 Ton./sqm
P3 = 10.35 Ton./sqm
P4 = 8.25 Ton./sqm
CLIENT M/S. REFEX ENERGY LIMITED
DOCUMENT NO
PROJECT SOLAR PV POWER PLANT OF 50MW AC
1617101-RFX-NLC-SWYD-F&C-018
DESIGNED CHECKED
TITLE FOUNDATION & COLUMN DESIGN FOR CRB
GS KN

Pressure due to over burden soil and raft


( 0.30 + 0.30 )/ 2 x 2.5
( 1.70 + 1.70 )/ 2 x 1.733
= 3.6961
Net pmax = 7.0139 T/m2
Net pmin = 1.596 T/m2

0.23

0.23 FGL FGL


2.00

2.00
0.885 0.885

0.30

2.00 2.00
PLAN SECTION

CHECK FOR FLEXURE ABOUT Z DIRECTION


Net pressure at edge = 7.0139 t/m2

Thickness of footing at column face = 300 mm

Effective depth of footing at z direction, d = 300 - 50 - 6 = 244 mm

Cantilever span of slab from column face = (2 - 0.3) / 2 = 0.85 m

Moment (max) at face of column = 7.0139 x 0.85 ^ 2 / 2 = 2.53 tm

Mu/bd2 = (2.53 x 2 x 9.81x10^6) / (1000 x 244 ^2) = 0.83 N/mm2

pt = 0.199 % Ast = 0.199 x1000 x 244 / 100 = 486


Minimum pt = 0.12 % Ast = 0.12 x 1000 x 300 / 100 = 360
(Ref .Cl.No.26.5.2.1 in IS 456-2000)
PROVIDE 12 TOR @ 100 c/c at bottom , (Ast) = 1131
SAFE
CHECK FOR FLEXURE ABOUT X DIRECTION
Cantilever span of slab from column face = (2 - 0.23) / 2 = 0.885
CLIENT M/S. REFEX ENERGY LIMITED
DOCUMENT NO
PROJECT SOLAR PV POWER PLANT OF 50MW AC
1617101-RFX-NLC-SWYD-F&C-018
DESIGNED CHECKED
TITLE FOUNDATION & COLUMN DESIGN FOR CRB
GS KN
Moment (max) at face of column = 7.0139 x 0.885 ^ 2 / 2 = 2.75
Effective depth of footing at x direction, d = 300 - 50 - 12 - 12/2 = 232
Mu/bd2 = (2.75 x 2x 9.81 x 10^6) / (1000 x 232 ^2) = 1.00
pt = 0.242 % Ast = 0.242 x1000 x 232 / 100 = 561
Minimum pt = 0.12 % Ast = 0.12 x 1000 x 300 / 100 = 360
PROVIDE 12 TOR @ 100 c/c at bottom , (Ast = 1131
(Ref .Cl.No.26.5.2.1 in IS 456-2000) SAFE

Provide nominal reinforcement @ top


Minimum pt = 0.06 % = 0.06 x 1000 x 300 / 100 = 180
PROVIDE 12 TOR @ 100 c/c bothways a, (Ast = 1131
SAFE

CHECK AGAINST ONE WAY SHEAR @ Z DIRECTION


Depth of footing = 300
Effective depth = 300 - 50 - 6 = 244
Shear force at critical section, V = 7.0139 x 1x (0.85 - 0.244) = 4.25
Cantilever length = 0.85
Critical section for shear is at a
distance 'd' from the face of the
pedestal = 0.85
= 0.606

Effective depth at critical sction d' = 0.244


(Ref .Cl.No.40.1 in IS 456-2000)
Nominal shear stress at critical section, tv = = V / (b' x d')
(4.25 x 2 x 9.81 x 10^3) / (1000 x 244) = 0.34

Percentage of reinforcement at critical section = [1130.97 / ( 1000 x 244 )]


= 0.460
Corresponding shear stress = tc 0.507 > 0.34
(Ref .Table 19. in IS 456-2000) Hence Safe
CHECK FOR TWO WAY SHEAR AT 'D/2' FROM THE PEDESTAL FACE
Maximum axial load on pedestal = 226.0
Effective depth at critical section = 0.24
Area resisted by shear stress = 496784
Actual punching shear = 0.682
Permissible stress in two way shear = 0.25 × √25 = 1.250
(Ref .Cl.31.6.3. in IS 456-2000) Hence safe in two way shear

Check against one way shear @ X direction


CLIENT M/S. REFEX ENERGY LIMITED
DOCUMENT NO
PROJECT SOLAR PV POWER PLANT OF 50MW AC
1617101-RFX-NLC-SWYD-F&C-018
DESIGNED CHECKED
TITLE FOUNDATION & COLUMN DESIGN FOR CRB
GS KN
Depth of footing D = 300
Effective depth ( d' ) = 300 - 50 -12-6 = 232

Shear force at critical section, V = 7.0139 x 1x (0.885 - 0.232) = 4.58


Cantilever length = 0.885

Critical section for shear is at a distance 'd' from the face of the column = 0.885
= 0.653

Effective depth at critical sction d' = 0.232


(Ref .Cl.No.40.1 in IS 456-2000)

Nominal shear stress at critical section, tv = V / (b' x d')


(4.58 x 2 x 9.81 x 10^3) / (1000 x 232) = 0.39

Percentage of reinforcement at critical section = = [1130.97 / ( 1000 x 232 )] x 10


=

Corresponding shear stress tc = 0.528 > 0.39


Hence Safe

Design Summary:-
Length of footing = 2000 mm
Breath of footing = 2000 mm
Thickness of footing = 300 mm
Reinforcement
Bottom of Footing:-
In Z-direction = 12 mm diameter @ 100 C/C (Bottom )
In X-direction = 12 mm diameter @ 100 C/C (Bottom )
Top of footing
In Z-direction = 12 mm diameter @ 100 C/C (Top )
In X-direction = 12 mm diameter @ 100 C/C (Top )
CUMENT NO DATE
-NLC-SWYD-F&C-018 06.03.18
CHECKED REV
KN 0
8)

mm

25.9035 T/m2

x 0.2352 / (2 x 2^2)
x 1.3951 / (2 x 2^2)
± 1.05

K < 25.9035 Ton./sqm


CUMENT NO DATE
-NLC-SWYD-F&C-018 06.03.18
CHECKED REV
KN 0

mm2
mm2

mm2

m
CUMENT NO DATE
-NLC-SWYD-F&C-018 06.03.18
CHECKED REV
KN 0
tm
mm
N/mm2
mm2
mm2
mm2

mm2
mm2

mm
mm
ton
m

- 0.244
m

V / (b' x d')
N/mm2

[1130.97 / ( 1000 x 244 )] x 100

N/mm2

KN
m
mm2

N/mm²
two way shear
CUMENT NO DATE
-NLC-SWYD-F&C-018 06.03.18
CHECKED REV
KN 0
mm
mm

ton
m

- 0.232
m

V / (b' x d')
N/mm2

130.97 / ( 1000 x 232 )] x 100


0.490

N/mm2
CLIENT M/S. REFEX ENERGY LIMITED
DOCUMENT NO
PROJECT SOLAR PV POWER PLANT OF 50MW AC
1617101-RFX-NLC-SWYD-F&C
DESIGNED
TITLE FOUNDATION & COLUMN DESIGN FOR CRB
GS

COLUMN REINFORCEMRNT SUMMARY


Col.Length
Cl.NO Node No. COLUMN No. Breath in mm Depth in mm Reinft (sq.mm)
(mm)
1 2450 230 300 552
C1 1 57 2500 230 300 552
43 1000 230 300 1395

2 2450 300 230 583


C2 2 58 2500 300 230 577
44 1000 300 230 999

3 2450 300 230 552


C2 3 59 2500 300 230 552
45 1000 300 230 685

4 2450 230 300 552


C1 4 60 2500 230 300 552
46 1000 230 300 1066

5 2450 230 300 552


C3 5 61 2500 230 300 560
54 1000 230 300 1804

6 2450 300 230 552


C4 6
53 3500 300 230 1061

7 2450 300 230 552


C4 7
52 3500 300 230 832

8 2450 230 300 552


64 2500 230 300 552
C3 8
79 350 230 300 552
47 650 230 300 1635

9 2450 230 450 828


C5 9 65 2500 230 450 828
51 1000 230 450 3231

10 2450 300 230 555


C6 10 66 2500 300 230 829
50 1000 300 230 2060

11 2450 300 230 552


C6 11 67 2500 300 230 700
49 1000 300 230 1480

12 2450 230 450 828


68 2500 230 450 828
C5 12
C5 12
80 350 230 450 828
48 650 230 450 2857
ITED
DOCUMENT NO DATE
1617101-RFX-NLC-SWYD-F&C-018 06.03.18
DESIGNED CHECKED REV
GS KN 0
DIA OF BAR

Reinft
###
4 16 ###
NOS + DIA 1608.50
4 16 OK

4 12 ###
NOS + DIA 1256.64
4 16 OK

4 12
NOS + DIA 1256.64
4 16 OK

4 16
NOS + DIA 1608.50
4 16 OK

4 16
NOS + DIA 2060.88
4 20 OK

4 12
NOS + DIA 1256.64
4 16 OK

4 12
NOS + DIA 1256.64
4 16 OK

4 20
+ 2060.88
NOS DIA
OK
4 16

8 20
NOS + DIA 3317.52
4 16 OK

4 20
NOS + DIA 2060.88
4 16 OK

4 20
NOS + DIA 2060.88
4 16 OK

8 20
+ 3317.52
NOS DIA
+
NOS DIA
OK