Ground Source Heat Pumps

1
Ground Source Heat Pumps
R407C R22

Reusable
Ground Source Heat Pump use solar energy stored in earth as
cooling/heating energy, and convert energy for heating and air
condition system. Ground source heat pump is a new technol-
ogy that use clean and reusable energy sources. Surface of soil
and water are a giant solar energy concentrator. Collectable
solar energy is 500 times more than energy used (underground
water accepts sun radiation from soil indirectly). It is a huge
dynamic energy balance system. The surface of soil and water
can accept and send out energy to keep balance naturally.
Successfully to use Ground Source Heat Pump technology
makes using unlimited energy from earth become true.

Efficiency
GSHP uses ground and water temperature 12-22°C in winter. The temperature is higher than environment temperature. The cycled
Heat pump increase evaporates temperature; GSHP uses ground and water temperature 18-32°C in summer. The temperature is
lower than environment temperature. Cooling system drops temperature very efficient and better than air cooling and condensing
tower. The efficiency of the unit is greatly improved. It can save about 30-40% operating expensive. Using 1KW electrical energy can
generate 4KW and more heat or 5KW and more Cooling energy.

Great Environmental and Economic Benefit


When operate GSHP, it doesnt consume and pollute the water. It doesnt need boiler, cooling tower and space for burning and
wasted material. It is perfect green environment. The power used of Ground Source Heat Pump is 40% less than air source heatpump,
and 70% less than electrical supply heating system. The efficiency of the heating system is higher than steam boiler 50% averagely,
and higher than burning oil furnace 75%.

Multi-Function in One Unit, Widely Usage Range .


GSHP can be used for heating, cooling, and also provide living water, it has multi-function in one unit. One set of the unit can replace
both boiler and air conditioner. GSHP has great advantage for the buildings where required heating and air conditioning. It not only
saves great energy, it also save equipment investment. GSHP can be used in hotels, apartments, villa, factories, shopping centers,
office buildings, and schools. Small size of GSHP is especially suitable for luxury villas heating and air conditioning system.

Operation Automatically
Because of GSHP works steady, system designing is simple, 50 the unit operating is reliable, lower maintenance fee, high automatic
control and long life.

The Working Principle


The compressor suck low pressures overheat condensing medium steam from dry evaporator. After compressing, it becomes high

2
temperature, high-pressure condensing gas. It passes by exhausting pipe and goes into condenser, and then heat energy transmit to
cooling water and generate heat water. The cooling medium of high temperature, high pressure is converted to cooling medium of normal
temperature, high pressure, and liquid status. After the liquid-status cooling medium from condenser eliminate water and impurity by
dry filter, goes through magnetic valve, expansion valve, throttle, and lower pressure, finally goes into evaporator. In evaporator, low
temperature, low-pressure liquid condensing medium absorbs heat from cycled cooling water continuously. When arriving to outlet of
evaporator, it totally becomes low temperature, low-pressure over heat gas, than return to compressor for next cycling. In this way,
Condensing medium is condensed by dry evaporator, is discharged from outlet of evaporator, and then goes into required air condition
zone, and so on to achieve heating or air conditioning.

The Product Technical Character


Environment

For heating, GSHP may replace boiler system. There is no burning process, so it avoids exhausting polluted smoking; for air conditioning,
GSHP may replace cooling tower. There is no condensing tower, so it avoids the noises and leaf mold. It makes excellent environment.

Save Energy

GSHP uses 1KW electrical energy to generate 4KW heating energy in winter.
GSHP uses 1KW electrical energy to generate 5KW air conditioning energy in summer
The energy usage rate is 3-4 times of electric heating.

Save Space

It save the space for placing boiler, coal and burned waster.

Save Water

The water is carrier. The water absorbs or releases heating energy, in this way to achieve providing heating and air condition ing. It
consumes neither water source nor other pollution.

Save Capital Investment

One GSHP unit performs functions for both heating and air conditioning. Capital investment is 1/2-1/3 of traditional heating/c ooling
system investment, and operating fee is only 1/2 -1/3 of traditional way.

The Product Performance Character


Ground Source Heat Pumps
Optimize Design

-The designing follows the international standard completely, and also acceding to China practicality.

-The system is designed to use independence module with high reliability.

- Using technology ideal of great different in temperature, and small amount in flow , to save water source and lower operating expense.
Ground Source Heat Pumps

-Computerize designing to ensure the unit works in best condition in any time.

The Best Parts

-The compressor, and condensing parts are imported from abroad for the unit operation efficiency

- The high efficient heat exchanger is professional mating product that developed by honorable designing institute, manufacturer, and
-our company. It is special designed for GSHP.

High quality controller combine special control program of water source heat pump. It is convenience for the unit computerize and networking.

3
Product Guide 2005

CS-imple Operation, Reliable Function

(1)Controlled by computer, and for manual operation back up.

(2)Perfect computer control system, multi protection devices to makes it reliable.

D. Widely Usage Range

(1)The usage range of water source temperature is from 8-35°C .

(2)It can not only provide 7°C or 54°C cooling/heating water for air conditioning, living heating water, and also be used as heating source
for city region.

2.Advance Control Technology and Networking Function


Simply and clear information display
-Big crystal digital screen to display the status of the unit

-Automatic alarm system

-Prompt equipments maintenance information. Display input, output status of controller.

Flexible, Convenient Specification Setting.


-There are over eighty adjustable setting for the unit specifications

-Password operation to make sure the unit not be damaged by mistake

-The cut-off memory protection for lost power to guarantee operation status continuously.

Advanced Networking Function


-It is easy to connect into control system in the building and realize remote centralize control.-

-It is easy to connect networking printers and print various needed information at any times.

-The ports obligate for upgrade input/output. It is convenience for upgrade.

Nomenclature
Ground Source Heat Pumps

4
Cooling condition

(1)When cooling system work, the well becomes


exhausting heat source; the condensing medium
absorbs heat and evaporates in the evaporator.
After make water cooled in temperature 7°C , the
cooled water is sent into rooms. The condensing
medium is sent into compressor again and forms
high pressure, high temperature overheat steam,
then it goes into condenser, and bring out heat by
well water.

Heating condition

(2)When heating system work, the well becomes


absorbing source; the condensing medium absorbs
Ground Source Heat Pumps

the well water heat and evaporates in evaporator.


The well water returns to well. The condensing
medium is sent into compressor again and forms
high pressure, high temperature overheat steam,
then it goes into condenser, heat cycled water, and
makes 45°C - 50°C hot water

5
Product Guide 2005

GSHP Series Small Size Ground Source Heat Pump

Technical Data
Model GSHP15 GSHP25 GSHP30 GSHP40 GSHP60 GSHP80

Nominal cooling capacity kW 11.5 22.5 25 30 50 60

Nominal heating capacity kW 13.0 25.5 29.5 34.0 59 68

Power supply 380V/3PH/50Hz

Power steps 0% 100% 0% 50% 100%


Compressor

Type Hermetic scroll

Comp. qty. Set 1 1 1 1 2 2

Input power (cool/heat) kW 2.55/2.80 3.8/6.2 4.5/7.2 4.8/7.8 9/14.4 9.6/15.6


Refrigerant

Refrigerant R22/R407C/R134a

Charge amount kg 2.65 5 5.5 6.6 11.0 13.2

Type Double pipe heat exchanger


Evaporator

Pressure drop water side kPa 40 40 42 742 42 42

Fouling factor m2 /KW 0.086

Water connection mm DN25 DN32 DN40 DN40 DN65 DN65

Water flow during cooling m3/h 1.98 3.84 4.27 5.12 8.54 10.24

Type Double pipe heat exchanger


Condenser

Pressure drop water side kPa 45 50 50 45 45 45

Fouling factor m2 /KW 0.086

Water connection mm DN25 DN32 DN40 DN40 DN65 DN65

Water flow during heating m3/h 1.72 3.24 3.63 4.52 7.26 9.04

Length 1028 1445


Dimension

mm 1120 1120 1365 1445

Width mm 740 740 740 840 940 940

Height mm 1028 1028 1028 1028 1128 1128

Weight Kg 225 250 300 320 450 600

Sound pressure level db(A) 50 55 57 58 60 60

Note: 1. Cooling capacity of the unit and nominal working condition of the compressor:
Ground Source Heat Pumps

The temperature of cooling water input water is 20°C , output water is 30°C .
The temperature of condensing water input water is 12°C , output water is 7°C .

2. Heating capacity of the unit and nominal working condition of the compressor :
The temperature of cooling water input water is 40°C , output water is 45°C .
The temperature of condensing water input water is 16°C , output water is 9°C .

3. Specifications are subject to change without prior notice:

6
GSHP Ground Source Heat Pump Main Technical Specifications

Unit Model GSHP130 GSHP150 GSHP180 GSHP220 GSHP280 GSHP350

Cooling capacity KW 130 150 180 221 278 348

Heating capacity KW 174 189 211 253 336 436

Power supply Three phases 380V 50Hz

Energy control 50 100 25 100

Type
Compressor

Herrmatic scroll compressor Semi-hermatic screw compressor

Amoumt Unit 2 2 1 1 1 1

Imput power (Cooling heating) kW 25/30 29/35 35.4/48.2 42.9/57.7 57/76.1 73.5/99.5

Refrigerant
Medium
Cooling

R22/R407C/R134a

Adding amoumt kg 28 33 40 48 62 77

Model Shell-pipe heat exchanger

Water resistant kPa 50 50 45 45 45 50


Evaporator

Foul coefficient m2 /KW 0.086

Connected pipe specification mm DN80 DN80 DN80 DN80 DN100 DN100

Cooling capacing in cooling m3/h 22.3 25.8 31.0 37.8 48.2 60.2

Cooling capacing in heating m3/h 14.7 17.2 18.6 22.5 29.9 38.6

Model Shell-pipe heat exchanger


Condensing Medium

Water sistant kPa 50 50 45 45 45 50

Foul coeffient m2 /KW 0.086

Pipe connected specification mm DN80 DN80 DN80 DN80 DN100 DN125

Capacity cooling in cooling capacy m3/h 14.0 16.1 19.4 23.7 30.1 37.6

Capacity Cooling in hating m3/h 28.4 31.0 34.4 41.3 54.9 71.2

Length mm 3310 3310 3100 3100 3150 3480


Outline size

Width mm 860 860 1000 1000 1100 1100

Height mm 1618 1793 1818 1818 2090 2090

Unit weight kg 1460 1600 1800 1900 2200 2640

Noise dB(A) 68 68 69 69 71 71

Suggest cable size mm2 3 10+2 4 3 16+2 6 3 35+2 16 3 50+2 25 3 50+2 25 3 70+2 35
Ground Source Heat Pumps

Note: 1. Cooling capacity of the unit and nominal working condition of the compressor:
The temperature of cooling water input water is 20°C , output water is 30°C .
The temperature of condensing water input water is 12°C , output water is 7°C .

2. Heating capacity of the unit and nominal working condition of the compressor :
The temperature of cooling water input water is 40°C , output water is 45°C .
The temperature of condensing water input water is 16°C , output water is 9°C .

3. Specifications are subject to change without prior notice:

7
Product Guide 2005

GSHP Ground Source Heat Pump Main Technical Specificatioon

Unit Model GSHP430 GSHP480 GSHP540 GSHP700 GSHP780 GSHP860

Cooling capacity KW 430 480 538 700 780 860

Heating capacity KW 519 554 661 872 955 1038

Power supply Three phases 380V 50Hz

Energy control 25 100 12.5 100

Type Semi-hermatic screw compressor


Compressor

Amoumt Unit 1 1 1 2 2 2

Imput power (Cooling heating) 88.9/117.5 91.7/124.8 109/148 147/198 162/217 176/234
Medium
Cooling

Refrigerant R22/R407C/R134a

Fillinagmoumt kg 95 106 120 155 173 191

Model R22 Shell-pipe heat exchanger

Water resistant kPa 45 45 45 50 5 50


Evaporator

Foul coefficient m2 /KW 0.086

Connected pipe specification mm DN100 DN100 DN125 DN125 DN150 DN150

Cooling capacing in cooling m3/h 74.0 82.6 92.9 120.4 134.2 147.9

Cooling capacing in heating m3/h 46.2 49.4 59.0 77.2 84.8 92.4

Model Shell-pipe heat exchanger


Condensing Medium

Water sistant kPa 45 45 45 50 5 50

Foul coeffient m2 /KW 0.086

Pipe connected specification mm DN125 DN125 DN125 2-DN100 2-DN125 2-DN125

Capacity cooling in cooling capacy m3/h 46.2 51.6 58.1 75.3 83.9 92.5

Capacity Cooling in hating m3/h 84.8 90.5 108.0 142.4 156.0 169.6

Length 3586 3800 4100 4484 4600 4600


Outline size

mm

Width mm 1174 1150 1150 1383 1450 1450

Height mm 2170 2057 2317 2190 2300 2300

Unit weight kg 3250 3550 3750 3890 4210 4740

Noise dB(A) 73 73 73 74 74 74

Suggest cable size mm2 3 95+2 50 3 95+2 50 3 95+2 50 3 150+2 70 2 (3 95+2 50) 2 (3 95+2 50)
Ground Source Heat Pumps

Note: 1. Cooling capacity of the unit and nominal working condition of the compressor:
The temperature of cooling water input water is 20°C , output water is 30°C .
The temperature of condensing water input water is 12°C , output water is 7°C .

2. Heating capacity of the unit and nominal working condition of the compressor :
The temperature of cooling water input water is 40°C , output water is 45°C .
The temperature of condensing water input water is 16°C , output water is 9°C .

3. Specifications are subject to change without prior notice:

8
GSHP Ground Source Heat Pump Main Technical Specification

Unit Model GSHP960 GSHP1020 GSHP1080 GSHP1200 GSHP1320

Cooling capacity KW 958 1020 1080 1200 1320

Heating capacity KW 1107 1215 1322 1468 1615

Power supply Three phases 50Hz

Energy control 12.5% 100%

Type Semi-hermatic scroll compressor


Compressor

Amoumt Unit 2 2 2 2 2

Imput power (Cooling heating) 182/249.6 200/272 218/296 241.7/330.7 265.4/365.4

Refrigerant R22/R407C/R134a
Medium
Cooling

Filling amoumt kg 212 226 240 266 293

Model Shell-pipe hest exchanger

Water resistant kPa 50 50 50 50 50


Evaporator

Foul coefficient m2 /KW 0.086

Connected pipe specification mm DN150 DN200 DN200 DN200 DN200

Cooling capacing in cooling m3/h 165.1 175.4 185.8 206.4 227.0

Cooling capacing in heating m3/h 98.8 108.4 118.0 171.4 188.5

Model Shell-pipe hest exchanger


Condensing Medium

Water sistant kPa 50 50 50 50 50

Foul coeffient m2 /KW 0.086

Pipe connected specification mm 2-DN125 2-DN150 2-DN150 2-DN150 2-DN150

Capacity cooling in cooling capacy m3/h 103.2 109.7 116.1 129.0 141.9

Capacity Cooling in hating m3/h 181.0 198.5 216.0 240.0 264.0

Length mm 4800 4800 4776 4800 5000


Outline size

Width mm 1500 1560 1566 1570 1570

Height mm 2300 2450 2524 2550 2550

Unit weight kg 5600 6600 6800 8500 9000

Noise dB(A) 75 75 76 78 81

Suggest cable size mm2 2 (3 95+2 50) 2 (3 95+2 50) 2 (3 95+2 50) 2 (3 120+2 70) 2 (3 120+2 70)
Ground Source Heat Pumps

Note: 1. Cooling capacity of the unit and nominal working condition of the compressor:
The temperature of cooling water input water is 20°C , output water is 30°C .
The temperature of condensing water input water is 12°C , output water is 7°C .

2. Heating capacity of the unit and nominal working condition of the compressor :
The temperature of cooling water input water is 40°C , output water is 45°C .
The temperature of condensing water input water is 16°C , output water is 9°C .

3. Specifications are subject to change without prior notice:

9
Product Guide 2005
Dimensions

1120
3634
1811
1020
2300
244
2670
525
350
465
830
269
668

1120
3364
1805
1020
1900
224
2470
525
350
495
830
270
670

1100
3039
1633
1000
1650
235

1100
2870
1545
1000
1460
222
1936
485
350
424
612
270
480

1800
900
1000
3134
1430
224

Model GSHP GSHP GSHP GSHP GSHP GSHP GSHP GSHP GSHP
Code 130 150 180 220 280 350 430 480 540
A 1680 1780 1450 1800 1460 1650 1900 2300 1730
B 700 760 900 900 1000 1000 1020 1020 1200
C 1430 1402 1411 1991
Ground Source Heat Pumps

1430 1545 1633 1805 1811


D 2971 3179 2807 3134 2870 3039 3364 3634 3151
E 800 860 1000 1000 1100 1100 1120 1120 1300
F 455 456 216 224 222 235 224 244 248
G 2078 2220 2030 2410 1936 2090 2470 2670 2170
H 439 502 571 499 480 714 670 668 732
J 263 215 220 259 270 270 270 269 250
K 515 510 530 542 612 677 830 830 717
L 393 302 378 374 424 409 495 465 490
M 250 300 330 302 350 352 350 350 400
N 329 370 399 435 485 475 525 525 554

10
Dimensions

Model GSHP700 GSHP780 GSHP860 GSHP960 GSHP1020 GSHP1080 GSHP1200 GSHP1320


Code
A 1900 1800 2150 2150 2150 2150 2150 2150
B 1200 1200 1100 1100 1100 1100 1200 1200
C 2032 2032 2116 2133 2269 2269 2386 2386
D 4333 4549 4482 4486 4784 4784 4817 4817
E 1308 1300 1300 1300 1300 1300 1467 1467
F 698 674 673 702 700 700 716 716
G 2940 3200 3140 3082 3380 3380 3382 3382
H 697 674 673 702 702 702 717 717
J 435 3200 325 325 325 325 380 380
K 465 465 450 450 450 450 550 550
L 400 350 325 325 325 325 270 270
M 268 255 215 215 235 235 285 285
N 196 220 270 270 270 270 228 228
O 1049 1049 1115 1105 1155 1155 1221 1221
P 400 400 380 450 450 450 550 550
Ground Source Heat Pumps

Q 240 208 241 171 171 171 215 215


R 900 1050 785 785 885 885 877 877
S 316 324 383 383 433 433 456 456

11
Price

VAT not included

Cooling
No. Type Model Power supply Refrigerant Unit Price
Capacity(kw) (€)
1 Heat pump GSHPC10 380/3/50Hz R407C 12,5 2.180 Ä
2 Heat pump GSHPC20 380/3/50Hz R407C 22,5 4.086 Ä
3 Heat pump GSHPC30 380/3/50Hz R407C 25 4.416 Ä
4 Heat pump GSHPC40 380/3/50Hz R407C 30 5.146 Ä
5 Heat pump GSHPC60 380/3/50Hz R407C 50 8.200 Ä
6 Heat pump GSHPC80 380/3/50Hz R407C 60 9.536 Ä
7 Heat pump GSHPC130 380/3/50Hz R407C 130 18.080 Ä
8 Heat pump GSHPC150 380/3/50Hz R407C 150 20.854 Ä
9 Heat pump GSHPC180 380/3/50Hz R407C 180 25.040 Ä
10 Heat pump GSHPC220 380/3/50Hz R407C 220 30.746 Ä
11 Heat pump GSHPC280 380/3/50Hz R407C 280 38.666 Ä
12 Heat pump GSHPC350 380/3/50Hz R407C 350 48.428 Ä
13 Heat pump GSHPC430 380/3/50Hz R407C 430 59.840 Ä
14 Heat pump GSHPC480 380/3/50Hz R407C 480 61.654 Ä
15 Heat pump GSHPC540 380/3/50Hz R407C 540 69.094 Ä
16 Heat pump GSHPC700 380/3/50Hz R407C 700 89.894 Ä
17 Heat pump GSHPC780 380/3/50Hz R407C 780 100.160 Ä
Ground Source Heat Pumps

18 Heat pump GSHPC860 380/3/50Hz R407C 860 110.426 Ä


19 Heat pump GSHPC960 380/3/50Hz R407C 960 123.014 Ä
20 Heat pump GSHPC1020 380/3/50Hz R407C 1020 130.986 Ä
21 Heat pump GSHPC1080 380/3/50Hz R407C 1080 138.694 Ä
22 Heat pump GSHPC1200 380/3/50Hz R407C 1200 154.108 Ä
23 Heat pump GSHPC1320 380/3/50Hz R407C 1320 169.520 Ä

12
13
Hydronic Fan Coil Units
Hydronic Fan Coil Units
Hydronic Fan Coil Units

14
Product Guide 2005

Brief Introduction Of Fan Coil


Bright Fan Coil Units are terminals of air conditioning system; it is widely used in central air conditioning system, where used in hotel,
office buildings, flats, hospitals, opera, exhibition hall, broadcast and TV buildings and civil architecture etc. especially in hospital

where need avoid air interchange between two rooms, for it can be controlled separately and is popular for hospitals.

Fan coil consist of fan, theat exchanger (coil), condenser water coil, filter and shell units. It includes cabinet, horizontal, suspended,

concealed, super thin and IAQ units etc. the units can be chosen by customers according to room structure, quantity of loading and
decorate character.

Unit frame
Galvanized sheet metal, All components are insulated against condensate with fire-retardant material.

Housing
Galvanized sheet metal with white gray plastic coating.

Grille
Plastic modular and adjustable grilles for adjustment of airflow.

Fan section
Electronically balanced centrifugal fans galvanized metal wheels and screw; independent from main structure for easy removal.

Motor
Single-phase with overload protection; three-speed.

Coils
Countercurrent with copper tubes and aluminum fins with hydrophilic oxidation film: three rows. Water connectors at right-hand
side.

Condensate drain pan


Pressing molded, with heat insulation material; easy discharge of the condensing water.

Air filter
Made from nylon, washable, easy to remove for cleaning.
Hydronic Fan Coil Units

Control box
Galvanized sheet metal frame; high/ med/ low adjustable; easy to install and maintain.

15
Fan Coil Unit Type

WITH PLENUM
NORMAL
HORIZONTAL WITHOUT PLENUM
CONCEALED
SERIES WITH REVERSE BOX
HIGH STATIC
VERTICAL WITHOUT REVERSE BOX

FAN
COIL

HORIZONTAL
VERTICAL 2-WAY DISCHARGE
SUSPENDED
SERIES CASSETTE 4-WAY DISCHARGE
WALL MOUNTED

FP-

Fan coil Z:High static type

Airflow

Water entering type:


Z:Left hand
Structure type Y:Right hand
DG:Wall mounted type
L:Floor standing type
XD:Cassette type Air inlet and discharge type
W:Horizontal type S:Top discharge
Q:Front discharge
X: Side discharge
XI:Below discharge
D:Bottom inlet
QU:Front inlet
H:Back inlet

Application
Hydronic Fan Coil Units

A:Concealed
AB:Concealed with low profile
M:Suspended

16
Product Guide 2005

General Technical Data

Model
FP-3.5 FP-5.0 FP-6.3 FP-7.1 FP-8.0 FP-10 FP-12.5 FP-16 FP-20
ltem

Air High 350 500 630 710 800 1000 1250 1600 2000

Flow Medium 300 420 540 600 680 850 1050 1350 1700
3
(m /h) Low 240 360 450 500 560 720 900 1150 1450

Cooling High 2000 2800 3500 4000 4500 5300 6600 8500 10600

capacity Medium 1800 2500 3200 3500 4000 4600 5800 7500 9200

(W) Low 1600 2200 2700 3100 3500 4100 5000 6500 8200

Heating High 3000 4200 5250 6000 6750 7950 9900 12750 15900

capacity Medium 2700 3750 4800 5300 6000 6800 8700 11250 13800

(W) Low 2400 3300 4000 4600 5300 6150 7500 9800 12300

Noise dB Hg C 35 30 36 30 37 32 37 32 37 33 39 35 41 37 42 39 42 40
(A) Lg H 37 32 39 32 40 33 40 33 40 34 41 36 43 38 44 40 44 41
Input High 30 33 40 50 65 80 96 140 180

power Medium 24 28 33 40 55 70 85 120 160

(W) Low 22 25 27 30 42 58 70 100 135


Water supply (kg/h) 350 500 700 700 800 1000 1250 1600 2000
Water resistance 1.52 2.02 2.7 3.2 3.68 4.32 3.04 3.74 4.76
(MH2O)

WA 18 19 20.5 22 23.5 27 29 30.5 36

WAB 15 16 17.5 19 20.5 24 25 27.5 36

Net LA 19.5 23.5 25 26 27.5 34.5 36 39.5 42

Weight LMS 26.5 31 31 34 34 43 45 48 50

(Kg) LMX 26.5 31 31 34 34 43 45 48 50

WM 27 31.5 31.5 34.5 34.5 43.5 45 46.5 48.5

XD 24 31 33.5 36 38.5 42 45 53 66

J 15 16 17.5 19 20.5 24 25 27.5 36


Inlet/outlet pipe 3/4 (Internal thread)

Discharging pipe Same side with water inlet/outlet WA, WAB, LA, LMS, LMX, WM, XD, J

Junction box position Same side with water inlet/outlet LMS,LMX,LA

1 Fan coil working pressure is under 1.2Mpa


2 Standard condition: cooling D.B.: t(d)=27°C, W.B.: t(w)=19.50C. Water inlet temperature: t=7°C Water
inlet and outlet temperature difference: t=50C, heat supply: 21°C D.B, heat water input temperature:
t=60°C
3 Noise figure is what we test where is 1m far from each unit surface.
Note
4 Rated airflow is tested when the outside temperature is 0Pa. And high static pressure is tested when
Hydronic Fan Coil Units

outside unit pressure difference is 50Pa.

5 Entering/ discharging tube is made with 3/4 if it doesn t inform us in advance.

17
PRICE
two pipes three rows
patten cooling capacityheating capacity air flow noise dimension price
pictures
7/12 °C(W) 60/55 °C(W) (mł/h) dB(A) L/W/H (mm) EURO

FP-3.4VEL 1800 2700 340 35 850/250/640 206


FP-5.1VEL 2700 4050 510 38 1000/250/640 226
FP-6.8VEL 3600 5400 680 40 1150/250/64 0 244

FP-8.5VEL 4500 6750 850 42 1350/250/640 266

FP-10.2VEL 5400 8100 1020 44 1500/250/640 286

FP-13.6VEL 7200 10800 1360 45 1650/250/640 360

FP-17.0VEL 9000 13500 1700 47 1950/250/640 406

FP-3.4VEOL 1800 2700 340 35 850/250/640 206

FP-5.1VEOL 2700 4050 510 38 1000/250/640 226

FP-6.8VEOL 3600 5400 680 40 1150/250/64 0 244

FP-8.5VEOL 4500 6750 850 42 1350/250/640 266

FP-10.2VEOL 5400 8100 1020 44 1500/250/640 286


FP-13.6VEOL 7200 10800 1360 45 1650/250/640 360

FP-17.0VEOL 9000 13500 1700 47 1950/250/640 406

FP-3.4NEL 1800 2700 340 35 850/250/540 200


FP-5.1NEL 2700 4050 510 38 1000/250/540 222
FP-6.8NEL 3600 5400 680 40 1150/250/54 0 241
FP-8.5NEL 4500 6750 850 42 1350/250/540 262
FP-10.2NEL 5400 8100 1020 44 1500/250/540 284
FP-13.6NEL 7200 10800 1360 45 1650/250/540 354
FP-17.0NEL 9000 13500 1700 47 1950/250/540 402

FP-3.4NEOL 1800 2700 340 35 850/250/540 196


FP-5.1NEOL 2700 4050 510 38 1000/250/540 214
FP-6.8NEOL 3600 5400 680 40 1150/250/54 0 234
FP-8.5NEOL 4500 6750 850 42 1350/250/540 250
FP-10.2NEOL 5400 8100 1020 44 1500/250/540 270
FP-13.6NEOL 7200 10800 1360 45 1650/250/540 340
FP-17.0NEOL 9000 13500 1700 47 1950/250/540 382

FP-3.4WEOFL 1800 2700 340 35 850/250/540 200


FP-5.1WEOFL 2700 4050 510 38 1000/250/540 222
FP-6.8WEOFL 3600 5400 680 40 1150/250/54 0 242
FP-8.5WEOFL 4500 6750 850 42 1350/250/540 262
FP-10.2WEOFL 5400 8100 1020 44 1500/250/540 284
FP-13.6WEOFL 7200 10800 1360 45 1650/250/540 354
FP-17.0WEOFL 9000 13500 1700 47 1950/250/540 402

FP-3.4WEAFL 1800 2700 340 35 850/250/540 196


FP-5.1WEAFL 2700 4050 510 38 1000/250/540 214
FP-6.8WEAFL 3600 5400 680 40 1150/250/54 0 234
FP-8.5WEAFL 4500 6750 850 42 1350/250/540 250
FP-10.2WEAFL 5400 8100 1020 44 1500/250/540 270
FP-13.6WEAFL 7200 10800 1360 45 1650/250/540 340
FP-17.0WEAFL 9000 13500 1700 47 1950/250/540 382
FP-3.4NCOL 1800 2700 340 35 600/230/506 152
FP-5.1NCOL 2700 4050 510 38 750/230/506 168
FP-6.8NCOL 3600 5400 680 40 900/230/506 182
FP-8.5NCOL 4500 6750 850 42 1050/230/506 196

FP-10.2NCOL 5400 8100 1020 44 1200/230/506 208


FP-13.6NCOL 7200 10800 1360 45 1350/230/506 274
FP-17.0NCOL 9000 13500 1700 47 1650/230/506 308

FP-20.4NCOL 10800 16200 2040 48 1950/230/506 332

FP-3.4NCOFL 1800 2700 340 35 600/230/506 152


FP-5.1NCOFL 2700 4050 510 38 750/230/506 168
FP-6.8NCOFL 3600 5400 680 40 900/230/506 182
FP-8.5NCOFL 4500 6750 850 42 1050/230/506 196
FP-10.2NCOFL 5400 8100 1020 44 1200/230/506 208
FP-13.6NCOFL 7200 10800 1360 45 1350/230/506 274

FP-17.0NCOFL 9000 13500 1700 47 1650/230/506 308


FP-20.4NCOFL 10800 16200 2040 48 1950/230/506 332

FP-3.4NCL 1800 2700 340 35 600/230/506 152


FP-5.1NCL 2700 4050 510 38 750/230/506 168
FP-6.8NCL 3600 5400 680 40 900/230/506 182
FP-8.5NCL 4500 6750 850 42 1050/230/506 196
FP-10.2NCL 5400 8100 1020 44 1200/230/506 208
FP-13.6NCL 7200 10800 1360 45 1350/230/506 274
FP-17.0NCL 9000 13500 1700 47 1650/230/506 308
FP-20.4NCL 10800 16200 2040 48 1950/230/506 332

FP-3.4NCFL 1800 2700 340 35 600/230/506 152


FP-5.1NCFL 2700 4050 510 38 750/230/506 168
FP-6.8NCFL 3600 5400 680 40 900/230/506 182
FP-8.5NCFL 4500 6750 850 42 1050/230/506 196
FP-10.2NCFL 5400 8100 1020 44 1200/230/506 208
FP-13.6NCFL 7200 10800 1360 45 1350/230/506 274
FP-17.0NCFL 9000 13500 1700 47 1650/230/506 308

FP-20.4NCFL 10800 16200 2040 48 1950/230/506 332

FP-3.4WCAFL 1800 2700 340 35 600/230/506 152


FP-5.1WCAFL 2700 4050 510 38 750/230/506 168
FP-6.8WCAFL 3600 5400 680 40 900/230/506 182
FP-8.5WCAFL 4500 6750 850 42 1050/230/506 196
FP-10.2WCAFL 5400 8100 1020 44 1200/230/506 208
FP-13.6WCAFL 7200 10800 1360 45 1350/230/506 274
FP-17.0WCAFL 9000 13500 1700 47 1650/230/506 308
FP-20.4WCAFL 10800 16200 2040 48 1950/230/506 332

FP-3.4WCOFL 1800 2700 340 35 600/230/506 152

FP-5.1WCOFL 2700 4050 510 38 750/230/506 168

FP-6.8WCOFL 3600 5400 680 40 900/230/506 182


FP-8.5WCOFL 4500 6750 850 42 1050/230/506 196
FP-10.2WCOFL 5400 8100 1020 44 1200/230/506 208
FP-13.6WCOFL 7200 10800 1360 45 1350/230/506 274
FP-17.0WCOFL 9000 13500 1700 47 1650/230/506 308
FP-20.4WCOFL 10800 16200 2040 48 1950/230/506 332
two pipes four rows
patten cooling capacity heating capacity air flow noise dimension price
pictures
7/12 °C(W) 60/55 °C(W) (mł/h) dB(A) L/W/H (mm) EURO

FP-3.4-VELF 2142 3213 316 35 850/250/640 220


FP-5.1-VELF 3213 4820 474 38 1000/250/640 242
FP-6.8-VELF 4284 6426 632 40 1150/250/64 0 264
FP-8.5-VELF 5355 8033 791 42 1350/250/640 286
FP-10.2-VELF 6426 9639 949 44 1500/250/640 310

FP-13.6-VELF 8568 12852 1265 45 1650/250/640 384

FP-17.0-VELF 10710 16065 1581 47 1950/250/640 438

FP-3.4-VEOLF 2142 3213 316 35 850/250/640 208


FP-5.1-VEOLF 3213 4820 474 38 1000/250/640 230
FP-6.8-VEOLF 4284 6426 632 40 1150/250/64 0 250
FP-8.5-VEOLF 5355 8033 791 42 1350/250/640 270
FP-10.2-VEOLF 6426 9639 949 44 1500/250/640 292
FP-13.6-VEOLF 8568 12852 1265 45 1650/250/640 366
FP-17.0-VEOLF 10710 16065 1581 47 1950/250/640 412

FP-3.4-NELF 2142 3213 316 35 850/250/540 214


FP-5.1-NELF 3213 4820 474 38 1000/250/540 236
FP-6.8-NELF 4284 6426 632 40 1150/250/54 0 258
FP-8.5-NELF 5355 8033 791 42 1350/250/540 280
FP-10.2-NELF 6426 9639 949 44 1500/250/540 306
FP-13.6-NELF 8568 12852 1265 45 1650/250/540 380
FP-17.0-NELF 10710 16065 1581 47 1950/250/540 432

FP-3.4-NEOLF 2142 3213 316 35 850/250/540 214


FP-5.1-NEOLF 3213 4820 474 38 1000/250/540 236
FP-6.8-NEOLF 4284 6426 632 40 1150/250/54 0 258
FP-8.5-NEOLF 5355 8033 791 42 1350/250/540 280
FP-10.2-NEOLF 6426 9639 949 44 1500/250/540 306
FP-13.6-NEOLF 8568 12852 1265 45 1650/250/540 380
FP-17.0-NEOLF 10710 16065 1581 47 1950/250/540 432

FP-3.4-WEOFLF 2142 3213 316 35 850/250/540 214


FP-5.1-WEOFLF 3213 4820 474 38 1000/250/540 236
FP-6.8-WEOFLF 4284 6426 632 40 1150/250/54 0 258
FP-8.5-WEOFLF 5355 8033 791 42 1350/250/540 280
FP-10.2-WEOFLF 6426 9639 949 44 1500/250/540 306
FP-13.6-WEOFLF 8568 12852 1265 45 1650/250/540 380
FP-17.0-WEOFLF 10710 16065 1581 47 1950/250/540 432

FP-3.4-WEAFLF 2142 3213 316 35 850/250/540 208


FP-5.1-WEAFLF 3213 4820 474 38 1000/250/540 230
FP-6.8-WEAFLF 4284 6426 632 40 1150/250/54 0 250
FP-8.5-WEAFLF 5355 8033 791 42 1350/250/540 270
FP-10.2-WEAFLF 6426 9639 949 44 1500/250/540 292
FP-13.6-WEAFLF 8568 12852 1265 45 1650/250/540 366
FP-17.0-WEAFLF 10710 16065 1581 47 1950/250/540 412
FP-3.4-NCOLF 2142 3213 316 35 600/230/506 164
FP-5.1-NCOLF 3213 4820 474 38 750/230/506 184
FP-6.8-NCOLF 4284 6426 632 40 900/230/506 198
FP-8.5-NCOLF 5355 8033 791 42 1050/230/506 214
FP-10.2-NCOLF 6426 9639 949 44 1200/230/506 230
FP-13.6-NCOLF 8568 12852 1265 45 1350/230/506 300
FP-17.0-NCOLF 10710 16065 1581 47 1650/230/506 338
FP-20.4-NCOLF 12852 19278 1897 48 1950/230/506 368

FP-3.4-NCOFLF 2142 3213 316 35 600/230/506 164


FP-5.1-NCOFLF 3213 4820 474 38 750/230/506 184
FP-6.8-NCOFLF 4284 6426 632 40 900/230/506 198
FP-8.5-NCOFLF 5355 8033 791 42 1050/230/506 214
FP-10.2-NCOFLF 6426 9639 949 44 1200/230/506 230
FP-13.6-NCOFLF 8568 12852 1265 45 1350/230/506 300
FP-17.0-NCOFLF 10710 16065 1581 47 1650/230/506 338

FP-20.4-NCOFLF 12852 19278 1897 48 1950/230/506 368

FP-3.4NCLF 2142 3213 316 35 600/230/506 164

FP-5.1NCLF 3213 4820 474 38 750/230/506 184

FP-6.8NCLF 4284 6426 632 40 900/230/506 198

FP-8.5NCLF 5355 8033 791 42 1050/230/506 214

FP-10.2NCLF 6426 9639 949 44 1200/230/506 230

FP-13.6NCLF 8568 12852 1265 45 1350/230/506 300

FP-17.0NCLF 10710 16065 1581 47 1650/230/506 338

FP-20.4NCLF 12852 19278 1897 48 1950/230/506 368

FP-3.4NCFLF 2142 3213 316 35 600/230/506 164


FP-5.1NCFLF 3213 4820 474 38 750/230/506 184
FP-6.8NCFLF 4284 6426 632 40 900/230/506 198
FP-8.5NCFLF 5355 8033 791 42 1050/230/506 214
FP-10.2NCFLF 6426 9639 949 44 1200/230/506 230
FP-13.6NCFLF 8568 12852 1265 45 1350/230/506 300
FP-17.0NCFLF 10710 16065 1581 47 1650/230/506 338
FP-20.4NCFLF 12852 19278 1897 48 1950/230/506 368

FP-3.4-WCAFLF 2142 3213 316 35 600/230/506 164


FP-5.1-WCAFLF 3213 4820 474 38 750/230/506 184
FP-6.8-WCAFLF 4284 6426 632 40 900/230/506 198
FP-8.5-WCAFLF 5355 8033 791 42 1050/230/506 214
FP-10.2-WCAFLF 6426 9639 949 44 1200/230/506 230
FP-13.6-WCAFLF 8568 12852 1265 45 1350/230/506 300
FP-17.0-WCAFLF 10710 16065 1581 47 1650/230/506 338
FP-20.4-WCAFLF 12852 19278 1897 48 1950/230/506 368

FP-3.4-WCOFLF 2142 3213 316 35 600/230/506 164


FP-5.1-WCOFLF 3213 4820 474 38 750/230/506 184
FP-6.8-WCOFLF 4284 6426 632 40 900/230/506 198
FP-8.5-WCOFLF 5355 8033 791 42 1050/230/506 214
FP-10.2-WCOFLF 6426 9639 949 44 1200/230/506 230
FP-13.6-WCOFLF 8568 12852 1265 45 1350/230/506 300
FP-17.0-WCOFLF 10710 16065 1581 47 1650/230/506 338
FP-20.4-WCOFLF 12852 19278 1897 48 1950/230/506 368

VAT not included