SS#29 SS#1B

Isc min Isc max Isc min Isc max


Bus D1 24.03 37.44 Bus 1B-1 6.37 12.4
Bus D2 24.03 37.69 Bus 1B-2 6.37 12.37
Bus D3 24.03 37.44 Bus 1B-D1 3.18 4.28
Bus D4 24.03 37.69
MCC B-1 6.34 9.72 SS#9
MCC B-2 6.34 10.18 Isc min Isc max
Bus 9-A 6.37 12.47
SS#1A Bus 9-B 6.37 12.44
Isc min Isc max Bus 9-D-1 20.43 31.14
Bus 1A-1 14.57 37.57 Bus 9-D-2 20.43 31.14
Bus 1A-2 14.57 37.57 Bus 9-D-3 11.36 19.32

SS#5-6 SS#8
Isc min Isc max Isc min Isc max
Bus 5A 4.9 8.91 Bus 8-A 6.37 12.47
Bus 5B 4.96 8.99 Bus 8-B 6.37 12.44
Bus 6A 4.74 8.68 Bus 8-D-1 23.22 38.23
Bus 6B 4.87 8.87 Bus 8-D-2 23.22 38.21
SS#2
Isc min Isc max
Bus 2-A 6.37 12.47
Bus 2-B 6.37 12.44
Bus 2D-1 23.53 36.77
Bus 2D-2 23.53 36.76
Bus 2D-3 23.91 39.18
Bus 2D-4 23.91 39.16

SS#4
Isc min Isc max
Bus 4A 15.98 26.64
Bus 4B 15.98 26.64
DAFTAR SETTING POINT RELAI PENGAMAN
AREA DISTRIBUSI LISTRIK PLAJU

SUB STATION NO. : SS #.29


AREA : Polypropylene

SS#29 Plaju Low Voltage


Setting
PERALATAN
Inverse Instant
NO TAG NO. CT RATIO Relay
Pick Up Pick Up delay
NOMOR FUNGSI Curve Type Time Dial
( x In) ( x In) (ms)
3000/5 50/51 RST OC IEC VERY INVERSE 1 0.45 4 40
1 LV -29 D-1 REF 615
200/5 51G GF IEC VERY INVERSE 0.1 0.35
3000/5 50/51 RST OC IEC VERY INVERSE 1 0.45 4 40
2 LV-29-D-2 REF 615
200/5 51G GF IEC VERY INVERSE 0.1 0.4
3000/5 50/51 RST OC IEC VERY INVERSE 1 0.45 4 40
3 LV-29-D-3 REF 615
200/5 51G GF IEC VERY INVERSE 0.1 0.4
3000/5 50/51 RST OC IEC VERY INVERSE 1 0.45 4 40
4 LV-29-D-4 REF 615
200/5 51G GF IEC VERY INVERSE 0.1 0.35

SS#29 Plaju Medium Voltage


Setting
PERALATAN
Inverse Instant
NO TAG NO. CT RATIO Relay
Pick Up Pick Up delay
NOMOR FUNGSI Curve Type Time Dial
( x In) ( x In) (ms)
800/5 50/51 1R OC IEC VERY INVERSE 1 0.1 4 40
1 INC 1 6.6 kV RET 615
400/5 51-GR-11 GF IEC VERY INVERSE 0.3 0.09
150/5 50/51 11R OC IEC VERY INVERSE 1.2 0.5 12 40
2 TR-29-B/D-1 RET 615
2 TR-29-B/D-1 RET 615
50/5 51G-11 GF IEC VERY INVERSE 0.4 0.09
150/5 50/51 11R OC IEC VERY INVERSE 1.2 0.5 12 40
3 TR-29-B/D-3 RET 615
50/5 51G-11 GF IEC VERY INVERSE 0.4 0.09
800/5 50/51 2R OC IEC VERY INVERSE 1 0.1 4 40
4 INC 2 6.6 kV RET 615
400/5 51-GR-21 GF IEC VERY INVERSE 0.3 0.09
150/5 50/51 21R OC IEC VERY INVERSE 1.2 0.5 14 40
5 TR-29-B/D-2 RET 615
50/5 51G-21 GF IEC VERY INVERSE 0.4 0.09
150/5 50/51 22R OC IEC VERY INVERSE 1.2 0.5 14 40
6 TR-29-B/D-4 RET 615
50/5 51G-22 GF IEC VERY INVERSE 0.4 0.09
150/5 50/51 23R OC IEC VERY INVERSE 0.8 0.35 12 40
7 TR-29-B/D/E-1 RET 615
50/5 51G-23 GF IEC VERY INVERSE 0.4 0.09

SS#29 Plaju Motor Medium Voltage

49 SETTING 51 SETTING
NO TAG NO. CT RATIO FUNGSI Relay IFL Motor
Rated Pick Up
TC Normal TC Start Time Dial Curve Type
Current ( x In)
40/5 OL 0.42 117 117 0.42 0.25 IEC - Long Inverse
1 KM-2203 REM 615 292
50/5 GF 2 0.2 IEC - Very Inverse
50/5 OL 0.6 80 80 0.6 0.2 IEC - Long Inverse
2 ZM-2501-2 REM 615 392
50/5 GF 2 0.2 IEC - Very Inverse
75/5 OL 0.55 860 860 0.55 1 IEC - Long Inverse
3 KM-101A REM 615 45.4
50/5 GF 2 0.2 IEC - Very Inverse
75/5 OL 0.55 860 860 0.55 1 IEC - Long Inverse
4 KM-101B REM 615 45.4
50/5 GF 2 0.2 IEC - Very Inverse
300/5 OL 0.52 1115 1115 0.52 1.5 IEC - Long Inverse
5 ZM-2501-1 REM 615 148
50/5 GF 2 0.2 IEC - Very Inverse
DAFTAR SETTING POINT RELAI PENGAMAN
AREA DISTRIBUSI LISTRIK PLAJU

SUB STATION NO. : SS #.2001K


AREA : UTL Power Plant

Setting
PERALATAN
Inverse Instant
NO TAG NO. CT RATIO Relay
Pick Up Pick Up delay
NOMOR FUNGSI Curve Type Time Dial
( x In) ( x In) (ms)
50/51 RST OC IEC - Definite 3 2 9 100
1 TR-29-A 400/5 REF 615
51 N GF IEC - Normal Inverse 0.025 0.05
50/51 RST OC IEC - Definite 3 2 9 100
2 TR-29-B 400/5 REF 615
51 N GF IEC - Normal Inverse 0.025 0.05
50/51 RST OC IEC - Definite 3 2 8 100
3 TR-28-A 200/5 REF 615
51 N GF IEC - Normal Inverse 0.05 0.05
50/51 RST OC IEC - Definite 3 2 8 100
4 TR-28-B 200/5 REF 615
51 N GF IEC - Normal Inverse 0.05 0.05
50/51 RST OC IEC - Definite 3 2.5 8.5 300
5 SS#1 SG A 800/5 REF 615
51 N GF IEC Normal Inverse 0.0125 0.05
50/51 RST OC IEC - Definite 3 2.5 8.5 300
6 SS#1 SG B 800/5 REF 615
51 N GF IEC Normal Inverse 0.0125 0.05
DAFTAR SETTING POINT RELAI PENGAMAN
AREA DISTRIBUSI LISTRIK SUNGAI GERONG

SUB STATION NO. : SS #.01 A PASIRAN 12 KV


AREA : UTL Kilang Sungai Gerong

Setting
PERALATAN
INSTALASI CT/PT Inverse Instant
NO Relay
PANEL RATIO
Pick Up Pick Up delay
NOMOR FUNGSI Curve Type Time Dial
( x In) ( x In) (ms)
50/51 RST OCR IEC Normal Inverse 0.6 0.3 7.8 40
Incoming A. 1500/5
01 01 - A - 1 A 51 G OCGFR REF 615 IEC Normal Inverse 0.15 0.13
(MO 20228)
12000/110 27 A UVR IEC Definite 0.73 2000 ms
50/51 RST OCR IEC Normal Inverse 0.6 0.3 7.8 40
Incoming B. 1500/5
02 51 G OCGFR REF 615 IEC Normal Inverse 0.15 0.13
01 - A - 1 B
12000/110 27 B UVR IEC Definite 0.73 2000 ms
50/51 RST OCR IEC Normal Inverse 1.4 0.15 15.4 40
03 TR - 01 - A/B - 1 600/1 RET 615
51 G OCGFR IEC Normal Inverse 0.3 0.15
50/51 RST OCR IEC Normal Inverse 1.4 0.15 15.4 40
04 TR - 01 - A/B - 2 600/1 RET 615
51 G OCGFR IEC Normal Inverse 0.3 0.15
50/51 RST OCR IEC Normal Inverse 0.85 0.2 23.8 40
05 05 - A - 1 A 400/5 REF 615
05 05 - A - 1 A 400/5 REF 615
51 G OCGFR IEC Normal Inverse 0.3 0.14
50/51 RST OCR IEC Normal Inverse 0.85 0.2 23.8 40
06 05 - A - 1 B 400/5 REF 615
51 G OCGFR IEC Normal Inverse 0.3 0.14
50/51 RST OCR IEC Normal Inverse 1 0.2 28 40
07 06 - A - 1 A 400/5 REF 615
51 G OCGFR IEC Normal Inverse 0.3 0.14
50/51 RST OCR IEC Normal Inverse 1 0.2 28 40
08 06 - A - 1 B 400/5 REF 615
51 G OCGFR IEC Normal Inverse 0.3 0.14
DAFTAR SETTING POINT RELAI PENGAMAN
AREA DISTRIBUSI LISTRIK SUNGAI GERONG

SUB STATION NO. : SS #.01 B PASIRAN 6,9 KV


AREA : UTL Kilang Sungai Gerong

Setting
PERALATAN
INSTALASI Inverse Instant
NO CT RATIO Relay
PANEL
Pick Up Pick Up delay
NOMOR FUNGSI Curve Type Time Dial
( x In) ( x In) (ms)
50/51 R OCR IEC Normal Inverse 0.8 0.15 7 300
Incoming A. 1250/5
01 51 G OCNR REF 615 IEC Normal Inverse 0.28 0.35
01 - B - 1 L
12000/110 27 A UVR IEC Definite 0.73 2500 ms
50/51 R OCR IEC Normal Inverse 0.8 0.15 7 300
Incoming B. 1250/5
02 51 G OCNR REF 615 IEC Normal Inverse 0.28 0.35
01 - B - 1 R
12000/110 27 B UVR IEC Definite 0.73 2500 ms
02 - B - 1 L 50/51 R OCR IEC Normal Inverse 0.8 0.1 6 100
03 750/5 REF 615
SS No. 2 A 51 G IEC Normal Inverse 0.1 0.2
02 - B - 1 R 50/51 R OCR IEC Normal Inverse 0.8 0.1 6 100
04 750/5 REF 615
SS No. 2 B 51 G OCGFR IEC Normal Inverse 0.1 0.2
50/51 RST OCR IEC Normal Inverse 0.9 0.1 8 100
05 08 - B - 1 A 750/5 REF 615
51 G OCGFR IEC Normal Inverse 0.1 0.35
50/51 R OCR IEC Normal Inverse 0.9 0.1 8 100
06 08 - B - 1 B 750/5 REF 615
51 G OCGFR IEC Normal Inverse 0.1 0.35
TR - 01 B/D - 1 50/51 RST OCR IEC Normal Inverse 1 0.45
11 12,5/5 REF 615
(61.1211) 51 G OCGFR IEC Normal Inverse 2.4 0.15
SUB STATION NO. : SS #.01 B PASIRAN 0.4 KV
AREA : UTL Kilang Sungai Gerong

Setting
PERALATAN
INSTALASI Inverse Instant
NO CT RATIO Relay
PANEL Pick Up Pick Up delay
NOMOR FUNGSI Curve Type Time Dial
( x In) ( x In) (ms)
50/51 R OCR IEC Normal Inverse 1 0.35 6 40
01 LV 01-D-1 200/5 REF 615
51 N OCNR IEC Normal Inverse 0.28 0.3
DAFTAR SETTING POINT RELAI PENGAMAN
AREA DISTRIBUSI LISTRIK SUNGAI GERONG

SUB STATION NO. : SS #.02 HV 6,9 KV


AREA : CD&L Kilang Sungai Gerong

Setting
PERALATAN
INSTALASI Inverse Instant
NO CT RATIO Relay
PANEL
Pick Up Pick Up delay
NOMOR FUNGSI Curve Type Time Dial
( x In) ( x In) (ms)
51/50 R OCR IEC Normal Inverse 0.8 0.1 6 100
Incoming A 750/5
01 50 G OCGFR REF 615 IEC Normal Inverse 0.1 0.2
02 - B - 1 A
6600/110 27 A UVR IEC Definite 0.73 2500 ms
51/50 R OCR IEC Normal Inverse 0.8 0.1 6 100
Incoming B 750/5
02 50 G OCGFR REF 615 IEC Normal Inverse 0.1 0.2
02 - B - 1 B
6600/110 27 A UVR IEC Definite 0.73 2500 ms
51/50 R OCR IEC Normal Inverse 1 0.3
03 TR - 02 B/D - 2 150/5 RET 615
51 G OCGFR IEC Normal Inverse 0.28 0.15
150/5 50/51 R OCR IEC Normal Inverse 1 0.3
04 TR - 02 B/D - 1 RET 615
51 G OCGFR IEC Normal Inverse 0.28 0.15
200/5 51/50 R OCR IEC Normal Inverse 1 0.25
05 TR - 02 B/D - 3 RET 615
51 G OCGFR IEC Normal Inverse 0.28 0.15
51/50 R OCR IEC Normal Inverse 1 0.25
06 TR - 02 B/D - 4 200/5 RET 615
51 G OCGFR IEC Normal Inverse 0.28 0.15
51/50 R OCR IEC Normal Inverse 1 0.2
07 TR - 04 B/D - 1 75/5 RET 615
51 G OCGFR IEC Normal Inverse 0.28 0.15
51/50 R OCR IEC Normal Inverse 1 0.2
08 TR - 04 B/D - 2 75/5 RET 615
51 G OCGFR IEC Normal Inverse 0.28 0.15
TS/SETRELAI/9/2001/SS-02

DAFTAR SETTING POINT RELAI PENGAMAN


AREA DISTRIBUSI LISTRIK SUNGAI GERONG

SUB STATION NO. : SS #.02 TEGANGAN 400 VOLT


AREA : CD&L Kilang Sungai Gerong

Setting
PERALATAN
INSTALASI Inverse Instant
NO CT RATIO Relay
PANEL
Pick Up Pick Up delay
NOMOR FUNGSI Curve Type Time Dial
( x In) ( x In) (ms)
3000/5 50/51 R OCR IEC Normal Inverse 1 0.15 5 40
INCOMING A
01 02 - D3 - 1 3000/5 51 N OCNR REF 615 IEC Normal Inverse 0.28 0.3
(02-D-3)
440/110 27 L UVR IEC Definite 0.68 3000 ms
3000/5 50/51 R OCR IEC Normal Inverse 1 0.15 5 40
INCOMING B
02 02 - D3 - 2 3000/5 51 N OCNR REF 615 IEC Normal Inverse 0.28 0.3
(02-D-4)
440/110 27 L UVR IEC Definite 0.68 3000 ms
2500/5 50/51 R OCR IEC Normal Inverse 1 0.2 5 40
INCOMING A
03 02 - D - 1 A 2500/5 51 N OCNR REF 615 IEC Normal Inverse 0.28 0.3
(02-D-1)
440/110 27 L UVR IEC Definite 0.68 3000 ms
2500/5 50/51 R OCR IEC Normal Inverse 1 0.2 5 40
INCOMING B
04 02 - D - 1 B 2500/5 51 N OCNR REF 615 IEC Normal Inverse 0.28 0.3
(02-D-2)
440/110 27 L UVR IEC Definite 0.68 3000 ms
50/51 R OCR IEC Normal Inverse 0.8 0.24 4 40
02-D 2 600/5
05 51 G OCGFR REF 615 IEC Normal Inverse 0.2 0.17
(busbar)
440/110 27 L UVR IEC Definite 0.77 3000 ms
TS/SETRELAI/9/2001/SS-08
DAFTAR SETTING POINT RELAI PENGAMAN
AREA DISTRIBUSI LISTRIK SUNGAI GERONG

SUB STATION NO. : SS #.02 FEEDER.A. MOTOR HV


AREA : CD&L Kilang Sungai Gerong

Setting
49 SETTING
INSTALASI Inverse Instant
NO CT RATIO FUNGSI Inom
PANEL
Rated Pick Up Pick Up delay
TC Normal TC Start Curve Type Time Dial
Current ( x In) ( x In) (ms)
OL 0.55 324 324 IEC - Long Inverse 0.55 0.2
01 PM - 14 - 001 A 60/5 35
GF 0.3 500
OL 0.5 344 344 IEC - Long Inverse 0.5 1
02 KM - 14 - 002 40/5 23
GF 0.3 500
OL 0.55 319 319 IEC - Long Inverse 0.55 1
03 PM - 14 - 003 A 30/5 16.5
GF 0.35 500
OL 0.6 308 308 IEC - Long Inverse 0.6 0.5
04 PM - 14 - 004A 50/5 32
GF 0.3 500
OL 0.55 453 453 IEC - Long Inverse 0.55 0.55
05 PM - 14 - 006 A 40/5 21
GF 0.3 500
OL
06 PM - 61 - 101 A 50/5 34
GF
OL
07 PM - 61 - 102 A 50/5 25
GF
OL
08 SPARE VCTT A 40/5 37 A
GF
TS/SETRELAI/9/2001/SS-02

DAFTAR SETTING POINT RELAI PENGAMAN


AREA DISTRIBUSI LISTRIK SUNGAI GERONG

SUB STATION NO. : SS #.02 FEEDER.B. MOTOR HV


AREA : CD&L Kilang Sungai Gerong

Setting
49 SETTING
INSTALASI Inverse Instant
NO CT RATIO FUNGSI Inom
PANEL
Rated Pick Up Pick Up delay
TC Normal TC Start Curve Type Time Dial
Current ( x In) ( x In) (ms)
01 PM - 14 - 001 B 60/5 OL 0.55 324 324 IEC - Long Inverse 0.6 0.4
35
GF 0.3 500
02 PM - 14 - 003 B 30/5 OL 0.5 344 344 IEC - Long Inverse 0.55 0.35
16.5
GF 0.35 500
03 PM - 14 - 004 B 50/5 OL 0.55 319 319 IEC - Long Inverse 0.6 0.4
32
GF 0.3 500
04 PM - 14 - 006 B 40/5 OL 0.6 308 308 IEC - Long Inverse 0.5 0.4
21
GF 0.3 500
05 PM - 14 - 002 40/5 OL
32
GF
06 PM - 61 - 001 50/5 OL
27
GF
07 PM - 61 - 101 B 50/5 OL
34
GF
08 PM - 61 - 102 B 50/5 OL
25
GF
TS/SETRELAI/9/2001/SS-02
DAFTAR SETTING POINT RELAI PENGAMAN
AREA DISTRIBUSI LISTRIK SUNGAI GERONG

SUB STATION NO. : SS #.08 HV 6,9 KV


AREA : CD&L Kilang Sungai Gerong

Setting
PERALATAN
INSTALASI Inverse Instant
NO CT RATIO Relay
PANEL Pick Up Time Pick Up delay
NOMOR FUNGSI Curve Type ( x In) Dial ( x In) (ms)
50/51 OCR IEC Normal Inverse 1.35 0.1 12 100
500/5
01 INC. 08 - B - 1 A 51 G OCGFR REF 615 IEC Normal Inverse 0.15 0.35
6600/110 27 A UVR IEC Definite 0.77 2500 ms
50/51 OCR IEC Normal Inverse 1.35 0.1 12 100
500/5
02 INC. 08 - B - 1 B 51 G OCGFR REF 615 IEC Normal Inverse 0.15 0.35
6600/110 27 A UVR IEC Definite 0.77 2500 ms
50/51 OCR IEC Normal Inverse 1 0.2 15 40
03 TR-08-B/D-1 150/5 RET 615
51 G OCGFR IEC Normal Inverse 0.3 0.1
50/51 OCR IEC Normal Inverse 1 0.2 15 40
04 TR-08-B/D-2 150/5 RET 615
51 G OCGFR IEC Normal Inverse 0.3 0.1

SUB STATION NO. : SS #.08 TEGANGAN 400 VOLT


AREA : CD&L Kilang Sungai Gerong

Setting
PERALATAN
INSTALASI CT Inverse Instant
NO Relay
PANEL RATIO Pick Up Time Pick Up delay
NOMOR FUNGSI Curve Type ( x In) Dial ( x In) (ms)
3000/5 50/51 RST OCR IEC Normal Inverse 0.85 0.05 5 40
01 INCOMING A 3000/5 51 N OCR REF 615 0.4 40
440/110 27 A UVR IEC Definite 0.6818182 3000 ms
3000/5 50/51 RST OCR IEC Normal Inverse 0.85 0.05 5 40
02 INCOMING B REF 615
02 INCOMING B 3000/5 51 N OCR REF 615 0.4 40
440/110 27 A UVR IEC Definite 0.6818182 3000 ms

SUB STATION NO. : SS #.08 HV MOTOR 6,9 KV FEEDER A


AREA : CD&L Kilang Sungai Gerong

Setting
49 SETTING
Inverse Instant
INSTALASI
NO CT RATIO FUNGSI Inom Rated
PANEL Pick Up Pick Up delay
Current TC Normal TC Start Curve Type Time Dial
( x In) ( x In) (ms)
(xIn)
TOLR 0.7 1003 1003 IEC - Long Inverse 0.7 1.25
01 FC - BM - 2 75/5 51
GF 0.3 1000
TOLR 0.6 310 310 IEC - Long Inverse 0.6 0.45
02 PM - 53 - 011 A 30/5 16.8
GF 0.3 400
TOLR 0.6 354 354 IEC - Long Inverse 0.6 0.5
03 PM - 61 - 221 A 100/5 60
GF 0.3 400
TOLR 0.6 293 293 IEC - Long Inverse 0.6 0.4
04 PM - 53 - 101 B 75/5 41
GF 0.3 400
TOLR 0.6 334 334 IEC - Long Inverse 0.6 0.5
05 PM - 61 - 313 A 30/5 17.5
GF 0.3 400
TOLR 0.35 390 390 IEC - Long Inverse 0.35 0.5
06 FC - PM - 25 A 30/5 11
GF 0.3 400
TOLR 0.55 335 335 IEC - Long Inverse 0.55 0.6
07 FC - PM - 21 A 30/5 16
GF 0.3 400
SUB STATION NO. : SS #.08 HV MOTOR 6,9 KV FEEDER B
AREA : CD&L Kilang Sungai Gerong

Setting
49 SETTING
INSTALASI Inverse Instant
NO CT RATIO FUNGSI Inom
PANEL Rated Pick Up Pick Up delay
TC Normal TC Start Curve Type Time Dial
Current ( x In) ( x In) (ms)
TOLR 0.6 354 354 IEC - Long Inverse 0.6 0.5
02 PM - 61 - 221 B 100/5 60
GF 0.3 400
TOLR 0.6 354 354 IEC - Long Inverse 0.6 0.5
03 PM - 61 - 221 C 100/5 60
GF 0.3 400
TOLR 0.6 293 293 IEC - Long Inverse 0.6 0.4
04 PM - 53 - 101 C 75/5 41
GF 0.3 400
TOLR 0.62 315 315 IEC - Long Inverse 0.62 0.5
05 PM - 61 - 313 B 30/5 17.5
GF 0.3 400
TOLR 0.35 390 390 IEC - Long Inverse 0.35 0.5
06 FC - PM - 25 B 30/5 11
GF 0.3 400
TOLR 0.55 335 335 IEC - Long Inverse 0.55 0.6
07 FC - PM - 21 B 30/5 16
GF 0.3 400
DAFTAR SETTING POINT RELAI PENGAMAN
AREA DISTRIBUSI LISTRIK SUNGAI GERONG

SUB STATION NO. : SS #.09 HV 6,9 KV


AREA : CD&L Kilang Sungai Gerong

PERALATAN Setting
INSTALASI
NO CT RATIO Relay Inverse Instant
PANEL
NOMOR FUNGSI Pick Up Pick Up delay
Curve Type Time Dial
( x In) ( x In) (ms)
50/51 R OCR IEC Very Inverse 0.6 0.19 4 20
600/5
01 Incoming A 51 N OCGFR REF 615 IEC Very Inverse 0.05 0.25 0.6 40
6600/110 27 UVR IEC Definite 0.82 3000 ms
50/51 R OCR IEC Very Inverse 0.6 0.19 4 20
600/5
02 Incoming B 51 N OCGFR REF 615 IEC Very Inverse 0.05 0.25 0.4 40
6600/110 27 UVR IEC Definite 0.82 3000 ms
50/51 R OCR IEC Very Inverse 0.8 0.42 12 20
TR - 1000 KVA 100/5
03 51 N OCGFR REF 615 IEC Very Inverse 0.14 0.4 0.8 40
No.1
6600/110 27 UVR IEC Definite 0.77 2500 ms
50/51 R OCR IEC Very Inverse 0.8 0.42 12 20
TR - 1000 KVA 100/5
04 51 N OCGFR REF 615 IEC Very Inverse 0.14 0.4 0.8 40
No.2
6600/110 27 UVR IEC Definite 0.77 2500 ms
50/51 R OCR IEC Very Inverse 0.8 0.42 12 20
50/5
05 TR - 400 KVA 51 N OCGFR REF 615 IEC Very Inverse 0.2 1 0.8 40
6600/110 27 UVR IEC Definite 0.77 2500 ms

Potrebbero piacerti anche