Tanks Essentials

Organic Liquid Above-Ground Storage Tank Basics

Jim Miller, P.E.


Senior Air Quality Engineer
(512) 297-6448

Bart Leininger, P.E.


Principal
Ashworth Leininger Group
Camarillo, CA

Special Note: Credit for the tank design diagrams and information used in this presentation is given to
Rob Ferry, TGB Partnership and associated content used under the permission of the 4C Conference.

Tanks Essentials 3/31/18 Page 1


Objectives
• Exposure to Tank Design Parameters

• Understand Source Emissions Driving Forces and Calculation Basics

• Evaluate Standard Practices for Emission Rate Determination

• Introduction to Federal Regulatory Requirements

Tanks Essentials 3/31/18 Page 2


Tank Categories
API 650
• 0 to 2.5 psig, “atmospheric tanks”
API 620
• Up to 15 psig, “low-pressure tanks”
ASME Boiler and Pressure Vessel Code, Section 8
• Above 15 psig, “pressure vessels”

Tanks Essentials 3/31/18 Page 3


Tank Design

• Types of Above-Ground Organic Liquid Storage Tanks


• Fixed-roof, IFR, EFR, Domed EFR
• Types of Floating Roofs
• IFR/EFR, bolted/welded, contact/noncontact
• Floating Roof Design Details
• Deck Seams, Rim Seals, Fittings

Tanks Essentials 3/31/18 Page 4


Types of Above-Ground Storage Tanks
• Fixed-roof
• Fixed roof at the top of the shell; no floating roof
• Internal floating roof (IFR)
• Fixed roof and a light-duty floating roof
• External floating roof (EFR)
• Open top (no fixed roof), with a floating roof
• Covered (Domed) external floating roof
• Fixed roof and an external-type floating roof

Tanks Essentials 3/31/18 Page 5


Fixed-Roof Tanks
• No floating roof
• Liquid surface is free to evaporate into the headspace
• Typically low-profile cone roof supported with columns
• Requires interior supports, frangible joint
• Vented to the atmosphere
• Open vents (gooseneck) or P/V breather vents

Tanks Essentials 3/31/18 Page 6


Fixed-Roof Tanks

Tanks Essentials 3/31/18 Page 7


Fixed-Roof Tank Driving Forces for Emissions:
Working Losses

Tanks Essentials 3/31/18 Page 8


Fixed-Roof Tank Driving Forces for Emissions:
Standing Losses

Tanks Essentials 3/31/18 Page 9


Fixed-Roof Tank Failures

Tanks Essentials 3/31/18 Page 10


Fixed-Roof Tank Failures

Tanks Essentials 3/31/18 Page 11


Fixed-Roof
Tank Failures

Tanks Essentials 3/31/18 Page 12


Fixed-Roof Tank Failures

Tanks Essentials 3/31/18 Page 13


Internal Floating-Roof Tanks (IFRTs)
• Floating roof covers the liquid surface
• Greatly reducing free evaporation into the headspace
• Fixed roof is freely vented
• For maintaining vapors << LEL (unless gas blanketed)
• Floating roof deck is lightweight, per API 650, App. H
• Protection by the fixed roof allows lightweight design
• Some vapors escape past the floating roof
• At rim seals, deck fittings, & deck seams (if bolted)

Tanks Essentials 3/31/18 Page 14


Internal Floating-Roof Tanks

Tanks Essentials 3/31/18 Page 15


IFRT Summary
• Deck construction can be lightweight
• Short sleeves (housings) for deck support legs
• Deck seams may be bolted (typ. for aluminum)
• Fixed roof may require support columns
• Which penetrate the deck, creating paths for emissions
• Wind is not a factor in emissions
• Vapors escape past the floating roof independent of ambient wind speed, and
daily breathing results in enough air movement to carry vapors out of the tank

Tanks Essentials 3/31/18 Page 16


External Floating-Roof Tanks (EFRTs)
• Floating roof covers the liquid surface
• Greatly reducing free evaporation
• Fixed roof is subject to wind action
• Tank shell provides a partial shield, but losses still wind driven
• Floating roof deck is heavyweight, per API 650, App. C
• Designed for external forces (e.g., snow, torrential rain)
• Some vapors escape past the floating roof
• At rim seals, deck fittings (but deck seams are welded)

Tanks Essentials 3/31/18 Page 17


External Floating-Roof Tank

Tanks Essentials 3/31/18 Page 18


EFRT Summary
• Deck construction is heavyweight
• Tall sleeves (housings) for deck support legs
• Welded deck seams
• No fixed roof; no support columns
• Typically fewer deck penetrations than for an IFRT
• Wind is a factor in emissions
• The rate at which vapors escape past the floating roof is very sensitive to
ambient wind speed
• Wind action offsets lower loss factors, fewer fittings

Tanks Essentials 3/31/18 Page 19


Covered (Domed) External Floating-Roof Tanks

• Differs from IFRT in the type of floating roof


• EFR-type deck, w/ welded deck seams, tall leg sleeves
• Fixed roof is freely vented (as for IFRT)
• Typically an aluminum dome over an EFRT
• Particularly for retrofit applications, where a dome can be installed in-service
• Could be a steel cone roof, but this would typically involve installing out-of-
service, roof support columns

Tanks Essentials 3/31/18 Page 20


Covered (Domed) External Floating-Roof Tank

Tanks Essentials 3/31/18 Page 21


Domed External Floating-Roof Tank Summary
• Deck construction is heavyweight
• Tall sleeves (housings) for deck support legs
• Welded deck seams
• Typically with dome roof; no columns
• Means typically fewer deck penetrations than for an IFRT
• Wind is not a factor in emissions
• Lower loss factors, fewer fittings, and not subject to wind action – lowest emitting
type of construction.

Tanks Essentials 3/31/18 Page 22


Floating Roof Tank Driving Forces for
Emissions: Working Losses

Tanks Essentials 3/31/18 Page 23


Floating Roof Tank Driving Forces for
Emissions: Standing Losses

Tanks Essentials 3/31/18 Page 24


Floating Roof Features
• Emissions sources
• Withdrawals
• Deck Seams (bolted decks only)
• Rim Seals
• Deck Fittings
• Controls
• Rim Seals
• Deck Fittings

Tanks Essentials 3/31/18 Page 25


Types of Floating Roof Decks

Tanks Essentials 3/31/18 Page 26


Floating Roof Cutaway

Tanks Essentials 3/31/18 Page 27


Pan Deck

Tanks Essentials 3/31/18 Page 28


Bulkheaded Deck

Tanks Essentials 3/31/18 Page 29


Pontoon Deck

Tanks Essentials 3/31/18 Page 30


Pontoon Deck

Tanks Essentials 3/31/18 Page 31


Double-Deck

Tanks Essentials 3/31/18 Page 32


Double Deck

Tanks Essentials 3/31/18 Page 33


On-Floats Deck
- aka skin & pontoon, or noncontact

Tanks Essentials 3/31/18 Page 34


On-Floats Deck
- aka skin & pontoon, or noncontact

Tanks Essentials 3/31/18 Page 35


Sandwich Panel Deck

Tanks Essentials 3/31/18 Page 36


Sandwich Panel Deck

Tanks Essentials 3/31/18 Page 37


Floating Roof Considerations
• Design:
• External floating roofs per API 650, Appendix C
• Internal floating roofs per API 650, Appendix H
• Costs
• Environmental
• Fire Safety

Tanks Essentials 3/31/18 Page 38


External Floating Roofs
• Potentially more economical to initially construct versus IFR
• But future costs may be unacceptable:
• Problems associated with water intrusion
• Drain lines pose maintenance problems
• Snow load poses maintenance problems
• Higher liquid surface temp = higher emissions
• This is not presently accounted for in the emission factors, but an API study is seeking to
quantify this

Tanks Essentials 3/31/18 Page 39


Floating Roof Considerations
• Design:
• External floating roofs per API 650, Appendix C
• Internal floating roofs per API 650, Appendix H
• Costs
• Environmental
• Fire Safety

Tanks Essentials 3/31/18 Page 40


Rainwater Problems with an EFRT

Tanks Essentials 3/31/18 Page 41


EFR Drain Line Problems

Tanks Essentials 3/31/18 Page 42


Snow Problems with an EFRT

Tanks Essentials 3/31/18 Page 43


Emissions Increased with an EFRT

Tanks Essentials 3/31/18 Page 44


Fixed Roofs for Floating Roof Tanks
• Steel cone roof
• Typically column supported
• Requires painting for maintenance
• Retrofit installation requires out-of-service
• Aluminum dome roof
• Self-supporting (no interior columns)
• No painting necessary
• Retrofit installation may be done in-service

Tanks Essentials 3/31/18 Page 45


Problems with Support Columns
• Increased air emissions
• Due to penetrations through the floating roof
• May involve significant foundation costs
• Soft soils may require piles under each column.
• High corrosion potential/unable to inspect
• Bottom corrosion & leaks are accelerated at columns
• Interfere with secondary bottom installation

Tanks Essentials 3/31/18 Page 46


Support Columns

Tanks Essentials 3/31/18 Page 47


IFR Comparison

Tanks Essentials 3/31/18 Page 48


Limitations for Pan-Type
• Does not meet NFPA 30 criteria
• Nor does the bulkheaded, as noted in the prior table - they do not have enclosed
flotation compartments

• Does not provide redundant buoyancy


• A single leak can flood the entire deck, whereas other designs still float with two
flooded compartments.

• Is readily sunk by upsets or turbulence


• Unsymmetrical loading may buckle the rim of the deck, allowing it to fold up like a
taco.

• Foam system must be for full surface area.

Tanks Essentials 3/31/18 Page 49


Floating Roof “Taco” Failure

Tanks Essentials 3/31/18 Page 50


Costs of Steel IFRs
• Higher than aluminum for initial installation
• More loss of capacity than aluminum
• Heavier material displaces more liquid
• Doorsheet escalates replacement costs
• The doorsheet itself involves additional construction
• A hydrotest is required when complete
• To test the integrity of the doorsheet, and
• To stress relieve the doorsheet welds

Tanks Essentials 3/31/18 Page 51


Comparison of Aluminum IFRs
• Sandwich panel type:
• More expensive than skin and pontoon,
• More length of deck seams (higher emissions),
• May require doorsheet/hydrotest to replace
• If closed cell core, inherent safety concerns
• Appendix H states that this type is “permitted however…enclosed spaces within a
module may result in undetectable combustible gas.”
• This type, then, does not provide the safety implicit in H.4.1.7

Tanks Essentials 3/31/18 Page 52


Comparison of Aluminum IFRs
• Skin and pontoon type:
• Least expensive,
• Lower emissions than sandwich panel,
• Replace without doorsheet or roof hole,
• Foam system must be designed for full surface
• Skin and pontoon type decks cost less than other types both initially and for replacement,
but if a foam system is required for fire protection the foam system will cost more for skin
and pontoon aluminum than for steel pontoon or doubledeck.

Tanks Essentials 3/31/18 Page 53


Aluminum Skin & Pontoon
• If best, why are others even considered?
• Seems to be clear choice from value engineering
• Negative perceptions in the market:
• Flexibility is disconcerting for personnel.
• Reputation of poor service history.
• The Question: Are they inherently flimsy,
OR have they been underdesigned?

Tanks Essentials 3/31/18 Page 54


Aluminum Skin & Pontoon – Negative
Perceptions
• Flexibility is disconcerting for personnel.
• Workers feel uneasy walking on it
• Safe, but sensation like walking on a huge waterbed

• A moot point in light of Confined Space Entry


• Workmen generally not allowed to enter any IFRT

• Reputation for poor service history.


• API 650 Appendix H has had a design loophole.
• Only required to support 500 pounds.

Tanks Essentials 3/31/18 Page 55


API 650, Appendix H pre-Revision
• Design standard for all IFRs
• Allowed waiver of uniform live load
• If equipped with deck drains
• Only design load was then 500 pound load
• As a result, some manufacturers use few legs
• ‘Typical’ tributary area assumed for emission estimates is about 400 square feet per leg
(an area 40 ft x 10 ft)

Tanks Essentials 3/31/18 Page 56


API 650, Appendix H post-Revision
• All IFRs to support uniform live load:
• Still 12.5 psf if no deck drains.
• Now 5 psf with deck drains.
• This translates to 2,000 lbs for a 400 sq.ft. area.

• Most failures have had too few deck legs.


• Legs on 40 ft spacing would now need 10 ft spacing, or
• Support 4-times more load than previously.

Tanks Essentials 3/31/18 Page 57


Aluminum Skin & Pontoon - Summary of
Service History
• Frequent failures occur with poor designs
• Successful deck leg design has featured:
• Limit on tributary area of about 200 square feet
• Designed to support 1000 pounds {5 psf}
• Designed for real world load conditions
• (i.e., out-of-plumb, out-of-level, & subject to cyclic loads)

• Properly designed skin & pontoon IFRs can last longer w/o major repairs
than the tank

Tanks Essentials 3/31/18 Page 58


Summary of IFR Types
• Steel pontoon and double deck:
• Most durable, lowest emissions, best fire safety
• Most expensive
• Aluminum skin-and-pontoon:
• Best value for many applications IF well made
• Quality varies greatly
• Higher emissions
• Other designs:
• May suit limited or specialized applications
Tanks Essentials 3/31/18 Page 59
Floating Roof Features

• Points of emissions from floating roofs


• Deck seams (if bolted), rim seals, deck fittings
• Types of devices to control emissions
• Features of common rim seals and deck fitting controls

Tanks Essentials 3/31/18 Page 60


Points of Emissions from Floating Roofs

• Deck Seams
• Contribute to emissions if bolted; but not if welded
• Rim Seals
• This is the closure device between the deck and tank
• Deck Fittings
• Only those features that open through the deck to the stored liquid are
considered to be deck fittings for emissions purposes

Tanks Essentials 3/31/18 Page 61


Deck Seams – Sheet Construction

Tanks Essentials 3/31/18 Page 62


Deck Seams – Panel Construction

Tanks Essentials 3/31/18 Page 63


Rim Seals

Tanks Essentials 3/31/18 Page 64


Rim Seal Vapor Space

Tanks Essentials 3/31/18 Page 65


Rim Seal Emissions

Tanks Essentials 3/31/18 Page 66


Types of Primary Rim Seals
• Vapor-mounted:
• Highest emissions - Fair service history
• Liquid-mounted:
• Lowest emissions - Poorest service history
• Mechanical-shoe:
• Fairly low emissions - Best service history
• Note that, in California, a mechanical-shoe seal is considered a type of liquid-mounted
seal, rather than a separate category of rim seal.

Tanks Essentials 3/31/18 Page 67


Vapor-Mounted Rim Seal
• Bottom is not in contact with the liquid surface
• Annular vapor space beneath the rim seal
• Between the rim of the deck and the shell of the tank
• Two common types:
• Flexible-wiper (blade)
• Continuous wiper blade around the rim of the deck

• Resilient-filled type
• A foam log within an elastomeric-coated fabric envelope
• The envelope protects the foam core from liquid & abrasion

Tanks Essentials 3/31/18 Page 68


Vapor-Mounted Rim Seal – Flexible-Wiper Type

Tanks Essentials 3/31/18 Page 69


Vapor-Mounted Rim Seal – Resilient-Filled
Type

Tanks Essentials 3/31/18 Page 70


Liquid-Mounted Rim Seal
• Bottom of the seal contacts the liquid surface
• The rim vapor space is virtually eliminated
• Resilient-filled design
• Typically a foam log in an elastomeric-coated fabric
• Differs from resilient-filled vapor-mounted rim seal in its position relative to
the liquid
• i.e., whether or not the bottom of the seal contacts the liquid surface

Tanks Essentials 3/31/18 Page 71


Liquid-Mounted Rim Seal

Tanks Essentials 3/31/18 Page 72


Mechanical-Shoe Rim Seal
• Metallic shoe - slides against the tank shell
• A series of overlapping sheets form a ring inside the shell
• Mechanical device - pushing the shoe outward
• Regularly spaced devices hold the shoe against the shell
• Primary seal fabric - to cover the annular space
• An elastomeric-coated fabric closes the annular space between the metallic shoe
and the rim of the deck

• In California, mechanical-shoe is considered a type of liquid-mounted seal,


rather than a separate category

Tanks Essentials 3/31/18 Page 73


Mechanical-Shoe Rim Seal

Tanks Essentials 3/31/18 Page 74


Strategies to Improve Rim Seal Effectiveness
• Minimize gaps between rim seal and tank shell
• Seek to keep the rim seal firmly against the tank shell

• Minimize the rim space tributary to a gap


• Fill the rim space or provide a baffle to isolate it
• Provide secondary closure of the rim space
• Equip the floating roof with a secondary rim seal

Tanks Essentials 3/31/18 Page 75


Minimize Rim Seal Gaps

Tanks Essentials 3/31/18 Page 76


Baffle-Type Controls

Tanks Essentials 3/31/18 Page 77


Rim Seal Gaps – Mechanical-shoe Seal

Tanks Essentials 3/31/18 Page 78


Eliminate the Rim Space (Filling It)

Tanks Essentials 3/31/18 Page 79


Rim Seal Gaps – Liquid-mounted Seal

Tanks Essentials 3/31/18 Page 80


Secondary Rim Seals
• Purpose is to reduce emissions
• Particularly effective for external floating roofs
• Mounted above the primary seal
• The secondary is the upper seal in a double seal system
• May be added to any type of primary seal
• Mounted sufficiently high to not interfere w/the primary
• Generally results in loss of tank capacity
• Particularly with internal floating roofs, where the fixed roof limits upward travel of
the floating roof

Tanks Essentials 3/31/18 Page 81


Secondary Rim Seals – Rim-Mounted
Secondary; Mechanical Shoe Primary

Tanks Essentials 3/31/18 Page 82


Secondary Rim Seals – Shoe-Mounted
Secondary; Mechanical Shoe Primary

Tanks Essentials 3/31/18 Page 83


Secondary Rim Seals – Wiper Secondary; Log
Seal Primary

Tanks Essentials 3/31/18 Page 84


Secondary Rim Seals – Wiper Secondary;
Wiper Primary

Tanks Essentials 3/31/18 Page 85


Deck Fittings – Common Features
• Only create emissions if through to liquid
• Deck opening may be round or square
• Shape of opening is a matter of fabricator preference
• Bottom of opening (for most) extends below the liquid surface
• Noncontact decks require a well extension or skirt
• If for a penetration, deck cover must be loose
• The cover must be allowed to slide for out-of-plumbness

Tanks Essentials 3/31/18 Page 86


Deck Fittings

Tanks Essentials 3/31/18 Page 87


Not
Deck
Fittings

Tanks Essentials 3/31/18 Page 88


Deck Fittings

Tanks Essentials 3/31/18 Page 89


Deck Fittings – Basic Categories
• Small opening (nozzle or pipe sleeve) type
• e.g., deck support legs, gauge hatches, deck drains.
• Vent devices
• Not required to extend below the liquid surface
• Large opening (well) type
• e.g., manways, gauge float wells, column wells, and vertical ladders
• Guidepoles–aka gaugepoles, gaugepipes, etc.
• Important enough to be a category unto themselves

Tanks Essentials 3/31/18 Page 90


Deck Fittings –
Support Legs

Tanks Essentials 3/31/18 Page 91


Deck
Support
Legs –
Control
Options

Tanks Essentials 3/31/18 Page 92


Sample Ports

Tanks Essentials 3/31/18 Page 93


Effectiveness of Slit Fabric/Slotted Membrane

• There is no apparent benefit to 90% closure at 0 mph wind


• By comparison, emission factor for an uncontrolled slotted guidepole at 10
mph is 4200 lb-mol/yr

Tanks Essentials 3/31/18 Page 94


Deck Drains
(that empty into stored liquid)

Tanks Essentials 3/31/18 Page 95


Rim Space Vents

Tanks Essentials 3/31/18 Page 96


Vacuum Breaker
(Automatic Bleeder Vent)

Tanks Essentials 3/31/18 Page 97


Vacuum Breaker (Automatic Bleeder Vent)

Tanks Essentials 3/31/18 Page 98


Access Hatch
(Manway)

Tanks Essentials 3/31/18 Page 99


Gauge Float
(Automatic Tank Gauge)

Tanks Essentials 3/31/18 Page 100


Fixed Roof Support Column

Tanks Essentials 3/31/18 Page 101


Fixed Roof Support Column

Tanks Essentials 3/31/18 Page 102


Fixed Roof Support Column

Tanks Essentials 3/31/18 Page 103


Fixed Roof Support Column

Tanks Essentials 3/31/18 Page 104


Vertical Ladder

Tanks Essentials 3/31/18 Page 105


Guidepoles

Tanks Essentials 3/31/18 Page 106


Guidepole Functions
• Anti-rotation devices

• Sampling location

• Level gauge location


To measure the level of the liquid in the tank

Tanks Essentials 3/31/18 Page 107


Unslotted Guidepoles

Tanks Essentials 3/31/18 Page 108


Slotted Guidepoles

Tanks Essentials 3/31/18 Page 109


Function of Slots in a Guidepole
• Allow bulk liquid to flow freely into the pole
• To achieve accurate sampling
• To achieve accurate level gauging
• Avoid confined space entry
• Definition of a slotted guidepole: (Per Generic MACT, 63 Subpart WW)
• A guidepole or gaugepole that has slots or holes through the wall of the pole
[that] allow the stored liquid to flow into the pole at liquid levels above the lowest
operating level

Tanks Essentials 3/31/18 Page 110


Unslotted Guidepole

Tanks Essentials 3/31/18 Page 111


Unslotted Guidepole

Tanks Essentials 3/31/18 Page 112


Unslotted Guidepole

Tanks Essentials 3/31/18 Page 113


Slotted Guidepole

Tanks Essentials 3/31/18 Page 114


Slotted Guidepole

Tanks Essentials 3/31/18 Page 115


Slotted Guidepole

Tanks Essentials 3/31/18 Page 116


Pole Float

Tanks Essentials 3/31/18 Page 117


Pole Float

Tanks Essentials 3/31/18 Page 118


Short Pole Float

Tanks Essentials 3/31/18 Page 119


Pole Sleeve

Tanks Essentials 3/31/18 Page 120


Flexible Enclosure
(Accordion)

Tanks Essentials 3/31/18 Page 121


Guidepole/Ladder Combination

Tanks Essentials 3/31/18 Page 122


Guidepole/Ladder Combination

Tanks Essentials 3/31/18 Page 123


Guidepole/Ladder Combination

Tanks Essentials 3/31/18 Page 124


Estimating Storage Tank Air Emissions

Tanks Essentials 3/31/18 Page 125


Brief History of Calculation Development
• Data from testing for over 20 years
• Sponsored by API, in cooperation with EPA
• Published by both API and EPA
• Chapter 19 of API’s MPMS
• Section 7.1 of EPA’s AP-42

• liquid in the tank Tanks Essentials 3/31/18 Page 126


Brief History of API Research
• Pilot tank testing in the late 1970’s
• Yielded useful results, such as effect of ambient wind
• Not feasible for isolating components
• Wind tunnel and bench scale tests
• Testing of individual deck fittings and rim seals
• Testing at various wind speeds
• ‘Zero wind speed’: frequent air changes (not still air)
• Bolted deck seams the most difficult to standardize

Tanks Essentials 3/31/18 Page 127


API’s MPMS Chapter 19
Manual of Petroleum Measurement Standards
Chapter 19 – Evaporative Loss Measurement
• 19.1 Evaporative Loss from Fixed-Roof Tanks
• 19.2 Evaporative Loss from Floating-Roof Tanks
• 19.3 Loss Factor Certification Program
• Parts A-E are test methods
• Parts F-H are for administration of the tests
• 19.4 Evaporative Loss Reference Information and Speciation Methodology
(Oct. 2012)

Tanks Essentials 3/31/18 Page 128


EPA’s AP-42
Compilation of Air Pollutant Emission Factors
• Volume I: Stationary Point and Area Sources
• Contains emission factors for all sorts of sources
• Section 7.1 – Organic Liquid Storage Tanks
• Fifth Edition, Supplement D – September ’97
• 2006 Revision added Floating Roof Landing Losses
• But Landing Losses not in TANKS 4.09D
• Most agencies reference AP-42 equations

Tanks Essentials 3/31/18 Page 129


MPMS 19 versus AP-42 7.1
• The loss factors and equations used are identical, with the following
exception:
• Bolted deck seam loss factor
• EPA reduced this factor by about 60% (0.14 vs 0.34) in response to data from testing in
the late 1990’s.
• API has not changed from the earlier value of 0.34

• Liquid surface temperature – no longer different


• Had been different for floating-roof tanks, but the API method was reconciled to
the EPA method in the Oct 2012 revisions to API MPMS 19.2 and 19.4

• Most agencies refer to emissions equations in AP-42

Tanks Essentials 3/31/18 Page 130


Emissions Driving Forces Review
• Losses due to liquid throughputs
• Fixed-roof: working loss (filling)
• Floating-roof: withdrawal loss (clingage)
• Losses when tank is static
• Fixed-roof: standing loss (breathing)
• Floating-roof: standing loss
• Due to vapors escaping past the rim seal and through deck fittings (and deck seams, if
bolted)

Tanks Essentials 3/31/18 Page 131


Fixed-Roof Tank: Filling Loss

Tanks Essentials 3/31/18 Page 132


Fixed-Roof Tank Filling (Working) Loss
Equation (1-35) for estimating working loss, LW:
LW = N [ HLX (π/4) D2 ] KN KP WV KB
where
N = turnover rate [turnovers/year]
HLX = maximum liquid height [feet]
D = tank diameter [feet]
KN = working loss turnover (saturation) factor [dimensionless]
KP = working loss product factor [dimensionless] (0.75 or 1)
WV = stock vapor density [lb/ft3]
KB = vent setting correction factor [dimensionless]

Tanks Essentials 3/31/18 Page 133


Fixed-Roof Tank Saturation Factor
KN = working loss turnover (saturation) factor [dimensionless]

For turnovers ≤36:


KN = 1

For turnovers >36:


KN = (180 + N)/6N

Asymptotically
approaches 0.167

Tanks Essentials 3/31/18 Page 134


Fixed-Roof Tank Filling (Working) Loss
• Stock vapor density, WV [lb/ft3] (Equation 1-21)
WV = MV PVA / (R TLA)
where:
• MV = vapor molecular weight [lb/lb-mole]

• R = the ideal gas constant (10.731 psia ft3/lb-mole °R)

• PVA = vapor pressure at daily avg liquid surface temperature [psia]

• TLA = daily average liquid surface temperature [°R]

Tanks Essentials 3/31/18 Page 135


Fixed-Roof Tank Filling (Working) Loss
• Vent setting correction factor, KB (Eq 1-37)
(Only used if breather vent settings are greater than the typical ±0.3 psig)
KB = [(PI + PA) / KN – PVA] / (PBP + PA - PVA)
where:
• PI = pressure of the vapor space at normal operating conditions [psig] (0 if
tank is atmospheric: not held at constant pres/vac)
• PA = atmospheric pressure [psia]
• KN = working loss turnover (saturation) factor [dimensionless]
• PVA = vapor pressure at the daily average liquid surface temperature [psia]
• PBP = breather vent pressure setting [psig]

Tanks Essentials 3/31/18 Page 136


Fixed-Roof Tank Standing Losses

Tanks Essentials 3/31/18 Page 137


Fixed-Roof Tank Standing (Breathing) Loss
Equation (1-4) for estimating standing loss, LS:
LS = 365 KE (π/4 D2) HVO KS WV
where
365 = number of daily events per year [year -1]
KE = vapor space expansion factor [dimensionless] (1-5, 1-7)
D = tank diameter [feet]
HVO = vapor space outage [feet] (1-15)
KS = vented vapor saturation factor [dimensionless] (1-20)
WV = stock vapor density [lb/ft3] (1-21)

Tanks Essentials 3/31/18 Page 138


Fixed-Roof Tank Standing (Breathing) Loss
Equation (1-5) for estimating vapor space expansion factor
for products with PV < 0.1 psia:
KE = 0.0018 [0.72 (TAX − TAN) + 0.028 α I]
where
TAX = daily maximum ambient temperature [°R]
TAN = daily minimum ambient temperature [°R]
α = tank paint solar absorptance [dimensionless]
I = daily total solar insolation on a horizontal surface [Btu/(ft2 day)]
0.0018 = constant, [(°R)-1]
0.72 = constant [dimensionless]
0.028 = constant [(°R ft2 day)/Btu]
Tanks Essentials 3/31/18 Page 139
Fixed-Roof Tank Standing (Breathing) Loss
Equation (1-7) for estimating vapor space expansion factor
for products with PV > 0.1 psia:
KE = Δ TV / TLA + (Δ PV - Δ PB) / (PA - PVA) > 0
where
Δ TV = daily vapor temperature range [°R] = (0.72 Δ TA + 0.028 α I)
Δ PV = daily vapor pressure range [psi]
Δ PB = breather vent pressure setting range [psi]
PA = atmospheric pressure [psia]
PVA = vapor pressure at daily average liquid surface temperature, [psia]
TLA = daily average liquid surface temperature [°R]

Tanks Essentials 3/31/18 Page 140


Fixed-Roof Tank Standing (Breathing) Loss
Equation (1-20) for estimating vented vapor saturation
factor:
KS = 1 / (1 + 0.053 PVA HVO)
where

PVA = vapor pressure at daily avg liquid surface temperature, [psia]

HVO = vapor space outage [ft]

0.053 = constant [(psia-ft)-1]

Tanks Essentials 3/31/18 Page 141


Fixed-Roof Tank Vapor Space Expansion Factor

HVO

Tanks Essentials 3/31/18 Page 142


Fixed-Roof Tank Emissions Strategy
Compliance calculations
Minimum data needs:
• Tank design parameters (diameter, color, shell height)
• Material properties (liquid density, MWs, vapor pressure
curve data)
• Operating parameters (liquid level, breather vent
settings, monthly throughput)

Tanks Essentials 3/31/18 Page 143


Fixed-Roof Tank Emissions Strategy
Compliance calculations
Specific data for special cases:
• Tank design parameters (paint and insulation specifics)
• Operating parameters (constant level, temperature
data)
• Material properties (monthly average sampling data –
vapor pressure and/or speciation)

Tanks Essentials 3/31/18 Page 144


Fixed-Roof Tank Emissions Strategy
Permit calculation considerations
Compliance challenges and NSR challenges:
• Maximize emissions? Capping emissions?
Annual calculation strategy:
• Total throughput on a tank basis (how one divides these into the month
can create flexibility, particularly when > 36 t/o per year)
• Total throughput on a product cap basis (greater flexibility)
• Product vapor pressures (or use maximum regulatory limit of 0.5 psia)
and speciations
• New, average, poor paint factors

Tanks Essentials 3/31/18 Page 145


Fixed-Roof Tank Emissions Strategy
Permit calculation considerations
Un-capped Options:
• Divide annual throughput evenly into each month (1/12)
• Normalize for number of days in month (31/365,
28/365,…)
• Total annual in each month, then use maximum working
loss
• Total annual in each month, then use max working loss
/ KN (hybrid)

Tanks Essentials 3/31/18 Page 146


Fixed-Roof Tank Emissions Strategy
Permit calculation considerations
Un-capped Options:

Tanks Essentials 3/31/18 Page 147


Fixed-Roof Tank Emissions Strategy
Permit calculation considerations
Hourly emissions:
• Use working loss equation only (neglect breathing)
• Use greater liquid surface temperature of either 95⁰F or maximum monthly
liquid surface temperature
• Use annual throughput based on maximum fill rate
• Set KN, KP, and KB = 1
• New after Dec. 2016, set KP = 0.6 for crude oil (was 0.4)
5.614 Q 1 1
LW,MAX = N [ HLX (π/4) D2 ] KN KP WV KB / 8760

LW,MAX = 5.614 QMAX KP WV / 8760 [lb/hr]

Tanks Essentials 3/31/18 Page 148


Floating Roof Tank: Working Losses

Tanks Essentials 3/31/18 Page 149


Floating-Roof Tank Withdrawal (Clingage) Loss
Equation (2-4) for estimating withdrawal loss, LWD:
LWD = 0.943 Q/D CS WL [ 1 + NC FC / D ]
where
0.943 = constant [1000 ft3-gal/bbl2]
Q = annual throughput [bbl/year]
D = tank diameter [feet]
CS = shell clingage factor [bbl/1000 ft3] (product and lining
dependent)
WL = organic liquid density [lb/gal]
NC = number of support columns [dimensionless]
FC = effective column diameter [feet]
Tanks Essentials 3/31/18 Page 150
Floating-Roof Tank Withdrawal (Clingage) Loss

Note:
When speciating emissions from floating roof tank
withdrawal losses, the liquid phase concentrations
must be applied

(This would not be appropriate for standing losses)

Tanks Essentials 3/31/18 Page 151


Floating Roof Tank Driving Forces for
Emissions: Standing Losses

Tanks Essentials 3/31/18 Page 152


Floating-Roof Tank Standing Loss
Equation for estimating standing storage loss, LS:
LS = [LR + LF + LD]
where
LR = total rim seal loss [lb/year] (2-2)
FF = total deck fitting loss [lb/year] (2-5)
FD = total deck seam loss [lb/year] (2-9)

Tanks Essentials 3/31/18 Page 153


Floating-Roof Tank Rim Seal Loss
Equation (2-2) for estimating rim seal loss, LR:
LR = [KRa + KRb Vn] D P* MV KC
where
KRa = zero wind speed rim seal loss factor [lbmol/ft-year]
(Table 7.1-8)
KRb = wind dependent rim seal loss factor [lbmol/(mph)n-ft-year]
V = average ambient wind speed at tank site [mph]
n = seal-related wind speed exponent [dimensionless]
P* = vapor pressure function [dimensionless] (2-3)
MV = stock vapor molecular weight [lb/lbmol]
KC = product factor [dimensionless – 0.4 or 1]
Tanks Essentials 3/31/18 Page 154
Floating-Roof Tank Rim Seal Loss
Equation (2-2) for estimating rim seal loss, LR:
P* = (PVA / PA) / [1 + (1 - PVA / PA )0.5]2
where
PVA = vapor pressure at daily average liquid surface temperature [psia]
PA = atmospheric pressure [psia]

Tanks Essentials 3/31/18 Page 155


Floating-Roof Tank Deck Fitting Loss
Equation (2-5) for estimating deck fitting loss, LF:
LF = FF P* MV KC
where
FF = total deck fitting loss factor [lbmol/year] (2-6, 2-7)
P* = vapor pressure function [dimensionless] (2-3)
MV = stock vapor molecular weight [lb/lbmol]
KC = product factor [dimensionless – 0.4 or 1]

Tanks Essentials 3/31/18 Page 156


Floating-Roof Tank Deck Fitting Loss
Equation (2-6) for estimating total deck fitting loss
factor, FF:
FF = [(NF1 KF1) + (NF2 KF2) +…+ (NFf KFf)]
where
NFi = number of fittings (i = 0, 1, 2,…,nf) [dimensionless]
KFi = deck fitting loss factor [lbmol/year] (2-7)

Tanks Essentials 3/31/18 Page 157


Floating-Roof Tank Deck Fitting Loss
Equation (2-7) for estimating deck fitting loss
factor, KFi:
KFi = Kfai + Kfbi (KV V)mi
where
Kfai = zero wind speed loss factor for fitting [lbmol/year]
Kfbi = wind speed dependent loss factor for fitting [lbmol/year]
KV = fitting wind speed correction factor [dimensionless – 0.7 or 0]
V = average ambient wind speed [mph]
mi = loss factor for deck fitting [dimensionless]

Tanks Essentials 3/31/18 Page 158


Floating-Roof Tank
Deck Fitting Loss
AP-42, Table 7.1-12

Tanks Essentials 3/31/18 Page 159


Floating-Roof Tank (Relative) Guidepole Losses

Tanks Essentials 3/31/18 Page 160


Floating-Roof Tank Deck Seam Loss
Equation (2-9) for estimating deck seam loss, LD:
LD = KD SD D2 P* MV KC
where
KD = deck seam loss factor [lbmol/ft-year]
SD = deck seam length factor [ft/ft2]
D = tank diameter [ft]
P* = vapor pressure function [dimensionless] (2-3)
MV = stock vapor molecular weight [lb/lbmol]
KC = product factor [dimensionless – 0.4 or 1]

Tanks Essentials 3/31/18 Page 161


Floating-Roof Tank Emissions Strategy
Permit calculation considerations
Compliance challenges and NSR challenges:
• Maximize flexibility? Capping emissions?
• Minimize emissions increases?
Annual calculation strategy:
• Total throughput on a tank basis (how one divides these into the
month can create issues for cascading tanks)
• Cap total throughput on a product basis (greater flexibility)
• Actual product vapor pressures (vs use maximum regulatory limit
of 11.0 psia) and speciation
• New, average, poor paint factors

Tanks Essentials 3/31/18 Page 162


Floating-Roof Tank Emissions Strategy
What about those throughput options?
• Divide annual throughput evenly into each month (1/12)
• Normalize for number of days in month (31/365, 28/365,…)
• Total annual in each month, then use maximum working loss
• Total annual / “x” in each month, then use “x” max working losses
(hybrid)

Tanks Essentials 3/31/18 Page 163


Floating-Roof Tank Emissions Strategy
Permit calculation considerations
Hourly emissions:
Use total emissions (working and breathing)
Use maximum monthly emission rate divided by hours in
the month
Hottest month for IFR tank
Not necessarily hottest month for EFR tank
Use throughput based on maximum withdrawal rate for
EFR tank, fill/withdrawal rate for IFR tank (TCEQ guidance)

Tanks Essentials 3/31/18 Page 164


Tank Emissions Speciation
• Guidance given in API MPMS 19.4
• Generally perform Partial Speciation to obtain emissions
of selected compounds (HAPs, Toxics, etc.)
• Requires knowing the concentration of the compounds of
interest in the liquid phase of the mixture
• Speciate fixed roof tank emissions based on vapor phase
• Speciate floating roof standing emissions based on vapor phase
• Speciate floating roof withdrawal emissions based on liquid phase

Tanks Essentials 3/31/18 Page 165


Air Regulations Introduction

Tanks Essentials 3/31/18 Page 166


Tanks Essentials 3/31/18 Page 167
Regulatory Basics
• The rules are confusing
• Even EPA staff have called them “incomprehensible”
• The rules are complex
• 16 or more air rules may apply to a floating-roof tank
• The rules are conflicting
• Requirements from one rule to the next are inconsistent
• The rules are cumbersome
• Monitoring/Inspection, Recordkeeping, and Reporting
Tanks Essentials 3/31/18 Page 168
Regulatory Basics – Common Considerations
• First step is determining applicability
• Is the tank new, newly modified/reconstructed, or existing?
• Is the site a major source of HAPs or a named industry in
the MACT/GACT rules?
• Are there state rules, permit conditions, or consent decrees
that might affect applicability?
• Most rules have a minimum applicable volume and vapor
pressure for triggering controls/inspection/reporting
• MACT may also have minimum HAPs concentration limits
Tanks Essentials 3/31/18 Page 169
Regulatory Basics – Common Considerations
• For new tanks, New Source Performance Standards (NSPS),
60 Supbart Kb, may apply
• Check with your environmental expert to determine additional
rule overlap
• Most* rules have vapor pressure cutoffs of 0.5 psia and 11.0
psia
• Below 0.5 psia, no floating roof required
• Above 0.5 psia, floating roof required
• Above 11.0 psia, add-on closed-vent to controls required
• *Be very careful to check when dealing with NESHAPs tanks,
MACT sites, or permit/applicability concerns
Tanks Essentials 3/31/18 Page 170
Regulatory Basics – Common Considerations
• Most tanks below 20K gallons will be exempt
• Some tanks between 20K gallons and 40K gallons will be
exempt
• Most tanks above 40K gallons will be applicable
• Applicable tanks will have monitoring and reporting
requirements

Tanks Essentials 3/31/18 Page 171


Regulatory Basics – “Universal” Controls
For floating roof tanks controls, as specified in MACT WW (63
Subpart WW), are:
• IFR Rim seal: liquid mounted, mechanical shoe, or vapor
mounted primary with a secondary wiper
• EFR Rim seal: liquid mounted primary with a secondary;
mechanical shoe primary with a secondary
• All fittings except rim vents and vacuum breakers should
have wells that extend into liquid surface

Tanks Essentials 3/31/18 Page 172


Regulatory Basics – “Universal” Controls
• All fitting wells (except roof legs and emergency drains),
should be equipped with gasketed covers, closure device, etc.
• May elect slotted membrane (90% closed) for sample wells

• May elect covers equivalent 90% closed for deck drains

• Gauge float and manway lids: gasketed and bolted/latched

Tanks Essentials 3/31/18 Page 173


Regulatory Basics – “Universal” Controls
• Unslotted guidepoles:
• Gasketed lid, wiper, and welded lid or gasketed hatch at top of
pole

• Slotted guidepoles:
• Gasketed lid, wiper, pole sleeve

• Gasketed lid, wiper, pole float

Tanks Essentials 3/31/18 Page 174


Open Discussion

Jim Miller, PE
(512) 297-6448

Special Note: Credit for the tank design diagrams and information used in this presentation is given to
Rob Ferry, TGB Partnership and associated content used under the permission of the 4C Conference.