ET10 Series Stand-alone

LCD Fan Coil Thermostat

Features
Modern Appearance
Stylish Rotary dial and buttons
Large LCD with backlight
Separate power supply unit with high
performance relay outputs
Retention of temperature set-point and fan-
speed upon power failure
Unoccupied mode contact for energy saving
Window contact for remote system on-off
control
Thermostat on-off interlocking digital output
2-wire on-off, 3-wire floating and 0-10 VDC
models available
Dual-output model provides auto cooling/
heating changeover with adjustable
deadband
PI Algorithm
Remote sensor capability
Seasonal changeover sensor availability
Optional remote controller
General
The ET10 Standalone LCD Fan Coil Thermostats are
Selectable Functions
designed to control heating, cooling, or year round air
Selectable ºC or ºF temperature display conditioning units in commercial, industrial and
Field selectable program to retain last residential Installation. Typical application includes the
operation mode upon power failure control of fan coil units, packaged terminal air
Measured temperature off-set conditioners and combination heating and cooling
Selectable P-band and I-time equipment. As part of the system that consists of two-
Selectable Actuator stroke time (3-wire way or three-way valve and a multi-speed line voltage
floating model) fan.
Selectable 1 to 5 K deadband (dual-output
models) ET10 consists of 2 units; Display Control Unit (DCU)
Field adjustable high and low set point limit and Power Supply Unit (PSU).
Field adjustable cooling and heating energy
saving mode set points Ordering
Selectable fan action in unoccupied mode To order the ET10 Series thermostat, contact the
Selectable Auto Fan sequence in heating nearest Cyrus’ representative. Specify the desired
mode product code number from model selection guide.
Selectable operating mode sequence for
dual-output models
Selectable manual/auto operating sequence
for single output models
Selectable constant display of temperature
between sensing or set-point

1
ET10-E004-1205 May 2012
Product Overview
The ET10 are line voltage LCD fan coil thermostat Model ET10-2 and ET12-2
with 11 basic models that cover all type of FCU The Model ET10-2 is line voltage LCD fan coil
standalone applications. The thermostat consists thermostat that is designed for cooling / heating fan
of 2 units; the Display Control Unit (DCU) and the coil unit with 2-wire line-voltage valve actuators
Power Supply Unit (PSU). There are models for application (ET12-2 provides 24 VAC valve outputs).
cooling only, heating only and heating/cooling fan coil Integral with system of Cooling-Heating-Auto-Fan-Off
system integrate with 2-wire, 3-wire or 0-10 VDC switch that allows users to cutoff power for fan and
input valve control. On-board high accuracy NTC the output for valve actuator. Simply pressing the fan
sensor allows precision comfort control over occupied speed button, allows users to select Auto-High-Med-
space area. Low fan speed. All fan outputs by relay that can
withstand max. of 5 Amp (resistive) 2 Amp (Inductive)
The DCU of ET10 can be surface mounted or operating current.
secured to a standard European 75 x 75 x 35 mm
electrical box. Two M3.5 mounting screws are Model ET10-2F and ET12-2F
included. The Model ET10-2F is line voltage LCD fan coil
thermostat that is designed for cooling / heating fan
Model ET10-1 and ET12-1 coil unit with 3-wire line-voltage valve actuators
The Model ET10-1 is line voltage LCD fan coil application (ET12-2F provides 24 VAC valve
thermostat that is designed for cooling only / heating outputs). Integral with system of Cooling-Heating-
only fan coil unit with 2-wire line-voltage valve Auto-Fan-Off switch that allows users to cutoff power
actuator application (ET12-1 provides 24 VAC valve for fan and the output for valve actuator. Simply
outputs). Integral with system of Cooling/Heating- pressing the fan speed button, allows users to select
Fan-Off switch that allows users to cutoff power for Auto-High-Med-Low fan speed. All fan outputs by
fan and the output for valve actuator. Simply relay that can withstand max. of 5 Amp (resistive) 2
pressing the fan speed button, allows users to select Amp (Inductive) operating current.
Auto-High-Med-Low fan speed. All fan outputs by
relay that can withstand max. of 5 Amp (resistive) 2 Model ET10-2A
Amp (Inductive) operating current. The Model ET10-2A is line voltage LCD fan coil
thermostat that is designed for cooling / heating fan
Model ET10-1F and ET12-1F coil unit with 0-10 VDC valve actuators application.
The Model ET10-1F is line voltage LCD fan coil Integral with system of Cooling-Heating-Auto-Fan-Off
thermostat that is designed for cooling only / heating switch that allows users to cutoff power for fan and
only fan coil unit with 3-wire valve line-voltage the output for valve actuator. Simply pressing the fan
actuator application (ET12-1F provides 24 VAC valve speed button, allows users to select Auto-High-Med-
output). Integral with system of Cooling/Heating-Fan- Low fan speed. All fan outputs by relay that can
Off switch that allows users to cutoff power for fan withstand max. of 5 Amp (resistive) 2 Amp (Inductive)
and the output for valve actuator. Simply pressing operating current.
the fan speed button, allows users to select Auto-
High-Med-Low fan speed. All fan outputs by relay
that can withstand max. of 5 Amp (resistive) 2 Amp
Model ET10-2AH
(Inductive) operating current. The Model ET10-2AH is line voltage LCD fan coil
thermostat that is designed for cooling / heating fan
coil unit with 0-10 VDC cooling valve actuator and 2-
Model ET10-1A wire on-off heating control application. Integral with
The Model ET10-1A is line voltage LCD fan coil system of Cooling-Heating-Auto-Fan-Off switch that
thermostat that is designed for cooling only / heating allows users to cutoff power for fan and the output for
only fan coil unit with 0-10 VDC valve actuator valve actuator. Simply pressing the fan speed button,
application. Integral with system of Cooling/Heating- allows users to select Auto-High-Med-Low fan speed.
Fan-Off switch that allows users to cutoff power for All fan outputs by relay that can withstand max. of 5
fan and the output for valve actuator. Simply Amp (resistive) 2 Amp (Inductive) operating current.
pressing the fan speed button, allows users to select
Auto-High-Med-Low fan speed. All fan outputs by
relay that can withstand max. of 5 Amp (resistive) 2
Amp (Inductive) operating current.

2
LCD Segments and Buttons

Auto Mode Fan Mode


Heating Mode Unoccupied Mode
Cooling Mode Window Mode

LCD
Fan key
Set-point dial
IR receiver
System key
Temperature

Med Fan
Auto Fan

Low Fan
88 8AUTO
o
o
C
F
Celsius
Fahrenheit

High fan

Operation Notes
Temperature Display LCD shows sensing temperature constantly except when temperature set point adjustment is being made

Backlight The backlight will light up for 5 seconds when any button is pressed

Mode of operation Press the system control key to enter into the desired operating mode: Cool-Heat-Auto-Fan Only-Off

Fan speed Press the fan control key to change the fan speed mode: High-Med-Low-Auto

Temperature Set-point Increase or decrease temperature set point by rotating the adjustment dial clockwise or counter-clockwise.

Unoccupied Mode The energy saving mode is activated while “OCU” contact is in closure. In unoccupied mode, all buttons are
locked and preset temperature set points are 26 oC and 16 oC for cooling and heating respectively. Fan
(Energy-saving)
speed is always set at “low”.

Window Contact Window contact closure turns off the thermostat and locks all buttons

Parameter setup menu The thermostat allows authorized service agent to change the certain number of operating parameters,
please refer to parameter setup manual for details.

Dimensions in mm

Power Supply Unit


Display Control Unit

Remote Controller

3
Wiring Diagrams and Application Notes
■ Cut jumper JP1 open if an external sensor is wired to SR1 and GND. Run the wiring away from any electrical
motors or power wiring. Failure to do so may result in poor thermostat performance due to electrical noise.
■ 22 or 24 AWG twisted shielded pair double-insulated cable is recommended as remote sensor wiring and its
length must not exceed 25 m.
■ Connecting wires between Display Control Unit and Power Supply Unit must not exceed 15 m.
■ Do not bundle and run power wiring and remote sensor wiring in the same conduit.
■ The seasonal changeover sensor should be wrapped around the supply water pipe when associated with a
water system. When the changeover sensor temperature exceeds 30 ºC, the thermostat enters into heating
mode.
■ Unoccupied contact closure activates unoccupied mode.
■ Window contact closure activates thermostat lockout mode.
■ DI1 provides a thermostat on-off interlocking output.
■ Hidden-line wiring for Terminals V2 and 6 are applicable to ET10-2 only.
■ The thermostat outputs are designed for controlling zone valves. If used for controlling electric heaters,
external contactors must be used.

More wiring diagrams are available, please contact the nearest Cyrus’ representative for details

WARNING
Incorrect wiring connection may cause permanent equipment damages to the thermostat

ET10-1/ET10-2 Wiring Diagram DO1+


DO-

CN3

6-conductor cable (shielded recommended)


Inter-connecting wires: Cat 5e Twisted
Sensor wires: 22 AWG twisted shielded
pair double-insulated cable

Power wires: wire size


1 mm2 or 18 AWG solid
copper recommended

4
Technical Specifications

Product Model See ET10 Series Model Number Selection Guide

Power Requirements 220 V, +/- 10%, 50/60 Hz,

Sensing Element NTC thermistor, 10 kΩ@25ºC; accuracy ±0.5 K@25ºC

Operating Temperature Differential Fixed at 1 K for both cooling and heating modes
(for 2-Wire On-Off Models)

Temperature Display Range 5-35ºC in 0.5 K increments: accuracy ±1 K


(41-95ºF in 1.0 R increments, accuracy ±2 R)

Temperature Set Point Range 5-35ºC in 0.5 K increments, initial factory setting at 22ºC
(41-95ºF in 1.0 R increments)

Deadband of Dual-Output Models 3 K (Adjustable 1 to 5 K in setup menu

Auto Fan Temperature Differential At 2 K (4 R) increments. At >0 K, fan is on low speed in cooling mode and fan
status in heating mode depends on auto fan action selection setting.

Offset of measured temperature +2, +1, 0, -1 and -2 K (+2, +1, 0, -1 and -2 R) , factory setting 0

Valve Stroke Time (3-Wire Models) 10, 60, 90,120, 150,180, 210 or 240 seconds

Proportional Band Adjustable 1 to 10 K (2-10 R) in 1 K (1 R) increments, factory setting 5 K (5 R)

Integral Time Adjustable 0 to 30 minutes in 1 minute increments, factory setting 15 minutes.


Setting = 0 means integral time being turned off.
Unoccupied & Window contacts Input signal from external voltage-free contact

Body Material Self-extinguishing, molded ABS

Finish Off white body / grey face plate (white face plate is available up on request)

Electrical Ratings Valve output 220 V, 3 A resistive, 1 A inductive, 50/60 Hz


24 V, 0.3A resistive / inductive, 50/60 Hz
Fan output relays 220 V, 5 A resistive, 2 A inductive, 50/60 Hz

Total rating 220 V, 5 A maximum, 50/60 Hz

0-10 VDC output impedance Minimum 10,000 Ω

Ambient/Storage Temperature Limits 0 to 50 oC / -30 to 50 oC, 10% to 90% RH non-condensing

Connections Non-removable terminal blocks

Power Wires Wire size 1 mm2 or 18 AWG solid copper recommended

Sensor Wires 22 AWG twisted shielded pair double-insulated cable

DCU to PSU Interconnection Cat 5e twisted 6-conductor cable (shielded or unshielded)

Agency Approval CE Mark compliant to EMC and low voltage directives

Shipping Weight 550 g

Dimensions See Dimensions drawing in mm

5
Model Selection Guide

ET1 0 - 2AH - W

Power 0 = 220 VAC, 50/60 Hz

2 = 220 VAC, 50/60 Hz with 24 VAC valve output 0

Valve Control Output 1 = 2-wire on-off (Heating only or Cooling only2-pipe)

1F = 3-wire floating (Heating only or Cooling only 2-pipe)

1A = 0-10 VDC (Heating only or Cooling only 2-pipe)

2 = 2-wire on-off (Heating / Cooling 4-pipe)

2F = 3-wire floating (Heating / Cooling 4-pipe)

2A = 0-10 VDC (Heating / Cooling 4-pipe)

2AH = 0-10 VDC Cooling + 2-wire on-off Heating (4-pipe) 2AH

Options & LCD layout Nil = Grey Face-plate

W = White Face-plate

R = IR Receiver for Remote Controller H

Repair and Replacement Ordering Information


If the thermostat fails to operate within its Use this ET10 Series Line Voltage Fan Coil
specifications, replace the unit of the DCU or the PSU Thermostat only as an operating control. Where
or a complete set. To order the replacement, contact failure or malfunction of the ET10 Series Thermostat
the nearest Cyrus’ representative. Specify the could lead to personal injury or property damage to
desired product code number from table above. the controlled equipment or other property, additional
precautions must be designed into the system.
IMPORTANT: Incorporate and maintain other devices such as
The power supply to the thermostat must include supervisory or alarm systems or safety or limit
overload protection. Failure to include overload controls intended to warn of, or protect against,
protection may result in damage to the thermostat. failure or malfunction of the ET10 Series Thermostat.

Error Codes
When the following errors are reported on the LED display unit, the thermostat will be out of operation:

E-1 EEPROM read/write error


E-2 Remote temperature sensor open-circuited while JP1 jumper is cut
E-3 Remote temperature sensor short-circuited while JP1 jumper is cut

Trouble-Shooting
Before trouble-shooting starts, ensure that the voltage output from Terminals 1 (GND) and 2 (+5 Vdc) on the
power supply unit is between 5 Vdc and 5.25 Vdc and not higher. Higher voltage may damage the internal
circuitry and components of the display control unit.

When abnormal power voltages are found, return the thermostat to the manufacturer for repair.

When there is no 5 Vdc power output, check the line voltage power and its 5 A fuse.

The specification above are normal and conform to generally acceptable industry standard. Cyrus is not
responsible for damages resulting from misapplication or misuse of its products.