Model: PKFY-P18NHMU-E

Job Name: Location:

Drawing Reference: Schedule No.

System No.: Date:

GENERAL FEATURES

Net Weight
Unit………………..…...……………..................29 lbs. / 13 kg

Coil Type………………...........................................….Cross Fin


(Aluminum Plate Fin and Copper Tube)

Fan
Type x Quantity………………..…………...Line Flow Fan x 1
Airflow Rate (Low-Mid-High)...…….……...320 - 370 - 425 CFM
Motor
• R410A refrigerant Type………..………..………..………..Direct-drive DC Motor
• Seven sizes from 6,000 to 30,000 Btu/h Output………..………..………..………..………..….0.030 kW
• Powerful airflow (CFM)
• Compact, lightweight, shiny-white, flat-panel design Air Filter..…………………………….Polypropylene Honeycomb
• Quiet operation
Refrigerant Piping Dimensions
• Multiple fan-speed settings Liquid (High Pressure)……............…1/4" / 6.35 mm (Flare)
• Intake grille filter is easily removed for cleaning Gas (Low Pressure)………………..…1/2" / 12.7 mm (Flare)
• Built-in receiver is standard
Drainpipe Dimension……............……...…….I.D. 5/8" / 16 mm

Sound Pressure Levels


Low-Mid-High….…………….…………….36 - 41 - 45 dB(A)

OPTIONS
□ Condensate Pump…………………………………SI3100-230
□ External Heat Adapter……………………….……PAC-725AD
□ CN24 Relay Kit…………………………CN24RELAY-KIT-CM
SPECIFICATIONS
* Cooling / Heating capacity indicated at the maximum value at
Capacity* operation under the following conditions:
Cooling…………………………………………….…18,000 Btu/h Cooling: Indoor 80°F (27°C) DB / 67°F (19°C) WB, Outdoor 95°F
Heating……………………………………………....20,000 Btu/h (35°C) DB
Heating: Indoor 70°F (21°C) DB, Outdoor 47°F (8°C) DB / 43°F (6°C) WB
Power
Power Source………………..........208 / 230V, 1-phase, 60Hz Note: Ventilation air: Providing sufficient ventilation air is an impor-
Power Consumption tant part of every building design. ASHRAE Standard 62 provides
Cooling…………………………………………….………0.03 kW the minimum ventilation air requirement. Also, check local codes.
Heating…………………………………………….………0.03 kW
Current
Cooling……...................................................……………0.30 A
Heating……...................................................……………0.30 A
Minimum Circuit Ampacity (MCA)……………….…..……...0.38 A
Maximum Overcurrent Protection (MOCP) Fuse..….......…..15 A

External Finish……………...….………Munsell No. 1.0Y 9.2 / 0.2

External Dimensions
Inches………………………..11-5/8 H x 35-3/8 W x 9-13/16 D
mm………………………………………295 H x 898 W x 249 D
Model: PKFY-P18NHMU-E – DIMENSIONS
15-3/16(387) 7-1/2(192)
Top side
Unit : in(mm)

7-3/4(197)
Mount board

23-9/16(599)
Front side Right side

11-9/16(295)
A

Left side 9-3/4(249) 3/16(5)


D 2-1/8 27-1/16(688) 6-1/16(155)
(55)
Knock out hole 35-5/16(898)
for left piping Knock out hole
for right piping
Front side(Grille open)
Sleeve
(purchased locally) Through hole

2-1/2~ 3-1/8 2-1/2~ 3-1/8


~ ~
( 65 80) ( 65 80)

Terminal block for power supply

Terminal block for transmission

Terminal block for


MA-remote controller

17-15/16(457)Gas pipe 6-5/8(169)


Emergency operation switch
21-3/16(539)Liquid pipe 6-3/16(158) (cooling/heating)
24(610)Drain hose 7-3/16(184)

Under side
Vane(auto) Operation lamp DEFROST/STAND BY lamp
24-1/16(612)
5/16(8)

Refrigerart
Piping Liquid pipe 1/4F ( 6.35)

Gas pipe 1/2F ( 12.7)

Drain hose 5/8 ( 16) I.D


Knock out hole
for lower piping

Louver(manual) Knock out hole Receiver


C for lower piping B

Center measurement hole 3/32( 2.5)


2-1/4(58)

Mount board
5/32(3.8)

4- 5/16( 9) Bolt hole


0
11-7/16(291.5)

11-7/16(291.5)
14-5/8(372.3)

12-7/8(327.5)

12-7/8(237.5)

14-5/8(372.3)
8-13/16(225)
7-13/16(200)

7-13/16(200)
8-13/16(225)

Indoor unit outline


10-3/8(265)

9-5/16(238)
10-3/8(265)
4-7/8(125)
14(356.3)

14(356.3)
2-3/4(70)

77- 3/16( 5.1)


Tapping
9/16(15)
9/16(15)

4-7/8(125)
2-3/4(70)

screw hole
0

13/16(21.8)
0
5/8(16) 0
1-1/16(28.5) 3/4(20)
1-9/16(41) 1-1/4(32.7)
3-1/16(78.5) 2-1/16(53.5)
3-9/16(91) 2-9/16(66)
4-1/16(103.5)
4-9/16(116) 5(128.5)
6-1/2(166) 6(153.5)
7(178.5)
8(203.5)
9-1/8(232.5) 9-1/16(231.5)
9-15/16(253.5)
10-3/4(273.2)
17-5/8(449)
0

Wall hole
10-15/16(278.3)

6-13/16(174)

for
4-1/2(115)
9-5/16(238)

6-9/16(167)

7-9/16(193.5)
5-1/2(140)

11-1/16(281)
15-1/2(394)

7-1/16(180.3)
8-3/8(213)
17-5/8(449)

left rear Knock out hole for


piping left rear piping Wall hole for
2-3/4×12-3/16(70×310) right rear piping

Knock out hole for piping Required space(Indoor unit)


(mm)
Min.1-31/32(50)

Air inlet
2-11/16(69)

250mm,9-13/16inch or greater with


2-3/16(56)

optional drain pump installation.

C Air inlet
1-11/16(43)

7/16(12.5) 2-3/16(56) D
Min.9-13/16(250)
3/16(6)

1-11/16(43)
Air outlet
Min.1-31/32(50)
Min.1/4(7)
2-3/16(56)

Min.8-5/8 Min.5-7/8(150)
1-3/4(46)

(220)
1-11/16(43)
2-5/16(59)

A
1-3/4(46)
3/16(6)

1-11/16(43) B
2-5/16(60)

Mitsubishi Electric Air Conditioning & Refrigeration Systems Works acquired ISO
9001 certification under Series 9000 of the International Standard Organization (ISO)
based on a review of quality warranties for the production of refrigeration and air
conditioning equipment.

ISO Authorization System


The ISO 9000 series is a plant authorization system relating to quality warranties as
stipulated by the ISO. ISO 9001 certifies quality warranties based on the "design,
Certificate Number FM33568 development, production, installation and auxiliary services" for products built at
an authorized plant. HVAC Advanced Products Division
Mitsubishi Electric & Electronics USA, Inc.
Mitsubishi Electric Air Conditioning & Refrigeration Systems Works acquired environmental
3400 Lawrenceville Suwanee Rd.
management system standard ISO 14001 certification. Suwanee, GA 30024
The ISO 14000 series is a set of standards applying to environmental protection set by the Tele: 678-376-2900 • Fax: 800-889-9904
International Standard Organization (ISO).
Toll Free: 800-433-4822 (#4)
Certificate Number EC97J1227
www.mehvac.com
C SD - PKFY-P18NHMU-E - 1 - 201104 Specifications are subject to change without notice.