by standard IEC 60947-2.
For complete protection of the motor and
its control device, overload protection may
be provided by either the circuit breaker or
Breaking H 70
a separate Telemecanique thermal relay. capacity (kA rms)
The control device may be of the direct 380/415 V
on-line type (with or without reversing) General circuit-breaker characteristics page 46
or of the “star-delta” type. The Compact NS80H-MA circuit breaker is specially designed for motor protection.
Accompanying trip unit page 46
Combinations are governed by standard A built-in MA magnetic trip unit provides short-circuit protection.
IEC 60947-4.1.
Motor protection up to 250 kW
E26988
045198
041624
Breaking N 25 36 45
capacity (kA rms) H 70 70 70
380/415 V L 150 150 150
General circuit-breaker characteristics page 18
Compact NS100 to 630 circuit breakers for motor protection are the same as those for
distribution systems, but are fitted with specific motor trip units.
Accompanying trip units pages 47 to 51
MA magnetic trip units provide short-circuit protection. Interchangeable ME electronic trip units
provide protection against short-circuits, overloads and phase unbalance.
44
Selection of a trip unit or Micrologic control unit
P (kW) (400 V, 50 Hz) 0.37 1.1 5.5 18.5 37 110 160 250 560 750
E26530
Ir (A) 1.5 2.5 12 40 50 80 100 160 200 220 320 500 800 1000 1350
Compact
MA
NS80H-MA
Compact MA
NS100 … NS250
STR22ME
Compact MA
NS400 … NS630
STR43ME
Compact
Micrologic 2.0 A / 5.0 A / 7.0 A
NS630b … NS1600
45
Functions and Motor protection
characteristics Compact NS80H-MA
This circuit breaker is specially designed for Compact circuit breakers NS80H-MA
the protection of motors rated up to 37 kW: Number of poles 3
b due to its high current-limiting capacity, Control manual (toggle, b
direct or extended rotary handle) b
it effectively protects motor starters (type-2 electric -
coordination as per IEC 60947-4, with Connections fixed front connection b
contactors) rear connection -
withdrawable front connection -
b small size for easy installation in motor rear connection -
control centre (MCC) switchboards. Electrical characteristics as per IEC 60947-2
Rated current (A) In 65 °C 80
Rated insulation Ui 750
voltage (V)
046751
46
Compact NS100 to 630 circuit
breakers with MA magnetic trip units
Compact NS250H
045198
Compact NS400H-MA
47
Functions and Motor protection
characteristics Compact NS100 to 250
circuit breakers with STR22ME
electronic trip unit
Compact NS100 to 250 circuit breakers, Compact NS100 to 250 circuit breakers
equipped with an STR22ME electronic trip See the circuit breakers for distribution systems on page 18.
unit with adjustable thresholds, offer:
b short-circuit protection
b phase-unbalance protection
STR22ME electronic trip unit
b overload protection Protection
b suitability for isolation. Overload protection
LT (long time) protection with adjustable Ir threshold, in compliance with tripping
class 10 as defined by IEC 60947-4.
052163
Short-circuit protection
Short-time and instantaneous protection:
b short-time protection with fixed pick-up (Im = 13 x Ir) and tripping delay
b instantaneous protection with fixed pick-up (15 x In).
Phase-unbalance protection
This function complies with the stipulations of standard IEC 60947-4.1 and trips the
circuit breaker whenever a phase-current unbalance of 40 % or more occurs. The
circuit-breaker opening time is between 3.5 and 6 seconds.
Test
A mini test kit or a portable test kit may be connected to the test connector on the
front to check circuit-breaker operation after installing the trip unit or accessories.
48
t 1 7 6
E26985
E94521
Ir
In=50A ImSTR 22 ME u1,05 Ir
Ir 37.5 40
7,2Ir IEC 947.4 / cl.10
35.5 42.5
3
33.5 45 7,0s
4
31.5 47.5
5 30 50
A Ir 13 Ir test
0 Ir 13Ir I
49
Functions and Motor protection
characteristics Compact NS400 to 630
circuit breakers with STR43ME
electronic trip unit
Compact NS400 to 630 circuit breakers, Compact NS400 to 630 circuit breakers
equipped with an STR43ME electronic trip See the circuit breakers for distribution systems on page 18.
unit with adjustable thresholds, offer:
b short-circuit protection
b phase-unbalance protection
STR43ME electronic trip unit
b overload protection Protection
b suitability for isolation. Overload protection
True (rms) long-time protection with an adjustable threshold:
b Io base setting (5 settings from 0.5 to 0.8) and Ir fine adjustment
(8 settings from 0.8 to 1)
053192
Fault indications
LEDs indicate the type of fault that caused tripping:
b overload (long-time protection) or abnormal component temperature (> Ir)
b short-circuit (short-time protection) or instantaneous (> Isd)
b phase unbalance (LED on the right)
b microprocessor malfunction:
v all four (%Ir), (> Ir), (> Isd) and (phase unbalance) LEDs ON.
Battery powered. Spare batteries are supplied in an adapter box. When a fault
occurs, the LED indicating the type of fault goes OFF after approximately ten
minutes to conserve battery power. The information is however stored in memory
and the LED can be turned back ON by pressing the battery/LED test pushbutton.
The LED automatically goes OFF and the memory is cleared when the circuit
breaker is reset.
Test
A mini test kit or a portable test kit may be connected to the test connector on the
front to check circuit-breaker operation after installing the trip unit or accessories.
The test pushbutton tests the battery and the LEDs.
Self monitoring
The circuit breaker trips if a microprocessor fault or an abnormal temperature is
detected.
Options
Three options are available:
b ammeter (I)
b contactor tripping module (SDTAM)
b communication (COM).
50
t
E26987
6 1 2 3 7
1
2
E32566
STR 43 ME %Ir >Ir >Isd test fault
Io Ir Isd µP
3 .71 .8 .90 .93 9 10
.63 .88 .95 8 11 > Ir
4 .56 .85 .98 7 12 A
.5 .8 .8 1 13 tr
5 x In x Io
6
x Ir
> Im
tsd
tr 20 20 > Ih
test 10 Ir I1 I2 I3
10
0 Ir Isd Ii I + - 10A 10A
Ir Isd li
Communication (COM)
This option transmits data to Digipact distribution monitoring and control modules.
Transmitted data:
b settings
b phase currents (rms values)
b highest current of the three phases
b overload-condition alarm
b cause of tripping (overload, short-circuit, etc.).