Sei sulla pagina 1di 13

L:\EED_DESIGN_DATA\CAD STANDARDS\WWS STD SUBMITTALS\LIFT STATION TO DEVELOPER\WWS WEBSITE 6.6.2013\WWED LIFT STATIONS TEMPLATE.

dwg, COVER SHEET (G-1), 6/6/2013 3:53:11 PM, CBGARCIA, Adobe PDF.pc3

TYPICAL STANDARD LIFT STATION


THESE TYPICAL LIFT STATION PLANS CONTAIN WWS MINIMUM REQUIREMENTS AND ARE INTENDED TO
PROVIDE A BASIS FOR SITE ADAPTATION AND DESIGN BY A QUALIFIED ENGINEER. THE INFORMATION
HEREIN CONTAINED SHALL ONLY BE USED AS A GENERAL GUIDELINE FOR THE INTENDED OPERATION
AND FUNCTIONS AND SHALL NOT BE CONSTRUED AS ALL INCLUSIVE.

ENGINEER OF RECORD AND CONSULTANTS USING THESE GUIDELINES SHALL VERIFY AND MODIFY ANY
REQUIREMENT NOT NECESSARILY SHOWN AS MAY BE REQUIRED BY ANY AND ALL APPLICABLE CODES
AND STANDARDS.

FOR TRIPLEX STATIONS AND FOR ALL LIFT STATIONS REQUIRING AN ONSITE GENERATOR, DESIGNER
SHALL CONSULT WITH WWS FOR ADDITIONAL REQUIREMENTS. THESE STANDARDS APPLY ONLY TO
DUPLEX LIFT STATIONS.

ALL CHANGES TO THESE MINIMUM REQUIREMENTS SHALL BE CLEARLY IDENTIFIED WHEN SUBMITTING
FOR APPROVAL.
N SAWGRASS
POWERLINE
95

US 1
EXWY
441
RD

SAMPLE RD

W E COPANS

XXXXXXXXXXXXXXXX
IA
RD
A

ATLANTIC

PROJECT NO XXXX
BLVD

XXXXXXXXXX
PROJECT NAME:
1
COMMERCIAL
BLVD DRAWING INDEX
OCEAN

OAKLAND PARK BLVD

SHEET
UNIVERSITY

FLORIDA'S TURNPIKE

DESCRIPTION
DR

SUNRISE
27
PROJECT LOCATION DESIGNATION
BLVD
TIC

BROWARD BLVD
84
ATLAN

COVER SHEET G-1


ABBREVIATIONS & LOCATION MAP G-2
US 1

GRIFFIN
AIA

RD
STIRLING
PLAN & ELEVATION M-1
RD
SITE PLAN M-2
75
HOLLYWOOD
95 STANDARD DETAILS M-3
BLVD
441 STANDARD DETAILS M-4
MIRAMAR PKWY
TURNPIKE EXTENSION
HALLANDALE BCH
BLVD PUMP STATIONS NOTES M-5
ELECTRICAL SITE PLAN & RISER E-1
BROWARD COUNTY, FL ELECTRICAL PLAN & CONNECTION PANEL E-2
PRELIMINARY SET DUPLEX CONTROLS CIRCUIT E-3
GENERAL LOCATION MAP
ELECTRICAL SCHEMATIC AND CONTROL PANEL E-4
6/2013 SEAL
ELECTRIC SERVICE AND TRANSFER SWITCH E-5
ELECTRICAL DETAILS E-6

DESIGN: DRAWN: CHECK:

DATE: REVISION DESCRIPTION:

THE SIZE OF THESE PLANS MAY HAVE BEEN ALTERED BY REPRODUCTION.


THIS MUST BE CONSIDERED WHEN OBTAINING DATA.
DRAWING NAME:
THE VERTICAL DATUM USED FOR THESE DRAWINGS WAS NAVD 88 COVER SHEET

SCALE: DWG NO:


CONTRACTOR TO COMPLY WITH FS CHAPTER 556 AS SHOWN
(UNDERGROUND FACILITY DAMAGE PREVENTION
AND SAFETY ACT). DESIGNATION:

LAST SAVED: 06/06/13 - 3:27PM G-1


L:\EED_DESIGN_DATA\CAD STANDARDS\WWS STD SUBMITTALS\LIFT STATION TO DEVELOPER\WWS WEBSITE 6.6.2013\WWED LIFT STATIONS TEMPLATE.dwg, GENERAL LOCATION MAP & ABBREVIATIONS (G-2), 6/6/2013 3:53:23 PM, CBGARCIA, Ad

GENERAL LOCATION MAP ABBREVIATIONS

N A E LF LINEAR FEET RJ RESTRAINED JOINT


A/C AIR CONDITION E EAST LN LANE RM ROOM
W E AASHTO AMERICAN ASSOCIATION OF STATE HIGHWAY EA EACH LP LIGHT POLE ROW RIGHT OF WAY
TRANSPORTATION OFFICIALS EB ELECTRIC BOX LS LIFT STATION RPBP REDUCED PRESSURE BACK
ABAN ABANDON EC EDGE OF CURB LT LEFT FLOW PREVENTER
S ABAN IP ABANDON IN PLACE ECC ECCENTRIC LWL LOW WATER LEVEL RPM REVOLUTIONS PER MINUTE
ABS ACRYLONITRILE BUTADIENE STYRENE ECC RDCR ECCENTRIC REDUCER RR RAILROAD
AC ASBESTOS CEMENT PIPE RST REINFORCING STEEL
EF EACH FACE M
ACCMP ASPHALT-COATED CORRUGATED METAL PIPE EL EASEMENT LINE RT RIGHT
m METER
ADDM ADDENDUM EL ELEVATION RUW REUSE WATER
MAINT MAINTENANCE
ADJ ADJACENT ELAST ELASTOMERIC RW RAW WATER
MAS MAINTENANCE ACCESS STRUCTURE, MASONRY
ALNMT ALIGNMENT ELEC ELECTRIC RW ROADWAY
MATL MATERIAL
ALT ALTERNATE EMER EMERGENCY RWM RAW WATER MAIN
MAX MAXIMUM
ALUM ALUMINUM ENGR ENGINEER RWW RECYCLED WASH WATER
MB MAIL BOX
AMP AMPERE EOS EDGE OF SLAB R/W RIGHT-OF-WAY
MCC MOTOR CONTROL CENTER
ANSI AMERICAN NATIONAL STANDARDS INSTITUTE EOW EDGE OF WATER ME MITERED END
APPX APPENDIX EP EDGE OF PAVEMENT MECH MECHANICAL S
APPROX APPROXIMATE EPDM ETHYLENE PROPYLENE DIENE MONOMER MFR MANUFACTURE(R) S SOUTH
ARV AIR OR VACUUM RELIEF VALVE EPRF EXPLOSION PROOF MG MILLION GALLONS SAMP SAMPLE
ASB ASBESTOS EQUIP EQUIPMENT MGD MILLION GALLONS PER DAY SAN SANITARY
ASPH ASPHALT ES EDGE OF SIDEWALK / SHOULDER MI MILE(S) SAN MAS SANITARY MAINTENANCE ACCESS STRUCTUR
ASSY ASSEMBLY ESMT EASEMENT MIN MINIMUM SB SOIL BORING
ASTM AMERICAN SOCIETY FOR TESTING AND MATERIAL EST ESTIMATE MISC MISCELLANEOUS SBT SOUTHERN BELL TEL
AUX AUXILIARY EW EACH WAY MJ MECHANICAL JOINT SCHED SCHEDULE
AVE AVENUE EXIST EXISTING MNR MANOR SCONC STAMPED CONCRETE
AVG AVERAGE EXP EXPANSION MON MONUMENT SD STORM DRAIN (GRAVITY)
AWWA AMERICAN WATER WORKS ASSOCIATION EXST GR EXISTING GRADE MPH MILES PER HOUR SDMAS STORM DRAIN MAINTENANCE ACCESS STRUC
MPT MALE PIPE THREAD SE SOUTHEAST
B F MS MOTOR STARTER SECT SECTION
BCBM BROWARD COUNTY BENCHMARK F/F FACE TO FACE MWL MEAN WATER LEVEL SF SQUARE FEET
BCEPD BROWARD COUNTY ENVIRONMENTAL FAC FLANGED ADAPTER COUPLING MWP MAXIMUM WORKING PRESSURE OR FOOT
PROTECTION DEPARTMENT FCV FLOW-CONTROL VALVE SHT SHEET
BCPHU BROWARD COUNTY PUBLIC HEALTH UNIT FD FLOOR DRAIN N SIG SIGNAL
BCV BALL CHECK VALVE FDOT FLORIDA DEPARTMENT OR TRANSPORTATION SLV SLEEVE
N NORTH
BCWWED BROWARD COUNTY WATER & WASTEWATER FE FILTER(ED) EFFLUENT SOLN SOLUTION
NA NOT APPLICABLE
ENGINEERING DIVISION FF EL FINISHED FLOOR ELEVATION SPEC SPECIFICATION
NAD27 NORTH AMERICAN DATUM 1927 (HORIZONTAL)
BCWWS BROWARD COUNTY WATER & WASTEWATER SERVICES FH FIRE HYDRANT SQ SQUARE
NAD83 NORTH AMERICAN DATUM 1983 (HORIZONTAL)
BE BURIED ELECTRIC FIG FIGURE SQ YD SQUARE YARD
NE NORTHEAST
BF BLIND FLANGE FIN FINISH(ED) SS SANITARY SEWER
NGVD NATIONAL GEODETIC DATUM 1929 (VERTICAL)
BFP BACKFLOW PREVENTER FIN FL FINISH FLOOR SST STAINLESS STEEL
NIC NOT IN CONTRACT

XXXXXXXXXXXXXXX
BFV BUTTERFLY VALVE FIN GR FINISHED GRADE ST STREET
NO NUMBER
BI BLACK IRON FJ FLANGED JOINT STA STATION
NOM NOMINAL
BITUM BITUMINOUS OR BITUMASTIC FL FLORIDA STD STANDARD
NPF NATIONAL PIPE THREAD
BL BASE LINE FLG FLANGE(D) STL STEEL
NPT NATIONAL PIPE TAPER (THREAD)

XXXX
BLDG BUILDING FLL FLOW LINE STRUCT STRUCTURAL
NPW NON-POTABLE WATER
BLK BLOCK FLTR FILTER SV SOLENOID VALVE
NTS NOT TO SCALE

PROJECT NAME:
BLVD BOULEVARD

XXXXXXXX
FM FORCE MAIN NW NORTHWEST SVCE SERVICE
BM BENCH MARK FPL FLORIDA POWER AND LIGHT SW SIDEWALK
BOB BOTTOM OF BAFFLE FPM FEET PER MINUTE SWD SIDEWATER DEPTH
BOC BACK OF CURB O
FPS FEET PER SECOND SYM SYMBOL
BOP BOTTOM OF PIPE O/E OR EQUAL
FRP FIBERGLASS REINFORCED PLASTIC
BOS BOTTOM OF STRUCTURE OC ON CENTER
FT FEET OR FOOT
OCEW ON CENTER EACH WAY T
BOT BOTTOM FV FOOT VALVE T&B TOP AND BOTTOM

PROJECT NO:
BP BRICK PAVERS OD OUTSIDE DIAMETER
FWP FACTORY WIRED PANEL TAN TANGENT
BT BURIED TELEPHONE OD OPEN DRIP PROOF
OF OUTSIDE FACE TEMP BM TEMPORARY BENCHMARK
BW BOTH WAYS
G OHW,OHD OVER HEAD WIRE TDH TOTAL DYNAMIC HEAD
G GROUND OH EL OVERHEAD ELECTRIC TEFC TOTALLY ENCLOSED FAN COOLED
C G LN GAS LINE TEL TELEPHONE
ORB OFFICIAL RECORDS BOOK
C TO C CENTER TO CENTER GA GAGE TEMP TEMPORARY
OSHA OCCUPATIONAL SAFETY AND HEALTH ACT
CAP CORRUGATED ALUMINUM PIPE GAL GALLON TERR TERRACE
CB CATCH BASIN GALV GALVANIZED THD THREAD
CFM CUBIC FEET PER MINUTE P
GALV STL GALVANIZED STEEL PIPE THD TROUGH FRAME HEAVY DUTY DOUBLE LEAF
CFS CUBIC FEET PER SECOND P POLE
GAS NATURAL GAS THK THICKNESS
CHKV CHECK VALVE PB PLAT BOOK
GJ GROOVE JOINT THD TROUGH FRAME HEAVY DUTY SINGLE LEAF
CI, CIP CAST IRON PIPE PBL POLYBUTYLENE
GLV GLOBE VALVE TN TON
CISP CAST IRON SOIL PIPE PC POINT OF CURVATURE
GPD GALLONS PER DAY TOB TOP OF BEAM
CJ CONSTRUCTION JOINT PCM PERMANENT CONTROL MONUMENT
GPH GALLONS PER HOUR TOC TOP OF CURB
CKT CIRCUIT PE PLAIN END
GPM GALLONS PER MINUTE TOP TOP OF PAVEMENT
CL CENTER LINE PG PRESSURE GAGE, PAGE
GR LN GRADE LINE TOS TOP OF SLAB
CL CLAY PI POINT OF INTERSECTION
GRTG GRATING TP TURNING POINT
CL2 CHLORINE GAS PL PROPERTY LINE
GS GRAVITY SEWER TR TOP OF RIM
CLF CHAIN LINK FENCE POB POINT OF BEGINNING
GTV GATE VALVE TR TRACK
CLS CHLORINE SOLUTION POJ PUSH-ON JOINT
TYP TYPICAL
CLVT CULVERT POLY POLYETHYLENE (PLASTIC)
CMP CORRUGATED METAL PIPE
H POTW POTABLE WATER
TWN TOWNSHIP (SURVEYING)
HB HOSE BIBB XFMR TRANSFORMER
CMU CONCRETE MASONRY UNIT PP POWER POLE
HD HEAVY-DUTY PRB POLLUTION RETARDANT BASIN
CND CONDUIT
HDPE HIGH-DENSITY POLYETHYLENE PREFAB PREFABRICATED U
CO CLEAN OUT/COMPANY
HNDRL HAND RAIL PRESS PRESSURE UEC UNDERGROUND ELECTRIC CABLE OR CONDU
CON CONNECTION
HOA HAND-OFF-AUTOMATIC PROP PROPERTY UED UNDERGROUND ELECTRIC DUCT
CONC CONCRETE
HORIZ HORIZONTAL PRV PRESSURE REDUCING VALVE UEE UTILITY EASEMENT (EXCLUSIVE)
CONSTR CONSTRUCTION
HP HORSEPOWER PRW PROCESS WATER UGND UNDERGROUND
CONT CONTINUOUS
HR HOUR PSF POUNDS PER SQUARE FOOT UTC UNDERGROUND TELEPHONE CABLE
CONTR CONTRACT(OR)
HWL HIGH WATER LEVEL PSI POUNDS PER SQUARE INCH UTIL UTILITY
COORD COORDINATE
HWY HIGHWAY PSIA POUNDS PER SQUARE INCH ABSOLUTE UTIL ESMT UTILITY EASEMENT
CORP CORPORATION
Hz HERTZ PSIG POUNDS PER SQUARE INCH GAGE UP UTILITY POLE
CP CONCRETE PIPE
CPP CORRUGATED HIGH DENSITY POLYETHYLENE PIPE PSM PROFESSIONAL SURVEYOR AND MAPPER
CPVC CHLORINATED POLYVINYL CHLORIDE I PT POINT OF TANGENCY V SEAL
CR CONCENTRIC REDUCER I&EE INGRESS AND EGRESS EASEMENT PV PLUG VALVE V VOLT(S)
CT COURT / COUNT ID INSIDE DIAMETER / DIMENSION PVC POLYVINYL CHLORIDE (PLASTIC) VAC VACUUM
CTV CABLE TELEVISION IE,INV EL INVERT ELEVATION PVMT PAVEMENT VAR VARIATION / VARIES
CU FT CUBIC FEET IEB INGROUND ELECTRIC BOX PWR POWER VCP VITRIFIED CLAY PIPE
CU YD CUBIC YARD IN INCH VERT VERTICAL
CY CUBIC YARD INF INFLUENT Q VFD VARIABLE FREQUENCY DRIVE
CYL CYLINDER IP IRON PIPE Q RATE OF FLOW
IPS INTERNATIONAL PIPE STANDARD QTY QUANTITY W
IW IRRIGATION WATER
D W/ WITH DESIGN: DRAWN: CHECK:

D DELTA ANGLE R W/O WITHOUT DATE: REVISION DESCRIPTION:


DBI DITCH BOTTOM INLET J R RADIUS W WATT
DCR MIAMI DADE COUNTY RECORD J-BOX JUCTION BOX R RANGE W WEST
DE DRAINAGE EASEMENT JT JOINT RCP REINFORCED CONCRETE PIPE WAY WAY
DEG DEGREE RCCP REINFORCED CONCRETE CULVERT PIPE WM WATER METER/WIRE MESH
DEPT DEPARTMENT K RCPP REINFORCED CONCRETE PRESSURE PIPE WM WATER MAIN
DESCR DESCRIPTION kV KILOVOLT RCW RECLAIMED WATER WPR WORKING PRESSURE
DFLCT JT DEFLECT JOINT(S) kVA KILOVOLT-AMPERE RD ROAD WSP WELDED STEEL PIPE
DFT DRY FILM THICKNESS kW KILOWATT RDC REDUCER WT WATER TABLE / WATERTIGHT
DIA DIAMETER kWh KILOWATT-HOUR RE RIM ELEVATION WT EL WATER ELEVATION
DIP DUCTILE IRON PIPE REV REVISION WTP WATER TREATMENT PLANT
DRAWING NAME:
WW WASTE WATER
DISCH DISCHARGE L REQD REQUIRED
ABBREVIATIONS AND
DR DRIVE RGE RANGE (SURVEYING) WWF WELDED WIRE FABRIC
LATL LATERAL
WWM WELDED WIRE MESH
DRWY DRIVEWAY LB/FT POUNDS PER FOOT
WWTP WASTEWATER TREATMENT PLANT
LOCATION MAP
DWG DRAWING LBR LIMEROCK BEARING RATIO
LBS POUND(S)
SCALE: DWG NO:
Y
YD YARD(S) AS SHOWN XXXX-XX-XXX
YH YARD HYDRANT
DESIGNATION:

LAST SAVED: 06/06/13 - 3:27PM G-2


L:\EED_DESIGN_DATA\CAD STANDARDS\WWS STD SUBMITTALS\LIFT STATION TO DEVELOPER\WWS WEBSITE 6.6.2013\WWED LIFT STATIONS TEMPLATE.dwg, PLAN AND ELEVATION (M-1), 6/6/2013 3:53:25 PM, CBGARCIA, Adobe PDF.pc3

1/2" EXPANSION
JOINT FILLER (TYP)

1'
1/2" STAINLESS REFER TO WWS MINIMUM DESIGN
STEEL PLATE AND CONSTRUCTION STANDARD LIFT STATION DATA TABLE
"GUIDELINE FOR MINIMUM
LIFT STATION COMMON NAME
FORCEMAIN SIZING"
PUMP MODEL NUMBER / IMPELLER SIZE
"HH" WWS STANDARD CURVE #
VALVE COLLAR
VOLTAGE/CYCLES/PHASE
HORSE POWER
"BB"
TEE 9" MIN. DIP FM RPM
VENT DESIGN POINT FLOW (GPM)
CL PUMP SEWER
DESIGN POINT HEAD (FT)

LONG SOLID "I-I" SHUT-OFF HEAD (FT)


CL "CC" SLEEVE MID-POINT FLOW (GPM)
"DD"
(RESTRAINED)
MID-POINT HEAD (FT)
PRESSURE GAUGE
CL PUMP (SERVICE SADDLE AND CORP) EFFICIENCY AT DESIGN POINT (%)
"AA" RUN OUT FLOW (GPM)
FLANGED PLUG VALVE, FLANGED KAMLOCK
GRAVITY 10" MIN ADAPTOR AND KAMLOCK CAP ALL MOUNTED RUN OUT HEAD (FT)
SEWER ON A FLANGED TEE (PUMP OUT CONNECTION)
CL PUMP "EE" 3' DIAMETER "O" FINISHED TOP OF SLAB EL "A"
(C-900)
MIN
WETWELL DIAMETER "B" (FT)
90° BEND WETWELL BOTTOM ELEVATION "C"
INFLUENT PIPE DIAMETER (INCHES)
CL
INFLUENT PIPE INVERT ELEVATION "D"
PLUG VALVE
BOTTOM VIEW 2' (TYP)
CHECK VALVE ELEVATION "E"

PLAN VIEW
NTS CHECK VALVE PIPE SUPPORT (SEE DETAIL) ALARM ELEVATION "F"
LAG PUMP "ON" ELEVATION "G"
NTS
LEAD PUMP "ON" ELEVATION "H"
CONCRETE SLAB BETWEEN WETWELL
REFER TO WWS MINIMUM DESIGN AND CONSTRUCTION STANDARD AND VAULT TOPS TO BE 4" THICK, BUBBLER ELEVATION "H-2"

XXXXXXXXXXXXXXXX
"LIFT STATION WETWELL SIZING REQUIREMENTS" UNREINFORCED, WITH EXPANSION PUMPS "OFF" ELEVATION "I"
JOINT MAT'L BETWEEN ADJACENT SLABS
ALARM/FLOAT PUMP "ON" ELEVATION "J"

PROJECT NO XXXX
FLOAT PUMP "OFF" ELEVATION "K"

XXXXXXXXXX
PUMP DISCHARGE DIAMETER "L" (INCHES)

PROJECT NAME:
SST SAFETY CHAINS (TYP)
FLANGED WEIGHT AND LEVER CHECK VALVE DISCHARGE PIPE DIAMETER "M" (INCHES)
ALUMINUM ACCESS HATCH W/SST BOLTS
DISCHARGE PIPE CL ELEVATION "N"
(ROTATED 90 DEG FOR CLARITY) FLANGE ADAPTOR
UPPER GUIDE (TYP) PUMP OUT DIAMETER "O" (INCHES)
RAIL BRACKET FLANGED PLUG VALVE
VENT WETWELL CL TO PUMP CL "AA" (IN)
ALUMINUM ACCESS HATCH WETWELL CL TO PUMP CL "BB" (IN)
EXPANSION
(ROTATED 90 DEG FOR CLARITY)
JOINT (TYP) PUMP CL TO PUMP CL "CC" (IN)
8" (MIN) 8" (MIN)
1'
MIN. WETWELL HATCH OPENING LENGTH "DD" (IN)
EL A 12 (TYP)
1
MIN. WETWELL HATCH OPENING WIDTH "EE" (IN)
VALVE VAULT WIDTH "HH" (IN)
TWO STRIPS OF "RAMNEK" 3' MIN PLUG VALVE (TYP) VALVE VAULT LENGTH "II" (IN)
OR APPROVED EQUAL (TYP)
2 STRIPS OF "RAMNEK" WETWELL BOTTOM TO VOLUTE BOTTOM "KK" (IN)
(OR APPROVED EQUAL) TO AIR BUBBLER
SYSTEM
3/4" x 45 DEG CHAMFER CAST IN SLAB ON EL"N"
TOP AND UNDERSIDES OF ALL SLAB
OPENINGS AND EXTERIOR SURFACES 12"X12"X12" TEE (FL X FL) (TYP)
3" PVC SCHED 40
DRAIN PIPE SUMP
CABLE HOLDER 316 SST "B" PIPE SUPPORT
(LOCATE BASED ON SLOPE 18"/FT (SEE DETAIL)
CONDUIT LOCATION) 12" MIN
GROUT SLOPE (1:12)
2 STRIPS OF "RAMNEK (OR TOWARD SUMP (MIN)
EL E
APPROVED EQUAL) AT ALL JOINTS
PRECAST VALVE VAULT, SHOP
WALL PENETRATION SEAL (TYP) 304 SST SCHED 40 DOUBLE GUIDE DRAWING SUBMITTAL REQ'D
ALL PIPE OPENINGS RAIL SYSTEM PER WWS PRODUCT 3" PLUG W/316 SST
SPECIFICATION SHEETS WIRE ROPE CABLE
EL D DISCHARGE PIPE SUPPORT 10' OC (MAX) ATTACH TO TOP SLAB
ALARM BACK-UP FLOAT "ON" EL J TIDE FLEX SERIES 37 FLANGED
INLINE CHECK VALVE W/BUNA-N
BUBBLER EL F RUBBER SLEEVE, OR APPROVED EQUAL SEAL
NOTES:
DIP DISCHARGE PIPING DIAMETER "M"
BUBBLER EL G
WETWELL TO BE COATED PER WWS
PRODUCT SPECIFICATION SHEETS 1. FOR ALL WATER & WASTEWATER MINIMUM DESIGN AND CONSTRUCTION STANDARDS VISIT THE WWS WEBSITE AT:
BUBBLER EL H LIFTING CABLE PER PUMP WWW.BROWARD.ORG/WATERSERVICES/PAGES/MINIMUMDESIGNANDCONSTRUCTIONSTANDARDS.ASPX
MANUFACTURER REQUIREMENTS
2" 2. VALVE VAULT INTERIOR WALL DIMENSIONS AND HATCH FRAME OPENING DIMENSIONS TO BE 60"X60" OR 72"X72" AS DIRECTED BY WWS.
BUBBLER EL I
DRAIN PIPE TO EXTEND BELOW LEAD PUMP ON ELEV. DESIGN: DRAWN: CHECK:
FLOAT PUMP "OFF" EL K
3. WETWELL AND VALVE VAULT HATCHES SHALL BE US FOUNDRY, HALLIDAY (OR APPROVED EQUAL) THD/TPD ALUMINUM ACCESS HATCHES. ALL HARDWARE DATE: REVISION DESCRIPTION:
ECCENTRIC INCREASER (IF REQUIRED)
TO BE 316 STAINLESS STEEL.
WETWELL BOTTOM EL C BUBBLER SYSTEM TUBING EL H-2
4. FALL PROTECTION REQUIRED FOR WETWELL AND VALVE VAULT (SUBMITTAL REQUIRED).
MIN.

PRECAST WETWELL, SHOP


12"

DRAWING SUBMITTAL REQ'D


5. HATCHES TO BE EQUIPPED WITH AUTOMATIC HOLD OPEN ARMS, HORIZONTAL COMPRESSION SPRINGS, WATERTIGHT SLAM LOCKS, RECESSED OVERSIZE
12" PADLOCK BOX, AND SAFETY CHAINS. HINGES TO BE ATTACHED USING TAMPER PROOF CARRIAGE BOLTS WITH WELDED NUTS.
"KK"

(TYP)

GROUT FILLET 6. SHOP DRAWINGS REQUIRED FOR PRECAST WETWELL, VALVE VAULT AND TOP SLABS. ALL PRECAST STRUCTURES MUST MEET ASTM C478 SPECIFICATIONS
BASE ELBOW DRAWING NAME:
ALL AROUND
ANGLE=30°-45° PUMP DISCHARGE DIAMETER "L" 7. FOR LIFT STATION COMMON NAME REFER TO WWS MINIMUM DESIGN AND CONSTRUCTION STANDARD "RETAIL LIFT STATION NAMING CONVENTION" PLAN AND ELEVATION
REFER TO WWS MINIMUM DESIGN AND CONSTRUCTION STANDARD 304 SST ANCHOR BOLTS PER PUMP
"LIFT STATION STANDARDS PUMPS" MANUFACTURER REQUIREMENTS SCALE: DWG NO:

AS SHOWN
ELEVATION DESIGNATION:

M-1
NTS

LAST SAVED: 06/06/13 - 3:27PM


EOP
L:\EED_DESIGN_DATA\CAD STANDARDS\WWS STD SUBMITTALS\LIFT STATION TO DEVELOPER\WWS WEBSITE 6.6.2013\WWED LIFT STATIONS TEMPLATE.dwg, SITE PLAN (M-2), 6/6/2013 3:53:28 PM, CBGARCIA, Adobe PDF.pc3

8"(MIN)-GS 8"(MIN)-GS

50' EOP

WM WM

XXXXXXXXXXXXXXXX
8"(MIN)-PVC-C-900-GS

PROJECT NO XXXX
XXXXXXXXXX
PROJECT NAME:
WATER METER SWING BOLLARDS (2)
SIDEWALK
GATE

R/W
X
x x x X X X

3/4" WASHED ROCK


10' OVER WEED BARRIER

X
X

1" PE-WATER SERVICE

3" (MIN) DEPTH

1'

X
X

SEE
NOTE 1
NOTES:

X
X

CONCRETE
BOLLARDS (2) 1. MAINTENANCE ACCESS STRUCTURES SHALL BE INSTALLED
FENCE DRIVE
WITHIN THE PUMP STATION EASEMENT AS SHOWN UNLESS
3'
WWS DIRECTS OTHERWISE.

X
X

MIN
2. FINISH GRADE ELEVATION FOR WETWELL AND VALVE

"B"
VAULT SHALL BE A MINIMUM OF ONE FOOT ABOVE THE
FEMA 100 YR FLOOD ELEVATION OR NOT LOWER THAN

X
X

CROWN OF ROAD.
SEAL
3. ALL CONCRETE SLABS ON GRADE SHALL BE CLASS A.
VALVE

X
X

VAULT 4. DRIVEWAY SHALL BE 6-INCH THICK CONCRETE, WITHOUT

"C"
REINFORCEMENT, UNLESS WWS DIRECTS OTHERWISE.

5. THIS SITE LAYOUT IS GENERAL IN NATURE AND SHOULD BE

X
X

WETWELL Ø MODIFIED AS REQUIRED FOR EACH INDIVIDUAL LIFT DESIGN: DRAWN: CHECK:

STATION. WWS RESERVES THE RIGHT TO MODIFY DATE: REVISION DESCRIPTION:


CONNECT CONTROL TRANSFER
BACKFLOW PANEL PANEL SWITCH PROPOSED LAYOUT TO MEET OPERATIONAL NEEDS.
X
X

PREVENTER
FPL METER
1'

1' WETWELL
X X X X X X X X DIAMETER "A" "B" "C" "D"

6' 30.00' 30.00' 13.34' 20.25'


DRAWING NAME:
"D" 8' 30.00' 30.00' 16.34' 22.25'
10' 32.00' 32.00' 19.00' 27.50' SITE PLAN
"A" 12' 35.00' 35.00' 20.00' 29.00'
SCALE: DWG NO:

TYPICAL SITE PLAN AS SHOWN

NTS DESIGNATION:

LAST SAVED: 06/06/13 - 3:27PM M-2


SLAB OPENING CONCRETE SLAB

1/2" DIA
WALL PENETRATION HOOKS
SEAL 316 SST
SEEPAGE RING
WALL PENETRATION
L:\EED_DESIGN_DATA\CAD STANDARDS\WWS STD SUBMITTALS\LIFT STATION TO DEVELOPER\WWS WEBSITE 6.6.2013\WWED LIFT STATIONS TEMPLATE.dwg, STD DETAILS (M-3), 6/6/2013 3:53:30 PM, CBGARCIA, Adobe PDF.pc3

DIP PIPE SLEEVE SEAL

DIP BLIND FLANGE

2"
2-4"PVC 2"
316 SST WASHER
CONDUITS
4- 3/4" X 6"
316 SST BOLTS

SEE TABLE
1/2" FLANGE FILLER W/316 NUTS & CABLE HOLDER / CONDUIT DETAIL

SEE TABLE
PASSING PIPE PASSING PIPE

"A"
LOCK WASHERS
20/20 316 SST MESH

"A"
(SCREEN) DETAIL
BOLT HEAD NTS

2"
4- 3/4"x 2 1/4"
316 SST NUTS & 6"X 8" DIP FLANGED
LOCK WASHER BRASS KAMLOCK ADAPTOR
INCREASER SEAL VOID W/NON-SHRINK
SEAL VOID MODEL 633F - MALE N.P.T
GROUT BOTH SIDES
W/NON-SHRINK GROUT W/DUST CAP
BOTH SIDES BRASS NIPPLE

NOTES:
6" NOTES: THREADED FLANGE
DIA 1. ALL DIMENSIONS ARE GIVEN IN INCHES.
2. USE ON NEW CONSTRUCTION, UNLESS OTHERWISE 1. ALL DIMENSIONS ARE GIVEN IN INCHES.
APPROVED BY BCWWS. 2. USE ON EXISTING CONSTRUCTION.

TO BE COATED NOMINAL NOMINAL


WITH WETWELL 4- 3/4"x 2 1/4"
PIPE SIZE SLEEVE "A" PIPE SIZE SLEEVE "A" PIPE SIZE "A" PIPE SIZE "A"
DIA DIA
316 SST EXP ANCHOR TEE PLUG VALVE
2 4 6 12 16 19 2 4 12 16
2-1/2 4 7 14 18 21 2-1/2 4 14 18
3 5 7-1/2 16 20 23-1/2 3 5 16 20
NOTE:
4 6 9 18 22 25 4 6 18 24

XXXXXXXXXXXXXXXX
6 10 13 20 24 27-1/2 6 10 20 24
THE PENETRATION FOR THE VENT ASSEMBLY SHALL BE LOCATED 1' 8 12 15 24 28 32 8 12 24 30
INSIDE THE INTERIOR WETWELL WALL AND CENTERED OPPOSITE 10 14 17 10 14
FROM THE DISCHARGE PIPING.

PROJECT NO XXXX
XXXXXXXXXX
PROJECT NAME:
6" WETWELL VENT WALL SLEEVE PENETRATION CORE DRILL PENETRATION PUMP OUT CONNECTION
DETAIL DETAIL DETAIL DETAIL
NTS NTS NTS NTS

PLUG VALVE PIPE FLANGE WETWELL WALL

PLUG VALVE
PRESSURE GAUGE

9"
CHAMFER TOP
EDGE 3/4", 45 DEG PRESSURE SIGNAL
1" X 3/4" TEE WIRE
1" BALL VALVE ,
NPT ENDS (TYP-3 PLACES) W/3/4" HOSE BIBB PIPE 1/2" DIA 316 SST EXP TYPE 316 SST

A
ANCHOR WASHER & PRESSURE SNUBBER
NUT (TYP OF 4) PENETRATE
6" DIAPHRAGM SEAL
5" MIN
CONVERT TO 1/2" X 1/2" - 1/2" TYPE 316 SST PIPE (TYP)
DRILL 5/8" DIA HOLE 316 SST TEE
BRASS/PVC
(TYP) W/SST PLUG
AT FITTING NON-SHRINK
CONCRETE SUPPORT 1/2" TYPE 316 SST BALL VALVE
MAX
48"

(SEE NOTES) GROUT


1" SST PIPE PEDESTAL FORMED IN PLACE
1/2" DIA 316 SST U-BOLT
SUPPORT WITH 1/2" TYPE 316 SST
WASHER & NUT
12"

SST ANCHOR BALL VALVE 1/2" TYPE 316 SST


PIPE DIA. + 4"

A
BALL VALVE
LIFT STATION PUMP
MIN

DISCHARGE PIPE
18"

3/8" 316 SST SEAL


4" CONCRETE WEDGE ANCHORS L 3"X3"X1/4" 316 SST
SLAB (TYP) EXTEND FULL LENGTH
1"-90 DEG CONSTRUCT 18" x 18" x 6" CONC BASE
ELBOW 1" REDUCED PRESSURE BFP OF WETWELL
WITH #4 REINFORCING STEEL @ 5" OCEW PLAN 1
IF SUPPORT IS NOT LOCATED ON AN 2" -316 SST TEE REDUCER
1" PE WATER SERVICE
EXISTING SLAB. 2-1/4"
BELOW GRADE 9" X 9" X 1/4" 316 SST BASE PLATE, 1" DOUBLE STRAP SERVICE
1-1/2"
INSTALL BEFORE LINING SADDLE AND CORP STOP (TYP)
(TYP) DESIGN: DRAWN: CHECK:
NOTES:
NOTES: DATE: REVISION DESCRIPTION:
5/8" DIA HOLE (TYP OF 4) PRESSURE GAUGE: ASHCROFT 45-2279-SSH-04L-XX#
1. BACKFLOW PREVENTER LOCATED INSIDE FENCED AREA SHALL 1. CONCRETE SHALL BE 4000 PSI, UNREINFORCED.
BE FEBCO MODEL 825YA (OR APPROVED EQUAL) AND SHALL 1/4" OR APPROVED EQUAL
2. SEE PLANS AND SECTIONS FOR PIPE ELEVATION REQUIREMENT.
USE SCHED 40 BRASS FOR ALL ABOVEGROUND PIPE/FITTINGS SNUBBER: ASHCROFT 50-1112SE
3. PIPE SUPPORT SUITABLE FOR PIPE SIZES 3" THROUGH 24" DIA. FORCE MAIN
AND VALVES. DIAPHRAGM SEAL: ASHCROFT TYPE 50-100SS-04T-XCG
4. SUPPORT STRAIGHT PIPE SECTION, FITTING OR PLUG VALVE. DO L 3" X 3" X 1/4" 316 SST
2. BACKFLOW PREVENTER LOCATED OUTSIDE FENCED AREA NOT PLACE UNDER CHECK VALVE.
NOTES:
SHALL BE UV RESISTANT COMPOSITE PLASTIC UBS RP-500 (OR
NOTE: MAX DISTANCE 1. TAP PIPE PER MANUFACTURER'S RECOMMENDATIONS AT SPRINGLINE.
APPROVED EQUAL) AND SHALL USE SCHED 40 PVC FOR ALL BETWEEN SUPPORTS 2. ALL PIPE AND FITTINGS SHALL BE SCHEDULE 80 STAINLESS STEEL. DRAWING NAME:
ABOVE GROUND PIPE/FITTINGS. SHALL NOT EXCEED 10 FEET
SECTION A-A 3. INSTALL PRESSURE GAUGE AND DIAPHRAGM SEAL PER MANUFACTURER'S
REQUIREMENTS. STANDARD DETAILS
4. PRESSURE RANGE FOR GAUGE TO BE BASED ON OPERATING CONDITIONS.
SCALE: DWG NO:
BACKFLOW PREVENTER PIPE SUPPORT - CONCRETE PEDESTAL LIFT STATION PUMP DISCHARGE PIPE SUPPORT PRESSURE GAUGE AS SHOWN
DETAILS DETAIL DETAIL DETAIL DESIGNATION:
NTS NTS NTS NTS
LAST SAVED: 06/06/13 - 3:27PM M-3
#4 BAR (TYP)
3-STRANDS BARBED
WIRE, ANGLE OUT (2) FDOT INDEX 17349 CASE II-REQUIRED
#9 GALV. AT 45 DEG WITH GALV.
CLIPS REFLECTORS MOUNTED BACK TO BACK,
MTG. BRACKETS
2'-0" MAX. PL TO FENCE FABRIC (TYP.)

PANEL WIDTH + 4"


SPACING 1'-6" (UNLESS OTHERWISE NOTED)
L:\EED_DESIGN_DATA\CAD STANDARDS\WWS STD SUBMITTALS\LIFT STATION TO DEVELOPER\WWS WEBSITE 6.6.2013\WWED LIFT STATIONS TEMPLATE.dwg, STD DETAILS (M-4), 6/6/2013 3:53:32 PM, CBGARCIA, Adobe PDF.pc3

4.0" O.D. GALV


GROUT INJECTION HOLE STEEL GATE/CORNER
10'-0" TO CENTER
POST WITH POST CAP
(MAX) 6' SECTION (2)
(SCHED 40 PIPE)

POST CAP

1'-6"
TOP RAIL
61 2 "
STRETCHER BARS #9 TIE WIRES #9 GALV. CLIPS,
POST 12" O.C. 14" MAX. SPACING

6'-0"
CORNER 3/8" ROUND
TRUSS BARS LINE POST
(SEE NOTE 8)
TENSION WIRE FABRIC PANEL LENGTH + 4"

61 2 "
2" TURNBUCKLE
GRADE
DRILL 6-15/16" 1-1/2"
HOLES TYP NOTE: VERIFY REBAR DOES NOT CONFLICT WITH PANEL ANCHOR BOLTS

3'-0"
3,000 PSI CONCRETE 36" 48" (TYP)
7/8" X 10" - 304 SST WEDGE ANCHOR 304 SST PUMP BASE ANCHOR
(EMBED 7" MIN) - TYP (6 LOCATIONS) BOLTS PER MANUFACTURER'S 6" TOP OF SLAB
CONSTRUCT 2" (TYP) 1" CHAMFER
RECOMMENDATION (TYP)
FENCE 1'-6"
1/2" - 316 NUT (TYP) FROM PROPERTY PL 12" 12" #9 TIE WIRES
SST PLATE LINE
3,000 PSI 24" (TYP) #4 BAR DOWEL
CONCRETE (TYP.) #4 BAR 4"
NOTES:

1. FABRIC: No 9 GALV STEEL WIRE, 2" MESH, BLACK VINYL COATED.


MIN

LEVELING NUT 1. FABRIC TIES: No 9 GALV STEEL WIRE SPACED 12" APART ON POST AND 24"
7"

APART ON RAILS. NOTES: 2"


2. CORNER POST: 3" OUTSIDE DIAMETER PIPE, 5.79 #/FT. BONDING AGENT
1. GATE SECTIONS SHALL BE HORIZONTALLY CROSS-BRACED AT THE MIDPOINT WITH IF SECOND POUR
3. LINE POST: 21 2" OUTSIDE DIAMETER PIPE, 5.79 #/FT - SCHED 40. SLAB
1.660" DIA. SCHEDULE 40 STEEL PIPE.
PUMP STATION BASE 4. TOP RAIL: 15 8" OUTSIDE DIAMETER PIPE, 2.27 #/FT. SET IN EPOXY IF
DRILL PUMP STATION 2. 3-BARB WIRE STRANDS W/GALV. BRACKETS, SET VERTICAL OVER GATE.
NON-SHRINK 5. NUTS, BOLTS & SCREWS: SHALL BE OF GALVANIZED STEEL, MIN SIZE 3 8" DIAMETER. SECOND POUR
SLAB 3. GATE POST: 4" OUTSIDE DIAMETER PIPE, 9.1 #/FT.
MACHINERY GROUT 6. BOTTOM WIRE: COIL SPRING WIRE 7 GA.

XXXXXXXXXXXXXXXX
(NO VOIDS) 7. TRUSS BARS ARE REQUIRED FOR THE FIRST SPAN ON EACH SIDE OF A CORNER POST
OR GATE SECTION.
8. ALL FENCING MATERIALS: TO BE HOT DIPPED GALVANIZED.
NOTE: SHOP DRAWING SUBMITTAL REQ'D

PROJECT NO XXXX
XXXXXXXXXX
PUMP PLATFORM CHAIN-LINK FENCE 12' SWING GATE ELECTRICAL PANEL SLAB

PROJECT NAME:
DETAIL DETAIL DETAIL DETAIL
NTS NTS NTS
NTS

NUMBER OF SPRINGS NUMBER OF SPRINGS


MAY VARY DEPENDING MAY VARY DEPENDING
ON HATCH SIZE ON HATCH SIZE

SST AUTOMATIC SST AUTOMATIC


HOLD OPEN ARM HOLD OPEN ARM
SST SLAMLOCK
SST SLAMLOCK
USFFABRICATION

USFFABRICATION

FLUSH DROP FLUSH DROP


HANDLE HANDLE

SEAL
SECTION VIEW
PLAN VIEW SIDE SECTION VIEW
1
PLAN VIEW SIDE
4 FLOOR PLATE
ODOR REDUCTION ODOR REDUCTION
1 GASKET AND CUSHION
GASKET AND CUSHION 4 FLOOR PLATE

1 1 2 DIA. DRAIN
COUPLING 1 1 2 DIA.DRAIN DESIGN: DRAWN: CHECK:
COUPLING DATE: REVISION DESCRIPTION:
3 1/2 3 1/2

SECTION VIEW 1/4 EXTRUDED TROUGH SECTION


W/INTEGRAL CONT. ANCHOR FLANGE
FRONT AND GROOVES FOR GASKET/CUSHION
FRAME MAT'L: ALUMINUM 6063-T5
NOTE: ALL STRUCTURES LOCATED IN THE RIGHT-OF-WAY MUST USE
THIS COVER UNLESS WWS DIRECTS OTHERWISE. NOTE: ALL STRUCTURES LOCATED IN EASEMENTS MUST USE FRAME DETAIL DRAWING NAME:
THIS COVER UNLESS WWS DIRECTS OTHERWISE. STANDARD DETAILS

TROUGH FRAME, HEAVY-DUTY, DOUBLE TROUGH FRAME, PEDESTRIAN, DOUBLE


SCALE: DWG NO:

ACCESS DOOR COVER (THD) AS SHOWN


ACCESS DOOR COVER (TPD)
DETAIL DETAIL DESIGNATION:

NTS NTS LAST SAVED: 06/06/13 - 3:27PM M-4


GENERAL
L:\EED_DESIGN_DATA\CAD STANDARDS\WWS STD SUBMITTALS\LIFT STATION TO DEVELOPER\WWS WEBSITE 6.6.2013\WWED LIFT STATIONS TEMPLATE.dwg, PUMP STATIONS NOTES (M-5), 6/6/2013 3:53:35 PM, CBGARCIA, Adobe PDF.pc3

7. CONCRETE SHALL BE EITHER CLASS A OR CLASS B, AS INDICATED ON THE DRAWINGS OR SPECIFIED IN D. ALL ACTIVE LEAKS IN THE STRUCTURE SHALL BE STOPPED USING CHEMICAL GROUTING AND HYDRAULIC 17. TUBBING FITTINGS SHALL BE SWAGELOK BRASS FITTINGS (OR APPROVED EQUAL).
1. ALL CONSTRUCTION AND MATERIALS SHALL COMPLY WITH BROWARD COUNTY WATER AND WASTEWATER THESE SPECIFICATIONS. IN GENERAL CLASS A CONCRETE SHALL BE USED FOR REINFORCED CONCRETE CEMENT.
SERVICES (WWS) "MINIMUM DESIGN AND CONSTRUCTION STANDARDS" AND APPLICABLE LOCAL AND CAST-IN-PLACE IN FORMS FOR SLABS, FOOTINGS, FOUNDATIONS, MAINTENANCE ACCESS STRUCTURES 18. COLOR CODING:
NATIONAL CODES. AND SIMILAR REINFORCED CONCRETE STRUCTURES COMING UNDER THE SCOPE OF ACI 318. CLASS B E. ALL CRACKS, VOIDS AND REMOVED STEP HOLES SHALL BE FILLED USING A WATER RESISTANT
CONCRETE SHALL BE PLAIN CONCRETE AND SHALL BE USED FOR PIPE CRADLES, PIPE AND CONDUIT FAST-SETTING CEMENT PATCH. A. SINGLE PHASE 120/240V-BLACK, WHITE, AND RED.
2. MINIMUM REQUIREMENTS FOR PRODUCTS USED IN BROWARD COUNTY DISTRIBUTION AND COLLECTION ENCASEMENT, BEDDING, GRADE CORRECTION, ANCHORS, COLLARS, THRUST BLOCKS, MASSIVE SECTIONS
SYSTEMS ARE DEFINED IN "PRODUCT SPECIFICATION SHEETS". AND OTHER NON-REINFORCED CONCRETE. 2. REBUILDING CONCRETE SURFACES B. THREE PHASE 120/240V 4 WIRE-HI LEG CENTER AND ORANGE, WHENEVER NEUTRAL IS PRESENT.
THE ABSENCE OF NEUTRAL, THEY WILL BE MARKED BLACK, RED, AND BLUE AND/OR A-B-C. WI
3. FOR ALL WATER & WASTEWATER "MINIMUM DESIGN AND CONSTRUCTION STANDARDS" AND "PRODUCT 8. CONCRETE INGREDIENTS SHALL BE SELECTED, PROPORTIONED, AND MIXED IN SUCH A MANNER AS A. THE CONCRETE SHALL BE RETURNED TO ITS ORIGINAL WALL THICKNESS USING A ONE COMPONENT CONSTITUTE CLOCKWISE ROTATION OF ALL 3-PHASE MOTORS. THIS IS TO ASSURE PHASE RELATIO
SPECIFICATION SHEETS" REFER TO: WILL PRODUCE A WATERTIGHT DURABLE CONCRETE THAT WILL DEVELOP THE FOLLOWING MINIMUM MORTAR, MINIMUM INSTALLED THICKNESS SHALL BE 1/2". THROUGHOUT THE SYSTEM.
WWW.BROWARD.ORG/WATERSERVICES/PAGES/MINIMUMDESIGNANDCONSTRUCTIONSTANDARDS.ASPX COMPRESSIVE STRENGTHS AT AN AGE OF 28 DAYS WHEN SAMPLED, CURED AND TESTED IN ACCORDANCE
WITH THE PROCEDURES SPECIFIED IN ASTM C 31 AND C 39: B. ONE COMPONENT REINFORCED WET MORTAR: THE ONE COMPONENT MORTAR SHALL BE MICROSILICA C. 120/208V, 4 WIRE, THREE PHASE SHALL BE BLACK, WHITE, RED, AND BLUE WHERE THE NEUTRAL
4. WHENEVER A MATERIAL, ARTICLE OR PIECE OF EQUIPMENT IS IDENTIFIED IN THE PROJECT MANUAL ENHANCED, FIBER REINFORCED AND BE DESIGNED FOR CORROSIVE ENVIRONMENTS WITH A pH=2.0 OR PRESENT. IF THE NEUTRAL IS ABSENT, BLACK, RED, AND BLUE AND/OR A-B-C WILL CONSTITUT
INCLUDING DRAWINGS (PLANS) AND SPECIFICATIONS BY REFERENCE TO MANUFACTURER'S OR VENDOR'S CLASS OF AVERAGE OF THREE MINIMUM ANY HIGHER. REINFORCED MORTAR SHALL HAVE THE FOLLOWING MINIMUM PHYSICAL PROPERTIES: CLOCKWISE ROTATION OF ALL THREE PHASE MOTORS, THIS IS TO ASSURE PHASE RELATIO
NAME, TRADE NAMES, CATALOG NUMBERS, OR OTHERWISE, IT IS INTENDED MERELY TO ESTABLISH A CONCRETE AGE CONSECUTIVE SPECIMENS ONE SPECIMEN THROUGHOUT THE SYSTEM.
STANDARD, AND UNLESS IT IS FOLLOWED BY WORDS INDICATING THAT NO SUBSTITUTION IS PERMITTED,
ANY MATERIAL, ARTICLE, OR EQUIPMENT OF OTHER MANUFACTURERS AND VENDORS WHICH WILL PERFORM A 28 DAYS 4,000 PSI 3,500 PSI 1. FLEXURAL STRENGTH 1000 PSI @ 28 DAYS ASTM C78-84 D. 277/480V, 4-WIRE-BROWN, ORANGE, YELLOW AND WHITE WHEN THE NEUTRAL IS PRESENT. IF TH
OR SERVE THE REQUIREMENTS OF THE GENERAL DESIGN WILL BE CONSIDERED EQUALLY ACCEPTABLE, B 28 DAYS 3,000 PSI 2,500 PSI NEUTRAL IS ABSENT, A-B-C WILL CONSTITUTE CLOCKWISE ROTATION OF ALL THREE PHASE MOTOR
PROVIDED THE MATERIAL, ARTICLE OR EQUIPMENT SO PROPOSED IS, IN THE OPINION OF THE WWS, EQUAL 2. COMPRESSIVE STRENGTH 9000 PSI @ 28 DAYS ASTM C109-92 THIS IS TO ASSURE PHASE RELATION THROUGHOUT THE SYSTEM.
IN SUBSTANCE, QUALITY, AND FUNCTION. REFER TO PRODUCT SPECIFICATION SHEETS AT
WWW.BROWARD.ORG/WATERSERVICES/PAGES/MINIMUMDESIGNANDCONSTRUCTIONSTANDARDS.ASPX
FINISHING UNFORMED SURFACES 3. DENSITY (WET): 130 LB/CU. FT. ASTM C138-92 19. FABRICATE ANTENNA MAST FROM A 21 FOOT LENGTH OF 212 " DIAMETER SCHEDULE 40 ALUMINUM PIP
PAINT LOWER THREE (3) FEET WITH ASPHALTUM PAINT, CAP THE TOP OF PIPE.
5. THE CONTRACTOR SHALL OBTAIN ALL NECESSARY PERMITS TO COMPLETE THE WORK AS SPECIFIED. 4. SPLITTING TENSILE STRENGTH: 700 PSI @ 28 DAYS ASTM C496-90
1. NO SURFACE TREATMENT WILL BE REQUIRED FOR BURIED CONCRETE NOT FORMING AN INTEGRAL PART OF
20. RUN 3/4 INCH RIGID ALUMINUM CONDUIT UP THE MAST FOR THE ANTENNA CABLE TO WITHIN 16 INCHE
6. IF APPLICABLE THE CONTRACTOR SHALL SUPPLY ALL LABOR AND EQUIPMENT NECESSARY TO BY-PASS THE STRUCTURE EXCEPT THAT REQUIRED TO OBTAIN THE SURFACE ELEVATIONS OR CONTOURS AND 5. SLANT SHEAR BOND STRENGTH: 2250PSI @ 28 DAYS ASTM C882-91 OF THE TOP. RUN SECOND 3/4 INCH CONDUIT UP THE MAST FOR ALARM AND FLOOD LIGHTS A
LIFT STATION DURING CONSTRUCTION AND MAINTAIN SAID BYPASS FOR THE DURATION OF ITS USE. SURFACES FREE OF LAITANCE. THE UNFORMED SURFACES OF ALL OTHER CONCRETE SHALL BE
SHOWN. USE STAINLESS STEEL UNISTRUT AND CLAMPS TO HOLD CONDUITS TO THE MAST.
SCREEDED AND GIVEN AN INITIAL FLOAT FINISH FOLLOWED BY ADDITIONAL FLOATING FOLLOWED BY 6. SULFATE RESISTANCE WEIGHTLOSS pH 1.0 <.97% ASTM C-267
7. COMPLIANCE TO "TRENCH SAFETY ACT" IS REQUIRED FOR ALL EXCAVATIONS IN EXCESS OF 5 FEET DEEP. TROWELING WHERE REQUIRED. CARE SHALL BE TAKEN THAT NO EXCESS WATER IS PRESENT WHEN THE 84 DAY IMMERSION pH 2.0 <.30% 21. MOUNT FLOOD LIGHT AND FLASHING RED LIGHT ON THE ANTENNA MAST AT TEN (10) FEET AND EIGH
CONTRACTOR SHALL COMPLY WITH THE U.S. DEPARTMENT OF LABOR OCCUPATIONAL SAFETY AND HEALTH FINISH IS MADE. NO SPECIAL CONCRETE OR CEMENT MORTAR TOPPING COURSE SHALL BE USED pH 3.0 <.18% (8) FEET ABOVE GRADE.
ADMINISTRATIONS STANDARDS OSHA 29 CFR 1910.146, 'PERMIT-REQUIRED CONFINED SPACES' AND OSHA UNLESS SO SHOWN ON THE DRAWING.
29 CFR 1926, 'SAFETY AND HEALTH REGULATIONS FOR CONSTRUCTION.' C. MATERIAL SHALL BE BASF SP15, OR APPROVED EQUAL. 22. TEST PUMPS AS FOLLOWS:
2. SCREEDING: SCREEDING SHALL PROVIDE A CONCRETE SURFACE CONFORMING TO THE PROPER
8. PRIOR TO CONSTRUCTION THE CONTRACTOR SHALL NOTIFY: ELEVATION AND CONTOUR WITH ALL AGGREGATES COMPLETELY EMBEDDED IN MORTAR. ALL
A. TECHNICIAN MUST BE PRESENT TO CONDUCT TESTS.
SUNSHINE STATE 1 CALL ............................. 811
SCREEDED SURFACES SHALL BE FREE OF SURFACE IRREGULARITIES WITH A HEIGHT OR DEPTH IN EXCESS
OF 1/4 INCH AS MEASURED FROM A 10-FOOT STRAIGHT EDGE. PAINTING & COATINGS: B. MEGGER MOTORS, MOTORS SHALL BE 20 MEGOHMS OR MORE TO GROUND, DO NOT MEGGER
BCWWS NETWORK ...................................... (954)-831- 0838
LOW VOLTAGE CONTROLS.
BCWWS INSPECTOR..................................... (954)-831- 0901 3. FLOATING: SCREEDED SURFACES SHALL BE GIVEN AN INITIAL FLOAT FINISH AS SOON AS THE 1. WETWELL & VALVE VAULT EXTERIOR: THE EXTERIOR OF WET WELL & VALVE VAULTS SHALL BE COATED
CONCRETE HAS STIFFENED SUFFICIENTLY FOR PROPER WORKING. INITIAL FLOATING SHALL BE WITH TWO (2), 10 MILS (DFT) EACH COAT OF A BITUMASTIC COATING (20 MILS TOTAL DFT). BITUMASTIC
C. CHECK VOLTAGE, CHECK PUMP ROTATION, RECORD VOLTAGE AND AMPS UNDER LOAD.
9. THE CONTRACTOR SHALL ATTACH PUMP GUIDE RAILS AS PER MANUFACTURER'S RECOMMENDATIONS. FOLLOWED BY A SECOND FLOATING AT THE TIME OF INITIAL SET. THE SECOND FLOATING SHALL COATING SHALL BE CARBOLINE (KOPPERS) 300M, OR APPROVED EQUAL.
PRODUCE A FINISH OF UNIFORM TEXTURE AND COLOR. UNLESS ADDITIONAL FINISHING IS
D. DEMONSTRATE PROPER OPERATION OF ALL CONTROLS.
10. ALL VALVES ARE TO BE TAGGED, STATING TYPE OF VALVE AND NUMBER OF TURNS TO OPERATE. IF THE SPECIFICALLY REQUIRED, THE COMPLETED FINISH FOR UNFORMED SURFACES SHALL BE THE FLOAT FINISH 2. WETWELL INTERIOR, OPTION A: THE INTERIOR OF A NEW OR REHABILITATED WET WELL, WHERE
VALVE IS BURIED, A BRASS PLATE WILL BE CAST IN THE CONCRETE APRON AROUND THE VALVE COVER. IF PRODUCED BY THE SECOND FLOATING. DIRECTED BY WWS, SHALL BE COATED WITH TWO (2) COATS, 15 MILS (DFT) EACH, OF A BITUMASTIC
E. CONDUCT DRAWDOWN TESTS AS REQUIRED.
THE VALVE IS LOCATED IN A PIT, THE TAG SHALL BE HUNG FROM THE VALVE WITH A PLASTIC STRAP. COATING (30 MILS DFT, TOTAL). BITUMASTIC COATING SHALL BE CARBOLINE (KOPPERS) 300M, OR
4. BROOMING: SURFACES OF EQUIPMENT BASES AND SLABS ON GRADE SHALL BE GIVEN A LIGHT BROOM APPROVED EQUAL.
F. CHECK OPERATION WITH OWNER'S PORTABLE GENERATOR AND CHANGE WIRE CONNECTIONS IN
11. ALL VALVE BOXES SHALL HAVE LOCKING LIDS. FINISH PROVIDING A NONSLIP SURFACE. BROOMING SHALL BE DONE AFTER THE SECOND FLOATING
THE PANEL TO GIVE CORRECT ROTATION.
AND FOR TRAFFIC AREAS SHALL BE AT RIGHT ANGLES TO THE NORMAL TRAFFIC DIRECTION. 3. WETWELL INTERIOR, OPTION B: THE INTERIOR OF A NEW OR REHABILITATED WET WELL, WHERE DIRECTED
12. DUCTILE IRON PIPE AND FITTINGS SHALL CONFORM TO BCWWS PRODUCT SPECIFICATION SHEETS. BY WWS, SHALL BE COATED WITH A SPRAYABLE, HIGH BUILD, MOISTURE TOLERANT, CHEMICAL RESISTANT
5. EDGING: ALL PERMANENTLY EXPOSED EDGES OF UNFORMED SURFACES SHALL BE CHAMFERED WITH A 3/4 EPOXY COATING DESIGNED TO BE APPLIED ON DRY OR DAMP CONCRETE SURFACES AND YIELDING A HARD
13. ALL JOINTS SHALL BE RESTRAINED IN ACCORDANCE WITH THE PLANS, SPECIFICATIONS AND IN INCH APPROVED EDGING TOOL UNLESS OTHER EDGE TREATMENT IS INDICATED ON THE DRAWINGS. DURABLE CHEMICAL RESISTANT FINISH TO A pH OF 1.0, EPOXY COATING SHALL BE BASF SEWER GUARD
COMPLIANCE WITH AWWA STANDARDS. HBS 100, OR OTHER APPROVED MATERIAL ON THE WWS PRODUCT SPECIFICATION SHEETS. APPLY

XXXXXXXXXXXXXXXX
6. CURING: ALL CONCRETE SHALL BE PROTECTED FROM LOSS OF MOISTURE BY CURING FOR AT LEAST 14 MATERIAL USING A 30:O OR 45:1 AIRLESS SPRAYER TO A MINIMUM DRY THICKNESS OF 60 MILS IN TWO 30
14. COMPLETE "AS-BUILT" INFORMATION RELATIVE TO VALVES, FITTINGS, LENGTH OF PIPE AND THE LIKE, DAYS FOLLOWING PLACEMENT. CURING OPERATIONS SHALL TAKE PLACE IMMEDIATELY AFTER CONCRETE MILS COATS. WHERE CONFLICTS EXIST BETWEEN THESE NOTES AND WWS
SHALL BE ACCURATELY RECORDED BY THE CONTRACTOR AND SUBMITTED TO THE ENGINEER PRIOR TO FINISHING IS COMPLETE OR FORMS ARE REMOVED. BREAKING OF FORM TIES OR OTHERWISE "MINIMUM DESIGN AND CONSTRUCTION STANDARDS", THE
FINAL ACCEPTANCE OF THE WORK. ALL ELEVATIONS SHALL BE TAKEN BY AN INDEPENDENT REGISTERED BREAKING THE SEAL BETWEEN THE CONCRETE SURFACE AND THE FORM SHALL BE CONSIDERED FORM 4. VALVE VAULT CONCRETE INTERIOR SURFACES: THE INTERIOR CONCRETE SURFACES OF VALVE VAULTS MINIMUM STANDARDS WILL GOVERN.

PROJECT NO XXXX
LAND SURVEYOR OR PROFESSIONAL SURVEYOR AND MAPPER AND INCLUDED IN THE "AS-BUILT" REMOVAL. SHALL BE COATED WITH A 100% SOLIDS POLYAMINE EPOXY SPECIFICALLY DESIGNED FOR WASTEWATER
INFORMATION FURNISHED BY THE CONTRACTOR. FINAL APPROVAL OF THE PROJECT IS SUBJECT TO THE IMMERSION AND LOW PERMEATION TO H2S GAS. MATERIAL SHALL BE IN CONFORM WITH THE PRODUCT

XXXXXXXXXX
FINAL REVIEW AND APPROVAL OF THE "AS-BUILT" INFORMATION FURNISHED TO THE REGULATORY
PRE-CAST CONCRETE SPECIFICATION SHEETS, OR APPROVED EQUAL, APPLIED IN TWO (2) COATS, 15.0 MILS (DFT) EACH,(30.0

PROJECT NAME:
AGENCIES AND WWS. MILS DFT, TOTAL). FINAL COLOR TO BE BEIGE. SURFACE PREPARATION, PRIMING AND APPLICATION SHALL
BE IN ACCORDANCE WITH THE MORE STRINGENT OF THE MANUFACTURERS RECOMMENDATIONS OR LISTED
15. ALL ELEVATIONS SHOWN ON THE CONSTRUCTION DRAWINGS ARE BASED ON THE NORTH AMERICAN 1. WALL AND SLAB THICKNESSES SHOWN ON THESE STANDARDS ARE MINIMUMS. MANUFACTURER IS SOLELY IN THE PRODUCT SPECIFICATION SHEETS.
VERTICAL DATUM OF 1988, (N.A.V.D. 88), HORIZONTAL DATUM NAD83 (HARN) FLORIDA EAST (0901) - US RESPONSIBLE FOR STRUCTURAL DESIGN.
FOOT, UNLESS OTHERWISE NOTED. 5. DUCTILE IRON PIPE AND FITTINGS: DIP EXTERIOR SURFACES SHALL BE COATED WITH A 100% POLYAMINE
2. PRE-CAST UNITS SHALL CONFORM TO THE REQUIREMENTS OF ASTM C-478 EPOXY SPECIFICALLY DESIGN FOR WASTEWATER IMMERSION AND LOW PERMEATION TO H2S GAS.
16. CONTRACTOR SHALL PROVIDE A IDENTIFICATION SIGN AS SHOWN. MATERIAL SHALL BE IN CONFORM WITH THE PRODUCT SPECIFICATION SHEETS, OR APPROVED EQUAL,
SIGN SHALL BE FABRICATED OF 1 8"ALUMINUM WITH WHITE REFLECTIVE BACKGROUND AND RED LETTERS. 3. LIFTING HOLES THROUGH THE STRUCTURE ARE NOT PERMITTED APPLIED IN TWO (2) COATS 20 MILS (DFT) EACH (40.0 MIL DFT, TOTAL). DIP INTERIOR SURFACES SHALL BE
LARGE LETTERS SHALL BE 1" HIGH COATED WITH 40 MILS (DFT) OF PROTECTO 401.
SMALL LETTERS SHALL BE 1/2" HIGH 4. THE BOTTOM SLAB SHALL BE CAST MONOLITHICALLY WITH THE LOWER WALL SECTION
BORDER SHALL BE 1 2" THICK, 6. VALVES SHALL RECEIVE ONLY THE FINAL 20 MIL (DFT) COAT. FINAL COLOR TO BE BEIGE. SURFACE
5. ALL STRUCTURES SHALL BE DESIGNED TO SUPPORT AN H-20 WHEEL LOADING PREPARATION, PRIMING AND APPLICATION SHALL BE IN ACCORDANCE WITH THE MORE STRINGENT OF THE
OFFSET 1 2" FROM EDGE OF SIGN
SIGN SHALL BE PERMANENTLY ATTACHED TO THE FENCE, IF AVAILABLE, OR CONTROL PANEL WHERE MANUFACTURER'S RECOMMENDATIONS OR THE WWS SPECIFICATIONS. SURFACE PREPARATION AND
VISIBLE FROM THE STREET 6. COMPLETE ENGINEERING AND PRODUCT DATA, SHALL BE SUBMITTED TO THE ENGINEER. APPLICATION SHALL BE IN ACCORDANCE WITH THE MANUFACTURER'S RECOMMENDATION. CERTIFICATION
XXX= WWS LIFT STATION COMMON NAME OF MANUFACTURER SHALL BE PROVIDED.

18" ACCESS HATCH


ELECTRICAL NOTES:
1. EACH HATCH SHALL BE DESIGNED ACCORDING TO THE OPENINGS SHOWN ON THE DRAWINGS. THE
ALUMINUM ACCESS FRAMES SHALL BE MANUFACTURED FROM 1/4-INCH THICK, EXTRUDED 6063-T5
BROWARD COUNTY ALUMINUM. 1. CONTROL PANEL ELECTRICAL SYSTEM SHALL BE COMPLETELY AND EFFECTIVELY GROUNDED AS REQUIRED
WATER & WASTEWATER SERVICES BY NEC.
STATION XXX 2. THE FRAME SHALL BE DRAINABLE WITH A 1 1/2-INCH THREADED DRAIN COUPLING LOCATED ON CORNER
FRAME. 2. ALL ELECTRICAL INSTALLATIONS SHALL BE IN ACCORDANCE WITH THE NEC AND SHALL COMPLY WITH ALL
NATIONAL AND LOCAL RULES, ORDINANCES, AND CODES AT TIME OF INSTALLATION.
IF EMERGENCY LIGHT FLASHES CALL... 3. THE DOOR PANELS SHALL CLOSE FLUSH AND SHALL BE 1/4-INCH THICK 5086-H34 ALUMINUM DIAMOND
(CHECKER) PLATE REINFORCED FOR AASHTO H-20-44 WHEEL LOADS. 3. ALL SERVICE CONDUCTORS SHALL BE STRANDED COPPER TYPE THWN.
(954) 831-0850 12"
4. REMOVABLE ALUMINUM CROSS-BEAMS SHALL BE PROVIDED BY THE HATCH SUPPLIER AS REQUIRED TO 4. ALL ENCLOSURES SHALL BE 316 STAINLESS STEEL WATERTIGHT NEMA 3R RIGHT SIDE OPENING. ALL
ACCOMPLISH THE STATED LOADING. MOUNTING HARDWARE MUST BE 316 SST.
FOR EMERGENCIES CALL... (954)831-0850
FOR PUMP OUT CALL... (954)831-0850 5. THE DOORS SHALL HAVE HEAVY DUTY STAINLESS STEEL BUTT HINGES WITH TAMPER-PROOF FASTENERS. 5. USE T & B CORROSION RESISTANT-LIQUIDTIGHT-STRAIN RELIEF THERMO-PLASTIC FLEXIBLE CORD & CABLE
FOR MAINTENANCE CALL... (954)831-0850 CONNECTOR ON THE INSIDE OF THE TOP CONNECTION PANEL TO FIT APPROPRIATE CABLE SIZE. TRANSFER
6. ALL HARDWARE SHALL BE MADE OF TYPE 316 STAINLESS STEEL. SWITCH MAY BE MOUNTED ON EITHER END BUT GENERATOR RECEPTACLE MUST BE ON OUTSIDE. (STATE
TO REPORT POLLUTION, CALL EPGMD
LEFT OR RIGHT SIDE GEN. RECPT. WHEN ORDERING.)
7. EACH DOOR SHALL HAVE SPRING OPERATORS, SUCH THAT THE MAXIMUM LIFTING EFFORT IS LESS THAN 25
POUNDS. 6. ALL PUMP MOTORS SHALL BE 3 PHASE. WHEN THE LOCAL POWER COMPANY CANNOT PROVIDE 3 PHASE
POWER TO THE STATION, A "ROTOPHASE" PHASE CONVERTER SHALL BE SUPPLIED TO PROVIDE 3 PHASE
SIGN DETAIL 2"
8. THE HATCH SUPPLIER SHALL PROVIDE THE NUMBER OF SPRING OPERATORS AS REQUIRED TO ACCOMPLISH
THE MAXIMUM LIFTING REQUIREMENT.
POWER TO THE STATION.
NTS
7. ALL CONTROL CIRCUIT WIRES SHALL BE TERMINATED WITH FORK TYPE CRIMP-ON CONNECTORS AND SHALL
17. ENGINEER SHALL PROVIDE FLOATATION CALCULATIONS FOR EACH STRUCTURE TO BE 9. EACH DOOR SHALL OPEN TO 90 DEGREE AND LOCK AUTOMATICALLY WITH A STAINLESS STEEL, POSITIVE HAVE AN ADJACENT HEAT SHRINK NUMBER, CORRESPONDING EACH CONNECTOR WITH NUMBERS AS SEAL
CONSTRUCTED. LOCKING ARM AND A STAINLESS STEEL RELEASE HANDLE. INDICATED ON THE SCHEMATIC. NO CONCEALED WIRING SHALL BE PERMITTED BEHIND THE SUB PANEL.

10. EACH DOOR SHALL HAVE A RECESSED STAINLESS STEEL LIFTING HANDLE AND RECESSED OVERSIZED 8. EACH DEVICE IN THE CONTROL CIRCUIT SHALL BE IDENTIFIED WITH THE PROPER CONTROL CIRCUIT
PADLOCK BOX.
PUMPS AND CONTROL PANEL ABBREVIATION AS SHOWN IN THE TABLE AND ON THE SCHEMATIC.
11. THE HATCH SHALL BE PROVIDED WITH A TYPE 316 STAINLESS STEEL SLAM-LOCK WITH A REMOVABLE 9. FROM THE REAR SIDE OF THE DEAD FRONT HINGED PANEL, ALL WIRES SHALL BE NEATLY LACED TOGETHER
1. PUMPS AND ALL APPURTENANCES REQUIRED TO MAKE A COMPLETE AND OPERATING SYSTEM SHALL BE HANDLE. INTO A HARNESS AND TERMINATED INTO A TERMINAL STRIP.
FURNISHED AND INSTALLED BY THE CONTRACTOR. PUMPS WILL TO BE SUPPLIED WITH 60 FT CABLES, REFER
TO WWS "LIFT STATION STANDARD PUMPS". 12. ALL ACCESS DOORS SHALL BE DESIGNED WITH A NEOPRENE GASKET ON THE INSIDE LIP OF THE FRAME 10. DRIVEN GROUND ROD WHICH DOES NOT HAVE A RESISTANCE TO GROUND OF 10 OHMS OR LESS SHALL BE
PERIMETER, TO FORM AN ESSENTIALLY AIR-TIGHT SEAL. DESIGN: DRAWN: CHECK:
AUGMENTED UNTIL THE RESISTANCE TO GROUND IS 10 OHMS OR LESS. LIGHTENING ARRESTER LEADS TO
2. CONTROL PANEL, CONNECTION PANEL AND TRANSFER SWITCH WITH LOUVERED ENCLOSURE ARE TO BE BE ATTACHED TO THE MCB AS PER MOST RECENT NEC ARTICLE # 280. DATE: REVISION DESCRIPTION:
PROVIDED BY THE CONTRACTOR AND MANUFACTURED BY CHAMPION CONTROLS INC. TO WWS 13. ALL ACCESS DOORS SHALL BE EQUIPPED WITH A MINIMUM OF FOUR (4) STAINLESS STEEL CARRIAGE BOLTS
SPECIFICATIONS (NO SUBSTITUTION). WITH WELDED NUTS TO SECURE THE DOORS IN THE DOWN POSITION. BOLTS SHALL BE PER THE 11. ALL BRANCH CIRCUITS SHALL HAVE PROPER SIZE WIRING.
MANUFACTURERS RECOMMENDATION.

CAST-IN-PLACE CONCRETE 12. WHEN CONNECTIONS ARE COMPLETE IN THE CONNECTION BOX, COAT THE TERMINAL BLOCKS AND WIRE
ENDS WITH PROTECTIVE COMPOUND, NO-OXIDE OR EQUAL, TO PREVENT CORROSION.

1. ALL CONCRETE WORK SHALL BE IN ACCORDANCE WITH FLORIDA BUILDING CODE (FBC), AMERICAN
WETWELL REHABILITATION 13. SCHEMATIC DRAWINGS SHALL BE PLACED IN STATION ARE TO BE ENCASED BETWEEN TWO PIECES OF 3/16"
CONCRETE INSTITUTE (ACI) 318 AND THE CONTRACT SPECIFICATIONS. PLEXIGLASS.
1. SURFACE PREPARATION
2. COMPLETE ENGINEERING AND PRODUCT DATA SHALL BE SUBMITTED TO THE ENGINEER ON ALL 14. ELECTRICAL SERVICE SHALL BE A MINIMUM OF 100 AMPS OF # 1 THWN STRANDED COPPER WIRE IN RIGID DRAWING NAME:
ADMIXTURES, CURING COMPOUNDS, HARDENERS, SEALERS, REINFORCING STEEL AND WATER STOPS IN A. ANY LOOSE, UNSOUND, OR CRACKED BRICK OR CONCRETE SHALL BE CHISELED OR HAMMERED OUT.
ALUMINUM CONDUIT-MINIMUM
ACCORDANCE WITH THE SPECIFICATIONS.
B. ALL SURFACES TO RECEIVE EITHER THE ONE COMPONENT REINFORCED MORTAR OR EPOXY LINING SHALL
SIZE = 1 1/2". INTERMEDIATE METAL CONDUIT UNACCEPTABLE. PUMP STATIONS NOTES
3. REINFORCEMENT STEEL SHALL CONFORM TO THE REQUIREMENTS OF ASTM A-615. BE STRUCTURALLY SOUND AND SHALL BE CLEANED TO REMOVE LAITANCE, GREASE. LOOSE MORTAR,
15. UNDERGROUND SERVICE PULL BOXES ARE TO BE INSTALLED AT EACH 250 FEET OF SERVICE PULL. VOLTAGE
PAINT OR OTHER SURFACE CONTAMINANTS USING SAND BLASTING, HYDRO-GRIT BLASTING AT 3,500 PSI
DROP TO BE LIMITED TO A MAXIMUM OF 3 PERCENT DROP. SCALE: DWG NO:
4. CONCRETE COVER FOR STEEL REINFORCEMENT SHALL BE AS SPECIFIED ON ACI 318. MINIMUM OR OTHER MECHANICAL SCARIFICATION TECHNIQUES APPROVED BY THE ENGINEER.

C. SURFACE SHALL BE TESTED BY THE CONTRACTOR, IN THE PRESENCE OF THE ENGINEER,USING A SURFACE
16. BUBBLER TUBING SHALL BE CLEAR, 1/4" TYGON (OR APPROVED EQUAL). BACK-UP SENSOR TUBING TO BE AS SHOWN
5. PIPES, INSERTS, AND OTHER METAL OBJECTS SHOWN SHALL BE BUILT INTO, SET IN, OR ATTACHED TO THE RED.
CONCRETE. ALL REQUIRED HOLES SHALL BE CAST AT TIME OF CONSTRUCTION. pH TESTER EQUAL TO INSTA-CHECK SURFACE pH PENCIL AS MANUFACTURED BY PHYDRION. SURFACE
SHALL INDICATE A pH=7.0 OR GREATER. DESIGNATION:

M-5
6. ALL CAST-IN-PLACE CONCRETE SHALL BE ACCURATELY FORMED AND PROPERLY PLACED AND FINISHED AS
SHOWN ON THE DRAWINGS AND SPECIFIED HEREIN.
LAST SAVED: 06/06/13 - 3:27PM
L:\EED_DESIGN_DATA\CAD STANDARDS\WWS STD SUBMITTALS\LIFT STATION TO DEVELOPER\WWS WEBSITE 6.6.2013\WWED LIFT STATIONS TEMPLATE.dwg, ELECTRICAL SITE PLAN (E-1), 6/6/2013 3:53:37 PM, CBGARCIA, Adobe PDF.pc3

TO BE COMPLETED TO BE COMPLETED
BY ENGINEER OF RECORD BY ENGINEER OF RECORD

XXXXXXXXXXXXXXXX

PROJECT NO XXXX
XXXXXXXXXX
PROJECT NAME:
SEAL

DESIGN: DRAWN: CHECK:

DATE: REVISION DESCRIPTION:

SITE PLAN ELECTRICAL RISER DIAGRAM DRAWING NAME:

ELECTRICAL SITE PLAN


SCALE: NTS
SCALE: DWG NO:

AS SHOWN
DESIGNATION:

LAST SAVED: 06/06/13 - 3:27PM E-1


L:\EED_DESIGN_DATA\CAD STANDARDS\WWS STD SUBMITTALS\LIFT STATION TO DEVELOPER\WWS WEBSITE 6.6.2013\WWED LIFT STATIONS TEMPLATE.dwg, ELECTRICAL PLAN & CONNECTION PANEL (E-2), 6/6/2013 3:53:39 PM, CBGARCIA, Adobe

ANTENNA MAST FOR RADIO MONITORING


ELECTRIC METER (DIGITAL) 18' ABOVE TOP OF SLAB MINIMUM
MOUNT TO BE VISIBLE FROM (TO BE WIRED TO GROUND ROD)
OUTSIDE OF FENCE ON SEPARATE
POST AS REQUIRED.
MICRO STROBE LIGHT BY TOMAR
UGND ELECTRICAL FEED ELECTRONICS PART No. 495-120 RED/POT,
FROM HAND HOLE 2-1/2" SCHED 40 ALUMINUM ANTENNA POLE MALE PIPE THREAD MOUNT ( OR APPROVED EQUAL)
PROVIDE MIN 8" CLEARANCE W/316 SST MOUNTING CLAMPS
BETWEEN ANY PANELS 3/4" PVC CONDUIT FOR GROUND CONDUCTOR POWER PRESENT LIGHT - 120V LED
CONNECTION PANEL NEMA 3R-SST W/BLUE LENS LEDTRONICS
PROVIDE 4" CONC. FILLED S100-1PB-120A (OR EQUAL) TIPPING BUCKET STYLE RAIN GAUGE, 6"
LOCKABLE W/BACK PANEL ALUMINUM POST AND SST PANEL MOUNT AS REQUIRED TO BE DIAMETER,8"HEIGHT,TEXAS
ANCHOR BOLTS NO PENETRATIONS ARE
VISIBLE FROM STREET ELECTRONICS, TR-525I, OR APPROVED
ALLOWED IN THE TOP O
EQUAL. INSTALL BY MANUFACTURER
CONCRETE SLAB FOR PANELS TO BE 8" THICK SIZED ANY PANEL BOX
RECOMMENDATIONS
ACCORDING TO PANEL CONFIGURATION, PROVIDE 6" MIN OF
SLAB BEYOND POSTS ON BACK AND SIDE OF PANELS CROUSE HINDS-ANGLE ADAPTER-45 DEG
100 AMP-RUSSEL-STOHL JAAB 10-30
ADD 1 EXTRA 2" ALUMINUM CONDUIT FOR SPARE 8" MIN (TYP) 8" MIN (TYP)
OR 200 AMP-AJI OR APPROVED EQUAL
FEMALE REVERSE-CROUSE HINDS
2-2" ALUMINUM CONDUIT FOR PROVIDE 4' MIN CLEARANCE IN FRONT 100 AMP AREA- 1042-S22-M72
FLOAT WIRES OF ELECTRIC PANEL OR 200 AMP AREA- 2042-S22-81
3/4" ALUMINUM CONDUIT FOR AIR BUBBLER PIPE 3-1" SCHED 40 PVC CONDUIT OR APPROVED EQUAL

USE SEALING LOCKNUTS ON TRANSFER CONTROL CONN.


SWITCH PANEL PANEL
ALL PANEL PENETRATIONS.

48" (MIN)
MYERS HUBS OR APPROVED EQUAL BELL-EDWARDS ADAPTABELL
HEAVY DUTY BELL 4" CAT
14 GAUGE 316 SST NEMA 3R ENCLOSURE
No 340-4N5 120V 60 Hz
OR APPROVED EQUAL
TRANSFER SWITCH PANEL
MAY BE MOUNTED ON
LIGHTNING ARRESTER GENERAL
EITHER END BUT GENERATOR
ELECTRIC TRANQUELL ARRESTER
RECEPTACLE MUST BE ON OUTSIDE.
MODEL 9L15E CC001 520V AC 3 POLE,
SEWER (STATE LEFT OR RIGHT SIDE 1 1/2"
OR APPROVED EQUAL
GEN. RECPT. WHEN ORDERING.) SST UNIT
LOWER PORTION OF POST STRUT 66
NOT SHOWN FOR CLARITY (TYP)

SCREENED LOUVERS
IN CONTROL PANEL AND
CONTROL PANEL
LOWER ENCLOSURE
W/LOUVERED
ENCLOSURE BELOW
2- 1/ 2" ALUMINUM PIPE-POLE
FOR ANTENNA TYPE 6061-T6

XXXXXXXXXXXXXXXX
STANDARD (20' LENGTH)
CONCRETE SLAB DOWEL INTO TOP SLAB
OF WETWELL #5 @ 12"OC
2-3" ALUMINUM CONDUIT 3 KVA, 400:120 VOLT CONTROL

PROJECT NO XXXX
FOR PUMP POWER CABLES TRANSFORMER TO BE MOUNTED
IN VENTED SST NEMA 3R ENCLOSURE

XXXXXXXXXX
IN POSITION ON RACK (IF REQUIRED)

PROJECT NAME:
# 6 (MIN) BARE COPPER WIRE
PLAN VIEW INSIDE 3/4" PVC CONDUIT AND
CLAMP FOR GROUND WIRE
316 SST ALL THREAD
NTS ROD SET IN EPOXY
TO MOUNT PANEL 5/8" DIA x 10' COPPER CLAD 2' MIN
4" x 4" ALUMINUM POST FILLED STEEL GROUND ROD-10 OHMS
CONNECTION PANEL CONTROL PANEL 6" MIN. WITH CONCRETE (TYP) OR LESS TO GROUND. 2 REQUIRED,
6 FEET (MIN) SEPARATION
USE ADDITIONAL RODS TO
ANCHOR BOLTS TO BE 58" x 8" REDUCE RESISTANCE.
316 SST (TYP) TRANSFER SW PANEL ALL GROUND RODS TO BE 3" ID PIPE CUP
6" MIN
CONNECTED USING # 6 (MIN)
BARE COPPER WIRE

PANEL SIDE VIEW PANEL REAR VIEW


NTS NTS

USE HEAT SHRINK TYPE WIRE


MARKERS (TYP)
30" MIN.

TERMINAL BLOCK

NON METALLIC
CORD GRIP
SIZED FOR PUMP CORROSION PROOF
POWER CORD AND CONDUIT SEALS
FLOAT SWITCHES BETWEEN CONNECTION
PANEL AND CONTROL PANEL
CROUSE - HINDS TYPE EYSR
OR APPROVED EQUAL (TYP) SEAL

3/4" SCHED 80 PVC AIR BUBBLER PIPE WITH LOUVERED ENCLOSURE


TYPE 316 SST PIPE SUPPORTS AND FASTENERS UNDER CONNECTION PANEL
MAX.
3' BETWEEN SUPPORTS
DESIGN: DRAWN: CHECK:

DATE: REVISION DESCRIPTION:


FLORIDA LICENSED PROFESSIONAL ENGINEER TO REVIEW AND
SST BLOCKHEAD
MODIFY ELECTRICAL DESIGN AS REQUIRED TO ACCOMPLISH UNION COMPRESSION
CONSTRUCTION IN ACCORDANCE WITH APPLICABLE CODES AND FITTING MOUNTED
STANDARDS. SPLIT SEALOFFS AND
TO BRACKET
CONDUIT SEAL (TYP)

NOTES: TYGON AIR LINE


6" MIN
1. AREA INSIDE WETWELL IS CONSIDERED A CLASS 1, DIVISION 2 AREA IN DRAWING NAME:
ACCORDANCE WITH THE NATIONAL ELECTRICAL CODE ELECTRICAL PLAN AND
ELEVATION
}
2. ALL OTHER AREAS ARE NOT CLASSIFIED
CONNECTION PANEL

}
3. NO PENETRATIONS SHALL BE PERMITTED IN THE TOP OF ANY PANEL BOX
NTS 4. CONTROL PANEL/CONNECTION PANEL AND TRANSFER SWITCH TO BE TO CONTROL PANEL
TO WETWELL SCALE: DWG NO:
MANUFACTURED BY CHAMPION CONTROLS, INC. TO WWS SPECIFICATIONS AND VALVE PIT
(NO SUBSTITUTION). AS SHOWN
DESIGNATION:
CONNECTION PANEL DETAIL
NTS LAST SAVED: 06/06/13 - 3:27PM E-2
L:\EED_DESIGN_DATA\CAD STANDARDS\WWS STD SUBMITTALS\LIFT STATION TO DEVELOPER\WWS WEBSITE 6.6.2013\WWED LIFT STATIONS TEMPLATE.dwg, DUPLEX CONTROLS CIRCUIT (E-3), 6/6/2013 3:53:42 PM, CBGARCIA, Adobe PDF.pc3

120VAC
FROM N
MAIN POWER FLORIDA LICENSED PROFESSIONAL ENGINEER TO REVIEW AND
CIRCUIT MODIFY ELECTRICAL DESIGN AS REQUIRED TO ACCOMPLISH
CONSTRUCTION IN ACCORDANCE WITH APPLICABLE CODES AND
F12
STANDARDS.
CONTROL 3L3 2L3 F11 FROM MAIN
30A C/B RTU 10A 3L2 2L2 F10 POWER
C/B
200 3L1 CIRCUIT
61 2L1

15 F5 1 2 3 4 5
A TO
UNPROTECTED INPUT BUBBLER
DATAFLOW TFS SYSTEM
PROTECTED OUTPUT FORCE MAIN
LEVEL
1 2 3 4 5 TRANSDUCER PRESSURE
DFS TCU PUMP CONTROLLER - + - + 61 41 N
TRANSDUCER
P1 P2
4L3 1 PHASE C SHUNT 24 210
4L2 2 PHASE B ANALOG - 23
4L1 3 PHASE A ANALOG 1+ 22 211 213
4 SPARE (NC) ANALOG 2+ 21 212
201 S
5 AC POWER CABLE SHIELD 20
N2
12V 6 AC NEUTRAL RS-232 GND 19
BACKUP 202 7 EARTH GROUND RS-232 RXD 18 213
8 BATTERY + RS-232 TXD 17 ON
203 OFF SIL
9 BATTERY - ISO +24VDC 16
SILENCE 215 213

{
HORN 10 TELEMETRY GRD ISO GND 15 OXX
216 213
67 65 F3 11 TELEMETRY PWR INPUT COM 2 14 RAIN GAUGE
R3
1A TO/FROM 12 TELEMETRY CTS ALARM SILENCE 13 217 213
OX TAC II 11 9
66 F4
13 TELEMETRY RXD AUX INPUT 12
TELEMETRY BOTTOM DOOR 213
7 2 1A 14 TELEMETRY TXD HIGH LEVEL 11
15 TELEMETRY RTS LAG 2 LEVEL 10 TOP DOOR
CR 11 218B 218A
204 16 ALARM HORN OUT LAG 1 LEVEL 9 213
218 HATCH
205 17 ALARM LIGHT OUT PNL ENTERED 8 CRAC
41

XXXXXXXXXXXXXXXX
18 ALARM POWER AIR COMP FAIL 7 219 8 6 213
19 AUX OUTLET LOW LEVEL 6
ALARM CR11 214 PM
20 AUX POWER INPUT COM 1 5 220 12 11 213
LIGHT 66A

PROJECT NO XXXX
R 1 3 21 MOTOR 3 STARTER EXTERNAL P.M. 4
208 2M MCP2 BACKUP CONTROL
22 MOTOR 2 STARTER MOTOR 3 RUN 3 R6 R7 PUMP 2

XXXXXXXXXX
209 23 MOTOR 1 STARTER MOTOR 2 RUN 2 225 226 227 11 9 228 9 11 N POWER

PROJECT NAME:
24 STARTER POWER MOTOR 1 RUN 1 R3
1M MCP1 R4 R5 N
PUMP 2
229 230 231 11 9 232 9 11 N 6 7 2 T3 7 DELAY ON
TIMER
213 N 41
41 43 44 N
2 R3 10 FLOAT
TROUBLE TROUBLE PUMP 2 TIME BACK-UP
FR1 FR2
SWITCH LIGHT SITE DELAY
F1 62 62 LIGHT PUMP 1 SEAL. FAIL
61 20A 63 N 61 R4
72 N
4 1
LIGHTING 63 N
41 62 N R5 PUMP 1 THERMO. FAIL
61 73 N
GFI 4 1
RECEPT. AIR COMP.
FAILURE
A N PUMP 2 SEAL. FAIL
AIR LOSS R6
A/C 61 76 N
PRESS. SW. 4 1
RESET
61 F2 64 64 64A 64B
2A 2 CR 7 N
AC PUMP 2 THERMO. FAIL
R7
AIR PS1 61 77 N
AIR COMP. RECEPT. 4 1
COMPRESSORS
CRAC 64A
64 EMERGENCY N
1 3

CRAC NORMAL 24VAC XFORMER N


64 64D N
61
1 4
1M 91 95
41 1 ET N
PUMP 1 91 OFF 93
R1 O/L R5 R4 PM 2 10
CONTROL 41 2 80 80A 80B N
1 3 1M 6 7 6 7 9 8 FR1
91 ON 94
O 2 10
F6 68 41 H A
61 FR2
2A F7 9 XOO 5
209 5 BACKUP FLOATS PUMP 1
1A 2 R1 7
OOX MOISTURE SEAL
8 5 91 70
2 R4 10
OOX
PUMP 1 PUMP 1 T'STAT
91 71 2 R5 10
2M
41 41 21 N PUMP 2
ET PUMP 2 MOISTURE
PUMP 2 91 74 DESIGN: DRAWN: CHECK:
R2 O/L R7 R6 2 R6 10
CONTROL 41 22 81 81A DATE: REVISION DESCRIPTION:
1 3 2M 6 7 6 7
O PUMP 2 T'STAT
41 H A 25 91 75
F8 2 R7 10
208 29 XOO
1A
25 25 2 R2 7
OOX
R3 T3
61 28 25
3 1 3 1
BACKUP CONTROL OOX
POWER PUMP 2 DRAWING NAME:
R3
DUPLEX CONTROLS CIRCUIT
61
SCALE: DWG NO:

NTS
ELECTRICAL CONTROLS CIRCUIT (DUPLEX) DESIGNATION:

LAST SAVED: 06/06/13 - 3:27PM E-3


L:\EED_DESIGN_DATA\CAD STANDARDS\WWS STD SUBMITTALS\LIFT STATION TO DEVELOPER\WWS WEBSITE 6.6.2013\WWED LIFT STATIONS TEMPLATE.dwg, ELECTRIC SCHEMATIC AND CONTOL PANET (E-4), 6/6/2013 3:53:44 PM, CBGARCIA, Ado

PHASE MONITOR 1A FUSES

DATAFLOW 47K RESISTOR TERMINALS


DATAFLOW TFS

FLUORESCENT TROUBLE LIGHT


1 2 3 4 5

OUTPUT

F1 F2 F3 F4 F5 F6 F7 F8
TFS001-02

INPUT

1 2 3 4 5

POWER BLOCK POWER BLOCK

TERMINALS
GND GND PHASE
ELAPSED
MONITOR
TIME
METERS
PUMP 1 PUMP 2 TIMERS

BELL-EDWARDS ADAPTABELL HEAVY DUTY


BELL, 4", CAT NO. 340-4N5 120V 60 Hz, UL TEMP SEAL TEMP SEAL
CIRCUIT BREAKERS CIRCUIT BREAKERS
APPROVED OR APPROVED EQUAL FAIL FAIL FAIL FAIL
RELAY
AIR COMP

TERMINALS
FAIL

HORN
RESET
RELAY
SURGE
SUPPRESSOR SURGE SUPPRESSOR

NEMA RATED STARTERS ON ON NEMA RATED STARTERS


RELAY

TERMINALS
HOA HOA
12V
RELAY BATT

66"
LEVEL GAUGE
6

3 9

LEVEL TRANS
0 12

TROUBLE HORN

XXXXXXXXXXXXXXXX
PURGE VALVE
PRESSURE SW

PROJECT NO XXXX
AIR COMPRESSOR A/C RECEPT.
SCREENED LOUVERS

XXXXXXXXXX
BOTH SIDES 3 AREAS

PROJECT NAME:
VALVE
VALVE
SHUT

SHUT
OFF

OFF
RECEPT.

RECEPT.
GFI
GFI
W/DEAD FRONT W/OUT DEAD FRONT

DUPLEX CONTROL PANEL LAYOUT


ENCLOSURE SIZE : 66" x 36" x 10"
RATING: NEMA 3R
MATERIAL: 316 STAINLESS STEEL

120V
FROM
F6
ELECTRICAL INPUT CONNECTION BLOCK SEAL

N 68 6 10 26 30 41 43 43 44 41 70 41 71 41 74 41 75 S 212 213 216 213 218


DESIGN: DRAWN: CHECK:

DATE: REVISION DESCRIPTION:

ON FM RAIN HATCH
OFF LEVEL PRESS. GAUGE COVER
FLORIDA LICENSED PROFESSIONAL ENGINEER TO REVIEW AND (IF USED)
LEVEL XDUCER LIMIT
MODIFY ELECTRICAL DESIGN AS REQUIRED TO ACCOMPLISH FR2
SWITCH
CONSTRUCTION IN ACCORDANCE WITH APPLICABLE CODES AND FR1
STANDARDS. SEAL PUMP SEAL PUMP DRAWING NAME:
SENSOR T-STAT SENSOR T-STAT ELECTRIC SCHEMATIC AND
CONTROL PANEL
IN PUMP 1 IN PUMP 2
SCALE: DWG NO:

NTS

DESIGNATION:

LAST SAVED: 06/06/13 - 3:27PM E-4


L:\EED_DESIGN_DATA\CAD STANDARDS\WWS STD SUBMITTALS\LIFT STATION TO DEVELOPER\WWS WEBSITE 6.6.2013\WWED LIFT STATIONS TEMPLATE.dwg, ELECTRICAL SERVICE AND TRANSFER SWITCH (E-5), 6/6/2013 3:53:47 PM, CBGARCIA, A

POWER PRESENT LIGHT POWER PRESENT LIGHT

GENERATOR RECEPTACLE GENERATOR RECEPTACLE

CIRCUIT BREAKER CIRCUIT BREAKER


INTERLOCK INTERLOCK

240 VOLT
CONDUCTOR GENERATOR SERVICE
HP MOTOR AMP (I) STARTER SIZE PUMP CB MAIN/EMER CB CONDUCTOR (B)
(A) PLUG* RACEWAY (MIN)
3 9.6 1 12 20 100 1 (44A) 100 2"
5 15.2 1 10 40 100 1 (58A) 100 2"
7.5 22 2 10 50 125 1 (75A) 100 2"
10 28 2 8 70 125 1 (90A) 100 2"
15 42 3 6 100 175 0 (125A) 100 2"
20 54 3 4 150 225 0 (155A) 100 2"
25 68 4 4 175 300 00 (190A) 100 2"
INDICATE APPLICABLE DATA 30 80 4 3 200 300 000 (220A) 100 2"
480 VOLT
CIRCUIT BREAKER HANDLES
CONDUCTOR GENERATOR SERVICE
THROUGH INNER DOOR CIRCUIT BREAKERS HP MOTOR AMP (I) STARTER SIZE PUMP CB MAIN/EMER CB CONDUCTOR (B)
(A) PLUG* RACEWAY (MIN)
FUSE PHASE 3 5 1 12 15 100 1 (32.5A) 200 2"
HOLDER MONITOR 5 8 1 12 15 100 1 (40A) 200 2"
7.5 11 1 12 20 100 1 (47.5A) 200 2"
10 14 2 12 30 100 1 (55A) 200 2"
15 21 2 10 50 125 1 (72.5A) 200 2"
20 27 2 10 60 125 1 (87.5A) 200 2"
GROUND 25 34 2 8 90 150 1 (105A) 200 2"
30 40 3 6 100 150 1 (120A) 200 2"
POWER 0 (150A) 2"
40 52 3 4 150 225 200
SUBFEEDER
TERM BLK 50 65 4 4 175 250 00 (182.5A) 200 3"

XXXXXXXXXXXXXXXX
60 77 4 3 200 300 000 (212.5A) 200 3"
75 96 4 1 250 350 0000 (260A) 200 3"
NOTE :

PROJECT NO XXXX
XXXXXXXXXX
1. THE ABOVE TABLE COMPILED PER CURRENT NATIONAL ELECTRIC CODE SECTION 430 TABLE 430.250

PROJECT NAME:
NOTE: 2. GROUNDING ELECTRODE SIZED PER NATIONAL ELECTRICAL CODE
LIGHTNING ARRESTER ENCLOSURE SIZE : 30" x 20" x 8" 3. *GENERATOR PLUGS ARE SIZED TO MATCH THE GENERATOR'S CORD, NOT THE ELECTRICAL SERVICE.
LIGHTNING ARRESTER
NEMA 3R STAINLESS STEEL 4. CONDUCTOR B IS A MOTOR CIRCUIT FEEDER, RATED AT 90 DEG C, SIZED FOR 2 PUMPS AT 125% 0F FLA PLUS A 20 AMP GENERAL LOAD.
5. DESIGNER TO VERIFY DATA IN THESE TABLES
6. SERVICE RACEWAY TO BE OVERSIZED AS SHOWN TO ACCOMMODATE FUTURE EXPANSION.

EMERGENCY CONNECTION/TRANSFER SWITCH


NTS
PHASE MONITOR POWER PRESENT
LIGHT
PHASE MONITOR POWER PRESENT F13
LIGHT 1A L1 NO B N

F13 NOTE: F14


1A L2
1A L1 NO B N MCB AND ECB ARE TO BE SUITABLE FOR
USE AS SERVICE EQUIPMENT ARE TO BE F15
F14 1A L3 C
1A L2 PERMANENTLY IDENTIFIED AS SERVICE
F15 DISCONNECTS, ARE TO BE CAPABLE OF
1A L3 C BEING OPERATED WITHOUT EXPOSING
OPERATOR TO CONTACT WITH LIVE PARTS.
GROUND FAULT PROTECTION-25000 IC
AT 240 V, 30000 IC AT 480 V. TRANSFER SWITCH CONTROL PANEL
TRANSFER SWITCH CONTROL PANEL POWER METER
POWER METER
B B CB1 A A
B B A MCB
MCB CB1 M1 OL
M1 OL

PUMP 1
PUMP 1
FPL
POWER METER

GROUND BUSS IN
CONTROL PANEL LIGHTNING
LIGHTNING
ARRESTER
ARRESTOR M2 OL
OL CB2
CB2 M2
FPL
GROUND BUSS SEAL
GROUND BUSS
IN TRANSFER PUMP 2
IN TRANSFER PUMP 2
PANEL
PANEL

ECB
ECB NEUTRAL BUSS
NEUTRAL BUSS L3
L3 IN CONTROL
IN CONTROL GENERATOR
GENERATOR NEUTRAL BUSS PANEL
PANEL RECEPTACLE L2
RECEPTACLE L2 IN TRANSFER
NEUTRAL BUSS DESIGN: DRAWN: CHECK:
IN TRANSFER PANEL L1
L1 5A FUSE DATE: REVISION DESCRIPTION:
PANEL NO 6 BC MIN
TO SERVICE
GROUND 3 KVA
120V TO CONTROL CIRCUITS
XFORMER USE
NO 6 BC MIN WITH 480V
TO SERVICE
GROUND
NOTE: CONTROL PANEL/CONNECTION PANEL AND TRANSFER SWITCH TO BE MANUFACTURED
BY CHAMPION CONTROLS, INC. TO WWS SPECIFICATIONS (NO SUBSTITUTION). TRANSFER SWITCH MUST BE RATED AS 120V
SERVICE ENTRANCE EQUIPMENT TO CONTROL CIRCUIT DRAWING NAME:
ELECTRICAL SERVICE AND
TRANSFER SWITCH MUST BE RATED AS
FLORIDA LICENSED PROFESSIONAL ENGINEER TO REVIEW AND TRANSFER SWITCH
SERVICE ENTRANCE EQUIPMENT
MODIFY ELECTRICAL DESIGN AS REQUIRED TO ACCOMPLISH SCALE: DWG NO:
CONSTRUCTION IN ACCORDANCE WITH APPLICABLE CODES AND
240V MAIN POWER CIRCUIT STANDARDS. 480V MAIN POWER CIRCUIT AS SHOWN
DESIGNATION:

LAST SAVED: 06/06/13 - 3:27PM E-5


L:\EED_DESIGN_DATA\CAD STANDARDS\WWS STD SUBMITTALS\LIFT STATION TO DEVELOPER\WWS WEBSITE 6.6.2013\WWED LIFT STATIONS TEMPLATE.dwg, ELECTRICAL DETAILS (E-6), 6/6/2013 3:53:49 PM, CBGARCIA, Adobe PDF.pc3

WETWELL TOP SLAB

3" ALUMINUM END BELL,


SEAL WITH FOAM

PUMP MOTOR
CABLE

CONTROL PANEL CONNECTION PANEL


PS1 LEVEL
TRANS
(F)

LG-1
2 1/2" SCHED 40
(D)
ALUMINUM PIPE
A/C # 1
3" ID PIPE CUP
GROUT FILL

8" (MIN)
(A) (C)
6"MIN CONCRETE SLAB (A) (A)

MIN
LEGEND (A) (E)

6"
A/C # 2 (B)
(A) MALE BRANCH TEE
(B) CONTROL VALVE
(D)
(C) BULKHEAD FITTING
GUIDE (D) CHECK VALVE
(E) SHUT- OFF VALVE
RAILS (F) 0-10 PSI PRESSURE TRANSDUCER
MIN 3/4" PVC SPACER CONCRETE SLAB
3" ALUMINUM
316
CONDUIT
SST
PUMP STRAP
MOTOR
WET WELL TO WETWELL
CABLE
WALL

XXXXXXXXXXXXXXXX
NOTE:
ALL MOUNTING HARDWARE

PROJECT NO XXXX
MUST BE 316 SST

XXXXXXXXXX
PROJECT NAME:
GUIDE RAIL AND PUMP CONDUIT BUBBLER PIPING BUBBLER PIPE SPACER 3" PIPE CUP
NTS NTS NTS NTS

SEAL

DESIGN: DRAWN: CHECK:

DATE: REVISION DESCRIPTION:

DRAWING NAME:

ELECTRICAL DETAILS

SCALE: DWG NO:

AS SHOWN
DESIGNATION:

LAST SAVED: 06/06/13 - 3:27PM E-6