Sei sulla pagina 1di 4

Specifying

Cable System BY BRUCE BROUSSARD, CSE,


Vice President of Operations,
Imcorp, Storrs, Conn.

Reliability
Power cable diagnostics enable Consulting engineers have been specifying DC Hi-Potting to com-
mission newly installed power cable systems for the past century.
consulting engineers to specify and While this cable test is very popular, the question remains whether
it is effective in locating cable system defects that may cause future
commission cable systems cable system failures? If not, is there an adequate alternative to
ensure that the cable system is free of defects and has been prop-
erly installed per the requirements of IEEE cable system standards?
Here, I will address this topic based on experience obtained over
the past ten years. But first, some history.

26 | PURE POWER // JUNE 2007

cse0706ppfea3_ID.indd 26 5/1/2007 4:43:08 PM


PILC cable Extruded cable Technology PD Reliability
(XLPE,EPR and PE) Advances Assessment

1900 1960s 1990s Today

Hi-Pot factory testing Factory PD testing • Hi-Pot destructive • Backed by IEC,


IEEE, and ICEA
• Simple • ICEA specified • Other options
evolve • Factory Grade
• Portable • Industry cont.
Hi-Pot • Advance of DSP • 10 years of data
Failure Mechanism:
opens door for field support
Conduction and PD Failure Mechanism:
PD diagnostics
Partial Discharge • Determine location
and severity
determination

Figure 1. Timeline of cable system testing

HISTORY OF CABLE TESTING were aware that the primary failure their factories. While the factory par-
The origin of shielded power cable mechanism of this type of insulated tial discharge test—known as a corona
(5-kV-rated cable and above) testing cable was partial discharge (over test back in the ‘60s—was able to
goes back approximately 100 years, 95%). In order to implement cable detect partial discharge in their cable,
when paper-insulated lead-covered manufacturing quality controls it was it involved expensive equipment and
(PILC) cable was first installed in necessary to develop the means to required a fabricated shielded environ-
the rapidly expanding United States detect this electrical phenomenon in ment to conduct the test.
electrical distribution grid. While it
was not fully understood at the time,
the primary failure mechanisms of
PILC cable falls into two categories:
The NETA Testing Specs
PILC cable will fail either thermally, The National Electrical Testing Assn. Maintenance Testing Specifications was de-
mostly due to moisture ingress, veloped for use by those responsible for the continued operation of existing electri-
which tends to increase insulation cal systems and equipment to guide them in specifying and performing the necessary
conductivity (approximately 40% of tests to ensure that these systems and apparatus perform satisfactorily, minimizing
failure incidences); or it fails due to downtime and maximizing life expectancy.
the electrical phenomenon known as
The NETA Acceptance Testing Specifications is a document to assist designers,
partial discharge (approximately 60%
specifiers, architects, and users of electrical equipment and systems in specifying
of failure incidences).
required tests on newly-installed power systems and apparatus, before energizing, to
The development of the DC Hi-Pot
ensure that the installation and equipment comply with specifications and intended
test (now categorized by IEEE as a
use as well as with regulatory and safety requirements.
Type 1 Destructive Withstand Test) by
the cable manufacturers was very suc- NETA’s specifications include topics such as Applicable Codes, Standards, and
cessful in causing conductive defects References; Qualifications of the Testing Agency; Division of Responsibility; General
to fail in the PILC cable. However, Information concerning Testing Equipment; Short Circuit Analysis and Coordinating
at that time the technology to detect Studies; System Function Tests; and Thermographic Surveys.
partial discharge activity in the cable
A major featured section includes tests to be performed on Switchgear and Switch-
did not exist. Since the DC Hi-Pot
board Assemblies, Transformers, Cables, Metal-Enclosed Busways, Switches, Circuit
test equipment was inexpensive and
Breakers, Network Protectors, Protective Relays, Instrument Transformers, Metering
simple to use, it was quickly adopted
and Instrumentation, Grounding Systems, Ground Fault Systems, Rotating Machinery,
for field use throughout the electrical
Motor Control, Direct Current Systems, Surge Arresters, Capacitors, Outdoor Bus
industry.
Structures, Emergency Systems, Automatic Circuit Reclosers and Line Sectionalizers,
When extruded dielectric cable (i.e.
Fiber-Optic Cables, and Electrical Safety Equipment.
HMWPE, XLPE, EPR) was introduced
in the 1960s, the cable manufacturers

http://www.csemag.com | 27

cse0706ppfea3_ID.indd 27 5/1/2007 4:43:21 PM


Therefore, the DC Hi-Pot test con- PARTIAL DISCHARGE
tinued as the most recognized option DIAGNOSTICS
for field cable system integrity testing, Off-line 50/60 Hz partial discharge
even though it was known by the diagnostics offers a major advantage
manufacturers to have limited value. over traditional DC and AC withstand
In fact, “from the work of Bach (TU test, because it enables the cable owner
Berlin), we know that even massive to pinpoint the exact defect location
insulation defects in extruded dielec- providing the details necessary to take
tric insulation cannot be detected precise action without destroying the
with DC at the recommended voltage cable. Type 2 non-destructive off-line
levels.” (IEEE 400, section 4.2) In partial discharge diagnostics also pro-
addition, “A major objection to Type 1 vides a second major advantage which
field tests is the concern that applica- is the ability to determine the future
tion of elevated voltages without any performance of the cable system. The above defect was not detected by IEEE
other accompanying diagnostic mea- During its service life, a cable will 400 Type 1 withstand test. It was detected and
surements trigger failure mechanisms be subjected to overvoltage condi- located by the IEEE 400 Type 2 off-line 50/60
that will not show during the test but tions caused by switching, lightning Hz PD diagnostics. This type of diagnostic
which may cause subsequent failures and other transient events. Any test provides a second advantage: the ability to
in service.” (IEEE 400, Section 4.3) conducted at operating voltage will be determine the future performance of the cable
This left a significant void in the unable to simulate in the cable system system.
industry’s ability to effectively test the conditions which may produce
new or existing shielded power cable partial discharge during operation. the cable, joints and terminations have
systems until the mid-nineties when Therefore, in order to effectively their own acceptable level of discharge
Dr. Matthew Mashikian, an innova- predict the future performance of the (see Figure 2 below) defined by IEEE
tive engineering professor at the cable system, a partial discharge test and ICEA.
University of Connecticut was able to at a reasonably elevated voltage must Because the offline 50/60 Hz
utilize evolving digital signal process- be conducted, as stipulated by IEEE partial discharge diagnostic approach
ing technologies to replicate the cable and ICEA. IEEE 400 section 7.4 states is non-destructive and predictive, it
manufacturers’ factory test in practical that “if the cable system can be tested represents a significant breakthrough
field applications (Figure 1, p.27). in the field to show that its partial for consulting engineers designing ap-
This technology, known as off-line discharge level is comparable with plications where reliability of critical
50/60 Hz partial discharge diagnos- that obtained in the factory [off-line loads is important. It is now possible
tics, has been developed over the past 50/60 Hz PD diagnostics test on the for cable system installation quality
10 years in the utility industry and cable and accessories], it is the most levels to be quantified, and therefore,
has evolved into a robust condition convincing evidence that the cable specified by owners and consulting
assessment and predictive diagnostics system is in excellent condition.” engineers. The power of this technol-
solution for power cable. Hence, each component of the system, ogy is evident when it is realized that
certain defects subjected to a IEEE 400
Type 1 destructive withstand test did
not fail, yet were located without fail-
IEEE Standard Thresholds ure by the IEEE Type 2 non-destructive
partial discharge technology.
IEEE 48-1996 Terminations No PD 욷 5pC up to 1.5Uo Consulting engineers develop-
ing specifications for facilities such
IEEE 404-2000 Joints No PD 욷 3pC up to 1.5Uo as data centers, casinos, hospitals,
industrial sites and other critical-
IEEE 386-1995 Separable Connectors No PD 욷 3pC up to 1.3Uo load facilities are now empowered to
establish specific installation quality
parameters based on IEEE and ICEA
ICEA S-93-639-2000 MV Extruded Cable No PD 욷 5pC up to 4Uo
standards (see Figure 2) to assure that
their cable system designs meet the
Figure 2. IEEE and ICEA standards for allowable partial discharge in various cable required reliability level desired by
system components their user clients.

28 | PURE POWER // JUNE 2007

cse0706ppfea3_ID.indd 28 5/1/2007 4:43:31 PM


THE SETUP three cable PD (defects) sites from
Testing Technology According to the manufacturer of a the previous test. In addition to three
The non-destructive diagnostic VLF source, a 25-kV class cable should sites, the second PD test showed
test from Imcorp is based on pulse be tested with 0.1Hz VLF at 3xUo for seven new sites after the 30 minute
reflectometry and time-of-arrival 30 minutes. This may be confusing for VLF Hi-Pot test.
techniques. At the core of the technol- some because 3xUo equals 3x13.2 kV The three original PD sites appeared
ogy is an expert system that uses rms, or 39.6 kV rms. The IEEE guide at a test voltage closer to operating
cutting edge digital signal processing for VLF Hi-Pot field testing (IEEE voltage after the VLF Hi-Pot demon-
techniques and high performance 400.2) recommends 23 kV rms for strating deterioration at each location.
electronics. This system empowers 25-kV cables. During the experiment, Note that the comparative PD tests
the user to locate defects and make the manufacturer of the VLF source were carried out within minutes of the
decisive recommendations for mainte- explained that even though their VLF Hi-Pot to ensure that the most ac-
nance. The technology makes use of equipment only produces a maximum curate comparison could be made.
the power frequency (50/60Hz) to ex- of 23 kV rms, they claim that only
cite defects in the cable being tested. the peak voltage needs to reach ~40 FINALCONSIDERATIONS
Power frequency testing exactly rep- kV to have an effective VLF Hi-Pot. While IEEE 400 Type 1 withstand test
licates service conditions and allows The manufacturer made the following (DC and AC Hi-Pot) provide some
comparisons to be made to standard statements: value when testing older PILC cables,
factory tests. In laboratory tests and Electrical tree growth rate is 472 they may not be effective in locating
comparative field tests, the technol- mils/hr or 12mm/hr in XLPE insula- defects in extruded dielectric insulated
ogy has proved itself especially in the tion. cables. Furthermore, they may un-
presence of high ambient noise. A VLF Hi-Pot left on for 30 minutes knowingly trigger failure mechanisms
will grow any significant defect to that may cause subsequent failures in
Acquisition of the cable topology
failure in a 25-kV class cable. service.
allows the user to locate cable joints
If the cable fails within the 30 min- On the other hand, IEEE 400 Type
and neutral discontinuities, and to
ute Hi-Pot test, the cable is “bad.” 2 non-destructive off-line 50/60 Hz
determine the cable length. Sensitiv-
If the cable survives the 30 minute partial discharge diagnostics provide
ity calibration allows the subsequent
Hi-Pot test, the cable is “good.” valuable information concerning the
test to be compared to the baseline
Only 3% to 4% of cables that test quality and workmanship of a newly
cable factory test. The HV diagnostic
“good” will fail within the next three installed or aged cable system. This
tests apply continuous 50/60 Hz volt-
years. information includes detecting cable
age to the cable for a few seconds.
It is recommended that the 30 defect locations and determining
During this time, the system takes
minute VLF Hi-Pot be repeated after their severity in accordance with
measurements and stores the data.
a failed cable is repaired to ensure the preset acceptable limits
The operator turns off the high voltage
reliability. (see Figure 2). Therefore, correc-
and analyzes the data with the help
tions can be made to assure that the
of the proprietary software system. A
THE RESULTS cable system is in excellent operating
preliminary report and recommenda-
Each phase was VLF Hi-Pot tested condition before the system is placed
tions are produced on site.
independently. The results follow: into service.
‘A’ phase survived 31 minutes of What does all of this information
VLF HIPOT. add up to for the consulting engineer?
A TEST CASE ‘B’ phase failed after 20 minutes of As mentioned at the beginning, con-
A utility asked us to perform a PD test VLF HIPOT application. sulting engineers have been specify-
on a 1,405-ft. long, 25-kV Class, 1000 ‘C’ phase failed after a prolonged ing DC Hi-Potting to commission
kcmil XLPE feeder cable. According to dwell time of 37 minutes. (The opera- newly installed power cable systems
the PD test results, multiple defects in tor of the test lost track of time and for the past century. But it’s time to
the cable insulation were present. The forgot to stop the Hi-Pot at 30 min- consider whether there is an alterna-
utility then asked a manufacturer of a utes.) tive to this type of testing. There is an
VLF voltage source to perform a VLF As for the PD Diagnostic test adequate alternative that ensures that
Hi-Pot on the cable. results, the only cable which could the cable system is free of defects and
If any of the condemned phases sur- be retested was ‘A’ phase, since the has been properly installed per the
vived, the PD test would be repeated other two phases failed during the requirements of IEEE cable system
on those phases. test. ‘A’ phase was known to have standards. 

30 | PURE POWER // JUNE 2007

cse0706ppfea3_ID.indd 30 5/1/2007 4:43:43 PM

Potrebbero piacerti anche