WAGO-I/O-PRO CAA library

WagoLibModbus_IP_01.lib

The library WagoLibModbus_IP_01.lib contains two function blocks:


ETHERNET_MODBUSMASTER_UDP and
ETHERNET_MODBUSMASTER_TCP
Using this function blocks communication with one or more slaves can be
established.
It is recommended to use the function block
ETHERNET_MODBUSMASTER_UDP since data exchange can be handled
more quickly than using the TCP block.

Content

WagoLibModbus_IP_01.lib 3
ETHERNET_MODBUSMASTER_UDP ................................................... 3
ETHERNET_MODBUSMASTER_TCP .................................................... 5

WAGO-I/O-PRO CAA Version 1.0.1 WagoLibModbus_IP_01.lib - 1


ETHERNET_MODBUSMASTER_UDP

2 – WagoLibModbus_IP_01.lib ml01800e WAGO-I/O-PRO CAA


WagoLibModbus_IP_01.lib

WagoLibModbus_IP_01.lib

ETHERNET_MODBUSMASTER_UDP

WAGO-I/O-PRO CAA Library elements


Category: Communication
Name: ETHERNET_MODBUSMASTER_UDP
Type: Function Function block X Program
Library : WagoLibModbus_IP_01.lib
Requiered libraries SysLibSocket.lib
Applicable to: 750-841(Release 07), 758-870(Release01)

Input: Data type: Comment:


xOPEN_SOCKET BOOL Opens a socket on the client
strIP_ADDRESS STRING IP address of server
wPORT WORD Port
bUNIT_ID BYTE -According to the “UnitId” in protocol header
-Slave-ID in a serial modbus network
- Buffer index of modbus slave on a PC
according to example ActiveMBTSlaveCtl.
bFUNCTION_CODE BYTE Supported function codes
0x1: Read Coil Status
0x2: Read Input Status
0x3: Read Holding Registers
0x4: Read Multiple Register
0x5: Force Single Coil
0x6: Write Single Register
0x7: Read Exception Status
0x0F: Write Multiple Coils
0x10: Write Multiple Register
0x17: Read and Write Multiple Registers
wREAD_ADDRESS WORD Start address for reading commands.
wREAD_QUANTITY WORD Number of data for reading.
ptREAD_DATA POINTER Pointer to array, where the read data will be
TO BYTE stored.
wWRITE_ADDRESS WORD Start address for writing commands.
wWRITE_QUANTITY WORD Number of data for writing
ptSEND_DATA POINTER Pointer to array, where the data, which shall
TO BYTE be written, are placed.
tTIME_OUT TIME Time within the slave ought to respond to
the request.
InOut: Data type: Comment:
xSEND BOOL Send modbus request. This variable will be
reset by the functionblock.

Output: Data type: Comment:

WAGO-I/O-PRO CAA Version 1.0.1 WagoLibModbus_IP_01.lib - 3


ETHERNET_MODBUSMASTER_UDP

WAGO-I/O-PRO CAA Library elements


xIS_OPEN BOOL Socket is created on the client. Client ready
to send modbus request.
wERROR WORD 0x0000 – Succesful
0x0001 – Illegal function code
0x0002 – Illegal data address
0x0003 – Illegal data value
0x0004 – Slave device failure
0x0005 – Acknowledge
0x0006 – Slave device busy
0x0007 – Negative acknowledge
0x0008 – Memory parity error
0x000A – Gateway path unavailable
0x000B – Gateway target no respond
0x0079 – no socket available
0x0097 – Illegal number of points
0x0098 – Internal buffer overrun
0x0099 - TimeOut
bRESPONSE_UNIT_ID BYTE According to the “UnitId” in protocoll header

Graphical description:

Description:
Using ETHERNET_MODBUSMASTER_UDP the IPC becomes a Modbus-Master.
First a socket has to be opened by the input xOPEN_SOCKET. If the socket could be opend
the output xIS_OPEN will show TRUE. Otherwise the wERROR output will display 0x79.
Modbus requests can be send by setting the IN_OUT variable xSEND to True. The function
block will reset this variable after execution of the command.
If the slave does not respond within the time tTIME_OUT error code 0x99 will be displayed.

The function block ETHERNET_MODBUSMASTER_UDP uses UDP as protocoll(User


Datagramm Protocoll) This allows quicker data exchange than using TCP protocoll.

4 – WagoLibModbus_IP_01.lib ml01800e WAGO-I/O-PRO CAA


WagoLibModbus_IP_01.lib

ETHERNET_MODBUSMASTER_TCP

WAGO-I/O-PRO CAA Library elements


Category: Communikation
Name: ETHERNET_MODBUSMASTER_TCP
Type: Function Function block X Program
Name of library: WagoLibModbus_IP_01.lib
Requiered libraries SysLibSocket.lib
Applicable to: 750-841(Release 07), 758-870(Release01)

Input: Data type: Comment:


xCONNECT BOOL Establishes the connection to the server
strIP_ADDRESS STRING IP address of server
wPORT WORD Port
bUNIT_ID BYTE -According to the “UnitId” in protocoll header
-Slave-ID in a serial modbus network
- Buffer index of modbus slave on a PC
according to example ActiveMBTSlaveCtl.
bFUNCTION_CODE BYTE Supported function codes
0x1: Read Coil Status
0x2: Read Input Status
0x3: Read Holding Registers
0x4: Read Multiple Register
0x5: Force Single Coil
0x6: Write Single Register
0x7: Read Exception Status
0x0F: Write Multiple Coils
0x10: Write Multiple Register
0x17: Read and Write Multiple Registers
wREAD_ADDRESS WORD Start address for reading commands.
wREAD_QUANTITY WORD Number of data for reading.
ptREAD_DATA POINTER Pointer to array, where the read data will be
TO BYTE stored.
wWRITE_ADDRESS WORD Start address for writing commands.
wWRITE_QUANTITY WORD Number of data for writing
ptSEND_DATA POINTER Pointer to array, where the data, which shall
TO BYTE be written, are placed.
tTIME_OUT TIME Time within the slave ought to respond to
the modbus request.
tCON_WATCHDOG TIME Time within the server ought to respond if
the connection is to be established.

WAGO-I/O-PRO CAA Version 1.0.1 WagoLibModbus_IP_01.lib - 5


ETHERNET_MODBUSMASTER_TCP

InOut: Data type: Comment:


xSEND BOOL Send modbus request. This variable will be
reset by the functionblock.
Output: Data type: Comment:
xIS_CONNECTED BOOL Connection to the server is established.
wERROR WORD 0x0000 – Succesful
0x0001 – Illegal function code
0x0002 – Illegal data address
0x0003 – Illegal data value
0x0004 – Slave device failure
0x0005 – Acknoledge
0x0006 – Slave device busy
0x0007 – Negative acknowledge
0x0008 – Memory parity error
0x000A – Gateway path unaviable
0x000B – Gateway target norespond
0x0079 – No socket available
0x0080 – Can not send modbus request
0x0096 – Server not available
0x0097 – Illegal number of points
0x0098 – Internal buffer overrun
0x0099 - TimeOut
bRESPONSE_UNIT_ID BYTE According to the “UnitId” in protocoll header

Graphical description:

Description:

6 – WagoLibModbus_IP_01.lib ml01800e WAGO-I/O-PRO CAA


WagoLibModbus_IP_01.lib

Using ETHERNET_MODBUSMASTER_TCP the IPC becomes a Modbus-Master.

Number of slaves is only limited by the modbus protocoll.

The function block ETHERNET_MODBUSMASTER_TCP uses TCP as protocoll.

The function block ETHERNET_MODBUSMASTER_TCP is recommended to use, if the


modbus slave only supports TCP protocoll rather than UDP.

Warning: This function block may block on the 750-841. It is therefore strongly recommended
to use this function block in an own task.