Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
Example 1:
d
A 1200/5, C400 CT with excitation curves shown on above figure, is connected to a
2.0Ω burden. Based on the accuracy classification, what is the maximum symmetrical
fault current that may be applied to this CT without exceeding a 10% ratio error?
Answer:
Based on the criteria that the CT can deliver 20 times rated secondary current
without exceeding a 10% ratio error, the maximum fault current will be 24000A.
However, with a 2.0Ω burden, this will result in a voltage below the knee point of the CT
and, as a practical matter, it will be within 10% accuracy at higher currents. This can only
be accurately determined from excitation or ratio correction curves and not from the
accuracy classification. For example, a CT with characteristics shown in above figure
will produce between 180-240A without exceeding the 10% ratio error, depending on the
power factor of the 2.0Ω burden.
2
Example 2:
A 1200/5, C400 CT is connected on the 1000/5 tap. What is the maximum secondary
burden that can be used and still maintain rated accuracy at 20 times rated symmetrical
secondary current?
Answer:
Since the secondary voltage capability is directly proportional to the connected tap, the
CT will support a voltage of 1000/1200 400V or 333V. Twenty times the rated
secondary current is 100A. Therefore, the maximum burden is 333V/100A or 3.33 Ω
Example 3:
Assume that secondary burden in a relay circuit is 5Ω. The relay setting is 2A and the CT
ratio is 300/5. Using above figure, calculate the primary current required to operate the
relay?
Answer:
VB=5 Ω times 2A=10V
The secondary exciting current from above figure is approximately 0.04A.
I P N ( I ST )
N (I E I S )
= 300/5(0.04+2) A=122A
Example 4:
A relay is expected to operate for a 7000A primary current. The CT ratio is 600/5.
Secondary burden is 3.5 Ω. What is the error for the CT shown in above figure?
Answer:
The total secondary fault current is (7000/600) 5=58A. Assume that exciting current is
negligible.
3
VS I S ( R B RS )
= 58(3.5+0.31)
= 221V
The exciting current will not be negligible, however, and the calculation will not be
iterated.
Lec – 7
N1 RI 0 Vm N1 R Vm Vm N1 N1 RI 0 -tt N1 I 0 -tt
fdcmax t t N1 Rt v2 (t )
dc
e i2 e
N 22 | Z line | N 22 | Z line | | Z line | N 22 N2 N2
t -t -t
1 N1 RI 0 t N1 RI 0
f (t ) - f (0) t (1 - e ) f (t ) f (0) t (1 - e t )
N2 �
v2 dt 2 2
0
N 2 N 2
Lec- 7
Vm N1 d V2
v2ac (t ) R sin(wt f - q ) jw f ac
| Z line | N 2 dt jw N 2
RVm N1 p RVm N1
fac (t ) sin(wt f - q - ) facmax
w | Z line | N 2
2
2 w | Z line | N 22
Vm N1
Rt
RVm N1 N1 RVmt | Z line | N 22 wL X
facmax fdcmax 2 1 1 wt 1 line 1 line
w | Z line | N 2 N 2 | Z line |
2
Vm N1 R Rline Rline
| Z line | N 2 w
2
X
1
R
Lec-6
Lec – 5
Ip Ip
- IS Ip IE - IS
N - I I �100 N 98�45�
�100 N S E
IS �100
IS IS
Lec - 9
Vth - VT 1 1
�100 (3f ) ( L )Dw w02 w02 1 LC < f Df �3Hz
Vth w02
LC
1t di dv di 1 d 2i
v(t ) Ri �
Ceq
-�
idt L
dt dt
R
dt Ceq
i L w
dt 2 0
d 1 1 1
DVL - DVC jI (w L - ) Dw I (2 2 )Dw w02 I ( L L )Dw
dw wCeq w0 Ceq LCeq
| V - V | 2 LI Dw 2 LI 2 LDw
j 2 LI Dw (DVL - DVC ) tan b L C 2 2 � 2p f Lm 106
| VR | a Rb I a Rb a 2 Rb
106
Lm 3183.1H
2p
5
source. The fault strikes at time t t 0 . This can be simulated by closing the switch at t t1
R jwL or Z q models the line impedance. The fault current in the line is given by
i (t ) 0 0 t t0
t -t 0
V sin(w t f - q ) -
t
t t0
i (t ) m I 0e
|Z |
Where τ is the time constant of the line τ =L/R. The fault current has two components in
it. The first component models the steady state sinusoidal ac response while the second current
is the dc offset current due to the presence of inductive component in the circuit. Recall that
current in an inductance can not change instantaneously. As t ∞, the instantaneous dc
theory persist till infinity, it’s trace in the actual wave form would not be seen beyond a certain
-t
time constants. Table-I illustrates the values of e t up to 10 time constants.
It is more or less obvious that, dc offset is not seen in the waveform after 5 time constants.
The value of I0 can be worked out by setting the current at t t o to zero.
This implies that
Vm
I0 - sin(wt 0 - q )
Z
Thus
t -t 0
V V -( )
i (t ) m sin(wt f - q ) - m sin(wt f - q )e t
Z Z
fig.2
It can be seen that severity of dc offset component in fault current is maximum when
a) f q
p
b) wt 0
2
p 1
For example, if angle of transmission line is 800, then with f = 800 & t 0 =
2 2p 50 200
V
sec = 5msec, the severity of dc offset current would equal I 0 Z , which is also the peak
m
We now plan to show that CT can saturate on dc offset current. Also, we plan to show
that the resulting distortions in the CT secondary current can be un-acceptably high. While
doing this analysis, we will neglect ac symmetrical component. In other words, we rest our
belief in superposition theorem atleast qualitatively and will finally evaluate effect using it
Notice that the current that we are dealing with is non-linear, a rigorous application of super
position theorem is simply out of question.
First consider an ideal CT excited by the dc offset current source. An ideal CT will faithfully
replicates primary current waveform on the secondary side. Hence, the secondary current
would be given by
-t
I0 t
i2 (t ) e
N
and the voltage developed across CT secondary would be given by
-t
RI N2
v 2 (t ) 0 e t where N N
N 1
For simplicity, let us assume that the initial flux in the transformer core at t=0 is zero
f ( 0 ) 0 ; Then we can compute the flux in the transformer core by using faraday’s law
df
V2 N 2 ---------(2)
dt
t
f (t ) - f (0) v
0
2 dt
RI 0
-t
t 1- e t
N2
-t
LI 0
(1 - e t )
N2
-t
LI 0
f (t ) f (0) (1 - e t )
N2
-t
LI 0
(1 - e t ) ------- (3)
N2
as a consequence of dc offset current,
Thus, flux in the core increases exponentially to a peak value of
f dmax
c
LI 0
N2
as t
L Vm Vm
N Z Z
f dmax
c
10
Note that unlike ac voltage induced flux, which is sinusoidal, this flux is unidirectional. The ac
voltage induced flux has zero average value. However, dc offset induced does not have this
nice feature. The total flux in ideal CT core is a summation of ac flux and dc flux.
d
The ac flux in the CT core can be obtained by substituting operator by jw . Hence
dt
If v2 (t ) Vm sin(wt f ) , then
Vm p
f ac sin(wt f - )
wN 2 2
The peak value of ac flux is given by
Vm
f acmax
wN 2
However Vm R2 I 0
max
R2 I 0max
Hence facmax
wN 2
and peak value of the total flux is given by
Vm LI 0max
facmax f dcmax
wN 2 N2
In practice, if this flux exceeds the knee-point flux in the core (see fig.), then the CT core
will saturate.
11
As a consequence of CT core saturation, the secondary current would not faithfully replicate
the primary current. Infact, in practice it is observed that CT secondary current is clipped. The
clipping of CT current leads to “blinding” of the relay which cannot function further. Hence,
CT saturation in presence of dc offset current is a serious problem which relay designers have
to face. Note that dc flux accumulates gradually. (Depends upon the transmission line time
constant ( t ). It is apparent that saturation should not occur immediately after the inception of
the fault. Thus, if the relay is fast enough in decision making, it is likely that a relaying
decision would be undertaken before the CT fully saturates. This is another important reason
for increasing the speed of relaying system. For bus-fault protection, where the dc saturation
due to dc offset current can be a significant contributing factor, quarter cycle operations *****
specifically are imposed. Similarly, a distance relay is expected to operate within ½-1 cycle
time.
CT oversizing factors
Typically, an efficient design of transformer would correspond to choosing the core cross
section such that f mac should be near the knee point of B-H curve. One obvious way of
avoiding the CT saturation on dc flux is to oversize the core so that for flux (f acmax f dcmax ) , the
(f acmax f dcmax )
corresponding B is below the knee-point. Hence, the factor is called core-
f acmax
oversizing factor.
12
f dcmax
Core-oversizing factor = 1 max
f ac
LI o N 2
1
RI 0 wN 2
wL
1
R
X
1
R
Note that X/R in above equation is the transmission line X/R ratio. For a 220KV line X/R 10.
This would imply that transformer core should be oversized by a factor of 11. For a 400KV
line, typical value of X/R 20. This would imply an oversizing required of about 21 times the
usual design. Clearly this high amount of oversizing is not practical. Thus, the important
conclusion is that, protection engineers have to live with the saturation problem.
Cautions in CT selection:
While choosing a CT for a particular application, it is necessary to observe following
precautions.
1. The CT rating and continuous load current should match. For example, if max load
current is 90A, a 100:5 Ct may be acceptable but 50:5 is not acceptable.
2. The maximum fault current should be less than 20 times the CT rated current. for
example 100:5 CT can be used, so long as burden on the CT & maximum primary fault
current is below 2000A.
3. The voltage rating of CT should be compatible. For example, 100:5 C100 would give
linear response, upto 20 times rated current provided CT burden is kept
below(100/20*5=1 Ω). With 2 Ω burden, this CT can be used only if maximum current
is limited to 1000A.
4. Parallel of CT’s e.g. in differential protection, or with SLG fault can create significant
errors in CT performance. One should in general ascertain that magnetizing current is
kept much below the pick up value.
Following example, illustrates this point
Exercise problems:
13
If the current ratio is adequate for a protection, but CT burden is high; then the
performance of CT may deteriorate due to large magnetizing current and/or saturation problem.
The CT performance can be improved by connecting the CT’s in series.
1) Electromechanical relays tend to saturate at high currents. This reduces the relay burden
on CT, and so that the CT performance at moderately high currents may be considered
better than at relay’s rated burden at 5A.
2) Use of instantaneous over current relays has the potential to overcome this problem of
saturation of CT’s
3) Differential protection can operate on external faults due to the un equal saturation of
CT’s
Lecture-6
Examples
6. If a 300:5 class C CT is connected to a meter with resistance R I 1 and
secondary current in the CT is 4.5A find out the primary current voltage
developed across the meter and % rate error. Lead wire resistance R L 0.02
secondary resistance RS of a 300/5 CT 0.15
Diagram
R I 1 , R L 0.02 RS 0.15 I S 4.5 A
Total secondary resistance RT R I R L RS
1.17
Secondary voltage I S RT
4.5 1.17
5.265V
From Fig 5.7,
Exciting current IE for 5.265V
= 0.03A
14
Lecture – 8
Examples
1. Design a CCVT for a 132kV transmission line using the following data.
Resistive Burden (3f )-150VA
Df 3Hz , phase angle error b = 40 min
Consider 4 choices of V2 as 33kV, 11kV, 6.6kV and 3.3kV
Diagram 1 Diagram 2
Transmission line voltage V = 132kV. Suppose V 2 (P_N) be the voltage to be
produced by the capacitive potential divider with capacitance values C1 and C2
and L the value of tuning inductor. The standardized VT secondary voltage is 110
volts (L-L).
Here specification for phase angle error b is 40 minutes variation in frequency
can be upto Df 3Hz . Phase angle error for change in w by Dw in the above
equation circuit, is given by
1
( L 2 )Dw
w C
1
At tuning frequency w 2
LC
Substituting w 1 LC
2
747.2 H
1 1
C1 C 2
w 2 L (3/ 4) 2 747.2
1.3610 -2 F
3) V2 6.6kV
3 �(6.6 �103 )2
Rb
'
150
87.1210 4
b �Rb' 0.01164 �87.12 �104
L
2 �Dw 2 �2p �3
269H ,
C1 C 2 3.7710 -2 F
4) V2 3.3kV
3 �(3.3 �103 ) 2
Rb'
150
21.7810 4
b �Rb' 0.01164 �21.78 �104
L
2 �Dw 2 �2p �3
67.25 H
C1 C2 0.151 F
The values of L, C1 C 2 for different values of V2 are tabulated below.
V2 L C1 C 2
33kV 6722.2H 0.00151 F
11kV 747.2H 0.0136 F
6.6kV 269H 0.0377 F
3.3kV 67.25H 0.151 F
From the above table it is clear that smaller the value of V 2, the smaller is the
value of L and higher the value of C 1 and C2 for tuning condition. If we select too low
value of V2 and L then capacitance values will be beyond available limits, and if we
select higher value of V2 and L, then CCVT and inductor will become bulky. So a
compromise is necessary and let us select V2 = 6.6kV
For V2 = 6.6kV
L = 269H
C1 C 2 0.0377 F
V C1 C 2
Now,
V2 C1
13210 3 0.037710 -6
36.610 3
C1
0.0377 36.610 3 10 -6 F
C1
13210 3
0.0033F
17
C 2 0.0344F
In this design, we explained the basic concept for CCVT design and we assumed
the transformer to be ideal. But in actual design practice the value of magnetizing
impedance of transformer, resistance of reactor etc have to be taken into account,
as ratio error a and phase angle error b will also get affected by these values.
2. Diagram
The equivalent circuit of a CCVT is shown in fig 8.3. The values of C 1 and C2 are
0.0018 F and 0.018 F respectively. Tuning inductor has an inductance of
497H and resistance of 4620 .
Xm of the 6.6kV VT is 1M , core loss = 20 watts per phase, VA burden =
150VA per phase. Value of Cm for compensating the current drawn by m is equal
to 3.18310 -9 F .
(a) Verify the appropriateness of choice of L and Cm.
Ans: If C1 0.0018F and C 2 0.0186F then the value L of tuning inductor
is given by
1
L 2
w (C1 C 2 )
where w 2p f and f = tuning frequency
1
L
(2p �50) (0.0018 0.0186) �10-6
2
1
Xm
w Cm
1 1
Cm
w X m (2p �50) �� 1 106
3.183 �10-9 F
The value is also same as the selected value of Cm Hence the selection of both L
and Cm is appropriate.
(c) If the frequency drops from 50Hz to 47Hz, what would be the values of ratio
error and phase angle error?
Ans: Core loss = 20w
V22
20W
Rm
18
V22 (6600) 2
Rm
20 20
2.18 �10
6
6600 0
A
260874.14 -2.44�
VT I th �Z
6600 0
�256147.5 1.82�
260874.14 -2.44�
6480.42 4.26�
(6600 - 6480.42)
Hence % ratio error �100
6600
=1.81%
Phase angle error = 4.26�
V2 6.6kV
r a w2 a 2
M
d 2i R di 1 1 R
t �t0 2
i0 wn 2p �50 2 Iwn
dt L dt LCeq LC L
d 2i
2
2a wn wn2i 0 a < 1
dt
Lec – 8
1
2p �50 2zw R d i 2zw w 2i 0 z wn z < 1
2
wn
LCeq n
L dt 2 n n
-t V
t I 0 - m sin(wt0 f - q ) f q
e | Z line |
20
Example 1:
d
21
Answer:
Based on the criteria that the CT can deliver 20 times rated secondary current
without exceeding a 10% ratio error, the maximum fault current will be 24000A.
However, with a 2.0Ω burden, this will result in a voltage below the knee point of the CT
and, as a practical matter, it will be within 10% accuracy at higher currents. This can only
be accurately determined from excitation or ratio correction curves and not from the
accuracy classification. For example, a CT with characteristics shown in above figure
will produce between 180-240A without exceeding the 10% ratio error, depending on the
power factor of the 2.0Ω burden.
Example 2:
A 1200/5, C400 CT is connected on the 1000/5 tap. What is the maximum secondary
burden that can be used and still maintain rated accuracy at 20 times rated symmetrical
secondary current?
Answer:
Since the secondary voltage capability is directly proportional to the connected tap, the
CT will support a voltage of 1000/1200 400V or 333V. Twenty times the rated
secondary current is 100A. Therefore, the maximum burden is 333V/100A or 3.33 Ω
Example 3:
Assume that secondary burden in a relay circuit is 5Ω. The relay setting is 2A and the CT
ratio is 300/5. Using above figure, calculate the primary current required to operate the
relay?
Answer:
22
N (I E I S )
= 300/5(0.04+2) A=122A
Example 4:
A relay is expected to operate for a 7000A primary current. The CT ratio is 600/5.
Secondary burden is 3.5 Ω. What is the error for the CT shown in above figure?
Answer:
The total secondary fault current is (7000/600) 5=58A. Assume that exciting current is
negligible.
VS I S ( R B RS )
= 58(3.5+0.31)
= 221V
The exciting current will not be negligible, however, and the calculation will not be
iterated.
Lec – 7
N1 RI 0 Vm N1 R Vm Vm N1 N1 RI 0 -tt N1 I 0 -tt
fdcmax t t N1 Rt v2 (t )
dc
e i2 e
N 22 | Z line | N 22 | Z line | | Z line | N 22 N2 N2
t -t -t
1 N1 RI 0 t N1 RI 0
f (t ) - f (0) t (1 - e ) f (t ) f (0) t (1 - e t )
N2 �
v2 dt 2 2
0
N 2 N 2
Lec- 7
23
Vm N1 d V2
v2ac (t ) R sin(wt f - q ) jw f ac
| Z line | N 2 dt jw N 2
RVm N1 p RVm N1
fac (t ) sin(wt f - q - ) facmax
w | Z line | N 2
2
2 w | Z line | N 22
Vm N1
Rt
RVm N1 N1 RVmt | Z line | N 22 wL X
facmax fdcmax 2 1 1 wt 1 line 1 line
w | Z line | N 2 N 2 | Z line |
2
Vm N1 R Rline Rline
| Z line | N 2 w
2
X
1
R
Lec-6
Lec – 5
Ip Ip
- IS Ip IE - IS
N - I I �100 N 98�45�
�100 N S E
IS �100
IS IS
Lec - 9
Vth - VT 1 1
�100 )Dw w02
(3f ) ( L w02 1 LC < f Df �3Hz
Vth w02
LC
1t di dv di 1 d 2i
v(t ) Ri �
Ceq
-�
idt L
dt dt
R
dt Ceq
i L 2 w0
dt
d 1 1 1
DVL - DVC jI (w L - ) Dw I (2 2 )Dw w02 I ( L L )Dw
dw wCeq w0 Ceq LCeq
24
| VL - VC | 2 LI Dw 2 LI 2 LDw
j 2 LI Dw (DVL - DVC ) tan b 2 2 2 � 2p f Lm 106
| VR | a Rb I a Rb a Rb
106
Lm 3183.1H
2p
source. The fault strikes at time t t 0 . This can be simulated by closing the switch at t t1
25
R jwL or Z q models the line impedance. The fault current in the line is given by
i (t ) 0 0 t t0
t -t 0
V sin(w t f - q ) -
t
t t0
i (t ) m I 0e
|Z |
Where τ is the time constant of the line τ =L/R. The fault current has two components in
it. The first component models the steady state sinusoidal ac response while the second current
is the dc offset current due to the presence of inductive component in the circuit. Recall that
current in an inductance can not change instantaneously. As t ∞, the instantaneous dc
It is more or less obvious that, dc offset is not seen in the waveform after 5 time constants.
The value of I0 can be worked out by setting the current at t t o to zero.
This implies that
Vm
I0 - sin(wt 0 - q )
Z
26
Thus
t -t 0
Vm V -( )
i (t ) sin(wt f - q ) - m sin(wt f - q )e t
Z Z
fig.2
It can be seen that severity of dc offset component in fault current is maximum when
a) f q
p
b) wt 0
2
27
p 1
For example, if angle of transmission line is 800, then with f = 800 & t 0 =
2 2p 50 200
V
sec = 5msec, the severity of dc offset current would equal I 0 Z , which is also the peak
m
We now plan to show that CT can saturate on dc offset current. Also, we plan to show
that the resulting distortions in the CT secondary current can be un-acceptably high. While
doing this analysis, we will neglect ac symmetrical component. In other words, we rest our
belief in superposition theorem atleast qualitatively and will finally evaluate effect using it
Notice that the current that we are dealing with is non-linear, a rigorous application of super
position theorem is simply out of question.
28
First consider an ideal CT excited by the dc offset current source. An ideal CT will faithfully
replicates primary current waveform on the secondary side. Hence, the secondary current
would be given by
-t
I0 t
i2 (t ) e
N
and the voltage developed across CT secondary would be given by
-t
RI N2
v 2 (t ) 0 e t where N N
N 1
For simplicity, let us assume that the initial flux in the transformer core at t=0 is zero
f ( 0 ) 0 ; Then we can compute the flux in the transformer core by using faraday’s law
df
V2 N 2 ---------(2)
dt
29
t
f (t ) - f (0) v 0
2 dt
RI 0
-t
t 1- e t
N2
-t
LI 0
(1 - e t )
N2
-t
LI 0
f (t ) f (0) (1 - e t )
N2
-t
LI 0
(1 - e t ) ------- (3)
N2
as a consequence of dc offset current,
Thus, flux in the core increases exponentially to a peak value of
f dmax
c
LI 0
N2
as t
L Vm Vm
N Z Z
f dmax
c
Note that unlike ac voltage induced flux, which is sinusoidal, this flux is unidirectional. The ac
voltage induced flux has zero average value. However, dc offset induced does not have this
nice feature. The total flux in ideal CT core is a summation of ac flux and dc flux.
d
The ac flux in the CT core can be obtained by substituting operator by jw . Hence
dt
If v2 (t ) Vm sin(wt f ) , then
Vm p
f ac sin(wt f - )
wN 2 2
The peak value of ac flux is given by
30
Vm
f acmax
wN 2
However Vm R2 I 0
max
R2 I 0max
Hence facmax
wN 2
and peak value of the total flux is given by
Vm LI 0max
facmax f dcmax
wN 2 N2
In practice, if this flux exceeds the knee-point flux in the core (see fig.), then the CT core
will saturate.
As a consequence of CT core saturation, the secondary current would not faithfully replicate
the primary current. Infact, in practice it is observed that CT secondary current is clipped. The
clipping of CT current leads to “blinding” of the relay which cannot function further. Hence,
CT saturation in presence of dc offset current is a serious problem which relay designers have
to face. Note that dc flux accumulates gradually. (Depends upon the transmission line time
constant ( t ). It is apparent that saturation should not occur immediately after the inception of
the fault. Thus, if the relay is fast enough in decision making, it is likely that a relaying
decision would be undertaken before the CT fully saturates. This is another important reason
for increasing the speed of relaying system. For bus-fault protection, where the dc saturation
due to dc offset current can be a significant contributing factor, quarter cycle operations *****
31
specifically are imposed. Similarly, a distance relay is expected to operate within ½-1 cycle
time.
CT oversizing factors
Typically, an efficient design of transformer would correspond to choosing the core cross
section such that f mac should be near the knee point of B-H curve. One obvious way of
avoiding the CT saturation on dc flux is to oversize the core so that for flux (f acmax f dcmax ) , the
(f acmax f dcmax )
corresponding B is below the knee-point. Hence, the factor is called core-
f acmax
oversizing factor.
f dcmax
Core-oversizing factor = 1
f acmax
LI o N 2
1
RI 0 wN 2
wL
1
R
X
1
R
Note that X/R in above equation is the transmission line X/R ratio. For a 220KV line X/R 10.
This would imply that transformer core should be oversized by a factor of 11. For a 400KV
line, typical value of X/R 20. This would imply an oversizing required of about 21 times the
usual design. Clearly this high amount of oversizing is not practical. Thus, the important
conclusion is that, protection engineers have to live with the saturation problem.
Cautions in CT selection:
While choosing a CT for a particular application, it is necessary to observe following
precautions.
5. The CT rating and continuous load current should match. For example, if max load
current is 90A, a 100:5 Ct may be acceptable but 50:5 is not acceptable.
32
6. The maximum fault current should be less than 20 times the CT rated current. for
example 100:5 CT can be used, so long as burden on the CT & maximum primary fault
current is below 2000A.
7. The voltage rating of CT should be compatible. For example, 100:5 C100 would give
linear response, upto 20 times rated current provided CT burden is kept
below(100/20*5=1 Ω). With 2 Ω burden, this CT can be used only if maximum current
is limited to 1000A.
8. Parallel of CT’s e.g. in differential protection, or with SLG fault can create significant
errors in CT performance. One should in general ascertain that magnetizing current is
kept much below the pick up value.
Following example, illustrates this point
Exercise problems:
If the current ratio is adequate for a protection, but CT burden is high; then the
performance of CT may deteriorate due to large magnetizing current and/or saturation problem.
The CT performance can be improved by connecting the CT’s in series.
4) Electromechanical relays tend to saturate at high currents. This reduces the relay burden
on CT, and so that the CT performance at moderately high currents may be considered
better than at relay’s rated burden at 5A.
5) Use of instantaneous over current relays has the potential to overcome this problem of
saturation of CT’s
33
6) Differential protection can operate on external faults due to the un equal saturation of
CT’s
Lecture-6
Examples
7. If a 300:5 class C CT is connected to a meter with resistance R I 1 and
secondary current in the CT is 4.5A find out the primary current voltage
developed across the meter and % rate error. Lead wire resistance R L 0.02
secondary resistance RS of a 300/5 CT 0.15
Diagram
R I 1 , R L 0.02 RS 0.15 I S 4.5 A
Total secondary resistance RT R I R L RS
1.17
Secondary voltage I S RT
4.5 1.17
5.265V
From Fig 5.7,
Exciting current IE for 5.265V
= 0.03A
Turns ratio N = 300/5 = 60
I p N (I S I E )
= 60(4.5 + 0.03)
= 271.8A
Voltage across meter I S R I
4.5 1 = 4.5V
IE 0.03
Ratio error 100 100
IS 4.5
= 0.67%
Rb
34
Lecture – 8
Examples
3. Design a CCVT for a 132kV transmission line using the following data.
Resistive Burden (3f )-150VA
Df 3Hz , phase angle error b = 40 min
Consider 4 choices of V2 as 33kV, 11kV, 6.6kV and 3.3kV
Diagram 1 Diagram 2
Transmission line voltage V = 132kV. Suppose V 2 (P_N) be the voltage to be
produced by the capacitive potential divider with capacitance values C1 and C2
and L the value of tuning inductor. The standardized VT secondary voltage is 110
volts (L-L).
Here specification for phase angle error b is 40 minutes variation in frequency
can be upto Df 3Hz . Phase angle error for change in w by Dw in the above
equation circuit, is given by
1
( L 2 )Dw
w C
1
At tuning frequency w 2
LC
Substituting w 1 LC
2
747.2 H
1 1
C1 C 2
w 2 L (3/ 4) 2 747.2
1.3610 -2 F
3) V2 6.6kV
3 �(6.6 �103 )2
Rb
'
150
87.1210 4
b �Rb' 0.01164 �87.12 �104
L
2 �Dw 2 �2p �3
269H ,
C1 C 2 3.7710 -2 F
4) V2 3.3kV
3 �(3.3 �103 ) 2
Rb'
150
21.7810 4
b �Rb' 0.01164 �21.78 �104
L
2 �Dw 2 �2p �3
67.25 H
C1 C2 0.151 F
The values of L, C1 C 2 for different values of V2 are tabulated below.
V2 L C1 C 2
33kV 6722.2H 0.00151 F
11kV 747.2H 0.0136 F
6.6kV 269H 0.0377 F
3.3kV 67.25H 0.151 F
From the above table it is clear that smaller the value of V 2, the smaller is the
value of L and higher the value of C 1 and C2 for tuning condition. If we select too low
value of V2 and L then capacitance values will be beyond available limits, and if we
select higher value of V2 and L, then CCVT and inductor will become bulky. So a
compromise is necessary and let us select V2 = 6.6kV
For V2 = 6.6kV
L = 269H
C1 C 2 0.0377 F
V C1 C 2
Now,
V2 C1
13210 3 0.037710 -6
36.610 3
C1
0.0377 36.610 3 10 -6 F
C1
13210 3
0.0033F
36
C 2 0.0344F
In this design, we explained the basic concept for CCVT design and we assumed
the transformer to be ideal. But in actual design practice the value of magnetizing
impedance of transformer, resistance of reactor etc have to be taken into account,
as ratio error a and phase angle error b will also get affected by these values.
4. Diagram
The equivalent circuit of a CCVT is shown in fig 8.3. The values of C 1 and C2 are
0.0018 F and 0.018 F respectively. Tuning inductor has an inductance of
497H and resistance of 4620 .
Xm of the 6.6kV VT is 1M , core loss = 20 watts per phase, VA burden =
150VA per phase. Value of Cm for compensating the current drawn by m is equal
to 3.18310 -9 F .
(d) Verify the appropriateness of choice of L and Cm.
Ans: If C1 0.0018F and C 2 0.0186F then the value L of tuning inductor
is given by
1
L 2
w (C1 C 2 )
where w 2p f and f = tuning frequency
1
L
(2p �50) (0.0018 0.0186) �10-6
2
1
Xm
w Cm
1 1
Cm
w X m (2p �50) �� 1 106
3.183 �10-9 F
The value is also same as the selected value of Cm Hence the selection of both L
and Cm is appropriate.
(f) If the frequency drops from 50Hz to 47Hz, what would be the values of ratio
error and phase angle error?
Ans: Core loss = 20w
V22
20W
Rm
37
V22 (6600) 2
Rm
20 20
2.18 �10
6
6600 0
A
260874.14 -2.44�
VT I th �Z
6600 0
�256147.5 1.82�
260874.14 -2.44�
6480.42 4.26�
(6600 - 6480.42)
Hence % ratio error �100
6600
=1.81%
Phase angle error = 4.26�
V2 6.6kV
r a w2 a 2
M
d 2i R di 1 1 R
t �t0 2
i0 wn 2p �50 2 Iwn
dt L dt LCeq LC L
d 2i
2
2a wn wn2i 0 a < 1
dt
Lec – 8
1
2p �50 2zw R d i 2zw w 2i 0 z wn z < 1
2
wn
LCeq n
L dt 2 n n
-t V
t I 0 - m sin(wt0 f - q ) f q
e | Z line |
39
Example 1:
d
40
Answer:
Based on the criteria that the CT can deliver 20 times rated secondary current
without exceeding a 10% ratio error, the maximum fault current will be 24000A.
However, with a 2.0Ω burden, this will result in a voltage below the knee point of the CT
and, as a practical matter, it will be within 10% accuracy at higher currents. This can only
be accurately determined from excitation or ratio correction curves and not from the
accuracy classification. For example, a CT with characteristics shown in above figure
will produce between 180-240A without exceeding the 10% ratio error, depending on the
power factor of the 2.0Ω burden.
Example 2:
A 1200/5, C400 CT is connected on the 1000/5 tap. What is the maximum secondary
burden that can be used and still maintain rated accuracy at 20 times rated symmetrical
secondary current?
Answer:
Since the secondary voltage capability is directly proportional to the connected tap, the
CT will support a voltage of 1000/1200 400V or 333V. Twenty times the rated
secondary current is 100A. Therefore, the maximum burden is 333V/100A or 3.33 Ω
Example 3:
Assume that secondary burden in a relay circuit is 5Ω. The relay setting is 2A and the CT
ratio is 300/5. Using above figure, calculate the primary current required to operate the
relay?
Answer:
41
N (I E I S )
= 300/5(0.04+2) A=122A
Example 4:
A relay is expected to operate for a 7000A primary current. The CT ratio is 600/5.
Secondary burden is 3.5 Ω. What is the error for the CT shown in above figure?
Answer:
The total secondary fault current is (7000/600) 5=58A. Assume that exciting current is
negligible.
VS I S ( R B RS )
= 58(3.5+0.31)
= 221V
The exciting current will not be negligible, however, and the calculation will not be
iterated.
Lec – 7
N1 RI 0 Vm N1 R Vm Vm N1 N1 RI 0 -tt N1 I 0 -tt
fdcmax t t N1 Rt v2 (t )
dc
e i2 e
N 22 | Z line | N 22 | Z line | | Z line | N 22 N2 N2
t -t -t
1 N1 RI 0 t N1 RI 0
f (t ) - f (0) t (1 - e ) f (t ) f (0) t (1 - e t )
N2 �
v2 dt 2 2
0
N 2 N 2
Lec- 7
42
Vm N1 d V2
v2ac (t ) R sin(wt f - q ) jw f ac
| Z line | N 2 dt jw N 2
RVm N1 p RVm N1
fac (t ) sin(wt f - q - ) facmax
w | Z line | N 2
2
2 w | Z line | N 22
Vm N1
Rt
RVm N1 N1 RVmt | Z line | N 22 wL X
facmax fdcmax 2 1 1 wt 1 line 1 line
w | Z line | N 2 N 2 | Z line |
2
Vm N1 R Rline Rline
| Z line | N 2 w
2
X
1
R
Lec-6
Lec – 5
Ip Ip
- IS Ip IE - IS
N - I I �100 N 98�45�
�100 N S E
IS �100
IS IS
Lec - 9
Vth - VT 1 1
�100 )Dw w02
(3f ) ( L w02 1 LC < f Df �3Hz
Vth w02
LC
1t di dv di 1 d 2i
v(t ) Ri �
Ceq
-�
idt L
dt dt
R
dt Ceq
i L 2 w0
dt
d 1 1 1
DVL - DVC jI (w L - ) Dw I (2 2 )Dw w02 I ( L L )Dw
dw wCeq w0 Ceq LCeq
43
| VL - VC | 2 LI Dw 2 LI 2 LDw
j 2 LI Dw (DVL - DVC ) tan b 2 2 2 � 2p f Lm 106
| VR | a Rb I a Rb a Rb
106
Lm 3183.1H
2p
source. The fault strikes at time t t 0 . This can be simulated by closing the switch at t t1
44
R jwL or Z q models the line impedance. The fault current in the line is given by
i (t ) 0 0 t t0
t -t 0
V sin(w t f - q ) -
t
t t0
i (t ) m I 0e
|Z |
Where τ is the time constant of the line τ =L/R. The fault current has two components in
it. The first component models the steady state sinusoidal ac response while the second current
is the dc offset current due to the presence of inductive component in the circuit. Recall that
current in an inductance can not change instantaneously. As t ∞, the instantaneous dc
It is more or less obvious that, dc offset is not seen in the waveform after 5 time constants.
The value of I0 can be worked out by setting the current at t t o to zero.
This implies that
Vm
I0 - sin(wt 0 - q )
Z
45
Thus
t -t 0
Vm V -( )
i (t ) sin(wt f - q ) - m sin(wt f - q )e t
Z Z
fig.2
It can be seen that severity of dc offset component in fault current is maximum when
a) f q
p
b) wt 0
2
46
p 1
For example, if angle of transmission line is 800, then with f = 800 & t 0 =
2 2p 50 200
V
sec = 5msec, the severity of dc offset current would equal I 0 Z , which is also the peak
m
We now plan to show that CT can saturate on dc offset current. Also, we plan to show
that the resulting distortions in the CT secondary current can be un-acceptably high. While
doing this analysis, we will neglect ac symmetrical component. In other words, we rest our
belief in superposition theorem atleast qualitatively and will finally evaluate effect using it
Notice that the current that we are dealing with is non-linear, a rigorous application of super
position theorem is simply out of question.
47
First consider an ideal CT excited by the dc offset current source. An ideal CT will faithfully
replicates primary current waveform on the secondary side. Hence, the secondary current
would be given by
-t
I0 t
i2 (t ) e
N
and the voltage developed across CT secondary would be given by
-t
RI N2
v 2 (t ) 0 e t where N N
N 1
For simplicity, let us assume that the initial flux in the transformer core at t=0 is zero
f ( 0 ) 0 ; Then we can compute the flux in the transformer core by using faraday’s law
df
V2 N 2 ---------(2)
dt
48
t
f (t ) - f (0) v 0
2 dt
RI 0
-t
t 1- e t
N2
-t
LI 0
(1 - e t )
N2
-t
LI 0
f (t ) f (0) (1 - e t )
N2
-t
LI 0
(1 - e t ) ------- (3)
N2
as a consequence of dc offset current,
Thus, flux in the core increases exponentially to a peak value of
f dmax
c
LI 0
N2
as t
L Vm Vm
N Z Z
f dmax
c
Note that unlike ac voltage induced flux, which is sinusoidal, this flux is unidirectional. The ac
voltage induced flux has zero average value. However, dc offset induced does not have this
nice feature. The total flux in ideal CT core is a summation of ac flux and dc flux.
d
The ac flux in the CT core can be obtained by substituting operator by jw . Hence
dt
If v2 (t ) Vm sin(wt f ) , then
Vm p
f ac sin(wt f - )
wN 2 2
The peak value of ac flux is given by
49
Vm
f acmax
wN 2
However Vm R2 I 0
max
R2 I 0max
Hence facmax
wN 2
and peak value of the total flux is given by
Vm LI 0max
facmax f dcmax
wN 2 N2
In practice, if this flux exceeds the knee-point flux in the core (see fig.), then the CT core
will saturate.
As a consequence of CT core saturation, the secondary current would not faithfully replicate
the primary current. Infact, in practice it is observed that CT secondary current is clipped. The
clipping of CT current leads to “blinding” of the relay which cannot function further. Hence,
CT saturation in presence of dc offset current is a serious problem which relay designers have
to face. Note that dc flux accumulates gradually. (Depends upon the transmission line time
constant ( t ). It is apparent that saturation should not occur immediately after the inception of
the fault. Thus, if the relay is fast enough in decision making, it is likely that a relaying
decision would be undertaken before the CT fully saturates. This is another important reason
for increasing the speed of relaying system. For bus-fault protection, where the dc saturation
due to dc offset current can be a significant contributing factor, quarter cycle operations *****
50
specifically are imposed. Similarly, a distance relay is expected to operate within ½-1 cycle
time.
CT oversizing factors
Typically, an efficient design of transformer would correspond to choosing the core cross
section such that f mac should be near the knee point of B-H curve. One obvious way of
avoiding the CT saturation on dc flux is to oversize the core so that for flux (f acmax f dcmax ) , the
(f acmax f dcmax )
corresponding B is below the knee-point. Hence, the factor is called core-
f acmax
oversizing factor.
f dcmax
Core-oversizing factor = 1
f acmax
LI o N 2
1
RI 0 wN 2
wL
1
R
X
1
R
Note that X/R in above equation is the transmission line X/R ratio. For a 220KV line X/R 10.
This would imply that transformer core should be oversized by a factor of 11. For a 400KV
line, typical value of X/R 20. This would imply an oversizing required of about 21 times the
usual design. Clearly this high amount of oversizing is not practical. Thus, the important
conclusion is that, protection engineers have to live with the saturation problem.
Cautions in CT selection:
While choosing a CT for a particular application, it is necessary to observe following
precautions.
9. The CT rating and continuous load current should match. For example, if max load
current is 90A, a 100:5 Ct may be acceptable but 50:5 is not acceptable.
51
10. The maximum fault current should be less than 20 times the CT rated current. for
example 100:5 CT can be used, so long as burden on the CT & maximum primary fault
current is below 2000A.
11. The voltage rating of CT should be compatible. For example, 100:5 C100 would give
linear response, upto 20 times rated current provided CT burden is kept
below(100/20*5=1 Ω). With 2 Ω burden, this CT can be used only if maximum current
is limited to 1000A.
12. Parallel of CT’s e.g. in differential protection, or with SLG fault can create significant
errors in CT performance. One should in general ascertain that magnetizing current is
kept much below the pick up value.
Following example, illustrates this point
Exercise problems:
If the current ratio is adequate for a protection, but CT burden is high; then the
performance of CT may deteriorate due to large magnetizing current and/or saturation problem.
The CT performance can be improved by connecting the CT’s in series.
7) Electromechanical relays tend to saturate at high currents. This reduces the relay burden
on CT, and so that the CT performance at moderately high currents may be considered
better than at relay’s rated burden at 5A.
8) Use of instantaneous over current relays has the potential to overcome this problem of
saturation of CT’s
52
9) Differential protection can operate on external faults due to the un equal saturation of
CT’s
Lecture-6
Examples
8. If a 300:5 class C CT is connected to a meter with resistance R I 1 and
secondary current in the CT is 4.5A find out the primary current voltage
developed across the meter and % rate error. Lead wire resistance R L 0.02
secondary resistance RS of a 300/5 CT 0.15
Diagram
R I 1 , R L 0.02 RS 0.15 I S 4.5 A
Total secondary resistance RT R I R L RS
1.17
Secondary voltage I S RT
4.5 1.17
5.265V
From Fig 5.7,
Exciting current IE for 5.265V
= 0.03A
Turns ratio N = 300/5 = 60
I p N (I S I E )
= 60(4.5 + 0.03)
= 271.8A
Voltage across meter I S R I
4.5 1 = 4.5V
IE 0.03
Ratio error 100 100
IS 4.5
= 0.67%
Rb
53
Lecture – 8
Examples
5. Design a CCVT for a 132kV transmission line using the following data.
Resistive Burden (3f )-150VA
Df 3Hz , phase angle error b = 40 min
Consider 4 choices of V2 as 33kV, 11kV, 6.6kV and 3.3kV
Diagram 1 Diagram 2
Transmission line voltage V = 132kV. Suppose V 2 (P_N) be the voltage to be
produced by the capacitive potential divider with capacitance values C1 and C2
and L the value of tuning inductor. The standardized VT secondary voltage is 110
volts (L-L).
Here specification for phase angle error b is 40 minutes variation in frequency
can be upto Df 3Hz . Phase angle error for change in w by Dw in the above
equation circuit, is given by
1
( L 2 )Dw
w C
1
At tuning frequency w 2
LC
Substituting w 1 LC
2
747.2 H
1 1
C1 C 2
w 2 L (3/ 4) 2 747.2
1.3610 -2 F
3) V2 6.6kV
3 �(6.6 �103 )2
Rb
'
150
87.1210 4
b �Rb' 0.01164 �87.12 �104
L
2 �Dw 2 �2p �3
269H ,
C1 C 2 3.7710 -2 F
4) V2 3.3kV
3 �(3.3 �103 ) 2
Rb'
150
21.7810 4
b �Rb' 0.01164 �21.78 �104
L
2 �Dw 2 �2p �3
67.25 H
C1 C2 0.151 F
The values of L, C1 C 2 for different values of V2 are tabulated below.
V2 L C1 C 2
33kV 6722.2H 0.00151 F
11kV 747.2H 0.0136 F
6.6kV 269H 0.0377 F
3.3kV 67.25H 0.151 F
From the above table it is clear that smaller the value of V 2, the smaller is the
value of L and higher the value of C 1 and C2 for tuning condition. If we select too low
value of V2 and L then capacitance values will be beyond available limits, and if we
select higher value of V2 and L, then CCVT and inductor will become bulky. So a
compromise is necessary and let us select V2 = 6.6kV
For V2 = 6.6kV
L = 269H
C1 C 2 0.0377 F
V C1 C 2
Now,
V2 C1
13210 3 0.037710 -6
36.610 3
C1
0.0377 36.610 3 10 -6 F
C1
13210 3
0.0033F
55
C 2 0.0344F
In this design, we explained the basic concept for CCVT design and we assumed
the transformer to be ideal. But in actual design practice the value of magnetizing
impedance of transformer, resistance of reactor etc have to be taken into account,
as ratio error a and phase angle error b will also get affected by these values.
6. Diagram
The equivalent circuit of a CCVT is shown in fig 8.3. The values of C 1 and C2 are
0.0018 F and 0.018 F respectively. Tuning inductor has an inductance of
497H and resistance of 4620 .
Xm of the 6.6kV VT is 1M , core loss = 20 watts per phase, VA burden =
150VA per phase. Value of Cm for compensating the current drawn by m is equal
to 3.18310 -9 F .
(g) Verify the appropriateness of choice of L and Cm.
Ans: If C1 0.0018F and C 2 0.0186F then the value L of tuning inductor
is given by
1
L 2
w (C1 C 2 )
where w 2p f and f = tuning frequency
1
L
(2p �50) (0.0018 0.0186) �10-6
2
1
Xm
w Cm
1 1
Cm
w X m (2p �50) �� 1 106
3.183 �10-9 F
The value is also same as the selected value of Cm Hence the selection of both L
and Cm is appropriate.
(i) If the frequency drops from 50Hz to 47Hz, what would be the values of ratio
error and phase angle error?
Ans: Core loss = 20w
V22
20W
Rm
56
V22 (6600) 2
Rm
20 20
2.18 �10
6
6600 0
A
260874.14 -2.44�
VT I th �Z
6600 0
�256147.5 1.82�
260874.14 -2.44�
6480.42 4.26�
(6600 - 6480.42)
Hence % ratio error �100
6600
=1.81%
Phase angle error = 4.26�
V2 6.6kV
r a w2 a 2
M
d 2i R di 1 1 R
t �t0 2
i0 wn 2p �50 2 Iwn
dt L dt LCeq LC L
d 2i
2
2a wn wn2i 0 a < 1
dt
Lec – 8
1
2p �50 2zw R d i 2zw w 2i 0 z wn z < 1
2
wn
LCeq n
L dt 2 n n
-t V
t I 0 - m sin(wt0 f - q ) f q
e | Z line |
58
Example 1:
d
59
Answer:
Based on the criteria that the CT can deliver 20 times rated secondary current
without exceeding a 10% ratio error, the maximum fault current will be 24000A.
However, with a 2.0Ω burden, this will result in a voltage below the knee point of the CT
and, as a practical matter, it will be within 10% accuracy at higher currents. This can only
be accurately determined from excitation or ratio correction curves and not from the
accuracy classification. For example, a CT with characteristics shown in above figure
will produce between 180-240A without exceeding the 10% ratio error, depending on the
power factor of the 2.0Ω burden.
Example 2:
A 1200/5, C400 CT is connected on the 1000/5 tap. What is the maximum secondary
burden that can be used and still maintain rated accuracy at 20 times rated symmetrical
secondary current?
Answer:
Since the secondary voltage capability is directly proportional to the connected tap, the
CT will support a voltage of 1000/1200 400V or 333V. Twenty times the rated
secondary current is 100A. Therefore, the maximum burden is 333V/100A or 3.33 Ω
Example 3:
Assume that secondary burden in a relay circuit is 5Ω. The relay setting is 2A and the CT
ratio is 300/5. Using above figure, calculate the primary current required to operate the
relay?
Answer:
60
N (I E I S )
= 300/5(0.04+2) A=122A
Example 4:
A relay is expected to operate for a 7000A primary current. The CT ratio is 600/5.
Secondary burden is 3.5 Ω. What is the error for the CT shown in above figure?
Answer:
The total secondary fault current is (7000/600) 5=58A. Assume that exciting current is
negligible.
VS I S ( R B RS )
= 58(3.5+0.31)
= 221V
The exciting current will not be negligible, however, and the calculation will not be
iterated.
Lec – 7
N1 RI 0 Vm N1 R Vm Vm N1 N1 RI 0 -tt N1 I 0 -tt
fdcmax t t N1 Rt v2 (t )
dc
e i2 e
N 22 | Z line | N 22 | Z line | | Z line | N 22 N2 N2
t -t -t
1 N1 RI 0 t N1 RI 0
f (t ) - f (0) t (1 - e ) f (t ) f (0) t (1 - e t )
N2 �
v2 dt 2 2
0
N 2 N 2
Lec- 7
61
Vm N1 d V2
v2ac (t ) R sin(wt f - q ) jw f ac
| Z line | N 2 dt jw N 2
RVm N1 p RVm N1
fac (t ) sin(wt f - q - ) facmax
w | Z line | N 2
2
2 w | Z line | N 22
Vm N1
Rt
RVm N1 N1 RVmt | Z line | N 22 wL X
facmax fdcmax 2 1 1 wt 1 line 1 line
w | Z line | N 2 N 2 | Z line |
2
Vm N1 R Rline Rline
| Z line | N 2 w
2
X
1
R
Lec-6
Lec – 5
Ip Ip
- IS Ip IE - IS
N - I I �100 N 98�45�
�100 N S E
IS �100
IS IS
Lec - 9
Vth - VT 1 1
�100 )Dw w02
(3f ) ( L w02 1 LC < f Df �3Hz
Vth w02
LC
1t di dv di 1 d 2i
v(t ) Ri �
Ceq
-�
idt L
dt dt
R
dt Ceq
i L 2 w0
dt
d 1 1 1
DVL - DVC jI (w L - ) Dw I (2 2 )Dw w02 I ( L L )Dw
dw wCeq w0 Ceq LCeq
62
| VL - VC | 2 LI Dw 2 LI 2 LDw
j 2 LI Dw (DVL - DVC ) tan b 2 2 2 � 2p f Lm 106
| VR | a Rb I a Rb a Rb
106
Lm 3183.1H
2p
source. The fault strikes at time t t 0 . This can be simulated by closing the switch at t t1
63
R jwL or Z q models the line impedance. The fault current in the line is given by
i (t ) 0 0 t t0
t -t 0
V sin(w t f - q ) -
t
t t0
i (t ) m I 0e
|Z |
Where τ is the time constant of the line τ =L/R. The fault current has two components in
it. The first component models the steady state sinusoidal ac response while the second current
is the dc offset current due to the presence of inductive component in the circuit. Recall that
current in an inductance can not change instantaneously. As t ∞, the instantaneous dc
It is more or less obvious that, dc offset is not seen in the waveform after 5 time constants.
The value of I0 can be worked out by setting the current at t t o to zero.
This implies that
Vm
I0 - sin(wt 0 - q )
Z
64
Thus
t -t 0
Vm V -( )
i (t ) sin(wt f - q ) - m sin(wt f - q )e t
Z Z
fig.2
It can be seen that severity of dc offset component in fault current is maximum when
a) f q
p
b) wt 0
2
65
p 1
For example, if angle of transmission line is 800, then with f = 800 & t 0 =
2 2p 50 200
V
sec = 5msec, the severity of dc offset current would equal I 0 Z , which is also the peak
m
We now plan to show that CT can saturate on dc offset current. Also, we plan to show
that the resulting distortions in the CT secondary current can be un-acceptably high. While
doing this analysis, we will neglect ac symmetrical component. In other words, we rest our
belief in superposition theorem atleast qualitatively and will finally evaluate effect using it
Notice that the current that we are dealing with is non-linear, a rigorous application of super
position theorem is simply out of question.
66
First consider an ideal CT excited by the dc offset current source. An ideal CT will faithfully
replicates primary current waveform on the secondary side. Hence, the secondary current
would be given by
-t
I0 t
i2 (t ) e
N
and the voltage developed across CT secondary would be given by
-t
RI N2
v 2 (t ) 0 e t where N N
N 1
For simplicity, let us assume that the initial flux in the transformer core at t=0 is zero
f ( 0 ) 0 ; Then we can compute the flux in the transformer core by using faraday’s law
df
V2 N 2 ---------(2)
dt
67
t
f (t ) - f (0) v 0
2 dt
RI 0
-t
t 1- e t
N2
-t
LI 0
(1 - e t )
N2
-t
LI 0
f (t ) f (0) (1 - e t )
N2
-t
LI 0
(1 - e t ) ------- (3)
N2
as a consequence of dc offset current,
Thus, flux in the core increases exponentially to a peak value of
f dmax
c
LI 0
N2
as t
L Vm Vm
N Z Z
f dmax
c
Note that unlike ac voltage induced flux, which is sinusoidal, this flux is unidirectional. The ac
voltage induced flux has zero average value. However, dc offset induced does not have this
nice feature. The total flux in ideal CT core is a summation of ac flux and dc flux.
d
The ac flux in the CT core can be obtained by substituting operator by jw . Hence
dt
If v2 (t ) Vm sin(wt f ) , then
Vm p
f ac sin(wt f - )
wN 2 2
The peak value of ac flux is given by
68
Vm
f acmax
wN 2
However Vm R2 I 0
max
R2 I 0max
Hence facmax
wN 2
and peak value of the total flux is given by
Vm LI 0max
facmax f dcmax
wN 2 N2
In practice, if this flux exceeds the knee-point flux in the core (see fig.), then the CT core
will saturate.
As a consequence of CT core saturation, the secondary current would not faithfully replicate
the primary current. Infact, in practice it is observed that CT secondary current is clipped. The
clipping of CT current leads to “blinding” of the relay which cannot function further. Hence,
CT saturation in presence of dc offset current is a serious problem which relay designers have
to face. Note that dc flux accumulates gradually. (Depends upon the transmission line time
constant ( t ). It is apparent that saturation should not occur immediately after the inception of
the fault. Thus, if the relay is fast enough in decision making, it is likely that a relaying
decision would be undertaken before the CT fully saturates. This is another important reason
for increasing the speed of relaying system. For bus-fault protection, where the dc saturation
due to dc offset current can be a significant contributing factor, quarter cycle operations *****
69
specifically are imposed. Similarly, a distance relay is expected to operate within ½-1 cycle
time.
CT oversizing factors
Typically, an efficient design of transformer would correspond to choosing the core cross
section such that f mac should be near the knee point of B-H curve. One obvious way of
avoiding the CT saturation on dc flux is to oversize the core so that for flux (f acmax f dcmax ) , the
(f acmax f dcmax )
corresponding B is below the knee-point. Hence, the factor is called core-
f acmax
oversizing factor.
f dcmax
Core-oversizing factor = 1
f acmax
LI o N 2
1
RI 0 wN 2
wL
1
R
X
1
R
Note that X/R in above equation is the transmission line X/R ratio. For a 220KV line X/R 10.
This would imply that transformer core should be oversized by a factor of 11. For a 400KV
line, typical value of X/R 20. This would imply an oversizing required of about 21 times the
usual design. Clearly this high amount of oversizing is not practical. Thus, the important
conclusion is that, protection engineers have to live with the saturation problem.
Cautions in CT selection:
While choosing a CT for a particular application, it is necessary to observe following
precautions.
13. The CT rating and continuous load current should match. For example, if max load
current is 90A, a 100:5 Ct may be acceptable but 50:5 is not acceptable.
70
14. The maximum fault current should be less than 20 times the CT rated current. for
example 100:5 CT can be used, so long as burden on the CT & maximum primary fault
current is below 2000A.
15. The voltage rating of CT should be compatible. For example, 100:5 C100 would give
linear response, upto 20 times rated current provided CT burden is kept
below(100/20*5=1 Ω). With 2 Ω burden, this CT can be used only if maximum current
is limited to 1000A.
16. Parallel of CT’s e.g. in differential protection, or with SLG fault can create significant
errors in CT performance. One should in general ascertain that magnetizing current is
kept much below the pick up value.
Following example, illustrates this point
Exercise problems:
If the current ratio is adequate for a protection, but CT burden is high; then the
performance of CT may deteriorate due to large magnetizing current and/or saturation problem.
The CT performance can be improved by connecting the CT’s in series.
10) Electromechanical relays tend to saturate at high currents. This reduces the relay burden
on CT, and so that the CT performance at moderately high currents may be considered
better than at relay’s rated burden at 5A.
11) Use of instantaneous over current relays has the potential to overcome this problem of
saturation of CT’s
71
12) Differential protection can operate on external faults due to the un equal saturation of
CT’s
Lecture-6
Examples
9. If a 300:5 class C CT is connected to a meter with resistance R I 1 and
secondary current in the CT is 4.5A find out the primary current voltage
developed across the meter and % rate error. Lead wire resistance R L 0.02
secondary resistance RS of a 300/5 CT 0.15
Diagram
R I 1 , R L 0.02 RS 0.15 I S 4.5 A
Total secondary resistance RT R I R L RS
1.17
Secondary voltage I S RT
4.5 1.17
5.265V
From Fig 5.7,
Exciting current IE for 5.265V
= 0.03A
Turns ratio N = 300/5 = 60
I p N (I S I E )
= 60(4.5 + 0.03)
= 271.8A
Voltage across meter I S R I
4.5 1 = 4.5V
IE 0.03
Ratio error 100 100
IS 4.5
= 0.67%
Rb
72
Lecture – 8
Examples
7. Design a CCVT for a 132kV transmission line using the following data.
Resistive Burden (3f )-150VA
Df 3Hz , phase angle error b = 40 min
Consider 4 choices of V2 as 33kV, 11kV, 6.6kV and 3.3kV
Diagram 1 Diagram 2
Transmission line voltage V = 132kV. Suppose V 2 (P_N) be the voltage to be
produced by the capacitive potential divider with capacitance values C1 and C2
and L the value of tuning inductor. The standardized VT secondary voltage is 110
volts (L-L).
Here specification for phase angle error b is 40 minutes variation in frequency
can be upto Df 3Hz . Phase angle error for change in w by Dw in the above
equation circuit, is given by
1
( L 2 )Dw
w C
1
At tuning frequency w 2
LC
Substituting w 1 LC
2
747.2 H
1 1
C1 C 2
w 2 L (3/ 4) 2 747.2
1.3610 -2 F
3) V2 6.6kV
3 �(6.6 �103 )2
Rb
'
150
87.1210 4
b �Rb' 0.01164 �87.12 �104
L
2 �Dw 2 �2p �3
269H ,
C1 C 2 3.7710 -2 F
4) V2 3.3kV
3 �(3.3 �103 ) 2
Rb'
150
21.7810 4
b �Rb' 0.01164 �21.78 �104
L
2 �Dw 2 �2p �3
67.25 H
C1 C2 0.151 F
The values of L, C1 C 2 for different values of V2 are tabulated below.
V2 L C1 C 2
33kV 6722.2H 0.00151 F
11kV 747.2H 0.0136 F
6.6kV 269H 0.0377 F
3.3kV 67.25H 0.151 F
From the above table it is clear that smaller the value of V 2, the smaller is the
value of L and higher the value of C 1 and C2 for tuning condition. If we select too low
value of V2 and L then capacitance values will be beyond available limits, and if we
select higher value of V2 and L, then CCVT and inductor will become bulky. So a
compromise is necessary and let us select V2 = 6.6kV
For V2 = 6.6kV
L = 269H
C1 C 2 0.0377 F
V C1 C 2
Now,
V2 C1
13210 3 0.037710 -6
36.610 3
C1
0.0377 36.610 3 10 -6 F
C1
13210 3
0.0033F
74
C 2 0.0344F
In this design, we explained the basic concept for CCVT design and we assumed
the transformer to be ideal. But in actual design practice the value of magnetizing
impedance of transformer, resistance of reactor etc have to be taken into account,
as ratio error a and phase angle error b will also get affected by these values.
8. Diagram
The equivalent circuit of a CCVT is shown in fig 8.3. The values of C 1 and C2 are
0.0018 F and 0.018 F respectively. Tuning inductor has an inductance of
497H and resistance of 4620 .
Xm of the 6.6kV VT is 1M , core loss = 20 watts per phase, VA burden =
150VA per phase. Value of Cm for compensating the current drawn by m is equal
to 3.18310 -9 F .
(j) Verify the appropriateness of choice of L and Cm.
Ans: If C1 0.0018F and C 2 0.0186F then the value L of tuning inductor
is given by
1
L 2
w (C1 C 2 )
where w 2p f and f = tuning frequency
1
L
(2p �50) (0.0018 0.0186) �10-6
2
1
Xm
w Cm
1 1
Cm
w X m (2p �50) �� 1 106
3.183 �10-9 F
The value is also same as the selected value of Cm Hence the selection of both L
and Cm is appropriate.
(l) If the frequency drops from 50Hz to 47Hz, what would be the values of ratio
error and phase angle error?
Ans: Core loss = 20w
V22
20W
Rm
75
V22 (6600) 2
Rm
20 20
2.18 �10
6
6600 0
A
260874.14 -2.44�
VT I th �Z
6600 0
�256147.5 1.82�
260874.14 -2.44�
6480.42 4.26�
(6600 - 6480.42)
Hence % ratio error �100
6600
=1.81%
Phase angle error = 4.26�
V2 6.6kV
r a w2 a 2
M
d 2i R di 1 1 R
t �t0 2
i0 wn 2p �50 2 Iwn
dt L dt LCeq LC L
d 2i
2
2a wn wn2i 0 a < 1
dt
Lec – 8
1
2p �50 2zw R d i 2zw w 2i 0 z wn z < 1
2
wn
LCeq n
L dt 2 n n
-t V
t I 0 - m sin(wt0 f - q ) f q
e | Z line |
77
Example 1:
d
78
Answer:
Based on the criteria that the CT can deliver 20 times rated secondary current
without exceeding a 10% ratio error, the maximum fault current will be 24000A.
However, with a 2.0Ω burden, this will result in a voltage below the knee point of the CT
and, as a practical matter, it will be within 10% accuracy at higher currents. This can only
be accurately determined from excitation or ratio correction curves and not from the
accuracy classification. For example, a CT with characteristics shown in above figure
will produce between 180-240A without exceeding the 10% ratio error, depending on the
power factor of the 2.0Ω burden.
Example 2:
A 1200/5, C400 CT is connected on the 1000/5 tap. What is the maximum secondary
burden that can be used and still maintain rated accuracy at 20 times rated symmetrical
secondary current?
Answer:
Since the secondary voltage capability is directly proportional to the connected tap, the
CT will support a voltage of 1000/1200 400V or 333V. Twenty times the rated
secondary current is 100A. Therefore, the maximum burden is 333V/100A or 3.33 Ω
Example 3:
Assume that secondary burden in a relay circuit is 5Ω. The relay setting is 2A and the CT
ratio is 300/5. Using above figure, calculate the primary current required to operate the
relay?
Answer:
79
N (I E I S )
= 300/5(0.04+2) A=122A
Example 4:
A relay is expected to operate for a 7000A primary current. The CT ratio is 600/5.
Secondary burden is 3.5 Ω. What is the error for the CT shown in above figure?
Answer:
The total secondary fault current is (7000/600) 5=58A. Assume that exciting current is
negligible.
VS I S ( R B RS )
= 58(3.5+0.31)
= 221V
The exciting current will not be negligible, however, and the calculation will not be
iterated.
Lec – 7
N1 RI 0 Vm N1 R Vm Vm N1 N1 RI 0 -tt N1 I 0 -tt
fdcmax t t N1 Rt v2 (t )
dc
e i2 e
N 22 | Z line | N 22 | Z line | | Z line | N 22 N2 N2
t -t -t
1 N1 RI 0 t N1 RI 0
f (t ) - f (0) t (1 - e ) f (t ) f (0) t (1 - e t )
N2 �
v2 dt 2 2
0
N 2 N 2
Lec- 7
80
Vm N1 d V2
v2ac (t ) R sin(wt f - q ) jw f ac
| Z line | N 2 dt jw N 2
RVm N1 p RVm N1
fac (t ) sin(wt f - q - ) facmax
w | Z line | N 2
2
2 w | Z line | N 22
Vm N1
Rt
RVm N1 N1 RVmt | Z line | N 22 wL X
facmax fdcmax 2 1 1 wt 1 line 1 line
w | Z line | N 2 N 2 | Z line |
2
Vm N1 R Rline Rline
| Z line | N 2 w
2
X
1
R
Lec-6
Lec – 5
Ip Ip
- IS Ip IE - IS
N - I I �100 N 98�45�
�100 N S E
IS �100
IS IS
Lec - 9
Vth - VT 1 1
�100 )Dw w02
(3f ) ( L w02 1 LC < f Df �3Hz
Vth w02
LC
1t di dv di 1 d 2i
v(t ) Ri �
Ceq
-�
idt L
dt dt
R
dt Ceq
i L 2 w0
dt
d 1 1 1
DVL - DVC jI (w L - ) Dw I (2 2 )Dw w02 I ( L L )Dw
dw wCeq w0 Ceq LCeq
81
| VL - VC | 2 LI Dw 2 LI 2 LDw
j 2 LI Dw (DVL - DVC ) tan b 2 2 2 � 2p f Lm 106
| VR | a Rb I a Rb a Rb
106
Lm 3183.1H
2p
source. The fault strikes at time t t 0 . This can be simulated by closing the switch at t t1
82
R jwL or Z q models the line impedance. The fault current in the line is given by
i (t ) 0 0 t t0
t -t 0
V sin(w t f - q ) -
t
t t0
i (t ) m I 0e
|Z |
Where τ is the time constant of the line τ =L/R. The fault current has two components in
it. The first component models the steady state sinusoidal ac response while the second current
is the dc offset current due to the presence of inductive component in the circuit. Recall that
current in an inductance can not change instantaneously. As t ∞, the instantaneous dc
It is more or less obvious that, dc offset is not seen in the waveform after 5 time constants.
The value of I0 can be worked out by setting the current at t t o to zero.
This implies that
Vm
I0 - sin(wt 0 - q )
Z
83
Thus
t -t 0
Vm V -( )
i (t ) sin(wt f - q ) - m sin(wt f - q )e t
Z Z
fig.2
It can be seen that severity of dc offset component in fault current is maximum when
a) f q
p
b) wt 0
2
84
p 1
For example, if angle of transmission line is 800, then with f = 800 & t 0 =
2 2p 50 200
V
sec = 5msec, the severity of dc offset current would equal I 0 Z , which is also the peak
m
We now plan to show that CT can saturate on dc offset current. Also, we plan to show
that the resulting distortions in the CT secondary current can be un-acceptably high. While
doing this analysis, we will neglect ac symmetrical component. In other words, we rest our
belief in superposition theorem atleast qualitatively and will finally evaluate effect using it
Notice that the current that we are dealing with is non-linear, a rigorous application of super
position theorem is simply out of question.
85
First consider an ideal CT excited by the dc offset current source. An ideal CT will faithfully
replicates primary current waveform on the secondary side. Hence, the secondary current
would be given by
-t
I0 t
i2 (t ) e
N
and the voltage developed across CT secondary would be given by
-t
RI N2
v 2 (t ) 0 e t where N N
N 1
For simplicity, let us assume that the initial flux in the transformer core at t=0 is zero
f ( 0 ) 0 ; Then we can compute the flux in the transformer core by using faraday’s law
df
V2 N 2 ---------(2)
dt
86
t
f (t ) - f (0) v 0
2 dt
RI 0
-t
t 1- e t
N2
-t
LI 0
(1 - e t )
N2
-t
LI 0
f (t ) f (0) (1 - e t )
N2
-t
LI 0
(1 - e t ) ------- (3)
N2
as a consequence of dc offset current,
Thus, flux in the core increases exponentially to a peak value of
f dmax
c
LI 0
N2
as t
L Vm Vm
N Z Z
f dmax
c
Note that unlike ac voltage induced flux, which is sinusoidal, this flux is unidirectional. The ac
voltage induced flux has zero average value. However, dc offset induced does not have this
nice feature. The total flux in ideal CT core is a summation of ac flux and dc flux.
d
The ac flux in the CT core can be obtained by substituting operator by jw . Hence
dt
If v2 (t ) Vm sin(wt f ) , then
Vm p
f ac sin(wt f - )
wN 2 2
The peak value of ac flux is given by
87
Vm
f acmax
wN 2
However Vm R2 I 0
max
R2 I 0max
Hence facmax
wN 2
and peak value of the total flux is given by
Vm LI 0max
facmax f dcmax
wN 2 N2
In practice, if this flux exceeds the knee-point flux in the core (see fig.), then the CT core
will saturate.
As a consequence of CT core saturation, the secondary current would not faithfully replicate
the primary current. Infact, in practice it is observed that CT secondary current is clipped. The
clipping of CT current leads to “blinding” of the relay which cannot function further. Hence,
CT saturation in presence of dc offset current is a serious problem which relay designers have
to face. Note that dc flux accumulates gradually. (Depends upon the transmission line time
constant ( t ). It is apparent that saturation should not occur immediately after the inception of
the fault. Thus, if the relay is fast enough in decision making, it is likely that a relaying
decision would be undertaken before the CT fully saturates. This is another important reason
for increasing the speed of relaying system. For bus-fault protection, where the dc saturation
due to dc offset current can be a significant contributing factor, quarter cycle operations *****
88
specifically are imposed. Similarly, a distance relay is expected to operate within ½-1 cycle
time.
CT oversizing factors
Typically, an efficient design of transformer would correspond to choosing the core cross
section such that f mac should be near the knee point of B-H curve. One obvious way of
avoiding the CT saturation on dc flux is to oversize the core so that for flux (f acmax f dcmax ) , the
(f acmax f dcmax )
corresponding B is below the knee-point. Hence, the factor is called core-
f acmax
oversizing factor.
f dcmax
Core-oversizing factor = 1
f acmax
LI o N 2
1
RI 0 wN 2
wL
1
R
X
1
R
Note that X/R in above equation is the transmission line X/R ratio. For a 220KV line X/R 10.
This would imply that transformer core should be oversized by a factor of 11. For a 400KV
line, typical value of X/R 20. This would imply an oversizing required of about 21 times the
usual design. Clearly this high amount of oversizing is not practical. Thus, the important
conclusion is that, protection engineers have to live with the saturation problem.
Cautions in CT selection:
While choosing a CT for a particular application, it is necessary to observe following
precautions.
17. The CT rating and continuous load current should match. For example, if max load
current is 90A, a 100:5 Ct may be acceptable but 50:5 is not acceptable.
89
18. The maximum fault current should be less than 20 times the CT rated current. for
example 100:5 CT can be used, so long as burden on the CT & maximum primary fault
current is below 2000A.
19. The voltage rating of CT should be compatible. For example, 100:5 C100 would give
linear response, upto 20 times rated current provided CT burden is kept
below(100/20*5=1 Ω). With 2 Ω burden, this CT can be used only if maximum current
is limited to 1000A.
20. Parallel of CT’s e.g. in differential protection, or with SLG fault can create significant
errors in CT performance. One should in general ascertain that magnetizing current is
kept much below the pick up value.
Following example, illustrates this point
Exercise problems:
If the current ratio is adequate for a protection, but CT burden is high; then the
performance of CT may deteriorate due to large magnetizing current and/or saturation problem.
The CT performance can be improved by connecting the CT’s in series.
13) Electromechanical relays tend to saturate at high currents. This reduces the relay burden
on CT, and so that the CT performance at moderately high currents may be considered
better than at relay’s rated burden at 5A.
14) Use of instantaneous over current relays has the potential to overcome this problem of
saturation of CT’s
90
15) Differential protection can operate on external faults due to the un equal saturation of
CT’s
Lecture-6
Examples
10. If a 300:5 class C CT is connected to a meter with resistance R I 1 and
secondary current in the CT is 4.5A find out the primary current voltage
developed across the meter and % rate error. Lead wire resistance R L 0.02
secondary resistance RS of a 300/5 CT 0.15
Diagram
R I 1 , R L 0.02 RS 0.15 I S 4.5 A
Total secondary resistance RT R I R L RS
1.17
Secondary voltage I S RT
4.5 1.17
5.265V
From Fig 5.7,
Exciting current IE for 5.265V
= 0.03A
Turns ratio N = 300/5 = 60
I p N (I S I E )
= 60(4.5 + 0.03)
= 271.8A
Voltage across meter I S R I
4.5 1 = 4.5V
IE 0.03
Ratio error 100 100
IS 4.5
= 0.67%
Rb
91
Lecture – 8
Examples
9. Design a CCVT for a 132kV transmission line using the following data.
Resistive Burden (3f )-150VA
Df 3Hz , phase angle error b = 40 min
Consider 4 choices of V2 as 33kV, 11kV, 6.6kV and 3.3kV
Diagram 1 Diagram 2
Transmission line voltage V = 132kV. Suppose V 2 (P_N) be the voltage to be
produced by the capacitive potential divider with capacitance values C1 and C2
and L the value of tuning inductor. The standardized VT secondary voltage is 110
volts (L-L).
Here specification for phase angle error b is 40 minutes variation in frequency
can be upto Df 3Hz . Phase angle error for change in w by Dw in the above
equation circuit, is given by
1
( L 2 )Dw
w C
1
At tuning frequency w 2
LC
Substituting w 1 LC
2
747.2 H
1 1
C1 C 2
w 2 L (3/ 4) 2 747.2
1.3610 -2 F
3) V2 6.6kV
3 �(6.6 �103 )2
Rb
'
150
87.1210 4
b �Rb' 0.01164 �87.12 �104
L
2 �Dw 2 �2p �3
269H ,
C1 C 2 3.7710 -2 F
4) V2 3.3kV
3 �(3.3 �103 ) 2
Rb'
150
21.7810 4
b �Rb' 0.01164 �21.78 �104
L
2 �Dw 2 �2p �3
67.25 H
C1 C2 0.151 F
The values of L, C1 C 2 for different values of V2 are tabulated below.
V2 L C1 C 2
33kV 6722.2H 0.00151 F
11kV 747.2H 0.0136 F
6.6kV 269H 0.0377 F
3.3kV 67.25H 0.151 F
From the above table it is clear that smaller the value of V 2, the smaller is the
value of L and higher the value of C 1 and C2 for tuning condition. If we select too low
value of V2 and L then capacitance values will be beyond available limits, and if we
select higher value of V2 and L, then CCVT and inductor will become bulky. So a
compromise is necessary and let us select V2 = 6.6kV
For V2 = 6.6kV
L = 269H
C1 C 2 0.0377 F
V C1 C 2
Now,
V2 C1
13210 3 0.037710 -6
36.610 3
C1
0.0377 36.610 3 10 -6 F
C1
13210 3
0.0033F
93
C 2 0.0344F
In this design, we explained the basic concept for CCVT design and we assumed
the transformer to be ideal. But in actual design practice the value of magnetizing
impedance of transformer, resistance of reactor etc have to be taken into account,
as ratio error a and phase angle error b will also get affected by these values.
10. Diagram
The equivalent circuit of a CCVT is shown in fig 8.3. The values of C 1 and C2 are
0.0018 F and 0.018 F respectively. Tuning inductor has an inductance of
497H and resistance of 4620 .
Xm of the 6.6kV VT is 1M , core loss = 20 watts per phase, VA burden =
150VA per phase. Value of Cm for compensating the current drawn by m is equal
to 3.18310 -9 F .
(m)Verify the appropriateness of choice of L and Cm.
Ans: If C1 0.0018F and C 2 0.0186F then the value L of tuning inductor
is given by
1
L 2
w (C1 C 2 )
where w 2p f and f = tuning frequency
1
L
(2p �50) (0.0018 0.0186) �10-6
2
1
Xm
w Cm
1 1
Cm
w X m (2p �50) �� 1 106
3.183 �10-9 F
The value is also same as the selected value of Cm Hence the selection of both L
and Cm is appropriate.
(o) If the frequency drops from 50Hz to 47Hz, what would be the values of ratio
error and phase angle error?
Ans: Core loss = 20w
V22
20W
Rm
94
V22 (6600) 2
Rm
20 20
2.18 �10
6
6600 0
A
260874.14 -2.44�
VT I th �Z
6600 0
�256147.5 1.82�
260874.14 -2.44�
6480.42 4.26�
(6600 - 6480.42)
Hence % ratio error �100
6600
=1.81%
Phase angle error = 4.26�
V2 6.6kV
r a w2 a 2
M
d 2i R di 1 1 R
t �t0 2
i0 wn 2p �50 2 Iwn
dt L dt LCeq LC L
d 2i
2
2a wn wn2i 0 a < 1
dt
Lec – 8
1
2p �50 2zw R d i 2zw w 2i 0 z wn z < 1
2
wn
LCeq n
L dt 2 n n
-t V
t I 0 - m sin(wt0 f - q ) f q
e | Z line |
96
Example 1:
d
97
Answer:
Based on the criteria that the CT can deliver 20 times rated secondary current
without exceeding a 10% ratio error, the maximum fault current will be 24000A.
However, with a 2.0Ω burden, this will result in a voltage below the knee point of the CT
and, as a practical matter, it will be within 10% accuracy at higher currents. This can only
be accurately determined from excitation or ratio correction curves and not from the
accuracy classification. For example, a CT with characteristics shown in above figure
will produce between 180-240A without exceeding the 10% ratio error, depending on the
power factor of the 2.0Ω burden.
Example 2:
A 1200/5, C400 CT is connected on the 1000/5 tap. What is the maximum secondary
burden that can be used and still maintain rated accuracy at 20 times rated symmetrical
secondary current?
Answer:
Since the secondary voltage capability is directly proportional to the connected tap, the
CT will support a voltage of 1000/1200 400V or 333V. Twenty times the rated
secondary current is 100A. Therefore, the maximum burden is 333V/100A or 3.33 Ω
Example 3:
Assume that secondary burden in a relay circuit is 5Ω. The relay setting is 2A and the CT
ratio is 300/5. Using above figure, calculate the primary current required to operate the
relay?
Answer:
98
N (I E I S )
= 300/5(0.04+2) A=122A
Example 4:
A relay is expected to operate for a 7000A primary current. The CT ratio is 600/5.
Secondary burden is 3.5 Ω. What is the error for the CT shown in above figure?
Answer:
The total secondary fault current is (7000/600) 5=58A. Assume that exciting current is
negligible.
VS I S ( R B RS )
= 58(3.5+0.31)
= 221V
The exciting current will not be negligible, however, and the calculation will not be
iterated.
Lec – 7
N1 RI 0 Vm N1 R Vm Vm N1 N1 RI 0 -tt N1 I 0 -tt
fdcmax t t N1 Rt v2 (t )
dc
e i2 e
N 22 | Z line | N 22 | Z line | | Z line | N 22 N2 N2
t -t -t
1 N1 RI 0 t N1 RI 0
f (t ) - f (0) t (1 - e ) f (t ) f (0) t (1 - e t )
N2 �
v2 dt 2 2
0
N 2 N 2
Lec- 7
99
Vm N1 d V2
v2ac (t ) R sin(wt f - q ) jw f ac
| Z line | N 2 dt jw N 2
RVm N1 p RVm N1
fac (t ) sin(wt f - q - ) facmax
w | Z line | N 2
2
2 w | Z line | N 22
Vm N1
Rt
RVm N1 N1 RVmt | Z line | N 22 wL X
facmax fdcmax 2 1 1 wt 1 line 1 line
w | Z line | N 2 N 2 | Z line |
2
Vm N1 R Rline Rline
| Z line | N 2 w
2
X
1
R
Lec-6
Lec – 5
Ip Ip
- IS Ip IE - IS
N - I I �100 N 98�45�
�100 N S E
IS �100
IS IS
Lec - 9
Vth - VT 1 1
�100 )Dw w02
(3f ) ( L w02 1 LC < f Df �3Hz
Vth w02
LC
1t di dv di 1 d 2i
v(t ) Ri �
Ceq
-�
idt L
dt dt
R
dt Ceq
i L 2 w0
dt
d 1 1 1
DVL - DVC jI (w L - ) Dw I (2 2 )Dw w02 I ( L L )Dw
dw wCeq w0 Ceq LCeq
100
| VL - VC | 2 LI Dw 2 LI 2 LDw
j 2 LI Dw (DVL - DVC ) tan b 2 2 2 � 2p f Lm 106
| VR | a Rb I a Rb a Rb
106
Lm 3183.1H
2p
source. The fault strikes at time t t 0 . This can be simulated by closing the switch at t t1
101
R jwL or Z q models the line impedance. The fault current in the line is given by
i (t ) 0 0 t t0
t -t 0
V sin(w t f - q ) -
t
t t0
i (t ) m I 0e
|Z |
Where τ is the time constant of the line τ =L/R. The fault current has two components in
it. The first component models the steady state sinusoidal ac response while the second current
is the dc offset current due to the presence of inductive component in the circuit. Recall that
current in an inductance can not change instantaneously. As t ∞, the instantaneous dc
It is more or less obvious that, dc offset is not seen in the waveform after 5 time constants.
The value of I0 can be worked out by setting the current at t t o to zero.
This implies that
Vm
I0 - sin(wt 0 - q )
Z
102
Thus
t -t 0
Vm V -( )
i (t ) sin(wt f - q ) - m sin(wt f - q )e t
Z Z
fig.2
It can be seen that severity of dc offset component in fault current is maximum when
a) f q
p
b) wt 0
2
103
p 1
For example, if angle of transmission line is 800, then with f = 800 & t 0 =
2 2p 50 200
V
sec = 5msec, the severity of dc offset current would equal I 0 Z , which is also the peak
m
We now plan to show that CT can saturate on dc offset current. Also, we plan to show
that the resulting distortions in the CT secondary current can be un-acceptably high. While
doing this analysis, we will neglect ac symmetrical component. In other words, we rest our
belief in superposition theorem atleast qualitatively and will finally evaluate effect using it
Notice that the current that we are dealing with is non-linear, a rigorous application of super
position theorem is simply out of question.
104
First consider an ideal CT excited by the dc offset current source. An ideal CT will faithfully
replicates primary current waveform on the secondary side. Hence, the secondary current
would be given by
-t
I0 t
i2 (t ) e
N
and the voltage developed across CT secondary would be given by
-t
RI N2
v 2 (t ) 0 e t where N N
N 1
For simplicity, let us assume that the initial flux in the transformer core at t=0 is zero
f ( 0 ) 0 ; Then we can compute the flux in the transformer core by using faraday’s law
df
V2 N 2 ---------(2)
dt
105
t
f (t ) - f (0) v 0
2 dt
RI 0
-t
t 1- e t
N2
-t
LI 0
(1 - e t )
N2
-t
LI 0
f (t ) f (0) (1 - e t )
N2
-t
LI 0
(1 - e t ) ------- (3)
N2
as a consequence of dc offset current,
Thus, flux in the core increases exponentially to a peak value of
f dmax
c
LI 0
N2
as t
L Vm Vm
N Z Z
f dmax
c
Note that unlike ac voltage induced flux, which is sinusoidal, this flux is unidirectional. The ac
voltage induced flux has zero average value. However, dc offset induced does not have this
nice feature. The total flux in ideal CT core is a summation of ac flux and dc flux.
d
The ac flux in the CT core can be obtained by substituting operator by jw . Hence
dt
If v2 (t ) Vm sin(wt f ) , then
Vm p
f ac sin(wt f - )
wN 2 2
The peak value of ac flux is given by
106
Vm
f acmax
wN 2
However Vm R2 I 0
max
R2 I 0max
Hence facmax
wN 2
and peak value of the total flux is given by
Vm LI 0max
facmax f dcmax
wN 2 N2
In practice, if this flux exceeds the knee-point flux in the core (see fig.), then the CT core
will saturate.
As a consequence of CT core saturation, the secondary current would not faithfully replicate
the primary current. Infact, in practice it is observed that CT secondary current is clipped. The
clipping of CT current leads to “blinding” of the relay which cannot function further. Hence,
CT saturation in presence of dc offset current is a serious problem which relay designers have
to face. Note that dc flux accumulates gradually. (Depends upon the transmission line time
constant ( t ). It is apparent that saturation should not occur immediately after the inception of
the fault. Thus, if the relay is fast enough in decision making, it is likely that a relaying
decision would be undertaken before the CT fully saturates. This is another important reason
for increasing the speed of relaying system. For bus-fault protection, where the dc saturation
due to dc offset current can be a significant contributing factor, quarter cycle operations *****
107
specifically are imposed. Similarly, a distance relay is expected to operate within ½-1 cycle
time.
CT oversizing factors
Typically, an efficient design of transformer would correspond to choosing the core cross
section such that f mac should be near the knee point of B-H curve. One obvious way of
avoiding the CT saturation on dc flux is to oversize the core so that for flux (f acmax f dcmax ) , the
(f acmax f dcmax )
corresponding B is below the knee-point. Hence, the factor is called core-
f acmax
oversizing factor.
f dcmax
Core-oversizing factor = 1
f acmax
LI o N 2
1
RI 0 wN 2
wL
1
R
X
1
R
Note that X/R in above equation is the transmission line X/R ratio. For a 220KV line X/R 10.
This would imply that transformer core should be oversized by a factor of 11. For a 400KV
line, typical value of X/R 20. This would imply an oversizing required of about 21 times the
usual design. Clearly this high amount of oversizing is not practical. Thus, the important
conclusion is that, protection engineers have to live with the saturation problem.
Cautions in CT selection:
While choosing a CT for a particular application, it is necessary to observe following
precautions.
21. The CT rating and continuous load current should match. For example, if max load
current is 90A, a 100:5 Ct may be acceptable but 50:5 is not acceptable.
108
22. The maximum fault current should be less than 20 times the CT rated current. for
example 100:5 CT can be used, so long as burden on the CT & maximum primary fault
current is below 2000A.
23. The voltage rating of CT should be compatible. For example, 100:5 C100 would give
linear response, upto 20 times rated current provided CT burden is kept
below(100/20*5=1 Ω). With 2 Ω burden, this CT can be used only if maximum current
is limited to 1000A.
24. Parallel of CT’s e.g. in differential protection, or with SLG fault can create significant
errors in CT performance. One should in general ascertain that magnetizing current is
kept much below the pick up value.
Following example, illustrates this point
Exercise problems:
If the current ratio is adequate for a protection, but CT burden is high; then the
performance of CT may deteriorate due to large magnetizing current and/or saturation problem.
The CT performance can be improved by connecting the CT’s in series.
11) Show the dotted terminals for correct secondary series connection
12) What is the VA of CT in fig (a) & (b) respectively?
16) Electromechanical relays tend to saturate at high currents. This reduces the relay burden
on CT, and so that the CT performance at moderately high currents may be considered
better than at relay’s rated burden at 5A.
17) Use of instantaneous over current relays has the potential to overcome this problem of
saturation of CT’s
109
18) Differential protection can operate on external faults due to the un equal saturation of
CT’s
Lecture-6
Examples
11. If a 300:5 class C CT is connected to a meter with resistance R I 1 and
secondary current in the CT is 4.5A find out the primary current voltage
developed across the meter and % rate error. Lead wire resistance R L 0.02
secondary resistance RS of a 300/5 CT 0.15
Diagram
R I 1 , R L 0.02 RS 0.15 I S 4.5 A
Total secondary resistance RT R I R L RS
1.17
Secondary voltage I S RT
4.5 1.17
5.265V
From Fig 5.7,
Exciting current IE for 5.265V
= 0.03A
Turns ratio N = 300/5 = 60
I p N (I S I E )
= 60(4.5 + 0.03)
= 271.8A
Voltage across meter I S R I
4.5 1 = 4.5V
IE 0.03
Ratio error 100 100
IS 4.5
= 0.67%
Rb
110
Lecture – 8
Examples
11. Design a CCVT for a 132kV transmission line using the following data.
Resistive Burden (3f )-150VA
Df 3Hz , phase angle error b = 40 min
Consider 4 choices of V2 as 33kV, 11kV, 6.6kV and 3.3kV
Diagram 1 Diagram 2
Transmission line voltage V = 132kV. Suppose V 2 (P_N) be the voltage to be
produced by the capacitive potential divider with capacitance values C1 and C2
and L the value of tuning inductor. The standardized VT secondary voltage is 110
volts (L-L).
Here specification for phase angle error b is 40 minutes variation in frequency
can be upto Df 3Hz . Phase angle error for change in w by Dw in the above
equation circuit, is given by
1
( L 2 )Dw
w C
1
At tuning frequency w 2
LC
Substituting w 1 LC
2
747.2 H
1 1
C1 C 2
w 2 L (3/ 4) 2 747.2
1.3610 -2 F
3) V2 6.6kV
3 �(6.6 �103 )2
Rb
'
150
87.1210 4
b �Rb' 0.01164 �87.12 �104
L
2 �Dw 2 �2p �3
269H ,
C1 C 2 3.7710 -2 F
4) V2 3.3kV
3 �(3.3 �103 ) 2
Rb'
150
21.7810 4
b �Rb' 0.01164 �21.78 �104
L
2 �Dw 2 �2p �3
67.25 H
C1 C2 0.151 F
The values of L, C1 C 2 for different values of V2 are tabulated below.
V2 L C1 C 2
33kV 6722.2H 0.00151 F
11kV 747.2H 0.0136 F
6.6kV 269H 0.0377 F
3.3kV 67.25H 0.151 F
From the above table it is clear that smaller the value of V 2, the smaller is the
value of L and higher the value of C 1 and C2 for tuning condition. If we select too low
value of V2 and L then capacitance values will be beyond available limits, and if we
select higher value of V2 and L, then CCVT and inductor will become bulky. So a
compromise is necessary and let us select V2 = 6.6kV
For V2 = 6.6kV
L = 269H
C1 C 2 0.0377 F
V C1 C 2
Now,
V2 C1
13210 3 0.037710 -6
36.610 3
C1
0.0377 36.610 3 10 -6 F
C1
13210 3
0.0033F
112
C 2 0.0344F
In this design, we explained the basic concept for CCVT design and we assumed
the transformer to be ideal. But in actual design practice the value of magnetizing
impedance of transformer, resistance of reactor etc have to be taken into account,
as ratio error a and phase angle error b will also get affected by these values.
12. Diagram
The equivalent circuit of a CCVT is shown in fig 8.3. The values of C 1 and C2 are
0.0018 F and 0.018 F respectively. Tuning inductor has an inductance of
497H and resistance of 4620 .
Xm of the 6.6kV VT is 1M , core loss = 20 watts per phase, VA burden =
150VA per phase. Value of Cm for compensating the current drawn by m is equal
to 3.18310 -9 F .
(p) Verify the appropriateness of choice of L and Cm.
Ans: If C1 0.0018F and C 2 0.0186F then the value L of tuning inductor
is given by
1
L 2
w (C1 C 2 )
where w 2p f and f = tuning frequency
1
L
(2p �50) (0.0018 0.0186) �10-6
2
1
Xm
w Cm
1 1
Cm
w X m (2p �50) �� 1 106
3.183 �10-9 F
The value is also same as the selected value of Cm Hence the selection of both L
and Cm is appropriate.
(r) If the frequency drops from 50Hz to 47Hz, what would be the values of ratio
error and phase angle error?
Ans: Core loss = 20w
V22
20W
Rm
113
V22 (6600) 2
Rm
20 20
2.18 �10
6
6600 0
A
260874.14 -2.44�
VT I th �Z
6600 0
�256147.5 1.82�
260874.14 -2.44�
6480.42 4.26�
(6600 - 6480.42)
Hence % ratio error �100
6600
=1.81%
Phase angle error = 4.26�
V2 6.6kV
r a w2 a 2
M
d 2i R di 1 1 R
t �t0 2
i0 wn 2p �50 2 Iwn
dt L dt LCeq LC L
d 2i
2
2a wn wn2i 0 a < 1
dt
Lec – 8
1
2p �50 2zw R d i 2zw w 2i 0 z wn z < 1
2
wn
LCeq n
L dt 2 n n
-t V
t I 0 - m sin(wt0 f - q ) f q
e | Z line |
115
Example 1:
d
116
Answer:
Based on the criteria that the CT can deliver 20 times rated secondary current
without exceeding a 10% ratio error, the maximum fault current will be 24000A.
However, with a 2.0Ω burden, this will result in a voltage below the knee point of the CT
and, as a practical matter, it will be within 10% accuracy at higher currents. This can only
be accurately determined from excitation or ratio correction curves and not from the
accuracy classification. For example, a CT with characteristics shown in above figure
will produce between 180-240A without exceeding the 10% ratio error, depending on the
power factor of the 2.0Ω burden.
Example 2:
A 1200/5, C400 CT is connected on the 1000/5 tap. What is the maximum secondary
burden that can be used and still maintain rated accuracy at 20 times rated symmetrical
secondary current?
Answer:
Since the secondary voltage capability is directly proportional to the connected tap, the
CT will support a voltage of 1000/1200 400V or 333V. Twenty times the rated
secondary current is 100A. Therefore, the maximum burden is 333V/100A or 3.33 Ω
Example 3:
Assume that secondary burden in a relay circuit is 5Ω. The relay setting is 2A and the CT
ratio is 300/5. Using above figure, calculate the primary current required to operate the
relay?
Answer:
117
N (I E I S )
= 300/5(0.04+2) A=122A
Example 4:
A relay is expected to operate for a 7000A primary current. The CT ratio is 600/5.
Secondary burden is 3.5 Ω. What is the error for the CT shown in above figure?
Answer:
The total secondary fault current is (7000/600) 5=58A. Assume that exciting current is
negligible.
VS I S ( R B RS )
= 58(3.5+0.31)
= 221V
The exciting current will not be negligible, however, and the calculation will not be
iterated.
Lec – 7
N1 RI 0 Vm N1 R Vm Vm N1 N1 RI 0 -tt N1 I 0 -tt
fdcmax t t N1 Rt v2 (t )
dc
e i2 e
N 22 | Z line | N 22 | Z line | | Z line | N 22 N2 N2
t -t -t
1 N1 RI 0 t N1 RI 0
f (t ) - f (0) t (1 - e ) f (t ) f (0) t (1 - e t )
N2 �
v2 dt 2 2
0
N 2 N 2
Lec- 7
118
Vm N1 d V2
v2ac (t ) R sin(wt f - q ) jw f ac
| Z line | N 2 dt jw N 2
RVm N1 p RVm N1
fac (t ) sin(wt f - q - ) facmax
w | Z line | N 2
2
2 w | Z line | N 22
Vm N1
Rt
RVm N1 N1 RVmt | Z line | N 22 wL X
facmax fdcmax 2 1 1 wt 1 line 1 line
w | Z line | N 2 N 2 | Z line |
2
Vm N1 R Rline Rline
| Z line | N 2 w
2
X
1
R
Lec-6
Lec – 5
Ip Ip
- IS Ip IE - IS
N - I I �100 N 98�45�
�100 N S E
IS �100
IS IS
Lec - 9
Vth - VT 1 1
�100 )Dw w02
(3f ) ( L w02 1 LC < f Df �3Hz
Vth w02
LC
1t di dv di 1 d 2i
v(t ) Ri �
Ceq
-�
idt L
dt dt
R
dt Ceq
i L 2 w0
dt
d 1 1 1
DVL - DVC jI (w L - ) Dw I (2 2 )Dw w02 I ( L L )Dw
dw wCeq w0 Ceq LCeq
119
| VL - VC | 2 LI Dw 2 LI 2 LDw
j 2 LI Dw (DVL - DVC ) tan b 2 2 2 � 2p f Lm 106
| VR | a Rb I a Rb a Rb
106
Lm 3183.1H
2p
source. The fault strikes at time t t 0 . This can be simulated by closing the switch at t t1
120
R jwL or Z q models the line impedance. The fault current in the line is given by
i (t ) 0 0 t t0
t -t 0
V sin(w t f - q ) -
t
t t0
i (t ) m I 0e
|Z |
Where τ is the time constant of the line τ =L/R. The fault current has two components in
it. The first component models the steady state sinusoidal ac response while the second current
is the dc offset current due to the presence of inductive component in the circuit. Recall that
current in an inductance can not change instantaneously. As t ∞, the instantaneous dc
It is more or less obvious that, dc offset is not seen in the waveform after 5 time constants.
The value of I0 can be worked out by setting the current at t t o to zero.
This implies that
Vm
I0 - sin(wt 0 - q )
Z
121
Thus
t -t 0
Vm V -( )
i (t ) sin(wt f - q ) - m sin(wt f - q )e t
Z Z
fig.2
It can be seen that severity of dc offset component in fault current is maximum when
a) f q
p
b) wt 0
2
122
p 1
For example, if angle of transmission line is 800, then with f = 800 & t 0 =
2 2p 50 200
V
sec = 5msec, the severity of dc offset current would equal I 0 Z , which is also the peak
m
We now plan to show that CT can saturate on dc offset current. Also, we plan to show
that the resulting distortions in the CT secondary current can be un-acceptably high. While
doing this analysis, we will neglect ac symmetrical component. In other words, we rest our
belief in superposition theorem atleast qualitatively and will finally evaluate effect using it
Notice that the current that we are dealing with is non-linear, a rigorous application of super
position theorem is simply out of question.
123
First consider an ideal CT excited by the dc offset current source. An ideal CT will faithfully
replicates primary current waveform on the secondary side. Hence, the secondary current
would be given by
-t
I0 t
i2 (t ) e
N
and the voltage developed across CT secondary would be given by
-t
RI N2
v 2 (t ) 0 e t where N N
N 1
For simplicity, let us assume that the initial flux in the transformer core at t=0 is zero
f ( 0 ) 0 ; Then we can compute the flux in the transformer core by using faraday’s law
df
V2 N 2 ---------(2)
dt
124
t
f (t ) - f (0) v 0
2 dt
RI 0
-t
t 1- e t
N2
-t
LI 0
(1 - e t )
N2
-t
LI 0
f (t ) f (0) (1 - e t )
N2
-t
LI 0
(1 - e t ) ------- (3)
N2
as a consequence of dc offset current,
Thus, flux in the core increases exponentially to a peak value of
f dmax
c
LI 0
N2
as t
L Vm Vm
N Z Z
f dmax
c
Note that unlike ac voltage induced flux, which is sinusoidal, this flux is unidirectional. The ac
voltage induced flux has zero average value. However, dc offset induced does not have this
nice feature. The total flux in ideal CT core is a summation of ac flux and dc flux.
d
The ac flux in the CT core can be obtained by substituting operator by jw . Hence
dt
If v2 (t ) Vm sin(wt f ) , then
Vm p
f ac sin(wt f - )
wN 2 2
The peak value of ac flux is given by
125
Vm
f acmax
wN 2
However Vm R2 I 0
max
R2 I 0max
Hence facmax
wN 2
and peak value of the total flux is given by
Vm LI 0max
facmax f dcmax
wN 2 N2
In practice, if this flux exceeds the knee-point flux in the core (see fig.), then the CT core
will saturate.
As a consequence of CT core saturation, the secondary current would not faithfully replicate
the primary current. Infact, in practice it is observed that CT secondary current is clipped. The
clipping of CT current leads to “blinding” of the relay which cannot function further. Hence,
CT saturation in presence of dc offset current is a serious problem which relay designers have
to face. Note that dc flux accumulates gradually. (Depends upon the transmission line time
constant ( t ). It is apparent that saturation should not occur immediately after the inception of
the fault. Thus, if the relay is fast enough in decision making, it is likely that a relaying
decision would be undertaken before the CT fully saturates. This is another important reason
for increasing the speed of relaying system. For bus-fault protection, where the dc saturation
due to dc offset current can be a significant contributing factor, quarter cycle operations *****
126
specifically are imposed. Similarly, a distance relay is expected to operate within ½-1 cycle
time.
CT oversizing factors
Typically, an efficient design of transformer would correspond to choosing the core cross
section such that f mac should be near the knee point of B-H curve. One obvious way of
avoiding the CT saturation on dc flux is to oversize the core so that for flux (f acmax f dcmax ) , the
(f acmax f dcmax )
corresponding B is below the knee-point. Hence, the factor is called core-
f acmax
oversizing factor.
f dcmax
Core-oversizing factor = 1
f acmax
LI o N 2
1
RI 0 wN 2
wL
1
R
X
1
R
Note that X/R in above equation is the transmission line X/R ratio. For a 220KV line X/R 10.
This would imply that transformer core should be oversized by a factor of 11. For a 400KV
line, typical value of X/R 20. This would imply an oversizing required of about 21 times the
usual design. Clearly this high amount of oversizing is not practical. Thus, the important
conclusion is that, protection engineers have to live with the saturation problem.
Cautions in CT selection:
While choosing a CT for a particular application, it is necessary to observe following
precautions.
25. The CT rating and continuous load current should match. For example, if max load
current is 90A, a 100:5 Ct may be acceptable but 50:5 is not acceptable.
127
26. The maximum fault current should be less than 20 times the CT rated current. for
example 100:5 CT can be used, so long as burden on the CT & maximum primary fault
current is below 2000A.
27. The voltage rating of CT should be compatible. For example, 100:5 C100 would give
linear response, upto 20 times rated current provided CT burden is kept
below(100/20*5=1 Ω). With 2 Ω burden, this CT can be used only if maximum current
is limited to 1000A.
28. Parallel of CT’s e.g. in differential protection, or with SLG fault can create significant
errors in CT performance. One should in general ascertain that magnetizing current is
kept much below the pick up value.
Following example, illustrates this point
Exercise problems:
If the current ratio is adequate for a protection, but CT burden is high; then the
performance of CT may deteriorate due to large magnetizing current and/or saturation problem.
The CT performance can be improved by connecting the CT’s in series.
13) Show the dotted terminals for correct secondary series connection
14) What is the VA of CT in fig (a) & (b) respectively?
19) Electromechanical relays tend to saturate at high currents. This reduces the relay burden
on CT, and so that the CT performance at moderately high currents may be considered
better than at relay’s rated burden at 5A.
20) Use of instantaneous over current relays has the potential to overcome this problem of
saturation of CT’s
128
21) Differential protection can operate on external faults due to the un equal saturation of
CT’s
Lecture-6
Examples
12. If a 300:5 class C CT is connected to a meter with resistance R I 1 and
secondary current in the CT is 4.5A find out the primary current voltage
developed across the meter and % rate error. Lead wire resistance R L 0.02
secondary resistance RS of a 300/5 CT 0.15
Diagram
R I 1 , R L 0.02 RS 0.15 I S 4.5 A
Total secondary resistance RT R I R L RS
1.17
Secondary voltage I S RT
4.5 1.17
5.265V
From Fig 5.7,
Exciting current IE for 5.265V
= 0.03A
Turns ratio N = 300/5 = 60
I p N (I S I E )
= 60(4.5 + 0.03)
= 271.8A
Voltage across meter I S R I
4.5 1 = 4.5V
IE 0.03
Ratio error 100 100
IS 4.5
= 0.67%
Rb
129
Lecture – 8
Examples
13. Design a CCVT for a 132kV transmission line using the following data.
Resistive Burden (3f )-150VA
Df 3Hz , phase angle error b = 40 min
Consider 4 choices of V2 as 33kV, 11kV, 6.6kV and 3.3kV
Diagram 1 Diagram 2
Transmission line voltage V = 132kV. Suppose V 2 (P_N) be the voltage to be
produced by the capacitive potential divider with capacitance values C1 and C2
and L the value of tuning inductor. The standardized VT secondary voltage is 110
volts (L-L).
Here specification for phase angle error b is 40 minutes variation in frequency
can be upto Df 3Hz . Phase angle error for change in w by Dw in the above
equation circuit, is given by
1
( L 2 )Dw
w C
1
At tuning frequency w 2
LC
Substituting w 1 LC
2
747.2 H
1 1
C1 C 2
w 2 L (3/ 4) 2 747.2
1.3610 -2 F
3) V2 6.6kV
3 �(6.6 �103 )2
Rb
'
150
87.1210 4
b �Rb' 0.01164 �87.12 �104
L
2 �Dw 2 �2p �3
269H ,
C1 C 2 3.7710 -2 F
4) V2 3.3kV
3 �(3.3 �103 ) 2
Rb'
150
21.7810 4
b �Rb' 0.01164 �21.78 �104
L
2 �Dw 2 �2p �3
67.25 H
C1 C2 0.151 F
The values of L, C1 C 2 for different values of V2 are tabulated below.
V2 L C1 C 2
33kV 6722.2H 0.00151 F
11kV 747.2H 0.0136 F
6.6kV 269H 0.0377 F
3.3kV 67.25H 0.151 F
From the above table it is clear that smaller the value of V 2, the smaller is the
value of L and higher the value of C 1 and C2 for tuning condition. If we select too low
value of V2 and L then capacitance values will be beyond available limits, and if we
select higher value of V2 and L, then CCVT and inductor will become bulky. So a
compromise is necessary and let us select V2 = 6.6kV
For V2 = 6.6kV
L = 269H
C1 C 2 0.0377 F
V C1 C 2
Now,
V2 C1
13210 3 0.037710 -6
36.610 3
C1
0.0377 36.610 3 10 -6 F
C1
13210 3
0.0033F
131
C 2 0.0344F
In this design, we explained the basic concept for CCVT design and we assumed
the transformer to be ideal. But in actual design practice the value of magnetizing
impedance of transformer, resistance of reactor etc have to be taken into account,
as ratio error a and phase angle error b will also get affected by these values.
14. Diagram
The equivalent circuit of a CCVT is shown in fig 8.3. The values of C 1 and C2 are
0.0018 F and 0.018 F respectively. Tuning inductor has an inductance of
497H and resistance of 4620 .
Xm of the 6.6kV VT is 1M , core loss = 20 watts per phase, VA burden =
150VA per phase. Value of Cm for compensating the current drawn by m is equal
to 3.18310 -9 F .
(s) Verify the appropriateness of choice of L and Cm.
Ans: If C1 0.0018F and C 2 0.0186F then the value L of tuning inductor
is given by
1
L 2
w (C1 C 2 )
where w 2p f and f = tuning frequency
1
L
(2p �50) (0.0018 0.0186) �10-6
2
1
Xm
w Cm
1 1
Cm
w X m (2p �50) �� 1 106
3.183 �10-9 F
The value is also same as the selected value of Cm Hence the selection of both L
and Cm is appropriate.
(u) If the frequency drops from 50Hz to 47Hz, what would be the values of ratio
error and phase angle error?
Ans: Core loss = 20w
V22
20W
Rm
132
V22 (6600) 2
Rm
20 20
2.18 �10
6
6600 0
A
260874.14 -2.44�
VT I th �Z
6600 0
�256147.5 1.82�
260874.14 -2.44�
6480.42 4.26�
(6600 - 6480.42)
Hence % ratio error �100
6600
=1.81%
Phase angle error = 4.26�
V2 6.6kV
r a w2 a 2
M
d 2i R di 1 1 R
t �t0 2
i0 wn 2p �50 2 Iwn
dt L dt LCeq LC L
d 2i
2
2a wn wn2i 0 a < 1
dt
Lec – 8
1
2p �50 2zw R d i 2zw w 2i 0 z wn z < 1
2
wn
LCeq n
L dt 2 n n
-t V
t I 0 - m sin(wt0 f - q ) f q
e | Z line |
134
Example 1:
d
135
Answer:
Based on the criteria that the CT can deliver 20 times rated secondary current
without exceeding a 10% ratio error, the maximum fault current will be 24000A.
However, with a 2.0Ω burden, this will result in a voltage below the knee point of the CT
and, as a practical matter, it will be within 10% accuracy at higher currents. This can only
be accurately determined from excitation or ratio correction curves and not from the
accuracy classification. For example, a CT with characteristics shown in above figure
will produce between 180-240A without exceeding the 10% ratio error, depending on the
power factor of the 2.0Ω burden.
Example 2:
A 1200/5, C400 CT is connected on the 1000/5 tap. What is the maximum secondary
burden that can be used and still maintain rated accuracy at 20 times rated symmetrical
secondary current?
Answer:
Since the secondary voltage capability is directly proportional to the connected tap, the
CT will support a voltage of 1000/1200 400V or 333V. Twenty times the rated
secondary current is 100A. Therefore, the maximum burden is 333V/100A or 3.33 Ω
Example 3:
Assume that secondary burden in a relay circuit is 5Ω. The relay setting is 2A and the CT
ratio is 300/5. Using above figure, calculate the primary current required to operate the
relay?
Answer:
136
N (I E I S )
= 300/5(0.04+2) A=122A
Example 4:
A relay is expected to operate for a 7000A primary current. The CT ratio is 600/5.
Secondary burden is 3.5 Ω. What is the error for the CT shown in above figure?
Answer:
The total secondary fault current is (7000/600) 5=58A. Assume that exciting current is
negligible.
VS I S ( R B RS )
= 58(3.5+0.31)
= 221V
The exciting current will not be negligible, however, and the calculation will not be
iterated.
Lec – 7
N1 RI 0 Vm N1 R Vm Vm N1 N1 RI 0 -tt N1 I 0 -tt
fdcmax t t N1 Rt v2 (t )
dc
e i2 e
N 22 | Z line | N 22 | Z line | | Z line | N 22 N2 N2
t -t -t
1 N1 RI 0 t N1 RI 0
f (t ) - f (0) t (1 - e ) f (t ) f (0) t (1 - e t )
N2 �
v2 dt 2 2
0
N 2 N 2
Lec- 7
137
Vm N1 d V2
v2ac (t ) R sin(wt f - q ) jw f ac
| Z line | N 2 dt jw N 2
RVm N1 p RVm N1
fac (t ) sin(wt f - q - ) facmax
w | Z line | N 2
2
2 w | Z line | N 22
Vm N1
Rt
RVm N1 N1 RVmt | Z line | N 22 wL X
facmax fdcmax 2 1 1 wt 1 line 1 line
w | Z line | N 2 N 2 | Z line |
2
Vm N1 R Rline Rline
| Z line | N 2 w
2
X
1
R
Lec-6
Lec – 5
Ip Ip
- IS Ip IE - IS
N - I I �100 N 98�45�
�100 N S E
IS �100
IS IS
Lec - 9
Vth - VT 1 1
�100 )Dw w02
(3f ) ( L w02 1 LC < f Df �3Hz
Vth w02
LC
1t di dv di 1 d 2i
v(t ) Ri �
Ceq
-�
idt L
dt dt
R
dt Ceq
i L 2 w0
dt
d 1 1 1
DVL - DVC jI (w L - ) Dw I (2 2 )Dw w02 I ( L L )Dw
dw wCeq w0 Ceq LCeq
138
| VL - VC | 2 LI Dw 2 LI 2 LDw
j 2 LI Dw (DVL - DVC ) tan b 2 2 2 � 2p f Lm 106
| VR | a Rb I a Rb a Rb
106
Lm 3183.1H
2p
source. The fault strikes at time t t 0 . This can be simulated by closing the switch at t t1
139
R jwL or Z q models the line impedance. The fault current in the line is given by
i (t ) 0 0 t t0
t -t 0
V sin(w t f - q ) -
t
t t0
i (t ) m I 0e
|Z |
Where τ is the time constant of the line τ =L/R. The fault current has two components in
it. The first component models the steady state sinusoidal ac response while the second current
is the dc offset current due to the presence of inductive component in the circuit. Recall that
current in an inductance can not change instantaneously. As t ∞, the instantaneous dc
It is more or less obvious that, dc offset is not seen in the waveform after 5 time constants.
The value of I0 can be worked out by setting the current at t t o to zero.
This implies that
Vm
I0 - sin(wt 0 - q )
Z
140
Thus
t -t 0
Vm V -( )
i (t ) sin(wt f - q ) - m sin(wt f - q )e t
Z Z
fig.2
It can be seen that severity of dc offset component in fault current is maximum when
a) f q
p
b) wt 0
2
141
p 1
For example, if angle of transmission line is 800, then with f = 800 & t 0 =
2 2p 50 200
V
sec = 5msec, the severity of dc offset current would equal I 0 Z , which is also the peak
m
We now plan to show that CT can saturate on dc offset current. Also, we plan to show
that the resulting distortions in the CT secondary current can be un-acceptably high. While
doing this analysis, we will neglect ac symmetrical component. In other words, we rest our
belief in superposition theorem atleast qualitatively and will finally evaluate effect using it
Notice that the current that we are dealing with is non-linear, a rigorous application of super
position theorem is simply out of question.
142
First consider an ideal CT excited by the dc offset current source. An ideal CT will faithfully
replicates primary current waveform on the secondary side. Hence, the secondary current
would be given by
-t
I0 t
i2 (t ) e
N
and the voltage developed across CT secondary would be given by
-t
RI N2
v 2 (t ) 0 e t where N N
N 1
For simplicity, let us assume that the initial flux in the transformer core at t=0 is zero
f ( 0 ) 0 ; Then we can compute the flux in the transformer core by using faraday’s law
df
V2 N 2 ---------(2)
dt
143
t
f (t ) - f (0) v 0
2 dt
RI 0
-t
t 1- e t
N2
-t
LI 0
(1 - e t )
N2
-t
LI 0
f (t ) f (0) (1 - e t )
N2
-t
LI 0
(1 - e t ) ------- (3)
N2
as a consequence of dc offset current,
Thus, flux in the core increases exponentially to a peak value of
f dmax
c
LI 0
N2
as t
L Vm Vm
N Z Z
f dmax
c
Note that unlike ac voltage induced flux, which is sinusoidal, this flux is unidirectional. The ac
voltage induced flux has zero average value. However, dc offset induced does not have this
nice feature. The total flux in ideal CT core is a summation of ac flux and dc flux.
d
The ac flux in the CT core can be obtained by substituting operator by jw . Hence
dt
If v2 (t ) Vm sin(wt f ) , then
Vm p
f ac sin(wt f - )
wN 2 2
The peak value of ac flux is given by
144
Vm
f acmax
wN 2
However Vm R2 I 0
max
R2 I 0max
Hence facmax
wN 2
and peak value of the total flux is given by
Vm LI 0max
facmax f dcmax
wN 2 N2
In practice, if this flux exceeds the knee-point flux in the core (see fig.), then the CT core
will saturate.
As a consequence of CT core saturation, the secondary current would not faithfully replicate
the primary current. Infact, in practice it is observed that CT secondary current is clipped. The
clipping of CT current leads to “blinding” of the relay which cannot function further. Hence,
CT saturation in presence of dc offset current is a serious problem which relay designers have
to face. Note that dc flux accumulates gradually. (Depends upon the transmission line time
constant ( t ). It is apparent that saturation should not occur immediately after the inception of
the fault. Thus, if the relay is fast enough in decision making, it is likely that a relaying
decision would be undertaken before the CT fully saturates. This is another important reason
for increasing the speed of relaying system. For bus-fault protection, where the dc saturation
due to dc offset current can be a significant contributing factor, quarter cycle operations *****
145
specifically are imposed. Similarly, a distance relay is expected to operate within ½-1 cycle
time.
CT oversizing factors
Typically, an efficient design of transformer would correspond to choosing the core cross
section such that f mac should be near the knee point of B-H curve. One obvious way of
avoiding the CT saturation on dc flux is to oversize the core so that for flux (f acmax f dcmax ) , the
(f acmax f dcmax )
corresponding B is below the knee-point. Hence, the factor is called core-
f acmax
oversizing factor.
f dcmax
Core-oversizing factor = 1
f acmax
LI o N 2
1
RI 0 wN 2
wL
1
R
X
1
R
Note that X/R in above equation is the transmission line X/R ratio. For a 220KV line X/R 10.
This would imply that transformer core should be oversized by a factor of 11. For a 400KV
line, typical value of X/R 20. This would imply an oversizing required of about 21 times the
usual design. Clearly this high amount of oversizing is not practical. Thus, the important
conclusion is that, protection engineers have to live with the saturation problem.
Cautions in CT selection:
While choosing a CT for a particular application, it is necessary to observe following
precautions.
29. The CT rating and continuous load current should match. For example, if max load
current is 90A, a 100:5 Ct may be acceptable but 50:5 is not acceptable.
146
30. The maximum fault current should be less than 20 times the CT rated current. for
example 100:5 CT can be used, so long as burden on the CT & maximum primary fault
current is below 2000A.
31. The voltage rating of CT should be compatible. For example, 100:5 C100 would give
linear response, upto 20 times rated current provided CT burden is kept
below(100/20*5=1 Ω). With 2 Ω burden, this CT can be used only if maximum current
is limited to 1000A.
32. Parallel of CT’s e.g. in differential protection, or with SLG fault can create significant
errors in CT performance. One should in general ascertain that magnetizing current is
kept much below the pick up value.
Following example, illustrates this point
Exercise problems:
If the current ratio is adequate for a protection, but CT burden is high; then the
performance of CT may deteriorate due to large magnetizing current and/or saturation problem.
The CT performance can be improved by connecting the CT’s in series.
15) Show the dotted terminals for correct secondary series connection
16) What is the VA of CT in fig (a) & (b) respectively?
22) Electromechanical relays tend to saturate at high currents. This reduces the relay burden
on CT, and so that the CT performance at moderately high currents may be considered
better than at relay’s rated burden at 5A.
23) Use of instantaneous over current relays has the potential to overcome this problem of
saturation of CT’s
147
24) Differential protection can operate on external faults due to the un equal saturation of
CT’s
Lecture-6
Examples
13. If a 300:5 class C CT is connected to a meter with resistance R I 1 and
secondary current in the CT is 4.5A find out the primary current voltage
developed across the meter and % rate error. Lead wire resistance R L 0.02
secondary resistance RS of a 300/5 CT 0.15
Diagram
R I 1 , R L 0.02 RS 0.15 I S 4.5 A
Total secondary resistance RT R I R L RS
1.17
Secondary voltage I S RT
4.5 1.17
5.265V
From Fig 5.7,
Exciting current IE for 5.265V
= 0.03A
Turns ratio N = 300/5 = 60
I p N (I S I E )
= 60(4.5 + 0.03)
= 271.8A
Voltage across meter I S R I
4.5 1 = 4.5V
IE 0.03
Ratio error 100 100
IS 4.5
= 0.67%
Rb
148
Lecture – 8
Examples
15. Design a CCVT for a 132kV transmission line using the following data.
Resistive Burden (3f )-150VA
Df 3Hz , phase angle error b = 40 min
Consider 4 choices of V2 as 33kV, 11kV, 6.6kV and 3.3kV
Diagram 1 Diagram 2
Transmission line voltage V = 132kV. Suppose V 2 (P_N) be the voltage to be
produced by the capacitive potential divider with capacitance values C1 and C2
and L the value of tuning inductor. The standardized VT secondary voltage is 110
volts (L-L).
Here specification for phase angle error b is 40 minutes variation in frequency
can be upto Df 3Hz . Phase angle error for change in w by Dw in the above
equation circuit, is given by
1
( L 2 )Dw
w C
1
At tuning frequency w 2
LC
Substituting w 1 LC
2
747.2 H
1 1
C1 C 2
w 2 L (3/ 4) 2 747.2
1.3610 -2 F
3) V2 6.6kV
3 �(6.6 �103 )2
Rb
'
150
87.1210 4
b �Rb' 0.01164 �87.12 �104
L
2 �Dw 2 �2p �3
269H ,
C1 C 2 3.7710 -2 F
4) V2 3.3kV
3 �(3.3 �103 ) 2
Rb'
150
21.7810 4
b �Rb' 0.01164 �21.78 �104
L
2 �Dw 2 �2p �3
67.25 H
C1 C2 0.151 F
The values of L, C1 C 2 for different values of V2 are tabulated below.
V2 L C1 C 2
33kV 6722.2H 0.00151 F
11kV 747.2H 0.0136 F
6.6kV 269H 0.0377 F
3.3kV 67.25H 0.151 F
From the above table it is clear that smaller the value of V 2, the smaller is the
value of L and higher the value of C 1 and C2 for tuning condition. If we select too low
value of V2 and L then capacitance values will be beyond available limits, and if we
select higher value of V2 and L, then CCVT and inductor will become bulky. So a
compromise is necessary and let us select V2 = 6.6kV
For V2 = 6.6kV
L = 269H
C1 C 2 0.0377 F
V C1 C 2
Now,
V2 C1
13210 3 0.037710 -6
36.610 3
C1
0.0377 36.610 3 10 -6 F
C1
13210 3
0.0033F
150
C 2 0.0344F
In this design, we explained the basic concept for CCVT design and we assumed
the transformer to be ideal. But in actual design practice the value of magnetizing
impedance of transformer, resistance of reactor etc have to be taken into account,
as ratio error a and phase angle error b will also get affected by these values.
16. Diagram
The equivalent circuit of a CCVT is shown in fig 8.3. The values of C 1 and C2 are
0.0018 F and 0.018 F respectively. Tuning inductor has an inductance of
497H and resistance of 4620 .
Xm of the 6.6kV VT is 1M , core loss = 20 watts per phase, VA burden =
150VA per phase. Value of Cm for compensating the current drawn by m is equal
to 3.18310 -9 F .
(v) Verify the appropriateness of choice of L and Cm.
Ans: If C1 0.0018F and C 2 0.0186F then the value L of tuning inductor
is given by
1
L 2
w (C1 C 2 )
where w 2p f and f = tuning frequency
1
L
(2p �50) (0.0018 0.0186) �10-6
2
1
Xm
w Cm
1 1
Cm
w X m (2p �50) �� 1 106
3.183 �10-9 F
The value is also same as the selected value of Cm Hence the selection of both L
and Cm is appropriate.
(x) If the frequency drops from 50Hz to 47Hz, what would be the values of ratio
error and phase angle error?
Ans: Core loss = 20w
V22
20W
Rm
151
V22 (6600) 2
Rm
20 20
2.18 �10
6
6600 0
A
260874.14 -2.44�
VT I th �Z
6600 0
�256147.5 1.82�
260874.14 -2.44�
6480.42 4.26�
(6600 - 6480.42)
Hence % ratio error �100
6600
=1.81%
Phase angle error = 4.26�
V2 6.6kV
r a w2 a 2
M
d 2i R di 1 1 R
t �t0 2
i0 wn 2p �50 2 Iwn
dt L dt LCeq LC L
d 2i
2
2a wn wn2i 0 a < 1
dt
Lec – 8
1
2p �50 2zw R d i 2zw w 2i 0 z wn z < 1
2
wn
LCeq n
L dt 2 n n
-t V
t I 0 - m sin(wt0 f - q ) f q
e | Z line |
153
Example 1:
d
154
Answer:
Based on the criteria that the CT can deliver 20 times rated secondary current
without exceeding a 10% ratio error, the maximum fault current will be 24000A.
However, with a 2.0Ω burden, this will result in a voltage below the knee point of the CT
and, as a practical matter, it will be within 10% accuracy at higher currents. This can only
be accurately determined from excitation or ratio correction curves and not from the
accuracy classification. For example, a CT with characteristics shown in above figure
will produce between 180-240A without exceeding the 10% ratio error, depending on the
power factor of the 2.0Ω burden.
Example 2:
A 1200/5, C400 CT is connected on the 1000/5 tap. What is the maximum secondary
burden that can be used and still maintain rated accuracy at 20 times rated symmetrical
secondary current?
Answer:
Since the secondary voltage capability is directly proportional to the connected tap, the
CT will support a voltage of 1000/1200 400V or 333V. Twenty times the rated
secondary current is 100A. Therefore, the maximum burden is 333V/100A or 3.33 Ω
Example 3:
Assume that secondary burden in a relay circuit is 5Ω. The relay setting is 2A and the CT
ratio is 300/5. Using above figure, calculate the primary current required to operate the
relay?
Answer:
155
N (I E I S )
= 300/5(0.04+2) A=122A
Example 4:
A relay is expected to operate for a 7000A primary current. The CT ratio is 600/5.
Secondary burden is 3.5 Ω. What is the error for the CT shown in above figure?
Answer:
The total secondary fault current is (7000/600) 5=58A. Assume that exciting current is
negligible.
VS I S ( R B RS )
= 58(3.5+0.31)
= 221V
The exciting current will not be negligible, however, and the calculation will not be
iterated.
Lec – 7
N1 RI 0 Vm N1 R Vm Vm N1 N1 RI 0 -tt N1 I 0 -tt
fdcmax t t N1 Rt v2 (t )
dc
e i2 e
N 22 | Z line | N 22 | Z line | | Z line | N 22 N2 N2
t -t -t
1 N1 RI 0 t N1 RI 0
f (t ) - f (0) t (1 - e ) f (t ) f (0) t (1 - e t )
N2 �
v2 dt 2 2
0
N 2 N 2
Lec- 7
156
Vm N1 d V2
v2ac (t ) R sin(wt f - q ) jw f ac
| Z line | N 2 dt jw N 2
RVm N1 p RVm N1
fac (t ) sin(wt f - q - ) facmax
w | Z line | N 2
2
2 w | Z line | N 22
Vm N1
Rt
RVm N1 N1 RVmt | Z line | N 22 wL X
facmax fdcmax 2 1 1 wt 1 line 1 line
w | Z line | N 2 N 2 | Z line |
2
Vm N1 R Rline Rline
| Z line | N 2 w
2
X
1
R
Lec-6
Lec – 5
Ip Ip
- IS Ip IE - IS
N - I I �100 N 98�45�
�100 N S E
IS �100
IS IS
Lec - 9
Vth - VT 1 1
�100 )Dw w02
(3f ) ( L w02 1 LC < f Df �3Hz
Vth w02
LC
1t di dv di 1 d 2i
v(t ) Ri �
Ceq
-�
idt L
dt dt
R
dt Ceq
i L 2 w0
dt
d 1 1 1
DVL - DVC jI (w L - ) Dw I (2 2 )Dw w02 I ( L L )Dw
dw wCeq w0 Ceq LCeq
157
| VL - VC | 2 LI Dw 2 LI 2 LDw
j 2 LI Dw (DVL - DVC ) tan b 2 2 2 � 2p f Lm 106
| VR | a Rb I a Rb a Rb
106
Lm 3183.1H
2p
source. The fault strikes at time t t 0 . This can be simulated by closing the switch at t t1
158
R jwL or Z q models the line impedance. The fault current in the line is given by
i (t ) 0 0 t t0
t -t 0
V sin(w t f - q ) -
t
t t0
i (t ) m I 0e
|Z |
Where τ is the time constant of the line τ =L/R. The fault current has two components in
it. The first component models the steady state sinusoidal ac response while the second current
is the dc offset current due to the presence of inductive component in the circuit. Recall that
current in an inductance can not change instantaneously. As t ∞, the instantaneous dc
It is more or less obvious that, dc offset is not seen in the waveform after 5 time constants.
The value of I0 can be worked out by setting the current at t t o to zero.
This implies that
Vm
I0 - sin(wt 0 - q )
Z
159
Thus
t -t 0
Vm V -( )
i (t ) sin(wt f - q ) - m sin(wt f - q )e t
Z Z
fig.2
It can be seen that severity of dc offset component in fault current is maximum when
a) f q
p
b) wt 0
2
160
p 1
For example, if angle of transmission line is 800, then with f = 800 & t 0 =
2 2p 50 200
V
sec = 5msec, the severity of dc offset current would equal I 0 Z , which is also the peak
m
We now plan to show that CT can saturate on dc offset current. Also, we plan to show
that the resulting distortions in the CT secondary current can be un-acceptably high. While
doing this analysis, we will neglect ac symmetrical component. In other words, we rest our
belief in superposition theorem atleast qualitatively and will finally evaluate effect using it
Notice that the current that we are dealing with is non-linear, a rigorous application of super
position theorem is simply out of question.
161
First consider an ideal CT excited by the dc offset current source. An ideal CT will faithfully
replicates primary current waveform on the secondary side. Hence, the secondary current
would be given by
-t
I0 t
i2 (t ) e
N
and the voltage developed across CT secondary would be given by
-t
RI N2
v 2 (t ) 0 e t where N N
N 1
For simplicity, let us assume that the initial flux in the transformer core at t=0 is zero
f ( 0 ) 0 ; Then we can compute the flux in the transformer core by using faraday’s law
df
V2 N 2 ---------(2)
dt
162
t
f (t ) - f (0) v 0
2 dt
RI 0
-t
t 1- e t
N2
-t
LI 0
(1 - e t )
N2
-t
LI 0
f (t ) f (0) (1 - e t )
N2
-t
LI 0
(1 - e t ) ------- (3)
N2
as a consequence of dc offset current,
Thus, flux in the core increases exponentially to a peak value of
f dmax
c
LI 0
N2
as t
L Vm Vm
N Z Z
f dmax
c
Note that unlike ac voltage induced flux, which is sinusoidal, this flux is unidirectional. The ac
voltage induced flux has zero average value. However, dc offset induced does not have this
nice feature. The total flux in ideal CT core is a summation of ac flux and dc flux.
d
The ac flux in the CT core can be obtained by substituting operator by jw . Hence
dt
If v2 (t ) Vm sin(wt f ) , then
Vm p
f ac sin(wt f - )
wN 2 2
The peak value of ac flux is given by
163
Vm
f acmax
wN 2
However Vm R2 I 0
max
R2 I 0max
Hence facmax
wN 2
and peak value of the total flux is given by
Vm LI 0max
facmax f dcmax
wN 2 N2
In practice, if this flux exceeds the knee-point flux in the core (see fig.), then the CT core
will saturate.
As a consequence of CT core saturation, the secondary current would not faithfully replicate
the primary current. Infact, in practice it is observed that CT secondary current is clipped. The
clipping of CT current leads to “blinding” of the relay which cannot function further. Hence,
CT saturation in presence of dc offset current is a serious problem which relay designers have
to face. Note that dc flux accumulates gradually. (Depends upon the transmission line time
constant ( t ). It is apparent that saturation should not occur immediately after the inception of
the fault. Thus, if the relay is fast enough in decision making, it is likely that a relaying
decision would be undertaken before the CT fully saturates. This is another important reason
for increasing the speed of relaying system. For bus-fault protection, where the dc saturation
due to dc offset current can be a significant contributing factor, quarter cycle operations *****
164
specifically are imposed. Similarly, a distance relay is expected to operate within ½-1 cycle
time.
CT oversizing factors
Typically, an efficient design of transformer would correspond to choosing the core cross
section such that f mac should be near the knee point of B-H curve. One obvious way of
avoiding the CT saturation on dc flux is to oversize the core so that for flux (f acmax f dcmax ) , the
(f acmax f dcmax )
corresponding B is below the knee-point. Hence, the factor is called core-
f acmax
oversizing factor.
f dcmax
Core-oversizing factor = 1
f acmax
LI o N 2
1
RI 0 wN 2
wL
1
R
X
1
R
Note that X/R in above equation is the transmission line X/R ratio. For a 220KV line X/R 10.
This would imply that transformer core should be oversized by a factor of 11. For a 400KV
line, typical value of X/R 20. This would imply an oversizing required of about 21 times the
usual design. Clearly this high amount of oversizing is not practical. Thus, the important
conclusion is that, protection engineers have to live with the saturation problem.
Cautions in CT selection:
While choosing a CT for a particular application, it is necessary to observe following
precautions.
33. The CT rating and continuous load current should match. For example, if max load
current is 90A, a 100:5 Ct may be acceptable but 50:5 is not acceptable.
165
34. The maximum fault current should be less than 20 times the CT rated current. for
example 100:5 CT can be used, so long as burden on the CT & maximum primary fault
current is below 2000A.
35. The voltage rating of CT should be compatible. For example, 100:5 C100 would give
linear response, upto 20 times rated current provided CT burden is kept
below(100/20*5=1 Ω). With 2 Ω burden, this CT can be used only if maximum current
is limited to 1000A.
36. Parallel of CT’s e.g. in differential protection, or with SLG fault can create significant
errors in CT performance. One should in general ascertain that magnetizing current is
kept much below the pick up value.
Following example, illustrates this point
Exercise problems:
If the current ratio is adequate for a protection, but CT burden is high; then the
performance of CT may deteriorate due to large magnetizing current and/or saturation problem.
The CT performance can be improved by connecting the CT’s in series.
17) Show the dotted terminals for correct secondary series connection
18) What is the VA of CT in fig (a) & (b) respectively?
25) Electromechanical relays tend to saturate at high currents. This reduces the relay burden
on CT, and so that the CT performance at moderately high currents may be considered
better than at relay’s rated burden at 5A.
26) Use of instantaneous over current relays has the potential to overcome this problem of
saturation of CT’s
166
27) Differential protection can operate on external faults due to the un equal saturation of
CT’s
Lecture-6
Examples
14. If a 300:5 class C CT is connected to a meter with resistance R I 1 and
secondary current in the CT is 4.5A find out the primary current voltage
developed across the meter and % rate error. Lead wire resistance R L 0.02
secondary resistance RS of a 300/5 CT 0.15
Diagram
R I 1 , R L 0.02 RS 0.15 I S 4.5 A
Total secondary resistance RT R I R L RS
1.17
Secondary voltage I S RT
4.5 1.17
5.265V
From Fig 5.7,
Exciting current IE for 5.265V
= 0.03A
Turns ratio N = 300/5 = 60
I p N (I S I E )
= 60(4.5 + 0.03)
= 271.8A
Voltage across meter I S R I
4.5 1 = 4.5V
IE 0.03
Ratio error 100 100
IS 4.5
= 0.67%
Rb
167
Lecture – 8
Examples
17. Design a CCVT for a 132kV transmission line using the following data.
Resistive Burden (3f )-150VA
Df 3Hz , phase angle error b = 40 min
Consider 4 choices of V2 as 33kV, 11kV, 6.6kV and 3.3kV
Diagram 1 Diagram 2
Transmission line voltage V = 132kV. Suppose V 2 (P_N) be the voltage to be
produced by the capacitive potential divider with capacitance values C1 and C2
and L the value of tuning inductor. The standardized VT secondary voltage is 110
volts (L-L).
Here specification for phase angle error b is 40 minutes variation in frequency
can be upto Df 3Hz . Phase angle error for change in w by Dw in the above
equation circuit, is given by
1
( L 2 )Dw
w C
1
At tuning frequency w 2
LC
Substituting w 1 LC
2
747.2 H
1 1
C1 C 2
w 2 L (3/ 4) 2 747.2
1.3610 -2 F
3) V2 6.6kV
3 �(6.6 �103 )2
Rb
'
150
87.1210 4
b �Rb' 0.01164 �87.12 �104
L
2 �Dw 2 �2p �3
269H ,
C1 C 2 3.7710 -2 F
4) V2 3.3kV
3 �(3.3 �103 ) 2
Rb'
150
21.7810 4
b �Rb' 0.01164 �21.78 �104
L
2 �Dw 2 �2p �3
67.25 H
C1 C2 0.151 F
The values of L, C1 C 2 for different values of V2 are tabulated below.
V2 L C1 C 2
33kV 6722.2H 0.00151 F
11kV 747.2H 0.0136 F
6.6kV 269H 0.0377 F
3.3kV 67.25H 0.151 F
From the above table it is clear that smaller the value of V 2, the smaller is the
value of L and higher the value of C 1 and C2 for tuning condition. If we select too low
value of V2 and L then capacitance values will be beyond available limits, and if we
select higher value of V2 and L, then CCVT and inductor will become bulky. So a
compromise is necessary and let us select V2 = 6.6kV
For V2 = 6.6kV
L = 269H
C1 C 2 0.0377 F
V C1 C 2
Now,
V2 C1
13210 3 0.037710 -6
36.610 3
C1
0.0377 36.610 3 10 -6 F
C1
13210 3
0.0033F
169
C 2 0.0344F
In this design, we explained the basic concept for CCVT design and we assumed
the transformer to be ideal. But in actual design practice the value of magnetizing
impedance of transformer, resistance of reactor etc have to be taken into account,
as ratio error a and phase angle error b will also get affected by these values.
18. Diagram
The equivalent circuit of a CCVT is shown in fig 8.3. The values of C 1 and C2 are
0.0018 F and 0.018 F respectively. Tuning inductor has an inductance of
497H and resistance of 4620 .
Xm of the 6.6kV VT is 1M , core loss = 20 watts per phase, VA burden =
150VA per phase. Value of Cm for compensating the current drawn by m is equal
to 3.18310 -9 F .
(y) Verify the appropriateness of choice of L and Cm.
Ans: If C1 0.0018F and C 2 0.0186F then the value L of tuning inductor
is given by
1
L 2
w (C1 C 2 )
where w 2p f and f = tuning frequency
1
L
(2p �50) (0.0018 0.0186) �10-6
2
1
Xm
w Cm
1 1
Cm
w X m (2p �50) �� 1 106
3.183 �10-9 F
The value is also same as the selected value of Cm Hence the selection of both L
and Cm is appropriate.
(aa) If the frequency drops from 50Hz to 47Hz, what would be the values of
ratio error and phase angle error?
Ans: Core loss = 20w
V22
20W
Rm
170
V22 (6600) 2
Rm
20 20
2.18 �10
6
6600 0
A
260874.14 -2.44�
VT I th �Z
6600 0
�256147.5 1.82�
260874.14 -2.44�
6480.42 4.26�
(6600 - 6480.42)
Hence % ratio error �100
6600
=1.81%
Phase angle error = 4.26�
V2 6.6kV
r a w2 a 2
M
d 2i R di 1 1 R
t �t0 2
i0 wn 2p �50 2 Iwn
dt L dt LCeq LC L
d 2i
2
2a wn wn2i 0 a < 1
dt
Lec – 8
1
2p �50 2zw R d i 2zw w 2i 0 z wn z < 1
2
wn
LCeq n
L dt 2 n n
-t V
t I 0 - m sin(wt0 f - q ) f q
e | Z line |
172
Example 1:
d
173
Answer:
Based on the criteria that the CT can deliver 20 times rated secondary current
without exceeding a 10% ratio error, the maximum fault current will be 24000A.
However, with a 2.0Ω burden, this will result in a voltage below the knee point of the CT
and, as a practical matter, it will be within 10% accuracy at higher currents. This can only
be accurately determined from excitation or ratio correction curves and not from the
accuracy classification. For example, a CT with characteristics shown in above figure
will produce between 180-240A without exceeding the 10% ratio error, depending on the
power factor of the 2.0Ω burden.
Example 2:
A 1200/5, C400 CT is connected on the 1000/5 tap. What is the maximum secondary
burden that can be used and still maintain rated accuracy at 20 times rated symmetrical
secondary current?
Answer:
Since the secondary voltage capability is directly proportional to the connected tap, the
CT will support a voltage of 1000/1200 400V or 333V. Twenty times the rated
secondary current is 100A. Therefore, the maximum burden is 333V/100A or 3.33 Ω
Example 3:
Assume that secondary burden in a relay circuit is 5Ω. The relay setting is 2A and the CT
ratio is 300/5. Using above figure, calculate the primary current required to operate the
relay?
Answer:
174
N (I E I S )
= 300/5(0.04+2) A=122A
Example 4:
A relay is expected to operate for a 7000A primary current. The CT ratio is 600/5.
Secondary burden is 3.5 Ω. What is the error for the CT shown in above figure?
Answer:
The total secondary fault current is (7000/600) 5=58A. Assume that exciting current is
negligible.
VS I S ( R B RS )
= 58(3.5+0.31)
= 221V
The exciting current will not be negligible, however, and the calculation will not be
iterated.
Lec – 7
N1 RI 0 Vm N1 R Vm Vm N1 N1 RI 0 -tt N1 I 0 -tt
fdcmax t t N1 Rt v2 (t )
dc
e i2 e
N 22 | Z line | N 22 | Z line | | Z line | N 22 N2 N2
t -t -t
1 N1 RI 0 t N1 RI 0
f (t ) - f (0) t (1 - e ) f (t ) f (0) t (1 - e t )
N2 �
v2 dt 2 2
0
N 2 N 2
Lec- 7
175
Vm N1 d V2
v2ac (t ) R sin(wt f - q ) jw f ac
| Z line | N 2 dt jw N 2
RVm N1 p RVm N1
fac (t ) sin(wt f - q - ) facmax
w | Z line | N 2
2
2 w | Z line | N 22
Vm N1
Rt
RVm N1 N1 RVmt | Z line | N 22 wL X
facmax fdcmax 2 1 1 wt 1 line 1 line
w | Z line | N 2 N 2 | Z line |
2
Vm N1 R Rline Rline
| Z line | N 2 w
2
X
1
R
Lec-6
Lec – 5
Ip Ip
- IS Ip IE - IS
N - I I �100 N 98�45�
�100 N S E
IS �100
IS IS
Lec - 9
Vth - VT 1 1
�100 )Dw w02
(3f ) ( L w02 1 LC < f Df �3Hz
Vth w02
LC
1t di dv di 1 d 2i
v(t ) Ri �
Ceq
-�
idt L
dt dt
R
dt Ceq
i L 2 w0
dt
d 1 1 1
DVL - DVC jI (w L - ) Dw I (2 2 )Dw w02 I ( L L )Dw
dw wCeq w0 Ceq LCeq
176
| VL - VC | 2 LI Dw 2 LI 2 LDw
j 2 LI Dw (DVL - DVC ) tan b 2 2 2 � 2p f Lm 106
| VR | a Rb I a Rb a Rb
106
Lm 3183.1H
2p
source. The fault strikes at time t t 0 . This can be simulated by closing the switch at t t1
177
R jwL or Z q models the line impedance. The fault current in the line is given by
i (t ) 0 0 t t0
t -t 0
V sin(w t f - q ) -
t
t t0
i (t ) m I 0e
|Z |
Where τ is the time constant of the line τ =L/R. The fault current has two components in
it. The first component models the steady state sinusoidal ac response while the second current
is the dc offset current due to the presence of inductive component in the circuit. Recall that
current in an inductance can not change instantaneously. As t ∞, the instantaneous dc
It is more or less obvious that, dc offset is not seen in the waveform after 5 time constants.
The value of I0 can be worked out by setting the current at t t o to zero.
This implies that
Vm
I0 - sin(wt 0 - q )
Z
178
Thus
t -t 0
Vm V -( )
i (t ) sin(wt f - q ) - m sin(wt f - q )e t
Z Z
fig.2
It can be seen that severity of dc offset component in fault current is maximum when
a) f q
p
b) wt 0
2
179
p 1
For example, if angle of transmission line is 800, then with f = 800 & t 0 =
2 2p 50 200
V
sec = 5msec, the severity of dc offset current would equal I 0 Z , which is also the peak
m
We now plan to show that CT can saturate on dc offset current. Also, we plan to show
that the resulting distortions in the CT secondary current can be un-acceptably high. While
doing this analysis, we will neglect ac symmetrical component. In other words, we rest our
belief in superposition theorem atleast qualitatively and will finally evaluate effect using it
Notice that the current that we are dealing with is non-linear, a rigorous application of super
position theorem is simply out of question.
180
First consider an ideal CT excited by the dc offset current source. An ideal CT will faithfully
replicates primary current waveform on the secondary side. Hence, the secondary current
would be given by
-t
I0 t
i2 (t ) e
N
and the voltage developed across CT secondary would be given by
-t
RI N2
v 2 (t ) 0 e t where N N
N 1
For simplicity, let us assume that the initial flux in the transformer core at t=0 is zero
f ( 0 ) 0 ; Then we can compute the flux in the transformer core by using faraday’s law
df
V2 N 2 ---------(2)
dt
181
t
f (t ) - f (0) v 0
2 dt
RI 0
-t
t 1- e t
N2
-t
LI 0
(1 - e t )
N2
-t
LI 0
f (t ) f (0) (1 - e t )
N2
-t
LI 0
(1 - e t ) ------- (3)
N2
as a consequence of dc offset current,
Thus, flux in the core increases exponentially to a peak value of
f dmax
c
LI 0
N2
as t
L Vm Vm
N Z Z
f dmax
c
Note that unlike ac voltage induced flux, which is sinusoidal, this flux is unidirectional. The ac
voltage induced flux has zero average value. However, dc offset induced does not have this
nice feature. The total flux in ideal CT core is a summation of ac flux and dc flux.
d
The ac flux in the CT core can be obtained by substituting operator by jw . Hence
dt
If v2 (t ) Vm sin(wt f ) , then
Vm p
f ac sin(wt f - )
wN 2 2
The peak value of ac flux is given by
182
Vm
f acmax
wN 2
However Vm R2 I 0
max
R2 I 0max
Hence facmax
wN 2
and peak value of the total flux is given by
Vm LI 0max
facmax f dcmax
wN 2 N2
In practice, if this flux exceeds the knee-point flux in the core (see fig.), then the CT core
will saturate.
As a consequence of CT core saturation, the secondary current would not faithfully replicate
the primary current. Infact, in practice it is observed that CT secondary current is clipped. The
clipping of CT current leads to “blinding” of the relay which cannot function further. Hence,
CT saturation in presence of dc offset current is a serious problem which relay designers have
to face. Note that dc flux accumulates gradually. (Depends upon the transmission line time
constant ( t ). It is apparent that saturation should not occur immediately after the inception of
the fault. Thus, if the relay is fast enough in decision making, it is likely that a relaying
decision would be undertaken before the CT fully saturates. This is another important reason
for increasing the speed of relaying system. For bus-fault protection, where the dc saturation
due to dc offset current can be a significant contributing factor, quarter cycle operations *****
183
specifically are imposed. Similarly, a distance relay is expected to operate within ½-1 cycle
time.
CT oversizing factors
Typically, an efficient design of transformer would correspond to choosing the core cross
section such that f mac should be near the knee point of B-H curve. One obvious way of
avoiding the CT saturation on dc flux is to oversize the core so that for flux (f acmax f dcmax ) , the
(f acmax f dcmax )
corresponding B is below the knee-point. Hence, the factor is called core-
f acmax
oversizing factor.
f dcmax
Core-oversizing factor = 1
f acmax
LI o N 2
1
RI 0 wN 2
wL
1
R
X
1
R
Note that X/R in above equation is the transmission line X/R ratio. For a 220KV line X/R 10.
This would imply that transformer core should be oversized by a factor of 11. For a 400KV
line, typical value of X/R 20. This would imply an oversizing required of about 21 times the
usual design. Clearly this high amount of oversizing is not practical. Thus, the important
conclusion is that, protection engineers have to live with the saturation problem.
Cautions in CT selection:
While choosing a CT for a particular application, it is necessary to observe following
precautions.
37. The CT rating and continuous load current should match. For example, if max load
current is 90A, a 100:5 Ct may be acceptable but 50:5 is not acceptable.
184
38. The maximum fault current should be less than 20 times the CT rated current. for
example 100:5 CT can be used, so long as burden on the CT & maximum primary fault
current is below 2000A.
39. The voltage rating of CT should be compatible. For example, 100:5 C100 would give
linear response, upto 20 times rated current provided CT burden is kept
below(100/20*5=1 Ω). With 2 Ω burden, this CT can be used only if maximum current
is limited to 1000A.
40. Parallel of CT’s e.g. in differential protection, or with SLG fault can create significant
errors in CT performance. One should in general ascertain that magnetizing current is
kept much below the pick up value.
Following example, illustrates this point
Exercise problems:
If the current ratio is adequate for a protection, but CT burden is high; then the
performance of CT may deteriorate due to large magnetizing current and/or saturation problem.
The CT performance can be improved by connecting the CT’s in series.
19) Show the dotted terminals for correct secondary series connection
20) What is the VA of CT in fig (a) & (b) respectively?
28) Electromechanical relays tend to saturate at high currents. This reduces the relay burden
on CT, and so that the CT performance at moderately high currents may be considered
better than at relay’s rated burden at 5A.
29) Use of instantaneous over current relays has the potential to overcome this problem of
saturation of CT’s
185
30) Differential protection can operate on external faults due to the un equal saturation of
CT’s
Lecture-6
Examples
15. If a 300:5 class C CT is connected to a meter with resistance R I 1 and
secondary current in the CT is 4.5A find out the primary current voltage
developed across the meter and % rate error. Lead wire resistance R L 0.02
secondary resistance RS of a 300/5 CT 0.15
Diagram
R I 1 , R L 0.02 RS 0.15 I S 4.5 A
Total secondary resistance RT R I R L RS
1.17
Secondary voltage I S RT
4.5 1.17
5.265V
From Fig 5.7,
Exciting current IE for 5.265V
= 0.03A
Turns ratio N = 300/5 = 60
I p N (I S I E )
= 60(4.5 + 0.03)
= 271.8A
Voltage across meter I S R I
4.5 1 = 4.5V
IE 0.03
Ratio error 100 100
IS 4.5
= 0.67%
Rb
186
Lecture – 8
Examples
19. Design a CCVT for a 132kV transmission line using the following data.
Resistive Burden (3f )-150VA
Df 3Hz , phase angle error b = 40 min
Consider 4 choices of V2 as 33kV, 11kV, 6.6kV and 3.3kV
Diagram 1 Diagram 2
Transmission line voltage V = 132kV. Suppose V 2 (P_N) be the voltage to be
produced by the capacitive potential divider with capacitance values C1 and C2
and L the value of tuning inductor. The standardized VT secondary voltage is 110
volts (L-L).
Here specification for phase angle error b is 40 minutes variation in frequency
can be upto Df 3Hz . Phase angle error for change in w by Dw in the above
equation circuit, is given by
1
( L 2 )Dw
w C
1
At tuning frequency w 2
LC
Substituting w 1 LC
2
747.2 H
1 1
C1 C 2
w 2 L (3/ 4) 2 747.2
1.3610 -2 F
3) V2 6.6kV
3 �(6.6 �103 )2
Rb
'
150
87.1210 4
b �Rb' 0.01164 �87.12 �104
L
2 �Dw 2 �2p �3
269H ,
C1 C 2 3.7710 -2 F
4) V2 3.3kV
3 �(3.3 �103 ) 2
Rb'
150
21.7810 4
b �Rb' 0.01164 �21.78 �104
L
2 �Dw 2 �2p �3
67.25 H
C1 C2 0.151 F
The values of L, C1 C 2 for different values of V2 are tabulated below.
V2 L C1 C 2
33kV 6722.2H 0.00151 F
11kV 747.2H 0.0136 F
6.6kV 269H 0.0377 F
3.3kV 67.25H 0.151 F
From the above table it is clear that smaller the value of V 2, the smaller is the
value of L and higher the value of C 1 and C2 for tuning condition. If we select too low
value of V2 and L then capacitance values will be beyond available limits, and if we
select higher value of V2 and L, then CCVT and inductor will become bulky. So a
compromise is necessary and let us select V2 = 6.6kV
For V2 = 6.6kV
L = 269H
C1 C 2 0.0377 F
V C1 C 2
Now,
V2 C1
13210 3 0.037710 -6
36.610 3
C1
0.0377 36.610 3 10 -6 F
C1
13210 3
0.0033F
188
C 2 0.0344F
In this design, we explained the basic concept for CCVT design and we assumed
the transformer to be ideal. But in actual design practice the value of magnetizing
impedance of transformer, resistance of reactor etc have to be taken into account,
as ratio error a and phase angle error b will also get affected by these values.
20. Diagram
The equivalent circuit of a CCVT is shown in fig 8.3. The values of C 1 and C2 are
0.0018 F and 0.018 F respectively. Tuning inductor has an inductance of
497H and resistance of 4620 .
Xm of the 6.6kV VT is 1M , core loss = 20 watts per phase, VA burden =
150VA per phase. Value of Cm for compensating the current drawn by m is equal
to 3.18310 -9 F .
(bb) Verify the appropriateness of choice of L and Cm.
Ans: If C1 0.0018F and C 2 0.0186F then the value L of tuning inductor
is given by
1
L 2
w (C1 C 2 )
where w 2p f and f = tuning frequency
1
L
(2p �50) (0.0018 0.0186) �10-6
2
1
Xm
w Cm
1 1
Cm
w X m (2p �50) �� 1 106
3.183 �10-9 F
The value is also same as the selected value of Cm Hence the selection of both L
and Cm is appropriate.
(dd) If the frequency drops from 50Hz to 47Hz, what would be the values of
ratio error and phase angle error?
Ans: Core loss = 20w
V22
20W
Rm
189
V22 (6600) 2
Rm
20 20
2.18 �10
6
6600 0
A
260874.14 -2.44�
VT I th �Z
6600 0
�256147.5 1.82�
260874.14 -2.44�
6480.42 4.26�
(6600 - 6480.42)
Hence % ratio error �100
6600
=1.81%
Phase angle error = 4.26�
V2 6.6kV
r a w2 a 2
M
d 2i R di 1 1 R
t �t0 2
i0 wn 2p �50 2 Iwn
dt L dt LCeq LC L
d 2i
2
2a wn wn2i 0 a < 1
dt
Lec – 8
1
2p �50 2zw R d i 2zw w 2i 0 z wn z < 1
2
wn
LCeq n
L dt 2 n n
-t V
t I 0 - m sin(wt0 f - q ) f q
e | Z line |
191
Example 1:
d
192
Answer:
Based on the criteria that the CT can deliver 20 times rated secondary current
without exceeding a 10% ratio error, the maximum fault current will be 24000A.
However, with a 2.0Ω burden, this will result in a voltage below the knee point of the CT
and, as a practical matter, it will be within 10% accuracy at higher currents. This can only
be accurately determined from excitation or ratio correction curves and not from the
accuracy classification. For example, a CT with characteristics shown in above figure
will produce between 180-240A without exceeding the 10% ratio error, depending on the
power factor of the 2.0Ω burden.
Example 2:
A 1200/5, C400 CT is connected on the 1000/5 tap. What is the maximum secondary
burden that can be used and still maintain rated accuracy at 20 times rated symmetrical
secondary current?
Answer:
Since the secondary voltage capability is directly proportional to the connected tap, the
CT will support a voltage of 1000/1200 400V or 333V. Twenty times the rated
secondary current is 100A. Therefore, the maximum burden is 333V/100A or 3.33 Ω
Example 3:
Assume that secondary burden in a relay circuit is 5Ω. The relay setting is 2A and the CT
ratio is 300/5. Using above figure, calculate the primary current required to operate the
relay?
Answer:
193
N (I E I S )
= 300/5(0.04+2) A=122A
Example 4:
A relay is expected to operate for a 7000A primary current. The CT ratio is 600/5.
Secondary burden is 3.5 Ω. What is the error for the CT shown in above figure?
Answer:
The total secondary fault current is (7000/600) 5=58A. Assume that exciting current is
negligible.
VS I S ( R B RS )
= 58(3.5+0.31)
= 221V
The exciting current will not be negligible, however, and the calculation will not be
iterated.
Lec – 7
N1 RI 0 Vm N1 R Vm Vm N1 N1 RI 0 -tt N1 I 0 -tt
fdcmax t t N1 Rt v2 (t )
dc
e i2 e
N 22 | Z line | N 22 | Z line | | Z line | N 22 N2 N2
t -t -t
1 N1 RI 0 t N1 RI 0
f (t ) - f (0) t (1 - e ) f (t ) f (0) t (1 - e t )
N2 �
v2 dt 2 2
0
N 2 N 2
Lec- 7
194
Vm N1 d V2
v2ac (t ) R sin(wt f - q ) jw f ac
| Z line | N 2 dt jw N 2
RVm N1 p RVm N1
fac (t ) sin(wt f - q - ) facmax
w | Z line | N 2
2
2 w | Z line | N 22
Vm N1
Rt
RVm N1 N1 RVmt | Z line | N 22 wL X
facmax fdcmax 2 1 1 wt 1 line 1 line
w | Z line | N 2 N 2 | Z line |
2
Vm N1 R Rline Rline
| Z line | N 2 w
2
X
1
R
Lec-6
Lec – 5
Ip Ip
- IS Ip IE - IS
N - I I �100 N 98�45�
�100 N S E
IS �100
IS IS
Lec - 9
Vth - VT 1 1
�100 )Dw w02
(3f ) ( L w02 1 LC < f Df �3Hz
Vth w02
LC
1t di dv di 1 d 2i
v(t ) Ri �
Ceq
-�
idt L
dt dt
R
dt Ceq
i L 2 w0
dt
d 1 1 1
DVL - DVC jI (w L - ) Dw I (2 2 )Dw w02 I ( L L )Dw
dw wCeq w0 Ceq LCeq
195
| VL - VC | 2 LI Dw 2 LI 2 LDw
j 2 LI Dw (DVL - DVC ) tan b 2 2 2 � 2p f Lm 106
| VR | a Rb I a Rb a Rb
106
Lm 3183.1H
2p
source. The fault strikes at time t t 0 . This can be simulated by closing the switch at t t1
196
R jwL or Z q models the line impedance. The fault current in the line is given by
i (t ) 0 0 t t0
t -t 0
V sin(w t f - q ) -
t
t t0
i (t ) m I 0e
|Z |
Where τ is the time constant of the line τ =L/R. The fault current has two components in
it. The first component models the steady state sinusoidal ac response while the second current
is the dc offset current due to the presence of inductive component in the circuit. Recall that
current in an inductance can not change instantaneously. As t ∞, the instantaneous dc
It is more or less obvious that, dc offset is not seen in the waveform after 5 time constants.
The value of I0 can be worked out by setting the current at t t o to zero.
This implies that
Vm
I0 - sin(wt 0 - q )
Z
197
Thus
t -t 0
Vm V -( )
i (t ) sin(wt f - q ) - m sin(wt f - q )e t
Z Z
fig.2
It can be seen that severity of dc offset component in fault current is maximum when
a) f q
p
b) wt 0
2
198
p 1
For example, if angle of transmission line is 800, then with f = 800 & t 0 =
2 2p 50 200
V
sec = 5msec, the severity of dc offset current would equal I 0 Z , which is also the peak
m
We now plan to show that CT can saturate on dc offset current. Also, we plan to show
that the resulting distortions in the CT secondary current can be un-acceptably high. While
doing this analysis, we will neglect ac symmetrical component. In other words, we rest our
belief in superposition theorem atleast qualitatively and will finally evaluate effect using it
Notice that the current that we are dealing with is non-linear, a rigorous application of super
position theorem is simply out of question.
199
First consider an ideal CT excited by the dc offset current source. An ideal CT will faithfully
replicates primary current waveform on the secondary side. Hence, the secondary current
would be given by
-t
I0 t
i2 (t ) e
N
and the voltage developed across CT secondary would be given by
-t
RI N2
v 2 (t ) 0 e t where N N
N 1
For simplicity, let us assume that the initial flux in the transformer core at t=0 is zero
f ( 0 ) 0 ; Then we can compute the flux in the transformer core by using faraday’s law
df
V2 N 2 ---------(2)
dt
200
t
f (t ) - f (0) v 0
2 dt
RI 0
-t
t 1- e t
N2
-t
LI 0
(1 - e t )
N2
-t
LI 0
f (t ) f (0) (1 - e t )
N2
-t
LI 0
(1 - e t ) ------- (3)
N2
as a consequence of dc offset current,
Thus, flux in the core increases exponentially to a peak value of
f dmax
c
LI 0
N2
as t
L Vm Vm
N Z Z
f dmax
c
Note that unlike ac voltage induced flux, which is sinusoidal, this flux is unidirectional. The ac
voltage induced flux has zero average value. However, dc offset induced does not have this
nice feature. The total flux in ideal CT core is a summation of ac flux and dc flux.
d
The ac flux in the CT core can be obtained by substituting operator by jw . Hence
dt
If v2 (t ) Vm sin(wt f ) , then
Vm p
f ac sin(wt f - )
wN 2 2
The peak value of ac flux is given by
201
Vm
f acmax
wN 2
However Vm R2 I 0
max
R2 I 0max
Hence facmax
wN 2
and peak value of the total flux is given by
Vm LI 0max
facmax f dcmax
wN 2 N2
In practice, if this flux exceeds the knee-point flux in the core (see fig.), then the CT core
will saturate.
As a consequence of CT core saturation, the secondary current would not faithfully replicate
the primary current. Infact, in practice it is observed that CT secondary current is clipped. The
clipping of CT current leads to “blinding” of the relay which cannot function further. Hence,
CT saturation in presence of dc offset current is a serious problem which relay designers have
to face. Note that dc flux accumulates gradually. (Depends upon the transmission line time
constant ( t ). It is apparent that saturation should not occur immediately after the inception of
the fault. Thus, if the relay is fast enough in decision making, it is likely that a relaying
decision would be undertaken before the CT fully saturates. This is another important reason
for increasing the speed of relaying system. For bus-fault protection, where the dc saturation
due to dc offset current can be a significant contributing factor, quarter cycle operations *****
202
specifically are imposed. Similarly, a distance relay is expected to operate within ½-1 cycle
time.
CT oversizing factors
Typically, an efficient design of transformer would correspond to choosing the core cross
section such that f mac should be near the knee point of B-H curve. One obvious way of
avoiding the CT saturation on dc flux is to oversize the core so that for flux (f acmax f dcmax ) , the
(f acmax f dcmax )
corresponding B is below the knee-point. Hence, the factor is called core-
f acmax
oversizing factor.
f dcmax
Core-oversizing factor = 1
f acmax
LI o N 2
1
RI 0 wN 2
wL
1
R
X
1
R
Note that X/R in above equation is the transmission line X/R ratio. For a 220KV line X/R 10.
This would imply that transformer core should be oversized by a factor of 11. For a 400KV
line, typical value of X/R 20. This would imply an oversizing required of about 21 times the
usual design. Clearly this high amount of oversizing is not practical. Thus, the important
conclusion is that, protection engineers have to live with the saturation problem.
Cautions in CT selection:
While choosing a CT for a particular application, it is necessary to observe following
precautions.
41. The CT rating and continuous load current should match. For example, if max load
current is 90A, a 100:5 Ct may be acceptable but 50:5 is not acceptable.
203
42. The maximum fault current should be less than 20 times the CT rated current. for
example 100:5 CT can be used, so long as burden on the CT & maximum primary fault
current is below 2000A.
43. The voltage rating of CT should be compatible. For example, 100:5 C100 would give
linear response, upto 20 times rated current provided CT burden is kept
below(100/20*5=1 Ω). With 2 Ω burden, this CT can be used only if maximum current
is limited to 1000A.
44. Parallel of CT’s e.g. in differential protection, or with SLG fault can create significant
errors in CT performance. One should in general ascertain that magnetizing current is
kept much below the pick up value.
Following example, illustrates this point
Exercise problems:
If the current ratio is adequate for a protection, but CT burden is high; then the
performance of CT may deteriorate due to large magnetizing current and/or saturation problem.
The CT performance can be improved by connecting the CT’s in series.
21) Show the dotted terminals for correct secondary series connection
22) What is the VA of CT in fig (a) & (b) respectively?
31) Electromechanical relays tend to saturate at high currents. This reduces the relay burden
on CT, and so that the CT performance at moderately high currents may be considered
better than at relay’s rated burden at 5A.
32) Use of instantaneous over current relays has the potential to overcome this problem of
saturation of CT’s
204
33) Differential protection can operate on external faults due to the un equal saturation of
CT’s
Lecture-6
Examples
16. If a 300:5 class C CT is connected to a meter with resistance R I 1 and
secondary current in the CT is 4.5A find out the primary current voltage
developed across the meter and % rate error. Lead wire resistance R L 0.02
secondary resistance RS of a 300/5 CT 0.15
Diagram
R I 1 , R L 0.02 RS 0.15 I S 4.5 A
Total secondary resistance RT R I R L RS
1.17
Secondary voltage I S RT
4.5 1.17
5.265V
From Fig 5.7,
Exciting current IE for 5.265V
= 0.03A
Turns ratio N = 300/5 = 60
I p N (I S I E )
= 60(4.5 + 0.03)
= 271.8A
Voltage across meter I S R I
4.5 1 = 4.5V
IE 0.03
Ratio error 100 100
IS 4.5
= 0.67%
Rb
205
Lecture – 8
Examples
21. Design a CCVT for a 132kV transmission line using the following data.
Resistive Burden (3f )-150VA
Df 3Hz , phase angle error b = 40 min
Consider 4 choices of V2 as 33kV, 11kV, 6.6kV and 3.3kV
Diagram 1 Diagram 2
Transmission line voltage V = 132kV. Suppose V 2 (P_N) be the voltage to be
produced by the capacitive potential divider with capacitance values C1 and C2
and L the value of tuning inductor. The standardized VT secondary voltage is 110
volts (L-L).
Here specification for phase angle error b is 40 minutes variation in frequency
can be upto Df 3Hz . Phase angle error for change in w by Dw in the above
equation circuit, is given by
1
( L 2 )Dw
w C
1
At tuning frequency w 2
LC
Substituting w 1 LC
2
747.2 H
1 1
C1 C 2
w 2 L (3/ 4) 2 747.2
1.3610 -2 F
3) V2 6.6kV
3 �(6.6 �103 )2
Rb
'
150
87.1210 4
b �Rb' 0.01164 �87.12 �104
L
2 �Dw 2 �2p �3
269H ,
C1 C 2 3.7710 -2 F
4) V2 3.3kV
3 �(3.3 �103 ) 2
Rb'
150
21.7810 4
b �Rb' 0.01164 �21.78 �104
L
2 �Dw 2 �2p �3
67.25 H
C1 C2 0.151 F
The values of L, C1 C 2 for different values of V2 are tabulated below.
V2 L C1 C 2
33kV 6722.2H 0.00151 F
11kV 747.2H 0.0136 F
6.6kV 269H 0.0377 F
3.3kV 67.25H 0.151 F
From the above table it is clear that smaller the value of V 2, the smaller is the
value of L and higher the value of C 1 and C2 for tuning condition. If we select too low
value of V2 and L then capacitance values will be beyond available limits, and if we
select higher value of V2 and L, then CCVT and inductor will become bulky. So a
compromise is necessary and let us select V2 = 6.6kV
For V2 = 6.6kV
L = 269H
C1 C 2 0.0377 F
V C1 C 2
Now,
V2 C1
13210 3 0.037710 -6
36.610 3
C1
0.0377 36.610 3 10 -6 F
C1
13210 3
0.0033F
207
C 2 0.0344F
In this design, we explained the basic concept for CCVT design and we assumed
the transformer to be ideal. But in actual design practice the value of magnetizing
impedance of transformer, resistance of reactor etc have to be taken into account,
as ratio error a and phase angle error b will also get affected by these values.
22. Diagram
The equivalent circuit of a CCVT is shown in fig 8.3. The values of C 1 and C2 are
0.0018 F and 0.018 F respectively. Tuning inductor has an inductance of
497H and resistance of 4620 .
Xm of the 6.6kV VT is 1M , core loss = 20 watts per phase, VA burden =
150VA per phase. Value of Cm for compensating the current drawn by m is equal
to 3.18310 -9 F .
(ee) Verify the appropriateness of choice of L and Cm.
Ans: If C1 0.0018F and C 2 0.0186F then the value L of tuning inductor
is given by
1
L 2
w (C1 C 2 )
where w 2p f and f = tuning frequency
1
L
(2p �50) (0.0018 0.0186) �10-6
2
1
Xm
w Cm
1 1
Cm
w X m (2p �50) �� 1 106
3.183 �10-9 F
The value is also same as the selected value of Cm Hence the selection of both L
and Cm is appropriate.
(gg) If the frequency drops from 50Hz to 47Hz, what would be the values of
ratio error and phase angle error?
Ans: Core loss = 20w
V22
20W
Rm
208
V22 (6600) 2
Rm
20 20
2.18 �10
6
6600 0
A
260874.14 -2.44�
VT I th �Z
6600 0
�256147.5 1.82�
260874.14 -2.44�
6480.42 4.26�
(6600 - 6480.42)
Hence % ratio error �100
6600
=1.81%
Phase angle error = 4.26�
V2 6.6kV
r a w2 a 2
M
d 2i R di 1 1 R
t �t0 2
i0 wn 2p �50 2 Iwn
dt L dt LCeq LC L
d 2i
2
2a wn wn2i 0 a < 1
dt
Lec – 8
1
2p �50 2zw R d i 2zw w 2i 0 z wn z < 1
2
wn
LCeq n
L dt 2 n n
-t V
t I 0 - m sin(wt0 f - q ) f q
e | Z line |
210
Example 1:
d
211
Answer:
Based on the criteria that the CT can deliver 20 times rated secondary current
without exceeding a 10% ratio error, the maximum fault current will be 24000A.
However, with a 2.0Ω burden, this will result in a voltage below the knee point of the CT
and, as a practical matter, it will be within 10% accuracy at higher currents. This can only
be accurately determined from excitation or ratio correction curves and not from the
accuracy classification. For example, a CT with characteristics shown in above figure
will produce between 180-240A without exceeding the 10% ratio error, depending on the
power factor of the 2.0Ω burden.
Example 2:
A 1200/5, C400 CT is connected on the 1000/5 tap. What is the maximum secondary
burden that can be used and still maintain rated accuracy at 20 times rated symmetrical
secondary current?
Answer:
Since the secondary voltage capability is directly proportional to the connected tap, the
CT will support a voltage of 1000/1200 400V or 333V. Twenty times the rated
secondary current is 100A. Therefore, the maximum burden is 333V/100A or 3.33 Ω
Example 3:
Assume that secondary burden in a relay circuit is 5Ω. The relay setting is 2A and the CT
ratio is 300/5. Using above figure, calculate the primary current required to operate the
relay?
Answer:
212
N (I E I S )
= 300/5(0.04+2) A=122A
Example 4:
A relay is expected to operate for a 7000A primary current. The CT ratio is 600/5.
Secondary burden is 3.5 Ω. What is the error for the CT shown in above figure?
Answer:
The total secondary fault current is (7000/600) 5=58A. Assume that exciting current is
negligible.
VS I S ( R B RS )
= 58(3.5+0.31)
= 221V
The exciting current will not be negligible, however, and the calculation will not be
iterated.
Lec – 7
N1 RI 0 Vm N1 R Vm Vm N1 N1 RI 0 -tt N1 I 0 -tt
fdcmax t t N1 Rt v2 (t )
dc
e i2 e
N 22 | Z line | N 22 | Z line | | Z line | N 22 N2 N2
t -t -t
1 N1 RI 0 t N1 RI 0
f (t ) - f (0) t (1 - e ) f (t ) f (0) t (1 - e t )
N2 �
v2 dt 2 2
0
N 2 N 2
Lec- 7
213
Vm N1 d V2
v2ac (t ) R sin(wt f - q ) jw f ac
| Z line | N 2 dt jw N 2
RVm N1 p RVm N1
fac (t ) sin(wt f - q - ) facmax
w | Z line | N 2
2
2 w | Z line | N 22
Vm N1
Rt
RVm N1 N1 RVmt | Z line | N 22 wL X
facmax fdcmax 2 1 1 wt 1 line 1 line
w | Z line | N 2 N 2 | Z line |
2
Vm N1 R Rline Rline
| Z line | N 2 w
2
X
1
R
Lec-6
Lec – 5
Ip Ip
- IS Ip IE - IS
N - I I �100 N 98�45�
�100 N S E
IS �100
IS IS
Lec - 9
Vth - VT 1 1
�100 )Dw w02
(3f ) ( L w02 1 LC < f Df �3Hz
Vth w02
LC
1t di dv di 1 d 2i
v(t ) Ri �
Ceq
-�
idt L
dt dt
R
dt Ceq
i L 2 w0
dt
d 1 1 1
DVL - DVC jI (w L - ) Dw I (2 2 )Dw w02 I ( L L )Dw
dw wCeq w0 Ceq LCeq
214
| VL - VC | 2 LI Dw 2 LI 2 LDw
j 2 LI Dw (DVL - DVC ) tan b 2 2 2 � 2p f Lm 106
| VR | a Rb I a Rb a Rb
106
Lm 3183.1H
2p
source. The fault strikes at time t t 0 . This can be simulated by closing the switch at t t1
215
R jwL or Z q models the line impedance. The fault current in the line is given by
i (t ) 0 0 t t0
t -t 0
V sin(w t f - q ) -
t
t t0
i (t ) m I 0e
|Z |
Where τ is the time constant of the line τ =L/R. The fault current has two components in
it. The first component models the steady state sinusoidal ac response while the second current
is the dc offset current due to the presence of inductive component in the circuit. Recall that
current in an inductance can not change instantaneously. As t ∞, the instantaneous dc
It is more or less obvious that, dc offset is not seen in the waveform after 5 time constants.
The value of I0 can be worked out by setting the current at t t o to zero.
This implies that
Vm
I0 - sin(wt 0 - q )
Z
216
Thus
t -t 0
Vm V -( )
i (t ) sin(wt f - q ) - m sin(wt f - q )e t
Z Z
fig.2
It can be seen that severity of dc offset component in fault current is maximum when
a) f q
p
b) wt 0
2
217
p 1
For example, if angle of transmission line is 800, then with f = 800 & t 0 =
2 2p 50 200
V
sec = 5msec, the severity of dc offset current would equal I 0 Z , which is also the peak
m
We now plan to show that CT can saturate on dc offset current. Also, we plan to show
that the resulting distortions in the CT secondary current can be un-acceptably high. While
doing this analysis, we will neglect ac symmetrical component. In other words, we rest our
belief in superposition theorem atleast qualitatively and will finally evaluate effect using it
Notice that the current that we are dealing with is non-linear, a rigorous application of super
position theorem is simply out of question.
218
First consider an ideal CT excited by the dc offset current source. An ideal CT will faithfully
replicates primary current waveform on the secondary side. Hence, the secondary current
would be given by
-t
I0 t
i2 (t ) e
N
and the voltage developed across CT secondary would be given by
-t
RI N2
v 2 (t ) 0 e t where N N
N 1
For simplicity, let us assume that the initial flux in the transformer core at t=0 is zero
f ( 0 ) 0 ; Then we can compute the flux in the transformer core by using faraday’s law
df
V2 N 2 ---------(2)
dt
219
t
f (t ) - f (0) v 0
2 dt
RI 0
-t
t 1- e t
N2
-t
LI 0
(1 - e t )
N2
-t
LI 0
f (t ) f (0) (1 - e t )
N2
-t
LI 0
(1 - e t ) ------- (3)
N2
as a consequence of dc offset current,
Thus, flux in the core increases exponentially to a peak value of
f dmax
c
LI 0
N2
as t
L Vm Vm
N Z Z
f dmax
c
Note that unlike ac voltage induced flux, which is sinusoidal, this flux is unidirectional. The ac
voltage induced flux has zero average value. However, dc offset induced does not have this
nice feature. The total flux in ideal CT core is a summation of ac flux and dc flux.
d
The ac flux in the CT core can be obtained by substituting operator by jw . Hence
dt
If v2 (t ) Vm sin(wt f ) , then
Vm p
f ac sin(wt f - )
wN 2 2
The peak value of ac flux is given by
220
Vm
f acmax
wN 2
However Vm R2 I 0
max
R2 I 0max
Hence facmax
wN 2
and peak value of the total flux is given by
Vm LI 0max
facmax f dcmax
wN 2 N2
In practice, if this flux exceeds the knee-point flux in the core (see fig.), then the CT core
will saturate.
As a consequence of CT core saturation, the secondary current would not faithfully replicate
the primary current. Infact, in practice it is observed that CT secondary current is clipped. The
clipping of CT current leads to “blinding” of the relay which cannot function further. Hence,
CT saturation in presence of dc offset current is a serious problem which relay designers have
to face. Note that dc flux accumulates gradually. (Depends upon the transmission line time
constant ( t ). It is apparent that saturation should not occur immediately after the inception of
the fault. Thus, if the relay is fast enough in decision making, it is likely that a relaying
decision would be undertaken before the CT fully saturates. This is another important reason
for increasing the speed of relaying system. For bus-fault protection, where the dc saturation
due to dc offset current can be a significant contributing factor, quarter cycle operations *****
221
specifically are imposed. Similarly, a distance relay is expected to operate within ½-1 cycle
time.
CT oversizing factors
Typically, an efficient design of transformer would correspond to choosing the core cross
section such that f mac should be near the knee point of B-H curve. One obvious way of
avoiding the CT saturation on dc flux is to oversize the core so that for flux (f acmax f dcmax ) , the
(f acmax f dcmax )
corresponding B is below the knee-point. Hence, the factor is called core-
f acmax
oversizing factor.
f dcmax
Core-oversizing factor = 1
f acmax
LI o N 2
1
RI 0 wN 2
wL
1
R
X
1
R
Note that X/R in above equation is the transmission line X/R ratio. For a 220KV line X/R 10.
This would imply that transformer core should be oversized by a factor of 11. For a 400KV
line, typical value of X/R 20. This would imply an oversizing required of about 21 times the
usual design. Clearly this high amount of oversizing is not practical. Thus, the important
conclusion is that, protection engineers have to live with the saturation problem.
Cautions in CT selection:
While choosing a CT for a particular application, it is necessary to observe following
precautions.
45. The CT rating and continuous load current should match. For example, if max load
current is 90A, a 100:5 Ct may be acceptable but 50:5 is not acceptable.
222
46. The maximum fault current should be less than 20 times the CT rated current. for
example 100:5 CT can be used, so long as burden on the CT & maximum primary fault
current is below 2000A.
47. The voltage rating of CT should be compatible. For example, 100:5 C100 would give
linear response, upto 20 times rated current provided CT burden is kept
below(100/20*5=1 Ω). With 2 Ω burden, this CT can be used only if maximum current
is limited to 1000A.
48. Parallel of CT’s e.g. in differential protection, or with SLG fault can create significant
errors in CT performance. One should in general ascertain that magnetizing current is
kept much below the pick up value.
Following example, illustrates this point
Exercise problems:
If the current ratio is adequate for a protection, but CT burden is high; then the
performance of CT may deteriorate due to large magnetizing current and/or saturation problem.
The CT performance can be improved by connecting the CT’s in series.
23) Show the dotted terminals for correct secondary series connection
24) What is the VA of CT in fig (a) & (b) respectively?
34) Electromechanical relays tend to saturate at high currents. This reduces the relay burden
on CT, and so that the CT performance at moderately high currents may be considered
better than at relay’s rated burden at 5A.
35) Use of instantaneous over current relays has the potential to overcome this problem of
saturation of CT’s
223
36) Differential protection can operate on external faults due to the un equal saturation of
CT’s
Lecture-6
Examples
17. If a 300:5 class C CT is connected to a meter with resistance R I 1 and
secondary current in the CT is 4.5A find out the primary current voltage
developed across the meter and % rate error. Lead wire resistance R L 0.02
secondary resistance RS of a 300/5 CT 0.15
Diagram
R I 1 , R L 0.02 RS 0.15 I S 4.5 A
Total secondary resistance RT R I R L RS
1.17
Secondary voltage I S RT
4.5 1.17
5.265V
From Fig 5.7,
Exciting current IE for 5.265V
= 0.03A
Turns ratio N = 300/5 = 60
I p N (I S I E )
= 60(4.5 + 0.03)
= 271.8A
Voltage across meter I S R I
4.5 1 = 4.5V
IE 0.03
Ratio error 100 100
IS 4.5
= 0.67%
Rb
224
Lecture – 8
Examples
23. Design a CCVT for a 132kV transmission line using the following data.
Resistive Burden (3f )-150VA
Df 3Hz , phase angle error b = 40 min
Consider 4 choices of V2 as 33kV, 11kV, 6.6kV and 3.3kV
Diagram 1 Diagram 2
Transmission line voltage V = 132kV. Suppose V 2 (P_N) be the voltage to be
produced by the capacitive potential divider with capacitance values C1 and C2
and L the value of tuning inductor. The standardized VT secondary voltage is 110
volts (L-L).
Here specification for phase angle error b is 40 minutes variation in frequency
can be upto Df 3Hz . Phase angle error for change in w by Dw in the above
equation circuit, is given by
1
( L 2 )Dw
w C
1
At tuning frequency w 2
LC
Substituting w 1 LC
2
747.2 H
1 1
C1 C 2
w 2 L (3/ 4) 2 747.2
1.3610 -2 F
3) V2 6.6kV
3 �(6.6 �103 )2
Rb
'
150
87.1210 4
b �Rb' 0.01164 �87.12 �104
L
2 �Dw 2 �2p �3
269H ,
C1 C 2 3.7710 -2 F
4) V2 3.3kV
3 �(3.3 �103 ) 2
Rb'
150
21.7810 4
b �Rb' 0.01164 �21.78 �104
L
2 �Dw 2 �2p �3
67.25 H
C1 C2 0.151 F
The values of L, C1 C 2 for different values of V2 are tabulated below.
V2 L C1 C 2
33kV 6722.2H 0.00151 F
11kV 747.2H 0.0136 F
6.6kV 269H 0.0377 F
3.3kV 67.25H 0.151 F
From the above table it is clear that smaller the value of V 2, the smaller is the
value of L and higher the value of C 1 and C2 for tuning condition. If we select too low
value of V2 and L then capacitance values will be beyond available limits, and if we
select higher value of V2 and L, then CCVT and inductor will become bulky. So a
compromise is necessary and let us select V2 = 6.6kV
For V2 = 6.6kV
L = 269H
C1 C 2 0.0377 F
V C1 C 2
Now,
V2 C1
13210 3 0.037710 -6
36.610 3
C1
0.0377 36.610 3 10 -6 F
C1
13210 3
0.0033F
226
C 2 0.0344F
In this design, we explained the basic concept for CCVT design and we assumed
the transformer to be ideal. But in actual design practice the value of magnetizing
impedance of transformer, resistance of reactor etc have to be taken into account,
as ratio error a and phase angle error b will also get affected by these values.
24. Diagram
The equivalent circuit of a CCVT is shown in fig 8.3. The values of C 1 and C2 are
0.0018 F and 0.018 F respectively. Tuning inductor has an inductance of
497H and resistance of 4620 .
Xm of the 6.6kV VT is 1M , core loss = 20 watts per phase, VA burden =
150VA per phase. Value of Cm for compensating the current drawn by m is equal
to 3.18310 -9 F .
(hh) Verify the appropriateness of choice of L and Cm.
Ans: If C1 0.0018F and C 2 0.0186F then the value L of tuning inductor
is given by
1
L 2
w (C1 C 2 )
where w 2p f and f = tuning frequency
1
L
(2p �50) (0.0018 0.0186) �10-6
2
1
Xm
w Cm
1 1
Cm
w X m (2p �50) �� 1 106
3.183 �10-9 F
The value is also same as the selected value of Cm Hence the selection of both L
and Cm is appropriate.
(jj) If the frequency drops from 50Hz to 47Hz, what would be the values of ratio
error and phase angle error?
Ans: Core loss = 20w
V22
20W
Rm
227
V22 (6600) 2
Rm
20 20
2.18 �10
6
6600 0
A
260874.14 -2.44�
VT I th �Z
6600 0
�256147.5 1.82�
260874.14 -2.44�
6480.42 4.26�
(6600 - 6480.42)
Hence % ratio error �100
6600
=1.81%
Phase angle error = 4.26�
V2 6.6kV
r a w2 a 2
M
d 2i R di 1 1 R
t �t0 2
i0 wn 2p �50 2 Iwn
dt L dt LCeq LC L
d 2i
2
2a wn wn2i 0 a < 1
dt
Lec – 8
1
2p �50 2zw R d i 2zw w 2i 0 z wn z < 1
2
wn
LCeq n
L dt 2 n n
-t V
t I 0 - m sin(wt0 f - q ) f q
e | Z line |
229
Example 1:
d
230
Answer:
Based on the criteria that the CT can deliver 20 times rated secondary current
without exceeding a 10% ratio error, the maximum fault current will be 24000A.
However, with a 2.0Ω burden, this will result in a voltage below the knee point of the CT
and, as a practical matter, it will be within 10% accuracy at higher currents. This can only
be accurately determined from excitation or ratio correction curves and not from the
accuracy classification. For example, a CT with characteristics shown in above figure
will produce between 180-240A without exceeding the 10% ratio error, depending on the
power factor of the 2.0Ω burden.
Example 2:
A 1200/5, C400 CT is connected on the 1000/5 tap. What is the maximum secondary
burden that can be used and still maintain rated accuracy at 20 times rated symmetrical
secondary current?
Answer:
Since the secondary voltage capability is directly proportional to the connected tap, the
CT will support a voltage of 1000/1200 400V or 333V. Twenty times the rated
secondary current is 100A. Therefore, the maximum burden is 333V/100A or 3.33 Ω
Example 3:
Assume that secondary burden in a relay circuit is 5Ω. The relay setting is 2A and the CT
ratio is 300/5. Using above figure, calculate the primary current required to operate the
relay?
Answer:
231
N (I E I S )
= 300/5(0.04+2) A=122A
Example 4:
A relay is expected to operate for a 7000A primary current. The CT ratio is 600/5.
Secondary burden is 3.5 Ω. What is the error for the CT shown in above figure?
Answer:
The total secondary fault current is (7000/600) 5=58A. Assume that exciting current is
negligible.
VS I S ( R B RS )
= 58(3.5+0.31)
= 221V
The exciting current will not be negligible, however, and the calculation will not be
iterated.
Lec – 7
N1 RI 0 Vm N1 R Vm Vm N1 N1 RI 0 -tt N1 I 0 -tt
fdcmax t t N1 Rt v2 (t )
dc
e i2 e
N 22 | Z line | N 22 | Z line | | Z line | N 22 N2 N2
t -t -t
1 N1 RI 0 t N1 RI 0
f (t ) - f (0) t (1 - e ) f (t ) f (0) t (1 - e t )
N2 �
v2 dt 2 2
0
N 2 N 2
Lec- 7
232
Vm N1 d V2
v2ac (t ) R sin(wt f - q ) jw f ac
| Z line | N 2 dt jw N 2
RVm N1 p RVm N1
fac (t ) sin(wt f - q - ) facmax
w | Z line | N 2
2
2 w | Z line | N 22
Vm N1
Rt
RVm N1 N1 RVmt | Z line | N 22 wL X
facmax fdcmax 2 1 1 wt 1 line 1 line
w | Z line | N 2 N 2 | Z line |
2
Vm N1 R Rline Rline
| Z line | N 2 w
2
X
1
R
Lec-6
Lec – 5
Ip Ip
- IS Ip IE - IS
N - I I �100 N 98�45�
�100 N S E
IS �100
IS IS
Lec - 9
Vth - VT 1 1
�100 )Dw w02
(3f ) ( L w02 1 LC < f Df �3Hz
Vth w02
LC
1t di dv di 1 d 2i
v(t ) Ri �
Ceq
-�
idt L
dt dt
R
dt Ceq
i L 2 w0
dt
d 1 1 1
DVL - DVC jI (w L - ) Dw I (2 2 )Dw w02 I ( L L )Dw
dw wCeq w0 Ceq LCeq
233
| VL - VC | 2 LI Dw 2 LI 2 LDw
j 2 LI Dw (DVL - DVC ) tan b 2 2 2 � 2p f Lm 106
| VR | a Rb I a Rb a Rb
106
Lm 3183.1H
2p
source. The fault strikes at time t t 0 . This can be simulated by closing the switch at t t1
234
R jwL or Z q models the line impedance. The fault current in the line is given by
i (t ) 0 0 t t0
t -t 0
V sin(w t f - q ) -
t
t t0
i (t ) m I 0e
|Z |
Where τ is the time constant of the line τ =L/R. The fault current has two components in
it. The first component models the steady state sinusoidal ac response while the second current
is the dc offset current due to the presence of inductive component in the circuit. Recall that
current in an inductance can not change instantaneously. As t ∞, the instantaneous dc
It is more or less obvious that, dc offset is not seen in the waveform after 5 time constants.
The value of I0 can be worked out by setting the current at t t o to zero.
This implies that
Vm
I0 - sin(wt 0 - q )
Z
235
Thus
t -t 0
Vm V -( )
i (t ) sin(wt f - q ) - m sin(wt f - q )e t
Z Z
fig.2
It can be seen that severity of dc offset component in fault current is maximum when
a) f q
p
b) wt 0
2
236
p 1
For example, if angle of transmission line is 800, then with f = 800 & t 0 =
2 2p 50 200
V
sec = 5msec, the severity of dc offset current would equal I 0 Z , which is also the peak
m
We now plan to show that CT can saturate on dc offset current. Also, we plan to show
that the resulting distortions in the CT secondary current can be un-acceptably high. While
doing this analysis, we will neglect ac symmetrical component. In other words, we rest our
belief in superposition theorem atleast qualitatively and will finally evaluate effect using it
Notice that the current that we are dealing with is non-linear, a rigorous application of super
position theorem is simply out of question.
237
First consider an ideal CT excited by the dc offset current source. An ideal CT will faithfully
replicates primary current waveform on the secondary side. Hence, the secondary current
would be given by
-t
I0 t
i2 (t ) e
N
and the voltage developed across CT secondary would be given by
-t
RI N2
v 2 (t ) 0 e t where N N
N 1
For simplicity, let us assume that the initial flux in the transformer core at t=0 is zero
f ( 0 ) 0 ; Then we can compute the flux in the transformer core by using faraday’s law
df
V2 N 2 ---------(2)
dt
238
t
f (t ) - f (0) v 0
2 dt
RI 0
-t
t 1- e t
N2
-t
LI 0
(1 - e t )
N2
-t
LI 0
f (t ) f (0) (1 - e t )
N2
-t
LI 0
(1 - e t ) ------- (3)
N2
as a consequence of dc offset current,
Thus, flux in the core increases exponentially to a peak value of
f dmax
c
LI 0
N2
as t
L Vm Vm
N Z Z
f dmax
c
Note that unlike ac voltage induced flux, which is sinusoidal, this flux is unidirectional. The ac
voltage induced flux has zero average value. However, dc offset induced does not have this
nice feature. The total flux in ideal CT core is a summation of ac flux and dc flux.
d
The ac flux in the CT core can be obtained by substituting operator by jw . Hence
dt
If v2 (t ) Vm sin(wt f ) , then
Vm p
f ac sin(wt f - )
wN 2 2
The peak value of ac flux is given by
239
Vm
f acmax
wN 2
However Vm R2 I 0
max
R2 I 0max
Hence facmax
wN 2
and peak value of the total flux is given by
Vm LI 0max
facmax f dcmax
wN 2 N2
In practice, if this flux exceeds the knee-point flux in the core (see fig.), then the CT core
will saturate.
As a consequence of CT core saturation, the secondary current would not faithfully replicate
the primary current. Infact, in practice it is observed that CT secondary current is clipped. The
clipping of CT current leads to “blinding” of the relay which cannot function further. Hence,
CT saturation in presence of dc offset current is a serious problem which relay designers have
to face. Note that dc flux accumulates gradually. (Depends upon the transmission line time
constant ( t ). It is apparent that saturation should not occur immediately after the inception of
the fault. Thus, if the relay is fast enough in decision making, it is likely that a relaying
decision would be undertaken before the CT fully saturates. This is another important reason
for increasing the speed of relaying system. For bus-fault protection, where the dc saturation
due to dc offset current can be a significant contributing factor, quarter cycle operations *****
240
specifically are imposed. Similarly, a distance relay is expected to operate within ½-1 cycle
time.
CT oversizing factors
Typically, an efficient design of transformer would correspond to choosing the core cross
section such that f mac should be near the knee point of B-H curve. One obvious way of
avoiding the CT saturation on dc flux is to oversize the core so that for flux (f acmax f dcmax ) , the
(f acmax f dcmax )
corresponding B is below the knee-point. Hence, the factor is called core-
f acmax
oversizing factor.
f dcmax
Core-oversizing factor = 1
f acmax
LI o N 2
1
RI 0 wN 2
wL
1
R
X
1
R
Note that X/R in above equation is the transmission line X/R ratio. For a 220KV line X/R 10.
This would imply that transformer core should be oversized by a factor of 11. For a 400KV
line, typical value of X/R 20. This would imply an oversizing required of about 21 times the
usual design. Clearly this high amount of oversizing is not practical. Thus, the important
conclusion is that, protection engineers have to live with the saturation problem.
Cautions in CT selection:
While choosing a CT for a particular application, it is necessary to observe following
precautions.
49. The CT rating and continuous load current should match. For example, if max load
current is 90A, a 100:5 Ct may be acceptable but 50:5 is not acceptable.
241
50. The maximum fault current should be less than 20 times the CT rated current. for
example 100:5 CT can be used, so long as burden on the CT & maximum primary fault
current is below 2000A.
51. The voltage rating of CT should be compatible. For example, 100:5 C100 would give
linear response, upto 20 times rated current provided CT burden is kept
below(100/20*5=1 Ω). With 2 Ω burden, this CT can be used only if maximum current
is limited to 1000A.
52. Parallel of CT’s e.g. in differential protection, or with SLG fault can create significant
errors in CT performance. One should in general ascertain that magnetizing current is
kept much below the pick up value.
Following example, illustrates this point
Exercise problems:
If the current ratio is adequate for a protection, but CT burden is high; then the
performance of CT may deteriorate due to large magnetizing current and/or saturation problem.
The CT performance can be improved by connecting the CT’s in series.
25) Show the dotted terminals for correct secondary series connection
26) What is the VA of CT in fig (a) & (b) respectively?
37) Electromechanical relays tend to saturate at high currents. This reduces the relay burden
on CT, and so that the CT performance at moderately high currents may be considered
better than at relay’s rated burden at 5A.
38) Use of instantaneous over current relays has the potential to overcome this problem of
saturation of CT’s
242
39) Differential protection can operate on external faults due to the un equal saturation of
CT’s
Lecture-6
Examples
18. If a 300:5 class C CT is connected to a meter with resistance R I 1 and
secondary current in the CT is 4.5A find out the primary current voltage
developed across the meter and % rate error. Lead wire resistance R L 0.02
secondary resistance RS of a 300/5 CT 0.15
Diagram
R I 1 , R L 0.02 RS 0.15 I S 4.5 A
Total secondary resistance RT R I R L RS
1.17
Secondary voltage I S RT
4.5 1.17
5.265V
From Fig 5.7,
Exciting current IE for 5.265V
= 0.03A
Turns ratio N = 300/5 = 60
I p N (I S I E )
= 60(4.5 + 0.03)
= 271.8A
Voltage across meter I S R I
4.5 1 = 4.5V
IE 0.03
Ratio error 100 100
IS 4.5
= 0.67%
Rb
243
Lecture – 8
Examples
25. Design a CCVT for a 132kV transmission line using the following data.
Resistive Burden (3f )-150VA
Df 3Hz , phase angle error b = 40 min
Consider 4 choices of V2 as 33kV, 11kV, 6.6kV and 3.3kV
Diagram 1 Diagram 2
Transmission line voltage V = 132kV. Suppose V 2 (P_N) be the voltage to be
produced by the capacitive potential divider with capacitance values C1 and C2
and L the value of tuning inductor. The standardized VT secondary voltage is 110
volts (L-L).
Here specification for phase angle error b is 40 minutes variation in frequency
can be upto Df 3Hz . Phase angle error for change in w by Dw in the above
equation circuit, is given by
1
( L 2 )Dw
w C
1
At tuning frequency w 2
LC
Substituting w 1 LC
2
747.2 H
1 1
C1 C 2
w 2 L (3/ 4) 2 747.2
1.3610 -2 F
3) V2 6.6kV
3 �(6.6 �103 )2
Rb
'
150
87.1210 4
b �Rb' 0.01164 �87.12 �104
L
2 �Dw 2 �2p �3
269H ,
C1 C 2 3.7710 -2 F
4) V2 3.3kV
3 �(3.3 �103 ) 2
Rb'
150
21.7810 4
b �Rb' 0.01164 �21.78 �104
L
2 �Dw 2 �2p �3
67.25 H
C1 C2 0.151 F
The values of L, C1 C 2 for different values of V2 are tabulated below.
V2 L C1 C 2
33kV 6722.2H 0.00151 F
11kV 747.2H 0.0136 F
6.6kV 269H 0.0377 F
3.3kV 67.25H 0.151 F
From the above table it is clear that smaller the value of V 2, the smaller is the
value of L and higher the value of C 1 and C2 for tuning condition. If we select too low
value of V2 and L then capacitance values will be beyond available limits, and if we
select higher value of V2 and L, then CCVT and inductor will become bulky. So a
compromise is necessary and let us select V2 = 6.6kV
For V2 = 6.6kV
L = 269H
C1 C 2 0.0377 F
V C1 C 2
Now,
V2 C1
13210 3 0.037710 -6
36.610 3
C1
0.0377 36.610 3 10 -6 F
C1
13210 3
0.0033F
245
C 2 0.0344F
In this design, we explained the basic concept for CCVT design and we assumed
the transformer to be ideal. But in actual design practice the value of magnetizing
impedance of transformer, resistance of reactor etc have to be taken into account,
as ratio error a and phase angle error b will also get affected by these values.
26. Diagram
The equivalent circuit of a CCVT is shown in fig 8.3. The values of C 1 and C2 are
0.0018 F and 0.018 F respectively. Tuning inductor has an inductance of
497H and resistance of 4620 .
Xm of the 6.6kV VT is 1M , core loss = 20 watts per phase, VA burden =
150VA per phase. Value of Cm for compensating the current drawn by m is equal
to 3.18310 -9 F .
(kk) Verify the appropriateness of choice of L and Cm.
Ans: If C1 0.0018F and C 2 0.0186F then the value L of tuning inductor
is given by
1
L 2
w (C1 C 2 )
where w 2p f and f = tuning frequency
1
L
(2p �50) (0.0018 0.0186) �10-6
2
1
Xm
w Cm
1 1
Cm
w X m (2p �50) �� 1 106
3.183 �10-9 F
The value is also same as the selected value of Cm Hence the selection of both L
and Cm is appropriate.
(mm) If the frequency drops from 50Hz to 47Hz, what would be the values of
ratio error and phase angle error?
Ans: Core loss = 20w
V22
20W
Rm
246
V22 (6600) 2
Rm
20 20
2.18 �10
6
6600 0
A
260874.14 -2.44�
VT I th �Z
6600 0
�256147.5 1.82�
260874.14 -2.44�
6480.42 4.26�
(6600 - 6480.42)
Hence % ratio error �100
6600
=1.81%
Phase angle error = 4.26�
V2 6.6kV
r a w2 a 2
M
d 2i R di 1 1 R
t �t0 2
i0 wn 2p �50 2 Iwn
dt L dt LCeq LC L
d 2i
2
2a wn wn2i 0 a < 1
dt
Lec – 8
1
2p �50 2zw R d i 2zw w 2i 0 z wn z < 1
2
wn
LCeq n
L dt 2 n n
-t V
t I 0 - m sin(wt0 f - q ) f q
e | Z line |
248
Example 1:
d
249
Answer:
Based on the criteria that the CT can deliver 20 times rated secondary current
without exceeding a 10% ratio error, the maximum fault current will be 24000A.
However, with a 2.0Ω burden, this will result in a voltage below the knee point of the CT
and, as a practical matter, it will be within 10% accuracy at higher currents. This can only
be accurately determined from excitation or ratio correction curves and not from the
accuracy classification. For example, a CT with characteristics shown in above figure
will produce between 180-240A without exceeding the 10% ratio error, depending on the
power factor of the 2.0Ω burden.
Example 2:
A 1200/5, C400 CT is connected on the 1000/5 tap. What is the maximum secondary
burden that can be used and still maintain rated accuracy at 20 times rated symmetrical
secondary current?
Answer:
Since the secondary voltage capability is directly proportional to the connected tap, the
CT will support a voltage of 1000/1200 400V or 333V. Twenty times the rated
secondary current is 100A. Therefore, the maximum burden is 333V/100A or 3.33 Ω
Example 3:
Assume that secondary burden in a relay circuit is 5Ω. The relay setting is 2A and the CT
ratio is 300/5. Using above figure, calculate the primary current required to operate the
relay?
Answer:
250
N (I E I S )
= 300/5(0.04+2) A=122A
Example 4:
A relay is expected to operate for a 7000A primary current. The CT ratio is 600/5.
Secondary burden is 3.5 Ω. What is the error for the CT shown in above figure?
Answer:
The total secondary fault current is (7000/600) 5=58A. Assume that exciting current is
negligible.
VS I S ( R B RS )
= 58(3.5+0.31)
= 221V
The exciting current will not be negligible, however, and the calculation will not be
iterated.
Lec – 7
N1 RI 0 Vm N1 R Vm Vm N1 N1 RI 0 -tt N1 I 0 -tt
fdcmax t t N1 Rt v2 (t )
dc
e i2 e
N 22 | Z line | N 22 | Z line | | Z line | N 22 N2 N2
t -t -t
1 N1 RI 0 t N1 RI 0
f (t ) - f (0) t (1 - e ) f (t ) f (0) t (1 - e t )
N2 �
v2 dt 2 2
0
N 2 N 2
Lec- 7
251
Vm N1 d V2
v2ac (t ) R sin(wt f - q ) jw f ac
| Z line | N 2 dt jw N 2
RVm N1 p RVm N1
fac (t ) sin(wt f - q - ) facmax
w | Z line | N 2
2
2 w | Z line | N 22
Vm N1
Rt
RVm N1 N1 RVmt | Z line | N 22 wL X
facmax fdcmax 2 1 1 wt 1 line 1 line
w | Z line | N 2 N 2 | Z line |
2
Vm N1 R Rline Rline
| Z line | N 2 w
2
X
1
R
Lec-6
Lec – 5
Ip Ip
- IS Ip IE - IS
N - I I �100 N 98�45�
�100 N S E
IS �100
IS IS
Lec - 9
Vth - VT 1 1
�100 )Dw w02
(3f ) ( L w02 1 LC < f Df �3Hz
Vth w02
LC
1t di dv di 1 d 2i
v(t ) Ri �
Ceq
-�
idt L
dt dt
R
dt Ceq
i L 2 w0
dt
d 1 1 1
DVL - DVC jI (w L - ) Dw I (2 2 )Dw w02 I ( L L )Dw
dw wCeq w0 Ceq LCeq
252
| VL - VC | 2 LI Dw 2 LI 2 LDw
j 2 LI Dw (DVL - DVC ) tan b 2 2 2 � 2p f Lm 106
| VR | a Rb I a Rb a Rb
106
Lm 3183.1H
2p
source. The fault strikes at time t t 0 . This can be simulated by closing the switch at t t1
253
R jwL or Z q models the line impedance. The fault current in the line is given by
i (t ) 0 0 t t0
t -t 0
V sin(w t f - q ) -
t
t t0
i (t ) m I 0e
|Z |
Where τ is the time constant of the line τ =L/R. The fault current has two components in
it. The first component models the steady state sinusoidal ac response while the second current
is the dc offset current due to the presence of inductive component in the circuit. Recall that
current in an inductance can not change instantaneously. As t ∞, the instantaneous dc
It is more or less obvious that, dc offset is not seen in the waveform after 5 time constants.
The value of I0 can be worked out by setting the current at t t o to zero.
This implies that
Vm
I0 - sin(wt 0 - q )
Z
254
Thus
t -t 0
Vm V -( )
i (t ) sin(wt f - q ) - m sin(wt f - q )e t
Z Z
fig.2
It can be seen that severity of dc offset component in fault current is maximum when
a) f q
p
b) wt 0
2
255
p 1
For example, if angle of transmission line is 800, then with f = 800 & t 0 =
2 2p 50 200
V
sec = 5msec, the severity of dc offset current would equal I 0 Z , which is also the peak
m
We now plan to show that CT can saturate on dc offset current. Also, we plan to show
that the resulting distortions in the CT secondary current can be un-acceptably high. While
doing this analysis, we will neglect ac symmetrical component. In other words, we rest our
belief in superposition theorem atleast qualitatively and will finally evaluate effect using it
Notice that the current that we are dealing with is non-linear, a rigorous application of super
position theorem is simply out of question.
256
First consider an ideal CT excited by the dc offset current source. An ideal CT will faithfully
replicates primary current waveform on the secondary side. Hence, the secondary current
would be given by
-t
I0 t
i2 (t ) e
N
and the voltage developed across CT secondary would be given by
-t
RI N2
v 2 (t ) 0 e t where N N
N 1
For simplicity, let us assume that the initial flux in the transformer core at t=0 is zero
f ( 0 ) 0 ; Then we can compute the flux in the transformer core by using faraday’s law
df
V2 N 2 ---------(2)
dt
257
t
f (t ) - f (0) v 0
2 dt
RI 0
-t
t 1- e t
N2
-t
LI 0
(1 - e t )
N2
-t
LI 0
f (t ) f (0) (1 - e t )
N2
-t
LI 0
(1 - e t ) ------- (3)
N2
as a consequence of dc offset current,
Thus, flux in the core increases exponentially to a peak value of
f dmax
c
LI 0
N2
as t
L Vm Vm
N Z Z
f dmax
c
Note that unlike ac voltage induced flux, which is sinusoidal, this flux is unidirectional. The ac
voltage induced flux has zero average value. However, dc offset induced does not have this
nice feature. The total flux in ideal CT core is a summation of ac flux and dc flux.
d
The ac flux in the CT core can be obtained by substituting operator by jw . Hence
dt
If v2 (t ) Vm sin(wt f ) , then
Vm p
f ac sin(wt f - )
wN 2 2
The peak value of ac flux is given by
258
Vm
f acmax
wN 2
However Vm R2 I 0
max
R2 I 0max
Hence facmax
wN 2
and peak value of the total flux is given by
Vm LI 0max
facmax f dcmax
wN 2 N2
In practice, if this flux exceeds the knee-point flux in the core (see fig.), then the CT core
will saturate.
As a consequence of CT core saturation, the secondary current would not faithfully replicate
the primary current. Infact, in practice it is observed that CT secondary current is clipped. The
clipping of CT current leads to “blinding” of the relay which cannot function further. Hence,
CT saturation in presence of dc offset current is a serious problem which relay designers have
to face. Note that dc flux accumulates gradually. (Depends upon the transmission line time
constant ( t ). It is apparent that saturation should not occur immediately after the inception of
the fault. Thus, if the relay is fast enough in decision making, it is likely that a relaying
decision would be undertaken before the CT fully saturates. This is another important reason
for increasing the speed of relaying system. For bus-fault protection, where the dc saturation
due to dc offset current can be a significant contributing factor, quarter cycle operations *****
259
specifically are imposed. Similarly, a distance relay is expected to operate within ½-1 cycle
time.
CT oversizing factors
Typically, an efficient design of transformer would correspond to choosing the core cross
section such that f mac should be near the knee point of B-H curve. One obvious way of
avoiding the CT saturation on dc flux is to oversize the core so that for flux (f acmax f dcmax ) , the
(f acmax f dcmax )
corresponding B is below the knee-point. Hence, the factor is called core-
f acmax
oversizing factor.
f dcmax
Core-oversizing factor = 1
f acmax
LI o N 2
1
RI 0 wN 2
wL
1
R
X
1
R
Note that X/R in above equation is the transmission line X/R ratio. For a 220KV line X/R 10.
This would imply that transformer core should be oversized by a factor of 11. For a 400KV
line, typical value of X/R 20. This would imply an oversizing required of about 21 times the
usual design. Clearly this high amount of oversizing is not practical. Thus, the important
conclusion is that, protection engineers have to live with the saturation problem.
Cautions in CT selection:
While choosing a CT for a particular application, it is necessary to observe following
precautions.
53. The CT rating and continuous load current should match. For example, if max load
current is 90A, a 100:5 Ct may be acceptable but 50:5 is not acceptable.
260
54. The maximum fault current should be less than 20 times the CT rated current. for
example 100:5 CT can be used, so long as burden on the CT & maximum primary fault
current is below 2000A.
55. The voltage rating of CT should be compatible. For example, 100:5 C100 would give
linear response, upto 20 times rated current provided CT burden is kept
below(100/20*5=1 Ω). With 2 Ω burden, this CT can be used only if maximum current
is limited to 1000A.
56. Parallel of CT’s e.g. in differential protection, or with SLG fault can create significant
errors in CT performance. One should in general ascertain that magnetizing current is
kept much below the pick up value.
Following example, illustrates this point
Exercise problems:
If the current ratio is adequate for a protection, but CT burden is high; then the
performance of CT may deteriorate due to large magnetizing current and/or saturation problem.
The CT performance can be improved by connecting the CT’s in series.
27) Show the dotted terminals for correct secondary series connection
28) What is the VA of CT in fig (a) & (b) respectively?
40) Electromechanical relays tend to saturate at high currents. This reduces the relay burden
on CT, and so that the CT performance at moderately high currents may be considered
better than at relay’s rated burden at 5A.
41) Use of instantaneous over current relays has the potential to overcome this problem of
saturation of CT’s
261
42) Differential protection can operate on external faults due to the un equal saturation of
CT’s
Lecture-6
Examples
19. If a 300:5 class C CT is connected to a meter with resistance R I 1 and
secondary current in the CT is 4.5A find out the primary current voltage
developed across the meter and % rate error. Lead wire resistance R L 0.02
secondary resistance RS of a 300/5 CT 0.15
Diagram
R I 1 , R L 0.02 RS 0.15 I S 4.5 A
Total secondary resistance RT R I R L RS
1.17
Secondary voltage I S RT
4.5 1.17
5.265V
From Fig 5.7,
Exciting current IE for 5.265V
= 0.03A
Turns ratio N = 300/5 = 60
I p N (I S I E )
= 60(4.5 + 0.03)
= 271.8A
Voltage across meter I S R I
4.5 1 = 4.5V
IE 0.03
Ratio error 100 100
IS 4.5
= 0.67%
Rb
262
Lecture – 8
Examples
27. Design a CCVT for a 132kV transmission line using the following data.
Resistive Burden (3f )-150VA
Df 3Hz , phase angle error b = 40 min
Consider 4 choices of V2 as 33kV, 11kV, 6.6kV and 3.3kV
Diagram 1 Diagram 2
Transmission line voltage V = 132kV. Suppose V 2 (P_N) be the voltage to be
produced by the capacitive potential divider with capacitance values C1 and C2
and L the value of tuning inductor. The standardized VT secondary voltage is 110
volts (L-L).
Here specification for phase angle error b is 40 minutes variation in frequency
can be upto Df 3Hz . Phase angle error for change in w by Dw in the above
equation circuit, is given by
1
( L 2 )Dw
w C
1
At tuning frequency w 2
LC
Substituting w 1 LC
2
747.2 H
1 1
C1 C 2
w 2 L (3/ 4) 2 747.2
1.3610 -2 F
3) V2 6.6kV
3 �(6.6 �103 )2
Rb
'
150
87.1210 4
b �Rb' 0.01164 �87.12 �104
L
2 �Dw 2 �2p �3
269H ,
C1 C 2 3.7710 -2 F
4) V2 3.3kV
3 �(3.3 �103 ) 2
Rb'
150
21.7810 4
b �Rb' 0.01164 �21.78 �104
L
2 �Dw 2 �2p �3
67.25 H
C1 C2 0.151 F
The values of L, C1 C 2 for different values of V2 are tabulated below.
V2 L C1 C 2
33kV 6722.2H 0.00151 F
11kV 747.2H 0.0136 F
6.6kV 269H 0.0377 F
3.3kV 67.25H 0.151 F
From the above table it is clear that smaller the value of V 2, the smaller is the
value of L and higher the value of C 1 and C2 for tuning condition. If we select too low
value of V2 and L then capacitance values will be beyond available limits, and if we
select higher value of V2 and L, then CCVT and inductor will become bulky. So a
compromise is necessary and let us select V2 = 6.6kV
For V2 = 6.6kV
L = 269H
C1 C 2 0.0377 F
V C1 C 2
Now,
V2 C1
13210 3 0.037710 -6
36.610 3
C1
0.0377 36.610 3 10 -6 F
C1
13210 3
0.0033F
264
C 2 0.0344F
In this design, we explained the basic concept for CCVT design and we assumed
the transformer to be ideal. But in actual design practice the value of magnetizing
impedance of transformer, resistance of reactor etc have to be taken into account,
as ratio error a and phase angle error b will also get affected by these values.
28. Diagram
The equivalent circuit of a CCVT is shown in fig 8.3. The values of C 1 and C2 are
0.0018 F and 0.018 F respectively. Tuning inductor has an inductance of
497H and resistance of 4620 .
Xm of the 6.6kV VT is 1M , core loss = 20 watts per phase, VA burden =
150VA per phase. Value of Cm for compensating the current drawn by m is equal
to 3.18310 -9 F .
(nn) Verify the appropriateness of choice of L and Cm.
Ans: If C1 0.0018F and C 2 0.0186F then the value L of tuning inductor
is given by
1
L 2
w (C1 C 2 )
where w 2p f and f = tuning frequency
1
L
(2p �50) (0.0018 0.0186) �10-6
2
1
Xm
w Cm
1 1
Cm
w X m (2p �50) �� 1 106
3.183 �10-9 F
The value is also same as the selected value of Cm Hence the selection of both L
and Cm is appropriate.
(pp) If the frequency drops from 50Hz to 47Hz, what would be the values of
ratio error and phase angle error?
Ans: Core loss = 20w
V22
20W
Rm
265
V22 (6600) 2
Rm
20 20
2.18 �10
6
6600 0
A
260874.14 -2.44�
VT I th �Z
6600 0
�256147.5 1.82�
260874.14 -2.44�
6480.42 4.26�
(6600 - 6480.42)
Hence % ratio error �100
6600
=1.81%
Phase angle error = 4.26�
V2 6.6kV
r a w2 a 2
M
d 2i R di 1 1 R
t �t0 2
i0 wn 2p �50 2 Iwn
dt L dt LCeq LC L
d 2i
2
2a wn wn2i 0 a < 1
dt
Lec – 8
1
2p �50 2zw R d i 2zw w 2i 0 z wn z < 1
2
wn
LCeq n
L dt 2 n n
-t V
t I 0 - m sin(wt0 f - q ) f q
e | Z line |
267
Example 1:
d
268
Answer:
Based on the criteria that the CT can deliver 20 times rated secondary current
without exceeding a 10% ratio error, the maximum fault current will be 24000A.
However, with a 2.0Ω burden, this will result in a voltage below the knee point of the CT
and, as a practical matter, it will be within 10% accuracy at higher currents. This can only
be accurately determined from excitation or ratio correction curves and not from the
accuracy classification. For example, a CT with characteristics shown in above figure
will produce between 180-240A without exceeding the 10% ratio error, depending on the
power factor of the 2.0Ω burden.
Example 2:
A 1200/5, C400 CT is connected on the 1000/5 tap. What is the maximum secondary
burden that can be used and still maintain rated accuracy at 20 times rated symmetrical
secondary current?
Answer:
Since the secondary voltage capability is directly proportional to the connected tap, the
CT will support a voltage of 1000/1200 400V or 333V. Twenty times the rated
secondary current is 100A. Therefore, the maximum burden is 333V/100A or 3.33 Ω
Example 3:
Assume that secondary burden in a relay circuit is 5Ω. The relay setting is 2A and the CT
ratio is 300/5. Using above figure, calculate the primary current required to operate the
relay?
Answer:
269
N (I E I S )
= 300/5(0.04+2) A=122A
Example 4:
A relay is expected to operate for a 7000A primary current. The CT ratio is 600/5.
Secondary burden is 3.5 Ω. What is the error for the CT shown in above figure?
Answer:
The total secondary fault current is (7000/600) 5=58A. Assume that exciting current is
negligible.
VS I S ( R B RS )
= 58(3.5+0.31)
= 221V
The exciting current will not be negligible, however, and the calculation will not be
iterated.
Lec – 7
N1 RI 0 Vm N1 R Vm Vm N1 N1 RI 0 -tt N1 I 0 -tt
fdcmax t t N1 Rt v2 (t )
dc
e i2 e
N 22 | Z line | N 22 | Z line | | Z line | N 22 N2 N2
t -t -t
1 N1 RI 0 t N1 RI 0
f (t ) - f (0) t (1 - e ) f (t ) f (0) t (1 - e t )
N2 �
v2 dt 2 2
0
N 2 N 2
Lec- 7
270
Vm N1 d V2
v2ac (t ) R sin(wt f - q ) jw f ac
| Z line | N 2 dt jw N 2
RVm N1 p RVm N1
fac (t ) sin(wt f - q - ) facmax
w | Z line | N 2
2
2 w | Z line | N 22
Vm N1
Rt
RVm N1 N1 RVmt | Z line | N 22 wL X
facmax fdcmax 2 1 1 wt 1 line 1 line
w | Z line | N 2 N 2 | Z line |
2
Vm N1 R Rline Rline
| Z line | N 2 w
2
X
1
R
Lec-6
Lec – 5
Ip Ip
- IS Ip IE - IS
N - I I �100 N 98�45�
�100 N S E
IS �100
IS IS
Lec - 9
Vth - VT 1 1
�100 )Dw w02
(3f ) ( L w02 1 LC < f Df �3Hz
Vth w02
LC
1t di dv di 1 d 2i
v(t ) Ri �
Ceq
-�
idt L
dt dt
R
dt Ceq
i L 2 w0
dt
d 1 1 1
DVL - DVC jI (w L - ) Dw I (2 2 )Dw w02 I ( L L )Dw
dw wCeq w0 Ceq LCeq
271
| VL - VC | 2 LI Dw 2 LI 2 LDw
j 2 LI Dw (DVL - DVC ) tan b 2 2 2 � 2p f Lm 106
| VR | a Rb I a Rb a Rb
106
Lm 3183.1H
2p
source. The fault strikes at time t t 0 . This can be simulated by closing the switch at t t1
272
R jwL or Z q models the line impedance. The fault current in the line is given by
i (t ) 0 0 t t0
t -t 0
V sin(w t f - q ) -
t
t t0
i (t ) m I 0e
|Z |
Where τ is the time constant of the line τ =L/R. The fault current has two components in
it. The first component models the steady state sinusoidal ac response while the second current
is the dc offset current due to the presence of inductive component in the circuit. Recall that
current in an inductance can not change instantaneously. As t ∞, the instantaneous dc
It is more or less obvious that, dc offset is not seen in the waveform after 5 time constants.
The value of I0 can be worked out by setting the current at t t o to zero.
This implies that
Vm
I0 - sin(wt 0 - q )
Z
273
Thus
t -t 0
Vm V -( )
i (t ) sin(wt f - q ) - m sin(wt f - q )e t
Z Z
fig.2
It can be seen that severity of dc offset component in fault current is maximum when
a) f q
p
b) wt 0
2
274
p 1
For example, if angle of transmission line is 800, then with f = 800 & t 0 =
2 2p 50 200
V
sec = 5msec, the severity of dc offset current would equal I 0 Z , which is also the peak
m
We now plan to show that CT can saturate on dc offset current. Also, we plan to show
that the resulting distortions in the CT secondary current can be un-acceptably high. While
doing this analysis, we will neglect ac symmetrical component. In other words, we rest our
belief in superposition theorem atleast qualitatively and will finally evaluate effect using it
Notice that the current that we are dealing with is non-linear, a rigorous application of super
position theorem is simply out of question.
275
First consider an ideal CT excited by the dc offset current source. An ideal CT will faithfully
replicates primary current waveform on the secondary side. Hence, the secondary current
would be given by
-t
I0 t
i2 (t ) e
N
and the voltage developed across CT secondary would be given by
-t
RI N2
v 2 (t ) 0 e t where N N
N 1
For simplicity, let us assume that the initial flux in the transformer core at t=0 is zero
f ( 0 ) 0 ; Then we can compute the flux in the transformer core by using faraday’s law
df
V2 N 2 ---------(2)
dt
276
t
f (t ) - f (0) v 0
2 dt
RI 0
-t
t 1- e t
N2
-t
LI 0
(1 - e t )
N2
-t
LI 0
f (t ) f (0) (1 - e t )
N2
-t
LI 0
(1 - e t ) ------- (3)
N2
as a consequence of dc offset current,
Thus, flux in the core increases exponentially to a peak value of
f dmax
c
LI 0
N2
as t
L Vm Vm
N Z Z
f dmax
c
Note that unlike ac voltage induced flux, which is sinusoidal, this flux is unidirectional. The ac
voltage induced flux has zero average value. However, dc offset induced does not have this
nice feature. The total flux in ideal CT core is a summation of ac flux and dc flux.
d
The ac flux in the CT core can be obtained by substituting operator by jw . Hence
dt
If v2 (t ) Vm sin(wt f ) , then
Vm p
f ac sin(wt f - )
wN 2 2
The peak value of ac flux is given by
277
Vm
f acmax
wN 2
However Vm R2 I 0
max
R2 I 0max
Hence facmax
wN 2
and peak value of the total flux is given by
Vm LI 0max
facmax f dcmax
wN 2 N2
In practice, if this flux exceeds the knee-point flux in the core (see fig.), then the CT core
will saturate.
As a consequence of CT core saturation, the secondary current would not faithfully replicate
the primary current. Infact, in practice it is observed that CT secondary current is clipped. The
clipping of CT current leads to “blinding” of the relay which cannot function further. Hence,
CT saturation in presence of dc offset current is a serious problem which relay designers have
to face. Note that dc flux accumulates gradually. (Depends upon the transmission line time
constant ( t ). It is apparent that saturation should not occur immediately after the inception of
the fault. Thus, if the relay is fast enough in decision making, it is likely that a relaying
decision would be undertaken before the CT fully saturates. This is another important reason
for increasing the speed of relaying system. For bus-fault protection, where the dc saturation
due to dc offset current can be a significant contributing factor, quarter cycle operations *****
278
specifically are imposed. Similarly, a distance relay is expected to operate within ½-1 cycle
time.
CT oversizing factors
Typically, an efficient design of transformer would correspond to choosing the core cross
section such that f mac should be near the knee point of B-H curve. One obvious way of
avoiding the CT saturation on dc flux is to oversize the core so that for flux (f acmax f dcmax ) , the
(f acmax f dcmax )
corresponding B is below the knee-point. Hence, the factor is called core-
f acmax
oversizing factor.
f dcmax
Core-oversizing factor = 1
f acmax
LI o N 2
1
RI 0 wN 2
wL
1
R
X
1
R
Note that X/R in above equation is the transmission line X/R ratio. For a 220KV line X/R 10.
This would imply that transformer core should be oversized by a factor of 11. For a 400KV
line, typical value of X/R 20. This would imply an oversizing required of about 21 times the
usual design. Clearly this high amount of oversizing is not practical. Thus, the important
conclusion is that, protection engineers have to live with the saturation problem.
Cautions in CT selection:
While choosing a CT for a particular application, it is necessary to observe following
precautions.
57. The CT rating and continuous load current should match. For example, if max load
current is 90A, a 100:5 Ct may be acceptable but 50:5 is not acceptable.
279
58. The maximum fault current should be less than 20 times the CT rated current. for
example 100:5 CT can be used, so long as burden on the CT & maximum primary fault
current is below 2000A.
59. The voltage rating of CT should be compatible. For example, 100:5 C100 would give
linear response, upto 20 times rated current provided CT burden is kept
below(100/20*5=1 Ω). With 2 Ω burden, this CT can be used only if maximum current
is limited to 1000A.
60. Parallel of CT’s e.g. in differential protection, or with SLG fault can create significant
errors in CT performance. One should in general ascertain that magnetizing current is
kept much below the pick up value.
Following example, illustrates this point
Exercise problems:
If the current ratio is adequate for a protection, but CT burden is high; then the
performance of CT may deteriorate due to large magnetizing current and/or saturation problem.
The CT performance can be improved by connecting the CT’s in series.
29) Show the dotted terminals for correct secondary series connection
30) What is the VA of CT in fig (a) & (b) respectively?
43) Electromechanical relays tend to saturate at high currents. This reduces the relay burden
on CT, and so that the CT performance at moderately high currents may be considered
better than at relay’s rated burden at 5A.
44) Use of instantaneous over current relays has the potential to overcome this problem of
saturation of CT’s
280
45) Differential protection can operate on external faults due to the un equal saturation of
CT’s
Lecture-6
Examples
20. If a 300:5 class C CT is connected to a meter with resistance R I 1 and
secondary current in the CT is 4.5A find out the primary current voltage
developed across the meter and % rate error. Lead wire resistance R L 0.02
secondary resistance RS of a 300/5 CT 0.15
Diagram
R I 1 , R L 0.02 RS 0.15 I S 4.5 A
Total secondary resistance RT R I R L RS
1.17
Secondary voltage I S RT
4.5 1.17
5.265V
From Fig 5.7,
Exciting current IE for 5.265V
= 0.03A
Turns ratio N = 300/5 = 60
I p N (I S I E )
= 60(4.5 + 0.03)
= 271.8A
Voltage across meter I S R I
4.5 1 = 4.5V
IE 0.03
Ratio error 100 100
IS 4.5
= 0.67%
Rb
281
Lecture – 8
Examples
29. Design a CCVT for a 132kV transmission line using the following data.
Resistive Burden (3f )-150VA
Df 3Hz , phase angle error b = 40 min
Consider 4 choices of V2 as 33kV, 11kV, 6.6kV and 3.3kV
Diagram 1 Diagram 2
Transmission line voltage V = 132kV. Suppose V 2 (P_N) be the voltage to be
produced by the capacitive potential divider with capacitance values C1 and C2
and L the value of tuning inductor. The standardized VT secondary voltage is 110
volts (L-L).
Here specification for phase angle error b is 40 minutes variation in frequency
can be upto Df 3Hz . Phase angle error for change in w by Dw in the above
equation circuit, is given by
1
( L 2 )Dw
w C
1
At tuning frequency w 2
LC
Substituting w 1 LC
2
747.2 H
1 1
C1 C 2
w 2 L (3/ 4) 2 747.2
1.3610 -2 F
3) V2 6.6kV
3 �(6.6 �103 )2
Rb
'
150
87.1210 4
b �Rb' 0.01164 �87.12 �104
L
2 �Dw 2 �2p �3
269H ,
C1 C 2 3.7710 -2 F
4) V2 3.3kV
3 �(3.3 �103 ) 2
Rb'
150
21.7810 4
b �Rb' 0.01164 �21.78 �104
L
2 �Dw 2 �2p �3
67.25 H
C1 C2 0.151 F
The values of L, C1 C 2 for different values of V2 are tabulated below.
V2 L C1 C 2
33kV 6722.2H 0.00151 F
11kV 747.2H 0.0136 F
6.6kV 269H 0.0377 F
3.3kV 67.25H 0.151 F
From the above table it is clear that smaller the value of V 2, the smaller is the
value of L and higher the value of C 1 and C2 for tuning condition. If we select too low
value of V2 and L then capacitance values will be beyond available limits, and if we
select higher value of V2 and L, then CCVT and inductor will become bulky. So a
compromise is necessary and let us select V2 = 6.6kV
For V2 = 6.6kV
L = 269H
C1 C 2 0.0377 F
V C1 C 2
Now,
V2 C1
13210 3 0.037710 -6
36.610 3
C1
0.0377 36.610 3 10 -6 F
C1
13210 3
0.0033F
283
C 2 0.0344F
In this design, we explained the basic concept for CCVT design and we assumed
the transformer to be ideal. But in actual design practice the value of magnetizing
impedance of transformer, resistance of reactor etc have to be taken into account,
as ratio error a and phase angle error b will also get affected by these values.
30. Diagram
The equivalent circuit of a CCVT is shown in fig 8.3. The values of C 1 and C2 are
0.0018 F and 0.018 F respectively. Tuning inductor has an inductance of
497H and resistance of 4620 .
Xm of the 6.6kV VT is 1M , core loss = 20 watts per phase, VA burden =
150VA per phase. Value of Cm for compensating the current drawn by m is equal
to 3.18310 -9 F .
(qq) Verify the appropriateness of choice of L and Cm.
Ans: If C1 0.0018F and C 2 0.0186F then the value L of tuning inductor
is given by
1
L 2
w (C1 C 2 )
where w 2p f and f = tuning frequency
1
L
(2p �50) (0.0018 0.0186) �10-6
2
1
Xm
w Cm
1 1
Cm
w X m (2p �50) �� 1 106
3.183 �10-9 F
The value is also same as the selected value of Cm Hence the selection of both L
and Cm is appropriate.
(ss)If the frequency drops from 50Hz to 47Hz, what would be the values of ratio
error and phase angle error?
Ans: Core loss = 20w
V22
20W
Rm
284
V22 (6600) 2
Rm
20 20
2.18 �10
6
6600 0
A
260874.14 -2.44�
VT I th �Z
6600 0
�256147.5 1.82�
260874.14 -2.44�
6480.42 4.26�
(6600 - 6480.42)
Hence % ratio error �100
6600
=1.81%
Phase angle error = 4.26�
V2 6.6kV
r a w2 a 2
M
d 2i R di 1 1 R
t �t0 2
i0 wn 2p �50 2 Iwn
dt L dt LCeq LC L
d 2i
2
2a wn wn2i 0 a < 1
dt
Lec – 8
1
2p �50 2zw R d i 2zw w 2i 0 z wn z < 1
2
wn
LCeq n
L dt 2 n n
-t V
t I 0 - m sin(wt0 f - q ) f q
e | Z line |
286
Example 1:
d
287
Answer:
Based on the criteria that the CT can deliver 20 times rated secondary current
without exceeding a 10% ratio error, the maximum fault current will be 24000A.
However, with a 2.0Ω burden, this will result in a voltage below the knee point of the CT
and, as a practical matter, it will be within 10% accuracy at higher currents. This can only
be accurately determined from excitation or ratio correction curves and not from the
accuracy classification. For example, a CT with characteristics shown in above figure
will produce between 180-240A without exceeding the 10% ratio error, depending on the
power factor of the 2.0Ω burden.
Example 2:
A 1200/5, C400 CT is connected on the 1000/5 tap. What is the maximum secondary
burden that can be used and still maintain rated accuracy at 20 times rated symmetrical
secondary current?
Answer:
Since the secondary voltage capability is directly proportional to the connected tap, the
CT will support a voltage of 1000/1200 400V or 333V. Twenty times the rated
secondary current is 100A. Therefore, the maximum burden is 333V/100A or 3.33 Ω
Example 3:
Assume that secondary burden in a relay circuit is 5Ω. The relay setting is 2A and the CT
ratio is 300/5. Using above figure, calculate the primary current required to operate the
relay?
Answer:
288
N (I E I S )
= 300/5(0.04+2) A=122A
Example 4:
A relay is expected to operate for a 7000A primary current. The CT ratio is 600/5.
Secondary burden is 3.5 Ω. What is the error for the CT shown in above figure?
Answer:
The total secondary fault current is (7000/600) 5=58A. Assume that exciting current is
negligible.
VS I S ( R B RS )
= 58(3.5+0.31)
= 221V
The exciting current will not be negligible, however, and the calculation will not be
iterated.
Lec – 7
N1 RI 0 Vm N1 R Vm Vm N1 N1 RI 0 -tt N1 I 0 -tt
fdcmax t t N1 Rt v2 (t )
dc
e i2 e
N 22 | Z line | N 22 | Z line | | Z line | N 22 N2 N2
t -t -t
1 N1 RI 0 t N1 RI 0
f (t ) - f (0) t (1 - e ) f (t ) f (0) t (1 - e t )
N2 �
v2 dt 2 2
0
N 2 N 2
Lec- 7
289
Vm N1 d V2
v2ac (t ) R sin(wt f - q ) jw f ac
| Z line | N 2 dt jw N 2
RVm N1 p RVm N1
fac (t ) sin(wt f - q - ) facmax
w | Z line | N 2
2
2 w | Z line | N 22
Vm N1
Rt
RVm N1 N1 RVmt | Z line | N 22 wL X
facmax fdcmax 2 1 1 wt 1 line 1 line
w | Z line | N 2 N 2 | Z line |
2
Vm N1 R Rline Rline
| Z line | N 2 w
2
X
1
R
Lec-6
Lec – 5
Ip Ip
- IS Ip IE - IS
N - I I �100 N 98�45�
�100 N S E
IS �100
IS IS
Lec - 9
Vth - VT 1 1
�100 )Dw w02
(3f ) ( L w02 1 LC < f Df �3Hz
Vth w02
LC
1t di dv di 1 d 2i
v(t ) Ri �
Ceq
-�
idt L
dt dt
R
dt Ceq
i L 2 w0
dt
d 1 1 1
DVL - DVC jI (w L - ) Dw I (2 2 )Dw w02 I ( L L )Dw
dw wCeq w0 Ceq LCeq
290
| VL - VC | 2 LI Dw 2 LI 2 LDw
j 2 LI Dw (DVL - DVC ) tan b 2 2 2 � 2p f Lm 106
| VR | a Rb I a Rb a Rb
106
Lm 3183.1H
2p
source. The fault strikes at time t t 0 . This can be simulated by closing the switch at t t1
291
R jwL or Z q models the line impedance. The fault current in the line is given by
i (t ) 0 0 t t0
t -t 0
V sin(w t f - q ) -
t
t t0
i (t ) m I 0e
|Z |
Where τ is the time constant of the line τ =L/R. The fault current has two components in
it. The first component models the steady state sinusoidal ac response while the second current
is the dc offset current due to the presence of inductive component in the circuit. Recall that
current in an inductance can not change instantaneously. As t ∞, the instantaneous dc
It is more or less obvious that, dc offset is not seen in the waveform after 5 time constants.
The value of I0 can be worked out by setting the current at t t o to zero.
This implies that
Vm
I0 - sin(wt 0 - q )
Z
292
Thus
t -t 0
Vm V -( )
i (t ) sin(wt f - q ) - m sin(wt f - q )e t
Z Z
fig.2
It can be seen that severity of dc offset component in fault current is maximum when
a) f q
p
b) wt 0
2
293
p 1
For example, if angle of transmission line is 800, then with f = 800 & t 0 =
2 2p 50 200
V
sec = 5msec, the severity of dc offset current would equal I 0 Z , which is also the peak
m
We now plan to show that CT can saturate on dc offset current. Also, we plan to show
that the resulting distortions in the CT secondary current can be un-acceptably high. While
doing this analysis, we will neglect ac symmetrical component. In other words, we rest our
belief in superposition theorem atleast qualitatively and will finally evaluate effect using it
Notice that the current that we are dealing with is non-linear, a rigorous application of super
position theorem is simply out of question.
294
First consider an ideal CT excited by the dc offset current source. An ideal CT will faithfully
replicates primary current waveform on the secondary side. Hence, the secondary current
would be given by
-t
I0 t
i2 (t ) e
N
and the voltage developed across CT secondary would be given by
-t
RI N2
v 2 (t ) 0 e t where N N
N 1
For simplicity, let us assume that the initial flux in the transformer core at t=0 is zero
f ( 0 ) 0 ; Then we can compute the flux in the transformer core by using faraday’s law
df
V2 N 2 ---------(2)
dt
295
t
f (t ) - f (0) v 0
2 dt
RI 0
-t
t 1- e t
N2
-t
LI 0
(1 - e t )
N2
-t
LI 0
f (t ) f (0) (1 - e t )
N2
-t
LI 0
(1 - e t ) ------- (3)
N2
as a consequence of dc offset current,
Thus, flux in the core increases exponentially to a peak value of
f dmax
c
LI 0
N2
as t
L Vm Vm
N Z Z
f dmax
c
Note that unlike ac voltage induced flux, which is sinusoidal, this flux is unidirectional. The ac
voltage induced flux has zero average value. However, dc offset induced does not have this
nice feature. The total flux in ideal CT core is a summation of ac flux and dc flux.
d
The ac flux in the CT core can be obtained by substituting operator by jw . Hence
dt
If v2 (t ) Vm sin(wt f ) , then
Vm p
f ac sin(wt f - )
wN 2 2
The peak value of ac flux is given by
296
Vm
f acmax
wN 2
However Vm R2 I 0
max
R2 I 0max
Hence facmax
wN 2
and peak value of the total flux is given by
Vm LI 0max
facmax f dcmax
wN 2 N2
In practice, if this flux exceeds the knee-point flux in the core (see fig.), then the CT core
will saturate.
As a consequence of CT core saturation, the secondary current would not faithfully replicate
the primary current. Infact, in practice it is observed that CT secondary current is clipped. The
clipping of CT current leads to “blinding” of the relay which cannot function further. Hence,
CT saturation in presence of dc offset current is a serious problem which relay designers have
to face. Note that dc flux accumulates gradually. (Depends upon the transmission line time
constant ( t ). It is apparent that saturation should not occur immediately after the inception of
the fault. Thus, if the relay is fast enough in decision making, it is likely that a relaying
decision would be undertaken before the CT fully saturates. This is another important reason
for increasing the speed of relaying system. For bus-fault protection, where the dc saturation
due to dc offset current can be a significant contributing factor, quarter cycle operations *****
297
specifically are imposed. Similarly, a distance relay is expected to operate within ½-1 cycle
time.
CT oversizing factors
Typically, an efficient design of transformer would correspond to choosing the core cross
section such that f mac should be near the knee point of B-H curve. One obvious way of
avoiding the CT saturation on dc flux is to oversize the core so that for flux (f acmax f dcmax ) , the
(f acmax f dcmax )
corresponding B is below the knee-point. Hence, the factor is called core-
f acmax
oversizing factor.
f dcmax
Core-oversizing factor = 1
f acmax
LI o N 2
1
RI 0 wN 2
wL
1
R
X
1
R
Note that X/R in above equation is the transmission line X/R ratio. For a 220KV line X/R 10.
This would imply that transformer core should be oversized by a factor of 11. For a 400KV
line, typical value of X/R 20. This would imply an oversizing required of about 21 times the
usual design. Clearly this high amount of oversizing is not practical. Thus, the important
conclusion is that, protection engineers have to live with the saturation problem.
Cautions in CT selection:
While choosing a CT for a particular application, it is necessary to observe following
precautions.
61. The CT rating and continuous load current should match. For example, if max load
current is 90A, a 100:5 Ct may be acceptable but 50:5 is not acceptable.
298
62. The maximum fault current should be less than 20 times the CT rated current. for
example 100:5 CT can be used, so long as burden on the CT & maximum primary fault
current is below 2000A.
63. The voltage rating of CT should be compatible. For example, 100:5 C100 would give
linear response, upto 20 times rated current provided CT burden is kept
below(100/20*5=1 Ω). With 2 Ω burden, this CT can be used only if maximum current
is limited to 1000A.
64. Parallel of CT’s e.g. in differential protection, or with SLG fault can create significant
errors in CT performance. One should in general ascertain that magnetizing current is
kept much below the pick up value.
Following example, illustrates this point
Exercise problems:
If the current ratio is adequate for a protection, but CT burden is high; then the
performance of CT may deteriorate due to large magnetizing current and/or saturation problem.
The CT performance can be improved by connecting the CT’s in series.
31) Show the dotted terminals for correct secondary series connection
32) What is the VA of CT in fig (a) & (b) respectively?
46) Electromechanical relays tend to saturate at high currents. This reduces the relay burden
on CT, and so that the CT performance at moderately high currents may be considered
better than at relay’s rated burden at 5A.
47) Use of instantaneous over current relays has the potential to overcome this problem of
saturation of CT’s
299
48) Differential protection can operate on external faults due to the un equal saturation of
CT’s
Lecture-6
Examples
21. If a 300:5 class C CT is connected to a meter with resistance R I 1 and
secondary current in the CT is 4.5A find out the primary current voltage
developed across the meter and % rate error. Lead wire resistance R L 0.02
secondary resistance RS of a 300/5 CT 0.15
Diagram
R I 1 , R L 0.02 RS 0.15 I S 4.5 A
Total secondary resistance RT R I R L RS
1.17
Secondary voltage I S RT
4.5 1.17
5.265V
From Fig 5.7,
Exciting current IE for 5.265V
= 0.03A
Turns ratio N = 300/5 = 60
I p N (I S I E )
= 60(4.5 + 0.03)
= 271.8A
Voltage across meter I S R I
4.5 1 = 4.5V
IE 0.03
Ratio error 100 100
IS 4.5
= 0.67%
Rb
300
Lecture – 8
Examples
31. Design a CCVT for a 132kV transmission line using the following data.
Resistive Burden (3f )-150VA
Df 3Hz , phase angle error b = 40 min
Consider 4 choices of V2 as 33kV, 11kV, 6.6kV and 3.3kV
Diagram 1 Diagram 2
Transmission line voltage V = 132kV. Suppose V 2 (P_N) be the voltage to be
produced by the capacitive potential divider with capacitance values C1 and C2
and L the value of tuning inductor. The standardized VT secondary voltage is 110
volts (L-L).
Here specification for phase angle error b is 40 minutes variation in frequency
can be upto Df 3Hz . Phase angle error for change in w by Dw in the above
equation circuit, is given by
1
( L 2 )Dw
w C
1
At tuning frequency w 2
LC
Substituting w 1 LC
2
747.2 H
1 1
C1 C 2
w 2 L (3/ 4) 2 747.2
1.3610 -2 F
3) V2 6.6kV
3 �(6.6 �103 )2
Rb
'
150
87.1210 4
b �Rb' 0.01164 �87.12 �104
L
2 �Dw 2 �2p �3
269H ,
C1 C 2 3.7710 -2 F
4) V2 3.3kV
3 �(3.3 �103 ) 2
Rb'
150
21.7810 4
b �Rb' 0.01164 �21.78 �104
L
2 �Dw 2 �2p �3
67.25 H
C1 C2 0.151 F
The values of L, C1 C 2 for different values of V2 are tabulated below.
V2 L C1 C 2
33kV 6722.2H 0.00151 F
11kV 747.2H 0.0136 F
6.6kV 269H 0.0377 F
3.3kV 67.25H 0.151 F
From the above table it is clear that smaller the value of V 2, the smaller is the
value of L and higher the value of C 1 and C2 for tuning condition. If we select too low
value of V2 and L then capacitance values will be beyond available limits, and if we
select higher value of V2 and L, then CCVT and inductor will become bulky. So a
compromise is necessary and let us select V2 = 6.6kV
For V2 = 6.6kV
L = 269H
C1 C 2 0.0377 F
V C1 C 2
Now,
V2 C1
13210 3 0.037710 -6
36.610 3
C1
0.0377 36.610 3 10 -6 F
C1
13210 3
0.0033F
302
C 2 0.0344F
In this design, we explained the basic concept for CCVT design and we assumed
the transformer to be ideal. But in actual design practice the value of magnetizing
impedance of transformer, resistance of reactor etc have to be taken into account,
as ratio error a and phase angle error b will also get affected by these values.
32. Diagram
The equivalent circuit of a CCVT is shown in fig 8.3. The values of C 1 and C2 are
0.0018 F and 0.018 F respectively. Tuning inductor has an inductance of
497H and resistance of 4620 .
Xm of the 6.6kV VT is 1M , core loss = 20 watts per phase, VA burden =
150VA per phase. Value of Cm for compensating the current drawn by m is equal
to 3.18310 -9 F .
(tt) Verify the appropriateness of choice of L and Cm.
Ans: If C1 0.0018F and C 2 0.0186F then the value L of tuning inductor
is given by
1
L 2
w (C1 C 2 )
where w 2p f and f = tuning frequency
1
L
(2p �50) (0.0018 0.0186) �10-6
2
1
Xm
w Cm
1 1
Cm
w X m (2p �50) �� 1 106
3.183 �10-9 F
The value is also same as the selected value of Cm Hence the selection of both L
and Cm is appropriate.
(vv) If the frequency drops from 50Hz to 47Hz, what would be the values of
ratio error and phase angle error?
Ans: Core loss = 20w
V22
20W
Rm
303
V22 (6600) 2
Rm
20 20
2.18 �10
6
6600 0
A
260874.14 -2.44�
VT I th �Z
6600 0
�256147.5 1.82�
260874.14 -2.44�
6480.42 4.26�
(6600 - 6480.42)
Hence % ratio error �100
6600
=1.81%
Phase angle error = 4.26�
V2 6.6kV
r a w2 a 2
M
d 2i R di 1 1 R
t �t0 2
i0 wn 2p �50 2 Iwn
dt L dt LCeq LC L
d 2i
2
2a wn wn2i 0 a < 1
dt
Lec – 8
1
2p �50 2zw R d i 2zw w 2i 0 z wn z < 1
2
wn
LCeq n
L dt 2 n n
-t V
t I 0 - m sin(wt0 f - q ) f q
e | Z line |
305
Example 1:
d
306
Answer:
Based on the criteria that the CT can deliver 20 times rated secondary current
without exceeding a 10% ratio error, the maximum fault current will be 24000A.
However, with a 2.0Ω burden, this will result in a voltage below the knee point of the CT
and, as a practical matter, it will be within 10% accuracy at higher currents. This can only
be accurately determined from excitation or ratio correction curves and not from the
accuracy classification. For example, a CT with characteristics shown in above figure
will produce between 180-240A without exceeding the 10% ratio error, depending on the
power factor of the 2.0Ω burden.
Example 2:
A 1200/5, C400 CT is connected on the 1000/5 tap. What is the maximum secondary
burden that can be used and still maintain rated accuracy at 20 times rated symmetrical
secondary current?
Answer:
Since the secondary voltage capability is directly proportional to the connected tap, the
CT will support a voltage of 1000/1200 400V or 333V. Twenty times the rated
secondary current is 100A. Therefore, the maximum burden is 333V/100A or 3.33 Ω
Example 3:
Assume that secondary burden in a relay circuit is 5Ω. The relay setting is 2A and the CT
ratio is 300/5. Using above figure, calculate the primary current required to operate the
relay?
Answer:
307
N (I E I S )
= 300/5(0.04+2) A=122A
Example 4:
A relay is expected to operate for a 7000A primary current. The CT ratio is 600/5.
Secondary burden is 3.5 Ω. What is the error for the CT shown in above figure?
Answer:
The total secondary fault current is (7000/600) 5=58A. Assume that exciting current is
negligible.
VS I S ( R B RS )
= 58(3.5+0.31)
= 221V
The exciting current will not be negligible, however, and the calculation will not be
iterated.
Lec – 7
N1 RI 0 Vm N1 R Vm Vm N1 N1 RI 0 -tt N1 I 0 -tt
fdcmax t t N1 Rt v2 (t )
dc
e i2 e
N 22 | Z line | N 22 | Z line | | Z line | N 22 N2 N2
t -t -t
1 N1 RI 0 t N1 RI 0
f (t ) - f (0) t (1 - e ) f (t ) f (0) t (1 - e t )
N2 �
v2 dt 2 2
0
N 2 N 2
Lec- 7
308
Vm N1 d V2
v2ac (t ) R sin(wt f - q ) jw f ac
| Z line | N 2 dt jw N 2
RVm N1 p RVm N1
fac (t ) sin(wt f - q - ) facmax
w | Z line | N 2
2
2 w | Z line | N 22
Vm N1
Rt
RVm N1 N1 RVmt | Z line | N 22 wL X
facmax fdcmax 2 1 1 wt 1 line 1 line
w | Z line | N 2 N 2 | Z line |
2
Vm N1 R Rline Rline
| Z line | N 2 w
2
X
1
R
Lec-6
Lec – 5
Ip Ip
- IS Ip IE - IS
N - I I �100 N 98�45�
�100 N S E
IS �100
IS IS
Lec - 9
Vth - VT 1 1
�100 )Dw w02
(3f ) ( L w02 1 LC < f Df �3Hz
Vth w02
LC
1t di dv di 1 d 2i
v(t ) Ri �
Ceq
-�
idt L
dt dt
R
dt Ceq
i L 2 w0
dt
d 1 1 1
DVL - DVC jI (w L - ) Dw I (2 2 )Dw w02 I ( L L )Dw
dw wCeq w0 Ceq LCeq
309
| VL - VC | 2 LI Dw 2 LI 2 LDw
j 2 LI Dw (DVL - DVC ) tan b 2 2 2 � 2p f Lm 106
| VR | a Rb I a Rb a Rb
106
Lm 3183.1H
2p
source. The fault strikes at time t t 0 . This can be simulated by closing the switch at t t1
310
R jwL or Z q models the line impedance. The fault current in the line is given by
i (t ) 0 0 t t0
t -t 0
V sin(w t f - q ) -
t
t t0
i (t ) m I 0e
|Z |
Where τ is the time constant of the line τ =L/R. The fault current has two components in
it. The first component models the steady state sinusoidal ac response while the second current
is the dc offset current due to the presence of inductive component in the circuit. Recall that
current in an inductance can not change instantaneously. As t ∞, the instantaneous dc
It is more or less obvious that, dc offset is not seen in the waveform after 5 time constants.
The value of I0 can be worked out by setting the current at t t o to zero.
This implies that
Vm
I0 - sin(wt 0 - q )
Z
311
Thus
t -t 0
Vm V -( )
i (t ) sin(wt f - q ) - m sin(wt f - q )e t
Z Z
fig.2
It can be seen that severity of dc offset component in fault current is maximum when
a) f q
p
b) wt 0
2
312
p 1
For example, if angle of transmission line is 800, then with f = 800 & t 0 =
2 2p 50 200
V
sec = 5msec, the severity of dc offset current would equal I 0 Z , which is also the peak
m
We now plan to show that CT can saturate on dc offset current. Also, we plan to show
that the resulting distortions in the CT secondary current can be un-acceptably high. While
doing this analysis, we will neglect ac symmetrical component. In other words, we rest our
belief in superposition theorem atleast qualitatively and will finally evaluate effect using it
Notice that the current that we are dealing with is non-linear, a rigorous application of super
position theorem is simply out of question.
313
First consider an ideal CT excited by the dc offset current source. An ideal CT will faithfully
replicates primary current waveform on the secondary side. Hence, the secondary current
would be given by
-t
I0 t
i2 (t ) e
N
and the voltage developed across CT secondary would be given by
-t
RI N2
v 2 (t ) 0 e t where N N
N 1
For simplicity, let us assume that the initial flux in the transformer core at t=0 is zero
f ( 0 ) 0 ; Then we can compute the flux in the transformer core by using faraday’s law
df
V2 N 2 ---------(2)
dt
314
t
f (t ) - f (0) v 0
2 dt
RI 0
-t
t 1- e t
N2
-t
LI 0
(1 - e t )
N2
-t
LI 0
f (t ) f (0) (1 - e t )
N2
-t
LI 0
(1 - e t ) ------- (3)
N2
as a consequence of dc offset current,
Thus, flux in the core increases exponentially to a peak value of
f dmax
c
LI 0
N2
as t
L Vm Vm
N Z Z
f dmax
c
Note that unlike ac voltage induced flux, which is sinusoidal, this flux is unidirectional. The ac
voltage induced flux has zero average value. However, dc offset induced does not have this
nice feature. The total flux in ideal CT core is a summation of ac flux and dc flux.
d
The ac flux in the CT core can be obtained by substituting operator by jw . Hence
dt
If v2 (t ) Vm sin(wt f ) , then
Vm p
f ac sin(wt f - )
wN 2 2
The peak value of ac flux is given by
315
Vm
f acmax
wN 2
However Vm R2 I 0
max
R2 I 0max
Hence facmax
wN 2
and peak value of the total flux is given by
Vm LI 0max
facmax f dcmax
wN 2 N2
In practice, if this flux exceeds the knee-point flux in the core (see fig.), then the CT core
will saturate.
As a consequence of CT core saturation, the secondary current would not faithfully replicate
the primary current. Infact, in practice it is observed that CT secondary current is clipped. The
clipping of CT current leads to “blinding” of the relay which cannot function further. Hence,
CT saturation in presence of dc offset current is a serious problem which relay designers have
to face. Note that dc flux accumulates gradually. (Depends upon the transmission line time
constant ( t ). It is apparent that saturation should not occur immediately after the inception of
the fault. Thus, if the relay is fast enough in decision making, it is likely that a relaying
decision would be undertaken before the CT fully saturates. This is another important reason
for increasing the speed of relaying system. For bus-fault protection, where the dc saturation
due to dc offset current can be a significant contributing factor, quarter cycle operations *****
316
specifically are imposed. Similarly, a distance relay is expected to operate within ½-1 cycle
time.
CT oversizing factors
Typically, an efficient design of transformer would correspond to choosing the core cross
section such that f mac should be near the knee point of B-H curve. One obvious way of
avoiding the CT saturation on dc flux is to oversize the core so that for flux (f acmax f dcmax ) , the
(f acmax f dcmax )
corresponding B is below the knee-point. Hence, the factor is called core-
f acmax
oversizing factor.
f dcmax
Core-oversizing factor = 1
f acmax
LI o N 2
1
RI 0 wN 2
wL
1
R
X
1
R
Note that X/R in above equation is the transmission line X/R ratio. For a 220KV line X/R 10.
This would imply that transformer core should be oversized by a factor of 11. For a 400KV
line, typical value of X/R 20. This would imply an oversizing required of about 21 times the
usual design. Clearly this high amount of oversizing is not practical. Thus, the important
conclusion is that, protection engineers have to live with the saturation problem.
Cautions in CT selection:
While choosing a CT for a particular application, it is necessary to observe following
precautions.
65. The CT rating and continuous load current should match. For example, if max load
current is 90A, a 100:5 Ct may be acceptable but 50:5 is not acceptable.
317
66. The maximum fault current should be less than 20 times the CT rated current. for
example 100:5 CT can be used, so long as burden on the CT & maximum primary fault
current is below 2000A.
67. The voltage rating of CT should be compatible. For example, 100:5 C100 would give
linear response, upto 20 times rated current provided CT burden is kept
below(100/20*5=1 Ω). With 2 Ω burden, this CT can be used only if maximum current
is limited to 1000A.
68. Parallel of CT’s e.g. in differential protection, or with SLG fault can create significant
errors in CT performance. One should in general ascertain that magnetizing current is
kept much below the pick up value.
Following example, illustrates this point
Exercise problems:
If the current ratio is adequate for a protection, but CT burden is high; then the
performance of CT may deteriorate due to large magnetizing current and/or saturation problem.
The CT performance can be improved by connecting the CT’s in series.
33) Show the dotted terminals for correct secondary series connection
34) What is the VA of CT in fig (a) & (b) respectively?
49) Electromechanical relays tend to saturate at high currents. This reduces the relay burden
on CT, and so that the CT performance at moderately high currents may be considered
better than at relay’s rated burden at 5A.
50) Use of instantaneous over current relays has the potential to overcome this problem of
saturation of CT’s
318
51) Differential protection can operate on external faults due to the un equal saturation of
CT’s
Lecture-6
Examples
22. If a 300:5 class C CT is connected to a meter with resistance R I 1 and
secondary current in the CT is 4.5A find out the primary current voltage
developed across the meter and % rate error. Lead wire resistance R L 0.02
secondary resistance RS of a 300/5 CT 0.15
Diagram
R I 1 , R L 0.02 RS 0.15 I S 4.5 A
Total secondary resistance RT R I R L RS
1.17
Secondary voltage I S RT
4.5 1.17
5.265V
From Fig 5.7,
Exciting current IE for 5.265V
= 0.03A
Turns ratio N = 300/5 = 60
I p N (I S I E )
= 60(4.5 + 0.03)
= 271.8A
Voltage across meter I S R I
4.5 1 = 4.5V
IE 0.03
Ratio error 100 100
IS 4.5
= 0.67%
Rb
319
Lecture – 8
Examples
33. Design a CCVT for a 132kV transmission line using the following data.
Resistive Burden (3f )-150VA
Df 3Hz , phase angle error b = 40 min
Consider 4 choices of V2 as 33kV, 11kV, 6.6kV and 3.3kV
Diagram 1 Diagram 2
Transmission line voltage V = 132kV. Suppose V 2 (P_N) be the voltage to be
produced by the capacitive potential divider with capacitance values C1 and C2
and L the value of tuning inductor. The standardized VT secondary voltage is 110
volts (L-L).
Here specification for phase angle error b is 40 minutes variation in frequency
can be upto Df 3Hz . Phase angle error for change in w by Dw in the above
equation circuit, is given by
1
( L 2 )Dw
w C
1
At tuning frequency w 2
LC
Substituting w 1 LC
2
747.2 H
1 1
C1 C 2
w 2 L (3/ 4) 2 747.2
1.3610 -2 F
3) V2 6.6kV
3 �(6.6 �103 )2
Rb
'
150
87.1210 4
b �Rb' 0.01164 �87.12 �104
L
2 �Dw 2 �2p �3
269H ,
C1 C 2 3.7710 -2 F
4) V2 3.3kV
3 �(3.3 �103 ) 2
Rb'
150
21.7810 4
b �Rb' 0.01164 �21.78 �104
L
2 �Dw 2 �2p �3
67.25 H
C1 C2 0.151 F
The values of L, C1 C 2 for different values of V2 are tabulated below.
V2 L C1 C 2
33kV 6722.2H 0.00151 F
11kV 747.2H 0.0136 F
6.6kV 269H 0.0377 F
3.3kV 67.25H 0.151 F
From the above table it is clear that smaller the value of V 2, the smaller is the
value of L and higher the value of C 1 and C2 for tuning condition. If we select too low
value of V2 and L then capacitance values will be beyond available limits, and if we
select higher value of V2 and L, then CCVT and inductor will become bulky. So a
compromise is necessary and let us select V2 = 6.6kV
For V2 = 6.6kV
L = 269H
C1 C 2 0.0377 F
V C1 C 2
Now,
V2 C1
13210 3 0.037710 -6
36.610 3
C1
0.0377 36.610 3 10 -6 F
C1
13210 3
0.0033F
321
C 2 0.0344F
In this design, we explained the basic concept for CCVT design and we assumed
the transformer to be ideal. But in actual design practice the value of magnetizing
impedance of transformer, resistance of reactor etc have to be taken into account,
as ratio error a and phase angle error b will also get affected by these values.
34. Diagram
The equivalent circuit of a CCVT is shown in fig 8.3. The values of C 1 and C2 are
0.0018 F and 0.018 F respectively. Tuning inductor has an inductance of
497H and resistance of 4620 .
Xm of the 6.6kV VT is 1M , core loss = 20 watts per phase, VA burden =
150VA per phase. Value of Cm for compensating the current drawn by m is equal
to 3.18310 -9 F .
(ww) Verify the appropriateness of choice of L and Cm.
Ans: If C1 0.0018F and C 2 0.0186F then the value L of tuning inductor
is given by
1
L 2
w (C1 C 2 )
where w 2p f and f = tuning frequency
1
L
(2p �50) (0.0018 0.0186) �10-6
2
1
Xm
w Cm
1 1
Cm
w X m (2p �50) �� 1 106
3.183 �10-9 F
The value is also same as the selected value of Cm Hence the selection of both L
and Cm is appropriate.
(yy) If the frequency drops from 50Hz to 47Hz, what would be the values of
ratio error and phase angle error?
Ans: Core loss = 20w
V22
20W
Rm
322
V22 (6600) 2
Rm
20 20
2.18 �10
6
6600 0
A
260874.14 -2.44�
VT I th �Z
6600 0
�256147.5 1.82�
260874.14 -2.44�
6480.42 4.26�
(6600 - 6480.42)
Hence % ratio error �100
6600
=1.81%
Phase angle error = 4.26�
V2 6.6kV
r a w2 a 2
M
d 2i R di 1 1 R
t �t0 2
i0 wn 2p �50 2 Iwn
dt L dt LCeq LC L
d 2i
2
2a wn wn2i 0 a < 1
dt
Lec – 8
1
2p �50 2zw R d i 2zw w 2i 0 z wn z < 1
2
wn
LCeq n
L dt 2 n n
-t V
t I 0 - m sin(wt0 f - q ) f q
e | Z line |
324
Example 1:
d
325
Answer:
Based on the criteria that the CT can deliver 20 times rated secondary current
without exceeding a 10% ratio error, the maximum fault current will be 24000A.
However, with a 2.0Ω burden, this will result in a voltage below the knee point of the CT
and, as a practical matter, it will be within 10% accuracy at higher currents. This can only
be accurately determined from excitation or ratio correction curves and not from the
accuracy classification. For example, a CT with characteristics shown in above figure
will produce between 180-240A without exceeding the 10% ratio error, depending on the
power factor of the 2.0Ω burden.
Example 2:
A 1200/5, C400 CT is connected on the 1000/5 tap. What is the maximum secondary
burden that can be used and still maintain rated accuracy at 20 times rated symmetrical
secondary current?
Answer:
Since the secondary voltage capability is directly proportional to the connected tap, the
CT will support a voltage of 1000/1200 400V or 333V. Twenty times the rated
secondary current is 100A. Therefore, the maximum burden is 333V/100A or 3.33 Ω
Example 3:
Assume that secondary burden in a relay circuit is 5Ω. The relay setting is 2A and the CT
ratio is 300/5. Using above figure, calculate the primary current required to operate the
relay?
Answer:
326
N (I E I S )
= 300/5(0.04+2) A=122A
Example 4:
A relay is expected to operate for a 7000A primary current. The CT ratio is 600/5.
Secondary burden is 3.5 Ω. What is the error for the CT shown in above figure?
Answer:
The total secondary fault current is (7000/600) 5=58A. Assume that exciting current is
negligible.
VS I S ( R B RS )
= 58(3.5+0.31)
= 221V
The exciting current will not be negligible, however, and the calculation will not be
iterated.
Lec – 7
N1 RI 0 Vm N1 R Vm Vm N1 N1 RI 0 -tt N1 I 0 -tt
fdcmax t t N1 Rt v2 (t )
dc
e i2 e
N 22 | Z line | N 22 | Z line | | Z line | N 22 N2 N2
t -t -t
1 N1 RI 0 t N1 RI 0
f (t ) - f (0) t (1 - e ) f (t ) f (0) t (1 - e t )
N2 �
v2 dt 2 2
0
N 2 N 2
Lec- 7
327
Vm N1 d V2
v2ac (t ) R sin(wt f - q ) jw f ac
| Z line | N 2 dt jw N 2
RVm N1 p RVm N1
fac (t ) sin(wt f - q - ) facmax
w | Z line | N 2
2
2 w | Z line | N 22
Vm N1
Rt
RVm N1 N1 RVmt | Z line | N 22 wL X
facmax fdcmax 2 1 1 wt 1 line 1 line
w | Z line | N 2 N 2 | Z line |
2
Vm N1 R Rline Rline
| Z line | N 2 w
2
X
1
R
Lec-6
Lec – 5
Ip Ip
- IS Ip IE - IS
N - I I �100 N 98�45�
�100 N S E
IS �100
IS IS
Lec - 9
Vth - VT 1 1
�100 )Dw w02
(3f ) ( L w02 1 LC < f Df �3Hz
Vth w02
LC
1t di dv di 1 d 2i
v(t ) Ri �
Ceq
-�
idt L
dt dt
R
dt Ceq
i L 2 w0
dt
d 1 1 1
DVL - DVC jI (w L - ) Dw I (2 2 )Dw w02 I ( L L )Dw
dw wCeq w0 Ceq LCeq
328
| VL - VC | 2 LI Dw 2 LI 2 LDw
j 2 LI Dw (DVL - DVC ) tan b 2 2 2 � 2p f Lm 106
| VR | a Rb I a Rb a Rb
106
Lm 3183.1H
2p
source. The fault strikes at time t t 0 . This can be simulated by closing the switch at t t1
329
R jwL or Z q models the line impedance. The fault current in the line is given by
i (t ) 0 0 t t0
t -t 0
V sin(w t f - q ) -
t
t t0
i (t ) m I 0e
|Z |
Where τ is the time constant of the line τ =L/R. The fault current has two components in
it. The first component models the steady state sinusoidal ac response while the second current
is the dc offset current due to the presence of inductive component in the circuit. Recall that
current in an inductance can not change instantaneously. As t ∞, the instantaneous dc
It is more or less obvious that, dc offset is not seen in the waveform after 5 time constants.
The value of I0 can be worked out by setting the current at t t o to zero.
This implies that
Vm
I0 - sin(wt 0 - q )
Z
330
Thus
t -t 0
Vm V -( )
i (t ) sin(wt f - q ) - m sin(wt f - q )e t
Z Z
fig.2
It can be seen that severity of dc offset component in fault current is maximum when
a) f q
p
b) wt 0
2
331
p 1
For example, if angle of transmission line is 800, then with f = 800 & t 0 =
2 2p 50 200
V
sec = 5msec, the severity of dc offset current would equal I 0 Z , which is also the peak
m
We now plan to show that CT can saturate on dc offset current. Also, we plan to show
that the resulting distortions in the CT secondary current can be un-acceptably high. While
doing this analysis, we will neglect ac symmetrical component. In other words, we rest our
belief in superposition theorem atleast qualitatively and will finally evaluate effect using it
Notice that the current that we are dealing with is non-linear, a rigorous application of super
position theorem is simply out of question.
332
First consider an ideal CT excited by the dc offset current source. An ideal CT will faithfully
replicates primary current waveform on the secondary side. Hence, the secondary current
would be given by
-t
I0 t
i2 (t ) e
N
and the voltage developed across CT secondary would be given by
-t
RI N2
v 2 (t ) 0 e t where N N
N 1
For simplicity, let us assume that the initial flux in the transformer core at t=0 is zero
f ( 0 ) 0 ; Then we can compute the flux in the transformer core by using faraday’s law
df
V2 N 2 ---------(2)
dt
333
t
f (t ) - f (0) v 0
2 dt
RI 0
-t
t 1- e t
N2
-t
LI 0
(1 - e t )
N2
-t
LI 0
f (t ) f (0) (1 - e t )
N2
-t
LI 0
(1 - e t ) ------- (3)
N2
as a consequence of dc offset current,
Thus, flux in the core increases exponentially to a peak value of
f dmax
c
LI 0
N2
as t
L Vm Vm
N Z Z
f dmax
c
Note that unlike ac voltage induced flux, which is sinusoidal, this flux is unidirectional. The ac
voltage induced flux has zero average value. However, dc offset induced does not have this
nice feature. The total flux in ideal CT core is a summation of ac flux and dc flux.
d
The ac flux in the CT core can be obtained by substituting operator by jw . Hence
dt
If v2 (t ) Vm sin(wt f ) , then
Vm p
f ac sin(wt f - )
wN 2 2
The peak value of ac flux is given by
334
Vm
f acmax
wN 2
However Vm R2 I 0
max
R2 I 0max
Hence facmax
wN 2
and peak value of the total flux is given by
Vm LI 0max
facmax f dcmax
wN 2 N2
In practice, if this flux exceeds the knee-point flux in the core (see fig.), then the CT core
will saturate.
As a consequence of CT core saturation, the secondary current would not faithfully replicate
the primary current. Infact, in practice it is observed that CT secondary current is clipped. The
clipping of CT current leads to “blinding” of the relay which cannot function further. Hence,
CT saturation in presence of dc offset current is a serious problem which relay designers have
to face. Note that dc flux accumulates gradually. (Depends upon the transmission line time
constant ( t ). It is apparent that saturation should not occur immediately after the inception of
the fault. Thus, if the relay is fast enough in decision making, it is likely that a relaying
decision would be undertaken before the CT fully saturates. This is another important reason
for increasing the speed of relaying system. For bus-fault protection, where the dc saturation
due to dc offset current can be a significant contributing factor, quarter cycle operations *****
335
specifically are imposed. Similarly, a distance relay is expected to operate within ½-1 cycle
time.
CT oversizing factors
Typically, an efficient design of transformer would correspond to choosing the core cross
section such that f mac should be near the knee point of B-H curve. One obvious way of
avoiding the CT saturation on dc flux is to oversize the core so that for flux (f acmax f dcmax ) , the
(f acmax f dcmax )
corresponding B is below the knee-point. Hence, the factor is called core-
f acmax
oversizing factor.
f dcmax
Core-oversizing factor = 1
f acmax
LI o N 2
1
RI 0 wN 2
wL
1
R
X
1
R
Note that X/R in above equation is the transmission line X/R ratio. For a 220KV line X/R 10.
This would imply that transformer core should be oversized by a factor of 11. For a 400KV
line, typical value of X/R 20. This would imply an oversizing required of about 21 times the
usual design. Clearly this high amount of oversizing is not practical. Thus, the important
conclusion is that, protection engineers have to live with the saturation problem.
Cautions in CT selection:
While choosing a CT for a particular application, it is necessary to observe following
precautions.
69. The CT rating and continuous load current should match. For example, if max load
current is 90A, a 100:5 Ct may be acceptable but 50:5 is not acceptable.
336
70. The maximum fault current should be less than 20 times the CT rated current. for
example 100:5 CT can be used, so long as burden on the CT & maximum primary fault
current is below 2000A.
71. The voltage rating of CT should be compatible. For example, 100:5 C100 would give
linear response, upto 20 times rated current provided CT burden is kept
below(100/20*5=1 Ω). With 2 Ω burden, this CT can be used only if maximum current
is limited to 1000A.
72. Parallel of CT’s e.g. in differential protection, or with SLG fault can create significant
errors in CT performance. One should in general ascertain that magnetizing current is
kept much below the pick up value.
Following example, illustrates this point
Exercise problems:
If the current ratio is adequate for a protection, but CT burden is high; then the
performance of CT may deteriorate due to large magnetizing current and/or saturation problem.
The CT performance can be improved by connecting the CT’s in series.
35) Show the dotted terminals for correct secondary series connection
36) What is the VA of CT in fig (a) & (b) respectively?
52) Electromechanical relays tend to saturate at high currents. This reduces the relay burden
on CT, and so that the CT performance at moderately high currents may be considered
better than at relay’s rated burden at 5A.
53) Use of instantaneous over current relays has the potential to overcome this problem of
saturation of CT’s
337
54) Differential protection can operate on external faults due to the un equal saturation of
CT’s
Lecture-6
Examples
23. If a 300:5 class C CT is connected to a meter with resistance R I 1 and
secondary current in the CT is 4.5A find out the primary current voltage
developed across the meter and % rate error. Lead wire resistance R L 0.02
secondary resistance RS of a 300/5 CT 0.15
Diagram
R I 1 , R L 0.02 RS 0.15 I S 4.5 A
Total secondary resistance RT R I R L RS
1.17
Secondary voltage I S RT
4.5 1.17
5.265V
From Fig 5.7,
Exciting current IE for 5.265V
= 0.03A
Turns ratio N = 300/5 = 60
I p N (I S I E )
= 60(4.5 + 0.03)
= 271.8A
Voltage across meter I S R I
4.5 1 = 4.5V
IE 0.03
Ratio error 100 100
IS 4.5
= 0.67%
Rb
338
Lecture – 8
Examples
35. Design a CCVT for a 132kV transmission line using the following data.
Resistive Burden (3f )-150VA
Df 3Hz , phase angle error b = 40 min
Consider 4 choices of V2 as 33kV, 11kV, 6.6kV and 3.3kV
Diagram 1 Diagram 2
Transmission line voltage V = 132kV. Suppose V 2 (P_N) be the voltage to be
produced by the capacitive potential divider with capacitance values C1 and C2
and L the value of tuning inductor. The standardized VT secondary voltage is 110
volts (L-L).
Here specification for phase angle error b is 40 minutes variation in frequency
can be upto Df 3Hz . Phase angle error for change in w by Dw in the above
equation circuit, is given by
1
( L 2 )Dw
w C
1
At tuning frequency w 2
LC
Substituting w 1 LC
2
747.2 H
1 1
C1 C 2
w 2 L (3/ 4) 2 747.2
1.3610 -2 F
3) V2 6.6kV
3 �(6.6 �103 )2
Rb
'
150
87.1210 4
b �Rb' 0.01164 �87.12 �104
L
2 �Dw 2 �2p �3
269H ,
C1 C 2 3.7710 -2 F
4) V2 3.3kV
3 �(3.3 �103 ) 2
Rb'
150
21.7810 4
b �Rb' 0.01164 �21.78 �104
L
2 �Dw 2 �2p �3
67.25 H
C1 C2 0.151 F
The values of L, C1 C 2 for different values of V2 are tabulated below.
V2 L C1 C 2
33kV 6722.2H 0.00151 F
11kV 747.2H 0.0136 F
6.6kV 269H 0.0377 F
3.3kV 67.25H 0.151 F
From the above table it is clear that smaller the value of V 2, the smaller is the
value of L and higher the value of C 1 and C2 for tuning condition. If we select too low
value of V2 and L then capacitance values will be beyond available limits, and if we
select higher value of V2 and L, then CCVT and inductor will become bulky. So a
compromise is necessary and let us select V2 = 6.6kV
For V2 = 6.6kV
L = 269H
C1 C 2 0.0377 F
V C1 C 2
Now,
V2 C1
13210 3 0.037710 -6
36.610 3
C1
0.0377 36.610 3 10 -6 F
C1
13210 3
0.0033F
340
C 2 0.0344F
In this design, we explained the basic concept for CCVT design and we assumed
the transformer to be ideal. But in actual design practice the value of magnetizing
impedance of transformer, resistance of reactor etc have to be taken into account,
as ratio error a and phase angle error b will also get affected by these values.
36. Diagram
The equivalent circuit of a CCVT is shown in fig 8.3. The values of C 1 and C2 are
0.0018 F and 0.018 F respectively. Tuning inductor has an inductance of
497H and resistance of 4620 .
Xm of the 6.6kV VT is 1M , core loss = 20 watts per phase, VA burden =
150VA per phase. Value of Cm for compensating the current drawn by m is equal
to 3.18310 -9 F .
(zz) Verify the appropriateness of choice of L and Cm.
Ans: If C1 0.0018F and C 2 0.0186F then the value L of tuning inductor
is given by
1
L 2
w (C1 C 2 )
where w 2p f and f = tuning frequency
1
L
(2p �50) (0.0018 0.0186) �10-6
2
1
Xm
w Cm
1 1
Cm
w X m (2p �50) �� 1 106
3.183 �10-9 F
The value is also same as the selected value of Cm Hence the selection of both L
and Cm is appropriate.
(bbb) If the frequency drops from 50Hz to 47Hz, what would be the values of
ratio error and phase angle error?
Ans: Core loss = 20w
V22
20W
Rm
341
V22 (6600) 2
Rm
20 20
2.18 �10
6
6600 0
A
260874.14 -2.44�
VT I th �Z
6600 0
�256147.5 1.82�
260874.14 -2.44�
6480.42 4.26�
(6600 - 6480.42)
Hence % ratio error �100
6600
=1.81%
Phase angle error = 4.26�
V2 6.6kV
r a w2 a 2
M
d 2i R di 1 1 R
t �t0 2
i0 wn 2p �50 2 Iwn
dt L dt LCeq LC L
d 2i
2
2a wn wn2i 0 a < 1
dt
Lec – 8
1
2p �50 2zw R d i 2zw w 2i 0 z wn z < 1
2
wn
LCeq n
L dt 2 n n
-t V
t I 0 - m sin(wt0 f - q ) f q
e | Z line |
343
Example 1:
d
344
Answer:
Based on the criteria that the CT can deliver 20 times rated secondary current
without exceeding a 10% ratio error, the maximum fault current will be 24000A.
However, with a 2.0Ω burden, this will result in a voltage below the knee point of the CT
and, as a practical matter, it will be within 10% accuracy at higher currents. This can only
be accurately determined from excitation or ratio correction curves and not from the
accuracy classification. For example, a CT with characteristics shown in above figure
will produce between 180-240A without exceeding the 10% ratio error, depending on the
power factor of the 2.0Ω burden.
Example 2:
A 1200/5, C400 CT is connected on the 1000/5 tap. What is the maximum secondary
burden that can be used and still maintain rated accuracy at 20 times rated symmetrical
secondary current?
Answer:
Since the secondary voltage capability is directly proportional to the connected tap, the
CT will support a voltage of 1000/1200 400V or 333V. Twenty times the rated
secondary current is 100A. Therefore, the maximum burden is 333V/100A or 3.33 Ω
Example 3:
Assume that secondary burden in a relay circuit is 5Ω. The relay setting is 2A and the CT
ratio is 300/5. Using above figure, calculate the primary current required to operate the
relay?
Answer:
345
N (I E I S )
= 300/5(0.04+2) A=122A
Example 4:
A relay is expected to operate for a 7000A primary current. The CT ratio is 600/5.
Secondary burden is 3.5 Ω. What is the error for the CT shown in above figure?
Answer:
The total secondary fault current is (7000/600) 5=58A. Assume that exciting current is
negligible.
VS I S ( R B RS )
= 58(3.5+0.31)
= 221V
The exciting current will not be negligible, however, and the calculation will not be
iterated.
Lec – 7
N1 RI 0 Vm N1 R Vm Vm N1 N1 RI 0 -tt N1 I 0 -tt
fdcmax t t N1 Rt v2 (t )
dc
e i2 e
N 22 | Z line | N 22 | Z line | | Z line | N 22 N2 N2
t -t -t
1 N1 RI 0 t N1 RI 0
f (t ) - f (0) t (1 - e ) f (t ) f (0) t (1 - e t )
N2 �
v2 dt 2 2
0
N 2 N 2
Lec- 7
346
Vm N1 d V2
v2ac (t ) R sin(wt f - q ) jw f ac
| Z line | N 2 dt jw N 2
RVm N1 p RVm N1
fac (t ) sin(wt f - q - ) facmax
w | Z line | N 2
2
2 w | Z line | N 22
Vm N1
Rt
RVm N1 N1 RVmt | Z line | N 22 wL X
facmax fdcmax 2 1 1 wt 1 line 1 line
w | Z line | N 2 N 2 | Z line |
2
Vm N1 R Rline Rline
| Z line | N 2 w
2
X
1
R
Lec-6
Lec – 5
Ip Ip
- IS Ip IE - IS
N - I I �100 N 98�45�
�100 N S E
IS �100
IS IS
Lec - 9
Vth - VT 1 1
�100 )Dw w02
(3f ) ( L w02 1 LC < f Df �3Hz
Vth w02
LC
1t di dv di 1 d 2i
v(t ) Ri �
Ceq
-�
idt L
dt dt
R
dt Ceq
i L 2 w0
dt
d 1 1 1
DVL - DVC jI (w L - ) Dw I (2 2 )Dw w02 I ( L L )Dw
dw wCeq w0 Ceq LCeq
347
| VL - VC | 2 LI Dw 2 LI 2 LDw
j 2 LI Dw (DVL - DVC ) tan b 2 2 2 � 2p f Lm 106
| VR | a Rb I a Rb a Rb
106
Lm 3183.1H
2p
source. The fault strikes at time t t 0 . This can be simulated by closing the switch at t t1
348
R jwL or Z q models the line impedance. The fault current in the line is given by
i (t ) 0 0 t t0
t -t 0
V sin(w t f - q ) -
t
t t0
i (t ) m I 0e
|Z |
Where τ is the time constant of the line τ =L/R. The fault current has two components in
it. The first component models the steady state sinusoidal ac response while the second current
is the dc offset current due to the presence of inductive component in the circuit. Recall that
current in an inductance can not change instantaneously. As t ∞, the instantaneous dc
It is more or less obvious that, dc offset is not seen in the waveform after 5 time constants.
The value of I0 can be worked out by setting the current at t t o to zero.
This implies that
Vm
I0 - sin(wt 0 - q )
Z
349
Thus
t -t 0
Vm V -( )
i (t ) sin(wt f - q ) - m sin(wt f - q )e t
Z Z
fig.2
It can be seen that severity of dc offset component in fault current is maximum when
a) f q
p
b) wt 0
2
350
p 1
For example, if angle of transmission line is 800, then with f = 800 & t 0 =
2 2p 50 200
V
sec = 5msec, the severity of dc offset current would equal I 0 Z , which is also the peak
m
We now plan to show that CT can saturate on dc offset current. Also, we plan to show
that the resulting distortions in the CT secondary current can be un-acceptably high. While
doing this analysis, we will neglect ac symmetrical component. In other words, we rest our
belief in superposition theorem atleast qualitatively and will finally evaluate effect using it
Notice that the current that we are dealing with is non-linear, a rigorous application of super
position theorem is simply out of question.
351
First consider an ideal CT excited by the dc offset current source. An ideal CT will faithfully
replicates primary current waveform on the secondary side. Hence, the secondary current
would be given by
-t
I0 t
i2 (t ) e
N
and the voltage developed across CT secondary would be given by
-t
RI N2
v 2 (t ) 0 e t where N N
N 1
For simplicity, let us assume that the initial flux in the transformer core at t=0 is zero
f ( 0 ) 0 ; Then we can compute the flux in the transformer core by using faraday’s law
df
V2 N 2 ---------(2)
dt
352
t
f (t ) - f (0) v 0
2 dt
RI 0
-t
t 1- e t
N2
-t
LI 0
(1 - e t )
N2
-t
LI 0
f (t ) f (0) (1 - e t )
N2
-t
LI 0
(1 - e t ) ------- (3)
N2
as a consequence of dc offset current,
Thus, flux in the core increases exponentially to a peak value of
f dmax
c
LI 0
N2
as t
L Vm Vm
N Z Z
f dmax
c
Note that unlike ac voltage induced flux, which is sinusoidal, this flux is unidirectional. The ac
voltage induced flux has zero average value. However, dc offset induced does not have this
nice feature. The total flux in ideal CT core is a summation of ac flux and dc flux.
d
The ac flux in the CT core can be obtained by substituting operator by jw . Hence
dt
If v2 (t ) Vm sin(wt f ) , then
Vm p
f ac sin(wt f - )
wN 2 2
The peak value of ac flux is given by
353
Vm
f acmax
wN 2
However Vm R2 I 0
max
R2 I 0max
Hence facmax
wN 2
and peak value of the total flux is given by
Vm LI 0max
facmax f dcmax
wN 2 N2
In practice, if this flux exceeds the knee-point flux in the core (see fig.), then the CT core
will saturate.
As a consequence of CT core saturation, the secondary current would not faithfully replicate
the primary current. Infact, in practice it is observed that CT secondary current is clipped. The
clipping of CT current leads to “blinding” of the relay which cannot function further. Hence,
CT saturation in presence of dc offset current is a serious problem which relay designers have
to face. Note that dc flux accumulates gradually. (Depends upon the transmission line time
constant ( t ). It is apparent that saturation should not occur immediately after the inception of
the fault. Thus, if the relay is fast enough in decision making, it is likely that a relaying
decision would be undertaken before the CT fully saturates. This is another important reason
for increasing the speed of relaying system. For bus-fault protection, where the dc saturation
due to dc offset current can be a significant contributing factor, quarter cycle operations *****
354
specifically are imposed. Similarly, a distance relay is expected to operate within ½-1 cycle
time.
CT oversizing factors
Typically, an efficient design of transformer would correspond to choosing the core cross
section such that f mac should be near the knee point of B-H curve. One obvious way of
avoiding the CT saturation on dc flux is to oversize the core so that for flux (f acmax f dcmax ) , the
(f acmax f dcmax )
corresponding B is below the knee-point. Hence, the factor is called core-
f acmax
oversizing factor.
f dcmax
Core-oversizing factor = 1
f acmax
LI o N 2
1
RI 0 wN 2
wL
1
R
X
1
R
Note that X/R in above equation is the transmission line X/R ratio. For a 220KV line X/R 10.
This would imply that transformer core should be oversized by a factor of 11. For a 400KV
line, typical value of X/R 20. This would imply an oversizing required of about 21 times the
usual design. Clearly this high amount of oversizing is not practical. Thus, the important
conclusion is that, protection engineers have to live with the saturation problem.
Cautions in CT selection:
While choosing a CT for a particular application, it is necessary to observe following
precautions.
73. The CT rating and continuous load current should match. For example, if max load
current is 90A, a 100:5 Ct may be acceptable but 50:5 is not acceptable.
355
74. The maximum fault current should be less than 20 times the CT rated current. for
example 100:5 CT can be used, so long as burden on the CT & maximum primary fault
current is below 2000A.
75. The voltage rating of CT should be compatible. For example, 100:5 C100 would give
linear response, upto 20 times rated current provided CT burden is kept
below(100/20*5=1 Ω). With 2 Ω burden, this CT can be used only if maximum current
is limited to 1000A.
76. Parallel of CT’s e.g. in differential protection, or with SLG fault can create significant
errors in CT performance. One should in general ascertain that magnetizing current is
kept much below the pick up value.
Following example, illustrates this point
Exercise problems:
If the current ratio is adequate for a protection, but CT burden is high; then the
performance of CT may deteriorate due to large magnetizing current and/or saturation problem.
The CT performance can be improved by connecting the CT’s in series.
37) Show the dotted terminals for correct secondary series connection
38) What is the VA of CT in fig (a) & (b) respectively?
55) Electromechanical relays tend to saturate at high currents. This reduces the relay burden
on CT, and so that the CT performance at moderately high currents may be considered
better than at relay’s rated burden at 5A.
56) Use of instantaneous over current relays has the potential to overcome this problem of
saturation of CT’s
356
57) Differential protection can operate on external faults due to the un equal saturation of
CT’s
Lecture-6
Examples
24. If a 300:5 class C CT is connected to a meter with resistance R I 1 and
secondary current in the CT is 4.5A find out the primary current voltage
developed across the meter and % rate error. Lead wire resistance R L 0.02
secondary resistance RS of a 300/5 CT 0.15
Diagram
R I 1 , R L 0.02 RS 0.15 I S 4.5 A
Total secondary resistance RT R I R L RS
1.17
Secondary voltage I S RT
4.5 1.17
5.265V
From Fig 5.7,
Exciting current IE for 5.265V
= 0.03A
Turns ratio N = 300/5 = 60
I p N (I S I E )
= 60(4.5 + 0.03)
= 271.8A
Voltage across meter I S R I
4.5 1 = 4.5V
IE 0.03
Ratio error 100 100
IS 4.5
= 0.67%
Rb
357
Lecture – 8
Examples
37. Design a CCVT for a 132kV transmission line using the following data.
Resistive Burden (3f )-150VA
Df 3Hz , phase angle error b = 40 min
Consider 4 choices of V2 as 33kV, 11kV, 6.6kV and 3.3kV
Diagram 1 Diagram 2
Transmission line voltage V = 132kV. Suppose V 2 (P_N) be the voltage to be
produced by the capacitive potential divider with capacitance values C1 and C2
and L the value of tuning inductor. The standardized VT secondary voltage is 110
volts (L-L).
Here specification for phase angle error b is 40 minutes variation in frequency
can be upto Df 3Hz . Phase angle error for change in w by Dw in the above
equation circuit, is given by
1
( L 2 )Dw
w C
1
At tuning frequency w 2
LC
Substituting w 1 LC
2
747.2 H
1 1
C1 C 2
w 2 L (3/ 4) 2 747.2
1.3610 -2 F
3) V2 6.6kV
3 �(6.6 �103 )2
Rb
'
150
87.1210 4
b �Rb' 0.01164 �87.12 �104
L
2 �Dw 2 �2p �3
269H ,
C1 C 2 3.7710 -2 F
4) V2 3.3kV
3 �(3.3 �103 ) 2
Rb'
150
21.7810 4
b �Rb' 0.01164 �21.78 �104
L
2 �Dw 2 �2p �3
67.25 H
C1 C2 0.151 F
The values of L, C1 C 2 for different values of V2 are tabulated below.
V2 L C1 C 2
33kV 6722.2H 0.00151 F
11kV 747.2H 0.0136 F
6.6kV 269H 0.0377 F
3.3kV 67.25H 0.151 F
From the above table it is clear that smaller the value of V 2, the smaller is the
value of L and higher the value of C 1 and C2 for tuning condition. If we select too low
value of V2 and L then capacitance values will be beyond available limits, and if we
select higher value of V2 and L, then CCVT and inductor will become bulky. So a
compromise is necessary and let us select V2 = 6.6kV
For V2 = 6.6kV
L = 269H
C1 C 2 0.0377 F
V C1 C 2
Now,
V2 C1
13210 3 0.037710 -6
36.610 3
C1
0.0377 36.610 3 10 -6 F
C1
13210 3
0.0033F
359
C 2 0.0344F
In this design, we explained the basic concept for CCVT design and we assumed
the transformer to be ideal. But in actual design practice the value of magnetizing
impedance of transformer, resistance of reactor etc have to be taken into account,
as ratio error a and phase angle error b will also get affected by these values.
38. Diagram
The equivalent circuit of a CCVT is shown in fig 8.3. The values of C 1 and C2 are
0.0018 F and 0.018 F respectively. Tuning inductor has an inductance of
497H and resistance of 4620 .
Xm of the 6.6kV VT is 1M , core loss = 20 watts per phase, VA burden =
150VA per phase. Value of Cm for compensating the current drawn by m is equal
to 3.18310 -9 F .
(ccc) Verify the appropriateness of choice of L and Cm.
Ans: If C1 0.0018F and C 2 0.0186F then the value L of tuning inductor
is given by
1
L 2
w (C1 C 2 )
where w 2p f and f = tuning frequency
1
L
(2p �50) (0.0018 0.0186) �10-6
2
1
Xm
w Cm
1 1
Cm
w X m (2p �50) �� 1 106
3.183 �10-9 F
The value is also same as the selected value of Cm Hence the selection of both L
and Cm is appropriate.
(eee) If the frequency drops from 50Hz to 47Hz, what would be the values of
ratio error and phase angle error?
Ans: Core loss = 20w
V22
20W
Rm
360
V22 (6600) 2
Rm
20 20
2.18 �10
6
6600 0
A
260874.14 -2.44�
VT I th �Z
6600 0
�256147.5 1.82�
260874.14 -2.44�
6480.42 4.26�
(6600 - 6480.42)
Hence % ratio error �100
6600
=1.81%
Phase angle error = 4.26�
V2 6.6kV
r a w2 a 2
M
d 2i R di 1 1 R
t �t0 2
i0 wn 2p �50 2 Iwn
dt L dt LCeq LC L
d 2i
2
2a wn wn2i 0 a < 1
dt
Lec – 8
1
2p �50 2zw R d i 2zw w 2i 0 z wn z < 1
2
wn
LCeq n
L dt 2 n n
-t V
t I 0 - m sin(wt0 f - q ) f q
e | Z line |
362
Example 1:
d
363
Answer:
Based on the criteria that the CT can deliver 20 times rated secondary current
without exceeding a 10% ratio error, the maximum fault current will be 24000A.
However, with a 2.0Ω burden, this will result in a voltage below the knee point of the CT
and, as a practical matter, it will be within 10% accuracy at higher currents. This can only
be accurately determined from excitation or ratio correction curves and not from the
accuracy classification. For example, a CT with characteristics shown in above figure
will produce between 180-240A without exceeding the 10% ratio error, depending on the
power factor of the 2.0Ω burden.
Example 2:
A 1200/5, C400 CT is connected on the 1000/5 tap. What is the maximum secondary
burden that can be used and still maintain rated accuracy at 20 times rated symmetrical
secondary current?
Answer:
Since the secondary voltage capability is directly proportional to the connected tap, the
CT will support a voltage of 1000/1200 400V or 333V. Twenty times the rated
secondary current is 100A. Therefore, the maximum burden is 333V/100A or 3.33 Ω
Example 3:
Assume that secondary burden in a relay circuit is 5Ω. The relay setting is 2A and the CT
ratio is 300/5. Using above figure, calculate the primary current required to operate the
relay?
Answer:
364
N (I E I S )
= 300/5(0.04+2) A=122A
Example 4:
A relay is expected to operate for a 7000A primary current. The CT ratio is 600/5.
Secondary burden is 3.5 Ω. What is the error for the CT shown in above figure?
Answer:
The total secondary fault current is (7000/600) 5=58A. Assume that exciting current is
negligible.
VS I S ( R B RS )
= 58(3.5+0.31)
= 221V
The exciting current will not be negligible, however, and the calculation will not be
iterated.
Lec – 7
N1 RI 0 Vm N1 R Vm Vm N1 N1 RI 0 -tt N1 I 0 -tt
fdcmax t t N1 Rt v2 (t )
dc
e i2 e
N 22 | Z line | N 22 | Z line | | Z line | N 22 N2 N2
t -t -t
1 N1 RI 0 t N1 RI 0
f (t ) - f (0) t (1 - e ) f (t ) f (0) t (1 - e t )
N2 �
v2 dt 2 2
0
N 2 N 2
Lec- 7
365
Vm N1 d V2
v2ac (t ) R sin(wt f - q ) jw f ac
| Z line | N 2 dt jw N 2
RVm N1 p RVm N1
fac (t ) sin(wt f - q - ) facmax
w | Z line | N 2
2
2 w | Z line | N 22
Vm N1
Rt
RVm N1 N1 RVmt | Z line | N 22 wL X
facmax fdcmax 2 1 1 wt 1 line 1 line
w | Z line | N 2 N 2 | Z line |
2
Vm N1 R Rline Rline
| Z line | N 2 w
2
X
1
R
Lec-6
Lec – 5
Ip Ip
- IS Ip IE - IS
N - I I �100 N 98�45�
�100 N S E
IS �100
IS IS
Lec - 9
Vth - VT 1 1
�100 )Dw w02
(3f ) ( L w02 1 LC < f Df �3Hz
Vth w02
LC
1t di dv di 1 d 2i
v(t ) Ri �
Ceq
-�
idt L
dt dt
R
dt Ceq
i L 2 w0
dt
d 1 1 1
DVL - DVC jI (w L - ) Dw I (2 2 )Dw w02 I ( L L )Dw
dw wCeq w0 Ceq LCeq
366
| VL - VC | 2 LI Dw 2 LI 2 LDw
j 2 LI Dw (DVL - DVC ) tan b 2 2 2 � 2p f Lm 106
| VR | a Rb I a Rb a Rb
106
Lm 3183.1H
2p
source. The fault strikes at time t t 0 . This can be simulated by closing the switch at t t1
367
R jwL or Z q models the line impedance. The fault current in the line is given by
i (t ) 0 0 t t0
t -t 0
V sin(w t f - q ) -
t
t t0
i (t ) m I 0e
|Z |
Where τ is the time constant of the line τ =L/R. The fault current has two components in
it. The first component models the steady state sinusoidal ac response while the second current
is the dc offset current due to the presence of inductive component in the circuit. Recall that
current in an inductance can not change instantaneously. As t ∞, the instantaneous dc
It is more or less obvious that, dc offset is not seen in the waveform after 5 time constants.
The value of I0 can be worked out by setting the current at t t o to zero.
This implies that
Vm
I0 - sin(wt 0 - q )
Z
368
Thus
t -t 0
Vm V -( )
i (t ) sin(wt f - q ) - m sin(wt f - q )e t
Z Z
fig.2
It can be seen that severity of dc offset component in fault current is maximum when
a) f q
p
b) wt 0
2
369
p 1
For example, if angle of transmission line is 800, then with f = 800 & t 0 =
2 2p 50 200
V
sec = 5msec, the severity of dc offset current would equal I 0 Z , which is also the peak
m
We now plan to show that CT can saturate on dc offset current. Also, we plan to show
that the resulting distortions in the CT secondary current can be un-acceptably high. While
doing this analysis, we will neglect ac symmetrical component. In other words, we rest our
belief in superposition theorem atleast qualitatively and will finally evaluate effect using it
Notice that the current that we are dealing with is non-linear, a rigorous application of super
position theorem is simply out of question.
370
First consider an ideal CT excited by the dc offset current source. An ideal CT will faithfully
replicates primary current waveform on the secondary side. Hence, the secondary current
would be given by
-t
I0 t
i2 (t ) e
N
and the voltage developed across CT secondary would be given by
-t
RI N2
v 2 (t ) 0 e t where N N
N 1
For simplicity, let us assume that the initial flux in the transformer core at t=0 is zero
f ( 0 ) 0 ; Then we can compute the flux in the transformer core by using faraday’s law
df
V2 N 2 ---------(2)
dt
371
t
f (t ) - f (0) v 0
2 dt
RI 0
-t
t 1- e t
N2
-t
LI 0
(1 - e t )
N2
-t
LI 0
f (t ) f (0) (1 - e t )
N2
-t
LI 0
(1 - e t ) ------- (3)
N2
as a consequence of dc offset current,
Thus, flux in the core increases exponentially to a peak value of
f dmax
c
LI 0
N2
as t
L Vm Vm
N Z Z
f dmax
c
Note that unlike ac voltage induced flux, which is sinusoidal, this flux is unidirectional. The ac
voltage induced flux has zero average value. However, dc offset induced does not have this
nice feature. The total flux in ideal CT core is a summation of ac flux and dc flux.
d
The ac flux in the CT core can be obtained by substituting operator by jw . Hence
dt
If v2 (t ) Vm sin(wt f ) , then
Vm p
f ac sin(wt f - )
wN 2 2
The peak value of ac flux is given by
372
Vm
f acmax
wN 2
However Vm R2 I 0
max
R2 I 0max
Hence facmax
wN 2
and peak value of the total flux is given by
Vm LI 0max
facmax f dcmax
wN 2 N2
In practice, if this flux exceeds the knee-point flux in the core (see fig.), then the CT core
will saturate.
As a consequence of CT core saturation, the secondary current would not faithfully replicate
the primary current. Infact, in practice it is observed that CT secondary current is clipped. The
clipping of CT current leads to “blinding” of the relay which cannot function further. Hence,
CT saturation in presence of dc offset current is a serious problem which relay designers have
to face. Note that dc flux accumulates gradually. (Depends upon the transmission line time
constant ( t ). It is apparent that saturation should not occur immediately after the inception of
the fault. Thus, if the relay is fast enough in decision making, it is likely that a relaying
decision would be undertaken before the CT fully saturates. This is another important reason
for increasing the speed of relaying system. For bus-fault protection, where the dc saturation
due to dc offset current can be a significant contributing factor, quarter cycle operations *****
373
specifically are imposed. Similarly, a distance relay is expected to operate within ½-1 cycle
time.
CT oversizing factors
Typically, an efficient design of transformer would correspond to choosing the core cross
section such that f mac should be near the knee point of B-H curve. One obvious way of
avoiding the CT saturation on dc flux is to oversize the core so that for flux (f acmax f dcmax ) , the
(f acmax f dcmax )
corresponding B is below the knee-point. Hence, the factor is called core-
f acmax
oversizing factor.
f dcmax
Core-oversizing factor = 1
f acmax
LI o N 2
1
RI 0 wN 2
wL
1
R
X
1
R
Note that X/R in above equation is the transmission line X/R ratio. For a 220KV line X/R 10.
This would imply that transformer core should be oversized by a factor of 11. For a 400KV
line, typical value of X/R 20. This would imply an oversizing required of about 21 times the
usual design. Clearly this high amount of oversizing is not practical. Thus, the important
conclusion is that, protection engineers have to live with the saturation problem.
Cautions in CT selection:
While choosing a CT for a particular application, it is necessary to observe following
precautions.
77. The CT rating and continuous load current should match. For example, if max load
current is 90A, a 100:5 Ct may be acceptable but 50:5 is not acceptable.
374
78. The maximum fault current should be less than 20 times the CT rated current. for
example 100:5 CT can be used, so long as burden on the CT & maximum primary fault
current is below 2000A.
79. The voltage rating of CT should be compatible. For example, 100:5 C100 would give
linear response, upto 20 times rated current provided CT burden is kept
below(100/20*5=1 Ω). With 2 Ω burden, this CT can be used only if maximum current
is limited to 1000A.
80. Parallel of CT’s e.g. in differential protection, or with SLG fault can create significant
errors in CT performance. One should in general ascertain that magnetizing current is
kept much below the pick up value.
Following example, illustrates this point
Exercise problems:
If the current ratio is adequate for a protection, but CT burden is high; then the
performance of CT may deteriorate due to large magnetizing current and/or saturation problem.
The CT performance can be improved by connecting the CT’s in series.
39) Show the dotted terminals for correct secondary series connection
40) What is the VA of CT in fig (a) & (b) respectively?
58) Electromechanical relays tend to saturate at high currents. This reduces the relay burden
on CT, and so that the CT performance at moderately high currents may be considered
better than at relay’s rated burden at 5A.
59) Use of instantaneous over current relays has the potential to overcome this problem of
saturation of CT’s
375
60) Differential protection can operate on external faults due to the un equal saturation of
CT’s
Lecture-6
Examples
25. If a 300:5 class C CT is connected to a meter with resistance R I 1 and
secondary current in the CT is 4.5A find out the primary current voltage
developed across the meter and % rate error. Lead wire resistance R L 0.02
secondary resistance RS of a 300/5 CT 0.15
Diagram
R I 1 , R L 0.02 RS 0.15 I S 4.5 A
Total secondary resistance RT R I R L RS
1.17
Secondary voltage I S RT
4.5 1.17
5.265V
From Fig 5.7,
Exciting current IE for 5.265V
= 0.03A
Turns ratio N = 300/5 = 60
I p N (I S I E )
= 60(4.5 + 0.03)
= 271.8A
Voltage across meter I S R I
4.5 1 = 4.5V
IE 0.03
Ratio error 100 100
IS 4.5
= 0.67%
Rb
376
Lecture – 8
Examples
39. Design a CCVT for a 132kV transmission line using the following data.
Resistive Burden (3f )-150VA
Df 3Hz , phase angle error b = 40 min
Consider 4 choices of V2 as 33kV, 11kV, 6.6kV and 3.3kV
Diagram 1 Diagram 2
Transmission line voltage V = 132kV. Suppose V 2 (P_N) be the voltage to be
produced by the capacitive potential divider with capacitance values C1 and C2
and L the value of tuning inductor. The standardized VT secondary voltage is 110
volts (L-L).
Here specification for phase angle error b is 40 minutes variation in frequency
can be upto Df 3Hz . Phase angle error for change in w by Dw in the above
equation circuit, is given by
1
( L 2 )Dw
w C
1
At tuning frequency w 2
LC
Substituting w 1 LC
2
747.2 H
1 1
C1 C 2
w 2 L (3/ 4) 2 747.2
1.3610 -2 F
3) V2 6.6kV
3 �(6.6 �103 )2
Rb
'
150
87.1210 4
b �Rb' 0.01164 �87.12 �104
L
2 �Dw 2 �2p �3
269H ,
C1 C 2 3.7710 -2 F
4) V2 3.3kV
3 �(3.3 �103 ) 2
Rb'
150
21.7810 4
b �Rb' 0.01164 �21.78 �104
L
2 �Dw 2 �2p �3
67.25 H
C1 C2 0.151 F
The values of L, C1 C 2 for different values of V2 are tabulated below.
V2 L C1 C 2
33kV 6722.2H 0.00151 F
11kV 747.2H 0.0136 F
6.6kV 269H 0.0377 F
3.3kV 67.25H 0.151 F
From the above table it is clear that smaller the value of V 2, the smaller is the
value of L and higher the value of C 1 and C2 for tuning condition. If we select too low
value of V2 and L then capacitance values will be beyond available limits, and if we
select higher value of V2 and L, then CCVT and inductor will become bulky. So a
compromise is necessary and let us select V2 = 6.6kV
For V2 = 6.6kV
L = 269H
C1 C 2 0.0377 F
V C1 C 2
Now,
V2 C1
13210 3 0.037710 -6
36.610 3
C1
0.0377 36.610 3 10 -6 F
C1
13210 3
0.0033F
378
C 2 0.0344F
In this design, we explained the basic concept for CCVT design and we assumed
the transformer to be ideal. But in actual design practice the value of magnetizing
impedance of transformer, resistance of reactor etc have to be taken into account,
as ratio error a and phase angle error b will also get affected by these values.
40. Diagram
The equivalent circuit of a CCVT is shown in fig 8.3. The values of C 1 and C2 are
0.0018 F and 0.018 F respectively. Tuning inductor has an inductance of
497H and resistance of 4620 .
Xm of the 6.6kV VT is 1M , core loss = 20 watts per phase, VA burden =
150VA per phase. Value of Cm for compensating the current drawn by m is equal
to 3.18310 -9 F .
(fff) Verify the appropriateness of choice of L and Cm.
Ans: If C1 0.0018F and C 2 0.0186F then the value L of tuning inductor
is given by
1
L 2
w (C1 C 2 )
where w 2p f and f = tuning frequency
1
L
(2p �50) (0.0018 0.0186) �10-6
2
1
Xm
w Cm
1 1
Cm
w X m (2p �50) �� 1 106
3.183 �10-9 F
The value is also same as the selected value of Cm Hence the selection of both L
and Cm is appropriate.
(hhh) If the frequency drops from 50Hz to 47Hz, what would be the values of
ratio error and phase angle error?
Ans: Core loss = 20w
V22
20W
Rm
379
V22 (6600) 2
Rm
20 20
2.18 �10
6
6600 0
A
260874.14 -2.44�
VT I th �Z
6600 0
�256147.5 1.82�
260874.14 -2.44�
6480.42 4.26�
(6600 - 6480.42)
Hence % ratio error �100
6600
=1.81%
Phase angle error = 4.26�
V2 6.6kV
r a w2 a 2
M
d 2i R di 1 1 R
t �t0 2
i0 wn 2p �50 2 Iwn
dt L dt LCeq LC L
d 2i
2
2a wn wn2i 0 a < 1
dt
Lec – 8
1
2p �50 2zw R d i 2zw w 2i 0 z wn z < 1
2
wn
LCeq n
L dt 2 n n
-t V
t I 0 - m sin(wt0 f - q ) f q
e | Z line |
381
Example 1:
d
382
Answer:
Based on the criteria that the CT can deliver 20 times rated secondary current
without exceeding a 10% ratio error, the maximum fault current will be 24000A.
However, with a 2.0Ω burden, this will result in a voltage below the knee point of the CT
and, as a practical matter, it will be within 10% accuracy at higher currents. This can only
be accurately determined from excitation or ratio correction curves and not from the
accuracy classification. For example, a CT with characteristics shown in above figure
will produce between 180-240A without exceeding the 10% ratio error, depending on the
power factor of the 2.0Ω burden.
Example 2:
A 1200/5, C400 CT is connected on the 1000/5 tap. What is the maximum secondary
burden that can be used and still maintain rated accuracy at 20 times rated symmetrical
secondary current?
Answer:
Since the secondary voltage capability is directly proportional to the connected tap, the
CT will support a voltage of 1000/1200 400V or 333V. Twenty times the rated
secondary current is 100A. Therefore, the maximum burden is 333V/100A or 3.33 Ω
Example 3:
Assume that secondary burden in a relay circuit is 5Ω. The relay setting is 2A and the CT
ratio is 300/5. Using above figure, calculate the primary current required to operate the
relay?
Answer:
383
N (I E I S )
= 300/5(0.04+2) A=122A
Example 4:
A relay is expected to operate for a 7000A primary current. The CT ratio is 600/5.
Secondary burden is 3.5 Ω. What is the error for the CT shown in above figure?
Answer:
The total secondary fault current is (7000/600) 5=58A. Assume that exciting current is
negligible.
VS I S ( R B RS )
= 58(3.5+0.31)
= 221V
The exciting current will not be negligible, however, and the calculation will not be
iterated.
Lec – 7
N1 RI 0 Vm N1 R Vm Vm N1 N1 RI 0 -tt N1 I 0 -tt
fdcmax t t N1 Rt v2 (t )
dc
e i2 e
N 22 | Z line | N 22 | Z line | | Z line | N 22 N2 N2
t -t -t
1 N1 RI 0 t N1 RI 0
f (t ) - f (0) t (1 - e ) f (t ) f (0) t (1 - e t )
N2 �
v2 dt 2 2
0
N 2 N 2
Lec- 7
384
Vm N1 d V2
v2ac (t ) R sin(wt f - q ) jw f ac
| Z line | N 2 dt jw N 2
RVm N1 p RVm N1
fac (t ) sin(wt f - q - ) facmax
w | Z line | N 2
2
2 w | Z line | N 22
Vm N1
Rt
RVm N1 N1 RVmt | Z line | N 22 wL X
facmax fdcmax 2 1 1 wt 1 line 1 line
w | Z line | N 2 N 2 | Z line |
2
Vm N1 R Rline Rline
| Z line | N 2 w
2
X
1
R
Lec-6
Lec – 5
Ip Ip
- IS Ip IE - IS
N - I I �100 N 98�45�
�100 N S E
IS �100
IS IS
Lec - 9
Vth - VT 1 1
�100 )Dw w02
(3f ) ( L w02 1 LC < f Df �3Hz
Vth w02
LC
1t di dv di 1 d 2i
v(t ) Ri �
Ceq
-�
idt L
dt dt
R
dt Ceq
i L 2 w0
dt
d 1 1 1
DVL - DVC jI (w L - ) Dw I (2 2 )Dw w02 I ( L L )Dw
dw wCeq w0 Ceq LCeq
385
| VL - VC | 2 LI Dw 2 LI 2 LDw
j 2 LI Dw (DVL - DVC ) tan b 2 2 2 � 2p f Lm 106
| VR | a Rb I a Rb a Rb
106
Lm 3183.1H
2p
source. The fault strikes at time t t 0 . This can be simulated by closing the switch at t t1
386
R jwL or Z q models the line impedance. The fault current in the line is given by
i (t ) 0 0 t t0
t -t 0
V sin(w t f - q ) -
t
t t0
i (t ) m I 0e
|Z |
Where τ is the time constant of the line τ =L/R. The fault current has two components in
it. The first component models the steady state sinusoidal ac response while the second current
is the dc offset current due to the presence of inductive component in the circuit. Recall that
current in an inductance can not change instantaneously. As t ∞, the instantaneous dc
It is more or less obvious that, dc offset is not seen in the waveform after 5 time constants.
The value of I0 can be worked out by setting the current at t t o to zero.
This implies that
Vm
I0 - sin(wt 0 - q )
Z
387
Thus
t -t 0
Vm V -( )
i (t ) sin(wt f - q ) - m sin(wt f - q )e t
Z Z
fig.2
It can be seen that severity of dc offset component in fault current is maximum when
a) f q
p
b) wt 0
2
388
p 1
For example, if angle of transmission line is 800, then with f = 800 & t 0 =
2 2p 50 200
V
sec = 5msec, the severity of dc offset current would equal I 0 Z , which is also the peak
m
We now plan to show that CT can saturate on dc offset current. Also, we plan to show
that the resulting distortions in the CT secondary current can be un-acceptably high. While
doing this analysis, we will neglect ac symmetrical component. In other words, we rest our
belief in superposition theorem atleast qualitatively and will finally evaluate effect using it
Notice that the current that we are dealing with is non-linear, a rigorous application of super
position theorem is simply out of question.
389
First consider an ideal CT excited by the dc offset current source. An ideal CT will faithfully
replicates primary current waveform on the secondary side. Hence, the secondary current
would be given by
-t
I0 t
i2 (t ) e
N
and the voltage developed across CT secondary would be given by
-t
RI N2
v 2 (t ) 0 e t where N N
N 1
For simplicity, let us assume that the initial flux in the transformer core at t=0 is zero
f ( 0 ) 0 ; Then we can compute the flux in the transformer core by using faraday’s law
df
V2 N 2 ---------(2)
dt
390
t
f (t ) - f (0) v 0
2 dt
RI 0
-t
t 1- e t
N2
-t
LI 0
(1 - e t )
N2
-t
LI 0
f (t ) f (0) (1 - e t )
N2
-t
LI 0
(1 - e t ) ------- (3)
N2
as a consequence of dc offset current,
Thus, flux in the core increases exponentially to a peak value of
f dmax
c
LI 0
N2
as t
L Vm Vm
N Z Z
f dmax
c
Note that unlike ac voltage induced flux, which is sinusoidal, this flux is unidirectional. The ac
voltage induced flux has zero average value. However, dc offset induced does not have this
nice feature. The total flux in ideal CT core is a summation of ac flux and dc flux.
d
The ac flux in the CT core can be obtained by substituting operator by jw . Hence
dt
If v2 (t ) Vm sin(wt f ) , then
Vm p
f ac sin(wt f - )
wN 2 2
The peak value of ac flux is given by
391
Vm
f acmax
wN 2
However Vm R2 I 0
max
R2 I 0max
Hence facmax
wN 2
and peak value of the total flux is given by
Vm LI 0max
facmax f dcmax
wN 2 N2
In practice, if this flux exceeds the knee-point flux in the core (see fig.), then the CT core
will saturate.
As a consequence of CT core saturation, the secondary current would not faithfully replicate
the primary current. Infact, in practice it is observed that CT secondary current is clipped. The
clipping of CT current leads to “blinding” of the relay which cannot function further. Hence,
CT saturation in presence of dc offset current is a serious problem which relay designers have
to face. Note that dc flux accumulates gradually. (Depends upon the transmission line time
constant ( t ). It is apparent that saturation should not occur immediately after the inception of
the fault. Thus, if the relay is fast enough in decision making, it is likely that a relaying
decision would be undertaken before the CT fully saturates. This is another important reason
for increasing the speed of relaying system. For bus-fault protection, where the dc saturation
due to dc offset current can be a significant contributing factor, quarter cycle operations *****
392
specifically are imposed. Similarly, a distance relay is expected to operate within ½-1 cycle
time.
CT oversizing factors
Typically, an efficient design of transformer would correspond to choosing the core cross
section such that f mac should be near the knee point of B-H curve. One obvious way of
avoiding the CT saturation on dc flux is to oversize the core so that for flux (f acmax f dcmax ) , the
(f acmax f dcmax )
corresponding B is below the knee-point. Hence, the factor is called core-
f acmax
oversizing factor.
f dcmax
Core-oversizing factor = 1
f acmax
LI o N 2
1
RI 0 wN 2
wL
1
R
X
1
R
Note that X/R in above equation is the transmission line X/R ratio. For a 220KV line X/R 10.
This would imply that transformer core should be oversized by a factor of 11. For a 400KV
line, typical value of X/R 20. This would imply an oversizing required of about 21 times the
usual design. Clearly this high amount of oversizing is not practical. Thus, the important
conclusion is that, protection engineers have to live with the saturation problem.
Cautions in CT selection:
While choosing a CT for a particular application, it is necessary to observe following
precautions.
81. The CT rating and continuous load current should match. For example, if max load
current is 90A, a 100:5 Ct may be acceptable but 50:5 is not acceptable.
393
82. The maximum fault current should be less than 20 times the CT rated current. for
example 100:5 CT can be used, so long as burden on the CT & maximum primary fault
current is below 2000A.
83. The voltage rating of CT should be compatible. For example, 100:5 C100 would give
linear response, upto 20 times rated current provided CT burden is kept
below(100/20*5=1 Ω). With 2 Ω burden, this CT can be used only if maximum current
is limited to 1000A.
84. Parallel of CT’s e.g. in differential protection, or with SLG fault can create significant
errors in CT performance. One should in general ascertain that magnetizing current is
kept much below the pick up value.
Following example, illustrates this point
Exercise problems:
If the current ratio is adequate for a protection, but CT burden is high; then the
performance of CT may deteriorate due to large magnetizing current and/or saturation problem.
The CT performance can be improved by connecting the CT’s in series.
41) Show the dotted terminals for correct secondary series connection
42) What is the VA of CT in fig (a) & (b) respectively?
61) Electromechanical relays tend to saturate at high currents. This reduces the relay burden
on CT, and so that the CT performance at moderately high currents may be considered
better than at relay’s rated burden at 5A.
62) Use of instantaneous over current relays has the potential to overcome this problem of
saturation of CT’s
394
63) Differential protection can operate on external faults due to the un equal saturation of
CT’s
Lecture-6
Examples
26. If a 300:5 class C CT is connected to a meter with resistance R I 1 and
secondary current in the CT is 4.5A find out the primary current voltage
developed across the meter and % rate error. Lead wire resistance R L 0.02
secondary resistance RS of a 300/5 CT 0.15
Diagram
R I 1 , R L 0.02 RS 0.15 I S 4.5 A
Total secondary resistance RT R I R L RS
1.17
Secondary voltage I S RT
4.5 1.17
5.265V
From Fig 5.7,
Exciting current IE for 5.265V
= 0.03A
Turns ratio N = 300/5 = 60
I p N (I S I E )
= 60(4.5 + 0.03)
= 271.8A
Voltage across meter I S R I
4.5 1 = 4.5V
IE 0.03
Ratio error 100 100
IS 4.5
= 0.67%
Rb
395
Lecture – 8
Examples
41. Design a CCVT for a 132kV transmission line using the following data.
Resistive Burden (3f )-150VA
Df 3Hz , phase angle error b = 40 min
Consider 4 choices of V2 as 33kV, 11kV, 6.6kV and 3.3kV
Diagram 1 Diagram 2
Transmission line voltage V = 132kV. Suppose V 2 (P_N) be the voltage to be
produced by the capacitive potential divider with capacitance values C1 and C2
and L the value of tuning inductor. The standardized VT secondary voltage is 110
volts (L-L).
Here specification for phase angle error b is 40 minutes variation in frequency
can be upto Df 3Hz . Phase angle error for change in w by Dw in the above
equation circuit, is given by
1
( L 2 )Dw
w C
1
At tuning frequency w 2
LC
Substituting w 1 LC
2
747.2 H
1 1
C1 C 2
w 2 L (3/ 4) 2 747.2
1.3610 -2 F
3) V2 6.6kV
3 �(6.6 �103 )2
Rb
'
150
87.1210 4
b �Rb' 0.01164 �87.12 �104
L
2 �Dw 2 �2p �3
269H ,
C1 C 2 3.7710 -2 F
4) V2 3.3kV
3 �(3.3 �103 ) 2
Rb'
150
21.7810 4
b �Rb' 0.01164 �21.78 �104
L
2 �Dw 2 �2p �3
67.25 H
C1 C2 0.151 F
The values of L, C1 C 2 for different values of V2 are tabulated below.
V2 L C1 C 2
33kV 6722.2H 0.00151 F
11kV 747.2H 0.0136 F
6.6kV 269H 0.0377 F
3.3kV 67.25H 0.151 F
From the above table it is clear that smaller the value of V 2, the smaller is the
value of L and higher the value of C 1 and C2 for tuning condition. If we select too low
value of V2 and L then capacitance values will be beyond available limits, and if we
select higher value of V2 and L, then CCVT and inductor will become bulky. So a
compromise is necessary and let us select V2 = 6.6kV
For V2 = 6.6kV
L = 269H
C1 C 2 0.0377 F
V C1 C 2
Now,
V2 C1
13210 3 0.037710 -6
36.610 3
C1
0.0377 36.610 3 10 -6 F
C1
13210 3
0.0033F
397
C 2 0.0344F
In this design, we explained the basic concept for CCVT design and we assumed
the transformer to be ideal. But in actual design practice the value of magnetizing
impedance of transformer, resistance of reactor etc have to be taken into account,
as ratio error a and phase angle error b will also get affected by these values.
42. Diagram
The equivalent circuit of a CCVT is shown in fig 8.3. The values of C 1 and C2 are
0.0018 F and 0.018 F respectively. Tuning inductor has an inductance of
497H and resistance of 4620 .
Xm of the 6.6kV VT is 1M , core loss = 20 watts per phase, VA burden =
150VA per phase. Value of Cm for compensating the current drawn by m is equal
to 3.18310 -9 F .
(iii) Verify the appropriateness of choice of L and Cm.
Ans: If C1 0.0018F and C 2 0.0186F then the value L of tuning inductor
is given by
1
L 2
w (C1 C 2 )
where w 2p f and f = tuning frequency
1
L
(2p �50) (0.0018 0.0186) �10-6
2
1
Xm
w Cm
1 1
Cm
w X m (2p �50) �� 1 106
3.183 �10-9 F
The value is also same as the selected value of Cm Hence the selection of both L
and Cm is appropriate.
(kkk) If the frequency drops from 50Hz to 47Hz, what would be the values of
ratio error and phase angle error?
Ans: Core loss = 20w
V22
20W
Rm
398
V22 (6600) 2
Rm
20 20
2.18 �10
6
6600 0
A
260874.14 -2.44�
VT I th �Z
6600 0
�256147.5 1.82�
260874.14 -2.44�
6480.42 4.26�
(6600 - 6480.42)
Hence % ratio error �100
6600
=1.81%
Phase angle error = 4.26�
V2 6.6kV
r a w2 a 2
M
d 2i R di 1 1 R
t �t0 2
i0 wn 2p �50 2 Iwn
dt L dt LCeq LC L
d 2i
2
2a wn wn2i 0 a < 1
dt
Lec – 8
1
2p �50 2zw R d i 2zw w 2i 0 z wn z < 1
2
wn
LCeq n
L dt 2 n n
-t V
t I 0 - m sin(wt0 f - q ) f q
e | Z line |
400
Example 1:
d
401
Answer:
Based on the criteria that the CT can deliver 20 times rated secondary current
without exceeding a 10% ratio error, the maximum fault current will be 24000A.
However, with a 2.0Ω burden, this will result in a voltage below the knee point of the CT
and, as a practical matter, it will be within 10% accuracy at higher currents. This can only
be accurately determined from excitation or ratio correction curves and not from the
accuracy classification. For example, a CT with characteristics shown in above figure
will produce between 180-240A without exceeding the 10% ratio error, depending on the
power factor of the 2.0Ω burden.
Example 2:
A 1200/5, C400 CT is connected on the 1000/5 tap. What is the maximum secondary
burden that can be used and still maintain rated accuracy at 20 times rated symmetrical
secondary current?
Answer:
Since the secondary voltage capability is directly proportional to the connected tap, the
CT will support a voltage of 1000/1200 400V or 333V. Twenty times the rated
secondary current is 100A. Therefore, the maximum burden is 333V/100A or 3.33 Ω
Example 3:
Assume that secondary burden in a relay circuit is 5Ω. The relay setting is 2A and the CT
ratio is 300/5. Using above figure, calculate the primary current required to operate the
relay?
Answer:
402
N (I E I S )
= 300/5(0.04+2) A=122A
Example 4:
A relay is expected to operate for a 7000A primary current. The CT ratio is 600/5.
Secondary burden is 3.5 Ω. What is the error for the CT shown in above figure?
Answer:
The total secondary fault current is (7000/600) 5=58A. Assume that exciting current is
negligible.
VS I S ( R B RS )
= 58(3.5+0.31)
= 221V
The exciting current will not be negligible, however, and the calculation will not be
iterated.
Lec – 7
N1 RI 0 Vm N1 R Vm Vm N1 N1 RI 0 -tt N1 I 0 -tt
fdcmax t t N1 Rt v2 (t )
dc
e i2 e
N 22 | Z line | N 22 | Z line | | Z line | N 22 N2 N2
t -t -t
1 N1 RI 0 t N1 RI 0
f (t ) - f (0) t (1 - e ) f (t ) f (0) t (1 - e t )
N2 �
v2 dt 2 2
0
N 2 N 2
Lec- 7
403
Vm N1 d V2
v2ac (t ) R sin(wt f - q ) jw f ac
| Z line | N 2 dt jw N 2
RVm N1 p RVm N1
fac (t ) sin(wt f - q - ) facmax
w | Z line | N 2
2
2 w | Z line | N 22
Vm N1
Rt
RVm N1 N1 RVmt | Z line | N 22 wL X
facmax fdcmax 2 1 1 wt 1 line 1 line
w | Z line | N 2 N 2 | Z line |
2
Vm N1 R Rline Rline
| Z line | N 2 w
2
X
1
R
Lec-6
Lec – 5
Ip Ip
- IS Ip IE - IS
N - I I �100 N 98�45�
�100 N S E
IS �100
IS IS
Lec - 9
Vth - VT 1 1
�100 )Dw w02
(3f ) ( L w02 1 LC < f Df �3Hz
Vth w02
LC
1t di dv di 1 d 2i
v(t ) Ri �
Ceq
-�
idt L
dt dt
R
dt Ceq
i L 2 w0
dt
d 1 1 1
DVL - DVC jI (w L - ) Dw I (2 2 )Dw w02 I ( L L )Dw
dw wCeq w0 Ceq LCeq
404
| VL - VC | 2 LI Dw 2 LI 2 LDw
j 2 LI Dw (DVL - DVC ) tan b 2 2 2 � 2p f Lm 106
| VR | a Rb I a Rb a Rb
106
Lm 3183.1H
2p
source. The fault strikes at time t t 0 . This can be simulated by closing the switch at t t1
405
R jwL or Z q models the line impedance. The fault current in the line is given by
i (t ) 0 0 t t0
t -t 0
V sin(w t f - q ) -
t
t t0
i (t ) m I 0e
|Z |
Where τ is the time constant of the line τ =L/R. The fault current has two components in
it. The first component models the steady state sinusoidal ac response while the second current
is the dc offset current due to the presence of inductive component in the circuit. Recall that
current in an inductance can not change instantaneously. As t ∞, the instantaneous dc
It is more or less obvious that, dc offset is not seen in the waveform after 5 time constants.
The value of I0 can be worked out by setting the current at t t o to zero.
This implies that
Vm
I0 - sin(wt 0 - q )
Z
406
Thus
t -t 0
Vm V -( )
i (t ) sin(wt f - q ) - m sin(wt f - q )e t
Z Z
fig.2
It can be seen that severity of dc offset component in fault current is maximum when
a) f q
p
b) wt 0
2
407
p 1
For example, if angle of transmission line is 800, then with f = 800 & t 0 =
2 2p 50 200
V
sec = 5msec, the severity of dc offset current would equal I 0 Z , which is also the peak
m
We now plan to show that CT can saturate on dc offset current. Also, we plan to show
that the resulting distortions in the CT secondary current can be un-acceptably high. While
doing this analysis, we will neglect ac symmetrical component. In other words, we rest our
belief in superposition theorem atleast qualitatively and will finally evaluate effect using it
Notice that the current that we are dealing with is non-linear, a rigorous application of super
position theorem is simply out of question.
408
First consider an ideal CT excited by the dc offset current source. An ideal CT will faithfully
replicates primary current waveform on the secondary side. Hence, the secondary current
would be given by
-t
I0 t
i2 (t ) e
N
and the voltage developed across CT secondary would be given by
-t
RI N2
v 2 (t ) 0 e t where N N
N 1
For simplicity, let us assume that the initial flux in the transformer core at t=0 is zero
f ( 0 ) 0 ; Then we can compute the flux in the transformer core by using faraday’s law
df
V2 N 2 ---------(2)
dt
409
t
f (t ) - f (0) v 0
2 dt
RI 0
-t
t 1- e t
N2
-t
LI 0
(1 - e t )
N2
-t
LI 0
f (t ) f (0) (1 - e t )
N2
-t
LI 0
(1 - e t ) ------- (3)
N2
as a consequence of dc offset current,
Thus, flux in the core increases exponentially to a peak value of
f dmax
c
LI 0
N2
as t
L Vm Vm
N Z Z
f dmax
c
Note that unlike ac voltage induced flux, which is sinusoidal, this flux is unidirectional. The ac
voltage induced flux has zero average value. However, dc offset induced does not have this
nice feature. The total flux in ideal CT core is a summation of ac flux and dc flux.
d
The ac flux in the CT core can be obtained by substituting operator by jw . Hence
dt
If v2 (t ) Vm sin(wt f ) , then
Vm p
f ac sin(wt f - )
wN 2 2
The peak value of ac flux is given by
410
Vm
f acmax
wN 2
However Vm R2 I 0
max
R2 I 0max
Hence facmax
wN 2
and peak value of the total flux is given by
Vm LI 0max
facmax f dcmax
wN 2 N2
In practice, if this flux exceeds the knee-point flux in the core (see fig.), then the CT core
will saturate.
As a consequence of CT core saturation, the secondary current would not faithfully replicate
the primary current. Infact, in practice it is observed that CT secondary current is clipped. The
clipping of CT current leads to “blinding” of the relay which cannot function further. Hence,
CT saturation in presence of dc offset current is a serious problem which relay designers have
to face. Note that dc flux accumulates gradually. (Depends upon the transmission line time
constant ( t ). It is apparent that saturation should not occur immediately after the inception of
the fault. Thus, if the relay is fast enough in decision making, it is likely that a relaying
decision would be undertaken before the CT fully saturates. This is another important reason
for increasing the speed of relaying system. For bus-fault protection, where the dc saturation
due to dc offset current can be a significant contributing factor, quarter cycle operations *****
411
specifically are imposed. Similarly, a distance relay is expected to operate within ½-1 cycle
time.
CT oversizing factors
Typically, an efficient design of transformer would correspond to choosing the core cross
section such that f mac should be near the knee point of B-H curve. One obvious way of
avoiding the CT saturation on dc flux is to oversize the core so that for flux (f acmax f dcmax ) , the
(f acmax f dcmax )
corresponding B is below the knee-point. Hence, the factor is called core-
f acmax
oversizing factor.
f dcmax
Core-oversizing factor = 1
f acmax
LI o N 2
1
RI 0 wN 2
wL
1
R
X
1
R
Note that X/R in above equation is the transmission line X/R ratio. For a 220KV line X/R 10.
This would imply that transformer core should be oversized by a factor of 11. For a 400KV
line, typical value of X/R 20. This would imply an oversizing required of about 21 times the
usual design. Clearly this high amount of oversizing is not practical. Thus, the important
conclusion is that, protection engineers have to live with the saturation problem.
Cautions in CT selection:
While choosing a CT for a particular application, it is necessary to observe following
precautions.
85. The CT rating and continuous load current should match. For example, if max load
current is 90A, a 100:5 Ct may be acceptable but 50:5 is not acceptable.
412
86. The maximum fault current should be less than 20 times the CT rated current. for
example 100:5 CT can be used, so long as burden on the CT & maximum primary fault
current is below 2000A.
87. The voltage rating of CT should be compatible. For example, 100:5 C100 would give
linear response, upto 20 times rated current provided CT burden is kept
below(100/20*5=1 Ω). With 2 Ω burden, this CT can be used only if maximum current
is limited to 1000A.
88. Parallel of CT’s e.g. in differential protection, or with SLG fault can create significant
errors in CT performance. One should in general ascertain that magnetizing current is
kept much below the pick up value.
Following example, illustrates this point
Exercise problems:
If the current ratio is adequate for a protection, but CT burden is high; then the
performance of CT may deteriorate due to large magnetizing current and/or saturation problem.
The CT performance can be improved by connecting the CT’s in series.
43) Show the dotted terminals for correct secondary series connection
44) What is the VA of CT in fig (a) & (b) respectively?
64) Electromechanical relays tend to saturate at high currents. This reduces the relay burden
on CT, and so that the CT performance at moderately high currents may be considered
better than at relay’s rated burden at 5A.
65) Use of instantaneous over current relays has the potential to overcome this problem of
saturation of CT’s
413
66) Differential protection can operate on external faults due to the un equal saturation of
CT’s
Lecture-6
Examples
27. If a 300:5 class C CT is connected to a meter with resistance R I 1 and
secondary current in the CT is 4.5A find out the primary current voltage
developed across the meter and % rate error. Lead wire resistance R L 0.02
secondary resistance RS of a 300/5 CT 0.15
Diagram
R I 1 , R L 0.02 RS 0.15 I S 4.5 A
Total secondary resistance RT R I R L RS
1.17
Secondary voltage I S RT
4.5 1.17
5.265V
From Fig 5.7,
Exciting current IE for 5.265V
= 0.03A
Turns ratio N = 300/5 = 60
I p N (I S I E )
= 60(4.5 + 0.03)
= 271.8A
Voltage across meter I S R I
4.5 1 = 4.5V
IE 0.03
Ratio error 100 100
IS 4.5
= 0.67%
Rb
414
Lecture – 8
Examples
43. Design a CCVT for a 132kV transmission line using the following data.
Resistive Burden (3f )-150VA
Df 3Hz , phase angle error b = 40 min
Consider 4 choices of V2 as 33kV, 11kV, 6.6kV and 3.3kV
Diagram 1 Diagram 2
Transmission line voltage V = 132kV. Suppose V 2 (P_N) be the voltage to be
produced by the capacitive potential divider with capacitance values C1 and C2
and L the value of tuning inductor. The standardized VT secondary voltage is 110
volts (L-L).
Here specification for phase angle error b is 40 minutes variation in frequency
can be upto Df 3Hz . Phase angle error for change in w by Dw in the above
equation circuit, is given by
1
( L 2 )Dw
w C
1
At tuning frequency w 2
LC
Substituting w 1 LC
2
747.2 H
1 1
C1 C 2
w 2 L (3/ 4) 2 747.2
1.3610 -2 F
3) V2 6.6kV
3 �(6.6 �103 )2
Rb
'
150
87.1210 4
b �Rb' 0.01164 �87.12 �104
L
2 �Dw 2 �2p �3
269H ,
C1 C 2 3.7710 -2 F
4) V2 3.3kV
3 �(3.3 �103 ) 2
Rb'
150
21.7810 4
b �Rb' 0.01164 �21.78 �104
L
2 �Dw 2 �2p �3
67.25 H
C1 C2 0.151 F
The values of L, C1 C 2 for different values of V2 are tabulated below.
V2 L C1 C 2
33kV 6722.2H 0.00151 F
11kV 747.2H 0.0136 F
6.6kV 269H 0.0377 F
3.3kV 67.25H 0.151 F
From the above table it is clear that smaller the value of V 2, the smaller is the
value of L and higher the value of C 1 and C2 for tuning condition. If we select too low
value of V2 and L then capacitance values will be beyond available limits, and if we
select higher value of V2 and L, then CCVT and inductor will become bulky. So a
compromise is necessary and let us select V2 = 6.6kV
For V2 = 6.6kV
L = 269H
C1 C 2 0.0377 F
V C1 C 2
Now,
V2 C1
13210 3 0.037710 -6
36.610 3
C1
0.0377 36.610 3 10 -6 F
C1
13210 3
0.0033F
416
C 2 0.0344F
In this design, we explained the basic concept for CCVT design and we assumed
the transformer to be ideal. But in actual design practice the value of magnetizing
impedance of transformer, resistance of reactor etc have to be taken into account,
as ratio error a and phase angle error b will also get affected by these values.
44. Diagram
The equivalent circuit of a CCVT is shown in fig 8.3. The values of C 1 and C2 are
0.0018 F and 0.018 F respectively. Tuning inductor has an inductance of
497H and resistance of 4620 .
Xm of the 6.6kV VT is 1M , core loss = 20 watts per phase, VA burden =
150VA per phase. Value of Cm for compensating the current drawn by m is equal
to 3.18310 -9 F .
(lll) Verify the appropriateness of choice of L and Cm.
Ans: If C1 0.0018F and C 2 0.0186F then the value L of tuning inductor
is given by
1
L 2
w (C1 C 2 )
where w 2p f and f = tuning frequency
1
L
(2p �50) (0.0018 0.0186) �10-6
2
1
Xm
w Cm
1 1
Cm
w X m (2p �50) �� 1 106
3.183 �10-9 F
The value is also same as the selected value of Cm Hence the selection of both L
and Cm is appropriate.
(nnn) If the frequency drops from 50Hz to 47Hz, what would be the values of
ratio error and phase angle error?
Ans: Core loss = 20w
V22
20W
Rm
417
V22 (6600) 2
Rm
20 20
2.18 �10
6
6600 0
A
260874.14 -2.44�
VT I th �Z
6600 0
�256147.5 1.82�
260874.14 -2.44�
6480.42 4.26�
(6600 - 6480.42)
Hence % ratio error �100
6600
=1.81%
Phase angle error = 4.26�
V2 6.6kV
r a w2 a 2
M
d 2i R di 1 1 R
t �t0 2
i0 wn 2p �50 2 Iwn
dt L dt LCeq LC L
d 2i
2
2a wn wn2i 0 a < 1
dt
Lec – 8
1
2p �50 2zw R d i 2zw w 2i 0 z wn z < 1
2
wn
LCeq n
L dt 2 n n
-t V
t I 0 - m sin(wt0 f - q ) f q
e | Z line |
419
Example 1:
d
420
Answer:
Based on the criteria that the CT can deliver 20 times rated secondary current
without exceeding a 10% ratio error, the maximum fault current will be 24000A.
However, with a 2.0Ω burden, this will result in a voltage below the knee point of the CT
and, as a practical matter, it will be within 10% accuracy at higher currents. This can only
be accurately determined from excitation or ratio correction curves and not from the
accuracy classification. For example, a CT with characteristics shown in above figure
will produce between 180-240A without exceeding the 10% ratio error, depending on the
power factor of the 2.0Ω burden.
Example 2:
A 1200/5, C400 CT is connected on the 1000/5 tap. What is the maximum secondary
burden that can be used and still maintain rated accuracy at 20 times rated symmetrical
secondary current?
Answer:
Since the secondary voltage capability is directly proportional to the connected tap, the
CT will support a voltage of 1000/1200 400V or 333V. Twenty times the rated
secondary current is 100A. Therefore, the maximum burden is 333V/100A or 3.33 Ω
Example 3:
Assume that secondary burden in a relay circuit is 5Ω. The relay setting is 2A and the CT
ratio is 300/5. Using above figure, calculate the primary current required to operate the
relay?
Answer:
421
N (I E I S )
= 300/5(0.04+2) A=122A
Example 4:
A relay is expected to operate for a 7000A primary current. The CT ratio is 600/5.
Secondary burden is 3.5 Ω. What is the error for the CT shown in above figure?
Answer:
The total secondary fault current is (7000/600) 5=58A. Assume that exciting current is
negligible.
VS I S ( R B RS )
= 58(3.5+0.31)
= 221V
The exciting current will not be negligible, however, and the calculation will not be
iterated.
Lec – 7
N1 RI 0 Vm N1 R Vm Vm N1 N1 RI 0 -tt N1 I 0 -tt
fdcmax t t N1 Rt v2 (t )
dc
e i2 e
N 22 | Z line | N 22 | Z line | | Z line | N 22 N2 N2
t -t -t
1 N1 RI 0 t N1 RI 0
f (t ) - f (0) t (1 - e ) f (t ) f (0) t (1 - e t )
N2 �
v2 dt 2 2
0
N 2 N 2
Lec- 7
422
Vm N1 d V2
v2ac (t ) R sin(wt f - q ) jw f ac
| Z line | N 2 dt jw N 2
RVm N1 p RVm N1
fac (t ) sin(wt f - q - ) facmax
w | Z line | N 2
2
2 w | Z line | N 22
Vm N1
Rt
RVm N1 N1 RVmt | Z line | N 22 wL X
facmax fdcmax 2 1 1 wt 1 line 1 line
w | Z line | N 2 N 2 | Z line |
2
Vm N1 R Rline Rline
| Z line | N 2 w
2
X
1
R
Lec-6
Lec – 5
Ip Ip
- IS Ip IE - IS
N - I I �100 N 98�45�
�100 N S E
IS �100
IS IS
Lec - 9
Vth - VT 1 1
�100 )Dw w02
(3f ) ( L w02 1 LC < f Df �3Hz
Vth w02
LC
1t di dv di 1 d 2i
v(t ) Ri �
Ceq
-�
idt L
dt dt
R
dt Ceq
i L 2 w0
dt
d 1 1 1
DVL - DVC jI (w L - ) Dw I (2 2 )Dw w02 I ( L L )Dw
dw wCeq w0 Ceq LCeq
423
| VL - VC | 2 LI Dw 2 LI 2 LDw
j 2 LI Dw (DVL - DVC ) tan b 2 2 2 � 2p f Lm 106
| VR | a Rb I a Rb a Rb
106
Lm 3183.1H
2p
source. The fault strikes at time t t 0 . This can be simulated by closing the switch at t t1
424
R jwL or Z q models the line impedance. The fault current in the line is given by
i (t ) 0 0 t t0
t -t 0
V sin(w t f - q ) -
t
t t0
i (t ) m I 0e
|Z |
Where τ is the time constant of the line τ =L/R. The fault current has two components in
it. The first component models the steady state sinusoidal ac response while the second current
is the dc offset current due to the presence of inductive component in the circuit. Recall that
current in an inductance can not change instantaneously. As t ∞, the instantaneous dc
It is more or less obvious that, dc offset is not seen in the waveform after 5 time constants.
The value of I0 can be worked out by setting the current at t t o to zero.
This implies that
Vm
I0 - sin(wt 0 - q )
Z
425
Thus
t -t 0
Vm V -( )
i (t ) sin(wt f - q ) - m sin(wt f - q )e t
Z Z
fig.2
It can be seen that severity of dc offset component in fault current is maximum when
a) f q
p
b) wt 0
2
426
p 1
For example, if angle of transmission line is 800, then with f = 800 & t 0 =
2 2p 50 200
V
sec = 5msec, the severity of dc offset current would equal I 0 Z , which is also the peak
m
We now plan to show that CT can saturate on dc offset current. Also, we plan to show
that the resulting distortions in the CT secondary current can be un-acceptably high. While
doing this analysis, we will neglect ac symmetrical component. In other words, we rest our
belief in superposition theorem atleast qualitatively and will finally evaluate effect using it
Notice that the current that we are dealing with is non-linear, a rigorous application of super
position theorem is simply out of question.
427
First consider an ideal CT excited by the dc offset current source. An ideal CT will faithfully
replicates primary current waveform on the secondary side. Hence, the secondary current
would be given by
-t
I0 t
i2 (t ) e
N
and the voltage developed across CT secondary would be given by
-t
RI N2
v 2 (t ) 0 e t where N N
N 1
For simplicity, let us assume that the initial flux in the transformer core at t=0 is zero
f ( 0 ) 0 ; Then we can compute the flux in the transformer core by using faraday’s law
df
V2 N 2 ---------(2)
dt
428
t
f (t ) - f (0) v 0
2 dt
RI 0
-t
t 1- e t
N2
-t
LI 0
(1 - e t )
N2
-t
LI 0
f (t ) f (0) (1 - e t )
N2
-t
LI 0
(1 - e t ) ------- (3)
N2
as a consequence of dc offset current,
Thus, flux in the core increases exponentially to a peak value of
f dmax
c
LI 0
N2
as t
L Vm Vm
N Z Z
f dmax
c
Note that unlike ac voltage induced flux, which is sinusoidal, this flux is unidirectional. The ac
voltage induced flux has zero average value. However, dc offset induced does not have this
nice feature. The total flux in ideal CT core is a summation of ac flux and dc flux.
d
The ac flux in the CT core can be obtained by substituting operator by jw . Hence
dt
If v2 (t ) Vm sin(wt f ) , then
Vm p
f ac sin(wt f - )
wN 2 2
The peak value of ac flux is given by
429
Vm
f acmax
wN 2
However Vm R2 I 0
max
R2 I 0max
Hence facmax
wN 2
and peak value of the total flux is given by
Vm LI 0max
facmax f dcmax
wN 2 N2
In practice, if this flux exceeds the knee-point flux in the core (see fig.), then the CT core
will saturate.
As a consequence of CT core saturation, the secondary current would not faithfully replicate
the primary current. Infact, in practice it is observed that CT secondary current is clipped. The
clipping of CT current leads to “blinding” of the relay which cannot function further. Hence,
CT saturation in presence of dc offset current is a serious problem which relay designers have
to face. Note that dc flux accumulates gradually. (Depends upon the transmission line time
constant ( t ). It is apparent that saturation should not occur immediately after the inception of
the fault. Thus, if the relay is fast enough in decision making, it is likely that a relaying
decision would be undertaken before the CT fully saturates. This is another important reason
for increasing the speed of relaying system. For bus-fault protection, where the dc saturation
due to dc offset current can be a significant contributing factor, quarter cycle operations *****
430
specifically are imposed. Similarly, a distance relay is expected to operate within ½-1 cycle
time.
CT oversizing factors
Typically, an efficient design of transformer would correspond to choosing the core cross
section such that f mac should be near the knee point of B-H curve. One obvious way of
avoiding the CT saturation on dc flux is to oversize the core so that for flux (f acmax f dcmax ) , the
(f acmax f dcmax )
corresponding B is below the knee-point. Hence, the factor is called core-
f acmax
oversizing factor.
f dcmax
Core-oversizing factor = 1
f acmax
LI o N 2
1
RI 0 wN 2
wL
1
R
X
1
R
Note that X/R in above equation is the transmission line X/R ratio. For a 220KV line X/R 10.
This would imply that transformer core should be oversized by a factor of 11. For a 400KV
line, typical value of X/R 20. This would imply an oversizing required of about 21 times the
usual design. Clearly this high amount of oversizing is not practical. Thus, the important
conclusion is that, protection engineers have to live with the saturation problem.
Cautions in CT selection:
While choosing a CT for a particular application, it is necessary to observe following
precautions.
89. The CT rating and continuous load current should match. For example, if max load
current is 90A, a 100:5 Ct may be acceptable but 50:5 is not acceptable.
431
90. The maximum fault current should be less than 20 times the CT rated current. for
example 100:5 CT can be used, so long as burden on the CT & maximum primary fault
current is below 2000A.
91. The voltage rating of CT should be compatible. For example, 100:5 C100 would give
linear response, upto 20 times rated current provided CT burden is kept
below(100/20*5=1 Ω). With 2 Ω burden, this CT can be used only if maximum current
is limited to 1000A.
92. Parallel of CT’s e.g. in differential protection, or with SLG fault can create significant
errors in CT performance. One should in general ascertain that magnetizing current is
kept much below the pick up value.
Following example, illustrates this point
Exercise problems:
If the current ratio is adequate for a protection, but CT burden is high; then the
performance of CT may deteriorate due to large magnetizing current and/or saturation problem.
The CT performance can be improved by connecting the CT’s in series.
45) Show the dotted terminals for correct secondary series connection
46) What is the VA of CT in fig (a) & (b) respectively?
67) Electromechanical relays tend to saturate at high currents. This reduces the relay burden
on CT, and so that the CT performance at moderately high currents may be considered
better than at relay’s rated burden at 5A.
68) Use of instantaneous over current relays has the potential to overcome this problem of
saturation of CT’s
432
69) Differential protection can operate on external faults due to the un equal saturation of
CT’s
Lecture-6
Examples
28. If a 300:5 class C CT is connected to a meter with resistance R I 1 and
secondary current in the CT is 4.5A find out the primary current voltage
developed across the meter and % rate error. Lead wire resistance R L 0.02
secondary resistance RS of a 300/5 CT 0.15
Diagram
R I 1 , R L 0.02 RS 0.15 I S 4.5 A
Total secondary resistance RT R I R L RS
1.17
Secondary voltage I S RT
4.5 1.17
5.265V
From Fig 5.7,
Exciting current IE for 5.265V
= 0.03A
Turns ratio N = 300/5 = 60
I p N (I S I E )
= 60(4.5 + 0.03)
= 271.8A
Voltage across meter I S R I
4.5 1 = 4.5V
IE 0.03
Ratio error 100 100
IS 4.5
= 0.67%
Rb
433
Lecture – 8
Examples
45. Design a CCVT for a 132kV transmission line using the following data.
Resistive Burden (3f )-150VA
Df 3Hz , phase angle error b = 40 min
Consider 4 choices of V2 as 33kV, 11kV, 6.6kV and 3.3kV
Diagram 1 Diagram 2
Transmission line voltage V = 132kV. Suppose V 2 (P_N) be the voltage to be
produced by the capacitive potential divider with capacitance values C1 and C2
and L the value of tuning inductor. The standardized VT secondary voltage is 110
volts (L-L).
Here specification for phase angle error b is 40 minutes variation in frequency
can be upto Df 3Hz . Phase angle error for change in w by Dw in the above
equation circuit, is given by
1
( L 2 )Dw
w C
1
At tuning frequency w 2
LC
Substituting w 1 LC
2
747.2 H
1 1
C1 C 2
w 2 L (3/ 4) 2 747.2
1.3610 -2 F
3) V2 6.6kV
3 �(6.6 �103 )2
Rb
'
150
87.1210 4
b �Rb' 0.01164 �87.12 �104
L
2 �Dw 2 �2p �3
269H ,
C1 C 2 3.7710 -2 F
4) V2 3.3kV
3 �(3.3 �103 ) 2
Rb'
150
21.7810 4
b �Rb' 0.01164 �21.78 �104
L
2 �Dw 2 �2p �3
67.25 H
C1 C2 0.151 F
The values of L, C1 C 2 for different values of V2 are tabulated below.
V2 L C1 C 2
33kV 6722.2H 0.00151 F
11kV 747.2H 0.0136 F
6.6kV 269H 0.0377 F
3.3kV 67.25H 0.151 F
From the above table it is clear that smaller the value of V 2, the smaller is the
value of L and higher the value of C 1 and C2 for tuning condition. If we select too low
value of V2 and L then capacitance values will be beyond available limits, and if we
select higher value of V2 and L, then CCVT and inductor will become bulky. So a
compromise is necessary and let us select V2 = 6.6kV
For V2 = 6.6kV
L = 269H
C1 C 2 0.0377 F
V C1 C 2
Now,
V2 C1
13210 3 0.037710 -6
36.610 3
C1
0.0377 36.610 3 10 -6 F
C1
13210 3
0.0033F
435
C 2 0.0344F
In this design, we explained the basic concept for CCVT design and we assumed
the transformer to be ideal. But in actual design practice the value of magnetizing
impedance of transformer, resistance of reactor etc have to be taken into account,
as ratio error a and phase angle error b will also get affected by these values.
46. Diagram
The equivalent circuit of a CCVT is shown in fig 8.3. The values of C 1 and C2 are
0.0018 F and 0.018 F respectively. Tuning inductor has an inductance of
497H and resistance of 4620 .
Xm of the 6.6kV VT is 1M , core loss = 20 watts per phase, VA burden =
150VA per phase. Value of Cm for compensating the current drawn by m is equal
to 3.18310 -9 F .
(ooo) Verify the appropriateness of choice of L and Cm.
Ans: If C1 0.0018F and C 2 0.0186F then the value L of tuning inductor
is given by
1
L 2
w (C1 C 2 )
where w 2p f and f = tuning frequency
1
L
(2p �50) (0.0018 0.0186) �10-6
2
1
Xm
w Cm
1 1
Cm
w X m (2p �50) �� 1 106
3.183 �10-9 F
The value is also same as the selected value of Cm Hence the selection of both L
and Cm is appropriate.
(qqq) If the frequency drops from 50Hz to 47Hz, what would be the values of
ratio error and phase angle error?
Ans: Core loss = 20w
V22
20W
Rm
436
V22 (6600) 2
Rm
20 20
2.18 �10
6
6600 0
A
260874.14 -2.44�
VT I th �Z
6600 0
�256147.5 1.82�
260874.14 -2.44�
6480.42 4.26�
(6600 - 6480.42)
Hence % ratio error �100
6600
=1.81%
Phase angle error = 4.26�
V2 6.6kV
r a w2 a 2
M
d 2i R di 1 1 R
t �t0 2
i0 wn 2p �50 2 Iwn
dt L dt LCeq LC L
d 2i
2
2a wn wn2i 0 a < 1
dt
Lec – 8
1
2p �50 2zw R d i 2zw w 2i 0 z wn z < 1
2
wn
LCeq n
L dt 2 n n
-t V
t I 0 - m sin(wt0 f - q ) f q
e | Z line |
438
Example 1:
d
439
Answer:
Based on the criteria that the CT can deliver 20 times rated secondary current
without exceeding a 10% ratio error, the maximum fault current will be 24000A.
However, with a 2.0Ω burden, this will result in a voltage below the knee point of the CT
and, as a practical matter, it will be within 10% accuracy at higher currents. This can only
be accurately determined from excitation or ratio correction curves and not from the
accuracy classification. For example, a CT with characteristics shown in above figure
will produce between 180-240A without exceeding the 10% ratio error, depending on the
power factor of the 2.0Ω burden.
Example 2:
A 1200/5, C400 CT is connected on the 1000/5 tap. What is the maximum secondary
burden that can be used and still maintain rated accuracy at 20 times rated symmetrical
secondary current?
Answer:
Since the secondary voltage capability is directly proportional to the connected tap, the
CT will support a voltage of 1000/1200 400V or 333V. Twenty times the rated
secondary current is 100A. Therefore, the maximum burden is 333V/100A or 3.33 Ω
Example 3:
Assume that secondary burden in a relay circuit is 5Ω. The relay setting is 2A and the CT
ratio is 300/5. Using above figure, calculate the primary current required to operate the
relay?
Answer:
440
N (I E I S )
= 300/5(0.04+2) A=122A
Example 4:
A relay is expected to operate for a 7000A primary current. The CT ratio is 600/5.
Secondary burden is 3.5 Ω. What is the error for the CT shown in above figure?
Answer:
The total secondary fault current is (7000/600) 5=58A. Assume that exciting current is
negligible.
VS I S ( R B RS )
= 58(3.5+0.31)
= 221V
The exciting current will not be negligible, however, and the calculation will not be
iterated.
Lec – 7
N1 RI 0 Vm N1 R Vm Vm N1 N1 RI 0 -tt N1 I 0 -tt
fdcmax t t N1 Rt v2 (t )
dc
e i2 e
N 22 | Z line | N 22 | Z line | | Z line | N 22 N2 N2
t -t -t
1 N1 RI 0 t N1 RI 0
f (t ) - f (0) t (1 - e ) f (t ) f (0) t (1 - e t )
N2 �
v2 dt 2 2
0
N 2 N 2
Lec- 7
441
Vm N1 d V2
v2ac (t ) R sin(wt f - q ) jw f ac
| Z line | N 2 dt jw N 2
RVm N1 p RVm N1
fac (t ) sin(wt f - q - ) facmax
w | Z line | N 2
2
2 w | Z line | N 22
Vm N1
Rt
RVm N1 N1 RVmt | Z line | N 22 wL X
facmax fdcmax 2 1 1 wt 1 line 1 line
w | Z line | N 2 N 2 | Z line |
2
Vm N1 R Rline Rline
| Z line | N 2 w
2
X
1
R
Lec-6
Lec – 5
Ip Ip
- IS Ip IE - IS
N - I I �100 N 98�45�
�100 N S E
IS �100
IS IS
Lec - 9
Vth - VT 1 1
�100 )Dw w02
(3f ) ( L w02 1 LC < f Df �3Hz
Vth w02
LC
1t di dv di 1 d 2i
v(t ) Ri �
Ceq
-�
idt L
dt dt
R
dt Ceq
i L 2 w0
dt
d 1 1 1
DVL - DVC jI (w L - ) Dw I (2 2 )Dw w02 I ( L L )Dw
dw wCeq w0 Ceq LCeq
442
| VL - VC | 2 LI Dw 2 LI 2 LDw
j 2 LI Dw (DVL - DVC ) tan b 2 2 2 � 2p f Lm 106
| VR | a Rb I a Rb a Rb
106
Lm 3183.1H
2p
source. The fault strikes at time t t 0 . This can be simulated by closing the switch at t t1
443
R jwL or Z q models the line impedance. The fault current in the line is given by
i (t ) 0 0 t t0
t -t 0
V sin(w t f - q ) -
t
t t0
i (t ) m I 0e
|Z |
Where τ is the time constant of the line τ =L/R. The fault current has two components in
it. The first component models the steady state sinusoidal ac response while the second current
is the dc offset current due to the presence of inductive component in the circuit. Recall that
current in an inductance can not change instantaneously. As t ∞, the instantaneous dc
It is more or less obvious that, dc offset is not seen in the waveform after 5 time constants.
The value of I0 can be worked out by setting the current at t t o to zero.
This implies that
Vm
I0 - sin(wt 0 - q )
Z
444
Thus
t -t 0
Vm V -( )
i (t ) sin(wt f - q ) - m sin(wt f - q )e t
Z Z
fig.2
It can be seen that severity of dc offset component in fault current is maximum when
a) f q
p
b) wt 0
2
445
p 1
For example, if angle of transmission line is 800, then with f = 800 & t 0 =
2 2p 50 200
V
sec = 5msec, the severity of dc offset current would equal I 0 Z , which is also the peak
m
We now plan to show that CT can saturate on dc offset current. Also, we plan to show
that the resulting distortions in the CT secondary current can be un-acceptably high. While
doing this analysis, we will neglect ac symmetrical component. In other words, we rest our
belief in superposition theorem atleast qualitatively and will finally evaluate effect using it
Notice that the current that we are dealing with is non-linear, a rigorous application of super
position theorem is simply out of question.
446
First consider an ideal CT excited by the dc offset current source. An ideal CT will faithfully
replicates primary current waveform on the secondary side. Hence, the secondary current
would be given by
-t
I0 t
i2 (t ) e
N
and the voltage developed across CT secondary would be given by
-t
RI N2
v 2 (t ) 0 e t where N N
N 1
For simplicity, let us assume that the initial flux in the transformer core at t=0 is zero
f ( 0 ) 0 ; Then we can compute the flux in the transformer core by using faraday’s law
df
V2 N 2 ---------(2)
dt
447
t
f (t ) - f (0) v 0
2 dt
RI 0
-t
t 1- e t
N2
-t
LI 0
(1 - e t )
N2
-t
LI 0
f (t ) f (0) (1 - e t )
N2
-t
LI 0
(1 - e t ) ------- (3)
N2
as a consequence of dc offset current,
Thus, flux in the core increases exponentially to a peak value of
f dmax
c
LI 0
N2
as t
L Vm Vm
N Z Z
f dmax
c
Note that unlike ac voltage induced flux, which is sinusoidal, this flux is unidirectional. The ac
voltage induced flux has zero average value. However, dc offset induced does not have this
nice feature. The total flux in ideal CT core is a summation of ac flux and dc flux.
d
The ac flux in the CT core can be obtained by substituting operator by jw . Hence
dt
If v2 (t ) Vm sin(wt f ) , then
Vm p
f ac sin(wt f - )
wN 2 2
The peak value of ac flux is given by
448
Vm
f acmax
wN 2
However Vm R2 I 0
max
R2 I 0max
Hence facmax
wN 2
and peak value of the total flux is given by
Vm LI 0max
facmax f dcmax
wN 2 N2
In practice, if this flux exceeds the knee-point flux in the core (see fig.), then the CT core
will saturate.
As a consequence of CT core saturation, the secondary current would not faithfully replicate
the primary current. Infact, in practice it is observed that CT secondary current is clipped. The
clipping of CT current leads to “blinding” of the relay which cannot function further. Hence,
CT saturation in presence of dc offset current is a serious problem which relay designers have
to face. Note that dc flux accumulates gradually. (Depends upon the transmission line time
constant ( t ). It is apparent that saturation should not occur immediately after the inception of
the fault. Thus, if the relay is fast enough in decision making, it is likely that a relaying
decision would be undertaken before the CT fully saturates. This is another important reason
for increasing the speed of relaying system. For bus-fault protection, where the dc saturation
due to dc offset current can be a significant contributing factor, quarter cycle operations *****
449
specifically are imposed. Similarly, a distance relay is expected to operate within ½-1 cycle
time.
CT oversizing factors
Typically, an efficient design of transformer would correspond to choosing the core cross
section such that f mac should be near the knee point of B-H curve. One obvious way of
avoiding the CT saturation on dc flux is to oversize the core so that for flux (f acmax f dcmax ) , the
(f acmax f dcmax )
corresponding B is below the knee-point. Hence, the factor is called core-
f acmax
oversizing factor.
f dcmax
Core-oversizing factor = 1
f acmax
LI o N 2
1
RI 0 wN 2
wL
1
R
X
1
R
Note that X/R in above equation is the transmission line X/R ratio. For a 220KV line X/R 10.
This would imply that transformer core should be oversized by a factor of 11. For a 400KV
line, typical value of X/R 20. This would imply an oversizing required of about 21 times the
usual design. Clearly this high amount of oversizing is not practical. Thus, the important
conclusion is that, protection engineers have to live with the saturation problem.
Cautions in CT selection:
While choosing a CT for a particular application, it is necessary to observe following
precautions.
93. The CT rating and continuous load current should match. For example, if max load
current is 90A, a 100:5 Ct may be acceptable but 50:5 is not acceptable.
450
94. The maximum fault current should be less than 20 times the CT rated current. for
example 100:5 CT can be used, so long as burden on the CT & maximum primary fault
current is below 2000A.
95. The voltage rating of CT should be compatible. For example, 100:5 C100 would give
linear response, upto 20 times rated current provided CT burden is kept
below(100/20*5=1 Ω). With 2 Ω burden, this CT can be used only if maximum current
is limited to 1000A.
96. Parallel of CT’s e.g. in differential protection, or with SLG fault can create significant
errors in CT performance. One should in general ascertain that magnetizing current is
kept much below the pick up value.
Following example, illustrates this point
Exercise problems:
If the current ratio is adequate for a protection, but CT burden is high; then the
performance of CT may deteriorate due to large magnetizing current and/or saturation problem.
The CT performance can be improved by connecting the CT’s in series.
47) Show the dotted terminals for correct secondary series connection
48) What is the VA of CT in fig (a) & (b) respectively?
70) Electromechanical relays tend to saturate at high currents. This reduces the relay burden
on CT, and so that the CT performance at moderately high currents may be considered
better than at relay’s rated burden at 5A.
71) Use of instantaneous over current relays has the potential to overcome this problem of
saturation of CT’s
451
72) Differential protection can operate on external faults due to the un equal saturation of
CT’s
Lecture-6
Examples
29. If a 300:5 class C CT is connected to a meter with resistance R I 1 and
secondary current in the CT is 4.5A find out the primary current voltage
developed across the meter and % rate error. Lead wire resistance R L 0.02
secondary resistance RS of a 300/5 CT 0.15
Diagram
R I 1 , R L 0.02 RS 0.15 I S 4.5 A
Total secondary resistance RT R I R L RS
1.17
Secondary voltage I S RT
4.5 1.17
5.265V
From Fig 5.7,
Exciting current IE for 5.265V
= 0.03A
Turns ratio N = 300/5 = 60
I p N (I S I E )
= 60(4.5 + 0.03)
= 271.8A
Voltage across meter I S R I
4.5 1 = 4.5V
IE 0.03
Ratio error 100 100
IS 4.5
= 0.67%
Rb
452
Lecture – 8
Examples
47. Design a CCVT for a 132kV transmission line using the following data.
Resistive Burden (3f )-150VA
Df 3Hz , phase angle error b = 40 min
Consider 4 choices of V2 as 33kV, 11kV, 6.6kV and 3.3kV
Diagram 1 Diagram 2
Transmission line voltage V = 132kV. Suppose V 2 (P_N) be the voltage to be
produced by the capacitive potential divider with capacitance values C1 and C2
and L the value of tuning inductor. The standardized VT secondary voltage is 110
volts (L-L).
Here specification for phase angle error b is 40 minutes variation in frequency
can be upto Df 3Hz . Phase angle error for change in w by Dw in the above
equation circuit, is given by
1
( L 2 )Dw
w C
1
At tuning frequency w 2
LC
Substituting w 1 LC
2
747.2 H
1 1
C1 C 2
w 2 L (3/ 4) 2 747.2
1.3610 -2 F
3) V2 6.6kV
3 �(6.6 �103 )2
Rb
'
150
87.1210 4
b �Rb' 0.01164 �87.12 �104
L
2 �Dw 2 �2p �3
269H ,
C1 C 2 3.7710 -2 F
4) V2 3.3kV
3 �(3.3 �103 ) 2
Rb'
150
21.7810 4
b �Rb' 0.01164 �21.78 �104
L
2 �Dw 2 �2p �3
67.25 H
C1 C2 0.151 F
The values of L, C1 C 2 for different values of V2 are tabulated below.
V2 L C1 C 2
33kV 6722.2H 0.00151 F
11kV 747.2H 0.0136 F
6.6kV 269H 0.0377 F
3.3kV 67.25H 0.151 F
From the above table it is clear that smaller the value of V 2, the smaller is the
value of L and higher the value of C 1 and C2 for tuning condition. If we select too low
value of V2 and L then capacitance values will be beyond available limits, and if we
select higher value of V2 and L, then CCVT and inductor will become bulky. So a
compromise is necessary and let us select V2 = 6.6kV
For V2 = 6.6kV
L = 269H
C1 C 2 0.0377 F
V C1 C 2
Now,
V2 C1
13210 3 0.037710 -6
36.610 3
C1
0.0377 36.610 3 10 -6 F
C1
13210 3
0.0033F
454
C 2 0.0344F
In this design, we explained the basic concept for CCVT design and we assumed
the transformer to be ideal. But in actual design practice the value of magnetizing
impedance of transformer, resistance of reactor etc have to be taken into account,
as ratio error a and phase angle error b will also get affected by these values.
48. Diagram
The equivalent circuit of a CCVT is shown in fig 8.3. The values of C 1 and C2 are
0.0018 F and 0.018 F respectively. Tuning inductor has an inductance of
497H and resistance of 4620 .
Xm of the 6.6kV VT is 1M , core loss = 20 watts per phase, VA burden =
150VA per phase. Value of Cm for compensating the current drawn by m is equal
to 3.18310 -9 F .
(rrr) Verify the appropriateness of choice of L and Cm.
Ans: If C1 0.0018F and C 2 0.0186F then the value L of tuning inductor
is given by
1
L 2
w (C1 C 2 )
where w 2p f and f = tuning frequency
1
L
(2p �50) (0.0018 0.0186) �10-6
2
1
Xm
w Cm
1 1
Cm
w X m (2p �50) �� 1 106
3.183 �10-9 F
The value is also same as the selected value of Cm Hence the selection of both L
and Cm is appropriate.
(ttt) If the frequency drops from 50Hz to 47Hz, what would be the values of
ratio error and phase angle error?
Ans: Core loss = 20w
V22
20W
Rm
455
V22 (6600) 2
Rm
20 20
2.18 �10
6
6600 0
A
260874.14 -2.44�
VT I th �Z
6600 0
�256147.5 1.82�
260874.14 -2.44�
6480.42 4.26�
(6600 - 6480.42)
Hence % ratio error �100
6600
=1.81%
Phase angle error = 4.26�
V2 6.6kV
r a w2 a 2
M
d 2i R di 1 1 R
t �t0 2
i0 wn 2p �50 2 Iwn
dt L dt LCeq LC L
d 2i
2
2a wn wn2i 0 a < 1
dt
Lec – 8
1
2p �50 2zw R d i 2zw w 2i 0 z wn z < 1
2
wn
LCeq n
L dt 2 n n
-t V
t I 0 - m sin(wt0 f - q ) f q
e | Z line |
457
Example 1:
d
458
Answer:
Based on the criteria that the CT can deliver 20 times rated secondary current
without exceeding a 10% ratio error, the maximum fault current will be 24000A.
However, with a 2.0Ω burden, this will result in a voltage below the knee point of the CT
and, as a practical matter, it will be within 10% accuracy at higher currents. This can only
be accurately determined from excitation or ratio correction curves and not from the
accuracy classification. For example, a CT with characteristics shown in above figure
will produce between 180-240A without exceeding the 10% ratio error, depending on the
power factor of the 2.0Ω burden.
Example 2:
A 1200/5, C400 CT is connected on the 1000/5 tap. What is the maximum secondary
burden that can be used and still maintain rated accuracy at 20 times rated symmetrical
secondary current?
Answer:
Since the secondary voltage capability is directly proportional to the connected tap, the
CT will support a voltage of 1000/1200 400V or 333V. Twenty times the rated
secondary current is 100A. Therefore, the maximum burden is 333V/100A or 3.33 Ω
Example 3:
Assume that secondary burden in a relay circuit is 5Ω. The relay setting is 2A and the CT
ratio is 300/5. Using above figure, calculate the primary current required to operate the
relay?
Answer:
459
N (I E I S )
= 300/5(0.04+2) A=122A
Example 4:
A relay is expected to operate for a 7000A primary current. The CT ratio is 600/5.
Secondary burden is 3.5 Ω. What is the error for the CT shown in above figure?
Answer:
The total secondary fault current is (7000/600) 5=58A. Assume that exciting current is
negligible.
VS I S ( R B RS )
= 58(3.5+0.31)
= 221V
The exciting current will not be negligible, however, and the calculation will not be
iterated.
Lec – 7
N1 RI 0 Vm N1 R Vm Vm N1 N1 RI 0 -tt N1 I 0 -tt
fdcmax t t N1 Rt v2 (t )
dc
e i2 e
N 22 | Z line | N 22 | Z line | | Z line | N 22 N2 N2
t -t -t
1 N1 RI 0 t N1 RI 0
f (t ) - f (0) t (1 - e ) f (t ) f (0) t (1 - e t )
N2 �
v2 dt 2 2
0
N 2 N 2
Lec- 7
460
Vm N1 d V2
v2ac (t ) R sin(wt f - q ) jw f ac
| Z line | N 2 dt jw N 2
RVm N1 p RVm N1
fac (t ) sin(wt f - q - ) facmax
w | Z line | N 2
2
2 w | Z line | N 22
Vm N1
Rt
RVm N1 N1 RVmt | Z line | N 22 wL X
facmax fdcmax 2 1 1 wt 1 line 1 line
w | Z line | N 2 N 2 | Z line |
2
Vm N1 R Rline Rline
| Z line | N 2 w
2
X
1
R
Lec-6
Lec – 5
Ip Ip
- IS Ip IE - IS
N - I I �100 N 98�45�
�100 N S E
IS �100
IS IS
Lec - 9
Vth - VT 1 1
�100 )Dw w02
(3f ) ( L w02 1 LC < f Df �3Hz
Vth w02
LC
1t di dv di 1 d 2i
v(t ) Ri �
Ceq
-�
idt L
dt dt
R
dt Ceq
i L 2 w0
dt
d 1 1 1
DVL - DVC jI (w L - ) Dw I (2 2 )Dw w02 I ( L L )Dw
dw wCeq w0 Ceq LCeq
461
| VL - VC | 2 LI Dw 2 LI 2 LDw
j 2 LI Dw (DVL - DVC ) tan b 2 2 2 � 2p f Lm 106
| VR | a Rb I a Rb a Rb
106
Lm 3183.1H
2p
source. The fault strikes at time t t 0 . This can be simulated by closing the switch at t t1
462
R jwL or Z q models the line impedance. The fault current in the line is given by
i (t ) 0 0 t t0
t -t 0
V sin(w t f - q ) -
t
t t0
i (t ) m I 0e
|Z |
Where τ is the time constant of the line τ =L/R. The fault current has two components in
it. The first component models the steady state sinusoidal ac response while the second current
is the dc offset current due to the presence of inductive component in the circuit. Recall that
current in an inductance can not change instantaneously. As t ∞, the instantaneous dc
It is more or less obvious that, dc offset is not seen in the waveform after 5 time constants.
The value of I0 can be worked out by setting the current at t t o to zero.
This implies that
Vm
I0 - sin(wt 0 - q )
Z
463
Thus
t -t 0
Vm V -( )
i (t ) sin(wt f - q ) - m sin(wt f - q )e t
Z Z
fig.2
It can be seen that severity of dc offset component in fault current is maximum when
a) f q
p
b) wt 0
2
464
p 1
For example, if angle of transmission line is 800, then with f = 800 & t 0 =
2 2p 50 200
V
sec = 5msec, the severity of dc offset current would equal I 0 Z , which is also the peak
m
We now plan to show that CT can saturate on dc offset current. Also, we plan to show
that the resulting distortions in the CT secondary current can be un-acceptably high. While
doing this analysis, we will neglect ac symmetrical component. In other words, we rest our
belief in superposition theorem atleast qualitatively and will finally evaluate effect using it
Notice that the current that we are dealing with is non-linear, a rigorous application of super
position theorem is simply out of question.
465
First consider an ideal CT excited by the dc offset current source. An ideal CT will faithfully
replicates primary current waveform on the secondary side. Hence, the secondary current
would be given by
-t
I0 t
i2 (t ) e
N
and the voltage developed across CT secondary would be given by
-t
RI N2
v 2 (t ) 0 e t where N N
N 1
For simplicity, let us assume that the initial flux in the transformer core at t=0 is zero
f ( 0 ) 0 ; Then we can compute the flux in the transformer core by using faraday’s law
df
V2 N 2 ---------(2)
dt
466
t
f (t ) - f (0) v 0
2 dt
RI 0
-t
t 1- e t
N2
-t
LI 0
(1 - e t )
N2
-t
LI 0
f (t ) f (0) (1 - e t )
N2
-t
LI 0
(1 - e t ) ------- (3)
N2
as a consequence of dc offset current,
Thus, flux in the core increases exponentially to a peak value of
f dmax
c
LI 0
N2
as t
L Vm Vm
N Z Z
f dmax
c
Note that unlike ac voltage induced flux, which is sinusoidal, this flux is unidirectional. The ac
voltage induced flux has zero average value. However, dc offset induced does not have this
nice feature. The total flux in ideal CT core is a summation of ac flux and dc flux.
d
The ac flux in the CT core can be obtained by substituting operator by jw . Hence
dt
If v2 (t ) Vm sin(wt f ) , then
Vm p
f ac sin(wt f - )
wN 2 2
The peak value of ac flux is given by
467
Vm
f acmax
wN 2
However Vm R2 I 0
max
R2 I 0max
Hence facmax
wN 2
and peak value of the total flux is given by
Vm LI 0max
facmax f dcmax
wN 2 N2
In practice, if this flux exceeds the knee-point flux in the core (see fig.), then the CT core
will saturate.
As a consequence of CT core saturation, the secondary current would not faithfully replicate
the primary current. Infact, in practice it is observed that CT secondary current is clipped. The
clipping of CT current leads to “blinding” of the relay which cannot function further. Hence,
CT saturation in presence of dc offset current is a serious problem which relay designers have
to face. Note that dc flux accumulates gradually. (Depends upon the transmission line time
constant ( t ). It is apparent that saturation should not occur immediately after the inception of
the fault. Thus, if the relay is fast enough in decision making, it is likely that a relaying
decision would be undertaken before the CT fully saturates. This is another important reason
for increasing the speed of relaying system. For bus-fault protection, where the dc saturation
due to dc offset current can be a significant contributing factor, quarter cycle operations *****
468
specifically are imposed. Similarly, a distance relay is expected to operate within ½-1 cycle
time.
CT oversizing factors
Typically, an efficient design of transformer would correspond to choosing the core cross
section such that f mac should be near the knee point of B-H curve. One obvious way of
avoiding the CT saturation on dc flux is to oversize the core so that for flux (f acmax f dcmax ) , the
(f acmax f dcmax )
corresponding B is below the knee-point. Hence, the factor is called core-
f acmax
oversizing factor.
f dcmax
Core-oversizing factor = 1
f acmax
LI o N 2
1
RI 0 wN 2
wL
1
R
X
1
R
Note that X/R in above equation is the transmission line X/R ratio. For a 220KV line X/R 10.
This would imply that transformer core should be oversized by a factor of 11. For a 400KV
line, typical value of X/R 20. This would imply an oversizing required of about 21 times the
usual design. Clearly this high amount of oversizing is not practical. Thus, the important
conclusion is that, protection engineers have to live with the saturation problem.
Cautions in CT selection:
While choosing a CT for a particular application, it is necessary to observe following
precautions.
97. The CT rating and continuous load current should match. For example, if max load
current is 90A, a 100:5 Ct may be acceptable but 50:5 is not acceptable.
469
98. The maximum fault current should be less than 20 times the CT rated current. for
example 100:5 CT can be used, so long as burden on the CT & maximum primary fault
current is below 2000A.
99. The voltage rating of CT should be compatible. For example, 100:5 C100 would give
linear response, upto 20 times rated current provided CT burden is kept
below(100/20*5=1 Ω). With 2 Ω burden, this CT can be used only if maximum current
is limited to 1000A.
100. Parallel of CT’s e.g. in differential protection, or with SLG fault can create
significant errors in CT performance. One should in general ascertain that magnetizing
current is kept much below the pick up value.
Following example, illustrates this point
Exercise problems:
If the current ratio is adequate for a protection, but CT burden is high; then the
performance of CT may deteriorate due to large magnetizing current and/or saturation problem.
The CT performance can be improved by connecting the CT’s in series.
49) Show the dotted terminals for correct secondary series connection
50) What is the VA of CT in fig (a) & (b) respectively?
73) Electromechanical relays tend to saturate at high currents. This reduces the relay burden
on CT, and so that the CT performance at moderately high currents may be considered
better than at relay’s rated burden at 5A.
74) Use of instantaneous over current relays has the potential to overcome this problem of
saturation of CT’s
470
75) Differential protection can operate on external faults due to the un equal saturation of
CT’s
Lecture-6
Examples
30. If a 300:5 class C CT is connected to a meter with resistance R I 1 and
secondary current in the CT is 4.5A find out the primary current voltage
developed across the meter and % rate error. Lead wire resistance R L 0.02
secondary resistance RS of a 300/5 CT 0.15
Diagram
R I 1 , R L 0.02 RS 0.15 I S 4.5 A
Total secondary resistance RT R I R L RS
1.17
Secondary voltage I S RT
4.5 1.17
5.265V
From Fig 5.7,
Exciting current IE for 5.265V
= 0.03A
Turns ratio N = 300/5 = 60
I p N (I S I E )
= 60(4.5 + 0.03)
= 271.8A
Voltage across meter I S R I
4.5 1 = 4.5V
IE 0.03
Ratio error 100 100
IS 4.5
= 0.67%
Rb
471
Lecture – 8
Examples
49. Design a CCVT for a 132kV transmission line using the following data.
Resistive Burden (3f )-150VA
Df 3Hz , phase angle error b = 40 min
Consider 4 choices of V2 as 33kV, 11kV, 6.6kV and 3.3kV
Diagram 1 Diagram 2
Transmission line voltage V = 132kV. Suppose V 2 (P_N) be the voltage to be
produced by the capacitive potential divider with capacitance values C1 and C2
and L the value of tuning inductor. The standardized VT secondary voltage is 110
volts (L-L).
Here specification for phase angle error b is 40 minutes variation in frequency
can be upto Df 3Hz . Phase angle error for change in w by Dw in the above
equation circuit, is given by
1
( L 2 )Dw
w C
1
At tuning frequency w 2
LC
Substituting w 1 LC
2
747.2 H
1 1
C1 C 2
w 2 L (3/ 4) 2 747.2
1.3610 -2 F
3) V2 6.6kV
3 �(6.6 �103 )2
Rb
'
150
87.1210 4
b �Rb' 0.01164 �87.12 �104
L
2 �Dw 2 �2p �3
269H ,
C1 C 2 3.7710 -2 F
4) V2 3.3kV
3 �(3.3 �103 ) 2
Rb'
150
21.7810 4
b �Rb' 0.01164 �21.78 �104
L
2 �Dw 2 �2p �3
67.25 H
C1 C2 0.151 F
The values of L, C1 C 2 for different values of V2 are tabulated below.
V2 L C1 C 2
33kV 6722.2H 0.00151 F
11kV 747.2H 0.0136 F
6.6kV 269H 0.0377 F
3.3kV 67.25H 0.151 F
From the above table it is clear that smaller the value of V 2, the smaller is the
value of L and higher the value of C 1 and C2 for tuning condition. If we select too low
value of V2 and L then capacitance values will be beyond available limits, and if we
select higher value of V2 and L, then CCVT and inductor will become bulky. So a
compromise is necessary and let us select V2 = 6.6kV
For V2 = 6.6kV
L = 269H
C1 C 2 0.0377 F
V C1 C 2
Now,
V2 C1
13210 3 0.037710 -6
36.610 3
C1
0.0377 36.610 3 10 -6 F
C1
13210 3
0.0033F
473
C 2 0.0344F
In this design, we explained the basic concept for CCVT design and we assumed
the transformer to be ideal. But in actual design practice the value of magnetizing
impedance of transformer, resistance of reactor etc have to be taken into account,
as ratio error a and phase angle error b will also get affected by these values.
50. Diagram
The equivalent circuit of a CCVT is shown in fig 8.3. The values of C 1 and C2 are
0.0018 F and 0.018 F respectively. Tuning inductor has an inductance of
497H and resistance of 4620 .
Xm of the 6.6kV VT is 1M , core loss = 20 watts per phase, VA burden =
150VA per phase. Value of Cm for compensating the current drawn by m is equal
to 3.18310 -9 F .
(uuu) Verify the appropriateness of choice of L and Cm.
Ans: If C1 0.0018F and C 2 0.0186F then the value L of tuning inductor
is given by
1
L 2
w (C1 C 2 )
where w 2p f and f = tuning frequency
1
L
(2p �50) (0.0018 0.0186) �10-6
2
1
Xm
w Cm
1 1
Cm
w X m (2p �50) �� 1 106
3.183 �10-9 F
The value is also same as the selected value of Cm Hence the selection of both L
and Cm is appropriate.
(www) If the frequency drops from 50Hz to 47Hz, what would be the values of
ratio error and phase angle error?
Ans: Core loss = 20w
V22
20W
Rm
474
V22 (6600) 2
Rm
20 20
2.18 �10
6
6600 0
A
260874.14 -2.44�
VT I th �Z
6600 0
�256147.5 1.82�
260874.14 -2.44�
6480.42 4.26�
(6600 - 6480.42)
Hence % ratio error �100
6600
=1.81%
Phase angle error = 4.26�
V2 6.6kV
r a w2 a 2
M
d 2i R di 1 1 R
t �t0 2
i0 wn 2p �50 2 Iwn
dt L dt LCeq LC L
d 2i
2
2a wn wn2i 0 a < 1
dt
Lec – 8
1
2p �50 2zw R d i 2zw w 2i 0 z wn z < 1
2
wn
LCeq n
L dt 2 n n
-t V
t I 0 - m sin(wt0 f - q ) f q
e | Z line |
476
Example 1:
d
477
Answer:
Based on the criteria that the CT can deliver 20 times rated secondary current
without exceeding a 10% ratio error, the maximum fault current will be 24000A.
However, with a 2.0Ω burden, this will result in a voltage below the knee point of the CT
and, as a practical matter, it will be within 10% accuracy at higher currents. This can only
be accurately determined from excitation or ratio correction curves and not from the
accuracy classification. For example, a CT with characteristics shown in above figure
will produce between 180-240A without exceeding the 10% ratio error, depending on the
power factor of the 2.0Ω burden.
Example 2:
A 1200/5, C400 CT is connected on the 1000/5 tap. What is the maximum secondary
burden that can be used and still maintain rated accuracy at 20 times rated symmetrical
secondary current?
Answer:
Since the secondary voltage capability is directly proportional to the connected tap, the
CT will support a voltage of 1000/1200 400V or 333V. Twenty times the rated
secondary current is 100A. Therefore, the maximum burden is 333V/100A or 3.33 Ω
Example 3:
Assume that secondary burden in a relay circuit is 5Ω. The relay setting is 2A and the CT
ratio is 300/5. Using above figure, calculate the primary current required to operate the
relay?
Answer:
478
N (I E I S )
= 300/5(0.04+2) A=122A
Example 4:
A relay is expected to operate for a 7000A primary current. The CT ratio is 600/5.
Secondary burden is 3.5 Ω. What is the error for the CT shown in above figure?
Answer:
The total secondary fault current is (7000/600) 5=58A. Assume that exciting current is
negligible.
VS I S ( R B RS )
= 58(3.5+0.31)
= 221V
The exciting current will not be negligible, however, and the calculation will not be
iterated.
Lec – 7
N1 RI 0 Vm N1 R Vm Vm N1 N1 RI 0 -tt N1 I 0 -tt
fdcmax t t N1 Rt v2 (t )
dc
e i2 e
N 22 | Z line | N 22 | Z line | | Z line | N 22 N2 N2
t -t -t
1 N1 RI 0 t N1 RI 0
f (t ) - f (0) t (1 - e ) f (t ) f (0) t (1 - e t )
N2 �
v2 dt 2 2
0
N 2 N 2
Lec- 7
479
Vm N1 d V2
v2ac (t ) R sin(wt f - q ) jw f ac
| Z line | N 2 dt jw N 2
RVm N1 p RVm N1
fac (t ) sin(wt f - q - ) facmax
w | Z line | N 2
2
2 w | Z line | N 22
Vm N1
Rt
RVm N1 N1 RVmt | Z line | N 22 wL X
facmax fdcmax 2 1 1 wt 1 line 1 line
w | Z line | N 2 N 2 | Z line |
2
Vm N1 R Rline Rline
| Z line | N 2 w
2
X
1
R
Lec-6
Lec – 5
Ip Ip
- IS Ip IE - IS
N - I I �100 N 98�45�
�100 N S E
IS �100
IS IS
Lec - 9
Vth - VT 1 1
�100 )Dw w02
(3f ) ( L w02 1 LC < f Df �3Hz
Vth w02
LC
1t di dv di 1 d 2i
v(t ) Ri �
Ceq
-�
idt L
dt dt
R
dt Ceq
i L 2 w0
dt
d 1 1 1
DVL - DVC jI (w L - ) Dw I (2 2 )Dw w02 I ( L L )Dw
dw wCeq w0 Ceq LCeq
480
| VL - VC | 2 LI Dw 2 LI 2 LDw
j 2 LI Dw (DVL - DVC ) tan b 2 2 2 � 2p f Lm 106
| VR | a Rb I a Rb a Rb
106
Lm 3183.1H
2p
source. The fault strikes at time t t 0 . This can be simulated by closing the switch at t t1
481
R jwL or Z q models the line impedance. The fault current in the line is given by
i (t ) 0 0 t t0
t -t 0
V sin(w t f - q ) -
t
t t0
i (t ) m I 0e
|Z |
Where τ is the time constant of the line τ =L/R. The fault current has two components in
it. The first component models the steady state sinusoidal ac response while the second current
is the dc offset current due to the presence of inductive component in the circuit. Recall that
current in an inductance can not change instantaneously. As t ∞, the instantaneous dc
It is more or less obvious that, dc offset is not seen in the waveform after 5 time constants.
The value of I0 can be worked out by setting the current at t t o to zero.
This implies that
Vm
I0 - sin(wt 0 - q )
Z
482
Thus
t -t 0
Vm V -( )
i (t ) sin(wt f - q ) - m sin(wt f - q )e t
Z Z
fig.2
It can be seen that severity of dc offset component in fault current is maximum when
a) f q
p
b) wt 0
2
483
p 1
For example, if angle of transmission line is 800, then with f = 800 & t 0 =
2 2p 50 200
V
sec = 5msec, the severity of dc offset current would equal I 0 Z , which is also the peak
m
We now plan to show that CT can saturate on dc offset current. Also, we plan to show
that the resulting distortions in the CT secondary current can be un-acceptably high. While
doing this analysis, we will neglect ac symmetrical component. In other words, we rest our
belief in superposition theorem atleast qualitatively and will finally evaluate effect using it
Notice that the current that we are dealing with is non-linear, a rigorous application of super
position theorem is simply out of question.
484
First consider an ideal CT excited by the dc offset current source. An ideal CT will faithfully
replicates primary current waveform on the secondary side. Hence, the secondary current
would be given by
-t
I0 t
i2 (t ) e
N
and the voltage developed across CT secondary would be given by
-t
RI N2
v 2 (t ) 0 e t where N N
N 1
For simplicity, let us assume that the initial flux in the transformer core at t=0 is zero
f ( 0 ) 0 ; Then we can compute the flux in the transformer core by using faraday’s law
df
V2 N 2 ---------(2)
dt
485
t
f (t ) - f (0) v 0
2 dt
RI 0
-t
t 1- e t
N2
-t
LI 0
(1 - e t )
N2
-t
LI 0
f (t ) f (0) (1 - e t )
N2
-t
LI 0
(1 - e t ) ------- (3)
N2
as a consequence of dc offset current,
Thus, flux in the core increases exponentially to a peak value of
f dmax
c
LI 0
N2
as t
L Vm Vm
N Z Z
f dmax
c
Note that unlike ac voltage induced flux, which is sinusoidal, this flux is unidirectional. The ac
voltage induced flux has zero average value. However, dc offset induced does not have this
nice feature. The total flux in ideal CT core is a summation of ac flux and dc flux.
d
The ac flux in the CT core can be obtained by substituting operator by jw . Hence
dt
If v2 (t ) Vm sin(wt f ) , then
Vm p
f ac sin(wt f - )
wN 2 2
The peak value of ac flux is given by
486
Vm
f acmax
wN 2
However Vm R2 I 0
max
R2 I 0max
Hence facmax
wN 2
and peak value of the total flux is given by
Vm LI 0max
facmax f dcmax
wN 2 N2
In practice, if this flux exceeds the knee-point flux in the core (see fig.), then the CT core
will saturate.
As a consequence of CT core saturation, the secondary current would not faithfully replicate
the primary current. Infact, in practice it is observed that CT secondary current is clipped. The
clipping of CT current leads to “blinding” of the relay which cannot function further. Hence,
CT saturation in presence of dc offset current is a serious problem which relay designers have
to face. Note that dc flux accumulates gradually. (Depends upon the transmission line time
constant ( t ). It is apparent that saturation should not occur immediately after the inception of
the fault. Thus, if the relay is fast enough in decision making, it is likely that a relaying
decision would be undertaken before the CT fully saturates. This is another important reason
for increasing the speed of relaying system. For bus-fault protection, where the dc saturation
due to dc offset current can be a significant contributing factor, quarter cycle operations *****
487
specifically are imposed. Similarly, a distance relay is expected to operate within ½-1 cycle
time.
CT oversizing factors
Typically, an efficient design of transformer would correspond to choosing the core cross
section such that f mac should be near the knee point of B-H curve. One obvious way of
avoiding the CT saturation on dc flux is to oversize the core so that for flux (f acmax f dcmax ) , the
(f acmax f dcmax )
corresponding B is below the knee-point. Hence, the factor is called core-
f acmax
oversizing factor.
f dcmax
Core-oversizing factor = 1
f acmax
LI o N 2
1
RI 0 wN 2
wL
1
R
X
1
R
Note that X/R in above equation is the transmission line X/R ratio. For a 220KV line X/R 10.
This would imply that transformer core should be oversized by a factor of 11. For a 400KV
line, typical value of X/R 20. This would imply an oversizing required of about 21 times the
usual design. Clearly this high amount of oversizing is not practical. Thus, the important
conclusion is that, protection engineers have to live with the saturation problem.
Cautions in CT selection:
While choosing a CT for a particular application, it is necessary to observe following
precautions.
101. The CT rating and continuous load current should match. For example, if max
load current is 90A, a 100:5 Ct may be acceptable but 50:5 is not acceptable.
488
102. The maximum fault current should be less than 20 times the CT rated current.
for example 100:5 CT can be used, so long as burden on the CT & maximum primary
fault current is below 2000A.
103. The voltage rating of CT should be compatible. For example, 100:5 C100 would
give linear response, upto 20 times rated current provided CT burden is kept
below(100/20*5=1 Ω). With 2 Ω burden, this CT can be used only if maximum current
is limited to 1000A.
104. Parallel of CT’s e.g. in differential protection, or with SLG fault can create
significant errors in CT performance. One should in general ascertain that magnetizing
current is kept much below the pick up value.
Following example, illustrates this point
Exercise problems:
If the current ratio is adequate for a protection, but CT burden is high; then the
performance of CT may deteriorate due to large magnetizing current and/or saturation problem.
The CT performance can be improved by connecting the CT’s in series.
51) Show the dotted terminals for correct secondary series connection
52) What is the VA of CT in fig (a) & (b) respectively?
76) Electromechanical relays tend to saturate at high currents. This reduces the relay burden
on CT, and so that the CT performance at moderately high currents may be considered
better than at relay’s rated burden at 5A.
77) Use of instantaneous over current relays has the potential to overcome this problem of
saturation of CT’s
489
78) Differential protection can operate on external faults due to the un equal saturation of
CT’s
Lecture-6
Examples
31. If a 300:5 class C CT is connected to a meter with resistance R I 1 and
secondary current in the CT is 4.5A find out the primary current voltage
developed across the meter and % rate error. Lead wire resistance R L 0.02
secondary resistance RS of a 300/5 CT 0.15
Diagram
R I 1 , R L 0.02 RS 0.15 I S 4.5 A
Total secondary resistance RT R I R L RS
1.17
Secondary voltage I S RT
4.5 1.17
5.265V
From Fig 5.7,
Exciting current IE for 5.265V
= 0.03A
Turns ratio N = 300/5 = 60
I p N (I S I E )
= 60(4.5 + 0.03)
= 271.8A
Voltage across meter I S R I
4.5 1 = 4.5V
IE 0.03
Ratio error 100 100
IS 4.5
= 0.67%
Rb
490
Lecture – 8
Examples
51. Design a CCVT for a 132kV transmission line using the following data.
Resistive Burden (3f )-150VA
Df 3Hz , phase angle error b = 40 min
Consider 4 choices of V2 as 33kV, 11kV, 6.6kV and 3.3kV
Diagram 1 Diagram 2
Transmission line voltage V = 132kV. Suppose V 2 (P_N) be the voltage to be
produced by the capacitive potential divider with capacitance values C1 and C2
and L the value of tuning inductor. The standardized VT secondary voltage is 110
volts (L-L).
Here specification for phase angle error b is 40 minutes variation in frequency
can be upto Df 3Hz . Phase angle error for change in w by Dw in the above
equation circuit, is given by
1
( L 2 )Dw
w C
1
At tuning frequency w 2
LC
Substituting w 1 LC
2
747.2 H
1 1
C1 C 2
w 2 L (3/ 4) 2 747.2
1.3610 -2 F
3) V2 6.6kV
3 �(6.6 �103 )2
Rb
'
150
87.1210 4
b �Rb' 0.01164 �87.12 �104
L
2 �Dw 2 �2p �3
269H ,
C1 C 2 3.7710 -2 F
4) V2 3.3kV
3 �(3.3 �103 ) 2
Rb'
150
21.7810 4
b �Rb' 0.01164 �21.78 �104
L
2 �Dw 2 �2p �3
67.25 H
C1 C2 0.151 F
The values of L, C1 C 2 for different values of V2 are tabulated below.
V2 L C1 C 2
33kV 6722.2H 0.00151 F
11kV 747.2H 0.0136 F
6.6kV 269H 0.0377 F
3.3kV 67.25H 0.151 F
From the above table it is clear that smaller the value of V 2, the smaller is the
value of L and higher the value of C 1 and C2 for tuning condition. If we select too low
value of V2 and L then capacitance values will be beyond available limits, and if we
select higher value of V2 and L, then CCVT and inductor will become bulky. So a
compromise is necessary and let us select V2 = 6.6kV
For V2 = 6.6kV
L = 269H
C1 C 2 0.0377 F
V C1 C 2
Now,
V2 C1
13210 3 0.037710 -6
36.610 3
C1
0.0377 36.610 3 10 -6 F
C1
13210 3
0.0033F
492
C 2 0.0344F
In this design, we explained the basic concept for CCVT design and we assumed
the transformer to be ideal. But in actual design practice the value of magnetizing
impedance of transformer, resistance of reactor etc have to be taken into account,
as ratio error a and phase angle error b will also get affected by these values.
52. Diagram
The equivalent circuit of a CCVT is shown in fig 8.3. The values of C 1 and C2 are
0.0018 F and 0.018 F respectively. Tuning inductor has an inductance of
497H and resistance of 4620 .
Xm of the 6.6kV VT is 1M , core loss = 20 watts per phase, VA burden =
150VA per phase. Value of Cm for compensating the current drawn by m is equal
to 3.18310 -9 F .
(xxx) Verify the appropriateness of choice of L and Cm.
Ans: If C1 0.0018F and C 2 0.0186F then the value L of tuning inductor
is given by
1
L 2
w (C1 C 2 )
where w 2p f and f = tuning frequency
1
L
(2p �50) (0.0018 0.0186) �10-6
2
1
Xm
w Cm
1 1
Cm
w X m (2p �50) �� 1 106
3.183 �10-9 F
The value is also same as the selected value of Cm Hence the selection of both L
and Cm is appropriate.
(zzz) If the frequency drops from 50Hz to 47Hz, what would be the values of
ratio error and phase angle error?
Ans: Core loss = 20w
V22
20W
Rm
493
V22 (6600) 2
Rm
20 20
2.18 �10
6
6600 0
A
260874.14 -2.44�
VT I th �Z
6600 0
�256147.5 1.82�
260874.14 -2.44�
6480.42 4.26�
(6600 - 6480.42)
Hence % ratio error �100
6600
=1.81%
Phase angle error = 4.26�
V2 6.6kV
r a w2 a 2
M
d 2i R di 1 1 R
t �t0 2
i0 wn 2p �50 2 Iwn
dt L dt LCeq LC L
d 2i
2
2a wn wn2i 0 a < 1
dt
Lec – 8
1
2p �50 2zw R d i 2zw w 2i 0 z wn z < 1
2
wn
LCeq n
L dt 2 n n
-t V
t I 0 - m sin(wt0 f - q ) f q
e | Z line |
495
Example 1:
d
496
Answer:
Based on the criteria that the CT can deliver 20 times rated secondary current
without exceeding a 10% ratio error, the maximum fault current will be 24000A.
However, with a 2.0Ω burden, this will result in a voltage below the knee point of the CT
and, as a practical matter, it will be within 10% accuracy at higher currents. This can only
be accurately determined from excitation or ratio correction curves and not from the
accuracy classification. For example, a CT with characteristics shown in above figure
will produce between 180-240A without exceeding the 10% ratio error, depending on the
power factor of the 2.0Ω burden.
Example 2:
A 1200/5, C400 CT is connected on the 1000/5 tap. What is the maximum secondary
burden that can be used and still maintain rated accuracy at 20 times rated symmetrical
secondary current?
Answer:
Since the secondary voltage capability is directly proportional to the connected tap, the
CT will support a voltage of 1000/1200 400V or 333V. Twenty times the rated
secondary current is 100A. Therefore, the maximum burden is 333V/100A or 3.33 Ω
Example 3:
Assume that secondary burden in a relay circuit is 5Ω. The relay setting is 2A and the CT
ratio is 300/5. Using above figure, calculate the primary current required to operate the
relay?
Answer:
497
N (I E I S )
= 300/5(0.04+2) A=122A
Example 4:
A relay is expected to operate for a 7000A primary current. The CT ratio is 600/5.
Secondary burden is 3.5 Ω. What is the error for the CT shown in above figure?
Answer:
The total secondary fault current is (7000/600) 5=58A. Assume that exciting current is
negligible.
VS I S ( R B RS )
= 58(3.5+0.31)
= 221V
The exciting current will not be negligible, however, and the calculation will not be
iterated.
Lec – 7
N1 RI 0 Vm N1 R Vm Vm N1 N1 RI 0 -tt N1 I 0 -tt
fdcmax t t N1 Rt v2 (t )
dc
e i2 e
N 22 | Z line | N 22 | Z line | | Z line | N 22 N2 N2
t -t -t
1 N1 RI 0 t N1 RI 0
f (t ) - f (0) t (1 - e ) f (t ) f (0) t (1 - e t )
N2 �
v2 dt 2 2
0
N 2 N 2
Lec- 7
498
Vm N1 d V2
v2ac (t ) R sin(wt f - q ) jw f ac
| Z line | N 2 dt jw N 2
RVm N1 p RVm N1
fac (t ) sin(wt f - q - ) facmax
w | Z line | N 2
2
2 w | Z line | N 22
Vm N1
Rt
RVm N1 N1 RVmt | Z line | N 22 wL X
facmax fdcmax 2 1 1 wt 1 line 1 line
w | Z line | N 2 N 2 | Z line |
2
Vm N1 R Rline Rline
| Z line | N 2 w
2
X
1
R
Lec-6
Lec – 5
Ip Ip
- IS Ip IE - IS
N - I I �100 N 98�45�
�100 N S E
IS �100
IS IS
Lec - 9
Vth - VT 1 1
�100 )Dw w02
(3f ) ( L w02 1 LC < f Df �3Hz
Vth w02
LC
1t di dv di 1 d 2i
v(t ) Ri �
Ceq
-�
idt L
dt dt
R
dt Ceq
i L 2 w0
dt
d 1 1 1
DVL - DVC jI (w L - ) Dw I (2 2 )Dw w02 I ( L L )Dw
dw wCeq w0 Ceq LCeq
499
| VL - VC | 2 LI Dw 2 LI 2 LDw
j 2 LI Dw (DVL - DVC ) tan b 2 2 2 � 2p f Lm 106
| VR | a Rb I a Rb a Rb
106
Lm 3183.1H
2p
source. The fault strikes at time t t 0 . This can be simulated by closing the switch at t t1
500
R jwL or Z q models the line impedance. The fault current in the line is given by
i (t ) 0 0 t t0
t -t 0
V sin(w t f - q ) -
t
t t0
i (t ) m I 0e
|Z |
Where τ is the time constant of the line τ =L/R. The fault current has two components in
it. The first component models the steady state sinusoidal ac response while the second current
is the dc offset current due to the presence of inductive component in the circuit. Recall that
current in an inductance can not change instantaneously. As t ∞, the instantaneous dc
It is more or less obvious that, dc offset is not seen in the waveform after 5 time constants.
The value of I0 can be worked out by setting the current at t t o to zero.
This implies that
Vm
I0 - sin(wt 0 - q )
Z
501
Thus
t -t 0
Vm V -( )
i (t ) sin(wt f - q ) - m sin(wt f - q )e t
Z Z
fig.2
It can be seen that severity of dc offset component in fault current is maximum when
a) f q
p
b) wt 0
2
502
p 1
For example, if angle of transmission line is 800, then with f = 800 & t 0 =
2 2p 50 200
V
sec = 5msec, the severity of dc offset current would equal I 0 Z , which is also the peak
m
We now plan to show that CT can saturate on dc offset current. Also, we plan to show
that the resulting distortions in the CT secondary current can be un-acceptably high. While
doing this analysis, we will neglect ac symmetrical component. In other words, we rest our
belief in superposition theorem atleast qualitatively and will finally evaluate effect using it
Notice that the current that we are dealing with is non-linear, a rigorous application of super
position theorem is simply out of question.
503
First consider an ideal CT excited by the dc offset current source. An ideal CT will faithfully
replicates primary current waveform on the secondary side. Hence, the secondary current
would be given by
-t
I0 t
i2 (t ) e
N
and the voltage developed across CT secondary would be given by
-t
RI N2
v 2 (t ) 0 e t where N N
N 1
For simplicity, let us assume that the initial flux in the transformer core at t=0 is zero
f ( 0 ) 0 ; Then we can compute the flux in the transformer core by using faraday’s law
df
V2 N 2 ---------(2)
dt
504
t
f (t ) - f (0) v 0
2 dt
RI 0
-t
t 1- e t
N2
-t
LI 0
(1 - e t )
N2
-t
LI 0
f (t ) f (0) (1 - e t )
N2
-t
LI 0
(1 - e t ) ------- (3)
N2
as a consequence of dc offset current,
Thus, flux in the core increases exponentially to a peak value of
f dmax
c
LI 0
N2
as t
L Vm Vm
N Z Z
f dmax
c
Note that unlike ac voltage induced flux, which is sinusoidal, this flux is unidirectional. The ac
voltage induced flux has zero average value. However, dc offset induced does not have this
nice feature. The total flux in ideal CT core is a summation of ac flux and dc flux.
d
The ac flux in the CT core can be obtained by substituting operator by jw . Hence
dt
If v2 (t ) Vm sin(wt f ) , then
Vm p
f ac sin(wt f - )
wN 2 2
The peak value of ac flux is given by
505
Vm
f acmax
wN 2
However Vm R2 I 0
max
R2 I 0max
Hence facmax
wN 2
and peak value of the total flux is given by
Vm LI 0max
facmax f dcmax
wN 2 N2
In practice, if this flux exceeds the knee-point flux in the core (see fig.), then the CT core
will saturate.
As a consequence of CT core saturation, the secondary current would not faithfully replicate
the primary current. Infact, in practice it is observed that CT secondary current is clipped. The
clipping of CT current leads to “blinding” of the relay which cannot function further. Hence,
CT saturation in presence of dc offset current is a serious problem which relay designers have
to face. Note that dc flux accumulates gradually. (Depends upon the transmission line time
constant ( t ). It is apparent that saturation should not occur immediately after the inception of
the fault. Thus, if the relay is fast enough in decision making, it is likely that a relaying
decision would be undertaken before the CT fully saturates. This is another important reason
for increasing the speed of relaying system. For bus-fault protection, where the dc saturation
due to dc offset current can be a significant contributing factor, quarter cycle operations *****
506
specifically are imposed. Similarly, a distance relay is expected to operate within ½-1 cycle
time.
CT oversizing factors
Typically, an efficient design of transformer would correspond to choosing the core cross
section such that f mac should be near the knee point of B-H curve. One obvious way of
avoiding the CT saturation on dc flux is to oversize the core so that for flux (f acmax f dcmax ) , the
(f acmax f dcmax )
corresponding B is below the knee-point. Hence, the factor is called core-
f acmax
oversizing factor.
f dcmax
Core-oversizing factor = 1
f acmax
LI o N 2
1
RI 0 wN 2
wL
1
R
X
1
R
Note that X/R in above equation is the transmission line X/R ratio. For a 220KV line X/R 10.
This would imply that transformer core should be oversized by a factor of 11. For a 400KV
line, typical value of X/R 20. This would imply an oversizing required of about 21 times the
usual design. Clearly this high amount of oversizing is not practical. Thus, the important
conclusion is that, protection engineers have to live with the saturation problem.
Cautions in CT selection:
While choosing a CT for a particular application, it is necessary to observe following
precautions.
105. The CT rating and continuous load current should match. For example, if max
load current is 90A, a 100:5 Ct may be acceptable but 50:5 is not acceptable.
507
106. The maximum fault current should be less than 20 times the CT rated current.
for example 100:5 CT can be used, so long as burden on the CT & maximum primary
fault current is below 2000A.
107. The voltage rating of CT should be compatible. For example, 100:5 C100 would
give linear response, upto 20 times rated current provided CT burden is kept
below(100/20*5=1 Ω). With 2 Ω burden, this CT can be used only if maximum current
is limited to 1000A.
108. Parallel of CT’s e.g. in differential protection, or with SLG fault can create
significant errors in CT performance. One should in general ascertain that magnetizing
current is kept much below the pick up value.
Following example, illustrates this point
Exercise problems:
If the current ratio is adequate for a protection, but CT burden is high; then the
performance of CT may deteriorate due to large magnetizing current and/or saturation problem.
The CT performance can be improved by connecting the CT’s in series.
53) Show the dotted terminals for correct secondary series connection
54) What is the VA of CT in fig (a) & (b) respectively?
79) Electromechanical relays tend to saturate at high currents. This reduces the relay burden
on CT, and so that the CT performance at moderately high currents may be considered
better than at relay’s rated burden at 5A.
80) Use of instantaneous over current relays has the potential to overcome this problem of
saturation of CT’s
508
81) Differential protection can operate on external faults due to the un equal saturation of
CT’s
Lecture-6
Examples
32. If a 300:5 class C CT is connected to a meter with resistance R I 1 and
secondary current in the CT is 4.5A find out the primary current voltage
developed across the meter and % rate error. Lead wire resistance R L 0.02
secondary resistance RS of a 300/5 CT 0.15
Diagram
R I 1 , R L 0.02 RS 0.15 I S 4.5 A
Total secondary resistance RT R I R L RS
1.17
Secondary voltage I S RT
4.5 1.17
5.265V
From Fig 5.7,
Exciting current IE for 5.265V
= 0.03A
Turns ratio N = 300/5 = 60
I p N (I S I E )
= 60(4.5 + 0.03)
= 271.8A
Voltage across meter I S R I
4.5 1 = 4.5V
IE 0.03
Ratio error 100 100
IS 4.5
= 0.67%
Rb
509
Lecture – 8
Examples
53. Design a CCVT for a 132kV transmission line using the following data.
Resistive Burden (3f )-150VA
Df 3Hz , phase angle error b = 40 min
Consider 4 choices of V2 as 33kV, 11kV, 6.6kV and 3.3kV
Diagram 1 Diagram 2
Transmission line voltage V = 132kV. Suppose V 2 (P_N) be the voltage to be
produced by the capacitive potential divider with capacitance values C1 and C2
and L the value of tuning inductor. The standardized VT secondary voltage is 110
volts (L-L).
Here specification for phase angle error b is 40 minutes variation in frequency
can be upto Df 3Hz . Phase angle error for change in w by Dw in the above
equation circuit, is given by
1
( L 2 )Dw
w C
1
At tuning frequency w 2
LC
Substituting w 1 LC
2
747.2 H
1 1
C1 C 2
w 2 L (3/ 4) 2 747.2
1.3610 -2 F
3) V2 6.6kV
3 �(6.6 �103 )2
Rb
'
150
87.1210 4
b �Rb' 0.01164 �87.12 �104
L
2 �Dw 2 �2p �3
269H ,
C1 C 2 3.7710 -2 F
4) V2 3.3kV
3 �(3.3 �103 ) 2
Rb'
150
21.7810 4
b �Rb' 0.01164 �21.78 �104
L
2 �Dw 2 �2p �3
67.25 H
C1 C2 0.151 F
The values of L, C1 C 2 for different values of V2 are tabulated below.
V2 L C1 C 2
33kV 6722.2H 0.00151 F
11kV 747.2H 0.0136 F
6.6kV 269H 0.0377 F
3.3kV 67.25H 0.151 F
From the above table it is clear that smaller the value of V 2, the smaller is the
value of L and higher the value of C 1 and C2 for tuning condition. If we select too low
value of V2 and L then capacitance values will be beyond available limits, and if we
select higher value of V2 and L, then CCVT and inductor will become bulky. So a
compromise is necessary and let us select V2 = 6.6kV
For V2 = 6.6kV
L = 269H
C1 C 2 0.0377 F
V C1 C 2
Now,
V2 C1
13210 3 0.037710 -6
36.610 3
C1
0.0377 36.610 3 10 -6 F
C1
13210 3
0.0033F
511
C 2 0.0344F
In this design, we explained the basic concept for CCVT design and we assumed
the transformer to be ideal. But in actual design practice the value of magnetizing
impedance of transformer, resistance of reactor etc have to be taken into account,
as ratio error a and phase angle error b will also get affected by these values.
54. Diagram
The equivalent circuit of a CCVT is shown in fig 8.3. The values of C 1 and C2 are
0.0018 F and 0.018 F respectively. Tuning inductor has an inductance of
497H and resistance of 4620 .
Xm of the 6.6kV VT is 1M , core loss = 20 watts per phase, VA burden =
150VA per phase. Value of Cm for compensating the current drawn by m is equal
to 3.18310 -9 F .
(aaaa) Verify the appropriateness of choice of L and Cm.
Ans: If C1 0.0018F and C 2 0.0186F then the value L of tuning inductor
is given by
1
L 2
w (C1 C 2 )
where w 2p f and f = tuning frequency
1
L
(2p �50) (0.0018 0.0186) �10-6
2
1
Xm
w Cm
1 1
Cm
w X m (2p �50) �� 1 106
3.183 �10-9 F
The value is also same as the selected value of Cm Hence the selection of both L
and Cm is appropriate.
(cccc) If the frequency drops from 50Hz to 47Hz, what would be the values of
ratio error and phase angle error?
Ans: Core loss = 20w
V22
20W
Rm
512
V22 (6600) 2
Rm
20 20
2.18 �10
6
6600 0
A
260874.14 -2.44�
VT I th �Z
6600 0
�256147.5 1.82�
260874.14 -2.44�
6480.42 4.26�
(6600 - 6480.42)
Hence % ratio error �100
6600
=1.81%
Phase angle error = 4.26�
V2 6.6kV
r a w2 a 2
M
d 2i R di 1 1 R
t �t0 2
i0 wn 2p �50 2 Iwn
dt L dt LCeq LC L
d 2i
2
2a wn wn2i 0 a < 1
dt
Lec – 8
1
2p �50 2zw R d i 2zw w 2i 0 z wn z < 1
2
wn
LCeq n
L dt 2 n n
-t V
t I 0 - m sin(wt0 f - q ) f q
e | Z line |
514
Example 1:
d
515
Answer:
Based on the criteria that the CT can deliver 20 times rated secondary current
without exceeding a 10% ratio error, the maximum fault current will be 24000A.
However, with a 2.0Ω burden, this will result in a voltage below the knee point of the CT
and, as a practical matter, it will be within 10% accuracy at higher currents. This can only
be accurately determined from excitation or ratio correction curves and not from the
accuracy classification. For example, a CT with characteristics shown in above figure
will produce between 180-240A without exceeding the 10% ratio error, depending on the
power factor of the 2.0Ω burden.
Example 2:
A 1200/5, C400 CT is connected on the 1000/5 tap. What is the maximum secondary
burden that can be used and still maintain rated accuracy at 20 times rated symmetrical
secondary current?
Answer:
Since the secondary voltage capability is directly proportional to the connected tap, the
CT will support a voltage of 1000/1200 400V or 333V. Twenty times the rated
secondary current is 100A. Therefore, the maximum burden is 333V/100A or 3.33 Ω
Example 3:
Assume that secondary burden in a relay circuit is 5Ω. The relay setting is 2A and the CT
ratio is 300/5. Using above figure, calculate the primary current required to operate the
relay?
Answer:
516
N (I E I S )
= 300/5(0.04+2) A=122A
Example 4:
A relay is expected to operate for a 7000A primary current. The CT ratio is 600/5.
Secondary burden is 3.5 Ω. What is the error for the CT shown in above figure?
Answer:
The total secondary fault current is (7000/600) 5=58A. Assume that exciting current is
negligible.
VS I S ( R B RS )
= 58(3.5+0.31)
= 221V
The exciting current will not be negligible, however, and the calculation will not be
iterated.
Lec – 7
N1 RI 0 Vm N1 R Vm Vm N1 N1 RI 0 -tt N1 I 0 -tt
fdcmax t t N1 Rt v2 (t )
dc
e i2 e
N 22 | Z line | N 22 | Z line | | Z line | N 22 N2 N2
t -t -t
1 N1 RI 0 t N1 RI 0
f (t ) - f (0) t (1 - e ) f (t ) f (0) t (1 - e t )
N2 �
v2 dt 2 2
0
N 2 N 2
Lec- 7
517
Vm N1 d V2
v2ac (t ) R sin(wt f - q ) jw f ac
| Z line | N 2 dt jw N 2
RVm N1 p RVm N1
fac (t ) sin(wt f - q - ) facmax
w | Z line | N 2
2
2 w | Z line | N 22
Vm N1
Rt
RVm N1 N1 RVmt | Z line | N 22 wL X
facmax fdcmax 2 1 1 wt 1 line 1 line
w | Z line | N 2 N 2 | Z line |
2
Vm N1 R Rline Rline
| Z line | N 2 w
2
X
1
R
Lec-6
Lec – 5
Ip Ip
- IS Ip IE - IS
N - I I �100 N 98�45�
�100 N S E
IS �100
IS IS
Lec - 9
Vth - VT 1 1
�100 )Dw w02
(3f ) ( L w02 1 LC < f Df �3Hz
Vth w02
LC
1t di dv di 1 d 2i
v(t ) Ri �
Ceq
-�
idt L
dt dt
R
dt Ceq
i L 2 w0
dt
d 1 1 1
DVL - DVC jI (w L - ) Dw I (2 2 )Dw w02 I ( L L )Dw
dw wCeq w0 Ceq LCeq
518
| VL - VC | 2 LI Dw 2 LI 2 LDw
j 2 LI Dw (DVL - DVC ) tan b 2 2 2 � 2p f Lm 106
| VR | a Rb I a Rb a Rb
106
Lm 3183.1H
2p
source. The fault strikes at time t t 0 . This can be simulated by closing the switch at t t1
519
R jwL or Z q models the line impedance. The fault current in the line is given by
i (t ) 0 0 t t0
t -t 0
V sin(w t f - q ) -
t
t t0
i (t ) m I 0e
|Z |
Where τ is the time constant of the line τ =L/R. The fault current has two components in
it. The first component models the steady state sinusoidal ac response while the second current
is the dc offset current due to the presence of inductive component in the circuit. Recall that
current in an inductance can not change instantaneously. As t ∞, the instantaneous dc
It is more or less obvious that, dc offset is not seen in the waveform after 5 time constants.
The value of I0 can be worked out by setting the current at t t o to zero.
This implies that
Vm
I0 - sin(wt 0 - q )
Z
520
Thus
t -t 0
Vm V -( )
i (t ) sin(wt f - q ) - m sin(wt f - q )e t
Z Z
fig.2
It can be seen that severity of dc offset component in fault current is maximum when
a) f q
p
b) wt 0
2
521
p 1
For example, if angle of transmission line is 800, then with f = 800 & t 0 =
2 2p 50 200
V
sec = 5msec, the severity of dc offset current would equal I 0 Z , which is also the peak
m
We now plan to show that CT can saturate on dc offset current. Also, we plan to show
that the resulting distortions in the CT secondary current can be un-acceptably high. While
doing this analysis, we will neglect ac symmetrical component. In other words, we rest our
belief in superposition theorem atleast qualitatively and will finally evaluate effect using it
Notice that the current that we are dealing with is non-linear, a rigorous application of super
position theorem is simply out of question.
522
First consider an ideal CT excited by the dc offset current source. An ideal CT will faithfully
replicates primary current waveform on the secondary side. Hence, the secondary current
would be given by
-t
I0 t
i2 (t ) e
N
and the voltage developed across CT secondary would be given by
-t
RI N2
v 2 (t ) 0 e t where N N
N 1
For simplicity, let us assume that the initial flux in the transformer core at t=0 is zero
f ( 0 ) 0 ; Then we can compute the flux in the transformer core by using faraday’s law
df
V2 N 2 ---------(2)
dt
523
t
f (t ) - f (0) v 0
2 dt
RI 0
-t
t 1- e t
N2
-t
LI 0
(1 - e t )
N2
-t
LI 0
f (t ) f (0) (1 - e t )
N2
-t
LI 0
(1 - e t ) ------- (3)
N2
as a consequence of dc offset current,
Thus, flux in the core increases exponentially to a peak value of
f dmax
c
LI 0
N2
as t
L Vm Vm
N Z Z
f dmax
c
Note that unlike ac voltage induced flux, which is sinusoidal, this flux is unidirectional. The ac
voltage induced flux has zero average value. However, dc offset induced does not have this
nice feature. The total flux in ideal CT core is a summation of ac flux and dc flux.
d
The ac flux in the CT core can be obtained by substituting operator by jw . Hence
dt
If v2 (t ) Vm sin(wt f ) , then
Vm p
f ac sin(wt f - )
wN 2 2
The peak value of ac flux is given by
524
Vm
f acmax
wN 2
However Vm R2 I 0
max
R2 I 0max
Hence facmax
wN 2
and peak value of the total flux is given by
Vm LI 0max
facmax f dcmax
wN 2 N2
In practice, if this flux exceeds the knee-point flux in the core (see fig.), then the CT core
will saturate.
As a consequence of CT core saturation, the secondary current would not faithfully replicate
the primary current. Infact, in practice it is observed that CT secondary current is clipped. The
clipping of CT current leads to “blinding” of the relay which cannot function further. Hence,
CT saturation in presence of dc offset current is a serious problem which relay designers have
to face. Note that dc flux accumulates gradually. (Depends upon the transmission line time
constant ( t ). It is apparent that saturation should not occur immediately after the inception of
the fault. Thus, if the relay is fast enough in decision making, it is likely that a relaying
decision would be undertaken before the CT fully saturates. This is another important reason
for increasing the speed of relaying system. For bus-fault protection, where the dc saturation
due to dc offset current can be a significant contributing factor, quarter cycle operations *****
525
specifically are imposed. Similarly, a distance relay is expected to operate within ½-1 cycle
time.
CT oversizing factors
Typically, an efficient design of transformer would correspond to choosing the core cross
section such that f mac should be near the knee point of B-H curve. One obvious way of
avoiding the CT saturation on dc flux is to oversize the core so that for flux (f acmax f dcmax ) , the
(f acmax f dcmax )
corresponding B is below the knee-point. Hence, the factor is called core-
f acmax
oversizing factor.
f dcmax
Core-oversizing factor = 1
f acmax
LI o N 2
1
RI 0 wN 2
wL
1
R
X
1
R
Note that X/R in above equation is the transmission line X/R ratio. For a 220KV line X/R 10.
This would imply that transformer core should be oversized by a factor of 11. For a 400KV
line, typical value of X/R 20. This would imply an oversizing required of about 21 times the
usual design. Clearly this high amount of oversizing is not practical. Thus, the important
conclusion is that, protection engineers have to live with the saturation problem.
Cautions in CT selection:
While choosing a CT for a particular application, it is necessary to observe following
precautions.
109. The CT rating and continuous load current should match. For example, if max
load current is 90A, a 100:5 Ct may be acceptable but 50:5 is not acceptable.
526
110. The maximum fault current should be less than 20 times the CT rated current.
for example 100:5 CT can be used, so long as burden on the CT & maximum primary
fault current is below 2000A.
111. The voltage rating of CT should be compatible. For example, 100:5 C100 would
give linear response, upto 20 times rated current provided CT burden is kept
below(100/20*5=1 Ω). With 2 Ω burden, this CT can be used only if maximum current
is limited to 1000A.
112. Parallel of CT’s e.g. in differential protection, or with SLG fault can create
significant errors in CT performance. One should in general ascertain that magnetizing
current is kept much below the pick up value.
Following example, illustrates this point
Exercise problems:
If the current ratio is adequate for a protection, but CT burden is high; then the
performance of CT may deteriorate due to large magnetizing current and/or saturation problem.
The CT performance can be improved by connecting the CT’s in series.
55) Show the dotted terminals for correct secondary series connection
56) What is the VA of CT in fig (a) & (b) respectively?
82) Electromechanical relays tend to saturate at high currents. This reduces the relay burden
on CT, and so that the CT performance at moderately high currents may be considered
better than at relay’s rated burden at 5A.
83) Use of instantaneous over current relays has the potential to overcome this problem of
saturation of CT’s
527
84) Differential protection can operate on external faults due to the un equal saturation of
CT’s
Lecture-6
Examples
33. If a 300:5 class C CT is connected to a meter with resistance R I 1 and
secondary current in the CT is 4.5A find out the primary current voltage
developed across the meter and % rate error. Lead wire resistance R L 0.02
secondary resistance RS of a 300/5 CT 0.15
Diagram
R I 1 , R L 0.02 RS 0.15 I S 4.5 A
Total secondary resistance RT R I R L RS
1.17
Secondary voltage I S RT
4.5 1.17
5.265V
From Fig 5.7,
Exciting current IE for 5.265V
= 0.03A
Turns ratio N = 300/5 = 60
I p N (I S I E )
= 60(4.5 + 0.03)
= 271.8A
Voltage across meter I S R I
4.5 1 = 4.5V
IE 0.03
Ratio error 100 100
IS 4.5
= 0.67%
Rb
528
Lecture – 8
Examples
55. Design a CCVT for a 132kV transmission line using the following data.
Resistive Burden (3f )-150VA
Df 3Hz , phase angle error b = 40 min
Consider 4 choices of V2 as 33kV, 11kV, 6.6kV and 3.3kV
Diagram 1 Diagram 2
Transmission line voltage V = 132kV. Suppose V 2 (P_N) be the voltage to be
produced by the capacitive potential divider with capacitance values C1 and C2
and L the value of tuning inductor. The standardized VT secondary voltage is 110
volts (L-L).
Here specification for phase angle error b is 40 minutes variation in frequency
can be upto Df 3Hz . Phase angle error for change in w by Dw in the above
equation circuit, is given by
1
( L 2 )Dw
w C
1
At tuning frequency w 2
LC
Substituting w 1 LC
2
747.2 H
1 1
C1 C 2
w 2 L (3/ 4) 2 747.2
1.3610 -2 F
3) V2 6.6kV
3 �(6.6 �103 )2
Rb
'
150
87.1210 4
b �Rb' 0.01164 �87.12 �104
L
2 �Dw 2 �2p �3
269H ,
C1 C 2 3.7710 -2 F
4) V2 3.3kV
3 �(3.3 �103 ) 2
Rb'
150
21.7810 4
b �Rb' 0.01164 �21.78 �104
L
2 �Dw 2 �2p �3
67.25 H
C1 C2 0.151 F
The values of L, C1 C 2 for different values of V2 are tabulated below.
V2 L C1 C 2
33kV 6722.2H 0.00151 F
11kV 747.2H 0.0136 F
6.6kV 269H 0.0377 F
3.3kV 67.25H 0.151 F
From the above table it is clear that smaller the value of V 2, the smaller is the
value of L and higher the value of C 1 and C2 for tuning condition. If we select too low
value of V2 and L then capacitance values will be beyond available limits, and if we
select higher value of V2 and L, then CCVT and inductor will become bulky. So a
compromise is necessary and let us select V2 = 6.6kV
For V2 = 6.6kV
L = 269H
C1 C 2 0.0377 F
V C1 C 2
Now,
V2 C1
13210 3 0.037710 -6
36.610 3
C1
0.0377 36.610 3 10 -6 F
C1
13210 3
0.0033F
530
C 2 0.0344F
In this design, we explained the basic concept for CCVT design and we assumed
the transformer to be ideal. But in actual design practice the value of magnetizing
impedance of transformer, resistance of reactor etc have to be taken into account,
as ratio error a and phase angle error b will also get affected by these values.
56. Diagram
The equivalent circuit of a CCVT is shown in fig 8.3. The values of C 1 and C2 are
0.0018 F and 0.018 F respectively. Tuning inductor has an inductance of
497H and resistance of 4620 .
Xm of the 6.6kV VT is 1M , core loss = 20 watts per phase, VA burden =
150VA per phase. Value of Cm for compensating the current drawn by m is equal
to 3.18310 -9 F .
(dddd) Verify the appropriateness of choice of L and Cm.
Ans: If C1 0.0018F and C 2 0.0186F then the value L of tuning inductor
is given by
1
L 2
w (C1 C 2 )
where w 2p f and f = tuning frequency
1
L
(2p �50) (0.0018 0.0186) �10-6
2
1
Xm
w Cm
1 1
Cm
w X m (2p �50) �� 1 106
3.183 �10-9 F
The value is also same as the selected value of Cm Hence the selection of both L
and Cm is appropriate.
(ffff) If the frequency drops from 50Hz to 47Hz, what would be the values of
ratio error and phase angle error?
Ans: Core loss = 20w
V22
20W
Rm
531
V22 (6600) 2
Rm
20 20
2.18 �10
6
6600 0
A
260874.14 -2.44�
VT I th �Z
6600 0
�256147.5 1.82�
260874.14 -2.44�
6480.42 4.26�
(6600 - 6480.42)
Hence % ratio error �100
6600
=1.81%
Phase angle error = 4.26�
V2 6.6kV
r a w2 a 2
M
d 2i R di 1 1 R
t �t0 2
i0 wn 2p �50 2 Iwn
dt L dt LCeq LC L
d 2i
2
2a wn wn2i 0 a < 1
dt
Lec – 8
1
2p �50 2zw R d i 2zw w 2i 0 z wn z < 1
2
wn
LCeq n
L dt 2 n n
-t V
t I 0 - m sin(wt0 f - q ) f q
e | Z line |
533
Example 1:
d
534
Answer:
Based on the criteria that the CT can deliver 20 times rated secondary current
without exceeding a 10% ratio error, the maximum fault current will be 24000A.
However, with a 2.0Ω burden, this will result in a voltage below the knee point of the CT
and, as a practical matter, it will be within 10% accuracy at higher currents. This can only
be accurately determined from excitation or ratio correction curves and not from the
accuracy classification. For example, a CT with characteristics shown in above figure
will produce between 180-240A without exceeding the 10% ratio error, depending on the
power factor of the 2.0Ω burden.
Example 2:
A 1200/5, C400 CT is connected on the 1000/5 tap. What is the maximum secondary
burden that can be used and still maintain rated accuracy at 20 times rated symmetrical
secondary current?
Answer:
Since the secondary voltage capability is directly proportional to the connected tap, the
CT will support a voltage of 1000/1200 400V or 333V. Twenty times the rated
secondary current is 100A. Therefore, the maximum burden is 333V/100A or 3.33 Ω
Example 3:
Assume that secondary burden in a relay circuit is 5Ω. The relay setting is 2A and the CT
ratio is 300/5. Using above figure, calculate the primary current required to operate the
relay?
Answer:
535
N (I E I S )
= 300/5(0.04+2) A=122A
Example 4:
A relay is expected to operate for a 7000A primary current. The CT ratio is 600/5.
Secondary burden is 3.5 Ω. What is the error for the CT shown in above figure?
Answer:
The total secondary fault current is (7000/600) 5=58A. Assume that exciting current is
negligible.
VS I S ( R B RS )
= 58(3.5+0.31)
= 221V
The exciting current will not be negligible, however, and the calculation will not be
iterated.
Lec – 7
N1 RI 0 Vm N1 R Vm Vm N1 N1 RI 0 -tt N1 I 0 -tt
fdcmax t t N1 Rt v2 (t )
dc
e i2 e
N 22 | Z line | N 22 | Z line | | Z line | N 22 N2 N2
t -t -t
1 N1 RI 0 t N1 RI 0
f (t ) - f (0) t (1 - e ) f (t ) f (0) t (1 - e t )
N2 �
v2 dt 2 2
0
N 2 N 2
Lec- 7
536
Vm N1 d V2
v2ac (t ) R sin(wt f - q ) jw f ac
| Z line | N 2 dt jw N 2
RVm N1 p RVm N1
fac (t ) sin(wt f - q - ) facmax
w | Z line | N 2
2
2 w | Z line | N 22
Vm N1
Rt
RVm N1 N1 RVmt | Z line | N 22 wL X
facmax fdcmax 2 1 1 wt 1 line 1 line
w | Z line | N 2 N 2 | Z line |
2
Vm N1 R Rline Rline
| Z line | N 2 w
2
X
1
R
Lec-6
Lec – 5
Ip Ip
- IS Ip IE - IS
N - I I �100 N 98�45�
�100 N S E
IS �100
IS IS
Lec - 9
Vth - VT 1 1
�100 )Dw w02
(3f ) ( L w02 1 LC < f Df �3Hz
Vth w02
LC
1t di dv di 1 d 2i
v(t ) Ri �
Ceq
-�
idt L
dt dt
R
dt Ceq
i L 2 w0
dt
d 1 1 1
DVL - DVC jI (w L - ) Dw I (2 2 )Dw w02 I ( L L )Dw
dw wCeq w0 Ceq LCeq
537
| VL - VC | 2 LI Dw 2 LI 2 LDw
j 2 LI Dw (DVL - DVC ) tan b 2 2 2 � 2p f Lm 106
| VR | a Rb I a Rb a Rb
106
Lm 3183.1H
2p
source. The fault strikes at time t t 0 . This can be simulated by closing the switch at t t1
538
R jwL or Z q models the line impedance. The fault current in the line is given by
i (t ) 0 0 t t0
t -t 0
V sin(w t f - q ) -
t
t t0
i (t ) m I 0e
|Z |
Where τ is the time constant of the line τ =L/R. The fault current has two components in
it. The first component models the steady state sinusoidal ac response while the second current
is the dc offset current due to the presence of inductive component in the circuit. Recall that
current in an inductance can not change instantaneously. As t ∞, the instantaneous dc
It is more or less obvious that, dc offset is not seen in the waveform after 5 time constants.
The value of I0 can be worked out by setting the current at t t o to zero.
This implies that
Vm
I0 - sin(wt 0 - q )
Z
539
Thus
t -t 0
Vm V -( )
i (t ) sin(wt f - q ) - m sin(wt f - q )e t
Z Z
fig.2
It can be seen that severity of dc offset component in fault current is maximum when
a) f q
p
b) wt 0
2
540
p 1
For example, if angle of transmission line is 800, then with f = 800 & t 0 =
2 2p 50 200
V
sec = 5msec, the severity of dc offset current would equal I 0 Z , which is also the peak
m
We now plan to show that CT can saturate on dc offset current. Also, we plan to show
that the resulting distortions in the CT secondary current can be un-acceptably high. While
doing this analysis, we will neglect ac symmetrical component. In other words, we rest our
belief in superposition theorem atleast qualitatively and will finally evaluate effect using it
Notice that the current that we are dealing with is non-linear, a rigorous application of super
position theorem is simply out of question.
541
First consider an ideal CT excited by the dc offset current source. An ideal CT will faithfully
replicates primary current waveform on the secondary side. Hence, the secondary current
would be given by
-t
I0 t
i2 (t ) e
N
and the voltage developed across CT secondary would be given by
-t
RI N2
v 2 (t ) 0 e t where N N
N 1
For simplicity, let us assume that the initial flux in the transformer core at t=0 is zero
f ( 0 ) 0 ; Then we can compute the flux in the transformer core by using faraday’s law
df
V2 N 2 ---------(2)
dt
542
t
f (t ) - f (0) v 0
2 dt
RI 0
-t
t 1- e t
N2
-t
LI 0
(1 - e t )
N2
-t
LI 0
f (t ) f (0) (1 - e t )
N2
-t
LI 0
(1 - e t ) ------- (3)
N2
as a consequence of dc offset current,
Thus, flux in the core increases exponentially to a peak value of
f dmax
c
LI 0
N2
as t
L Vm Vm
N Z Z
f dmax
c
Note that unlike ac voltage induced flux, which is sinusoidal, this flux is unidirectional. The ac
voltage induced flux has zero average value. However, dc offset induced does not have this
nice feature. The total flux in ideal CT core is a summation of ac flux and dc flux.
d
The ac flux in the CT core can be obtained by substituting operator by jw . Hence
dt
If v2 (t ) Vm sin(wt f ) , then
Vm p
f ac sin(wt f - )
wN 2 2
The peak value of ac flux is given by
543
Vm
f acmax
wN 2
However Vm R2 I 0
max
R2 I 0max
Hence facmax
wN 2
and peak value of the total flux is given by
Vm LI 0max
facmax f dcmax
wN 2 N2
In practice, if this flux exceeds the knee-point flux in the core (see fig.), then the CT core
will saturate.
As a consequence of CT core saturation, the secondary current would not faithfully replicate
the primary current. Infact, in practice it is observed that CT secondary current is clipped. The
clipping of CT current leads to “blinding” of the relay which cannot function further. Hence,
CT saturation in presence of dc offset current is a serious problem which relay designers have
to face. Note that dc flux accumulates gradually. (Depends upon the transmission line time
constant ( t ). It is apparent that saturation should not occur immediately after the inception of
the fault. Thus, if the relay is fast enough in decision making, it is likely that a relaying
decision would be undertaken before the CT fully saturates. This is another important reason
for increasing the speed of relaying system. For bus-fault protection, where the dc saturation
due to dc offset current can be a significant contributing factor, quarter cycle operations *****
544
specifically are imposed. Similarly, a distance relay is expected to operate within ½-1 cycle
time.
CT oversizing factors
Typically, an efficient design of transformer would correspond to choosing the core cross
section such that f mac should be near the knee point of B-H curve. One obvious way of
avoiding the CT saturation on dc flux is to oversize the core so that for flux (f acmax f dcmax ) , the
(f acmax f dcmax )
corresponding B is below the knee-point. Hence, the factor is called core-
f acmax
oversizing factor.
f dcmax
Core-oversizing factor = 1
f acmax
LI o N 2
1
RI 0 wN 2
wL
1
R
X
1
R
Note that X/R in above equation is the transmission line X/R ratio. For a 220KV line X/R 10.
This would imply that transformer core should be oversized by a factor of 11. For a 400KV
line, typical value of X/R 20. This would imply an oversizing required of about 21 times the
usual design. Clearly this high amount of oversizing is not practical. Thus, the important
conclusion is that, protection engineers have to live with the saturation problem.
Cautions in CT selection:
While choosing a CT for a particular application, it is necessary to observe following
precautions.
113. The CT rating and continuous load current should match. For example, if max
load current is 90A, a 100:5 Ct may be acceptable but 50:5 is not acceptable.
545
114. The maximum fault current should be less than 20 times the CT rated current.
for example 100:5 CT can be used, so long as burden on the CT & maximum primary
fault current is below 2000A.
115. The voltage rating of CT should be compatible. For example, 100:5 C100 would
give linear response, upto 20 times rated current provided CT burden is kept
below(100/20*5=1 Ω). With 2 Ω burden, this CT can be used only if maximum current
is limited to 1000A.
116. Parallel of CT’s e.g. in differential protection, or with SLG fault can create
significant errors in CT performance. One should in general ascertain that magnetizing
current is kept much below the pick up value.
Following example, illustrates this point
Exercise problems:
If the current ratio is adequate for a protection, but CT burden is high; then the
performance of CT may deteriorate due to large magnetizing current and/or saturation problem.
The CT performance can be improved by connecting the CT’s in series.
57) Show the dotted terminals for correct secondary series connection
58) What is the VA of CT in fig (a) & (b) respectively?
85) Electromechanical relays tend to saturate at high currents. This reduces the relay burden
on CT, and so that the CT performance at moderately high currents may be considered
better than at relay’s rated burden at 5A.
86) Use of instantaneous over current relays has the potential to overcome this problem of
saturation of CT’s
546
87) Differential protection can operate on external faults due to the un equal saturation of
CT’s
Lecture-6
Examples
34. If a 300:5 class C CT is connected to a meter with resistance R I 1 and
secondary current in the CT is 4.5A find out the primary current voltage
developed across the meter and % rate error. Lead wire resistance R L 0.02
secondary resistance RS of a 300/5 CT 0.15
Diagram
R I 1 , R L 0.02 RS 0.15 I S 4.5 A
Total secondary resistance RT R I R L RS
1.17
Secondary voltage I S RT
4.5 1.17
5.265V
From Fig 5.7,
Exciting current IE for 5.265V
= 0.03A
Turns ratio N = 300/5 = 60
I p N (I S I E )
= 60(4.5 + 0.03)
= 271.8A
Voltage across meter I S R I
4.5 1 = 4.5V
IE 0.03
Ratio error 100 100
IS 4.5
= 0.67%
Rb
547
Lecture – 8
Examples
57. Design a CCVT for a 132kV transmission line using the following data.
Resistive Burden (3f )-150VA
Df 3Hz , phase angle error b = 40 min
Consider 4 choices of V2 as 33kV, 11kV, 6.6kV and 3.3kV
Diagram 1 Diagram 2
Transmission line voltage V = 132kV. Suppose V 2 (P_N) be the voltage to be
produced by the capacitive potential divider with capacitance values C1 and C2
and L the value of tuning inductor. The standardized VT secondary voltage is 110
volts (L-L).
Here specification for phase angle error b is 40 minutes variation in frequency
can be upto Df 3Hz . Phase angle error for change in w by Dw in the above
equation circuit, is given by
1
( L 2 )Dw
w C
1
At tuning frequency w 2
LC
Substituting w 1 LC
2
747.2 H
1 1
C1 C 2
w 2 L (3/ 4) 2 747.2
1.3610 -2 F
3) V2 6.6kV
3 �(6.6 �103 )2
Rb
'
150
87.1210 4
b �Rb' 0.01164 �87.12 �104
L
2 �Dw 2 �2p �3
269H ,
C1 C 2 3.7710 -2 F
4) V2 3.3kV
3 �(3.3 �103 ) 2
Rb'
150
21.7810 4
b �Rb' 0.01164 �21.78 �104
L
2 �Dw 2 �2p �3
67.25 H
C1 C2 0.151 F
The values of L, C1 C 2 for different values of V2 are tabulated below.
V2 L C1 C 2
33kV 6722.2H 0.00151 F
11kV 747.2H 0.0136 F
6.6kV 269H 0.0377 F
3.3kV 67.25H 0.151 F
From the above table it is clear that smaller the value of V 2, the smaller is the
value of L and higher the value of C 1 and C2 for tuning condition. If we select too low
value of V2 and L then capacitance values will be beyond available limits, and if we
select higher value of V2 and L, then CCVT and inductor will become bulky. So a
compromise is necessary and let us select V2 = 6.6kV
For V2 = 6.6kV
L = 269H
C1 C 2 0.0377 F
V C1 C 2
Now,
V2 C1
13210 3 0.037710 -6
36.610 3
C1
0.0377 36.610 3 10 -6 F
C1
13210 3
0.0033F
549
C 2 0.0344F
In this design, we explained the basic concept for CCVT design and we assumed
the transformer to be ideal. But in actual design practice the value of magnetizing
impedance of transformer, resistance of reactor etc have to be taken into account,
as ratio error a and phase angle error b will also get affected by these values.
58. Diagram
The equivalent circuit of a CCVT is shown in fig 8.3. The values of C 1 and C2 are
0.0018 F and 0.018 F respectively. Tuning inductor has an inductance of
497H and resistance of 4620 .
Xm of the 6.6kV VT is 1M , core loss = 20 watts per phase, VA burden =
150VA per phase. Value of Cm for compensating the current drawn by m is equal
to 3.18310 -9 F .
(gggg) Verify the appropriateness of choice of L and Cm.
Ans: If C1 0.0018F and C 2 0.0186F then the value L of tuning inductor
is given by
1
L 2
w (C1 C 2 )
where w 2p f and f = tuning frequency
1
L
(2p �50) (0.0018 0.0186) �10-6
2
1
Xm
w Cm
1 1
Cm
w X m (2p �50) �� 1 106
3.183 �10-9 F
The value is also same as the selected value of Cm Hence the selection of both L
and Cm is appropriate.
(iiii) If the frequency drops from 50Hz to 47Hz, what would be the values of
ratio error and phase angle error?
Ans: Core loss = 20w
V22
20W
Rm
550
V22 (6600) 2
Rm
20 20
2.18 �10
6
6600 0
A
260874.14 -2.44�
VT I th �Z
6600 0
�256147.5 1.82�
260874.14 -2.44�
6480.42 4.26�
(6600 - 6480.42)
Hence % ratio error �100
6600
=1.81%
Phase angle error = 4.26�
V2 6.6kV
r a w2 a 2
M
d 2i R di 1 1 R
t �t0 2
i0 wn 2p �50 2 Iwn
dt L dt LCeq LC L
d 2i
2
2a wn wn2i 0 a < 1
dt
Lec – 8
1
2p �50 2zw R d i 2zw w 2i 0 z wn z < 1
2
wn
LCeq n
L dt 2 n n
-t V
t I 0 - m sin(wt0 f - q ) f q
e | Z line |
552
Example 1:
d
553
Answer:
Based on the criteria that the CT can deliver 20 times rated secondary current
without exceeding a 10% ratio error, the maximum fault current will be 24000A.
However, with a 2.0Ω burden, this will result in a voltage below the knee point of the CT
and, as a practical matter, it will be within 10% accuracy at higher currents. This can only
be accurately determined from excitation or ratio correction curves and not from the
accuracy classification. For example, a CT with characteristics shown in above figure
will produce between 180-240A without exceeding the 10% ratio error, depending on the
power factor of the 2.0Ω burden.
Example 2:
A 1200/5, C400 CT is connected on the 1000/5 tap. What is the maximum secondary
burden that can be used and still maintain rated accuracy at 20 times rated symmetrical
secondary current?
Answer:
Since the secondary voltage capability is directly proportional to the connected tap, the
CT will support a voltage of 1000/1200 400V or 333V. Twenty times the rated
secondary current is 100A. Therefore, the maximum burden is 333V/100A or 3.33 Ω
Example 3:
Assume that secondary burden in a relay circuit is 5Ω. The relay setting is 2A and the CT
ratio is 300/5. Using above figure, calculate the primary current required to operate the
relay?
Answer:
554
N (I E I S )
= 300/5(0.04+2) A=122A
Example 4:
A relay is expected to operate for a 7000A primary current. The CT ratio is 600/5.
Secondary burden is 3.5 Ω. What is the error for the CT shown in above figure?
Answer:
The total secondary fault current is (7000/600) 5=58A. Assume that exciting current is
negligible.
VS I S ( R B RS )
= 58(3.5+0.31)
= 221V
The exciting current will not be negligible, however, and the calculation will not be
iterated.
Lec – 7
N1 RI 0 Vm N1 R Vm Vm N1 N1 RI 0 -tt N1 I 0 -tt
fdcmax t t N1 Rt v2 (t )
dc
e i2 e
N 22 | Z line | N 22 | Z line | | Z line | N 22 N2 N2
t -t -t
1 N1 RI 0 t N1 RI 0
f (t ) - f (0) t (1 - e ) f (t ) f (0) t (1 - e t )
N2 �
v2 dt 2 2
0
N 2 N 2
Lec- 7
555
Vm N1 d V2
v2ac (t ) R sin(wt f - q ) jw f ac
| Z line | N 2 dt jw N 2
RVm N1 p RVm N1
fac (t ) sin(wt f - q - ) facmax
w | Z line | N 2
2
2 w | Z line | N 22
Vm N1
Rt
RVm N1 N1 RVmt | Z line | N 22 wL X
facmax fdcmax 2 1 1 wt 1 line 1 line
w | Z line | N 2 N 2 | Z line |
2
Vm N1 R Rline Rline
| Z line | N 2 w
2
X
1
R
Lec-6
Lec – 5
Ip Ip
- IS Ip IE - IS
N - I I �100 N 98�45�
�100 N S E
IS �100
IS IS
Lec - 9
Vth - VT 1 1
�100 )Dw w02
(3f ) ( L w02 1 LC < f Df �3Hz
Vth w02
LC
1t di dv di 1 d 2i
v(t ) Ri �
Ceq
-�
idt L
dt dt
R
dt Ceq
i L 2 w0
dt
d 1 1 1
DVL - DVC jI (w L - ) Dw I (2 2 )Dw w02 I ( L L )Dw
dw wCeq w0 Ceq LCeq
556
| VL - VC | 2 LI Dw 2 LI 2 LDw
j 2 LI Dw (DVL - DVC ) tan b 2 2 2 � 2p f Lm 106
| VR | a Rb I a Rb a Rb
106
Lm 3183.1H
2p
source. The fault strikes at time t t 0 . This can be simulated by closing the switch at t t1
557
R jwL or Z q models the line impedance. The fault current in the line is given by
i (t ) 0 0 t t0
t -t 0
V sin(w t f - q ) -
t
t t0
i (t ) m I 0e
|Z |
Where τ is the time constant of the line τ =L/R. The fault current has two components in
it. The first component models the steady state sinusoidal ac response while the second current
is the dc offset current due to the presence of inductive component in the circuit. Recall that
current in an inductance can not change instantaneously. As t ∞, the instantaneous dc
It is more or less obvious that, dc offset is not seen in the waveform after 5 time constants.
The value of I0 can be worked out by setting the current at t t o to zero.
This implies that
Vm
I0 - sin(wt 0 - q )
Z
558
Thus
t -t 0
Vm V -( )
i (t ) sin(wt f - q ) - m sin(wt f - q )e t
Z Z
fig.2
It can be seen that severity of dc offset component in fault current is maximum when
a) f q
p
b) wt 0
2
559
p 1
For example, if angle of transmission line is 800, then with f = 800 & t 0 =
2 2p 50 200
V
sec = 5msec, the severity of dc offset current would equal I 0 Z , which is also the peak
m
We now plan to show that CT can saturate on dc offset current. Also, we plan to show
that the resulting distortions in the CT secondary current can be un-acceptably high. While
doing this analysis, we will neglect ac symmetrical component. In other words, we rest our
belief in superposition theorem atleast qualitatively and will finally evaluate effect using it
Notice that the current that we are dealing with is non-linear, a rigorous application of super
position theorem is simply out of question.
560
First consider an ideal CT excited by the dc offset current source. An ideal CT will faithfully
replicates primary current waveform on the secondary side. Hence, the secondary current
would be given by
-t
I0 t
i2 (t ) e
N
and the voltage developed across CT secondary would be given by
-t
RI N2
v 2 (t ) 0 e t where N N
N 1
For simplicity, let us assume that the initial flux in the transformer core at t=0 is zero
f ( 0 ) 0 ; Then we can compute the flux in the transformer core by using faraday’s law
df
V2 N 2 ---------(2)
dt
561
t
f (t ) - f (0) v 0
2 dt
RI 0
-t
t 1- e t
N2
-t
LI 0
(1 - e t )
N2
-t
LI 0
f (t ) f (0) (1 - e t )
N2
-t
LI 0
(1 - e t ) ------- (3)
N2
as a consequence of dc offset current,
Thus, flux in the core increases exponentially to a peak value of
f dmax
c
LI 0
N2
as t
L Vm Vm
N Z Z
f dmax
c
Note that unlike ac voltage induced flux, which is sinusoidal, this flux is unidirectional. The ac
voltage induced flux has zero average value. However, dc offset induced does not have this
nice feature. The total flux in ideal CT core is a summation of ac flux and dc flux.
d
The ac flux in the CT core can be obtained by substituting operator by jw . Hence
dt
If v2 (t ) Vm sin(wt f ) , then
Vm p
f ac sin(wt f - )
wN 2 2
The peak value of ac flux is given by
562
Vm
f acmax
wN 2
However Vm R2 I 0
max
R2 I 0max
Hence facmax
wN 2
and peak value of the total flux is given by
Vm LI 0max
facmax f dcmax
wN 2 N2
In practice, if this flux exceeds the knee-point flux in the core (see fig.), then the CT core
will saturate.
As a consequence of CT core saturation, the secondary current would not faithfully replicate
the primary current. Infact, in practice it is observed that CT secondary current is clipped. The
clipping of CT current leads to “blinding” of the relay which cannot function further. Hence,
CT saturation in presence of dc offset current is a serious problem which relay designers have
to face. Note that dc flux accumulates gradually. (Depends upon the transmission line time
constant ( t ). It is apparent that saturation should not occur immediately after the inception of
the fault. Thus, if the relay is fast enough in decision making, it is likely that a relaying
decision would be undertaken before the CT fully saturates. This is another important reason
for increasing the speed of relaying system. For bus-fault protection, where the dc saturation
due to dc offset current can be a significant contributing factor, quarter cycle operations *****
563
specifically are imposed. Similarly, a distance relay is expected to operate within ½-1 cycle
time.
CT oversizing factors
Typically, an efficient design of transformer would correspond to choosing the core cross
section such that f mac should be near the knee point of B-H curve. One obvious way of
avoiding the CT saturation on dc flux is to oversize the core so that for flux (f acmax f dcmax ) , the
(f acmax f dcmax )
corresponding B is below the knee-point. Hence, the factor is called core-
f acmax
oversizing factor.
f dcmax
Core-oversizing factor = 1
f acmax
LI o N 2
1
RI 0 wN 2
wL
1
R
X
1
R
Note that X/R in above equation is the transmission line X/R ratio. For a 220KV line X/R 10.
This would imply that transformer core should be oversized by a factor of 11. For a 400KV
line, typical value of X/R 20. This would imply an oversizing required of about 21 times the
usual design. Clearly this high amount of oversizing is not practical. Thus, the important
conclusion is that, protection engineers have to live with the saturation problem.
Cautions in CT selection:
While choosing a CT for a particular application, it is necessary to observe following
precautions.
117. The CT rating and continuous load current should match. For example, if max
load current is 90A, a 100:5 Ct may be acceptable but 50:5 is not acceptable.
564
118. The maximum fault current should be less than 20 times the CT rated current.
for example 100:5 CT can be used, so long as burden on the CT & maximum primary
fault current is below 2000A.
119. The voltage rating of CT should be compatible. For example, 100:5 C100 would
give linear response, upto 20 times rated current provided CT burden is kept
below(100/20*5=1 Ω). With 2 Ω burden, this CT can be used only if maximum current
is limited to 1000A.
120. Parallel of CT’s e.g. in differential protection, or with SLG fault can create
significant errors in CT performance. One should in general ascertain that magnetizing
current is kept much below the pick up value.
Following example, illustrates this point
Exercise problems:
If the current ratio is adequate for a protection, but CT burden is high; then the
performance of CT may deteriorate due to large magnetizing current and/or saturation problem.
The CT performance can be improved by connecting the CT’s in series.
59) Show the dotted terminals for correct secondary series connection
60) What is the VA of CT in fig (a) & (b) respectively?
88) Electromechanical relays tend to saturate at high currents. This reduces the relay burden
on CT, and so that the CT performance at moderately high currents may be considered
better than at relay’s rated burden at 5A.
89) Use of instantaneous over current relays has the potential to overcome this problem of
saturation of CT’s
565
90) Differential protection can operate on external faults due to the un equal saturation of
CT’s
Lecture-6
Examples
35. If a 300:5 class C CT is connected to a meter with resistance R I 1 and
secondary current in the CT is 4.5A find out the primary current voltage
developed across the meter and % rate error. Lead wire resistance R L 0.02
secondary resistance RS of a 300/5 CT 0.15
Diagram
R I 1 , R L 0.02 RS 0.15 I S 4.5 A
Total secondary resistance RT R I R L RS
1.17
Secondary voltage I S RT
4.5 1.17
5.265V
From Fig 5.7,
Exciting current IE for 5.265V
= 0.03A
Turns ratio N = 300/5 = 60
I p N (I S I E )
= 60(4.5 + 0.03)
= 271.8A
Voltage across meter I S R I
4.5 1 = 4.5V
IE 0.03
Ratio error 100 100
IS 4.5
= 0.67%
Rb
566
Lecture – 8
Examples
59. Design a CCVT for a 132kV transmission line using the following data.
Resistive Burden (3f )-150VA
Df 3Hz , phase angle error b = 40 min
Consider 4 choices of V2 as 33kV, 11kV, 6.6kV and 3.3kV
Diagram 1 Diagram 2
Transmission line voltage V = 132kV. Suppose V 2 (P_N) be the voltage to be
produced by the capacitive potential divider with capacitance values C1 and C2
and L the value of tuning inductor. The standardized VT secondary voltage is 110
volts (L-L).
Here specification for phase angle error b is 40 minutes variation in frequency
can be upto Df 3Hz . Phase angle error for change in w by Dw in the above
equation circuit, is given by
1
( L 2 )Dw
w C
1
At tuning frequency w 2
LC
Substituting w 1 LC
2
747.2 H
1 1
C1 C 2
w 2 L (3/ 4) 2 747.2
1.3610 -2 F
3) V2 6.6kV
3 �(6.6 �103 )2
Rb
'
150
87.1210 4
b �Rb' 0.01164 �87.12 �104
L
2 �Dw 2 �2p �3
269H ,
C1 C 2 3.7710 -2 F
4) V2 3.3kV
3 �(3.3 �103 ) 2
Rb'
150
21.7810 4
b �Rb' 0.01164 �21.78 �104
L
2 �Dw 2 �2p �3
67.25 H
C1 C2 0.151 F
The values of L, C1 C 2 for different values of V2 are tabulated below.
V2 L C1 C 2
33kV 6722.2H 0.00151 F
11kV 747.2H 0.0136 F
6.6kV 269H 0.0377 F
3.3kV 67.25H 0.151 F
From the above table it is clear that smaller the value of V 2, the smaller is the
value of L and higher the value of C 1 and C2 for tuning condition. If we select too low
value of V2 and L then capacitance values will be beyond available limits, and if we
select higher value of V2 and L, then CCVT and inductor will become bulky. So a
compromise is necessary and let us select V2 = 6.6kV
For V2 = 6.6kV
L = 269H
C1 C 2 0.0377 F
V C1 C 2
Now,
V2 C1
13210 3 0.037710 -6
36.610 3
C1
0.0377 36.610 3 10 -6 F
C1
13210 3
0.0033F
568
C 2 0.0344F
In this design, we explained the basic concept for CCVT design and we assumed
the transformer to be ideal. But in actual design practice the value of magnetizing
impedance of transformer, resistance of reactor etc have to be taken into account,
as ratio error a and phase angle error b will also get affected by these values.
60. Diagram
The equivalent circuit of a CCVT is shown in fig 8.3. The values of C 1 and C2 are
0.0018 F and 0.018 F respectively. Tuning inductor has an inductance of
497H and resistance of 4620 .
Xm of the 6.6kV VT is 1M , core loss = 20 watts per phase, VA burden =
150VA per phase. Value of Cm for compensating the current drawn by m is equal
to 3.18310 -9 F .
(jjjj) Verify the appropriateness of choice of L and Cm.
Ans: If C1 0.0018F and C 2 0.0186F then the value L of tuning inductor
is given by
1
L 2
w (C1 C 2 )
where w 2p f and f = tuning frequency
1
L
(2p �50) (0.0018 0.0186) �10-6
2
1
Xm
w Cm
1 1
Cm
w X m (2p �50) �� 1 106
3.183 �10-9 F
The value is also same as the selected value of Cm Hence the selection of both L
and Cm is appropriate.
(llll) If the frequency drops from 50Hz to 47Hz, what would be the values of
ratio error and phase angle error?
Ans: Core loss = 20w
V22
20W
Rm
569
V22 (6600) 2
Rm
20 20
2.18 �10
6
6600 0
A
260874.14 -2.44�
VT I th �Z
6600 0
�256147.5 1.82�
260874.14 -2.44�
6480.42 4.26�
(6600 - 6480.42)
Hence % ratio error �100
6600
=1.81%
Phase angle error = 4.26�
V2 6.6kV
r a w2 a 2
M
d 2i R di 1 1 R
t �t0 2
i0 wn 2p �50 2 Iwn
dt L dt LCeq LC L
d 2i
2
2a wn wn2i 0 a < 1
dt
Lec – 8
1
2p �50 2zw R d i 2zw w 2i 0 z wn z < 1
2
wn
LCeq n
L dt 2 n n
-t V
t I 0 - m sin(wt0 f - q ) f q
e | Z line |
571
Example 1:
d
572
Answer:
Based on the criteria that the CT can deliver 20 times rated secondary current
without exceeding a 10% ratio error, the maximum fault current will be 24000A.
However, with a 2.0Ω burden, this will result in a voltage below the knee point of the CT
and, as a practical matter, it will be within 10% accuracy at higher currents. This can only
be accurately determined from excitation or ratio correction curves and not from the
accuracy classification. For example, a CT with characteristics shown in above figure
will produce between 180-240A without exceeding the 10% ratio error, depending on the
power factor of the 2.0Ω burden.
Example 2:
A 1200/5, C400 CT is connected on the 1000/5 tap. What is the maximum secondary
burden that can be used and still maintain rated accuracy at 20 times rated symmetrical
secondary current?
Answer:
Since the secondary voltage capability is directly proportional to the connected tap, the
CT will support a voltage of 1000/1200 400V or 333V. Twenty times the rated
secondary current is 100A. Therefore, the maximum burden is 333V/100A or 3.33 Ω
Example 3:
Assume that secondary burden in a relay circuit is 5Ω. The relay setting is 2A and the CT
ratio is 300/5. Using above figure, calculate the primary current required to operate the
relay?
Answer:
573
N (I E I S )
= 300/5(0.04+2) A=122A
Example 4:
A relay is expected to operate for a 7000A primary current. The CT ratio is 600/5.
Secondary burden is 3.5 Ω. What is the error for the CT shown in above figure?
Answer:
The total secondary fault current is (7000/600) 5=58A. Assume that exciting current is
negligible.
VS I S ( R B RS )
= 58(3.5+0.31)
= 221V
The exciting current will not be negligible, however, and the calculation will not be
iterated.
Lec – 7
N1 RI 0 Vm N1 R Vm Vm N1 N1 RI 0 -tt N1 I 0 -tt
fdcmax t t N1 Rt v2 (t )
dc
e i2 e
N 22 | Z line | N 22 | Z line | | Z line | N 22 N2 N2
t -t -t
1 N1 RI 0 t N1 RI 0
f (t ) - f (0) t (1 - e ) f (t ) f (0) t (1 - e t )
N2 �
v2 dt 2 2
0
N 2 N 2
Lec- 7
574
Vm N1 d V2
v2ac (t ) R sin(wt f - q ) jw f ac
| Z line | N 2 dt jw N 2
RVm N1 p RVm N1
fac (t ) sin(wt f - q - ) facmax
w | Z line | N 2
2
2 w | Z line | N 22
Vm N1
Rt
RVm N1 N1 RVmt | Z line | N 22 wL X
facmax fdcmax 2 1 1 wt 1 line 1 line
w | Z line | N 2 N 2 | Z line |
2
Vm N1 R Rline Rline
| Z line | N 2 w
2
X
1
R
Lec-6
Lec – 5
Ip Ip
- IS Ip IE - IS
N - I I �100 N 98�45�
�100 N S E
IS �100
IS IS
Lec - 9
Vth - VT 1 1
�100 )Dw w02
(3f ) ( L w02 1 LC < f Df �3Hz
Vth w02
LC
1t di dv di 1 d 2i
v(t ) Ri �
Ceq
-�
idt L
dt dt
R
dt Ceq
i L 2 w0
dt
d 1 1 1
DVL - DVC jI (w L - ) Dw I (2 2 )Dw w02 I ( L L )Dw
dw wCeq w0 Ceq LCeq
575
| VL - VC | 2 LI Dw 2 LI 2 LDw
j 2 LI Dw (DVL - DVC ) tan b 2 2 2 � 2p f Lm 106
| VR | a Rb I a Rb a Rb
106
Lm 3183.1H
2p
source. The fault strikes at time t t 0 . This can be simulated by closing the switch at t t1
576
R jwL or Z q models the line impedance. The fault current in the line is given by
i (t ) 0 0 t t0
t -t 0
V sin(w t f - q ) -
t
t t0
i (t ) m I 0e
|Z |
Where τ is the time constant of the line τ =L/R. The fault current has two components in
it. The first component models the steady state sinusoidal ac response while the second current
is the dc offset current due to the presence of inductive component in the circuit. Recall that
current in an inductance can not change instantaneously. As t ∞, the instantaneous dc
It is more or less obvious that, dc offset is not seen in the waveform after 5 time constants.
The value of I0 can be worked out by setting the current at t t o to zero.
This implies that
Vm
I0 - sin(wt 0 - q )
Z
577
Thus
t -t 0
Vm V -( )
i (t ) sin(wt f - q ) - m sin(wt f - q )e t
Z Z
fig.2
It can be seen that severity of dc offset component in fault current is maximum when
a) f q
p
b) wt 0
2
578
p 1
For example, if angle of transmission line is 800, then with f = 800 & t 0 =
2 2p 50 200
V
sec = 5msec, the severity of dc offset current would equal I 0 Z , which is also the peak
m
We now plan to show that CT can saturate on dc offset current. Also, we plan to show
that the resulting distortions in the CT secondary current can be un-acceptably high. While
doing this analysis, we will neglect ac symmetrical component. In other words, we rest our
belief in superposition theorem atleast qualitatively and will finally evaluate effect using it
Notice that the current that we are dealing with is non-linear, a rigorous application of super
position theorem is simply out of question.
579
First consider an ideal CT excited by the dc offset current source. An ideal CT will faithfully
replicates primary current waveform on the secondary side. Hence, the secondary current
would be given by
-t
I0 t
i2 (t ) e
N
and the voltage developed across CT secondary would be given by
-t
RI N2
v 2 (t ) 0 e t where N N
N 1
For simplicity, let us assume that the initial flux in the transformer core at t=0 is zero
f ( 0 ) 0 ; Then we can compute the flux in the transformer core by using faraday’s law
df
V2 N 2 ---------(2)
dt
580
t
f (t ) - f (0) v 0
2 dt
RI 0
-t
t 1- e t
N2
-t
LI 0
(1 - e t )
N2
-t
LI 0
f (t ) f (0) (1 - e t )
N2
-t
LI 0
(1 - e t ) ------- (3)
N2
as a consequence of dc offset current,
Thus, flux in the core increases exponentially to a peak value of
f dmax
c
LI 0
N2
as t
L Vm Vm
N Z Z
f dmax
c
Note that unlike ac voltage induced flux, which is sinusoidal, this flux is unidirectional. The ac
voltage induced flux has zero average value. However, dc offset induced does not have this
nice feature. The total flux in ideal CT core is a summation of ac flux and dc flux.
d
The ac flux in the CT core can be obtained by substituting operator by jw . Hence
dt
If v2 (t ) Vm sin(wt f ) , then
Vm p
f ac sin(wt f - )
wN 2 2
The peak value of ac flux is given by
581
Vm
f acmax
wN 2
However Vm R2 I 0
max
R2 I 0max
Hence facmax
wN 2
and peak value of the total flux is given by
Vm LI 0max
facmax f dcmax
wN 2 N2
In practice, if this flux exceeds the knee-point flux in the core (see fig.), then the CT core
will saturate.
As a consequence of CT core saturation, the secondary current would not faithfully replicate
the primary current. Infact, in practice it is observed that CT secondary current is clipped. The
clipping of CT current leads to “blinding” of the relay which cannot function further. Hence,
CT saturation in presence of dc offset current is a serious problem which relay designers have
to face. Note that dc flux accumulates gradually. (Depends upon the transmission line time
constant ( t ). It is apparent that saturation should not occur immediately after the inception of
the fault. Thus, if the relay is fast enough in decision making, it is likely that a relaying
decision would be undertaken before the CT fully saturates. This is another important reason
for increasing the speed of relaying system. For bus-fault protection, where the dc saturation
due to dc offset current can be a significant contributing factor, quarter cycle operations *****
582
specifically are imposed. Similarly, a distance relay is expected to operate within ½-1 cycle
time.
CT oversizing factors
Typically, an efficient design of transformer would correspond to choosing the core cross
section such that f mac should be near the knee point of B-H curve. One obvious way of
avoiding the CT saturation on dc flux is to oversize the core so that for flux (f acmax f dcmax ) , the
(f acmax f dcmax )
corresponding B is below the knee-point. Hence, the factor is called core-
f acmax
oversizing factor.
f dcmax
Core-oversizing factor = 1
f acmax
LI o N 2
1
RI 0 wN 2
wL
1
R
X
1
R
Note that X/R in above equation is the transmission line X/R ratio. For a 220KV line X/R 10.
This would imply that transformer core should be oversized by a factor of 11. For a 400KV
line, typical value of X/R 20. This would imply an oversizing required of about 21 times the
usual design. Clearly this high amount of oversizing is not practical. Thus, the important
conclusion is that, protection engineers have to live with the saturation problem.
Cautions in CT selection:
While choosing a CT for a particular application, it is necessary to observe following
precautions.
121. The CT rating and continuous load current should match. For example, if max
load current is 90A, a 100:5 Ct may be acceptable but 50:5 is not acceptable.
583
122. The maximum fault current should be less than 20 times the CT rated current.
for example 100:5 CT can be used, so long as burden on the CT & maximum primary
fault current is below 2000A.
123. The voltage rating of CT should be compatible. For example, 100:5 C100 would
give linear response, upto 20 times rated current provided CT burden is kept
below(100/20*5=1 Ω). With 2 Ω burden, this CT can be used only if maximum current
is limited to 1000A.
124. Parallel of CT’s e.g. in differential protection, or with SLG fault can create
significant errors in CT performance. One should in general ascertain that magnetizing
current is kept much below the pick up value.
Following example, illustrates this point
Exercise problems:
If the current ratio is adequate for a protection, but CT burden is high; then the
performance of CT may deteriorate due to large magnetizing current and/or saturation problem.
The CT performance can be improved by connecting the CT’s in series.
61) Show the dotted terminals for correct secondary series connection
62) What is the VA of CT in fig (a) & (b) respectively?
91) Electromechanical relays tend to saturate at high currents. This reduces the relay burden
on CT, and so that the CT performance at moderately high currents may be considered
better than at relay’s rated burden at 5A.
92) Use of instantaneous over current relays has the potential to overcome this problem of
saturation of CT’s
584
93) Differential protection can operate on external faults due to the un equal saturation of
CT’s
Lecture-6
Examples
36. If a 300:5 class C CT is connected to a meter with resistance R I 1 and
secondary current in the CT is 4.5A find out the primary current voltage
developed across the meter and % rate error. Lead wire resistance R L 0.02
secondary resistance RS of a 300/5 CT 0.15
Diagram
R I 1 , R L 0.02 RS 0.15 I S 4.5 A
Total secondary resistance RT R I R L RS
1.17
Secondary voltage I S RT
4.5 1.17
5.265V
From Fig 5.7,
Exciting current IE for 5.265V
= 0.03A
Turns ratio N = 300/5 = 60
I p N (I S I E )
= 60(4.5 + 0.03)
= 271.8A
Voltage across meter I S R I
4.5 1 = 4.5V
IE 0.03
Ratio error 100 100
IS 4.5
= 0.67%
Rb
585
Lecture – 8
Examples
61. Design a CCVT for a 132kV transmission line using the following data.
Resistive Burden (3f )-150VA
Df 3Hz , phase angle error b = 40 min
Consider 4 choices of V2 as 33kV, 11kV, 6.6kV and 3.3kV
Diagram 1 Diagram 2
Transmission line voltage V = 132kV. Suppose V 2 (P_N) be the voltage to be
produced by the capacitive potential divider with capacitance values C1 and C2
and L the value of tuning inductor. The standardized VT secondary voltage is 110
volts (L-L).
Here specification for phase angle error b is 40 minutes variation in frequency
can be upto Df 3Hz . Phase angle error for change in w by Dw in the above
equation circuit, is given by
1
( L 2 )Dw
w C
1
At tuning frequency w 2
LC
Substituting w 1 LC
2
747.2 H
1 1
C1 C 2
w 2 L (3/ 4) 2 747.2
1.3610 -2 F
3) V2 6.6kV
3 �(6.6 �103 )2
Rb
'
150
87.1210 4
b �Rb' 0.01164 �87.12 �104
L
2 �Dw 2 �2p �3
269H ,
C1 C 2 3.7710 -2 F
4) V2 3.3kV
3 �(3.3 �103 ) 2
Rb'
150
21.7810 4
b �Rb' 0.01164 �21.78 �104
L
2 �Dw 2 �2p �3
67.25 H
C1 C2 0.151 F
The values of L, C1 C 2 for different values of V2 are tabulated below.
V2 L C1 C 2
33kV 6722.2H 0.00151 F
11kV 747.2H 0.0136 F
6.6kV 269H 0.0377 F
3.3kV 67.25H 0.151 F
From the above table it is clear that smaller the value of V 2, the smaller is the
value of L and higher the value of C 1 and C2 for tuning condition. If we select too low
value of V2 and L then capacitance values will be beyond available limits, and if we
select higher value of V2 and L, then CCVT and inductor will become bulky. So a
compromise is necessary and let us select V2 = 6.6kV
For V2 = 6.6kV
L = 269H
C1 C 2 0.0377 F
V C1 C 2
Now,
V2 C1
13210 3 0.037710 -6
36.610 3
C1
0.0377 36.610 3 10 -6 F
C1
13210 3
0.0033F
587
C 2 0.0344F
In this design, we explained the basic concept for CCVT design and we assumed
the transformer to be ideal. But in actual design practice the value of magnetizing
impedance of transformer, resistance of reactor etc have to be taken into account,
as ratio error a and phase angle error b will also get affected by these values.
62. Diagram
The equivalent circuit of a CCVT is shown in fig 8.3. The values of C 1 and C2 are
0.0018 F and 0.018 F respectively. Tuning inductor has an inductance of
497H and resistance of 4620 .
Xm of the 6.6kV VT is 1M , core loss = 20 watts per phase, VA burden =
150VA per phase. Value of Cm for compensating the current drawn by m is equal
to 3.18310 -9 F .
(mmmm) Verify the appropriateness of choice of L and Cm.
Ans: If C1 0.0018F and C 2 0.0186F then the value L of tuning inductor
is given by
1
L 2
w (C1 C 2 )
where w 2p f and f = tuning frequency
1
L
(2p �50) (0.0018 0.0186) �10-6
2
1
Xm
w Cm
1 1
Cm
w X m (2p �50) �� 1 106
3.183 �10-9 F
The value is also same as the selected value of Cm Hence the selection of both L
and Cm is appropriate.
(oooo) If the frequency drops from 50Hz to 47Hz, what would be the values of
ratio error and phase angle error?
Ans: Core loss = 20w
V22
20W
Rm
588
V22 (6600) 2
Rm
20 20
2.18 �10
6
6600 0
A
260874.14 -2.44�
VT I th �Z
6600 0
�256147.5 1.82�
260874.14 -2.44�
6480.42 4.26�
(6600 - 6480.42)
Hence % ratio error �100
6600
=1.81%
Phase angle error = 4.26�
V2 6.6kV
r a w2 a 2
M
d 2i R di 1 1 R
t �t0 2
i0 wn 2p �50 2 Iwn
dt L dt LCeq LC L
d 2i
2
2a wn wn2i 0 a < 1
dt
Lec – 8
1
2p �50 2zw R d i 2zw w 2i 0 z wn z < 1
2
wn
LCeq n
L dt 2 n n
-t V
t I 0 - m sin(wt0 f - q ) f q
e | Z line |
590
Example 1:
d
591
Answer:
Based on the criteria that the CT can deliver 20 times rated secondary current
without exceeding a 10% ratio error, the maximum fault current will be 24000A.
However, with a 2.0Ω burden, this will result in a voltage below the knee point of the CT
and, as a practical matter, it will be within 10% accuracy at higher currents. This can only
be accurately determined from excitation or ratio correction curves and not from the
accuracy classification. For example, a CT with characteristics shown in above figure
will produce between 180-240A without exceeding the 10% ratio error, depending on the
power factor of the 2.0Ω burden.
Example 2:
A 1200/5, C400 CT is connected on the 1000/5 tap. What is the maximum secondary
burden that can be used and still maintain rated accuracy at 20 times rated symmetrical
secondary current?
Answer:
Since the secondary voltage capability is directly proportional to the connected tap, the
CT will support a voltage of 1000/1200 400V or 333V. Twenty times the rated
secondary current is 100A. Therefore, the maximum burden is 333V/100A or 3.33 Ω
Example 3:
Assume that secondary burden in a relay circuit is 5Ω. The relay setting is 2A and the CT
ratio is 300/5. Using above figure, calculate the primary current required to operate the
relay?
Answer:
592
N (I E I S )
= 300/5(0.04+2) A=122A
Example 4:
A relay is expected to operate for a 7000A primary current. The CT ratio is 600/5.
Secondary burden is 3.5 Ω. What is the error for the CT shown in above figure?
Answer:
The total secondary fault current is (7000/600) 5=58A. Assume that exciting current is
negligible.
VS I S ( R B RS )
= 58(3.5+0.31)
= 221V
The exciting current will not be negligible, however, and the calculation will not be
iterated.
Lec – 7
N1 RI 0 Vm N1 R Vm Vm N1 N1 RI 0 -tt N1 I 0 -tt
fdcmax t t N1 Rt v2 (t )
dc
e i2 e
N 22 | Z line | N 22 | Z line | | Z line | N 22 N2 N2
t -t -t
1 N1 RI 0 t N1 RI 0
f (t ) - f (0) t (1 - e ) f (t ) f (0) t (1 - e t )
N2 �
v2 dt 2 2
0
N 2 N 2
Lec- 7
593
Vm N1 d V2
v2ac (t ) R sin(wt f - q ) jw f ac
| Z line | N 2 dt jw N 2
RVm N1 p RVm N1
fac (t ) sin(wt f - q - ) facmax
w | Z line | N 2
2
2 w | Z line | N 22
Vm N1
Rt
RVm N1 N1 RVmt | Z line | N 22 wL X
facmax fdcmax 2 1 1 wt 1 line 1 line
w | Z line | N 2 N 2 | Z line |
2
Vm N1 R Rline Rline
| Z line | N 2 w
2
X
1
R
Lec-6
Lec – 5
Ip Ip
- IS Ip IE - IS
N - I I �100 N 98�45�
�100 N S E
IS �100
IS IS
Lec - 9
Vth - VT 1 1
�100 )Dw w02
(3f ) ( L w02 1 LC < f Df �3Hz
Vth w02
LC
1t di dv di 1 d 2i
v(t ) Ri �
Ceq
-�
idt L
dt dt
R
dt Ceq
i L 2 w0
dt
d 1 1 1
DVL - DVC jI (w L - ) Dw I (2 2 )Dw w02 I ( L L )Dw
dw wCeq w0 Ceq LCeq
594
| VL - VC | 2 LI Dw 2 LI 2 LDw
j 2 LI Dw (DVL - DVC ) tan b 2 2 2 � 2p f Lm 106
| VR | a Rb I a Rb a Rb
106
Lm 3183.1H
2p
source. The fault strikes at time t t 0 . This can be simulated by closing the switch at t t1
595
R jwL or Z q models the line impedance. The fault current in the line is given by
i (t ) 0 0 t t0
t -t 0
V sin(w t f - q ) -
t
t t0
i (t ) m I 0e
|Z |
Where τ is the time constant of the line τ =L/R. The fault current has two components in
it. The first component models the steady state sinusoidal ac response while the second current
is the dc offset current due to the presence of inductive component in the circuit. Recall that
current in an inductance can not change instantaneously. As t ∞, the instantaneous dc
It is more or less obvious that, dc offset is not seen in the waveform after 5 time constants.
The value of I0 can be worked out by setting the current at t t o to zero.
This implies that
Vm
I0 - sin(wt 0 - q )
Z
596
Thus
t -t 0
Vm V -( )
i (t ) sin(wt f - q ) - m sin(wt f - q )e t
Z Z
fig.2
It can be seen that severity of dc offset component in fault current is maximum when
a) f q
p
b) wt 0
2
597
p 1
For example, if angle of transmission line is 800, then with f = 800 & t 0 =
2 2p 50 200
V
sec = 5msec, the severity of dc offset current would equal I 0 Z , which is also the peak
m
We now plan to show that CT can saturate on dc offset current. Also, we plan to show
that the resulting distortions in the CT secondary current can be un-acceptably high. While
doing this analysis, we will neglect ac symmetrical component. In other words, we rest our
belief in superposition theorem atleast qualitatively and will finally evaluate effect using it
Notice that the current that we are dealing with is non-linear, a rigorous application of super
position theorem is simply out of question.
598
First consider an ideal CT excited by the dc offset current source. An ideal CT will faithfully
replicates primary current waveform on the secondary side. Hence, the secondary current
would be given by
-t
I0 t
i2 (t ) e
N
and the voltage developed across CT secondary would be given by
-t
RI N2
v 2 (t ) 0 e t where N N
N 1
For simplicity, let us assume that the initial flux in the transformer core at t=0 is zero
f ( 0 ) 0 ; Then we can compute the flux in the transformer core by using faraday’s law
df
V2 N 2 ---------(2)
dt
599
t
f (t ) - f (0) v 0
2 dt
RI 0
-t
t 1- e t
N2
-t
LI 0
(1 - e t )
N2
-t
LI 0
f (t ) f (0) (1 - e t )
N2
-t
LI 0
(1 - e t ) ------- (3)
N2
as a consequence of dc offset current,
Thus, flux in the core increases exponentially to a peak value of
f dmax
c
LI 0
N2
as t
L Vm Vm
N Z Z
f dmax
c
Note that unlike ac voltage induced flux, which is sinusoidal, this flux is unidirectional. The ac
voltage induced flux has zero average value. However, dc offset induced does not have this
nice feature. The total flux in ideal CT core is a summation of ac flux and dc flux.
d
The ac flux in the CT core can be obtained by substituting operator by jw . Hence
dt
If v2 (t ) Vm sin(wt f ) , then
Vm p
f ac sin(wt f - )
wN 2 2
The peak value of ac flux is given by
600
Vm
f acmax
wN 2
However Vm R2 I 0
max
R2 I 0max
Hence facmax
wN 2
and peak value of the total flux is given by
Vm LI 0max
facmax f dcmax
wN 2 N2
In practice, if this flux exceeds the knee-point flux in the core (see fig.), then the CT core
will saturate.
As a consequence of CT core saturation, the secondary current would not faithfully replicate
the primary current. Infact, in practice it is observed that CT secondary current is clipped. The
clipping of CT current leads to “blinding” of the relay which cannot function further. Hence,
CT saturation in presence of dc offset current is a serious problem which relay designers have
to face. Note that dc flux accumulates gradually. (Depends upon the transmission line time
constant ( t ). It is apparent that saturation should not occur immediately after the inception of
the fault. Thus, if the relay is fast enough in decision making, it is likely that a relaying
decision would be undertaken before the CT fully saturates. This is another important reason
for increasing the speed of relaying system. For bus-fault protection, where the dc saturation
due to dc offset current can be a significant contributing factor, quarter cycle operations *****
601
specifically are imposed. Similarly, a distance relay is expected to operate within ½-1 cycle
time.
CT oversizing factors
Typically, an efficient design of transformer would correspond to choosing the core cross
section such that f mac should be near the knee point of B-H curve. One obvious way of
avoiding the CT saturation on dc flux is to oversize the core so that for flux (f acmax f dcmax ) , the
(f acmax f dcmax )
corresponding B is below the knee-point. Hence, the factor is called core-
f acmax
oversizing factor.
f dcmax
Core-oversizing factor = 1
f acmax
LI o N 2
1
RI 0 wN 2
wL
1
R
X
1
R
Note that X/R in above equation is the transmission line X/R ratio. For a 220KV line X/R 10.
This would imply that transformer core should be oversized by a factor of 11. For a 400KV
line, typical value of X/R 20. This would imply an oversizing required of about 21 times the
usual design. Clearly this high amount of oversizing is not practical. Thus, the important
conclusion is that, protection engineers have to live with the saturation problem.
Cautions in CT selection:
While choosing a CT for a particular application, it is necessary to observe following
precautions.
125. The CT rating and continuous load current should match. For example, if max
load current is 90A, a 100:5 Ct may be acceptable but 50:5 is not acceptable.
602
126. The maximum fault current should be less than 20 times the CT rated current.
for example 100:5 CT can be used, so long as burden on the CT & maximum primary
fault current is below 2000A.
127. The voltage rating of CT should be compatible. For example, 100:5 C100 would
give linear response, upto 20 times rated current provided CT burden is kept
below(100/20*5=1 Ω). With 2 Ω burden, this CT can be used only if maximum current
is limited to 1000A.
128. Parallel of CT’s e.g. in differential protection, or with SLG fault can create
significant errors in CT performance. One should in general ascertain that magnetizing
current is kept much below the pick up value.
Following example, illustrates this point
Exercise problems:
If the current ratio is adequate for a protection, but CT burden is high; then the
performance of CT may deteriorate due to large magnetizing current and/or saturation problem.
The CT performance can be improved by connecting the CT’s in series.
63) Show the dotted terminals for correct secondary series connection
64) What is the VA of CT in fig (a) & (b) respectively?
94) Electromechanical relays tend to saturate at high currents. This reduces the relay burden
on CT, and so that the CT performance at moderately high currents may be considered
better than at relay’s rated burden at 5A.
95) Use of instantaneous over current relays has the potential to overcome this problem of
saturation of CT’s
603
96) Differential protection can operate on external faults due to the un equal saturation of
CT’s
Lecture-6
Examples
37. If a 300:5 class C CT is connected to a meter with resistance R I 1 and
secondary current in the CT is 4.5A find out the primary current voltage
developed across the meter and % rate error. Lead wire resistance R L 0.02
secondary resistance RS of a 300/5 CT 0.15
Diagram
R I 1 , R L 0.02 RS 0.15 I S 4.5 A
Total secondary resistance RT R I R L RS
1.17
Secondary voltage I S RT
4.5 1.17
5.265V
From Fig 5.7,
Exciting current IE for 5.265V
= 0.03A
Turns ratio N = 300/5 = 60
I p N (I S I E )
= 60(4.5 + 0.03)
= 271.8A
Voltage across meter I S R I
4.5 1 = 4.5V
IE 0.03
Ratio error 100 100
IS 4.5
= 0.67%
Rb
604
Lecture – 8
Examples
63. Design a CCVT for a 132kV transmission line using the following data.
Resistive Burden (3f )-150VA
Df 3Hz , phase angle error b = 40 min
Consider 4 choices of V2 as 33kV, 11kV, 6.6kV and 3.3kV
Diagram 1 Diagram 2
Transmission line voltage V = 132kV. Suppose V 2 (P_N) be the voltage to be
produced by the capacitive potential divider with capacitance values C1 and C2
and L the value of tuning inductor. The standardized VT secondary voltage is 110
volts (L-L).
Here specification for phase angle error b is 40 minutes variation in frequency
can be upto Df 3Hz . Phase angle error for change in w by Dw in the above
equation circuit, is given by
1
( L 2 )Dw
w C
1
At tuning frequency w 2
LC
Substituting w 1 LC
2
747.2 H
1 1
C1 C 2
w 2 L (3/ 4) 2 747.2
1.3610 -2 F
3) V2 6.6kV
3 �(6.6 �103 )2
Rb
'
150
87.1210 4
b �Rb' 0.01164 �87.12 �104
L
2 �Dw 2 �2p �3
269H ,
C1 C 2 3.7710 -2 F
4) V2 3.3kV
3 �(3.3 �103 ) 2
Rb'
150
21.7810 4
b �Rb' 0.01164 �21.78 �104
L
2 �Dw 2 �2p �3
67.25 H
C1 C2 0.151 F
The values of L, C1 C 2 for different values of V2 are tabulated below.
V2 L C1 C 2
33kV 6722.2H 0.00151 F
11kV 747.2H 0.0136 F
6.6kV 269H 0.0377 F
3.3kV 67.25H 0.151 F
From the above table it is clear that smaller the value of V 2, the smaller is the
value of L and higher the value of C 1 and C2 for tuning condition. If we select too low
value of V2 and L then capacitance values will be beyond available limits, and if we
select higher value of V2 and L, then CCVT and inductor will become bulky. So a
compromise is necessary and let us select V2 = 6.6kV
For V2 = 6.6kV
L = 269H
C1 C 2 0.0377 F
V C1 C 2
Now,
V2 C1
13210 3 0.037710 -6
36.610 3
C1
0.0377 36.610 3 10 -6 F
C1
13210 3
0.0033F
606
C 2 0.0344F
In this design, we explained the basic concept for CCVT design and we assumed
the transformer to be ideal. But in actual design practice the value of magnetizing
impedance of transformer, resistance of reactor etc have to be taken into account,
as ratio error a and phase angle error b will also get affected by these values.
64. Diagram
The equivalent circuit of a CCVT is shown in fig 8.3. The values of C 1 and C2 are
0.0018 F and 0.018 F respectively. Tuning inductor has an inductance of
497H and resistance of 4620 .
Xm of the 6.6kV VT is 1M , core loss = 20 watts per phase, VA burden =
150VA per phase. Value of Cm for compensating the current drawn by m is equal
to 3.18310 -9 F .
(pppp) Verify the appropriateness of choice of L and Cm.
Ans: If C1 0.0018F and C 2 0.0186F then the value L of tuning inductor
is given by
1
L 2
w (C1 C 2 )
where w 2p f and f = tuning frequency
1
L
(2p �50) (0.0018 0.0186) �10-6
2
1
Xm
w Cm
1 1
Cm
w X m (2p �50) �� 1 106
3.183 �10-9 F
The value is also same as the selected value of Cm Hence the selection of both L
and Cm is appropriate.
(rrrr) If the frequency drops from 50Hz to 47Hz, what would be the values of
ratio error and phase angle error?
Ans: Core loss = 20w
V22
20W
Rm
607
V22 (6600) 2
Rm
20 20
2.18 �10
6
6600 0
A
260874.14 -2.44�
VT I th �Z
6600 0
�256147.5 1.82�
260874.14 -2.44�
6480.42 4.26�
(6600 - 6480.42)
Hence % ratio error �100
6600
=1.81%
Phase angle error = 4.26�
V2 6.6kV
r a w2 a 2
M
d 2i R di 1 1 R
t �t0 2
i0 wn 2p �50 2 Iwn
dt L dt LCeq LC L
d 2i
2
2a wn wn2i 0 a < 1
dt
Lec – 8
1
2p �50 2zw R d i 2zw w 2i 0 z wn z < 1
2
wn
LCeq n
L dt 2 n n
-t V
t I 0 - m sin(wt0 f - q ) f q
e | Z line |
609
Example 1:
d
610
Answer:
Based on the criteria that the CT can deliver 20 times rated secondary current
without exceeding a 10% ratio error, the maximum fault current will be 24000A.
However, with a 2.0Ω burden, this will result in a voltage below the knee point of the CT
and, as a practical matter, it will be within 10% accuracy at higher currents. This can only
be accurately determined from excitation or ratio correction curves and not from the
accuracy classification. For example, a CT with characteristics shown in above figure
will produce between 180-240A without exceeding the 10% ratio error, depending on the
power factor of the 2.0Ω burden.
Example 2:
A 1200/5, C400 CT is connected on the 1000/5 tap. What is the maximum secondary
burden that can be used and still maintain rated accuracy at 20 times rated symmetrical
secondary current?
Answer:
Since the secondary voltage capability is directly proportional to the connected tap, the
CT will support a voltage of 1000/1200 400V or 333V. Twenty times the rated
secondary current is 100A. Therefore, the maximum burden is 333V/100A or 3.33 Ω
Example 3:
Assume that secondary burden in a relay circuit is 5Ω. The relay setting is 2A and the CT
ratio is 300/5. Using above figure, calculate the primary current required to operate the
relay?
Answer:
611
N (I E I S )
= 300/5(0.04+2) A=122A
Example 4:
A relay is expected to operate for a 7000A primary current. The CT ratio is 600/5.
Secondary burden is 3.5 Ω. What is the error for the CT shown in above figure?
Answer:
The total secondary fault current is (7000/600) 5=58A. Assume that exciting current is
negligible.
VS I S ( R B RS )
= 58(3.5+0.31)
= 221V
The exciting current will not be negligible, however, and the calculation will not be
iterated.
Lec – 7
N1 RI 0 Vm N1 R Vm Vm N1 N1 RI 0 -tt N1 I 0 -tt
fdcmax t t N1 Rt v2 (t )
dc
e i2 e
N 22 | Z line | N 22 | Z line | | Z line | N 22 N2 N2
t -t -t
1 N1 RI 0 t N1 RI 0
f (t ) - f (0) t (1 - e ) f (t ) f (0) t (1 - e t )
N2 �
v2 dt 2 2
0
N 2 N 2
Lec- 7
612
Vm N1 d V2
v2ac (t ) R sin(wt f - q ) jw f ac
| Z line | N 2 dt jw N 2
RVm N1 p RVm N1
fac (t ) sin(wt f - q - ) facmax
w | Z line | N 2
2
2 w | Z line | N 22
Vm N1
Rt
RVm N1 N1 RVmt | Z line | N 22 wL X
facmax fdcmax 2 1 1 wt 1 line 1 line
w | Z line | N 2 N 2 | Z line |
2
Vm N1 R Rline Rline
| Z line | N 2 w
2
X
1
R
Lec-6
Lec – 5
Ip Ip
- IS Ip IE - IS
N - I I �100 N 98�45�
�100 N S E
IS �100
IS IS
Lec - 9
Vth - VT 1 1
�100 )Dw w02
(3f ) ( L w02 1 LC < f Df �3Hz
Vth w02
LC
1t di dv di 1 d 2i
v(t ) Ri �
Ceq
-�
idt L
dt dt
R
dt Ceq
i L 2 w0
dt
d 1 1 1
DVL - DVC jI (w L - ) Dw I (2 2 )Dw w02 I ( L L )Dw
dw wCeq w0 Ceq LCeq
613
| VL - VC | 2 LI Dw 2 LI 2 LDw
j 2 LI Dw (DVL - DVC ) tan b 2 2 2 � 2p f Lm 106
| VR | a Rb I a Rb a Rb
106
Lm 3183.1H
2p
source. The fault strikes at time t t 0 . This can be simulated by closing the switch at t t1
614
R jwL or Z q models the line impedance. The fault current in the line is given by
i (t ) 0 0 t t0
t -t 0
V sin(w t f - q ) -
t
t t0
i (t ) m I 0e
|Z |
Where τ is the time constant of the line τ =L/R. The fault current has two components in
it. The first component models the steady state sinusoidal ac response while the second current
is the dc offset current due to the presence of inductive component in the circuit. Recall that
current in an inductance can not change instantaneously. As t ∞, the instantaneous dc
It is more or less obvious that, dc offset is not seen in the waveform after 5 time constants.
The value of I0 can be worked out by setting the current at t t o to zero.
This implies that
Vm
I0 - sin(wt 0 - q )
Z
615
Thus
t -t 0
Vm V -( )
i (t ) sin(wt f - q ) - m sin(wt f - q )e t
Z Z
fig.2
It can be seen that severity of dc offset component in fault current is maximum when
a) f q
p
b) wt 0
2
616
p 1
For example, if angle of transmission line is 800, then with f = 800 & t 0 =
2 2p 50 200
V
sec = 5msec, the severity of dc offset current would equal I 0 Z , which is also the peak
m
We now plan to show that CT can saturate on dc offset current. Also, we plan to show
that the resulting distortions in the CT secondary current can be un-acceptably high. While
doing this analysis, we will neglect ac symmetrical component. In other words, we rest our
belief in superposition theorem atleast qualitatively and will finally evaluate effect using it
Notice that the current that we are dealing with is non-linear, a rigorous application of super
position theorem is simply out of question.
617
First consider an ideal CT excited by the dc offset current source. An ideal CT will faithfully
replicates primary current waveform on the secondary side. Hence, the secondary current
would be given by
-t
I0 t
i2 (t ) e
N
and the voltage developed across CT secondary would be given by
-t
RI N2
v 2 (t ) 0 e t where N N
N 1
For simplicity, let us assume that the initial flux in the transformer core at t=0 is zero
f ( 0 ) 0 ; Then we can compute the flux in the transformer core by using faraday’s law
df
V2 N 2 ---------(2)
dt
618
t
f (t ) - f (0) v 0
2 dt
RI 0
-t
t 1- e t
N2
-t
LI 0
(1 - e t )
N2
-t
LI 0
f (t ) f (0) (1 - e t )
N2
-t
LI 0
(1 - e t ) ------- (3)
N2
as a consequence of dc offset current,
Thus, flux in the core increases exponentially to a peak value of
f dmax
c
LI 0
N2
as t
L Vm Vm
N Z Z
f dmax
c
Note that unlike ac voltage induced flux, which is sinusoidal, this flux is unidirectional. The ac
voltage induced flux has zero average value. However, dc offset induced does not have this
nice feature. The total flux in ideal CT core is a summation of ac flux and dc flux.
d
The ac flux in the CT core can be obtained by substituting operator by jw . Hence
dt
If v2 (t ) Vm sin(wt f ) , then
Vm p
f ac sin(wt f - )
wN 2 2
The peak value of ac flux is given by
619
Vm
f acmax
wN 2
However Vm R2 I 0
max
R2 I 0max
Hence facmax
wN 2
and peak value of the total flux is given by
Vm LI 0max
facmax f dcmax
wN 2 N2
In practice, if this flux exceeds the knee-point flux in the core (see fig.), then the CT core
will saturate.
As a consequence of CT core saturation, the secondary current would not faithfully replicate
the primary current. Infact, in practice it is observed that CT secondary current is clipped. The
clipping of CT current leads to “blinding” of the relay which cannot function further. Hence,
CT saturation in presence of dc offset current is a serious problem which relay designers have
to face. Note that dc flux accumulates gradually. (Depends upon the transmission line time
constant ( t ). It is apparent that saturation should not occur immediately after the inception of
the fault. Thus, if the relay is fast enough in decision making, it is likely that a relaying
decision would be undertaken before the CT fully saturates. This is another important reason
for increasing the speed of relaying system. For bus-fault protection, where the dc saturation
due to dc offset current can be a significant contributing factor, quarter cycle operations *****
620
specifically are imposed. Similarly, a distance relay is expected to operate within ½-1 cycle
time.
CT oversizing factors
Typically, an efficient design of transformer would correspond to choosing the core cross
section such that f mac should be near the knee point of B-H curve. One obvious way of
avoiding the CT saturation on dc flux is to oversize the core so that for flux (f acmax f dcmax ) , the
(f acmax f dcmax )
corresponding B is below the knee-point. Hence, the factor is called core-
f acmax
oversizing factor.
f dcmax
Core-oversizing factor = 1
f acmax
LI o N 2
1
RI 0 wN 2
wL
1
R
X
1
R
Note that X/R in above equation is the transmission line X/R ratio. For a 220KV line X/R 10.
This would imply that transformer core should be oversized by a factor of 11. For a 400KV
line, typical value of X/R 20. This would imply an oversizing required of about 21 times the
usual design. Clearly this high amount of oversizing is not practical. Thus, the important
conclusion is that, protection engineers have to live with the saturation problem.
Cautions in CT selection:
While choosing a CT for a particular application, it is necessary to observe following
precautions.
129. The CT rating and continuous load current should match. For example, if max
load current is 90A, a 100:5 Ct may be acceptable but 50:5 is not acceptable.
621
130. The maximum fault current should be less than 20 times the CT rated current.
for example 100:5 CT can be used, so long as burden on the CT & maximum primary
fault current is below 2000A.
131. The voltage rating of CT should be compatible. For example, 100:5 C100 would
give linear response, upto 20 times rated current provided CT burden is kept
below(100/20*5=1 Ω). With 2 Ω burden, this CT can be used only if maximum current
is limited to 1000A.
132. Parallel of CT’s e.g. in differential protection, or with SLG fault can create
significant errors in CT performance. One should in general ascertain that magnetizing
current is kept much below the pick up value.
Following example, illustrates this point
Exercise problems:
If the current ratio is adequate for a protection, but CT burden is high; then the
performance of CT may deteriorate due to large magnetizing current and/or saturation problem.
The CT performance can be improved by connecting the CT’s in series.
65) Show the dotted terminals for correct secondary series connection
66) What is the VA of CT in fig (a) & (b) respectively?
97) Electromechanical relays tend to saturate at high currents. This reduces the relay burden
on CT, and so that the CT performance at moderately high currents may be considered
better than at relay’s rated burden at 5A.
98) Use of instantaneous over current relays has the potential to overcome this problem of
saturation of CT’s
622
99) Differential protection can operate on external faults due to the un equal saturation of
CT’s
Lecture-6
Examples
38. If a 300:5 class C CT is connected to a meter with resistance R I 1 and
secondary current in the CT is 4.5A find out the primary current voltage
developed across the meter and % rate error. Lead wire resistance R L 0.02
secondary resistance RS of a 300/5 CT 0.15
Diagram
R I 1 , R L 0.02 RS 0.15 I S 4.5 A
Total secondary resistance RT R I R L RS
1.17
Secondary voltage I S RT
4.5 1.17
5.265V
From Fig 5.7,
Exciting current IE for 5.265V
= 0.03A
Turns ratio N = 300/5 = 60
I p N (I S I E )
= 60(4.5 + 0.03)
= 271.8A
Voltage across meter I S R I
4.5 1 = 4.5V
IE 0.03
Ratio error 100 100
IS 4.5
= 0.67%
Rb
623
Lecture – 8
Examples
65. Design a CCVT for a 132kV transmission line using the following data.
Resistive Burden (3f )-150VA
Df 3Hz , phase angle error b = 40 min
Consider 4 choices of V2 as 33kV, 11kV, 6.6kV and 3.3kV
Diagram 1 Diagram 2
Transmission line voltage V = 132kV. Suppose V 2 (P_N) be the voltage to be
produced by the capacitive potential divider with capacitance values C1 and C2
and L the value of tuning inductor. The standardized VT secondary voltage is 110
volts (L-L).
Here specification for phase angle error b is 40 minutes variation in frequency
can be upto Df 3Hz . Phase angle error for change in w by Dw in the above
equation circuit, is given by
1
( L 2 )Dw
w C
1
At tuning frequency w 2
LC
Substituting w 1 LC
2
747.2 H
1 1
C1 C 2
w 2 L (3/ 4) 2 747.2
1.3610 -2 F
3) V2 6.6kV
3 �(6.6 �103 )2
Rb
'
150
87.1210 4
b �Rb' 0.01164 �87.12 �104
L
2 �Dw 2 �2p �3
269H ,
C1 C 2 3.7710 -2 F
4) V2 3.3kV
3 �(3.3 �103 ) 2
Rb'
150
21.7810 4
b �Rb' 0.01164 �21.78 �104
L
2 �Dw 2 �2p �3
67.25 H
C1 C2 0.151 F
The values of L, C1 C 2 for different values of V2 are tabulated below.
V2 L C1 C 2
33kV 6722.2H 0.00151 F
11kV 747.2H 0.0136 F
6.6kV 269H 0.0377 F
3.3kV 67.25H 0.151 F
From the above table it is clear that smaller the value of V 2, the smaller is the
value of L and higher the value of C 1 and C2 for tuning condition. If we select too low
value of V2 and L then capacitance values will be beyond available limits, and if we
select higher value of V2 and L, then CCVT and inductor will become bulky. So a
compromise is necessary and let us select V2 = 6.6kV
For V2 = 6.6kV
L = 269H
C1 C 2 0.0377 F
V C1 C 2
Now,
V2 C1
13210 3 0.037710 -6
36.610 3
C1
0.0377 36.610 3 10 -6 F
C1
13210 3
0.0033F
625
C 2 0.0344F
In this design, we explained the basic concept for CCVT design and we assumed
the transformer to be ideal. But in actual design practice the value of magnetizing
impedance of transformer, resistance of reactor etc have to be taken into account,
as ratio error a and phase angle error b will also get affected by these values.
66. Diagram
The equivalent circuit of a CCVT is shown in fig 8.3. The values of C 1 and C2 are
0.0018 F and 0.018 F respectively. Tuning inductor has an inductance of
497H and resistance of 4620 .
Xm of the 6.6kV VT is 1M , core loss = 20 watts per phase, VA burden =
150VA per phase. Value of Cm for compensating the current drawn by m is equal
to 3.18310 -9 F .
(ssss) Verify the appropriateness of choice of L and Cm.
Ans: If C1 0.0018F and C 2 0.0186F then the value L of tuning inductor
is given by
1
L 2
w (C1 C 2 )
where w 2p f and f = tuning frequency
1
L
(2p �50) (0.0018 0.0186) �10-6
2
1
Xm
w Cm
1 1
Cm
w X m (2p �50) �� 1 106
3.183 �10-9 F
The value is also same as the selected value of Cm Hence the selection of both L
and Cm is appropriate.
(uuuu) If the frequency drops from 50Hz to 47Hz, what would be the values of
ratio error and phase angle error?
Ans: Core loss = 20w
V22
20W
Rm
626
V22 (6600) 2
Rm
20 20
2.18 �10
6
6600 0
A
260874.14 -2.44�
VT I th �Z
6600 0
�256147.5 1.82�
260874.14 -2.44�
6480.42 4.26�
(6600 - 6480.42)
Hence % ratio error �100
6600
=1.81%
Phase angle error = 4.26�
V2 6.6kV
r a w2 a 2
M
d 2i R di 1 1 R
t �t0 2
i0 wn 2p �50 2 Iwn
dt L dt LCeq LC L
d 2i
2
2a wn wn2i 0 a < 1
dt
Lec – 8
1
2p �50 2zw R d i 2zw w 2i 0 z wn z < 1
2
wn
LCeq n
L dt 2 n n
-t V
t I 0 - m sin(wt0 f - q ) f q
e | Z line |
628
Example 1:
d
629
Answer:
Based on the criteria that the CT can deliver 20 times rated secondary current
without exceeding a 10% ratio error, the maximum fault current will be 24000A.
However, with a 2.0Ω burden, this will result in a voltage below the knee point of the CT
and, as a practical matter, it will be within 10% accuracy at higher currents. This can only
be accurately determined from excitation or ratio correction curves and not from the
accuracy classification. For example, a CT with characteristics shown in above figure
will produce between 180-240A without exceeding the 10% ratio error, depending on the
power factor of the 2.0Ω burden.
Example 2:
A 1200/5, C400 CT is connected on the 1000/5 tap. What is the maximum secondary
burden that can be used and still maintain rated accuracy at 20 times rated symmetrical
secondary current?
Answer:
Since the secondary voltage capability is directly proportional to the connected tap, the
CT will support a voltage of 1000/1200 400V or 333V. Twenty times the rated
secondary current is 100A. Therefore, the maximum burden is 333V/100A or 3.33 Ω
Example 3:
Assume that secondary burden in a relay circuit is 5Ω. The relay setting is 2A and the CT
ratio is 300/5. Using above figure, calculate the primary current required to operate the
relay?
Answer:
630
N (I E I S )
= 300/5(0.04+2) A=122A
Example 4:
A relay is expected to operate for a 7000A primary current. The CT ratio is 600/5.
Secondary burden is 3.5 Ω. What is the error for the CT shown in above figure?
Answer:
The total secondary fault current is (7000/600) 5=58A. Assume that exciting current is
negligible.
VS I S ( R B RS )
= 58(3.5+0.31)
= 221V
The exciting current will not be negligible, however, and the calculation will not be
iterated.
Lec – 7
N1 RI 0 Vm N1 R Vm Vm N1 N1 RI 0 -tt N1 I 0 -tt
fdcmax t t N1 Rt v2 (t )
dc
e i2 e
N 22 | Z line | N 22 | Z line | | Z line | N 22 N2 N2
t -t -t
1 N1 RI 0 t N1 RI 0
f (t ) - f (0) t (1 - e ) f (t ) f (0) t (1 - e t )
N2 �
v2 dt 2 2
0
N 2 N 2
Lec- 7
631
Vm N1 d V2
v2ac (t ) R sin(wt f - q ) jw f ac
| Z line | N 2 dt jw N 2
RVm N1 p RVm N1
fac (t ) sin(wt f - q - ) facmax
w | Z line | N 2
2
2 w | Z line | N 22
Vm N1
Rt
RVm N1 N1 RVmt | Z line | N 22 wL X
facmax fdcmax 2 1 1 wt 1 line 1 line
w | Z line | N 2 N 2 | Z line |
2
Vm N1 R Rline Rline
| Z line | N 2 w
2
X
1
R
Lec-6
Lec – 5
Ip Ip
- IS Ip IE - IS
N - I I �100 N 98�45�
�100 N S E
IS �100
IS IS
Lec - 9
Vth - VT 1 1
�100 )Dw w02
(3f ) ( L w02 1 LC < f Df �3Hz
Vth w02
LC
1t di dv di 1 d 2i
v(t ) Ri �
Ceq
-�
idt L
dt dt
R
dt Ceq
i L 2 w0
dt
d 1 1 1
DVL - DVC jI (w L - ) Dw I (2 2 )Dw w02 I ( L L )Dw
dw wCeq w0 Ceq LCeq
632
| VL - VC | 2 LI Dw 2 LI 2 LDw
j 2 LI Dw (DVL - DVC ) tan b 2 2 2 � 2p f Lm 106
| VR | a Rb I a Rb a Rb
106
Lm 3183.1H
2p
source. The fault strikes at time t t 0 . This can be simulated by closing the switch at t t1
633
R jwL or Z q models the line impedance. The fault current in the line is given by
i (t ) 0 0 t t0
t -t 0
V sin(w t f - q ) -
t
t t0
i (t ) m I 0e
|Z |
Where τ is the time constant of the line τ =L/R. The fault current has two components in
it. The first component models the steady state sinusoidal ac response while the second current
is the dc offset current due to the presence of inductive component in the circuit. Recall that
current in an inductance can not change instantaneously. As t ∞, the instantaneous dc
It is more or less obvious that, dc offset is not seen in the waveform after 5 time constants.
The value of I0 can be worked out by setting the current at t t o to zero.
This implies that
Vm
I0 - sin(wt 0 - q )
Z
634
Thus
t -t 0
Vm V -( )
i (t ) sin(wt f - q ) - m sin(wt f - q )e t
Z Z
fig.2
It can be seen that severity of dc offset component in fault current is maximum when
a) f q
p
b) wt 0
2
635
p 1
For example, if angle of transmission line is 800, then with f = 800 & t 0 =
2 2p 50 200
V
sec = 5msec, the severity of dc offset current would equal I 0 Z , which is also the peak
m
We now plan to show that CT can saturate on dc offset current. Also, we plan to show
that the resulting distortions in the CT secondary current can be un-acceptably high. While
doing this analysis, we will neglect ac symmetrical component. In other words, we rest our
belief in superposition theorem atleast qualitatively and will finally evaluate effect using it
Notice that the current that we are dealing with is non-linear, a rigorous application of super
position theorem is simply out of question.
636
First consider an ideal CT excited by the dc offset current source. An ideal CT will faithfully
replicates primary current waveform on the secondary side. Hence, the secondary current
would be given by
-t
I0 t
i2 (t ) e
N
and the voltage developed across CT secondary would be given by
-t
RI N2
v 2 (t ) 0 e t where N N
N 1
For simplicity, let us assume that the initial flux in the transformer core at t=0 is zero
f ( 0 ) 0 ; Then we can compute the flux in the transformer core by using faraday’s law
df
V2 N 2 ---------(2)
dt
637
t
f (t ) - f (0) v 0
2 dt
RI 0
-t
t 1- e t
N2
-t
LI 0
(1 - e t )
N2
-t
LI 0
f (t ) f (0) (1 - e t )
N2
-t
LI 0
(1 - e t ) ------- (3)
N2
as a consequence of dc offset current,
Thus, flux in the core increases exponentially to a peak value of
f dmax
c
LI 0
N2
as t
L Vm Vm
N Z Z
f dmax
c
Note that unlike ac voltage induced flux, which is sinusoidal, this flux is unidirectional. The ac
voltage induced flux has zero average value. However, dc offset induced does not have this
nice feature. The total flux in ideal CT core is a summation of ac flux and dc flux.
d
The ac flux in the CT core can be obtained by substituting operator by jw . Hence
dt
If v2 (t ) Vm sin(wt f ) , then
Vm p
f ac sin(wt f - )
wN 2 2
The peak value of ac flux is given by
638
Vm
f acmax
wN 2
However Vm R2 I 0
max
R2 I 0max
Hence facmax
wN 2
and peak value of the total flux is given by
Vm LI 0max
facmax f dcmax
wN 2 N2
In practice, if this flux exceeds the knee-point flux in the core (see fig.), then the CT core
will saturate.
As a consequence of CT core saturation, the secondary current would not faithfully replicate
the primary current. Infact, in practice it is observed that CT secondary current is clipped. The
clipping of CT current leads to “blinding” of the relay which cannot function further. Hence,
CT saturation in presence of dc offset current is a serious problem which relay designers have
to face. Note that dc flux accumulates gradually. (Depends upon the transmission line time
constant ( t ). It is apparent that saturation should not occur immediately after the inception of
the fault. Thus, if the relay is fast enough in decision making, it is likely that a relaying
decision would be undertaken before the CT fully saturates. This is another important reason
for increasing the speed of relaying system. For bus-fault protection, where the dc saturation
due to dc offset current can be a significant contributing factor, quarter cycle operations *****
639
specifically are imposed. Similarly, a distance relay is expected to operate within ½-1 cycle
time.
CT oversizing factors
Typically, an efficient design of transformer would correspond to choosing the core cross
section such that f mac should be near the knee point of B-H curve. One obvious way of
avoiding the CT saturation on dc flux is to oversize the core so that for flux (f acmax f dcmax ) , the
(f acmax f dcmax )
corresponding B is below the knee-point. Hence, the factor is called core-
f acmax
oversizing factor.
f dcmax
Core-oversizing factor = 1
f acmax
LI o N 2
1
RI 0 wN 2
wL
1
R
X
1
R
Note that X/R in above equation is the transmission line X/R ratio. For a 220KV line X/R 10.
This would imply that transformer core should be oversized by a factor of 11. For a 400KV
line, typical value of X/R 20. This would imply an oversizing required of about 21 times the
usual design. Clearly this high amount of oversizing is not practical. Thus, the important
conclusion is that, protection engineers have to live with the saturation problem.
Cautions in CT selection:
While choosing a CT for a particular application, it is necessary to observe following
precautions.
133. The CT rating and continuous load current should match. For example, if max
load current is 90A, a 100:5 Ct may be acceptable but 50:5 is not acceptable.
640
134. The maximum fault current should be less than 20 times the CT rated current.
for example 100:5 CT can be used, so long as burden on the CT & maximum primary
fault current is below 2000A.
135. The voltage rating of CT should be compatible. For example, 100:5 C100 would
give linear response, upto 20 times rated current provided CT burden is kept
below(100/20*5=1 Ω). With 2 Ω burden, this CT can be used only if maximum current
is limited to 1000A.
136. Parallel of CT’s e.g. in differential protection, or with SLG fault can create
significant errors in CT performance. One should in general ascertain that magnetizing
current is kept much below the pick up value.
Following example, illustrates this point
Exercise problems:
If the current ratio is adequate for a protection, but CT burden is high; then the
performance of CT may deteriorate due to large magnetizing current and/or saturation problem.
The CT performance can be improved by connecting the CT’s in series.
67) Show the dotted terminals for correct secondary series connection
68) What is the VA of CT in fig (a) & (b) respectively?
100) Electromechanical relays tend to saturate at high currents. This reduces the relay
burden on CT, and so that the CT performance at moderately high currents may be
considered better than at relay’s rated burden at 5A.
101) Use of instantaneous over current relays has the potential to overcome this
problem of saturation of CT’s
641
102) Differential protection can operate on external faults due to the un equal
saturation of CT’s
Lecture-6
Examples
39. If a 300:5 class C CT is connected to a meter with resistance R I 1 and
secondary current in the CT is 4.5A find out the primary current voltage
developed across the meter and % rate error. Lead wire resistance R L 0.02
secondary resistance RS of a 300/5 CT 0.15
Diagram
R I 1 , R L 0.02 RS 0.15 I S 4.5 A
Total secondary resistance RT R I R L RS
1.17
Secondary voltage I S RT
4.5 1.17
5.265V
From Fig 5.7,
Exciting current IE for 5.265V
= 0.03A
Turns ratio N = 300/5 = 60
I p N (I S I E )
= 60(4.5 + 0.03)
= 271.8A
Voltage across meter I S R I
4.5 1 = 4.5V
IE 0.03
Ratio error 100 100
IS 4.5
= 0.67%
Rb
642
Lecture – 8
Examples
67. Design a CCVT for a 132kV transmission line using the following data.
Resistive Burden (3f )-150VA
Df 3Hz , phase angle error b = 40 min
Consider 4 choices of V2 as 33kV, 11kV, 6.6kV and 3.3kV
Diagram 1 Diagram 2
Transmission line voltage V = 132kV. Suppose V 2 (P_N) be the voltage to be
produced by the capacitive potential divider with capacitance values C1 and C2
and L the value of tuning inductor. The standardized VT secondary voltage is 110
volts (L-L).
Here specification for phase angle error b is 40 minutes variation in frequency
can be upto Df 3Hz . Phase angle error for change in w by Dw in the above
equation circuit, is given by
1
( L 2 )Dw
w C
1
At tuning frequency w 2
LC
Substituting w 1 LC
2
747.2 H
1 1
C1 C 2
w 2 L (3/ 4) 2 747.2
1.3610 -2 F
3) V2 6.6kV
3 �(6.6 �103 )2
Rb
'
150
87.1210 4
b �Rb' 0.01164 �87.12 �104
L
2 �Dw 2 �2p �3
269H ,
C1 C 2 3.7710 -2 F
4) V2 3.3kV
3 �(3.3 �103 ) 2
Rb'
150
21.7810 4
b �Rb' 0.01164 �21.78 �104
L
2 �Dw 2 �2p �3
67.25 H
C1 C2 0.151 F
The values of L, C1 C 2 for different values of V2 are tabulated below.
V2 L C1 C 2
33kV 6722.2H 0.00151 F
11kV 747.2H 0.0136 F
6.6kV 269H 0.0377 F
3.3kV 67.25H 0.151 F
From the above table it is clear that smaller the value of V 2, the smaller is the
value of L and higher the value of C 1 and C2 for tuning condition. If we select too low
value of V2 and L then capacitance values will be beyond available limits, and if we
select higher value of V2 and L, then CCVT and inductor will become bulky. So a
compromise is necessary and let us select V2 = 6.6kV
For V2 = 6.6kV
L = 269H
C1 C 2 0.0377 F
V C1 C 2
Now,
V2 C1
13210 3 0.037710 -6
36.610 3
C1
0.0377 36.610 3 10 -6 F
C1
13210 3
0.0033F
644
C 2 0.0344F
In this design, we explained the basic concept for CCVT design and we assumed
the transformer to be ideal. But in actual design practice the value of magnetizing
impedance of transformer, resistance of reactor etc have to be taken into account,
as ratio error a and phase angle error b will also get affected by these values.
68. Diagram
The equivalent circuit of a CCVT is shown in fig 8.3. The values of C 1 and C2 are
0.0018 F and 0.018 F respectively. Tuning inductor has an inductance of
497H and resistance of 4620 .
Xm of the 6.6kV VT is 1M , core loss = 20 watts per phase, VA burden =
150VA per phase. Value of Cm for compensating the current drawn by m is equal
to 3.18310 -9 F .
(vvvv) Verify the appropriateness of choice of L and Cm.
Ans: If C1 0.0018F and C 2 0.0186F then the value L of tuning inductor
is given by
1
L 2
w (C1 C 2 )
where w 2p f and f = tuning frequency
1
L
(2p �50) (0.0018 0.0186) �10-6
2
1
Xm
w Cm
1 1
Cm
w X m (2p �50) �� 1 106
3.183 �10-9 F
The value is also same as the selected value of Cm Hence the selection of both L
and Cm is appropriate.
(xxxx) If the frequency drops from 50Hz to 47Hz, what would be the values of
ratio error and phase angle error?
Ans: Core loss = 20w
V22
20W
Rm
645
V22 (6600) 2
Rm
20 20
2.18 �10
6
6600 0
A
260874.14 -2.44�
VT I th �Z
6600 0
�256147.5 1.82�
260874.14 -2.44�
6480.42 4.26�
(6600 - 6480.42)
Hence % ratio error �100
6600
=1.81%
Phase angle error = 4.26�
V2 6.6kV
r a w2 a 2
M
d 2i R di 1 1 R
t �t0 2
i0 wn 2p �50 2 Iwn
dt L dt LCeq LC L
d 2i
2
2a wn wn2i 0 a < 1
dt
Lec – 8
1
2p �50 2zw R d i 2zw w 2i 0 z wn z < 1
2
wn
LCeq n
L dt 2 n n
-t V
t I 0 - m sin(wt0 f - q ) f q
e | Z line |
647
Example 1:
d
648
Answer:
Based on the criteria that the CT can deliver 20 times rated secondary current
without exceeding a 10% ratio error, the maximum fault current will be 24000A.
However, with a 2.0Ω burden, this will result in a voltage below the knee point of the CT
and, as a practical matter, it will be within 10% accuracy at higher currents. This can only
be accurately determined from excitation or ratio correction curves and not from the
accuracy classification. For example, a CT with characteristics shown in above figure
will produce between 180-240A without exceeding the 10% ratio error, depending on the
power factor of the 2.0Ω burden.
Example 2:
A 1200/5, C400 CT is connected on the 1000/5 tap. What is the maximum secondary
burden that can be used and still maintain rated accuracy at 20 times rated symmetrical
secondary current?
Answer:
Since the secondary voltage capability is directly proportional to the connected tap, the
CT will support a voltage of 1000/1200 400V or 333V. Twenty times the rated
secondary current is 100A. Therefore, the maximum burden is 333V/100A or 3.33 Ω
Example 3:
Assume that secondary burden in a relay circuit is 5Ω. The relay setting is 2A and the CT
ratio is 300/5. Using above figure, calculate the primary current required to operate the
relay?
Answer:
649
N (I E I S )
= 300/5(0.04+2) A=122A
Example 4:
A relay is expected to operate for a 7000A primary current. The CT ratio is 600/5.
Secondary burden is 3.5 Ω. What is the error for the CT shown in above figure?
Answer:
The total secondary fault current is (7000/600) 5=58A. Assume that exciting current is
negligible.
VS I S ( R B RS )
= 58(3.5+0.31)
= 221V
The exciting current will not be negligible, however, and the calculation will not be
iterated.
Lec – 7
N1 RI 0 Vm N1 R Vm Vm N1 N1 RI 0 -tt N1 I 0 -tt
fdcmax t t N1 Rt v2 (t )
dc
e i2 e
N 22 | Z line | N 22 | Z line | | Z line | N 22 N2 N2
t -t -t
1 N1 RI 0 t N1 RI 0
f (t ) - f (0) t (1 - e ) f (t ) f (0) t (1 - e t )
N2 �
v2 dt 2 2
0
N 2 N 2
Lec- 7
650
Vm N1 d V2
v2ac (t ) R sin(wt f - q ) jw f ac
| Z line | N 2 dt jw N 2
RVm N1 p RVm N1
fac (t ) sin(wt f - q - ) facmax
w | Z line | N 2
2
2 w | Z line | N 22
Vm N1
Rt
RVm N1 N1 RVmt | Z line | N 22 wL X
facmax fdcmax 2 1 1 wt 1 line 1 line
w | Z line | N 2 N 2 | Z line |
2
Vm N1 R Rline Rline
| Z line | N 2 w
2
X
1
R
Lec-6
Lec – 5
Ip Ip
- IS Ip IE - IS
N - I I �100 N 98�45�
�100 N S E
IS �100
IS IS
Lec - 9
Vth - VT 1 1
�100 )Dw w02
(3f ) ( L w02 1 LC < f Df �3Hz
Vth w02
LC
1t di dv di 1 d 2i
v(t ) Ri �
Ceq
-�
idt L
dt dt
R
dt Ceq
i L 2 w0
dt
d 1 1 1
DVL - DVC jI (w L - ) Dw I (2 2 )Dw w02 I ( L L )Dw
dw wCeq w0 Ceq LCeq
651
| VL - VC | 2 LI Dw 2 LI 2 LDw
j 2 LI Dw (DVL - DVC ) tan b 2 2 2 � 2p f Lm 106
| VR | a Rb I a Rb a Rb
106
Lm 3183.1H
2p
source. The fault strikes at time t t 0 . This can be simulated by closing the switch at t t1
652
R jwL or Z q models the line impedance. The fault current in the line is given by
i (t ) 0 0 t t0
t -t 0
V sin(w t f - q ) -
t
t t0
i (t ) m I 0e
|Z |
Where τ is the time constant of the line τ =L/R. The fault current has two components in
it. The first component models the steady state sinusoidal ac response while the second current
is the dc offset current due to the presence of inductive component in the circuit. Recall that
current in an inductance can not change instantaneously. As t ∞, the instantaneous dc
It is more or less obvious that, dc offset is not seen in the waveform after 5 time constants.
The value of I0 can be worked out by setting the current at t t o to zero.
This implies that
Vm
I0 - sin(wt 0 - q )
Z
653
Thus
t -t 0
Vm V -( )
i (t ) sin(wt f - q ) - m sin(wt f - q )e t
Z Z
fig.2
It can be seen that severity of dc offset component in fault current is maximum when
a) f q
p
b) wt 0
2
654
p 1
For example, if angle of transmission line is 800, then with f = 800 & t 0 =
2 2p 50 200
V
sec = 5msec, the severity of dc offset current would equal I 0 Z , which is also the peak
m
We now plan to show that CT can saturate on dc offset current. Also, we plan to show
that the resulting distortions in the CT secondary current can be un-acceptably high. While
doing this analysis, we will neglect ac symmetrical component. In other words, we rest our
belief in superposition theorem atleast qualitatively and will finally evaluate effect using it
Notice that the current that we are dealing with is non-linear, a rigorous application of super
position theorem is simply out of question.
655
First consider an ideal CT excited by the dc offset current source. An ideal CT will faithfully
replicates primary current waveform on the secondary side. Hence, the secondary current
would be given by
-t
I0 t
i2 (t ) e
N
and the voltage developed across CT secondary would be given by
-t
RI N2
v 2 (t ) 0 e t where N N
N 1
For simplicity, let us assume that the initial flux in the transformer core at t=0 is zero
f ( 0 ) 0 ; Then we can compute the flux in the transformer core by using faraday’s law
df
V2 N 2 ---------(2)
dt
656
t
f (t ) - f (0) v 0
2 dt
RI 0
-t
t 1- e t
N2
-t
LI 0
(1 - e t )
N2
-t
LI 0
f (t ) f (0) (1 - e t )
N2
-t
LI 0
(1 - e t ) ------- (3)
N2
as a consequence of dc offset current,
Thus, flux in the core increases exponentially to a peak value of
f dmax
c
LI 0
N2
as t
L Vm Vm
N Z Z
f dmax
c
Note that unlike ac voltage induced flux, which is sinusoidal, this flux is unidirectional. The ac
voltage induced flux has zero average value. However, dc offset induced does not have this
nice feature. The total flux in ideal CT core is a summation of ac flux and dc flux.
d
The ac flux in the CT core can be obtained by substituting operator by jw . Hence
dt
If v2 (t ) Vm sin(wt f ) , then
Vm p
f ac sin(wt f - )
wN 2 2
The peak value of ac flux is given by
657
Vm
f acmax
wN 2
However Vm R2 I 0
max
R2 I 0max
Hence facmax
wN 2
and peak value of the total flux is given by
Vm LI 0max
facmax f dcmax
wN 2 N2
In practice, if this flux exceeds the knee-point flux in the core (see fig.), then the CT core
will saturate.
As a consequence of CT core saturation, the secondary current would not faithfully replicate
the primary current. Infact, in practice it is observed that CT secondary current is clipped. The
clipping of CT current leads to “blinding” of the relay which cannot function further. Hence,
CT saturation in presence of dc offset current is a serious problem which relay designers have
to face. Note that dc flux accumulates gradually. (Depends upon the transmission line time
constant ( t ). It is apparent that saturation should not occur immediately after the inception of
the fault. Thus, if the relay is fast enough in decision making, it is likely that a relaying
decision would be undertaken before the CT fully saturates. This is another important reason
for increasing the speed of relaying system. For bus-fault protection, where the dc saturation
due to dc offset current can be a significant contributing factor, quarter cycle operations *****
658
specifically are imposed. Similarly, a distance relay is expected to operate within ½-1 cycle
time.
CT oversizing factors
Typically, an efficient design of transformer would correspond to choosing the core cross
section such that f mac should be near the knee point of B-H curve. One obvious way of
avoiding the CT saturation on dc flux is to oversize the core so that for flux (f acmax f dcmax ) , the
(f acmax f dcmax )
corresponding B is below the knee-point. Hence, the factor is called core-
f acmax
oversizing factor.
f dcmax
Core-oversizing factor = 1
f acmax
LI o N 2
1
RI 0 wN 2
wL
1
R
X
1
R
Note that X/R in above equation is the transmission line X/R ratio. For a 220KV line X/R 10.
This would imply that transformer core should be oversized by a factor of 11. For a 400KV
line, typical value of X/R 20. This would imply an oversizing required of about 21 times the
usual design. Clearly this high amount of oversizing is not practical. Thus, the important
conclusion is that, protection engineers have to live with the saturation problem.
Cautions in CT selection:
While choosing a CT for a particular application, it is necessary to observe following
precautions.
137. The CT rating and continuous load current should match. For example, if max
load current is 90A, a 100:5 Ct may be acceptable but 50:5 is not acceptable.
659
138. The maximum fault current should be less than 20 times the CT rated current.
for example 100:5 CT can be used, so long as burden on the CT & maximum primary
fault current is below 2000A.
139. The voltage rating of CT should be compatible. For example, 100:5 C100 would
give linear response, upto 20 times rated current provided CT burden is kept
below(100/20*5=1 Ω). With 2 Ω burden, this CT can be used only if maximum current
is limited to 1000A.
140. Parallel of CT’s e.g. in differential protection, or with SLG fault can create
significant errors in CT performance. One should in general ascertain that magnetizing
current is kept much below the pick up value.
Following example, illustrates this point
Exercise problems:
If the current ratio is adequate for a protection, but CT burden is high; then the
performance of CT may deteriorate due to large magnetizing current and/or saturation problem.
The CT performance can be improved by connecting the CT’s in series.
69) Show the dotted terminals for correct secondary series connection
70) What is the VA of CT in fig (a) & (b) respectively?
103) Electromechanical relays tend to saturate at high currents. This reduces the relay
burden on CT, and so that the CT performance at moderately high currents may be
considered better than at relay’s rated burden at 5A.
104) Use of instantaneous over current relays has the potential to overcome this
problem of saturation of CT’s
660
105) Differential protection can operate on external faults due to the un equal
saturation of CT’s
Lecture-6
Examples
40. If a 300:5 class C CT is connected to a meter with resistance R I 1 and
secondary current in the CT is 4.5A find out the primary current voltage
developed across the meter and % rate error. Lead wire resistance R L 0.02
secondary resistance RS of a 300/5 CT 0.15
Diagram
R I 1 , R L 0.02 RS 0.15 I S 4.5 A
Total secondary resistance RT R I R L RS
1.17
Secondary voltage I S RT
4.5 1.17
5.265V
From Fig 5.7,
Exciting current IE for 5.265V
= 0.03A
Turns ratio N = 300/5 = 60
I p N (I S I E )
= 60(4.5 + 0.03)
= 271.8A
Voltage across meter I S R I
4.5 1 = 4.5V
IE 0.03
Ratio error 100 100
IS 4.5
= 0.67%
Rb
661
Lecture – 8
Examples
69. Design a CCVT for a 132kV transmission line using the following data.
Resistive Burden (3f )-150VA
Df 3Hz , phase angle error b = 40 min
Consider 4 choices of V2 as 33kV, 11kV, 6.6kV and 3.3kV
Diagram 1 Diagram 2
Transmission line voltage V = 132kV. Suppose V 2 (P_N) be the voltage to be
produced by the capacitive potential divider with capacitance values C1 and C2
and L the value of tuning inductor. The standardized VT secondary voltage is 110
volts (L-L).
Here specification for phase angle error b is 40 minutes variation in frequency
can be upto Df 3Hz . Phase angle error for change in w by Dw in the above
equation circuit, is given by
1
( L 2 )Dw
w C
1
At tuning frequency w 2
LC
Substituting w 1 LC
2
747.2 H
1 1
C1 C 2
w 2 L (3/ 4) 2 747.2
1.3610 -2 F
3) V2 6.6kV
3 �(6.6 �103 )2
Rb
'
150
87.1210 4
b �Rb' 0.01164 �87.12 �104
L
2 �Dw 2 �2p �3
269H ,
C1 C 2 3.7710 -2 F
4) V2 3.3kV
3 �(3.3 �103 ) 2
Rb'
150
21.7810 4
b �Rb' 0.01164 �21.78 �104
L
2 �Dw 2 �2p �3
67.25 H
C1 C2 0.151 F
The values of L, C1 C 2 for different values of V2 are tabulated below.
V2 L C1 C 2
33kV 6722.2H 0.00151 F
11kV 747.2H 0.0136 F
6.6kV 269H 0.0377 F
3.3kV 67.25H 0.151 F
From the above table it is clear that smaller the value of V 2, the smaller is the
value of L and higher the value of C 1 and C2 for tuning condition. If we select too low
value of V2 and L then capacitance values will be beyond available limits, and if we
select higher value of V2 and L, then CCVT and inductor will become bulky. So a
compromise is necessary and let us select V2 = 6.6kV
For V2 = 6.6kV
L = 269H
C1 C 2 0.0377 F
V C1 C 2
Now,
V2 C1
13210 3 0.037710 -6
36.610 3
C1
0.0377 36.610 3 10 -6 F
C1
13210 3
0.0033F
663
C 2 0.0344F
In this design, we explained the basic concept for CCVT design and we assumed
the transformer to be ideal. But in actual design practice the value of magnetizing
impedance of transformer, resistance of reactor etc have to be taken into account,
as ratio error a and phase angle error b will also get affected by these values.
70. Diagram
The equivalent circuit of a CCVT is shown in fig 8.3. The values of C 1 and C2 are
0.0018 F and 0.018 F respectively. Tuning inductor has an inductance of
497H and resistance of 4620 .
Xm of the 6.6kV VT is 1M , core loss = 20 watts per phase, VA burden =
150VA per phase. Value of Cm for compensating the current drawn by m is equal
to 3.18310 -9 F .
(yyyy) Verify the appropriateness of choice of L and Cm.
Ans: If C1 0.0018F and C 2 0.0186F then the value L of tuning inductor
is given by
1
L 2
w (C1 C 2 )
where w 2p f and f = tuning frequency
1
L
(2p �50) (0.0018 0.0186) �10-6
2
1
Xm
w Cm
1 1
Cm
w X m (2p �50) �� 1 106
3.183 �10-9 F
The value is also same as the selected value of Cm Hence the selection of both L
and Cm is appropriate.
(aaaaa) If the frequency drops from 50Hz to 47Hz, what would be the values of
ratio error and phase angle error?
Ans: Core loss = 20w
V22
20W
Rm
664
V22 (6600) 2
Rm
20 20
2.18 �10
6
6600 0
A
260874.14 -2.44�
VT I th �Z
6600 0
�256147.5 1.82�
260874.14 -2.44�
6480.42 4.26�
(6600 - 6480.42)
Hence % ratio error �100
6600
=1.81%
Phase angle error = 4.26�
V2 6.6kV
r a w2 a 2
M
d 2i R di 1 1 R
t �t0 2
i0 wn 2p �50 2 Iwn
dt L dt LCeq LC L
d 2i
2
2a wn wn2i 0 a < 1
dt
Lec – 8
1
2p �50 2zw R d i 2zw w 2i 0 z wn z < 1
2
wn
LCeq n
L dt 2 n n
-t V
t I 0 - m sin(wt0 f - q ) f q
e | Z line |
666
Example 1:
d
667
Answer:
Based on the criteria that the CT can deliver 20 times rated secondary current
without exceeding a 10% ratio error, the maximum fault current will be 24000A.
However, with a 2.0Ω burden, this will result in a voltage below the knee point of the CT
and, as a practical matter, it will be within 10% accuracy at higher currents. This can only
be accurately determined from excitation or ratio correction curves and not from the
accuracy classification. For example, a CT with characteristics shown in above figure
will produce between 180-240A without exceeding the 10% ratio error, depending on the
power factor of the 2.0Ω burden.
Example 2:
A 1200/5, C400 CT is connected on the 1000/5 tap. What is the maximum secondary
burden that can be used and still maintain rated accuracy at 20 times rated symmetrical
secondary current?
Answer:
Since the secondary voltage capability is directly proportional to the connected tap, the
CT will support a voltage of 1000/1200 400V or 333V. Twenty times the rated
secondary current is 100A. Therefore, the maximum burden is 333V/100A or 3.33 Ω
Example 3:
Assume that secondary burden in a relay circuit is 5Ω. The relay setting is 2A and the CT
ratio is 300/5. Using above figure, calculate the primary current required to operate the
relay?
Answer:
668
N (I E I S )
= 300/5(0.04+2) A=122A
Example 4:
A relay is expected to operate for a 7000A primary current. The CT ratio is 600/5.
Secondary burden is 3.5 Ω. What is the error for the CT shown in above figure?
Answer:
The total secondary fault current is (7000/600) 5=58A. Assume that exciting current is
negligible.
VS I S ( R B RS )
= 58(3.5+0.31)
= 221V
The exciting current will not be negligible, however, and the calculation will not be
iterated.
Lec – 7
N1 RI 0 Vm N1 R Vm Vm N1 N1 RI 0 -tt N1 I 0 -tt
fdcmax t t N1 Rt v2 (t )
dc
e i2 e
N 22 | Z line | N 22 | Z line | | Z line | N 22 N2 N2
t -t -t
1 N1 RI 0 t N1 RI 0
f (t ) - f (0) t (1 - e ) f (t ) f (0) t (1 - e t )
N2 �
v2 dt 2 2
0
N 2 N 2
Lec- 7
669
Vm N1 d V2
v2ac (t ) R sin(wt f - q ) jw f ac
| Z line | N 2 dt jw N 2
RVm N1 p RVm N1
fac (t ) sin(wt f - q - ) facmax
w | Z line | N 2
2
2 w | Z line | N 22
Vm N1
Rt
RVm N1 N1 RVmt | Z line | N 22 wL X
facmax fdcmax 2 1 1 wt 1 line 1 line
w | Z line | N 2 N 2 | Z line |
2
Vm N1 R Rline Rline
| Z line | N 2 w
2
X
1
R
Lec-6
Lec – 5
Ip Ip
- IS Ip IE - IS
N - I I �100 N 98�45�
�100 N S E
IS �100
IS IS
Lec - 9
Vth - VT 1 1
�100 )Dw w02
(3f ) ( L w02 1 LC < f Df �3Hz
Vth w02
LC
1t di dv di 1 d 2i
v(t ) Ri �
Ceq
-�
idt L
dt dt
R
dt Ceq
i L 2 w0
dt
d 1 1 1
DVL - DVC jI (w L - ) Dw I (2 2 )Dw w02 I ( L L )Dw
dw wCeq w0 Ceq LCeq
670
| VL - VC | 2 LI Dw 2 LI 2 LDw
j 2 LI Dw (DVL - DVC ) tan b 2 2 2 � 2p f Lm 106
| VR | a Rb I a Rb a Rb
106
Lm 3183.1H
2p
source. The fault strikes at time t t 0 . This can be simulated by closing the switch at t t1
671
R jwL or Z q models the line impedance. The fault current in the line is given by
i (t ) 0 0 t t0
t -t 0
V sin(w t f - q ) -
t
t t0
i (t ) m I 0e
|Z |
Where τ is the time constant of the line τ =L/R. The fault current has two components in
it. The first component models the steady state sinusoidal ac response while the second current
is the dc offset current due to the presence of inductive component in the circuit. Recall that
current in an inductance can not change instantaneously. As t ∞, the instantaneous dc
It is more or less obvious that, dc offset is not seen in the waveform after 5 time constants.
The value of I0 can be worked out by setting the current at t t o to zero.
This implies that
Vm
I0 - sin(wt 0 - q )
Z
672
Thus
t -t 0
Vm V -( )
i (t ) sin(wt f - q ) - m sin(wt f - q )e t
Z Z
fig.2
It can be seen that severity of dc offset component in fault current is maximum when
a) f q
p
b) wt 0
2
673
p 1
For example, if angle of transmission line is 800, then with f = 800 & t 0 =
2 2p 50 200
V
sec = 5msec, the severity of dc offset current would equal I 0 Z , which is also the peak
m
We now plan to show that CT can saturate on dc offset current. Also, we plan to show
that the resulting distortions in the CT secondary current can be un-acceptably high. While
doing this analysis, we will neglect ac symmetrical component. In other words, we rest our
belief in superposition theorem atleast qualitatively and will finally evaluate effect using it
Notice that the current that we are dealing with is non-linear, a rigorous application of super
position theorem is simply out of question.
674
First consider an ideal CT excited by the dc offset current source. An ideal CT will faithfully
replicates primary current waveform on the secondary side. Hence, the secondary current
would be given by
-t
I0 t
i2 (t ) e
N
and the voltage developed across CT secondary would be given by
-t
RI N2
v 2 (t ) 0 e t where N N
N 1
For simplicity, let us assume that the initial flux in the transformer core at t=0 is zero
f ( 0 ) 0 ; Then we can compute the flux in the transformer core by using faraday’s law
df
V2 N 2 ---------(2)
dt
675
t
f (t ) - f (0) v 0
2 dt
RI 0
-t
t 1- e t
N2
-t
LI 0
(1 - e t )
N2
-t
LI 0
f (t ) f (0) (1 - e t )
N2
-t
LI 0
(1 - e t ) ------- (3)
N2
as a consequence of dc offset current,
Thus, flux in the core increases exponentially to a peak value of
f dmax
c
LI 0
N2
as t
L Vm Vm
N Z Z
f dmax
c
Note that unlike ac voltage induced flux, which is sinusoidal, this flux is unidirectional. The ac
voltage induced flux has zero average value. However, dc offset induced does not have this
nice feature. The total flux in ideal CT core is a summation of ac flux and dc flux.
d
The ac flux in the CT core can be obtained by substituting operator by jw . Hence
dt
If v2 (t ) Vm sin(wt f ) , then
Vm p
f ac sin(wt f - )
wN 2 2
The peak value of ac flux is given by
676
Vm
f acmax
wN 2
However Vm R2 I 0
max
R2 I 0max
Hence facmax
wN 2
and peak value of the total flux is given by
Vm LI 0max
facmax f dcmax
wN 2 N2
In practice, if this flux exceeds the knee-point flux in the core (see fig.), then the CT core
will saturate.
As a consequence of CT core saturation, the secondary current would not faithfully replicate
the primary current. Infact, in practice it is observed that CT secondary current is clipped. The
clipping of CT current leads to “blinding” of the relay which cannot function further. Hence,
CT saturation in presence of dc offset current is a serious problem which relay designers have
to face. Note that dc flux accumulates gradually. (Depends upon the transmission line time
constant ( t ). It is apparent that saturation should not occur immediately after the inception of
the fault. Thus, if the relay is fast enough in decision making, it is likely that a relaying
decision would be undertaken before the CT fully saturates. This is another important reason
for increasing the speed of relaying system. For bus-fault protection, where the dc saturation
due to dc offset current can be a significant contributing factor, quarter cycle operations *****
677
specifically are imposed. Similarly, a distance relay is expected to operate within ½-1 cycle
time.
CT oversizing factors
Typically, an efficient design of transformer would correspond to choosing the core cross
section such that f mac should be near the knee point of B-H curve. One obvious way of
avoiding the CT saturation on dc flux is to oversize the core so that for flux (f acmax f dcmax ) , the
(f acmax f dcmax )
corresponding B is below the knee-point. Hence, the factor is called core-
f acmax
oversizing factor.
f dcmax
Core-oversizing factor = 1
f acmax
LI o N 2
1
RI 0 wN 2
wL
1
R
X
1
R
Note that X/R in above equation is the transmission line X/R ratio. For a 220KV line X/R 10.
This would imply that transformer core should be oversized by a factor of 11. For a 400KV
line, typical value of X/R 20. This would imply an oversizing required of about 21 times the
usual design. Clearly this high amount of oversizing is not practical. Thus, the important
conclusion is that, protection engineers have to live with the saturation problem.
Cautions in CT selection:
While choosing a CT for a particular application, it is necessary to observe following
precautions.
141. The CT rating and continuous load current should match. For example, if max
load current is 90A, a 100:5 Ct may be acceptable but 50:5 is not acceptable.
678
142. The maximum fault current should be less than 20 times the CT rated current.
for example 100:5 CT can be used, so long as burden on the CT & maximum primary
fault current is below 2000A.
143. The voltage rating of CT should be compatible. For example, 100:5 C100 would
give linear response, upto 20 times rated current provided CT burden is kept
below(100/20*5=1 Ω). With 2 Ω burden, this CT can be used only if maximum current
is limited to 1000A.
144. Parallel of CT’s e.g. in differential protection, or with SLG fault can create
significant errors in CT performance. One should in general ascertain that magnetizing
current is kept much below the pick up value.
Following example, illustrates this point
Exercise problems:
If the current ratio is adequate for a protection, but CT burden is high; then the
performance of CT may deteriorate due to large magnetizing current and/or saturation problem.
The CT performance can be improved by connecting the CT’s in series.
71) Show the dotted terminals for correct secondary series connection
72) What is the VA of CT in fig (a) & (b) respectively?
106) Electromechanical relays tend to saturate at high currents. This reduces the relay
burden on CT, and so that the CT performance at moderately high currents may be
considered better than at relay’s rated burden at 5A.
107) Use of instantaneous over current relays has the potential to overcome this
problem of saturation of CT’s
679
108) Differential protection can operate on external faults due to the un equal
saturation of CT’s
Lecture-6
Examples
41. If a 300:5 class C CT is connected to a meter with resistance R I 1 and
secondary current in the CT is 4.5A find out the primary current voltage
developed across the meter and % rate error. Lead wire resistance R L 0.02
secondary resistance RS of a 300/5 CT 0.15
Diagram
R I 1 , R L 0.02 RS 0.15 I S 4.5 A
Total secondary resistance RT R I R L RS
1.17
Secondary voltage I S RT
4.5 1.17
5.265V
From Fig 5.7,
Exciting current IE for 5.265V
= 0.03A
Turns ratio N = 300/5 = 60
I p N (I S I E )
= 60(4.5 + 0.03)
= 271.8A
Voltage across meter I S R I
4.5 1 = 4.5V
IE 0.03
Ratio error 100 100
IS 4.5
= 0.67%
Rb
680
Lecture – 8
Examples
71. Design a CCVT for a 132kV transmission line using the following data.
Resistive Burden (3f )-150VA
Df 3Hz , phase angle error b = 40 min
Consider 4 choices of V2 as 33kV, 11kV, 6.6kV and 3.3kV
Diagram 1 Diagram 2
Transmission line voltage V = 132kV. Suppose V 2 (P_N) be the voltage to be
produced by the capacitive potential divider with capacitance values C1 and C2
and L the value of tuning inductor. The standardized VT secondary voltage is 110
volts (L-L).
Here specification for phase angle error b is 40 minutes variation in frequency
can be upto Df 3Hz . Phase angle error for change in w by Dw in the above
equation circuit, is given by
1
( L 2 )Dw
w C
1
At tuning frequency w 2
LC
Substituting w 1 LC
2
747.2 H
1 1
C1 C 2
w 2 L (3/ 4) 2 747.2
1.3610 -2 F
3) V2 6.6kV
3 �(6.6 �103 )2
Rb
'
150
87.1210 4
b �Rb' 0.01164 �87.12 �104
L
2 �Dw 2 �2p �3
269H ,
C1 C 2 3.7710 -2 F
4) V2 3.3kV
3 �(3.3 �103 ) 2
Rb'
150
21.7810 4
b �Rb' 0.01164 �21.78 �104
L
2 �Dw 2 �2p �3
67.25 H
C1 C2 0.151 F
The values of L, C1 C 2 for different values of V2 are tabulated below.
V2 L C1 C 2
33kV 6722.2H 0.00151 F
11kV 747.2H 0.0136 F
6.6kV 269H 0.0377 F
3.3kV 67.25H 0.151 F
From the above table it is clear that smaller the value of V 2, the smaller is the
value of L and higher the value of C 1 and C2 for tuning condition. If we select too low
value of V2 and L then capacitance values will be beyond available limits, and if we
select higher value of V2 and L, then CCVT and inductor will become bulky. So a
compromise is necessary and let us select V2 = 6.6kV
For V2 = 6.6kV
L = 269H
C1 C 2 0.0377 F
V C1 C 2
Now,
V2 C1
13210 3 0.037710 -6
36.610 3
C1
0.0377 36.610 3 10 -6 F
C1
13210 3
0.0033F
682
C 2 0.0344F
In this design, we explained the basic concept for CCVT design and we assumed
the transformer to be ideal. But in actual design practice the value of magnetizing
impedance of transformer, resistance of reactor etc have to be taken into account,
as ratio error a and phase angle error b will also get affected by these values.
72. Diagram
The equivalent circuit of a CCVT is shown in fig 8.3. The values of C 1 and C2 are
0.0018 F and 0.018 F respectively. Tuning inductor has an inductance of
497H and resistance of 4620 .
Xm of the 6.6kV VT is 1M , core loss = 20 watts per phase, VA burden =
150VA per phase. Value of Cm for compensating the current drawn by m is equal
to 3.18310 -9 F .
(bbbbb) Verify the appropriateness of choice of L and Cm.
Ans: If C1 0.0018F and C 2 0.0186F then the value L of tuning inductor
is given by
1
L 2
w (C1 C 2 )
where w 2p f and f = tuning frequency
1
L
(2p �50) (0.0018 0.0186) �10-6
2
1
Xm
w Cm
1 1
Cm
w X m (2p �50) �� 1 106
3.183 �10-9 F
The value is also same as the selected value of Cm Hence the selection of both L
and Cm is appropriate.
(ddddd) If the frequency drops from 50Hz to 47Hz, what would be the
values of ratio error and phase angle error?
Ans: Core loss = 20w
V22
20W
Rm
683
V22 (6600) 2
Rm
20 20
2.18 �10
6
6600 0
A
260874.14 -2.44�
VT I th �Z
6600 0
�256147.5 1.82�
260874.14 -2.44�
6480.42 4.26�
(6600 - 6480.42)
Hence % ratio error �100
6600
=1.81%
Phase angle error = 4.26�
V2 6.6kV
r a w2 a 2
M
d 2i R di 1 1 R
t �t0 2
i0 wn 2p �50 2 Iwn
dt L dt LCeq LC L
d 2i
2
2a wn wn2i 0 a < 1
dt
Lec – 8
1
2p �50 2zw R d i 2zw w 2i 0 z wn z < 1
2
wn
LCeq n
L dt 2 n n
-t V
t I 0 - m sin(wt0 f - q ) f q
e | Z line |
685