CO M F LO R ® CO M P O S I T E F LO O R SY S T E M

MONTREAL · TORONTO · CALGARY · EDMONTON · VANCOUVER

T E C H N I C A L A N D S T R U C T U R A L I N F O R M AT I O N
TA B L E O F CO N T E N T S

Preface, The Product, Scope of this Catalogue ............................................................................................................................ 2


Advantages .............................................................................................................................................................................................. 3

CO M F LO R ® CO M P O S I T E F LO O R SYS T E M | TA B L E O F CO N T E N T S
Design Criteria and Technical Data.................................................................................................................................................. 3
COMFLOR® Steel Deck Cross Section................................................................................................................................................ 5
COMFLOR® Steel Deck Section Properties ...................................................................................................................................... 5
COMFLOR® Composite Slab Example .............................................................................................................................................. 6
Use of Deflection Parameter .............................................................................................................................................................. 6
COMFLOR® Composite Slab Load Tables, SI Units ...................................................................................................................... 7
0.96 mm Deck - 10 mm Nominal Rebar .................................................................................................................................... 7
0.96 mm Deck - 15 mm Nominal Rebar .................................................................................................................................... 8
0.96 mm Deck - 20 mm Nominal Rebar .................................................................................................................................... 9
0.96 mm Deck - 25 mm Nominal Rebar .................................................................................................................................. 10
0.96 mm Deck - 30 mm Nominal Rebar .................................................................................................................................. 11
1.21 mm Deck - 10 mm Nominal Rebar .................................................................................................................................. 12
1.21 mm Deck - 15 mm Nominal Rebar .................................................................................................................................. 13
1.21 mm Deck - 20 mm Nominal Rebar .................................................................................................................................. 14
1.21 mm Deck - 25 mm Nominal Rebar .................................................................................................................................. 15
1.21 mm Deck - 30 mm Nominal Rebar .................................................................................................................................. 16
COMFLOR® Composite Slab Load Tables, Imperial Units ........................................................................................................ 17
0.0378 in. Deck - 10 mm Nominal Rebar ................................................................................................................................ 17
0.0378 in. Deck - 15 mm Nominal Rebar ................................................................................................................................ 18
0.0378 in. Deck - 20 mm Nominal Rebar ................................................................................................................................ 19
0.0378 in. Deck - 25 mm Nominal Rebar ................................................................................................................................ 20
0.0378 in. Deck - 30 mm Nominal Rebar ................................................................................................................................ 21
0.0476 in. Deck - 10 mm Nominal Rebar ................................................................................................................................ 22
0.0476 in. Deck - 15 mm Nominal Rebar ................................................................................................................................ 23
0.0476 in. Deck - 20 mm Nominal Rebar ................................................................................................................................ 24
0.0476 in. Deck - 25 mm Nominal Rebar ................................................................................................................................ 25
0.0476 in. Deck - 30 mm Nominal Rebar ................................................................................................................................ 26 1
Construction Guidelines...................................................................................................................................................................... 27
Examples of Construction Applications.......................................................................................................................................... 32
COMFLOR® Sound and Fire Ratings................................................................................................................................................ 36
Typical COMFLOR® Round Service Hole Detail............................................................................................................................ 37
Maximum Round Service Hole Diameters .................................................................................................................................... 37
COMFLOR® Concrete Volume Values for Estimating .................................................................................................................. 38
Reinforcing Bar Information .............................................................................................................................................................. 38
COMFLOR® Steel Deck and Accessories........................................................................................................................................ 39
COMFLOR® Specifications .................................................................................................................................................................. 40
Deflection Due to Slab Weight ........................................................................................................................................................ 42
References Documents........................................................................................................................................................................ 43
SI – Imperial Conversions .................................................................................................................................................................. 43

03/2005 Printed in Canada


PREFACE
The information contained herein is intended as a general guide to the design professional. Anyone making use of the
information contained herein assumes any and all liability arising from such use. This document supersedes all earlier
publications, including catalogues, brochures, flyers, technical bulletins, load tables, etc. regarding COMFLOR ®.
P R E FAC E | T H E P RO D U C T | S CO P E O F T H I S C ATA LO G U E

THE PRODUCT

COMFLOR® is a registered trademark of BMP, and provides a composite slab solution for spans up to 11 m (36 ft). COMFLOR®
is a unique deep deck composite cold formed galvanised steel profile. The COMFLOR® composite slab system is well suited to
spanning between cold formed steel, concrete or masonry loadbearing walls, or between hot rolled steel or concrete beams.
This versatility means that COMFLOR® is an ideal floor system for low, medium and high rise buildings where non-combustible
construction, a thin floor profile, or long clear spans are required.

S CO P E O F T H I S C ATA LO G U E

This catalogue provides technical and structural information for the COMFLOR® composite concrete slab system. All calculations,
whenever applicable, were based on CSA Standard S1361 and CSSBI documents2,3,4. Design load tables are also presented, as
well as various construction applications to assist the designer in detailing common structural assemblies. Additional assistance
regarding the COMFLOR® composite slab system construction method may be obtained by contacting the BMP sales office in
your area.
The structural load tables and technical information contained in this catalogue were prepared by Dr. R.M. Schuster, P.Eng.,
Professor Emeritus of Structural Engineering at the University of Waterloo.
A DVA N TAG E S

COMFLOR® COMPOSITE SL AB
• Unshored spans of up to 5 m (16.4 ft) can be achieved using normal density concrete.

A DVA N TAG E S | D E S I G N C R I T E R I A A N D T E C H N I C A L DATA


• The COMFLOR® composite slabs have a relatively light self-weight when compared to either reinforced concrete or pre-cast
units, resulting in potential savings in both steel and foundation costs.
• The COMFLOR® steel deck provides a safe working platform during construction, and also functions as a safe and dry cover
for people working underneath.
• Apart from the inherent composite action of the embossed COMFLOR® deck, every rib element of the slab is further reinforced
with a single steel reinforcing bar. This not only provides additional structural strength to the slab, but also results in improved fire
resistance performance.
• It is possible to accommodate services within the profile depth, and the geometry of the slab ribs allows for transverse
services shown on the Service Hole Table, on page 37.
• Ceilings can easily be suspended directly from the profile troughs, which at 610 mm (24 in.) on centre, ideally line up with
standard ceiling tile grids.
• The long span decking allows for maximum architectural design freedom while maintaining steel deck advantages with
regard to service penetrations and on-site fastening flexibility. Due to the reduced number of beams, the number of
connections and fasteners is also reduced.
• The overall building cost can be reduced due to the fast-track construction.
• The COMFLOR® slab has an inherent fire resistance of up to 120 minutes without additional fire protection (ULC D500).
• Contact BMP regarding additional advantages and information.

D E S I G N C R I T E R I A A N D T E C H N I C A L DATA

3
M AT E R I A L S
• Steel deck meets the requirements of ASTM A653 Standard Specification of Steel Sheet, Zinc-coated (Galvanized) by the Hot-
dip Process, Structural (Physical) Quality. Guaranteed minimum yield strength is 280 MPa (40.6 ksi) with a minimum zinc
coating mass of 275 g/m2 (G90) total both sides. Steel deck base thickness is 0.96 mm (0.0378 in.) or 1.21 mm (0.0476 in.).
• Reinforcing steel meets the requirements of CAN/CSA G30.18-M19925. Guaranteed minimum yield strength is 400 MPa (58.0 ksi).
The clear distance of each reinforcing bar from the bottom of the steel deck is 40 mm (1.57 in.).
• Concrete is assumed to have a minimum cylinder strength of 30 MPa (4.35 ksi) with a maximum aggregate size of 20 mm
(0.75 in.). Normal density structural concrete is 2400 kg/m3 (150 lb/ft3).

L I M I T S TAT E S D E S I G N ( L S D )
• Strength – Limit states design principles were used in the development of the structural load tables, i.e., the factored
resistance under consideration, φR ≥ the effect of the factored loads. This is in accordance with the National Building Code
of Canada, 19956. Since the self weight of the steel deck and the concrete have already been included in the structural load
tables, the maximum specified load (from the appropriate structural table) shall be:
≥ (LL + 1.25/1.5DL),
where LL - Specified live load
DL - Specified superimposed dead load
1.25 - Dead load factor
1.5 - Live load
• Serviceability – If deflection controls, the maximum specified load (from the
appropriate structural table) shall be:
≥ (LL + DL).

SECTION PROPERTIES OF STEEL DECK


All structural section properties of the steel deck were calculated in accordance with
CSA Standard S136-941. See page 5 for section properties and cross section details.

S T R U C T U R A L LOA D TA B L E S
The structural load tables provide maximum specified loads and were established in
accordance with CSSBI 12M-963 and CSSBI S3-20024.
D E S I G N C R I T E R I A A N D T E C H N I C A L DATA

• Shoring During Construction


Shoring requirements for the steel deck during construction were established in
accordance with CSSBI 12M-963. The following strength and deflection criteria were used:
Strength – Calculations were based on the combined loads due to the wet concrete,
the steel deck and certain construction live loads. The minimum construction live
loads applied separately are:
1) 1 kPa (21 psf) uniform load.
2) 2 kN/m (137 lb/ft) transverse line load at the centre of the span.
Serviceability – Calculated deflections were based on the uniform load of concrete
slab and steel deck and the maximum deflections were limited to L/180 or
20 mm (0.787 in.).
Presented in the COMFLOR® composite slab load tables are two maximum
unshored span conditions, i.e.,
1) Maximum Unshored Span – based on the above stated strength and
serviceability criteria.
2) Maximum Unshored Span – based on the above stated strength and
serviceability criteria, except a 2 kPa (42 psf) uniform load was used instead of
1 kPa (21 psf). This was done because in some jurisdictions a 2 kPa (42 psf)
uniform live load is required.

4 At the top of each structural load table, two maximum unshored span
conditions are given. Using this information, one can determine the number
of shores required for any given span condition.

• Load Tables
Both strength and deflection criteria were considered in accordance with CSSBI S3-20024, as follows.
Strength – Flexure was the only criteria considered in the calculations since shear-bond is not a mode of failure. In
accordance with Table 4.1.6.10 of the National Building Code of Canada, 19956, a 9 kN (2023 lb) specified concentrated live
load was included in the strength calculations.
Serviceability – Calculated deflections due to specified superimposed loads (LL + DL) were based on a uniform load with
the maximum deflection limited to L/360. The modular ratio for normal density concrete was taken as 10 and the moment of
inertia is the average of the uncracked and cracked moment of inertias. For use of the deflection parameter, SLDP, see
example on page 5. To determine the deflection due to the slab weight, see page 42.
Use of Load Tables – See example on page 6 for use of structural load tables.

STRUCTURAL TESTING
Structural COMFLOR® composite slab tests were carried out at the University of Salford, England by Prof. D. O’Leary (April, 1993).
Based on these tests, shear-bond was not a mode of failure. Typically, composite slab systems fail in shear-bond. However, since
the COMFLOR® composite slab system also has reinforcing steel, shear-bond is not a governing failure mode.
COMFLOR® STEEL DECK CROSS SECTION

COMFLOR® STEEL DECK CROSS SECTION | SECTION PROPERTIES


185 mm 425 mm 185 mm

203 mm
72.5º
Side-lap
Washer

56 mm 92.5 mm

Cover width 610 mm


L
C L
C

COMFLOR® STEEL DECK SECTION PROPERTIES

SI-UNITS
NORMAL BASE PROFILE PROFILE A g1 Ae2 Sp3 Ix4 5
THICKNESS THICKNESS DEPTH WEIGHT
(mm) (mm) (mm) (kPa) (mm /m)
2
(mm /m)
2
(10 mm /m)
3 3
(10 mm /m)
6 4

1.00 0.96 203 0.124 1548 636 37.8 4.73


1.25 1.21 203 0.155 1951 887 63.2 7.14

IMPERIAL UNITS
NORMAL BASE PROFILE PROFILE Ag1 Ae2 Sp3 Ix4
THICKNESS THICKNESS DEPTH WEIGHT
(in.) (in.) (in.) (psf) (in.2/ft) (in.2/ft) (in.3/ft) (in.4/ft)
0.0394 0.0378 8.00 2.59 0.731 0.300 0.705 3.47
0.0492 0.0476 8.00 3.24 0.921 0.418 1.18 5.24

NOTES:
1
Ag = Gross cross sectional area of profile per unit width.
2
Ae = Effective cross sectional area of profile per unit width.
3
Sp = Effective section modulus of profile per unit width for positive bending.
4
Ix = Effective moment of inertia of profile per unit width.
COMFLOR® COMPOSITE SL AB EXAMPLE
CO M F LO R ® CO M P O S I T E S L A B E X A M P L E | D E F L E C T I O N PA R A M E T E R

Determine the specified live load that can be placed on the COMFLOR® composite slab,
given the following information:

GIVEN:
Steel deck - Base steel design thickness = 1.21 mm; yield strength = 280 MPa
Reinforcing steel - Nominal bar diameter = 15 mm; yield strength = 400 MPa
Concrete - Normal density = 2400 kg/m3
Overall slab depth = 260 mm
Single span length = 5.5 m (one shore required)
Specified superimposed dead load:
a) floor finish = 0.4 kPa
b) partitions = 0.7 kPa
DL = 1.1 kPa

U S E O F LOA D TA B L E :
The maximum specified load in (kPa) from load table shall be: ≥ (LL + 1.25/1.5 DL),
Where
LL = Specified live load
DL = Specified superimposed dead load.
From the load table on page 13, the maximum specified load is 8.15 kPa, therefore,
8.15 ≥ (LL + 1.25/1.5 DL),
and the specified live load is
LL = 8.15 – (1.25/1.5)(1.1) = 7.23 kPa

NOTE: The self-weight of the steel deck, the reinforcing bar and the concrete have already been accounted for in the load tables
for strength requirements only.

USE OF SUPERIMPOSED LOAD DEFLECTION PARAMETER (SLDP)

6 SI-UNITS IMPERIAL UNITS


SLDP x 103 SLDP x 106
wd = wd =
DC x (L)3 DC x (L)3
Where:
wd = Maximum specified superimposed deflection load in kPa or psf,
SLDP = Superimposed load deflection parameter from appropriate load table,
DC = Deflection constant such as 360,
L = Span length in metres or feet

EXAMPLES:
Base steel thickness = 0.96 mm Base steel thickness = 0.0378 in.
Nominal bar diameter = 30 mm Nominal bar diameter = 30 mm
Slab depth = 260 mm Slab depth = 10.5 in.
Span length, L, = 6 m Span length, L, = 25ft
From table on page 10, DP = 920 From table on page 20, DP = 731
Assume DC = 360 Assume DC = 360

920 x 103 731 x 106


wd = = 11.8 kPa wd = = 130 psf
360 x (6)3 360 x (25)3
For confirmation of values, see appropriate load tables.
CO M F LO R ® CO M P O S I T E S L A B LOA D TA B L E – S I - M E T R I C U N I T S

BASE STEEL DECK THICKNESS = 0.96 mm | NOMINAL REBAR DIAMETER = 10 mm


NORMAL DENSITY CONCRETE = 2400 kg/m3

CO M F LO R ® CO M P O S I T E S L A B LOA D TA B L E | S I - M E T R I C U N I T S
SLAB WEIGHT (kPa) 2.42 2.66 2.89 3.13 3.36 3.60 3.83 4.07
CONCRETE VOLUME (m3/10m2) 0.971 1.07 1.17 1.27 1.37 1.47 1.57 1.67
1) MAX. UNSHORED SPAN (mm) 4106 3975 3839 3717 3607 3506 3414 3329
2) MAX. UNSHORED SPAN (mm) 3559 3475 3397 3324 3255 3191 3130 3072
Iu x 106 mm4 59.9 67.1 74.9 83.2 92.2 102 112 124
Ic x 106 mm4 24.4 26.7 29.2 31.8 34.5 37.4 40.4 43.6
DEFL. PARAMETER (SLDP) 657 731 811 896 987 1085 1190 1303
DEFL. PARAMETER (SWDP) 2.59 2.54 2.48 2.41 2.34 2.27 2.19 2.11
SLAB THICKNESS (mm) 260 270 280 290 300 310 320 330

SHORING SPAN (m) MAXIMUM SPECIFIED LOAD (kPa)


To be established 4.5 8.39 8.76 9.14 9.51 9.88 10.3 10.6 11.0
by the designer. 4.6 7.94 8.29 8.64 8.99 9.34 9.69 10.0 10.4
See notes below. 4.8 7.13 7.43 7.74 8.04 8.35 8.65 8.96 9.26
5.0 6.41 6.68 6.94 7.21 7.47 7.74 8.00 8.27
5.2 5.78 6.01 6.24 6.47 6.70 6.93 7.16 7.39
5.4 5.21 5.41 5.61 5.81 6.01 6.21 6.41 6.60
5.5 4.95 5.13 5.32 5.50 5.69 5.87 6.06 6.24
5.6 4.70 4.87 5.05 5.22 5.39 5.56 5.73 5.90
5.8 4.25 4.39 4.54 4.69 4.83 4.98 5.13 5.27
6.0 3.84 3.96 4.08 4.21 4.33 4.46 4.58 4.71
6.2 3.47 3.57 3.67 3.78 3.88 3.98 4.09 4.19
6.4 3.13 3.21 3.30 3.38 3.47 3.55 3.64 3.72
6.5 2.97 3.05 3.12 3.20 3.28 3.35 3.43 3.51
6.6 2.82 2.89 2.96 3.03 3.09 3.16 3.23 3.30
6.8 2.54 2.59 2.65 2.70 2.75 2.81 2.86 2.91
7.0 2.28 2.32 2.36 2.40 2.44 2.48 2.52 2.56

NOTES: 3. “d” next to values in Table indicates deflection controls due to specified
1. The “SLAB WEIGHT” is made up of the self weight of the steel deck, superimposed loads.
the reinforcing bar and the concrete slab, which has been accounted 4. For explanation of deflection parameters SLDP and SWDP, see page 6.
for in the load table for strength requirements only. 5. “SLAB THICKNESS” is measured from top of concrete to bottom
2. Shoring may be required. See maximum unshored span conditions of steel deck.
above to establish the number of shores required. Also, see page 4 6. Iu is the uncracked moment if inertia based on equivalent steel
for explanation of above maximum unshored span conditions. 7. Ic is the cracked moment if inertia based on equivalent steel
BASE STEEL DECK THICKNESS = 0.96 mm | NOMINAL REBAR DIAMETER = 15 mm
NORMAL DENSITY CONCRETE = 2400 kg/m3

SLAB WEIGHT (kPa) 2.44 2.67 2.91 3.14 3.38 3.61 3.85 4.08
CO M F LO R ® CO M P O S I T E S L A B LOA D TA B L E | S I - M E T R I C U N I T S

CONCRETE VOLUME (m3/10m2) 0.971 1.07 1.17 1.27 1.37 1.47 1.57 1.67
1) MAX. UNSHORED SPAN (mm) 4099 3967 3832 3711 3601 3501 3409 3324
2) MAX. UNSHORED SPAN (mm) 3554 3470 3393 3320 3251 3187 3127 3069
Iu x 106 mm4 62.5 70.0 78.1 86.7 96.0 106 117 128
Ic x 106 mm4 28.6 31.4 34.3 37.5 40.7 44.2 47.8 51.6
DEFL. PARAMETER (SLDP) 710 790 876 968 1066 1171 1283 1403
DEFL. PARAMETER (SWDP) 2.50 2.45 2.39 2.32 2.26 2.19 2.11 2.04
SLAB THICKNESS (mm) 260 270 280 290 300 310 320 330

SHORING SPAN (m) MAXIMUM SPECIFIED LOAD (kPa)


To be established 4.5 11.2 11.8 12.3 12.8 13.3 13.8 14.4 14.9
by the designer. 4.6 10.7 11.2 11.6 12.1 12.6 13.1 13.6 14.1
See notes below. 4.8 9.63 10.1 10.5 10.9 11.4 11.8 12.2 12.7
5.0 8.71 9.10 9.48 9.87 10.3 10.6 11.0 11.4
5.2 7.90 8.24 8.58 8.93 9.27 9.61 10.0 10.3
5.4 7.18 7.48 7.78 8.09 8.39 8.69 8.99 9.29
5.5 6.85 7.13 7.42 7.70 7.98 8.27 8.55 8.84
5.6 6.53 6.80 7.07 7.34 7.60 7.87 8.14 8.40
5.8 5.95 6.19 6.43 6.66 6.90 7.13 7.37 7.60
6.0 5.43 5.64 5.85 6.05 6.26 6.47 6.67 6.88
6.2 4.96 5.14 5.32 5.50 5.68 5.87 6.05 6.23
6.4 4.53 4.69 4.84 5.00 5.16 5.32 5.48 5.64
6.5 4.33 4.47 4.62 4.77 4.92 5.07 5.21 5.36
6.6 4.14 4.27 4.41 4.55 4.69 4.82 4.96 5.10
6.8 3.78 3.90 4.01 4.13 4.25 4.37 4.49 4.60
7.0 3.45 3.55 3.65 3.75 3.85 3.95 4.05 4.15
7.2 3.15 3.24 3.32 3.40 3.49 3.57 3.66 3.74
7.4 2.88 2.94 3.01 3.08 3.15 3.22 3.29 3.36
8 7.5 2.75 2.81 2.87 2.93 2.99 3.06 3.12 3.18
7.6 2.62 2.68 2.73 2.79 2.84 2.90 2.95 3.01
7.8 2.39 2.43 2.47 2.51 2.56 2.60 2.64 2.68
8.0 2.17 2.20 2.23 2.26 2.29 2.32 2.35 2.38

NOTES: 3. “d” next to values in Table indicates deflection controls due to specified
1. The “SLAB WEIGHT” is made up of the self weight of the steel deck, superimposed loads.
the reinforcing bar and the concrete slab, which has been accounted 4. For explanation of deflection parameters SLDP and SWDP, see page 6.
for in the load table for strength requirements only. 5. “SLAB THICKNESS” is measured from top of concrete to bottom
2. Shoring may be required. See maximum unshored span conditions of steel deck.
above to establish the number of shores required. Also, see page 4 6. Iu is the uncracked moment if inertia based on equivalent steel
for explanation of above maximum unshored span conditions. 7. Ic is the cracked moment if inertia based on equivalent steel
BASE STEEL DECK THICKNESS = 0.96 mm | NOMINAL REBAR DIAMETER = 20 mm
NORMAL DENSITY CONCRETE = 2400 kg/m3

SLAB WEIGHT (kPa) 2.45 2.68 2.92 3.15 3.39 3.62 3.86 4.09

CO M F LO R ® CO M P O S I T E S L A B LOA D TA B L E | S I - M E T R I C U N I T S
CONCRETE VOLUME (m3/10m2) 0.971 1.07 1.17 1.27 1.37 1.47 1.57 1.67
1) MAX. UNSHORED SPAN (mm) 4092 3960 3826 3705 3596 3496 3404 3320
2) MAX. UNSHORED SPAN (mm) 3549 3466 3389 3316 3248 3184 3123 3066
Iu x 106 mm4 64.8 72.6 81.0 89.9 100 110 121 133
Ic x 106 mm4 32.3 35.5 38.9 42.5 46.3 50.3 54.4 58.8
DEFL. PARAMETER (SLDP) 757 843 935 1032 1136 1248 1366 1493
DEFL. PARAMETER (SWDP) 2.42 2.37 2.31 2.25 2.19 2.12 2.05 1.98
SLAB THICKNESS (mm) 260 270 280 290 300 310 320 330

SHORING SPAN (m) MAXIMUM SPECIFIED LOAD (kPa)


To be established 4.5 13.9 14.6 15.2 15.9 16.5 17.2 17.9 18.5
by the designer. 4.6 13.2 13.8 14.5 15.1 15.7 16.3 17.0 17.6
See notes below. 4.8 12.0 12.5 13.1 13.6 14.2 14.8 15.3 15.9
5.0 10.9 11.4 11.9 12.4 12.9 13.4 13.9 14.4
5.2 9.89 10.3 10.8 11.2 11.7 12.1 12.6 13.0
5.4 9.02 9.42 9.82 10.2 10.6 11.0 11.4 11.8
5.5 8.62 9.00 9.38 9.76 10.1 10.5 10.9 11.3
5.6 8.24 8.60 8.96 9.32 9.68 10.0 10.4 10.8
5.8 7.55 7.87 8.19 8.51 8.83 9.16 9.48 9.80
6.0 6.92 7.21 7.49 7.78 8.07 8.36 8.65 8.93
6.2 6.35 6.61 6.86 7.12 7.38 7.64 7.89 8.15
6.4 5.83 6.06 6.29 6.52 6.75 6.98 7.21 7.44
6.5 5.59 5.81 6.03 6.24 6.46 6.68 6.89 7.11
6.6 5.36 5.57 5.77 5.98 6.18 6.38 6.59 6.79
6.8 4.94 5.12 5.30 5.48 5.66 5.84 6.02 6.20
7.0 4.54 4.70 4.86 5.02 5.18 5.34 5.50 5.66
7.2 4.18 4.32 4.46 4.60 4.74 4.88 5.02 5.16
7.4 3.85 3.97 4.09 4.22 4.34 4.46 4.58 4.70
7.5 3.69 3.81 3.92 4.03 4.15 4.26 4.38 4.49 9
7.6 3.54 3.65 3.76 3.86 3.97 4.07 4.18 4.28
7.8 3.26 3.35 3.44 3.53 3.62 3.71 3.80 3.89
8.0 3.00 3.08 3.15 3.23 3.30 3.38 3.46 3.53
8.2 2.76 2.82 2.88 2.95 3.01 3.07 3.13 3.20
8.4 2.53 2.58 2.63 2.68 2.73 2.79 2.84 2.89
8.5 2.42 2.47 2.51 2.56 2.60 2.65 2.69 2.74

NOTES: 3. “d” next to values in Table indicates deflection controls due to specified
1. The “SLAB WEIGHT” is made up of the self weight of the steel deck, superimposed loads.
the reinforcing bar and the concrete slab, which has been accounted 4. For explanation of deflection parameters SLDP and SWDP, see page 6.
for in the load table for strength requirements only. 5. “SLAB THICKNESS” is measured from top of concrete to bottom
2. Shoring may be required. See maximum unshored span conditions of steel deck.
above to establish the number of shores required. Also, see page 4 6. Iu is the uncracked moment if inertia based on equivalent steel
for explanation of above maximum unshored span conditions. 7. Ic is the cracked moment if inertia based on equivalent steel
BASE STEEL DECK THICKNESS = 0.96 mm | NOMINAL REBAR DIAMETER = 25 mm
NORMAL DENSITY CONCRETE = 2400 kg/m3

SLAB WEIGHT (kPa) 2.47 2.71 2.94 3.18 3.41 3.65 3.88 4.12
CO M F LO R ® CO M P O S I T E S L A B LOA D TA B L E | S I - M E T R I C U N I T S

CONCRETE VOLUME (m3/10m2) 0.971 1.07 1.17 1.27 1.37 1.47 1.57 1.67
1) MAX. UNSHORED SPAN (mm) 4078 3945 3812 3693 3584 3486 3395 3311
2) MAX. UNSHORED SPAN (mm) 3540 3458 3381 3309 3241 3177 3117 3060
Iu x 106 mm4 69.1 77.5 86.4 95.9 106 117 129 141
Ic x 106 mm4 39.1 43.1 47.4 51.9 56.6 61.5 66.8 72.2
DEFL. PARAMETER (SLDP) 843 940 1043 1152 1268 1392 1524 1664
DEFL. PARAMETER (SWDP) 2.30 2.24 2.19 2.13 2.06 2.00 1.94 1.87
SLAB THICKNESS (mm) 260 270 280 290 300 310 320 330

SHORING SPAN (m) MAXIMUM SPECIFIED LOAD (kPa)


To be established 4.5 19.4 20.4 21.3 22.3 23.3 24.2 25.2 26.1
by the designer. 4.6 18.5 19.4 20.3 21.2 22.1 23.0 23.9 24.9
See notes below. 4.8 16.8 17.6 18.5 19.3 20.1 20.9 21.7 22.5
5.0 15.3 16.1 16.8 17.6 18.3 19.0 19.8 20.5
5.2 14.0 14.7 15.4 16.0 16.7 17.4 18.0 18.7
5.4 12.9 13.5 14.1 14.7 15.3 15.9 16.5 17.1
5.5 12.3 12.9 13.5 14.1 14.6 15.2 15.8 16.4
5.6 11.8 12.4 12.9 13.5 14.0 14.6 15.1 15.7
5.8 10.9 11.4 11.9 12.4 12.9 13.4 13.9 14.4
6.0 10.0 10.5 10.9 11.4 11.8 12.3 12.7 13.2
6.2 9.25 9.67 10.1 10.5 10.9 11.3 11.7 12.1
6.4 8.56 8.93 9.31 9.68 10.1 10.4 10.8 11.2
6.5 8.23 8.59 8.95 9.31 9.66 10.0 10.4 10.7
6.6 7.92 8.26 8.61 8.95 9.29 9.63 10.0 10.3
6.8 7.35 7.66 7.96 8.27 8.58 8.89 9.20 9.51
7.0 6.82 7.10 7.38 7.66 7.94 8.22 8.50 8.78
7.2 6.27d 6.58 6.84 7.09 7.35 7.60 7.86 8.11
7.4 5.78d 6.11 6.34 6.57 6.80 7.04 7.27 7.50
10 7.5 5.55d 5.89 6.11 6.33 6.55 6.77 6.99 7.21
7.6 5.33d 5.68 5.89 6.10 6.30 6.51 6.72 6.93
7.8 4.93d 5.28 5.46 5.65 5.84 6.03 6.22 6.40
8.0 4.57d 4.90 5.07 5.24 5.41 5.58 5.75 5.92
8.2 4.24d 4.56 4.71 4.86 5.01 5.17 5.32 5.47
8.4 3.95d 4.24 4.37 4.51 4.64 4.78 4.91 5.05
8.5 3.81d 4.09 4.21 4.34 4.47 4.60 4.72 4.85
8.6 3.68d 3.94 4.06 4.18 4.30 4.42 4.54 4.66
8.8 3.43d 3.66 3.77 3.87 3.98 4.08 4.19 4.30
9.0 3.21d 3.40 3.49 3.59 3.68 3.77 3.86 3.96
9.2 3.01d 3.16 3.24 3.32 3.40 3.48 3.56 3.64
9.4 2.82d 2.93 3.00 3.07 3.14 3.20 3.27 3.34
9.5 2.73d 2.82 2.88 2.95 3.01 3.07 3.14 3.20
9.6 2.65d 2.72 2.77 2.83 2.89 2.95 3.00 3.06
9.8 2.47 2.52 2.56 2.61 2.66 2.70 2.75 2.80
10.0 2.29 2.33 2.36 2.40 2.44 2.48 2.51 2.55
NOTES: 3. “d” next to values in Table indicates deflection controls due to specified
1. The “SLAB WEIGHT” is made up of the self weight of the steel deck, superimposed loads.
the reinforcing bar and the concrete slab, which has been accounted 4. For explanation of deflection parameters SLDP and SWDP, see page 6.
for in the load table for strength requirements only. 5. “SLAB THICKNESS” is measured from top of concrete to bottom
2. Shoring may be required. See maximum unshored span conditions of steel deck.
above to establish the number of shores required. Also, see page 4 6. Iu is the uncracked moment if inertia based on equivalent steel
for explanation of above maximum unshored span conditions. 7. Ic is the cracked moment if inertia based on equivalent steel
BASE STEEL DECK THICKNESS = 0.96 mm | NOMINAL REBAR DIAMETER = 30 mm
NORMAL DENSITY CONCRETE = 2400 kg/m3

SLAB WEIGHT (kPa) 2.50 2.73 2.97 3.20 3.44 3.68 3.91 4.15

CO M F LO R ® CO M P O S I T E S L A B LOA D TA B L E | S I - M E T R I C U N I T S
CONCRETE VOLUME (m3/10m2) 0.971 1.07 1.17 1.27 1.37 1.47 1.57 1.67
1) MAX. UNSHORED SPAN (mm) 4064 3929 3798 3680 3573 3475 3385 3302
2) MAX. UNSHORED SPAN (mm) 3531 3449 3373 3301 3234 3171 3111 3054
Iu x 106 mm4 72.9 81.8 91.3 101 112 124 136 149
Ic x 106 mm4 45.1 49.8 54.9 60.2 65.8 71.7 77.9 84.4
DEFL. PARAMETER (SLDP) 920 1026 1140 1260 1387 1523 1667 1820
DEFL. PARAMETER (SWDP) 2.20 2.14 2.09 2.03 1.97 1.91 1.84 1.78
SLAB THICKNESS (mm) 260 270 280 290 300 310 320 330

SHORING SPAN (m) MAXIMUM SPECIFIED LOAD (kPa)


To be established 5.5 15.3d 16.1 16.9 17.7 18.5 19.2 20.0 20.8
by the designer. 5.6 14.5d 15.5 16.2 17.0 17.7 18.5 19.2 19.9
See notes below. 5.8 13.1d 14.3 15.0 15.6 16.3 17.0 17.7 18.4
6.0 11.8d 13.2d 13.8 14.4 15.1 15.7 16.3 16.9
6.2 10.7d 12.0d 12.8 13.4 13.9 14.5 15.1 15.6
6.4 9.74d 10.9d 11.8 12.4 12.9 13.4 13.9 14.5
6.5 9.30d 10.4d 11.4 11.9 12.4 12.9 13.4 13.9
6.6 8.88d 9.91d 11.0 11.5 11.9 12.4 12.9 13.4
6.8 8.12d 9.06d 10.1d 10.7 11.1 11.5 12.0 12.4
7.0 7.44d 8.31d 9.22d 9.90 10.3 10.7 11.1 11.5
7.2 6.84d 7.63d 8.48d 9.21 9.58 9.95 10.3 10.7
7.4 6.30d 7.03d 7.81d 8.57 8.92 9.26 9.60 9.94
7.5 6.05d 6.75d 7.50d 8.28 8.60 8.93 9.26 9.58
7.6 5.82d 6.49d 7.21d 7.97d 8.30 8.62 8.93 9.24
7.8 5.38d 6.00d 6.67d 7.37d 7.74 8.03 8.31 8.60
8.0 4.99d 5.57d 6.18d 6.83d 7.21 7.48 7.74 8.00
8.2 4.63d 5.17d 5.74d 6.34d 6.73 6.97 7.21 7.45
8.4 4.31d 4.81d 5.34d 5.90d 6.28 6.50 6.72 6.94
8.5 4.16d 4.64d 5.15d 5.69d 6.06 6.27 6.49 6.70 11
8.6 4.01d 4.48d 4.97d 5.50d 5.86 6.06 6.26 6.46
8.8 3.75d 4.18d 4.64d 5.13d 5.46 5.65 5.83 6.02
9.0 3.50d 3.91d 4.34d 4.80d 5.10 5.27 5.43 5.60
9.2 3.28d 3.66d 4.06d 4.49d 4.76 4.91 5.06 5.21
9.4 3.07d 3.43d 3.81d 4.21d 4.44 4.57 4.71 4.85
9.5 2.98d 3.32d 3.69d 4.08d 4.28 4.41 4.54 4.67
9.6 2.89d 3.22d 3.58d 3.95d 4.13 4.26 4.38 4.50
9.8 2.71d 3.03d 3.36d 3.72d 3.85 3.96 4.07 4.18
10.0 2.55d 2.85d 3.16d 3.49 3.59 3.68 3.78 3.88
10.2 2.41d 2.68d 2.98d 3.25 3.33 3.42 3.51 3.59
10.4 2.27d 2.53d 2.81d 3.02 3.10 3.17 3.25 3.33
10.5 2.21d 2.46d 2.73d 2.91 2.99 3.06 3.13 3.20
10.6 2.14d 2.39d 2.66d 2.81 2.88 2.94 3.01 3.07
10.8 2.03d 2.26d 2.51d 2.61 2.66 2.72 2.78 2.83
11.0 1.92d 2.14d 2.37 2.42 2.47 2.51 2.56 2.61
NOTES: 3. “d” next to values in Table indicates deflection controls due to specified
1. The “SLAB WEIGHT” is made up of the self weight of the steel deck, superimposed loads.
the reinforcing bar and the concrete slab, which has been accounted 4. For explanation of deflection parameters SLDP and SWDP, see page 6.
for in the load table for strength requirements only. 5. “SLAB THICKNESS” is measured from top of concrete to bottom
2. Shoring may be required. See maximum unshored span conditions of steel deck.
above to establish the number of shores required. Also, see page 4 6. Iu is the uncracked moment if inertia based on equivalent steel
for explanation of above maximum unshored span conditions. 7. Ic is the cracked moment if inertia based on equivalent steel
BASE STEEL DECK THICKNESS = 1.21 mm | NOMINAL REBAR DIAMETER = 10 mm
NORMAL DENSITY CONCRETE = 2400 kg/m3

SLAB WEIGHT (kPa) 2.45 2.69 2.92 3.16 3.39 3.63 3.87 4.10
CO M F LO R ® CO M P O S I T E S L A B LOA D TA B L E | S I - M E T R I C U N I T S

CONCRETE VOLUME (m3/10m2) 0.971 1.07 1.17 1.27 1.37 1.47 1.57 1.67
1) MAX. UNSHORED SPAN (mm) 5284 5122 4974 4838 4712 4596 4488 4387
2) MAX. UNSHORED SPAN (mm) 4585 4478 4377 4284 4196 4113 4035 3962
Iu x 106 mm4 63.3 70.9 78.9 87.6 96.9 107 118 130
Ic x 106 mm4 28.5 31.2 34.1 37.2 40.5 43.9 47.5 51.3
DEFL. PARAMETER (SLDP) 716 796 881 973 1071 1176 1289 1410
DEFL. PARAMETER (SWDP) 2.48 2.43 2.38 2.31 2.25 2.18 2.10 2.03
SLAB THICKNESS (mm) 260 270 280 290 300 310 320 330

SHORING SPAN (m) MAXIMUM SPECIFIED LOAD (kPa)


To be established 4.5 10.4 11.0 11.5 12.0 12.6 13.1 13.6 14.2
by the designer. 4.6 9.87 10.4 10.9 11.4 11.9 12.4 12.9 13.4
See notes below. 4.8 8.90 9.35 9.80 10.3 10.7 11.2 11.6 12.1
5.0 8.04 8.44 8.84 9.24 9.64 10.0 10.4 10.8
5.2 7.28 7.63 7.99 8.34 8.70 9.05 9.41 9.76
5.4 6.60 6.92 7.23 7.55 7.86 8.18 8.49 8.80
5.5 6.29 6.59 6.88 7.18 7.48 7.77 8.07 8.36
5.6 5.99 6.27 6.55 6.83 7.11 7.39 7.67 7.95
5.8 5.45 5.70 5.94 6.19 6.44 6.68 6.93 7.18
6.0 4.96 5.18 5.39 5.61 5.83 6.05 6.26 6.48
6.2 4.51 4.71 4.90 5.09 5.28 5.47 5.66 5.85
6.4 4.11 4.28 4.45 4.61 4.78 4.95 5.12 5.28
6.5 3.92 4.08 4.24 4.39 4.55 4.71 4.86 5.02
6.6 3.74 3.89 4.04 4.18 4.33 4.47 4.62 4.76
6.8 3.41 3.53 3.66 3.79 3.91 4.04 4.16 4.29
7.0 3.10 3.21 3.32 3.42 3.53 3.64 3.75 3.86
7.2 2.82 2.91 3.00 3.09 3.18 3.28 3.37 3.46
7.4 2.56 2.64 2.71 2.79 2.86 2.94 3.02 3.09
12 7.5 2.44 2.51 2.58 2.64 2.71 2.78 2.85 2.92
7.6 2.32 2.38 2.44 2.51 2.57 2.63 2.69 2.75
7.8 2.10 2.15 2.20 2.25 2.29 2.34 2.39 2.44
8.0 1.89 1.93 1.97 2.00 2.04 2.08 2.11 2.15

NOTES: 3. “d” next to values in Table indicates deflection controls due to specified
1. The “SLAB WEIGHT” is made up of the self weight of the steel deck, superimposed loads.
the reinforcing bar and the concrete slab, which has been accounted 4. For explanation of deflection parameters SLDP and SWDP, see page 6.
for in the load table for strength requirements only. 5. “SLAB THICKNESS” is measured from top of concrete to bottom
2. Shoring may be required. See maximum unshored span conditions of steel deck.
above to establish the number of shores required. Also, see page 4 6. Iu is the uncracked moment if inertia based on equivalent steel
for explanation of above maximum unshored span conditions. 7. Ic is the cracked moment if inertia based on equivalent steel
BASE STEEL DECK THICKNESS = 1.21 mm | NOMINAL REBAR DIAMETER = 15 mm
NORMAL DENSITY CONCRETE = 2400 kg/m3

SLAB WEIGHT (kPa) 2.47 2.70 2.94 3.17 3.41 3.64 3.88 4.11

CO M F LO R ® CO M P O S I T E S L A B LOA D TA B L E | S I - M E T R I C U N I T S
CONCRETE VOLUME (m3/10m2) 0.971 1.07 1.17 1.27 1.37 1.47 1.57 1.67
1) MAX. UNSHORED SPAN (mm) 5275 5114 4966 4831 4706 4590 4482 4382
2) MAX. UNSHORED SPAN (mm) 4579 4472 4372 4279 4191 4109 4031 3958
Iu x 106 mm4 65.9 73.7 82.0 91.0 101 111 122 134
Ic x 106 mm4 32.5 35.7 39.1 42.6 46.4 50.4 54.6 59.0
DEFL. PARAMETER (SLDP) 767 853 944 1042 1147 1258 1378 1506
DEFL. PARAMETER (SWDP) 2.40 2.35 2.30 2.24 2.17 2.10 2.04 1.97
SLAB THICKNESS (mm) 260 270 280 290 300 310 320 330

SHORING SPAN (m) MAXIMUM SPECIFIED LOAD (kPa)


To be established 4.5 13.2 13.9 14.6 15.3 15.9 16.6 17.3 18.0
by the designer. 4.6 12.5 13.2 13.8 14.5 15.1 15.8 16.4 17.1
See notes below. 4.8 11.3 11.9 12.5 13.1 13.7 14.2 14.8 15.4
5.0 10.3 10.8 11.3 11.9 12.4 12.9 13.4 13.9
5.2 9.36 9.82 10.3 10.8 11.2 11.7 12.2 12.6
5.4 8.53 8.94 9.36 9.78 10.2 10.6 11.0 11.5
5.5 8.15 8.54 8.94 9.33 9.73 10.1 10.5 10.9
5.6 7.78 8.16 8.53 8.91 9.28 9.66 10.0 10.4
5.8 7.12 7.45 7.79 8.12 8.46 8.80 9.13 9.47
6.0 6.52 6.82 7.12 7.42 7.72 8.02 8.32 8.62
6.2 5.97 6.24 6.51 6.78 7.05 7.32 7.59 7.86
6.4 5.48 5.72 5.96 6.20 6.44 6.68 6.92 7.16
6.5 5.25 5.48 5.70 5.93 6.16 6.39 6.61 6.84
6.6 5.03 5.24 5.46 5.67 5.89 6.10 6.32 6.53
6.8 4.62 4.81 5.00 5.19 5.38 5.57 5.76 5.95
7.0 4.24 4.41 4.58 4.75 4.92 5.09 5.26 5.43
7.2 3.90 4.05 4.20 4.34 4.49 4.64 4.79 4.94
7.4 3.58 3.71 3.84 3.97 4.10 4.23 4.36 4.49
7.5 3.43 3.55 3.67 3.80 3.92 4.04 4.16 4.28 13
7.6 3.29 3.40 3.51 3.63 3.74 3.86 3.97 4.08
7.8 3.02 3.11 3.21 3.31 3.41 3.51 3.60 3.70
8.0 2.77 2.85 2.93 3.02 3.10 3.18 3.27 3.35
8.2 2.53 2.60 2.67 2.74 2.81 2.88 2.95 3.02
8.4 2.32 2.38 2.43 2.49 2.55 2.61 2.66 2.72
8.5 2.22 2.27 2.32 2.37 2.42 2.47 2.53 2.58

NOTES: 3. “d” next to values in Table indicates deflection controls due to specified
1. The “SLAB WEIGHT” is made up of the self weight of the steel deck, superimposed loads.
the reinforcing bar and the concrete slab, which has been accounted 4. For explanation of deflection parameters SLDP and SWDP, see page 6.
for in the load table for strength requirements only. 5. “SLAB THICKNESS” is measured from top of concrete to bottom
2. Shoring may be required. See maximum unshored span conditions of steel deck.
above to establish the number of shores required. Also, see page 4 6. Iu is the uncracked moment if inertia based on equivalent steel
for explanation of above maximum unshored span conditions. 7. Ic is the cracked moment if inertia based on equivalent steel
BASE STEEL DECK THICKNESS = 1.21 mm | NOMINAL REBAR DIAMETER = 20 mm
NORMAL DENSITY CONCRETE = 2400 kg/m3

SLAB WEIGHT (kPa) 2.48 2.71 2.95 3.18 3.42 3.66 3.89 4.13
CO M F LO R ® CO M P O S I T E S L A B LOA D TA B L E | S I - M E T R I C U N I T S

CONCRETE VOLUME (m3/10m2) 0.971 1.07 1.17 1.27 1.37 1.47 1.57 1.67
1) MAX. UNSHORED SPAN (mm) 5266 5106 4959 4824 4699 4584 4477 4377
2) MAX. UNSHORED SPAN (mm) 4573 4467 4367 4274 4187 4105 4027 3954
Iu x 106 mm4 68.1 76.2 84.9 94.1 104 115 126 139
Ic x 106 mm4 36.1 39.7 43.5 47.5 51.7 56.2 60.9 65.8
DEFL. PARAMETER (SLDP) 813 904 1000 1104 1215 1333 1459 1593
DEFL. PARAMETER (SWDP) 2.33 2.28 2.23 2.17 2.11 2.04 1.98 1.91
SLAB THICKNESS (mm) 260 270 280 290 300 310 320 330

SHORING SPAN (m) MAXIMUM SPECIFIED LOAD (kPa)


To be established 4.5 15.8 16.6 17.4 18.3 19.1 19.9 20.8 21.6
by the designer. 4.6 15.0 15.8 16.6 17.4 18.2 18.9 19.7 20.5
See notes below. 4.8 13.6 14.3 15.0 15.7 16.4 17.2 17.9 18.6
5.0 12.4 13.0 13.7 14.3 14.9 15.6 16.2 16.8
5.2 11.3 11.9 12.4 13.0 13.6 14.2 14.7 15.3
5.4 10.3 10.8 11.4 11.9 12.4 12.9 13.4 13.9
5.5 9.88 10.4 10.9 11.4 11.8 12.3 12.8 13.3
5.6 9.45 9.92 10.4 10.9 11.3 11.8 12.3 12.7
5.8 8.67 9.10 9.52 9.94 10.4 10.8 11.2 11.6
6.0 7.97 8.35 8.73 9.11 9.50 9.88 10.3 10.6
6.2 7.33 7.68 8.02 8.37 8.71 9.06 9.40 9.75
6.4 6.75 7.07 7.38 7.69 8.00 8.31 8.62 8.94
6.5 6.49 6.78 7.08 7.37 7.67 7.97 8.26 8.56
6.6 6.23 6.51 6.79 7.07 7.35 7.63 7.92 8.20
6.8 5.75 6.00 6.25 6.51 6.76 7.02 7.27 7.52
7.0 5.31 5.54 5.76 5.99 6.22 6.45 6.68 6.90
7.2 4.90 5.11 5.31 5.52 5.72 5.93 6.13 6.34
7.4 4.53 4.72 4.90 5.08 5.27 5.45 5.63 5.82
14 7.5 4.36 4.53 4.70 4.88 5.05 5.22 5.40 5.57
7.6 4.19 4.35 4.52 4.68 4.84 5.01 5.17 5.34
7.8 3.87 4.02 4.16 4.31 4.46 4.60 4.75 4.89
8.0 3.58 3.71 3.84 3.97 4.09 4.22 4.35 4.48
8.2 3.31 3.42 3.53 3.65 3.76 3.87 3.99 4.10
8.4 3.05 3.15 3.25 3.35 3.45 3.55 3.65 3.74
8.5 2.93 3.03 3.12 3.21 3.30 3.39 3.48 3.58
8.6 2.82 2.90 2.99 3.07 3.16 3.24 3.33 3.41
8.8 2.60 2.67 2.74 2.82 2.89 2.96 3.03 3.11
9.0 2.39 2.46 2.52 2.58 2.64 2.70 2.76 2.82

NOTES: 3. “d” next to values in Table indicates deflection controls due to specified
1. The “SLAB WEIGHT” is made up of the self weight of the steel deck, superimposed loads.
the reinforcing bar and the concrete slab, which has been accounted 4. For explanation of deflection parameters SLDP and SWDP, see page 6.
for in the load table for strength requirements only. 5. “SLAB THICKNESS” is measured from top of concrete to bottom
2. Shoring may be required. See maximum unshored span conditions of steel deck.
above to establish the number of shores required. Also, see page 4 6. Iu is the uncracked moment if inertia based on equivalent steel
for explanation of above maximum unshored span conditions. 7. Ic is the cracked moment if inertia based on equivalent steel
BASE STEEL DECK THICKNESS = 1.21 mm | NOMINAL REBAR DIAMETER = 25 mm
NORMAL DENSITY CONCRETE = 2400 kg/m3

SLAB WEIGHT (kPa) 2.50 2.74 2.97 3.21 3.45 3.68 3.92 4.15

CO M F LO R ® CO M P O S I T E S L A B LOA D TA B L E | S I - M E T R I C U N I T S
CONCRETE VOLUME (m3/10m2) 0.971 1.07 1.17 1.27 1.37 1.47 1.57 1.67
1) MAX. UNSHORED SPAN (mm) 5248 5089 4944 4810 4687 4572 4466 4366
2) MAX. UNSHORED SPAN (mm) 4561 4456 4357 4265 4178 4096 4019 3946
Iu x 106 mm4 72.3 80.9 90.2 100 111 122 134 147
Ic x 106 mm4 42.7 47.0 51.6 56.5 61.6 67.1 72.8 78.7
DEFL. PARAMETER (SLDP) 896 997 1105 1220 1342 1472 1611 1758
DEFL. PARAMETER (SWDP) 2.22 2.17 2.12 2.06 2.00 1.94 1.88 1.81
SLAB THICKNESS (mm) 260 270 280 290 300 310 320 330

SHORING SPAN (m) MAXIMUM SPECIFIED LOAD (kPa)


To be established 4.5 21.3 22.4 23.5 24.7 25.8 26.9 28.0 29.2
by the designer. 4.6 20.3 21.4 22.4 23.5 24.6 25.6 26.7 27.8
See notes below. 4.8 18.5 19.4 20.4 21.4 22.3 23.3 24.3 25.2
5.0 16.9 17.7 18.6 19.5 20.3 21.2 22.1 23.0
5.2 15.4 16.2 17.0 17.8 18.6 19.4 20.2 21.0
5.4 14.2 14.9 15.6 16.3 17.0 17.8 18.5 19.2
5.5 13.6 14.3 14.9 15.6 16.3 17.0 17.7 18.4
5.6 13.0 13.7 14.3 15.0 15.6 16.3 17.0 17.6
5.8 12.0 12.6 13.2 13.8 14.4 15.0 15.6 16.2
6.0 11.1 11.6 12.2 12.7 13.3 13.8 14.3 14.9
6.2 10.2 10.7 11.2 11.7 12.2 12.7 13.2 13.7
6.4 9.47 9.93 10.4 10.8 11.3 11.8 12.2 12.7
6.5 9.05d 9.55 9.99 10.4 10.9 11.3 11.7 12.2
6.6 8.65d 9.20 9.62 10.0 10.5 10.9 11.3 11.7
6.8 7.91d 8.53 8.91 9.30 9.68 10.1 10.4 10.8
7.0 7.25d 7.92 8.27 8.62 8.97 9.32 9.67 10.0
7.2 6.66d 7.36 7.68 8.00 8.32 8.64 8.96 9.28
7.4 6.14d 6.83d 7.14 7.43 7.73 8.02 8.31 8.60
7.5 5.89d 6.56d 6.89 7.17 7.45 7.73 8.00 8.28 15
7.6 5.66d 6.31d 6.64 6.91 7.18 7.44 7.71 7.98
7.8 5.24d 5.83d 6.18 6.42 6.67 6.91 7.15 7.40
8.0 4.86d 5.41d 5.75 5.97 6.20 6.42 6.64 6.86
8.2 4.51d 5.02d 5.36 5.56 5.76 5.96 6.16 6.36
8.4 4.20d 4.67d 4.99 5.17 5.35 5.54 5.72 5.90
8.5 4.05d 4.51d 4.81 4.99 5.16 5.34 5.51 5.68
8.6 3.91d 4.35d 4.64 4.81 4.98 5.14 5.31 5.47
8.8 3.65d 4.06d 4.32 4.47 4.62 4.77 4.92 5.07
9.0 3.41d 3.80d 4.03 4.16 4.29 4.43 4.56 4.70
9.2 3.19d 3.55d 3.75 3.87 3.99 4.11 4.23 4.35
9.4 2.99d 3.33d 3.48 3.59 3.70 3.80 3.91 4.02
9.5 2.90d 3.23d 3.36 3.46 3.56 3.66 3.76 3.86
9.6 2.81d 3.13d 3.24 3.33 3.43 3.52 3.61 3.71
9.8 2.64d 2.92 3.01 3.09 3.17 3.25 3.34 3.42
10.0 2.49d 2.72 2.79 2.86 2.93 3.00 3.08 3.15
NOTES: 3. “d” next to values in Table indicates deflection controls due to specified
1. The “SLAB WEIGHT” is made up of the self weight of the steel deck, superimposed loads.
the reinforcing bar and the concrete slab, which has been accounted 4. For explanation of deflection parameters SLDP and SWDP, see page 6.
for in the load table for strength requirements only. 5. “SLAB THICKNESS” is measured from top of concrete to bottom
2. Shoring may be required. See maximum unshored span conditions of steel deck.
above to establish the number of shores required. Also, see page 4 6. Iu is the uncracked moment if inertia based on equivalent steel
for explanation of above maximum unshored span conditions. 7. Ic is the cracked moment if inertia based on equivalent steel
BASE STEEL DECK THICKNESS = 1.21 mm | NOMINAL REBAR DIAMETER = 30 mm
NORMAL DENSITY CONCRETE = 2400 kg/m3

SLAB WEIGHT (kPa) 2.53 2.76 3.00 3.24 3.47 3.71 3.94 4.18
CO M F LO R ® CO M P O S I T E S L A B LOA D TA B L E | S I - M E T R I C U N I T S

CONCRETE VOLUME (m3/10m2) 0.971 1.07 1.17 1.27 1.37 1.47 1.57 1.67
1) MAX. UNSHORED SPAN (mm) 5230 5073 4929 4796 4674 4560 4455 4356
2) MAX. UNSHORED SPAN (mm) 4549 4445 4347 4255 4169 4088 4011 3939
Iu x 106 mm4 76.0 85.2 95.0 105 116 128 141 155
Ic x 106 mm4 48.4 53.5 58.9 64.5 70.5 76.9 83.5 90.5
DEFL. PARAMETER (SLDP) 970 1081 1199 1324 1458 1599 1750 1910
DEFL. PARAMETER (SWDP) 2.13 2.08 2.03 1.97 1.91 1.85 1.79 1.73
SLAB THICKNESS (mm) 260 270 280 290 300 310 320 330

SHORING SPAN (m) MAXIMUM SPECIFIED LOAD (kPa)


To be established 5.5 16.2d 17.3 18.2 19.1 20.0 20.9 21.8 22.7
by the designer. 5.6 15.3d 16.6 17.5 18.3 19.2 20.0 20.9 21.7
See notes below. 5.8 13.8d 15.4 16.1 16.9 17.7 18.5 19.2 20.0
6.0 12.5d 13.9d 14.9 15.6 16.3 17.1 17.8 18.5
6.2 11.3d 12.6d 13.8 14.5 15.1 15.8 16.4 17.1
6.4 10.3d 11.5d 12.7d 13.4 14.0 14.6 15.2 15.8
6.5 9.81d 10.9d 12.1d 12.9 13.5 14.1 14.7 15.2
6.6 9.37d 10.4d 11.6d 12.4 13.0 13.6 14.1 14.7
6.8 8.56d 9.54d 10.6d 11.6 12.1 12.6 13.1 13.6
7.0 7.85d 8.75d 9.70d 10.7d 11.2 11.7 12.2 12.7
7.2 7.22d 8.04d 8.92d 9.85d 10.5 10.9 11.3 11.8
7.4 6.65d 7.41d 8.21d 9.07d 9.75 10.2 10.6 11.0
7.5 6.38d 7.11d 7.89d 8.71d 9.41 9.8 10.2 10.6
7.6 6.13d 6.84d 7.58d 8.37d 9.09 9.46 9.83 10.2
7.8 5.67d 6.32d 7.01d 7.75d 8.48 8.83 9.17 9.51
8.0 5.26d 5.86d 6.50d 7.18d 7.90d 8.24 8.56 8.87
8.2 4.88d 5.44d 6.04d 6.67d 7.34d 7.69 7.98 8.28
8.4 4.54d 5.06d 5.62d 6.20d 6.83d 7.19 7.45 7.72
16 8.5 4.39d 4.89d 5.42d 5.99d 6.59d 6.95 7.20 7.46
8.6 4.23d 4.72d 5.23d 5.78d 6.36d 6.71 6.96 7.21
8.8 3.95d 4.40d 4.88d 5.39d 5.94d 6.27 6.50 6.73
9.0 3.69d 4.12d 4.57d 5.04d 5.55d 5.86 6.07 6.28
9.2 3.46d 3.85d 4.27d 4.72d 5.20d 5.48 5.67 5.86
9.4 3.24d 3.61d 4.01d 4.43d 4.87d 5.12 5.29 5.47
9.5 3.14d 3.50d 3.88d 4.29d 4.72d 4.94 5.11 5.28
9.6 3.04d 3.39d 3.76d 4.15d 4.57d 4.78 4.94 5.10
9.8 2.86d 3.19d 3.54d 3.91d 4.30d 4.46 4.61 4.75
10.0 2.69d 3.00d 3.33d 3.68d 4.03 4.16 4.29 4.42
10.2 2.54d 2.83d 3.14d 3.46d 3.76 3.88 4.00 4.12
10.4 2.39d 2.67d 2.96d 3.27d 3.51 3.61 3.72 3.83
10.5 2.33d 2.59d 2.87d 3.18d 3.39 3.49 3.59 3.69
10.6 2.26d 2.52d 2.79d 3.09d 3.27 3.36 3.46 3.56
10.8 2.14d 2.38d 2.64d 2.92d 3.04 3.13 3.21 3.30
11.0 2.02d 2.25d 2.50d 2.75 2.83 2.90 2.98 3.05
NOTES: 3. “d” next to values in Table indicates deflection controls due to specified
1. The “SLAB WEIGHT” is made up of the self weight of the steel deck, superimposed loads.
the reinforcing bar and the concrete slab, which has been accounted 4. For explanation of deflection parameters SLDP and SWDP, see page 6.
for in the load table for strength requirements only. 5. “SLAB THICKNESS” is measured from top of concrete to bottom
2. Shoring may be required. See maximum unshored span conditions of steel deck.
above to establish the number of shores required. Also, see page 4 6. Iu is the uncracked moment if inertia based on equivalent steel
for explanation of above maximum unshored span conditions. 7. Ic is the cracked moment if inertia based on equivalent steel
CO M F LO R ® CO M P O S I T E S L A B LOA D TA B L E – I M P E R I A L U N I T S

BASE STEEL DECK THICKNESS = 0.0378 in. | NOMINAL REBAR DIAMETER = 10 mm


NORMAL DENSITY CONCRETE = 150 lb/ft3

CO M F LO R ® CO M P O S I T E S L A B LOA D TA B L E | I M P E R I A L U N I T S
SLAB WEIGHT (psf) 53.9 60.2 66.4 72.7 78.9 85.2 91.4 97.7
CONCRETE VOLUME (yd3/100ft2) 1.26 1.42 1.57 1.72 1.88 2.03 2.19 2.34
1) MAX. UNSHORED SPAN (ft) 13.2 12.6 12.1 11.7 11.3 10.9 10.6 10.3
2) MAX. UNSHORED SPAN (ft) 11.5 11.2 10.9 10.6 10.3 10.1 9.9 9.6
Iu (in.4) 47.4 54.5 62.3 70.8 80.3 90.7 102.1 114.7
Ic (in.4) 19.0 21.3 23.7 26.3 29.1 32.0 35.1 38.3
DEFL. PARAMETER (SLDP) 521 595 675 763 858 963 1077 1201
DEFL. PARAMETER (SWDP) 0.870 0.844 0.815 0.784 0.751 0.718 0.684 0.651
SLAB THICKNESS (in.) 10.5 11.0 11.5 12.0 12.5 13.0 13.5 14.0

SHORING SPAN (ft) MAXIMUM SPECIFIED LOAD (psf)


To be established 14.0 205 217 228 240 251 263 275 286
by the designer. 14.5 188 199 209 220 230 240 251 261
See notes below. 15.0 173 182 192 201 211 220 229 239
15.5 159 168 176 185 193 202 210 218
16.0 147 154 162 169 177 185 192 200
16.5 135 142 149 156 163 169 176 183
17.0 125 131 137 143 149 156 162 168
17.5 115 121 126 132 137 143 148 154
18.0 106 111 116 121 126 131 136 141
18.5 98 103 107 112 116 120 125 129
19.0 91 95 99 103 106 110 114 118
19.5 84 87 91 94 98 101 105 108
20.0 78 81 84 87 90 93 96 99
20.5 72 74 77 80 82 85 87 90
21.0 66 68 71 73 75 77 80 82
21.5 61 63 65 67 69 71 73 74
22.0 56 58 60 61 63 64 66 67
22.5 52 53 54 56 57 58 60 61 17
23.0 48 49 50 51 52 53 54 55

NOTES: 3. “d” next to values in Table indicates deflection controls due to specified
1. The “SLAB WEIGHT” is made up of the self weight of the steel deck, superimposed loads.
the reinforcing bar and the concrete slab, which has been accounted 4. For explanation of deflection parameters SLDP and SWDP, see page 6.
for in the load table for strength requirements only. 5. “SLAB THICKNESS” is measured from top of concrete to bottom
2. Shoring may be required. See maximum unshored span conditions of steel deck.
above to establish the number of shores required. Also, see page 4 6. Iu is the uncracked moment if inertia based on equivalent steel
for explanation of above maximum unshored span conditions. 7. Ic is the cracked moment if inertia based on equivalent steel
BASE STEEL DECK THICKNESS = 0.0378 in. | NOMINAL REBAR DIAMETER = 15 mm
NORMAL DENSITY CONCRETE = 150 lb/ft3

SLAB WEIGHT (psf) 54.2 60.4 66.7 72.9 79.2 85.4 91.7 97.9
CO M F LO R ® CO M P O S I T E S L A B LOA D TA B L E | I M P E R I A L U N I T S

CONCRETE VOLUME (yd3/100ft2) 1.26 1.42 1.57 1.72 1.88 2.03 2.19 2.34
1) MAX. UNSHORED SPAN (ft) 13.2 12.6 12.1 11.7 11.3 10.9 10.6 10.3
2) MAX. UNSHORED SPAN (ft) 11.5 11.1 10.8 10.6 10.3 10.1 9.80 9.60
Iu (in.4) 49.4 56.8 64.9 73.7 83.5 94.2 105.90 118.80
Ic (in.4) 22.3 25.0 28.0 31.1 34.4 37.9 41.60 45.40
DEFL. PARAMETER (SLDP) 563 643 729 823 925 1037 1158 1290
DEFL. PARAMETER (SWDP) 0.838 0.813 0.786 0.756 0.725 0.693 0.661 0.630
SLAB THICKNESS (in.) 10.5 11.0 11.5 12.0 12.5 13.0 13.5 14.0

SHORING SPAN (ft) MAXIMUM SPECIFIED LOAD (psf)


To be established 14.0 273 289 305 321 337 353 369 385
by the designer. 14.5 252 266 281 295 310 324 339 353
See notes below. 15.0 232 245 259 272 285 298 311 325
15.5 215 227 239 251 263 275 287 299
16.0 199 210 221 232 243 254 265 275
16.5 184 194 204 214 224 234 244 254
17.0 171 180 189 198 207 216 226 235
17.5 159 167 175 184 192 200 209 217
18.0 147 155 163 170 178 185 193 201
18.5 137 144 151 158 165 172 179 185
19.0 128 134 140 147 153 159 165 172
19.5 119 125 130 136 142 147 153 159
20.0 111 116 121 126 131 137 142 147
20.5 103 108 113 117 122 127 131 136
21.0 96 101 105 109 113 117 121 126
21.5 90 94 97 101 105 109 112 116
22.0 84 87 90 94 97 101 104 107
22.5 78 81 84 87 90 93 96 99
18 23.0 73 75 78 81 83 86 89 91
23.5 68 70 72 75 77 79 82 84
24.0 63 65 67 69 71 73 75 77
24.5 59 61 62 64 66 67 69 71
25.0 55 56 58 59 60 62 63 65
25.5 51 52 53 54 55 57 58 59
26.0 47 48 49 50 51 52 53 54

NOTES: 3. “d” next to values in Table indicates deflection controls due to specified
1. The “SLAB WEIGHT” is made up of the self weight of the steel deck, superimposed loads.
the reinforcing bar and the concrete slab, which has been accounted 4. For explanation of deflection parameters SLDP and SWDP, see page 6.
for in the load table for strength requirements only. 5. “SLAB THICKNESS” is measured from top of concrete to bottom
2. Shoring may be required. See maximum unshored span conditions of steel deck.
above to establish the number of shores required. Also, see page 4 6. Iu is the uncracked moment if inertia based on equivalent steel
for explanation of above maximum unshored span conditions. 7. Ic is the cracked moment if inertia based on equivalent steel
BASE STEEL DECK THICKNESS = 0.0378 in. | NOMINAL REBAR DIAMETER = 20 mm
NORMAL DENSITY CONCRETE = 150 lb/ft3

SLAB WEIGHT (psf) 54.4 60.7 66.9 73.2 79.4 85.7 91.9 98.2

CO M F LO R ® CO M P O S I T E S L A B LOA D TA B L E | I M P E R I A L U N I T S
CONCRETE VOLUME (yd3/100ft2) 1.26 1.42 1.57 1.72 1.88 2.03 2.19 2.34
1) MAX. UNSHORED SPAN (ft) 13.1 12.6 12.1 11.7 11.3 10.9 10.6 10.3
2) MAX. UNSHORED SPAN (ft) 11.5 11.1 10.8 10.6 10.3 10.1 9.80 9.60
Iu (in.4) 51.2 58.9 67.3 76.4 86.4 97.4 109.50 122.70
Ic (in.4) 25.3 28.4 31.7 35.3 39.1 43.1 47.40 51.90
DEFL. PARAMETER (SLDP) 601 685 777 877 986 1104 1232 1371
DEFL. PARAMETER (SWDP) 0.812 0.787 0.761 0.732 0.702 0.672 0.642 0.612
SLAB THICKNESS (in.) 10.5 11.0 11.5 12.0 12.5 13.0 13.5 14.0

SHORING SPAN (ft) MAXIMUM SPECIFIED LOAD (psf)


To be established 14.0 337 357 377 397 418 438 458 478
by the designer. 14.5 311 329 348 366 385 403 422 440
See notes below. 15.0 288 305 321 338 355 372 389 406
15.5 266 282 297 313 328 344 359 375
16.0 247 262 276 290 304 318 333 347
16.5 230 243 256 269 282 295 308 321
17.0 214 226 238 250 262 274 286 298
17.5 199 210 221 232 243 254 265 276
18.0 186 196 206 216 226 237 247 257
18.5 174 183 192 201 211 220 229 239
19.0 162 171 179 188 196 205 214 222
19.5 152 160 167 175 183 191 199 207
20.0 142 149 156 164 171 178 185 192
20.5 133 140 146 153 159 166 173 179
21.0 125 131 137 143 149 155 161 167
21.5 117 122 128 133 139 144 150 156
22.0 109 114 120 125 130 135 140 145
22.5 103 107 112 116 121 126 130 135
23.0 96 100 105 109 113 117 121 126 19
23.5 90 94 98 102 105 109 113 117
24.0 85 88 92 95 98 102 105 109
24.5 79 83 86 89 92 95 98 101
25.0 74 77 80 83 85 88 91 94
25.5 70 72 75 77 80 82 84 87
26.0 65 68 70 72 74 76 78 80
26.5 61 63 65 67 69 71 73 74
27.0 57 59 61 62 64 65 67 69
27.5 54 55 56 58 59 61 62 63
28.0 50 51 52 54 55 56 57 58
28.5 47 48 49 50 51 51 52 53
29.0 44 44 45 46 47 47 48 49

NOTES: 3. “d” next to values in Table indicates deflection controls due to specified
1. The “SLAB WEIGHT” is made up of the self weight of the steel deck, superimposed loads.
the reinforcing bar and the concrete slab, which has been accounted 4. For explanation of deflection parameters SLDP and SWDP, see page 6.
for in the load table for strength requirements only. 5. “SLAB THICKNESS” is measured from top of concrete to bottom
2. Shoring may be required. See maximum unshored span conditions of steel deck.
above to establish the number of shores required. Also, see page 4 6. Iu is the uncracked moment if inertia based on equivalent steel
for explanation of above maximum unshored span conditions. 7. Ic is the cracked moment if inertia based on equivalent steel
BASE STEEL DECK THICKNESS = 0.0378 in. | NOMINAL REBAR DIAMETER = 25 mm
NORMAL DENSITY CONCRETE = 150 lb/ft3

SLAB WEIGHT (psf) 55.0 61.2 67.5 73.7 80.0 86.2 92.5 98.7
CO M F LO R ® CO M P O S I T E S L A B LOA D TA B L E | I M P E R I A L U N I T S

CONCRETE VOLUME (yd3/100ft2) 1.26 1.42 1.57 1.72 1.88 2.03 2.19 2.34
1) MAX. UNSHORED SPAN (ft) 13.1 12.5 12.1 11.6 11.2 10.9 10.6 10.3
2) MAX. UNSHORED SPAN (ft) 11.4 11.1 10.8 10.5 10.3 10.0 9.80 9.60
Iu (in.4) 54.7 62.9 71.8 81.5 92.0 103.6 116.30 130.10
Ic (in.4) 30.6 34.5 38.7 43.2 47.9 53.0 58.30 63.90
DEFL. PARAMETER (SLDP) 669 765 867 979 1099 1230 1371 1523
DEFL. PARAMETER (SWDP) 0.769 0.744 0.719 0.692 0.664 0.636 0.608 0.580
SLAB THICKNESS (in.) 10.5 11.0 11.5 12.0 12.5 13.0 13.5 14.0

SHORING SPAN (ft) MAXIMUM SPECIFIED LOAD (psf)

To be established 16.0 342 363 384 405 426 446 467 488
by the designer. 16.5 319 338 358 377 396 415 435 454
See notes below. 17.0 298 316 334 351 369 387 405 423
17.5 278 295 312 328 345 361 378 394
18.0 261 276 291 307 322 338 353 368
18.5 244 259 273 287 301 316 330 344
19.0 229 243 256 269 282 296 309 322
19.5 215 228 240 252 265 277 289 302
20.0 202 214 225 237 248 260 271 283
20.5 191 201 212 222 233 244 254 265
21.0 179 189 199 209 219 229 239 249
21.5 169 178 187 197 206 215 224 234
22.0 159 168 177 185 194 202 211 219
22.5 150 158 166 174 182 190 198 206
23.0 142 149 157 164 172 179 186 194
23.5 134 141 148 155 161 168 175 182
24.0 127 133 139 146 152 158 165 171
24.5 120 126 131 137 143 149 155 161
20 25.0 113 119 124 129 135 140 146 151
25.5 107 112 117 122 127 132 137 142
26.0 101 106 110 115 120 124 129 134
26.5 96 100 104 108 113 117 121 126
27.0 90 94 98 102 106 110 114 118
27.5 86 89 93 96 100 104 107 111
28.0 81 84 87 91 94 97 101 104
28.5 76 79 82 85 88 91 94 97
29.0 72 75 78 80 83 86 89 91
29.5 68 71 73 76 78 81 83 85
30.0 65 67 69 71 73 76 78 80
30.5 61 63 65 67 69 71 73 75
31.0 58 59 61 63 64 66 68 70
31.5 54 56 57 59 60 62 63 65
32.0 51 52 54 55 56 58 59 60
32.5 48 49 50 52 53 54 55 56
33.0 45 46 47 48 49 50 51 52
NOTES: 3. “d” next to values in Table indicates deflection controls due to specified
1. The “SLAB WEIGHT” is made up of the self weight of the steel deck, superimposed loads.
the reinforcing bar and the concrete slab, which has been accounted 4. For explanation of deflection parameters SLDP and SWDP, see page 6.
for in the load table for strength requirements only. 5. “SLAB THICKNESS” is measured from top of concrete to bottom
2. Shoring may be required. See maximum unshored span conditions of steel deck.
above to establish the number of shores required. Also, see page 4 6. Iu is the uncracked moment if inertia based on equivalent steel
for explanation of above maximum unshored span conditions. 7. Ic is the cracked moment if inertia based on equivalent steel
BASE STEEL DECK THICKNESS = 0.0378 in. | NOMINAL REBAR DIAMETER = 30 mm
NORMAL DENSITY CONCRETE = 150 lb/ft3

SLAB WEIGHT (psf) 55.5 61.8 68.0 74.3 80.5 86.8 93.0 99.3

CO M F LO R ® CO M P O S I T E S L A B LOA D TA B L E | I M P E R I A L U N I T S
CONCRETE VOLUME (yd3/100ft2) 1.26 1.42 1.57 1.72 1.88 2.03 2.19 2.34
1) MAX. UNSHORED SPAN (ft) 13.1 12.5 12.0 11.6 11.2 10.8 10.5 10.2
2) MAX. UNSHORED SPAN (ft) 11.4 11.1 10.8 10.5 10.3 10.0 9.80 9.60
Iu (in.4) 57.7 66.4 75.9 86.1 97.3 109.4 122.60 137.10
Ic (in.4) 35.4 40.0 45.0 50.3 55.9 61.9 68.30 75.00
DEFL. PARAMETER (SLDP) 731 836 949 1071 1203 1345 1499 1665
DEFL. PARAMETER (SWDP) 0.735 0.710 0.685 0.659 0.633 0.606 0.580 0.553
SLAB THICKNESS (in.) 10.5 11.0 11.5 12.0 12.5 13.0 13.5 14.0

SHORING SPAN (ft) MAXIMUM SPECIFIED LOAD (psf)


To be established 18.0 332 352 373 394 415 435 456 477
by the designer. 18.5 312 331 350 370 389 408 428 447
See notes below. 19.0 293 311 329 347 365 383 401 419
19.5 273d 293 310 326 343 360 377 394
20.0 253d 276 292 307 323 339 355 370
20.5 235d 260 275 290 304 319 334 349
21.0 219d 245 259 273 287 301 314 328
21.5 204d 232 245 258 271 283 296 309
22.0 190d 218d 231 243 255 267 280 292
22.5 178d 204d 218 230 241 253 264 275
23.0 167d 191d 207 217 228 239 249 260
23.5 156d 179d 196 206 216 225 235 245
24.0 147d 168d 185 194 204 213 223 232
24.5 138d 158d 175 184 193 202 210 219
25.0 130d 148d 166 174 183 191 199 207
25.5 122d 140d 158 165 173 181 188 196
26.0 115d 132d 149 157 164 171 178 185
26.5 109d 125d 141d 148 155 162 169 175
27.0 103d 118d 134d 141 147 153 160 166
27.5 97d 111d 127d 133 139 145 151 157
28.0 92d 106d 120d 126 132 137 143 148
21
28.5 88d 100d 114d 120 125 130 135 140
29.0 83d 95d 108d 114 118 123 128 133
29.5 79d 90d 103d 108 112 117 121 126
30.0 75d 86d 97d 102 106 110 115 119
30.5 71d 82d 93d 97 101 104 108 112
31.0 68d 78d 88 92 95 99 102 106
31.5 65d 74d 84 87 90 93 97 100
32.0 62d 71d 79 82 85 88 91 94
32.5 59d 68d 75 78 81 83 86 89
33.0 56d 65d 71 74 76 79 81 84
33.5 54d 62d 67 70 72 74 77 79
34.0 52d 59d 64 66 68 70 72 74
34.5 49d 56d 60 62 64 66 68 70
35.0 47d 54d 57 59 60 62 64 65
35.5 45d 52d 54 55 57 58 60 61
36.0 43d 50 51 52 53 55 56 57
NOTES: 3. “d” next to values in Table indicates deflection controls due to specified
1. The “SLAB WEIGHT” is made up of the self weight of the steel deck, superimposed loads.
the reinforcing bar and the concrete slab, which has been accounted 4. For explanation of deflection parameters SLDP and SWDP, see page 6.
for in the load table for strength requirements only. 5. “SLAB THICKNESS” is measured from top of concrete to bottom
2. Shoring may be required. See maximum unshored span conditions of steel deck.
above to establish the number of shores required. Also, see page 4 6. Iu is the uncracked moment if inertia based on equivalent steel
for explanation of above maximum unshored span conditions. 7. Ic is the cracked moment if inertia based on equivalent steel
BASE STEEL DECK THICKNESS = 0.0476 in. | NOMINAL REBAR DIAMETER = 10 mm
NORMAL DENSITY CONCRETE = 150 lb/ft3

SLAB WEIGHT (psf) 54.6 60.8 67.1 73.3 79.6 85.8 92.1 98.3
CO M F LO R ® CO M P O S I T E S L A B LOA D TA B L E | I M P E R I A L U N I T S

CONCRETE VOLUME (yd3/100ft2) 1.26 1.42 1.57 1.72 1.88 2.03 2.19 2.34
1) MAX. UNSHORED SPAN (ft) 17.0 16.4 15.8 15.3 14.8 14.4 14.0 13.6
2) MAX. UNSHORED SPAN (ft) 14.8 14.4 14.0 13.6 13.3 13.0 12.7 12.4
Iu (in.4) 50.0 57.4 65.5 74.4 84.2 95.0 107 120
Ic (in.4) 22.2 24.9 27.8 30.8 34.1 37.6 41.4 45.3
DEFL. PARAMETER (SLDP) 567 646 732 827 929 1042 1164 1297
DEFL. PARAMETER (SWDP) 0.834 0.809 0.782 0.753 0.722 0.690 0.658 0.627
SLAB THICKNESS (in.) 10.5 11.0 11.5 12.0 12.5 13.0 13.5 14.0

SHORING SPAN (ft) MAXIMUM SPECIFIED LOAD (psf)


To be established 14.0 254 271 287 304 320 337 353 369
by the designer. 14.5 234 249 264 279 294 309 324 339
See notes below. 15.0 216 229 243 257 270 284 298 311
15.5 199 211 224 236 249 261 274 286
16.0 184 195 207 218 230 241 252 264
16.5 170 181 191 201 212 222 233 243
17.0 158 167 177 186 196 205 215 224
17.5 146 155 164 172 181 190 198 207
18.0 136 144 152 160 167 175 183 191
18.5 126 133 141 148 155 162 169 177
19.0 117 124 130 137 143 150 157 163
19.5 109 115 121 127 133 139 145 151
20.0 101 107 112 118 123 128 134 139
20.5 94 99 104 109 114 119 124 129
21.0 88 92 97 101 105 110 114 119
21.5 82 86 90 94 98 101 105 109
22.0 76 79 83 87 90 94 97 101
22.5 71 74 77 80 83 86 90 93
22 23.0 66 68 71 74 77 80 82 85
23.5 61 63 66 68 71 73 76 78
24.0 56 59 61 63 65 67 69 72
24.5 52 54 56 58 60 62 64 65
25.0 48 50 52 53 55 56 58 60
25.5 45 46 47 49 50 51 53 54
26.0 41 42 44 45 46 47 48 49

NOTES: 3. “d” next to values in Table indicates deflection controls due to specified
1. The “SLAB WEIGHT” is made up of the self weight of the steel deck, superimposed loads.
the reinforcing bar and the concrete slab, which has been accounted 4. For explanation of deflection parameters SLDP and SWDP, see page 6.
for in the load table for strength requirements only. 5. “SLAB THICKNESS” is measured from top of concrete to bottom
2. Shoring may be required. See maximum unshored span conditions of steel deck.
above to establish the number of shores required. Also, see page 4 6. Iu is the uncracked moment if inertia based on equivalent steel
for explanation of above maximum unshored span conditions. 7. Ic is the cracked moment if inertia based on equivalent steel
BASE STEEL DECK THICKNESS = 0.0476 in. | NOMINAL REBAR DIAMETER = 15 mm
NORMAL DENSITY CONCRETE = 150 lb/ft3

SLAB WEIGHT (psf) 54.8 61.1 67.3 73.6 79.8 86.1 92.3 98.6

CO M F LO R ® CO M P O S I T E S L A B LOA D TA B L E | I M P E R I A L U N I T S
CONCRETE VOLUME (yd3/100ft2) 1.26 1.42 1.57 1.72 1.88 2.03 2.19 2.34
1) MAX. UNSHORED SPAN (ft) 17.0 16.3 15.8 15.3 14.8 14.4 14.0 13.6
2) MAX. UNSHORED SPAN (ft) 14.8 14.4 14.0 13.6 13.3 13.0 12.7 12.4
Iu (in.4) 52.0 59.7 68.1 77.3 87.4 98.5 110.7 124.0
Ic (in.4) 25.4 28.5 31.8 35.4 39.2 43.2 47.5 52.1
DEFL. PARAMETER (SLDP) 608 692 784 885 994 1113 1242 1382
DEFL. PARAMETER (SWDP) 0.806 0.782 0.756 0.728 0.698 0.668 0.638 0.608
SLAB THICKNESS (in.) 10.5 11.0 11.5 12.0 12.5 13.0 13.5 14.0

SHORING SPAN (ft) MAXIMUM SPECIFIED LOAD (psf)


To be established 14.0 321 342 362 383 404 425 446 467
by the designer. 14.5 296 315 334 353 372 391 410 429
See notes below. 15.0 273 291 308 326 343 361 378 396
15.5 253 269 285 301 317 333 349 365
16.0 235 250 264 279 294 308 323 338
16.5 218 232 245 259 272 286 299 313
17.0 203 215 228 240 253 265 278 290
17.5 189 200 212 223 235 246 258 269
18.0 176 187 197 208 218 229 239 250
18.5 164 174 184 193 203 213 222 232
19.0 153 162 171 180 189 198 207 216
19.5 143 151 160 168 176 184 192 201
20.0 134 141 149 156 164 172 179 187
20.5 125 132 139 146 153 160 167 174
21.0 117 124 130 136 143 149 155 162
21.5 110 115 121 127 133 139 145 150
22.0 103 108 113 119 124 129 135 140
22.5 96 101 106 111 116 121 125 130
23.0 90 94 99 103 108 112 117 121 23
23.5 84 88 92 96 100 105 109 113
24.0 79 83 86 90 94 97 101 105
24.5 74 77 81 84 87 90 94 97
25.0 69 72 75 78 81 84 87 90
25.5 65 67 70 73 75 78 81 83
26.0 61 63 65 68 70 72 75 77
26.5 57 59 61 63 65 67 69 71
27.0 53 55 56 58 60 62 64 65
27.5 49 51 52 54 55 57 59 60
28.0 46 47 49 50 51 52 54 55

NOTES: 3. “d” next to values in Table indicates deflection controls due to specified
1. The “SLAB WEIGHT” is made up of the self weight of the steel deck, superimposed loads.
the reinforcing bar and the concrete slab, which has been accounted 4. For explanation of deflection parameters SLDP and SWDP, see page 6.
for in the load table for strength requirements only. 5. “SLAB THICKNESS” is measured from top of concrete to bottom
2. Shoring may be required. See maximum unshored span conditions of steel deck.
above to establish the number of shores required. Also, see page 4 6. Iu is the uncracked moment if inertia based on equivalent steel
for explanation of above maximum unshored span conditions. 7. Ic is the cracked moment if inertia based on equivalent steel
BASE STEEL DECK THICKNESS = 0.0476 in. | NOMINAL REBAR DIAMETER = 20 mm
NORMAL DENSITY CONCRETE = 150 lb/ft3

SLAB WEIGHT (psf) 55.1 61.3 67.6 73.8 80.1 86.3 92.6 98.8
CO M F LO R ® CO M P O S I T E S L A B LOA D TA B L E | I M P E R I A L U N I T S

CONCRETE VOLUME (yd3/100ft2) 1.26 1.42 1.57 1.72 1.88 2.03 2.19 2.34
1) MAX. UNSHORED SPAN (ft) 16.9 16.3 15.7 15.2 14.8 14.4 14.0 13.6
2) MAX. UNSHORED SPAN (ft) 14.8 14.3 14.0 13.6 13.3 13.0 12.7 12.4
Iu (in.4) 53.8 61.7 70.4 79.9 90.3 101.6 114.1 127.7
Ic (in.4) 28.2 31.7 35.4 39.5 43.7 48.3 53.1 58.2
DEFL. PARAMETER (SLDP) 644 734 831 937 1052 1177 1313 1460
DEFL. PARAMETER (SWDP) 0.782 0.759 0.734 0.706 0.678 0.649 0.620 0.591
SLAB THICKNESS (in.) 10.5 11.0 11.5 12.0 12.5 13.0 13.5 14.0

SHORING SPAN (ft) MAXIMUM SPECIFIED LOAD (psf)


To be established 14.0 383 408 433 458 483 508 533 558
by the designer. 14.5 354 377 400 423 446 469 492 515
See notes below. 15.0 328 349 370 391 412 433 455 476
15.5 304 323 343 362 382 401 421 440
16.0 282 300 318 336 354 372 390 408
16.5 263 279 296 312 329 346 362 379
17.0 245 260 275 291 306 321 337 352
17.5 228 243 257 271 285 299 313 328
18.0 213 227 240 253 266 279 292 305
18.5 200 212 224 236 248 260 272 284
19.0 187 198 209 221 232 243 254 265
19.5 175 185 196 206 217 227 237 248
20.0 164 174 183 193 203 212 222 232
20.5 154 163 172 181 190 199 207 216
21.0 145 153 161 169 178 186 194 202
21.5 136 144 151 159 166 174 182 189
22.0 128 135 142 149 156 163 170 177
22.5 120 127 133 140 146 153 159 166
24 23.0 113 119 125 131 137 143 149 155
23.5 106 112 117 123 128 134 139 145
24.0 100 105 110 115 120 125 131 136
24.5 94 99 103 108 113 117 122 127
25.0 89 93 97 101 106 110 114 119
25.5 83 87 91 95 99 103 107 111
26.0 78 82 86 89 93 96 100 103
26.5 74 77 80 83 87 90 93 96
27.0 69 72 75 78 81 84 87 90
27.5 65 68 70 73 76 78 81 84
28.0 61 64 66 68 71 73 75 78
28.5 58 60 62 64 66 68 70 72
29.0 54 56 58 60 61 63 65 67
29.5 51 52 54 55 57 59 60 62
30.0 47 49 50 52 53 54 56 57

NOTES: 3. “d” next to values in Table indicates deflection controls due to specified
1. The “SLAB WEIGHT” is made up of the self weight of the steel deck, superimposed loads.
the reinforcing bar and the concrete slab, which has been accounted 4. For explanation of deflection parameters SLDP and SWDP, see page 6.
for in the load table for strength requirements only. 5. “SLAB THICKNESS” is measured from top of concrete to bottom
2. Shoring may be required. See maximum unshored span conditions of steel deck.
above to establish the number of shores required. Also, see page 4 6. Iu is the uncracked moment if inertia based on equivalent steel
for explanation of above maximum unshored span conditions. 7. Ic is the cracked moment if inertia based on equivalent steel
BASE STEEL DECK THICKNESS = 0.0476 in. | NOMINAL REBAR DIAMETER = 25 mm
NORMAL DENSITY CONCRETE = 150 lb/ft3

SLAB WEIGHT (psf) 55.6 61.9 68.1 74.4 80.6 86.9 93.1 99.4

CO M F LO R ® CO M P O S I T E S L A B LOA D TA B L E | I M P E R I A L U N I T S
CONCRETE VOLUME (yd3/100ft2) 1.26 1.42 1.57 1.72 1.88 2.03 2.19 2.34
1) MAX. UNSHORED SPAN (ft) 16.9 16.3 15.7 15.2 14.7 14.3 13.9 13.6
2) MAX. UNSHORED SPAN (ft) 14.7 14.3 13.9 13.6 13.2 12.9 12.7 12.4
Iu (in.4) 57.1 65.6 74.8 84.8 95.7 107.7 120.8 135.0
Ic (in.4) 33.4 37.6 42.2 47.0 52.2 57.8 63.6 69.8
DEFL. PARAMETER (SLDP) 711 810 918 1035 1162 1299 1448 1608
DEFL. PARAMETER (SWDP) 0.769 0.744 0.719 0.692 0.664 0.636 0.608 0.580
SLAB THICKNESS (in.) 10.5 11.0 11.5 12.0 12.5 13.0 13.5 14.0

SHORING SPAN (ft) MAXIMUM SPECIFIED LOAD (psf)


To be established 16.0 375 399 424 449 473 498 522 547
by the designer. 16.5 350 373 395 418 441 464 487 509
See notes below. 17.0 327 348 369 390 411 433 454 475
17.5 306 325 345 365 385 404 424 444
18.0 286 305 323 341 360 378 396 415
18.5 269 286 303 320 337 354 371 388
19.0 252 268 284 300 316 332 348 364
19.5 237 252 267 282 297 311 326 341
20.0 223 237 251 265 279 293 306 320
20.5 210 223 236 249 262 275 288 301
21.0 198 210 222 234 247 259 271 283
21.5 187 198 209 221 232 243 255 266
22.0 176 187 198 208 219 229 240 250
22.5 167 176 186 196 206 216 226 236
23.0 157 167 176 185 194 204 213 222
23.5 149 157 166 175 183 192 201 209
24.0 141 149 157 165 173 181 189 197
24.5 133 141 148 156 163 171 178 186
25.0 126d 133 140 147 154 161 168 175
25.5 119d 126 133 139 146 152 159 165
26.0 112d 119 125 131 137 144 150 156
25
26.5 106d 113 118 124 130 135 141 147
27.0 100d 107 112 117 123 128 133 138
27.5 95d 101 106 111 116 121 125 130
28.0 90d 96 100 105 109 114 118 123
28.5 85d 91 95 99 103 107 111 116
29.0 81d 86 90 93 97 101 105 109
29.5 77d 81 85 88 92 95 99 102
30.0 73d 77 80 83 87 90 93 96
30.5 69d 73 76 79 82 85 88 90
31.0 66 69 71 74 77 79 82 85
31.5 62 65 67 70 72 75 77 80
32.0 59 61 63 66 68 70 72 75
32.5 56 58 60 62 64 66 68 70
33.0 53 54 56 58 60 62 63 65
33.5 50 51 53 54 56 58 59 61
34.0 47 48 50 51 52 54 55 57
NOTES: 3. “d” next to values in Table indicates deflection controls due to specified
1. The “SLAB WEIGHT” is made up of the self weight of the steel deck, superimposed loads.
the reinforcing bar and the concrete slab, which has been accounted 4. For explanation of deflection parameters SLDP and SWDP, see page 6.
for in the load table for strength requirements only. 5. “SLAB THICKNESS” is measured from top of concrete to bottom
2. Shoring may be required. See maximum unshored span conditions of steel deck.
above to establish the number of shores required. Also, see page 4 6. Iu is the uncracked moment if inertia based on equivalent steel
for explanation of above maximum unshored span conditions. 7. Ic is the cracked moment if inertia based on equivalent steel
BASE STEEL DECK THICKNESS = 0.0476 in. | NOMINAL REBAR DIAMETER = 30 mm
NORMAL DENSITY CONCRETE = 150 lb/ft3

SLAB WEIGHT (psf) 56.2 62.4 68.7 74.9 81.2 87.4 93.7 99.9
CO M F LO R ® CO M P O S I T E S L A B LOA D TA B L E | I M P E R I A L U N I T S

CONCRETE VOLUME (yd3/100ft2) 1.26 1.42 1.57 1.72 1.88 2.03 2.19 2.34
1) MAX. UNSHORED SPAN (ft) 16.8 16.2 15.7 15.2 14.7 14.3 13.9 13.6
2) MAX. UNSHORED SPAN (ft) 14.7 14.3 13.9 13.5 13.2 12.9 12.6 12.4
Iu (in.4) 60.1 69.1 78.8 89.4 100.8 113.4 127.0 141.8
Ic (in.4) 37.9 42.9 48.2 53.9 59.9 66.4 73.2 80.5
DEFL. PARAMETER (SLDP) 770 879 997 1125 1262 1411 1572 1745
DEFL. PARAMETER (SWDP) 0.735 0.710 0.685 0.659 0.633 0.606 0.580 0.553
SLAB THICKNESS (in.) 10.5 11.0 11.5 12.0 12.5 13.0 13.5 14.0

SHORING SPAN (ft) MAXIMUM SPECIFIED LOAD (psf)


To be established 18.0 356 379 403 427 450 474 498 521
by the designer. 18.5 334 356 378 401 423 445 467 489
See notes below. 19.0 311d 335 356 376 397 418 439 459
19.5 288d 315 335 354 374 393 412 432
20.0 267d 297 316 334 352 370 388 406
20.5 248d 281 298 315 332 349 366 383
21.0 231d 263d 281 297 313 329 345 361
21.5 215d 245d 265 280 295 310 325 340
22.0 201d 229d 251 265 279 293 307 321
22.5 188d 214d 237 251 264 277 290 304
23.0 176d 200d 225 237 250 262 275 287
23.5 165d 188d 213 224 236 248 260 271
24.0 155d 176d 200d 213 224 235 246 257
24.5 145d 166d 188d 202 212 222 233 243
25.0 137d 156d 177d 191 201 211 220 230
25.5 129d 147d 167d 181 190 200 209 218
26.0 122d 139d 157d 172 181 189 198 206
26.5 115d 131d 149d 163 171 179 188 196
27.0 109d 124d 141d 155 163 170 178 185
27.5 103d 117d 133d 147 154 161 169 176
26 28.0 97d 111d 126d 140 146 153 160 167
28.5 92d 105d 119d 133 139 145 152 158
29.0 88d 100d 113d 126 132 138 144 150
29.5 83d 95d 108d 120 125 131 136 142
30.0 79d 90d 102d 114 119 124 129 134
30.5 75d 86d 97d 108 113 118 122 127
31.0 72d 82d 93d 102 107 111 116 121
31.5 68d 78d 88d 97 101 106 110 114
32.0 65d 74d 84d 92 96 100 104 108
32.5 62d 71d 81d 88 91 95 99 102
33.0 59d 68d 77d 83 86 90 93 97
33.5 57d 65d 74d 79 82 85 88 91
34.0 54d 62d 70d 75 78 80 83 86
34.5 52d 59d 67d 71 73 76 79 81
35.0 50d 57d 64 67 69 72 74 77
35.5 48d 55d 61 63 66 68 70 72
36.0 46d 52d 58 60 62 64 66 68
NOTES: 3. “d” next to values in Table indicates deflection controls due to specified
1. The “SLAB WEIGHT” is made up of the self weight of the steel deck, superimposed loads.
the reinforcing bar and the concrete slab, which has been accounted 4. For explanation of deflection parameters SLDP and SWDP, see page 6.
for in the load table for strength requirements only. 5. “SLAB THICKNESS” is measured from top of concrete to bottom
2. Shoring may be required. See maximum unshored span conditions of steel deck.
above to establish the number of shores required. Also, see page 4 6. Iu is the uncracked moment if inertia based on equivalent steel
for explanation of above maximum unshored span conditions. 7. Ic is the cracked moment if inertia based on equivalent steel
CONSTRUCTION GUIDELINES

D E C K I N G I N S TA L L AT I O N
COMFLOR® PANEL DECKING – shall be positively fastened to the supporting structure to avoid movement during construction
and excessive deflection during placement of concrete. The fastening frequency of main fasteners is 1 per trough at each panel
end at 610 mm (24 in.) on centre along the support structure. The COMFLOR® deck panels shall bear a minimum of 50 mm (2
in.) onto the support structure. When fastening panels to structural steel work, use heavy-duty shotfired pins or self-drilling
fasteners as designed and specified by the engineer of record. For brick, block and concrete, the decking shall be fastened
using adequate masonry fasteners as designed and specified by the engineer of record. In addition to the main fasteners, the
top flanges of the End Closures shall be fastened to the decking, one fastener per module, either centred or 610 mm (24 in.)
on centre. Side-lap Washers shall be fastened at 350 mm (13.8 in.) centres
along the bottom trough, using No. 12 x 25.4 mm (1 in.) self-drilling fasteners or
better. The location of the fasteners is prepunched on the male trough flange,
which overlaps the female trough flange.
NOTE 1: Every side-lap fastener shall include a Side-lap Washer. This washer
is required to properly attach the individual steel deck panels together.

CONSTRUCTION GUIDELINES
NOTE 2: When a suspended ceiling is used, the minimum thread length of the
fastener is 25 mm (1 in.).
The bottom flange of the End Closure shall be fastened to the supporting
structure with 1 fastener per module at 610 mm (24 in.) on centre, or as specified
by the engineer of record.

END CLOSURES – To minimise grout loss at the profile ends during concrete
placement, End Closures are provided to contain the concrete. These closures
are manufactured from 1.52 mm (0.060 in.) galvanised steel, generally 1830
mm (6 ft) long or longer for angle cut installations. End Closures shall be
fastened to the support structure at maximum intervals of 610 mm (24 in.),
using shot-fired pins, self-drilling fasteners or as specified by the engineer of
record. Apart from minimising grout loss during concrete placement, these
End Closures provide strength to prevent web crippling of the steel deck and 27
proper alignment of the decking during construction. When used in
conjunction with hot-rolled steel beams, these End Closures provide concrete
cover to the steel beam for fire resistance.

SIDE-LAP WASHERS – Since the COMFLOR® deck acts in part compositely with
the concrete, Side-lap Washers are important connecting elements. These
washers are prepunched to receive the self-drilling fastener.

CANTILEVERS – COMFLOR® decking can be end cantilevered as shown in the


“Examples of Construction Applications” section. When side cantilevers are
required, stub beams or brackets shall be provided by the structural steel
fabricator, as designed by the engineer of record. Cantilevers shall also be
assessed for reinforcement by the engineer of record.
PERIMETER TRIMS – Are required for the retention of wet concrete to the correct level
at the decked floor perimeters and designed openings. They are supplied in 3 m (10
ft) lengths of galvanised steel. Perimeter Trims are usually fastened by shot-fired pins
to the structural steel or by self-drilling fasteners to the support structure at 610 mm (24
in.) on centre, or as specified by the engineer of record.

RESTRAINT STRAPS – The top of the perimeter edge trim is connected to the decking
with Restraint Straps at approximately 400 mm (16 in.) on centre using either pop
rivets or self-drilling fasteners. The Restraint Strap can be adjusted to suit the pitch and
alignment of the perimeter edge trim.

PENETRATIONS – Penetrations through the floor decking shall be cut after the concrete
has cured. Before placing concrete, any openings shall be boxed out with form work
as specified by the engineer of record. The following guidelines are suggested for isolated
CONSTRUCTION GUIDELINES

openings at right angles to the deck span, or as specified by the engineer of record:
• Up to 300 mm (12 in.) square penetrations centred on the top of the profile of the
deck is acceptable without additional reinforcement, other than the minimum
shrinkage and temperature mesh.
• Up to 425 mm (16.7 in.) width by 1000 mm (39.4 in.) length opening with additional
reinforcement.
• Openings larger than 425 mm (16.7 in.) require structural steel framing as specified
by the engineer of record.
• Close grouping of openings transverse to the profile shall be treated as one
opening, requiring additional reinforcement as specified by the engineer of record.
• After the slab has reached 75% of the required concrete compressive strength, a
nibbler, power saw or coring machine can be used to cut out openings in the top
profile with the approval by the engineer of record.

28
COLUMNS AND COMFLOR® DECKING – The steel deck sheeting can be cut and fitted
to accommodate various column shapes to minimise grout loss. Where no supporting
steel work is provided, steel angle brackets shall be provided to support the steel
decking, as specified by the engineer of record.

RIB REINFORCEMENT AND MESH PLACEMENT – The COMFLOR® design requires that
one steel reinforcing bar be placed in each rib profile. The bar size, as shown in the
load tables, can vary from 10 mm (0.394 in.) to 30 mm (1.18 in.) in diameter. The bars
shall be placed on Rebar Supports which ensure a 40 mm (1.57 in.) spacing from
the bottom flange to the underside of the reinforcing bars. Spacing of the Rebar
Supports shall be in accordance with good practice guidelines, and not exceeding
1220 mm (48 in.) on centre. To ensure both vertical and horizontal stability during
concrete placement, the reinforcing bars shall be tied down periodically through the
Side-lap Washers with 1.21 mm (0.0476 in.) diameter tie wiring. It is recommended
that a minimum standard shrinkage and temperature reinforcing mesh of
152x152xMW18.7xMW18.7 (6x6x6/6) be placed above the top of the steel decking
and positioned towards the top of the slab, or as specified by the engineer of record.
CONCRETE PLACEMENT – Concrete shall be placed in accordance with CAN/CSA
A23.1-947. Before starting concrete placement, the steel decking shall be cleared of
dirt, grease and debris, which could adversely influence the composite slab
performance. Care shall be taken to avoid concrete heaping in any area during
concrete placement. Typical construction live loads have been accounted for in the
load tables. Should additional construction loading be required, approval by the
engineer of record is required.

TEMPORARY SUPPORTS – When the design span exceeds the maximum unshored
span shown in the load tables, the wet concrete weight and construction loads shall
be supported by adding temporary supports (shoring), as designed by the engineer
of record. Where temporary supports are required, it is important that:
• Beams and the support structure have adequate strength to support the
construction loads as designed and specified by the engineer of record.
• Shoring is normally placed at midspan or at other suitable intervals, as required.

CONSTRUCTION GUIDELINES
• Shoring beams shall provide a minimum bearing width of 100 mm (4 in.).
• The shoring structure shall remain in place until the concrete has reached 75% of its
design strength, or as specified by the engineer of record.

HANGER SYSTEM – The geometry of the ribs allows for the suspension of services from
the profile top flange between ribs. Pre-set threaded rod hangers are easily installed
before the concrete is placed. Consult your mechanical and electrical consultants, and
installation contractors for accepted specifications.

29
SERVICE HOLES – Refer to table on page 37 for size and location of round holes
through COMFLOR® ribs. Sleeves shall be fastened in place before concrete
placement. Cut-out of holes shall be done only after the concrete has reached 75% of
its design strength, or as specified by the engineer of record.

CEILING HANGER SYSTEMS – Ceilings can be suspended directly from the bottom of
the steel deck.
I N S TA L L I N G E N D C L O S U R E S
Install with mechanical fasteners to any lateral beam or bearing wall substrate
at minimum 610 mm (24 in.) on centre.
CONSTRUCTION GUIDELINES

I N S TA L L I N G P E R I M E T E R T R I M S
Install Perimeter Trims for concrete containment and alignment. The top edge is
used as a screed guide to achieve the overall required concrete slab depth.

30

P L AC I N G O F CO M F LO R ® D E C K
Install the deck progressively (male to female flange overlap) and fasten at 350 mm
(13.8 in.) on centre with Side-lap Washers and self-drilling fasteners.
TEMPORARY SHORING
Install in accordance with load tables based on maximum unshored span condition.
The engineer of record shall approve shoring requirement and installation.

I N - F L O O R R A D I A N T H E AT I N G
Install flat sheets of wire mesh or other equivalent material, i.e. 10 mm reinforcing

CONSTRUCTION GUIDELINES
bar @ 560 mm (22 in.) on centre commonly used.

PL ACEMENT OF CONCRETE
Place concrete uniformly and screed to top of perimeter trims and avoid
concrete heaping. Cylinder strength shall not be less than 30 MPa (4.35 ksi),
with a maximum aggregate size of 20 mm (0.75 in.).
31

UNDERSIDE VIEW
The installed ribbed ceiling provides suitable substrate for direct finishing;
applying additional fire safety protection; enhanced acoustical treatment and
finishing with a variety of finished ceiling materials.
EXAMPLES OF CONSTRUCTION APPLIC ATIONS

The various examples of construction applications presented herein are illustrative only and
should not be used unless the engineer of record has approved them.

Beam reinforcing by Shrinkage and


engineer of record
E X A M P L E S O F CO N S T RU C T I O N A P P L I C AT I O N S

temperature
reinforcement
Perimeter Trim Concrete slab
Shrinkage and
temperature
reinforcement Concrete slab Restraint Strap 57 mm (min.)

COMFLOR®deck 57 mm (min.)

203 mm

Rebar Supports
with rebar at 203 mm
610 mm o.c. 40 mm
End Closure

Deck and edge trim


40 mm COMFLOR®deck
fastened to steelwork
Side-lap Washers
fastened at 350 mm o.c.
Temporary shoring
Refer to load tables
End Closure for span limitations
Loadbearing BMP steel stud
wall or structural support

E N D C LO S U R E D E TA I L S H O R I N G D E TA I L

Beam reinforcing by Beam reinforcing by


32 engineer of record engineer of record

Perimeter Trim Shrinkage and


temperature Perimeter Trim
reinforcement Shrinkage and
temperature
reinforcement
Restraint Straps
57 mm (min.) Restraint Strap
57 mm (min.)

203 mm Rebar Supports


with rebar at
610 mm o.c. 203 mm

40 mm
End Closure COMFLOR® deck
40 mm
COMFLOR® deck
Deck and edge trim
Side-lap Washers
Deck and edge trim fastened to steelwork
fastened at
fastened to steelwork 350 mm o.c.
Loadbearing BMP steel stud Loadbearing BMP steel stud
Rib reinforcing at wall or structural support wall or structural support
610 mm o.c.

E N D B E A R I N G D E TA I L P E R I M E T E R B E A R I N G D E TA I L
The various examples of construction applications presented herein are illustrative only and
should not be used unless the engineer of record has approved them.

Beam reinforcing by Top flange of deck fastened to top


engineer of record of end closure using 1 self-drilling

E X A M P L E S O F CO N S T RU C T I O N A P P L I C AT I O N S
fastener per pitch (typical)

Rib reinforcing as Shrinkage and


temperature Shrinkage and
specified by design Wide flange beam (WF)
reinforcement temperature
reinforcement
Concrete slab Rib reinforcing as
57 mm (min.)
specified by design 57 mm (min.)

203 mm
203 mm

40 mm
COMFLOR®deck 40 mm
End Closure
End Closure
Deck and End Closures
fastened to bearing using
heavy-duty shot-fired pins or Deck and End Closures
self-drilling fasteners (typical) COMFLOR®deck fastened to bearing using
heavy-duty shot-fired pins or
self-drilling fasteners (typical)
Loadbearing BMP steel stud
wall or structural support 6 mm steel plate
welded to WF beam

WA L L CO N N E C T I O N D E TA I L W I D E F L A N G E B E A M D E TA I L

Beam reinforcing by
engineer of record
Shrinkage and
Beam reinforcing by
engineer of record 33
temperature Perimeter Trim
reinforcement
Shrinkage and
temperature
reinforcement Restraint Strap

57 mm (min.) 102 mm max.


57 mm (min.)

203 mm ®
COMFLOR deck
COMFLOR®deck 203 mm cut to suit dimensions

40 mm Inside Trim
Rib reinforcing as 40 mm
End Closure specified by design
Rib reinforcing with
Side-lap Washer Rebar Supports
Deck and End Closures fastened at
fastened to bearing using 350 mm o.c.
heavy-duty shot-fired pins or
self-drilling fasteners (typical)
Loadbearing BMP steel stud
wall or structural support
Loadbearing BMP steel stud
wall or structural support

PA N E L D I R E C T I O N C H A N G E D E TA I L S I D E P E R I M E T E R B E A R I N G D E TA I L
The various examples of construction applications presented herein are illustrative only and
should not be used unless the engineer of record has approved them.

Corridor deck (by others) Shrinkage and


E X A M P L E S O F CO N S T RU C T I O N A P P L I C AT I O N S

Perimeter Trim Shrinkage and temperature


temperature reinforcement
Restraint Strap reinforcement
Beam reinforcing and
End Closure Refer to structural drawings for stirrups, as required by
reinforcing in cantilever slab engineer of record
38 mm
87 mm (min.) 57 mm (min.)

Angle 203 mm

COMFLOR®deck
Rib reinforcing as 135 mm clearance 40 mm
End Closure
specified by design to top of wall
COMFLOR®deck
Temporary shoring
as required by Rib reinforcing as
engineer of record specified by design
End Closure
Cantilever slab varies,
see structural drawings Deck and End Closures Loadbearing BMP steel stud
fastened to support using wall or structural support
Loadbearing BMP steel stud
heavy-duty shot-fired pins or
wall or structural support
self-drilling fasteners (typical)

E N D C A N T I L E V E R D E TA I L CO R R I D O R B E A R I N G D E TA I L

Shrinkage and Shrinkage and

34 Corridor deck (by others)


temperature
reinforcement
Perimeter Trim temperature
reinforcement
Restraint Strap
End Closure Beam reinforcing and
Corridor Trim stirrups, as required by
engineer of record

COMFLOR®deck

38 mm 57 mm (min.)
87 mm (min.)

203 mm

40 mm
Furring channel

Furring channel End Closure


135 mm clearance
to top of wall
COMFLOR®deck
Interior finish

Tie-wire as required Loadbearing BMP steel stud


for suspended ceiling Loadbearing BMP steel stud wall with insulation
wall or structural support
Exterior sheathing and/or insulation
(as required). See architectural drawings
Corridor finish

C O R R I D O R F I N I S H I N G D E TA I L E N D B E A R I N G F I N I S H I N G D E TA I L
The various examples of construction applications presented herein are illustrative only and
should not be used unless the engineer of record has approved them.

610 mm
As specified

E X A M P L E S O F CO N S T RU C T I O N A P P L I C AT I O N S
92.5 mm

425 mm

203 mm Plumbing pipe

102 mm

COMFLOR®deck
Furring channel

16 mm 16 mm
305 mm to 330 mm
or as specified
Non-loadbearing
BMP steel stud wall

Plumbing pipe
610 mm
As specified 212.5 mm 212.5 mm
92.5 mm 92.5 mm
35

203 mm

102 mm

40 mm

COMFLOR®deck Fill material

Furring channel

** **
16 mm 16 mm
6.4 mm
25.4 mm
** Indicates various stud widths 305 mm to 330 mm
or as specified
Non-loadbearing
BMP steel stud wall

S U G G E S T E D C L E A R A N C E N E A R P L U M B I N G S TA C K S
COMFLOR® SOUND AND FIRE RATIN GS

ACOUSTICAL PERFORMANCE TESTS


The acoustical performance of COMFLOR® in conjunction with non-loadbearing steel stud partition walls was tested in the field
in a newly constructed building. The results are presented below. The unit designator FSTC refers to the Field obtained Sound
Transmission Class, and is an industry standard used to classify sound transmission losses through a floor or partition.
FLOOR – COMFLOR®
Bare Steel Ceiling .................................................................................................................................. FSTC 55
Uninsulated, Furred, Gypsum Wall Board (GWB) .......................................................................... FSTC 57
Insulated, Furred, GWB ........................................................................................................................ FSTC 60
Diagonal Measurement ........................................................................................................................ FSTC 66
CO M F LO R ® S O U N D A N D F I R E R AT I N G S

NOTE: Copy of the test report by Kenneth E. Barron, P.Eng. 98-02-10 is available upon request.
WALL – CMP – NON-LOADBEARING STEEL STUD AND TRACK8
2 - 2 1/2 in. x 0.0181 in. Studs, 1 in. airspace
R8 Batt both Cavities
2 Layers, 5/8 in. GWB Type X.............................................................................................................. FSTC 57

FIRE SAFETY PERFORMANCE TESTS


ULC Design No. F9099 D5009
UL Design No. D93010 D50410

Assembly Concrete Topping Concrete Topping Concrete Topping


COMFLOR® 64 mm (2.52 in.) 90 mm (3.54 in.) 90 mm (3.54 in.)
Restrained 1 Hour 1.5 Hour 2.0 Hour
Unrestrained 1 Hour 1.5 Hour 2.0 Hour
Span ≤ 10 m (32 ft 10 in.)

36

MULTI-STORY HOTEL IN RICHMOND, B.C.


T Y P I C A L CO M F LO R ® RO U N D S E RV I C E H O L E D E TA I L

RO U N D S E RV I C E H O L E D E TA I L | RO U N D S E RV I C E H O L E D I A M E T E R S
2D 2h (min.)
COMFLOR®deck
57 mm
(min.)

20 mm
(N.A.) h
D 203 mm
d

As specified 40 mm

2D 2h (min.)
CL
NOTATIONS:
D = Overall Slab Depth;
d = Rebar diameter;
h = Maximum hole diameter;
Outside third of span Outside third of span
N.A. = Neutral Axis

MAXIMUM ROUND SERVICE HOLE DIAMETERS

SI-UNITS
SLAB NOMINAL REBAR DIAMETER
THICKNESS
d = 10 mm d = 15 mm d = 20 mm d = 25 mm d = 30 mm
(mm)
h (mm) h (mm) h (mm) h (mm) h (mm)
260 135 125 120 110 100
270 145 135 130 115 105
280 150 145 135 125 115
290 160 150 145 130 120
300 170 160 150 140 130
310 175 170 160 150 140
320 185 175 170 155 145
330 195 185 175 165 155 37
IMPERIAL UNITS
SLAB NOMINAL REBAR DIAMETER
THICKNESS
d = 10 mm d = 15 mm d = 20 mm d = 25 mm d = 30 mm
(in.)
h (in.) h (in.) h (in.) h (in.) h (in.)
10.5 5.50 5.25 5.00 4.50 4.00
11.0 6.00 5.50 5.25 4.75 4.50
11.5 6.25 6.00 5.75 5.25 4.75
12.0 6.75 6.50 6.00 5.75 5.25
12.5 7.25 6.75 6.50 6.00 5.50
13.0 7.50 7.25 7.00 6.50 6.00
13.5 8.00 7.75 7.25 6.75 6.50
14.0 8.50 8.00 7.75 7.25 6.75

NOTES:
* 20 mm (0.787 in.) of concrete is required above each rebar.
* The clear distance from the bottom of each rebar is 40 mm (1.57 in.) minimum.
* No more than 2 holes shall be placed side by side, with the end distance spacing not less than 2D.
* The spacing between any two holes shall not be less than 2h.
* Hole(s) shall be positioned in the outside thirds of the span, as shown above.
VO LU M E VA LU E S F O R E S T I M AT I N G | R E I N F O RC I N G B A R I N F O R M AT I O N

COMFLOR® CON CRETE VOLUME VALUES F OR ESTIMATIN G

SI UNITS IMPERIAL UNITS


SLAB CONCRETE SLAB CONCRETE
THICKNESS VOLUME THICKNESS VOLUME
(mm) (m3/10m2) (in.) (yd3/100ft2)
260 0.971 10.5 1.26
270 1.07 11.0 1.42
280 1.17 11.5 1.57
290 1.27 12.0 1.72
300 1.37 12.5 1.88
310 1.47 13.0 2.03
320 1.57 13.5 2.19
330 1.67 14.0 2.34

REINF ORCIN G BAR INF ORMATION

NOMINAL BAR ACTUAL VALUES MASS PER


DESIGNATION UNIT LENGTH
DIAMETER AREA
mm in. mm 2
in.2 kg/m lb/ft
10M 11.3 0.445 100 0.155 0.785 0.527
15M 16.0 0.630 200 0.310 1.57 1.06
20M 19.5 0.768 300 0.465 2.36 1.58
25M 25.2 0.992 400 0.775 3.93 2.64
30M 29.9 1.18 500 1.09 5.50 3.69
NOTES: Welded Wire Mesh Sheets - CSA G30.5
1) 152x152xMW18.7xMW18.7 (6x6x6/6)
2) Minimum wire mesh used in ULC F9097 - (UL D930)8
38 3) Concrete volumes are given for COMFLOR® slab only

SINGLE-FAMILY RESIDENCE IN VANCOUVER, B.C.


COMFLOR® STEEL DECK AND ACCESSORIES
( M AT E R I A L S , W E I G H T S , PAC K AG I N G )

MATERIALS THICKNESS WEIGHT PACKAGING


mm in. SI Imperial Pieces

COMFLOR® STEEL DECK 0.96 0.0378 0.124 kPa 2.59 psf 30 pieces per bundle
(Z275 FINISH) cut to length
203 mm 1.21 0.0476 0.155 kPa 3.24 psf

610 mm

COMFLOR® STEEL DECK AND ACCESSORIES


END CLOSURES 1.52 0.060 2.98 kg/m 2 lb/ft 50 pieces per bundle
(Z275 FINISH) or
38 mm
5.44 kg/pc 12 lb/pc Custom angles
50 mm
203 mm available
1830 mm

38 mm
PERIMETER TRIMS 1.52 0.060 17.7 kg/pc 39 lb/pc 10 pieces per bundle
(Z275 FINISH) to to
20.4 kg/pc 45 lb/pc 10 ft lengths
203 mm

D = Overall slab depth


50 mm

INSIDE TRIMS 25.4 mm 0.914 0.036 9.1 kg/pc 20 lb/pc 10 pieces per bundle
(Z180 FINISH) 1.22 0.048 11.3 kg/pc 25 lb/pc
D 45∞ 10 ft lengths
CORRIDOR TRIMS 1.52 0.060 13.6 kg/pc 30 lb/pc
(Z180 FINISH)
50 mm

SIDE-LAP WASHERS 1.22 0.048 11.3 kg per 25 lb per 500 pieces per carton
(Z180 FINISH) carton carton
39

REBAR SUPPORTS 0.914 0.036 20.4 kg per 45 lb per 300 pieces per carton
(Z180 FINISH) carton carton

RESTRAINT STRAPS 0.838 0.033 9.1 kg per 20 lb per 100 pieces per carton
(Z180 FINISH) carton carton

FASTENERS 20.4 kg per 45 lb per 3 000 pieces


#12 x 1" Hex S.D. Zinc carton carton per carton

SCREWS 15.9 kg per 35 lb per 10 000 pieces


#8 x 1/2" Wafer S.D. Zinc carton carton per carton
COMFLOR® SPECIFIC ATIONS

PA RT 1 – G E N E R A L :
1.1 SCOPE
These Specifications cover the design, manufacture and use of the COMFLOR® composite floor system.
• Furnish all materials and services for the fabrication of the COMFLOR® composite floor system in accordance with these
Specifications and applicable drawings. COMFLOR® composite floor systems shall be manufactured and marketed by Bailey
Metal Products.
• Fully co-ordinate the COMFLOR® composite floor system with structural, mechanical, electrical and architectural components
of the building.

1.2 CODES
• Design and manufacturing shall be in strict accordance with the COMFLOR® composite floor systems, BMP, using steel
conforming to the requirements of ASTM A653, Standard Specification for Steel Sheet, Zinc-coated (Galvanized) by the Hot
CO M F LO R ® S P E C I F I C AT I O N S

Dip Process and Having Structural Physical Quality. Guaranteed minimum yield strength shall be 280 MPa (40.6 ksi) with a
minimum zinc coating mass of 275 g/m2 (G90) total including both sides. Steel deck base thickness shall be either 0.96 mm
(0.0378 in.) or 1.21 mm (0.0476 in.).
• Reinforcing steel shall meet the requirements of CAN/CSA G30.18-M19925. Guaranteed minimum yield strength shall be 400
MPa (58 ksi). The clear distance of each reinforcing bar from the bottom of the steel deck shall be 40 mm (1.57 in.).
• Concrete shall have a minimum cylinder strength of 30 MPa (4.35 ksi) with a maximum aggregate size of 20 mm (0.75 in.).
Normal density structural concrete used shall be 2400 kg/m3 (150 lb/ft3).

1.3 DESIGN
• Strength – Flexural design shall be by limit states design principles which were used in the development of the structural load tables:
• The factored resistance under consideration, φR ≥ the effect of the factored loads. This is in accordance with the National
Building Code of Canada 19956.
• Since the self-weight of the steel deck, the reinforcing bar and the concrete have been included in the structural load tables,
40 the maximum specified load (from the appropriate structural load table) shall be:
≥ (LL + 1.25/1.5DL),
where:
LL - Specified live load
DL - Specified superimposed dead load
1.25 - Dead load factor
1.5 - Live load factor
• Serviceability – If deflection controls, the maximum specified load (from the appropriate structural load table) shall be:
≥ (LL + DL).

1.4 SHOP DRAWINGS


• Detailed erection drawings shall be submitted by the purchaser to the Architect, Engineer, General Contractor or
representative for approval, showing material lists, mark numbers, types, locations, spacing of floor pans and accessories
showing method of attachment to supporting members. Contract drawing notes relative to the COMFLOR® composite floor
system shall be considered a part of this Specification as though fully set forth herein.
• Shop drawings, prepared only from approved erection drawings, shall be used for fabrication and erection.
• Figured dimensions only shall be used. Scaling drawings shall NOT be permitted.
1.5 HANDLING & STORAGE
• Care shall be exercised at all times to avoid damage to COMFLOR® composite floor system components during loading,
storing and erecting. Damaged decking must be replaced.
• COMFLOR® deck panels are supplied in bundles of up to 30 sheets. Each bundle can weigh up to 2.5 tonnes (5500 lb).
Individual decking elements can twist when lifted so care shall be taken when lifting with slings or forks.
• COMFLOR® deck panels shall be stored on timber supports, clear of the ground. The bundles are marked and shall be
positioned on and/or in the area indicated on the layout drawings. The bundles shall be placed with the pre-punched holes
in the lap on the same side, unless otherwise noted on the layout drawings.

1.6 PRODUCTS
• COMFLOR® steel deck panels are fabricated using Z275 (G90) galvanised steel sheet, of either 0.96 mm (0.0378 in.) or 1.21 mm
(0.0476 in.) in thickness.
• End Closures are fabricated using Z275 (G90) galvanised steel sheet, 1.52 mm (0.060 in.) in thickness.

CO M F LO R ® S P E C I F I C AT I O N S
• Perimeter Trims are fabricated using Z275 (G90) galvanised steel sheet, 1.52 mm (0.060 in.) in thickness.
• Inside Trims are fabricated using Z180 (G60) galvanised steel sheet of either 0.914 mm (0.036 in.) or 1.22 mm (0.048 in.) in
thickness, depending on the COMFLOR® steel deck thickness.
• Corridor Trims are fabricated using Z180 (G60) galvanised steel sheet, 1.52 mm (0.060 in.) in thickness.
• Side-lap Washers are fabricated using Z180 (G60) galvanised steel sheet, 1.22 mm (0.048 in.) in thickness.
• Rebar Supports are fabricated using Z180 (G60) galvanised steel sheet, 0.914 mm (0.036 in.) in thickness.
• Restraint Straps are fabricated using Z180 (G60) galvanised steel sheet, minimum 0.838 mm (0.033 in.) in thickness.

1.7 EXECUTION
• Installation shall be in accordance with the latest Construction Guidelines for the COMFLOR® composite floor system. Care
shall be exercised to avoid damage through careless handling during unloading, storing and erecting. Suitably qualified
personnel shall install COMFLOR® floor components. 41
• End Closures shall be fixed to the support structure prior to the decking being installed, using a minimum of 2 fasteners (such
as shot-fired pins or self-drilling fasteners, and using the following fastener Specifications or equivalency:

In addition to the main structural fastening, the profile top flanges are fixed to the upper flange of the End Closures using
self-drilling fasteners at a frequency of 1 fastener per profile. The following fastener Specification shall be used:
No. 12 x 25.4 mm (1 in.) or better, hexagon washer head, zinc coated or equivalent. The above fasteners shall be
installed using a correctly set screw gun to the data available from the fastener supplier.

• Ensure that current decking drawings are being used. The COMFLOR® deck panels shall be correctly fastened at each end
to the bearing wall substrate with appropriate mechanical fasteners. The COMFLOR® deck panels shall bear a minimum of
50 mm (2 in.) onto the support structure.
• Perimeter Trims shall be fastened to the wall substrate in a true and plumb manner, using the appropriate fastener to suit
the steel or concrete substrate at 350 mm (13.8 in.) intervals in accordance with the data available from the fastener supplier.
• Interior deck panel closures shall be fastened to the COMFLOR® deck panel with a minimum of 50 mm (2 in.) overlap,
fastened together with No. 12 x 25.4 mm (1 in.) or better, hexagon washer head self-drilling screws spaced at 350 mm (13.8
in.) on centre. Panel closures shall be the equivalent thickness of the COMFLOR® deck panel specified. Alternately, the
COMFLOR® panel can be cut longitudinally and overlapped a minimum of 75 mm (3 in.) and fastened together at 300 mm
(12 in.) on centre with 2 fasteners paired 25.4 mm (1 in.) apart.
CO M F LO R ® S P E C I F I C AT I O N S | D E F L E C T I O N D U E TO S L A B W E I G H T

• Side-lap Washers shall be installed at 350 mm (13.8 in.) along the bottom trough of each vault profile using No. 12 x 25.4
mm (1 in.) or better, hexagon washer head self-drilling screws. The fastener location is indicated by pre-punched holes in the
male overlap. The laps shall be correctly connected together as they form a critical part of the flooring system.
• Rebar Supports shall be installed at 1220 mm (4 ft) on centre maximum, to support the reinforcing bars (10 mm to 30 mm,
as specified) in each vault or trough in accordance with Section 1.2 of these Specifications – 40 mm (1.57 in.) clearance.
• Restraint Straps shall be installed 400 mm (16 in.) on centre, one end to the Perimeter Trim return flange and the other end
to the top of the deck panel for concrete pressure restraint during the concrete placement phase of construction.
• Shoring shall be supplied and installed by qualified personnel at the locations specified on the drawings. If in doubt, check
with the supplier’s technical department and the engineer of record. Shoring shall not be removed until the concrete has
reached 75% of its required design strength, or as authorised by the engineer of record. Consult with the engineer of record
to be sure that the shoring meets the local jurisdictional requirements before placing of concrete.
• Concrete shall be placed in accordance with CAN/CSA A23.1-947. Good concrete placement practices shall be carried out
at all times. Refer to concrete practice guidelines before starting concrete placement.

DEFLECTION DUE TO SL AB WEIGHT

The deflection due to the slab weight can be calculated as follows. The calculation is based on the uncracked moment of inertia
of the section and the deflection parameter, SWDP, can be obtained from the load tables.

SI-UNITS IMPERIAL UNITS


SWDP x (L) 4
SWDP x (L)4
δsw = = mm δsw = = in.
103 106
L = metres L = feet

42

CONDOMINIUM COMPLEX IN COQUITLAM, B.C.


REFERENCE DOCUMENTS

REFERENCE DOCUMENTS | SI-METRIC – IMPERIAL CONVERSIONS


1
S136-94, “Cold Formed Steel Structural Members”, Canadian Standards Association, Rexdale (Toronto), 1994.
2
CSSBI S2-2002, “Criteria for Testing of Composite Slabs”, Canadian Sheet Steel Building Institute, Cambridge, Ontario, March 2002.
3
CSSBI 12M-96, “Standard for Composite Steel Deck”, Canadian Sheet Steel Building Institute, Cambridge, Ontario, October 1996.
4
CSSBI S3-2002, “Criteria for the Design of Composite Slabs”, Canadian Sheet Steel Building Institute, Cambridge, Ontario, March 2002.
5
CAN/CSA G30.18-M1992, “Billet-Steel Bars for Concrete Reinforcement”, Canadian Standards Association, Rexdale (Toronto), 1992.
6
NBC 1995, “National Building Code of Canada”, National Research Council of Canada, Ottawa, 1995.
7
CAN/CSA A23.1-94, “Concrete Materials and Methods of Concrete Construction”, Canadian Standards Association, Rexdale
(Toronto), 1994.
8
Warnock, A.C.C “Factors Affecting Sound Transmission Loss”, Canadian Building Digest No. 239, National Research Council
of Canada, Ottawa, July 1985.
9
“List of Equipment and Materials, Volume II, Building Materials”, Underwriters’ Laboratories of Canada, Scarborough, Ontario
Canada.
10
“Fire Resistance Directory, Volume 1”, Underwriters Laboratories Inc., Northbrook, Illinois.

SI-METRIC – IMPERIAL CONVERSIONS

Listed below are some common conversion factors to assist users with the
information contained in this catalogue.

FROM SI-METRIC UNITS TO IMPERIAL UNITS DIVIDE BY


mm in. 25.4
mm2 in.2 645.2
43
mm3 in.3 16 387
mm4 in.4 416 231
m ft 0.3048
m2 ft2 0.0929
kN kips 4.44822
kPa (kN/m2) psf 0.04788
kg/m lb/ft 1.488
MPa (N/mm2) kips/in.2 6.895
N-m kips-in. 113
BAILEY METAL PRODUCTS LIMITED
MONTREAL TORONTO CALGARY EDMONTON VANCOUVER
LES PRODUITS METALLIQUES BAILEY LTEE
One Caldari Road 2515 Centre Avenue S.E. 5710 Roper Road N.W., Suite 101 7715 Anvil Way
5890 Avenue Andover
3512-0305-????

Concord ON L4K 3Z9 Calgary AB T2A 2L1 Edmonton AB T6B 3G7 Surrey BC V3W 6A2
Ville Mont-Royal QC H4T 1H4
Tel: (905) 738 6738 Tel: (403) 248 3536 Tel: (780) 462 5757 Tel: (604) 590 5100
Tel: (514) 735 3455
(800) 668 2154 (800) 665 2013 (800) 563 1751 (800) 818 2666
(800) 263 3455
Fax: (905) 738 5712 Fax: (403) 248 0288 Fax: (780) 465 3791 Fax: (604) 599 5371
Fax: (514) 735 5052

sales@bmp-group.com · www.bmp-group.com

Potrebbero piacerti anche