ROOM AIR FLOW CALCULATION

DIKCHU AIR REQUIREMENT CALCULATION SHEET

AHUs Capacity Req.


Air changers as per
Height/Length (for

eaquipments heat
Floor/ area Name

Supply air fow as


Floor area/X-area

Indoor Dry Temp.

No. of calculated
Air fow required
Total room loads

Selected air fow


loads(both units

per air changers


Average volume

Supply Air temp


Occupants load

AHU's capacity
Lightng Load

air changers
(for tunnel)
Floor Level

(summer)
working)
Efectve

installed
IS 4720
tunnel)
m Description m m2 m3 w w w w ˚c ˚c m3/h m3/h m3/h
Power house & Transformer Cavern
587 Machine hall/Service way area 5 924.48 4622.4 7800 13966 140 21906 37 30 9421 2.04 2 9245 9421 8000 2x4000
582.5 Generator floor 4.5 398 1791 17150 1485 140 18775 37 30 8074 4.51 2 3582 8074 8000 2x4000
578.5 Turbine floor 4 412 1648 9920 920 140 10980 37 30 4722 2.87 2 3296 4722 8000 2x4000
573 Miv floor area 5.1 472.2 2409 2550 1291 140 3981 37 30 1712 0.71 2 4818 4818
29.27 &
587 Bus duct gallery(for 2 nos) 11& 23 18.28 1484.8 19200 156 0 19356 37 30 8324 5.61 4 5940 8324 8000 2x4000
587 Transformer cavern 12 571.05 6853 32650 172 0 32650 37 30 14041 2.05 2 13706 14041 0
Control Block
577 colling water room 5.2 126.96 661 11520 623 140 12283 37 30 5282 7.99 2 1322 5282 3169.2
582.5 Sat Room 4.2 63.48 267 10000 256 140 10186 37 30 4381 16.41 2 534 4381 2628.6
587 SSB & DC Room 4 126.96 508 12400 488 0 12446 37 30 5353 10.54 2 1016 5353 3211.8
Lift Lobby
573 Lift loby 4 63.48 254 0 46 70 116 37 30 50 0.20 8 2032 2032 1219.2
577 Lift loby 5.5 63.48 350 0 46 70 116 37 30 50 0.14 8 2800 2800 1680
582.5 Lift loby 4.5 63.48 286 0 46 70 116 37 30 50 0.17 8 2288 2288 1372.8
587 Lift loby 4 63.48 254 0 46 70 116 37 30 50 0.20 8 2032 2032 1219.2 2x10000
591 Lift loby 4 50.98 204 0 46 70 116 37 30 50 0.25 8 1632 1632 979.2
595 Lift loby 3 50.98 153 0 46 70 116 37 30 50 0.33 8 1224 1224 734.4
Toilet , Pantry & Battery Room
591 Toilet 4 12.5 50 0 20 0 20 37 30 9 0.18 10 500 500 300
595 Toilet 3 12.5 38 0 20 0 20 37 30 9 0.24 10 380 380 228
595 Pantry 4 13.7 55 100 125 210 435 37 30 188 3.42 10 550 550 330
582.5 Battery Room 4.5 63.48 286 300 215 0 515 37 30 222 0.78 10 2860 2860 1716
Tunnel & Gallery
587 Connecting tunnel 34 47.2 1604.8 0 152 0 152 37 30 66 0.04 2 3210 3210
587-581 Escape gallery 110 22.3 2453 0 140 0 140 37 30 61 0.02 2 4906 4906
Total Supply air 88830
Control Room & Office Area
591 Control room 4 126.96 508 9075 2419 560 12054 24 16 4536 8.93 8 4064 4536
Supplied
595 Conference room & Office 3 79.35 239 500 725 700 1925 24 16 725 3.03 8 1912 1912 by Split
595 Library 3 11.116 34 500 724 280 1504 24 16 566 16.65 8 272 566 AC
598 For Outdoor Unit of Split AC 77000 37 30 33112 33112
AC Supply Air 7014
Fresh Air required with split AC 0
Total supply air requirememt 121942 50788.4
Total AHU Capacity 50788
Total fresh air requirement 71154
Recirculation percentage 41.65%
Toilet ,Battery and Pantry exhaust 4290
Total Exhaust air requirement 59748
AHU Water capacity calculation

Total AHU capacity Qa 50788.4 CMH Total AHU


Inlet air temp T1 37 deg.C Inlet air t
Supply air temp T2 30 deg.C Supply air
Specific Heat capacity Cp 1.005 Kj/Kg K Specific He
Specific Air Density d 1.19 kg/m3 Specific Ai
Heat Load P Heat Load
P=Q(cmh)x∆TxCpxd/3600 118.1063 kW P=Q(cmh)x∆TxCpxd/360
33.74466 TR
Water Inlet Temp. t1 20 Water Inle
Water Outlet temperature t2 25 Water Outl
Specific heat of water S 4.184 J/g deg.C Specific he
Mass of water required m Mass of wa
m=(P/(Sx∆t))x3600/1000 20.32422 m3/hr m=(P/(Sx∆t))x3600/1000
Margin of 15 % Margin of
Total Capacity of water required m 23.37285 m3/hr Total Capac

Chiller Unit Calculation


Total Fresh Air Unit Capacity Qf 71153.6 CMH
Ambient Temperature T1 32 deg.C
Supply air temp T2 30 deg.C
Specific Heat capacity Cp 1.005 Kj/Kg K
Specific Air Density d 1.19 kg/m3
Heat Load P
P=Q(cmh)x∆TxCpxd/3600 P 47.27564 kW
This much heat has to be removed by water
Water Inlet Temp. t1 20 t1
Water Outlet temperature t2 25 t2
Specific heat of water S 4.184 J/g deg.C S
Mass of water required m m
m=(P/(Sx∆t))x3600/1000 8.135387 m3/hr
Margin of 15 %
Total Capacity of water required m 9.355695 m3/hr m
Qa 17000 CMH
T1 25 deg.C
T2 14 deg.C
Cp 1.005 Kj/Kg K
d 1.19 kg/m3
P
P=Q(cmh)x∆TxCpxd/3600 62.1229583333 kW
17.7494166667 TR 1 LPS = 2 CFM = 3.4 CMH
t1 15
t2 20
S 4.184 J/g deg.C
m
m=(P/(Sx∆t))x3600/1000 10.690375239 m3/hr
Margin of 15 %
m 12.294 m3/hr

50000
32
30
1.005
1.19

9.49166667 TR

20
25
4.184

1.6333652
15
1.87836998
= 2 CFM = 3.4 CMH
Air Quantity Calculation for Split AC Unit
Total AC Tonnage TR 22
Heat to be dissipated P 77.4 kW
P * 3600 Diference between Supply and
Q return air ∆t 7K
t * Cp * d
Specific Heat of Air Cp 1.005 KJ/Kg K
Density of air d 1.19 kg/m3
Air Flow required Q 33270.69 CMH

Water quantity calculation for PAC


Water Inlet Temp. t1 20
Water Outlet temperature t2 26
P * 3600 Density of water d 1000 kg/m3
m 
s * t * d Specific heat of water S 4.184 J/g deg.C
Flow of water required m 11.09507 m3/hr
Margin of 15 %
Total Capacity of water
required m 12.75933 m3/hr